ACCX Air Conditioning

Size: px
Start display at page:

Download "ACCX Air Conditioning"

Transcription

1 ACCX Air Conditioning CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: Run / Stand-by changeover Controller Installation and operation Manual 1

2 Two Air conditioning Changeover Unit The unit consists of two volt free contacts (Start/Stop AHU1 & 2) and will control both AHUS. Both contacts are normally closed, this allows a failsafe for when the unit is powered down or becomes faulty as both AHUS will start. In normal operation the Run AHU volt free contact will be closed (relay deenergized) and the standby AHU volt free contact will be open (relay energized). Both AHUS will need to supply an individual control interlock through the units control relays. Three fault inputs are provided, AHU1, AHU2 and Room over temperature TEMP. A four way selector switch has been provided within the unit to allow the individual fault signals to be set at normally open or normally closed. Any combination of normally open/closed can be set by this switch, i.e. AHU1 normally open (close in fault), AHU2 the same and Room over temperature normally closed (open in fault). This switch is located on the left hand side of the main PCB just above the terminals marked RS485. Identification numbers on the switch relate to, 1 = AHU1 is a normally open input when the switch is pushed to the far left or normally closed when pushed to the far right, 2 = the same but for AHU2 and 4 = the same but for Room over Temperature (switch 3 is unused). The control unit will provide a 12vdc signal to all the remote fault contacts which should be volt free. A common alarm relay is provided which again will be energized in normal operation, de-energize in alarm. Again, this allows a failsafe for when the unit is powered down or becomes faulty as it will start a remote alarm if fitted or signal a fault to the BMS due to power failure. The unit has been designed to control two air handling units and allows one unit to provide heating / cooling with the second unit being off and in standby. After a time delay which is user selected between 1 and 999 hours, the run unit will stop and the standby unit will start up. This feature allows even ware of both AHUS. In the event of a fault developing with the run unit, the system would automatically shut down the run unit, start the standby unit, give an audible warning (requiring a Mute to stop) and operate the common alarm relay. The system would remain in this configuration until the faulty AHU had been rectified and the Reset push button operated. Having changed as described above to the standby unit, if a fault developed with the standby unit i.e. both AHU1 and 2 faulty, both AHUS would start. This has been done in an endeavour to obtain some heating / cooling from both units whilst waiting for repair. If a fault developed with the standby unit, the system would inhibit automatic transfer after the preset time delay, start the audible warning and operate the common alarm relay. Again, if during this configuration the run unit became faulty, both units would be started as described above. On over temperature fault signal has been provided which would be connected to a standard thermostat within the room. If the thermostat detected an over temperature within the room, the system would start both AHUS to give the maximum cooling to the room. Again, the system would remain in this configuration until the Reset push button was operated. A non volatile memory store has been used within the unit to hold the Time between automatic changeovers and the time until the next changeover. In the event of power failure both time periods would remain held within the unit so that on re-powering the time delay to the next changeover continues from where it stopped i.e. on power down it was 63 hours to the next changeover, on re-powering up of the system it will still be 63 hours to the next changeover. Three push buttons are provided Mute to stop the audible warning device, Reset to revert the system back to normal operation after a fault and Set used to manually select which unit is to be run unit or change the time period between automatic changeovers. A timer is activated when entering the Set mode which will automatically revert the system back to normal operation if a push button has not been operated within 10 seconds. All events are displayed in a back lit 16 character 2 line alpha numeric display. 2

3 In Normal Operation With the system up and running without any faults and AHU1 selected as the run unit the display will show the following. AHU1 is Running Time run 030 hrs The display shows that AHU1 has been selected as the run unit and has been running for 30 hours. Relay Start/Stop AHU1 will be de-energized (contact closed) and relay Start/Stop AHU2 will be energized (contact open). A few seconds later the display will change to the following. AHU2 in Standby C/Over in 136hrs This shows that AHU2 is the standby unit and will become the run unit in 136 hours. Again after a few seconds the display will go back to displaying AHU1 status and continue to cycle through both screens. Once AHU2 becomes the run unit the same display format is used but showing AHU1 in Standby and. The Start/Stop relays would change to AHU1 energized ( contact open) and AHU2 de-energized ( contact closed). AHU1 or 2 is selected as the run unit but becomes fault. The display would change from normal operation to the following. STANDBY AHU HAS BEEN ACTIVATED The run unit would stop, the standby unit would start up, the audible warning device would sound and the common alarm relay would operate. This would remain until the Mute push button were operated when the display would show the following. Standby Running A few seconds later a new screen would display the following. Again after a few seconds the display would change back to the first screen and continue to cycle through both screens. This would remain until the faulty AHU had been rectified when the screens would change to the following. Followed by. 3

4 Even though the faulty unit has been repaired, the system will not allow a transfer back to it until the Reset button had been operated. Whilst in this configuration, the automatic transfer due to time would be inhibited. However once the fault had be rectified and reset, the timer would start from where it had been stopped i.e. fault happened with 63 hours until next changeover, fault lasted 5 hours after reset time to next changeover would be 63 hours. AHU1 or 2 is running but the standby unit becomes faulty The display would change from normal operation to the following. The Standby Unit Is Faulty The run unit would continue to run, the standby unit would be locked out, the audible warning device would sound and the common alarm relay would operate. This would remain until the Mute push button were operated when the display would show the following. Followed after a few seconds by. Again after a few seconds the display would change back to the first screen and continue to cycle through both screens. This would remain until the faulty AHU had been rectified when the screens would change to the following. Followed by. Again even though the faulty unit has been repaired, the system will not allow a transfer back to it until the Reset button had been operated. Whilst in this configuration, the automatic transfer due to time would be inhibited as above. Both AHUS become faulty In the unlikely event that at some time both AHUS be come faulty. The display would change to the following. STANDBY AHU HAS BEEN ACTIVATED 4

5 The run and standby units would both run, the audible warning device would sound and the common alarm relay would operate if not already done so. This would remain until the Mute push button were operated when the display would show the following. All AHUS Faulty A few seconds later a new screen would display the following. AHU2 is Faulty All AHUS Faulty After a few seconds the display would change back to the first screen and continue to cycle through both screens. This would remain until one or both faulty AHUs had been rectified. when the screens would change to the following. Only AHU1 rectified. Followed by. Or both AHUS rectified Followed by. Again, even though both faulty unit had been repaired, the system will not allow a transfer back to it until the Reset button had been operated. Whilst in this configuration, the automatic transfer due to time would be inhibited as above. If only one of the AHUS had been rectified and depending upon weather it was a run or standby unit, the system would display one of the fault screens shown above. This would required a second Reset after the remaining faulty unit were rectified. Room Over Temperature If the room becomes to hot, the system will start both AHUS, start the audible warning device and operate the common fault relay. The display will show the following. 5

6 C/O ACTIVATED BY HIGH TEMP This would remain until the Mute push button were operated when the display would show the following. AHU1 is Running Room over Temp Followed after a few seconds by. Room over temp Again after a few seconds the display would change back to the first screen and continue to cycle through both screens. This would remain until the room temperature fell back to normal when the screens would change to the following. AHU1 is Running Room over Temp Followed after a few seconds by. If again the room became to hot before a manual reset occurred, the display would revert back to both AHUS running and Room Over Temp. The audible warning device would not start again nor would the relays change. Once the room reached the normal temperature, the system will not allow a transfer back to normal running until the Reset button had been operated. Whilst in this configuration, the automatic transfer due to time would be inhibited as above. Manually select which AHU is to be the run unit This feature can only be used when the system is in normal running with no current faults. It allows at any time to manually select which unit is to be the run unit i.e. AHU2 is now the run unit with 100 hours before it becomes the standby. After manual selection AHU2 becomes the run unit with AHU1 as standby. After using this feature the time clock will reset back to the maximum hours before the next changeover. A timer is activated when entering the Set mode which will automatically revert back to normal operation if a push button has not been operated after 10 seconds. First press the Set push button, the display changes to the following. Mute = C/O Time Reset= AHU Duty Press the Reset push button, the display changes to the following. 6

7 S=Save, M=Change Run Unit AHU 2 The display is showing that the current run AHU is number 2. S = the Set push button and M = the Mute push button. Press the M (Mute) push button changes the 2 i.e. AHU2 into 1 i.e. AHU1. More presses of the M (Mute) button will toggle between AHU1 and 2. When satisfied with the selection press the S (Set) push button. The system will change the run / standby configuration, restart the time delay to next changeover and display the normal running screens. Change the time delay between automatic change between run and standby configurations. This feature allows a user to determine the period between changing the run unit into a standby unit. By using this feature twice, an automatic changeover can occur at a specific time on a specific day i.e. Monday at 5pm. However attendance may be required to carry this out. To do this first workout the hours between now and Monday 5pm and set the system up for this time, next on Monday at 5pm use this feature again to set the next changeover to 168 hours. The system will then carry out a changeover every Monday at 5pm. Any time period between 1 and 999 hours can be set i.e. 1 hour to 41 day 15 hours. A timer is activated when entering the Set mode which will automatically revert back to normal operation if a push button has not been operated after 10 seconds. First press the Set push button, the display changes to the following. Mute = C/O Time Reset= AHU Duty Press the Mute push button, the display changes to the following. S=Save, R=Next M= Change 999hrs The display is showing the current time delay between changeovers (999 hrs) S = the Set push button, R = the Reset button and M = the Mute button. The cursor will be flashing over the hundreds number to indicate that this is the number being worked on. Pressing the M (Mute) button will increment the number as shown by the flashing cursor. If no change is required to the hundreds, or you are satisfied with your selection, press the R (Reset) push button to move the cursor to the tens number. Again using the M (Mute) button will increment the number as previously described. pressing the R (Reset) push button once again to move the cursor to the units number which can be change as described above. One more press of the R (Reset) push button will take the system back to the hundreds number. Once you have selected your required time delay press the S (Set) push button. This will save the new time, reset the time until next changeover back to the new time and reset the system back to normal operation. The S (Set) push button can be used at any time. 7

8 Notes Both AHU 1 & 2 must have a volt free contact normaly open or closed to indicate to the unit of a fault within the AHU. The unit providers a 240VAC 8amp normaly closed contacts to start and stop the AHUS An over temperature thermostat can be used to start both AHUS. The contact can be normaly open or closed How to change AHU1and or AHU2 and or Thermostat from normaly open to closed contact arrangment. A small 4 way switch can be found on the far LEFT of the PCB located about 30mm from the bottom of the PCB. For normally Open contacts the relivant switch should be pushed to the LEFT, normaly closed the switch should be pushed to the right. Normaly Closed Contact Normaly Open Contact AHU1 Fault AHU2 Fault NOT USED Thermostat AHU 1 AHU 2 AHU Fault Circuit N/O or N/C Volt Free contact Stop/Start Circuit AHU Fault Circuit N/O or N/C Volt Free contact Stop/Start Circuit Thermostat if required Volt Free Common Alarm Contacts L E N NOT USED AHU 1 FAULT CONTACT N/C COM N/O AHU 2 FAULT CONTACT NOT USED REMOTE THERMOSTAT IF REQUIRED 8 AHU 1 START/STOP AHU 2 START/STOP NOT USED OUTPUT ALARM CONTACTS 230VAC Mains Input "L" = Live, "N" = Neurtal, "E" =Earth

9 9

BLDA-1 & 2 Water Leak Detection Manual. CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel:

BLDA-1 & 2 Water Leak Detection Manual. CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: BLDA-1 & 2 Water Leak Detection Manual CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 Contents 1) System Overview 2) Installation 3) Wiring 4) Water

More information

DIGITAL PUMP CONTROLLER. Model Version October 24, 2011

DIGITAL PUMP CONTROLLER. Model Version October 24, 2011 DIGITAL PUMP CONTROLLER Model 9954-1 Version October 24, 2011 9954-1 Controller Interconnection Diagram PROGRAMMABLE VOLT-FREE CONTACT (10A 240vAC) (FACTORY FITTED OPTION) FOR REMOTE SIGNALLING CONTROL

More information

Model: Available in : Sapphire Black and Glacier White

Model: Available in : Sapphire Black and Glacier White Model: Available in : Sapphire Black and Glacier White 1 Table of Contents Product Image 1 Locking/Unlocking the SmartStat 20 Table of Contents 2 Standby/Away Mode 21 What is a Programmable Room Thermostat?

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS SEZ7656E1045B Installation Guide f BACnet MS/TP RTU Terminal with IAQ Control CONTENTS Installation 2 Location 2 Installation 2 BACnet System Overview 3 Terminal, Identification and Function 4 Wiring 4

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

Instruction Manual. ICENI/MA-01 MODBUS Master Module. Pub_ Issue 1

Instruction Manual. ICENI/MA-01 MODBUS Master Module. Pub_ Issue 1 Instruction Manual ICENI/MA-01 MODBUS Master Module Pub_363 - Issue 1 Regulateurs Europa Ltd 2014 The contents of this document are the exclusive Property of Regulateurs Europa Ltd They must not be copied

More information

Model: Available in : Sapphire Black and Glacier White

Model: Available in : Sapphire Black and Glacier White 1 Model: Available in : Sapphire Black and Glacier White 1 Table of Contents Product Image 1 Locking/Unlocking the SmartStat 20 23 Table of Contents 2 Standby/Away Mode Mode 21 24 What is a Programmable

More information

Touchpad User Guide. National Sales. Product Support. Freecall: Ph:

Touchpad User Guide. National Sales. Product Support. Freecall: Ph: Touchpad User Guide National Sales Ph: 1300 306 125 sales@ias.net.au Product Support Freecall: 1800 354 434 support@ias.net.au Designed and Manufactured in Australia by: Innovative Air Systems Pty Ltd.

More information

ME3 Mobile Cabinet Three Phase Frequency Converter, Operation and Maintenence.

ME3 Mobile Cabinet Three Phase Frequency Converter, Operation and Maintenence. 29-30 Brunel Road, Churchfields Industrial Estate, St. Leonards-on-Sea East Sussex. TN38 9RT. United Kingdom Sales & Service : 01424 853 013 All Other Departments : 01424 853 464 Fax : 01424 852 268 magnuspower.sales@akersolutions.com

More information

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

Iso DIN. User Manual. 1 channel Earth Fault Monitoring Page 1 of 5 2017 03 20 User Manual Iso DIN Iso DIN User Manual 1 channel Earth Fault Monitoring Megacon AB Ranhammarsvägen 20 S 168 67 Bromma Sweden Tel: 08 402 42 50 sales@megacon.se www.megacon.se eee

More information

Operation 6035 ENGLISH PROG MENU

Operation 6035 ENGLISH PROG MENU Operation 6035 PROG MENU ENGLISH Operation 6035 Program button Time of day Day Time Slot Current Room Temperature Target Temperature Menu button PROG MENU FAN AUTO ON COOL OFF HEAT Fan Switch Touch Screen

More information

Digital Keypad Introduction

Digital Keypad  Introduction K2 Digital Keypad Introduction The K02 uses the latest microprocessor technology to operate door strikes and security systems that require a momentary (timed) or latching dry contact closure. All programming

More information

SELENA. TEMPERATURE MONITORING AND CONTROL ( Option # 711, # 712 and # 713 ) Rev. 32

SELENA. TEMPERATURE MONITORING AND CONTROL ( Option # 711, # 712 and # 713 ) Rev. 32 SELENA TEMPERATURE MONITORING AND CONTROL ( Option # 711, # 712 and # 713 ) Rev. 32 In all temperature monitoring or control configurations the function Fn 61 must be enabled. The functions Fn 0 and Fn

More information

TS InteliSwitch Digital Time Switch 24VDC/VAC

TS InteliSwitch Digital Time Switch 24VDC/VAC SPECIFICATIONS InteliSwitch Digital Time Switch 24VDC/VAC Voltages... 24VAC, 24VDC, VAC Half Rectified Current Consumption............................ Max. 15mA DC........................................

More information

SEZ7656R1045B / SEZ7656H1045B

SEZ7656R1045B / SEZ7656H1045B SEZ7656R1045B / SEZ7656H1045B Installation Guide f BACnet MS-TP RTU / HP Room Controllers F Commercial Zoning Systems CONTENTS Installation 2 Location 2 Installation 2 BACnet System Overview 3 Terminal,

More information

SS2200 Remote Controller

SS2200 Remote Controller SS2200 Remote Controller General Purpose, DC Voltage General The SS2200 Remote Controller is a microprocessor-based programmable controller specifically designed to control single line and dual line centralized

More information

PAC1 Door Access Controller

PAC1 Door Access Controller PAC1 Door Access Controller Series 1 TABLE OF CONTENTS i PAGE Introduction...1 Features...1 Specifications...2 Terminal Descriptions...3 Programmable Features Description...5 Automatic Relock Function...5

More information

Installation Instructions

Installation Instructions SPECIFICATIONS InteliSwitch Digital Time Switch 24VDC/VAC Voltages...... 24VDC, 24VAC, 24VAC Half Wave Rectified Current Consumption...................Max. 15mA DC.................................Max.

More information

CentaurPlus C17 User Operating Instructions

CentaurPlus C17 User Operating Instructions CentaurPlus C17 User Operating Instructions Single Channel Timeswitch The Horstmann CentaurPlus C17 time switch will allow up to 3 ON/ settings per day for each day of the week and has a 1 hour manual

More information

PAC1 Door Access Controller

PAC1 Door Access Controller PAC1 Door Access Controller Series 1 100% Designed and Manufactured by: NIDAC SECURITY PTY. LTD. 2 CROMWELL STREET BURWOOD, VICTORIA Tel: (03) 9808 6244 AUSTRALIA 3125 Fax: (03) 9808 9335 Revision 1.1

More information

SPS5.7. Operating Instructions. Notes

SPS5.7. Operating Instructions. Notes SPS5.7 Operating Instructions Stanton Pottery Supplies Ltd., Canal Lane, Westport Lake, Tunstall, STOKE-ON-TRENT, Staffordshire, England. ST6 4NZ 24 Tel: +44 (0)1782 835467 Issue: 1.0A Fax: +44 (0)1782

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

SE7600F Series. Installation Guide for RTU with Modulating Heat CONTENTS

SE7600F Series. Installation Guide for RTU with Modulating Heat CONTENTS SE7600F Series Installation Guide for RTU with Modulating Heat ONTENTS Installation 2 Location 2 Installation 2 Model hart 3 Network ready 3 Terminal, Identification and Function 3 Screw terminal arrangement

More information

VANDAL RESISTANT BACK-LIT WEATHERPROOF ACCESS CONTROL KEYPAD

VANDAL RESISTANT BACK-LIT WEATHERPROOF ACCESS CONTROL KEYPAD VANDAL RESISTANT BACK-LIT WEATHERPROOF ACCESS CONTROL KEYPAD Post Mount Keypad Programming & Installation Manual 1. Connect Power 12V DC to 24V AC/DC to terminals (+) and (-) Post Mount Keypad Quick Start

More information

DEKKER KNOWLEDGE DATABASE KNOWLEDGE IS POWER

DEKKER KNOWLEDGE DATABASE KNOWLEDGE IS POWER DEKKER KNOWLEDGE DATABASE For Use with DEKKER Vacuum Systems Equipped with the DEKKER Controller Each Vmax system is tested and checked at the factory prior to shipment to ensure trouble-free operation.

More information

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel The heart of the Starzone 4000 system is the Starzone Master controller (SZM-4000). Each AHU that is to be zoned will have its own SZM-4000

More information

Temperature control unit

Temperature control unit Temperature control unit 5739 18/19 Installation manual Part. U3582A - 12/08-01 PC Contents 1 - Introduction 5 1.1 - Warnings and tips 5 1.2 - Contents of package 5 2 - Description of the Control unit

More information

Operating and Maintenance Instructions

Operating and Maintenance Instructions Part No Description Dual EC Fan Controller Issue Date Bug no Comments 1 10 July 2012 1205 Signed CE front sheet & instructions clarified 2 28 Jan 2013 1205 Instructions clarified, identify Live & SELV

More information

PAC2 Dual Door Access Controller

PAC2 Dual Door Access Controller PAC2 Dual Door Access Controller Series 2 IMPORTANT DIFFERENCES FROM SERIES 1 1. All programming can only be done through devices attached to DTA1. 2. A PACDL data logger revision 4.0 or higher attached

More information

9212i INSTALLATION. Stand-Alone Keypad. Instructions

9212i INSTALLATION. Stand-Alone Keypad. Instructions INSTALLATION 9212i Stand-Alone Keypad Instructions Features: 4 Independent Outputs 4 Independent Timers All Outputs Assignable by Code On board 5 Amp Form C Relay 120 Users Remote Triggering Input Keypad

More information

SE7600E Series. Installation Guide for Commerical HVAC Applications CONTENTS

SE7600E Series. Installation Guide for Commerical HVAC Applications CONTENTS SE7600E Series Installation Guide for ommerical HVA Applications ONTENTS Installation 2 Location 2 Installation 2 Terminal, Identification and Function 3 Screw terminal arrangement and wiring 3 Main outputs

More information

AMBIFLEX MF626 - USER GUIDE

AMBIFLEX MF626 - USER GUIDE AMBIFLEX MF626 - USER GUIDE CONTENTS Page No Product Overview 2 Features 3 Standby Display 4 User Facilities 5 Status Display Mode 6 Measured Temperatures 6 Time Channel Information 7 What is happening

More information

Solid State Relays and Timers Family

Solid State Relays and Timers Family Solid State Relays and Timers Family Vehicle Control Modules Waytek Stock No. Volt Rating Amp Rating Notes Dual Input Relay Activating either Input A or Input B sets output. 75532 12 15 Dual inputs Latching

More information

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide BlueWave ~ Intelligent Energy Control Installation and User Manual for BW2/C and BW3/C versions Quick Guide Press button to override or activate Channel 1 Press button to override or activate Channel 2

More information

Product Manual SZ2141

Product Manual SZ2141 Product Manual SZ11 Refrigeration Controller Communicating Controls Description The SZ11 is a microprocessor-based refrigeration controller and alarm interface designed to control three coolers or freezers

More information

AP41 / AP81 SERIES TIME SWITCHES

AP41 / AP81 SERIES TIME SWITCHES FN:AP41_81M1.DOC AP41 / AP81 SERIES TIME SWITCHES AP41 AP81 TABLE OF CONTENTS INTRODUCTION 2 SPECIFICATIONS 2 INSTALLATION 5 FRONT PANEL DESCRIPTION 7 OPERATION 8 Filling out the Program Record Sheet 8

More information

Safety Control Relay Product Catalog

Safety Control Relay Product Catalog Product Catalog Wall Mount for use with Safety Mats Safety Edges Safety Bumpers Safety Sensors 2 wire Safety Sensors 4 wire DIN Rail Mount Intrinsically Safe Explosion Proof Wall Mount Introduction The

More information

Installation & Operation and Maintenance

Installation & Operation and Maintenance Gas Safety Products Dual Current Monitor Installation & Operation and Maintenance Read these instructions carefully before operating or servicing Rev: 01 Date: 12-02-18 1 CONTENTS Chapter Content Page

More information

Instruction Manual HID-2

Instruction Manual HID-2 Specifications HID-2 Amps / Volts requirements 15 amps @ 120 volts Min / Max operating temperature 32 to 120 F Min / Max operating humidity 0-99% RH Time setting Hours, Minutes, Seconds Hi-temp setting

More information

AS Keypad User Manual

AS Keypad User Manual AS Keypad User Manual Specifications Operating Voltage: 12~24 VAC/DC Current Draw: TBA Input: request-to-exit (for Relay 1) time out reed switch contact (for Relay 1) Output: Relay 1: N.O./N.C./Com. Output

More information

Application program: description and examples

Application program: description and examples F a n C o i l U n i t C o n t r o l l e r F a n C o i l 4 9 5 5 1 Application program: description and examples Woertz AG Electrotechnical accessories, installation systems Hofackerstrasse 47, P.O. Box

More information

MULTI-PURPOSE SELF-CONTAINED DIGITAL ACCESS CONTROL KEYPAD

MULTI-PURPOSE SELF-CONTAINED DIGITAL ACCESS CONTROL KEYPAD MULTI-PURPOSE SELF-CONTAINED DIGITAL ACCESS CONTROL PAD Programming & Installation Manual An Innovative Product Developed By: PROTECT - ON SYSTEMS LTD. MANUFACTURED BY: 20 R SINCE 1979 ADVANCED ELECTRONICS

More information

SCC Inc. TS Series Application Guide. Technical Instructions. Document No. TS 8000 January 9, Description

SCC Inc. TS Series Application Guide. Technical Instructions. Document No. TS 8000 January 9, Description SCC Inc. Application Guide Technical Instructions January 9, 2018 Description The Application Guide includes programming, wiring, and operation examples of the control system for the most common applications.

More information

Model Instruction Manual. Heat Stress Meter. reedinstruments. www. com

Model Instruction Manual. Heat Stress Meter. reedinstruments. www. com Model 8778 Heat Stress Meter Instruction Manual reedinstruments com Table of Contents Features... 3 Specifications...3-4 Instrument Description... 4 Operating Instructions...5-9 Select display mode...

More information

ACTpro Single Door IP Controller. Operating & Installation Instructions

ACTpro Single Door IP Controller. Operating & Installation Instructions ACTpro 1500 Single Door IP Controller Operating & Installation Instructions 18-00079 Issue 1 This manual refers to the ACTpro 1500 a TCP/IP based control unit supporting up to 32 doors. Access Control

More information

MAINS DISTRIBUTION UNIT MDU14-CO

MAINS DISTRIBUTION UNIT MDU14-CO MAINS DISTRIBUTION UNIT MDU14-CO Dual Input Auto Changeover 14 Output Mains Distribution Unit. Handbook Television Systems Limited. Vanwall Road, Maidenhead, Berkshire, SL6 4UB Telephone +44 (0)1628 676200,

More information

LF1-400 Frequency Converter, Operation and Maintenance

LF1-400 Frequency Converter, Operation and Maintenance Vision House, 41 Brunel Road, Churchfields Industrial Estate, St. Leonards-on-Sea East Sussex. TN38 9RT. United Kingdom Sales & Service : 01424 856 172 magnuspower.sales@akersolutions.com magnuspower.service@akersolutions.com

More information

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 Rev. A

More information

Model: TM-1 / TM1-N. 1 Time Clock Series

Model: TM-1 / TM1-N. 1 Time Clock Series Model: TM-1 / TM1-N Model: TM-1 / TM1-N 1 Time Clock Series Table of Contents Product Image Table of Contents Installation Procedure LCD Display Operating Modes Setting the Operating Mode Setting the Clock

More information

SK-3133-PPQ Heavy-Duty Outdoor Access Control Keypad with Proximity Reader

SK-3133-PPQ Heavy-Duty Outdoor Access Control Keypad with Proximity Reader SK-3133-PPQ Heavy-Duty Outdoor Access Control Keypad with Proximity Reader Features: Rugged construction heavy-duty stainless steel faceplate with coated steel housing Built-in proximity card reader 12~24

More information

Owner s Manual RBC-AX32U(W)-E RBC-AX32U(WS)-E AIR CONDITIONER (SPLIT TYPE) Wireless remote controller kit. Model name: English.

Owner s Manual RBC-AX32U(W)-E RBC-AX32U(WS)-E AIR CONDITIONER (SPLIT TYPE) Wireless remote controller kit. Model name: English. AIR CDITIER (SPLIT TYPE) Owner s Manual Wireless remote controller kit Model name: RBC-AX3U(W)-E RBC-AX3U(WS)-E Generic model name RBC-AX3U(W)-E Wireless remote controller model name WH-LSE Signal receiving

More information

RITZ / Turbine controls DISPLAY

RITZ / Turbine controls DISPLAY RITZ / Turbine controls DISPLAY CANCEL EXIT OK MENU F1 F2 F3 F4 The control/display unit has a CPU, an LCD display and 8 keys. 2 LEDs also display particular operational conditions (e.g. plant ON, faults,

More information

CCM-204 MULTI-PURPOSE TEMPERATURE CONTROLLER

CCM-204 MULTI-PURPOSE TEMPERATURE CONTROLLER CCM-204 MULTI-PURPOSE TEMPERATURE CONTROLLER BACnet Enabled C-037 08/12 DESCRIPTION The BACnet enabled CCM-204 Multi-Purpose temperature controller is designed to offer complete control flexibility for

More information

Touchpad User Guide (Model: C-LCD-122-TL)

Touchpad User Guide (Model: C-LCD-122-TL) MESSAGE LIBRARY Refer to BBP-5 Instal Guide for information on input triggers. The same message may be linked to more than one trigger. ABBREVIATED VERSION DISPLAYED IN SELECTION SCREEN MESSAGE DISPLAYED

More information

Installation Manual for D244X Series 24-volt Power Supplies

Installation Manual for D244X Series 24-volt Power Supplies Installation Manual for D244X Series 24-volt Power Supplies D2441-B D2441-C D2443-B D2443-C D2445-B D2445-C D2400 Series 1A 24 volts 1A 24 volts 3A 24 volts 3A 24 volts 5A 24 volts 5A 24 volts Dycon Power

More information

AEXX SERIES MULTI-FUNCTION CLOCK/TIMERS

AEXX SERIES MULTI-FUNCTION CLOCK/TIMERS FN:XXMFCT1.DOC AEXX SERIES MULTI-FUNCTION CLOCK/TIMERS AEXX SERIES MULTI-FUNCTION CLOCK/TIMERS REV 04/09/09 DESCRIPTION The AEXX Series of Multi-Function Clock/Timers are available with 1, 2.3, 4, 8, or

More information

OP10. Pre-programmed, configurable controller for simple applications

OP10. Pre-programmed, configurable controller for simple applications revision 10 2013 OP10 Pre-programmed, configurable controller for simple applications The Optigo OP10 range of controllers can be set to handle everything from temperature or humidity control to control

More information

XRS 3000 Controller Reference Guide V-2

XRS 3000 Controller Reference Guide V-2 XRS 3000 Controller Reference Guide V-2 XRS-3000 1 WHITE MAIN POWER COLLIGHTLIGHT THREE POSITION KEY SWITCH 1. OFF 2. STANDBY 3. ON XRS-3000 SAFETY CIRCUIT ENGAGED X- RAY PREWARNING X- RAY BEING PRODUCED

More information

FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW.

FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW. CENTRIFLOW PUR 3D (A, PLUG B, C, D) FAN GMPM FC101 AND SLIDE IN FREQUENCY ROTOR CASSETTE CONVERTER QUICK GUIDE FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS

More information

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook FANCOIL CONTROLLER UNIT TC17B01KNX Product Handbook Product: TC17B01KNX Description: FANCOIL CONTROLLER UNIT Document Version: 1.2 Date: 09/09/2016 1/37 INDEX 1. General Introduction... 4 2. Product and

More information

MT400 MOTION CONTROLLER

MT400 MOTION CONTROLLER MT400 MOTION CONTROLLER INSTALLATION & TECHNICAL MANUAL 5/30/2012 417 Wards Corner Road Loveland, OH 45140 800.659.8250 FAX: 513.398.2536 www.maxitronic.com Table of Contents Page 3: Page 4: Page 5: Page

More information

Model SFS01-V2 IMPORTANT! MULTI-ATTEMPT AUTOMATIC ENGINE SMART SWITCH

Model SFS01-V2 IMPORTANT! MULTI-ATTEMPT AUTOMATIC ENGINE SMART SWITCH MULTI-ATTEMPT AUTOMATIC ENGINE SMART SWITCH Model SFS01-V2 DESCRIPTION The Model SFS01-V2 is a Multi-attempt Automatic Engine Smart Switch designed to automatically [remotely] or manually start and stop

More information

BIO-PRO Standalone / Weigand fingerprint reader

BIO-PRO Standalone / Weigand fingerprint reader BIO-PRO Standalone / Weigand fingerprint reader www.locksonline.co.uk Tel 0845 30 0 0 v 4 x Master Card x0 User Card IP5 DEEE -0 C to +50 C The BIOSYS product complies with Directive 999/5/CE REMINDERS

More information

SK Installation Instructions

SK Installation Instructions Guestroom HVAC Energy Management System SK200-001 Installation Instructions GENERAL SYSTEM COMPONENTS INTRODUCTION The S200 series hospitality HVAC Energy Management (HEM) System is specially designed

More information

Fan Coil Controller - 4 Relay Outputs. Main Features. Detailed Features

Fan Coil Controller - 4 Relay Outputs. Main Features. Detailed Features Consumer Module Data Sheet Fan Coil Controller - 4 Relay Outputs F2 Main Features 4 Pipe Fan Coils Modulating control of heating and cooling coils (no fan enable) Works in conjunction with SeaChange Zone

More information

ADVANCED REMOTE CONTROL

ADVANCED REMOTE CONTROL ADVANCED REMOTE CONTROL (SUITS IP28) INSTALLATION & OPERATING INSTRUCTIONS 918-962 12/07/10 The Advanced Remote Control is tested safe when installed in accordance with this installation manual. It is

More information

Control system for rotary heat exchanger EQRB, L=3,4

Control system for rotary heat exchanger EQRB, L=3,4 Installation instructions, drive system EQRB, L=3.4 sizes 005-072 General description A speed controlled drive system specifically adapted to drive rotary heat exchangers. No tuning is necessary. All control

More information

Domestia DME-LAN-002

Domestia DME-LAN-002 Domestia DME-LAN-002 Table of Contents 1. Hardware... 3 2. Description... 3 3. Connecting the DME-LAN-002... 4 4. Tablet configuration... 6 a) Language chosen for the tablet... 6 b) IP configuration...

More information

Optidrive Applications Support Library

Optidrive Applications Support Library Optidrive Applications Support Library Application Note Title AN-ODV-3-038 Related Products Optidrive Eco Overview Level 3 Modbus RTU Control and Register Mapping 1 Fundamental - No previous experience

More information

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51 Dryer M720 Programming and Operation Manual July 15, 2015 Revision 1.51 Contents 1 Important Safety Information 1 1.1 FOR YOUR SAFETY - CAUTION!............................. 1 2 Control Overview 2 2.1

More information

Phoebe LED Spectrum 10W RGB/Tuneable White downlight INSTALLATION AND APP INSTRUCTIONS

Phoebe LED Spectrum 10W RGB/Tuneable White downlight INSTALLATION AND APP INSTRUCTIONS Phoebe LED Spectrum 10W RGB/Tuneable White downlight INSTALLATION AND APP INSTRUCTIONS Contents 1. Product Installation...4 2. Space Requirements & Wiring Diagram...6 3. App Set-up & Adding Lights...7

More information

P4472 Save A Watt HD Operation Manual

P4472 Save A Watt HD Operation Manual P4472 Save A Watt HD Operation Manual Thank you for purchasing the P4472 Save A Watt HD. This operating manual will provide an overview of the product, safety instructions, a quick guide to operation,

More information

MODEL 9386 MULTI-SPORT TIMER

MODEL 9386 MULTI-SPORT TIMER MODEL 9386 MULTI-SPORT TIMER Instruction Manual Address: 34 Main Street, Whitesboro, NY 13492 Phone: 315-736-3967 Toll Free: 800-383-6060 Fax: 315-736-4058 SCOREBOARDS TIMERS MESSAGE SIGNS VIDEO DISPLAYS

More information

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide Beyond Comfort VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide August 10 th, 2010 (For Commercial and Lodging HVAC Fan Coil Applications) 028-0296-R1-LIT-VC3000-E01 Index

More information

MSR 2400W. Multi purpose Power System for Telecom and Industrial Applications. Nominal Output Voltage. Voltage Setting Range

MSR 2400W. Multi purpose Power System for Telecom and Industrial Applications. Nominal Output Voltage. Voltage Setting Range MSR 2400W Multi purpose Power System for Telecom and Industrial Applications 2400 W modular system All voltages available 0 144VDC per module U and I adjustable from 0 to max value Hot-swap plug-in modules

More information

Operation Guide CT32 ENGLISH

Operation Guide CT32 ENGLISH Operation Guide CT32 The CT32 communicating thermostat operates via a high-quality, easy-to-use touch screen. To set or adjust your CT32, simply touch your finger firmly to the screen. The screen will

More information

DC3IOB Revision User Guide Updated 3/29/10. Overview

DC3IOB Revision User Guide Updated 3/29/10. Overview Revision 080910 User Guide Updated 3/29/10 Overview The is a three axis DC brush motor drive with an integrated PLC. A range of motor drive currents are selectable with jumper blocks. The integrated PLC

More information

FP735Si Electronic 3-Channel Full Programmer for Heating and Hot Water with Service Interval Timer. Installation Guide MAKING MODERN LIVING POSSIBLE

FP735Si Electronic 3-Channel Full Programmer for Heating and Hot Water with Service Interval Timer. Installation Guide MAKING MODERN LIVING POSSIBLE MAKING MODERN LIVING POSSIBLE FP735Si Electronic 3-Channel Full Programmer for Heating and Hot Water with Service Interval Timer Danfoss Heating Installation Guide For a large print version of these instructions

More information

ALTERNATING RELAYS & CONTROLLERS ARM Series

ALTERNATING RELAYS & CONTROLLERS ARM Series ALTERNATING RELAYS & CONTROLLERS ARM Series Process Control Equipment for Hazardous Locations 7M26 UL913 INCLUDES INTRINSICALLY SAFE INPUTS Integrated Duplex Controller SOSO Operation (Sequence-on, Simultaneous-off)

More information

RT4F-110V/25A RECTIFIER

RT4F-110V/25A RECTIFIER The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

SBS-S SERIES DC LOAD BANK USER MANUAL

SBS-S SERIES DC LOAD BANK USER MANUAL 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com SBS-S SERIES DC LOAD BANK USER MANUAL Models Covered SBS-4830S SBS-1110S SBS-2206S

More information

REMOTE CONTROL OPERATING INSTRUCTIONS

REMOTE CONTROL OPERATING INSTRUCTIONS REMOTE CONTROL OPERATING INSTRUCTIONS 918-582a 07/11/06 Copyright 2006, FPI Fireplace Products International Ltd. All rights reserved. FPI FireWizard TM Remote Control Manual Page 1 WARNING Shock Hazard

More information

SPICE RACK DIMMER OPERATING MANUAL

SPICE RACK DIMMER OPERATING MANUAL SPICE RACK DIMMER OPERATING MANUAL SPICE RACK DIMMER OPERATING MANUAL This equipment is designed for professional stage lighting control only, and is unsuitable for any other purpose. It should only be

More information

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 TABLE OF

More information

DC3IOB Revision User Guide Updated 7/12/12. Overview

DC3IOB Revision User Guide Updated 7/12/12. Overview DC3IOB Revision 080910 User Guide Updated 7/12/12 Overview The DC3IOB is a three axis DC brush motor drive with an integrated PLC. A range of motor drive currents are selectable with jumper blocks. The

More information

Installation Instructions

Installation Instructions SPECIFICATIONS TS-400 InteliSwitch Digital Time Switch 20/277VAC Voltages... 20/277VAC, 50/60Hz Requirements @ 20VAC... 0-800W ballast @ 277VAC... 0-200W ballast @ 25VAC.../6 hp Time-Out Adjustment...

More information

Model P4470 Save A Watt Operation Manual

Model P4470 Save A Watt Operation Manual Model P4470 Save A Watt Operation Manual Thank you for purchasing the P4470 Save A Watt. This operating manual will provide an overview of the product, safety instructions, a quick guide to operation,

More information

Programmer User Manual CF800PROG

Programmer User Manual CF800PROG Programmer User Manual CF800PROG Cooper Safety Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB Tel: 01302 303 999 Fax:01302 303 333 South Yorkshire Web: www.cooperfire.com 1. General Description

More information

From lab to production, providing a window into the process. Universal Input Indicator Start-up Guide. Operating Manual.

From lab to production, providing a window into the process. Universal Input Indicator Start-up Guide. Operating Manual. Universal Input Indicator Start-up Guide Operating Manual -1- Contents 1. Setting up a unit straight out of the box 1.1. Entry into Configuration mode 1.2. Scrolling through Parameters and Values 1.3.

More information

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free Instruction Manual Model 1582-45L Data Switch September 2010, Rev A REMOTE LOCAL SWITCH STATUS SELECT REMOTE LOCAL LOCAL SELECT CHANNEL SELECT POWER MODEL 1582 SWITCH CROSS TECHNOLOGIES, INC. Data, drawings,

More information

ELSEMA 3 Phase Control Board, 3PH2, 3PHE

ELSEMA 3 Phase Control Board, 3PH2, 3PHE 3PH2 or 3PHE 3 Phase Control Board Features 2 versions - card only (3PH2) or enclosed with weatherproof box (3PHE) Built-in push buttons High-rated contactors for direct connection to the motor Separate

More information

DIN16A DIGITAL INPUT MODULE USER MANUAL

DIN16A DIGITAL INPUT MODULE USER MANUAL DIN16A DIGITAL INPUT MODULE USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO.,LTD. Chinese trademark English trademark SmartGen make your generator smart SmartGen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou

More information

Installation Instructions

Installation Instructions SPECIFICATIONS TS-400 InteliSwitch Digital Time Switch 00/20/230/277VAC Voltages....................... 00-277VAC, 50/60Hz Load Requirements @ 00/20VAC..................... 0-800W ballast @ 230/277VAC....................

More information

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment. Film-Tech The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment. These manuals are designed to facilitate the exchange of information related to cinema

More information

ARCTIC AIR DC OLED. Digital Control Operations Manual

ARCTIC AIR DC OLED. Digital Control Operations Manual ARCTIC AIR DC OLED Digital Control Operations Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526 WWW.Microair.net Allentown NJ 08501 Fax (609) 259-6601 Before you start: 1. Applying power:

More information

MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning

MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning Installation and User Guide www.microtrol.co.uk Contents 1. Supplied Parts...2 2. Important Information...3 3. Product Overview...4

More information

CT1 Series 2. General Purpose Timer. Installation Manual 1 st Edition

CT1 Series 2. General Purpose Timer. Installation Manual 1 st Edition CT1 Series 2 General Purpose Timer Installation Manual 1 st Edition FEATURES 4 Timing Ranges: - 1 to 127 seconds in 1 second increments. - 10 seconds to 21 minutes in 10 second increments. - 1 to 127 minutes

More information

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL USER'S GUIDE BARD-LINK TM LC1000-100/LC1500-100 SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead,

More information