1 Cyfrowy przetwornik wzmacniający dedykowany dla czujników tensometrycznych RQ INSTALLATION MANUAL Rev. 0.2
2 INDEX DEVICE PROPERTIES TECHNICAL PROPERTIES Pag. 2 TECHNICAL PROPERTIES (follow) Pag. 3 SYMBOLS Pag. 3 WARNINGS Pag. 3 DEVICE ID TAG Pag. 3 DEVICE CONNECTIONS DEVICE POWER Pag. 4 LOADING CELL CONNECTION Pag. 4 LOGICAL INPUT CONNECTION Pag. 5 RELE OUTPUT CONNECTION Pag. 5 SERIAL RS485 LINK UP (OPTION) Pag. 5 SERIAL RS232 LINK UP Pag. 6 ANALOG OUTPUT LINK UP Pag. 6 PROFIBUS LINK UP (OPTION) Pag. 7 DEVICENET CONNECTION (OPTION) Pag. 7 CONNECTION LIST Pag. 8 Pag. 1 RQ: Device Installation
3 TECHNICAL PROPERTIES 24 Vdc +-10% polarity revert protected. Power Protection device with replaceable fuse. Max Power tolerance 2 W (3W with field bus) Insulation Class II Working temperature -10 C +50 C (max 85% moist without water) Stocking temperature -20 C +60 C Weight Display Led Keyboard Red led 5 digit numeric 7-seg (h 7 mm) 2 3-mm led (output logic state) 3 mech button (behind the red front cover) Dimensions 110 mm x 120 mm x 23 mm (l x h x p) attachment included 110 mm x 120 mm x 35 mm (l x h x p) field bus present Installing material DIN profile support or OMEGA bar Supporting material Self extinguishing PC/ABS blend Connections Screw extract attachments size mm 5.08 The following are the setup data of the cell input: max 4 (350 Ohm in line) o Ohm cells. Input voltage 4Vdc Linearity < 0.01% lower edge Shift in temperature < 0.001% lower edge / C Internal Resolve bit Field measure From -2.6 mv/v to +2.6 mv/v Digital filter 0.1 Hz - 50 Hz on selection Weight decimal char Between 0 and 3 char Zero calibration and lower edge From keyboard. Cable interrupt check Ever online Logical output alarm Logical input Serial Port Baud rate Maximum cable lenght Field bus (OPTION) 2 relè output (24 Vcc/Vac NA connection) Rele maximum load 1A N 2 optoinsulated Rs232 half duplex Rs485 half duplex (opzionale) Fino a 115 kb/s (default 9600 b/s) 15m (Rs232) e 1000m (Rs485) PROFIBUS DP-V1 DeviceNet Next... RQ: Device Installation Pag. 2
4 Next TECHNICAL PROPERTIES Analog output voltage ± 10 V / ± 5 V Resolution 16 bits Calibration From keyboard Impede minimum 10K Linearity 0.03% lower edge Shift in temperature 0.002% lower edge / C Analog output Amperage 0 20 ma / 4 20 ma Resolution 16 bits Calibration From keyboard Impede max 300 Linearity 0.03% lower edge Shift in temperature 0.002% lower edge / C Memory for program code Data memory Law compliancy 32 Kbytes 2 Kbytes EMC EN , EN Electrical Security EN SIGNALS In this section the signals used in this handbook to catch the reader s notice: Warning! This procedure has to be executed by authorized personnel. Follow closely the following description. More information. WARNING The following procedures must be executed by authorized personnel. All the connection must be executed with the device offline and turned off DEVICE ID TAG It s important to report these data when requesting info or instructions regarding the device, moreover it s important to report the software version number and the release number (on the cover of the operating handbook or shown at device startup). Pag. 3 RQ: Device Installation
5 The device is powered thru connectors 23 and 24. The power cable must be kept aside from cables with different voltage, from the loading cells cables and from those for the logic input/output. The internal circuitry is fully insulated from the power voltage. DEVICE POWER Voltage : 24 Vdc/ 10 % max 3W CONNECTORS Alim LOADING CELLS CONNECTION The cell s (or cells) cable must not be kept in other cable s conduit (i.e. output connected with power cables or circuit breaker), but it must follow its own path. If cable extensions are needed these are to be safely shielded, taking note of the color code and the cable type stated from the device s builder. The extension s connection must be executed via soldering machines or via links or with a junction box that can be ordered aside. The cable must have a number of connector not higher than the ones used (4 or 6). If more connectors are present, link the remaining to cell power (link 2). No more than ohm cells can be connected to the device. The voltage is 4 Vcc and is shielded from temporary shortages. The device field measure needs the use of loading cells with an accuracy between 1 mv/v and 2.5 mv/v. The cable has to be connected to the terminals from 2 to 7 on the 7-pole extractable terminal. In the case of a 4-connector cable, the terminal to be connected are the following ( ). Connect the cable shielding to terminal 1. 4 CONNECTOR 2. POWER - 3. POWER + 4. CONNECT TO TERMINAL 3 5. CONNECT TO TERMINAL 2 6. SIGNAL - 7. SIGNAL + - SIGNAL + POWER + SIGNAL - POWER 2. POWER - 3. POWER + 4. REFEER + 5. REFEER - 6. SIGNAL - 7. SIGNAL + 6 CONNECTOR - SIGNAL + POWER + REEFER + SIGNAL - REEFER - POWER RQ: Device Installation Pag. 4
6 LOGICAL INPUT CONNECTION Both the logical input are shielded from the internal circuitry with an optoisolant. The connection cable for the logical input is to be kept aside from power cables. It has to be the shorter possible. To activate a logical input it has to be linked to the positive end of a 24Vcc output while the common connector is linked to the negative. In the following diagram there 2 types of connection using a button on input 2 and a circuit breaker on input 1. D E V I C E input input common 2 1 RELE OUTPUT CONNECTION Both output are connected to a common via relè. Every connection has a voltage of 24 Vcc/Vac 1 A. D E V I C E Output connect Output connect common SERIAL RS485 LINKUP (OPTION) This cable has to be kept aside from the others (power cables or cables connected to a circuit breaker), and has to keep its own path TX/RX + TX/RX - Pag. 5 RQ: Device Installation
7 SERIAL RS232 LINKUP To get a serial connection a shielded connection cable must be used, linking to mass the shield at one of the ends. In the case that the cable should have more connectors than needed, the unused ones should have to be connected to the shielding material. The serial connection cable must have a maximum lenght of 15 meters (as per EIA RS- 232-C rules), if the lenght is over that measure the device Rs422 interface must be used. This cable must be set aside from others cable (power cables or the one connected to circuit breaker), and it should follow a path on its own. The personal computer used for the connection must be EN compliant. The following is the diagram for the connection with a PC 9-poles connector: Data transmission Data reception Mass PC Connector (9poles) ANALOG OUTPUT LINK UP The device has two analog output one for the low frequency the other for the high. Data: Analog output high voltage: range between -10 and 10 Volt or between -5 and 5 Volt, minimum load 10K Analog output low voltage: range between 0 and 20 ma or between 4 and 20 ma, maximum load 300. With a factory reset it is possible to have an output 0-10V or 0-5V. To get the connection a shielded cable must be used, One of the end must be put to ground. Analog transmission can be disturbed by electo magnetic pulse. The cables must be shorter as possible and directed on a path of their own Low Voltage High Voltage Shared Analog Output RQ: Device Installation Pag. 6
8 PROFIBUS LINK UP (option) When this option is present the device is equipped in the lower side with a field bus PROFIBUS DP connector. Data: PROFIBUS baudrate from 9.6 kbps to 12 Mbps. PROFIBUS LINE LINK UP DSUB-9P male connector for the PROFIBUS cable PROFIBUS CABLE To get this connection a PROFIBUS cable must be used. For the link up the file HMS_1810.GSD (given with the device) must be present on the PLC/LC. WARNING: if PROFIBUS connection is present, there can be no RS485 output. DEVICENET LINK UP (opzionale) The device, with this hardware setup, carries in the lower part a 5-pole extractable terminal. Data: DEVICENET baudrate 125, 250, 500 kbps. DEVICENET LINE CONNECTION 5-poles male connector Pag. 7 RQ: Device Installation
9 CONNECTION LIST NUM. 9P terminale 5.08 mm 8 RS232 TX 9 RS232 RX 10 RS232 GND 11 RS RS485 - OPTION 13 Display 14 Analog Output GND 15 Analog Output 4-20 / 0-20 ma 16 Analog Output ± 10V / ± 5V NUM. 8P terminal 5.08 mm 17 Common input 18 Input 1 (optoinsulated) 19 Input 2 (optoinsulated) 20 Common output 21 output 1 (24 Vdc relè 1A NA) 22 output 2 (24 Vdc relè 1A NA) 23 Power 24 Vdc 24 Powe 0 Vdc 7P terminal 5.08 mm NUM. 6 cables cells version 1 Display 2 - cells power 3 + cells power 4 + refeer 5 - refeer 6 - signal 7 + signal 7P terminal 5.08 mm NUM. 4 cables cells version 1 Display - Cell power 2 Bridge with terminal 5 + Cell power 3 Bridge with terminal Signal 7 + Signal RQ: Device Installation Pag. 8
INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3
INSTALLATION MANUAL LC 200 Electronic Overload Guard Software versione PW0501 R 0.3 CONTENTS MAIN FEATURES LC 200 TECHNICAL FEATURES Page 2 SYMBOLS Page 3 WARNINGS Page 3 IDENTIFICATION DATA PLATE Page
More informationCDN502 HIGH DENSITY I/O ADAPTER USER GUIDE
CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE 13050201 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS DN502 PRODUCT OVERVIEW 1 DN502 INSTALLATION 1 POWER
More informationUSER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX
USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX DOCUMENT NO: TDC 0550 MANUAL - 2 1.0) INTRODUCTION. PAGE 2 1.1) ABOUT THIS MANUAL. PAGE 2 1.2) INTRODUCTION. PAGE
More informationCDN503 HIGH DENSITY I/O ADAPTER USER GUIDE
CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE 13050301 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS DN503 PRODUCT OVERVIEW 1 DN503 INSTALLATION 1 POWER
More informationSee instructions to download and install the latest version of LinkBoxMB and the user's manual at
Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationXPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name
Product data sheet Characteristics XPSMF3542 Preventa safety PLC compact - Profibus DP protocol Main Range of product Product or component type Safety module name Safety module application Nov 13, 2018
More informationicex-cmtm General specs and Installation guide
icex-cmtm General specs and Installation guide 1. General view 2. Specifications 2.1. Common specs: Ethernet 1 x 10/100Base/T, RJ45 connector with traffic and link LED Serial Interface 1 x RS232/485 USB
More informationR1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)
Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE
More informationSCB-C08 USB to RS232/422/485 Converter
SCB-C08 USB to RS232/422/485 Converter USB Interface RS-232 signal RS-422 signal: RS-485 signal: Cable Type Transmission distance Signal LED Direct power from USB port Power consumption: Compliant with
More informationSee instructions to download and install the latest version of LinkBoxEIB and the user's manual at
Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationSee instructions to download and install the latest version of LinkBoxMB and the user's manual at
Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationSee instructions to download and install the latest version of LinkBoxMB and the user's manual at
Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationICF-1150 Series Quick Installation Guide
ICF-1150 Series Quick Installation Guide Second Edition, March 2012 2012 Moxa Inc. All rights reserved. P/N: 1802011500011 Overview Introduction The ICF-1150 series fiber converters are equipped with a
More informationSee instructions to download and install the latest version of LinkBoxEIB and the user's manual at
Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationSerial Communication Converters & Adapters Instruction Manual
Serial Communication Converters & Adapters Instruction Manual RS-232 to RS-422/485 Converter Isolated RS-232 to RS-422/485 Converter USB to RS-232 Converter USB to RS-422/485 Converter Isolated USB to
More informationReference Guide METTLER TOLEDO WMH Weighing Platforms
Reference Guide METTLER TOLEDO Weighing Platforms Mettler-Toledo GmbH 2005 Doc.No. KA021, 42908713C Weighing Platforms Reference Guide Contents 1 Initial Setup... 4 1.1 Installation... 4 1.2 Electrical
More informationSee instructions to download and install the latest version of LinkBoxMB and the user's manual at
Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationRTU560 Connections and Settings DIN Rail RTU 560CIG10
Connections and Settings DIN Rail RTU 560CIG10 Application, characteristics and technical data have to be taken from the hardware data sheet: 560CIG10 1KGT 150 719 Operation The 560CIG10 is a DIN rail
More informationIntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng
IntesisBox Modbus Server KILSEN KSA-7xx User s Manual 08/2013 r1.2 eng Intesis Software S.L. 2013 All rights reserved. Information in this document is subject to change without notice. The software described
More informationInstruction Manual for BE-SP3 Circuit. 10/21/07
Page 1 of 54 Instruction Manual for BE-SP3 Circuit. 10/21/07 Page 1 Index: Page 2 BE-SP3 Circuit Specifications. Page 3-4 Intro to the BE-SP3. Page 5 Basics of serial to parallel. Page 6-7 ASCII Code.
More informationG3 Series PROFIBUS DP Technical Manual
G3 Series PROFIBUS DP Technical Manual Table of Contents G3 Series PROFIBUS DP Technical Manual PAGE About PROFIBUS-DP...3 Overview...3 G3 PROFIBUS-DP Features...3 Cabling and Drop Line Lengths (as defined
More informationBSL Hardware Guide for MP35 and MP30-1 -
BSL Hardware Guide for MP35 and MP30-1 - MP35/30 ACQUISITION UNIT The MP35/30 data acquisition unit is the heart of the Biopac Student Lab PRO System. The MP35/30 has an internal microprocessor to control
More informationStrain Gauge Converter
EN Z-SG General Description Module Z-SG is a strain gauge signal converter. Measurements taken using the 6-wires or 4-wires technique are available through Modbus-RTU serial protocol or the analog output.
More informationUSER S MANUAL SI-700 SI EIA-232/ EIA-485 INTERFACE JUL / 05 SI-700 VERSION 1 FOUNDATION
USER S MANUAL SI-700 SI-700 - EIA-232/ EIA-485 INTERFACE JUL / 05 SI-700 VERSION 1 TM FOUNDATION S I 7 0 0 M E smar www.smar.com Specifications and information are subject to change without notice. Up-to-date
More informationAFO485 : FIBRE OPTIC MODEM RFO485 : FIBRE OPTIC REPEATER. USER GUIDE Doc. ref : Distribué par : Contact :
Distribué par : Contact : hvssystem@hvssystem.com Tél : 0326824929 Fax : 0326851908 Siège social : 2 rue René Laennec 51500 Taissy France www.hvssystem.com AFO485 : FIBRE OPTIC MODEM RFO485 : FIBRE OPTIC
More informationA general-purpose industrial input/output
A general-purpose industrial input/output Iono MKR is a versatile and compact IO module compatible with all the Arduino MKR boards. All the power of the Arduino platform, combined with WiFi, BLE, GSM,
More informationGSV-1A4 M12/2 M12/2. Highlights
GSV-1A4 M12/2 M12/2 Highlights Input sensitivity: 2mV/V; 4mV/V, 2 mv/v, 1mV/V, 0.5mV/V configurable via jumpers Output signals ±10V AND 12mA+-8mA on 15 pin Sub-D Integrated half and quarter bridge completion
More informationSafety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationBACnet/IP to BACnet MS/TP Router
BACnet/IP to BACnet MS/TP Router Features Compact Size Routes between BACnet /IP and BACnet MS/TP networks 10/100Mbps Ethernet Auto-MDIX port Optically isolated MS/TP communications port MS/TP baud rates:
More informationXPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output
Product datasheet Characteristics XPSMF4000 Preventa safety PLC compact - Safe Ethernet Main Range of product Product or component type Safety module name Safety module application Preventa Safety automation
More informationi-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products
i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual (Version 1.01) PAGE:1
More informationWiring Section 3-3. NQ-Series communication ports support various types of (serial) communication.
3-3 Wiring NQ-Series models have, besides one power connector, a number of communication ports. Please refer to Table 2.2: Common specifications for NQ-Series and Table 2.3: Specifications per NQ-Series
More informationEL731 PROFIBUS INTERFACE
Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/el731 EL731 PROFIBUS INTERFACE Revision 0-A-032816 Copyright 2016 Littelfuse Startco All rights reserved. Document Number: PM-1011-EN
More informationG3 Series DeviceNet TM Technical Manual
G3 Series DeviceNet TM Technical Manual Table of Contents G3 Series DeviceNet Technical Manual PAGE About DeviceNet... 3 Overview... 3 G3 DeviceNet Features... 3 Cabling and Drop Line Lengths (as defined
More informationVersaMax IP I/O Module
Module accepts four digital input signals and provides four digital outputs. It connects to a local bus that is interfaced to a Profibus-DP / PROFINET network by a Profibus Interface Unit (IC677PBI001)
More informationCDN220 HIGH DENSITY I/O ADAPTER USER GUIDE
CDN220 HIGH DENSITY I/O ADAPTER USER GUIDE 13022001 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS CDN220 PRODUCT OVERVIEW 1 CDN220 INSTALLATION 2 POWER
More informationAD-8923-BCD. Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD
AD-8923-BCD Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD4002137 2010 A&D Company, Limited. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, or translated
More informationFieldbus slave modules w/o I/Os
tem SLIO Fieldbus slave modules w/o I/Os tem 500S tem 300S tem 100V Order number Figure Type IM 053CAN, CANopen slave IM 053DN, DeviceNet slave IM 053DP, PROFIBUS-DP slave IM 053EC, EtherCAT slave General
More informationInstruction Manual. M Pump Motor Controller. For file reference, please record the following data:
Instruction Manual M Pump Motor Controller For file reference, please record the following data: Model No: Serial No: Installation Date: Installation Location: When ordering replacement parts for your
More informationThe accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.
INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. This manual
More informationOperation Manual Profibus DP -Display HE 5120 P with digital I/O's
Operation Manual Profibus DP -Display HE 510 P with digital I/O's "HESCH" Schröder GmbH Boschstraße 8 31535 Neustadt Telefon +49 (0) 503 / 9535-0 Telefax +49 (0) 503 / 9535-99 e-mail: info@hesch.de http://www.hesch.de
More informationABB Drives. User s Manual Modbus Adapter Module FMBA-01
ABB Drives User s Manual Modbus Adapter Module FMBA-01 Modbus Adapter Module FMBA-01 User s Manual 3AFE68586704 REV A EN EFFECTIVE: 27.06.2005 2005 ABB Oy. All Rights Reserved. 5 Safety instructions
More informationSCHMIDT Sensor interface PROFIBUS Instructions for use
SCHMIDT Sensor interface PROFIBUS Instructions for use Table of contents 1 Important information... 3 2 Intended use... 4 3 Electrical connection... 4 4 Signalizations... 7 5 Startup... 9 6 Technical data...
More informationProfiHub A5. 5 Channel DP Repeater
ProfiHub A Channel DP Repeater The well-known ProfiHub A is a robust network component for PROFIBUS DP installations. It allows long multi-device spur lines and backbone structures with star/tree segments
More informationPROFIBUS-DP/MODBUS RTU REPEATER
RP303 PROFIBUS-DP/MODBUS RTU REPEATER USER S MANUAL JAN/15 RP303 R P 3 0 3 M E smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is available
More informationSee instructions to download and install the latest version of LinkBoxLON and the user's manual at
Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any
More informationFiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers
Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers Analog Data Links Multi-Channel Contact Closures Multiplexers Digital Data Links - Contact Closures Power Supply
More informationADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual
ADAM-510 RS-/RS-85 Repeater ADAM-510S Isolated RS-/85 Repeater ADAM-50 Isolated RS-/85 Converter Startup Manual Packing List Before you begin installing your module, please make sure that the following
More informationLCI Load Cell Junction Box with Fault Monitor
LCI Load Cell Junction Box with Fault Monitor User Manual www.mantracourt.co.uk The LCI Load Cell Failure Alarm Manual Chapter 1 Introduction to the LCI...2 Chapter 2 Installing the LCI...3 Figure 2.1
More informationPAC BI-DP BIM and 8701-CA-BI Carrier
June 2013 PAC8000 8507-BI-DP BIM and 8701-CA-BI Carrier PROFIBUS DP Bus Interface Module and Carrier The 8507-BI-DP Bus Interface Module (BIM) provides the communications link between the PAC8000 series
More informationS125 Multi-Purpose 125 KHz RFID Reader USER MANUAL. 9V/24V DC Operating Voltage, AC (optional) KHz RFID EM4100/2 Cards & Tags
S125 Multi-Purpose 125 KHz RFID Reader 44 mm USER MANUAL MULTI PURPOSE 84 mm ONLINE & OFFLINE MODE BUILT-IN RELAY 125 KHz RFID EM4100/2 Cards & Tags 9V/24V DC Operating Voltage, AC (optional) 3 Online
More informationVAL-62. Fieldbus modules FD67 Series Input, output and analog modules with IP67 ingress protection. Valves
Valves Fieldbus modules Reduced cabling and installation costs 256 I/O per node Single channel diagnostics IP67 Ingress protection Fully configurable I/O points Compact, robust construction Fieldbus nodes,
More informationI/O SIGNAL CONDITIONER
Technical Data Sheet No. TD9809M Rev. F Date of Issue: December 9, 2009 OPERATING MANUAL I/O SIGNAL CONDITIONER CAUTION: THIS PRODUCT DOES NOT PROVIDE GALVANIC ISOLATION. DO NOT ATTEMPT USE OF THIS PRODUCT
More informationEXPANSION PERIPHERAL CVM-R10 C. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.
EXPANSION PERIPHERAL CVM-R10 C (Code 7 70 217 ) INSTRUCTION MANUAL ( M 981 170 / 00 A ) (c) CIRCUTOR S.A. ------ CVM-R10 C Peripheral --------------- Pag. 1 CVM-R10C EXPANSION PERIPHERAL 1.- DESCRIPTION
More informationMCX08M2 Programmable controller
Data sheet MCX08M2 Programmable controller MCX08M2 is an electronic controller that holds all the typical functionalities of MCX controllers in the compact size of 8 DIN modules: programmability connection
More informationInstallation Guide Controller Series E130/E230/E430
Controller Series E0/0/0 Installation Guide Controller Series E0/E0/E0 Products E0-DP E0-DP E0-DP Content IMPORTANT NOTES FOR E0/E0/E0 SERIES CONTROLLERS... SYSTEM OVERVIEW... E0 SERIES FUNCTION AND WIRING...
More informationAnalog Current Input - 16 Channel IC693ALG223. Current Ranges. Power Requirements and LEDs. Location in System. Analog Input Modules
Analog Input Modules Analog Current Input - 16 Channel IC693ALG223 The 16-Channel Analog Current Input module provides up to 16 single-ended input channels, each capable of converting an analog input signal
More informationGateway 1400 Reference Manual
Profibus-DP Gateway 1400 Reference Manual Copyright All Rights Reserved. No part of this document may be copied, reproduced, republished, uploaded, posted, transmitted, distributed, stored in or introduced
More informationGeneral Specifications. P2-8AD4DA-2 Analog Input/Output
General Specifications Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic Side Isolation Insulation Resistance Heat Dissipation 1.95W º to 6ºC (32º to 14ºF)
More informationFeatures. Target Applications. V1.6 TBS07 RS485 to SDI-12 Converter
The is an interface box for connecting a PC, data logger or telemetry unit to one or more sensors with SDI-12 interface. The connects to a data logger, telemetry unit or other device with RS485 interface
More informationSerial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS
Serial Communications Accessories SITRANS RD200/300 Operating Instructions 05/2013 SITRANS Siemens Auto SIT SITRANS RD300RANS RD300 Safety Guidelines: Warning notices must be observed to ensure personal
More informationICF-1150 Series Quick Installation Guide
ICF-1150 Series Quick Installation Guide Fifth Edition, July 2015 2015 Moxa Inc. All rights reserved. P/N: 1802011500014 1802011500014 Overview Introduction ICF-1150 series fiber converters have a multi-interface
More informationUSER MANUAL Z-SG / Z-SG-L
USER MANUAL Z-SG / Z-SG-L Strain gauge converter with ModbusRTU protocol MI002633 Page 1 Non è stata trovata alcuna voce d'indice. Seneca Z-PC Line modules: Z-SG / Z-SG-L The Z-SG / Z-SG-L modules allows
More informationLCI User Manual mantracourt.com
LCI User Manual mantracourt.com LCI Load Cell Junction Box with Fault Monitor Contents Chapter 1 Introduction to the LCI... 2 Chapter 2 Installing the LCI... 3 Chapter 3 Setting up the LCI... 4 Sequence
More informationStrain Gage Measuring Amplifier GSV-3
Strain Gage Measuring Amplifier GS-3 Tel 03302 559 282, Fax: 03302 559 141, info@me-systeme.de, www.me-systeme.de 1 Strain Gage Measuring Amplifier GS-3 Description...4 Models...5 Measurement Resolution...5
More information1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882
1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature
More informationPM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features
PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER The PM174 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging
More informationECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.
ECAN-240 (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.0 Page: 1 Table of Contents Table of Contents -----------------------------------------------------------------------------2
More informationProfiPro Distributed PROFIBUS I/O Modules User Manual
ProfiPro Distributed PROFIBUS I/O Modules User Manual 15/03/2012 V1.0 22/195 Prospect Highway Seven Hills 2147 NSW Australia Tel: +61 (02) 96248376 Fax: +61 (02) 96208709 Email: proconel@proconel.com Web:
More informationMeasuring Amplifier DMS 50 Weight - Force - Pressure - Torque with strain gauges
+49-(0)40-670 73-0 Fax +49-(0)40-670 73-288 info@martens-elektronik.de www.ghm-messtechnik.de Measuring mplifier DMS 50 Weight - Force - Pressure - Torque with strain gauges Features M Bridge sensitivity
More informationDKG-210 UNIVERSAL INTERNET GATEWAY UNIT
DKG-210 UNIVERSAL INTERNET GATEWAY UNIT AC & DC SUPPLY VERSIONS DESCRIPTION The DKG-210 is designed for internet monitoring and control of industrial devices using different protocols through the RAINBOW
More information8-Port IP40 IEEE802.3af PoE Unmanaged Industrial Switch User s Manual
8-Port IP40 IEEE802.3af PoE Unmanaged Industrial Switch User s Manual Version 1.1 Content Overview... 1 Introduction... 1 Features... 2 Technical Specifications... 3 Packing List... 5 Safety Precaution...
More informationEnerSure Installation Guide
EnerSure Installation Guide Danger!!! The electrical components of this system may contain voltage and /or amperage sufficient to injure or kill. Installation is only to be performed by a licensed, bonded
More informationP2-04DA Analog Output. Removable Terminal Block Specifications
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from
More informationCSI 6300 SIS Overview
Overview The Digital Overspeed Protection System is TÜV - certified according to IEC 61508:2010 and provides speed measurement and detection of rotational direction for rotating machines such as turbines,
More informationUSB to RS-485/RS-422 Interface Converter. User Manual
USB to RS-485/RS-422 Interface Converter User Manual CONTENTS I. Summary 3 II. Functions..3 III. Hardware installment and application... 3 IV. Performance parameters........4 V. Connector and signal.......4
More informationProduct Description. Altus S. A. 1
Product Description The PO5064 and PO5065 modules are Ponto Series modular PROFIBUS-DPV1 slave heads for PROFIBUS fieldbus that can use all I/O modules from this Series. They can be connected to HMIs (keyboards
More informationLVX Control Unit. Features:
Date 2013-02-28 Control Unit Features: Most parameters can be defined as required for your interfaces. You decide which information is output and how. Fast cycle times, just a few µs/beam. Maximum beam-count
More informationInterfacing BU-70 Display Units and BU-100/BU-101 Panels
Interfacing BU-70 Display Units and BU-100/BU-101 Panels AutroSafe BU-70 Interface BSL-337 Protecting life, environment and property... 116-P-BSL337/EE, Rev. D, 2007-01-25 COPYRIGHT This publication, or
More informationTrident and Trident X2 Digital Process and Temperature Panel Meter
Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products
More informationThe TRSUN is the complete solution for the remote monitoring of photovoltaic plants.
The TRSUN is the complete solution for the remote monitoring of photovoltaic plants. Monitoring of inverters and string combiner boxes (up to 64 devices); Complete configuration of the monitoring system
More informationVPGate Manual PROFIBUS to serial
VPGate Manual PROFIBUS to serial Important information Purpose of the Manual This user manual provides information how to work with the VPGate PROFIBUS to serial. Document Updates You can obtain constantly
More informationP/N: AX Applications: power gen set engine control systems oil and gas equipment automation off-highway machine automation
TECHNICAL DATASHEET #TDAX031200 11:9 CAN CONTROLLER 11 Inputs (Analog, Digital, Magnetic Pick Up, Universal Signal) 4 Relay, 4 Analog, 1 Valve Driver Outputs 2 CAN (SAE J1939) with Electronic Assistant
More informationMiniAmp. Electronics & Software. Miniature Charge Amplifier. Type 5030A...
Electronics & Software MiniAmp Type 5030A... Miniature Charge Amplifier The MiniAmp Type 5030A is a single channel, industrial charge amplifier, which converts the charge signal from piezoelectric sensors
More informationioselect Z-NET Z-SG Bridge Input Isolating I/O Module
-wire Bridge Connection Excitation for to 30 Ω Load Cells 00 Volt (3-way) Isolation Excellent Accuracy (0.0%) DIP Switch Configuration Digital Input Tare Calibration RS8 Modbus RTU Superior Flexible Power:
More informationCMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual
CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual CMU 100 / 2.5.6.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6.6 12, CMU 100 / 2.5.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6 12,
More informationP2-04AD Analog Input. Removable Terminal Block Specifications
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from
More informationModbus Server - M-Bus (EN ) Gateway for the integration of M-BUS meters with Modbus RTU and TCP based control systems.
IntesisBox Server - M-Bus (EN 13757-3) Gateway for the integration of M-BUS meters with and based control systems. Integrate M-Bus meters into your master device or system (BMS, SCADA, PLC, HMI, TouchPanels
More informationSP336E Evaluation Board Manual Rev 2.1
SP336E Evaluation Board Manual 11-23-10 Rev 2.1 Features Easy Evaluation of the SP336E Transceiver RS-232 and RS-485 Protocols Local or Remote Loop Back testing 10Mbps Differential Transmission Rates Test
More informationUSER MANUAL Z-SG / Z-SG-L. Advanced Digital Strain gauge converter. Via Austria, PADOVA ITALY
USER MANUAL Z-SG / Z-SG-L Advanced Digital Strain gauge converter SENECA s.r.l. Via Austria, 26 35127 PADOVA ITALY Tel. +39.049.8705355 8705359 Fax. +39.049.8706287 Web site: www.seneca.it Technical assistance:
More informationDual Channel Monitor for Measurement of Speed and Ratio with SIL1 requirements Series D224.xx
D224 Dual Channel Monitor for Measurement of Speed and Ratio with SIL1 requirements Series D224.xx D224 Front View KEY FEATURES SIL1 / IEC 61508:2010 compliant Dual Channel Speed and Ratio Monitor with
More informationDiagnostics (Physical)
DeviceNet Spanner Rugged, Fully Potted Stations IP 67 Protection Communicate Between s Connect Two DeviceNet Networks FDN-DN1 Electrical Operating Current: 125 ma from segment A, 30 ma from segment B Power
More informationIndustriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH
Industriefunkuhren Technical Manual Signal Converter for DIN Rail Mounting Series 4800xx-yy ENGLISH Version: 01.01-19.07.2007 2 / 23 Signal Converter 4800 - V01.01 INPORTANT NOTES Downloading Technical
More informationConnecting a Cisco Input Module
CHAPTER 4 Overview The optional Cisco Input Module (Figure 4-1) is attached to a Cisco Physical Access Gateway or Cisco Reader Module to provide additional connections for up to ten input devices. Each
More informationUSB to RS232 Converter USB-013 (Rev3) User s Manual Ver. 1.2 HuMANDATA LTD.
USB to RS232 Converter USB-013 (Rev3) User s Manual Ver. 1.2 HuMANDATA LTD. Table of Contents Precautions... 1 Revision History... 2 Introduction... 2 1. Overview... 3 2. Power Supply... 3 3. Specifications...
More informationWS115 BREAKOUT ADAPTER USER MANUAL
STATIC WATER LEVEL MEASUREMENT WS115 BREAKOUT ADAPTER USER MANUAL www.enoscientific.com Page 1 Eno Scientific 1606 Faucette Mill Rd Hillsborough, NC 27278 USA www.enoscientific.com 910-778-2660 Copyright
More informationFLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW.
CENTRIFLOW PUR 3D (A, PLUG B, C, D) FAN GMPM FC101 AND SLIDE IN FREQUENCY ROTOR CASSETTE CONVERTER QUICK GUIDE FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS
More informationMC CO MODBUS ADDRESSABLE SENSOR
MC-4210 - CO MODBUS ADDRESSABLE SENSOR Manual Part Number 180-0545A March 31, 2003 PAGE 1 TABLE OF CONTENTS TITLE PAGE Table of Contents...2 List Of Figures...4 1. Introduction...5 1.0. General...5 1.1.
More informationMPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice
MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction... 3 Product Overview... 3 About DeviceNet... 4 Overview... 4 MPCR DeviceNet Features... 4 Cabling and Drop Line Lengths
More informationProgrammable Set for Simple I/O Communication via PROFIBUS-DP in IP67 TI-BL67-PG-DP-S-8
Type designation Ident no. 1545097 Number of channels 8 Dimensions (W x L x H) 204 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 12 Mbps
More information