1 1 HVDC Innovation, XECHNO Power & Fresh HVDC Energy Saving Technology for the Data Center Green Consulting Business Unit Solution Business Division NTT DATA INTELLILINK Corp.
2 Problems facing data centers: Energy efficiency There are so many AC/DC and DC/AC converts in a data center. Conversion causes power loss and dissipates heat, and requires more power to cool. Power Grid Transformer UPS PDU ITE ( e.g. Server ) AC DC AC DC Energy ( Power ) Loss More heat, more cooling Copyright 2013 NTT DATA INTELLILINK Corporation 2
3 IT equipment are fundamentally DC powered Most electric appliances have an internal power supply converting AC to DC. Why not directly feed them DC power? Power Supply Power Supply Power Supply Power Supply Inverter Copyright 2013 NTT DATA INTELLILINK Corporation 3
4 4 Trend: from UPS to DC+Battery Google AC480V AC200V SERVER RACK AC-SERVER DC12V Microsoft SERVER RACK DC12V-SERVER DC12V Facebook DC48V SERVER RACK AC DC48V-SERVER DC12V Battery RACK Facebook Open Compute project Open Rack Hardware v1.0 V1 Power shelf DC48V Battery RACK SERVER RACK DC12V-SERVER DC12V Facebook Open Compute project Open Rack Hardware v1.0 V2 Power shelf SERVER RACK DC12V-SERVER DC12V
5 Our proposition: HVDC and DC 12V ITEs Our HVDC power system reduces AC/DC conversions between Grid and ITE. Power loss is reduced approximately by 10-20%. Fresh HVDC XECHNO Power Power Grid Transformer PS Rack PDU Server Rack Central Redundant Power Supply AC DC 340V DC 12V Copyright 2013 NTT DATA INTELLILINK Corporation 5
6 Safety Traditional HVDC pain points have been removed AC PS Rack AC DC DC340V HVDC PDU DC340V HVDC Server Rack DC12V Server DC12V Mother CPU Memory HDD Battery Key Technology : Middle Point Ground Central Redundant Power Supply Key Technology : Bus Bar Current is limited within safety limit for Key Technology : Arc Suppression Circuit W/O Suppression Circuit W/ Suppression Circuit Less chance of fire Copyright 2013 NTT DATA INTELLILINK Corporation Resolved the arc discharge issue at the time of switch-on/off and disconnection. 6
7 7 Reliability: redundancy Non-stop maintenance and expansion through N+1,2 redundancy Server Rack 4kW Rectifier Rack ITE ( DC Server ) Input Failure PDU DC/DC 2kW Failure ITE ( DC Server ) ITE ( DC Server ) ITE ( DC Server ) ITE ( DC Server ) DC12V Central Redundant Power Supply DC/DC 2kW DC/DC 2kW Backup Backup
8 8 Reliability: fewer failure points Simpler architecture = less component count and failure points. Failure Point Failure Point Failure Point UPS Battery Switch Failure Point Mother Board AC ITE ( Server ) HVDC + DC12V Natural flow like a River Path- Through Mother Board Non-Voltage Flicker, Non-Stop, Non- Interruptible Power through N+1 Redundant Operation Battery HVDC Non-Voltage Flicker, Non-Stop, Non- Interruptible Power through N+1 Redundant Operation DC12V ITE ( Server )
9 9 Pass-through box A drop-in replacement for AC/DC power supply of conventional ITEs Only some protection circuitry No fan No liquid capacitor No need for certification Lots of space to add value Battery Sensors... and more
10 10 Combining DC sources: HVDC + Solar + Battery No need for power conditioner (no MPPT) Locally generate & consume Existing Solar Power Generation Power Conditioner DC Our testbed AC Power Company Data Center HVDC + Solar Simple & Direct Power Loss Reduction : 5 % - 10% DC Power Company HVDC DC Data Center
11 11 Production use: Ishikari DC, Sakura Internet Co. Ltd. In service, March racks, 160 kw
12 12 For greater ecosystem of HVDC -through box. What can we do to support Open Compute compliant equipment? Conventional ITE ( DC12V ) Open Compute ITE ( DC12V )
13 13 Discussion Points AC/DC --DC conversion for Facebook data centers (or Colo sites adopting OC servers)? Can we collaborate? DC/DC (Any issues?) Bus Bar (Bus bar-midplane connectors: Simply a choice of which physical shape?) ITE Input voltage fluctuation tolerance: Can we standardize on it? Open Compute mobo: 12.5 Vdc within range Conventional mobo: 12.0 Vdc within range ( 5%) Protection circuitry: Is there an Open Compute spec? Can we eliminate redundancy if any?
14 Global IT Innovator Copyright 2011 NTT DATA Corporation Copyright 2013 NTT Copyright DATA INTELLILINK 2013 NTT Corporation DATA INTELLILINK Corporation 14
Cisco CRS 16-Slot Chassis Power Systems
This chapter includes the following sections: Power specifications are provided in Technical Specifications Power Systems Overview, on page 1 Power Component Information Common to the Two Types of Power
More informationHVDC (High Voltage Direct Current) New Feeding Method for High Efficiency Data Centre
(High Voltage Direct Current) New Feeding Method for High Efficiency Data Centre Background APEC at Yokohama JAPAN (Nov. 2010) One of the Action list supporting the APEC leaders strategic growth is, Promote
More informationE f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n
E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; 4 0 0 V D C p o w e r f e e d s o l u t i o n Juha Klemola / HW Architect / Nokia Introduction to the challenge Datacenter
More informationWhy Not Operate Data Centers & Telecom Central Offices at 400 VDC???
Why Not Operate Data Centers & Telecom Central Offices at 400 VDC??? Dennis P. Symanski Senior Project Manager 2009 IBM Power and Cooling Technology Symposium 20-21OCT2009 Rochester, MN Data Center Energy
More informationInfinisolar V Hybrid-On Grid Inverter with Energy Storage
Infinisolar V Hybrid-On Grid Inverter with Energy Storage Pure sine wave output Self-consumption and Feed-in to the grid Programmable supply priority for PV, Battery or Grid User-adjustable charging current
More information24/48V Battery Bank Ah High Cycling Long Life
Outdoor Power Cabinets, 48V DC Free Cooled with Combined Air-Con. PreFactory assembled with 19 inch Power sub rack, 2 or 4 battery Shelf s, 3U DCAC Panel combined with rectifiers 2U or 4U Power Module
More informationInverter W and 12500W
Inverter SIRIO EVO 10000W and 12500W w w w. a r o s - s o l a r. c o m w w w. a r o s - s o l a r. c o m SIRIO EVO CLASS B DIFFERENTIAL Each device has an internal type B differential protection in compliance
More informationComposed by 3 partners: Polesso, Huang and Bet; Started manufacturing OEM power supplies for computers.
ABOUT US Established in 1984 (São Paulo Brazil); Composed by 3 partners: Polesso, Huang and Bet; Started manufacturing OEM power supplies for computers. 2 CORE BUSINESS Design and production of: Power
More informationPros and Cons of Various DC Distribution Architectures
Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification
More informationThe 3-phase, 5-wire model name is PF LNM. The 3-phase, 4-wire model name is PF LNN.
The 12.5kW power shelf accepts 3-phase input power and provides stable DC output power (1000A at 12.5VDC). The OCP 21-inch power shelf includes a total of 5+5 high-power, hot-swappable PSUs in redundant
More informationPRODUCT FEATURES AND ADVANTAGES
Flatpack2 24/1800 HE 24VDC Rectifier/Converter Modules The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out. With efficiency up to 96.2%, the losses have been
More informationFS Series PV Modules Reverse Current Overload
FS Series PV Modules Reverse Current Overload Purpose The purpose of this document is: to describe the system conditions that can cause reverse current overload (RCOL) and the behavior of FS modules in
More informationGRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2
USER MANUAL MPI-1500/2000/3000/4000/6000 Series GRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2 WWW.MPPSOLAR.COM WARNING: ONLY A CERTIFIED ELECTRICIAN OR TRAINED ASSEMBLING PROFESSIONAL SHOULD OPEN OR INSTALL
More informationHuawei FusionHome Smart Energy Solution
Smarter Energy for a Better Life Huawei FusionHome Smart Energy Solution Smart Energy Center SUN2000-3.8/5/7.6/9/10/11.4KTL-USL0 Higher Yields High efficiency inverter topology, CEC efficiency 99% Simple
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More information1. Introduction. 3. Features. 2. Background of the Development. 3.1 All-In-One Structure. New Products Introduction
New Products Introduction Development of Power Conditioner for Photovoltaic Power Generation, SANUPS P73D103 Norio Tazawa Akinori Matsuzaki Takeshi Hama Yuuji Wada Hiroshi Yamada Tomohiro Nishibori Katsutoshi
More informationHYBRID PV INVERTERS HySpirit Series. 4kW-10kW. Hybrid Inverter with Battery Backup Smart Energy for Smart Home
HYBRID PV INVERTERS HySpirit Series Hybrid Inverter with Battery Backup Smart Energy for Smart Home 4kW-10kW FSP HySpirit series Offers a more intelligent power solution for our customers to reduce the
More informationLinkedin Open19 Deep Dive
Linkedin Open19 Deep Dive Yuval Bachar Principal Engineer, Global Infrastructure & Strategy at Data Center Philosophy Every element in the data center is a server Appliance free data centers Multi-Supplier
More information1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA
The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance
More informationHigh Voltage Direct Current Power Solutions for Data Centers
High Voltage Direct Current Power Solutions for Data Centers Professor: Dr. Danny Silver Acadia University Student Name: Jim Nasium Published: April 10 th, 2011 1. Introduction As the demand on data centers
More informationConverged Power Solutions. Data center power reinvented
Converged Power Solutions Data center power reinvented always on anywhere anytime With Eltek s Converged Power Solutions, the next generation power solution for data centers is here. It offers unmatched
More informationCPS VS UPS FOR POWERING DATA CENTERS
CPS VS UPS FOR POWERING DATA CENTERS HOW THE ADVANTAGES OF A NO BREAK CONVERGED POWER SYSTEM (CPS) PROVIDED BETTER POWER RELIABILITY, SYSTEM AVAILABILITY AND REDUCED COSTS OVER A UNINTERRUPTABLE POWER
More informationCompute Engineering Workshop March 9, 2015 San Jose
Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud
More informationGTI 300W GTI 500W GTI 600W GTI 800W GTI 1000W
GTI 300W GTI 500W GTI 600W GTI 800W GTI 1000W GTI Series Inverters For Grid User Manual System Function Directly connected to the solar panels (do not need to connect the battery) Using precise MPPT function,
More informationMICRO BURN IN PRODUCTS LISTED IN MODEL NUMBER ORDER FOLLOWED BY A BRIEF DESCRIPTION
MICRO BURN IN PRODUCTS LISTED IN MODEL NUMBER ORDER FOLLOWED BY A BRIEF DESCRIPTION MODEL 102P 102R DESCRIPTION Floor Stand (Plane) Floor Stand (Modified) HTRB Burn-In System (diode) Component Burn-In
More informationthe Centric 300 An advanced modular UPS up to 1800kVA/kW
the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has
More informationUser s Manual USB 3.0 Expansion Card TS-PDU3
User s Manual USB 3.0 Expansion Card TS-PDU3 (Version 1.6) Table of Contents Introduction...1 Package Contents...1 Features...2 System Requirements...2 Safety Precautions...3 General Use... 3 Transferring
More informationPCM SLK- Series Inverter Specification
PCM SLK- Series Inverter Specification Page 1 of 7 General Specification Introduction Environment The inverters are designed to be outdoor types. Models In field applications, the power demands from 1.5kW
More informationALL PSU Ltd ROTATION+ 6kVA - 10kVA PARALLEL ON LINE DOUBLE CONVERSION
ALL PSU Ltd Unit D6 Laser Quay, Culpeper Close Medway City Estate, Rochester, Kent, ME2 4HU Phone: 01634-725527 Fax: 01634-739111 E-mail: sales@allpsu.co.uk Web: www.allpsu.co.uk ROTATION+ 6kVA - 10kVA
More informationLBC Series 3-phase PSU / Battery Charger
3-phase PSU / Battery Charger The shelf consists of a ruggedized Battery Charger, PSU with a 3-phase input for 400 / 480 VAC (line to line) and with an output suitable for 110V battery charging. DC-DC
More information380VDC Data Center Duke Energy Charlotte, NC
380VDC Data Center Duke Energy Charlotte, NC Dennis P. Symanski EPRI - Senior Project Manager Silicon Valley Leadership Group 2011 Data Center Efficiency Summit 18NOV2011 IBM - San Jose, CA 380VDC Data
More informationCooling System. Cooling System Overview. 16-Slot Line Card Chassis Airflow
This chapter describes the components that make up the cooling system of the Cisco CRS Series Carrier Routing System 16-Slot Line Card Chassis. It contains the following sections: 16-Slot Line Card Chassis
More informationPS2328 Integrated Power. System
PS2328 Integrated Power System 1 Power System consists of: CONTROL / EXPANSION MODULE One rack (Power Supply Housing). Two identical 48V @ 2000W (1+1 redundant) or Two identical 1500W (1+1 redundant) or
More informationAC-DC Converter RECE K21
Thanks to the variety of modules available, the RECE3200-230-48-K21 system offers the perfect solution for all areas of applications requiring a power output of up to 3,2kW. Modular Battery Charger / Inverter
More informationDevelopment of Small Capacity UPS, "SANUPS 001 ASC"
1 / 6 SANYO DENKI Technical Report No.5 May 1998 Feature Development of Small Capacity UPS, "SANUPS 001 ASC" Yoshihiro Wada Chiaki Seki Hitoshi Yoshiike Akira Yajima 1. Introduction Computers are becoming
More informationExtending Energy Efficiency. From Silicon To The Platform. And Beyond Raj Hazra. Director, Systems Technology Lab
Extending Energy Efficiency From Silicon To The Platform And Beyond Raj Hazra Director, Systems Technology Lab 1 Agenda Defining Terms Why Platform Energy Efficiency Value Intel Research Call to Action
More informationDC / AC True RMS Watt Clamp DMM
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 380940 Product Page DC / AC True RMS Watt Clamp DMM 10W or 100mA
More informationNext Generation Data Center Facilities Design. Presenter: Ping Lin
Next Generation Data Center Facilities Design Presenter: Ping Lin ping.lin@cqinc.com.tw What is the greatest facility problem with your primary data center? 1. Excessive Heat 2. Insufficient raised floor
More informationLinkedin Open19 Deep Dive
Linkedin Open19 Deep Dive Yuval Bachar Principal Engineer, Global Infrastructure & Strategy at Data Center Philosophy Every element in the data center is a server Appliance free data centers Multi-Supplier
More informationSAT BMS. User Guide. Rev
SAT BMS User Guide Rev001. 2015.11 CONTENTS 1 SAFETY... 3 1.1 General guidance... 3 2 SAT BMS Introduction... 4 2.1 General overview... 4 2.2 BMS General wiring structure... 4 2.3 Hardware... 4 2.4 Program...
More informationAlternative Energy. Application Guide. Series and Field of Use. LVD Series. LVD Series. DCDC 1000 Watt. DCDC Series. GMT Series DB5-MG.
Alternative Energy Series and Field of Use LVD Series Low-Voltage Disconnect (LVD) stops battery damage due to over discharge by disconnecting the battery at an adjustable voltage. DCDC Series Regulated
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationRT12-240V/2.4kW Rectifier Specification
The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between
More informationHP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems
HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device
More informationPOWERING TECHNOLOGY. Reliably powering your business. Solving your power needs. DC POWER SYSTEMS
POWERING TECHNOLOGY Reliably powering your business. Solving your power needs. DC POWER SYSTEMS P O W E R I N G T E C H N O L O G Y UNIPOWER Systems today incorporates products from the former Power-One
More information380VDC Data Center At Duke Energy
380VDC Data Center At Duke Energy Dennis P. Symanski EPRI - Senior Project Manager Curtis Watkins Duke Energy - Senior Project Manager Emerging Technology (ET) Summit November 9, 2010 Sacramento, CA From
More informationMPPT Solar charge controller
MPPT Solar charge controller etracer series etracer is an industrial grade product with advanced Maximum Power Point Tracking (MPPT) algorithm. It can deliver the maximum available power for charging batteries
More informationSolis Single Phase Inverter
PV Grid Tie Inverter Solis Single Phase Inverter Installation and Operation Manual Ningbo Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712,
More informationAC-DC Converter REC /60-K20
Thanks to the variety of modules available, the REC3200-230-48-K20 system offers the perfect solution for all areas of applications requiring a power output of up to 3,2kW. Modular Battery Charger / Inverter
More informationAC-DC Converter REC K10
Rectifier System for Telecom-, Industry- and Rail applications General Electrical Safety EN 60950, UL 94 Protection class 1 Pollution degree 2 Isolation primary secondary 3.75kVDC PFC Ventilation EN 6100-3-2,
More informationHow Redundant Power Supplies Prevent System Downtime
How Redundant Power Supplies Prevent System Downtime When designing systems or products that must have a minimum downtime, the system s power source must be carefully selected. When and how to consider
More informationICTD-100CP / ICTD-101CP ICTD-102CP / ICTD-103CP
PATENT PENDING ICTD-100CP / ICTD-101CP ICTD-102CP / ICTD-103CP Capacitor Trip Devices with Contact Protect Technology TM Operation Manual and Data sheet 2015 Intermountain Electronics, Inc. Important Notice
More informationGAMATRONIC, A SolarEdge Division.
GAMATRONIC, A SolarEdge Division. 17 Hartum Street, POB 45029, Jerusalem 9777517,Israel Tel: +972-2-5888222 Fax: +972-2-5828875 e-mail: info@gamatronic.com www.gamatronic.com The Power+ Premium 60 is
More informationFusionSolar. Residential Smart PV Solution. FusionSolar
FusionSolar Residential Smart PV Solution FusionSolar Elegant design that fits your home more naturally SUNRISE Waking up from darkness to life, Energy is floating in and brightening Page 2 FusionSolar
More informationaentron Energy System 1 to 900 Vdc
aentron Energy System 1 to 900 Vdc The aentron lithium-ion energy system enables the realisation of a modular and scalable lithium-ion battery solution. The management of large lithium-ion batteries systems
More informationCisco TelePresence MSE 8000
Data Sheet Cisco TelePresence MSE 8000 Figure 1. Cisco TelePresence MSE 8000 Product Overview The Cisco TelePresence MSE 8000 (MSE 8000) is a high-capacity voice and video conferencing media services engine.
More informationPower On. In the Negative Space.
GE Critical Power Power On. In the Negative Space. Overview Throughout our history, we have developed innovations that meet the demands of an ever-changing market. Our approach is explorative; reimagining
More informationDATA CENTER TRANSFORMATION: THE IMPACT OF EMERGING POWER ARCHITECTURES ON TODAY S DATA CENTERS
DATA CENTER TRANSFORMATION: THE IMPACT OF EMERIN POWER ARCHITECTRES ON TODAY S DATA CENTERS TWO STAE POWER DISTRIBTION Entering the Cloud eneration The unprecedented capacity requirements of large social
More informationUPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications
INFINITE POWER Mission Critical Applications UPS UNINTERRUPTIBLE POWER SUPPLY centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw Rack-mountable modules designed for blades, data-center,
More informationQuick Start Guide. SEB-710 I/O Expansion board. Introduction
SEB-710 I/O Expansion board Revision 1.0 - (March, 2011) Saflec Systems (Pty) Ltd Quick Start Guide Introduction The SEB-710 is an I/O expansion device for additional inputs and outputs. It has eight relay
More informationGrid PV Inverter M30A & M50A. The power behind competitiveness Delta M30A & M50A. Product Features
The power behind competitiveness Delta M30A & M50A Grid PV Inverter M30A & M50A Product Features Transformerless inverter Dual MPP Trackers Peak efficiency up to 98.6% Connect up to 10 strings PV arrays
More informationDevelopment of small-capacity UPS "SANUPS ASD"
1 / 7 SANYO DENKI TECHNICAL REPORT No.11 May-2001 Feature Development of small-capacity UPS "SANUPS ASD" Tetsuo Suzuki Yoshitsugu Kashiwagi Hideaki Miyajima Masahiko Nagai Makoto Kitazawa Akira Yajima
More informationSLK Grid PV-inverter (UL) Installation and Operation Manual
SLK Grid PV-inverter (UL) Installation and Operation Manual Only an electro-skilled person or trained assembly staff can install or open the Inverter. Before you start Thanks for purchasing SLK Grid PV-Inverter.
More informationPowering Compute Platforms in High Efficiency Data Centers. Annabelle Pratt, Pavan Kumar, Kevin Bross, Tomm Aldridge
Powering Compute Platforms in High Efficiency Data Centers Annabelle Pratt, Pavan Kumar, Kevin Bross, Tomm Aldridge Agenda Defining a power-efficient efficient data center Improving power delivery efficiency
More informationSmart Inrush Current Limiter Enables Higher Efficiency In AC-DC Converters
ISSUE: May 2016 Smart Inrush Current Limiter Enables Higher Efficiency In AC-DC Converters by Benoît Renard, STMicroelectronics, Tours, France Inrush current limiting is required in a wide spectrum of
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1, 2N, 2(N+1) UPS topologies Large Free standing
More informationAC Power Quality and Protection
Lab 5-2 Video System Troubleshooting Copyright 2006 Heathkit Company, Inc. All Rights Reserved AC Power Quality and Protection 2 Today we will look at... AC Line Surge Suppressors Phone Line Surge Suppressors
More informationUser Manual. Solar Inverter for Water Pump
User Manual Solar Inverter for Water Pump SP Revival Series Version: 1.2 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 Inspection... 1 Installation... 1 Operation...
More informationPower Supply System for BTS Site
Power Supply System for BTS Site 48V300A extendable to 350A FnS Power Technology Inc. www.sacredsun.com, www.fnspower.com Page 1 of 7 48V300A(15KW) Power System Solutions and configurations 1 FS-Rectifier-48V50A
More informationUninterruptible power supply (UPS) S8BA & BU_2RWL series
Uninterruptible power supply (UPS) S8BA & BU_2RWL series Small size: 800g (Li-Ion batteries) Life expectancy of 10 years Plug-in installation industrial.omron.eu/s8ba 2 Uninterruptible power supply (UPS)
More informationoutput devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date:
Class: Date: MECH1500Quiz1ReviewVersion2 True/False Indicate whether the statement is true or false. 1. The number and type of I/Os cannot be changed in a fixed PLC. 2. In a PLC system, there is a physical
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationLiebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW. AC Power For Business-Critical Continuity
Liebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW AC Power For Business-Critical Continuity Emerson Network Power, a division of Emerson, is a global company that combines
More informationPRODUCT DESCRIPTION. Vertically cooled 2RU rectifiers with wide range of output modules available.
High Efficiency Module Eltek V-series rectifiers provide industry-leading efficiency in a 2 RU footprint. Reliability, scalability, and hot-swap capability make for optimal system design and cost-effective
More information1. Chapter 1 24/48/110/220VDC Power Supply System
1. Chapter 1 24/48/110/220VDC Power Supply System A. Outline of 24/48/110/220VDC Power Supply System Picture Picture 2*Rectifier module 3*Rectifier module 6*Rectifier module 10*Rectifier module Rectifier
More informationPEM Faults and Blower Failures
CHAPTER 2 The following sections provide methods for troubleshooting faults involving the Cisco 10000 series router Power Entry Modules (PEMs) and blower modules. This chapter contains the following major
More informationATK-2040 AC/DC TRMS Watt Clamp Meter Users Manual
ATK-2040 AC/DC TRMS Watt Clamp Meter Users Manual EN 61010-2-032 CAT II 600V, CAT III 300V Pollution Degree 2 SYMBOLS showed on the clamp meter or in this manual: Caution, risk of danger. Refer to accompanying
More informationMicroinverters And The Solar Industry
Microinverters And The Solar Industry Peter Lum Senior Learning And Development Professional Assistant Professor Skyline College Solar Continues Its Growth 2 Significant Growth Of Microinverters in Solar
More informationProduct Design Assessment (PDA) Certificate for Component Details
Product Design Assessment (PDA) Certificate for Component Details HIMax X-CPU01 Processor X-SB01 System Bus X-COM01 PS1000 X-DI 64 01 X-DI 3201 X-DI 3202 X-DI 3203 X-DI 3204 X-DI 3205 X-DI 1601 X-AI 3201
More informationEvolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development
Evolution of Facebook s data center design Veerendra Mulay, PhD Strategic Engineering and Development Agenda 1 Introduction 2 Electrical design 3 Mechanical design 4 Design evolution 5 RDDC Introduction
More informationDC Power Standards. Brian Fortenbery Energy Efficiency Group Power Delivery and Utilization Sector EPRI
DC Power Standards Brian Fortenbery Energy Efficiency Group Power Delivery and Utilization Sector EPRI Data Center Power Delivery System UPS 85-92% Power Dist 98-99% Power Supply 68-72% DC/DC 78-85% The
More informationEnergy efficiency management and environmental impact assessment for ICTs
http://eustandards.in/ Energy efficiency management and environmental impact assessment for ICTs Beniamino Gorini (ETSI TC-EE chairman) 2 Contents What is required to define sustainable ICT products/networks/services
More information22-60VDC Grid Tie Microinverter User Manual
22-60VDC Grid Tie Microinverter User Manual Thanks for using Smart Grid Tie Microinverters. Read the following instruction carefully before installation and operating, install and operate as specified
More informationSERVICE MESSAGES FRONIUS GALVO SERIES 1 ST OF SEPTEMBER 2013
SERVICE MESSAGES FRONIUS GALVO SERIES 1 ST OF SEPTEMBER 2013 Dear Fronius customer! These state codes will help you to ascertain errors of the FRONIUS Galvo inverters, the photovoltaic system as well as
More informationIntroduction to the Personal Computer
Introduction to the Personal Computer 2.1 Describe a computer system A computer system consists of hardware and software components. Hardware is the physical equipment such as the case, storage drives,
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More information-5K-2G. Solar PV Grid Tie Inverter. inverter. Installation and Operation Manual. 2013, Ningbo Ginlong Technologies Co., Ltd.
Solar PV Grid Tie Inverter -5K-2G inverter Installation and Operation Manual Ver 1.0 Ningbo Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712,
More informationISMG Solar Inverter. General Description. Type Selection. Ordering Key ISMG 1 50 EN. Approvals RD 1663/2000 RD 661/2007 DK5940 VDE
ISMG 1 60 General Description High PV input voltage range (suitable for voltage between 100 VDC to 450VDC) and efficient MPP Tracking Up to 2 / 3 independent MPP Tracking controlled by an exclusive Smart
More information(12) (10) Patent No.: US 9,622,373 B1. Sarti (45) Date of Patent: Apr. 11, (54) HIGH VOLTAGE DIRECT CURRENT s ck 358. SE et al.
United States Patent US009622373B1 (12) (10) Patent No.: Sarti (45) Date of Patent: Apr. 11, 2017 (54) HIGH VOLTAGE DIRECT CURRENT s ck 358. SE et al. HOSK 7/14-4 W ait........................ POWER SYSTEM
More informationPRODUCTS AND SERVICES. At a glance
PRODUCTS AND SERVICES At a glance ELTEK DEUTSCHLAND GMBH Eltek Deutschland is a full-range provider of protected power supplies for the telecom, renewable and OEM power industries and industrial applications.
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1 UPS topologies Large Free standing Static Switches
More informationTechnical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment
Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment TR No. 176002 1.1.EDITION April 1st, 2015 Nippon Telegraph and Telephone Corporation Introduction This document describes
More information3. Alignment and Adjustments
3. 3-1 Test Mode How to Approach Test Mode You can approach the Test Mode by pressing the on/off switch of indoor unit for 5 seconds. on/off switch Test Mode Operation Option After installing the air conditioner,
More informationSolarEdge SolarEdge, Enphase Value Comparison July 8, 2011
SolarEdge SolarEdge, Enphase Value Comparison July 8, 2011 1 Introduction Both the SolarEdgepower optimizer system and the Enphase microinverter system offer significant improvements over a traditional
More informationSmartOnline 208/120V or 240/120V 16kVA 11.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial
SmartOnline 208/120V or 240/120V 16kVA 11.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU16000RT4U Description Tripp Lite 16kVA SmartOnline
More informationSolis Single Phase Inverter
PV Grid Tie Inverter Solis Single Phase Inverter Installation and Operation Manual Ningbo Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712,
More information48V 2KW 1U AC-DC Power Supply PS Electrical Specification for: Telkoor Model:
Electrical Specification for: Telkoor Model: 48V 2KW 1U AC-DC Power Supply PS-2048 SCALE RELEASE DATE 26/06/11 SHEET 1 OF 11 REVISION HISTORY Rev Level Rev Date Change Made Reason for Change Effective
More informationSERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF CABLES AND OTHER ELEMENTS OF OUTSIDE PLANT
International Telecommunication Union ITU-T L.1201 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (03/2014) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF CABLES AND OTHER ELEMENTS OF OUTSIDE
More informationJanuary Bob Wright. 1 P age Bob Wright
The upgrade is completed using the 401 control board and three Step1 driver boards supplied as a kit by Conqueror Design and Engineering Ltd. The kit includes all cable terminators for connections to the
More informationS5-115U. Application
S5-115U S5-115U Design Central configuration Distributed configuration Note General technical specifications S5-115U Principle of operation Program memory Processor Programming S5-115U Cyclic program execution
More information