Evolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development
|
|
- Joan Nichols
- 6 years ago
- Views:
Transcription
1
2 Evolution of Facebook s data center design Veerendra Mulay, PhD Strategic Engineering and Development
3 Agenda 1 Introduction 2 Electrical design 3 Mechanical design 4 Design evolution 5 RDDC
4 Introduction
5 Facebook Greenfield Datacenter Goal Design and build the most efficient datacenter eco-system possible Control Application Server configuration Datacenter design Sites Prineville, OR Forest City, NC Luleå, Sweden Altoona, IA
6 Prineville, OR
7 Forest City, NC
8 Luleå, Sweden
9 Altoona, IA
10 Electrical design
11 Electrical Overview Eliminate 480V to 208V transformation Used 480/277VAC distribution to IT equipment Remove centralized UPS Implemented 48VDC UPS System Result a highly efficient electrical system and small failure domain
12 Typical Power Prineville Power Utility Transformer 480/277 VAC 2% loss Standby Generator Utility Transformer 480/277 VAC 2% loss Standby Generator AC/DC DC/AC UPS 480VAC 6% - 12% loss ASTS/PDU 208/120VAC 3% loss % Availability 480/277VAC % Availability SERVER PS 10% loss (assuming 90% plus PS) FB SERVER PS 5.5% loss Total loss up to server: Total loss up to server: 21% to 27% 7.5% 48VDC DC UPS (Stand-by)
13 DC UPS Backup Scheme 48VDC Battery Cabinet 277VAC 48VDC Battery Charger Server PS Normal Power Backup Power 4x12V Batt 4x12V Batt 4x12V Batt 48VDC Standby Back-up Converter 48VDC- 12VDC AC to DC 277VAC- 12VDC 12VDC 4x12V Batt 4x12V Batt MOBO
14 Battery Cabinet Custom DC UPS 56kW or 85kW 480VAC, 3-phase input 45 second back-up 20 sealed VRLA batteries Battery Validation System Six 48VDC Output Two 50A 48VDC aux outputs
15 Reactor Power Panel Custom Fabricated RPP Delivers 165kW, 480/277V, 3-phase to CAB level Contains Cam-Lock connector for maintenance wrap around Line Reactor Reduces short circuit current < 10kA Corrects leading power factor towards unity (3% improvement) Reduces THD for improved electrical system performance (ithd 2% improvement) Power consumption = 360 Watt
16 Mechanical design
17 Overview Removed Centralized chiller plant HVAC ductwork System Basis of Design ASHRAE Weather Data: N=50 years TC : Recommended Envelopes Built-up penthouse air handling system Server waste heat is used for office space heating
18 Typical Datacenter Cooling Return Ductwork CT CHILLER AHU SUPPLY DUCT DATA CENTER Facebook Data Center Cooling Return Air Ductless Return Air Relief Air Ductless Relief Air 100% Outside Air Intake DUCTLESS SUPPLY DATA CENTER Return Air Plenum Filter Wall DX System Misting System Fan Wall
19 PRN1 Datacenter Cooling Filter Wall Misting System Fan Wall 100% Outside Air Intake Mixed Air Corridor Supply Air Corridor Relief Air Corridor Relief Air Fan Hot Aisle Return Air Common Return Air Plenum Hot Aisle Relief Air Hot Aisle Common Cold Aisle Hot Aisle Data Center Server Cabinets Server Cabinets
20 Vertical drainable louvers Outside air intake corridor
21 Air mixing section Evaporative cooling / humidification corridor
22 DX Cooling Coil Forest City Only 50 year extreme weather conditions
23
24
25 Fan wall array inlet corridor Fan array outlet / supply air corridor
26 Cold aisle pressurization ductless supply
27
28
29 Design evolution
30 Basis of Design Comparison 80ºF inlet 85ºF inlet 85ºF inlet 85ºF inlet 65% humidity 80% humidity 90% humidity 80% humidity 20ºF ΔT 22ºF ΔT 22ºF ΔT 22ºF ΔT PRN1A1B PRN1C1D FRC1A1B LLA1A1B
31 Wetted Media
32 Typical Generator Topology
33 LLA Reduced Generator Topology
34 Rapid Deployment Data Center
35 PRE MANUFACTURED UNIT ASSEMBLIES RDDC FLAT PACKED PANELIZED ASSEMBLIES
36 RDDC Pre-fab Assemblies
37 RDDC building plans MECH UNITS MECH UNITS A ELEC SKIDS B MECH UNITS MECH UNITS
38 RDDC Unitized IT Modules
39 RDDC Section Unit IT Unit IT a b c
40 RDDC Power Modules
41 Luleå, Sweden
42 RDDC Flat Pack Solution
43 Flat pack solution RACK RACK 14-0
44 Flat pack solution
45 Flat pack solution RACK RACK
46 Leaner simplification
47
48 (c) 2007 Facebook, Inc. or its licensors. "Facebook" is a registered trademark of Facebook, Inc.. All rights reserved. 1.0
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationData Center Energy and Cost Saving Evaluation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationAir-Side Economizer Cycles Applied to the Rejection of Data Center Heat
Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat B. Keith Dunnavant, P.E. Manager, Data Center Cooling Solutions Munters Corporation Founded in 1955 Manufacturing & Sales Locations
More informationInternet Scale Infrastructure Innovation
Compute Summit Internet Scale Infrastructure Innovation Open Compute Summit 2011 James Hamilton VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog:
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationCase study on Green Data Center. Reliance Jio Infocomm Limited
Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationInternet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011
Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011 James Hamilton, 2011/10/24 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationDesign and Installation Challenges: Aisle Containment Systems
Design and Installation Challenges: Aisle Containment Systems 1 We all know the Benefits of Containment 1. Reduces Total Cost of Data Center Ownership 2. Eliminates hot spots 3. Supports higher heat and
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationINSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE
INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE Dr Jon Summers Scientific Leader in Data Centers, RISE Adjunct Professor of Fluid Mechanics, Lulea University of
More informationYour Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant
Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationLiebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability
Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationZTE ZXCR Series DX In-Row Air Conditioning Product Description
ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationEffectiveness and Implementation of Modular Containment in Existing Data Centers
WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationA separate CRAC Unit plant zone was created between the external façade and the technical space.
Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More informationAndover Continuum. Power Supplies with or without UPS
Andover Continuum Power Supplies with or without UPS The Andover Continuum TM PS 120/240 AC 50-U, PS 120/240 AC 65-U and PS120/240 AC 85-U power supply modules are designed to provide 24 VDC power for
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationEcoflair Air Economizers
Ecoflair Air Economizers Cooling to maximize value for the cloud schneider-electric.com/ecoflair Life is On Schneider Electric 1 Ecoflair takes data center efficiency to new heights 2 Imagine cooling your
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director
ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationREPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:
REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationTen Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42
Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationHVDC Innovation, XECHNO Power & Fresh HVDC
1 HVDC Innovation, XECHNO Power & Fresh HVDC Energy Saving Technology for the Data Center Green Consulting Business Unit Solution Business Division NTT DATA INTELLILINK Corp. Problems facing data centers:
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationWhat s New for Data Centers in Title Jeff Stein, PE Taylor Engineering
What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationPerformance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report
Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationDaikin McQuay. Incremental Comfort System. PKEI, PKES, PKHS 007, 009, 012, 014 Design 2. Replacement Parts List No Revision G 12/2013
Replacement Parts List No. 700017400 Revision G 12/2013 Daikin McQuay Incremental Comfort System PKEI, PKES, PKHS 007, 009, 012, 014 Design 2 To find your Daikin Applied parts distributor, call 1-800-377-2787
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationData centers control: challenges and opportunities
1 Data centers control: challenges and opportunities Damiano Varagnolo Luleå University of Technology Aug. 24th, 2015 First part: what is a datacenter and what is its importance in our society Data centers
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationChapter 5 Review. Power Supplies
Chapter 5 Review Power Supplies Name Period Date Score Write your answers in the spaces provided at the end of the question. For fill-in-the-blank questions, provide the word or words needed to complete
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationFCU (FREE COOLING UNIT)
FCU (FREE COOLING UNIT) FCU reduces the AC running hours on the telecom site Controller Features: Can control upto two AC and one free cooling unit Temperature control Humidity sensor Structural Features:
More informationAir Containment Design Choices and Considerations
Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationPros and Cons of Various DC Distribution Architectures
Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification
More informationHOURLY ANALYSIS PROGRAM 5.10
HOURLY ANALYSIS PROGRAM Carrier Software Systems Carrier Corporation Syracuse, New York Rev. August 21, 2017 Copyright 2017 Carrier Corporation Contents LEED v4 ASHRAE Standards Updates Modeling Capabilities
More informationNREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions
NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center
More informationThe noise of cloud computing
The noise of cloud computing Radek Kochanowski (1) (1) Acoustic Engineer, Aurecon, Sydney, Australia ABSTRACT With Cloud computing and Cloud data storage being sold as the way of the future for storing
More informationInRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.
InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat
More informationSmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity
SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.
More informationHigh Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach
High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationCase Study: Energy Systems Integration Facility (ESIF)
Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case
More informationE e n rgy g y St S ud u y y Pr P og o r g ams December 2011
Energy Study Programs December 2011 1 Agenda Energy Study Programs Overview Recommissioning Engineering Studies Data Center Studies Custom Rebates What makes a good energy study? 2 Energy Study Program
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationbrightsolid Data Hall 1 Keysource Technical Specifications
brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)
(ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET TCY-BH-T-U Wall controller with sensor TDC-BH-T-U Duct controller with sensor SOA-Tn10 Outdoor temperature sensor (Optional) OVERVIEW For wall applications
More informationBest Practices Guide for Energy-Efficient Data Center Design
FEDERAL ENERGY MANAGEMENT PROGRAM Best Practices Guide for Energy-Efficient Data Center Design Revised March 2011 Prepared by the National Renewable Energy Laboratory (NREL), a national laboratory of the
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More information1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA
The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationIT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw
IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE
More informationRunning Your Data Center Under Ideal Temperature Conditions
TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient
More informationA Design Guidelines Sourcebook January High Performance Data Centers
A Design Guidelines Sourcebook January 2011 High Performance Data Centers Table of Contents Introduction...1 1. Information Technology (IT) Systems...3 2. Air Management...10 3. Air-Side Economizer...19
More informationthe Centric 300 An advanced modular UPS up to 1800kVA/kW
the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has
More informationPowering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM
Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and
More informationCisco CRS 16-Slot Chassis Power Systems
This chapter includes the following sections: Power specifications are provided in Technical Specifications Power Systems Overview, on page 1 Power Component Information Common to the Two Types of Power
More information