Evolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development

Size: px
Start display at page:

Download "Evolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development"

Transcription

1

2 Evolution of Facebook s data center design Veerendra Mulay, PhD Strategic Engineering and Development

3 Agenda 1 Introduction 2 Electrical design 3 Mechanical design 4 Design evolution 5 RDDC

4 Introduction

5 Facebook Greenfield Datacenter Goal Design and build the most efficient datacenter eco-system possible Control Application Server configuration Datacenter design Sites Prineville, OR Forest City, NC Luleå, Sweden Altoona, IA

6 Prineville, OR

7 Forest City, NC

8 Luleå, Sweden

9 Altoona, IA

10 Electrical design

11 Electrical Overview Eliminate 480V to 208V transformation Used 480/277VAC distribution to IT equipment Remove centralized UPS Implemented 48VDC UPS System Result a highly efficient electrical system and small failure domain

12 Typical Power Prineville Power Utility Transformer 480/277 VAC 2% loss Standby Generator Utility Transformer 480/277 VAC 2% loss Standby Generator AC/DC DC/AC UPS 480VAC 6% - 12% loss ASTS/PDU 208/120VAC 3% loss % Availability 480/277VAC % Availability SERVER PS 10% loss (assuming 90% plus PS) FB SERVER PS 5.5% loss Total loss up to server: Total loss up to server: 21% to 27% 7.5% 48VDC DC UPS (Stand-by)

13 DC UPS Backup Scheme 48VDC Battery Cabinet 277VAC 48VDC Battery Charger Server PS Normal Power Backup Power 4x12V Batt 4x12V Batt 4x12V Batt 48VDC Standby Back-up Converter 48VDC- 12VDC AC to DC 277VAC- 12VDC 12VDC 4x12V Batt 4x12V Batt MOBO

14 Battery Cabinet Custom DC UPS 56kW or 85kW 480VAC, 3-phase input 45 second back-up 20 sealed VRLA batteries Battery Validation System Six 48VDC Output Two 50A 48VDC aux outputs

15 Reactor Power Panel Custom Fabricated RPP Delivers 165kW, 480/277V, 3-phase to CAB level Contains Cam-Lock connector for maintenance wrap around Line Reactor Reduces short circuit current < 10kA Corrects leading power factor towards unity (3% improvement) Reduces THD for improved electrical system performance (ithd 2% improvement) Power consumption = 360 Watt

16 Mechanical design

17 Overview Removed Centralized chiller plant HVAC ductwork System Basis of Design ASHRAE Weather Data: N=50 years TC : Recommended Envelopes Built-up penthouse air handling system Server waste heat is used for office space heating

18 Typical Datacenter Cooling Return Ductwork CT CHILLER AHU SUPPLY DUCT DATA CENTER Facebook Data Center Cooling Return Air Ductless Return Air Relief Air Ductless Relief Air 100% Outside Air Intake DUCTLESS SUPPLY DATA CENTER Return Air Plenum Filter Wall DX System Misting System Fan Wall

19 PRN1 Datacenter Cooling Filter Wall Misting System Fan Wall 100% Outside Air Intake Mixed Air Corridor Supply Air Corridor Relief Air Corridor Relief Air Fan Hot Aisle Return Air Common Return Air Plenum Hot Aisle Relief Air Hot Aisle Common Cold Aisle Hot Aisle Data Center Server Cabinets Server Cabinets

20 Vertical drainable louvers Outside air intake corridor

21 Air mixing section Evaporative cooling / humidification corridor

22 DX Cooling Coil Forest City Only 50 year extreme weather conditions

23

24

25 Fan wall array inlet corridor Fan array outlet / supply air corridor

26 Cold aisle pressurization ductless supply

27

28

29 Design evolution

30 Basis of Design Comparison 80ºF inlet 85ºF inlet 85ºF inlet 85ºF inlet 65% humidity 80% humidity 90% humidity 80% humidity 20ºF ΔT 22ºF ΔT 22ºF ΔT 22ºF ΔT PRN1A1B PRN1C1D FRC1A1B LLA1A1B

31 Wetted Media

32 Typical Generator Topology

33 LLA Reduced Generator Topology

34 Rapid Deployment Data Center

35 PRE MANUFACTURED UNIT ASSEMBLIES RDDC FLAT PACKED PANELIZED ASSEMBLIES

36 RDDC Pre-fab Assemblies

37 RDDC building plans MECH UNITS MECH UNITS A ELEC SKIDS B MECH UNITS MECH UNITS

38 RDDC Unitized IT Modules

39 RDDC Section Unit IT Unit IT a b c

40 RDDC Power Modules

41 Luleå, Sweden

42 RDDC Flat Pack Solution

43 Flat pack solution RACK RACK 14-0

44 Flat pack solution

45 Flat pack solution RACK RACK

46 Leaner simplification

47

48 (c) 2007 Facebook, Inc. or its licensors. "Facebook" is a registered trademark of Facebook, Inc.. All rights reserved. 1.0

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat B. Keith Dunnavant, P.E. Manager, Data Center Cooling Solutions Munters Corporation Founded in 1955 Manufacturing & Sales Locations

More information

Internet Scale Infrastructure Innovation

Internet Scale Infrastructure Innovation Compute Summit Internet Scale Infrastructure Innovation Open Compute Summit 2011 James Hamilton VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog:

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011

Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011 Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011 James Hamilton, 2011/10/24 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Design and Installation Challenges: Aisle Containment Systems

Design and Installation Challenges: Aisle Containment Systems Design and Installation Challenges: Aisle Containment Systems 1 We all know the Benefits of Containment 1. Reduces Total Cost of Data Center Ownership 2. Eliminates hot spots 3. Supports higher heat and

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE

INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE Dr Jon Summers Scientific Leader in Data Centers, RISE Adjunct Professor of Fluid Mechanics, Lulea University of

More information

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,

More information

APC APPLICATION NOTE #146

APC APPLICATION NOTE #146 #146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating

More information

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

Rack cooling solutions for high density racks management, from 10 to 75 kw

Rack cooling solutions for high density racks management, from 10 to 75 kw Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

ZTE ZXCR Series DX In-Row Air Conditioning Product Description

ZTE ZXCR Series DX In-Row Air Conditioning Product Description ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

Effectiveness and Implementation of Modular Containment in Existing Data Centers

Effectiveness and Implementation of Modular Containment in Existing Data Centers WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

A separate CRAC Unit plant zone was created between the external façade and the technical space.

A separate CRAC Unit plant zone was created between the external façade and the technical space. Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure

More information

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing

More information

Andover Continuum. Power Supplies with or without UPS

Andover Continuum. Power Supplies with or without UPS Andover Continuum Power Supplies with or without UPS The Andover Continuum TM PS 120/240 AC 50-U, PS 120/240 AC 65-U and PS120/240 AC 85-U power supply modules are designed to provide 24 VDC power for

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

Ecoflair Air Economizers

Ecoflair Air Economizers Ecoflair Air Economizers Cooling to maximize value for the cloud schneider-electric.com/ecoflair Life is On Schneider Electric 1 Ecoflair takes data center efficiency to new heights 2 Imagine cooling your

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

Highly Efficient Power Protection for High Density Computing Applications

Highly Efficient Power Protection for High Density Computing Applications Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

Planning a Green Datacenter

Planning a Green Datacenter Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data

More information

Close Coupled Cooling for Datacentres

Close Coupled Cooling for Datacentres Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close

More information

HVDC Innovation, XECHNO Power & Fresh HVDC

HVDC Innovation, XECHNO Power & Fresh HVDC 1 HVDC Innovation, XECHNO Power & Fresh HVDC Energy Saving Technology for the Data Center Green Consulting Business Unit Solution Business Division NTT DATA INTELLILINK Corp. Problems facing data centers:

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering

What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,

More information

LCP Hybrid Efficient performance with heat pipe technology

LCP Hybrid Efficient performance with heat pipe technology LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies

More information

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and

More information

Daikin McQuay. Incremental Comfort System. PKEI, PKES, PKHS 007, 009, 012, 014 Design 2. Replacement Parts List No Revision G 12/2013

Daikin McQuay. Incremental Comfort System. PKEI, PKES, PKHS 007, 009, 012, 014 Design 2. Replacement Parts List No Revision G 12/2013 Replacement Parts List No. 700017400 Revision G 12/2013 Daikin McQuay Incremental Comfort System PKEI, PKES, PKHS 007, 009, 012, 014 Design 2 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

Liquid Cooling Package LCP Cooling Systems

Liquid Cooling Package LCP Cooling Systems Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

Data centers control: challenges and opportunities

Data centers control: challenges and opportunities 1 Data centers control: challenges and opportunities Damiano Varagnolo Luleå University of Technology Aug. 24th, 2015 First part: what is a datacenter and what is its importance in our society Data centers

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Chapter 5 Review. Power Supplies

Chapter 5 Review. Power Supplies Chapter 5 Review Power Supplies Name Period Date Score Write your answers in the spaces provided at the end of the question. For fill-in-the-blank questions, provide the word or words needed to complete

More information

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total

More information

FCU (FREE COOLING UNIT)

FCU (FREE COOLING UNIT) FCU (FREE COOLING UNIT) FCU reduces the AC running hours on the telecom site Controller Features: Can control upto two AC and one free cooling unit Temperature control Humidity sensor Structural Features:

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

Pros and Cons of Various DC Distribution Architectures

Pros and Cons of Various DC Distribution Architectures Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification

More information

HOURLY ANALYSIS PROGRAM 5.10

HOURLY ANALYSIS PROGRAM 5.10 HOURLY ANALYSIS PROGRAM Carrier Software Systems Carrier Corporation Syracuse, New York Rev. August 21, 2017 Copyright 2017 Carrier Corporation Contents LEED v4 ASHRAE Standards Updates Modeling Capabilities

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information

The noise of cloud computing

The noise of cloud computing The noise of cloud computing Radek Kochanowski (1) (1) Acoustic Engineer, Aurecon, Sydney, Australia ABSTRACT With Cloud computing and Cloud data storage being sold as the way of the future for storing

More information

InRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.

InRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling. InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat

More information

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.

More information

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

Case Study: Energy Systems Integration Facility (ESIF)

Case Study: Energy Systems Integration Facility (ESIF) Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case

More information

E e n rgy g y St S ud u y y Pr P og o r g ams December 2011

E e n rgy g y St S ud u y y Pr P og o r g ams December 2011 Energy Study Programs December 2011 1 Agenda Energy Study Programs Overview Recommissioning Engineering Studies Data Center Studies Custom Rebates What makes a good energy study? 2 Energy Study Program

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

brightsolid Data Hall 1 Keysource Technical Specifications

brightsolid Data Hall 1 Keysource Technical Specifications brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U) (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET TCY-BH-T-U Wall controller with sensor TDC-BH-T-U Duct controller with sensor SOA-Tn10 Outdoor temperature sensor (Optional) OVERVIEW For wall applications

More information

Best Practices Guide for Energy-Efficient Data Center Design

Best Practices Guide for Energy-Efficient Data Center Design FEDERAL ENERGY MANAGEMENT PROGRAM Best Practices Guide for Energy-Efficient Data Center Design Revised March 2011 Prepared by the National Renewable Energy Laboratory (NREL), a national laboratory of the

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

A Design Guidelines Sourcebook January High Performance Data Centers

A Design Guidelines Sourcebook January High Performance Data Centers A Design Guidelines Sourcebook January 2011 High Performance Data Centers Table of Contents Introduction...1 1. Information Technology (IT) Systems...3 2. Air Management...10 3. Air-Side Economizer...19

More information

the Centric 300 An advanced modular UPS up to 1800kVA/kW

the Centric 300 An advanced modular UPS up to 1800kVA/kW the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has

More information

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and

More information

Cisco CRS 16-Slot Chassis Power Systems

Cisco CRS 16-Slot Chassis Power Systems This chapter includes the following sections: Power specifications are provided in Technical Specifications Power Systems Overview, on page 1 Power Component Information Common to the Two Types of Power

More information