1 MAINTENANCE STANDARDS SPECIFICATION TITLE Power System Study Procedure VALE # Ontario Operations MPROC VALE # October 14, 2016 PAGE 1/14 Rev 3 Training Code (not applicable) Document Owner: Name: Phil Langlois Department: Lead Engineer Table of Contents 1. PURPOSE APPLICATION EXCEPTIONS REFERENCE DOCUMENTATION COMMITMENTS DEFINITIONS TOOLS ENGINEERING REQUIREMENTS DELIVERABLES APPENDICES Page 1 of 14
2 1. PURPOSE This procedure describes the methodology for dealing with power system studies; it is understood that the study should include a short circuit study, a device evaluation, a protective device coordination study (phase & ground), and an arc flash study. Standardizing the studies within the Vale Ontario division will ensure that higher quality studies are produced consistently, thereby making them easier to use and update as required. Furthermore, this standardization will minimize unnecessary duplication within the document. If a large site is fed by more than one main incoming substation/transformer, the site may elect to have more than one study. This will allow for a quicker completion turn-around time, facilitate ongoing revisions/addendums, and will assist in the recommended 5-year updates. 2. APPLICATION A new study will not be created if a completed study is available. The existing study will therefore be updated; or an addendum to the study will be issued. The following examples are guides to clarify what types of changes will necessitate a study update: adding/removing MPCs or MCCs or new 600V distribution racks, changes to settings or fuse sizes which cause posted labels to be inaccurate to the point that posted PPE will no longer adequately protect workers, adding a large load to a main rack that is fed with large protective devices which might interfere with the existing coordination. The following examples would not necessitate study updates but rather the creation of an addendum and would be incorporated during the 5-year updates: adding/removing loads on any of the 600V distribution racks. 3. EXCEPTIONS This procedure, applies at all Vale Ontario operation locations No exceptions to these procedures will be permitted without specific permission by the Vale Specialty Engineering Department. Page 2 of 14
3 4. REFERENCE DOCUMENTATION The following references were used in the development of this document. Engineering Standard Design Guide SPEC Guidelines for Power System Studies 3 Phase A.C. Systems 5. COMMITMENTS The latest issues, amendments, and supplements of the following standards shall apply to this procedure, unless stated otherwise: CSA M Use of Electricity in Mines CSA Z Workplace electrical safety IEEE Guide for Performing Arc-Flash Hazard Calculations IEEE Standard Recommended Practice for Power Distribution for Industrial Plants (Red Book) IEEE Standard Recommended Practice for Grounding of Industrial and Commercial Power Systems (Green Book) IEEE Standard Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (Buff Book) IEEE Standard Recommended Practice for Calculating Short Circuit Currents in Industrial and Commercial Power Systems (Violet Book) IEEE C Application Guide for AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis IEEE C Guide for Calculation of Fault Currents for Application of AC High Voltage Circuit Breakers Rated on a Total Current Basis IEEE C Standard for Low Voltage AC Power Circuit Breaker NFPA 70E Standard for Safety in the Workplace OESC Ontario Safety Code Page 3 of 14
4 6. DEFINITIONS For the purpose of this procedure, the terms and definitions as identified in IEEE Standard 1584 and CSA Standard Z462 shall apply. For any terms not defined in this standard, IEEE Standard The Authoritative Dictionary of IEEE Standard Terms; shall be referred. Further definitions include the following: ARM Arc Reduction Maintenance TCC Time-Current Curve Page 4 of 14
5 7. TOOLS Software used for modeling and analyzing must include the latest revision of EasyPower. No software substitution is permitted. Longhand calculations performed by a professional engineer licensed by the province are acceptable for small systems; or for cases for which the software does not have provisions or yields anomalous results. 8. ENGINEERING REQUIREMENTS To assist in the preparation and publishing of a study, a completed study example will be provided to ensure symmetry to all other studies for the division. Plant and mine personnel must be able to navigate each study to obtain required information without having to re-learn the process at each site or for different studies. The layout and design of the study report will include: Section Content Description Title Page The title page will show: customer and consultant names; consultant s project identifier; brief substation description and identifier; month and year of issue; and tabled summary of the last five revisions. Table of Contents The table of contents will identify subsection titles and page numbers. Table of Appendices The order must be consistent with the suggested format to allow plant personnel to quickly locate tables, TCCs, diagrams and charts. A disclaimer page may be included by the consultant. Section 1.0 Scope of Work and Objectives Subsection #0 is reserved for the scope of work and objectives. Subsection #1 is reserved for the computer software details. Subsection #2 is reserved for the revision summary. The original release will be called Revision 0 ; with all significant subsequent revisions incrementing by one. Page 5 of 14
6 Section Content Description If a minor revision or addendum is issued, the number will remain the same; however, a letter will be added to the extension (i.e. Rev 1A, 1B, etc.). Detailed descriptions will be given regarding the nature of subsequent revisions; such as additions, deletions, and mitigation. Section 2.0 Executive Summary An executive summary that only summarize where the results of each study can be found within the report in order to avoid duplication. Section 3.0 Methodology Subsection#0 indicates how the information was collected and by whom; and gives the utility min/max fault contributions, and the dated source of this information. Fault contribution levels from previous studies will also be kept. Subsection #1 contains the table of all possible distribution scenarios. Scenario 1 is always the normal case. Arc flash labels will be printed to match the worst case of all scenarios except those assuming main substation tie-breaker closures, transformer paralleling or emergency/backup operation. Only the main substation breakers will have labels using the paralleling scenario. The device evaluation will use the normal case and the paralleling case. Buses which can be fed from a generator or have ARM switches are given a dual value label since arc flash values differ greatly from the other cases. Vale understands and assumes all liability for risks that arise when two incident values are displayed on a single piece of equipment. Section 4.0 Short Circuit Study and Device Evaluation Definitions, information, and explanations regarding the short circuit study and device evaluations are given. Appendix C is to be referenced. Page 6 of 14
7 Section Content Description Subsection#3 tables present all marginal and overdutied distribution and protection equipment along with which scenario they belong to. Recommendations will be made to resolve strictly the over-duty issues. Section 5.0 Section 6.0 Protective Device Coordination Study Arc Flash and Shock Risk Assessment This section is not only for problem areas but for the whole distribution and for both phase and ground faults. After a quick description regarding the intended purpose and the guidelines used, Appendix B is to be referenced. Subsection#2 must not only look at selectivity but also at electrical code compliance and must ensure that incident energy is not increased with the proposed settings. These results and general recommendations will be given for each TCC thereby keeping details in Appendices E and I. A tabular format presentation of recommendations can be used. Definitions, information, and explanations regarding the arc flash study are given. Incident energy calculations shall be made based on calculated arcing currents. Appendix D is to be referenced. Recommendations are expected for all buses with incident energies greater than 8 cal/cm 2. Do not indicate the exact calculated incident energy but rather use categories such as >8, >8 but<12, >12 but <25, >25 but <40, or >40. Where the most recent arc flash standard, definitions, and generic report body has already been presented in an earlier report version of the same area, subsequent addendum do not need to present the same body. This generic body needs only to be updated when: there is an update to the Standard or when issuing a full update. Page 7 of 14
8 Section Content Description Section 7.0 Signatures and References When making any reference to a standard, the date will be omitted and kept only in subsection 7.2 to avoid further updating needs. Appendix A Impedance Diagrams This appendix will include: a list of all impedance diagrams; and all legible impedance diagrams are to be presented in ledger (11 x 17) format. While modeling >600 V equipment, a bus must be selected for each piece of equipment, so that switch room and field labels can be applied on all equipment. While modeling the 600 V equipment, all main switch room equipment will be labeled; but only the field equipment rated >1.2cal/cm 2 will be labeled to minimize the number of labels. To accomplish this, a fictitious fused disconnect labeled as FD- will be added with the largest fuse on that rack - its cable size and a fictitious length of cable to mimic the longest possible cable length, or worst case to show that all downstream equipment is rated <1.2cal/cm 2 and does not otherwise need labeling. When modeling the motor loads, group all <50 HP motors together while grouping the >50 HP together. Show the largest loads/motors by themselves if rated over 1.2cal/cm 2. Motors which are >50HP and utilize a VFD, are to be modeled independently and a label is to be supplied for the VFD. Modeling of loads <600 V will be required if the 3-phase supply transformer is larger than 125kVA (even though some industry best practice is suggesting 75kVA, IEEE 1584 and CSA- Z462 mention that transformers smaller than 125kVA need not be included). All distribution data assumptions will be shown in a box format so that they cannot be missed. Single phase loads do not need to be modelled. For assumptions that are made which cannot be confirmed later (such as fallen nameplates resulting in assumed impedance ), these will be marked directly on the impedance diagrams. Page 8 of 14
9 Section Content Description Appendix B TCCs List all TCCs numbers followed by the TCCs. Colour TCC curves to be issued will have a single line beside them on the left side. To maintain a historical record of all installations, each TCC will have up to three possible versions: original, present/existing/current, and recommended settings. Vale may decide to eliminate original TCCs during some updates. For all 600 V ground fault feeder breaker TCCs on solidly grounded systems, a 60 A Mersen AJT fuse curve will be shown to remind the plant of this minimum coordination requirement. Numbering of the ground curves will start at 50 or 100 to avoid having to re-number existing phase TCCs when new ones are added or deleted (depends on the size of the study). These will all be printed on 8.5x11 paper in a matter such as to minimize the number of sheets required (tweaking with scale, font size ). Appendix C Short Circuit and Equipment Duty Tables List of HV and LV momentary tables and equipment duty tables followed by the tables themselves for the normal scenario and the paralleling scenario. The equipment duty results table will be color coded in black for acceptable, orange for marginal and, red for overdutied Marginal is defined as being between 80% and 100% dutied. These will all be printed on 8.5x11 paper in a matter such as to minimize the number of sheets required (tweaking with scale, font size ). Page 9 of 14
10 Section Content Description Appendix D Arc Flash Summary Tables A list of all tables will be made available for all scenarios. A separate worst-case scenario table will also be issued. The worst-case table will be issued containing: arc flash protection boundary in feet-inches; working distance in inches; incident energy level in cal/cm 2 ; required Vale PPE level the number of labels issued, and scenario which resulted in the worst-case for each bus (to name a few). Not all labels will necessarily be printed from the same scenario. Where it makes sense to do so, provide a second working distance which would drop incident energy levels when using a racking device extension, an ARM switch or working with a hotstick. Some labels may contain two sets of numbers for arc flash boundaries and incident energy levels. The worst-case summary table is to be provided in Ledger (11x17) format. Appendix E Assumptions and Recommendations All document assumptions must be listed in this appendix. The action item tables are to be divided into the following three groups: E-1 for equipment duty; E-2 for protective device coordination; and E-3 for arc flash study. The E-3 table will have a column which shows recommended mitigation or permanent/temporary measure(s) which have to been taken (brief). It will be the site s responsibility to obtain missing information, verify assumptions, correct the issues or implement solutions before the next revision of the document. Page 10 of 14
11 Section Content Description During the initial or early study revisions which contain many recommendations, the tables may refer to Appendix I for setting changes, to avoid duplicating a large number of recommendations. Appendix F Vale Single Line Drawings A list of all single line drawings and their revision numbers grouped into practical subsections to make the 5 year updates easier. The plants may store their drawings in this section but are not required to be included as part of the study. Appendix G Photographs Photos can be provided but must be supported by a list of photos for ease of identification. Photos should be trimmed to focus on electrical equipment. All worker faces may be blurred to maintain privacy. All pictures should be of a reduced quality format in order to maintain the document at a reasonable size. Appendix H Appendix I Reference Documents Protective Device Settings Summary List of all documents followed by the relevant documents. This section should be kept as small as possible. This section will consist of a PDF copy of the spreadsheet showing all relevant fuses and relay settings, and also all low voltage breaker settings. Original settings and changeover dates will be kept. Outstanding items will be highlighted in yellow. The Protective Device Settings Summary table is to be provided in Ledger (11x17) format. Page 11 of 14
12 9. DELIVERABLES The following deliverables will be supplied by Vale and external consultants as required; to assist in the preparation of the study. Vale-Supplied Deliverables All single line drawings from the substation to the most downstream switch room connected loads (Specialty Engineering will provide with assistance from the plant electrical contact); All fuse sizes and types (the plant or mine electrical contact will confirm the accuracy of the drawings and obtain the missing information using planned shutdowns); All asfound protective device settings (Specialty Engineering to request this information from the Vale Power Department s P&C Group); Minimum and maximum available fault contributions (Specialty Engineering to request this information from the Vale Power Department s Engineering Group); All missing information not requiring the consultant s expertise (such as cable lengths) shall be obtained by the plant or mine electrical contact after receiving such requests; in order to maximize efficiencies and lower costs; The plant or mine may choose to provide a photo record of the site installation (Optional); If a study already exists, it will be made available for updating; and An MS Excel template of protective devices and settings will be provided. Consultant-Supplied Deliverables Paper copies (color): one (1) binder for the plant or mine and one (1) binder for Specialty Engineering. For larger studies, the binder will be an 11x17 binder.; Electronic report - The electronic report containing the model (.dez format), the report (.pdf format) and the device settings spreadsheet (.xlsx format) shall be sent in three separate documents to Specialty Engineering. Vale will own the model, the report, and the Excel files; The modeling software must be EasyPower and the bus names must be plant specific and not generic (plant electrical contact must agree with convention); A spreadsheet containing all 600V-69,000V fuses, adjustable relay, and breaker settings shall be provided for the plant or mine s future use; and Issue the labels in an easy to post order/format. Page 12 of 14
13 10. APPENDICES Appendix A Revisions Notes and Approvals Page 13 of 14
14 Appendix A: Revision Notes and Approvals Note: The revision notes are a summary of the changes and may not necessarily be a complete list. Refer to the document owner for reference to previous versions. Revision Notes 3 Aligned procedure with existing practices of the last 4 years. Updated reference documents to recent versions: CSA Z462-15, NFPA 70E and OESC-2015 Standard applies to Vale Ontario operations reference to North Atlantic removed. Table of Contents added to document. 2 SPI-ENG-0003 Power Study Procedure Rev: 1-7/9/2012 reformatted to Maintenance Standard document: MPROC Power System Study Procedure. 1 SPI-ENG-0003 Initial document 7/9/2012 Page 14 of 14
SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY
SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices
More informationSiemens Dynamic Arc Flash Reduction System and its application in motor control centers
Siemens Dynamic Arc Flash Reduction System and its application in motor control centers www.sea.siemens.com www.usa.siemens.com/mcc Prepared by Mike Sachau, Product Engineer The risk of Arc Flash is a
More informationPOWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT
26 05 73 POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT Delete the following current section in its entirety (deletions are shown struck through)..01 General A. Short circuit Studies,
More informationMitigating Arc Flash Hazards
1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash
More informationDynamic Arc Flash Reduction System
www.usa.siemens.com/mcc Dynamic Arc Flash Reduction System and its application in motor control centers White Paper Author: Pablo Medina Product Manager, tiastar MCC Executive Summary The risk of Arc Flash
More informationSE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,
SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, integrity, and innovation. Our mission is to offer the safest,
More informationRELT Reduced Energy Let Thru 2018
RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru Rick Schlobohm, P.E Senior Specification Engineer, There is an increasing concern in the electrical industry about arc flash energy levels
More informationName: Dave Duczeminski Position: Reliability Manager (Mines) Department: Maintenance Engineering
of 9 Training Code: (N/A) Document Owner: Name: Dave Duczeminski Position: Reliability Manager (Mines) Department: Maintenance Engineering TABLE OF CONTENTS. PURPOSE... 2 2. APPLICATION... 2 2.. EXCEPTIONS...
More informationThis specification describes the minimum requirements for Process Hazards Reviews at the design stage (Design PHRs).
2016/0/10 1/ 1.0 PURPOSE This specification describes the minimum requirements for Process Hazards Reviews at the design stage (Design PHRs). 2.0 REFERENCE DOCUMENTATION The following documents are related
More informationLV MCC with Arc Flash Mitigation (AFM) Units
LV MCC with Arc Flash Mitigation (AFM) Units Technical Tuesday June 30, 2015 Imagination at work. Markets Oil and Gas Petro-Chemical Mining and metals Pulp and paper Mass-production manufacturing Water
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft
More informationPRC Coordination of Protection Systems for Performance During Faults
PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To
More information1. Coordination of series-rated devices is permitted where indicated on Drawings.
SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationFree Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL
SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent
More informationBest practices for making switchgear safer.
Best practices for making switchgear safer. www.sea.siemens.com www.usa.siemens.com/switchgear Prepared by: Ken Newsome - Consulting Business Developer Kevin Mullins - Consulting Business Developer Joe
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft
More informationExercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION
Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.
More informationFor normal duty, design the VFD voltage level at 480 Volt, 3 Phase, 60 Hertz. (In Canada, 600 Volt, 3 Phase, 60 Hertz.)
Introduction The Variable Frequency Drive Design Guidelines provides design criteria and specifications used in the procurement and application of variable frequency drives (VFDs). Table of Contents 1.
More informationConext CL-60 Inverter Firmware Upgrade Process
Conext CL-60 Inverter Firmware Upgrade Process http://solar.schneider-electric.com 976-0380-01-01/B August 2017 Application Note EXCLUSION FOR DOCUMENTATION UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
More informationCertification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician
Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician Certification Exams How to Use the Detailed Content Outlines These Detailed
More informationDPM Active Harmonic Filter Quick Start Instructions
DPM Active Harmonic Filter Quick Start Instructions These instructions will guide you through installing, testing your installation, and starting up your DPM. For additional information please refer to
More informationARC-FLASH INCIDENT ENERGY REDUCTION USING ZONE SELECTIVE INTERLOCKING
ARC-FLASH INCIDENT ENERGY REDUCTION USING ZONE SELECTIVE INTERLOCKING Copyright Material IEEE Paper No. PCIC-2007-XX Donna Lee Hodgson David Shipp Shell Exploration and Production Co. Eaton Electrical
More informationUnderstanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing
Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime
More informationShort-Circuit Calculation Methods
Short-Circuit Calculation Methods Oct 1, 2004 12:00 PM, By Massimo Mitolo, Ph.D., Chu & Gassman Consulting Engineers Ref.: http:// ecmweb.com/mag/electric_shortcircuit_calculation_methods/ The task may
More informationVariable Frequency Drive Design Guidelines
Variable Frequency Drive Design Guidelines The Variable Frequency Drive Design Standard provides design criteria and specifications used in the procurement and application of variable frequency drives
More informationRecording and Reporting of High Voltage and Low Voltage Switching
1 SCOPE This document details the procedures to be adopted prior to, during, and on completion of Switching operations, and details the manner in which HV and LV Switching shall be recorded in order to
More informationBest practices for making switchgear safer
Best practices for making switchgear safer White Paper Introduction What could be more important than protecting the safety of our most valuable assets, our people? Today s workers hold the keys to an
More informationDisturbance Monitoring and
PRC-002-2 R1 Notification Disturbance Monitoring and Reporting Requirements Compliance Spring Workshop May 10, 2017 Objectives This presentation will discuss: Requirement R1 Part 1.2 notifications Definition
More informationIndustrial Control Panels Tested product combinations to meet NEC Article 409 and UL 508A Standard
Industrial Control Panels Tested product combinations to meet NEC Article 409 and UL 508A Standard Short circuit current ratings and the new NEC Article 409 The 2005 Edition of the National Electrical
More informationWhen the template is complete, the whole Project Initiation Document can be printed and approved.
HOW TO USE THIS TEMPLATE: Introduction The template reflects the steps set out in the PRINCE2 Method and is designed to prompt the Project Manager and help in the creation of the Project Initiation Document
More informationDrive Technology \ Drive Automation \ System Integration \ Services. Manual. Electronic Motor DRC Functional Safety
Drive Technology \ Drive Automation \ System Integration \ Services Manual Electronic Motor DRC Functional Safety Edition 02/2012 19376812 / EN SEW-EURODRIVE Driving the world Contents Contents 1 General
More informationGE Energy Industrial Solutions. Entellisys 4.5. Low-Voltage Switchgear Application Guide
GE Energy Industrial Solutions Entellisys 4.5 Low-Voltage Switchgear Application Guide Contents Section Page 1 Introduction 1 2 General Description 3 3 System Architecture 5 4 Minimizing Potential Exposure
More informationSERIES RATED COMBINATIONS
October 15, 2012 ELECTRICAL SECTION SERIES RATED COMBINATIONS The following information has been compiled from various equipment manufacture literature and the 22nd Edition of the BCEC for educational
More informationSURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT
SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT ESTABLISHED SINCE 1985 Circuit Breaker Solid State Controls with RMS-2007AF LOGIC (All logics come with ARC FLASH as a standard) The SURE TRIP SOLID STATE
More informationInformation Document PRC-001-AB3-1.1(ii) Protection System Coordination ID # RS
Information Documents are not authoritative. Information Documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between an Information Document
More informationDRAFT Reliability Standard Audit Worksheet 1
DRAFT Reliability Standard Audit Worksheet 1 PRC-025-2 Generator Relay Loadability This section to be completed by the Compliance Enforcement Authority. Audit ID: Registered Entity: NCR Number: Compliance
More informationUL508Afor Panel Builders Getting Started
UL508Afor Panel Builders Getting Started Restricted Siemens AG 2016 siemens.tld/keyword Exclusion of Liability The typical circuit diagrams and interpretations of the standard are not binding and do not
More informationFORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE
FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE INSTRUCTIONS PLEASE READ CAREFULLY Type or print legibly in black ink. Use a separate copy for each proposal. Limit each proposal to a SINGLE section.
More information1-Line Load Calculation Software. User s Manual APPROVED. Copyright 2013 Durand & Associates. Page 1
1-Line 2014 Load Calculation Software User s Manual APPROVED Copyright 2013 Durand & Associates Page 1 1-LINE 2014 COPYRIGHT 2013 - DURAND & ASSOCIATES This software and manual are protected by Federal
More informationBulletin of the Director-General and Executive Director
V.10-51543 (E) 6. The final version of a manuscript and a Request for document services (D1) form should be submitted electronically to the Documents Management Unit through DCPMS. Any special instructions
More informationApplication Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters
Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters 976-0312-01-01 Revision A DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND
More informationCONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected Generation (DCG)]
Project Name: Kitchener-Wilmot Hydro Inc. 301 Victoria Street South Kitchener, Ontario, Canada N2G 4L2 Appendix F2: Form DG06 CONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected
More informationNEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers
NEMA Standards Publication AB 5-2011 Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite
More informationSTCP Amendment Proposal Form
STCP Amendment Proposal Form PA036 1. Title of Amendment Proposal STCP 09-2 Incorporation material currently within SPT SCS and making standard for both TOs. 2. Description of the Proposed Amendment (mandatory
More information5521 Potentiometer Analog Input Module
55 Potentiometer Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical
More informationBulletin Installation of solar photovoltaic systems Rules , , , , and
Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic
More informationDistributor Information Bulletin Distributed Generation (Codes, Publications & Standards)
GENERAL: This bulletin highlights some of the most commonly referenced technical codes, publications and standards when reviewing a connection to under the Feed-in Tariff (FIT) Program, including micro-fit.
More informationReliability Standard Audit Worksheet 1
Reliability Standard Audit Worksheet 1 CIP-012-1 Cyber Security Communications between Control Centers This section to be completed by the Compliance Enforcement Authority. Audit ID: Registered Entity:
More informationSENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions
Introduction 1 Selectivity - terms and definitions 2 SENTRON Methods of implementing selectivity using circuit breakers 3 Protective devices Selectivity for 3VA molded case circuit breakers Configuration
More information<PROJECT NAME> IMPLEMENTATION PLAN
IMPLEMENTATION PLAN Version VERSION HISTORY [Provide information on how the development and distribution of the Project Implementation Plan was controlled and tracked.
More informationSECTION ELECTRIC METERING
SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable
More informationManual: Distribution Substation Manual (DSM) Section 1: Customer Supply Arrangements
Manual: Distribution Substation Manual (DSM) Section 1: Customer Supply Arrangements Standard Number: HPC-5DA-07-0001-2012 Document Control Author Name: Viswa Easwaran Position: Standards Engineer Document
More informationLine reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4
Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA
More informationEDS SCADA NUMBERING SYSTEM
Document Number: EDS 05-9007 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 05-9007 SCADA NUMBERING SYSTEM This standard describes the system for numbering SCADA wiring within switchgear
More information30-Cycle Rated Switchboards - Selectivity Tradeoffs
30-Cycle Rated Switchboards - Selectivity Tradeoffs By Rick Schlobohm, P.E. Senior Specification Engineer, Franklin Bohac, P.E. Specification Engineer, Increased focus on selective coordination has resulted
More information2008 Code Changes for Power Distribution
2008 Schaedler Yesco Expo 2008 Code Changes for Power Distribution April 17, 2008 / Version 1.0 For internal use only / Copyright Siemens AG 2007. 2008. All rights reserved. Contact Consulting Account
More information1510 MOTOR CONTROLLERS
SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,
More information1. Introduction. 2. Design. Safety and Emergency Stop Circuit Design Standard. Safety and Emergency Stop Circuit Design Standard.
Safety and Emergency Stop Circuit Design Standard The Safety and Emergency Stop Circuit Design Standard provide design criteria and specifications for safety and emergency stop circuits used in General
More informationPower System Protection Training
Power System Protection Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Refresh your knowledge of
More informationReliability Standard Audit Worksheet 1
Reliability Standard Audit Worksheet 1 CIP-002-5.1 Cyber Security BES Cyber System Categorization This section to be completed by the Compliance Enforcement Authority. Audit ID: Registered Entity: NCR
More informationSECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)
SECTION 26 29 23 VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) PART 1 -GENERAL 1.1 SYSTEM DESCRIPTION A. Definitions: The Variable Speed AC Motor Drive (hereafter referred to as "VFD") shall be designed to
More informationGalaxy Shore Connection 500 kva. Operation 04/
Galaxy 7000 Shore Connection 500 kva Operation 04/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred
More informationCONTROL PANEL WIRING SPECIFICATIONS
CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,
More informationMemorandum. This memorandum requires Board action. EXECUTIVE SUMMARY
California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Keith Casey, Vice President, Market & Infrastructure Development Date: May 21, 2014 Re: Decision on interconnection
More informationName: Denis Deschamps Position: Maintenance Business Process Specialist Department: Base Metals
MPROC-2008 207-08-07 of 8 Training Code (If applicable): Document Owner: Name: Denis Deschamps Position: Maintenance Business Process Specialist Department: Base Metals Table of Contents.0 PURPOSE... 2
More informationWASHINGTON UNIVERSITY HIPAA Privacy Policy # 7. Appropriate Methods of Communicating Protected Health Information
WASHINGTON UNIVERSITY HIPAA Privacy Policy # 7 Appropriate Methods of Communicating Protected Health Information Statement of Policy Washington University and its member organizations (collectively, Washington
More informationEngineering Document Control
Division / Business Unit: Function: Document Type: Enterprise Services All Disciplines Procedure Engineering Document Control Applicability ARTC Network Wide SMS Publication Requirement Internal / External
More informationArchitecture and Standards Development Lifecycle
Architecture and Standards Development Lifecycle Architecture and Standards Branch Author: Architecture and Standards Branch Date Created: April 2, 2008 Last Update: July 22, 2008 Version: 1.0 ~ This Page
More informationSECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
More informationDrive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety
Drive Technology \ Drive Automation \ System Integration \ Services Manual Control Cabinet Inverter MOVITRAC B Functional Safety Edition 05/2009 16811216 / EN SEW-EURODRIVE Driving the world Content Content
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 11 FROM:
More informationISO INTERNATIONAL STANDARD. Ergonomics of human-system interaction Part 110: Dialogue principles
INTERNATIONAL STANDARD ISO 9241-110 First edition 2006-04-01 Ergonomics of human-system interaction Part 110: Dialogue principles Ergonomie de l'interaction homme-système Partie 110: Principes de dialogue
More informationVoluntary Product Accessibility Report
Voluntary Product Accessibility Report Compliance and Remediation Statement for Section 508 of the US Rehabilitation Act for OpenText Process Suite 16.3 October 2017 OPENTEXT PRODUCT VPAT ACCESSIBILITY
More informationExplosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter
Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2
More information5504 Thermocouple Analog Input Module
550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical
More informationCOMPUTER/INFORMATION FLOOD STANDARDS
COMPUTER/INFORMATION FLOOD STANDARDS CIF-1 Flood Model Documentation A. Flood model functionality and technical descriptions shall be documented formally in an archival format separate from the use of
More informationAPPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE:
APPLICATION No. To the ALBERTA ENERGY AND UTILITIES BOARD RE: New 240 kv Montana Alberta Tie Ltd. (MATL) Substation 120S and Reconfigure 240kV Transmission Line 923L AltaLink Management Ltd. 2611 3 rd
More informationOVERLOAD RELAYS POWER & ACTUATION PROVEN. series
POWER & ACTUATION OVERLOAD RELAYS series Need reliable, accurate overload and phase-loss protection for your motors? c3controls Series Bimetallic Overload Relays provide unmatched protection and can be
More informationHPE Data Center Operations Consulting Service
Data sheet HPE Data Center Operations Consulting Service HPE Packaged Consulting Services Data centers are large-scale capital investments that may not meet their capacity, availability, and operational
More informationSolar Combiner Enclosure
Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the
More informationCOMPUTER FLOOD STANDARDS
COMPUTER FLOOD STANDARDS CF-1 Flood Model Documentation A. Flood model functionality and technical descriptions shall be documented formally in an archival format separate from the use of letters, slides,
More informationStandard for more efficient design review
Standard for more efficient design review BEAst 07/11/2017 BEAst AB, November 2017 www.beast.se info@beast.se Page 1 Contents 1. Introduction... 3 1.1 Statement regarding rights... 3 1.2 Change log...
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 20kW 600kW
PRODUCT BROCHURE Conceptpower DPA 120 208V UL Modular UPS 20kW 600kW 2 CONCEPTPOWER DPA 120 280V MODULAR UPS Today s data centers require continuous uptime. That target is why ABB s Conceptpower DPA 120
More informationStandards Designation and Organization Manual
Standards Designation and Organization Manual InfoComm International Standards Program Ver. 2014-1 April 28, 2014 Issued by: Joseph Bocchiaro III, Ph.D., CStd., CTS-D, CTS-I, ISF-C Director of Standards
More informationMANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY. Subject: Control Reliability for Machinery & Equipment
DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY Subject: Control Reliability for Machinery & Equipment ISSUE DATE: January 3, 2005 EFFECTIVE DATE: January 31, 2005 REVIEW DATE. June 26, 2007
More informationDNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08
DNB Power and Control System Information and Interim Safety Procedures Version draft 5/06/08 DNB Power and Control System Information There are four sources of power for the DNB in the power supply and
More informationBuildingName The Description of the Project P DOCUMENTS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More informationCALIFORNIA INDEPENDENT SYSTEM OPERATOR CORPORATION FERC ELECTRIC TARIFF FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 727 METERING PROTOCOL
FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 727 METERING PROTOCOL FIRST REPLACEMENT VOLUME NO. II Original Sheet No. 728 METERING PROTOCOL Table of Contents MP 1 OBJECTIVES, DEFINITIONS AND SCOPE
More informationApplying branch circuit breakers and supplementary protectors in North America
Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee
More informationSIMATIC. Process Control System PCS 7 OS Process Control (V8.1) Security information 1. Preface 2. Additional documentation 3
Security information 1 Preface 2 SIMATIC Process Control System PCS 7 Operating Instructions Additional documentation 3 Functions of the PCS 7 OS in process mode 4 PCS 7 OS process mode - user interface
More informationPROJ 302. Project Report, Poster and Digest Guidelines. for Industrial Engineering Students. Summer 2017
PROJ 302 Project Report, Poster and Digest Guidelines for Industrial Engineering Students Summer 2017 General Notes - Read this document carefully before writing your internship report, poster, and digest.
More informationCALIFORNIA INDEPENDENT SYSTEM OPERATOR CORPORATION FERC ELECTRIC TARIFF ORIGINAL VOLUME NO. III Original Sheet No. 977 METERING PROTOCOL
ORIGINAL VOLUME NO. III Original Sheet No. 977 METERING PROTOCOL ORIGINAL VOLUME NO. III Original Sheet No. 978 METERING PROTOCOL Table of Contents MP 1 OBJECTIVES, DEFINITIONS AND SCOPE MP 1.1 Objective
More informationSIMPLIFi Compliance Software User Manual
SIMPLIFi Compliance Software User Manual Version 1.7 2013 Simplifi-Solutions Ltd, Environmental Center, Unit B5, The Gordon Manley Building, Lancaster University, LA1 4WA Telephone: 01524 510431 Email:
More informationProduct brochure. Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW
Product brochure Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW 2 Product brochure Conceptpower DPA 120 UL UPS Conceptpower DPA 120 The modular UPS for small and medium-sized data centers UPS
More informationSECTION DISTRIBUTION SWITCHBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 26 24 11 This section specifies the furnishing, installation, and connection of the distribution switchboards. 1.2 RELATED WORK: A. Section 13 05 41, SEISMIC RESTRAINT
More informationMAPILab Statistics for SharePoint User Guide
MAPILab Statistics for SharePoint User Guide Edition 1.0, April 2010, MAPILab LTD. Contents Introduction... 3 Quick start... 3 Getting started... 4 Report selection... 6 Report generation... 10 Filters
More informationPRODUCT BROCHURE. Cyberex Remote Power Panel (RPP) Power distribution system
PRODUCT BROCHURE Cyberex Remote Power Panel (RPP) Power distribution system 2 CYBEREX RPP POWER DISTRIBUTION REMOTE POWER PANEL Cyberex power distribution Remote Power Panel (RPP) With constantly evolving
More informationApplying branch circuit breakers and supplementary protectors in North America
Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North
More informationMESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset
More information