Hardware Installation Guide
|
|
- Oliver Brooks
- 5 years ago
- Views:
Transcription
1 Hardware Installation Guide LonMark Certified VAV/VVT Controllers: ECL-VAVS-O, ECL-VAVS, ECL-VAV, ECL-VVTS, ECL-VAV-N 10-Point LonMark Certified Programmable Controllers: ECL Product escription This document describes the hardware installation procedures for the Single uct Variable Air Volume / Variable Volume Temperature Controllers (ECL-VAVS-O, ECL-VAVS, ECL-VAV, ECL-VVTS, and ECL-VAV-N), and the 10-Point Programmable Controller (ECL-103). The istech Controls Variable Air Volume / Variable Volume Temperature product line is designed to control and monitor various types of HVAC equipment such as baseboards, single and multi-stage duct heaters, fans, valves, lights, etc. When connected to a Wireless Receiver, this product line can be used with a variety of wireless battery-less sensors and switches. Each controller uses the LONWORKS technology for peer-to-peer communication between controllers and are LONMARK certified. This document describes the hardware installation procedures for the following controllers: ECL-VAVS-O, ECL-VAVS, ECL-VAV, ECL-VVTS, ECL-VAV-N and ECL-103. For more information on the specific layout and functionality of each controller, please refer to their individual datasheets and user guides. Figure 1-1: ECL-VAV Figure 1-2: ECL-VAVS Figure 1-3: ECL-VAV-N 1/12
2 2. General Installation Requirements For proper installation and subsequent operation of the controller, pay special attention to the following recommendations: - It is recommended that the controller(s) be kept at room temperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature during shipping/storage to evaporate. - Upon unpacking the product, inspect the contents of the carton for shipping damages. o not install damaged controllers. - Avoid areas where corroding, deteriorating or explosive vapors, fumes or gases may be present. - Allow for proper clearance around the controller s enclosure, wiring terminals, and service pin (see Figure 17-1) to provide easy access for hardware configuration and maintenance, and to ventilate heat generated by the controller. Remember to record the 12-character Neuron I located on a sticker on top of the device (shown on a sticker below the barcode), for later commissioning. When installed in an enclosure, select one that provides sufficient surface area to dissipate the heat generated by the controller and by any other devices installed in the enclosure. A metal enclosure is preferred. If necessary, provide active cooling for the enclosure. - The controller s datasheet specifies the power consumption (amount of heat generated), the operating temperature range, and other environmental conditions the controller is designed to operate under. - Ensure that all equipment is installed according to local, regional, and national regulations. - o not drop the controller or subject it to physical shock. - If the controller is used and/or installed in a manner not specified by istech Controls, the functionality and the protection provided by the controller may be impaired. Any type of modification to any istech Controls product will void the product s warranty. Before installation of the Wireless Receiver, verify that local communication regulations allow the installation of wireless devices that operate at a frequency of 315 MHz or 868.3MHz. Refer to the Open-to-Wireless Solution Guide for more information. Take reasonable precautions to prevent electrostatic discharges to the controller when installing, servicing or operating the controller. ischarge accumulated static electricity by touching one s hand to a securely grounded object before working with the controller. 3. General Wiring Recommendations Turn off power before any kind of servicing. - All wiring must comply with electrical wiring diagrams as well as national and local electrical codes. - To connect the wiring to a controller, use the terminal connectors. Use a small flat screwdriver to tighten the terminal connector screws once the wires have been inserted. - Power type cables (i.e. for power, 2- and 3-wire voltage and current inputs and outputs, as well as triac outputs) should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires. - The board connectors accept wires or flat cables ranging from 22 to 14AWG (0.644 to 1.630mm diameter) per pole. However, power cables must be between 18 and 14AWG (1.024 to 1.630mm diameter). - o not connect the universal inputs, analog/digital outputs or common terminals to earth or chassis ground (unless stated otherwise). - Keep all wires away from high speed data transmission cables (for example, Ethernet, etc.). - Keep input and output wiring in conduits, trays or close to the building frame if possible. 4. Mounting Instructions The following mounting instructions pertain to controllers that have a built-in actuator (ECL-VAVS-O, ECL-VAVS, ECL-VAV, or ECL-VVTS). If mounting a controller without a built-in actuator (ECL-VAV-N and ECL-103), simply mount the controller using the integrated mounting bracket(s) and screw(s) that are provided with the controller. Each controller is specially designed for easy installation either directly on an air duct or in a panel by using the integrated mounting collar and the screw that is provided with the controller. This mounting arrangement opposes the torque applied to the damper shaft. Mount the controller as follows: 1. Orient the controller into position on to the damper shaft so that wiring connections are easily accessible. The controller must be fitted onto the shaft such that the base of the controller is parallel to the VAV box (perpendicular to the damper shaft). If the damper shaft has an external bushing that prevents the controller from being mounted flush to the side of the VAV box, use a spacer of the same thickness to compensate and to ensure the controller is at a right-angle to the shaft to prevent binding. Condensation from the damper shaft will damage the controller s electronics. When the VAV box air supply is below 10 C (50 F), ensure that any condensation from the damper shaft or from the VAV box does not enter the controller s electronics. Under these conditions, mount the controller vertically above the damper shaft so that any condensation from the damper shaft will fall away from the controller. Further countermeasures may be required in some installations. 2. Using a power screwdriver, attach the controller to the VAV box with the screw provided with the controller through the controller s mounting bracket slider. Otherwise, mark the screw s position on the VAV box with a punch and then drill a hole into the VAV box. Then attach the controller to the VAV box with the screw provided with the controller. Avoid over tightening the mounting screw so as to not strip the threads. Make sure the screws do not interfere with damper blade movement. 3. Find the damper position by the marking typically found on the end of the damper shaft. Figure 4-1: Typical amper Shaft End Marking 4. etermine the direction required to close the damper: Clockwise (CW) or Counterclockwise (CCW). Turn the damper shaft with a pair of pliers to fully close the damper for 90 boxes or fully open the damper for 45 or 60 boxes. 5. Press and hold down the Actuator Clutch for Manual Adjustment button (see Figure 5-3), and turn the controller s shaft coupler until 2/12
3 PRESSURE HIGH LOW E E E E it touches the mechanical end-stop to either the fully closed position (90 boxes) or the fully open position (45 and 60 boxes). 6. For 90 VAV boxes: If the damper closes CCW, turn the coupler to the CCW mechanical stop limit. If the damper closes CW, turn the coupler to the CW mechanical stop limit. The open mechanical stop is factory preset for 90 boxes. For 45 and 60 VAV boxes: The mechanical stops must be set for both the fully closed and fully open damper positions. By installing the controller at the fully open position, the controller provides the open mechanical stop for 45 and 60 boxes. The closed damper seal provides the fully closed stop. 7. Tighten the U-Bolt clamp on to the damper shaft using an 8 mm (5/16 in.) wrench or socket. Tighten the bolts between 11 and 15 N m (100 and 130 lb in). 8. Test for free damper shaft movement: Press and hold down the Actuator Clutch for Manual Adjustment button and manually turn the actuator coupling to be certain that the actuator can rotate from full closed to full open positions without binding. 9. Connect the VAV box s flow sensor tubing to the controller s Pressure Sensor Inputs. Create a condensation trap in the pneumatic tubing by forming it into a vertical loop. 10. Finalize the installation by rotating the damper to the full open position. CAUTION: Risk of Property amage. Ensure that the damper is at the full open position before starting the air handler. Failure to rotate the damper to its full-open position may result in damage to the Variable Air Volume (VAV) box or ductwork when the air handler is started. min. 40 mm (1.5") 61.5 [2.42] 10 [0.40] Units Legend: mm [in] 190 [7.48 ] High pressure Low pressure Figure 5-2: VAV-N and ECL-103 series dimensions amper Shaft Clamping Mechanism Opening for amper Shaft Mechanical Stops Actuator Clutch for Manual Adjustment 11 [0.43] 3 mm 0.12 in 54 [2.13 ] 5 [0.2] Bracket mouting kit 26.5 [1.04] Connectors Integrated Mounting Brackets PRESSURE HIGH LOW Pressure Sensor Inputs (when equipped) Service Pin Figure 4-2: Mounting a controller on a damper shaft Figure 5-3: VAVS-O, VAVS, VAV & VVTS series components 5. Controller imensions & Components Connectors Integrated Mounting Bracket Integrated Mounting Brackets Pressure Sensor Inputs (when equipped) Service Pin Figure 5-4: VAV-N and ECL-103 series components Figure 5-1: VAVS-O, VAVS, VAV & VVTS series dimensions 3/12
4 6. Configuration Jumper Location and Identification Controllers have the following onsite configurable jumpers. 4/12 Wireless Port Figure 6-1: 7. Power Wiring igital Outputs (O) Power Source Triac Internal Power* Net to Subnet Port Settings Enabled Triac External Powered * Factory-default positions isabled* Jumpers for O3 & O4 Jumpers for O1 & O2 Typical locations: Quantity may vary according to controller model Subnet Port ECL-VAV Series and ECL-103 Controller Jumper Locations Voltage: 24VAC; ± 15%, Class 2 This is a Class 2 Product. Use a Class 2 transformer only (rated at 100VA or less at 24VAC) to power the controller(s). The Network Guide provides extensive information and requirements for powering a VAV that uses a LONWORKS network for communications. It can be downloaded from our website. It is recommended to wire only one controller per 24VAC transformer. If only one 24VAC transformer is available, determine the maximum number of VAVs that can be supplied on a single power cable supplied by a 100 VA transformer, according to the cable s wire gauge and the total cable length from the following table. Table 7-1: Maximum Number of VAV evices on a Power Run AWG Power Run Total Cable Length Maximum Number of 7 VA per device 1 Maximum Number of 10 VA per device M (250 feet) M (200 feet) M (150 feet) M (100 feet) M (200 feet) M (150 feet) M (100 feet) M (150 feet) M (100 feet) Maximum Number of evices@ 15 VA per device 3 1. Typical VAV with 1 Allure EC-Smart-Vue sensor (without CO 2 sensor) and actuator activated. No external loads. 2. Typical VAV with 1 Allure EC-Smart- Vue sensor (without CO 2 sensor), 2 triac loads (1.6 VA each), 1 analog output (20 ma), and actuator activated. 3. Typical VAV with 1 Allure EC-Smart- Vue sensor (without CO 2 sensor), 4 triac loads (1.6 VA each), 2 analog outputs (20 ma each), and actuator activated. OR Typical VAV with 1 Allure EC-Smart-Vue with CO 2 sensor, 2 triac loads (1.6 VA each), 1 analog output (20 ma), and actuator activated. 4. evice terminals are not capable of accepting two 14 AWG wires (when daisy-chaining devices). Use a wire nut with a pig tail to make such a connection. Any installation condition that is outside of the parameters of Table 7-1 should be avoided. Use an external fuse on the 24VAC side (secondary side) of the transformer, as shown in Figure 7-1 and Figure 7-2, to protect all controllers against power line spikes. Maintain consistent polarity when connecting controllers and devices to the transformer. That is, the terminal of each controller and each peripheral should be connected to the same terminal on the secondary side of the transformer. Figure 7-1: Figure 7-2: The terminals of the controller are internally wired to the 24V terminal of the power supply. Connecting a peripheral or another controller to the same transformer without maintaining polarity between these devices will cause a short circuit. Controller 1 24V AC/C 24V Controller 2 24V AC/C 24V Controller 1 24V AC/C 24V Controller 2 24V AC/C 24V Fuse: 4 A Max. Fast Acting Power wiring AC 24 VAC Fuse: 4 A Max. Fast Acting Power wiring C AC Transformer OPTIONAL: Connect to Electrical System Ground - At Power Supply Only 24 VC OPTIONAL: Connect to Electrical System Ground - At Power Supply Only Connecting the power source to Electrical System Ground is not a requirement for proper system operation. However it is good installation practice to do so in order to maintain the same potential between all controllers and Protective Earth. 8. Input Wiring Each controller has physical connections for inputs (marked as ) that are configured with EC-gfxProgram. Each input can be configured for digital, resistive, current, voltage, or pulse signals. Input types must be configured properly in software to ensure proper input readings. Before connecting a sensor to the controller, refer to the installation guide of the equipment manufacturer. For a wire length less than 75 (23m), either a shielded or unshielded 18AWG wire may be used. For a wire up to 200 (61m) long, a shielded 18AWG wire is recommended. The shield of the wire should be grounded on
5 the controller side and the shield length should be kept as short as possible. Wiring igital Inputs This input configuration is used to monitor digital dry contacts, as well as pulsed contacts. igital ry Contact NO-NC Figure 8-1: igital dry contact (NO & NC) To igital Input Wiring Resistive Inputs This input configuration is used to monitor Resistance Temperature etectors (RT), thermistors such as 1000Ω RTs, 10kΩ type II and III thermistors, as well as 10kΩ and 100kΩ potentiometers. RT/ Thermistor To-igital Figure 8-2:Resistive input RT /Thermistor input Potentiometer 10kΩ To-igital Figure 8-3: Resistive input 10kΩ Potentiometer input Wiring Current Inputs Current inputs have a range of 0 to 20mA. epending on the transducer power requirements, any one of the following input configurations can be used. Use the following configuration for a 2- wire, 0 to 20mA transducer powered by the controller s internal 15VC power supply. Transducer mA 249Ω / ¼W +15VC To Controller s Analog-To-igital Figure 8-4: Current input 2-wire transducer powered by the controller Use the following configuration for a 2-wire, 0 to 20mA transducer powered by an external 24 AC/C power supply. 0-20mA - Transducer + 249Ω ¼W 24VC To-igital Figure 8-5: Current input 2-wire transducer, externally powered Use the following configuration for a 3-wire, 0 to 20mA transducer powered by an external 24 AC/C power supply mA Common Transducer 24VAC 249Ω ¼W AC To-igital Figure 8-6: Current input 3-wire transducer, externally powered Use the following configuration for a transducer powered by its own power source. 249Ω ¼W Figure 8-7: Current input Transducer with its own power source Wiring Voltage Inputs Voltage inputs have a range of 0 to 10VC or 0 to 5VC. Connect the voltage input according to the following figure if a 3-wire 0 to 10V or 0 to 5V transducer is being used V Common Transducer 24VAC AC To-igital Figure 8-8: Voltage input 3-wire transducer Connect the voltage input according to the following figure if the transducer is powered by its own power source. 0-10V + Transducer - To-igital Figure 8-9: Voltage input Transducer with its own power source 9. Allure EC-Smart-Vue Wiring The Allure EC-Smart-Vue sensor is a communicating room temperature sensor with backlit display and graphical menus. and has VAV balancing capabilities. Connect the Allure EC-Smart-Vue sensor to the controller with a standard Category 5e Ethernet patch cable fitted with RJ-45 connectors. The Network Guide provides extensive information and requirements for the connection of Allure EC-Smart-Vue sensors. It contains information about network topology and length, cable type, setting the Subnet I, etc. It can be downloaded from our website. See also the Hardware Installation Guide supplied with the Allure EC-Smart-Vue sensor. If you make your own patch cable, use Category 5e cable crimped with RJ-45 connectors either as T568A or T568B. - o not crimp one connector as T568A and crimp the other connector as T568B on the same cable. - Protect the controller s connector from being pulled on when a cable to the Allure EC-Smart-Vue sensor is connected. Create a strain-relief by looping the cable and attaching it to a solid object with a nylon tie so that a tug on the cable will not pull out the connector on the controller. Table 9-1: T568A and T568B Terminations for an RJ-45 Connector Pin T568A (at both cable ends) T568B (at both cable ends) Pair Color Pair Color white/green stripe white/orange stripe green solid orange solid white/orange stripe white/green stripe blue solid blue solid white/blue stripe white/blue stripe orange solid green solid white/brown stripe white/brown stripe brown solid brown solid The final result of a crimped RJ-45 connector is shown graphically below. T568A T568B Key: mA + Transducer - To-igital Stripe Solid Pair 3 Pair 1 Pair 2 Pair 4 Pair 2 Pair 1 Pair 3 Pair 4 5/12
6 Figure 9-1: T568A and T568B Crimp Wire Sequence for an RJ-45 Connector Ox JUMPER SETTINGS Cx-x AC A1 A2 24VAC Relay Figure 10-1: igital output with external power supply Relay Figure 9-2: Pins on RJ-45 Jack Face Patch cables fitted with connectors supplied by istech Controls are wired as T568B. 10. Output Wiring Each controller has physical connections for either digital (triac) and/or universal outputs, depending on the type and model. The power source type for digital outputs is hardware configurable and must be configured by changing the jumper settings on the printed circuit board (for jumper location, see Section 6). The universal outputs are software configurable. Before connecting an output device (actuator, relay, etc.) to the controller, refer to the installation guide of the equipment manufacturer. For a wire length less than 75 (23m) long, either a shielded or unshielded 18AWG wire may be used. For a wire up to 200 (61m) long, a shielded 18AWG wire is recommended. The shield of the wire should be grounded on the controller side and the shield length should be kept as short as possible. Wiring igital Outputs (Ox) igital outputs are all made of triacs and can be configured as either powered outputs or non-powered outputs and output wiring must be done accordingly. - The non-powered output type does not have any voltage on the output terminals when the output is active. Power must be supplied externally. - The powered output type has 24VAC on the output terminals when the output is active. Power is therefore supplied internally by the controller. It should be noted that all controllers are shipped with all digital outputs configured as powered outputs. Maximum output current for all digital outputs (whether powered or non-powered) is 0.5A continuous or 15% duty cycle for a 10-minute period. To measure the state of a digital output (TRIAC), an external load must be connected. O1 and O2 share the same C1-2 common terminal and are controlled by a single jumper and must therefore be set identically. Similarly, O3 and O4 (VAV, VVT and ECL-103 product lines only) share the same C3-4 common terminal and are controlled by a single jumper and must therefore be set identically. The jumpers are used to specify whether an internal or external power source is being used. For jumper location, see Section 6. If a 24VAC relay is being controlled using an external or internal power supply, connect the digital output according to the following figures. External power supplies must be grounded as shown in Figure 10-1 and Figure Figure 10-2: JUMPER SETTINGS Ox Cx-x A2 24VAC Relay igital output with internal power supply Relay If a floating actuator is being controlled using an external or internal power supply, connect the digital output according to the following figures. Figure 10-3: JUMPER SETTINGS A1 Ox ~ 24VAC Cx-x Ox ~ Actuator igital output with external power supply Floating actuator JUMPER SETTINGS Actuator Ox ~ Cx-x Ox ~ Figure 10-4: igital output with internal power supply Floating actuator Wiring Universal Outputs (UOx) Universal outputs can be configured to provide either a discrete signal of 0 or 12VC or a linear signal ranging from 0 to 10VC. The discrete signal can be used to generate a pulse wave modulation (PWM) signal or a simple two-state signal. These outputs are protected by an auto-reset fuse. Wiring iscrete Outputs If a 12VC relay is being controlled, connect it to a universal output according to the following figure. From igital Output UOx A1 A2 12VC Relay Figure 10-5: iscrete 0 or 12VC universal output Relay Wiring Voltage Outputs Connect the 0 to 10VC output according to the following figure. From igital- To-Analog Output UOx 0-10V Common Figure 10-6: Voltage 0 to 10VC universal output If an analog actuator is being controlled, connect the 0 to 10VC output, along with an external 24VAC power source, to the analog actuator according to the following figure. From igital- To-Analog Output UOx Actuator 0-10V ~ or + 24VAC or - Figure 10-7: Voltage 0 to 10VC universal output Analog actuator 11. Communications Wiring The recommended cable type for LONWORKS communications is 22AWG (0.65 mm), twisted pair, unshielded. The LONWORKS communication wire is polarity insensitive and can be laid out in a bus, star, loop or free topology. For loop topology, polarity is important, special care must be taken when connecting the LONWORKS network to avoid short circuit. 6/12
7 It is recommended to use the bus topology network configuration for all LonWorks communication wiring, as it allows for easy network troubleshooting. Connect both wires to the LON+ and LON- terminals of the controller. If inserting multiple wires in the terminals, ensure to properly twist wires together prior to inserting them in the terminal connectors. LON Network To Next Controller Controller 1 LON+ LON- Controller 2 LON+ LON- Figure 11-1: Communications wiring For more information and detailed explanations on network topology and wire length restrictions, refer to the Network Guide. It can be downloaded from our website. It is important to use proper network terminators depending on the type of network topology used. Failure to do so might result in communication errors between controllers. Selecting Network Terminators Topology istech Controls Part # Bus PII-BT-TP10XX Free PII-FT-TP10XX For a bus topology, 2 network terminators are required (1 at each end of the bus topology channel). For a free topology, 1 network terminator is required and it can be put anywhere on the channel. When used with an Allure EC-Smart-Vue sensor, the network can be accessed at the sensor s audio plug port for commissioning and maintenance purposes, when the two Net to Subnet Port Settings jumpers inside the ECL series controller are set to Enable (for jumper location, see Section 6). This will connect the main LONWORKS network to the Allure EC-Smart-Vue subnetwork Cat5e cable. Recommendation: Only a limited number of controllers on a LONWORKS network segment should have their Net to Subnet Port Settings jumpers enabled. Enabling too many Allure EC-Smart-Vue sensors with network access may cause network communication issues. If there are any network communication problems, refer to Section 18. The Cat5e cable length is restricted by the maximum allowable subnetwork bus length (see the Allure EC-Smart-Vue Hardware Installation Guide for more information). contacts and light switches. These devices are easy to install, and can be mounted on a wide range of building materials. The Wireless Receiver is available in 315MHz or 868.3MHz frequencies. Before connecting any wireless equipment to the controller, refer to the Open-to-Wireless Solution Guide. Connecting the Wireless Receiver The Wireless Receiver is connected to the controller using a 2m (6.5ft) telephone cable with 4P4C modular connectors at both ends. o not exceed this cable length. The Wireless Receiver s telephone socket is located inside the device. To locate it, open the Wireless Receiver by separating its front and back plates. Figure 12-1: Location of the Wireless Receiver s telephone socket Connecting to the Controller s Wireless Port Each controller has a wireless port in which one end of the Wireless Receiver s telephone cable plugs in. Uncover the controller to locate the wireless port on the PCB board (marked as Wireless Module). 13. Terminal Block Cover In certain jurisdictions, terminal block covers are required to meet local safety regulations. Terminal block covers are available for all controllers and are used to conceal the controllers wire terminals. Terminal block covers are optional and are sold as peripherals. The terminal block cover can be clipped on to the controller as shown below. Bus Network Topology: 22AWG (0.65mm) Unshielded Twisted Pair Network Cable Controller Standard Net to Subnet Port Settings: ISABLE - this is the factory default setting For a Few Controllers ONLY: Net to Subnet Port Settings Optionally Enabled E Figure 13-1: Terminal block cover installation Allure EC-Smart-Vue Figure 11-2: LonWorks Network Bus Topology 12. Wireless Installation Cat5e communications cable: Allure EC-Smart-Vue Sub-Network Bus LONWORKS Network when Net to Subnet Port Settings jumpers are Enabled When connected to a Wireless Receiver, controllers can receive input signals from a wide selection of wireless devices. Compatible wireless devices include temperature sensors, duct sensors, window/door Enable isable 14. Maintenance Turn off power before any kind of servicing. Each controller requires minimal maintenance, but it is important to take note of the following: - If it is necessary to clean the outside of the controller, use a dry cloth. - Retighten terminal connector screws annually to ensure the wires remain securely attached. 7/12
8 15. isposal The Waste Electrical and Electronic Equipment (WEEE) irective sets out regulations for the recycling and disposal of products. The WEEE2002/96/EG irective applies to standalone products, ie. products that can function entirely on their own and are not a part of another system or piece of equipment. For this reason istech Controls products are exempt from the WEEE irective. Nevertheless, istech Controls products are marked with the WEEE symbol, indicating that disposal of the devices shall not be done together with municipal waste. Products must be disposed of at the end of their useful life according to local regulations and the WEEE irective. 16. FCC Statement Changes or modifications not expressly approved by istech Controls could void the user's authority to operate the equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/tv technician for help. 8/12
9 E E 17. Typical Variable Air Volume Application Wiring iagram Back of Allure EC-Smart-Vue EOL Enabled at the last sensor at the end of the Bus From Previous evice LONWORKS Network To Next evice ON OFF BAC LON EOL Wireless Port (beneath cover) Heating Floating Actuator HIGH PRESSURE LOW Service PIN Button Fuse 24VAC L N GN 120 / 220 VAC OPTIONAL: Connect to Electrical System Ground Allure EC-Smart-Vue Figure 17-1: Typical Power and Network Connections with an Allure EC-Smart-Vue Input and Floating Actuator Output 9/12
10 18. Troubleshooting guide Controller is powered but does not turn on Fuse has blown isconnect the power. Check the fuse integrity. Reconnect the power. Power supply polarity Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the 24V terminal of each controller is connected to the same terminal on the secondary side of the transformer. See Figure 7-1 and Figure 7-2. Controller cannot communicate on the LONWORKS network Absent or incorrect supply voltage 1. Check power supply voltage between 24VAC ±15% and 24V pins and ensure that it is within acceptable limits. 2. Check for tripped fuse or circuit breaker. Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers. Network not wired properly ouble check that the wire connections are correct. Absent or incorrect network termination Check the network termination(s). Too many Allure EC-Smart-Vue sensors are isable the Net to Subnet Port Settings jumpers on all controllers (for jumper location, see Section 6). If communications providing network access are re-established, re-enable only a few Allure EC-Smart-Vue sensors to have network access. Controller communicates well over a short network, but does not communicate on large network Network length Check that the total wire length does not exceed the specifications of the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks. Wire type Check that the wire type agrees with the specification of the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks. Network wiring problem ouble check that the wire connections are correct. Absent or incorrect network termination Check the network termination(s). Incorrect or broken termination(s) will make the communication integrity dependent upon a controller s position on the network. Extra capacitance Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit and a maximum of a 3 meter stub (in bus topology). Number of controllers on network segment The number of controllers on a channel should never exceed 64. Use a router or a repeater in accordance to the Junction exceeded Box and Wiring Guideline for Twisted Pair LonWorks Networks. Network traffic Query node statistics to check for errors. Use a LONWORKS protocol analyzer to check network traffic. Hardware input is not reading the correct value Input wiring problem Check that the wiring is correct according to this manual and according to the peripheral device s manufacturer. Open circuit or short circuit Using a voltmeter, check the voltage on the input terminal. For example, for a digital input, a short circuit shows approximately 0V C and an open circuit shows approximately 5V C. Configuration problem Using EC-gfxProgram, check the configuration of the input. Refer to the controller s user guide for more information. Over-voltage or over-current at an input An over-voltage or over-current at one input can affect the reading of other inputs. Respect the allowed voltage / current range limits of all inputs. Consult the appropriate datasheet for the input range limits of this controller. Hardware output is not operating correctly Fuse has blown (auto-reset fuse) isconnect the power and outputs terminals. Then wait a few seconds to allow the auto-reset fuse to cool down. Check the power supply and the output wiring. Reconnect the power. Output wiring problem Check that the wiring is correct according to this manual and according to the peripheral device s manufacturer. Configuration problem Using the controller configuration plug-in or wizard, check the configuration of the output. Refer to the controller s user guide for more information. 0-10V output, 24VAC powered actuator is not moving. Wireless devices not working correctly Check the polarity of the 24VAC power supply connected to the actuator while connected to the controller. Reverse the 24VAC wire if necessary. Check the jumper settings for the external power supply as shown in Figure evice not associated to controller Using EC-gfxProgram, check the configuration of the input. Refer to the device s user guide for more information. Power discharge 1. Recharge device with light (if solar-powered) or replace battery (if battery-powered), 2. Ensure sufficient light intensity (200lx for 4 hours/day). evice too far from the Wireless Receiver Reposition the device to be within the range of the Wireless Receiver. For information on typical transmission ranges, refer to the Open-to-Wireless Solution Guide. Configuration problem Using the device configuration plug-in or wizard, check the configuration of the input. Refer to the Wireless Battery-less Sensors and Switches Solutions Guide for more information. Flow sensor is not giving proper readings Tubing connection problem 1. Make sure that the tubing is installed properly and that the tubing is not bent. 2. Verify that the high and low pressure sensors are not inversed. Controller is not calibrated properly Recalibrate the controller. Refer to the controller s user guide for more information. amper is not opening or closing properly Mechanical stops not in proper position The two mechanical stops must be positioned to stop the damper motion when it is completely closed and completely opened. The mechanical stops can be moved by increments of 5. Controller in Override Set the Override to OFF in the wizard. Rx/Tx LEs RX LE not blinking ata is not being received from the LONWORKS data bus. TX LE not blinking ata is not being transmitted onto the LONWORKS data bus. 10/12
11 Status LE Normal Operation One fast blink Fast blink continuous: (150ms On, 150ms Off, continuous) The Status LE is always OFF Initialization: The device is starting up. Firmware upgrade in progress. Controller operation is temporarily unavailable. The new firmware is being loaded into memory. This takes a few seconds. o not interrupt power to the device during this time. The controller is operating normally. Status LE blink patterns Repeats every 2 seconds (highest priority shown first) Long blink continuous: The controller is unconfigured. Appropriate action: Commission the controller (1s On, 1s Off, continuous) Long Long Long blink (800ms On, 300ms Off, 800ms On, 300ms Off, 800ms On) Long Short Short Short blink (800ms On, 300ms Off, 150ms On, 300ms Off, 150ms On, 300ms Off, 150ms On) Short Short Long blink (150ms On, 300ms Off, 150ms On, 300ms Off, 800 ms On) Fast blink 12x: (80ms On, 80ms Off, 12x) The controller is offline. Appropriate action: Set the controller Online The controller is in bypass mode. Appropriate action: Set the controller Online Poor-quality power; The device has browned-out: The voltage at the 24VAC and 24V terminals has gone below the device s acceptable limit during power up. Wink. The wink function is used to identify a device. For issues with the Allure EC-Smart-Vue sensor, refer to the Allure EC-Smart-Vue Hardware Installation Guide. 11/12
12 Total Quality Commitment All istech Controls product lines are built to meet rigorous quality standards. istech Controls is an ISO 9001 registered company. Hardware Installation Guide - ECL-VAV, ECL-VAV-N, ECL-VAVS-O, ECL-VVTS, ECL-VAVS, ECL-103, Copyright istech Controls Inc., All rights reserved. Images are simulated. While all efforts have been made to verify the accuracy of information in this manual, istech Controls is not responsible for damages or claims arising from the use of this manual. Persons using this manual are assumed to be trained HVAC specialist / installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail-safe environments. istech Controls reserves the right to change, delete or add to the information in this manual at any time without notice. istech Controls, the istech Controls logo, Open-to-Wireless, Innovative Solutions for Greener Buildings, ECO-Vue, and Allure are trademarks of istech Controls Inc. Echelon, Neuron, LON, LONWORKS, LONMARK and LNS are registered trademarks of Echelon Corporation. Niagara AX Framework is a registered trademark of Tridium, Inc. 12/12 *05I-HILVAVT-12* 05I-HILVAVT-12
SLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)
SLX Series Document No. 997-1000 Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L) Free Programmable Controllers (SLX-PC-203, SLX-PC-300, SLX-PC-400, SLX-PC-500
More informationHardware Installation Guide
Hardware Installation Guide IO Extension Module for ECL600 and ECB600 Series Controllers: 1. Product Description This document describes the hardware installation procedures for the I/O Extension Modules.
More informationHardware Installation Guide
Hardware Installation Guide BACnet Application Specific controller: ECB-203, ECB-300 and ECB-400 1. Product Description This document describes the hardware installation procedures for the ECB-series BACnet
More informationContent. Product Description
EY-modulo 4 EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications en Guidelines for the electrician Content 1 Product
More informationECB-VAV Series & ECB-103 Controllers
Hardware Installation Guide ECB-VAV Series & ECB-103 Controllers Figure 1: From left to right: ECB-VAV and ECB-103 Product Description This document describes the hardware installation procedures for the
More informationAllure EC-Smart-Vue Sensor Series
H a r d w a r e I n s t a l l a t i o n G u i d e Allure EC-Smart-Vue Sensor Series Figure 1: (Left image) Allure EC Smart Vue, Allure EC Smart Vue-H/-C/-CH sensors. (Right image) Models equipped with
More informationECP-VAV Series. ECP-VAV Series. 10-Point Single Duct VAV / VVT Free Programmable Controller. Applications. Features
ECP-VAV Series 10-Point Single Duct VAV / VVT Free Programmable Controller Applications Designed to meet the requirements of single duct variable air volume (VAV) or variable volume according to temperature
More informationDatasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview
Datasheet BACnet B-ASC Powered Terminal Unit Programmable Controllers Overview Applications Meets the requirements of the following applications: Fan Coil Units Heat Pumps Chilled Beams Reversible Ceiling
More informationLN Series Communicating Sensors
LN Series Communicating Sensors LN-SVSEN-0, LN-SVSENH-0 Code No. LIT-12011795 Issued November 2017 Application Refer to the QuickLIT website for the most up-to-date version of this document. The LN Series
More informationLN Free Programmable PRG 600 Series Controllers
LN Free Programmable PRG 600 Series Controllers Installation Instructions LN-PRG600-2, LN-PRG610-2 Code No. LIT-12011691 Issued July 17, 2014 Refer to the QuickLIT website for the most up-to-date version
More informationOverview. Seen as an extension of the main HVAC controller when configuring, allowing you to save engineering time.
Datasheet Lighting Expansion Modules Overview Applications On/Off lighting 1-10 V dimming lighting The Expansion Modules are microprocessor-based interfaces that extend the number of inputs and outputs
More informationLN Series Input/Output (I/O) Extension Modules
LN Series Input/Output (I/O) Extension Modules Installation Instructions LN-IOE400-0, LN-IOE410-0, LN-IOE420-0 Code No. LIT-12011693 Issued April 24, 2014 Supersedes January 30, 2013 Refer to the QuickLIT
More informationOverview. Seen as an extension of the main HVAC controller when configuring, allowing you to save engineering time.
Datasheet Shades / Sunblinds Expansion Modules Overview Applications 100-240 VAC shades / sunblinds 24 VDC shades / sunblinds The Expansion Modules are microprocessor-based interfaces that extend the number
More informationDatasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview
Datasheet ECB-103 BACnet B-ASC 10-Point Programmable Controller Overview Applications Meets the requirements of the following applications: Fan Coil Units Heat Pumps Unit Ventilators Chilled Ceilings Improves
More informationTECH/DATA SHEET. Application. Model Chart. Installation. slon-v1. slon-v2. slon VAV Controller
TECH/DATA SHEET s-v1 s-v2 s VAV Controller Application Solidyne s s-v1 and s-v2 VAV Controllers are interoperable MARK -compliant variable air volume controllers. These controllers provide pressure independent
More informationDatasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview
Datasheet BACnet B-ASC 10-Point Programmable Controller Overview Applications Meets the requirements of the following applications: Fan Coil Units Heat Pumps Unit Ventilators Chilled Ceilings Improves
More informationBACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview
Datasheet BACnet B-ASC Powered Terminal Unit Programmable Controllers Applications Meets the requirements of the following applications: Fan Coil Units Heat Pumps Chilled Beams Reversible Ceiling with
More informationVAV Modular Assembly (VMA) 1410/1420
Installation Instructions Issue Date June 9, 2004 VAV Modular Assembly (VMA) 1410/1420 Application The Variable Air Volume (VAV) Modular Assembly (VMA) 1400 Series consists of configurable digital controllers.
More informationOverview. Integrated fail-safe mode in case of communication or power failure to comply with most regulation requirements
Datasheet Lighting and Sunblind Expansion Modules Overview Applications When connected to any compatible HVAC programmable controller, the ECx-Light/Blind expansion modules allow to control up to 8 lights
More informationLantech. IPES /100TX with 4 PoE Injectors 24~48VDC Industrial Switch. User Manual
Lantech IPES-0008-4 8 10/100TX with 4 PoE Injectors 24~48VDC Industrial Switch User Manual V1.00 Jun 2010 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
More informationENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.
TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101 TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions Application
More informationFCC Regulatory Information
DVW32C Advanced Wireless Voice Gateway - Safety and Installation Product Insert Federal Communications Commission (FCC) Interference Statement This equipment has been tested and found to comply with the
More informationECB-VAVS. Features and Benefits. Applications Cooling Only VAV Boxes Cooling with Reheat VAV Boxes Room Pressurization.
D a t a s h e e t ECB-VAVS Overview The ECB-VAVS controllers are microprocessorbased programmable variable air volume (VAV) controllers designed to control cooling only and cooling with reheat single duct
More informationIQ-SBS LCU Series Installation Instructions
Installation Instructions LCU-1 The IQ-SBS LCU-1 is a self-contained device for integrating control of facility lighting with IQ-SBS. The LCU-1 controls lighting zones, accepts input from override switches
More information4-port 10/100TX + 1 or 2-port 100FX Industrial Switch. User Manual
4-port 10/100TX + 1 or 2-port 100FX Industrial Switch User Manual Rev.1.03 Sep-2010 FCC Warning This Equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
More informationECP-PTU Series. ECP-PTU Series. 14-Point High-Voltage Programmable Power Terminal Unit Controller. Applications. Features
ECP-PTU Series 14-Point High-Voltage Programmable Power Terminal Unit Controller Applications Control of equipment such as: roof top units, fan coils, heat pumps, ventilator units, terminal units, lighting
More informationLTEC Heat Pump DDC Controller
Document No. 09 Rev., May, 00 LTEC Heat Pump DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) HP (Heat Pump) DDC Controller
More informationUSER GUIDE. AXIS T8120 Midspan 15 W 1-port ENGLISH
USER GUIDE AXIS T8120 Midspan 15 W 1-port ENGLISH Legal Considerations Video and audio surveillance can be prohibited by laws that vary from country to country. Check the laws in your local region before
More informationMNL-V1RVx MNL-V2RVx. Application. Model Chart. TAC I/A Series MicroNet Variable Air Volume Controllers Installation Instructions
TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com MNL-V1RVx MNL-V2RVx TAC I/A Series MicroNet Variable Air Volume Controllers Installation Instructions Application TAC I/A Series
More informationThis simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power input.
LMC5103A-R2 1-slot Multipower Desktop Chassis (Module Not Included) This simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power
More informationECB-VAVS and ECB-VAV Series
ECB-VAVS and ECB-VAV Series BACnet B-ASC VAV / VVT Controllers Overview Applications Meets the requirements of single duct VAV zone applications, including: Cooling Only VAV Boxes Cooling with Reheat VAV
More informationSpecification Sheet For electronically commutated motors
SC-VAV-N Specification Sheet For electronically commutated motors Used in constant pressure applications The SC-EFC is designed to control exhaust air in various building applications. The system includes
More informationInstallation manual for for Schleifenbauer DPM3
Installation manual for for Schleifenbauer DPM3 Installatie handleiding voor Schleifenbauer DPM3 Installationsanleitung für Schleifenbauer DPM3 Guide d installation du Schleifenbauer DPM3 Installation
More informationUSB 2.0 CAT5E/6/7 EXTENDER
USER MANUAL IC402A-R2 USB 2.0 CAT5E/6/7 EXTENDER 24/7 AT OR VISIT BLACKBOX.COM + + + + Mode Config Power Link Host Activity Power Link Host Activity TABLE OF CONTENTS PRODUCT OPERATION AND STORAGE... 3
More informationLN Series Free Programmable LN-PRGxxx-12 Controllers
LN Series Free Programmable LN-PRGxxx-12 Controllers Installation Instructions LN-PRG203-12, LN-PRG300-12, LN-PRG4x0-12, LN-PRG6x0-12 Code No. LIT-12011796 Issued April 24, 2014 Supersedes January 30,
More informationDatasheet. ECB-VAV Series. 1/8. BACnet B-ASC Single Duct VAV / VVT Controllers. Overview
Datasheet ECB-VAV Series BACnet B-ASC Single Duct VAV / VVT Controllers Applications Meets the requirements of VAV zone applications, including: Cooling Only VAV Boxes Cooling with Reheat VAV Boxes Parallel
More informationLN Application Specific, Remote I/O, and Free Programmable Controllers
LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions LN-RTUL-1, LN-FCUL-1, LN-UVL-1, LN-HPUL-1, LN-IOxxx-1, LN-PRG203-2, LN-PRG300-2, LN-PRG4x0-2, LN-PRG5x0-2
More informationDatasheet. ECB-VAV Series. 1/8. BACnet B-ASC Single Duct VAV / VVT Controllers. Overview
Datasheet BACnet B-ASC Single Duct VAV / VVT Controllers Overview Applications Meets the requirements of VAV zone applications, including: Cooling Only VAV Boxes Cooling with Reheat VAV Boxes Parallel
More informationUNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN
1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,
More informationLONMARK Certified Powered Fan Coil Configurable Controllers. Overview
Datasheet RCL-PFC Series LONMARK Certified Powered Fan Coil Configurable Controllers Overview Applications Meets the requirements of the following applications: Fan Coil Units Unit Ventilators Chilled
More informationMulti-Power Miniature Media Converter 10/100/1000 JUNE 2007 LGC322A-NPS LGC320A-NPS, LGC321A-NPS,
Copyright 2006. Black Box Corporation. All rights reserved 1000 Park Drive * Lawrence, PA. 35055-1018 * 724-746-5500 * Fax 724-746-0746 56-80830BB-00 Rev A1 June 2007 JUNE 2007 LGC320A, LGC321A, LGC322A,
More informationInstallation & Operation Guide
Installation & Operation Guide Direct Digital VAV Controllers KMD-7001/7051 - VAV Terminal Units KMD-7002/7052 - Dual Duct VAV Units KMD-7003/7053 - Fan Induction Units 907-019-01C 1 Introduction This
More informationLTEC Unit Ventilator DDC Controller
Document No. 09 Rev., May, 00 LTEC Unit Ventilator DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) UV (Unit Vent)
More information10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter. AMG9011G-H (-40 to 75C) User Manual
10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter AMG9011G-H (-40 to 75C) User Manual www.amgsystems.com Content Overview...1 Introduction... 1
More informationDDW36A Advanced Wireless Gateway - Safety and Installation Product Insert. Federal Communications Commission (FCC) Interference Statement
DDW36A Advanced Wireless Gateway - Safety and Installation Product Insert Federal Communications Commission (FCC) Interference Statement This device has been tested and found to comply with the limits
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS LonWorks Communication Card RXRX-AY02 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
More informationBACnet vs. Lonworks Specifications (Network Guide)
Connections IP, MS/TP, Ethernet TCP/IP with Fox connections Topology BACnet p. 17-19 Lon pp. 39-40 Termination Requirements BACnet pp. 17-19 Lon pp. 39-40 Cable Requirements BACnet p. 16 Lon p. 41 Daisy
More informationAS1008-P AS1026-P AS2008-P AS2024-P User Manual
Fast Ethernet and Gigabit Ethernet PoE+ Unmanaged Switches AS1008-P AS1026-P AS2008-P AS2024-P User Manual Version 1.0.0.1 Sep 2017 Contents Compliances and Safety Statements... 3 1. AS1000 Series Product
More informationIEC-0101FT Industrial 10/100TX to 100M-FX Slim Type Converter User Manual
Lantech IEC-0101FT Industrial 10/100TX to 100M-FX Slim Type Converter User Manual FCC Warning This Equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
More informationCOMMERCIAL. VAM24-90-(A) Series Installation Instructions
MERCIAL VAM24-90-(A) Series Installation Instructions Bray Controls Commercial Division 13788 West Road, Suite 200A Houston, Texas 77041 BCDSales@Bray.com Phone: 1-888-412-2729 Fax: 1-888-412-2720 www.braycommercialdivision.com
More informationNow with Picture Memory
Intrasonic Technology, Inc. Color Video Door Phone / Intercom Installer s Manual Model No.V304KIT-R Now with Picture Memory Please read this manual carefully before the products are installed.technical
More informationUSB 3.1 CAT6A/7 EXTENDER
USER MANUAL ICU504A USB 3.1 CAT6A/7 EXTENDER 24/7 AT OR VISIT BLACKBOX.COM Power Mode Config Status Link Video USB 2 USB 3 Power Mode Config Status Link Video USB 2 USB 3 TABLE OF CONTENTS PRODUCT OPERATION
More informationALTAI C1N SUPER WIFI CPE INSTALLATION GUIDE. Version 1.0 Date: September, Altai Technologies Ltd. All rights reserved
ALTAI C1N SUPER WIFI CPE INSTALLATION GUIDE Version 1.0 Date: September, 2013 Copyright 2007 Altai Technologies Limited ALL RIGHTS RESERVED. Altai Technologies Limited Unit 209, 2/F, East Wing, Building
More informationLN Series Remote Input/Output (I/O) Modules
LN Series Remote Input/Output (I/O) Modules Product Bulletin LN-IO301-1, LN-IO401-1, LN-IO520-1 Code No. LIT-12011316 Issued June 5, 2012 Supersedes November 9, 2007 The LN Series Remote Input/Output (I/O)
More informationCTS-iCPE Gateway Controller User s Manual Version: Revision B1
CTS-iCPE Gateway Controller User s Manual Version: Revision B1 Trademarks Contents are subject to revision without prior notice. All other trademarks remain the property of their respective owners. Copyright
More informationDatasheet. ECB-600 and ECx-400 Series. ECB-600 & ECx-400. Overview. Applications. Features & Benefits.
Datasheet ECB-600 and ECx-400 Series BACnet Programmable Controllers and I/O Extension Modules Overview Applications Meets the requirements of the following applications: Central Plant Air Handling Units
More informationHARDWARE GUIDE. VAV Zone Controller C1000 Series. Specifications and Operational Guide
HARDWARE GUIDE VAV Zone Controller C1000 Series Specifications and Operational Guide www.proloncontrols.com info@proloncontrols.com 17 510, rue Charles, Suite 100, Mirabel, QC, J7J 1X9 REV. 6.1.6 PL-HRDW-VAV-C1000-C/F-EN
More informationT775S Series 2000 Expansion Module
T775S Series 000 Expansion Module INSTALLATION INSTRUTIONS PRODUT DESRIPTION The T775S008 Relay Expansion Module is a four relay device for use with the T775L007 and T775P00 Series 000 Electronic Stand-Alone
More informationQuick Installation Guide
Quick Installation Guide For Network Attached Storage Ver.1.1.0.0517 Table of Contents Notices... 3 Safety Precautions... 4 1. Package Contents... 5 2. Hardware Installation Guide... 6 2.1. Hard Disk Installation...
More informationHARDWARE GUIDE. Water Loop Controller C1000 Series. Specifications and Operational Guide
HARDWARE GUIDE Water Loop Controller C1000 Series Specifications and Operational Guide www.proloncontrols.com info@proloncontrols.com 17 510, rue Charles, Suite 100, Mirabel, QC, J7J 1X9 REV. 6.1.6 PL-HRDW-WLC-C1000-C/F-EN
More informationDatasheet. ECB-203 Series. 1/6. BACnet B-ASC 14-Point Programmable Controllers. Overview
Datasheet ECB-203 Series BACnet B-ASC 14-Point Programmable Controllers Overview Applications Meets the requirements of the following applications: Rooftop Units Fan Coil Units Chilled Ceilings Heat Pumps
More informationCDD4 Duct Carbon Dioxide Transmitter
Drill or punch a 1-1/8 or 1-1/4 hole in the duct at the preferred location and insert the probe into the hole to mark the enclosure mounting holes. Remove the unit and drill the four mounting holes. Clean
More informationClipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems
Clipsal Bus Couplers Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Instruction Bulletin Retain for future use. Clipsal Bus Couplers 63249-420-236A2 Instruction
More informationAX3000 Platine Terminal Ethernet TCP/IP
AX3000 Platine Terminal Ethernet TCP/IP Model 80WMS Installation Guide January 2012 - Ref: I80ME0922-2 Model AX3000/M80M Type EA The reproduction of this material, in part or whole, is strictly prohibited.
More informationUSB Raven Port USB 3.1, 100m CAT 6a/7 Point-to-Point Extender System User Guide
USB 3-2-1 Raven 3104 4-Port USB 3.1, 100m CAT 6a/7 Point-to-Point Extender System User Guide Thank you for purchasing the USB 3-2-1 Raven 3104. Please read this guide thoroughly. This document applies
More informationRMB Peripheral Units Installation Guide
RMB Peripheral Units Installation Guide Part Number 65-000101 2011 by Kentrox, Inc. All rights reserved. Copyright 2011 by Kentrox, Inc. All Rights Reserved. The material discussed in this publication
More informationDatasheet. ECB-300 Series. 1/6. BACnet B-AAC 18-Point Programmable Controllers. Overview
Datasheet ECB-300 Series BACnet B-AAC 18-Point Programmable Controllers Overview Applications Meets the requirements of the following applications: Air Handling Units Chillers Boilers Cooling Towers Heat-Exchangers
More informationCardax Prox Plus Mifare Reader
Installation Note Cardax Prox Plus Mifare Reader CAUTION This equipment contains components that can be damaged by electrostatic discharge. Ensure both you and the equipment are earthed before beginning
More informationHES-3109 SERIES 9 PORTS 10/100/1000BASE-T MANAGEMENT ETHERNET SWITCH
HES-3109 SERIES 9 PORTS 10/100/1000BASE-T MANAGEMENT ETHERNET SWITCH 8 PORTS 10/100/1000BASE-T MANAGEMENT ETHERNET SWITCH WITH 1 PORT 1000BASE-X UPLINK OR 1 PORT 100/1000BASE-X UPLINK 8 PORTS 10/100/1000BASE-T
More informationBAC-9000 Series VAV Controller Installation Guide
BAC-9000 Series VAV Controller Installation Guide CONTENTS Introduction... 1 Set Drive Hub (45/60 ) Rotation Limit... 1 Mount Controller... 2 Connect Sensors and Equipment... 3 Connect (Optional) Pressure
More informationDS A 10/99 MN 500 I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION SPECIFICATION
DS 10.103A 10/99 MN 500 WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION Order Type: MNN-50-100 MicroNet NCP 500 Controller I/A Series MicroNet 500 Series Controllers
More informationAX3000 Platine Terminal Ethernet TCP/IP
AX3000 Platine Terminal Ethernet TCP/IP Model 80 Installation Guide January 2012 - Ref: I80E0922-2 Model AX3000/M80 Type EA The reproduction of this material, in part or whole, is strictly prohibited.
More information1101 Universal Transmitter
INSTALLATION SHEET 1101 Universal Description The 1101 is a two input transmitter that is typically used for door/window applications. The 1101 provides two internal magnetic reed switches and an on-board
More informationLNP series. 5-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 1*10/100Tx, 12~36VDC Input.
LNP-0500-24 series 5-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 1*10/100Tx, 12~36VDC Input User Manual FCC Warning This Equipment has been tested and found to comply with
More informationDS A MN LCD I/A SERIES MICRONET LCD APPLICATION SPECIFICATION
DS 10.060A 10/01 TM MN LCD WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET LCD APPLICATION Order Types: MN-LCD-100 - MicroNet LCD - Controller or Wall Mount MNN-LCDP-100 - MicroNet LCD - Panel
More informationQuick Installation Guide
Quick Installation Guide For Network Attached Storage Ver.1.1.0.0320 Table of Contents Notices... 3 Safety Precautions... 4 1. Package Contents... 5 2. Hardware Installation Guide... 6 2.1. Hard Disk Installation...
More informationInnoMedia ipbx-400. Quick Install Guide.
InnoMedia ipbx-400 Quick Install Guide www.innomedia.com Table of Contents Introduction 2 Package Contents 2 Installation 3 Wall-Mounting Instructions 5 Troubleshooting 6 Appendix A. LED Status Summary
More informationLantech. IPGS-0005T /100/1000T PoE at T Industrial Unmanaged Switch. User Manual
Lantech IPGS-0005T-4 4 10/100/1000T PoE at + 1 1000T Industrial Unmanaged Switch User Manual V1.00 Jan-2018 Content Overview... 1 Introduction... 1 Features / Model List... 2 Packing List... 3 Safety Precaution...
More informationAllure EC-Smart-Comfort Series
Datasheet Allure EC-Smart-Comfort Series Communicating sensors with Smart-Light and Smart-Blind add-on modules Overview Features & Benefits The Allure EC-Smart-Comfort Series are versatile communicating
More informationUSB 2.0 RG2304 Network Series
USB 2.0 RG2304 Network Series 4-Port USB 2.0 Gigabit Ethernet LAN Extender Systems User Guide Thank you for purchasing the USB 2.0 RG2304N, 2304S or 2304GE-LAN. Please read this guide thoroughly. This
More information4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT
4 10/100/1000T + 2 1000 Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch User Manual V1.0 September-2013 FCC Warning This Equipment has been tested and found to comply with
More informationLN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note
LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note LN-IOE400-0, LN-IOE410-0, LN-IOE420-0, LN-VAVCF-12, LN-PRGxxx-12
More informationECL-VAV LONMARK Certified VAV Controller
D a t a s h e e t ECL-VAV LONMARK Certified VAV Controller Overview The ECL-VAV Series controllers are microprocessor-based programmable variable air volume (VAV) controllers designed to control any variable
More informationDESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications
3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for
More informationAllure EC-Smart-Comfort Series
Datasheet Allure EC-Smart-Comfort Series Communicating sensors with Smart-Light and Smart-Blind add-on modules Overview The Allure EC-Smart-Comfort series are versatile communicating sensor which provide
More informationLX-Display. Installation Instructions LX-DSWSC1-0, LX-DSWSC2-0. Mounting. Applications. North American Emissions Compliance
LX-Display Installation Instructions LX-DSWSC1-0, LX-DSWSC2-0 Code No. LIT-12011572 Issued April 28, 2014 Supersedes August 6, 2009 Applications The LX-Display controllers have multifunction Liquid Crystal
More informationRXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications
s 3 856 Desigo RXC Room controller RXC39.5 Communicating room controller for fan-coil applications The RXC39.5 room controller is used for temperature control in individual rooms. For fan-coil systems
More informationManual. Network Expansion Port 2 NEP-2. English. Brands by Navico - Leader in Marine Electronics
Manual Network Expansion Port 2 NEP-2 English www.lowrance.com www.simrad-yachting.com Brands by Navico - Leader in Marine Electronics Disclaimer As Navico is continuously improving this product, we retain
More informationQuick Installation Guide
Quick Installation Guide Applicable Models: AS6004U Ver.3.0.0 (2017-4-13) Table of Contents Notices... 3 Safety Precautions... 4 1. Package Contents... 5 2. Optional Accessories... 6 3. Hardware Installation
More informationMC 11 EB-2 Power supply cabinet with external bus, AC version
MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures
More informationBA/BS4S Temperature Sensor Installation & Operating Instructions
Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.
More informationLNP-0602 series. 6-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 2*100Fx. User Manual
LNP-0602 series 6-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 2*100Fx User Manual FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A
More informationLantech. IPGS-0204DSFP 4 10/100/1000T PoE at/af + 2 Dual Speed SFP Industrial Unmanaged Switch
Lantech IPGS-0204DSFP 4 10/100/1000T PoE at/af + 2 Dual Speed SFP Industrial Unmanaged Switch IGS-0204DSFP 4 10/100/1000T + 2 Dual Speed SFP Industrial Unmanaged Switch User Manual V1.00 Jul-2016 Content
More informationEasyIO FW 08VUser Reference
EasyIO FW 08VUser Reference 1 Document Change Log 26 th Dec 2016 Document created. 2 Disclaimer EasyIO FW 08V is a product by EasyIO Holdings Pte Ltd The EasyIO FW 08V was built on the Sedona Framework.
More informationMARQUE: TP-LINK REFERENCE: TPL_TLSF1016D CODIC:
MARQUE: TP-LINK REFERENCE: TPL_TLSF1016D CODIC: 4076656 TL-SF1005D TL-SF1008D TL-SF1016D 10/100Mbps Desktop Switch REV: 1.0.0 1910010004 COPYRIGHT & TRADEMARKS Specifications are subject to change without
More information6 10/100/1000TX + 2G Fiber Industrial Ethernet Switch User Manual
6 10/100/1000TX + 2G Fiber Industrial Ethernet Switch User Manual FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital device, pursuant to Part 15 of the
More informationFRG-3105 Series Residential Gateway
FRG-3105 Series Residential Gateway User s Guide Version 0.90 Revision History Version Date Description 0.90 20170605 First Release 2 Trademarks Contents are subject to revision without prior notice. All
More informationHypercable injecteur HPOE - Industrial IEEE 802.3at Gigabit PoE Injector. User Manual. v.1.0 Jun Mail :
Industrial IEEE 802.3at Gigabit PoE Injector User Manual v.1.0 Jun-2011 FCC Warning This Equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15
More informationHES-3106-PLUS SERIES
HES-3106-PLUS SERIES 5 PORTS 10/100/1000BASE-T ETHERNET MANAGED SWITCH WITH 1 PORT 1000BASE-X or 100/1000BASE-X UPLINK User s Guide Version 0.92 Trademarks CTS is a registered trademark of Connection Technology
More informationChoose from four different ways to power these hardened media converters.
LIC022A-R2 LIC026A-R2 LIC054A-R2 LIC023A-R2 LIC027A-R2 LIC055A-R2 LIC024A-R2 LIC052A-R2 LIC056A-R2 LIC025A-R2 LIC053A-R2 LIC057A-R2 MultiPower Industrial Media Converters Choose from four different ways
More information