1 TECHNICAL SPECIAL PROVISION FOR SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM (SCADA) FINANCIAL PROJECT NO.: MARION COUNTY The official record of this Technical Special Provision is the electronic file signed and sealed under rule 61G , F.A.C. PREPARED BY: Robert Mastascusa, P.E Fla. License No Certificate of Authorization No Metric Engineering 615 Crescent Executive Court Suite 524 Lake Mary, Florida Date: 03/31/2015 Page 1 of 7

2 T SUPERVISORY CONTROL AND DATA ACQUISITION (SCADA) SYSTEM T Description. Furnish and install Supervisory Control and Data Acquisition (SCADA) in accordance with the Contract Documents. The SCADA Control Panel will use IEEE 802.3u, 100 Mbps, Fast Ethernet protocol to communicate with the Department s Ethernet network. Voltage/Current Analog sensors, monitors, and position indicating contacts will be installed to provide inputs to the SCADA system. The remote sensors, monitors and components will be connected to the SCADA system with power and communication cables labeled and stored neatly in raceways to form a complete system. Some equipment, such as cabinet door switches, will send information indirectly to the SCADA system. A technician from the Department will load the final programming at the primary SCADA control panel necessary for final acceptance and commissioning tests. T Materials. Furnish all labor and materials necessary to provide, install, and test a Supervisory Control and Data Acquisition (SCADA) System in each local hub cabinet and master hub building. Refer to the Supervisory Control and Data Acquisition Details in the ITS Plans. A SCADA system to monitor various parameters and conditions associated with the ITS equipment and electrical distribution system to be installed at each location will include at a minimum but not be limited to the following components listed in Table 1: Table 1 QUANTITY PART NUMBER DESCRIPTION 1 OTB1E0DM9LP TCP/IP Network Interface Module 1 TM2AMM6HT Analog Expansion (Analog 4 In, 2 Out) 2 H921 Veris Current Sensor (4-20mA output) 2 RMCV60BD Voltage/Current Analog Converter 6 RXZE2S108M Relay Socket (Spares to be provided to Department) 6 RXM2AB2BD 24 VDC Relay rated for 12 A / 250 VAC All ancillary items required for a fully operational SCADA system including but not limited to connectors, wires (colored per plans), wireway (cable management ducts), VDC terminal block, Grounding terminal block, fuse block, fuse(s) as required. Page 2 of 7

3 Provide a SCADA power supply Module (Sola SDN C or Equivalent). The SCADA power supply module shall include a 24 VDC power supply module to power SCADA system components as well as other DC powered ITS devices per plans, and shall have the following specifications: Input voltage range of VAC, Output voltage of 24 VDC (23.5 VDC Min. to 28.5 VDC Max.), Operating Temperature range of -25 Celsius to +60 Celsius, Weight of 1.1 pounds or less, Din Rail mountable (Din Rail included), Internally fused, and a 5-Year limited Warranty. T Component Input/Output Parameters. T Analog Inputs. The SCADA system shall be capable of receiving up to four Analog Inputs At all local hub cabinet installations, the incoming utility power voltage and current will be monitored between the primary surge protection device and the UPS, by a RMCV60BD Voltage/Current Analog Converter and a H921 Veris Current Sensor (4-20mA output). At all local hub cabinet installations, the UPS output power voltage and current will be monitored between after the UPS, by a RMCV60BD Voltage/Current Analog Converter and a H921 Veris Current Sensor (4-20mA output). T Digital Inputs. The SCADA system shall be capable of receiving up to twelve Digital Inputs. The door positions on the local hub cabinet doors (front and back) will be monitored by door position dry contact tamper switches. The door tamper switches contacts will be open when the door(s) are open and closed when the door(s) are closed. The position of the UPS external maintenance bypass switch will be monitored using factory installed dry contacts to indicate the switch position. The alarm contact on the surge suppression devices at each local hub cabinet shall be monitored by the SCADA system. T Digital Outputs. The SCADA system shall be capable of sending up to eight Digital Outputs. Digital Outputs shall be wired to the Relay Sockets to be installed for the CCTV Power, Device Server power, MVDS power, and Media Converter power. T Power Input/Outputs. The SCADA system will utilize the 120 VAC power circuit powering the local hub cabinet and all of its components. This 120 VAC circuit will feed the 24 VDC power converter which will feed the SCADA devices as required. T Environmental Specifications. T Ambient Temperature. The SCADA system shall have a minimum operating temperature range of 0 C to +60 C and a storage temperature of 0 C to +60 C. Page 3 of 7

4 T Relative Humidity. The SCADA system shall have a minimum operating relative humidity range of 10 to 95% non-condensing, and a storage temperature of 10 to 95% noncondensing. T Shop Drawings. Shop drawings shall be submitted for the SCADA system. The SCADA system shop drawings shall include hardware product information including, but not be limited to catalog cut sheets, data sheets, performance surveys, test reports, equipment lists, material list, diagrams, pictures, and descriptive material. The product information shall cover all items including mechanical devices, mounting components, wiring, terminal strips, connectors, accessories, and spare parts. The submittal information shall show the standard and optional product features, as well as all performance data and specifications. Prior to commencement of manufacture (or shipment for stock items), the SCADA System Provider shall submit for review product information for all equipment and material specified in this Section. Include specification sheets on each remote sensor, power meter, or interface card that will communicate or provide status to the SCADA system. T Quality Assurance. The SCADA Control Panel Integrator minimum qualifications include a minimum of ten years of experience in the design, manufacture, testing, or installation of solidstate PLC systems. Before shipment, the manufacturer fully and completely tests the system to assure compliance with the specifications. T Product and Product Fabrication. Products submitted other than listed part numbers are the responsibility of the contractor for system integration and revised PLC programming to make any substitute product integrate into the SCADA system. All materials and components making up the SCADA system will be new, of current design, and not in prior service except as required during factory testing. The SCADA system will be constructed of replaceable subassemblies. Products submitted other than listed part numbers are the responsibility of the contractor for system integration and revised PLC programming to make any substitute product integrate into the SCADA system. T Wiring. Wiring practices, materials, and coding will be in accordance with the requirements of the National Electrical Code (NFPA 70) and the National Electrical Page 4 of 7

5 Manufacturer Association. Cables with shields and/or drain wires will have the shield and/or drain wire grounded at the SCADA control panel end only. Each cable or conductor installed for the SCADA system will be field labeled at both ends of the cable or conductor. Labels will be installed within 6 inches of the ends of each cable or conductor. Ensure the labels are self-laminating and the label material is vinyl with white matte finish and black 12 point text that is heat and solvent resistant. Contact the TSM&O Engineering Department for wire naming conventions and label syntax. Wiring inside the SCADA control cabinet will be routed through proposed cable management ducts. The white wiring ducts will have removable covers. The wiring duct will be equal to Panduit, Type G wide finger wiring duct. T Location. The SCADA system shall be installed with the local hub or master hub as detailed in the ITS plans. T Network Connection. The SCADA system shall be connected to the Local Hub Ethernet Switch or the Master Hub Ethernet Switch. The Ethernet switches are to be paid for separately. T Contractor Field Services and Department Provided Services. T Contractor Provided Field Services. The contractor shall install, inspect, and test the SCADA installation before notifying the Department that the SCADA system is ready to be programmed. All inspections and test procedures shall be performed by trained field service personnel during the SCADA system start-up and commissioning. Visually inspect the installation to ensure the equipment shows no signs of shipping or installation damage. Visually verify the completed installation has been installed per the plans and detail drawings. Visually inspect the installation to ensure that all I/O modules are correctly fitted, all power supply modules are correctly fitted, and all terminal screws, nuts, and/or spade lugs for tightness. Mechanical Inspections shall include the verification that all I/O modules are correctly fitted, all power supply modules are correctly fitted, and all terminal screws, nuts, and/or spade lugs for tightness. Electrical Inspections shall include the verification that SCADA system control panel is energized at each local hub, and that the input and output voltages for all SCADA system related components are within tolerance. Confirm the Remote I/O is connected to the local area network. Confirm each remote sensor, meter, and interface card is functioning correctly. Page 5 of 7

6 T Department Provided Services. The Department will provide and install the back end SCADA hardware to be installed at the Traffic Management Center and the software program for the SCADA system PLC. Upon Contractor completion of all Contractor required field services in this section, notify the Department 4 weeks prior to proposed testing date, which includes 14 days for the Department to install and test the PLC program. T Replacement Part Stocking and Availability. Replacement parts shall be available through a local distributor within 100 miles of the job site. All SCADA parts and materials will be available 24 hours a day, 7 days a week, 365 days a year from a local distributor. Include the local distributors name on the shop drawings. T Test and Performance Verification. The completed SCADA system will be operationally tested in accordance with the following requirements. Verify capability to remotely power off all ITS devices connected to Relay each Socket. Verify capability to remotely power on all ITS devices connected to Relay Sockets. Verify receipt of accurate current readings from both Analog Current Sensors. Verify receipt of accurate voltage readings from both Analog Voltage Sensors. Verify digital inputs trigger alarms when Front Door Opens, Rear Door Opens, UPS set to bypass, and Surge Protection Device (SPD) trips. T Warranty. The manufacturer will warranty all components against defects in materials and workmanship for five years from the date of final acceptance by the Engineer. The warranty will cover all parts and onsite labor required for troubleshooting and repair. Contractor hereby assigns to the Department any and all manufacturers' or other sellers' warranties that come with any products, material or supplies which are incorporated into or are consumed in the project in any way. To the extent that any such warranties do not extend to subsequent purchasers or owners or such warranties contain a limitation on assignment, Contractor agrees that Contractor purchased the products, materials and supplies on behalf of the Department with the intent that the Department be the intended recipient of any warranties. All documents associated with or describing any such warranties shall be delivered to the Department along with the other project final acceptance documents and shall be deemed to be a part of the required final acceptance documentation. Contractor shall not take any action or fail to act in any way which voids any such warranties. All subcontracts shall contain a similar provision which requires subcontractors to assign any such warranties to the Department. Page 6 of 7

7 T Method of Measurement. The Contract unit price for each SCADA system furnished and installed, will include furnishing, placement, and testing of all equipment and materials, and for all tools, labor, hardware, supplies, support, personnel training, shop drawings, documentation, and incidentals necessary to complete the work. T Basis of Payment. Price and payment will be full compensation for all work specified in this Technical Special Provision. Payment will be made under: Item No SCADA System-assembly. Page 7 of 7

Master Hub Ethernet Switch (MHES)

Master Hub Ethernet Switch (MHES) TECHNICAL SPECIAL PROVISION FOR Master Hub Ethernet Switch (MHES) FINANCIAL PROJECT NO.: 428213-2-52-02 MARION COUNTY The official record of this Technical Special Provision is the electronic file signed

More information

TECHNICAL SPECIAL PROVISION FOR. ITS Automatic Vehicle Identification System (AVI): Financial Project ID:

TECHNICAL SPECIAL PROVISION FOR. ITS Automatic Vehicle Identification System (AVI): Financial Project ID: TECHNICAL SPECIAL PROVISION FOR ITS Automatic Vehicle Identification System (AVI): Financial Project ID: 435443-2-52-01 ORANGE COUNTY & SEMINOLE COUNTY The official record of this Technical Special Provision

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL LoadTrack LTL Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA TEL: 800-647-1911 www.tpssurge.com LOADTRACK LTL INSTALLATION, OPERATION AND

More information

SECTION SURGE PROTECTIVE DEVICES

SECTION SURGE PROTECTIVE DEVICES SECTION 16289 PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) SECTION 26 29 23 VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) PART 1 -GENERAL 1.1 SYSTEM DESCRIPTION A. Definitions: The Variable Speed AC Motor Drive (hereafter referred to as "VFD") shall be designed to

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM ITS:CLC 1 of 6 APPR:LWB:DBP:07-31-13 FHWA:APPR:09-23-13 a. Description. This work consists of one or more

More information

E1 Plus Electronic Overload Relay

E1 Plus Electronic Overload Relay ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION E1 Plus NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific installations

More information

4300 WINDFERN RD #100 - HOUSTON TX VOICE (713) FAX (713) web: IMPORTANT!!!

4300 WINDFERN RD #100 - HOUSTON TX VOICE (713) FAX (713) web:   IMPORTANT!!! 4300 WINDFERN RD #100 - HOUSTON TX 77041-8943 VOICE (713) 973-6905 - FAX (713) 973-9352 web: www.twrlighting.com IMPORTANT!!! PLEASE TAKE THE TIME TO FILL OUT THIS FORM COMPLETELY. FILE IT IN A SAFE PLACE.

More information

ITS DEVICE INTEGRATION AND TESTING

ITS DEVICE INTEGRATION AND TESTING TECHNICAL SPECIAL PROVISION FOR ITS DEVICE INTEGRATION AND TESTING FINANCIAL PROJECT NO.: 428213-2-52-02 MARION COUNTY The official record of this Technical Special Provision is the electronic file signed

More information

4300 WINDFERN RD #100 HOUSTON TX VOICE (713) FAX (713) web: IMPORTANT!!!

4300 WINDFERN RD #100 HOUSTON TX VOICE (713) FAX (713) web:   IMPORTANT!!! 4300 WINDFERN RD #100 HOUSTON TX 77041-8943 VOICE (713) 973-6905 FAX (713) 973-9352 web: www.twrlighting.com IMPORTANT!!! PLEASE TAKE THE TIME TO FILL OUT THIS FORM COMPLETELY. FILE IT IN A SAFE PLACE.

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM ITS:CLC 1 of 5 APPR:JVG:DBP:06-29-17 FHWA:APPR:08-02-17 a. Description. This work consists of one or more

More information

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285. SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed

More information

SPECIAL SPECIFICATION 8939 Retrofit Existing Fiber Optic Dynamic Message Sign System to LED

SPECIAL SPECIFICATION 8939 Retrofit Existing Fiber Optic Dynamic Message Sign System to LED 2004 Specifications CSJ 0025-02-194, 0017-10-261, 0017-10-268 & 0017-10-271 SPECIAL SPECIFICATION 8939 Retrofit Existing Fiber Optic Dynamic Message Sign System to LED 1. Description. Retrofit existing

More information

SPECIAL SPECIFICATION 6230 Fiber Optic RS-232 Data Modem

SPECIAL SPECIFICATION 6230 Fiber Optic RS-232 Data Modem 2004 Specifications CSJ 0924-06-258 SPECIAL SPECIFICATION 6230 Fiber Optic RS-232 Data Modem 1. Description. This Item shall govern for the furnishing and installation of Fiber Optic RS- 232 Data Modem

More information

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor Aluminum-detecting Proximity Sensor EEY CSM_EEY_DS_E_5_1 A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Non-ferrous metals, such as aluminum and brass, are detected.

More information

SPECIAL SPECIFICATION 8143 Wireless Ethernet Radio System

SPECIAL SPECIFICATION 8143 Wireless Ethernet Radio System 2004 Specifications CSJ 0002-01-080 SPECIAL SPECIFICATION 8143 Wireless Ethernet Radio System 1. Description. Furnish and install Wireless Ethernet Radio System (WERS) links for pointto-point applications,

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

SPECIAL SPECIFICATION 6518 IP Video Codec

SPECIAL SPECIFICATION 6518 IP Video Codec 2004 Specifications CSJ 0922-33-098 SPECIAL SPECIFICATION 6518 IP Video Codec 1. Description. A. This Item governs the furnishing and installation of IP Video Codec in field location(s) as shown on the

More information

ITS DEVICE INTEGRATION AND TESTING

ITS DEVICE INTEGRATION AND TESTING TECHNICAL SPECIAL PROVISION FOR ITS DEVICE INTEGRATION AND TESTING FINANCIAL PROJECT NO.: 435443-2-52-01 ORANGE COUNTY & SEMINOLE COUNTY The official record of this Technical Special Provision has been

More information

SECTION ( ) LIGHTING CONTROL PANELBOARD

SECTION ( ) LIGHTING CONTROL PANELBOARD (26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting

More information

TECHNICAL SPECIAL PROVISION FOR. Network Devices: Financial Project ID: ORANGE COUNTY & SEMINOLE COUNTY

TECHNICAL SPECIAL PROVISION FOR. Network Devices: Financial Project ID: ORANGE COUNTY & SEMINOLE COUNTY TECHNICAL SPECIAL PROVISION FOR Network Devices: Financial Project ID: 435443-2-52-01 ORANGE COUNTY & SEMINOLE COUNTY The official record of this Technical Special Provision has been electronically signed

More information

PIMA COUNTY REGIONAL WASTEWATER RECLAMATION DEPARTMENT SCADA STANDARDIZATION PROJECT TABLE OF CONTENTS

PIMA COUNTY REGIONAL WASTEWATER RECLAMATION DEPARTMENT SCADA STANDARDIZATION PROJECT TABLE OF CONTENTS PIMA COUNTY REGIONAL WASTEWATER RECLAMATION DEPARTMENT SCADA STANDARDIZATION PROJECT TABLE OF CONTENTS Section Page DIVISION 13 - SPECIAL CONSTRUCTION 13401 SCADA System, General Requirements... 13401-1

More information

X-12s Users Manual. X-12s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc.

X-12s Users Manual. X-12s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc. X-12s User Manual Revisions Revision Description 1.0 Page 2 Initial release Introduction Section 1: Introduction The X-12s 8-Relay expansion module is used with the X-600M controller. The X-12s has eight

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

Connecting a Cisco Output Module

Connecting a Cisco Output Module CHAPTER 5 Overview The optional Cisco Output Module (Figure 5-1) is attached to a Cisco Physical Access Gateway or Cisco Reader Module to provide additional connections for up to 8 outputs, each of which

More information

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free Instruction Manual Model 1582-45L Data Switch September 2010, Rev A REMOTE LOCAL SWITCH STATUS SELECT REMOTE LOCAL LOCAL SELECT CHANNEL SELECT POWER MODEL 1582 SWITCH CROSS TECHNOLOGIES, INC. Data, drawings,

More information

*REQUIRED* 169 Main Street 700 Plaza Middlesex Middletown, CT T: F:

*REQUIRED* 169 Main Street 700 Plaza Middlesex Middletown, CT T: F: ADDENDUM COVER & RECEIPT CONFIRMATION SHEET 169 Main Street 700 Plaza Middlesex Middletown, CT 06457 T: 860-343-8297 F: 860-343-9504 www.wright-pierce.com DATE: 9/6/16 ADDENDUM CONSISTS OF (Including this

More information

Total Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400

Total Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400 Total Protection Solutions SurgeTrack Series: 080, 120, 160, 240, 300 and 400 Surge Protective Devices Installation, Operation and Maintenance Manual SURGETRACK INSTALLATION, OPERATION AND MAINTENANCE

More information

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4. Flat Proximity Sensor EK-F CSM_EK-F_DS_E Flat Capacitive Sensor with a Thickness of Only mm Flat Sensor with excellent space efficiency. (Model with built-in Amplifier is only mm thick.) Direct mounting

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1993 Specifications CSJ s 0924-06-221,etc. & 0924-06-223 SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1. Description. This specification describes the minimum acceptable requirements for a weatherproof

More information

SECTION MODEL 2577 INDOOR SCOREBOARD. A. Single-face electronic scoreboard and control console for indoor use.

SECTION MODEL 2577 INDOOR SCOREBOARD. A. Single-face electronic scoreboard and control console for indoor use. SECTION 116643 MODEL 2577 INDOOR SCOREBOARD PART 1 GENERAL 1.01 SECTION INCLUDES A. Single-face electronic scoreboard and control console for indoor use. 1.02 REFERENCES A. Standard for Electric Signs,

More information

SVP110 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL

SVP110 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL SVP110 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL REVISION: 01/03/03 COPYRIGHT (c) 1995-2000 CAMPBELL SCIENTIFIC, INC. This is a blank page. WARRANTY AND ASSISTANCE The SVP110 SURGE VOLTAGE PROTECTOR is

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION PROGRAMMABLE LOGIC CONTROLLER (PLC)

SECTION PROGRAMMABLE LOGIC CONTROLLER (PLC) SECTION 13450 PROGRAMMABLE LOGIC CONTROLLER (PLC) PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the requirements for the Programmable Logic Controller (PLC) and PLC spare parts and tools. The

More information

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP. DIVERSIFIED HEAT TRANSFER SERIES 700 STEAM GENERATOR CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE AT SIGMACONTROLS.COM SERIES 700 DHT STEAM GENERATOR MANUAL 042514 2 TABLE OF CONTENTS INTRODUCTION.

More information

SPECIAL SPECIFICATION 6322 Digital Video Encoder/Decoder (Ethernet) System

SPECIAL SPECIFICATION 6322 Digital Video Encoder/Decoder (Ethernet) System 2004 Specifications CSJ 0902-48-433 SPECIAL SPECIFICATION 6322 Digital Video Encoder/Decoder (Ethernet) System 1. Description. Furnish and install Digital Video Encoder/Decoder (Ethernet) System (DVE/DES)

More information

Power Meter PowerMonitor 500

Power Meter PowerMonitor 500 ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION PowerMonitor 500 NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific

More information

IF-80x Outdoor Terminal

IF-80x Outdoor Terminal 95-10330_IF-800 V2016-10-20 Outdoor Terminal IF-80x Outdoor Terminal 1 IF-800 Outdoor / IF-801 We are pleased that you have decided to use a terminal of the IF-80x series for recording access data. Scope

More information

E2KQ-X. Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster. Chemical-resistant Proximity Sensor. Ordering Information

E2KQ-X. Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster. Chemical-resistant Proximity Sensor. Ordering Information Chemical-resistant Proximity Sensor E2KQ-X CSM_E2KQ-X_DS_E_4_3 Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster Excellent resistance against chemicals and oil with fluororesincoated case.

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 Display: EZ100 11/12/04-1 - Congratulations on your purchase of the EZ100 Display.

More information

SECTION MODEL INDOOR SCOREBOARD. A. Four-face electronic scoreboard and control console for indoor use.

SECTION MODEL INDOOR SCOREBOARD. A. Four-face electronic scoreboard and control console for indoor use. SECTION 116643 MODEL 2650-4 INDOOR SCOREBOARD PART 1 GENERAL 1.01 SECTION INCLUDES A. Four-face electronic scoreboard and control console for indoor use. 1.02 REFERENCES A. Standard for Electric Signs,

More information

Sensing method Appearance Connection method Sensing distance Model. Pre-wired (2 m) Power supply Application Appearance Function Model

Sensing method Appearance Connection method Sensing distance Model. Pre-wired (2 m) Power supply Application Appearance Function Model Small Spot/Mark (Separate Amplifier) EC-VS/VM CSM_EC-VS/VM_DS_E_6_ Extremely thin beam ideal for detection of minute objects and marks Ideal for detection of small objects and slight color differences

More information

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007 RE-82 RACK MOUNT DIMMER 8 X 2400Watts OWNERS MANUAL Revision 2.4 11/29/2007 Page 2 of 8 RE-82 CONTROL PANEL DESCRIPTION The RE-82 is an 8 channel dimmer with a maximum capacity of 2,400 watts per channel

More information

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating

More information

G3B/G3BD. Model Number Structure. Ordering Information. Solid State Relays Model Number Legend. List of Models

G3B/G3BD. Model Number Structure. Ordering Information. Solid State Relays Model Number Legend. List of Models Solid State Relays G3@-VD CSM_G3B_G3BD_DS_E_5_1 International Standards for G3B Series, Same Profile as MK Power Relays Shape-compatible with mechanical relays. Certified by UL, CSA, and VDE (models numbers

More information

SECTION VARIABLE FREQUENCY DRIVES

SECTION VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 DESCRIPTION This specification section establishes the requirements for variable frequency motor drives. The associated motor(s) shall be specified separate from the drive and listed

More information

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel I/O Relay CSM DS_E_4_4 Slim-styled I/O Relay Saves Space in Panel SPST-NO, SPST-NC, and SPDT contact forms available for output (SPST-NO only for input). Ultra-slim housing measuring 29 (W) x 0 (D) x 2

More information

The Next-generation Sensor Networking Units That Revolutionize the Workplace from Introduction and Startup though Operation. Fiber Units.

The Next-generation Sensor Networking Units That Revolutionize the Workplace from Introduction and Startup though Operation. Fiber Units. Sensor Communications Unit CSM DS_E_1_1 The Next-generation Sensor Networking Units That Revolutionize the Workplace from Introduction and Startup though Operation Low initial cost achieved by distributed

More information

Power Supply (48Vdc, 2.5A)

Power Supply (48Vdc, 2.5A) Telecommunications Group Section 855-180-201 Equipment Issue 1 Fourth Printing, September 2006 8551-80 Power Supply (48Vdc, 2.5A) Compliant with UL Standard 60950, Second Edition* CONTENTS PAGE Part 1.

More information

LCI User Manual mantracourt.com

LCI User Manual mantracourt.com LCI User Manual mantracourt.com LCI Load Cell Junction Box with Fault Monitor Contents Chapter 1 Introduction to the LCI... 2 Chapter 2 Installing the LCI... 3 Chapter 3 Setting up the LCI... 4 Sequence

More information

SPECIAL SPECIFICATION 8885 Wireless Ethernet Radio (Backhaul) Link

SPECIAL SPECIFICATION 8885 Wireless Ethernet Radio (Backhaul) Link 2004 Specifications CSJ 0016-06-046, etc. SPECIAL SPECIFICATION 8885 Wireless Ethernet Radio (Backhaul) Link 1. Description. Furnish and install Wireless Ethernet Radio (WER) (Backhaul) Link in the 5.8

More information

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment Installation Service Statement of Work Start-up Service for Cooling Start-up - 1 - Service for Cooling Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0

More information

SECTION FARE COLLECTION SYSTEM

SECTION FARE COLLECTION SYSTEM SECTION 17830 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for the Ticket Vending Machines (TVMs) and for the Clipper Network Card Interface Devices (CIDs) as a subsystem of the station

More information

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 Rev. A

More information

G3FM. Model Number Structure. Ordering Information. Solid State Relays. Model Number Legend. List of Models

G3FM. Model Number Structure. Ordering Information. Solid State Relays. Model Number Legend. List of Models Solid State Relays CSM DS_E_5_3 100-μA-max. Leakage Current, No Bleeder Resistor Required Reduces wiring work by 60% when combined with the PFY-08- PU Push-In Plus Socket (according to actual OMRON measurements).

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

LINCOLN AUTHORIZED SERVICE FACILITY (LASF) SERVICE CODE TERMS & CONDITIONS

LINCOLN AUTHORIZED SERVICE FACILITY (LASF) SERVICE CODE TERMS & CONDITIONS The Lincoln Electric Company 22801 St. Clair Avenue Cleveland, Ohio 44117-1199 LASF Contract Attachment Last revision: February, 2016 LINCOLN AUTHORIZED SERVICE FACILITY (LASF) SERVICE POLICY: CODE TERMS

More information

AirTest Model CN9000 Series Sensor Controller

AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller THEORY OF OPERATION A basic CN9000 configuration consists of Input/Process/Display combination modules, a 3 relay

More information

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M Chip-immune Inductive EEZ CSM_EEZ_DS_E_6_ Chip-immune Inductive Correct operation even with aluminum or iron chips sticking to the. Only the sensing object is detected. Pre-wired Smartclick Connector s

More information

Connecting a Cisco Input Module

Connecting a Cisco Input Module CHAPTER 4 Overview The optional Cisco Input Module (Figure 4-1) is attached to a Cisco Physical Access Gateway or Cisco Reader Module to provide additional connections for up to ten input devices. Each

More information

X-11s Users Manual. X-11s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc.

X-11s Users Manual. X-11s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc. X-11s User Manual Revisions Revision Description 1.0 Page 2 Initial release Introduction Section 1: Introduction The X-11s 2-relay expansion module is used in conjunction with the X-600M controller. The

More information

Basketball Shot Clock Set LX2180 Manual

Basketball Shot Clock Set LX2180 Manual Basketball Shot Clock Set LX2180 Manual 72 Industrial Boulevard Wrightsville, GA 31096 Phone: (800) 445-7843 Fax: (800) 864-0212 www.electro-mech.com LX2180 Revision 5 February 8, 2013 Table of Contents

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console 1993 Specifications CSJ 0598-01-057 1.0 Description SPECIAL SPECIFICATION ITEM 6398 Transportation Management Console This Item shall govern for the furnishing and installation of Transportation Management

More information

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 TABLE OF

More information

OZONE SWITCH Model OS-6. OS-6 Features

OZONE SWITCH Model OS-6. OS-6 Features USER MANUAL OZONE SWITCH Model OS-6 OS-6 Features The OS-6 is an industrial grade ozone controller and monitor. The OS-6 design is optimized for accuracy and ease of installation, setup and operation.

More information

SPECIAL SPECIFICATION 6146 Fiber Optic RS-232 Data Modem

SPECIAL SPECIFICATION 6146 Fiber Optic RS-232 Data Modem 2004 Specifications CSJ s 0508-07-027, 0177-06-064, 0271-04-067, 0389-13-049 SPECIAL SPECIFICATION 6146 Fiber Optic RS-232 Data Modem 1. Description. Furnish and install Fiber Optic RS-232 Data Modem (FO-MODEM)

More information

LCI Load Cell Junction Box with Fault Monitor

LCI Load Cell Junction Box with Fault Monitor LCI Load Cell Junction Box with Fault Monitor User Manual www.mantracourt.co.uk The LCI Load Cell Failure Alarm Manual Chapter 1 Introduction to the LCI...2 Chapter 2 Installing the LCI...3 Figure 2.1

More information

SPECIAL SPECIFICATION 7443 Radar Vehicle Sensing Device (RVSD) System Maintenance

SPECIAL SPECIFICATION 7443 Radar Vehicle Sensing Device (RVSD) System Maintenance 2004 Specifications CSJ 6185-04-001 SPECIAL SPECIFICATION 7443 Radar Vehicle Sensing Device (RVSD) System Maintenance 1. Description. Furnish, install, replace, or remove components of a Radar Vehicle

More information

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual 506 and 507 Relay Output Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

G3NE. Model Number Structure. Solid State Relays. Model Number Legend. Compact, Low-cost, SSR Switching 5 to 20 A

G3NE. Model Number Structure. Solid State Relays. Model Number Legend. Compact, Low-cost, SSR Switching 5 to 20 A Solid State Relays CSM DS_E_4_1 Compact, Low-cost, SSR Switching 5 to 20 A Wide load voltage range: 75 to 264 VAC. Both 100-V and 200-V loads can be handled with the same model. Dedicated, compact aluminum

More information

S82S (3/7.5-W Models)

S82S (3/7.5-W Models) Switch Mode Power Supply (3/7.5-W Models) CSM DS_E_4_3 Miniature DIN Rail Mounting DC-DC Power Supplies 65 mm depth enables mounting onto control panels with 100 mm depth. Inputs: 10.2 to 27.6 VDC (DC

More information

SAVE THESE INSTRUCTIONS

SAVE THESE INSTRUCTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION IMPORTANT SAFEGUARDS! When using electrical equipment, basic safety precautions should always be

More information

TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT

TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT 06045-0191 TRAFFIC SIGNAL INSTALLATIONS MIDDLE TURNPIKE EAST AT SUMMIT STREET MIDDLE TURNPIKE EAST AT

More information

Model Number Structure

Model Number Structure Digital Panel Meter CSM DS_E_3_1 Easy-to-use, w-cost Digital Panel Meter that Accepts DC Input Compact DIN-size (96 x 48 (W x H)) body. Mounting thickness of only 3.5 mm required. Highly visible display

More information

High Voltage DC Meter

High Voltage DC Meter High Voltage DC Meter Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

Aluminum Excellent Performance, with Aluminum Chip Immunity! The indicator is visible from any direction.

Aluminum Excellent Performance, with Aluminum Chip Immunity! The indicator is visible from any direction. All Metals and Long- Types CSM DS_E and Both Detectable from Long Distances times the aluminum detection of previous models Twice the max. Equipped with a function to prevent the detection of aluminum

More information

Name No. of I/O points Model Safety inputs: 12, test outputs: 4

Name No. of I/O points Model Safety inputs: 12, test outputs: 4 Safety I/O s DST1 Series CSM_DST1 Series_DS_E_7_3 Distributed Safety s That Reduce Wiring. Lineup includes four models to accommodate various I/O types and number of I/O points. Monitor the safety system

More information

SPECIAL SPECIFICATION 1303 Lifelink

SPECIAL SPECIFICATION 1303 Lifelink 1993 Specifications CSJ 0024-08-110 SPECIAL SPECIFICATION 1303 Lifelink 1. Description. This Item shall govern for the furnishing and installation of LifeLink equipment in Fiber Hubs (existing and proposed)

More information

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M Chip-immune Inductive EEZ CSM_EEZ_DS_E Chip-immune Inductive Correct operation even with aluminum or iron chips sticking to the. Only the sensing object is detected. Pre-wired Smartclick Connector s also

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1.1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481200 VGD-100 Vari-Green Drive Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

212iL Rev. 1.1

212iL Rev. 1.1 212iL 1 International Electronics, Inc. 427 Turnpike Street Canton, Massachusetts 02021 212iL (illuminated Luxury) Keypad Single Unit Keypad- Control Installation Manual Features: 120 User Capability Illuminated

More information

I/O Expansion Box Installation & Operator s Instruction Manual

I/O Expansion Box Installation & Operator s Instruction Manual I/O Expansion Box Installation & Operator s Instruction Manual May 2004 CTB Inc. Warranty I/O Expansion Box CTB Inc. Warranty CTB Inc. warrants each new Chore-Tronics product manufactured by it to be free

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

E3Z-G. Photoelectric Sensor with Grooved Design and Easy Settings. Grooved-type Photoelectric Sensor with Built-in Amplifier. Ordering Information

E3Z-G. Photoelectric Sensor with Grooved Design and Easy Settings. Grooved-type Photoelectric Sensor with Built-in Amplifier. Ordering Information Grooved-type with Built-in Amplifier EZ-G CSM_EZ-G_DS_E_9_ with Grooved Design and Easy Settings Groove-type with groove width of 5 mm. Models are available with one or two light axes. Models are available

More information

Solid State Relays with Failure Detection Function

Solid State Relays with Failure Detection Function Solid State Relays with Failure Detection Function CSM DS_E_2_1 Refer to Safety Precautions for All Solid State Relays. Detects failures in SSR used for heater temperature control and simultaneously outputs

More information

SPECIAL SPECIFICATION 6838 Wireless Ethernet Microwave Radio

SPECIAL SPECIFICATION 6838 Wireless Ethernet Microwave Radio 2004 Specifications CSJ 1068-02-124 SPECIAL SPECIFICATION 6838 Wireless Ethernet Microwave Radio 1. Description. Furnish and install Wireless Ethernet Microwave Radio (WEMR) as shown on the plans, as detailed

More information

Sync Control for Eaton 9395P and 93PM User s and Installation Guide

Sync Control for Eaton 9395P and 93PM User s and Installation Guide Sync Control for Eaton 9395P and 93PM IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the

More information

FBT-10. Fieldbus Commissioning Box. User Manual FBT-10 User Manual Rev A.0

FBT-10. Fieldbus Commissioning Box. User Manual FBT-10 User Manual Rev A.0 FBT-10 Fieldbus Commissioning Box User Manual www.relcominc.com 1 Relcom, Inc. 2221 Yew St. Forest Grove, OR 97116 USA Tel: (503) 357-5607 Fax: (503) 357-0491 www.relcominc.com Copyright Relcom, Inc. 2013

More information

E2EC. Subminiature Sensors with Long-distance Detection. Cable Amplifier Proximity Sensor. Ordering Information

E2EC. Subminiature Sensors with Long-distance Detection. Cable Amplifier Proximity Sensor. Ordering Information Cable Amplifier Proximity Sensor EEC CSM_EEC_DS_E_9_ Subminiature Sensors with Long-distance Detection Shielded Sensor Heads from -mm to M diameters that can be embedded in metal. Robotics cables provided

More information

SECTION MICROPROCESSORS

SECTION MICROPROCESSORS SECTION 13580 MICROPROCESSORS PART 1 GENERAL 1.01 DESCRIPTION A. The contractor shall furnish a MicroLok II Vital Microprocessor Based Interlocking System (VMIS) and Non-Vital Based Interlocking Systems

More information

CK3W-PD048 CSM_CK3W-PD048_DS_E_DITA_1_2

CK3W-PD048 CSM_CK3W-PD048_DS_E_DITA_1_2 CK3W Power Supply Unit CK3W-PD048 CSM_CK3W-PD048_DS_E_DITA_1_2 Supplies power to the CK3M Controller CK3W-PD048 Features 24 VDC input The power supply status indicator shows operating status 1 Ordering

More information

X-18s Users Manual. X-18s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc.

X-18s Users Manual. X-18s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc. X-18s User Manual Revisions Revision Description 1.0 Page 2 Initial release Introduction Section 1: Introduction The X-18s expansion module is used with the X-600M controller. The X-18s has ten, high-current

More information

HIGH-VOLTAGE DC METER

HIGH-VOLTAGE DC METER HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

MAXIMA+ Series Rotary Level Indicator

MAXIMA+ Series Rotary Level Indicator MAXIMA+ Series Rotary Level Indicator BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE

More information