DATA LOGGERS GL800 & 1000

Size: px
Start display at page:

Download "DATA LOGGERS GL800 & 1000"

Transcription

1 DATA LOGGERS GL800 & 1000 I N S T R U C T I O N M A N U A L

2 2

3 CONTENTS Page 1.0 INTRODUCTION General description Theory of operation Main components Multiplexer (Flexi-Mux) Flexi-Mux identification Flexi-Mux connections - overview Flexi-Mux reset Flexi-Mux clock Flexi-Mux earth/ground Modem Software Electro magnetic compatibility CONFORMITY MARKINGS DELIVERY Packaging Handling Inspection Storage INSTALLATION Getting started Wiring Mains power connection Battery power connection Solar power connection Sensor cable connections - braided cable Sensor cable connections - non braided cable Connecting logger to PC Typical Flexi-Mux wiring connections Flexi-Mux to a Vibrating Wire sensor Flexi-Mux to an In-Place Inclinometer- biaxial Flexi-Mux in parallel to switch 8 wires Modem Installing antenna Installing SIM card 31 3

4 CONTENTS contd... Page 6.0 DATA ACQUISITION SOFTWARE Introduction Resource discs Laptop/PC computer set up Establish connection to the Logger Downloading data Logger programs Retrieving a program from the logger Changing the scan interval Entering the calibration values Changing the excitation frequency for VW sensors Sending a program to the logger MAINTENANCE TROUBLESHOOTING SPECIFICATION SPARE PARTS RETURN OF GOODS LIMITED WARRANTY APPENDIX 63 4

5 1.0 INTRODUCTION This manual is intended for all users of the Geosense GeoLoggers 800/1000 data loggers and provides a guide for its installation, operation and maintenance. It is VITAL that personnel responsible for the installation and use of the GeoLogger 800/1000 READ and UNDERSTAND the manual, prior to working with the equipment. 1.1 General Description The Geosense GeoLogger 800/1000 is an automatic data logging system used typically within Geotechnical & Structural instrumentation for monitoring and logging of many types and numbers of sensors with output signals such as :- Frequency Voltage Current Resistance RS-485 BUS They are built around the Campbell Scientific CR800 and CR1000 control modules and their particular features are:- Reliable long term performance Rugged; suitable for demanding environments Proven technology & components Fully reprogrammable remotely & on site Real time monitoring possible Data can be accessed remotely Various power options including solar for remote locations The Geosense GeoLogger 800/1000 is pre-assembled and configured to suit individual project requirements and will come partly programmed in accordance with customers requirements. 1.2 Theory of Operation A wide range of sensors (digital or analogue) can be connected to a Geosense GeoLogger 800/1000 which controls the sampling interval times and the storage of the output signals onto the CPU. On-board software (LoggerNet) is used to program all the settings within the unit and the data can be downloaded either directly to a PC or remotely via GSM/GPRS. Explanation of all the main components is outlined in section

6 1.3 Main components - V W Sensors 1. Central processing unit (CPU) to which all the components are linked. CR800 or 1000 fully programmable controller with non-volatile memory and battery backed clock. 2. Interface Modules: Vibrating wire sensors require an additional interface (AVW200) which is connected between the CPU and the instrument.. 3. Multiplexers: A relay mechanism controlled by the CPU to switch between multiple sensors so that they can be monitored by a single CPU. Allows multi sensors to be fed into the measurement & control module Power Supplies: A power supply provides regulated power to the logger and sensors. 12 volt DC fed either by 220 volt mains adaptor and charger with 12 Volt DC battery backup, 12 Volt DC battery with solar panel Communication: Remote or local connection to the CPU to program or download data including GSM, GPRS, radio and cable Software: To allow the monitoring interval of the sensors to be set at defined times. (Loaded onto CPU) 7. Barometer - for compensation due to changes in barometric pressure for sensors used for pressure monitoring. (Not fitted in photograph) 8. Enclosure - which houses all the above components mounted, prewired and pre-programed in a robust IP65 enclosure for mounting on a suitable location such as a wall or support frame. 6

7 1.3 Main components - Digital Sensors 1. Central processing unit (CPU) to which all the components are linked. CR800 or 1000 fully programmable controller with non-volatile memory and battery backed clock. 2. Interface Module: Digital sensors require Digital sensors require an RS485 to RS232 interface which is connected between the CPU and the instrument. 3. Multiplexers: A relay mechanism controlled by the CPU to switch between multiple sensors so that they can be monitored by a single CPU. Allows multi sensors to be fed into the measurement & control module Power Supplies: A power supply provides regulated power to the logger and sensors. 12 volt DC fed either by 230 volt mains adaptor and charger with 12 Volt DC battery backup, 12 Volt DC battery with solar panel. 5. Communication: Remote or local connection to the CPU to program or download data including GSM, GPRS, radio and cable. 6. Software: To allow the monitoring interval of the sensors to be set at defined times. (Loaded onto CPU) 7. Barometer - for compensation due to changes in barometric pressure for sensors used for pressure monitoring. (Not fitted in photograph) 8. Enclosure - which houses all the above components mounted, prewired and pre-programed in a robust IP65 enclosure for mounting on a suitable location such as a wall or support frame

8 1.4 Multiplexer (Flexi-Mux) A multiplexer is used to increase the number of sensors that can be measured with a data logger and is located between the data logger and the sensors which allows a single channel of the data logger to be sequentially connected to numerous sensors. The most common multiplexer used in the Geosense GeoLogger is the RST Flexi-Mux and can sequentially multiplex 5 groups of 4 wire inputs or 10 groups of 2 wire inputs and these settings can be changed using the Internal DIP switches. The number of sensors can be expanded by connecting (chaining) multiple Flexi-Muxs allowing the signals to cascade through the system. This allows a virtually unlimited number of sensors to be connected to a single channel. The data logger program and control ports advance the Flexi-Mux through each sensor. The Flexi-Mux is fitted with internal transient protection on each individual line which eliminates the need for external protection unlike traditional multiplexers Flexi-Mux identification Earth/ground spade terminal 2. Channel identification 3. Multiplexed terminal channel identification 4. Sensor connection ports (fitted with removable terminal blocks) 5. Modular 18-pole Mux control terminal 6. DIP switch setting illustration (switch accessed through rubber grommet on base) 7. Mounting tabs 8

9 1.4.2 Flexi-Mux connections - overview The sensors are connected into the terminal blocks (4) which are capable of taking the outputs in two different settings :- With temperature (4 pole) Without temperature (2 pole). The mode will have been configured for your individual project requirements at manufacturing stage and cannot be easily changed. Contact Geosense for advice pin Mux terminal block This is all pre-wired and therefore nothing needs to be done with this. Where multiple Flexi-Muxs are used this is where they are linked together. 4 5-pin sensor connection ports This is where all the sensor cables are wired into the Geosense GeoLogger. These 5 pin tabs are generally shipped separately. The sensor wires are easily connected and the tabs placed into position. For the wiring details for the most common types of sensors see sections to KEY THINGS TO CONSIDER WHEN WIRING Route cables away from the power supply Strip cables ~10mm Ensure shield is connected with VW Refer to labels on inside of cabinet Label each cable and reference the terminal blocks and Flexi-Muxs 9

10 1.4.7 Flexi-Mux reset The reset line is used to activate the Flexi-Mux. It is activated by a signal in the range of +2.0V to +10V DC. When this line drops lower than 0.9V DC the Flexi-Mux enters a quiescent low current drain state and the common terminals (A, B, C, D) are electronically disconnected from all the sensor input channels. Reset should always connect to a data logger control port Flexi-Mux clock Pulsing the Flexi-Mux clock line high (with reset set high) advances the channel. When the reset first goes high the common terminals A, B, C, D are disconnected from all sensor input terminals. With the Flexi-Mux set in the 4-Pole mode, when the first clock pulse arrives the common terminals are switched to connect with the sensor input channel 1 which consists of 5 wires : A, B, C, D and shield. When a second clock pulse arrives the common lines are switched to connect to channel 2. The Flexi-mux advances along the leading edge of the positive going clock pulse. The voltage level must fall below 1.5V DC and then rise above 2.0V DC to clock it. The clock pulse should be at least 1 ms long. A delay (typically 10 to 20 ms) should be inserted into the data logger program between the beginning of the clock pulse and the measurement instruction to ensure sufficient setting time for the relay contacts. Generally a control port is used to clock the multiplexer however switched excitation can also be used Earth/ground The earth terminal of the Flexi-Mux must be connected to the data logger power earth/ ground. 1.5 Modem Where remote communication is required the Geosense GeoLogger 800/1000 can be fitted with a GSM/GPRS modem to provide:- Remote access to data Remote access to re-configure the data logger Provide alarms The modem should have a 3G data enabled fixed IP SIM card to allow communication via telephone modem and IP protocol. For setting up of communication see section

11 1.6 Software LoggerNet software is used to control and schedule the data acquisition. During manufacture a program written in LoggerNet is loaded onto the Central processing unit (CPU) based on the customer/project requirements and covers:- Sensor type Sensor quantity Sampling interval timing Method of communication Alarms (if applicable) In order to communicate with the Geosense GeoLogger 800/1000 LoggerNet software will need to be installed onto a laptop/pc in order to finish configuring the unit on site together with the ability to download data and will include:- Base readings (VW sensors) Sensor identification (serial number) Sensor location (channel in Flexi-Mux) Sensor calibration factors 1.7 EMC - Electro Magnetic Compatibility EMC is the electromagnetic interaction of electrical and electronic equipment with other electrical and electronic equipment. All electronic devices have the potential to emit and be affected by electromagnetic fields. With the reduction in size of electrical components and the ever increasing amount of electrical & electronic devices such as mobile phones, twoway radios, safety control systems, signalling, generators, welding equipment, power cables etc in all environments, especially construction sites, there is a huge potential for devices to interfere with each other. Geosense GeoLoggers 800/1000 have been designed and tested for EMC under the relevant CE marking directives to comply with the highest standards including requirements set out in London Underground requirements G-222 & This ensures correct operation under the harshest of site conditions. Cables attached to a Geosense GeoLogger should have adequate shielding to minimise the affects of electrical noise (EMI) and have the correct functional earth (see section 5.2). FAILURE TO PROVIDE SUITABLY SCREENED CABLES & TOGETHER WITH EMC GLANDS COULD RESULT IN INCORRECT OPERATION OF THE EQUIPMENT ENSURE THERE IS SUITABLE FUNCTIONAL EARTHING TO ENSURE CORRECT OPERATION OF THE EQUIPMENT 11

12 2.0 CONFORMITY Geosense Ltd Nova House Rougham Industrial Estate Rougham, Bury St Edmunds Suffolk, IP30 9ND United Kingdom Tel: +44 (0) , Fax: +44 (0) Declaration of Conformity We Geosense Ltd at above address declare that the equipment detailed below, complies with the requirements of the following EU Directives:- Low Voltage Directive 2006/95/EC Electromagnetic Compatibility Directive 2004/108/EC Radio & Telecommunications Terminal Equipment 1999/5/EC Restriction on the use of certain Hazardous Substances (RoHS2) 2011/65/EU Equipment description: Make/Brand: Model Numbers: Data Logger Geosense GeoLogger GL800/1000 Compliance has been assessed with reference to the following harmonised standards: EN :2013 Electrical equipment for measurement, control and laboratory use. EMC requirements. General requirements. EN :2010 Safety requirements for electrical equipment for measurement, control, and laboratory use. General requirements A technical file for this equipment is retained at the above address. Martin Clegg Director 12

13 3.0 MARKINGS 230 Geosense GeoLoggers 800/1000 are labelled with the following information:- Manufacturers telephone number & website address Product group: Data logger Product type: GeoLogger Model: GL800/1000 Input supply: 230 Volts AC to 12 Volt DC (mains with battery backup) or 12 Volt DC (battery only) Serial number: CE & WEEE mark Inside the cabinet there is a sheet with basic details about the configuration of each specific logger as follows:- Sensors = IPI The logger is configured to read 4 strings of 10 bussed IPI sensors, connected to a Flexi-Mux as follows :- Connection 1 = 12 Volts Connection 2 = A+ Connection 3 is the screen. Connection 4 = B- Connection 5 = GND The serial numbers for the IPI s must be added to the logger program on installation. Battery and Power Supply The Logger is shipped with the battery disconnected and the power connector to the logger removed. To use first reconnect the + connection to the battery and then plug in the power connector of the logger. The mains supply to the logger can be between 90 and 240VAC 13

14 4.0 DELIVERY This section should be read by all users of Geosense GeoLoggers. 4.1 Packaging Geosense GeoLoggers are packed for transportation to site. Packaging is suitably robust to allow normal handling by transportation companies. Inappropriate handling techniques may cause damage to the packaging and the enclosed equipment. The packaging should be carefully inspected upon delivery and any damage MUST be reported to both the transportation company and Geosense. 4.2 Handling Geosense GeoLoggers are precision measuring instruments. They and their associated equipment should always be handled with care during transportation, storage and installation. Once the shipment has been inspected ( see below ), it is recommended that Geosense GeoLoggers remain in their original packaging for storage or transportation. Cable should also be handled with care. Do not allow it to be damaged by sharp edges, rocks for example, and do not exert force on the cable as this my damage the internal conductors and could render the installation useless. 4.3 Inspection It is important to check all the equipment in the shipment as soon as possible after taking delivery and well before installation is to be carried out. Check that all the components detailed on the documents are included in the shipment. Check that the equipment has not been physically damaged. 4.4 Storage DO NOT DROP AS THIS MAY CAUSE DAMAGE TO INTERNAL COMPONENTS ALWAYS CHECK UNIT WEIGHT BEFORE LIFTING Geosense GeoLoggers contain electronics and whilst they are designed for outside use and mounted within a waterproof (IP66) enclosure the internal circuit board can be affected by excessive moisture, dust and temperature. When not in use they should be stored in a cool, dry location with the cabinet door closed. Most units have a sealed battery fitted and therefore this should be disconnected if not in use to avoid discharging. DISCONNECT BATTERY WHEN NOT IN USE 14

15 5.0 INSTALLATION This section of the manual is intended for all users of Geosense GeoLoggers and is intended to provide guidance with respect to their installation. It must be remembered that no two installations will be the same and it is inevitable that some fine tuning of the following procedures will be required to suit specific site conditions. 5.1 Getting started Prior to installation of a Geosense GeoLogger it is essential to establish and confirm details of the installation to be carried out. Some of the main considerations are listed below :- 1. Intended location (ideally away from moving equipment) 2. Mounting of the enclosure - wall, mounting frame or pole (to suit unit weight) 3. Cable protection 4. Power supply (mains/battery/solar) 5. Position of solar panel 6. Tools - the following is a brief list of tools typically used during the installation:- Mounting frame Drill Drill Bit Spirit Level Bolts & fasteners Set of spanners Typical mounting frame supplied by Geosense including solar panel 15

16 5.0 INSTALLATION contd Wiring The individual components of the Geosense GeoLoggers are all pre-wired so that the only wiring that is required will be:- Mains power (where applicable) Solar panel power (where applicable) Sensor cables (Multiplexer where applicable) Each GeoLogger is fitted with the following cable glands (standard or EMC type):- One for the power supply (mains or solar) One for aerial if modem fitted One for each sensor WHERE SHIELDED CABLE IS REQUIRED ENSURE THAT THE GEOLOGGER IS FITTED WITH EMC GLANDS THE BOTTOM PLATE IS FITTED UPSIDE DOWN FOR SHIPPING PURPOSES TO PROTECT THE CABLE GLANDS AND SHOULD BE REVERSED BEFORE CARRYING OUT ANY WIRING THE GEOLOGGER IS SHIPPED WITH THE BATTERY AND CPU DISCONNECTED. CONNECT IN THE SEQUENCE ADVISED Undo the 8 screws in the bottom plate and remove Re-fit the bottom plate with the dome nuts on the outside. 16

17 5.0 INSTALLATION contd Wiring contd Mains power with battery back up The unit is mains powered with a battery back up which means that it can be operated using mains only but it is recommended to have a back up in case of mains failure. The unit is supplied with the red cable + POSITIVE terminal on the battery removed to preserve the battery when not in use. Re-connect the + POSITIVE terminal. Once the battery has been re-connected the power to the CPU (logger) should now be connected by placing the green terminal block into the POWER IN socket. 17

18 5.0 INSTALLATION contd Wiring contd Mains power connection with battery back up contd... The power supply required is volt AC but this is then transformed down to 12 volt DC for the operating components. The battery is trickled charged from the mains as a back up in case of mains power The Geosense GeoLogger is supplied with the mains cable already pre-wired into the internal power transformer from 220 to 12 volt and only needs connecting to a mains supply. Undo the cable gland nut and feed the end of the power cable down through the cable gland labelled MAINS fitted on the bottom plate. Once the cable has been fed through place the rubber seal and gland nut over the cable. Push home the rubber seal and tighten the gland nut. Connect to a suitable mains supply. ONLY QUALIFIED ELECTRICIANS SHOULD CONNECT TO A LIVE SUPPLY ALWAYS DISCONNECT THE MAINS POWER BEFORE CARRYING OUT A CONNECTION 18

19 5.0 INSTALLATION contd Wiring contd Battery powered connection Where a battery only is used everything will be pre-wired so there is no wiring to be done but the following will be required:- Connect the battery Connect the CPU (POWER IN) Solar power connection The internal power cable will already be wired internally and the only requirements are:- Connect battery Feed cable out through a gland & connect to solar panel Connect the CPU (POWER IN) CONNECT BATTERY BEFORE CONNECTING TO THE SOLAR PANEL 19

20 5.0 INSTALLATION contd Wiring contd Sensor cable connections - braided cable (typically MEMS sensors) Undo the dome nut and feed the cable through the rubber seal allowing enough length to reach the required Flexi-Mux terminal Measure ~ 25mm of braid Strip off the braid, clear wrapping and any fillers to leave ~ 25mm of braid 20

21 5.0 INSTALLATION contd Wiring contd Sensor cable connections - braided cable (typically MEMS sensors) Measure ~ 10 mm along the outer sheath and mark Pull the cable back out through the gland until the mark is visible Push the cable back into the gland to the mark and tighten 21

22 5.0 INSTALLATION contd Wiring contd Sensor cable connections - braided cable (typically MEMS sensors) Remove required sensor connection port from the Flexi-Mux Strip ~10mm off the end of each of the conductor outer sheaths and bend conductors over. Place conductors into each individual terminal Replace sensor connection port in the Flex-Mux Repeat for ALL Flexi-Muxs ALWAYS ENSURE THE CABLES & CHANNEL LOCATIONS ARE CAREFULLY PLANNED AND DOCUMENTED AS THESE WILL NEED TO BE INPUTTED INTO THE SOFTWARE 22

23 5.0 INSTALLATION contd Wiring contd Sensor cable connections - foil screened cable (typically VW sensors) Undo the dome nut and feed the cable through the rubber seal allowing enough length to reach the required Flexi-Mux terminal Strip off the outer sheath, foil and Mylar to expose the four conductors and the drain wire. ELECTRICAL NOISE (EMI) Vibrating wire instruments can be affected by electrical noise which typically comes from power lines, generators, motors, transformers and arc welders. Typically spikes in the data will be observed and the cause can often be identified by looking at the time when this interference occurs e.g. starting a welder on site. One benefit of vibrating wire sensors is that when the readings are affected they are very evident and do not have any long term detrimental effect on the sensor itself. The cable has a foil shield and a drain wire which should be connected into the middle port on the Flexi-Mux to minimise this problem. 23

24 5.0 INSTALLATION contd Wiring contd Sensor cable connections - foil screened cable (typically VW sensors) contd... Remove required sensor connection port from the Flexi-Mux Strip ~10mm off the end of each of the conductor outer sheaths and bend conductors over. Place conductors into each individual terminal including the drain wire Replace sensor connection port in the Flex-Mux Repeat for ALL Flexi-Muxs ALWAYS ENSURE THE CABLES & CHANNEL LOCATIONS ARE CAREFULLY PLANNED AND DOCUMENTED AS THESE WILL NEED TO BE INPUTTED INTO THE SOFTWARE 24

25 5.0 INSTALLATION contd Connecting logger to PC The logger is connected to a PC through the RS 232 (Not Isolated) port Connect one end of the RS 232 cable into the RS 232 (Not Isolated) port on the logger Connect the other end of the RS 232 cable into the RS 232 port on a PC If the PC does not have an RS 232 port use the RS232-USB adaptor provided YOU MAY NEED TO LOAD THE DRIVERS FOR THE RS 232-USB ADAPTOR 25

26 5.4 Modem Where remote monitoring is required the GeoLogger will be typically fitted with a preconfigured COM110A* modem that allows data to be collected from a remote datalogger across the GSM cell phone network. It also allows remote access for:- Downloading data Programming the logger Setting sampling intervals Setting alarms Configure how sensors are interrogated * other modems available on request Modem antenna connection Where a modem is fitted the antenna should be located on the outside the GeoLogger enclosure. Feed through the cable gland marked ANTENNA in the bottom panel and secure into required place on the modem. The standard aerial cable comes with a 2m cable which normally allows it to be located in in a suitable location in order to receive a good signal. Should the antenna need to be located further away a longer cable is available. Please contact Geosense for advice. 30

27 5.4.2 Installing SIM card GEOSENSE SUPPLY If the SIM card has been supplied by Geosense everything will have been configured as per customer requirements and there will be nothing required to be done. SUPPLIED BY OTHERS If the SIM card is to be supplied by others then we would recommend using systems with a fixed IP address. The SIM card is installed in the COM110A modem in the slot at the aerial end of the case in a small tray that has to be ejected by pushing in the small green button which is to the right of the slot holding the tray. Use a pen or similar to push the button inwards. Insert the SIM with card with the gold contact side of the card facing upwards in the tray. Ensure the cut-out of one corner of the card is orientated to match the recess in the tray so the SIM sits flat in the tray. Push the tray back into the slot until fully in then, with the aerial connected, power on the modem and check if the LED starts flashing within a minute or so to indicate successful registration on the network. Configuration should be carried out in accordance with the COM110A manual in the Appendix. BEFORE INSTALLING THE SIM MAKE SURE POWER IS DISCONNECTED FROM THE MODEM 31

28 6.0 DATA ACQUISITION SOFTWARE 6.1 Introduction The main operation of the Geosense GeoLogger is determined by the LoggerNet software which is already loaded onto the CR800 or CR1000 CPU. However the Geosense GeoLogger has been hardware preconfigured and is provided partially pre-programed to collect data from all channels generally in accordance with customers requirements. Where no preference has been provided the Geosense GeoLogger 800/1000 is set to log and store readings at hourly intervals. The Geosense GeoLogger is shipped with the clock set to UST/GMT, and the battery disconnected. Re-connect the battery before operation. 6.2 Resource discs Each unit is supplied with the following discs / Flash Drive:- LoggerNet software from Campbell Scientific Ltd CR800/1000 program created by GEOSENSE Ltd Campbell Scientific resource which includes the manuals for CR800, CR100 and AVW200 plus all other products in their range. 6.3 Laptop/PC Computer Setup The Campbell LoggerNet software is shipped on a CD. Therefore a CD drive on a laptop or PC will be required for a straightforward installation. Where a CD drive is not available on the machine on to which it is to be installed, the contents of the CD can be copied to a USB memory device and installed from there. From the CD, the installation may begin automatically. If not, either double click on the Setup.exe file in LoggerNet directory of the CD, using Explorer. 32

29 or from the DOS command prompt, type d:\loggernet\setup.exe to start the installation. The software will then begin to load, showing the following window. Select the button. It may ask for permission to continue the installation and Administrators Rights may be required to complete the installation. The software will begin Preparing for the setup. 33

30 Once preparation has been completed, it is necessary to complete the following screen. All field must contain characters and the LoggerNet CD Key can be found on the back of the original CD case. When complete the Next button will be activated. Press the next button to continue the installation. It may be necessary to close all other windows.. including the initial LoggerNet Introduction window, before pressing OK. The installation will then continue... 34

31 If the following error message is received, the computer should be shut down, re-booted and the process started fresh from the beginning. When the installation process has been completed the following window will appear. Press Finish and then start LoggerNet from either the Start menu or from the new desktop icon that will have been installed automatically. 35

32 From LoggerNet s opening window, select Main and Setup to open the setup window In the Setup screen, click on the icon to start the following setup window Press the button to display the following window 36

33 From the Introduction screen, press the Next button... Select the logger type from the scroll down list. This will normally be a CR800 series or a CR1000. This information will be provided with each logger installation package. Select the connection type and press Next. If in doubt contact Geosense Ltd. For setting up an configuring a data logger it will be necessary to establish a Direct Connection so, initially, select this option for the setup. 37

34 Select the communications port that will be used by the PC or Notebook to connect to the Logger, in this case we have selected the COMM1 RS232C port and press Next. For additional information on determining the COMM port number see the appendix of this manual. During the initial configuration, it is suggested that a Baud Rate of 9600 is used in the next setup window. This is the communication speed between the PC and the logger. The other options remain unchanged. 38

35 The next window is ignored. Press Next. The next window is a summary of the setup. Press Next to test communications between the PC and the logger. To connect the Logger and PC see section of this manual, If the Logger is not connected to the computer press No 39

36 The following windows should appear as indicators of progress. When communications have been established and the tests completed, the following window appears. Press Next to continue. It now possible to set the data logger s internal clock. This can either match the PC s clock or it can be offset from the PC s clock to another specific time zone using the options in the following window. When the setup has bee completed, press the Next button. 40

37 A site specific data logger program will have been provided by Geosense. For the 800 series loggers it will end in.cr8 and for the 1000 series loggers it will end.cr1. The program may be pre-loaded onto the logger or it may need to be up-loaded. The program will also be provided on either a CD or a Geosense Flash Drive. The following window displays the program that is currently loaded onto the logger ( if any ) and allows for a new program to be selected and sent to the logger. If necessary, select the program from the source provided follow the instructions to complete the up-load. If the program has been pre-installed on the logger, it is not necessary to re-install it as the program will be re-activated and will run when power to the logger is activated. The following messages are likely to appear. If no data has been recorded or it has all been downloaded, this can be ignored. Otherwise press NO and download data before re-trying. The logger will compile the file as it is loaded When the upload is complete it will be confirmed. Press OK When done, press the Next button on the Send Data window. 41

38 Various information is generated by a logger during it normal running routine. The following window allows the user to select what data it stores for future downloading. Commonly the Public and the Status information are not required so these are de-selected as can be seen below. The other Table ( in this case Test ) will have been generated within the site specific logger file and should be selected, as below. Tick the Table Collection and select the Append data to file option, as above. Select the final destination and name of the data file. Where data is to be collected automatically by LoggerNet, a schedule is defined in the next two windows. The first window include the option to activate the schedule and is used to define the start of the schedule and the collection interval. The second window in Scheduled Collection is used to define the interval and number of re-tries LoggerNet will initiate to obtain the data in the event that it fails to do so at the first attempt. The following re-try are commonly adopted: Primary Retry is set to 2 minutes with 3 re-tries Secondary Retry is set to 1 day, if enabled 42

39 The setup wizard is now complete, press Finish to return to the window below. This window contains details of the data logger highlighted on the left, defined in the above processes. Click on the icon in the above window to display the following setup window. 43

40 The Standard Setup window is used to change the configuration details once the initial setup has been completed and the local connection to the logger checked. Close the Setup window and move to the next section to Connect to the logger. 6.4 Establish Connection to the Logger From the main menu, select Main / Connect to open the Connect Screen Highlight the named data logger from the list on the left and press the button. The icon in the lower left hand corner changes from to as the software tries to connect to the logger and then to when it successfully connects. 44

41 The connect button changes to as the connection is attempted and then to when a connection is achieved. 6.5 Downloading Data from a Logger With connection established, it is possible to download data, observe the data as it is recorded, up-date the time settings and recover / re-install the logger software, all from this window. If the logger has been recording data, it is essential that all the stored data is collected prior to up-loading a program to the logger as this process may corrupt data that is stored in the logger memory. Press the button to download the data to a file on the PC. This window appears when the downloading process is complete and offers a chance to View the data file. Only the data that has not already been downloaded to the connected PC will be downloaded. 45

42 Pressing the button will open package in a where the data displayed. View File the View new window, file will be Rudimentary graphing of the data is possible from this View window. Close this window and press OK in the Data Collection Results window to return to the Connect Window. 46

43 6.6 Logger Programs A site and hardware specific logger program is written to instruct the data logger how and when to perform certain activities. This will be supplied by GEOSENSE on a CD or USB Flash Drive Retrieving a program from a logger If the logger program is stored on the PC that is connected ( or to be connected ) to the logger or the program is available on the CD or USB Flash Drive, there is no need retrieve the program from the logger. However, if the program is not available or it has already been modified from it original form, the current version must be downloaded from the logger. To do this, open the Connect Screen from the Main option on the LoggerNet main window. Click on the Retrieve button located on the lower right of the window. 47

44 In the Save As window, choose a name and location for the downloaded file. The default location is within the LoggerNet directory. If file of the same name already exists in this directory, give the new file a unique name so that it can be easily identified as a variant of the logger file. In this case the file has been given a -v1 identifier. Confirmation of the download is provided when it has been completed. Close or minimise the Connect window. It is not important weather or not the connection to the logger remains connected or is disconnected, at this stage Changing the Scan Interval It may be necessary to change the time interval between each scan that the logger performs. This will involve changing the parameter embedded in the software that is running within the logger. From the main LoggerNet window, select to open the Program software package called CRBasic Editor 48

45 The Editor will open with either the default program in its window or the last file that was Use the File, Open commands to select and open the file that has just been downloaded To alter the SCAN INTERVAL scroll down the program to locate the Main Program section. Locate the Scan command. A typical layout can be seen in the window below. The units within the brackets (in this case 60,Min,0,0) set the scan interval. Change only the first two parameters. Right click the mouse on the parameter to select alternatives. Type the numeric value. (text beginning with a is a comment, NOT part of the program) 49

46 6.6.3 Entering the Calibration Values Some logger programs require the use of instruments specific calibration and/or initial/zero reading values to automatically convert the raw data into values in engineering units. This will require the user to enter these values into the logger program for instruments installed on site. The default settings for each sensor are Calibration Constant (K) =1 and the Zero or Initial Reading (Z)=0 for each sensor. The characters in the brackets next to the K or Z are the names or numbers of the instruments, in the order that they are connected to the logger. Without the calibration values in the software, only the Raw values from each sensor will be recorded. For the first instrument,enter the Linear calibration Constant from the Calibration sheet for the instrument connected to the loggers first input channel, replacing the 1. For example K(1) = Then enter the Zero or Initial reading corresponding to the same instrument, replacing the 0. For example Z(1) = A Zero Reading ( most commonly associated with Vibrating Wire pressure sensing equipment ) is the value recorded when the instrument has Zero pressure acting on it. An Initial Reading ( for most other instruments is the reading recorded when the sensor is installed and it s readings have stabilised. This is the starting point to which all subsequent readings will be referenced to calculate changes. For details of how to determine the Zero or Initial reading, consult the manual for the instruments being connected to the logger. 50

47 When the required values have been entered into the software, it is necessary to up-load the program to the logger. However, to check that no format errors have occurred, it is necessary to first compile the program. From the menu bar in the Editor, select Compile and Compile. This operation will return a result of the compilation and indicate if, and where, any errors exist. For example in the window above, a typing mistake has resulted in an error in Line 74 where the wrong characters have been included in the calibration value. Select the File, Save As option to save the file with a new name to indicate that it has been updated with the calibration details. For example, this file could be called :- Crackmeter-Cal.CR8 Now follow the file up-loading sequence detailed in section 6.7 in this manual to send the modified program to the logger and re-start the logger. 51

48 6.6.4 Changing the Excitation Frequency for Vibrating Wire Sensors It may be necessary to set or change the frequency range that an AVW200 Vibrating Wire interface uses to excite a particular type, or types, of sensors. Where the program has been configured for a particular site using specified sensors, this should not be necessary. However, the need to change this range could arise for a number of reasons some of which are :- A different type of Vibrating Wire sensor is attached to the logger where its normal operating range varies from that specified when the program was written. External interference at a particular frequency may be affecting the instrument readings. Modifying the excitation range can be carried out from within the logger program. Having either Retrieved the program from the logger or loaded it from another drive, use the main LoggerNet window, to open the Program software package called CRBasic Editor Open the logger program file to be edited. 52

49 Scroll down to locate the sub routine called Sub Read_VW. The typical line of code highlighted in the above window is detailed below... AVW200 (AVW_Result,Com1,200,200,Dest(),1,1,1,1400,2800,2,_50Hz,1,0) The two numbers in RED can be edited to change the Minimum and Maximum range of the excitation frequency used to read the sensors. This Excitation Value is in FREQUENCY (Hertz - H z ) NOT in Linear DIGITS To determine a suitable excitation frequency for a particular instrument, it is necessary to have its current reading in Hz or convert its operating range from Digits to Frequency Frequency = Square Root of (the value in digits x 1000) For example if the Digits reading is 4556, the equivalent frequency would be In this example and excitation range of 2000 to 2500 could be used. This would be a suitable excitation range for a single instrument at its current reading. It must be remembered that if the reading changes significantly or a number of instruments are read using the same reading routine, they may be outside this range. To set a range that would suit a group of instruments, look at their calibration sheets and convert the Lowest and Highest Digit values recorded during their calibration, into Frequency. Round these to the nearest 100 Hz and use these values as the upper and lower limits of the sensor excitation range. Type in the new values, replacing those in the position of the numbers highlighted in red above. 53

50 When the required values have been entered into the software, it is necessary to up-load the program to the logger. However, to check that no format errors have occurred, it is necessary to first compile the program. From the menu bar in the Editor, select Compile and Compile. This operation will return a result of the compilation and indicate if, and where, any errors exist. For example in the window above, a typing mistake has resulted in an error in Line 74 where the wrong characters have been included in the calibration value. Select the File, Save As option to save the file with a new name to indicate that it has been updated with the calibration details. For example, this file could be called :-Crackmeter -Cal.CR8 Now follow the file up-loading sequence detailed in section 6.7 in this manual to send the modified program to the logger and re-start the logger. 54

51 6.7 Sending a program to a Logger Whether or not the program has been modified, the following procedure is adopted to load it onto the logger. From the Connect window, establish a connection to the logger following the procedure detailed in section 6.4 of this manual. Press the Send button of the right side of the window. This will open a file selection window allowing the user to browse to the location of the logger program. The default save and open location is the LoggerNet folder but if the file is on a CD or Flash drive, its location must be selected. Select the program to be uploaded to the logger. And press Open. A warning will be displayed. If any important data is still stored on the logger, it must be downloaded first so press No at this stage and follow the instructions in section 6.5 of this manual before continuing. 55

52 When ready to load the program onto the logger, press YES on the warning window, shown As soon as the program is loaded and the compiling completed, it will run. It may not take a set of readings immediately as it will wait until a suitable starting time that is consistent with the scan interval that has been set in the program. For example, if a scan interval of 1 hour has been selected, the logger will wait until the beginning of the next hour to start its scan. 56

53 7.0 MAINTENANCE Geosense GeoLoggers are basically maintenance free device for most applications but the following should be checked periodically:- ITEM Enclosure Cable glands External cables Internal cables Battery Flexi-Mux ACTION Check for damage, water ingress Check tightness Check for damage Check for loose connections Check voltage Functionality 57

54 8.0 TROUBLESHOOTING 58

55 59

56 9.0 SPECIFICATION ITEM GL800 GL1000 Control module CR800 CR1000 Processor Renesas H8S 2322 Renesas H8S 2322 Memory for operating 2MB flash 2MB flash Battery backed SRAM/CPU 4MB 4MB Clock accuracy ± 3 minutes per year ± 3 minutes per year Analogue inputs 3 differential or 6 single ended 8 differential or 16 single ended Analogue outputs 2 switched voltage 3 switched voltage Resistance measurements 4 & 6 wire full bridges 4 & 6 wire full bridges Pulse counters 2 inputs 2 inputs Digital I/O 4 ports 8 ports Communication ports RS-232, SDi-12, COM1 to COM2 RS-232, SDi-12, COM1 to COM2 Power requirement 9.6 to 16 Volt DC 9.6 to 16 Volt DC External battery 12 Volt DC 12 Volt DC Typical current drain 0.6 ma in sleep mode 0.6 ma in sleep mode Enclosure 500 x 500 x 210mm 500 x 500 x 210mm Weight* Maximum 35 Kg Maximum 35kg Dependent on specification 10.0 SPARE PARTS In general spare parts are not usually required for Geosense GeoLoggers GL800/1000 but as they consists of various electronic components there is always the possibility of an item failing. In this case new components are available as follows:- Part number Description Q CR1000 Control Module Q CR800 Control Module Q GPRS modem Q Flexi-Mux multiplexer Q Vibrating wire interface Q RS interface Q Solar panel Q Solar panel voltage regulator Q Battery (12V-7 Ah) Q Battery (12V-45 Ah) - Solar Panel Q Fuse Q EMC filter 60

57 11.0 RETURN OF GOODS 11.1 Returns procedure If goods are to be returned for either service/repair or warranty, the customer should contact Geosense for a Returns Authorisation Number, request a Returned Equipment Report Form QF034 and, prior to shipment. Numbers must be clearly marked on the outside of the shipment. Complete the Returned Equipment Report Form QF034, including as much detail as possible, and enclose it with the returned goods and a copy of the form should be faxed or ed in advance to the factory Chargeable Service or Repairs Inspection & estimate It is the policy of Geosense that an estimate is provided to the customer prior to any repair being carried out. A set charge for inspecting the equipment and providing an estimate is also chargeable Warranty Claim (See Limited Warranty Conditions) This covers defects which arise as a result of a failure in design or manufacturing. It is a condition of the warranty that the Geosense GeoLogger GL must be installed and used in accordance with the manufacturer s instructions and has not been subject to misuse. In order to make a warranty claim, contact Geosense and request a Returned Equipment Report Form QF034. Tick the warranty claim box and return the form with the goods as above. You will then be contacted and informed whether your warranty claim is valid Packaging and Carriage All used goods shipped to the factory must be sealed inside a clean plastic bag and packed in a suitable carton. If the original packaging is not available, Geosense should be contacted for advice. Geosense will not be responsible for damage resulting from inadequate returns packaging or contamination under any circumstances Transport & Storage All goods should be adequately packaged to prevent damage in transit or intermediate storage. 61

58 12.0 LIMITED WARRANTY The manufacturer, Geosense Ltd, warrants the Geosense GeoLogger GL 800/1000 manufactured by it, under normal use and service, to be free from defects in material and workmanship under the following terms and conditions:- Sufficient site data has been provided to Geosense by the purchaser as regards the nature of the installation to allow Geosense to select the correct components and configuration for the Geosense GeoLogger GL 800/1000. The Geosense GeoLogger GL 800/1000 shall be installed in accordance with the manufacturer s recommendations. The equipment is warranted for 1 year from the date of shipment from the manufacturer to the purchaser. The warranty is limited to replacement of part or parts which, are determined to be defective upon inspection at the factory. Shipment of defective part or parts to the factory shall be at the expense of the Purchaser. Return shipment of repaired/replaced part or parts covered by this warranty shall be at the expense of the Manufacturer. Unauthorised alteration and/or repair by anyone which, causes failure of the unit or associated components will void this LIMITED WARRANTY in its entirety. The Purchaser warrants through the purchase of the Geosense GeoLogger GL 800/1000 equipment that he is familiar with the equipment and its proper use. In no event shall the manufacturer be liable for any injury, loss or damage, direct or consequential, special, incidental, indirect or punitive, arising out of the use of or inability to use the equipment sold to the Purchaser by the Manufacturer. The Purchaser assumes all risks and liability whatsoever in connection with the Geosense GeoLogger GL 800/1000 equipment from the time of delivery to Purchaser. 62

59 13.0 APPENDIX COM Port Identification To determine the communication port on the PC that is being used to connect to a logger, locate and run the Device Manager software program that is supplied with Windows. Scroll down the list of hardware and click on the Ports (COM & LPT) icon to reveal the ports currently active on the PC. If the connection is via an RS232C port on the PC, it s number will be found in the list of ports as in the screen shot below. Where a USB to RS232C interface is used, the name of the USB Serial Port will be listed together with the COM port number. 63

60 Nova House. Rougham Industrial Estate. Rougham. Bury St Edmunds. Suffolk. IP30 9ND. England. Tel: +44 (0) Fax: +44 (0)

SMART MUX INTERFACE (SMI)

SMART MUX INTERFACE (SMI) SMART MUX INTERFACE (SMI) I N S T R U C T I O N M A N U A L 2 CONTENTS Page 1.0 INTRODUCTION 1 1.1 General Description 1 1.2 Device Compatibility 2 1.3 Theory of Operation 3 2.0 CONFORMITY 5 3.0 MARKINGS

More information

DATA LOGGER GEOLOGGER G8 PLUS

DATA LOGGER GEOLOGGER G8 PLUS A D V A C E D DATA LOGGER GEOLOGGER G8 PLUS I N S T CONFIGURATION & WIRING OF PERIPHERALS R U C T I O N M A N U A L 1 CONTENTS DESCRIPTION PAGE Main components 3 G8 Module Connections 4 G8 Module Connections

More information

Product Manual ASL Document Ref.: U doc Issue: 04 complete, approved - Date: 16/08/10 Part Number: M0618_23

Product Manual ASL Document Ref.: U doc Issue: 04 complete, approved - Date: 16/08/10 Part Number: M0618_23 Product Manual ASL Document Ref.: U-0618-0103.doc Issue: 04 complete, approved - Date: 16/08/10 Part Number: M0618_23 RCS01 RPA Transmitter Charging Station This equipment is designed and manufactured

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Vision OPLC V350-35-R34/V350-J-R34 Installation Guide The Unitronics V350-35-R34/V350-J-R34 offers the following onboard I/Os: 22 Digital Inputs, configurable via wiring to include 2 Analog and 3 HSC/Shaft-encoder

More information

Vision OPLC V TR6/V350-J-TR6

Vision OPLC V TR6/V350-J-TR6 Vision OPLC V350-35-TR6/V350-J-TR6 Installation Guide The Unitronics V350-35-TR6/V350-J-TR6 offers the following onboard I/Os: 8 Digital Inputs, configurable via wiring to include 2 Analog (current/voltage)

More information

CA-A480-A Elevator Controller. Reference & Installation Manual

CA-A480-A Elevator Controller. Reference & Installation Manual CA-A480-A Elevator Controller Reference & Installation Manual TABLE OF CONTENTS INTRODUCTION.................................................................. 4 Introduction.............................................................................................

More information

G-LOG Mobile Application

G-LOG Mobile Application G-LOG Mobile Application I N S T R U C T I O N M A N U A L Version 1.0.12 February 2015 CONTENTS 1. ABOUT THIS DOCUMENT... 3 2. INITIAL STEPS... 3 2.1. App installation... 3 2.2. Connection... 3 2.3. Power...

More information

QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE

QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE User s Manual SR250HL Power Supply/ Float Charger for Lead Acid Batteries STANDARD FEATURES OPTIONAL FEATURES 3 Relay Alarms-Form

More information

LCI User Manual mantracourt.com

LCI User Manual mantracourt.com LCI User Manual mantracourt.com LCI Load Cell Junction Box with Fault Monitor Contents Chapter 1 Introduction to the LCI... 2 Chapter 2 Installing the LCI... 3 Chapter 3 Setting up the LCI... 4 Sequence

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

OPLC Installation Guide

OPLC Installation Guide Samba OPLC SM35-J-R20/SM43-J-R20 SM70-J-R20 SM35-J-T20/SM43-J-T20 SM70-J-T20 OPLC Installation Guide 12 Digital Inputs, include 1 HSC/Shaft-encoder Input, 2 Analog inputs (only when the digital inputs

More information

VDI Pro Voltage & Dry Contact Interface Installation and programming Guide MODEL VDI MK2

VDI Pro Voltage & Dry Contact Interface Installation and programming Guide MODEL VDI MK2 VDI Pro Voltage & Dry Contact Interface Installation and programming Guide MODEL VDI MK2 1 of 18 PREFACE Important Installation Information It is the purchasers responsibility to determine the suitability

More information

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 UniStream HMI Panel Installation Guide USP-070-B10, USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for

More information

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual This package is designed to simplify the connections to our Secured Series Hub Plus Controller. This will translate into

More information

OZONE SWITCH Model OS-6. OS-6 Features

OZONE SWITCH Model OS-6. OS-6 Features USER MANUAL OZONE SWITCH Model OS-6 OS-6 Features The OS-6 is an industrial grade ozone controller and monitor. The OS-6 design is optimized for accuracy and ease of installation, setup and operation.

More information

Broadband Automatic Disconnect Switch. User Manual

Broadband Automatic Disconnect Switch. User Manual Reset/Test Primary/ Primary Broadband Automatic Disconnect Switch User Manual Local Power Remote Pwer Local 63V Fault Secondary Select Secondary 220V Normal 990-1929 09/2004 Introduction Introduction

More information

EPS Power Supply

EPS Power Supply EPS - 600 Power Supply Installation and Operation Manual Version 1.0 *This instrument is intended for laboratory use only Index A. Important Notice ----------------------------------------------------------------

More information

22 Digital Inputs, including 2 Analog, 2 HSC/Shaft-encoder inputs 16 Transistor Outputs

22 Digital Inputs, including 2 Analog, 2 HSC/Shaft-encoder inputs 16 Transistor Outputs Vision PLC+HMI V130-33-T38/V130-J-T38 V350-35-T38/V350-J-T38 V430-J-T38 Installation Guide 22 Digital Inputs, including 2 Analog, 2 HSC/Shaft-encoder inputs 16 Transistor Outputs General Description All

More information

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

LCI Load Cell Junction Box with Fault Monitor

LCI Load Cell Junction Box with Fault Monitor LCI Load Cell Junction Box with Fault Monitor User Manual www.mantracourt.co.uk The LCI Load Cell Failure Alarm Manual Chapter 1 Introduction to the LCI...2 Chapter 2 Installing the LCI...3 Figure 2.1

More information

2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM

2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM 2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM CONTENTS PAGE Manual Introduction 3 Product Overview 3 Operation and Connection 3 RS232 Connection 3-4 RS485 Connection 3-4 2214 PCB layout 5 RS485 Bus Terminal

More information

This guide provides basic information for Unitronics controller model V T2.

This guide provides basic information for Unitronics controller model V T2. Vision OPLC 12 pnp/npn Digital, including 2 Analog, 3 HSC/Shaftencoder Inputs, 12 Transistor Outputs This guide provides basic information for Unitronics controller model V350-35-T2. General Description

More information

MD9 MULTIDROP INTERFACE INSTRUCTION MANUAL

MD9 MULTIDROP INTERFACE INSTRUCTION MANUAL MD9 MULTIDROP INTERFACE INSTRUCTION MANUAL REVISION: 01/05/03 COPYRIGHT (c) 1987-2003 CAMPBELL SCIENTIFIC, INC. This is a blank page. WARRANTY AND ASSISTANCE The MD9 MULTIDROP INTERFACE is warranted by

More information

NX21 USER MANUAL. Telemetry Unit. Version 1.5

NX21 USER MANUAL. Telemetry Unit. Version 1.5 USER MANUAL Version 1.5 Nortech Management Ltd, United Kingdom NOV 2016 www.nortechonline.co.uk Doc Ref D_000344 Publication Notice Copyright Nortech Management Limited (NML). All rights reserved. No part

More information

The identified danger could cause physical and property damage.

The identified danger could cause physical and property damage. Samba OPLC SM35-J-T20 Installation Guide The Unitronics SM35-J-T20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include 2 Analog and 3 HSC/Shaft-encoder Inputs 8 Transistor

More information

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B. Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable

More information

Vision OPLC. V T38 Installation Guide. General Description

Vision OPLC. V T38 Installation Guide. General Description Vision OPLC V130-33-T38 Installation Guide The Unitronics V130-33-T38 offers the following onboard I/Os: 22 Digital Inputs, configurable via wiring to include 2 Analog and 2 HSC/Shaft-encoder Inputs 16

More information

Campbell Based Multi-Channel Data Logger. User Manual. Man /08/2014 Final David Farnham. Chris Rasmussen. Chris Rasmussen. Manual No.

Campbell Based Multi-Channel Data Logger. User Manual. Man /08/2014 Final David Farnham. Chris Rasmussen. Chris Rasmussen. Manual No. Campbell Based Multi-Channel Data Logger Man158 2.1.1. 06/08/2014 Final David Farnham Chris Rasmussen Chris Rasmussen Manual No. Revision Date Status Originator Checked Authorised for Issue 1 Contents

More information

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions DUAL DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL

More information

FA-2448 SIX POSITION Filter Wheel

FA-2448 SIX POSITION Filter Wheel 15 Discovery Way, Acton, MA 01720 Phone: (978)263-3584, Fax: (978)263-5086 Web Site: www.acton-research.com Operating Instructions Acton Research Corporation FA-2448 SIX POSITION Filter Wheel Rev. 3.05.17

More information

Tempco Instruction Manual

Tempco Instruction Manual Tempco Instruction Manual 1/16 DIN Solid State Temperature Controller Relay Output Solid State Output For Heating Model Numbers: TEC-901, TEC-902, TEC-905 Temperature controls in this series are designed

More information

THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL. Digi-modems. Issue 3

THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL. Digi-modems. Issue 3 THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL Digi-modems Issue 3 Contents Com300 & Com2400 Installation Manual Contents 1. Regulatory Requirements... 3 General...3 Approval... 3 REN Rating... 3 2.

More information

General Description V TR34/V130-J-TR34 V TR34/V350-J-TR34 V430J-R34 V R34/V130-J-R34 V R34/V350-J-R34

General Description V TR34/V130-J-TR34 V TR34/V350-J-TR34 V430J-R34 V R34/V130-J-R34 V R34/V350-J-R34 Vision OPLC V130-33-TR34/V130-J-TR34 V350-35-TR34/V350-J-TR34 V430-J-TR34 V130-33-R34/V130-J-R34 V350-35-R34/V350-J-R34 V430-J-R34 Installation Guide 22 Digital Inputs, including 3 HSC/Shaft-encoder Inputs,

More information

MTX-A Temperature Gauge User Manual

MTX-A Temperature Gauge User Manual MTX-A Temperature Gauge User Manual 1. Installation... 2 1.1 Gauge Mounting... 2 1.2 Temperature Sensor Mounting... 2 1.2.1 Changing the MTX-A s Gauge Bezel... 2 1.3 Main Gauge Wiring... 3 1.3.1 Single

More information

1. Carefully unpack the um260 s shipping carton and check the contents for damage.

1. Carefully unpack the um260 s shipping carton and check the contents for damage. um260 Installation Manual um260 Installation Chapter 4 um260 MICRO MONITOR INSTALLATION This section of the um260 Micro Monitor Installation Manual describes the requirements and procedures for installing

More information

Intrinsically safe batch controller Batching Master 110i

Intrinsically safe batch controller Batching Master 110i Intrinsically safe batch controller Batching Master 110i Installation Guide BVS 04 AT E 172 Revision 12.2 IBS BatchControl GmbH Im Sträßchen 2-4 Tel.: ++49 2441 9199 801 53925 Kall Fax.: ++49 2441 9199

More information

TETRIS 2500 High Impedance Active Probe. Instruction Manual

TETRIS 2500 High Impedance Active Probe. Instruction Manual TETRIS 2500 High Impedance Active Probe Instruction Manual Copyright 2018 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

Operating Instructions

Operating Instructions PRIMETEST 100 PRIMETEST 100 Bracken Hill South West Industrial Estate Peterlee Co Durham SR8 2SW ENGLAND Tel: +44(0)191 5863511 www.seaward.co.uk sales@seaward.co.uk service@seaward.co.uk Part Number

More information

EPS 06 in rear housing type A1

EPS 06 in rear housing type A1 Field Installation and / or Replacement of RACO Electronic Position Sensor Board EPS 02 & EPS 06 - Electronic Limit Switches - Analog Output Position Signal - Very Accurate - Easy To Use - Robust - Dependable

More information

MAXIMA+ Series Rotary Level Indicator

MAXIMA+ Series Rotary Level Indicator MAXIMA+ Series Rotary Level Indicator BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE

More information

Manual Control Unit GFC 32

Manual Control Unit GFC 32 Manual Control Unit 1400004_EN/05.2017 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Settings 6 7. Remote control

More information

ABB Drives. User s Manual. Analogue I/O Extension Module RAIO-01

ABB Drives. User s Manual. Analogue I/O Extension Module RAIO-01 ABB Drives User s Manual Analogue I/O Extension Module RAIO-01 Analogue I/O Extension Module RAIO-01 User s Manual 3AFE 64484567 REV A EN EFFECTIVE: 1.2.2002 2002 ABB Oy. All Rights Reserved. Safety

More information

ABB Drives. User s Manual. Digital I/O Extension Module RDIO-01

ABB Drives. User s Manual. Digital I/O Extension Module RDIO-01 ABB Drives User s Manual Digital I/O Extension Module RDIO-01 Digital I/O Extension Module RDIO-01 User s Manual 3AFE 64485733 REV B EN EFFECTIVE: 10.2.2003 2003 ABB Oy. All Rights Reserved. Safety Instructions

More information

ES-600 Ozone Controller Operation Manual

ES-600 Ozone Controller Operation Manual ES-600 Ozone Controller Operation Manual Questions about your product? Find answers here: Web: www.ozonesolutions.com/es-600 Phone: 712-439-6880 Ozone Solutions OZONE CONTROLLER Model ES-600 Instructions

More information

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating

More information

RXTH DUAL ROOM SENSOR / SWITCH

RXTH DUAL ROOM SENSOR / SWITCH DUAL ROOM SENSOR / SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE

More information

OPERATOR MANUAL OSD157 FIBER OPTIC RS422/RS232 MODEM/MULTIPLEXER

OPERATOR MANUAL OSD157 FIBER OPTIC RS422/RS232 MODEM/MULTIPLEXER / OPERATOR MANUAL OSD157 FIBER OPTIC RS422/RS232 MODEM/MULTIPLEXER PAGE 2 OF 17 INDEX 1 1. TECHNICAL SUMMARY... 4 1.1 BRIEF DESCRIPTION... 4 1.1.1 OVERVIEW... 4 1.1.2 APPLICATIONS... 4 1.1.3 FEATURES AND

More information

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Liebert PSA iton User Manual Version: V2.8 Revision date: November 14, 2005 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or

More information

Operating Instructions

Operating Instructions Bracken Hill South West Industrial Estate Peterlee Co Durham SR8 2SW ENGLAND Tel: +44(0)191 5863511 www.seaward.co.uk sales@seaward.co.uk service@seaward.co.uk Part Number 344A550 Revision 1 2006 Seaward

More information

Operating Manual RISH DPM Hz

Operating Manual RISH DPM Hz Operating Manual RISH DPM 72mm x 144mm 96mm x 96mm 48mm x 96mm 2-60-006-00-00512_Rev. B - 7/2016 DIGITAL MULTIFUNCTION INSTRUMENT Programmable Digital Panel Meter Installation & Operating Instructions

More information

Operation Manual. Concorde 600 Power Supply. *This instrument is intended for laboratory use only.

Operation Manual. Concorde 600 Power Supply. *This instrument is intended for laboratory use only. Concorde 600 Power Supply Operation Manual Cat.no. R10-1001011 *This instrument is intended for laboratory use only http://www.recenttec.com E-mail : support@recenttec.com Version 1.1 Packing List x 1

More information

GREISINGER electronic GmbH. D Regenstauf, Hans-Sachs-Straße 26. T-Logg 120 W -... T-Logg 120 K -...

GREISINGER electronic GmbH. D Regenstauf, Hans-Sachs-Straße 26. T-Logg 120 W -... T-Logg 120 K -... E39.0.1X.6C-01 Data logger for standard signals as of version 1.0 Operating Instruction T-Logg 120... T-Logg 120 W -... T-Logg 120 K -... GREISINGER electronic GmbH D - 93128 Regenstauf, Hans-Sachs-Straße

More information

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions DIFFERENTIAL PRESSURE Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL

More information

Gobo Projector XP 80W

Gobo Projector XP 80W Gobo Projector XP 80W User Manual Order code: EQLED084 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CARE- FULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up, please

More information

PS8 - II. Professional Power Sequencer. User s Manual

PS8 - II. Professional Power Sequencer. User s Manual PS8 - II Professional Power Sequencer User s Manual IMPORTANT SAFETY INSTRUCTIONS READ FIRST This symbol, whenever it appears, alerts you to the presence of uninsulated dangerous voltage inside the enclosure.

More information

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual. The power behind competitiveness Delta Infrasuite Power Management Power Distribution Unit User Manual www.deltapowersolutions.com Save This Manual This manual contains important instructions and warnings

More information

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina Progressive Industries Warranty Progressive warrants its products are free from defects in materials and workmanship for a period of three years. This is in lieu of all other warranties, obligations, or

More information

OPERATOR MANUAL OSD156 SYNCHRONOUS FIBER OPTIC RS232 MODEM

OPERATOR MANUAL OSD156 SYNCHRONOUS FIBER OPTIC RS232 MODEM OPERATOR MANUAL OSD156 SYNCHRONOUS FIBER OPTIC RS232 MODEM OSD156 SYNCHRONOUS FIBER OPTIC RS232 MODEM Document No. 10104401 Page 2 of 14 INDEX 1. TECHNICAL SUMMARY... 4 1.1 BRIEF DESCRIPTION...4 1.1.1

More information

Blitzer Strobe. User Manual. Order code: EQLED366

Blitzer Strobe. User Manual. Order code: EQLED366 Blitzer Strobe User Manual Order code: EQLED366 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up, please make

More information

DL6 Data Logger. Quick Start Guide Version 1.2. Delta-T Devices Ltd

DL6 Data Logger. Quick Start Guide Version 1.2. Delta-T Devices Ltd DL6 Data Logger Soil Moisture Logger with 6 Soil Moisture Channels, Temperature and Rain Gauge Channels and Versatile Relay Channel Quick Start Guide Version 1.2 Delta-T Devices Ltd 1 Unpacking n 4 Install

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use General and New Features The OS-6 is an industrial grade Ozone controller and monitor. The OS-6 design has been optimized for accuracy, ease

More information

STUDIO 1800 OPERATING INSTRUCTIONS MANUFACTURED IN THE UK

STUDIO 1800 OPERATING INSTRUCTIONS MANUFACTURED IN THE UK STUDIO 1800 OPERATING INSTRUCTIONS MANUFACTURED IN THE UK The Studio 1800 is a combined Programmer and Temperature Controller which has been specifically designed for use with pottery kilns. Control of

More information

2-Way Wireless I/O Expander Installation Guide

2-Way Wireless I/O Expander Installation Guide 2-Way Wireless I/O Expander Installation Guide For more detailed information please refer to the iconnect Installer Manual provided on our website: www.electronics-line.com Table of Contents 1. Introduction...

More information

Resolver to Digital Expansion Board

Resolver to Digital Expansion Board Resolver to Digital Expansion Board Catalog No. EXB009A01 Installation and Operating Manual 6/98 MN1313 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

Manual Simatek Control Unit GFC 32

Manual Simatek Control Unit GFC 32 Manual Simatek Control Unit GFC 32 Original instructions 1400004_GB Ver. 2014.01.09 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections

More information

DEEP SEA ELECTRONICS PLC DSE103 MK II Speed Switch Operators Manual

DEEP SEA ELECTRONICS PLC DSE103 MK II Speed Switch Operators Manual DEEP SEA ELECTRONICS PLC DSE103 MK II Speed Switch Operators Manual Document number 057-135 Author : Paul Gibbons DSE103 MKII Operator Manual Issue 1 Deep Sea Electronics Plc Highfield House Hunmanby North

More information

Crossfire. User Manual. Order code: EQLED061

Crossfire. User Manual. Order code: EQLED061 Crossfire User Manual Order code: EQLED061 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up, please make sure

More information

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL Price $5.00 MAXIMA + Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY Division of Garner Industries 7201 North 98th Street Lincoln, NE 68507-9741 (402) 434-9102 925-0268 Rev. A

More information

icp installation guide

icp installation guide The Information Control Point (icp) is the latest SmartFarm Technology by Inc. The icp is the ultimate on-farm data-management tool. The icp has all the power of a basic personal computer, but instead

More information

High Speed Remote I/O Module

High Speed Remote I/O Module High Speed Remote I/O Module EXF-RC15 The Unitronics EXF-RC15 is a High Speed Remote I/O Module that offers three High Speed Counter inputs and four high speed outputs. Overall, the EXF-RC15 offers 9 digital

More information

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies ADC7520 SERIES 1600W Battery Chargers and Power Supplies Wide output adjustment range 0 72VDC Analog control by external 0-5VDC voltage Temp.comp charging, sense as on option Power fail relay alarm Master-Slave

More information

CU USB-Extender-Rx (USB and DVI Extender) Version: 0.3 Date:

CU USB-Extender-Rx (USB and DVI Extender) Version: 0.3 Date: CU8860-0000 USB-Extender-Rx (USB and DVI Extender) Version: 0.3 Date: 2006-02-20 Table of Contents Table of Contents 1 Foreword 1 1.1 Notes on the documentation 1 1.1.1 Liability Conditions 1 1.1.2 Conditions

More information

CS2 DMX Distribution Splitter

CS2 DMX Distribution Splitter CS2 DMX Distribution Splitter User Manual Order code: BOTE72 Safety advice WARNING FOR YOUR OWN SAFETY, PLEASE READ THIS USER MANUAL CAREFULLY BEFORE YOUR INITIAL START-UP! Before your initial start-up,

More information

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01 ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview

More information

PWRguard PLUS Spring City Drive Waukesha, WI

PWRguard PLUS Spring City Drive Waukesha, WI PWRguard PLUS www.westmountainradio.com 1020 Spring City Drive Waukesha, WI 53186 262-522-6503 sales@westmountainradio.com 2016, All rights reserved. All trademarks are the property of their respective

More information

AC4G-D User s Manual

AC4G-D User s Manual AC4G-D User s Manual Entire contents of this manual 2004 Active Cool Ltd. Ashkelon, Israel. Reproduction in whole or in part without permission is prohibited. Active Cool and AC4G-D are registered of Active

More information

Installation, Operation & Maintenance Instructions / Technical Document

Installation, Operation & Maintenance Instructions / Technical Document Installation, Operation & Maintenance Instructions / Technical Document Model VHL Mini Vibrating Fork Point Level Sensor for Liquids Thank you for purchasing the Model VHL Mini Vibrating Fork Point Level

More information

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter Operation Manual MODEL 2TX 2-wire Isolated ph/orp Transmitter 0 2TX CONTENTS INITIAL INSPECTION.....2 INTRODUCTION......2 ASSEMBLY...3 PREPARATION....4 CONNECTING THE ELECTRODE...4 CONNECTING THE TEMPERATURE

More information

3700 SERIES USER MANUAL

3700 SERIES USER MANUAL SAFETY GUIDE This manual contains the precautions necessary to ensure your personal safety as well as for protection for the products and the connected equipment. These precautions are highlighted with

More information

SIRIUS CAPACITOR MODULE User Manual. Model number: A-1.7C-M-SD-G Version 1.0; Release Date: April 2018

SIRIUS CAPACITOR MODULE User Manual. Model number: A-1.7C-M-SD-G Version 1.0; Release Date: April 2018 SIRIUS CAPACITOR MODULE User Manual Model number: 3550-48-A-1.7C-M-SD-G Version 1.0; Release Date: April 2018 Introduction The Sirius Capacitor Module ( Sirius ) is supercapacitor-based storage that uses

More information

PKP Prozessmesstechnik GmbH. Borsigstrasse 24. D Wiesbaden-Nordenstadt. Tel: / Fax: / Operating manual PSA06

PKP Prozessmesstechnik GmbH. Borsigstrasse 24. D Wiesbaden-Nordenstadt. Tel: / Fax: / Operating manual PSA06 PKP Prozessmesstechnik GmbH Borsigstrasse 24 D-65205 Wiesbaden-Nordenstadt Tel: 06122 / 7055-0 Fax: 06122 / 7055 50 Operating manual PSA06 Electronical pressure switch Content Page 19-34 1. Foreword 19

More information

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS PRODUCT DESCRIPTION ARTICLE CODES INTENDED AREA OF USE TECHNICAL DATA STANDARDS OPERATIONAL DIAGRAMS WIRING AND CONNECTIONS

More information

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens). Vision OPLC Installation Guide Models 230/260/280/290 (Non-color Screens) This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens). General Description Vision OPLCs

More information

MTX-A, Fuel Pressure Gauge PSI

MTX-A, Fuel Pressure Gauge PSI MTX-A, Fuel Pressure Gauge 0-100 PSI Contents 1 Mounting and Sensor Installation... 2 1.1 Gauge Mounting... 2 1.1.1 Changing the MTX-A s Gauge Bezel... 2 1.2 Fuel Pressure Sensor... 2 2 Wiring... 3 2.1

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

I/O SIGNAL CONDITIONER

I/O SIGNAL CONDITIONER Technical Data Sheet No. TD9809M Rev. F Date of Issue: December 9, 2009 OPERATING MANUAL I/O SIGNAL CONDITIONER CAUTION: THIS PRODUCT DOES NOT PROVIDE GALVANIC ISOLATION. DO NOT ATTEMPT USE OF THIS PRODUCT

More information

Start Here. All-in-One Printer. Print Copy Scan

Start Here. All-in-One Printer. Print Copy Scan Start Here All-in-One Printer Print Copy Scan Note: A USB 2.0 cable is required to connect your Kodak All-in-One printer to your Windows or Macintosh OS computer. Available in the Kodak online store or

More information

ORB TM 4-20 ma Input Box Installation & Operation Manual

ORB TM 4-20 ma Input Box Installation & Operation Manual IOM ORB TM 4-20 ma Input Box Installation & Operation Manual ORB TM 4-20 ma Input Box Installation & Operation Manual CONTENTS I. HANDLING & STORAGE... 1 Inspection and Handling Disposal and Recycling

More information

BrewTroller Phoenix. Owners Manual. Updated - March 14, 2016 BREWTROLLER PHOENIX 1

BrewTroller Phoenix. Owners Manual. Updated - March 14, 2016 BREWTROLLER PHOENIX 1 BrewTroller Phoenix Owners Manual Updated - March 14, 2016 BREWTROLLER PHOENIX 1 2016 BrewTroller All Rights Reserved. Product warranty or service will not be extended if: (1) the product is repaired,

More information

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL 1 IMPORTANT SAFETY INSTRUCTION READ FIRST This symbol, whenever it appears, alerts you to the presence of uninsulated dangerous voltage inside the enclosure-voltage

More information

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual Omnitron Systems Technology, Inc. 1 iconverter 19-Module Managed Power Chassis User s Manual 27 Mauchly, #201, Irvine, CA 92618 Phone: (949) 250-6510; Fax: (949) 250-6514 2 Omnitron Systems Technology,

More information

Energy Management System. Operation and Installation Manual

Energy Management System. Operation and Installation Manual Energy Management System Operation and Installation Manual AA Portable Power Corp 825 S 19 TH Street, Richmond, CA 94804 www.batteryspace.com Table of Contents 1 Introduction 3 2. Packing List 5 3. Specifications

More information

Neutrik 20A powercon with 2nd order EMI filter & GDT/VDR protection circuit against Lightning Strike & Local Power Surge Circuit A

Neutrik 20A powercon with 2nd order EMI filter & GDT/VDR protection circuit against Lightning Strike & Local Power Surge Circuit A PDU16-AV 20A AC PDU WITH POWER MONITOR 2U Rack Mount PDU with Overload Protection & Power Monitoring 2U high Horizontal Mounting unit designed to provide versatile hook-up for the distribution of AC power

More information

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features

Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use. General and New Features Eco Sensors OZONE CONTROLLER Model OS-6 Instructions for Use General and New Features The OS-6 is an industrial grade Ozone controller and monitor. The OS-6 design has been optimized for accuracy, ease

More information

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND

More information

Drive 3G-S ENGLISH. Cellular Signal Booster A Customer Support: Mon-Fri 8 am to 6 pm.

Drive 3G-S ENGLISH. Cellular Signal Booster A Customer Support: Mon-Fri 8 am to 6 pm. ENGLISH Drive 3G-S Cellular Signal Booster A512626 ENGLISH!! IT IS VERY IMPORTANT TO POWER YOUR SIGNAL BOOSTER USING A SURGE PROTECTED AC POWER STRIP WITH AT LEAST A 1000 JOULE RATING. FAILURE TO DO THIS

More information

GREISINGER electronic GmbH. D Regenstauf, Hans-Sachs-Straße 26. T-Logg 100. T-Logg 100 E

GREISINGER electronic GmbH. D Regenstauf, Hans-Sachs-Straße 26. T-Logg 100. T-Logg 100 E E39.0.0X.6C-03 Data logger for temperature as of version V1.3 Operating Manual T-Logg 100 T-Logg 100 T-Logg 100 E GREISINGER electronic GmbH D - 93128 Regenstauf, Hans-Sachs-Straße 26 +49 (0) 9402 / 9383-0

More information