Technical Information RIA15
|
|
- Amos Watts
- 6 years ago
- Views:
Transcription
1 T004K/09/EN/ Products Solutions Services Technical nformation RA5 Loop-powered 4 to 0 ma with optional HART communication Compact with very low voltage drop for universal use to display 4 to 0 ma/hart signals Application Display of 4 to 0 ma measured values or optionally up to four of a sensor's HART process variables in all industries Use as primary or secondary HART master Panel-mount housing or field housing as local display Scalable display value our benefits No external power supply required Voltage drop V (HART.9 V) 5-digit measured value display with 7 mm (0.67 in) digit height with dimension and bar graph; background lighting can be activated Minimal installation depth Easy -key operation for configuring the device nternational approvals ATEX, ECEx, FM, CSA SL interference freeness acc. to EN 6508 GL marine approval
2 RA5 Function and system design Measuring principle The RA5 is integrated in the 4 to 0 ma or HART loop and transmits the measuring signal or HART process variables in digital form. The does not require an external power supply. t is powered directly from the current loop. The device meets the requirements of the HART Communication Protocol Specifications and can be used with devices with HART Revision 5.0. The LC display is easy to read even in bright sunlight and enables 5-digit, scalable measured value display. n addition to measured value display, the associated value dimension and a bar graph can be easily configured with simple -key operation. The device can also be operated with backlighting where necessary. n such cases pay attention to the higher voltage drop. Measuring system Zone 0,, Zone, Zone, RA5 as field and panel display A00895-EN nput Voltage drop Standard device with 4 to 0 ma communication Device with HART communication Display lighting.0 V.9 V additionally.9 V HART input impedance Rx = 40 kω Cx =. nf Measured variable Measuring range The input variable is either the 4 to 0 ma current signal or the HART signal. HART signals are not affected. 4 to 0 ma (scalable, reverse polarity protection) Max. input current 00 ma EndressHauser
3 RA5 Power supply Terminal assignment NOTCE SELV / Class device The device may only be powered by a power unit with an energy-limited circuit in accordance with EC 600-: 'SELV or Class circuit'. Device destroyed if current too high Do not operate the device at a voltage source without a current limiter. nstead, operate the device only in the current loop with a transmitter. Terminal Description Positive connection, current measurement - Negative connection, current measurement (without backlighting) Negative connection, current measurement (with backlighting) Auxiliary terminals (electrically connected internally) Functional grounding: Panel-mounted device: Terminal on the rear of the housing Field device: Terminal in the housing Connection 4 to 0 ma Connection without backlighting Connection with backlighting Connection with transmitter power supply and transmitter Transmitter power supply A A Transmitter power supply Connection with transmitter power supply and transmitter using the auxiliary terminal Transmitter power supply A A Transmitter power supply Connection with PLC and transmitter - - A00970 A0097 PLC PLC Connection without transmitter power supply directly in the 4 to 0 ma circuit to 0 ma power source A A to 0 ma power source EndressHauser
4 RA5 HART connection Circuit diagram / Description -wire sensor with and loop power supply, without backlighting R s DC A Sensor Power supply HART resistance -wire sensor with and loop power supply, with backlighting R s DC A Sensor Power supply HART resistance 4-wire sensor with and loop power supply, without backlighting 4 A HART resistance Current meter Sensor 4 Power supply 4-wire sensor with and loop power supply, with backlighting 4 A00957 HART resistance Current meter Sensor 4 Power supply 4 EndressHauser
5 RA5 Circuit diagram / Description Current output with and actor (e.g. actuator valve), without backlighting A00957 Actor Power supply Current output Current output with and actor (e.g. actuator valve), with backlighting A Actor Power supply Current output Multi-drop -wire sensors with process display unit and loop power supply R s DC A Sensors Power supply HART resistance Multidrop -wire sensors with process display unit and loop power supply, with backlighting R s DC A0097 Sensors Power supply HART resistance EndressHauser 5
6 RA5 Circuit diagram / Description -wire sensor with and active barrier RNN as loop power supply R s RNN O O- R A Sensor HART primary master HART resistance The HART communication resistor of 0 Ω in the signal line is always necessary in the case of a low-impedance power supply. t must be installed between the power supply and the display unit. A HART communication resistance module is available as an accessory ( ). Connection with optional HART communication resistance module Wiring / Description -wire sensor with and loop power supply, without backlighting R s DC A00089 HART communication resistance module Sensor Power supply -wire sensor with and loop power supply, with backlighting R s DC A HART communication resistance module Sensor Power supply 6 EndressHauser
7 RA5 Wiring / Description 4-wire sensor with and loop power supply, without backlighting A00087 HART communication resistance module Power supply 4-wire device Sensor 4-wire sensor with and loop power supply, with backlighting A00088 HART communication resistance module Power supply 4-wire device Sensor Supply voltage The display unit is loop-powered and does not require any external power supply. The voltage drop is V in the standard version with 4 to 0 ma communication,.9 V with HART communication and an additional.9 V if display lighting is used. Performance characteristics Reference operating conditions Reference temperature 5 C±5 C (77 F±9 F) Humidity 0 to 60 % relative humidity Maximum measured error nput Range Measured error of measuring range Current 4 to 0 ma Over range up to ma ±0. % Resolution nfluence of ambient temperature Warm-up period Signal resolution > bit < 0.0 %/K (0.0 %/ F) of measuring range 0 minutes EndressHauser 7
8 RA5 nstallation Mounting location Panel housing The device is designed for use in a panel. Required panel cutout 45x9 mm (.77x.6 in) Field housing The field housing version is designed for use in the field. The unit is mounted directly on a wall, or on a pipe with a diameter of up to " with the aid of an optional mounting bracket. An optional weather protection cover protects the device from the effects of weather conditions. Orientation Panel housing The orientation is horizontal. Field housing The device must be mounted in such a way that the cable entries point downwards. Environment Ambient temperature range Storage temperature Climate class Altitude Degree of protection Electromagnetic compatibility 40 to 60 C ( 40 to 40 F) At temperatures below 5 C ( F) the readability of the display can no longer be guaranteed. 40 to 85 C ( 40 to 85 F) EC , Class B Up to m (6 400 ft) above MSL in accordance with EC600- Panel housing P65 at front, P0 at rear Field housing P66, NEMA4x (aluminum housing) nterference immunity: As per EC66 (ndustrial Environments) / NAMUR NE Maximum measured error < % of MR nterference emission: As per EC66, Class B Electrical safety Class, overvoltage protection category, pollution degree 8 EndressHauser
9 RA5 Mechanical construction Design, dimensions Panel-mount housing (4.) 48 (.89) 4.75 (.68) 96 (.78) 7 (.46) 4.5 (0.8) mm (in) 89.5 (.5) Dimensions of the panel housing A0077 Required panel cutout 45x9 mm (.77x.6 in), max. panel thickness mm (0.5 in). Field housing (5.6) 55.5 (.9) 06.5 (4.9) 8.5 (.) mm (in) Dimensions of the field housing incl. cable glands (M6) A0077 Weight Panel-mount housing 5 g (0.5 lb.) Field housing Aluminum: 50 g (.5 lb) Plastic: 00 g (0.66 lb) Materials Panel-mount housing Front: aluminum Rear panel: polycarbonate PC Field housing Aluminum or plastic (PBT with steel fibers, antistatic) EndressHauser 9
10 RA5 Operability Local operation Display and operating elements of the Symbol: operating menu disabled Symbol: error Symbol: warning 4 Symbol: Communication active (only for HART option) 5 Operating keys "-", "", "E" 6 4-segment display for unit/tag 7 Bar graph with indicators for under range and over range 8 5-digit 7-segment display for measured value, digit height 7 mm (0.67 in), display range to A00779 The device is operated with the operating keys on the front of the housing. The device setup can be disabled with a 4-digit user code. f the setup is disabled, a padlock symbol appears on the display when an operating parameter is selected. A00776 A00774 Enter key; calling up the operating menu, confirming the option/setting parameters in the operating menu Selecting and setting values in the operating menu; pressing the - and keys simultaneously takes the user back up a menu level. The configured value is not saved (ESC) A00775 Certificates and approvals CE mark Ex approval Functional safety Marine approval HART communication The measuring system meets the legal requirements of the EU Directives. EndressHauser confirms that the device has been successfully tested by applying the CE mark. nformation about currently available Ex versions (ATEX, FM, CSA, etc.) can be supplied by your EH Sales Center on request. All explosion protection data are given in a separate documentation which is available upon request. SL interference freeness according to EN6508 (optional) GL marine approval (optional) The display unit is registered by the HART Communication Foundation. The device meets the requirements of the HART Communication Protocol Specifications, May 008, Revision 7.. This version is downwards compatible with all sensors/actuators with HART versions EndressHauser
11 RA5 Other standards and guidelines EC 6059: Degrees of protection provided by enclosures (P code) EC 600-: 00 cor 0 Safety requirements for electrical equipment for measurement, control and laboratory use EC 66 series: Electromagnetic compatibility (EMC requirements) NAMUR NE, NE4 Association for Standards for Control and Regulation in the Chemical ndustry Ordering information Detailed ordering information is available from the following sources: n the Product Configurator on the EndressHauser web site: Choose your country Products Select measuring technology, software or components Select product (picklists: measurement method, product family etc.) Device support (right-hand column): Configure the selected product The Product Configurator for the selected product is opened. From your EndressHauser Sales Center: Product Configurator - the tool for individual product configuration Up-to-the-minute configuration data Depending on the device: Direct input of measuring point-specific information such as measuring range or operating language Automatic verification of exclusion criteria Automatic creation of the order code and its breakdown in PDF or Excel output format Ability to order directly in the EndressHauser Online Shop Accessories Various accessories, which can be ordered with the device or subsequently from EndressHauser, are available for the device. Detailed information on the order code in question is available from your local EndressHauser sales center or on the product page of the EndressHauser website: EndressHauser
12 RA5 Device-specific accessories Protective cover 6 0 (7.9) 98 (.7) (.48) 05 (8.07) 5 Dimensions of the protective cover, dimension unit mm (in) A0077 Mounting kit for wall/ pipe mounting 80 (.5) 8 (.) 5 (4.5).5 (0.45) 6 Dimensions of the mounting bracket, dimension unit mm (in) A00780 HART communication resistance module 54 (.) (0.87) 8. (0.) 4 (0.94) (.) 7 A Dimensions of the communication resistance module, dimension unit mm (in) Documentation System Components and Data Managers - Solutions for the loop: FA0006K/09 Operating instructions Process display unit RA5: BA007K/09 Operating instructions Process display unit RA5 with HART communication: BA070K/09 Ex Safety nstructions: ATEX/EC ()G Ex ia C T6: XA008R/09 EndressHauser
13
14
15
16
Technical Information RIA16
TI00144R/09/EN/02.13 71217088 Products Solutions Services Technical Information Field indicator Loop-powered field indicator for looping into the 4 to 20 ma current circuit Application Oil & gas Petrochemical
More informationTechnical Information RIA16
TI00144R/09/EN/04.14 71251374 Products Solutions Services Technical Information RIA16 Field indicator Looppowered field indicator for looping into the 4 to 20 ma current circuit Application Oil & gas Petrochemical
More informationEngyVolt RV12 and RV15
Technical Information EngyVolt RV12 and RV15 Multifunctional electrical energy meters for top-hat rail installation or panel mounting Application For measuring voltage, frequency, current, power, as well
More informationitemp TMT180 Technical information
Technical information itemp TMT180 Temperature head transmitter For resistance thermometers Pt100, settable using a PC, for installation in a sensor head Form B Application PC programmable (PCP) Temperature
More information4 â RIA251. Technical Information. Process display Digital loop powered display for ma current loops
Technical Information RIA251 Process display Digital loop powered display for 4...20 ma current loops Application Plant and machine construction Control panels Laboratory fittings Process display, monitoring
More informationTechnical Information Promonitor NRF560
TI00462G/08/EN/03.14 71264171 Products Solutions Services Technical Information For tank side monitor and control of Proservo NMS5 intelligent tank gauge Application is a monitoring unit for use with Proservo
More informationOperating Instructions Soliswitch FTE20
BA01069F/09/EN/05.15 71307741 Products Solutions Services Operating Instructions Soliswitch FTE20 Point level switch Soliswitch FTE20 Table of contents Table of contents 1 Important document information...
More information4 â Active barrier RN221N with optional HART diagnosis. Technical Information
Technical Information Active barrier with optional HART diagnosis Active barrier with power supply for safe separation of 4 to 20 ma current circuits Application Galvanic isolation of 4 to 20 ma current
More informationProcess display RIA 251. Digital loop powered display for ma current loops. Application areas. Plant and machine construction.
Technical information TI 063R/09/en Mat. No. 510 00857 Process display RIA 251 Digital loop powered display for 4...20 ma current loops Application areas Plant and machine construction Control panels Laboratory
More informationLiquipoint T FTW31, FTW32
TI00375F/00/EN/14.16 71336942 Products Solutions Services Technical Information Liquipoint T FTW31, FTW32 Conductive Point level switch for multiple point detection in conductive liquids Applications The
More informationOperating Instructions
Operating Instructions t i SPAN NOT USED - - 4...20mA DISPLAY t i SPAN END POINT DISPLAY Ð - 4...20mA p Safety information, Note Ex area Safety information Please read this manual carefully, and also take
More informationWirelessHART Adapter SWA70
Technical Information WirelessHART Adapter SWA70 Intelligent WirelessHART interface module for connection to 4...20 ma/hart devices Application WirelessHART Adapter SWA70 is a battery powered, interface
More informationTermination Board FC-GPCS-SAI16-PF. Features. Assembly. Function. Connection. SAI-1620m HART 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.
Features Assembly System board for Honeywell Safety Manager For 6-channel AI card SAI-60m For 6 modules Recommended module: HiC05 (AI) 4 V DC supply Hazardous area: pluggable screw terminals, blue Non-hazardous
More informationFlow Measurement SITRANS F M. Transmitter MAG 6000 I/6000 I Ex de. 3/46 Siemens FI
Overview The MAG 6000 I/6000 I Ex de is a microprocessorbased transmitter with a buildin alphanumeric display in several languages. The transmitters evaluate the signals from the associated electromagnetic
More informationDigital Output Module 8-Channel Version for Zone 2 Series 9475/
> 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Line fault monitoring per channel > Diagnostics based on NE107 > Module can be replaced in
More informationDigital Output Module 8-Channel Version for Zone 2 Series 9475/
> 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Line fault monitoring per channel > Diagnostics based on NE107 > Module can be replaced in
More informationSITRANS F C. Transmitter MASS 6000 Ex d compact/remote 3/195
Overview MASS 6000 is based on the latest developments within digital signal processing technology engineered for high performance, fast flow step response, fast batching applications, high immunity against
More informationtechnical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas
technical datasheet technical datasheet MTL0 Displays Loop-powered indicators for hazardous areas Loop powered -0mA Field and panel mounting Environmental protection to IP7 Easy to configure Number of
More informationDigital Output Module 4-Channel Version for Zone 1 Series 9475/
www.stahl.de > 4-channel digital output > Intrinsically safe outputs Ex ib > Suitable for Ex i hydraulic valves and solenoid valves > Additional Ex i control input for (in accordance with IEC 61508 through
More informationSegment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.
egment Protector for Cabinet nstallation Features Assembly 4... 12 outputs Ex ic (FCO or Entity) or non-incendive (Div 2) Advanced fault isolation at the spur egment Protector in Zone 2/Div. 2 nstruments
More informationTechnical Information Fieldgate SFG500
TI00029S/04/EN/10.16 71324508 Products Solutions Services Technical Information Fieldgate SFG500 Smart Ethernet/PROFIBUS gateway Parallel access to PROFIBUS networks Monitoring of PROFIBUS and HART device
More informationDigital Output Module 8-Channel Version for Zone 1 Series 9475/
www.stahl.de > 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Additional Ex i control input for "Plant STOP" (acc. IEC61508 up to SIL2) >
More informationTechnical Data. General specifications. Rated operating distance s n 3 mm
0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection ATEX & IECEX certifications Usable up to SIL 2 acc. to IEC 61508 Weatherproof
More informationTermination Board FC-GPCS-RIO16-PF. Features. Assembly. Function. Connection USIO/UPIO 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.
Features Assembly System board for Honeywell Universal Safety IO System board for Honeywell Universal Process IO For 6-channel cards USIO and UPIO For 6 modules Recommended modules: HiC8R (DI), HiC85R
More informationDigital Output Module 4-Channel Version for Zone 1 Series 9475/
www.stahl.de > 4-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Additional Ex i control input for "Plant STOP" (acc. IEC61508 up to SIL2) >
More informationAssembly. Front view. LED yellow: Relay output. LED red: LB/SC Power Rail
Switch Amplifier Features Assembly -channel isolated barrier 4 V DC supply (Power Rail) Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL
More informationOperating Instructions 12/2010 MN Z-EN XV-152 MICRO PANEL
Operating Instructions 12/2010 MN04802006Z-EN MICRO PANEL 2 Device description 2.3 Device versions 2.3 Device versions Fig. 1 MICRO PANELs are available in the following versions: Basic device Display
More informationTechnical Information WirelessHART Adapter SWA70. Smart WirelessHART interface module with power supply for field devices. Products Solutions Services
TI00026S/04/EN/18.15 71279737 Products Solutions Services Technical Information WirelessHART Adapter SWA70 Smart WirelessHART interface module with power supply for field devices Application The WirelessHART
More information4 Remote I/O. Analog Output Module HART Ex i / I.S. Outputs, 8 Channels Series 9466/12
0 4 Remote I/O 8 channels for controlling HART control valves and positioners Intrinsically safe outputs Ex ia IIC Galvanic isolation between outputs and system Open-circuit and short-circuit monitoring
More informationSegment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.
egment Protector for Cabinet nstallation Features Assembly 4... 12 outputs Ex ic (FCO or Entity) or non-incendive (Div 2) Advanced fault isolation at the spur egment Protector in Zone 2/Div. 2 nstruments
More informationLMP 308. Separable Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO / 0.
LMP 08 Separable Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.25 % FSO / 0. % FSO Nominal pressure from 0... mh 2 O up to 0... 250 mh 2 O Output signals 2-wire:
More informationTermination Board. HiCTB08-SCT-44C-SC-RA. Features. Assembly. Function. Connection. 24 V DC (I), 24 V DC (II), Fault. Zone 0, 1, 2 Div.
Termination Board HiCTB08-SCT-C-SC-RA Features Assembly For 8 modules V DC supply Supported signal types: DI/DO/AI/TI/AO Hazardous area: screw terminals, blue Safe area: screw terminals, black Function
More informationPressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2
Electronic pressure measurement Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2 WIKA data sheet PE 81.53 Applications Test bench construction Water jet
More informationTFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5
EN/2018-03-14 Design and specifications subject to change without notice Operating instructions for temperature sensor English page 1...5 Field of application CombiTemp is a temperature sensor, based on
More informationData Sheet T 8493 EN. Series 3793 TROVIS 3793 Electropneumatic Positioner with HART communication
Data Sheet T 8493 EN Series 3793 TROVIS 3793 Electropneumatic Positioner with HART communication Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Self-calibrating,
More informationLiquipoint T FTW 31, FTW 32 Level limit switch for multiple point detection in conductive liquids
Technical Information Level limit switch for multiple point detection in conductive liquids Applications The Liquipoint T sensors are used in conductive liquids (down to 0 µs/cm) for determining level
More informationTechnical Information WirelessHART Fieldgate SWG70
TI00027S/04/EN/14.14 71247524 Products Solutions Services Technical Information WirelessHART Fieldgate SWG70 Intelligent WirelessHART gateway with Ethernet and RS-485 interfaces Application Fieldgate SWG70
More informationLevel sensor Stainless steel version Model RLT-1000, for industrial applications
Level measurement Level sensor Stainless steel version Model RLT-1000, for industrial applications WIKA data sheet LM 50.02 Applications Level measurement of liquids in machine building Control and monitoring
More information2 Device description. 2 Device description 2.1 Function. 2.1 Function. 2.2 Intended use. 2.3 Device versions
2 Device description 2.1 Function 2 Device description 2.1 Function MICRO PANELs can be used as HMI devices or as integrated HMI/PLC devices. 2.2 Intended use MICRO PANELs are primarily used in machine
More informationTechnical Information Memobase Plus CYZ71D
TI00502C/07/EN/02.13 71228167 Products Solutions Services Technical Information Memobase Plus CYZ71D Multichannel multiparameter software for liquid analysis with digital Memosens sensors Measure - Calibrate
More informationTechnical Information Memobase Plus CYZ71D
TI00502C/07/EN/01.12 71162017 Products Solutions Services Technical Information Multichannel multiparameter software for liquid analysis with digital Memosens sensors Measure - Calibrate - Document - Improve
More informationMODEL: 6DV-B. [2] TERMINAL BLOCK 0: None (Euro terminal block at the rear of indicator module)
Field-mounted Two-wire Signal Conditioners 6-UNIT -DIGIT LOOP POWERED INDICATOR (outdoor enclosure, intrinsically safe/explosion-proof) Functions & Features -digit LED display No external power source
More informationCombiView DFON Graphical display
Main features with backlight Showing errors and limits by steady or flashing colours Fits Baumer CombiSeries TM (Ø80 mm FlexHousing) Hygienic design Option: Two configurable relay outputs Programmable
More informationTechnical Information Minicap FTC260, FTC262
TI00287F/00/EN/16.16 71312209 Products Solutions Services Technical Information Minicap FTC260, FTC262 Capacitive Point level switch with buildup compensation No calibration necessary Application The Minicap
More informationMicro Motion Model 2200S 2-Wire Transmitter with MVD Technology
Product Data Sheet PS-001094, Rev. C September 2009 Micro Motion Model 2200S 2-Wire Transmitter with MVD Technology The Micro Motion Model 2200S 2-wire transmitter enables the use of reliable and accurate
More information5 Fieldbus Technology
5 Fieldbus Technology Ex e / Ex i 10922E00 The s Ex e/ex i connect intrinsically safe Foundation Fieldbus H1 or Profibus PA field devices to a non-intrinsically safe / Ex e trunk. Up to four intrinsically
More informationFlow Measurement SITRANS F C
Overview MASS 6 is based on digital signal processing technology engineered for high performance, fast flow step response, fast batching applications, high immunity against process noise, easy to install,
More informationABL1REM24025 regulated SMPS - single phase V input - 24 V output - 60 W
Characteristics regulated SMPS - single phase - 100..240 V input - 24 V output - 60 W Main Range of product Product or component type Power supply type Rated power in W Input voltage Output voltage Power
More informationTechnical Information HAW562
TI00K/09/EN/5. 75536 Products Solutions Services Technical Information HAW56 Surge arresters for DIN rail according to EN 6075 Application Surge arresters are used to weaken residual currents from upstream
More informationRA33. Technical Information. Batch controller For the batching and dosing of mass and volume
Technical Information RA33 Batch controller For the batching and dosing of mass and volume Highlights Swift commissioning and easy operation with plaintext display in selectable language Valve control
More informationSITOP in the SIMATIC Design
Siemens AG 2017 /2 Introduction /3 1-phase, 24 V DC (for S7-300 and ET 200M) /9 1-phase, 24 V DC (for S7-1200) /11 1-phase, 24 V DC (for S7-1500 and ET 200MP) /14 3-phase, 24 V DC (ET 200pro) Siemens KT
More informationD6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D
D600S - D600D INSTRUCTI MANUAL SIL Switch/Proximity Detector Repeater Relay, DIN Rail, Models D600S, D600D D600 - SIL Switch/Proximity Detector Repeater Relay G.M. International ISM0- Characteristics General
More informationMINI MCR-SL-UI-2I-NC. Extract from the online catalog. Order No.:
Extract from the online catalog MINI MCR-SL-UI-2I-NC Order No.: 2864176 4-way signal duplicator for electrical isolation and duplication of analog signals with screw connection, standard configuration
More informationTHE BARRIER and the Universal Barrier Cabinets from Pepperl+Fuchs
THE BARRIER and the Universal Barrier Cabinets from Pepperl+Fuchs Overview This document provides information relating to the use of THE BARRIER HiC2, the SMART universal barrier from Pepperl+Fuchs, a
More informationTechnical Information WirelessHART Adapter SWA70. Smart WirelessHART interface module with power supply for field devices. Products Solutions Services
TI00026S/04/EN/21.16 71339584 Products Solutions Services Technical Information WirelessHART Adapter SWA70 Smart WirelessHART interface module with power supply for field devices Application The WirelessHART
More informationProduct type designation. Control elements. Installation type/mounting
Datasheet SIMATIC HMI KP32F PN, KEY PANEL, 32 SHORT-STROKE KEYS WITH MULTI-COLOR LED'S, PROFINET INTERFACES WITH PROFISAFE, 16DI+16DI/DO, 4 SAFETY DI PINS, 24V DC LOOP THROUGH CONFIGURABLE FROM STEP7 V5.5
More informationMODEL: 6DV-B. [2] TERMINAL BLOCK 0: None (Euro terminal block at the rear of indicator module)
Field-mounted Two-wire Signal Conditioners 6-UNIT -DIGIT LOOP POWERED INDICATOR (outdoor enclosure, intrinsically safe/explosion-proof) Functions & Features -digit LED display No external power source
More informationFlow Measurement SITRANS F C
Overview MASS 6 is based on digital signal processing technology engineered for high performance, fast flow step response, fast batching applications, high immunity against process noise, easy to install,
More informationSeries 3793 TROVIS SAFE 3793 Electropneumatic Positioner with HART communication
Series 3793 TROVIS SAFE 3793 Electropneumatic Positioner with HART communication Application Single-acting or double-acting positioner for attachment to pneumatic on/off valves in safety-instrumented systems.
More informationTechnical Information Liquipoint FTW23
TI0202F/00/EN/04.6 736230 Products Solutions Services Technical Information Capacitance point level measurement Point level switch for liquids in the food and beverage industry Application The is a point
More informationOnline data sheet TBS-1BSGT3506FM TBS TEMPERATURE SENSORS
Online data sheet TBS-1BSGT3506FM TBS A B C D E F Illustration may differ Detailed technical data Features Ordering information Type Part no. TBS-1BSGT3506FM 6053202 Other models and accessories www.sick.com/tbs
More informationSeries 3730 Electropneumatic Positioner Type
Series 3730 Electropneumatic Positioner Type 3730-0 Application Single-acting or double-acting positioner for attachment to pneumatic control valves Reference variable Travels 4 to 20 ma 5.3 to 200 mm
More informationDINALOG A 144 x 36 A1400 Light-Strip Indicator
DINALOG A x 6 A00 Light-Strip Indicator -9-0-0 /.00 Front panel dimensions: x 6 mm Light-strip indicator with 7 high-contrast LEDs Red LED display color Digital display range for portrait format: 999 to
More informationSeries 3731 Type Electropneumatic Ex d Positioner with HART communication
Series 3731 Type 3731-3 Electropneumatic Ex d Positioner with HART communication Application Single-acting or double-acting Ex d positioner for attachment to pneumatic control valves. Self-calibrating,
More informationTechnical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection
NCN-FK-N-V-V 002 Model Number NCN-FK-N-V-V Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting EC-Type Examination Certificate TÜV99
More informationElectropneumatic Positioner Type and Type with HART communication
Electropneumatic Positioner Type 3730-2 and Type 3730-3 with HART communication Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Self-adjusting, automatic
More informationHMT360 Series Intrinsically Safe Humidity and Temperature Transmitters
HMT360 Series Intrinsically Safe Humidity and Temperature Transmitters For operation in up to Zone 0 / 20 Features Measures humidity and temperature, outputs also dew point, mixing ratio, absolute humidity
More informationABL1REM24062 regulated SMPS - single phase V input - 24 V output W
Characteristics regulated SMPS - single phase - 100..240 V input - 24 V output - 150 W Product availability : Stock - Normally stocked in distribution facility Price* : 143.00 USD Main Range of product
More informationAssembly. max Example: 2-wire connection IH More connection types see section electrical connections. Auxiliary voltage.
Guided Level Radar Features Measurement independent of density, temperature, and dust Measurement also possible with foam on the surface Simple, menu-guided on-site operation with four-line plain text
More informationAssembly. Front view. LED yellow/red: Status output Ι/ Fault signal Function. Switch Power Rail
Switch Amplifier KCD-SR-Ex.LB Features Assembly -channel isolated barrier V DC supply (Power Rail) Dry contact or NAMUR inputs Usable as signal splitter ( input and outputs) Relay contact output Fault
More informationFlow Measurement SITRANS F M
Overview Mode of operation The flow measuring principle is based on araday s law of electromagnetic induction according to which the sensor converts the flow into an electrical voltage proportional to
More informationTemperature process values at a glance
Temperature process values at a glance PERFORMANCE MADE SMARTER COMMUNIC AT I ON F OUND AT I O N TEMPERATURE I.S. INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY 7501 Field mounted
More informationUFD 5. Display for ALTOSONIC 5. Technical Datasheet. Configurable display for ALTOSONIC 5 Easy installation Durable design
UFD 5 Technical Datasheet Display for ALTOSONIC 5 Configurable display for ALTOSONIC 5 Easy installation Durable design KROHNE 04/2015-0.00000.00.00 CONTENTS UFD 5 1 Product features 3 1.1 Local display
More informationInductive angle sensor with analog output Ri360P1-DSU35TC-ELi-Exi
ATEX category II 2 G, Ex Zone 1 ATEX category II 2 D, Ex Zone 21 Rectangular, housing DSU35 Plastic, PP-GF30-VO Detection of angular range 0 to 360 P1-Ri-QR14 positioning element included in delivery Measuring
More informationRedundancy unit CP-A RU
2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power
More informationFlow Measurement SITRANS F US Inline
Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication
More informationFlow Measurement SITRANS F US Inline
Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication
More informationAssembly MAU. MUX 4 Channels 8 Channels Zone 1
Multi-Input/Output Device for Cabinet Installation Features Assembly For discrete inputs and outputs Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus acc.
More informationSensor boxes SRBC. Festo core product range Covers 80% of your automation tasks
Sensor boxes SRBC q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement and storing complexity
More informationSITOP 3-phase 24 V DC, 20 to 40 A
Siemens AG 2013 SITOP 3-phase, 20 to 40 A /2 SITOP 20 A /2 SITOP 20 A /2 20 A /3 SITOP PSU300B 30 A /3 SITOP 40 A /3 SITOP 40 A /3 40 A /8 Ordering data and further information For AL and ECCN export regulations
More informationLineMaster 100. Continuous-line Recorder. ABB Instrumentation 10/ EN
LineMaster 100 Continuous-line Recorder 10/43-1.10 EN 1 to 4 measuring channels Format 144 mm x 144 mm; installed depth 250 mm Combined chart unit for roll chart (32 m) or folded chart paper (16 m) Measuring
More informationPanelView Plus/VersaView CE Terminals and Display Modules
Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3
More informationFieldIT Multi Barrier NMB204/NMB204-EX (MB 204/MB 204-Ex)
Data Sheet FieldIT Multi Barrier NMB204/NMB204-EX (MB 204/MB 204-Ex) Intrinsically safe power supply of up to 31 stations on the bus cascadable multi barrier Intrinsically safe connection of up to 4 field
More informationMinilog RDL10. Technical Information. Measured value collector with 2 input channels for storing analog and digital values
Technical Information Minilog RDL10 Measured value collector with 2 input channels for storing analog and digital values Application Data storage for termperature, humidity, pressure, flow, level, and
More informationT EN TROVIS Electropneumatic Positioner
T 8484-1 EN TROVIS 3730-1 Electropneumatic Positioner Application Single-acting positioner for attachment to pneumatic globe and rotary valves. Self-calibrating, automatic adaptation to valve and actuator.
More informationSIY. Features. PC-Programmable Signal Isolator/Converter
September 2017 Description Moore Industries Signal Isolator/Converter combines smart digital technology with advanced analog operation to deliver superior reliability, accuracy, and ease of use. The highly
More informationFlow Measurement SITRANS F M
low sensor MAG P Overview Mode of operation The flow measuring principle is based on araday s law of electromagnetic induction according to which the sensor converts the flow into an electrical voltage
More informationABL1REM Main. Rated power in W. Power supply output current V. <= 100 Aat 230 V AC. 2.5 Aat 240 V
Product datasheet Characteristics ABL1REM24062 Complementary Input voltage limits Network frequency Inrush current Main Cos phi 0.65 Range of product Product or component type Power supply type Rated power
More informationExBin-D Transducers for ExPro-B... sensors (probes) ExPro-B... Thermostats / humidistats ( C, % rh)
Transducers for ExPro-B... sensors (probes) ExPro-B... Thermostats / humidistats ( C, % rh) Electrical, explosion proof transducers only connectable to ExPro-B... thermostats and humidistats 24 VAC/DC
More informationReed sensor For bypass level indicators Model BLR
Level measurement Reed sensor For bypass level indicators Model BLR WIKA data sheet LM 10.04 for further approvals see page 3 Applications Sensor for the continuous level measurement of liquids in bypass
More informationTechnical Information EngyCal RS33
TI00154K/09/EN/02.13 71241342 Products Solutions Services Technical Information EngyCal RS33 Steam calculator For recording and billing the steam mass and energy flow in applications with saturated steam
More information4 Remote I/O. Digital Output Module 8-Channel Version Type 9475/ from Rev. F
4 Remote I/O Digital Output Module 8-Channel Version 8 channels for Ex i solenoid valves, piezo and booster-valves Intrinsically safe Ex ia IIC outputs Additional input for Plant-STOP available (acc. to
More informationTMT470L Temperature Transmitter
Technical information TMT470L Temperature Transmitter OEM components for compact thermometer/cable transmitter. 2/3 or 4-wire Pt100 can be connected. 4 to 20 ma transmitter, programmable via PC. Application
More informationCombiTemp TFRN/TFRH. Operating instructions. Temperature sensor. Operating Instructions: EN.
EN/2017-04-03 Design and specifications subject to change without notice English page 1 8 Field of application CombiTemp TFRx is a temperature sensor, based on RTD technology, which is designed and produced
More informationRoom unit with PPS2 interface
1 626 Room unit with PPS2 interface for use with: controllers with a PPS2 interface QAA88.3 Room temperature measurement Key buttons for adjustment of the room temperature setpoint Key buttons for operating
More informationMINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description
Repeater power supply, active Data sheet 09_en_0 PHOENIX CONTACT 0--0 Description The. mm wide... repeater power supply supplies transmitters in the field and electrically isolates the input signal from
More informationSEM310 SEM310X HART UNIVERSAL TEMPERATURE TRANSMITTER
HART 5,6,7 COMPATABLE UNIVERSAL INPUT, DUAL CHANNEL ATEX & IEC Ex Version MATHS FUNCTIONS FLASH TESTED TO 4 KV DC INTRODUCTION The SEM310 is a HART 5 upwards, (generic device) compatible universal transmitter.
More informationSeparating and protective. Separating and protective instruments. VEGATRENN 149AEx Separator type KFDO Barrier type Product Information
Separating and protective instruments Separating and protective instruments VEGATRENN 149AEx Separator type KFDO Barrier type 9001 Product Information Content Content 1 Product description..........................................................................
More informationSeries 3730 Type Electropneumatic Positioner
Series 3730 Type 3730-0 Electropneumatic Positioner Application Single-acting or double-acting positioner for attachment to pneumatic control valves Set point Travel 4 to 20 ma 5.3 to 200 mm The positioner
More informationSafety Instructions Cerabar S PMP71, PMP75
/00/EN/01.14 71249311 Products Solutions Services Safety Instructions PMP71, PMP75 4-20 ma HART, PROFIBUS PA, FOUNDATION Fieldbus Ex d IIC T* Gb TÜV 13.0902X Segurança TÜV INMETRO OCP 0004 Document: Safety
More information