CPX terminal Electronics manual Manual

Size: px
Start display at page:

Download "CPX terminal Electronics manual Manual"

Transcription

1 CPX terminal Electronics manual CPX field bus node Type CPX-FB13 Field bus protocol PROFIBUS-DP as per EN Manual en 0112NH [ ]

2

3 Contents and general instructions Authors... U.Reimann,U.Gräff Editors... H.-J. Drung, M. Holder Original... de Translation... transline Deutschland Layout... Festo AG & Co., Dept. KG-GD Type setting... KI-DT Edition... en 0112NH Designation... P.BE-CPX-FB13-EN Order no E (Festo AG & Co., D Esslingen, Federal Republic of Germany, 2002) Internet: service_international@festo.com The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights are reserved, in particular the right to carry out patent, utility model or ornamental design registration. I

4 Contents and general instructions II

5 Contents and general instructions Contents Designated use... Target group... Service... Notesontheuseofthismanual... Important user instructions... VII VIII VIII VIII IX 1. Installation General instructions on installation Settings of the DIL switches on the field bus node Removing and fitting the cover over the DIL switches Setting the DIL switches Connecting the field bus Field bus cable Field bus baud rate and field bus length Connecting the field bus Bus termination with terminating resistors Optical-fibre waveguide connection for PROFIBUS-DP Pin assignment of power supply Commissioning Configuration General information Preparing the CPX terminal for the configuration Device master file (GSD) and symbol files Configuration with a Siemens master Parametrizing Parametrizing when the terminal is switched on Parametrizing the CPX terminal with STEP Parametrizing with the handheld Application example of parametrizing Commissioning the CPX terminal in the system Faultless commissioning, normal operating status III

6 Contents and general instructions 3. Diagnosis Overview of diagnostic possibilities Diagnosis via LEDs Fault displays of the bus fault/status LED BF Error displays of the LEDs for system diagnosis PS, PL, SF, M Diagnosis via status bits Diagnosis via the I/O diagnostic interface Diagnosis via PROFIBUS-DP Diagnostic steps Overview of diagnostic bytes Details on standard diagnostic information Module-related diagnosis Channel-related diagnosis Error treatment ( Fail safe ) Siemens SIMATIC S5/S Online diagnosis with STEP Read diagnostic buffer with STEP 7 (version 4.x, 5.1) Read device-specific diagnosis with STEP 7 (version 5.1) A. Technical appendix... A-1 A.1 Technical specifications of field bus node CPX-FB13... A-3 A.2 Operation with the general DP master... A-4 A.2.1 Bus start... A-4 A.2.2 Send parametriziung data... A-5 A.2.3 Send configuration data... A-7 A.2.4 Error treatment... A-10 A.2.5 Request diagnostic information... A-10 A.2.6 Start cyclic exchange of data... A-10 A.2.7 Implemented functions and service access points (SAP)... A-12 A.2.8 Bus parameters/reaction times... A-13 A.2.9 Transmission times on the PROFIBUS-DP... A-13 A.3 Access to the CPX terminal via DPV1... A-14 A.3.1 Reading and writing data records... A-14 A.3.2 Data records... A-17 IV

7 Contents and general instructions B. Index... B-1 B.1 Index... B-3 V

8 Contents and general instructions VI

9 Contents and general instructions Designated use The field bus node type CPX-FB13 described in this manual has been designed exclusively for use as a slave on the PROFIBUS-DP. The CPX terminal may only be used as follows: in accordance with designated use in its original state without any modifications by the user in faultless technical condition. The maximum values specified for pressures, temperatures, electrical data, torques etc. must be observed. Please comply with national and local safety laws and regulations. VII

10 Contents and general instructions Target group This manual is intended exclusively for technicians trained in control and automation technology, who have experience in installing, commissioning, programming and diagnosing slaves on the PROFIBUS-DP. Service Please consult your local Festo service centre if you have any technical problems. Notesontheuseofthismanual This manual contains specific information on installing, configuring, parametrizing, commissioning, programming and diagnosing with the CPX field bus node for PROFIBUS-DP. Further information on the PROFIBUS-DP can be found in: The setting up guidelines for the PROFIBUS-DP The manuals from the master manufacturer VIII

11 Contents and general instructions Important user instructions Danger categories This manual contains instructions on the possible dangers which may occur if the product is not used correctly. These instructions are marked (Warning, Caution, etc.), printed on a shaded background and marked additionally with a pictogram. A distinction is made between the following danger warnings: Warning This means that failure to observe this instruction may result in serious personal injury or damage to property. Caution This means that failure to observe this instruction may result in personal injury or damage to property. Please note This means that failure to observe this instruction may result in damage to property. The following pictogram marks passages in the text which describe activities with electrostatically sensitive components. Electrostatically sensitive components may be damaged if they are not handled correctly. IX

12 Contents and general instructions Marking special information The following pictograms mark passages in the text containing special information. Pictograms Information: Recommendations, tips and references to other sources of information. Accessories: Information on necessary or sensible accessories for the Festo product. Environment: Information on environment-friendly use of Festo products. Text markings The bullet indicates activities which may be carried out in any order. 1. Figures denote activities which must be carried out in the numerical order specified. Hyphens indicate general activities. X

13 Contents and general instructions Type Title Description Electronics Manual Pneumatics Manual System manual type P.BE-CPX-SYS-... CPX I/O modules type P.BE-CPX-EA-... CPX field bus node type P.BE-CPX-FB... Valve terminals with CPA pneumatics type P.BE-CPA-... Valve terminals with Midi/Maxi pneumatics type P.BE-Midi/Maxi Overview of structure, components and method of operation of CPX terminals; installation and commissioning instructions as well as basic principles of parametrization Connection technology and instructions on fitting, installing and commissioning both input and output modules of type CPX-... as well as CPA and Midi/Maxi pneumatic interfaces Instructions on fitting, installing and diagnosing the appropriate field bus node Instructions on fitting, installing and commissioning CPA pneumatics (type 12) Instructions on fitting, installing and commissioning CPA Midi/Maxi pneumatics (type 03) Tab. 0/1: Manuals on the CPX terminal XI

14 Contents and general instructions The following product-specific terms and abbreviations are used in this manual: Term/abbreviation A0 h CP CP modules CPX terminal DIL switches DPV1 Field bus node Handheld I I/O modules I/Os O Octet Output byte PLC/IPC Pneumatic interface Meaning Hexadecimal numbers are marked by a low-set h. Compact performance CommontermforthevariousmoduleswhichcanbeincorporatedinaCPX terminal. CompletesystemconsistingofCPXmoduleswithorwithoutpneumatics. Dual-in-line switches consist of several switch elements with which settings can be made. PROFIBUS extension for acyclic access to system data during running time. Provides the connection to specific field buses. Transmits control signals to the connected modules and monitors their ability to function. Handheld programmer for commissioning and service purposes. Digital input Common term for the CPX modules which provide digital inputs and outputs. Digital inputs and outputs Digital output Number of address bytes assigned by the CPX terminal. Output byte Programmable logic controller/industrial PC The pneumatic interface is the interface between the modular electric periphery and the pneumatics. Tab. 0/2: Product-specific terms and abbreviations XII

15 Installation Chapter 1 1-1

16 1. Installation Contents 1. Installation General instructions on installation Settings of the DIL switches on the field bus node Removing and fitting the cover over the DIL switches Setting the DIL switches Connecting the field bus Field bus cable Field bus baud rate and field bus length Connecting the field bus Bus termination with terminating resistors Optical-fibre waveguide connection for PROFIBUS-DP Pin assignment of power supply

17 1. Installation Contents of this chapter In this chapter you will find information on setting the CPX field bus node with DIL switches the connection to the field bus the pin assignment of the power supply. Further information Information on fitting and installing the complete CPX terminal can be found in the CPX system manual (P.BE-CPX-SYS-..). Information on installing the I/O modules and the pneumatic interfaces can be found in the manual for the CPX pneumatic interfaces and the CPX I/O modules (P.BE-CPX-EA-..). Instructions on installing the pneumatics can be found in the relevant pneumatics manual. 1-3

18 1. Installation 1.1 General instructions on installation Warning Before carrying out installation and maintenance work, switch off the following: the compressed air supply the operating voltage supply for the electronics/sensors the load voltage supply for the outputs and valves. You can thereby avoid: uncontrolled movements of loose tubing unexpected movements of the connected actuators non-defined switching states of the electronic components. Caution The CPX field bus node contains electrostatically sensitive components. Do not therefore touch any contacts. Observe the regulations for handling electrostatically sensitive components. You will then prevent the electronics from being damaged. Information on fitting the CPX terminal can be found in the CPX system manual (P.BE-CPX-SYS-..). 1-4

19 1. Installation Electrical connecting and display elements You will find the following electrical connecting and display elements on the CPX field bus node for PROFIBUS-DP: 4 BF PS PL SF M Bus status and CPX-specific LEDs 4 Service interface for handheld (V24) 2 Field bus connection (9-pin sub-d socket) 3 Cover of the DIL switches Fig. 1/1: Connecting and display elements on the CPX field bus node 1-5

20 1. Installation Fitting and removing The field bus node is fitted in a manifold sub-base of the CPX terminal (see Fig. 1/2). Removing Remove the field bus node as follows: 1. Loosenthe4screwsinthefieldbusnodewithaTorx screwdriver size T Pull the field bus node carefully and without tilting away from the contact rails of the manifold sub-base. 1 Field bus node CPX-FB Manifold sub-base 3 Contact rails 1 4 Screws 3 2 Fig. 1/2: Fitting/removing the field bus node 1-6

21 1. Installation Fitting Fit the field bus node as follows: 1. Place the field bus node in the manifold sub-base. Make sure that the grooves with the contact terminals on the bottom of the field bus node lie above the contact rails. Then push the field bus node carefully and without tilting as far as possible into the manifold sub-base. 2. Tighten the screws only by hand. Place the screws so that the self-cutting threads can be used. Tighten the screws with a Torx screwdriver size T10 with torque Nm. 1-7

22 1. Installation 1.2 Settings of the DIL switches on the field bus node In order to set the CPX field bus node you must first remove the cover over the DIL switches. Caution The CPX field bus node contains electrostatically sensitive components. Do not therefore touch any contacts. Observe the regulations for handling electrostatically sensitive components. You will then prevent the electronics in the node from being damaged Removing and fitting the cover over the DIL switches In order to set the CPX field bus node you must first remove the cover over the DIL switches. Removing 1. Switch off the power supply. 2. Unscrew the two fastening screws in the switch cover. 3. Lift up the cover. Fitting 1. Place the cover carefully on the node. Please note Make sure that the seal is seated correctly. 2. Tighten the two fastening screws at first by hand and then with torque Nm. 1-8

23 1. Installation Setting the DIL switches When you have removed the cover for the DIL switches, you will see three DIL switches in the field bus node (see Fig. 1/3). You can set the following parameters with the DIL switches: the PROFIBUS address the diagnostic mode. Proceed as follows: 1. Switch off the power supply. 2. Remove the cover over the DIL switches (section 1.2.1). 3. Assign an unused station number to the CPX terminal. Set the desired station number (8-position DIL switch, elements 1...7). 4. Set the diagnostic mode (8-position DIL switch, element 8). 5. Fit the cover again (section 1.2.1). 1-9

24 1. Installation 1 DIL switch 1: reserved 2 DIL switch 2: reserved 3 DIL switch 3: setting the diagnostic mode DIL switch 3: setting the station number Fig. 1/3: DIL switch in the field bus node Reserved DIL switches 1 and 2 Leave all switch elements of the 2-element DIL switches 1 and 2at: Reserved Fig. 1/4: Setting of the 2-element DIL switch 1-10

25 1. Installation Setting the diagnostic mode 3 The following diagnosis can be activated/deactivated with switch element 8 of the 8-element DIL switch 3: PROFIBUS-DP: Device-related diagnosis active/inactive If the device-related diagnosis is deactivated with switch element 8, no device-related diagnostic information about the CPX terminal will be sent to the master system, e.g. short circuitattheoutputsorundervoltageatthevalves(seesection 3.5). Device-related diagnosis active Device-related diagnosis inactive Fig. 1/5: Setting the diagnostic mode 1-11

26 1. Installation Setting the station number 4 Please note Station numbers may only be assigned once per field bus master. You can set the PROFIBUS address of the CPX terminal in binary coded form with the 8-element DIL switch 3. 1 Setting the station number (switch elements 1...7) Fig. 1/6: Setting the station number (8-element DIL switch) The following station numbers are permitted: Protocol Address identification Permitted station numbers PROFIBUS-DP PROFIBUS address 1;...; 125 Recommendation: Assign the station numbers in ascending order. Assign the station addresses to suit the machine structure of your system. 1-12

27 1. Installation Example: Set station number: 05 Example: Set station number: = 1+4= = = 38 Fig. 1/7: Examples of set station numbers (binary coded) The following pages contain a summary of the settings for the station numbers. 1-13

28 1. Installation Station no Station no reserved Tab. 1/1: Settings of station numbers : Position of the DIL switch elements 1-14

29 1. Installation Station no Station no Tab. 1/2: Settings of station numbers : Position of the DIL switch elements 1-15

30 1. Installation Station no Station no Tab. 1/3: Settings of station numbers : Position of the DIL switch elements 1-16

31 1. Installation Station no Station no Tab. 1/4: Settings of station numbers : Position of the DIL switch elements 1-17

32 1. Installation 1.3 Connectingthefieldbus Field bus cable Please note With incorrect installation and high baud rates, data transmission errors may occur as a result of signal reflexions and attenuations. Causes of the transmission errors may be: missing or incorrect terminating resistor incorrect screening connection branches transmission over long distances unsuitablecables. Observe the cable specifications. Refer to the manual for your controller for information on the type of cable to be used. Useatwistedscreened2-corecableforthefieldbusin accordance with PROFIBUS specification (EN 50170, cable type A): Surge impedance: Ohm ( MHz) Capacity: < 30 nf/km Loop resistance: < 110 Ohm/km Core diameter: > 0.64 mm Core cross-sectional area: > 0.34 mm 2 If the Festo IP65 plug is used, cables with a diameter of or mm are permitted. Bus length Exact specifications on the bus length can be found in section and in the manuals for your control system. 1-18

33 1. Installation Field bus baud rate and field bus length Please note The maximum permitted field bus length and branch line length depend on the baud rate used. Please observe the maximum permitted length of the field bus cable if you connect the CPX terminal via a branch line. Take into account also the sum of the branch line lengths when calculating the maximum permitted length of the field bus cable. The CPX terminal sets itself automatically to one of the following baud rates: Baud rate (in kbaud) Field bus length (max.) Max. permitted branch line length m 500 m m 500 m m 100 m m 33.3 m m 20 m m 6.6 m m Tab. 1/5: Max. field bus length and branch line length for PROFIBUS-DP depending on the baud rate. 1-19

34 1. Installation Connecting the field bus Please note If the CPX terminal is fitted onto the moving part of a machine, the field bus cable on the moving part must be provided with strain relief. Please observe also the relevant regulations in EN part 1. Thereisa9-pinsub-Dsocketonthefieldbusnodeforconnecting the CPX terminal to the field bus. This connection serves for the incoming and continuing field bus cable. You can connect the CPX terminal with the sub-d plug from Festo (part nos ). Bus connection Socket Pin Festo sub-d plug (IP65) PROFIBUS-DP Designation Housing - - B A - Cable clip Screening/shield n.c. RxD/TxD-P CNTR-P 1) DGND VP n.c. RxD/TxD-N n.c. Screening/shield Connection to functional earth not connected Receive/send data P Repeater control signal Data reference potential (M5V) Power supply positive (P5V) not connected Receive/send data N not connected Connection to functional earth 1) Repeater control signal CNTR-P is designed as a TTL signal. Tab. 1/6: Pin assignment of the field bus interface of the CPX field bus node 1-20

35 1. Installation Please note Please note that only the Festo plug complies with protection class IP65. Before connecting the sub-d plugs of other manufacturers: replace the two flat screws by bolts (type UNC 4-40/M3x6). Sub-D plugs from Festo A floating screening connection is intended with the sub-d plug from Festo: Clamp the screening/shield for the field bus cable under the cable clip of the Festo plug. The diagram below shows the pin assignment in the Festo sub-d plug. 1 Screening connection, cable clip 2 Only connected capacitively 3 CPX field bus node (smaller than actual size) 1 2 A B 4 4 Pin assignment in the plug A: RxD/TxD-N B: RxD/TxD-P 3 BF PS PL SF M not assigned not assigned Fig. 1/8: Sub-D plugs from Festo: Pin assignment and screening connection 1-21

36 1. Installation Please note The cable clip in the sub-d plug from Festo is connected internally only capacitively with the metallic outer ring of the plug. This is to prevent equalizing currents flowing through the screening of the field bus cable (Fig. 1/8). 1-22

37 1. Installation 1.4 Bus termination with terminating resistors Please note If the CPX terminal is at the beginning or end of the field bus system, a bus termination will be required. Fit a bus termination to both ends of the bus segment. Recommendation: Use the sub-d plug from Festo (part no ) for the bus termination. A suitable resistor network is incorporated in the housing of this plug. The bus termination must be switched manually with slide switches. 1 Blanking plug 2 Slide switch 1 2 A B A B not Bus termination switched on switched on Fig. 1/9: Switch for bus termination in the Festo sub-d plug 1-23

38 1. Installation 1 Switch in the Festo sub-d plug 1 2 Pin 6 2 Pin 6: Power supply 390 Ω 3 Pin 5: Data reference potential Receive/send data P (data cable B) Pin nh 220 Ω Receive/send data N (data cable A) Pin nh 390 Ω 1 3 Pin 5 Fig. 1/10: Circuit diagram for bus connection network for cable type A as per EN

39 1. Installation 1.5 Optical-fibre waveguide connection for PROFIBUS-DP Optical-fibre waveguide technology is to be recommended when transmission is affected by heavy interference, as well as for extending the transmission range when high baud rates are used. This also offers the following advantages: high EMC compatibility, ESD protection due to the optical transmission of signals protection against lightning potential isolation of the individual DP slaves. The PROFIBUS-DP interface of the CPX terminal has been designed in accordance with specification EN Volume 2, and can therefore be used for controlling network components for optical-fibre waveguides. Example of optical-fibre waveguide network components: Siemens Optical Link Module (OLM) for PROFIBUS plus Siemens Optical Link Plug (OLM) for PROFIBUS (IP20) HartingHan-InduNet Media converter IP65 in combination with adapter cable for Festo valve terminals (optical data transmission in DESINA installation concept). 1-25

40 1. Installation 1.6 Pin assignment of power supply Warning Use only power units which guarantee reliable isolation of the operating voltages as per IEC 742/EN 60742/VDE 0551 with at least 4 kv isolation resistance (Protected Extra Low Voltage PELV). Switch power packs are permitted, providing they guarantee reliable isolation in accordance with EN 60950/VDE By the use of PELV power units, protection against electric shock (protection against direct and indirect contact) is guaranteed in accordance with EN /IEC 204. Safety transformers with the adjacent symbol must be used for supplying PELV networks. The CPX terminal must be earthed to ensure that it functions correctly (e.g. EMC). The current consumption of a CPX terminal depends on the number and type of integrated modules and components. Read the information on power supply as well as on the earthing measures to be carried out in the CPX system manual. 1-26

41 1. Installation System supply and additional supply The load and operating voltages are supplied to the CPX terminal via the manifold sub-bases with system supply and additional supply type CPX-GE-EV-S or CPX-GE-EV Pin assignment 1: Operating voltage for electronics/ sensors (V EL/SEN ) 2: Load voltage for valves and outputs (V VAL /V OUT ) 3: 0 V : Earth/ground connection Fig. 1/11: Pin assignment of the system supply (manifold sub-base type CPX-GE-EV-S) 1 Pin assignment 1: Not connected 1 1 2: Load voltage 2 3: 0 V 4 4: Earth/ground connection 3 Fig. 1/12: Pin assignment of the additional supply (manifold sub-base type CPX-GE-EV-..) 1-27

42 1. Installation 1-28

43 Commissioning Chapter 2 2-1

44 2. Commissioning Contents 2. Commissioning Configuration General information Preparing the CPX terminal for the configuration Device master file (GSD) and symbol files Configuration with a Siemens master Parametrizing Parametrizing when the terminal is switched on Parametrizing the CPX terminal with STEP Parametrizing with the handheld Application example of parametrizing Commissioning the CPX terminal in the system Faultless commissioning, normal operating status

45 2. Commissioning Contents of this chapter In this chapter you will find information on commissioning the CPX terminal on the PROFIBUS-DP. CPX terminal configuration and addressing. The bus configuration is explained using as an example the software COM PROFIBUS 5.x and STEP 7 V5.1 SP2. The reaction of the CPX terminal can be adapted to individual requirements by parametrizing. This permits e.g. the setting of debouncing times, signal extensions or the reaction to faults. Further information Before commissioning the CPX terminal, you must install it correctly. Information on this can be found in Chapter 1. Commissioning with a general DP master can be found in Appendix A. General information on commissioning the CPX terminal as well as a detailed description of the individual parameters can be found in the CPX system manual (P.BE-CPX-SYS-..). Information on commissioning the pneumatic interfaces and I/O modules can be found in the manual for the CPX I/O modules (P.BE-CPX-EA-..). Instructions on commissioning the pneumatics can be found in the relevant pneumatics manual. 2-3

46 2. Commissioning 2.1 Configuration General information Control commands The control commands FREEZE, SYNC and CLEAR_DATA are supported by the CPX terminal in accordance with EN (DIN 19245). The method of accessing these commands depends on the controller used. Please refer here to the documentation for your field bus module. InformationonDPV1commandscanbefoundinsectionA.3 in Appendix A. Caution Inthefollowingcases,theFREEZEorSYNCmodewillbe reset automatically: when the CPX terminal is switched on or off when the field bus module is stopped. The FREEZE mode will also be reset automatically in the following case: when the bus connection to the CPX terminal is interrupted (response monitoring active). FREEZE With this function all the inputs of the CPX terminal can be frozen. The CPX terminal then sends a constant input image of all the inputs to the master. The following FREEZE commandcausestheinputimagetobeupdated.theupdated input image is then sent constantly to the master. Return to normal operation: UNFREEZE command. 2-4

47 2. Commissioning SYNC With this function all the outputs of the CPX terminal can be frozen. The CPX terminal then no longer reacts to modifications of the output image in the master. The following SYNC command causes the output image of the master to be updated and accepted. Return to normal operation: UNSYNC command. CLEAR_DATA With this function all the outputs of the CPX terminal will be reset Preparing the CPX terminal for the configuration Addressing the CPX terminal The CPX terminal has an address range of up to 64 bytes inputsand64bytesoutputs: Max_Data_Len = 128 (80 H ) Inputs Counting is module-orientated, irrespective of the position of the field bus node. Counting from left to right. Depending on the configuration, the field bus node can occupy status information as logical inputs. Outputs Counting is module-orientated, irrespective of the position of the field bus node. Counting from left to right. 2-5

48 2. Commissioning Electric modules Each module, including the field bus node, has its own identifier. Enter the identifiers corresponding to the physical sequence of the modules from left to right in your configuration program. Module (order code) Occupied bytes Identifier Siemens Identifier EN Field bus node (FB13: DP slave-...) Without I/O diagnostic access 0 byte With status bits: 1 byte I With system diagnosis/ DPV1: 2 bytes I, 2 byte O h 10 h 70 h Digital 4-input module (F: CPX-4DE) Digital 4-output module (A: CPX-4DA) Digital 8-input module (E: CPX-8DE) Digital multi I/O module (Y: CPX-8DE-8DA) Analogue 2-input module (U: CPX-2AE-U/I) Analogue 2-output module (P: CPX-2AA-U/I) 1byteI 8DI 10 h 4bitsI * 0 00 h 1byteO 8DO 20 h 4bitsO * 0 00 h 1byteI 8DI 10 h 1byteI+1byteO 8DX 30 h 2wordsI 2AI 51 h 2wordsO 2AO 61 h * Identifiers can be grouped together Tab. 2/1: Overview of identifiers for CPX modules 2-6

49 2. Commissioning Special identifier format and groupable identifiers Configuration is made PROFIBUS-specific byte-by-byte. By means of a special identifier format you can group some modules within a byte together. The data volume will then be reduced (e.g. 2 x 4DO) 2. Module 1. Module Fig. 2/1: 2 modules grouped together in an identifier byte You can only group together modules of the same type: inputmodules output modules Any other module types may be placed between the grouped modules. Further information can be found in the configuration example below. 2-7

50 2. Commissioning Valves The valves are configured according to the pneumatic interface used: Valves of type CPA and type 03: Only one identifier is used for the pneumatic interface when the valve side is extended. In the pneumatic interface the number of valve coils is set with a DIL switch (grid pattern 1 byte). Pneumatic interface (order code) Occupied bytes Identifier Siemens Identifier EN Pneumatic interface for CPA valves (VI: CPX type 12: 1-...VS) valve coils, 1 byte O valve coils, 2 bytes O valve coils, 3 bytes O 8DO 16DO 24DO 20 h 21 h 22 h Pneumatic interface for Midi/Maxi valves (VI: CPX type 03: 1-...VS) valve coils, 1 byte O valve coils, 2 bytes O valve coils, 3 bytes O valve coils, 4 bytes O 8DO 16DO 24DO 32DO 20 h 21 h 22 h 23 h Tab. 2/2: Overview of identifiers for CPX pneumatic interfaces 2-8

51 2. Commissioning Configuration example The following CPX terminal is used throughout this manual as the configuration example: Module no.: DI 8DI 4DO 8DI 8DO 4DO OPEN Field bus node CPX-FB input module 3 8-input module 4 4-output module 5 Multi I/O module 6 4-output module 7 Pneumatic interface (set with DIL switch to valve coils) 8 Valves/CPA pneumatics Fig. 2/2: Example of a CPX terminal with electric modules with M12 connections and CPA pneumatics Configure the CPX terminal module-by-module from left to right. The following table shows the configuration of the sample terminal: 2-9

52 2. Commissioning Mod. no. Module DP identifier Siemens DP identifier EN Explanation 0 Field bus node (FB13: DP slave system status) 1 Digital 8-input module (E: CPX-8DE) 2 Digital 8-input module (E: CPX-8DE) 3 Digital 4-output module (A: CPX-4DA 2x) 4 Digital multi I/O module (Y: CPX-8DE-8DA) 5 Digital 4-output module (* A: CPX-4DA) 6 CPA pneumatic interface, set with DIL switch to valve coils. (VI: CPX-GP-CPA-...) 64 d 70 h Configured with status bits 8DI 10 h Identifier byte used completely 8DI 10 h Identifier byte used completely 8DO 20 h Only the first 4 bits of the identifier byte are used. 1) 8DX 30 h Identifier byte used completely 0 d 00 h The remaining 4 bits of the identifier byte of module no. 3 are used. 16DO 21 h The pneumatic interface must be configured correctly according to the connected pneumatics. * Identifier grouped together 1) If no module with groupable identifier is used on the subsequent locations, 8 bits will be occupied (4 used). Tab. 2/3: Configuration of the sample terminal from Fig. 2/2 The identifier bytes from locations 3 and 5 are grouped together. The identifier with the star symbol is used in location 5. Please note Make sure that the modules are correctly grouped together. This is not checked by the planning software COM PROFIBUS or STEP

53 2. Commissioning Device master file (GSD) and symbol files In order to configure the CPX terminal with a PC/programmer you will require the appropriate GSD file. In addition to slavetypical entries (Ident. number, Revision, etc.), the device master file (GSD) also contains a selection of identifiers. GSD files Current GSD files can be found in Internet under the following addresses: Go to the Business Area Pneumatics and then to Download Area. Go to Libraries and then to Festo AG & Co. You will require the following files for the CPX terminal: Cpx_059e.gsd (German version) Cpx_059e.gse (International version) Symbol files In order to represent the CPX terminal in your configuration software, you will find symbol files for Festo CPX terminals at the above-mentioned Internet addresses: Normal operating status Diagnostic case Special operating status File: Pb_cpx_n.dib File: Pb_cpx_d.dib File: Pb_cpx_s.dib Tab. 2/4: Symbol files for configuration software 2-11

54 2. Commissioning Configuration with a Siemens master Please note Various configuration programs are available for use in conjunction with a Siemens master. Please observe the relevant procedure for your configuration program. The following sections describe as an example the most important steps required for configuring the Festo valve terminal with the COM PROFIBUS software or with STEP 7. In the following, it is assumed that the user is already familiar with the contents of the manual for the COM PROFIBUS software or for STEP 7. COM PROFIBUS 5.0 Preparations Device master file (GSD) 1. Copy the GSD (see section 2.1.3) into directory...\ SIEMENS\CPBV50\GSD on your PC or programmer. Please note Update the slave catalogue, if you copy the device master file (GSD) during work with COM PROFIBUS. Menu File - Load GSD file. 2-12

55 2. Commissioning Symbol files 2. Copy the symbol files (see section 2.1.3) for the CPX terminal into directory...\siemens\cpbv50\bitmaps on your PC or programmer. This will make the configuration easier. 3. Make entries in the following fields in the mask Bus parameter in the menu Configure: Bus profile Baud rate. 2-13

56 2. Commissioning Station selection with COM PROFIBUS Fig. 2/3: Station selection with COM PROFIBUS 5.0 (explanations see text) 1. Open the following directory in the hardware catalogue: \DP slave\valves\ The Festo valve terminals are listed. (Prerequisites: You must have copied the GSD files as in step 1 of the preparations). 2-14

57 2. Commissioning 2. Click with the left-hand mouse key on the symbol of the CPX terminal in the hardware catalogue 2.With the mouse key pressed down, pull the symbol onto the PROFIBUS line on the DP master 3. The symbol of the CPX terminal will appear 4. (prerequisite: You must have copied the symbol files as in step 2 of the preparations). 3. Double click on the symbol of the CPX terminal 4. The dialogue window Slave Parameters appears Select the PROFIBUS address identical to the selected setting on the DIL switch in the switching module of the field bus node (see section 1.2.1) and confirm this with OK. This concludes the station selection. Configuration with COM PROFIBUS 5.0 Prerequisites: The device master file must exist in the directory of your PC/programmer. The mask Bus parameter must be processed (bus profile, baud rate). The PROFIBUS address must be assigned (see above). Station type FESTO CPX must be selected (see above). Configuring Access the dialogue window Configure as follows: 1. Double click with the left-hand mouse key or once with the right-hand mouse key on the symbol of the CPX terminal. Click on Configure in the menu which now appears. The dialogue window Configure now appears (Fig. 2/4). 2-15

58 2. Commissioning Fig. 2/4: Configuration with COM PROFIBUS 5.0 with the example from Fig. 2/2 2. Mark the field in line 0 in the column Identifier and click the button Module. The dialogue window Module selection now appears (Fig. 2/4). 3. MarkthemoduleintheappropriatelocationonyourCPX terminal and click on Apply. The module appears in the configuration table. 4. Repeat step 2 for further modules in your CPX terminal. Please note Accept the modules in the configuration table corresponding to the physical sequence (from left to right) on your CPX terminal. 2-16

59 2. Commissioning Addressing with COM PROFIBUS 5.0 Enter the starting addresses of the inputs and outputs under I-address or O-address (see Fig. 2/4). Example: CPXterminalasinexampleabove,addressesusedasfrom input/output word 42: Mod. no. Module DP identifier Siemens I address O address 0 Field bus node (FB13: DP slave system status) 1 Digital 8-input module (E: CPX-8DE) 2 Digital 8-input module (E: CPX-8DE) 3 Digital 4-output module (A: CPX-4DA 2x) 4 Digital multi I/O module (Y: CPX-8DE-8DA) 5 Digital 4-output module ( * A: CPX-4DA) 6 CPA pneumatic interface (VI: CPX type 12: 1-16VS) P042 1) 8DI P043 8DI P044 8DO P042 8DX P045 P (P042) 2) 16DO P044 1) Status bits 2) Occupies bits of the periphery output byte 042 automatically. Tab. 2/5: Input and output addresses for the example from Fig. 2/2 In the case of a marked I/O address range, the function Auto address carries out an automatic assignment of the free addresses of the system depending on the system limits. This concludes the configuration and address assignment. 2-17

60 2. Commissioning STEP7V5.1-Hardwareconfigurator Preparations 1. Copy the GSD file (see section 2.1.3) into directory...\step7\s7data\gsd on your PC or programmer. The device master files (GSD) can either be copied manually into the above mentioned directory (e.g. with Windows Explorer) or via the menu item Extras Install new GSD in the dialogue window HW Config. Please note Update the hardware catalogue, if you copy the device master file (GSD) during work with STEP 7. Menu in Hardware Config: Extras - Update catalog Please note As from STEP 7 V4.02, device master files (GSD) are stored within the STEP 7 project (station GSD). This can cause the updating/reading of new GSD files to appear as if incorrect. Please inform yourself about handling the station GSD files in the STEP 7 help. 2-18

61 2. Commissioning Symbols 2. Copy the symbol files (see section 2.1.3) for the CPX terminal into directory...\step7\s7data\nsbmp on your PC or programmer. The symbol files can either be copied manually into the above-named directory or read via the menu item Extras Install new GSD file type Bitmap in HW Config. 3. Process the following entries in the dialogue window Properties of the DP Master: the bus profile thebaudrate. 4. Activate the DP master in the rack. 2-19

62 2. Commissioning Station selection with STEP Fig. 2/5: Station selection with STEP 7 V5.1 HW Config (The masks shown are not all visible at the same time, see text) 1. If the hardware catalogue is not open: Click on the catalogue symbol 1. The hardware catalogue now opens. 2-20

63 2. Commissioning 2. In the hardware catalogue mark the folder FESTO CPX 2 (...\PROFIBUS-DP\Additional Field Devices\Valves) with the left-hand mouse key. The slave type VALVES appears under folder Additional Field Devices if you have copied the GSD correctly (see step 1 of the preparations). 3. Pull the folder FESTO CPX onto the PROFIBUS line on the DP master (Drag & Drop) 3. The dialogue window Properties PROFIBUS Interface appears. 4. Select the address identical to the selected setting of the DIL switch in the node (see Chapter 1.2.2) 4 and confirm with OK. The symbol of the CPX terminal appears on the PROFIBUS line 5. Configuration with STEP 7 Fill the configuration table with the modules of your CPX system (see Fig. 2/6): 1. MarkthesymboloftheCPXterminaltobeconfiguredin HW Config. 2. Mark the first (left-hand) module of your CPX terminal in the hardware catalogue. Pull it onto line 0 in the configuration table. 3. Repeat step 2 for further modules in your CPX terminal. You must pull these onto the next free line. Please note Pull the modules into the configuration table corresponding to their physical sequence on your CPX terminal (from left to right). 2-21

64 2. Commissioning Fig. 2/6: Configuration with STEP 7 V5.1 - Hardware Catalog Addressing The input addresses and output addresses are assigned automatically by STEP 7. Proceed as follows, if you wish to modify this address assignment. 1. Double click in the configuration table on the appropriate lineofthedpslave(seefig.2/6). The dialogue window Properties DP slave appears. 2. Modify the starting address of the inputs/outputs. Please note With S7-400 controllers, 4 bytes of addresses are in some cases reserved for each DP identifier. This concludes the station selection and configuration. 2-22

65 2. Commissioning Addressing example Example: CPXterminalasinFig.2/2,addressesusedasfrominput/ output word 42: Location Module DP identifier Siemens I address O address 0 Field bus node (FB13: DP slave system status) 1 Digital 8-input module (E: CPX-8DE) 2 Digital 8-input module (E: CPX-8DE) 3 Digital 4-output module (A: CPX-4DA 2x) 4 Digital multi I/O module (Y: CPX-8DE-8DA) 5 Digital 4-output module (* A: CPX-4DA) 6 CPA pneumatic interface (VI: CPX type 12: 1-16VS) DI 43 8DI 44 8DO 42 8DX (42) *) 16DO 44 *) Occupies bits of output byte 042 automatically. Tab. 2/6: Input and output addresses for the example from Fig. 2/2 2-23

66 2. Commissioning Status bits: I I42.7 I I43.7 I I44.7 O O42.3 I I45.7 O O43.7 O O42.7 O O45.7 8DI 8DI 4DO 8DI 8DO 4DO Field bus node CPX-FB13 3 CPA pneumatics 2 Pneumatic interface Fig. 2/7: Addressing the CPX terminal on the example from Fig. 2/2 2-24

67 2. Commissioning 2.2 Parametrizing You can set the reaction of the CPX terminal individually by means of parameters. A distinction is made between the following parametrizings: system parametrierung, e.g.: switching out error messages, etc. parametrizing the diagnostic memory module parametrizing (module and channel-specific), e.g.: monitorings, settings in the event of faults, settings the debouncing times of the inputs. A detailed description of the individual parameters as well as basic information on application can be found in the CPX system manual (P.BE-CPX-SYS-..). Parameter lists for CPX I/O modules and CPX pneumatic interfaces can be found in the manual for the CPX I/O modules (P.BE-CPX-EA-..) Parametrizing when the terminal is switched on 1 The parameter set is loaded into thenodebythe master. 2 The parameter set is distributed to the modules by the node. 1 PLC/ IPC PROFI- BUS-DP Master 2 Fig. 2/8: Sequence of the start parametrizing 2-25

68 2. Commissioning When the PROFIBUS system is switched on, the start parametrizing of the CPX terminal is undertaken by the parameter set 1 saved in the PROFIBUS master. The field bus node then distributes the parameters module-orientated to the CPX modules 2. Please note After each interruption of the field bus system (e.g. after interruption of the power supply to the field bus node), the parameter set will be sent again by the PROFIBUS master to the field bus node. An exchange of individual CPX modules is therefore possible without the need once again for manual parametrizing Parametrizing the CPX terminal with STEP 7 System parameters 1. Double click the symbol of the CPX terminal on the PROFIBUS line 1 (see Fig. 2/9). The dialogue window Properties - DP slave appears Select the register Parameter assignment 3. The list with the parameters and the present active values will be displayed. 3. Click the value of the parameter you wish to modify. A dropdown list with the possible values will open up Modify the value by clicking and confirm with OK. 2-26

69 2. Commissioning Fig. 2/9: Setting the system parameters with STEP 7 Parametrizing the diagnostic memory Maximum 40 diagnostic messages can be saved in the diagnostic memory. With the aid of the HW Config, DPV1 or the handheld, you can parametrize the way in which the messages are to be saved. 1. Click the value of the parameter Diag.Buffer Mode or Diag.Buffer Error end A dropdown list with the possible values will open up. 2. Modify the value as follows and confirm with OK. 2-27

70 2. Commissioning Possibilities of parametrizing the diagnostic memory (memory mode): Stop after 40 records, remanent: Save the first 40 diagnostic messages, no further messages will then be saved. The diagnostic messages remain saved when the operating voltage is switched off/fails. Stopafter40records: As above, the diagnostic messages remain saved when the operating voltage is switched off/fails. Record continually, remanent: Continuous saving of messages. If the limit of 40 messages is exceeded, the oldest message will be overwritten. Record continually: As above, the diagnostic messages remain saved when the operating voltage is switched off/fails. Fig. 2/10: Parametrizing the diagnostic memory with STEP 7 Possibilities of parametrizing the diagnostic memory (fault end filter): Record Coming/going : Outgoing faults (fault ends) are recorded. Record coming only : Outgoing faults (fault ends) are not recorded. 2-28

71 2. Commissioning Module parameters 1. Double click in the configuration table on the line of the module you wish to parametrize 1. The dialogue window Properties DP slave appears. 2. Proceed further as described in System parameters under 3. and 4. 1 Fig. 2/11: Parametrizing the module with STEP 7 Please note Module parameters can refer to: features of the complete module features of an individual channel of a module. 2-29

72 2. Commissioning Parametrizing with the handheld The CPX handheld offers menu-orientated access to parametrizing the CPX terminal without configuration software. Information on operating the handheld can be found in the appropriate manual Application example of parametrizing 1 Input with default parametrizing 2 Input with reduction of the input debounce time and increase in the signal extension time Sensor 2. Sensor Fig. 2/12: Application example of parametrizing the debounce time and the pulse extension (here on the right-hand sensor) In the example above packets are transported on a fast conveyor belt. With the following parametrizing, signal registering and processing are improved: Reduction of the input debounce time of 3 ms (factory setting) to 0.1 ms: It is possible to register shorter signals. (Applies to the complete module). Modification of the signal extension time to 50 ms: The signal is registered reliably by the controller. (Applies only to the input channel of the 2nd. sensor). 2-30

73 2. Commissioning 2.3 Commissioning the CPX terminal in the system Please note Please observe also the switching-on instructions in the manualforyourcontroller. Proceed as follows: 1. Connect the field bus cable to the CPX field bus node. 2. Switch on the operating voltage: of all field bus slaves ofthecpxterminal. 3. Switch on the operating voltage for the master module. Configuration run The master systems carry out a comparison between the NOMINAL and ACTUAL configurations (= DIL switch setting for station number and modules used) automatically when the system is switched on. For this configuration run it is important that: the specifications for the NOMINAL configuration are complete and correct. the power supply for the programmable logic controller and for the field bus slaves is switched on either simultaneously or in the sequence indicated above. Recommendation: Providing the safety concept of your machine/system permits this, commission the CPX terminal with both operating voltages (pins 1 and 2), but without compressed air. You can then test the CPX terminal without triggering undesired reactions. 2-31

74 2. Commissioning Faultless commissioning, normal operating status After faultless commissioning the LEDs PS (power system) and PL (power load) light up green. Information on the other LEDs for diagnosis and error treatment can be found in chapter 3 of this manual and in the CPX system manual (P.BE-CPX-SYS-..). LED Colour Operating status Error treatment PS Green lights up Normal None PL Green lights up Normal None BF LED is off Normal None Tab. 2/7: Normal operating status of the CPX terminal 2-32

75 Diagnosis Chapter 3 3-1

76 3. Diagnosis Contents 3. Diagnosis Overview of diagnostic possibilities Diagnosis via LEDs Fault displays of the bus fault/status LED BF Error displays of the LEDs for system diagnosis PS, PL, SF, M Diagnosis via status bits Diagnosis via the I/O diagnostic interface Diagnosis via PROFIBUS-DP Diagnostic steps Overview of diagnostic bytes Details on standard diagnostic information Module-related diagnosis Channel-related diagnosis Error treatment ( Fail safe ) Siemens SIMATIC S5/S Online diagnosis with STEP Read diagnostic buffer with STEP 7 (version 4.x, 5.1) Read device-specific diagnosis with STEP 7 (version 5.1)

77 3. Diagnosis Contents of this chapter The CPX terminal offers you extensive diagnostic possibilities. In this chapter you will find an overview of as well as detailed information on the diagnostic possibilities with: LEDs status bits thei/odiagnostic interface PROFIBUS-DP the handheld. Further information Information on general diagnosis of the CPX terminal can be found in the CPX system manual (P.BE-CPX-SYS-..). Information on diagnosing the pneumatic interface and the I/O modules can be found in the manual CPX I/O modules (P.BE-CPX-EA-..). Information on diagnosing the pneumatics can be found in the relevant pneumatics manual. 3-3

78 3. Diagnosis 3.1 Overview of diagnostic possibilities The CPX terminal offers extensive and user-friendly possibilities of diagnosis and error treatment. The following possibilities are available depending on the configuration: Diagnostic possibility Brief description Advantages Detailed description LED display The LEDs show directly configuration faults, hardware faults, bus faults, etc. Fast on-the-spot fault recognition Section 3.2 Status bits Internal inputs which supply coded common diagnostic messages. The 8 status bits are transmitted to the module as inputs cyclically with the normal inputs. Fast access to error messages in the PLC user program, irrespective of the module and the master. Section 3.3 Diagnosis via PROFIBUS-DP DiagnosisasperPROFIBUS standard Detailed module-related and channel-related fault recognitionintheonline mode of the programming/ configuration software and in the PLC user program. Section 3.5 Diagnosis with PROFIBUS DPV1 Access to all system data of the CPX terminal via the field bus. Extended access to diagnostic data in the PLC user program (e.g. diagnostic memory). Appendix A.3 Tab. 3/1: Diagnostic possibilities part 1 3-4

79 3. Diagnosis Diagnostic possibility Brief description Advantages Detailed description I/O diagnostic interface Bus-independent diagnostic interface at I/O level which permits access to internal data of the CPX terminal (16 inputs and 16 outputs). Read access to internal parameters and data at I/O level. CPX system manual (P.BE-CPX-SYS-..) Diagnosis with the handheld Convenient and menulisted diagnostic information can be displayed on the CPX handheld. Fast on-the-spot fault recognition without programming in clear text. Manual for the handheld Tab. 3/2: Diagnostic possibilities part 2 Please note Note that the diagnostic information shown can depend on the settings (see section 1.2.2) as well as on the parametrizing (see section 2.2) of the CPX terminal. 3-5

80 3. Diagnosis 3.2 Diagnosis via LEDs The LEDs on the cover indicate the operating status of the CPX field bus node. 1 LED BF: Bus fault/status (red) 1 2 LEDs for the system diagnosis: PS: Power system (green) PL: Power load (green) SF: System fault (red) M: Modify (yellow) BF PS PL SF M 2 Fig. 3/1: LEDs of the CPX node The LEDs in their various states are represented as follows: lights up ; flashes ; out 3-6

81 3. Diagnosis Fault displays of the bus fault/status LED BF If the device-related diagnosis is active, faults will also be passed on to the master PLC via the field bus. BF (bus fault) LED (red) Sequence Status Error treatment LED is off No fault (when the green PS LED lights up) LED flashes Field bus connection not OK. Possible causes: Station number not correct (e.g. address assigned twice) Defective field bus module Interrupted, shortcircuited or faulty field bus connection Configuration not correct Check the... address setting of the DIL switch in the field bus node. field bus module/master. field bus connection. Configuration of the master in respect of the modules of the CPX terminal. Tab. 3/3: Error diagnosis with the red LED BF 3-7

82 3. Diagnosis Error displays of the LEDs for system diagnosis PS, PL, SF, M PS (power system) power sensor/logic supply LED (green) Sequence Status Error treatment LED lights up No error. Operating/sensor voltage applied LED flashes Operating voltage/sensor supply outside of tolerance range 1. Eliminate short circuit/overload 2. Depending on parametrizing: The sensor supply will be switched on again automatically when short circuit is eliminated (default) Power Off/On necessary LED is out Operating voltage/sensor supply not applied Check operating voltage connection for the electronics PL (power load) power load supply (outputs/valves) LED (green) Sequence Status Error treatment LED lights up No error. Load voltage applied None LED flashes Load voltage outside of tolerance range 1. Eliminate undervoltage 2. Depending on parametrization: The load voltage supply will be switched on again automatically when the undervoltage is eliminated (default) Power Off/On necessary LED is out Load voltage (valves and outputs) not applied Check load voltage connection for the electronics Tab. 3/4: Error diagnosis with the LEDs PS and PL 3-8

83 3. Diagnosis SF (system failure) system fault LED (red) Sequence Status Meaning/error treatment No error. LED is out LED flashes once Simple fault/information (error class 1) Fault (error class 2) See description of the error numbers in the CPX system manual. LED flashes twice Serious fault (error class 3) LED flashes three times 1) The system fault LED flashes in accordance with the error class. Error class 1 (simple fault): 1 flash, interval Error class 2 (fault): 2 flashes, interval Error class 3 (serious fault): 3 flashes, interval Tab. 3/5: Error diagnosis with the LED SF 3-9

84 3. Diagnosis M (modify) Parametrizing modified or Force active LED (yellow) Sequence Status Meaning/errortreatment LED is out System start with default parametrizing (factory setting) and current CPX equipment status is set; external parametrizing is possible (pre-setting) None LED lights up System start with saved parametrizing and saved CPX equipment status is set; parameters and CPX equipment status are saved remanently; external parametrizing is blocked 1) Be careful when replacing CPX terminals with saved parametrizing. With these CPX terminals, parametrizing is not carried out automatically by the higher-order PLC/IPC during replacement. In these cases check before replacing to see which settings are required and, if necessary, carry out these settings. LED flashes Force is active 1) The function Force is enabled (see system parameter Force mode; function no. 4402). 1) The display of the function Force (LED flashes) has precedence over the display of the setting for system start (LED lights up). Tab. 3/6: Messages of the LED M 3-10

85 3. Diagnosis 3.3 Diagnosis via status bits The CPX terminal will provide 8 status bits if you have parametrized it with option FB13 DP slave system status. The status bits serve for displaying common diagnostic messages (global error messages). They are configured like inputs; you can select the address when configuring. If all status bits supply a 0-signal, no fault will be registered. Bit Diagnostic information with 1-signal Description 0 Faultatvalve Module type with which a fault has occurred. 1 Faultatoutput 2 Faultatinput 3 Fault in analogue module/ function module 4 Undervoltage Type of fault 5 Short circuit/overload 6 Wire fracture 7 Other faults Tab. 3/7: Status bits of the CPX FB13 (optional) 3.4 Diagnosis via the I/O diagnostic interface The CPX terminal will provide a 16-bit diagnostic interface if you have configured it with option FB13 DP slave system diagnosis. InformationontheI/Odiagnosticinterfacecanbefoundin the CPX system manual P.BE-CPX-SYS

86 3. Diagnosis 3.5 Diagnosis via PROFIBUS-DP 1 The CPX terminal supports the following diagnostic possibilities via PROFIBUS as per EN 50170: Device-related diagnosis: Status message (see also section 3.7.2) Module-related diagnosis (see section 3.5.4). One bit is reserved pro module for displaying a current diagnosis. Channel-related diagnosis (see section 3.5.5). - module number - channel number and type - type of diagnosis (fault number) Device-related diagnosis 2 Module-related diagnosis 3 Channel-related diagnosis Fig. 3/2: Diagnostic possibilities 3-12

87 3. Diagnosis Diagnostic steps The diagram below shows you the steps required for diagnosing the CPX terminal Bit Station status 1 1. Step (evaluation of bits 0 and 2): CPX terminal without power, bus plug is not inserted, Step: Evaluation of the diagnostic byte Planned configuration of the CPX terminal does not correspond to the actual configuration. Device-related diagnosis (see Tab. 3/9) Module-related diagnosis (Tab. 3/10) Channel-related diagnosis (Tab. 3/11) (max. 11 messages) variable 7bytes 16 bytes Fig. 3/3: Diagnostic steps Please note The diagnostic information is only sent to the master system if the device-related diagnosis is activated with the DIL switch. In order to do this, set switch element 8 of the 8-element DIL switch to. 3-13

88 3. Diagnosis It can in some cases be helpful if you switch off the device-related diagnosis when commissioning your system. If your controller does not start, try with the setting Device-related diagnosis inactive on the 8-element DIL switch (see section 1.2.2) Overview of diagnostic bytes In the following the diagnostic bytes are represented in four tables. Standard diagnostic information Byte Contents Explanation 0 Station status 1 See Tab. 3/12 1 Station status 2 See Tab. 3/13 2 Station status 3 See Tab. 3/14 3 Diag. master_add Master address: The address of the master, which parametrized the CPX terminal, is entered in this byte. 4 Ident_number high byte Manufacturer identifier high byte (05 h ) 5 Ident_number low byte Manufacturer identifier low byte (9E h ) Tab. 3/8: Overview of diagnostic bytes: Standard diagnostic information 3-14

89 3. Diagnosis Device-related diagnosis (16 bytes), (module status DPV1) Byte Contents Explanation 6 Header On the CPX terminal fixed C h 7 Type On the CPX terminal fixed 82 h 8 Slot On the CPX terminal fixed 0 h 9 Slot On the CPX terminal fixed 0 h 10 Module 0 (bits 1 and 2)... Module 3 (bits 6 and 7) 2bitspermodule: 00 = No fault (valid work data) 01 = Module fault (work data invalid) 10 = Incorrect module (work data invalid) 11 = Module has failed or does not exist (work data invalid) 11 Modules Like byte Modules (bits 6 and 7 are reserved) Like byte Reserved Tab. 3/9: Overview of device-related diagnosis (fixed at length of 16 bytes) 3-15

90 3. Diagnosis Module-related diagnosis (7 bytes) Byte Contents Explanation 22 Header On the CPX terminal fixed 47 h 23 Module-related diagnostic modules The relevant module has diagnostic message 24 Module-related diagnostic modules The relevant module has diagnostic message Reserved Tab. 3/10: Overview of diagnostic bytes: Module-related diagnosis (details in section 3.5.4) Channel-related diagnosis (variable length) Byte Contents Explanation 29 Channel-related diagnostic module x byte 1 Contains module number 30 Channel-related diagnostic module x byte 2 Channel number and input/output 31 Channel-related diagnostic module x byte 3 Fault type and channel type 32 Channel-related diagnostic module y byte 1 Contains module number 33 Channel-related diagnostic module y byte 2 Channel number and input/output 34 Channel-related diagnostic module y byte 3 Fault type and channel type Channel-related diagnostic module z byte 1 Contains module number 60 Channel-related diagnostic module z byte 2 Channel number and input/output 61 Channel-related diagnostic module z byte 3 Fault type and channel type x, y, z: See explanation in the following text. Tab. 3/11: Overview of diagnostic bytes: Channel-related diagnosis (details in section 3.5.5) 3-16

91 3. Diagnosis The following applies for the entries in the diagnostic bytes of the channel-related diagnosis: Entry according to module numbers in ascending order and without gaps: The entries are always listed according to the module numbers, irrespective of the time sequence of the diagnostic messages (if necessary, the entries with higher module numbers will be postponed). In the case of module-orientated and channel-orientated faults on a module, only the module-orientated diagnostic message will be entered. In the case of several channel-orientated faults on a module, only the diagnostic message of the channel with the lowest channel number will be entered. Maximum 11 diagnostic messages can be processed. 3-17

92 3. Diagnosis Details on standard diagnostic information The following diagnostic information can be requested by the DP master from the CPX terminal with the function Slave_Diag. The procedure for reading out this diagnostic information with a SIMATIC S5/S7 system is described inchapter Station status_1 Bit Meaning Explanation 0 *) Diag.Station_Non_Existent CPX terminal is no longer/not yet addressable. Possible causes: operating voltage not applied data cable interrupted fault in data cable 1 *) Diag.Station_Not_Ready CPX terminal is not yet ready for data exchange 2 *) Diag.Cfg_Fault The configuration data received from the master do not agree with those ascertained by the CPX terminal. 3 *) Diag.Ext_Diag There is a diagnosis. Possible causes: cable fracture on input/output module short circuit/overload at electric outputs,... 4 Diag.Not_Supported 1 = CPX terminal does not support the function requested 5 Diag.Invalid_Slave_Response Always 0 (set by CPX terminal) 6 Diag.Prm_Fault Last parametrizing telegram faulty 7 Diag.Master_Lock Always 0 (set by CPX terminal) *) Valve terminal related bits Tab. 3/12: Diagnostic bits Station status_1 3-18

93 3. Diagnosis Station status_2 Bit Meaning Explanation 0 *) Diag.Prm_Req 1 = Master must configure the CPX terminal again 1 Diag.Stat_Diag 1 = Master must request diagnostic data until this bit is set to 0 2 Always 1 (set by CPX terminal) 3 *) Diag.WD_On 1 = Response monitoring/watchdog activated 4 Diag.Freeze_Mode 1 = Freeze activated 5 Diag.Sync_Mode 1=Syncactivated 6 Reserved 7 Diag.Deactivated Always 0 (set by CPX terminal) *) Valve terminal related bits Tab. 3/13: Diagnostic bits station status_2 Station status_3 Bit Meaning Explanation Reserved 7 Diag.Ext_Diag_Overflow 1 = CPX terminal has more diagnostic messages than can be buffered or master receives more diagnostic messages than it can buffer. Tab. 3/14: Diagnostic bits station status_3 3-19

94 3. Diagnosis Module-related diagnosis One bit is reserved for each module assigned during the configuration (identifier byte). A set bit means that there is a diagnostic message in this I/O range Bit Header byte of the module-related diagnosis Length of the module-related diagnostic record in bytes inclusive header byte. Bit7,6fixedat01 Fig. 3/4: Header byte of the module-related diagnosis Bit Module-related diagnosis Module 0 has diagnosis Module 1 has diagnosis Module 7 has diagnosis Fig. 3/5: Module-related diagnosis Channel-related diagnosis 3 bytes of diagnostic data are available for each channel. Byte 1: Module number Byte 2: Channel number Byte 3: Type of diagnosis 3-20

95 3. Diagnosis Bit Module number of the channel-related diagnosis 1 0 Module number Fig. 3/6: Channel-related diagnostic byte 1 Bit7,6fixedat Bit Channel number Fig. 3/7: Channel-related diagnostic byte 2 Channel number Input/output 00 = reserved 10 = output 01 = input 11 = input/output Bit Type of diagnosis Fig. 3/8: Channel-related diagnostic byte 3 Faulttype(seeTab.3/15) Channel type 000 = reserved 100 = 1 byte 001 = 1 bit 101 = 1 word 010 = 2 bits 110 = 2 words 011 = 4 bits 111 = reserved 3-21

96 3. Diagnosis Value Fault type (standard) Value Fault type (Festo) 0 Reserved 16 Valve setting incorrect 1 Short circuit 17 Valve: Switching cycle counter, limit exceeded 2 Undervoltage 18 Reserved 3 Overvoltage 19 Reserved 4 Overload 20 Parametrizing fault (configurable) 5 Overtemperature 21 Parametrizing fault (data format) 6 Cable fracture 22 Parametrizingfault (linearscaling) 7 Switching cycle counter, limit exceeded 23 Parametrizing fault (digital filter) 8 Lower limit exceeded 24 Parametrizing fault (lower limit) 9 Reserved 25 Parametrizing fault (upper limit) 10 Reserved 26 Reserved 11 Reserved 27 Reserved 12 Reserved 28 Reserved 13 Reserved 29 Reserved 14 Reserved 30 Slave has no bus connection 15 Reserved 31 Channel failure Tab. 3/15: Fault types (byte 3 of the channel-related diagnosis) 3-22

97 3. Diagnosis 3.6 Error treatment ( Fail safe ) Parametrizing With the following faults, the reaction of the CPX terminal depends on the configured reaction of the master module and the parametrized Fail safe setting: telegram failure master stopped interruptioninbuscable. Depending on the parametrizing, the outputs (valves and electric outputs) will be switched off (factory setting), switched on or retain their status (see CPX system manual). Warning Make sure that valves and outputs are put into a safe state when the faults named occur. An incorrect status of the valves and outputs may lead to dangerous situations. Further information on the fail-safe setting can be found in the CPX system manual P.BE-CPX-SYS-... Please note If the outputs are reset in the event of a PLC stop, field bus interruption or field bus fault, please observe the following: Single-solenoid valves move to the basic position. Double-solenoid valves remain in the current position. Mid-position valves move to the mid-position (depending on valve type: pressurized, exhausted or blocked). 3-23

98 3. Diagnosis Siemens SIMATIC S5/S7 With these controllers, you have the possibility of determining the reaction of the CPX terminal to the faults named (details see controller manual). Almost all configuration programs contain the function Response monitoring. For the operating modes named, the time specified corresponds to the drop-off time of the valves and electric outputs. Further details on response monitoring can be found in the relevant manuals. 3-24

99 3. Diagnosis You can set two ways in which the control system reacts to faults: when a fault occurs, the controller switches to the operating mode STOP (hard fault reaction) or when a fault occurs, the controller remains in the operating mode RUN (soft fault reaction). Control system Module Meaning STOP RUN SIMATIC S5 with IM 308C OB23 Reaction to QVZ with direct periphery access default OB is programmed OB24 Reaction to QVZ with periphery access via process image default OB is programmed OB35 Reactionto PEU default OB is programmed SIMATIC S7/M7 OB82 Reactionto a devicespecific diagnosis default OB is programmed OB86 Reaction to failure of a DP slave default OB is programmed QVZ: Quitting delay OB: Organisation module PEU: Periphery not clear Tab. 3/16: Fault reaction of the control system Further details can be found in the relevant manuals for the control systems. 3-25

100 3. Diagnosis Possibilities for reading out the diagnosis for S5/S7 The diagnosis for PROFIBUS-DP is supported in the various control systems by function modules. These read out the slave diagnosis and write it into a data range of the user program. Control system Function module See... Manufacturer SIMATIC S5 with IM 308C FB192 IM308C Manual ET 200 decentral periphery system Siemens SIMATIC S5 with S5-95U/DP master FB230 S_DIAG Manual ET 200 decentral periphery system Siemens SIMATIC S5 with SF 50/DP master FB230 S_DIAG Manual Programmable valve terminal with SB/SF 50 Festo SIMATICS7/M7 SFC13 DP NRM_DG Reference manual System functions and standard functions Siemens SIMATIC S7/M7 FB125 Siemens download in Internet Siemens Tab. 3/17: Possibilities for reading out the diagnosis for S5/S7 Example for a STEP 7 user program: STL CALL SFC 13 REQ:=TRUE LADDR:=W#16#03FE RET_VAL:=MW100 RECORD:=P#M110.0 BYTE 64 BUSY:=M10.0 Explanation Request to read Pointer to diagnostic address, e.g d = 03FE h (see mask Properties DP slave in HW Config) When errors occur, output error code Pointer at start of data range for diagnosis and length of diagnostic data Reading concluded Fig. 3/9: Program example in STL 3-26

101 3. Diagnosis 3.7 Online diagnosis with STEP 7 Direct diagnostic events in conjunction with the CPX terminal can be: Decentral periphery: Station failure. Communication between slave and master is interrupted. Component faulty (see device-related diagnosis, Tab. 3/9). Operating status transition from START to RUN (nominal/ actual difference exists): Configuration data of the CPX node do not correspond with the periphery. Incorrect DIL switch setting in the CPX node Read diagnostic buffer with STEP 7 (version 4.x, 5.1) Prerequisites: HW Config has been accessed Proceed as follows (Fig. 3/10): 1. Switch from offline to online Click with the right-hand mouse button on the CPU in the rack 2. Click on Module information in the context menu which now appears. The dialogue window Module information appears Select the register Diagnostic Buffer Mark the event and read the details on the event. These supply more detailed information on the further procedure and depend on the S7 controller 5 used. 3-27

102 3. Diagnosis Fig. 3/10: Online diagnosis via diagnostic buffer (explanation see text) 3-28

103 3. Diagnosis Read device-specific diagnosis with STEP 7 (version 5.1) You can display error messages of the device-specific diagnosis with STEP 7 HW Config V5.1, if you mark the CPX terminal instead of the CPU. Proceed as follows (see Fig. 3/11): Prerequisites: HW Config has been accessed. 1. Switch from offline to online. 2. Click with the right-hand mouse key on the symbol of the CPX terminal 1. Click on Module information in the context menu which now appears. The dialogue window Module information appears. 3. Select the register DP Slave Diagnostics. 4. Read the diagnostic information

104 3. Diagnosis 1 2 Fig. 3/11: Device-related diagnosis with STEP 7 V5.1 (explanation see text) 3-30

105 Technical appendix Appendix A A-1

106 A. Technical appendix Contents A. Technical appendix... A-1 A.1 Technical specifications of field bus node CPX-FB13... A-3 A.2 Operation with the general DP master... A-4 A.2.1 Bus start... A-4 A.2.2 Send parametriziung data... A-5 A.2.3 Send configuration data... A-7 A.2.4 Error treatment... A-10 A.2.5 Request diagnostic information... A-10 A.2.6 Start cyclic exchange of data... A-10 A.2.7 Implemented functions and service access points (SAP)... A-12 A.2.8 Bus parameters/reaction times... A-13 A.2.9 Transmission times on the PROFIBUS-DP... A-13 A.3 Access to the CPX terminal via DPV1... A-14 A.3.1 Reading and writing data records... A-14 A.3.2 Data records... A-17 A-2

107 A. Technical appendix A.1 Technical specifications of field bus node CPX-FB13 General General technical specifications Protection class as per EN 60529, CPX-FB13 fitted completely, plug connector inserted or provided with protective cap Protection against electric shock (protection against direct and indirect contact as per EN /IEC 204) See CPX system manual: P.BE-CPX-SYS-.. IP65 By means of PELV power units (Protected Extra-Low Voltage) Module code (CPX-specific) 202 Power supply Operating voltage / Load voltage Current consumption of field bus node CPX-FB13 From operating voltage supply for electronics/ sensors (V SEN ) Electrical isolation See CPX system manual: P.BE-CPX-SYS-.. Max. 200 ma (only CPX-FB13) Bus interface opto-decoupled Field bus PROFIBUS chip Design Transmission type Protocol Baud rate Cable type SPC 3 with DPV1 RS 485, floating Serial asynchronous, half-duplex PROFIBUS-DP kbaud, automatic baud rate recognition Depending on cable length and field bus baud rate set: see controller manual A-3

108 A. Technical appendix A.2 Operation with the general DP master The Festo CPX terminal can be controlled from any PLC, PC or industrial PC with a PROFIBUS-DP module in accordance with EN (DIN 19245). Information on the functions FREEZE, SYNC and the DP identifiers can be found in section A.2.1 Bus start In order to commission the CPX terminal correctly, the DP master must carry out the following functions in the sequence specified: 1. Request diagnosis. 2. Send parametrizing data. In the case of the start parametrizing, the parameter set will be loaded into the field bus node by the master. The node distributes the parameters to the modules. 3. Send configuration data. 4. Diagnosis request before data exchange. 5. Start cyclic exchange of data. The composition and contents of the individual telegrams are described in the following sections. Please note After each interruption of the field bus system (e.g. after interruption of the power supply to the field bus node), the parameter set will be sent again by the PROFIBUS master to the field bus node. An exchange of individual CPX modules is therefore possible without the need for manual parametrizing. A-4

109 A. Technical appendix A.2.2 Set_Prm Send parametrizing data The parametrizing data are sent to the CPX terminal by the DP master with the function Set_Prm. Octet 1: Station status Bit Meaning Explanation 0 Reserved WD_On Response monitoring of the CPX terminal on/off: 0= Off 1= On 4 Freeze_Req 0 = Freeze mode not requested by the master 1 = Freeze mode set by the master 5 Sync_Req 0 = Sync mode not requested by the master 1 = Sync mode set by the master 6 Unlock_Req Bit 7 Bit 6 Explanation 7 Lock_Req 0 0 Min T SDR +slaveparametermaybeoverwritten 0 1 CPX terminal released for other masters 1 0 CPX terminal blocked for other masters 1 1 CPX terminal released for other masters Tab. A/1: Octet 1: Station status A-5

110 A. Technical appendix Further octets Octet Designation Explanation 2and3 WD_Fact_1 WD_Fact_2 Range : The response monitoring time of the CPX terminal is transmitted with these two octets: TWD [s] = 10 ms x WD_Fact_1 x WD_Fact_2 4 Minimum station delay responder (min T SDR ) The minimum time the CPX terminal must wait, before the reply telegram may be sent to the DP master. 5and6 Ident_number Transmit the Ident. number (= 059E H )ofthecpx terminal; parametrizing telegrams to the CPX terminal are only accepted if the transmitted and the programmed Ident. numbers are the same. 7 Group_Ident Not supported by the CPX terminal User_Prm_Data Information on the slave-specific parameters can be foundinthesection2.2andthecpxsystemmanual P.BE-CPX-SYS-.. as well as in the manual for the I/O modules P.BE-CPX-EA-... Tab. A/2: Further octets A-6

111 A. Technical appendix A.2.3 Chk_Cfg Send configuration data The configuration data are transmitted to the CPX terminal by the DP master with the function Chk_Cfg. Overview of parameters: Octet 1-n: DP identifier Permitted identifiers for the Festo CPX terminal: Module (order code) Field bus node (FB13: DP slave-...) Digital 4-input module (F: CPX-4DE) Digital 4-output module (A: CPX-4DA) Digital 8-input module (E: CPX-8DE) Digital multi I/O module (Y: CPX-8DE-8DA) Analogue 2-input module (U: CPX-2AE-U/I) Analogue 2-output module (P: CPX-2AA-U/I) Occupied bytes Without I/O diagnostic access 0 byte With status bits: 1 byte E With system diagnosis/dpv1: 1byteI 4bitsI * 1byteO 4bitsO * 1byteI 1byteI+1byteO 2wordsI 2wordsO Identifier EN h 10 h 70 h 10 h 00 h 20 h 00 h 10 h 30 h 51 h 61 h * Identifiers can be grouped together. Tab. A/3: Overview of identifiers for CPX modules A-7

112 A. Technical appendix Pneumatic interface (order code) Pneumatic interface for CPA valves (VI: CPX type 12: 1-..VS) Pneumatic interface for Midi/Maxi valves (VI: CPX type 03: 1-..VS) Occupied bytes valve coils 1byteO valve coils 2bytesO valve coils 3bytesO valve coils 1byteO valve coils 2bytesO valve coils 3bytesO valve coils 4bytesO Identifier EN h 21 h 22 h 20 h 21 h 22 h 23 h Tab. A/4: Overview of identifiers for CPX pneumatic interfaces A-8

113 A. Technical appendix Example: Configuring a CPX terminal Location Module DP identifier EN Comment 0 Field bus node (FB13: DP slave system status) 1 Digital 8-input module (E: CPX-8DE) 2 Digital 8-input module (E: CPX-8DE) 3 Digital 4-output module (A: CPX-4DA 2x) 4 Digital multi I/O module (Y: CPX-8DE-8DA) 5 Digital 4-output module (*A: CPX-4DA) 6 CPA pneumatic interface, set with DIL switch to valve coils. (VI: CPX type 12: 1-16VS) 70 h Configured with status bits 10 h Identifier byte used completely 10 h Identifier byte used completely 20 h Only 4 bits of the identifier byte are used. 30 h Identifier byte used completely 00 h The identifier byte from location 3 is filled with the remaining 4 bits. 21 h The pneumatic interface must be configured correctly according to the connected pneumatics. Tab. A/5: Example of the configuration of a CPX terminal (see Fig. 2/2) with different modules and CPA pneumatics A-9

114 A. Technical appendix A.2.4 Error treatment With the function Set_Prm you have the possibility of determining the watchdog time (WD_Fact_1, Octet 2, WD_Fact_2, Octet 3). The reaction of the CPX terminal to a fault (e.g. bus failure) depends on the parametrizing. Further information can be found in chapter 3.6. A.2.5 Request diagnostic information Slave_Diag The diagnostic data are requested by the CPX terminal with the function Slave_Diag. A description of this function can be found in section 3.5.3, Diagnosis via PROFIBUS-DP. A.2.6 Start cyclic exchange of data Data_Exchange The cyclic exchange of data is accomplished with the function Data_Exchange. With this function the output data for CPX terminals are transmitted as an octet string of length x. The octet string length depends on the number of identifier bytes. Please note With the function Data_Exchange, the CPX terminal expects the output information for the valves and electric outputs. The input information is sent to the master as a reply telegram. A-10

115 A. Technical appendix Overview of the work data (Data_Exchange) for the example in Fig. 2/2: Output information (output bytes) Octet 1: O-data byte_1 *) (4DO modules in locations 3 and 5) Bit0:Outputx Bit1:Outputx+1 Bit2:Outputx+2 Bit3:Outputx+3 Bit4:Outputx+4 Bit5:Outputx+5 Bit6:Outputx+6 Bit7:Outputx+7 Octet 2: O-data byte_2 (8DI/8DO module in location 4) Bit0:Outputy Bit1:Outputy+1... Bit7:Outputy+7 Octet 3: O-data byte_3 (Pneumatic interface in location 6) Bit0:Outputz Bit1:Outputz+1... Bit7:Outputz+7 Input information (input bytes) Octet 1: I-data byte_1 (8DI module in location 1) Bit 0: Input u Bit 1: Input u+1 Bit 2: Input u+2 Bit 3: Input u+3 Bit 4: Input u+4 Bit 5: Input u+5 Bit 6: Input u+6 Bit 7: Input u+7 Octet 2: I-data byte_2 (8DI module in location 2) Bit 0: Input v Bit 1: Input v+1... Bit 7: Input u+7 Octet 3: I-data byte_3 (8DI/8DO module in location 4) Bit 0: Input w Bit 1: Input w+1... Bit 7: Input u+7 Octet 4: O-data byte_3 (Pneumatic interface in location 6) Bit0:Outputt+8 Bit1:Outputt+9... Bit7:Outputt+15 *) Two 4DO modules are grouped together in this byte. x, y, z, t, u, v, w = Address offset of master module A-11

116 A. Technical appendix A.2.7 Implemented functions and service access points (SAP) Function Available Destination SAP (DSAP) Data_Exchange Yes NIL RD_Inp Yes 56 RD_Outp Yes 57 Slave_Diag Yes 60 Set_Prm *) Yes 61 Chk_Cfg Yes 62 Get_Cfg Yes 59 Global_Control Yes 58 Set_Slave_Add No 55 MSAC_C1 Yes 50, 51 MSAC_C2 Yes *) The CPX parameters are herewith also sent during the initialization phase. Tab. A/6: Overview of functions and service access points You can access the DPV1 services with the following functions: MSAC_C1: For masters of class 1 (e.g. PLC), fixed service access points. MSAC_C2: For masters of class 2 (e.g. PC/programmer), dynamic use, service access points are specified when connections are set up. A-12

117 A. Technical appendix A.2.8 Bus parameters/reaction times Baud rate (kbaud) Max T SDR (T Bit ) Max T SDR (T Bit ) Tab. A/7: Bus parameters and reaction times A.2.9 Transmission times on the PROFIBUS-DP Please note ObserveherethecycletimeofyourPLCandtheupdate time of the PROFIBUS-DP. The delay time within the CPX terminal is very brief. It is considerably less than 1 ms, irrespective of the equipment fitted on your CPX terminal. Pleaserefertothemanualforyourcontrollerforascertaining the total time required for transmission. A-13

118 A. Technical appendix A.3 Access to the CPX terminal via DPV1 By means of DPV1 commands you can access all the data and parameters which the CPX terminal provides: Parameter and status information Systemdata DPV1 commands are only available if you configure the field bus node as follows: FB13: DP slave system diagnosis You can easily access the system data by means of the PROFI- BUS configuration software. Background information can be found in the CPX system manual P.BE-CPX-SYS-... A.3.1 Reading and writing data records Use the function module SFC 59 for reading and SFC 58 for writing data. First set the DPV1 compatibility S7-conform as follows: Set the DPV1 compatibility Parametrize the field bus node S7-conform if you are working with a Siemens master: 1. Proceed as described in section 2.2.2, double-click in step 1 but on the line of the field bus node in the configuration table. The mask Properties DP slave appears. 2. Select the register Parameter Assignment and modify the value of the DPV1-Services to S7 compatible (see following diagram). 3. Confirm with OK. A-14

119 A. Technical appendix Fig. A/1: Setting the compatibility for accessing the DPV1 Siemens S7 Function module SFC 59 in STL for reading a data record: STL Explanation CALL SFC 59 RD_REC REQ :=TRUE Request to read IOID :=B#16#54 Identifier of the address range (here always 54) LADDR :=W#16#6 Logical address of the field bus node (see mask Properties - DP slave in HW Config) RECNUM :=B#16#14 Data record number 20 (see table Tab. A/8) RET_VAL :=MW100 If faults occur, output fault code RECORD :=P#M110.0 BYTE 8 Target range for data record read and length of data record BUSY :=M10.0 Reading in process Fig. A/2: Example program for reading out the diagnostic memory status A-15

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV...-DI02 PROFIBUS-DP CPV...

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV...-DI02 PROFIBUS-DP CPV... Compact performance Elektronics manual CPV valve terminal with field bus direct connection Types: CPV...-DI02 PROFIBUS-DP CPV...-CS02 ABB CS31 Manual 548732 en 1201a [762106] Contents and general instructions

More information

Compact Performance CPV valve terminal with direct connection Electronics

Compact Performance CPV valve terminal with direct connection Electronics Compact Performance CPV valve terminal with direct connection Electronics Field bus protocols: PROFIBUS-DP, Festo, ABB CS31, SUCOnet K Direct connection type CPV..-DI01 Contents and safety instructions

More information

Compact performance. Electronics manual. System manual. Installing and commissioning CP systems. Manual en 0010b

Compact performance. Electronics manual. System manual. Installing and commissioning CP systems. Manual en 0010b Compact performance Electronics manual System manual Installing and commissioning CP systems Manual 165 226 en 0010b Contents and general instructions Author... S. Breuer Editors... H.-J. Drung, M.Holder

More information

CPX terminal. Manual Electronics. Digital CPX I/O modules and Connection blocks Types: - CPX-8DE-8DA - CPX-AB- CPX pneumatic interfaces Types:

CPX terminal. Manual Electronics. Digital CPX I/O modules and Connection blocks Types: - CPX-8DE-8DA - CPX-AB- CPX pneumatic interfaces Types: CPX terminal Manual Electronics Digital CPX I/O modules and Connection blocks Types: - CPX- DE - CPX- DA - CPX-8DE-8DA - CPX-M- - CPX-L- - CPX-AB- CPX pneumatic interfaces Types: - VMPA -FB-EPL- - VMPAL

More information

CPA SC/CPV SC PROFIBUS DP

CPA SC/CPV SC PROFIBUS DP Valve terminals CPA SC/CPV SC PROFIBUS DP Electronics Manual Valve terminals Field bus direct Field bus protocol: PROFIBUS DP as per EN 50170 Type CPA SC DP Type CPV SC DP Manual 548 726 en 0610NH [705

More information

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV... DI02 PROFIBUS DP CPV...

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV... DI02 PROFIBUS DP CPV... Compact performance Elektronics manual CPV valve terminal with field bus direct connection Types: CPV... DI02 PROFIBUS DP CPV... CS02 ABB CS31 Manual 548 732 en 0704NH [706 006] Contents and general instructions

More information

Compact Performance CP system Installation and commissioning

Compact Performance CP system Installation and commissioning Compact Performance CP system Installation and commissioning Author: Translation: Editors: Layout: Type setting: S. Breuer Douglas Smith H.-J. Drung, M. Holder Festo, Dept. PV-IDM PV-IDM Edition: 9806A

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB13

Valve terminal type 03/05 Electronics Manual Field bus connection FB13 Valve terminal type 03/05 Electronics Manual Field bus connection FB13 Field bus protocol: PROFIBUS DP 12 MBaud 163958 GB Only valid in agreement with the printed documentation accompanying the product!

More information

Smart Positioning Controller SPC200 Fieldbus module PROFIBUS-DP

Smart Positioning Controller SPC200 Fieldbus module PROFIBUS-DP Smart Positioning Controller SPC200 Fieldbus module PROFIBUS-DP Type SPC200-COM-PDP Author: Translation: Editors: Layout: Type setting: S. Breuer Douglas Smith H.-J. Drung, M. Holder Festo AG & Co., Dept.

More information

CPX terminal. Manual Electronics. CPX bus node. Type CPX-M-FB20 and CPX-M-FB21. Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus

CPX terminal. Manual Electronics. CPX bus node. Type CPX-M-FB20 and CPX-M-FB21. Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus CPX terminal Manual Electronics CPX bus node Type CPX-M-FB20 and CPX-M-FB21 Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus Manual 575 108 en 1202a [8002868] Contents and general

More information

Manual. Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI. Manual en 9910NH

Manual. Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI. Manual en 9910NH Manual Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI Manual 396 535 en 9910NH Contents and general instructions Authors... Uwe Reimann, Timo Engelfried Editors... H.-J. Drung, M.Holder

More information

CPX terminal. Bus node CPX-FB38. Electronics description. Network protocol EtherCAT. Description en 1301a [ ]

CPX terminal. Bus node CPX-FB38. Electronics description. Network protocol EtherCAT. Description en 1301a [ ] CPX terminal Bus node CPX-FB38 Electronics description Network protocol EtherCAT Description 562525 en 1301a [8024385] Contents and general safety instructions Original... de Edition... en 1301a Designation...

More information

CPX terminal. Electronics Manual. CPX field bus node. Type CPX FB32. Field bus protocol EtherNet/IP. Manual [ ]

CPX terminal. Electronics Manual. CPX field bus node. Type CPX FB32. Field bus protocol EtherNet/IP. Manual [ ] CPX terminal Electronics Manual CPX field bus node Type CPX FB32 Field bus protocol EtherNet/IP Manual 541 305 en 0605NH [693 135] Contents and general instructions Original.......................................

More information

CPX terminal. Manual Electronics. CPX field bus node. Type CPX FB11. Field bus protocol DeviceNet. Manual en 0503b [ ]

CPX terminal. Manual Electronics. CPX field bus node. Type CPX FB11. Field bus protocol DeviceNet. Manual en 0503b [ ] CPX terminal Manual Electronics CPX field bus node Type CPX FB11 Field bus protocol DeviceNet Manual 526 422 en 0503b [689 002] Contents and general instructions Original.......................................

More information

CDVI-DN Valve Terminal (Type 15) DeviceNet

CDVI-DN Valve Terminal (Type 15) DeviceNet CDVI-DN Valve Terminal (Type 15) DeviceNet Description Electronics Valve terminal with direct fieldbus connection Fieldbus protocol: - DeviceNet CDVI-DN type Description 539 045 en 0805a [720 999] Contents

More information

Terminal CPX. Bus node CPX-FB14. Description. CANopen networkprotocol en 1411d [ ]

Terminal CPX. Bus node CPX-FB14. Description. CANopen networkprotocol en 1411d [ ] Terminal CPX Bus node CPX-FB14 Description CANopen networkprotocol 526410 en 1411d [8041138] Contents and general instructions Original... de Edition... en 1411d Designation... P.BE-FB14-EN Order no....

More information

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ]

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ] Compact performance Brief description CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8 English 8080251 2017-11e [8080244] Translation of the original instructions Documentation on the

More information

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ]

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ] CPX-Terminal Brief description CPX analogue I/O modules CPX-2AE CPX-4AE CPX-2AA English 8080173 2017-11e [8080175] Translation of the original instructions Documentation on the product For all available

More information

CPX terminal. Electronics Manual. CPX I/O modules, sub bases, pneumatic. electronic modules. Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB...

CPX terminal. Electronics Manual. CPX I/O modules, sub bases, pneumatic. electronic modules. Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB... CPX terminal Electronics Manual CPX I/O modules, sub bases, pneumatic interfaces and MPA electronic modules Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB... VMPA FB EPL... CPX GP... VABA 0S6 X VMPA...

More information

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ]

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ] Terminal CPX Electrical interface CPX CTEL 4 M12 5POL Description CTEL master module I-Port 574601 1411a [8041791] Electrical interface CPX CTEL 4 M12 5POL Translation of the original instructions P.BE-CPX-CTEL-EN

More information

Smart Positioning Controller SPC200 Stepping motor indexer module

Smart Positioning Controller SPC200 Stepping motor indexer module Smart Positioning Controller SPC200 Stepping motor indexer module Type SPC200-SMX-1 Author: Editors: Layout: Type setting: P. Mauch H.-J. Drung, M. Holder Festo AG & Co., Dept. KI-TD KI-TD Edition: 9904NH

More information

CPX terminal. Description Electronics. CPX fieldbus node. Type CPX-FB6. Fieldbus protocol: Interbus in accordance with EN 50254

CPX terminal. Description Electronics. CPX fieldbus node. Type CPX-FB6. Fieldbus protocol: Interbus in accordance with EN 50254 CPX terminal Description Electronics CPX fieldbus node Type CPX-FB6 Fieldbus protocol: Interbus in accordance with EN 50254 Description 526434 en 1207c [762320] Contents and general safety instructions

More information

Valve terminal types 03/04-B

Valve terminal types 03/04-B Valve terminal types 03/04-B Electronics manual Valve terminal with field bus connection PROFIBUS-DP 12 MBaud Type IFB13-03 Manual 163 958 en 0003c Contents and general instructions Authors... U. Reimann,

More information

Valve terminal types 03/04-B

Valve terminal types 03/04-B Valve terminal types 03/04-B Electronics manual Valve terminal with field bus connection FB8 Allen-Bradley RIO network Type IFB08-03 Manual 152 768 Contents and general instructions Author... H.-J. Drung

More information

CPX Terminal. Manual electronics. CPX control block. Type CPX SF34 Type CPX SF35. PC WORX integrated Network protocol PROFINET IO.

CPX Terminal. Manual electronics. CPX control block. Type CPX SF34 Type CPX SF35. PC WORX integrated Network protocol PROFINET IO. CPX Terminal Manual electronics CPX control block Type CPX SF34 Type CPX SF35 PC WORX integrated Network protocol PROFINET IO Manual 570 541 en 1007NH [748 167] Contents and general instructions Original.......................................

More information

CPX terminal. Electronics manual. CPX field bus node. Type CPX FB6. Field bus protocol: Interbus as per EN Manual en 0402b [ ]

CPX terminal. Electronics manual. CPX field bus node. Type CPX FB6. Field bus protocol: Interbus as per EN Manual en 0402b [ ] CPX terminal Electronics manual CPX field bus node Type CPX FB6 Field bus protocol: Interbus as per EN 50254 Manual 526 434 en 0402b [674 154] Contents and general instructions Author...................................

More information

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ]

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ] System CPX-E IO-Link master module CPX-E-4IOL- Description Protocol IO-Link Function Parameterisation 877 27-7 [879] IO-Link master module CPX-E-4IOL- Original instructions CPX-E-4IOL- -E N IO-Link is

More information

System CPX-E. Bus module CPX-E-PB. Description. Protocol PROFIBUS DP. Function Parameterisation [ ]

System CPX-E. Bus module CPX-E-PB. Description. Protocol PROFIBUS DP. Function Parameterisation [ ] System CPX-E Bus module CPX-E-PB Description Protocol PROFIBUS DP Function Parameterisation 8723 27-7 [8725] Bus module CPX-E-PB Original instructions CPX-E-PB-E N PI PROFIBUS PROFINET is a registered

More information

PROFIBUS for motor controller

PROFIBUS for motor controller Beschneiden: Oben: 61,5 mm Unten: 61,5 mm Links: 43,5 mm Rechts: 43,5 mm PROFIBUS for motor controller CMMP Description PROFIBUS CMMP Description 557 338 de 0708NH [723 751] Edition de 0708NH Description

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB15

Valve terminal type 03/05 Electronics Manual Field bus connection FB15 Valve terminal type 03/05 Electronics Manual Field bus connection FB15 Field bus protocol: EAE field bus-2 Only valid in agreement with the printed documentation accompanying the product! Compare this

More information

SPC200 Smart Positioning Controller

SPC200 Smart Positioning Controller SPC200 Smart Positioning Controller Electronics manual Field bus module for PROFIBUS DP type SPC200 COM PDP Manual 188 893 en 0901c [744 896] Contents and general instructions Original.......................................

More information

Compact performance. Electronics manual. CPV valve terminal with direct connection. Type CPV.. GE DN2 8. Field bus protocol: DeviceNet

Compact performance. Electronics manual. CPV valve terminal with direct connection. Type CPV.. GE DN2 8. Field bus protocol: DeviceNet Compact performance Electronics manual CPV valve terminal with direct connection Type CPV.. GE DN2 8 Field bus protocol: DeviceNet Manual 526 017 en 0503a [693835] Contents and general instructions Authors........................

More information

Terminal CPX. Bus node CPX-FB40. Description Electronics. Network protocol Ethernet POWERLINK NH [ ]

Terminal CPX. Bus node CPX-FB40. Description Electronics. Network protocol Ethernet POWERLINK NH [ ] Terminal CPX Bus node CPX-FB40 Description Electronics Network protocol Ethernet POWERLINK 8028651 1408NH [8028657] Bus node CPX-FB40 Translation of the original instructions P.BE-CPX-FB40-EN Ethernet

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB17

Valve terminal type 03/05 Electronics Manual Field bus connection FB17 Valve terminal type 03/05 Electronics Manual Field bus connection FB17 Field bus protocol: Jetter JETway-R 164226 GB Only valid in agreement with the printed documentation accompanying the product! Compare

More information

Compact performance. Electronics manual. CP modules. Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL

Compact performance. Electronics manual. CP modules. Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL Compact performance Electronics manual CP modules Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL Output module type CP A04 M12 CL Manual 539 300 en 0404NH [681 792] Contents and

More information

Compact Performance. Description. Electronics. CP fieldbus node 5. Programming and diagnosis. Type CP FB5 E

Compact Performance. Description. Electronics. CP fieldbus node 5. Programming and diagnosis. Type CP FB5 E Compact Performance Description Electronics CP fieldbus node 5 Programming and diagnosis Type CP FB5 E Fieldbus protocols: Festo fieldbus ABB CS 31 Moeller SUCOnet K Description 165 205 en 0802c [730 598]

More information

Compact performance. Description. Programming and diagnosis. CP fieldbus node 8. Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03

Compact performance. Description. Programming and diagnosis. CP fieldbus node 8. Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03 Compact performance Description Programming and diagnosis CP fieldbus node 8 Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03 Description 165 08 en 080e [730 609] Contents and general

More information

CPX terminal. US patent no. 6,216,738. Electronics manual. CPX CP interface. Type CPX CP 4 FB. Manual [ ]

CPX terminal. US patent no. 6,216,738. Electronics manual. CPX CP interface. Type CPX CP 4 FB. Manual [ ] US patent no. 6,216,738 CPX terminal Electronics manual CPX CP interface Type CPX CP 4 FB Manual 539 294 en 0405NH [681 785] Contents and general instructions Author...................................

More information

Terminal CPX. Bus node CPX-FB37. Description. Network protocol EtherCAT NH [ ]

Terminal CPX. Bus node CPX-FB37. Description. Network protocol EtherCAT NH [ ] Terminal CPX Bus node CPX-FB37 Description Network protocol EtherCAT 8029675 1406NH [8029664] CPX-FB37 Translation of the original instructions P.BE-CPX-FB37-EN EtherCAT,TwinCAT,CANopen,SPEEDCON,Torx,Windows

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB14

Valve terminal type 03/05 Electronics Manual Field bus connection FB14 Valve terminal type 03/05 Electronics Manual Field bus connection FB14 Field bus protocols: CANopen SDS Smart Distributed System 163959 GB 9801A Author: Editor: Translation: Layout: Type setting: S. Breuer,

More information

Valve terminal type 03/04 B

Valve terminal type 03/04 B Valve terminal type 03/04 B Electronics manual Field bus node Type IFB13 03 Field bus protocol PROFIBUS DP 12 MBaud Manual 163 958 en 0503f Contents and general instructions Author.................................

More information

Terminal CPX. Electrical interface CPX-CTEL-2-M12-5POL-LK. Description Electronics NH [ ]

Terminal CPX. Electrical interface CPX-CTEL-2-M12-5POL-LK. Description Electronics NH [ ] Terminal CPX Electrical interface CPX-CTEL-2-M12-5POL-LK Description Electronics 8034116 1405NH [8034124] Electrical interface CPX-CTEL-2-M12-5POL-LK Translation of the original instructions P.BE-CPX-CTEL-LK-EN

More information

Terminal CPX. Bus node CPX-(M)-FB33/34/35/41. Description. Network protocol PROFINET IO en 1410d [ ]

Terminal CPX. Bus node CPX-(M)-FB33/34/35/41. Description. Network protocol PROFINET IO en 1410d [ ] Terminal CPX Bus node CPX-(M)-FB33/34/35/41 Description Network protocol PROFINET IO 548760 en 1410d [8041494] Contents and general safety instructions Original... de Version... en 1410d Designation...

More information

Compact performance. Manual Electronics. CPV valve terminal with direct connection. Type CPV..-GE-DN-8. Field bus protocol: - DeviceNet

Compact performance. Manual Electronics. CPV valve terminal with direct connection. Type CPV..-GE-DN-8. Field bus protocol: - DeviceNet Compact performance Manual Electronics CPV valve terminal with direct connection Type CPV..-GE-DN-8 Field bus protocol: - DeviceNet Manual 175 563 en 0009a Contents and general instructions Authors...

More information

Fieldbus Direct Key features

Fieldbus Direct Key features Key features The system Extremely compact and spacesaving design Low-cost solution for the connection of a small number of valves to a fieldbus Extremely safe, protection class up to IP65 depending on

More information

SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation

SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation Introduction Prerequisites This guide takes you through

More information

PROFIBUS for Motor Controller

PROFIBUS for Motor Controller Trimming: Top: 61.5 mm Bottom: 61.5 mm Left: 43.5 mm Right: 43.5 mm PROFIBUS for Motor Controller CMMS Manual PROFIBUS CMMS Manual 554 346 en 0708NH [720 652] Version... en 0708NH Designation... P.BE-CMMS-FHPP-PB-SW-EN

More information

Electronics manual. Universal handheld. Commissioning and diagnosing CPX terminals. Manual [ ]

Electronics manual. Universal handheld. Commissioning and diagnosing CPX terminals. Manual [ ] Universal handheld Electronics manual Universal handheld type CPX MMI 1 Commissioning and diagnosing CPX terminals Manual 534 825 en 0305NH [668 828] Contents and general instructions Author Editor.....................................................................

More information

Valve terminal type 03/05 Electronics Manual Control block SB-202

Valve terminal type 03/05 Electronics Manual Control block SB-202 Valve terminal type 03/05 Electronics Manual Control block SB-202 Only valid in agreement with the printed documentation accompanying the product! Compare this edition code. 9602 Authors: Editors: Translation:

More information

CPX terminal. Description Electronics. System manual. Installing and. terminals. Description en 0902e [742939]

CPX terminal. Description Electronics. System manual. Installing and. terminals. Description en 0902e [742939] CPX terminal Description Electronics System manual Installing and commissioning CPX terminals Description 526 446 en 0902e [742939] Contents and general safety instructions Original.......................................

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB16

Valve terminal type 03/05 Electronics Manual Field bus connection FB16 Valve terminal type 03/05 Electronics Manual Field bus connection FB16 Field bus protocols: FIPIO standard Telemecanique - APRIL 164222 GB Only valid in agreement with the printed documentation accompanying

More information

Installation and Setup

Installation and Setup Installation and Setup 1 In This Chapter Installing the H PBC The Profibus Network Configuring the Controller Installing the H PBC Setting the Node Address Setting the Node Address Profibus DP is usually

More information

Compact performance. Programming and diagnostics manual. CP field bus node 11 Type CP FB11 E. Field bus protocol: DeviceNet

Compact performance. Programming and diagnostics manual. CP field bus node 11 Type CP FB11 E. Field bus protocol: DeviceNet Compact performance Programming and diagnostics manual CP field bus node 11 Type CP FB11 E Field bus protocol: DeviceNet Manual 165 211 en 0802d [730 616] Contents and general instructions Original.......................................

More information

DVPPF02-SL PROFIBUS DP Slave Communication Module

DVPPF02-SL PROFIBUS DP Slave Communication Module DVPPF02-SL PROFIBUS DP Slave Communication Module Operation Manual DVP-0155320-01 Warning This operation manual provides introduction on the functions, specifications, installation, basic operation, settings

More information

Operating Instructions (Compact) SIMATIC. Industrial PC SIMATIC Microbox PC 420. Siemens. Release 11/2006 A5E

Operating Instructions (Compact) SIMATIC. Industrial PC SIMATIC Microbox PC 420. Siemens. Release 11/2006 A5E Operating Instructions (Compact) 1 SIMATIC Industrial PC Release 11/2006 A5E00344128-04 Siemens Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety,

More information

CPX Terminal. Manual Electronics. CPX Bus Node. Type CPX FB33 Type CPX FB34. Network protocol PROFINET IO. Manual [ ]

CPX Terminal. Manual Electronics. CPX Bus Node. Type CPX FB33 Type CPX FB34. Network protocol PROFINET IO. Manual [ ] CPX Terminal Manual Electronics CPX Bus Node Type CPX FB33 Type CPX FB34 Network protocol PROFINET IO Manual 548 760 en 0710NH [706 040] Contents and general instructions Original.......................................

More information

Siemens Drives & PLCs

Siemens Drives & PLCs Automation System S7-300: Getting Started CPU 31xC: Commissioning Introduction 1 Preparation 2 SIMATIC S7-300 Automation System S7-300: Getting Started CPU 31xC: Commissioning Learning units 3 Further

More information

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module Installation and Setup 1 2 In This Chapter.... Installing the H0 PSCM The Profibus Network Configuring the Module 2 2 Installing the H0 PSCM Remove the Slot Cover The first step in installing the option

More information

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description Inline Block IO Module for PROFIBUS With 32 Digital Outputs AUTOMATIONWORX Data Sheet 6889_en_04 Description PHOENIX CONTACT - 03/2007 & & ' ) The ILB PB 24 DO32 module is designed for use within a PROFIBUS

More information

CPX-E-CEC-... Controller. Description Function, Parameterisation [ ]

CPX-E-CEC-... Controller. Description Function, Parameterisation [ ] CPX-E-CEC-... Controller Description Function, Parameterisation 8071235 8071235 2018-09 [8071237] Translation of the original instructions CODESYS, EtherCAT, MODBUS are registered trademarks of the respective

More information

BNI PBS Z001. IP67 module, Profibus IO-Link Master Short Guide

BNI PBS Z001. IP67 module, Profibus IO-Link Master Short Guide BNI PBS-502-001-Z001 IP67 module, Profibus IO-Link Master Short Guide 1 Notes for the User 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations 2 1.3.2

More information

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001. Quick start guide

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001. Quick start guide BNI PBS-104-000-Z001 BNI PBS-102-000-Z001 BNI PBS-302-000-Z001 Quick start guide Content 1 Notes for the User 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations

More information

SPC200 Smart Positioning Controller

SPC200 Smart Positioning Controller SPC200 Smart Positioning Controller Electronics Manual Field bus module for DeviceNet type SPC200 COM DN2 Manual 196 608 en 0511a [688 393] Contents and general instructions Original.......................................

More information

Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366

Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366 Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366 AS-i master profile: M4 Firmware: from version RTS 3.0 onwards Target: from V.15 onwards for CoDeSys from

More information

VIFB9-02. Michael Holder, H.-J. Drung. Festo, Dept. PV-IDM. Type setting: Edition (Festo AG & Co., D Esslingen, 1997)

VIFB9-02. Michael Holder, H.-J. Drung. Festo, Dept. PV-IDM. Type setting: Edition (Festo AG & Co., D Esslingen, 1997) Author: Editors: Translation: Layout: Type setting: Heinz Hohner Michael Holder, H.-J. Drung Douglas Smith Festo, Dept. PV-IDM DUCOM Edition 9706 printed on 100% receycling paper (Festo AG & Co., D-73726

More information

Positioner CMSX-...-C-U-F1-...

Positioner CMSX-...-C-U-F1-... Positioner CMSX-...-C-U-F-.... CMSX-SE-... (linear) Festo AG & Co. KG Postfach Esslingen Germany +9-0 www.festo.com aj 9 8 (en) Operating instructions 8088 09NH [8080] Original: de Positioner CMSX... English

More information

SIMATIC. DP/DP Coupler A B. Preface, Contents. Product Overview. Installation. Wiring. Manual. Configuring and commissioning

SIMATIC. DP/DP Coupler A B. Preface, Contents. Product Overview. Installation. Wiring. Manual. Configuring and commissioning SIMATIC Manual Preface, Contents Product Overview Installation Wiring Configuring and commissioning Operation of the Diagnostics 1 2 3 4 5 6 Appendices Technical data Order numbers and accessories A B

More information

RMx621. Appendix to the operating manual

RMx621. Appendix to the operating manual Appendix to the operating manual RMx621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 to PROFIBUS DP via the RS485 serial interface using the external module (HMS AnyBus Communicator

More information

SIMATIC. FM 356 Application Function Module, Installation and Startup. Preface, Contents. User Information. Product Overview

SIMATIC. FM 356 Application Function Module, Installation and Startup. Preface, Contents. User Information. Product Overview Preface, Contents User Information SIMATIC FM 356 Application Function Module, Installation and Startup Manual Product Overview 1 Designing the Mechanical Configuration 2 Addressing the M7-300 Modules

More information

Operation Manual Profibus DP -Display HE 5120 P with digital I/O's

Operation Manual Profibus DP -Display HE 5120 P with digital I/O's Operation Manual Profibus DP -Display HE 510 P with digital I/O's "HESCH" Schröder GmbH Boschstraße 8 31535 Neustadt Telefon +49 (0) 503 / 9535-0 Telefax +49 (0) 503 / 9535-99 e-mail: info@hesch.de http://www.hesch.de

More information

MOVITRAC 31.. Frequency Inverter

MOVITRAC 31.. Frequency Inverter MOVITRAC 31.. Frequency Inverter PROFIBUS Fieldbus (FFP 31.. Option and Size 0/DP) Manual Edition 04/98 08/198/96 0922 6818 / 0498 Important Notes Read this User Manual carefully before you start installation

More information

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date: Documentation Sixteen channel digital output module with D-Sub Connector Version: Date: 2.0.0 2017-11-20 Table of contents Table of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety

More information

Device manual Field modules DP AC2630 / AC2631 / AC2634 AC2636 / AC2637 / AC / / 2013

Device manual Field modules DP AC2630 / AC2631 / AC2634 AC2636 / AC2637 / AC / / 2013 Device manual Field modules DP AC2630 / AC2631 / AC2634 AC2636 / AC2637 / AC2638 7390983 / 00 03 / 2013 Contents 1 Preliminary note................................................. 4 2 Safety instructions...............................................

More information

RMx621 /FML621. Appendix to the operating manual

RMx621 /FML621. Appendix to the operating manual Appendix to the operating manual RMx621 /FML621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 /FML621 to PROFIBUS DP via the RS485 serial interface using the external module

More information

VersaMax IP Input Module

VersaMax IP Input Module Module is used to accept digital input signals. Module Specifications Housing dimensions (width x height x depth) Connection style Operating temperature Storage temperature Operating/storage humidity 60mm

More information

Fieldbus Direct Key features

Fieldbus Direct Key features Fieldbus Direct Fieldbus Direct Key features The system Extremely compact and spacesaving design Low-cost solution for the connection of a small number of valves to a fieldbus Extremely safe, protection

More information

Device manual Profibus encoder. RM30xx RN30xx /00 06/2013

Device manual Profibus encoder. RM30xx RN30xx /00 06/2013 Device manual Profibus encoder RM30xx RN30xx 706355/00 06/2013 Contents 1 Preliminary note................................................. 4 1.1 Symbols used...............................................

More information

FESTO Valve Terminals with EMERSON DeltaV Software

FESTO Valve Terminals with EMERSON DeltaV Software FESTO Valve Terminals with EMERSON DeltaV Software - Made by RAFT & SSIM - Contents: Page 1. CPX-FB13 & Emerson DeltaV 3 1.1. Configuring CPX-FB13 3 1.2. CPX-FB13 online diagnostics 11 1.3. How to use

More information

Positioner CMSX-...-C-U-F1-...

Positioner CMSX-...-C-U-F1-... Positioner CMSX-...-C-U-F-.... CMSX-SE-... (linear) 5 Festo AG & Co. KG Postfach Esslingen Germany +9-0 www.festo.com (en) Operating instructions 80595 0a [80595] aj 9 8 Housing cover Inspection window

More information

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date:

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date: Documentation KM2604 and KM2614 Four channel relay module Version: Date: 2.1.0 2017-12-01 Tabel of contents Tabel of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety instructions...

More information

A B

A B ET 200U Distributed I/O Station Manual System Overview Technical Description Mechanical and Electrical Configuration ET 200U(DP Siemens): Address Assignment, Starting Up, Diagnosing Faults ET 200U(DP Standard):

More information

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide BNI PBS-104-000-Z001 BNI PBS-302-000-Z001 BNI PBS-501-000-Z001 BNI PBS-502-000-Z001 Short Guide English 1 2 3 4 Notes to the User 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical

More information

Operation Manual. Fieldbus system EX510-GPR1. PROFIBUS DP Compatible GW unit

Operation Manual. Fieldbus system EX510-GPR1. PROFIBUS DP Compatible GW unit Fieldbus system PROFIBUS DP Compatible GW unit Operation Manual EX50-GPR URL http://www.smcworld.com Akihabara UDX 5F, --, Sotokanda, Chiyoda-ku, Tokyo 0-00, JAPAN Phone: +8 3-507-89 Fax: +8 3-598-536

More information

PROFIsafe SITRANS. Pressure transmitter SITRANS P, DS III PROFIsafe series. Product Information 7MF4*34 04/2008 A5E

PROFIsafe SITRANS. Pressure transmitter SITRANS P, DS III PROFIsafe series. Product Information 7MF4*34 04/2008 A5E 1 SITRANS Pressure transmitter SITRANS P, DS III PROFIsafe series Product Information 7MF4*34 04/2008 A5E00732533-02 Safety Guidelines This manual contains notices you have to observe in order to ensure

More information

SUBCON-PLUS-PROFIB...

SUBCON-PLUS-PROFIB... Fast connector for PROFIBUS systems Data sheet 101610_en_10 PHOENIX CONTACT 2017-03-27 1 Description The SUBCON-PLUS-PROFIB... D-SUB series is specifically designed for use in PROFIBUS systems up to 12

More information

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date: Documentation Sixteen Channel Digital Output Module with D-Sub Connector Version: Date: 2.0 2016-08-03 Table of contents Table of contents 1 Foreword... 4 1.1 Notes on the documentation... 4 1.2 Safety

More information

This manual may not be reproduced in whole or in part by any means, without written permission of Accuenergy.

This manual may not be reproduced in whole or in part by any means, without written permission of Accuenergy. Copyright 2008 V1.10 This manual may not be reproduced in whole or in part by any means, without written permission of Accuenergy. The information contained in this document is believed to be accurate

More information

Compact Performance. Electronics manual. CPV valve terminal with direct connection Type CPV.. GE CC 8. Field bus protocol: CC link.

Compact Performance. Electronics manual. CPV valve terminal with direct connection Type CPV.. GE CC 8. Field bus protocol: CC link. Compact Performance Electronics manual CPV valve terminal with direct connection Type CPV.. GE CC 8 Field bus protocol: CC link Manual 197 964 en 0304NH [674 139] Contents and general instructions Author...................................

More information

PumpDrive DPM. Installation and Operating Instructions Dual Pump Module (DPM) /4--10

PumpDrive DPM. Installation and Operating Instructions Dual Pump Module (DPM) /4--10 4070.83/4--10 PumpDrive DPM Installation and Operating Instructions Dual Pump Module (DPM) These installation and operating instructions are not valid on their own. They must always be applied in conjunction

More information

TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES. Pg. 1 di 14

TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES. Pg. 1 di 14 TB3P/TB4P I/O PROFIBUS DP FIELDBUS MODULE FOR PNEUMATIC MANIFOLD VALVES Pg. 1 di 14 INDEX Legend of Symbols... 3 Conformity Declaration... 3 System Descripiton... 4 Module Specifications... 4 Installation

More information

CPX Terminal. Electronics Manual. CoDeSys Controller. Type CPX CEC C1. Manual [ ]

CPX Terminal. Electronics Manual. CoDeSys Controller. Type CPX CEC C1. Manual [ ] CPX Terminal Electronics Manual CoDeSys Controller Type CPX CEC C1 Manual 569 122 en 0907NH [745 684] Contents and general instructions Original....................................... de Edition.................................

More information

Motion Terminal VTEM. Description. Motion App #04. Model-based proportional pressure regulation [ ]

Motion Terminal VTEM. Description. Motion App #04. Model-based proportional pressure regulation [ ] Motion Terminal VTEM Description Motion App #04 Model-based proportional pressure regulation 8086805 2018-05 [8086807] VTEM Translation of the original instructions VTEM-MA04-E N Firefox is a registered

More information

PROFIBUS MODULE (CB15) English Operating Instructions. Contents. Warning and Caution Notes

PROFIBUS MODULE (CB15) English Operating Instructions. Contents. Warning and Caution Notes Contents Warning and Caution Notes 1. OVERVIEW 1.1 Description and Features 1.2 Application on a PROFIBUS Link 2. INSTALLATION 2.1 Connecting the Bus Cable 2.1.1 Terminals 2.1.2 Bus Cabling 2.2 EMC Measures

More information

Sample project Filling Station SIMATIC. STEP 7 Professional / WinCC Advanced V11 for Sample project Filling Station. Overview of the Getting.

Sample project Filling Station SIMATIC. STEP 7 Professional / WinCC Advanced V11 for Sample project Filling Station. Overview of the Getting. Overview of the Getting Started 1 Create "Filling Station" example project 2 SIMATIC STEP 7 Professional / WinCC Advanced V11 for Getting Started Inserting and configuring hardware 3 Programming the PLC

More information

Type ME43. Quickstart

Type ME43. Quickstart Type ME43 Fieldbus gateway büs to Industrial Ethernet, PROFIBUS DPV1, CC-Link Feldbus-Gateway büs zu Industrial Ethernet, PROFIBUS DPV1, CC-Link Passerelle bus de terrain büs vers Ethernet industriel,

More information

Terminal CPX. Bus node CPX FB36. Description. Network protocol EtherNet/IP Modbus TCP. Industrial Ethernet 2-Port en 1611a [ ]

Terminal CPX. Bus node CPX FB36. Description. Network protocol EtherNet/IP Modbus TCP. Industrial Ethernet 2-Port en 1611a [ ] Terminal CPX Bus node CPX FB36 Description Network protocol EtherNet/IP Modbus TCP Industrial Ethernet 2-Port 8024075 en 1611a [8067476] Contents and general instructions Original... de Version... en

More information

Terminal CPX. Input module CPX-F8DE-P. Description en 1505NH [ ]

Terminal CPX. Input module CPX-F8DE-P. Description en 1505NH [ ] Terminal CPX Input module CPX-F8DE-P Description 8035497 en 1505NH [8035505] Contents and general instructions Translation of the original instructions Original... de Version... en 1505NH Designation...

More information

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block USER S MANUAL FX2N-64DNET DeviceNet Interface Block FX2N-64DNET DeviceNet Interface Block Foreword This manual contains text, diagrams and explanations which will guide the reader in the correct installation

More information

PROFIBUS for motor controller CMMS/CMMD

PROFIBUS for motor controller CMMS/CMMD Trimming: On top: 61.5 mm Underneath: 61.5 mm Left: 43.5 mm Right: 43.5 mm PROFIBUS for motor controller CMMS/CMMD Description DeviceNet CMMS-ST CMMS-AS CMMD-AS Description 554 358 en 1103a [757 722] Edition

More information

Motor unit MTR-DCI. Brief overview MTR-DCI. English d [ ]

Motor unit MTR-DCI. Brief overview MTR-DCI. English d [ ] Motor unit MTR-DCI Brief overview MTR-DCI English 8076565 2017-12d [8076567] Translation of the original instructions Documentation on the product For all available product documentation www.festo.com/pk

More information