CPA SC/CPV SC PROFIBUS DP

Size: px
Start display at page:

Download "CPA SC/CPV SC PROFIBUS DP"

Transcription

1 Valve terminals CPA SC/CPV SC PROFIBUS DP Electronics Manual Valve terminals Field bus direct Field bus protocol: PROFIBUS DP as per EN Type CPA SC DP Type CPV SC DP Manual en 0610NH [ ]

2

3 Contents and general instructions Original de Edition en 0610NH Designation P.BE CPASC CPVSC DP EN Order no (Festo AG & Co. KG, D Esslingen, Germany, 2006) Internet: E Mail: service_international@festo.com The reproduction, distribution and utilization of this document as well as the communicaton of its contents to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility module or design. I

4 Contents and general instructions PROFIBUS, PROFIBUS DP SIMATIC TORX are registered trade marks of PROFIBUS International (P.I.) is a registered trade name of Siemens AG is a registered trade name of CAMCAR TEXTRON INC., Rockford, Ill., USA II

5 Contents and general instructions Contents Designated use of the valve terminals Notes on the use of this manual Service Important user instructions VII VIII VIII IX 1. Installation General notes on installation Setting the rotary and DIL switches Setting the station number Deactivating the device related diagnosis Setting the CP extension Connecting to the field bus Field bus cable Field bus baud rate and field bus length Field bus interface Connection possibilities Bus connection with terminating resistors Power supply Calculating the current consumption Selecting the cable Selecting the power unit Connect the power supply of the valve terminal Extending the CP... SC DP on the CP extension connection Rules for extending the CPI system III

6 Contents and general instructions 2. Commissioning Preparing the valve terminal for commissioning Switching on the operating voltages Address assignment CPA SC DP Address assignment CPV SC DP Address assignment of CPI/CP modules Commissioning on the PROFIBUS DP Device master file (GSD) and icon files Configuration with a Siemens master STEP 7 HW Config (up to V 5.2) preparations Station selection with STEP Configuration with STEP Tool change configuration Examples of configuration Standard configuration Tool change configuration Diagnosis Diagnosis via LEDs Normal operating status Fault displays LEDs for status display of the valve solenoid coils Reaction to faults in the control system Diagnosis via PROFIBUS DP Diagnosis steps Overview of the diagnostic bytes Details on standard diagnostic information Details of the identification related diagnosis Channel related diagnosis Diagnosis with tool change configuration Siemens SIMATIC S5/S Online diagnosis with STEP Read out diagnostic buffer with STEP 7 (up to V 5.2) Channel related diagnosis with STEP 7 (up to V 5.3) IV

7 Contents and general instructions A. Technical appendix A 1 A.1 Technical specifications A 3 A.2 Accessories A 5 B. General DP master B 1 B.1 PROFIBUS DP: Commissioning with the general DP master B 3 B.1.1 Bus start B 3 B.1.2 Send parametriziung data B 4 B.1.3 Check the configuration data B 6 B.1.4 Transferring input and output data B 7 B.1.5 Read diagnostic information B 7 B.1.6 Implemented functions and service access points (SAP) B 8 B.1.7 Bus parameters/reaction times B 9 B.1.8 Transmission times on the PROFIBUS DP B 9 C. Index C 1 V

8 Contents and general instructions VI

9 Contents and general instructions Designated use of the valve terminals The valve terminals of types CPA SC DP and CPV SC DP with field bus direct connection described in this manual are in tended exclusively for use as slaves on the PROFIBUS DP. The valve terminals may only be used as follows: as designated in industrial applications. without any modifications by the user. Only the conver sions or modifications described in the documentation supplied with the product are permitted. in faultless technical condition. The maximum values specified for pressures, temperatures, electrical data, torques etc. must be observed. If additional commercially available components such as sen sors and actuators are connected, the specified limits for pressures, temperatures, electrical data, torques, etc. must not be exceeded. Observe also the standards specified in the relevant chapters, as well as national and local laws and technical regulations. If implementing an emergency stop function, note the measures listed in section VII

10 Contents and general instructions Notes on the use of this manual Areas of application and approval by authorities Certain configurations of the product have been approved by the Underwriters Laboratories Inc. (UL) as UL Recognized Component" for the USA and Canada. These configurations are marked as follows: Only for connection to a 24 V DC NEC Class 2 supply. Raccorder Uniquement a un circuit de Classe 2. Please note Please note the following if this product is intended for use in the USA and Canada: Rules for observing the UL approval can be found in the separate UL specific brief operating instructions. The relevant technical specifications listed there also apply here. The technical specifications in this documentation may show different values. Target group This manual is intended exclusively for technicians trained in control and automation technology who have experience in installing, commissioning, programming and diagnosing slaves on the field bus named. Information on the pneumatics can be found in: 1. CPA SC: Pneumatics Manual P.BE CPASC.. 2. CPV SC: Pneumatics Manual P.BE CPVSC.. Service Please consult your local Festo repair service if you have any technical problems. VIII

11 Contents and general instructions Important user instructions Danger categories This manual contains instructions on the possible dangers which may occur if the product is not used correctly. These instructions are marked (Warning, Caution, etc.), printed on a shaded background and marked additionally with a picto gram. A distinction is made between the following danger warnings: Warning This means that failure to observe this instruction may result in serious personal injury or damage to property. Caution This means that failure to observe this instruction may result in personal injury or damage to property. Please note This means that failure to observe this instruction may result in damage to property. The following pictogram marks passages in the text which describe activities with electrostatically sensitive compo nents. Electrostatically sensitive components may be damaged if they are not handled correctly. IX

12 Contents and general instructions Marking special information The following pictograms mark passages in the text containing special information. Pictograms Information: Recommendations, tips and references to other sources of information. Accessories: Information on necessary or sensible accessories for the Festo product. Environment: Information on environment friendly use of Festo products. Text markings The bullet indicates activities which may be carried out in any order. 1. Figures denote activities which must be carried out in the numerical order specified. Hyphens indicate general activities. X

13 Contents and general instructions The following product specific terms and abbreviations are used in this manual: Term/abbreviation CP CP connection CP functions CP string CP system Meaning Compact performance Plug or socket on the CP modules which enable the modules to be connected with the aid of the CP cable. Supports the CP protocol without extended functions CPI or CP modules which are connected via a CPI/CP cable and to a CPI master. For reasons of simplicity, only the term CP string" is used, even if it has CPI functions. Complete electrical installation system consisting of a CP master with one or more CP strings. The system consists of CP modules (without extended functions). CPA SC CPA Smart Cubic valve terminal, type 82 CPI/CP cable CPI/CP modules CPI functions CPI master CPI system Special cable for connecting the different CPI/CP modules. CPI cables are required for CPI modules with extended functions. Collective term for the various modules that can be incorporated in a CPI/CP system. Supports the CPI protocol with extended functions The CP... SC DP is a CPI master. CPI modules with extended functions can be connected to the CP extension connection. Complete electrical installation system consisting of a CP master with one or more CP strings. The system consists of CPI/CP modules with and without extended functions. The system need not consist exclusively of CPI modules. CPV SC CPV Smart Cubic valve terminal, type 80 I I/O modules I/Os Load voltage Digital input Common term for the CP modules which provide digital inputs and outputs (CP input modules and CP output modules). Digital inputs and outputs Power supply for valves XI

14 Contents and general instructions Term/abbreviation O Operating voltage PLC/IPC Meaning Digital output Power supply for the electronics Programmable logic controller/industrial PC Tab. 0/1: Product specific terms and abbreviations XII

15 Installation Chapter 1 1 1

16 1. Installation Contents 1. Installation General notes on installation Setting the rotary and DIL switches Setting the station number Deactivating the device related diagnosis Setting the CP extension Connecting to the field bus Field bus cable Field bus baud rate and field bus length Field bus interface Connection possibilities Bus connection with terminating resistors Power supply Calculating the current consumption Selecting the cable Selecting the power unit Connect the power supply of the valve terminal Extending the CP... SC DP on the CP extension connection Rules for extending the CPI system

17 1. Installation 1.1 General notes on installation Warning Sudden unexpected movements of the connected actua tors and uncontrolled movements of loose tubing can cause injury to human beings and/or damage to property. Make sure that the higher order controller has not sent control signals to the valve solenoid coils. Switch off the following on the CP... SC DP before carrying out conversion work: the compressed air supply the power supply. Please note The CP... SC DP valve terminal contains electrostatically sensitive components. Do not therefore touch the electrical contacts of the components. Observe the regulations for handling electrostatically sensitive components. You will then prevent the electronics from being damaged. Please note Please note the following if this product is intended for use in the USA and Canada: Rules for observing the UL approval can be found in the UL specific brief operating instructions. The relevant technical specifications listed there also apply here. The technical specifications in this documentation may show different values. 1 3

18 1. Installation Electrical connections and operating elements You will find the following connections and operating elements on the valve terminals type CP... SC DP: CPA SC DP CPV SC DP Rotary switch for station number 2 DIL switch for CP extension and for deactivating the device related diagnosis 3 LEDs (see section 3.1) 5 Connection for CP extension 6 Connection for power supply 7 Connection for field bus 8 Cover (for IP40) 4 Earth connection Fig. 1/1: Electrical connections and operating elements 1 4

19 1. Installation 1.2 Setting the rotary and DIL switches Address 1 Setting the station number 2 Device related diagnosis deactivated/activated 3 Setting/recognizing the CP extension Fig. 1/2: Rotary and DIL switches on the CP... SC DP 1 5

20 1. Installation Setting the station number Set the PROFIBUS address of the valve terminal by means of the rotary switches. Station numbers between 0 and 125 are permitted. Station numbers may only be assigned once per field bus master. If a non permitted station number is set, the BF LED will flash fast (see section 3.1). Station number set: 05 Station number set: 110 Tab. 1/1: Examples of set station numbers 1 6

21 1. Installation Deactivating the device related diagnosis You can deactivate the device related diagnosis with DIL switch element 2 (see also section 3.3): Device related diagnosis Position of DIL switches DIL switch element 2 = OFF: Device related diagnosis activated (factory setting) ON OFF DIL switch element 2 = ON: Device related diagnosis deactivated ON OFF Tab. 1/2: Deactivate the device related diagnosis Switch elements 3 and 4 are reserved (position: OFF). 1 7

22 1. Installation Setting the CP extension Further CPI/CP modules can be connected to the CP connec tion of the CP... SC DP (see section 1.6). Recognition is controlled by DIL switch element 1: Extending the valve terminal Position of the DIL switches If no CP extension is connected, switch element 1 must be set to OFF ON OFF Modifying the CP extension (adding or removing CPI/CP modules): 1. Switch off all sources of energy (voltage, compressed air). 2. Connect or remove CPI/CP modules 3. Set DIL1 to ON. 4. Switch on the operating voltage (electronics) again. The CP... SC now searches for connected CPI/CP modules. If modifications to the CP configuration are recognized, the SF LED will flash. 5. Set DIL1 to OFF again. Then set to ON again and leave it on. The CP system is now configured and ready to run (LED SF is out). If modifications have been made to the CP extension: 6. Start the recognition procedure again (steps ) ON OFF ON OFF Tab. 1/3: Set the CP extension with DIL switch element 1 Please note The CP system will occupy a different number of input and output addresses depending on the extension recognized. The CP... SC DP supports CPI modules with extended func tionality. Further information can be found in section

23 1. Installation 1.3 Connecting to the field bus Field bus cable Please note If installation has not been carried out correctly and if high baud rates are used, data transmission errors may occur as a result of signal reflections and attenuations. Causes of the transmission faults may be: missing or incorrect terminating resistor incorrect screening/shield connection branches transmission over long distances unsuitable cables. Observe the cable specifications. Refer to your controller manual for information on the type of cable to be used. Please note If the valve terminal is fitted into a moving part of a machine, the field bus cable on the moving part must be provided with strain relief. Please observe also the relevant regulations in EN part

24 1. Installation Use a twisted screened 2 core cable for the field bus in accordance with PROFIBUS specifications (EN 50170, cable type A): Surge impedance: ( MHz) Capacitance per unit length: < 30 nf/km Loop resistance: < 110 /km Core diameter: > 0.64 mm Core cross sectional area: > 0.34 mm 2 Bus length Exact specifications on the bus length can be found in the next section and in the manuals for your control system Field bus baud rate and field bus length Please note The maximum permitted field bus segment lengths depend on the baud rate used. Note the maximum permitted segment length (cable length without repeater), if you connect the SFC DC to a field bus segment. Avoid branch lines. The valve terminal sets itself automatically to one of the following baud rates: Baud rate Maximum segment length 9.6; 19.2; kbaud 1200 m kbaud 1000 m 500 kbaud 400 m 1500 kbaud 200 m kbaud 100 m Tab. 1/4: Maximum field bus segment lengthsfor PROFIBUS DP depending on the baud rate 1 10

25 1. Installation Field bus interface There is a 9 pin sub D socket on the valve terminal for connecting it to the field bus. This connection serves for the incoming and continuing field bus cable. Pin PROFIBUS DP Designation Housing Screening/shield n.c. RxD/TxD P CNTR P 2) DGND VP n.c. RxD/TxD N n.c. Screening Connection to functional earth not connected Receive/transmit data P Repeater control signal (TTL) Data reference potential (M5V) Power supply positive (P5V) not connected Receive/transmit data N not connected Connection to functional earth Socket on valve terminal Tab. 1/5: Pin assignment of the field bus interface 1 11

26 1. Installation Connection possibilities Field bus plug Use the following for connecting the field bus plug for PROFIBUS: Possible plugs with protection class IP40 e.g.: Siemens 6ES BA10 0XA0 Siemens 6ES BA20 0XA0 Connection with optical fibre waveguide The PROFIBUS DP interface of the node complies with specifi cation EN and supports the control of network com ponents for optical fibre waveguides. Use optical fibre waveguides when transmission is affected by heavy interference, as well as for extending the trans mission range when high baud rates are used. Example of optical fibre waveguide network components: Siemens Optical Link Module (OLM) for PROFIBUS plus Siemens Optical Link Plug (OLP) for PROFIBUS (IP20) Harting Han InduNet Media converter IP65 in combina tion with adapter cable for Festo products (optical data transmission in DESINA installation concept). 1 12

27 1. Installation 1.4 Bus connection with terminating resistors Please note If the valve terminal is at the beginning or the end of the field bus system, a bus termination will be required. Fit a bus termination to both ends of a bus segment. Recommendation Use a ready made field bus plug with a suitable resistance network in the housing for the bus connection (see Fig. 1/3). This can be activated/deactivated by a switch. Pin 6: Supply voltage 390 Receive/send data P (data cable B) Pin nh 220 Receive/send data N (data cable A) Pin nh 390 Pin 5: Data reference potential Fig. 1/3: Circuit diagram for bus termination network for cable type A as per EN

28 1. Installation 1.5 Power supply Calculating the current consumption Calculate the current consumption before selecting power units, cables and fuses: Current consumption Sums Electronics and sensors (pin 1) CP... SC DP 200 ma In the CP extension: Valve terminal 1) or CP output module 1) CPI/CP input module 1) ma ma Sensors 1) on the CPI/CP input module x ma ma Sum of pin 1 = ma Valves and outputs (pin 2) CP... SC DP: all energized simultaneously Solenoid coils 2) 3) x ma ma In the CP extension: All solenoid coils energized simultaneously 2) 3) x ma ma All digital outputs 1) 4) x ma ma Sum of pin 2 Total = ma = ma 1) See technical specifications for the relevant product. 2) The valves have one or two solenoid coils depending on the type. 3) When switching on, with LEDs. 4) If not with own load voltage supply. Tab. 1/6: Calculating the current consumption 1 14

29 1. Installation Selecting the cable Calculate the necessary cross sectional area and the maximum permitted cable length. Avoid long distances between the power unit and the valve terminal. Long cables reduce the voltage supplied by the power unit Selecting the power unit Warning For the power supply use only PELV circuits as per IEC/DIN EN (Protective Extra Low Voltage, PELV). Take into account also the general requirements for PELV circuits as per IEC/DIN EN Use only power packswhich guarantee reliable electrical isolation of the operating voltage as per IEC/DIN EN By the use of PELV power units, protection against electric shock (protection against direct and indirect contact) is guar anteed in accordance with IEC/DIN EN (electrical equipment of machines, general requirements). The current requirement of a CP system depends on the number of CP modules and valve coils. Recommendation: Use closed loop controlled power units. When selecting the power unit, check that it provides sufficient output. Calculate the total current requirement in accordance with section

30 1. Installation Connect the power supply of the valve terminal Please note Use only a socket in accordance with appendix A.2 for the power supply and connect this only to the connection for the power supply (see Fig. 1/1). Pin assignment of the power supply connection Assignment Pin Plug on CP... SC (A coded) 24 V DC electronics and sensors 24 V DC valves and outputs 0 V electronics and sensors 0 V valves and outputs FE Pin 1 Pin 2 Pin 3 Pin 4 Pin Tab. 1/7: Pin assignment of the power supply connection Please note In order to extend CP valve terminals or output modules without additional supply, you must insert a bridge between pins 3 and 4. However, the electrical isolation will then no longer be effective (see Fig. 1/6). 1 16

31 1. Installation 1 Cable 2 Strain relief 3 Housing 4 Connecting part Fitting the connector socket Fig. 1/4: Preparing Individual parts of plug and cable exit When you have selected suitable cables, connect them as follows (Fig. 1/4): 1. In order to open the plug, loosen the centre knurled nut. 2. Open the strain relief on the rear part of the housing. Then pass the cable through. 3. Remove 5 mm of insulation from the end of the cable and fit end sleeves on the strands. 4. Connect the ends of the conductors. 5. Replace the connector part on the housing of the socket. Pull the cable back so that there are no loops inside the housing. 6. Tighten the strain relief. 1 17

32 1. Installation Observe the following when connecting the 24 V load voltage (pin 2): Observe the tolerance ( V DC). Check the 24 V load voltage of the valves while the system is operating. Caution Excessive voltages or short circuits can lead to functional damage to the CP... SC DP, whereby actuators can no longer be controlled. Protect the load voltage of the valve coils with external fuses. In order to ascertain the size of the fuses, calculate first the maximum current consumption in accordance with section Please note Check your emergency stop circuit, in order to ascertain the measures necessary for switching your machine/sys tem into a safe state in the event of an emergency stop. Switching off the load voltage for the valves and output modules in the secondary circuit of the power unit. Switching off the compressed air supply for the valve terminal. Due to energy stored in the input circuitry of valve ter minals, there may be a delayed reaction of the valves when the load voltage is switched off. Take this into consideration, e.g. as follows: by using an input signal in the controller for checking whether the load voltage has been switched off. by blocking the control signal for the valves by locking the output signal with the input signal Load voltage". 1 18

33 1. Installation Potential equalization Earth the valve terminal: at the power supply connection (pin 5) and at the earth connection of the housing (see Fig. 1/1). Please note By means of low impedance connections, make sure that the housing of the valve terminal and the earth connection at pin 5 have the same potential and that there are no equalizing currents. In this way, you will avoid interference caused by electro magnetic influences. 1 19

34 1. Installation Connecting the voltage supply Connection for voltage supply 2 Potential equalization 3 Earth connection at pin 5 4 Load voltage can be switched off separately and external fuses (design as per section 1.5.2) 5 Protective earth (PE) Fig. 1/5: Example of connections for power supply with a PELV power unit 1 20

35 1. Installation Connecting the power supply with electrical isolation of the electronics and the load voltage 1 Power unit for load voltage (valves and outputs) 2 Device for isolation monitoring 3 Load voltage can be switched off separately and external fuses (design as per section 1.5.2) Power unit for operating voltage (electronics and sensors) 4 2 Fig. 1/6: Example of connections for power supply with two PELV power units Please note Electrical isolation will not be possible if you loop the voltage through to further I/O modules without electrical isolation. 1 21

36 1. Installation 1.6 Extending the CP... SC DP on the CP extension connection Further CPI/CP modules can be connected to the CP... SC DP via the CP extension connection. 1 1 CP extension connection Fig. 1/7: CP extension connection on the CPA SC DP Proceed as follows 1. Connect the modules to the extension connection. 2. Start the automatic recognition process with DIL switch element 1 (see section 1.2.3). Please note The rules for CPI systems also apply for extending the CP... SC DP (see section 1.6.1). You can connect the following CPI/CP modules to the CP extension connection: CP input and output modules CPI input and output modules (with extended functions) 1 22

37 1. Installation CPV SC with CPI connection CPV/CPA valve terminals with and without extended functions. Caution The maximum cable length between rhe CP... SC DP and the last CP module must not exceed 10 m. The CP connecting cables must have special electrical properties. Always use, therefore, Festo CP connecting cables. Ready to use CP connecting cables are available from Festo. These are available in various lengths and designs. Recommendation Use blanking plugs for sealing unused connections. 1 23

38 1. Installation Rules for extending the CPI system The CPI system supports a different number of modules per CP string, depending on the type of CP master and on the CPI/CP modules connected. The CP... SC DP is a CPI master. Modules can be placed in two different groups: CPI modules (with extended functions) CP modules (without extended functions). CPI system 1) Rules Master Input modules, output modules, valve terminals with CPI connection Maximum 4 modules on the CP string Max. 32 I and 32 O (per CP string) The sequence of the modules within the CP string is optional A mixture of CPI modules is possible on CPI masters: Only one CP input module is possible at the end of each CP string Only one CP valve terminal 2) or one CP output module 2) is possible per CP string. Unused" locations on the CP string can be filled" with CPI modules 1) There is an incoming and continuing interface on all CPI modules 1) with extended functions 2) without extended functions Tab. 1/8: Rules for extending the CPI system 1 24

39 1. Installation Please note Irrespective of the type of CPI/CP modules, not more than 32 inputs and 32 outputs may be connected (sum of all modules on a CP string). CPI master X X X X X X X I X X I X VI/O X: any CPI module (with extended functions) I: CP input module VI/O: CP valve terminal or CP output module Fig. 1/8: Extension examples of a CPI system with CPI master and CPI/CP modules (grey: CPI modules with extended functions) 1 25

40 1. Installation 1 26

41 Commissioning Chapter 2 2 1

42 2. Commissioning Contents 2. Commissioning Preparing the valve terminal for commissioning Switching on the operating voltages Address assignment CPA SC DP Address assignment CPV SC DP Address assignment of CPI/CP modules Commissioning on the PROFIBUS DP Device master file (GSD) and icon files Configuration with a Siemens master STEP 7 HW Config (up to V 5.2) preparations Station selection with STEP Configuration with STEP Tool change configuration Examples of configuration Standard configuration Tool change configuration

43 2. Commissioning 2.1 Preparing the valve terminal for commissioning Switching on the operating voltages Please note Please observe the switching on instructions in the manual for your controller. Before switching on, make sure that the field bus has been configured completely and correctly as specified. Recommendation: Providing the safety concept of your machine/system permits this, commission the CP... SC DP at first with both supply volt ages (pins 1 and 2), but without compressed air. A suitable test function is therefore available which does not trigger undesired reactions. Please observe the following when switching on the power supply: Common supply Separate supply Common power supply for the control system and all field bus slaves via a central power unit or a central switch. If the control system and the field bus slaves have separate power supplies, the devices must be switched on in the following sequence: 1. the operating voltage supply for all field bus slaves 2. the operating voltage supply for the controller. 2 3

44 2. Commissioning Address assignment CPA SC DP The CPA SC DP valve terminal always occupies 32 output addresses, irrespective of the number of valve solenoid coils fitted. This enables the valve terminal to be extended at a later date without the need to shift the addresses. Please note As the CPA SC DP always occupies 32 addresses, the next free address in the CP extension is 32. Depending on the configuration (number of valve loca tions and internal cabling), a valve location supports the control of one or two solenoid coils. Accordingly, the valve locations occupy one or two addresses, irrespective of whether the valve location is fitted with a valve plate or a blanking plate. The internal circuitry cannot be modified at a later stage. The following diagram shows how many solenoid coils can be controlled on the individual valve locations. Pos = number of the valve location Coils = total number of valve solenoid coils light grey = 1 valve coil dark grey = 2 valve coils Fig. 2/1: Address assignment on the CPA SC DP 2 4

45 2. Commissioning If a valve location for 2 addresses is actually equipped with two solenoid coils, the following allocation applies: pilot solenoid coil 14 occupies the less significant address pilot solenoid coil 12 occupies the more significant address. If a valve location for two addresses is fitted with only one solenoid coil, the more significant address will remain unused. However, the valve location still occupies two addresses. Address assignment of the valve coils on the CPA SC DP is from left to right and on the individual valve locations from the front to the rear. Example in the following diagram. The first 8 valve locations support control of two solenoid coils each. ab ad ab Manual overrides and LEDs for the solenoid coils 12 ad Manual overrides and LEDs for the solenoid coils 14 Fig. 2/2: Addressing example on the CPA SC DP (with 24 valve locations) 2 5

46 2. Commissioning Address assignment CPV SC DP The valve terminal type CPV SC DP always occupies 16 out put addresses, irrespective of the number of valve solenoid coils fitted. This enables the valve terminal to be extended at a later date without the need to shift the addresses. Please note As the CPV SC DP always occupies 16 addresses, the next free address in the CP extension is Single solenoid valves occupy one valve location 2 Double solenoid valves occupy two valve locations Fig. 2/3: Address assignment on the CPV SC DP If a valve location for 2 addresses is actually equipped with two solenoid coils, the following allocation applies: pilot solenoid coil 14 occupies the less significant address pilot solenoid coil 12 occupies the more significant address. 2 6

47 2. Commissioning Address assignment of CPI/CP modules Tab. 2/1 provides an overview of the assigned addresses for the various CPI/CP modules (as at autumn 2006). CPI/CP modules Assigned I/Os on... Design Type CPI capable 1) CPI masters 1) CP masters 2) I O I O CPI/CP input modules CP E08 M8 CL CP E08 M12 CL CP E16 KL CL CP E16 M8 CP E16N M8 CP E16 M8 Z CP E16 M12x2 5POL CP E16N M12x2 CP E16 KL IP20 Z Yes Yes Yes No No No No No No 8 I 8 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I 16 I CPI/CP output modules CP A04 M12 CL CP A08 M12 5POL CP A08N M12 Yes No No 8 O 16 O 16 O 16 O 16 O 16 O CP valve terminals CPV... CPI CPV... GE FB 4 CPV... GE FB 6 CPV... GE FB 8 CPA10/14 IFB CP Yes No No No No 16 O 16 O 16 O 16 O 16 O 16 O 16 O 16 O 16 O 16 O 1) with extended functions 2) without extended functions Further CPI modules and CPI capable valve terminals in preparation. Tab. 2/1: Assigned I/Os of the CPI/CP modules 2 7

48 2. Commissioning 2.2 Commissioning on the PROFIBUS DP FREEZE and SYNC The operating modes FREEZE and SYNC are supported in accordance with EN The method of accessing the commands FREEZE and SYNC depends on the controller used. Please refer here to the documentation for your field bus module. Caution The operating mode FREEZE or SYNC will be reset auto matically: after Power OFF/ON when the field bus module stops. Only the operating mode FREEZE will be reset automati cally: when the bus connection to the PROFIBUS is interrupted (response monitoring active). FREEZE command All the inputs of the DP slave will be frozen". The CP... SC DP now sends a constant image of all the inputs to the master. With each further FREEZE command, the input image is up dated and sent again to the master. Return to normal operation: UNFREEZE command SYNC command All the outputs of the DP slave will be frozen". The CP... SC DP now no longer reacts to modifications to the output image in the master. With each further SYNC command, the output image will be updated and transferred. Return to normal operation: UNSYNC command 2 8

49 2. Commissioning Module consistency The CP... SC DP supports the following variants in module consistency: over the selected format (word). Please note Make sure that extensions connected at the CP connection are recognized by the DIL switch setting (see section 1.2.3). 2 9

50 2. Commissioning The following table provides an overview of the possible DP identifiers for the CP system: CP... SC and extension DP identifier Comment Siemens EN CPA SC DP (without extension) ID: 32DO ID: 23 h /35 d 32 digital outputs/valve coils of the CPA SC CPV SC DP (without extension) ID: 16DO ID: 21 h /33 d 16 digital outputs/valve coils of the CPV SC Extension 8 digital inputs ID: 8DI ID: 10 h /16 d e.g. CPI/CP input modules Extension 16 digital inputs ID: 16DI ID: 11 h /17 d Extension 24 digital inputs ID: 24DI ID: 12 h /18 d Extension 32 digital inputs ID: 32DI ID: 13 h /19 d Extension 8 digital outputs ID: 8DO ID: 20 h /32 d e.g. CPI/CP output modules, CP valve Extension 16 digital outputs ID: 16DO ID: 21 h /33 d terminals Extension 24 digital outputs ID: 24DO ID: 22 h /34 d Extension 32 digital outputs ID: 32DO ID: 23 h /35 d Extension tool change mode" configuration (32 digital inputs and outputs) ID: 32DX ID: 33 h /51 d see section Tab. 2/2: Overview of DP identifiers for various extensions to the CPV Direct Please note Enter the identifiers corresponding to the physical sequence of the modules on the CP extension string, starting with the CP... SC DP. 2 10

51 2. Commissioning 2.3 Device master file (GSD) and icon files In order to configure the CP... SC DP with a programmer/pc, you will require the appropriate GSD file. In addition to the slave typical entries (Ident. number, Revision, etc.), the de vice master file (GSD) also contains a selection of identifiers. Reference sources Current GSD files can be found on the Festo Internet pages under: GSD files For the CP... SC DP you will require one of the following files: SC_0A44.GSD (German version) or SC_0A44.GSE (international version) Icon files You will find icon files to represent the valve terminal in your configuration software under the above mentioned Internet address. Normal operating status Diagnostic case Special operating status File: SC_0A44_N.dib File: SC_0A44_D.dib File: SC_0A44_S.dib Tab. 2/3: Icon files for configuration software 2 11

52 2. Commissioning 2.4 Configuration with a Siemens master Please note Various configuration programs are available for use in conjunction with a Siemens master. Please observe the relevant procedure for your configuration program. The following sections describe as an example the main con figuration steps with the STEP 7 software. It is assumed that the reader is already familiar with the information in the man ual for the STEP 7 software. Information on operation with general DP masters can be found in appendix B STEP 7 HW Config (up to V 5.2) preparations GSD 1. Copy the GSD of the valve terminal into the directory...\step7\s7data\gsd on your PC/programmer. File: SC_0A44.GS* (Reference sources for the GSD see section 2.3) The GSDs can either be: copied manually into the above mentioned directory (e. g. with Windows Explorer) or loaded via the menu [Options] [Install new GSD]. Please note Update the hardware catalogue if you copy the GSD during work with STEP 7. Menu in HW Config : [Options] [Update Catalog] 2 12

53 2. Commissioning Please note As from STEP 7 V4.02, GSDs are stored within the STEP 7 project (station GSD). This can cause the updating/reading of new GSD files to appear as if incorrect. Please inform yourself about handling the station GSD files in the STEP 7 help. 2. Process the dialogue window Properties PROFIBUS interface" Baud rate Profile Icons 3. Copy the icon files (see section 2.3) for the CP... SC into directory...\step7\s7data\nsbmp on your PC or programmer. The icon files can either be: copied manually into the above named directory or loaded via the menu [Options] [Install new GSD] file type Bitmap files" in HW Config. 4. Insert a DP master system: Right hand mouse click on DP" under CPU" in the rack. Click on [Insert master system] in the context menu. The line of the DP master system will be displayed. 2 13

54 2. Commissioning Station selection with STEP Fig. 2/4: Station selection with STEP 7 HW Config (The windows displayed are not all visible at the same time, see text) 1. If the hardware catalogue is not open: click on the catalogue icon (see Fig. 2/4 1 ). The hardware catalogue will be displayed. 2. Open the following folder in the hardware catalogue: \PROFIBUS DP\Additional Field Devices\Valves". The folder Valves" is displayed when you copy the GSD (see step 1 of the preparations). 2 14

55 2. Commissioning Pull the station type Festo CP SC" onto the line of the DP master system 2. The dialogue window Properties PROFIBUS interface" will be displayed Select the PROFIBUS address identical to the setting on the rotary switches (see section 1.2.1) and close with OK Configuration with STEP Fig. 2/5: Configuration with STEP 7 V HW Config (example for adding one CP input module with 16 inputs, explanations see text) 2 15

56 2. Commissioning 1. Click on the icon of the valve terminal to be configured in the HW Config 1. The configuration table will be dis played under the rack Open the module Festo CP SC" (folder\profibus DP\ Additional Field Devices\Valves\...) in the hardware cata logue 3. Basic configuration The valve terminals type CPV SC DP always occupy 16 out put addresses; valve terminals type CPA SC DP always occupy 32 output addresses (see section 2.1.3). Therefore carry out first of all a configuration of the basic device as follows. 3. Depending on your valve terminal pull the appropriate entry out of the hardware catalogue onto the 1st. line of the configuration table 4 : CPV SC (O 16)" CPA SC (O 32)" Configuring the extension If you have connected modules to the CP extension connec tion of the CP... SC DP, assign the configuration table further as follows: 4. Pull the entries out of the hardware catalogue onto the next free line of the configuration table, according to the physi cal sequence of the modules on the CP extension string. tool change mode" configuration Alternatively you can use the tool change mode" configur ation (see section 2.4.4). Modifying the address The addresses are assigned automatically. Double click on the appropriate line in the configuration table and modify the starting address of the inputs or outputs in the window Properties DP slave" 5. Please note With S7 400 controllers, up to 4 bytes of addresses are reserved for each DP identifier, depending on the version status. 2 16

57 2. Commissioning Tool change configuration With the tool change mode" configuration you can commission modules without new configuration on the CP extension con nection. The tool change mode" configuration is useful if various extensions are connected in turn to the CP... SC DP during operation. 1 2 Fig. 2/6: Tool change configuration 2 17

58 2. Commissioning Procedure: 1. Carry out the basic configuration Pull the entry tool change mode I/O 32/32" out of the hardware catalogue onto the 2nd. line of the configur ation table 2. Addressing and function With the tool change mode" configuration the maximum possible 32 inputs and 32 outputs will be assigned, irre spective of whether these are used or not. The addresses are assigned without gaps, module after module in ascend ing sequence. Please take this into account when program ming the controller. Caution Communication via the PROFIBUS DP will start in any case, even if the addresses are used incorrectly. Incorrect addressing can cause functional damage with the tool change mode" configuration. With the tool change mode" configuration make sure that the input and output signals are used correctly in your control sequence (see example in Tab. 2/7). Configuration Advantages Disadvantages Standard configuration tool change mode" configuration Good diagnostic possibilities Protection against confusion of the modules on the CP string. Modifications to the CP extension string are possible without new configuration. Can be configured Modifications to the CP extension string must be configured again. Limited diagnostic possibilities (see section 3.3.6) Address assignment of the change configurations must be carried out very carefully. Tab. 2/4: Advantages and disadvantages of the tool change mode" configuration 2 18

59 2. Commissioning 2.5 Examples of configuration Standard configuration The following table shows three examples of configuration and addressing extensions on the CPI extension connection of a CPV SC DP. No. Standard configuration DP identifiers Addressing 1 16DO 1) O O21.7 CPV SC DP + CP E08 M12 CL 8DI I I DO 1) O O21.7 8DO O O22.7 CPV SC DP + CP A04 M12 CL + CP E08 M12 CL 8DI I I DO 1) O O21.7 8DI I I20.7 CPV SC DP + 4x CP E08 M12 CL CL 8DI I I21.7 8DI I I22.7 8DI I I23.7 1) CPV SC DP basic device Tab. 2/5: Examples of standard configuration and addressing a CPV SC DP with different CPI extensions 2 19

60 2. Commissioning Tool change configuration The following table shows the same CPI extensions as Tab. 2/5, but this time with the tool change mode" configuration. Inthis way you can connect the extensions 1, 2 or 3 without a new configuration. Tool change mode" configuration DP identifiers Assigned addresses 16DO 1) O O I I DX I I23.7 O O25.7 O O O O22.3 I I I I20.7 Addresses used I I21.7 I I22.7 I I CPV SC DP + CP E08 M12 CL 2 CPV SC DP + CP A04 M12 CL + CP E08 M12 CL 3 CPV SC DP + 4x CP E08 M12 CL 1) CPV SC DP basic device Tab. 2/6: Different extensions with tool change mode" configuration (compare with example in Tab. 2/5) 2 20

61 2. Commissioning Please note The following example makes clear that with the tool change configuration you must be very careful, especially in using the input and output addresses. Explanation of the example In configuration 1 in Tab. 2/7 a lamp is connected to the 2nd. output module as a signal generator. In configuration 2 an actuator is connected to the 2nd. output module. In both cases address O23.7 is used. Take into account in the controller that the lamp now lies at address O25.7 and an actuator at O23.7. Tool change mode" configuration DP identifiers Assigned addresses O O22.3 O O DO 1) O O DX I I23.7 O23.7 O O25.7 O O21.7 O O22.7 O O23.7 O O24.7 O O Addresses used 1 CPV SC DP + 2x CP A08 M12 CL 2 CPV SC DP + 4x CP A08 M12 CL 1) CPV SC DP basic device O23.77 O25.77 Tab. 2/7: Example of a tool change mode" configuration which requires special attention with the addressing (see text above) 2 21

62 2. Commissioning 2 22

63 Diagnosis Chapter 3 3 1

64 3. Diagnosis Contents 3. Diagnosis Diagnosis via LEDs Normal operating status Fault displays LEDs for status display of the valve solenoid coils Reaction to faults in the control system Diagnosis via PROFIBUS DP Diagnosis steps Overview of the diagnostic bytes Details on standard diagnostic information Details of the identification related diagnosis Channel related diagnosis Diagnosis with tool change configuration Siemens SIMATIC S5/S Online diagnosis with STEP Read out diagnostic buffer with STEP 7 (up to V 5.2) Channel related diagnosis with STEP 7 (up to V 5.3)

65 3. Diagnosis 3.1 Diagnosis via LEDs The LEDs indicate the operating status of the valve terminals: CPV SC DP CPA SC DP LEDs of the valve solenoid coils (12 or 14) 2 PS Power System": Operating voltage supply for the electronics (and sensors in a CP input module) PL Power Load": Load voltage supply for the valves (and valves/outputs in the CP extension string) SF CP system faults BF Bus fault/status 3 LEDs of valve solenoid coils 12 4 LEDs of valve solenoid coils 14 Fig. 3/1: LEDs of the CP... SC DP 3 3

66 3. Diagnosis Normal operating status In the normal operating status two LEDs light up green. The LEDs SF and BF are out. lights up; flashes; out LED Sequence Reaction Operating status Fault treatment PS ON OFF lights up green Power supply for the electronics OK none PL ON OFF lights up green Power supply for the valves OK none SF ON OFF off No system fault none BF ON OFF off No bus fault none Tab. 3/1: LEDs: normal operating status 3 4

67 3. Diagnosis Fault displays Fault diagnosis with the LED PS The PS LED (Power status) indicates faults in the operating voltage supply. LED Sequence Reaction Operating status Fault treatment PS ON OFF off Power supply for the electronics (and sensors) not applied. Check power supply (pin 1). PS ON OFF flashes green Power supply for the electronics (and sensors) outside the tolerance (see appendix with technical data) Check power supply (pin 1). Tab. 3/2: LED PS Fault diagnosis with the LED PL The PL LED (Power load) indicates faults in the load voltage supply. LED Sequence Reaction Operating status Fault treatment PL ON OFF off Power supply for the valves (and CP outputs) not applied. Check power supply (pin 2). PL ON OFF flashes green Power supply for the valves (and CP outputs) outside the tolerance (see appendix with technical data) Check power supply (pin 2). Tab. 3/3: LED PL 3 5

68 3. Diagnosis Fault diagnosis with the LED SF The SF LED indicates CP system faults and special CP system states. LED Sequence Reaction Operating status Fault treatment SF ON OFF off Normal operating status None SF ON OFF flashes red fast CP string faults: Deviation nominal status < > actual status of the CP configuration CP configuration not permitted Check the CP configur ation and, if necessary, carry out new recognition (see section 1.2.3) Alternative: use the tool change configuration SF ON OFF flashes red slowly Periphery fault in the CP string: The module has a diag nostic fault (short circuit, overload,...) Check the modules in the CP string for diagnosis (see section 3.3) SF ON OFF lights up red Module failure in the CP string: Cable interrupted Module defective Check CPI/CP cables Servicing required Tab. 3/4: LED SF 3 6

69 3. Diagnosis Fault diagnosis with the LED BF The BF LED indicates the bus fault or bus status. LED Sequence Reaction Operating status Fault treatment BF ON OFF off No fault (if the green PS LED lights up) None BF ON OFF flashes red fast Field bus connection not OK. Possible causes: station number not correct (e.g. address assigned twice) defective field bus module Interrupted, short cir cuited or faulty field bus connection faulty configuration Check the... address setting of the rotary switches in the field bus node field bus module/master field bus connection configuration of the master Tab. 3/5: LED BF 3 7

70 3. Diagnosis LEDs for status display of the valve solenoid coils There is a yellow LED for every valve solenoid coil. This LED shows the switching status of the valve solenoid coil. LED Colour Solenoid coil Meaning off yellow lights up Basic position Switch position Switch position Basic position There is no signal (logical 0") There is a signal (logical 1") but: the load voltage of the valves lies below the permitted tolerance range < 20.4 V DC) There is a signal (logical 1") There is a signal (logical 1") but: compressed air supply not OK or pilot exhaust blocked or servicing required Tab. 3/6: LEDs for solenoid coils 3 8

71 3. Diagnosis 3.2 Reaction to faults in the control system The reaction of the outputs to control or communication faults can be set by means of the parameters Fault mode" and Fault state" Idle value" and Idle action" The standard setting is Reset output". Further information on parametrizing can be found in section B.1. Please note Please note the following if the outputs are reset after PLC stop, field bus interruption or fault: Single solenoid valves move to the basic position. Double solenoid valves remain in the current position. Mid position valves move to the mid position (depend ing on valve type: pressurized, exhausted or blocked). 3 9

72 3. Diagnosis 3.3 Diagnosis via PROFIBUS DP The CP... SC DP supports the following diagnostic possibility via PROFIBUS as per EN 50170: identification related diagnosis (see section 3.3.4) identification number. channel related diagnosis (section 3.3.5) module number and type type of diagnosis (fault number). Please note If you are operating the CP... SC DP with the tool change configuration, only one diagnostic information will be output for the CP extension (see section 3.3.6). Please note The diagnostic information is only sent to the master system if the device related diagnosis is activated in the switch module. In order to do this, set switch element 2 of the DIL switch to OFF". 3 10

73 3. Diagnosis Diagnosis steps The diagram below shows you the steps required for diagnosing the CP... SC DP Bit Station status 1 1. Step (evaluation of bits 0 and 2): CP... SC DP without voltage, bus plug is not inserted,... (Diag.Station_Non_Existent) The planned configuration of the CP... SC DP is not the same as the actual configuration (Diag.Cfg_Fault) 2. Step: Additional device specific diagnosis (Diag.Ext_Diag see section 3.3.4) Fig. 3/2: Diagnosis steps In order to commission your system, it may be useful in some cases to switch off the device related diagnosis. If your con troller does not start, try with the DIL switch setting Device related diagnosis inactive" (see section 1.2.2). 3 11

74 3. Diagnosis Overview of the diagnostic bytes In the following the diagnostic bytes are represented in four tables. Standard diagnostic information Byte Contents Explanation 1 Station status 1 see Tab. 3/9 2 Station status 2 see Tab. 3/10 3 Station status 3 see Tab. 3/11 4 Diag.Master_add Master address: The address of the master, which parametrized the CP... SC DP, is entered in this byte. 5 Ident_number high byte Manufacturer identifier high byte (05 h ) 6 Ident_number low byte Manufacturer identifier low byte (9E h ) 7... External diagnostic data Data block of the identification and channel related diagnosis Tab. 3/7: Overview of diagnostic bytes: standard diagnostic information Identification related diagnosis (variable length) Byte Contents Explanation 1 Header Fixed for CP... SC DP 2 Identification related diagnosis Specifies the identification with diagnosis. Tab. 3/8: Overview of diagnostic bytes: identification related diagnosis (details in section 3.3.4) 3 12

75 3. Diagnosis The following applies to entries in the diagnostic bytes of the identification related diagnosis: entries according to identification must be in ascending order without gaps. The entries must always be in the same sequence as the configured identifications, irre spective of the time sequence of the diagnostic messages (if necessary, the entries with large module numbers will be shifted). 3 13

76 3. Diagnosis Details on standard diagnostic information The following diagnostic information can be requested by the DP master via the function Slave_Diag from the CP... SC DP. The procedure for reading out this diagnostic information with a SIMATIC S5/S7 system is described in section Station status_1 Bit Meaning Explanation 0 Diag.Station_Non_Existent CP... SC DP no longer/not yet addressable. Possible causes: Operating voltage not applied Data cable interrupted Fault in data cable 1 Diag.Station_Not_Ready CP... SC DP not yet ready for data exchange 2 Diag.Cfg_Fault The configuration data received from the master are not the same as those ascertained by the CP... SC DP. 3 Diag.Ext_Diag There is a diagnosis. Possible causes: Cable fracture on input/output module Short circuit/overload at electrical outputs,... 4 Diag.Not_Supported 1 = CP... SC DP does not support the function requested 5 Diag.Invalid_Slave_Response Always 0 (set by the CP... SC DP) 6 Diag.Prm_Fault Last parametrizing telegram faulty 7 Diag.Master_Lock Always 0 (set by the CP... SC DP) bold = CP... SC DP related bits Tab. 3/9: Diagnostic bits Station status_1 3 14

77 3. Diagnosis Station status_2 Bit Meaning Explanation 0 Diag.Prm_Req 1 = Master must configure the CP... SC DP again 1 Diag.Stat_Diag 1 = The master must request diagnostic data until this bit is set to 0 2 Always 1 (set by the CP... SC DP) 3 Diag.WD_On 1 = response monitoring/watchdog activated 4 Diag.Freeze_Mode 1 = Freeze activated 5 Diag.Sync_Mode 1 = Sync activated 6 Reserved 7 Diag.Deactivated Always 0 (set by the CP... SC DP) bold = CP... SC DP related bits Tab. 3/10: Diagnostic bits station status_2 Station status_3 Bit Meaning Explanation Reserved 7 Diag.Ext_Diag_Overflow 1 = The CP... SC DP has more diagnostic messages than can be buffered or the master receives more diagnostic messages than it can buffer. Tab. 3/11: Diagnostic bits station status_3 3 15

78 3. Diagnosis Details of the identification related diagnosis One bit is reserved for every module (identifier byte) assigned during configuration. A set bit means that there is a diagnos tic message in this I/O range Bit Header byte of the identification related diagnosis Length of the diagnostic block in bytes including the header byte (fixed at 2 h ) fixed at 0, 1 Fig. 3/3: Header byte of the identification related diagnosis Bit Identification related diagnosis 1. Identification byte has diagnosis (Basis CP... SC DP) Identification byte 1 has diagnosis Identification byte 2 has diagnosis Identification byte 3 has diagnosis Identification byte 4 has diagnosis Reserved Fig. 3/4: Identification related diagnosis 3 16

79 3. Diagnosis Channel related diagnosis On the CP... SC DP detailed diagnostic information is given not channel by channel but module by module via the channel related diagnosis. 3 bytes of diagnostic data are available: Bit Module number 1 0 Module number (0: Basis CP... SC DP, : Modules in the CP extension string) Bit 7, 6 fixed at 10 Fig. 3/5: Channel related diagnostic byte 1: Module number Bit Module type Bit fixed at 0 Input/output 00 = reserved 10 = output 01 = input 11 = input/output Fig. 3/6: Channel related diagnostic byte 2: Module type Bit Type of diagnosis Fault type (see Tab. 3/12) Data format of the channel: 000 = reserved 100 = byte 001 = bit 101 = word 010 = 2 bits 110 = 2 words 011 = 4 bits 111 = reserved Fig. 3/7: Channel related diagnostic byte 3: Type of diagnosis 3 17

80 3. Diagnosis Value Fault type (standard) Value Fault type (CP... SC DP) 0 Reserved 16 Incorrect valve setting 1 Short circuit 17 Valve: Switching counter, limit value exceeded 2 Undervoltage 18 Periphery fault tool change configuration 3 Overvoltage 19 Reserved 4 Overload 20 Parameterizing fault (signal range) 5 Overtemperature 21 Parametrizing fault (data format) 6 Cable fracture 22 Parametrizing fault (linear scaling) 7 Upper limit value exceeded 23 Parametrizing fault (digital filter) 8 Lower limit value exceeded 24 Parametrzing fault (lower limit value) 9 Reserved 25 Parametrzing fault (upper limit value) 10 Reserved 26 Faulty actuator supply 11 Reserved 27 CPI/CP module failed/faulty 12 Reserved 28 CPI/CP configuration faulty 13 Reserved 29 Short circuit in the CP string (CP line) 14 Reserved 30 Periphery fault in CPI/CP module (slave does not have bus connection) 15 Reserved 31 Channel failed Tab. 3/12: Fault types (byte 3 of the channel related diagnosis) 3 18

81 3. Diagnosis Diagnosis with tool change configuration In the tool change configuration only a simple diagnostic message is output for the CP string via the channel related diagnosis. (Information on the tool change configuration see section ) Please note In the tool change configuration the diagnostic information for all modules in the CP string is entered in the 2nd. diag nostic byte. No information is given as to which module registers the fault. Note the module LEDs in the CP string for ascertaining the exact location of the fault. Value Fault type (standard) Value Fault type (Festo) Periphery fault in the tool change configuration Tab. 3/13: Diagnosis with tool change configuration The diagnostic information of the CP... SC DP basic device is normally entered in the 1st. diagnostic byte in the tool change configuration. 3 19

82 3. Diagnosis Siemens SIMATIC S5/S7 With these controllers you have the possibility of specifying the reaction of the CP... SC DP to the faults named (details see controller manual). Almost all configuration programs contain the function Response monitoring". For the operating modes named, the specified time corresponds to the drop out time of the valves and electrical outputs. Further details on response monitoring can be found in the relevant controller manuals. 3 20

83 3. Diagnosis You can set two types of fault reactions of the control system: hard fault reaction: the controller switches to the operat ing mode STOP" when a fault occurs. soft fault reaction: the controller remains in the operating mode RUN" when a fault occurs. Control system Module Meaning STOP RUN SIMATIC S5 with IM 308C OB23 Reaction to QVZ with direct access to peripherals default OB is programmed OB24 Reaction to QVZ with access to peripherals via process image default OB is programmed OB35 Reaction to PEU (periphery not clear) default OB is programmed SIMATIC S7/M7 OB82 Reaction to a device related diagnosis default OB is programmed OB86 Reaction to failure of a DP slave default OB is programmed QVZ: quitting delay OB: organisation module PEU: periphery not clear Tab. 3/14: Fault reactions STOP and RUN with S5/S7 3 21

84 3. Diagnosis Possibilities for downloading the diagnosis for S5/S7 The diagnosis for PROFIBUS DP is supported in the different control systems by means of function modules. These down load the slave diagnosis and write it into a data range of the user program. Control system Function module See... Manufact. SIMATIC S5 with IM 308C FB192 IM 308C" ET 200 Decentral Periphery System" manual Siemens SIMATIC S5 with S5 95U/DP master FB230 S_DIAG" ET 200 Decentral Periphery System" manual Siemens SIMATIC S5 with SF 50/DP master FB230 S_DIAG" Programmable valve terminal with SB/SF 50" manual Festo SIMATIC S7/M7 SFC13 DP NRM_DG" System and Standard Functions" reference manual Siemens SIMATIC S7/M7 FB125 Siemens download in Internet Siemens Tab. 3/15: Possibilities for downloading the diagnosis for S5/S7 Example for a STEP 7 user program STL CALL SFC 13 REQ:=TRUE LADDR:=W#16#03FE RET_VAL:=MW100 RECORD:=P#M110.0 BYTE 20 BUSY:=M10.0 Explanation Read request Pointer at diagnostic address, e.g d = 03FE h (see mask Properties DP slave" in the HW Config) When faults occur, output fault code Pointer at start of data range for diagnosis and maximum length of the diagnostic data Read procedure finished Fig. 3/8: Programming example in STL 3 22

85 3. Diagnosis 3.4 Online diagnosis with STEP 7 Direct diagnostic events in conjunction with the CP... SC DP can be: Decentral periphery station failure communication between slave and master interrupted Module faulty (see identification related diagnosis in Fig. 3/4) Change of operating status from START to RUN (nominal/ actual difference exists) configuration data of the CP... SC DP are not the same as the periphery Read out diagnostic buffer with STEP 7 (up to V 5.2) Prerequisites: HW Config must be accessed. Proceed as follows (Fig. 3/9): 1. Switch from offline to online Click with the right hand mouse button on the CPU in rack Click on [Module information...] in the context menu shown. The window Module information" will then appeart Click on the register Diagnostic buffer" Click on the event and read the details 5. Here you will find more detailed information on proceding further, de pending on the S7 controller used. 3 23

86 3. Diagnosis Fig. 3/9: Online diagnosis via the diagnostic buffer (explanation see text, screenshot only in German) 3 24

87 3. Diagnosis Channel related diagnosis with STEP 7 (up to V 5.3) You can display fault messages of the channel related diag nosis with STEP 7 HW Config V5.1 if you mark the icon of the CP... SC DP instead of the CPU. Proceed as follows (see Fig. 3/10): Prerequisite: HW Config has been accessed 1. Switch from offline to online. 2. Click with the right hand mouse key on the icon of the CP... SC DP 1. Click on Module information" in the context menu which now appears. The dialogue window Module information" now appears. 3. Select the register DP slave diagnosis". 4. Read the diagnostic information

88 3. Diagnosis 1 2 Fig. 3/10: Channel related diagnosis with STEP 7 (explanation see text, screenshot only in German) 3 26

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV...-DI02 PROFIBUS-DP CPV...

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV...-DI02 PROFIBUS-DP CPV... Compact performance Elektronics manual CPV valve terminal with field bus direct connection Types: CPV...-DI02 PROFIBUS-DP CPV...-CS02 ABB CS31 Manual 548732 en 1201a [762106] Contents and general instructions

More information

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV... DI02 PROFIBUS DP CPV...

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV... DI02 PROFIBUS DP CPV... Compact performance Elektronics manual CPV valve terminal with field bus direct connection Types: CPV... DI02 PROFIBUS DP CPV... CS02 ABB CS31 Manual 548 732 en 0704NH [706 006] Contents and general instructions

More information

Compact Performance CPV valve terminal with direct connection Electronics

Compact Performance CPV valve terminal with direct connection Electronics Compact Performance CPV valve terminal with direct connection Electronics Field bus protocols: PROFIBUS-DP, Festo, ABB CS31, SUCOnet K Direct connection type CPV..-DI01 Contents and safety instructions

More information

CPX terminal Electronics manual Manual

CPX terminal Electronics manual Manual CPX terminal Electronics manual CPX field bus node Type CPX-FB13 Field bus protocol PROFIBUS-DP as per EN 50170 Manual 526 428 en 0112NH [653 614] Contents and general instructions Authors... U.Reimann,U.Gräff

More information

Compact performance. Electronics manual. System manual. Installing and commissioning CP systems. Manual en 0010b

Compact performance. Electronics manual. System manual. Installing and commissioning CP systems. Manual en 0010b Compact performance Electronics manual System manual Installing and commissioning CP systems Manual 165 226 en 0010b Contents and general instructions Author... S. Breuer Editors... H.-J. Drung, M.Holder

More information

CDVI-DN Valve Terminal (Type 15) DeviceNet

CDVI-DN Valve Terminal (Type 15) DeviceNet CDVI-DN Valve Terminal (Type 15) DeviceNet Description Electronics Valve terminal with direct fieldbus connection Fieldbus protocol: - DeviceNet CDVI-DN type Description 539 045 en 0805a [720 999] Contents

More information

Compact performance. Electronics manual. CP modules. Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL

Compact performance. Electronics manual. CP modules. Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL Compact performance Electronics manual CP modules Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL Output module type CP A04 M12 CL Manual 539 300 en 0404NH [681 792] Contents and

More information

Compact Performance CP system Installation and commissioning

Compact Performance CP system Installation and commissioning Compact Performance CP system Installation and commissioning Author: Translation: Editors: Layout: Type setting: S. Breuer Douglas Smith H.-J. Drung, M. Holder Festo, Dept. PV-IDM PV-IDM Edition: 9806A

More information

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ]

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ] Compact performance Brief description CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8 English 8080251 2017-11e [8080244] Translation of the original instructions Documentation on the

More information

CPX terminal. Manual Electronics. Digital CPX I/O modules and Connection blocks Types: - CPX-8DE-8DA - CPX-AB- CPX pneumatic interfaces Types:

CPX terminal. Manual Electronics. Digital CPX I/O modules and Connection blocks Types: - CPX-8DE-8DA - CPX-AB- CPX pneumatic interfaces Types: CPX terminal Manual Electronics Digital CPX I/O modules and Connection blocks Types: - CPX- DE - CPX- DA - CPX-8DE-8DA - CPX-M- - CPX-L- - CPX-AB- CPX pneumatic interfaces Types: - VMPA -FB-EPL- - VMPAL

More information

Compact performance. Description. Programming and diagnosis. CP fieldbus node 8. Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03

Compact performance. Description. Programming and diagnosis. CP fieldbus node 8. Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03 Compact performance Description Programming and diagnosis CP fieldbus node 8 Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03 Description 165 08 en 080e [730 609] Contents and general

More information

SPC200 Smart Positioning Controller

SPC200 Smart Positioning Controller SPC200 Smart Positioning Controller Electronics manual Field bus module for PROFIBUS DP type SPC200 COM PDP Manual 188 893 en 0901c [744 896] Contents and general instructions Original.......................................

More information

Smart Positioning Controller SPC200 Fieldbus module PROFIBUS-DP

Smart Positioning Controller SPC200 Fieldbus module PROFIBUS-DP Smart Positioning Controller SPC200 Fieldbus module PROFIBUS-DP Type SPC200-COM-PDP Author: Translation: Editors: Layout: Type setting: S. Breuer Douglas Smith H.-J. Drung, M. Holder Festo AG & Co., Dept.

More information

CPX terminal. Electronics Manual. CPX field bus node. Type CPX FB32. Field bus protocol EtherNet/IP. Manual [ ]

CPX terminal. Electronics Manual. CPX field bus node. Type CPX FB32. Field bus protocol EtherNet/IP. Manual [ ] CPX terminal Electronics Manual CPX field bus node Type CPX FB32 Field bus protocol EtherNet/IP Manual 541 305 en 0605NH [693 135] Contents and general instructions Original.......................................

More information

Valve terminal type 03/04 B

Valve terminal type 03/04 B Valve terminal type 03/04 B Electronics manual Field bus node Type IFB13 03 Field bus protocol PROFIBUS DP 12 MBaud Manual 163 958 en 0503f Contents and general instructions Author.................................

More information

Compact performance. Electronics manual. CPV valve terminal with direct connection. Type CPV.. GE DN2 8. Field bus protocol: DeviceNet

Compact performance. Electronics manual. CPV valve terminal with direct connection. Type CPV.. GE DN2 8. Field bus protocol: DeviceNet Compact performance Electronics manual CPV valve terminal with direct connection Type CPV.. GE DN2 8 Field bus protocol: DeviceNet Manual 526 017 en 0503a [693835] Contents and general instructions Authors........................

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB13

Valve terminal type 03/05 Electronics Manual Field bus connection FB13 Valve terminal type 03/05 Electronics Manual Field bus connection FB13 Field bus protocol: PROFIBUS DP 12 MBaud 163958 GB Only valid in agreement with the printed documentation accompanying the product!

More information

CPX terminal. Manual Electronics. CPX field bus node. Type CPX FB11. Field bus protocol DeviceNet. Manual en 0503b [ ]

CPX terminal. Manual Electronics. CPX field bus node. Type CPX FB11. Field bus protocol DeviceNet. Manual en 0503b [ ] CPX terminal Manual Electronics CPX field bus node Type CPX FB11 Field bus protocol DeviceNet Manual 526 422 en 0503b [689 002] Contents and general instructions Original.......................................

More information

Compact performance. Programming and diagnostics manual. CP field bus node 11 Type CP FB11 E. Field bus protocol: DeviceNet

Compact performance. Programming and diagnostics manual. CP field bus node 11 Type CP FB11 E. Field bus protocol: DeviceNet Compact performance Programming and diagnostics manual CP field bus node 11 Type CP FB11 E Field bus protocol: DeviceNet Manual 165 211 en 0802d [730 616] Contents and general instructions Original.......................................

More information

Compact Performance. Description. Electronics. CP fieldbus node 5. Programming and diagnosis. Type CP FB5 E

Compact Performance. Description. Electronics. CP fieldbus node 5. Programming and diagnosis. Type CP FB5 E Compact Performance Description Electronics CP fieldbus node 5 Programming and diagnosis Type CP FB5 E Fieldbus protocols: Festo fieldbus ABB CS 31 Moeller SUCOnet K Description 165 205 en 0802c [730 598]

More information

Fieldbus Direct Key features

Fieldbus Direct Key features Key features The system Extremely compact and spacesaving design Low-cost solution for the connection of a small number of valves to a fieldbus Extremely safe, protection class up to IP65 depending on

More information

Manual. Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI. Manual en 9910NH

Manual. Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI. Manual en 9910NH Manual Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI Manual 396 535 en 9910NH Contents and general instructions Authors... Uwe Reimann, Timo Engelfried Editors... H.-J. Drung, M.Holder

More information

CPX terminal. Manual Electronics. CPX bus node. Type CPX-M-FB20 and CPX-M-FB21. Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus

CPX terminal. Manual Electronics. CPX bus node. Type CPX-M-FB20 and CPX-M-FB21. Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus CPX terminal Manual Electronics CPX bus node Type CPX-M-FB20 and CPX-M-FB21 Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus Manual 575 108 en 1202a [8002868] Contents and general

More information

Smart Positioning Controller SPC200 Stepping motor indexer module

Smart Positioning Controller SPC200 Stepping motor indexer module Smart Positioning Controller SPC200 Stepping motor indexer module Type SPC200-SMX-1 Author: Editors: Layout: Type setting: P. Mauch H.-J. Drung, M. Holder Festo AG & Co., Dept. KI-TD KI-TD Edition: 9904NH

More information

CPX terminal. US patent no. 6,216,738. Electronics manual. CPX CP interface. Type CPX CP 4 FB. Manual [ ]

CPX terminal. US patent no. 6,216,738. Electronics manual. CPX CP interface. Type CPX CP 4 FB. Manual [ ] US patent no. 6,216,738 CPX terminal Electronics manual CPX CP interface Type CPX CP 4 FB Manual 539 294 en 0405NH [681 785] Contents and general instructions Author...................................

More information

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ]

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ] CPX-Terminal Brief description CPX analogue I/O modules CPX-2AE CPX-4AE CPX-2AA English 8080173 2017-11e [8080175] Translation of the original instructions Documentation on the product For all available

More information

CPX terminal. Electronics Manual. CPX I/O modules, sub bases, pneumatic. electronic modules. Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB...

CPX terminal. Electronics Manual. CPX I/O modules, sub bases, pneumatic. electronic modules. Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB... CPX terminal Electronics Manual CPX I/O modules, sub bases, pneumatic interfaces and MPA electronic modules Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB... VMPA FB EPL... CPX GP... VABA 0S6 X VMPA...

More information

Valve terminal types 03/04-B

Valve terminal types 03/04-B Valve terminal types 03/04-B Electronics manual Valve terminal with field bus connection PROFIBUS-DP 12 MBaud Type IFB13-03 Manual 163 958 en 0003c Contents and general instructions Authors... U. Reimann,

More information

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ]

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ] Terminal CPX Electrical interface CPX CTEL 4 M12 5POL Description CTEL master module I-Port 574601 1411a [8041791] Electrical interface CPX CTEL 4 M12 5POL Translation of the original instructions P.BE-CPX-CTEL-EN

More information

Terminal CPX. Bus node CPX-FB14. Description. CANopen networkprotocol en 1411d [ ]

Terminal CPX. Bus node CPX-FB14. Description. CANopen networkprotocol en 1411d [ ] Terminal CPX Bus node CPX-FB14 Description CANopen networkprotocol 526410 en 1411d [8041138] Contents and general instructions Original... de Edition... en 1411d Designation... P.BE-FB14-EN Order no....

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB17

Valve terminal type 03/05 Electronics Manual Field bus connection FB17 Valve terminal type 03/05 Electronics Manual Field bus connection FB17 Field bus protocol: Jetter JETway-R 164226 GB Only valid in agreement with the printed documentation accompanying the product! Compare

More information

Valve terminal types 03/04-B

Valve terminal types 03/04-B Valve terminal types 03/04-B Electronics manual Valve terminal with field bus connection FB8 Allen-Bradley RIO network Type IFB08-03 Manual 152 768 Contents and general instructions Author... H.-J. Drung

More information

Valve terminal type 03 and type 44/45

Valve terminal type 03 and type 44/45 Valve terminal type 03 and type 44/45 Electronics manual Valve terminal with INTERBUS field bus connection Fibre optical waveguide remote bus Rugged Line" Type IFB21 03 Manual 191 085 en 0807c [739 015]

More information

Compact performance. Manual Electronics. CPV valve terminal with direct connection. Type CPV..-GE-DN-8. Field bus protocol: - DeviceNet

Compact performance. Manual Electronics. CPV valve terminal with direct connection. Type CPV..-GE-DN-8. Field bus protocol: - DeviceNet Compact performance Manual Electronics CPV valve terminal with direct connection Type CPV..-GE-DN-8 Field bus protocol: - DeviceNet Manual 175 563 en 0009a Contents and general instructions Authors...

More information

Fieldbus Direct Key features

Fieldbus Direct Key features Fieldbus Direct Fieldbus Direct Key features The system Extremely compact and spacesaving design Low-cost solution for the connection of a small number of valves to a fieldbus Extremely safe, protection

More information

PROFIBUS for motor controller

PROFIBUS for motor controller Beschneiden: Oben: 61,5 mm Unten: 61,5 mm Links: 43,5 mm Rechts: 43,5 mm PROFIBUS for motor controller CMMP Description PROFIBUS CMMP Description 557 338 de 0708NH [723 751] Edition de 0708NH Description

More information

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ]

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ] System CPX-E IO-Link master module CPX-E-4IOL- Description Protocol IO-Link Function Parameterisation 877 27-7 [879] IO-Link master module CPX-E-4IOL- Original instructions CPX-E-4IOL- -E N IO-Link is

More information

SPC200 Smart Positioning Controller

SPC200 Smart Positioning Controller SPC200 Smart Positioning Controller Electronics Manual Field bus module for DeviceNet type SPC200 COM DN2 Manual 196 608 en 0511a [688 393] Contents and general instructions Original.......................................

More information

CPX Terminal. Manual electronics. CPX control block. Type CPX SF34 Type CPX SF35. PC WORX integrated Network protocol PROFINET IO.

CPX Terminal. Manual electronics. CPX control block. Type CPX SF34 Type CPX SF35. PC WORX integrated Network protocol PROFINET IO. CPX Terminal Manual electronics CPX control block Type CPX SF34 Type CPX SF35 PC WORX integrated Network protocol PROFINET IO Manual 570 541 en 1007NH [748 167] Contents and general instructions Original.......................................

More information

CPX terminal. Bus node CPX-FB38. Electronics description. Network protocol EtherCAT. Description en 1301a [ ]

CPX terminal. Bus node CPX-FB38. Electronics description. Network protocol EtherCAT. Description en 1301a [ ] CPX terminal Bus node CPX-FB38 Electronics description Network protocol EtherCAT Description 562525 en 1301a [8024385] Contents and general safety instructions Original... de Edition... en 1301a Designation...

More information

Compact Performance. Electronics manual. CPV valve terminal with direct connection Type CPV.. GE CC 8. Field bus protocol: CC link.

Compact Performance. Electronics manual. CPV valve terminal with direct connection Type CPV.. GE CC 8. Field bus protocol: CC link. Compact Performance Electronics manual CPV valve terminal with direct connection Type CPV.. GE CC 8 Field bus protocol: CC link Manual 197 964 en 0304NH [674 139] Contents and general instructions Author...................................

More information

Operating Instructions (Compact) SIMATIC. Industrial PC SIMATIC Microbox PC 420. Siemens. Release 11/2006 A5E

Operating Instructions (Compact) SIMATIC. Industrial PC SIMATIC Microbox PC 420. Siemens. Release 11/2006 A5E Operating Instructions (Compact) 1 SIMATIC Industrial PC Release 11/2006 A5E00344128-04 Siemens Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety,

More information

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide BNI PBS-104-000-Z001 BNI PBS-302-000-Z001 BNI PBS-501-000-Z001 BNI PBS-502-000-Z001 Short Guide English 1 2 3 4 Notes to the User 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical

More information

CPX terminal. Electronics manual. CPX field bus node. Type CPX FB6. Field bus protocol: Interbus as per EN Manual en 0402b [ ]

CPX terminal. Electronics manual. CPX field bus node. Type CPX FB6. Field bus protocol: Interbus as per EN Manual en 0402b [ ] CPX terminal Electronics manual CPX field bus node Type CPX FB6 Field bus protocol: Interbus as per EN 50254 Manual 526 434 en 0402b [674 154] Contents and general instructions Author...................................

More information

BNI PBS Z001. IP67 module, Profibus IO-Link Master Short Guide

BNI PBS Z001. IP67 module, Profibus IO-Link Master Short Guide BNI PBS-502-001-Z001 IP67 module, Profibus IO-Link Master Short Guide 1 Notes for the User 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations 2 1.3.2

More information

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001. Quick start guide

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001. Quick start guide BNI PBS-104-000-Z001 BNI PBS-102-000-Z001 BNI PBS-302-000-Z001 Quick start guide Content 1 Notes for the User 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB15

Valve terminal type 03/05 Electronics Manual Field bus connection FB15 Valve terminal type 03/05 Electronics Manual Field bus connection FB15 Field bus protocol: EAE field bus-2 Only valid in agreement with the printed documentation accompanying the product! Compare this

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB14

Valve terminal type 03/05 Electronics Manual Field bus connection FB14 Valve terminal type 03/05 Electronics Manual Field bus connection FB14 Field bus protocols: CANopen SDS Smart Distributed System 163959 GB 9801A Author: Editor: Translation: Layout: Type setting: S. Breuer,

More information

CPX terminal. Description Electronics. System manual. Installing and. terminals. Description en 0902e [742939]

CPX terminal. Description Electronics. System manual. Installing and. terminals. Description en 0902e [742939] CPX terminal Description Electronics System manual Installing and commissioning CPX terminals Description 526 446 en 0902e [742939] Contents and general safety instructions Original.......................................

More information

CP2 Series Electric functioning manual

CP2 Series Electric functioning manual pagina 1/39 CP2 Series Electric functioning manual PROFIBUS-DP Fieldbus Node Conforming to normative IEC 61158/61784 pagina 2/39 SAFETY INSTRUCTIONS To use this product safely, basic knowledge of pneumatic

More information

Fieldbus Direct Extremely compact and space-saving

Fieldbus Direct Extremely compact and space-saving Fieldbus Direct Extremely compact and space-saving The ideal fieldbus solution for confined fitting spaces. Info 201 Fieldbus Direct and valve terminals fromfesto theflexiblespacesaving system Convincingly

More information

Electronics manual. Universal handheld. Commissioning and diagnosing CPX terminals. Manual [ ]

Electronics manual. Universal handheld. Commissioning and diagnosing CPX terminals. Manual [ ] Universal handheld Electronics manual Universal handheld type CPX MMI 1 Commissioning and diagnosing CPX terminals Manual 534 825 en 0305NH [668 828] Contents and general instructions Author Editor.....................................................................

More information

CPX terminal. Description Electronics. CPX fieldbus node. Type CPX-FB6. Fieldbus protocol: Interbus in accordance with EN 50254

CPX terminal. Description Electronics. CPX fieldbus node. Type CPX-FB6. Fieldbus protocol: Interbus in accordance with EN 50254 CPX terminal Description Electronics CPX fieldbus node Type CPX-FB6 Fieldbus protocol: Interbus in accordance with EN 50254 Description 526434 en 1207c [762320] Contents and general safety instructions

More information

System CPX-E. Bus module CPX-E-PB. Description. Protocol PROFIBUS DP. Function Parameterisation [ ]

System CPX-E. Bus module CPX-E-PB. Description. Protocol PROFIBUS DP. Function Parameterisation [ ] System CPX-E Bus module CPX-E-PB Description Protocol PROFIBUS DP Function Parameterisation 8723 27-7 [8725] Bus module CPX-E-PB Original instructions CPX-E-PB-E N PI PROFIBUS PROFINET is a registered

More information

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description Inline Block IO Module for PROFIBUS With 32 Digital Outputs AUTOMATIONWORX Data Sheet 6889_en_04 Description PHOENIX CONTACT - 03/2007 & & ' ) The ILB PB 24 DO32 module is designed for use within a PROFIBUS

More information

Motor controller SFC-DC

Motor controller SFC-DC Motor controller SFC-DC Brief overview SFC-DC-...-IO SFC-DC-...-PB SFC-DC-...-CO SFC-DC-...-DN English 8081484 2018-01f [8081486] Translation of the original instructions Documentation on the product For

More information

PROFIBUS for Motor Controller

PROFIBUS for Motor Controller Trimming: Top: 61.5 mm Bottom: 61.5 mm Left: 43.5 mm Right: 43.5 mm PROFIBUS for Motor Controller CMMS Manual PROFIBUS CMMS Manual 554 346 en 0708NH [720 652] Version... en 0708NH Designation... P.BE-CMMS-FHPP-PB-SW-EN

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB16

Valve terminal type 03/05 Electronics Manual Field bus connection FB16 Valve terminal type 03/05 Electronics Manual Field bus connection FB16 Field bus protocols: FIPIO standard Telemecanique - APRIL 164222 GB Only valid in agreement with the printed documentation accompanying

More information

Terminal CPX. Electrical interface CPX-CTEL-2-M12-5POL-LK. Description Electronics NH [ ]

Terminal CPX. Electrical interface CPX-CTEL-2-M12-5POL-LK. Description Electronics NH [ ] Terminal CPX Electrical interface CPX-CTEL-2-M12-5POL-LK Description Electronics 8034116 1405NH [8034124] Electrical interface CPX-CTEL-2-M12-5POL-LK Translation of the original instructions P.BE-CPX-CTEL-LK-EN

More information

Terminal CPX. Bus node CPX-FB40. Description Electronics. Network protocol Ethernet POWERLINK NH [ ]

Terminal CPX. Bus node CPX-FB40. Description Electronics. Network protocol Ethernet POWERLINK NH [ ] Terminal CPX Bus node CPX-FB40 Description Electronics Network protocol Ethernet POWERLINK 8028651 1408NH [8028657] Bus node CPX-FB40 Translation of the original instructions P.BE-CPX-FB40-EN Ethernet

More information

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date: Documentation Fan cartridge for EtherCAT and Bus Terminals Version: Date: 1.5 2017-08-07 Table of contents Table of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety instructions...

More information

SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation

SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation Introduction Prerequisites This guide takes you through

More information

Valve terminal type 03/05 Electronics Manual Control block SB-202

Valve terminal type 03/05 Electronics Manual Control block SB-202 Valve terminal type 03/05 Electronics Manual Control block SB-202 Only valid in agreement with the printed documentation accompanying the product! Compare this edition code. 9602 Authors: Editors: Translation:

More information

CPX Terminal. Manual Electronics. CPX Bus Node. Type CPX FB33 Type CPX FB34. Network protocol PROFINET IO. Manual [ ]

CPX Terminal. Manual Electronics. CPX Bus Node. Type CPX FB33 Type CPX FB34. Network protocol PROFINET IO. Manual [ ] CPX Terminal Manual Electronics CPX Bus Node Type CPX FB33 Type CPX FB34 Network protocol PROFINET IO Manual 548 760 en 0710NH [706 040] Contents and general instructions Original.......................................

More information

VIFB9-02. Michael Holder, H.-J. Drung. Festo, Dept. PV-IDM. Type setting: Edition (Festo AG & Co., D Esslingen, 1997)

VIFB9-02. Michael Holder, H.-J. Drung. Festo, Dept. PV-IDM. Type setting: Edition (Festo AG & Co., D Esslingen, 1997) Author: Editors: Translation: Layout: Type setting: Heinz Hohner Michael Holder, H.-J. Drung Douglas Smith Festo, Dept. PV-IDM DUCOM Edition 9706 printed on 100% receycling paper (Festo AG & Co., D-73726

More information

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module Installation and Setup 1 2 In This Chapter.... Installing the H0 PSCM The Profibus Network Configuring the Module 2 2 Installing the H0 PSCM Remove the Slot Cover The first step in installing the option

More information

RMx621. Appendix to the operating manual

RMx621. Appendix to the operating manual Appendix to the operating manual RMx621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 to PROFIBUS DP via the RS485 serial interface using the external module (HMS AnyBus Communicator

More information

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3 Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger

More information

RMx621 /FML621. Appendix to the operating manual

RMx621 /FML621. Appendix to the operating manual Appendix to the operating manual RMx621 /FML621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 /FML621 to PROFIBUS DP via the RS485 serial interface using the external module

More information

Terminal CPX. Bus node CPX-(M)-FB33/34/35/41. Description. Network protocol PROFINET IO en 1410d [ ]

Terminal CPX. Bus node CPX-(M)-FB33/34/35/41. Description. Network protocol PROFINET IO en 1410d [ ] Terminal CPX Bus node CPX-(M)-FB33/34/35/41 Description Network protocol PROFINET IO 548760 en 1410d [8041494] Contents and general safety instructions Original... de Version... en 1410d Designation...

More information

S7-300 Programmable Controller

S7-300 Programmable Controller S7-300 Programmable Controller This description belongs to the following documentation packages with the order numbers given: S7 300 Programmable Controller 6ES7 398 8AA02 8BA0 ET 200M Distributed I/O

More information

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016 Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target

More information

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~ Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

Device manual Profibus encoder. RM30xx RN30xx /00 06/2013

Device manual Profibus encoder. RM30xx RN30xx /00 06/2013 Device manual Profibus encoder RM30xx RN30xx 706355/00 06/2013 Contents 1 Preliminary note................................................. 4 1.1 Symbols used...............................................

More information

SIMATIC S7-300 Product information for the S7-300 Automation System Manual, Module Data

SIMATIC S7-300 Product information for the S7-300 Automation System Manual, Module Data SIMATIC S7-300 Product information for the S7-300 Automation System Manual, Data Product Information Introduction The present product information describes additions and corrections to the S7-300 Automation

More information

Installation and Setup

Installation and Setup Installation and Setup 1 In This Chapter Installing the H PBC The Profibus Network Configuring the Controller Installing the H PBC Setting the Node Address Setting the Node Address Profibus DP is usually

More information

Motor unit MTR-DCI. Brief overview MTR-DCI. English d [ ]

Motor unit MTR-DCI. Brief overview MTR-DCI. English d [ ] Motor unit MTR-DCI Brief overview MTR-DCI English 8076565 2017-12d [8076567] Translation of the original instructions Documentation on the product For all available product documentation www.festo.com/pk

More information

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date: Documentation Sixteen channel digital output module with D-Sub Connector Version: Date: 2.0.0 2017-11-20 Table of contents Table of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety

More information

Terminal CPX. Bus node CPX-FB37. Description. Network protocol EtherCAT NH [ ]

Terminal CPX. Bus node CPX-FB37. Description. Network protocol EtherCAT NH [ ] Terminal CPX Bus node CPX-FB37 Description Network protocol EtherCAT 8029675 1406NH [8029664] CPX-FB37 Translation of the original instructions P.BE-CPX-FB37-EN EtherCAT,TwinCAT,CANopen,SPEEDCON,Torx,Windows

More information

7.3 ASM Features. Area of application. Communication modules 7.3 ASM 452

7.3 ASM Features. Area of application. Communication modules 7.3 ASM 452 7.3 ASM 452 7.3 ASM 452 7.3.1 Features Area of application The ASM 452 interface module is a MOBY module for operating MOBY and RF300 components with RS422 over PROFIBUS DP-V1 on Any computers and PCs

More information

ST (6ES7132-6FD00-0BB1)

ST (6ES7132-6FD00-0BB1) SIMATIC ET 200SP Digital output module DQ 4x24..230VAC/2A ST (6ES7132-6FD00-0BB1) Manual Edition 02/2014 Answers for industry. DQ 4x24..230VAC/2A ST Preface Guide to documentation 1 SIMATIC ET 200SP DQ

More information

Device manual AS-i PowerSwitch ZB0028 ZB0040

Device manual AS-i PowerSwitch ZB0028 ZB0040 Device manual AS-i PowerSwitch ZB0028 ZB0040 System AS-i Page 1 of 16 Device manual POWERSWITCH ZB0028 ZB0040 Date: 04/02/02 Contents 1. Views... 3 1.1 Top view... 3 1.2 Front view... 4 1.3 Bottom view...

More information

SIMATIC. FM 356 Application Function Module, Installation and Startup. Preface, Contents. User Information. Product Overview

SIMATIC. FM 356 Application Function Module, Installation and Startup. Preface, Contents. User Information. Product Overview Preface, Contents User Information SIMATIC FM 356 Application Function Module, Installation and Startup Manual Product Overview 1 Designing the Mechanical Configuration 2 Addressing the M7-300 Modules

More information

SUBCON-PLUS-PROFIB...

SUBCON-PLUS-PROFIB... Fast connector for PROFIBUS systems Data sheet 101610_en_10 PHOENIX CONTACT 2017-03-27 1 Description The SUBCON-PLUS-PROFIB... D-SUB series is specifically designed for use in PROFIBUS systems up to 12

More information

CPX-E-CEC-... Controller. Description Function, Parameterisation [ ]

CPX-E-CEC-... Controller. Description Function, Parameterisation [ ] CPX-E-CEC-... Controller Description Function, Parameterisation 8071235 8071235 2018-09 [8071237] Translation of the original instructions CODESYS, EtherCAT, MODBUS are registered trademarks of the respective

More information

2005/2012 Series Profibus DP Technical Manual

2005/2012 Series Profibus DP Technical Manual 2005/2012 Series Profibus DP Technical Manual LT2005/2012PBTECH-1 04/02 www.numatics.com Table of Contents 2005/2012 Series Profibus DP Technical Manual PAGE About Profibus DP... 3 Overview... 3 G2-2 Profibus-DP

More information

Operation Manual Profibus DP -Display HE 5120 P with digital I/O's

Operation Manual Profibus DP -Display HE 5120 P with digital I/O's Operation Manual Profibus DP -Display HE 510 P with digital I/O's "HESCH" Schröder GmbH Boschstraße 8 31535 Neustadt Telefon +49 (0) 503 / 9535-0 Telefax +49 (0) 503 / 9535-99 e-mail: info@hesch.de http://www.hesch.de

More information

Electronics Manual. Manual. Compact Vision System. Type SBO.. M... Manual [ ]

Electronics Manual. Manual. Compact Vision System. Type SBO.. M... Manual [ ] Compact Vision System Electronics Manual Manual Compact Vision System Type SBO.. M... Manual 542 123 en 0511NH [691 639] Contents and general instructions Original.......................................

More information

Assembly and Operating Instructions. M2 module for BDC-i440 control units

Assembly and Operating Instructions. M2 module for BDC-i440 control units BDC-i440 M2 en Assembly and Operating Instructions M2 module for BDC-i440 control units Important information for: Fitters / Electricians / Users Please forward accordingly! These instructions must be

More information

L5353 Profibus-DP Communications Interface

L5353 Profibus-DP Communications Interface L5353 Profibus-DP Communications Interface Technical Manual HA470380 Issue 2 Copyright SSD Drives, Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or

More information

SCHMIDT Sensor interface PROFIBUS Instructions for use

SCHMIDT Sensor interface PROFIBUS Instructions for use SCHMIDT Sensor interface PROFIBUS Instructions for use Table of contents 1 Important information... 3 2 Intended use... 4 3 Electrical connection... 4 4 Signalizations... 7 5 Startup... 9 6 Technical data...

More information

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date: Documentation Sixteen Channel Digital Output Module with D-Sub Connector Version: Date: 2.0 2016-08-03 Table of contents Table of contents 1 Foreword... 4 1.1 Notes on the documentation... 4 1.2 Safety

More information

USER S MANUAL. FX2N-32DP-IF Profibus-DP Interface Unit

USER S MANUAL. FX2N-32DP-IF Profibus-DP Interface Unit USER S MANUAL FX2N-32DP-IF Profibus-DP Interface Unit FX2N-32DP-IF Profibus-DP Interface Unit Foreword This manual contains text, diagrams and explanations which will guide the reader in the correct installation

More information

User Manual BLCDP-2M12MT-2RFID-S

User Manual BLCDP-2M12MT-2RFID-S User Manual : 2010-6-18 All brand and product names are trademarks or registered trade marks of the owner concerned. Hans Turck GmbH, Mülheim an der Ruhr All rights reserved, including those of the translation.

More information

Positioner CMSX-...-C-U-F1-...

Positioner CMSX-...-C-U-F1-... Positioner CMSX-...-C-U-F-.... CMSX-SE-... (linear) Festo AG & Co. KG Postfach Esslingen Germany +9-0 www.festo.com aj 9 8 (en) Operating instructions 8088 09NH [8080] Original: de Positioner CMSX... English

More information

BNI USB A501. USB IO-Link Master User's Guide. english

BNI USB A501. USB IO-Link Master User's Guide. english User's Guide english 1 2 4 Notes to the user 1.1 About this guide 1.2 Structure of the guide 1. Typographical conventions 1.4 Symbols 1.5 Abbreviations Safety 4 2.1 Intended use 4 2.2 General safety notes

More information

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3 Overview Safety notes 1 SITOP power supply Manual Description, device design, dimension drawing 2 Mounting/removal 3 Mounting position, mounting clearances 4 Installation 5 Technical data 6 Safety, approvals,

More information

DVPPF02-SL PROFIBUS DP Slave Communication Module

DVPPF02-SL PROFIBUS DP Slave Communication Module DVPPF02-SL PROFIBUS DP Slave Communication Module Operation Manual DVP-0155320-01 Warning This operation manual provides introduction on the functions, specifications, installation, basic operation, settings

More information

CPX Terminal. Electronics Manual. CoDeSys Controller. Type CPX CEC C1. Manual [ ]

CPX Terminal. Electronics Manual. CoDeSys Controller. Type CPX CEC C1. Manual [ ] CPX Terminal Electronics Manual CoDeSys Controller Type CPX CEC C1 Manual 569 122 en 0907NH [745 684] Contents and general instructions Original....................................... de Edition.................................

More information

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5

More information