Valve terminal type 03/05 Electronics Manual Field bus connection FB17

Size: px
Start display at page:

Download "Valve terminal type 03/05 Electronics Manual Field bus connection FB17"

Transcription

1 Valve terminal type 03/05 Electronics Manual Field bus connection FB17 Field bus protocol: Jetter JETway-R GB Only valid in agreement with the printed documentation accompanying the product! Compare this edition code. 9610NH

2 Authors: Editors Translation: Layout: Type setting: Eberhard Klotz, D. Ruckwied, H. Wilhelm H.J. Drung, M.Holder Douglas Smith Festo KG, Dept. PV-IDM DUCOM 1st. edition October 1996 Printed on 100% recycled paper 1996 Festo KG, D Esslingen Federal Republic of Germany All rights reserved, including translation rights. No part of this publication may be reproduced or transmitted in any form or by any means, electronic, mechanical photocopying or otherwise, without the prior written permission of Festo KG NH I

3 Part no.: Title: Designation: MANUAL P.BE-VIFB17-03/05-GB II 9610 NH

4 Contents GENERAL SAFETY INSTRUCTIONS Designated use Target group IMPORTANT USER INSTRUCTIONS Danger categories Pictograms Instructions on this manual Service VII VII VIII IX IX X XI XII Chapter 1 SYSTEM SUMMARY SYSTEM SUMMARY 1-3 System structure 1-3 Type 03: Description of components 1-5 Type 05: Description of components 1-9 Method of operation 1-11 Chapter 2 FITTING FITTING THE COMPONENTS 2-3 Input/output modules 2-4 End plates 2-6 Hat rail clamping unit (type 03) TYPE 03: FITTING THE VALVE TERMINAL 2-9 Wall fitting (type 03) 2-9 Fitting the hat rail (type 03) TYPE 05: FITTING THE VALVE TERMINAL 2-12 Wall fitting (type 05) NH III

5 Chapter 3 INSTALLATION GENERAL CONNECTING METHODS 3-3 Selecting the field bus cable 3-4 Selecting the operating voltage cable 3-5 Connecting the cables to the plugs/sockets FIELD BUS NODE 3-8 Opening and closing the node 3-8 Configuring the valve terminal 3-10 Setting the field bus address (network address) 3-11 Setting the baud rate 3-14 Setting the protocol Type 03: Connecting the operating voltages Type 05: Connecting the operating voltages Connecting the JETway-R 3-30 General instructions on the controllers CONNECTING THE INPUT MODULES 3-39 Pin assignment CONNECTING THE OUTPUT MODULES 3-42 Pin assignment 3-44 IV 9610 NH

6 Chapter 4 COMMISSIONING BASIC PRINCIPLES OF CONFIGURATION AND ADDRESSING 4-3 General 4-3 Switching on the operating voltages 4-4 Calculating the configuration data 4-5 Calculating the number of inputs and outputs (type 03) 4-6 Calculating the number of inputs and outputs (type 05) 4-7 Address assignment of the valve terminal 4-8 General for type 03 and Basic rule Basic rule Basic rule Address assignment after extension/conversion 4-13 Example of addressing type 03 MIDI/MAXI valves 4-15 Example of addressing type 05 ISO valves JETTER 4-17 Register for the configuration 4-17 Instructions on the registers 4-17 Register 2: Number of input bytes 4-17 Register 3: Number of output bytes 4-18 Register 6: Register offset 4-18 Register 7: Input offset 4-18 Register 8: Output offset 4-18 Register 9: Version number NH V

7 Chapter 5 DIAGNOSIS AND ERROR TREATMENT SUMMARY OF DIAGNOSTIC POSSIBILITIES ON-THE-SPOT DIAGNOSIS 5-4 LED displays 5-4 Field bus node 5-4 Valves 5-6 Input/output modules 5-8 Testing the valves DIAGNOSIS VIA JETway REGISTER 5-11 Register for the diagnosis 5-11 Register 0: Status register 5-11 Registers 10, 11, 14 and 15: status of the inputs and outputs ERROR TREATMENT 5-13 Reaction to faults in the control system 5-13 Short circuit/overload at an output module 5-14 Faults in initialization 5-15 Appendix A TECHNICAL APPENDIX A-1 TECHNICAL SPECIFICATIONS A-3 CABLE LENGTH AND CROSS SECTION A-7 CIRCUITRY EXAMPLES A-12 Appendix B INDEX B-1 VI 9610 NH

8 General safety instructions GENERAL SAFETY INSTRUCTIONS Designated use The valve terminal type 03/05 described in this manual is designated exclusively for use as follows: for controlling pneumatic and electrical actuators (valves and output modules) for interrogating electrical sensor signals by means of the input modules. Use the valve terminal only as follows: as designated in the instructions in technically faultless condition without any modifications. The specified limit values for pressures, temperatures, electrical data, moments, etc. must be observed when additional commerciallyavailable components such as sensors and actuators are connected. Please comply also with national and local safety laws and regulations NH VII

9 General safety instructions Target group This manual is directed exclusively at technicians who are trained in control and automation technology and who have experience in installing, commissioning, programming and diagnosing programmable logic controllers (PLC) and field bus systems. VIII 9610 NH

10 General safety instructions IMPORTANT USER INSTRUCTIONS Danger categories This manual contains instructions on the hazards which may arise from improper or negligent use of the valve terminal. A distinction is made between the following instructions: WARNING This means that injury to human beings as well as material damage can occur if these instructions are not observed. CAUTION This means that material damage can occur if these instructions are not observed. PLEASE NOTE This means that this instruction must also be observed NH IX

11 General safety instructions Pictograms Pictograms and symbols supplement the danger instructions and draw attention to the consequences of dangers. The following pictograms are used: Uncontrolled movements of loose tubing. Uncontrolled movement of the connected actuators. High electric voltage or undefined switching states of the electronic components which affect the connected circuits. Electrostatically vulnerable components which will be destroyed if their contact surfaces are touched. The ISO valve terminal type 05 is very heavy. Please ensure that it is fastened correctly and see that all operating personnel wear safety shoes. X 9610 NH

12 General safety instructions Instructions on this manual This manual contains specific information on the installation, commissioning, programming and disgnosis of the valve terminals types 03/05 and the input/output modules. The following product-specific abbreviations are used in this manual: Abbreviation Terminal or Valve terminal Node Valve-sub base S sub-base D sub-base ISO sub-base I O I/O P module I/O module PLC Meaning Valve terminal type 03 (MIDI/MAXI) or type 05 (ISO) with/without electric I/Os Field bus node Pneumatic sub-base for valves For two single valves type 03 (MIDI/MAXI) For two double solenoid valves or mid-position valves type 03 (MIDI/MAXI) Sub-base for 4, 8 or 12 ISO valves type 05 (as per ISO 5599/I, size 1 or 2) Input Output Input and/or output Pneumatic module in general Module with digital inputs/outputs in general (input/output modules Programmable logic controller; or simply controller Fig. 0/1: Abbreviations 9610 NH XI

13 General safety instructions PLEASE NOTE All information on the pneumatic modules is to be found in the Pneumatics Manual P.BE-MIDI/MAXI-03-GB or P.BE-ISO-05-GB. A valve terminal with four pneumatic valve sub-bases and four input/output modules is used for the diagrams in this manual. Fig. 0/2: Standard fitting for the drawings The valve terminals can be connected to all processing PLCs from Jetter via the JETway-R. Service If you have any technical problems, please consult your local Festo Service XII 9610 NH

14 1. System summary 1. SYSTEM SUMMARY 9610 NH 1-1

15 1. System summary Contents 1.1 SYSTEM SUMMARY 1-3 System structure 1-3 Type 03: Description of components 1-5 Type 05: Description of components 1-9 Method of operation NH

16 1. System summary 1.1 SYSTEM SUMMARY System structure Festo solves your automation tasks at the machine level by means of valve terminals. Valve terminals types 03 and 05 are constructed on a modular basis and permit combinations of pneumatic and electronic modules. The following groupings are possible. Processing PLC - JETTER AAAA AAAAAAA AAAA AAAAAAA AAAA AAAAAAA AAAA AAAAAAA AAAA AAAAAAA AAAA AAAAAAA AAAAAAAAA AAAA AAAA AAAA AAAA A AAAA AAAA AAAA AAAA A AAAA AAAA AAAA AAAA A AAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAA AAAA AAAA AAAA AAAA AAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AAA AAAAAAAAA AA AAA AAAA AAA AAAA AAA AAA AAAAAAAAA AA AAA AAAA AAA AAAA AAA AAA AAAAAAAAA AA AAA AAAA AAA AAAA AAA AAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAA Valve terminal type 03: MIDI/MAXI valves and electronic modules Field bus JETway-R Valve terminal type 03: MAXI valves only Valve terminal type 05: ISO valves and electronic modules Further field bus slaves Fig. 1/1: Summary of system and possible variants of valve terminals 9610 NH 1-3

17 1. System summary The valve terminal with field bus connection offers the following advantages: can be equipped in various ways with digital I/Os and pneumatic valve locations subsequent extension/conversion possible different valve designs can be fitted can be connected to various control systems fewer cabling required due to two-core cables easy-to-understand system structure due to physical separation of controller and machine. valves already fitted wired pilot valve solenoid coils central air supply central exhaust valve terminal is tested before leaving the factory. A field bus system also offers the following advantages: fewer output assemblies in the controller economic data transfer over long distances high baud rate a large number of slaves can be connected error diagnosis is made easier NH

18 1. System summary Type 03: Description of components Valve terminal type 03 consists of individual modules. Each module is assigned with different functions and different elements for connection, display and operation. The diagram below summarizes the modules No. Modules 1 Node 2 Electronic modules (input/output modules), fitted with digital inputs (modules with 4 or 8 inputs) digital outputs (modules with 4 outputs) 3 End plate left with hole for additional earth cable connection 4 Pneumatic MIDI, MAXI modules (valve sub-bases) fitted with S valves: 5/2 single solenoid valves 5/2 double solenoid valves 5/3 mid-position valves (exhausted, pressurized, blocked) blanking plates S = Auxiliary pilot air 5 Pneumatic MIDI or MAXI modules: pressure supply with integrated exhaust (MIDI) intermediate air supply with integrated exhaust (MIDI) pressure supply adapter with/without regulator (MIDI/MAXI) additional air supply module (MAXI) Fig. 1/2: Modules of the valve terminal type NH 1-5

19 1. System summary The following connection and display elements are to be found on the electronic modules: Further modules A4 A4 E4 E No Meaning Output socket for electronic output Yellow LED (status display per output) Red LED (error display per output) Input socket for one electrical input Green LED (per input) Input socket for two electrical inputs Two green LEDs (one LED per input) Node with LEDs and field bus connection, detailed description in Chapter "Installation" Right-hand end plate Fuse for internal inputs/sensors Operating voltage connection Further modules (e.g. additional supply, high current outputs PNP/NPN) Fig. 1/3: Display and connection elements of the electronic modules NH

20 1. System summary The following connection, display and operating elements are to be found on the pneumatic MIDI modules type 03: 1 2a 3a b 2b No. 1 2a 2b 3a 3b Meaning Node with LEDs an field bus connection, further details in the chapter "Installation" Yellow LED upper valve solenoid coil Yellow LED lower valve solenoid coil Manual override upper valve solenoid coil (14, A) Manual override lower valve solenoid coil (12, B) Valve location inscription field Unused valve location with cover plate Common pneumatic tubing connections Work connections (per valve) Fuse for inputs/sensors Power supply connection Fig. 1/4: Operation, display and connection elements of the pneumatic MIDI modules type NH 1-7

21 1. System summary The following connection, display and operating elements are to be found on the pneumatic MAXI modules type 03: No Fig. 1/5: Meaning Node with LEDs an field bus connection, further details in the chapter "Installation" Yellow LED (per valve solenoid coil) Manual override (per valve solenoid coil) Valve location inscription field (labels) Unused valve location with cover plate Common pneumatic tubing connections Work connections (2 per valve, placed one obove the other) Regulator for limitted pressure of auxiliary pilot air Common pneumatic tubing connection Exhausts Operation, display and connection elements of the pneumatic MAXI modules type NH

22 1. System summary Type 05: Description of components Valve terminal type 05 consists of individual modules. Each module is assigned with different functions and different elements for connection, display and operation. The diagram below summarizes the modules No. Modules 1 Node 2 Electronic modules (input/output modules), fitted with digital inputs (modules with 4 or 8 inputs) digital outputs (modules with 4 outputs) 3 End plate left with opening for additional earth connection 4 Adapter plate for ISO sub-base (manifold) as per ISO 5599/I sizes 1 or 2 5 ISO sub-base (manifolds for 4, 8 or 12 locations) fitted with: Pneumatic valves with hole pattern as per ISO 5599/I - single pneumatic valves - double pneumatic valves - pneumatic mid-position valves components for vertical stacking (regulator plates, flow control plates etc.) blanking plates Fig. 1/6: Modules of the valve terminal type NH 1-9

23 1. System summary The following connection, display and operating elements are to be found on the pneumatic ISO modules type 05: No Meaning Node with LEDs and field bus connection, detailed description see chapter "Installation" Fuse for inputs/sensors (pin 1) Adapter plate Operating voltage connection of valve terminal type 05 Fuse for valves (pin 2) Valve location inscription field Yellow LEDs (per pilot solenoid) Manual override (per pilot solenoid, pressing or locking) External air control connection Common connections Work connections (per valve) Adapter cable for operating voltage of node and I/O modules Fig. 1/7: Operating, display and connection elements of ISO modules type 05 The electronic modules are described in the section "Description of components type 03" NH

24 1. System summary Method of operation Incoming field bus Continuing field bus 1 Node 4 2 AA AA AAA AAA A 2, 1 4 = Compressd air = Work air Electrical signal flow Fig. 1/8: Function summary of valve terminal type 03/05 The node controls the following functions: connection of the terminal to the field bus module of the control system and to further field bus slaves via the field bus interface adaption of the field bus baud rate and field bus protocol to the control system control of data transfer to/from the field bus module of the control system. internal control of the terminal NH 1-11

25 1. System summary The input modules process the input signals (e.g. from sensors) and transmit these signals via the field bus to the controller. The output modules are universal electrical outputs and control small current-consuming devices with positive logic, e.g. further valves, lights etc.. The pneumatic modules are used for the following: common channels for supply and exhaust air electrical signals from all solenoid valve coils. Work connections 2 and 4 are supplied for each valve location on the individual pneumatic modules. By means of the common channels on the pneumatic end plate, the valves are supplied with compressed air and both the exhaust air and the pilot air from the valves are vented. Further modules for air supply are also available, in order that different work pressures can be used or in order that either MIDI/MAXI valves or ISO valves can be fitted on a terminal. Further information on their use is to be found in the Pneumatics Manual for the valve terminal. Only the electronic modules and the node are described here NH

26 2. Fitting 2. FITTING 9610 NH 2-1

27 2. Fitting Contents 2. FITTING 2.1 FITTING THE COMPONENTS 2-3 Input/output modules 2-4 End plates 2-6 Hat rail clamping unit (type 03) TYPE 03: FITTING THE VALVE TERMINAL 2-9 Wall fitting (type 03) 2-9 Fitting the hat rail (type 03) TYPE 05: FITTING THE VALVE TERMINAL 2-12 Wall fitting (type 05) NH

28 2. Fitting 2.1 FITTING THE COMPONENTS WARNING Before fitting the components switch off the following: the compressed air supply the power supply for the outputs (pin 2) the power supply for the electronic components (pin 1) You thereby avoid: uncontrolled movement of loose tubing undesired movements of the connected actuators undefined switching states of the electronic components. CAUTION The valve terminal components contain parts which can be damaged by electrostatic charges. Do not therefore touch the contact surfaces of the plug connectors at the side of the modules. Observe the instructions for dealing with components liable to damage by electrostatic charges. You thereby avoid destroying the valve terminal components NH 2-3

29 2. Fitting PLEASE NOTE Treat all the modules and the components of the valve terminal with the utmost care. Pay special attention to the following: Screw connectors must not be twisted or subjected to mechanical stress. The screws must fit accurately (otherwise the threads will be damaged). The specified torques must be observed. The modules must be aligned correctly (IP 65). The contact surfaces must be clean (avoid leakage and faulty contacts). The contacts of the type 03 MIDI valve solenoid coils must not be bent (they are not resistant to alternate bending and will break off if bent backwards). In the case of modules and components ordered at a later stage, observe also the fitting instructions included with the product. Input/output modules Before the valve terminal can be extended or converted, it must first be dismantled. Dismantling (see also following diagram) Remove completely the screws of the relevant modules. The modules are now held together only by the electrical plug connectors. Pull the modules carefully and without tipping away from the electrical plug connectors. Replace broken or damaged seals NH

30 2. Fitting Fitting (see also following diagram) PLEASE NOTE Always place the subsequently ordered modules after the last module before the end plate. Do not fit more than 12 electronic modules. Please note also the addressing limits of your field bus protocol. Fit the modules as follows: Fit a new seal on the right-hand contact surface facing the node. Fit the module as shown below. Seal Fastening screws max. 1 Nm Fig. 2/1: Fitting electronic I/O modules 9610 NH 2-5

31 2. Fitting End plates A left-hand and a right-hand plate are required as mechanical termination of the modular terminal. These end plates fulfil the following functions: They comply with protection class IP 65. They contain connections/contacts for the protective earth cable. They contain holes for fitting onto walls and onto the hat rail clamping unit. By means of screw connectors and the ready fitted spring contacts, the right-hand end plate of the ISO terminal is connected conductively to the manifold sub-bases. It is therefore sufficiently earthed. There are various designs of right-hand end plate for the terminls of type 03 (MIDI/MAXI). Each design is already fitted with a protective earth cable. CAUTION Earth the right-hand end plate with the protective earth cable before fitting the terminal type 03. You thereby avoid high voltages on the metal surfaces in the case of a fault NH

32 2. Fitting Earth the end plates as follows: Right-hand end plate (type 03): To earth the right-hand end plate connect the cable fitted on the inside to the appropriate contacts on the pneumatic modules or on the node (see following diagram). Left-hand end plate (type 03 and type 05): The left-hand end plate is connected conductively to the other components via spring contacts which are already fitted. Please note: Instructions on earthing the complete valve terminal are to be found in the chapter "Installation". The diagram below shows how both end plates are fitted. Seal Contact for earth cable Seal Ready-fitted earth cable Fastening screws max. 1 Nm Fig. 2/2: Fitting the end plates (example with terminal type 03) 9610 NH 2-7

33 2. Fitting Hat rail clamping unit (type 03) If the terminal is to be fitted onto a hat rail (support rail as per EN 50022), you will require the hat rail clamping unit. This unit must be fastened to the rear of the end plates as shown in the following diagram. Before fitting ensure that: the glueing surfaces are clean (clean with spirit) the flat-head screws are tightened (6) After fitting ensure that: the levers are secured with the locking screw (7). 1 Rubber foot, self-adhesive 2 Clamping elements 3 Left-hand lever *) 4 Right-hand lever *) 5 O ring 6 Flat head screw 7 Retaining screw *) Levers differ in length for MIDI or MAXI Fig. 2/3: Fitting the hat rail clamping unit NH

34 2. Fitting 2.2 TYPE 03: FITTING THE VALVE TERMINAL Wall fitting (type 03) WARNING With long terminals use additional support brackets approximately every 200 mm. You thereby avoid: overloading the fastening eyes on the end plates the terminal sagging natural resonances 7.6 mm Proceed as follows: Calculate the weight of your terminal (weigh or estimate). General rule: MIDI MAXI per pneumatic module 800 g 1200 g per node 1000 g 1000 g per electronic module 400 g 400 g Make sure that the fastening surface can carry this weight. Fasten the terminal with four M6 screws as shown below (fitting position as desired). Use spacers if necessary. M6 Fig. 2/4: Fitting the valve terminal typ 03 on the wall 9610 NH 2-9

35 2. Fitting Fitting the hat rail (type 03) The terminal is suitable for fitting onto a hat rail (support rail as per EN 50022). For this purpose there is a guide groove on the rear of all modules for hanging the terminal on the hat rail. CAUTION Hat rail fitting without the hat rail clamping unit is not permitted. If the terminal is fitted in a sloping position or at a point subjected to vibration, protect the hat rail clamping unit against slipping and, by means of the screws (7), against unintentional loosening/opening. PLEASE NOTE If the terminal is fitted in a horizontal position without vibration, the screws (7) are not required for fastening the hat rail clamping unit. If your terminal does not have a hat rail clamping unit, this can be ordered and fitted later. The use of MIDI or MAXI clamping units depends on the end plates fitted (MIDI/MAXI). Proceed as follows: Calculate the weight of your terminal (weigh or estimate). General rule: MIDI MAXI per pneumatic module 800 g 1200 g per node 1000 g 1000 g per electronic module 400 g 400 g NH

36 2. Fitting Make sure that the fastening surface can carry this weight. Fit a hat rail (support rail as per EN x15; width 35 mm, height 15 mm). Fasten the hat rail approximately every 100 mm on the fastening surface. Hang the terminal onto the hat rail. Use the hat rail clamping unit to secure the terminal on both sides against tilting or slipping (see diagram below). If the terminal is fitted in a sloping position or at a point subjected to vibration, protect the hat rail clamping unit with two screws (7) against unintentional loosening/opening. Valve terminal type 03 Hat rail clamping unit unlocked Hat rail clamping unit (locked) Retaining screw (7) Fig. 2/5: Fitting the valve terminal typ 03 onto a hat rail 9610 NH 2-11

37 2. Fitting 2.3 TYPE 05: FITTING THE VALVE TERMINAL Wall fitting (type 05) WARNING With long terminals use additional support brackets approximately every 200 mm. You thereby avoid: overloading the fastening eyes on the end plates the terminal sagging (I/O side) natural resonances Proceed as follows: Calculate the weight of your terminal (weigh or estimate). General rule: Sub-base *) - 4 valve locations incl. valves - 8 valve locations incl. valves - 12 valve locations incl. valves ISO size 1 ISO size 2 8 kg 14 kg 20 kg 12 kg 20 kg 28 kg per node 1 kg per electronic module 0.4 kg *) Components for vertical stacking: Please see pneumatics manual P.BE-ISO-05-GB for weights. Make sure that the fastening surface can carry this weight NH

38 2. Fitting Fasten the terminal as follows: with three M10 screws on the adapter plate and on the right-hand end plate (2) with two M6 screws on the left-hand end plate (1) If required, use the following additional fastening methods: the hole on the bottom of the right-hand end plate with an M10 thread "blind hole" (3) the supporting angles for the I/O modules (see fitting instructions supplied with the angles) The terminal can be fitted in any desired position. If necessary, use spacers as well as the mounting and transport threads M8 (e.g. lifting eye bolts for crane hooks). 1 2 Thread M8 for lifting eye bolts 3 M6 M10 Fig. 2/6: Fitting the ISO valve terminal type 05 on the wall 9610 NH 2-13

39 2. Fitting NH

40 3. Installation 3. INSTALLATION 9610 NH 3-1

41 3. Installation Contents 3. INSTALLATION 3.1 GENERAL CONNECTING METHODS 3-3 Selecting the field bus cable 3-4 Selecting the operating voltage cable 3-5 Connecting the cables to the plugs/sockets FIELD BUS NODE 3-8 Opening and closing the node 3-8 Configuring the valve terminal 3-10 Setting the field bus address (network address) 3-11 Setting the baud rate 3-14 Setting the protocol Type 03: Connecting the operating voltages Type 05: Connecting the operating voltages Connecting the JETway-R 3-30 General instructions on the controllers CONNECTING THE INPUT MODULES 3-39 Pin assignment CONNECTING THE OUTPUT MODULES 3-42 Pin assignment NH

42 3. Installation 3.1 GENERAL CONNECTING METHODS WARNING Before installation or maintenance work is carried out, the following must be switched off: the compressed air supply the power supply to the electronic components (pin 1). the power supply to the outputs/valves (pin 2). You thereby avoid: uncontrolled movement of loose tubing undesired movements of the connected actuators undefined switching states of the electronic components NH 3-3

43 3. Installation Selecting the field bus cable PLEASE NOTE The cable specifications must be observed. Signal reflections and attenuation occur in data transmission particularly with high baud rates. These can lead to faults in transmission. The causes of reflection can be: missing or incorrect terminating resistor branches Causes of signal attenuation can be: transmission over long distances unsuitable cables A twisted, screened two-core cable must be used for the field bus cable. The cable types to be used are specified in the PLC manual for your controller. Take into account the distance and the field bus baud rate set NH

44 3. Installation Selecting the operating voltage cable Several parameters must be considered when the two operating voltages are connected. Further information can be found in the following chapters: Chapter 3: Installation Section: "Connecting the operating voltage" - Calculating the current consumption - Design of power unit - Cable cross section and length (worst case) Appendix A: Cable length and cross section - Determining the cross section and length by means of tables - Calculating with a formula NH 3-5

45 3. Installation Connecting the cables to the plugs/sockets CAUTION The position of the pins is different depending on whether plugs or sockets are used. The connections of the input and output modules have been designed as sockets. The connections of the field bus interface and the operating voltage connections have been designed as plugs. The pin assignment is to be found in the following chapters. When you have selected suitable cables, connect them to the plugs/sockets according to the sequence of steps Open the plugs/sockets as follows (see diagram): Power supply socket: Insert the power supply socket into the operating voltage connection on the valve terminal. Unscrew the housing of the socket, then remove the connection part of the socket which is plugged into the operating voltage connection. Sensor plug and field bus socket: Unscrew the centre knurled nut NH

46 3. Installation 2. Open the strain relief on the rear part of the housing. Pass the cable through as shown below (see diagram). Cable outer diameter: PG 7: mm PG 9: mm PG 13.5: mm Plugs/sockets (straight/angled): Power supply socket: PG 7, 9 or 13.5 Sensor plug: PG 7 Bus cable socket: PG 7, 9 or 13.5 AAA AAA A Cable Strain relief Housing AAAAAAA AAAA AAA AAAAAAA AAAAAAA AAAAAAA AAAA AAAA AAAA AAAA AAAA AAAAAAA AAA AAAA AAAAAAA AAAAAAA AAAAAAA Connection part Socket Plug Fig. 3/1: Individual plug/socket parts and cable routing 3. Remove 5 mm of insulation from the end of the cable. 4. Fit the strands with cable end sleeves. 5. Connect the ends of the conductors. 6. Place the connection part onto the housing of the plug/socket again and fasten both parts with screws. Pull the cable back so that it is not looped inside the housing. 7. Tighten the strain relief NH 3-7

47 3. Installation 3.2 FIELD BUS NODE Opening and closing the node WARNING Before installation or maintenance work is carried out, the following must be switched off: the compressed air supply the power supply to the electronic components (pin 1). the power supply to the outputs/valves (pin 2). You thereby avoid: uncontrolled movement of loose tubing undesired movements of the connected actuators undefined switching states of the electronic components. CAUTION The node contains electrostatically vulnerable components. Do not therefore touch any components. Observe the regulations for handling electrostatically vulnerable components. You thereby avoid destroying the electronic components in the node NH

48 3. Installation The following connection and display elements are to be found on the cover of the node. Gren LED Red LED Plug for field bus cables BUS Fuse for operating voltage of inputs Power supply connection Fig. 3/2: Cover of the node PLEASE NOTE The cover is connected to the internal printed circuit boards by means of the operating voltage cable and cannot therefore be removed completely. Opening Unscrew and remove the 6 Philips screws in the cover and lift the cover up carefully. Do not damage the cable through mechanical stress. Closing Replace the cover. Place the operating voltage cables back into the housing so that they are not clamped. Tighten the Philips screws in the cover in diagonally opposite sequence NH 3-9

49 3. Installation Configuring the valve terminal There are four printed circuit boards in the node. Board 2 contains an LED and two plugs for the field bus cables; board 3 contains an LED and a switch for setting the configuration. Gren LED AA Red LED Plug for field bus cables AAA 1 2 AAA AAA 3 AAA 4 A Address selector switch DIL switch Screening plate Board 1 Board 2 Flat plug for operating voltage connection Board 4 Board 3 Fir. 3/3: Connection, display and operation elements of the node NH

50 3. Installation Setting the field bus address (network address) Use the two address selector switches on board 3 for setting the field bus address of the valve terminal. The switches are numbered from The arrow on the switches indicates the units figure or tens figure of the field bus address set. UNITS TENS Address selector switch UNITS figure Address selector switch TENS figure Fig. 3/4: Address selector switch PLEASE NOTE The valve terminal can only be used as a slave. Set only addresses from 2 to 99. Factory setting: address 2. Field bus (network) addresses must only be assigned once per field bus module. Recommendation Assign the field bus addresses in ascending order. Select field bus addresses to suit the machine structure of your system NH 3-11

51 3. Installation Possible (network) addresses PLC Addresses JETTER Factory setting: 2 Fig. 3/5: Possible (network) addresses Proceed as follows: 1. Switch off the operating voltage. 2. Assign a non-reserved field bus address to the valve terminal. 3. Use a screwdriver to set the arrow of the appropriate address selector switch to the units or tens figure of the desired field bus address. Example: UNITS TENS UNITS TENS Field bus address set: 05 Field bus address set: 38 Fig. 3/6: Example of (network) addresses set NH

52 3. Installation In addition to the address selector switch, the node also contains a DIL switch on which the following functions can be set: the baud rate. the protocol The DIL switch consists of four switch elements. These are numbered from The position "ON" is marked. 1 AAA AAA baud rate O N AAA AAA AAA AAA AAA AAA AAA baud rate protocol protocol Fig. 3/7: Position and function of the DIL switch 9610 NH 3-13

53 3. Installation Setting the baud rate The baud rate must be set with switches 1 and 2. PLEASE NOTE Set the baud rate of the valve terminal so that it corresponds to the setting of the field bus module (master) in the control system. The system only permits the baud rates 19.2 and kbaud. Factory setting: kbaud. Baud rate [kbaud] DIL switch ON Factory setting: kbaud. Fig. 3/8: Setting the baud rate NH

54 3. Installation Setting the protocol The protocol must be set with switches 3 and 4. If both switches are in the ON position, the valve terminal will operate as slave on the JETway-R. If both switches are in the OFF position, a test routine can be activated, see chapter 5, "Testing the valves". DIL switch JETway-R Test routine Factory setting: JETway-R ON Fig. 3/9: Setting the protocol 9610 NH 3-15

55 3. Installation Type 03: Connecting the operating voltages WARNING In order that the operating voltage can be isolated reliably, you must use an isolating transformer with at least 4 kv isolation resistance complying with standard EN CAUTION The power supply to the outputs/valves (pin 2) must be separately fused externally with max. 10 A. The external fuse prevents the valve terminal from being destroyed in the event of a short circuit NH

56 3. Installation The 24 V operating voltages are connected at the lower left-hand edge of the node. Operating voltage connection type 03 Fig. 3/10: Position of the operating voltage connection The following components of valve terminal type 03 are supplied separately with + 24 V DC via this connection: The operating voltage for the internal electronic components and the inputs of the input modules (pin 1: DC + 24 V, tolerance ± 25 %). The operating voltage for the valve outputs and the ouputs of the output modules (pin 2: DC + 24 V, tolerance ± 10 %, external fuse maximum 10 A required). Recommendation The operating voltage for the outputs should be connected to the EMERGENCY STOP circuit or EMERGENCY STOP contacts NH 3-17

57 3. Installation PLEASE NOTE With common voltage supply for pin 1 (electronic components and inputs) and pin 2 (outputs/valves) the lower tolerance of ± 10 % for both circuits must be observed. Check the 24V operating voltage of the outputs whilst your system is operating. Make sure that the operating voltage of the outputs lies within the permitted tolerances even during full operation. Recommendation Use a closed loop power unit. Calculate the complete current consumption according to the following table and select both a suitable power unit and cable cross section. Avoid long distances between the power unit and the terminal. Calculate also the permitted distance according to Appendix A. The following rule applies for type 03: Operating voltage Valve terminal Pin 1 = 2.2 A Pin 2 = 10 A Vo = 24 V Cable cross section Distance 1.5 mm 2 8 m 2.5 mm 2 14 m NH

58 3. Installation Calculating the current consumption (type 03) The following table shows the calculation of the total current consumption for terminal type 03. The values given are rounded up. If you use other valves or modules, you should consult the appropriate technical specifications for their current consumption. Current consumption of electronic components node and inputs type 03 (pin 1, 24 V ± 25 %) Node A Number of simultaneously occupied sensor inputs: x A + A Sensor supplies: x A (see manufacturer specifications) + A Current consumption of electronic components, node and inputs (pin 1) max. 2.2 A = A A Current consumption of outputs type 03 (pin 2, 24 V ± 10 %) Number of MIDI valve coils (simultaneously under power): x A + A Number of MAXI valve coils (simultaneously under power): x A + A Number of simultaneously activated electrical outputs: x A + A Load current of simultaneously activated electrical outputs x A + A Current consumption of outputs = A (pin 2) max. 10 A + A Total current consumption of valve terminal type 03 = A Fig. 3/11: Calculating the total current consumption of terminal type NH 3-19

59 3. Installation The diagram below shows the pin assignment of the operating voltage connection. 24 V supply for electronic components and inputs 1 24 V supply valves, outputs 4 PE 3 (protective earth connection, leading socket) 0 V Fig. 3/12: Pin assignment of the operating voltage connection (type 03) Protective earthing The valve terminal has two protective earthing connections: at the operating voltage connection (pin 4 incoming socket). at the left-hand end plate (M4 thread). 2 PLEASE NOTE Always connect the earth cable to pin 4 of the operating voltage connection. Make sure that the housing of the valve terminal and the earth cable at pin 4 have the same potential and that no equalizing currents flow. Connect an earth cable of sufficient crosssection to the left-hand end plate if the valve terminal is not mounted on an earthed machine stand. In this way you can avoid interference due to electromagnetic sources NH

60 3. Installation Example of connection (type 03) The following diagram shows the connection of a common 24 V supply for pin 1 and pin 2. Please note that: the supply to the outputs/slaves must be protected against short circuit/overload with an external fuse 10 A max. the electronic components and inputs must be protected against short circuit/overload with an external 3.15 A fuse (recommendation). the supply to the sensors is also protected by the internal fuse (2 A). the common tolerance of DC 24 V ± 10 % must be observed. equalizing currents must be avoided when both earth cables are connected, e.g. by means of cables with appropriate cross section as potential compensation NH 3-21

61 3. Installation Connection cable for potential equalization of earthing connections AC 230 V 0 V 24 V 3.15 A Fuse for inputs/sensors (2A) External fuses DC 24V ± 10% 10 A EMERGERCY STOP Protective earth connection pin 4 designed for 12 A Fig. 3/13: Example connecting a common 24 V supply and both protective earth cables (type 03) NH

62 3. Installation Type 05: Connecting the operating voltages WARNING In order that the operating voltage can be isolated reliably, you must use an isolating transformer with at least 4 kv isolation resistance complying with standard EN CAUTION The power supply to the outputs/valves (pin 2) must be separately fused externally with max. 10 A. The external fuse prevents the valve terminal from being destroyed in the event of a short circuit NH 3-23

63 3. Installation The 24 V operating voltages are connected on the adapter plate between the node and the valves. The node and the I/O-modules are supplied with operating voltage via the adapter cable. Operating voltage connection type 05 Fuse for valves (4 A slow blowing) Adapter cable Fig 3/14: Position of the operating voltage connection type 05 The following components of valve terminal type 05 are supplied separately with + 24 V DC via this connection: The operating voltage for the internal electronic components and the inputs of the input modules (pin 1: DC + 24 V, tolerance ± 25 %, external fuse max A recommended). The operating voltage for the valve outputs and the ouputs of the output modules (pin 2: DC + 24 V, tolerance ± 10 %, external fuse max. 10 A slow-blowing required). Recommendation: The operating voltage for the outputs/valves should be connected to the EMERGENCY STOP circuit or EMERGENCY STOP contacts NH

64 3. Installation PLEASE NOTE With common voltage supply for pin 1 (electronic components and inputs) and pin 2 (outputs/valves) the lower tolerance of ± 10 % for both circuits must be observed. Check the 24V operating voltage of the outputs whilst your system is operating. Make sure that the operating voltage of the outputs lies within the permitted tolerances even during full operation. Recommendation Use a closed-loop power unit. Calculate the complete current consumption according to the following table and select both a suitable power unit and cable cross section. Avoid long distances between the power unit and the terminal. Calculate also the permitted distance according to Appendix A. The following rule applies for type 05: Operating voltage*) Cable cross section Distance Valve terminal 1.5 mm 2 8 m Pin 1 = 2.2 A Pin 2 = 10 A Vo = 24 V 2.5 mm 2 14 m *) Please note that the max. total current consumption (pins 1 and 2) is 12.2 A 9610 NH 3-25

65 3. Installation Calculating the current consumption (type 05) The following table shows the calculation of the total current consumption for ISO terminal type 05. The values given are rounded up. If you use other valves or modules, you shuld consult the appropriate technical specifications for their current consumption. Current consumption of electronic components node and inputs type 05 (pin 1, 24 V ± 25 %) Node A Number of simultaneously occupied sensor inputs: x A + A Sensor supplies: x A (see manufacturer specifications) + A Current consumption of electronic components, node and inputs (pin 1) max. 2.2 A = A A Current consumption of outputs type 05 (pin 2, 24 V ± 10 %) Number of valve coils (simultaneously under power): x A + A Number of simultaneously activated electrical outputs: x A + A Load current of simultaneously activated electrical outputs x A + A Current consumption of outputs (pin 2) max. 10 A = A + A A Fig. 3/15: Calculating the total current consumption type NH

66 3. Installation The diagram below shows the pin assignment of the operating voltage connection on the adapter plate. 24 V supply for electronic components and inputs 1 24 V supply valves, outputs 4 PE 3 (protective earth connection, leading socket) 0 V Fig. 3/16: Pin assignment of the operating voltage connection (type 05) Protective earthing The valve terminal has two protective earthing connections as follows: at the operating voltage connection (pin 4 incoming socket) at the left-hand end plate (M4 thread) 2 PLEASE NOTE Always connect the earth cable to pin 4 of the operating voltage connection. Make sure that the housing of the valve terminal and the earth cable at pin 4 have the same potential and that no equalizing currents flow. Connect an earth cable of sufficient crosssection to the left-hand end plate if the valve terminal is not mounted on an earthed machine stand. In this way you can avoid interference due to electromagnetic sources NH 3-27

67 3. Installation Example of connection (type 05) The diagram overleaf shows the connection of a common 24 V supply for pin 1 and pin 2. Please note that: the outputs/valves must be protected against short circuit/overload with external 10 A fuse (slow blowing) the electronic components and inputs must be protected against short circuit/overload with an external 3.15 A fuse (recommendation) the supply of the sensors is protected additionally by the internal 2 A fuse the valves are protected additionally by the internal 4 A fuse (slow blowing) the common tolerance of DC 24 V ± 10 % must be observed the node must be supplied via the adapter cable equalizing currents must be avoided when both earth cables are connected, e.g. by means of cables with appropriate cross section as a potential compensation NH

68 3. Installation Fuse for inputs/sensors (2A) Operating voltage connection Fuse for valves (4 A, slow blowing) Connected adapter cable Connecting cable for potential compensation of earth connections AC 0 V 230V 24 V DC 24V ± 10% 3.15 A External fuses 10 A EMERGENCY STOP Earth cable connection pin 4 designed for 12 A Fig. 3/17: Example connecting a common 24 V supply and both earth cables (type 05) 9610 NH 3-29

69 3. Installation Connecting the JETway-R There are two field bus plugs on the node for connecting the valve terminal to the JETway-R. One of these connections is for the incoming cable and the other is for the continuing field bus cable. The signal cables of both plugs are connected with each other internally. Two methods of connection are therefore possible. Looping the field bus cable from terminal to terminal. Both field bus plugs are required here. Connecting the field bus cable by means of a T-adapter. Only one field bus plug is required here. CAUTION Branches (e.g. T-adapters) cause signal reflections under certain circumstances with high baud rates. This can lead to "telegram faults" with brief "failure" of valves. Recommendation Observe the maximum permitted distance of 15 cm between the T-adapter and the field bus plug in order to avoid signal reflections. Use the ready-made Festo T-adapter FB-TA for this purpose NH 3-30

70 3. Installation Incoming JETway-R Continuing JETway-R BUS Fig. 3/18 A: Connection variant for JETway-R Incoming JETway-R Continuing JETway-R T-adapter (e.g. Festo FB-adapter) Branch line max. 15 cm BUS Cover with protective cap (IP 65) Fig 3/18 B: Connection variant for JETway-R NH

71 3. Installation CAUTION Observe the polarity when connecting the field bus interface. Connect the screening. The diagram below shows the pin assignment of the field bus interface. Connect the field bus cables to the contacts of the bus cable socket accordingly. Note also the connection instructions in following diagrams, as well as the instructions in the PLC manual of your controller. S- 3 2 free Screening 4 1 S + BUS S free S + 1 MΩ 220 nf Internal resistor-capacity network Housing of node Fig 3/19: Pin assignment of field bus interface 9610 NH 3-32

72 3. Installation General instructions on the controllers Connection drawings The following drawings show the different possibilities of connecting a valve terminal to a controller from the JETTER processing PLC family. The framework of broken lines represents the screening connection on the controller side. Screening/shielding With PASE-E and Delta, connection to the field bus is made via the SUB-D plug. The cable screening must be connected here over a large area under the conductive strain relief. With Micro, the signal connections are on plug-in terminals. The screening connection is made via specially provided strain relief, under which the screening braiding of the cable must be fastened over a large area. Further instructions on screening can be found in the appropriate controller manuals NH

73 3. Installation Connection to PASE-E/CPU PLEASE NOTE The connnection instructions in the PASE-E manual must also be observed. With the PASE-E controller, the field bus is connected via the 9-pin or 15-pin SUB-D plug connector on the front panel of the CPU. With both plugs, the field bus signals are transmitted through pins 8 and 9. SUB-D plug 9-/15-pin 8 D D 3 PASE Screening 4 Valve terminal Fig. 3/20: Connecting cable for PASE-E/CPU 9610 NH 3-34

74 3. Installation Connection to PASE-E via INT5 card PLEASE NOTE The connnection instructions for the INT5 card in the PASE-E manual must also be observed. With the INT5 card, the field bus is connected for the operating mode "remote scan" via the 9-pin SUB-D plug connector of the second interface. The field bus signals are transmitted through pins 1 and 6. SUB-D plug 9-pin 8 DATA+ Bus cable socket 9-pin 1 9 DATA 3 PASE-E INT5 Screening 4 Valve terminal Fig. 3/21: Connecting cable for controller/int5 card NH

75 3. Installation Connection to Delta PLEASE NOTE The connnection instructions in the Delta manual must also be observed. With the Delta controller, the field bus is connected for network 1 via the 9-pin or SUB-D plug connector designated NET 1 and for network 2 via the 9-pin SUB-D plug connector designated NET 2. With both plugs, the field bus signals are transmitted through pins 8 and 9. SUB-D plug 9-pin Bus cable socket 4-pin 8 DATA DATA 3 Delta Screening Valve terminal 4 Fig. 3/22: Connecting cable for Delta 9610 NH 3-36

76 3. Installation Connection to Micro PLEASE NOTE The connnection instructions in the Micro manual must also be observed. With the Micro controller, the field bus is connected for network 1 via the terminal NET and for network 2 via the terminal SERIAL. Terminal NET D D DATA + DATA 1 3 Micro (network 1) 4 Valve terminal D2 D2 Terminal SERIAL DATA + DATA 1 3 Micro (network 2) 4 Valve terminal Fig. 3/23: Connecting cable for Micro NH

77 3. Installation Terminating resistor If the terminal to be connected is at the end of a field bus line, a terminating resistor must be fitted into the socket of the incoming field bus cable (120 Ohm, 0.25 Watt). The socket must be adapted for this purpose. The free field bus plug must be fitted with a protective cap (protection class IP 65). Proceed as follows (see diagram below): 1. Crimp the wires of the resistor together with those of the incoming field bus cable between the cores D+ (D, pin 1) and D- (D, pin 3) of the bus cable socket. In order to guarantee reliable contact, we recommend that the wires of the resistor and those of the incoming field bus cable be crimped together in common end sleeves. AAAA AAAA AAAA AAAAAA AAAA AAAA AAAA AAAAAA AAAA AAAA AAAA AAAA AAAAAAAAAAAAA AAAA AAAA AAAA AAAA AAAA AAAAAAAAAAAAAA AAAA AAAA AAAA AAAA AAAA AAAAAAAAAAAAAA AAAA AAAA AAAA AAAA AAAAAAAAAAAAAA AAAA AAAA AAAA AAAAAA AAAA AAAA AAAA AAAAAA 3 A 120 Ω 4 1 Fig 3/24: Fitting the terminating resistor 2. Fit the bus cable socket onto one of the field bus plugs. 3. Cover the unused field bus plug with a protective cap NH 3-38

Valve terminal type 03/05 Electronics Manual Field bus connection FB15

Valve terminal type 03/05 Electronics Manual Field bus connection FB15 Valve terminal type 03/05 Electronics Manual Field bus connection FB15 Field bus protocol: EAE field bus-2 Only valid in agreement with the printed documentation accompanying the product! Compare this

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB13

Valve terminal type 03/05 Electronics Manual Field bus connection FB13 Valve terminal type 03/05 Electronics Manual Field bus connection FB13 Field bus protocol: PROFIBUS DP 12 MBaud 163958 GB Only valid in agreement with the printed documentation accompanying the product!

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB14

Valve terminal type 03/05 Electronics Manual Field bus connection FB14 Valve terminal type 03/05 Electronics Manual Field bus connection FB14 Field bus protocols: CANopen SDS Smart Distributed System 163959 GB 9801A Author: Editor: Translation: Layout: Type setting: S. Breuer,

More information

Valve terminal type 03/05 Electronics Manual Control block SB-202

Valve terminal type 03/05 Electronics Manual Control block SB-202 Valve terminal type 03/05 Electronics Manual Control block SB-202 Only valid in agreement with the printed documentation accompanying the product! Compare this edition code. 9602 Authors: Editors: Translation:

More information

Valve terminal type 03/05 Electronics Manual Field bus connection FB16

Valve terminal type 03/05 Electronics Manual Field bus connection FB16 Valve terminal type 03/05 Electronics Manual Field bus connection FB16 Field bus protocols: FIPIO standard Telemecanique - APRIL 164222 GB Only valid in agreement with the printed documentation accompanying

More information

Compact Performance CP system Installation and commissioning

Compact Performance CP system Installation and commissioning Compact Performance CP system Installation and commissioning Author: Translation: Editors: Layout: Type setting: S. Breuer Douglas Smith H.-J. Drung, M. Holder Festo, Dept. PV-IDM PV-IDM Edition: 9806A

More information

Valve terminal types 03/04-B

Valve terminal types 03/04-B Valve terminal types 03/04-B Electronics manual Valve terminal with field bus connection FB8 Allen-Bradley RIO network Type IFB08-03 Manual 152 768 Contents and general instructions Author... H.-J. Drung

More information

Compact performance. Electronics manual. System manual. Installing and commissioning CP systems. Manual en 0010b

Compact performance. Electronics manual. System manual. Installing and commissioning CP systems. Manual en 0010b Compact performance Electronics manual System manual Installing and commissioning CP systems Manual 165 226 en 0010b Contents and general instructions Author... S. Breuer Editors... H.-J. Drung, M.Holder

More information

Valve terminal types 03/04-B

Valve terminal types 03/04-B Valve terminal types 03/04-B Electronics manual Valve terminal with field bus connection PROFIBUS-DP 12 MBaud Type IFB13-03 Manual 163 958 en 0003c Contents and general instructions Authors... U. Reimann,

More information

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ]

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ] Compact performance Brief description CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8 English 8080251 2017-11e [8080244] Translation of the original instructions Documentation on the

More information

CPX terminal. Manual Electronics. Digital CPX I/O modules and Connection blocks Types: - CPX-8DE-8DA - CPX-AB- CPX pneumatic interfaces Types:

CPX terminal. Manual Electronics. Digital CPX I/O modules and Connection blocks Types: - CPX-8DE-8DA - CPX-AB- CPX pneumatic interfaces Types: CPX terminal Manual Electronics Digital CPX I/O modules and Connection blocks Types: - CPX- DE - CPX- DA - CPX-8DE-8DA - CPX-M- - CPX-L- - CPX-AB- CPX pneumatic interfaces Types: - VMPA -FB-EPL- - VMPAL

More information

VIFB9-02. Michael Holder, H.-J. Drung. Festo, Dept. PV-IDM. Type setting: Edition (Festo AG & Co., D Esslingen, 1997)

VIFB9-02. Michael Holder, H.-J. Drung. Festo, Dept. PV-IDM. Type setting: Edition (Festo AG & Co., D Esslingen, 1997) Author: Editors: Translation: Layout: Type setting: Heinz Hohner Michael Holder, H.-J. Drung Douglas Smith Festo, Dept. PV-IDM DUCOM Edition 9706 printed on 100% receycling paper (Festo AG & Co., D-73726

More information

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ]

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ] CPX-Terminal Brief description CPX analogue I/O modules CPX-2AE CPX-4AE CPX-2AA English 8080173 2017-11e [8080175] Translation of the original instructions Documentation on the product For all available

More information

Valve terminal type 03 and type 44/45

Valve terminal type 03 and type 44/45 Valve terminal type 03 and type 44/45 Electronics manual Valve terminal with INTERBUS field bus connection Fibre optical waveguide remote bus Rugged Line" Type IFB21 03 Manual 191 085 en 0807c [739 015]

More information

Valve terminal type 03/04 B

Valve terminal type 03/04 B Valve terminal type 03/04 B Electronics manual Field bus node Type IFB13 03 Field bus protocol PROFIBUS DP 12 MBaud Manual 163 958 en 0503f Contents and general instructions Author.................................

More information

Programmable Valve Terminal type 02 Electronics Manual Control block SF 3

Programmable Valve Terminal type 02 Electronics Manual Control block SF 3 Programmable Valve Terminal type 02 Electronics Manual Control block SF 3 Festo PLC integrated Field bus protocol: Festo field bus 0503b Authors: Editors: Layout: Translation: Uwe Gräff Eberhard Klotz

More information

CDVI-DN Valve Terminal (Type 15) DeviceNet

CDVI-DN Valve Terminal (Type 15) DeviceNet CDVI-DN Valve Terminal (Type 15) DeviceNet Description Electronics Valve terminal with direct fieldbus connection Fieldbus protocol: - DeviceNet CDVI-DN type Description 539 045 en 0805a [720 999] Contents

More information

Smart Positioning Controller SPC200 Stepping motor indexer module

Smart Positioning Controller SPC200 Stepping motor indexer module Smart Positioning Controller SPC200 Stepping motor indexer module Type SPC200-SMX-1 Author: Editors: Layout: Type setting: P. Mauch H.-J. Drung, M. Holder Festo AG & Co., Dept. KI-TD KI-TD Edition: 9904NH

More information

Compact Performance CPV valve terminal with direct connection Electronics

Compact Performance CPV valve terminal with direct connection Electronics Compact Performance CPV valve terminal with direct connection Electronics Field bus protocols: PROFIBUS-DP, Festo, ABB CS31, SUCOnet K Direct connection type CPV..-DI01 Contents and safety instructions

More information

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV...-DI02 PROFIBUS-DP CPV...

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV...-DI02 PROFIBUS-DP CPV... Compact performance Elektronics manual CPV valve terminal with field bus direct connection Types: CPV...-DI02 PROFIBUS-DP CPV...-CS02 ABB CS31 Manual 548732 en 1201a [762106] Contents and general instructions

More information

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date:

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date: Documentation KM2604 and KM2614 Four channel relay module Version: Date: 2.1.0 2017-12-01 Tabel of contents Tabel of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety instructions...

More information

Terminal CPX. Bus node CPX-FB14. Description. CANopen networkprotocol en 1411d [ ]

Terminal CPX. Bus node CPX-FB14. Description. CANopen networkprotocol en 1411d [ ] Terminal CPX Bus node CPX-FB14 Description CANopen networkprotocol 526410 en 1411d [8041138] Contents and general instructions Original... de Edition... en 1411d Designation... P.BE-FB14-EN Order no....

More information

Compact performance. Description. Programming and diagnosis. CP fieldbus node 8. Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03

Compact performance. Description. Programming and diagnosis. CP fieldbus node 8. Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03 Compact performance Description Programming and diagnosis CP fieldbus node 8 Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03 Description 165 08 en 080e [730 609] Contents and general

More information

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ]

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ] Terminal CPX Electrical interface CPX CTEL 4 M12 5POL Description CTEL master module I-Port 574601 1411a [8041791] Electrical interface CPX CTEL 4 M12 5POL Translation of the original instructions P.BE-CPX-CTEL-EN

More information

CPX terminal. Manual Electronics. CPX bus node. Type CPX-M-FB20 and CPX-M-FB21. Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus

CPX terminal. Manual Electronics. CPX bus node. Type CPX-M-FB20 and CPX-M-FB21. Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus CPX terminal Manual Electronics CPX bus node Type CPX-M-FB20 and CPX-M-FB21 Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus Manual 575 108 en 1202a [8002868] Contents and general

More information

Compact performance. Electronics manual. CP modules. Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL

Compact performance. Electronics manual. CP modules. Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL Compact performance Electronics manual CP modules Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL Output module type CP A04 M12 CL Manual 539 300 en 0404NH [681 792] Contents and

More information

Programmable valve terminals type 02 with control block SB 50 / SF 50 Manual

Programmable valve terminals type 02 with control block SB 50 / SF 50 Manual Programmable valve terminals type 02 with control block SB 50 / SF 50 Manual SIMATIC Integrated 9706 174 829 TN 350 650 VISB - 50 Authors: Translation: Editor: Layout: Typesetting: Uwe Gräff Siegfried

More information

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B. Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date: Documentation Sixteen channel digital output module with D-Sub Connector Version: Date: 2.0.0 2017-11-20 Table of contents Table of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety

More information

CPX terminal. Electronics Manual. CPX field bus node. Type CPX FB32. Field bus protocol EtherNet/IP. Manual [ ]

CPX terminal. Electronics Manual. CPX field bus node. Type CPX FB32. Field bus protocol EtherNet/IP. Manual [ ] CPX terminal Electronics Manual CPX field bus node Type CPX FB32 Field bus protocol EtherNet/IP Manual 541 305 en 0605NH [693 135] Contents and general instructions Original.......................................

More information

SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation

SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation Introduction Prerequisites This guide takes you through

More information

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006 s SIWAREX JB Aluminum Housing Instruction Manual Edition 03/2006 Table of Contents Table of Contents... 2 Warning and Safety Terms... 3 General... 4 1 Technical Description... 5 1.1 Area of Application...

More information

Operating instructions valve control box AS-i

Operating instructions valve control box AS-i THIS LEAFLET SHOULD BE KEPT IN A SAFE PLACE FOR REFERENCE Operating instructions valve control box AS-i 1 System description The Norgren Herion valve control box is used for controlling pneumatic swivel

More information

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date: Documentation Sixteen Channel Digital Output Module with D-Sub Connector Version: Date: 2.0 2016-08-03 Table of contents Table of contents 1 Foreword... 4 1.1 Notes on the documentation... 4 1.2 Safety

More information

Operating Instructions VEGAMET 381

Operating Instructions VEGAMET 381 Operating Instructions VEGAMET 381 in out Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6 2.1 Authorised personnel...

More information

CPX terminal. Electronics Manual. CPX I/O modules, sub bases, pneumatic. electronic modules. Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB...

CPX terminal. Electronics Manual. CPX I/O modules, sub bases, pneumatic. electronic modules. Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB... CPX terminal Electronics Manual CPX I/O modules, sub bases, pneumatic interfaces and MPA electronic modules Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB... VMPA FB EPL... CPX GP... VABA 0S6 X VMPA...

More information

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B. Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable

More information

Compact performance. Manual Electronics. CPV valve terminal with direct connection. Type CPV..-GE-DN-8. Field bus protocol: - DeviceNet

Compact performance. Manual Electronics. CPV valve terminal with direct connection. Type CPV..-GE-DN-8. Field bus protocol: - DeviceNet Compact performance Manual Electronics CPV valve terminal with direct connection Type CPV..-GE-DN-8 Field bus protocol: - DeviceNet Manual 175 563 en 0009a Contents and general instructions Authors...

More information

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3 Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger

More information

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens). Vision OPLC Installation Guide Models 230/260/280/290 (Non-color Screens) This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens). General Description Vision OPLCs

More information

CPX terminal. Manual Electronics. CPX field bus node. Type CPX FB11. Field bus protocol DeviceNet. Manual en 0503b [ ]

CPX terminal. Manual Electronics. CPX field bus node. Type CPX FB11. Field bus protocol DeviceNet. Manual en 0503b [ ] CPX terminal Manual Electronics CPX field bus node Type CPX FB11 Field bus protocol DeviceNet Manual 526 422 en 0503b [689 002] Contents and general instructions Original.......................................

More information

Siemens Drives & PLCs

Siemens Drives & PLCs Automation System S7-300: Getting Started CPU 31xC: Commissioning Introduction 1 Preparation 2 SIMATIC S7-300 Automation System S7-300: Getting Started CPU 31xC: Commissioning Learning units 3 Further

More information

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport PTX5000 Packet Transport Router Quick Start September 2017 Part Number: 530-066788 Revision 01 This document describes how to install the Juniper Networks PTX5000 Packet Transport Router. Contents Quick

More information

Keysight M8000 Series BER Test Solutions

Keysight M8000 Series BER Test Solutions Keysight M8000 Series BER Test Solutions J-BERT M8020A High-Performance BERT M8030A Multi-Channel BERT M8040A High-Performance BERT M8041A, M8051A, M8061A, M8062A, M8045A, M8046A & M8057A Tips for Preventing

More information

Documentation KM2002, KM2004, KM2008. Terminal modules with digital outputs, 24 V, 0.5 A. Version: Date:

Documentation KM2002, KM2004, KM2008. Terminal modules with digital outputs, 24 V, 0.5 A. Version: Date: Documentation KM2002, KM2004, KM2008 Terminal modules with digital outputs, 24 V, 0.5 A Version: Date: 3.2.0 2017-01-23 Table of contents Table of contents 1 Foreword... 4 1.1 Notes on the documentation...

More information

Documentation. KM10xx. Terminal Modules with Digital Inputs. Version: Date:

Documentation. KM10xx. Terminal Modules with Digital Inputs. Version: Date: Documentation KM10xx Terminal Modules with Digital Inputs Version: Date: 3.1.0 2017-01-23 Product overview KM10xx Product overview KM10xx KM1002, KM1012 [} 11] - 16 inputs, input filter 3 or 0.2 ms KM1004,

More information

Type Quickstart

Type Quickstart Type 8605 Digital Control Electronics for Proportional Valves Digitale Ansteuerelektronik für Proportionalventile Régulateur électronique numérique pour vannes proportionnelles Quickstart Contents 1 Quickstart...

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

WINSTA. Full Line Catalog 2008/2009

WINSTA. Full Line Catalog 2008/2009 WINSTA Full Line Catalog 2008/2009 5 Contents FULL LINE CATALOG W4, Volume 1 Rail-Mounted Terminal Block Systems FULL LINE CATALOG W4 Rail-Mounted Terminal Blocks Volume 1 X-COM -SYSTEM Terminal Strips

More information

Compact Performance. Description. Electronics. CP fieldbus node 5. Programming and diagnosis. Type CP FB5 E

Compact Performance. Description. Electronics. CP fieldbus node 5. Programming and diagnosis. Type CP FB5 E Compact Performance Description Electronics CP fieldbus node 5 Programming and diagnosis Type CP FB5 E Fieldbus protocols: Festo fieldbus ABB CS 31 Moeller SUCOnet K Description 165 205 en 0802c [730 598]

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Operating instructions ClassicLine module AC5203 / AC5205 AC5208 / AC5211 AC5213 / AC5214 AC5215 / AC5233 AC /00 02/2015

Operating instructions ClassicLine module AC5203 / AC5205 AC5208 / AC5211 AC5213 / AC5214 AC5215 / AC5233 AC /00 02/2015 Operating instructions ClassicLine module AC5203 / AC5205 AC5208 / AC5211 AC5213 / AC5214 AC5215 / AC5233 AC5294 80226775/00 02/2015 Contents 1 Preliminary note...3 2 Safety instructions...3 3 Functions

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808R, UID-0808T, UID-1600,UID-0016R, UID-0016T Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides

More information

Intrinsically safe batch controller Batching Master 110i

Intrinsically safe batch controller Batching Master 110i Intrinsically safe batch controller Batching Master 110i Installation Guide BVS 04 AT E 172 Revision 12.2 IBS BatchControl GmbH Im Sträßchen 2-4 Tel.: ++49 2441 9199 801 53925 Kall Fax.: ++49 2441 9199

More information

Electromotoric actuators Torques up to 60 Nm Running times ¹) s. ¹) Predefined by the basic unit (LMV5...)

Electromotoric actuators Torques up to 60 Nm Running times ¹) s. ¹) Predefined by the basic unit (LMV5...) 7 818 Actuators SQM9... Electromotoric actuators Torques up to 60 Nm Running times ¹) 30...120 s ¹) Predefined by the basic unit (LMV5...) The SQM9... and this Data Sheet are intended for use by OEMs which

More information

DX561 Digital Input/Output Module

DX561 Digital Input/Output Module Ordering Data DATA SHEET DX561 Digital Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R2301 1TNE 968 901 R3101 DX561, digital input/output module, 8 DI

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808THS Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH Industriefunkuhren Technical Manual Signal Converter for DIN Rail Mounting Series 4800xx-yy ENGLISH Version: 01.01-19.07.2007 2 / 23 Signal Converter 4800 - V01.01 INPORTANT NOTES Downloading Technical

More information

Operating Instructions

Operating Instructions Innovative by tradition. Operating Instructions Control Unit SG-RSV 239 Version 1 1003986 SG-RSV 239/24 24 V= 1005372 SG-RSV 239/36 36 V= 1003271 SG-RSV 239 50-150 V= Mayser GmbH & Co. KG Örlinger Straße

More information

CPX terminal. Bus node CPX-FB38. Electronics description. Network protocol EtherCAT. Description en 1301a [ ]

CPX terminal. Bus node CPX-FB38. Electronics description. Network protocol EtherCAT. Description en 1301a [ ] CPX terminal Bus node CPX-FB38 Electronics description Network protocol EtherCAT Description 562525 en 1301a [8024385] Contents and general safety instructions Original... de Edition... en 1301a Designation...

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIA-0402N Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

DC562, digital input/output module,

DC562, digital input/output module, Ordering Data DATA SHEET DC562 Digital Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 231 900 R0000 1TNE 968 901 R3101 1TNE 968 901 R3102 1TNE 968 901 R3103 1TNE

More information

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~ Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

PNOZ m ES RS232. Configurable Control System PNOZmulti. Operating Manual EN-01

PNOZ m ES RS232. Configurable Control System PNOZmulti. Operating Manual EN-01 PNOZ m ES RS232 Configurable Control System PNOZmulti Operating Manual-1002701-EN-01 This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies

More information

BNI DNT Z004 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005 Short Guide

BNI DNT Z004 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005 Short Guide BNI DNT-104-000-Z004 BNI DNT-202-000-Z005 BNI DNT-302-000-Z005 BNI DNT-305-000-Z005 Short Guide English 1 2 3 4 Notes to the User 3 1.1 About this guide 3 1.2 Structure of the guide 3 1.3 Typographical

More information

AO561 Analog Output Module

AO561 Analog Output Module Ordering Data DATA SHEET AO561 Analog Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R1201 AO561, analog output module, 2 AO, U/I 1TNE 968 901 R3102 Terminal

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UID-W1616R, UID-W1616T Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide

More information

TCNM-ACBB1 Installation Manual

TCNM-ACBB1 Installation Manual The TCNM-ACBB1 is a connection box that can be used as an accessory to facilitate system connections for installation and device replacement of several Banner family reading devices. System cabling is

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIS-04PTN Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

Operating instructions ClassicLine module AC5204 / AC5209 / AC5212 AC5235 / AC5236 / AC5237 AC /00 07/2017

Operating instructions ClassicLine module AC5204 / AC5209 / AC5212 AC5235 / AC5236 / AC5237 AC /00 07/2017 Operating instructions ClassicLine module AC5204 / AC5209 / AC5212 AC5235 / AC5236 / AC5237 AC5274 7390889/00 07/2017 Contents 1 Functions and features...3 2 Operating and display elements...3 3 Installation...4

More information

Extension module for lighting control

Extension module for lighting control s 3 842 DESIGO RXC Extension module for lighting control Extension to the RXC30 / RXC31 / RXC38 room controller RXC40.1 RXC40.5 The RXC40 extension module is used in conjunction with an RXC30, RXC31 or

More information

DI561 Digital Input Module

DI561 Digital Input Module Ordering Data DATA SHEET DI561 Digital Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R2101 1TNE 968 901 R3101 1TNE 968 901 R3103 1TNE 968 901 R3105 DI561, digital

More information

Type 6150 AS-Interface Module. Type 3372 Electropneumatic Actuator with AS-interface module. Mounting and Operating Instructions EB 6150 EN

Type 6150 AS-Interface Module. Type 3372 Electropneumatic Actuator with AS-interface module. Mounting and Operating Instructions EB 6150 EN Type 6150 AS-Interface Module Type 3372 Electropneumatic Actuator with AS-interface module Mounting and Operating Instructions EB 6150 EN Edition July 2013 Definition of the signal words used in these

More information

SUBCON-PLUS-PROFIB...

SUBCON-PLUS-PROFIB... Fast connector for PROFIBUS systems Data sheet 101610_en_10 PHOENIX CONTACT 2017-03-27 1 Description The SUBCON-PLUS-PROFIB... D-SUB series is specifically designed for use in PROFIBUS systems up to 12

More information

DT1102 V (PS) Fully Configurable Galvanic Isolator. Operating Instructions

DT1102 V (PS) Fully Configurable Galvanic Isolator. Operating Instructions (PS) Fully Configurable Galvanic Isolator Operating Instructions Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized

More information

Universal Tristop Cylinder for Cam Brakes

Universal Tristop Cylinder for Cam Brakes Tristop for Cam Brakes 3rd Edition This publication is not subject to any update service. New versions are available in INFORM at www.wabco-auto.com Copyright WABCO 2006 Vehicle Control Systems An American

More information

Compact performance. Programming and diagnostics manual. CP field bus node 11 Type CP FB11 E. Field bus protocol: DeviceNet

Compact performance. Programming and diagnostics manual. CP field bus node 11 Type CP FB11 E. Field bus protocol: DeviceNet Compact performance Programming and diagnostics manual CP field bus node 11 Type CP FB11 E Field bus protocol: DeviceNet Manual 165 211 en 0802d [730 616] Contents and general instructions Original.......................................

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

CPX terminal Electronics manual Manual

CPX terminal Electronics manual Manual CPX terminal Electronics manual CPX field bus node Type CPX-FB13 Field bus protocol PROFIBUS-DP as per EN 50170 Manual 526 428 en 0112NH [653 614] Contents and general instructions Authors... U.Reimann,U.Gräff

More information

DI572 Digital Input Module

DI572 Digital Input Module Ordering Data DATA SHEET DI572 Digital Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 230 500 R0000 1TNE 968 901 R3101 1TNE 968 901 R3102 1TNE 968 901 R3103 1TNE 968

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

Terminal CPX. Bus node CPX-FB37. Description. Network protocol EtherCAT NH [ ]

Terminal CPX. Bus node CPX-FB37. Description. Network protocol EtherCAT NH [ ] Terminal CPX Bus node CPX-FB37 Description Network protocol EtherCAT 8029675 1406NH [8029664] CPX-FB37 Translation of the original instructions P.BE-CPX-FB37-EN EtherCAT,TwinCAT,CANopen,SPEEDCON,Torx,Windows

More information

VARIOSUB D-SUB 25 Contact Inserts, Sleeve Housings

VARIOSUB D-SUB 25 Contact Inserts, Sleeve Housings Contact Inserts, Sleeve Housings Introduction VARIOSUB is a range of plug connectors specially designed for signal and data technology in an industrial environment with high degrees of protection, temperatures

More information

AI561 Analog Input Module

AI561 Analog Input Module Ordering Data DATA SHEET AI561 Analog Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R1101 AI561, analog input module, 4 AI, U/I 1TNE 968 901 R3101 1TNE 968

More information

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5

More information

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the

More information

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3 Overview Safety notes 1 SITOP power supply Manual Description, device design, dimension drawing 2 Mounting/removal 3 Mounting position, mounting clearances 4 Installation 5 Technical data 6 Safety, approvals,

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V Innovative by tradition. Control unit SG-EFS 104/4L EN Operating instructions Version 2 1004128 SG-EFS 104/4L AC/DC 24 V Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

SmartWire-DT Modules IP67

SmartWire-DT Modules IP67 Manual 05/15 MN120006EN SmartWire-DT Modules IP67 All proprietary names and product designations are brand names or trademarks registered to the relevant title holders. Break-Down Service Please call your

More information

4.7 Digital Input/Output Module 07 DC digital inputs, 8 digital outputs, 8 configurable inputs/outputs, 24 V DC, CS31 system bus

4.7 Digital Input/Output Module 07 DC digital inputs, 8 digital outputs, 8 configurable inputs/outputs, 24 V DC, CS31 system bus 4.7 Digital Input/Output Module 16 digital inputs, 8 digital outputs, 8 configurable inputs/outputs, 4 V DC, CS31 system bus 1 3 Advant Controller 31 I/O Unit ERR Test 4 1 Fig. 4.7-1: Digital input/output

More information

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections Data sheet 3379_en_B 1 Description PHOENIX CONTACT 2015-07-14 2 Features Media converters provide

More information

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name Product data sheet Characteristics XPSMF3542 Preventa safety PLC compact - Profibus DP protocol Main Range of product Product or component type Safety module name Safety module application Nov 13, 2018

More information

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1 Operating Instructions Control Unit SGTRS 3X8 Version 1 100597 SGTRS 318 110 V= 100596 SGTRS 38 4 V= Original instructions GmbH & Co KG Örlinger Straße 1 3 89073 Ulm GERMANY Tel: +49 731 0610 Fax: +49

More information

PNEUMATIC CRIMPER PC 12-8B OPERATING MANUAL

PNEUMATIC CRIMPER PC 12-8B OPERATING MANUAL PNEUMATIC CRIMPER PC 12-8B OPERATING MANUAL CONTENTS www.americanelectrical.com SAFETY BASIC INFORMATION... 1 SYMBOLS.1 OPERATION OF MACHINE & POSSIBLE DANGERS. 1 DESIGNATED USE. 2 DANGERS 2 PLACES FOR

More information

Terminal CPX. Bus node CPX-FB40. Description Electronics. Network protocol Ethernet POWERLINK NH [ ]

Terminal CPX. Bus node CPX-FB40. Description Electronics. Network protocol Ethernet POWERLINK NH [ ] Terminal CPX Bus node CPX-FB40 Description Electronics Network protocol Ethernet POWERLINK 8028651 1408NH [8028657] Bus node CPX-FB40 Translation of the original instructions P.BE-CPX-FB40-EN Ethernet

More information

This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens).

This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens). Vision OPLC Installation Guide Models V230/260/280/290 (Non-color Screens) This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens). General Description Vision OPLCs

More information

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005 Product and Applications Description Application Programs The application programs of the dimmer UP 525/01 consist of two elements: the actuating and the sensor program element. The tasks actuating program

More information

CPX terminal. Description Electronics. System manual. Installing and. terminals. Description en 0902e [742939]

CPX terminal. Description Electronics. System manual. Installing and. terminals. Description en 0902e [742939] CPX terminal Description Electronics System manual Installing and commissioning CPX terminals Description 526 446 en 0902e [742939] Contents and general safety instructions Original.......................................

More information