VersaMax* DeviceNet Network Master/Slave

Size: px
Start display at page:

Download "VersaMax* DeviceNet Network Master/Slave"

Transcription

1 Product Description Quick Start Guide Revision: Firmware version: 1.10 Firmware upgrades: Specifications Operating Modes: Slaves Supported: Configuration: IC200BEM103-MA None Master only, Slave only, Combined Master/Slave Up to 40 slave devices may be configured for the Master mode Configured as a Generic Communication Module with contiguous %I, %Q, %AI, and %AQ references. Status Data: Slave presence bit per each slave device, 64 bits total. DeviceNet Features: Slave only - Group 2 Only Server or UCMM Capable (COMMREQ selectable) DeviceNet network address: DeviceNet network data rate: Indicators (3): Master or Master/Slave - UCMM Capable 0 to 63. COMMREQ selectable. 125K, 250K, 500K baud. COMMREQ selectable. OK LED to indicate the status of the NCM after powerup. Mod LED to indicate the status of the NCM module. Net LED to indicate communication status on the DeviceNet network. Power Consumption: Backplane: 140mA at 5V, 10mA at 3.3V DeviceNet: 125mA maximum The DeviceNet Network Control Module is a DeviceNet master/slave module that provides an interface to a DeviceNet network. One or more NCMs may be installed at any location in the PLC. 1. Install the Communications Carrier on the DIN Rail by simply clicking it into place. Note: Connecting carriers must be installed on the same section of 35mm x 7.5mm DIN rail. The DIN rail must have a conductive (unpainted) finish for proper grounding. 2. Install the Module on the Communications Carrier. The latch on the module must be in the unlocked position. Align the connectors and the latch post and press the NCM down until the two tabs on the bottom of the NCM click into place. Turn the latch to the locked position to secure the NCM to the top of the carrier. 3. Connect the communications bus to the connector on the front of the Network Control Module. (Refer to the heading Bus Installation Guidelines for detailed bus installation instructions.) 4. Remove the connector cover on the right-hand side of the Communications Carrier. Do not discard this cover; you will need to install it on the last carrier. It protects the connector pins from damage and ESD during handling and use. Connector Cover PLC CPU power supply Optional booster power supply DeviceNet Network Control Module 5. Install additional modules by mounting modules on their carriers and sliding them along the DIN rail to fully engage the connectors in the sides of the carriers. Preinstallation Check Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system. 6. Power up the System, and Observe the Module LEDs. The LEDs indicate the presence of power and show the operating mode and status of the NCM. OK MOD NET 1

2 OK MOD NET OFF when the NCM has not yet started its powerup sequence. Blinking green indicates the NCM is performing its powerup sequence and has not yet finished successfully. Green indicates the NCM has successfully completed powerup diagnostics. Amber when the NCM has either failed powerup diagnostics or has not yet received a valid from the CPU. Blinking amber means the NCM has failed powerup diagnostics. The number of blinks indicates the fault type. OFF when the NCM is not powered. blinks green if the NCM is missing, incomplete, or incorrect. The NCM may be in Standby state. green when the NCM is operating normally. blinks red if there is a recoverable fault. red if there is an unrecoverable fault. The NCM may need replacing. OFF when the NCM is not online or not powered. blinks red and green if the NCM detects a Network Access error and is in the Communications Faulted state. blinks green if the NCM is online but has no connections in the established state. It has no established connections to other nodes. green when the NCM is online and has connections in the established state. blinks red if one or more I/O Connections are in the Timed-Out state. red if an error renders the NCM incapable of communicating on the network. Bus Installation Guidelines The network cable required for DeviceNet operation is specified in the following table. A 5-conductor cable is necessary. One wire is a drain, two wires are for carrying power on the network, and the remaining two wires are to carry the data transmission. On a DeviceNet fieldbus, every device must, at least, power its network transceivers from the network power source. Some devices draw all of their power from the network supply. DeviceNet specifies two types of network cable, Thick and Thin cable. Thick cable provides for longer distances and more power. Generally, Thick cable is used for the Trunk cable. Thin cable is used for shorter distances and is generally used for drop cables or where cable flexibility is necessary. DeviceNet Cable Specifications Thick Cable General Specifications Thin Cable General Specifications Network Topology Redundancy Network Power for Node devices Allowed Nodes (Bridging excluded) Data Packet Size Duplicate Address Detection Error Detection / Correction Two shielded pairs - Common axis with drain wire in center Overall braid shield - 65% coverage; 36 AWG or 0.12mm tinned Cu braid minimum (individually tinned) Drain wire- #18 Copper minimum; 19 strands minimum (individually tinned) Outside diameter inches (min) to inches (max.) roundness radius delta to be within 15% of 0.5 O.D. Two shielded pairs - Common axis with drain wire in center Overall braid shield - 65% coverage; 36 AWG or 0.12mm tinned Cu braid minimum (individually tinned) Drain wire - #22 Copper; 19 strands minimum (individually tinned) Outside diameter inches (min.) to inches (max.) roundness radius delta to be within 20% of 0.5 O.D. Bus with limited branching (trunkline/dropline) Not Supported Nominal 24 volt DC ±4% 64 nodes 0-8 bytes with allowance for message fragmentation Addresses verified at power-up CRC - retransmission of message if validity not acknowledged by recipient Installation in Hazardous Locations This equipment is suitable for use in CLASS I, DIVISION 2, GROUPS A, B, C, D or non-hazardous locations only. WARNING - EXPLOSION HAZARD - substitution of components may impair suitability for CLASS I, DIVISION 2; WARNING - EXPLOSION HAZARD - when in hazardous locations, turn off power before replacing or wiring modules; and WARNING - EXPLOSION HAZARD - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. 2

3 Bus Length The maximum length of the bus is limited by the cable type, transfer rate, and the number and accumulated length of drop lines. Individual branch lengths may not exceed 6 meters and are limited to one network node per drop. However, the node may be a node offering multiple ports. With Thin cable, the maximum bus length, regardless of data rate, is 100m. With Thick cable used as the trunk line, the maximum bus length is as shown in the following table. Data Rate 500Kbps 250Kbps 125Kbps Bus length and drop length restrictions 100m bus length and branches totaling < 39m 250m bus length and branches totaling < 78m 500m bus length and branches totaling < 156m Bus Connectors and Termination DeviceNet uses several forms of connectors. The NCM provides the 5- pin standard Phoenix open-style pluggable connector. The pin-to-signalto-wire color assignments are shown in the following table: Pin Signal Wire Color 1 V- Black 2 CAN_L Blue 3 Shield Bare 4 CAN_H White 5 V+ Red Connector orientation on the NCM is shown in figure below: 1 - V- 2 - CAN_L 3 Shield 4 - CAN_H 5 - V+ Termination of a DeviceNet network is passive and includes one resistor at each end of the network. A terminating resistor is placed across the data communication signals at pin 2 (CAN_L) and pin 4 (CAN_H). Correct terminating resistor is a 121 ohm 1% ¼ watt resistor. Bus Power Supply and Grounding DeviceNet requires a power supply of 24VDC (±4%) at a 16A maximum. However, with the use of Thick cable, a maximum of 8A is permitted on a single network segment. This is possible if the power supply is placed at the center point of two network segments, thus supplying 8A to each segment. With the use of thin cable, a maximum of 3A is permitted. As with most Fieldbus networks, grounding of the network and its devices is very important. In DeviceNet, it is required that all cable shields be tied to ground at each device connection. This is done by tying the bare wire of the cable to pin 3 (Shield) of the connector. In addition, the DeviceNet network power supply must be grounded, but only at one point. The V- signal must be connected to Protective Earth Ground at the power supply only. If multiple power supplies are used, only one power supply must have V- connected to Earth Ground. Configuration Guidelines The DeviceNet Network Control Module must be configured in two steps. The first step uses the software to include the module in the PLC. The second step uses the programming software to send a COMMREQ containing the network addressing and data lengths to the NCM. PLC Configuration for the DeviceNet NCM The NCM is configured as part of the overall PLC system. The software is used to specify the following module characteristics: A location. The NCM can be placed in any module location in the system. In the selected location, insert a Communication Carrier. On that Carrier, insert a Generic Communications Module. Settings: Select the Reference Address and Length for an I/O area in each of the 4 reference types: I, AI, Q, and AQ. The length for each must exactly match the total amount of data of that type for all the slave devices controlled by the NCM, including the 64 bits of Communications Status Data provided by the NCM itself. For example, the %I length must equal the total amount of all discrete input data contained in the NCM s input data area, described later in this chapter. And the %AI length must equal the total amount of all analog input data contained in the NCM's input data area. Conversely, the %Q and %AQ lengths must equal the total amount of all discrete and analog output data, respectively. Enter the Module ID: FFFF9808. Wiring: can be used to enter tags for the different data points. Programming Guidelines The second part of configuring an NCM is to send a single COMMREQ from the application program to the NCM. No communications can occur until a valid COMMREQ is received by the NCM. The format of this COMMREQ is shown below. The COMMREQ defines whether the NCM is used as a DeviceNet Master, a DevceNet Slave, or as both simultaneously. It specifies the network address and data rate of the NCM. It also specifies the network address of each device, the I/O mode, and the lengths of each slave s data. The sum of the I/O data for each slave device (including the NCM itself, if the NCM is a Slave) and the 64 bits of Communications Status Data must exactly equal the length for each reference type entered using the software. Configuring the NCM as a DeviceNet Master Only When configuring the NCM as a Master, the COMMREQ must specify: Network address of the Master Network data rate of the Master For each subordinate slave: its network address its I/O mode the amount of I/O data of each type: I, AI, Q, AQ Configuring the NCM as a DeviceNet Slave Only When configuring the NCM as a Slave, the COMMREQ must specify: Network address Network data rate Network mode Amount of I/O data of each type: I, AI, Q, AQ 3

4 Configuring the NCM as a Master and Slave Combined When configuring the NCM as both a DeviceNet Master and Slave, the COMMREQ must provide all of the information for both a Master and Slave. Note that in this combined scenario, the network mode of the slave is ignored as the Master requires the slave to be UCMM-capable. Network address of the Master/Slave. Network data rate of the Master/Slave. For the NCM as a Slave the amount of I/O data of each reference type: I, AI, Q, AQ For each subordinate slave: the network address the I/O mode the amount of I/O data of each type: I, AI, Q, AQ COMMREQ Command Block Word # Contents 1 Length of the data block in words. (Shown below, number of slaves = length): 0 slave = 8, 1 slave =11, 2 slaves = 14, 3 slaves =17,, n slaves = 8 + n * 3. 2 Always 0 3 Status Pointer Memory (8 = R, 10 = AI, 12 = AQ) 4 Status Pointer Offset (0 based) 5-6 Always 0 The slave devices can be entered in the COMMREQ in any order. The NCM checks that the lengths for the four data areas sent in the PLC file match the sum of the lengths sent in the COMMREQ. For convenience, the units of length in the of a Generic Communication Module match the units of length defined in the COMMREQ. Any bit length field must be entered as a multiple of 8 bits, such as 8, 16, 24, etc. COMMREQ Data Block Word # Byte # Contents COMMREQ Command Number = 1000H 2 3 Master Address (0 63) 4 Master Baud Rate (0 = 125k, 1 = 250k, 2 = 500k) 3 5 If NCM is Slave, Length of its I data (in bits, 0 if none) 6 If NCM is Slave, Length of its AI data (in words, 0 if none) 4 7 If NCM is Slave, Length of its Q data (in bits, 0 if none) 8 If NCM is Slave, Length of its AQ data (in words, 0 if none) Reserved for Master Scan Rate, 0 = Scan as fast as possible NCM Slave communication mode (0 = UCMM-capable, 1 = Group 2 Only) This field is only applicable when the NCM is configured as a Slave only. This field is also ignored when the NCM is configured as a Master device. In the Master case, the NCM Slave communication mode is fixed as UCMM-capable Reserved 9 17 First Slave s Address (0 63) 18 First Slave s I/O mode (1 = Poll, 2 = Strobe, 4 = COS w/ack, 0xC = COS w/o Ack) Word # Byte # Contents First Slave s I data length (in bits, 0 if none) 20 First Slave s AI data length (in words, 0 if none) First Slave s Q data length (in bits, 0 if none) 22 First Slave s AQ data length (in words, 0 if none) Second Slave s : : : : : Fortieth Slave s COMMREQ Return Codes The following table lists the possible return codes returned by the COMMREQ upon completion. The return code is written to the Status Pointer location specified by Words 3 and 4 of the COMMREQ Command Block. Return Description Code (Hex) 1 Successful Status - Network operation can proceed 2 NCM has already received a COMMREQ 3 NCM has not been configured via PLC 4 NCM is using the default, i.e. includes 64 bits %I only 5 COMMREQ does not include sufficient data (length must be 8 when configured as a Slave Only) 6 Slave information is incomplete (length must be 11,14,17, etc when configured as a Master) 7 COMMREQ Command number is invalid (must be 0x1000) 8 Reserved fields (Words 7-8) are not 0 as required 9 Total Discrete Input length does not match the module A Total Discrete Output length does not match the module B Total Analog Input length does not match the module C Total Analog Output length does not match the module D NCM network address is invalid (must be 0-63) E NCM network data rate is invalid (must be 0,1,2) F Slave network address is invalid (must be 0-63) 10 Reserved 11 Slave I/O type is invalid (must be 1,2,4, or 0xC) 12 Multiple I/O types are specified for a slave (must be 1,2,4,or 0xC) 13 When configured as a Strobe device, the output data length must be 0 14 When configured as a Strobe device, input data length must 1-8 bytes 15 Duplicate for a slave device. There are two or more entries with the same Slave network address. 16 Master or Slave Discrete Input Length must be divisible by 8 (8,16,24, etc) 17 Master or Slave Discrete Output Length must be divisible by 8 (8,16,24, etc) 18 Unknown Configuration error 19 Headend stopped - aborted 4

5 COMMREQ Example The following example illustrates the COMMREQ function block of the PLC logic and the COMMREQ Command Block, Data Block, and Return Code. IN SYSID TASK COMMREQ Parameters The IN parameter specifies the location of the Command and Data Block. The SYSID parameter specifies the physical slot location of the NCM. In the following example, the NCM is in slot 1 next to the PLC CPU. The TASK parameter specifies the NCM application task to which the COMMREQ is directed. The TASK must always be 0. %R COMM REQ IN SYSID TASK The following example configures the NCM to communicate with 5 slave devices with Slave Addresses 1 through 5. The Master will use address 0 and operate the network at 500Kbits/sec. The Master will not act as a slave device in this. Address Device Description Network I/O Requirements 1 2 input points 2 output points 2 4 input points 4 output points 3 4 input points 4 output points, 2 analog inputs 2 analog outputs 4 2 input points 2 output points 5 1 input point 1 output point FT 2 bytes Input (1 byte of data +1 byte of status) 2 bytes Input (1 byte of data + 1 byte of status) 2 bytes Input (1 byte of data + 1 byte of status) 2 words Input 2 words Output 1 byte Input 1 byte Input The COMMREQ Command Block is placed at %R00001 through %R00006 and the Data Block follows immediately from %R00007 through %R When specifying the input and output lengths for the slave devices, specify the number of bits for discrete data and the number of words for analog data. Hence, 1 byte of input data is specified as 8 bits. And 1 word of output data is specified as 1 word. COMMREQ Area Command Block Data Block Ref Table Value Description %R1 23 Length of Data Block (23 words, %R7-%R29) %R2 0 Not used (must be 0) %R3 8 Reference Table (8=%R) %R4 99 Reference Table Offset %R100 %R5 0 Not used (must be 0) %R6 0 Not used (must be 0) %R7 0x1000 COMMREQ Command %R8 0x200 Master Address = 0 Baud Rate = 500K %R9 0 NCM is not a slave %R10 0 NCM is not a slave %R11 0 Reserved (must be 0) %R12 0 NCM is not a slave %R13 0 Reserved (must be 0) %R14 0 Reserved (must be 0) %R15 0x101 Slave Address 1 %R16 0x10 (16) 16 bits (2 bytes) input %R17 0x08 8 bits (1 byte) output %R18 0x102 Slave Address 2 %R19 0x10 (16) 16 bits (2 bytes) input %R20 0x08 8 bits (1 byte) output %R21 0x103 Slave Address 3 %R22 0x210 2 words input 16 bits (2 bytes) input %R23 0x208 2 words output 8 bits (1 byte) output %R24 0x104 Slave Address 4 %R25 0x08 8 bits (1 byte) input %R26 0x08 8 bits (1 byte) output %R27 0x105 Slave Address 5 %R28 0x08 8 bits (1 byte) output %R29 0x08 8 bits (1 byte) input 5

6 Finally, when specifying the Generic Communication Module for the NCM, it is necessary to add up the I/O requirements of each of the slave devices. Also add the 64 bytes of status for the NCM. Generic Communication Module Reference and Lengths %I 128 (64 for the NCM status ) %Q 40 ( ) %AI 2 %AQ 2 Communications Status Data Format The first 8 bytes (64 bits) of the NCM input data contain the communications status of each of the 64 node addresses. By looking at this data first, the application program in the PLC can determine the validity of each device s input data. MSB 7 6 Byte Byte Byte 2 LSB 0 Byte 0 - Node addresses 0-7 Byte 1 - Node addresses 8-15 Byte 2 - Node addresses Byte 3 - Node addresses Byte 4 - Node addresses Byte 5 - Node addresses Byte 6 - Node addresses Byte 7 - Node addresses Byte 3 Byte 4 Byte 5 MSB Byte Byte LSB 48 Product Revision History Rev Date Description IC200BEM103-MA Oct 2016 EU RoHS compliant module per directive 2011/65/EU dated 8-June No changes to features, performance or compatibility. IC200BEM103-LA Feb 2012 Label change. No changes to IC200BEM103-KA Mar 2011 features, performance or compatibility. IC200BEM103-JA Mar 2010 IC200BEM103-HA Oct 2008 Changed manufacturing location. No changes to features, performance or compatibility. Updated Power Supply OK signal circuitry. IC200BEM103-GA Apr 2005 Improvement to latching mechanism IC200BEM103-EA Apr 2004 Changed to V0 plastic for module housing. IC200BEM103-DA Jan 2004 Improved noise immunity. IC200BEM103-CA Jan 2004 IC200BEM103-BA Nov 2002 ATEX approval for Group 2 Category 3 applications. Improved reporting of Open Input error at higher temperatures. Added parallel RC connection for ODVA compliance. IC200BEM103-AA Aug 1999 Initial product release Each bit represents the status of the device corresponding to that node address. For example, bit 0 in byte 0 represents the status of the device with node address 0. Bit 1 in byte 0 represents the status of the device with node address 1, and so on. When the NCM is configured as a Slave device, the corresponding bit for the NCM address represents the status of the Slave device. When the NCM is configured as a Master only, the corresponding bit is 0. Bit Value Description 0 The device is NOT successfully exchanging I/O data on the DeviceNet network 1 The device is successfully exchanging I/O data on the DeviceNet network Operating Notes/Restrictions 1. The DNCM is limited to communicating with up to 40 slave devices. 2. Because a quick RUN-STOP-RUN transition of the CPU headend may cause the NCM to become confused during, it is suggested that the Configuration COMMREQ to the NCM be delayed at least 4 seconds after first scan General Electric Company. All Rights Reserved. * Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective owners. 6

GE FANUC Parts 1. DeviceNet Network Master/Slave August 2002 GFK-1539A. Quick Start Guide. Product Description. Specifications. Preinstallation Check

GE FANUC Parts 1. DeviceNet Network Master/Slave August 2002 GFK-1539A. Quick Start Guide. Product Description. Specifications. Preinstallation Check Product Description Revision Letter: BA Firmware version: 1.10 Firmware upgrades: DeviceNet Certification: Product Name: None Certificate available upon request. DeviceNet Network Control Module (NCM)

More information

VersaMax* Serial Communications Module

VersaMax* Serial Communications Module Product The VersaMax Serial Communications Module, IC200CMM020, operates as a Modbus RTU Master in a VersaMax I/O Station controlled by a Genius Network Interface Unit or a PROFINET Scanner. Revision Firmware

More information

VersaMax* Analog Input, 16-Bit Thermocouple Module

VersaMax* Analog Input, 16-Bit Thermocouple Module VersaMax* Analog Input, 16-Bit Module Product Description The Analog Input Module is an intelligent module that accepts seven independent thermocouple or millivolt inputs. The module receives power from

More information

GE Fanuc Automation. Series Programmable Controller. Programmable Control Products. DeviceNet Modules

GE Fanuc Automation. Series Programmable Controller. Programmable Control Products. DeviceNet Modules GE Fanuc Automation Programmable Control Products Series 90-30 Programmable Controller DeviceNet Modules GFK-2196 November 2002 Warnings, Cautions, and Notes as Used in this Publication GFL-002 Warning

More information

VersaMax* PROFIBUS Network Interface Unit

VersaMax* PROFIBUS Network Interface Unit December 0 Product Description The PROFIBUS Network Interface Unit (NIU) is a PROFIBUS slave module that acts as controller for a set of I/O modules. Power for module operation is provided by a power supply

More information

VersaMax* IC200BEM003. PROFIBUS Master Module. Ordering Information. Specifications. GFK-2739 April of their respective owners.

VersaMax* IC200BEM003. PROFIBUS Master Module. Ordering Information. Specifications. GFK-2739 April of their respective owners. April 2012 The VersaMax * IC200BEM003 PROFIBUS Master Module allows a VersaMax CPU005, CPUE05 or PROFINET Scanner (PNS) to send and receive data on a PROFIBUS-DP V1 network. The PROFIBUS Master module

More information

GE Intelligent Platforms Programmable Control Products. DeviceNet Modules for PACSystems* RX3i and Series 90*-30 User's Manual

GE Intelligent Platforms Programmable Control Products. DeviceNet Modules for PACSystems* RX3i and Series 90*-30 User's Manual GE Intelligent Platforms Programmable Control Products DeviceNet Modules for PACSystems* RX3i and Series 90*-30 User's Manual GFK-2196B October 2014 g Warnings, Cautions, and Notes as Used in this Publication

More information

Analog Input, 16-Bit Thermocouple Module

Analog Input, 16-Bit Thermocouple Module Analog Input, 16-Bit Module Product Description The Analog Input Module is an intelligent module that accepts seven independent thermocouple or millivolt inputs. The module receives power from the backplane

More information

IMPORTANT PRODUCT INFORMATION

IMPORTANT PRODUCT INFORMATION November 13, 1999 IMPORTANT PRODUCT INFORMATION READ THIS INFORMATION FIRST Product: Control Station Hardware Products (Operator Control Station [OCS], Remote Control Station [RCS]) IC300OCS100, IC300OCS200,

More information

Shown with terminal block Supports diagnostic point fault contacts in the logic program

Shown with terminal block Supports diagnostic point fault contacts in the logic program GFK-2482F PACSystems* RX3i Isolated Analog Input Modules, IC695ALG106-EA, IC695ALG112-EA Product Description Isolated Analog Voltage/Current Input module IC695ALG106 provides 6 isolated input channels.

More information

PACSystems* RX3i IC694ALG232

PACSystems* RX3i IC694ALG232 November 2015 PACSystems* RX3i IC694ALG232 Advanced Diagnostics 16 Channel Input Analog Voltage Module The PACSystems* RX3i 16-Channel Analog Voltage Input module provides 16 single-ended or 8 differential

More information

L5351 DeviceNet Communications Interface

L5351 DeviceNet Communications Interface L5351 DeviceNet Communications Interface Technical Manual HG353798 Issue 2 Copyright SSD Drives, Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or

More information

PACSystems* RX3i IC694ALG233

PACSystems* RX3i IC694ALG233 November 2015 PACSystems* RX3i IC694ALG233 Advanced Diagnostics Analog Current Input Module 16 Channel The PACSystems* RX3i 16-Channel Analog Current Input module provides 16 single-ended input channels.

More information

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction... 3 Product Overview... 3 About DeviceNet... 4 Overview... 4 MPCR DeviceNet Features... 4 Cabling and Drop Line Lengths

More information

PACSystems* RX3i and Series 90*-30 IC694ALG223 and IC693ALG223

PACSystems* RX3i and Series 90*-30 IC694ALG223 and IC693ALG223 May 2014 PACSystems* RX3i and Series 90*-30 IC694ALG223 and IC693ALG223 Analog Current Input Module 16 Channel The PACSystems* RX3i/Series 90* 16-Channel Analog Current Input module provides 16 single-ended

More information

PACSystems* RX3i IC695PBM300

PACSystems* RX3i IC695PBM300 June 2010 PACSystems* RX3i IC695PBM300 PROFIBUS Master Module The PACSystems * RX3i PROFIBUS Master Module, IC695PBM300, allows the RX3i CPU to send and receive data on a PROFIBUS-DP network. The IC695PBM300

More information

GE Fanuc Automation. Generation D Real-Time Operating System. Programmable Control Products. DeviceNet Reference Guide

GE Fanuc Automation. Generation D Real-Time Operating System. Programmable Control Products. DeviceNet Reference Guide GE Fanuc Automation Programmable Control Products Generation D Real-Time Operating System DeviceNet Reference Guide GFK-2208 June 2002 Warnings, Cautions, and Notes as Used in this Publication GFL-002

More information

GE Fanuc IC695CMM004. Rx3i PacSystem

GE Fanuc IC695CMM004. Rx3i PacSystem GE Fanuc IC695CMM004 http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/ic695cmm004 Rx3i PacSystem RX3i serial communications module. Four isolated RS-232/485 port. IC695C IC695CM IC695CMM 919-535-3180

More information

PACSystems* RX3i and Series 90*-30 IC694ALG442-CC and IC693ALG442-EC

PACSystems* RX3i and Series 90*-30 IC694ALG442-CC and IC693ALG442-EC January 214 MODULE K USER SUPPLY IC694ALG442 I1 I2 I3 I4 Q1 Q2 PACSystems* RX3i and Series 9*-3 IC694ALG442-CC and IC693ALG442-EC Analog Module, 4 Inputs/2 Outputs, Current/Voltage Analog Current/Voltage

More information

Current: 0 to 20mA, 4 to 20mA. Voltage: ±10V, 0 to 10V. Isolated +24 VDC Power

Current: 0 to 20mA, 4 to 20mA. Voltage: ±10V, 0 to 10V. Isolated +24 VDC Power September 2013 PACSystems* RX3i Isolated Analog Output Module, IC695ALG808-EA Isolated Analog Voltage/Current Output module IC695ALG808 provides eight configurable voltage or current output channels. Analog

More information

VersaMax Genius Network Interface Unit

VersaMax Genius Network Interface Unit The Genius Network Interface Unit acts as controller for a set of I/O modules. Power for module operation is provided by a power supply that installs directly on the NIU NIU power supply or greater. VersaMax

More information

MPCR Series DeviceNet Technical Manual

MPCR Series DeviceNet Technical Manual MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction...3 Product Overview...3 About DeviceNet...4 Overview...4 MPCR DeviceNet Features...4 Cabling and Drop Line Lengths (as

More information

PACSystems* RX3i IC695CMM002 and IC695CMM004

PACSystems* RX3i IC695CMM002 and IC695CMM004 May 2010 PACSystems* RX3i IC695CMM002 and IC695CMM004 Serial Communications Modules PACSystems* RX3i Serial Communications modules expand the serial communications capabilities of the RX3i system. Serial

More information

PACSystems* RX3i IC695CMM002 and IC695CMM004

PACSystems* RX3i IC695CMM002 and IC695CMM004 April 2010 PACSystems* RX3i IC695CMM002 and IC695CMM004 Serial Communications Modules PACSystems * RX3i Serial Communications modules expand the serial communications capabilities of the RX3i system. Serial

More information

INSTRUCTION SHEET. Eaton Logic Controller DeviceNet Distributed I/O Adapter Module. [Applicable Distributed I/O Adapter Module] ELC-CADNET

INSTRUCTION SHEET. Eaton Logic Controller DeviceNet Distributed I/O Adapter Module. [Applicable Distributed I/O Adapter Module] ELC-CADNET 2010-12-10 5011697801-ECD1 Eaton Logic Controller DeviceNet Distributed I/O Adapter INSTRUCTION SHEET [Applicable Distributed I/O Adapter ] IL05004007E 002-1214120-02 Thank you for choosing the Eaton Logic

More information

GE Intelligent Platforms Programmable Control Products PACSystems* RX3i DNP3 Slave Module IC695EDS001. Quick Start Guide GFK-2912 October 2014

GE Intelligent Platforms Programmable Control Products PACSystems* RX3i DNP3 Slave Module IC695EDS001. Quick Start Guide GFK-2912 October 2014 GE Intelligent Platforms Programmable Control Products PACSystems* RX3i DNP3 Slave Module IC695EDS001 Quick Start Guide GFK-2912 October 2014 g Contents 1. User Features...1 1.1. Overview... 1 1.2. Restart

More information

BridgeWay. PROFIBUS to DeviceNet Gateway User Manual. Part No. AB7605. Publication PUB-AB

BridgeWay. PROFIBUS to DeviceNet Gateway User Manual. Part No. AB7605. Publication PUB-AB BridgeWay PROFIBUS to DeviceNet Gateway User Manual Part No. AB7605 Pyramid Solutions 1850 Research Drive, Suite 300 Troy, Michigan 48083 Phone 248-524-3890 Web www.pyramid-solutions.com Publication PUB-AB7605-005

More information

VLT 5000 DeviceNet and Allen Bradley Control logix 5550

VLT 5000 DeviceNet and Allen Bradley Control logix 5550 Foreword... 2 VLT 5000 DeviceNet card... 2 Configuring the VLT 5000 with RS Networx... 4 I/O communication with RS Logix 5000... 6 Explicit messages with RS Logix 5000... 8 1 Foreword This application

More information

This Datasheet for the IC660BBA026. Block 24/48Vdc Analog Current Source 6 Inputs.

This Datasheet for the IC660BBA026. Block 24/48Vdc Analog Current Source 6 Inputs. This Datasheet for the IC660BBA026 Block 24/48Vdc Analog Current Source 6 Inputs http://www.cimtecautomation.com/parts/p-14421-ic660bba026.aspx Provides the wiring diagrams and installation guidelines

More information

PACSystems* RX3i and Series IC693MDL940 / IC694MDL940

PACSystems* RX3i and Series IC693MDL940 / IC694MDL940 May 2015 PACSystems* RX3i and Series 90-30 IC693MDL940 / IC694MDL940 Output Module, Relay, NO, 2 Amp, 16 Point The Series 90*-30 and PACSystems * MDL940 2 Amp Relay Output module provides 16 normally-open

More information

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block USER S MANUAL FX2N-64DNET DeviceNet Interface Block FX2N-64DNET DeviceNet Interface Block Foreword This manual contains text, diagrams and explanations which will guide the reader in the correct installation

More information

G3 Series DeviceNet TM Technical Manual

G3 Series DeviceNet TM Technical Manual G3 Series DeviceNet TM Technical Manual Table of Contents G3 Series DeviceNet Technical Manual PAGE About DeviceNet... 3 Overview... 3 G3 DeviceNet Features... 3 Cabling and Drop Line Lengths (as defined

More information

This Datasheet for the IC660BBA104. Block 115Vac/125Vdc Analog Current Source 4 Inputs / 2 Outputs

This Datasheet for the IC660BBA104. Block 115Vac/125Vdc Analog Current Source 4 Inputs / 2 Outputs This Datasheet for the IC660BBA104 Block 115Vac/125Vdc Analog Current Source 4 Inputs / 2 Outputs http://www.qualitrol.com/shop/p-14425-ic660bba104.aspx Provides the wiring diagrams and installation guidelines

More information

PACSystems* RX3i Genius* Communications Gateway, IC695GCG001. Quick Start Guide, GFK-2891C August 2016

PACSystems* RX3i Genius* Communications Gateway, IC695GCG001. Quick Start Guide, GFK-2891C August 2016 PACSystems* RX3i Genius* Communications Gateway, IC695GCG001 Quick Start Guide, GFK-2891C August 2016 Contents 1. User Features... 2 1.1. Ethernet Ports... 2 1.2. Genius Serial Bus Connectors... 3 1.3.

More information

CPU Module IC200CPU005

CPU Module IC200CPU005 December 0 GFK-0J PWR PORT PORT RS RS Features Supports up to 6 modules with up to 0 I/O points Can be either autoconfigured or configured from a programmer using configuration software KB of configurable

More information

Instructions to printer DO NOT PRINT THIS PAGE

Instructions to printer DO NOT PRINT THIS PAGE Instructions to printer DO NOT PRINT THIS PAGE This document is intended to be printed in color as a 5.9 x 5.9 inch (150 mm square) booklet with saddle-stitched (stapled) binding. Use high-quality, glossy

More information

PAC BI-DP BIM and 8701-CA-BI Carrier

PAC BI-DP BIM and 8701-CA-BI Carrier June 2013 PAC8000 8507-BI-DP BIM and 8701-CA-BI Carrier PROFIBUS DP Bus Interface Module and Carrier The 8507-BI-DP Bus Interface Module (BIM) provides the communications link between the PAC8000 series

More information

ELC-CODNETM. Effective December Users Manual

ELC-CODNETM. Effective December Users Manual Effective December Users Manual Introduction This is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, excessive humidity, shock and vibration. The enclosure

More information

This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT.

This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT. This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT http://www.qualitrol.com/shop/p-14508-ic670gbi002.aspx Provides the wiring diagrams and installation guidelines for this GE Field Control module.

More information

2002 Series DeviceNet Technical Manual

2002 Series DeviceNet Technical Manual 2002 Series DeviceNet Technical Manual Table of Contents 2002 Series DeviceNet Technical Manual 2002 Introduction...4 Product Overview...4 About DeviceNet...5 Overview...5 2002 DeviceNet Features...5 Cabling

More information

(Controller Area Network)

(Controller Area Network) CAN (Controller Area Network) CAN is open technology supporting multiple applications Chips available today from Intel, Motorola, Philips/Signetics, NEC, Hitachi, Siemens Volumes from multiple industry

More information

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs. This Datasheet for the IC0BBA00 Block /8Vdc Analog Inputs / Outputs. http://www.cimtecautomation.com/parts/p--ic0bba00.aspx Provides the wiring diagrams and installation guidelines for this GE Series 90-0

More information

Allen-Bradley Automation

Allen-Bradley Automation Product Data 1791D CompactBlock I/O for DeviceNet 1791D CompactBlock I/O modules contain I/O circuits, a built-in power supply, and a built-in DeviceNet I/O adapter. CompactBlock I/O modules are ideal

More information

Bus Transmitter Expansion Module (Fiber Media) with built-in switch. PROFINET Slave, Version 2.2 Class A IO-Device

Bus Transmitter Expansion Module (Fiber Media) with built-in switch. PROFINET Slave, Version 2.2 Class A IO-Device Remote I/O Units A Remote I/O Unit connects modules to a host PLC or computer via a variety of networks. This makes it easy to include in the innovative PROFINET interface, as well as Genius, Profibus-DP,

More information

HE-65 CAN-BUS. (DeviceNet-Slave) Technical Information TR - ECE - TI - GB /30/2016

HE-65 CAN-BUS. (DeviceNet-Slave) Technical Information TR - ECE - TI - GB /30/2016 TR - ECE - TI - GB - 0021-01 03/30/2016 HE-65 CAN-BUS (DeviceNet-Slave) Technical Information TR-Electronic GmbH D-78647 Trossingen Eglishalde 6 Tel.: (0049) 07425/228-0 Fax: (0049) 07425/228-33 email:

More information

Preface Digital Electronics Corporation. All rights reserved. Digital Electronics Corporation December LT Type-D User Manual Supplement 1

Preface Digital Electronics Corporation. All rights reserved. Digital Electronics Corporation December LT Type-D User Manual Supplement 1 Preface Thank you for purchasing the Pro-face LogiTouch Type-D DeviceNet master unit. The LogiTouch Type-D (also referred to as the LT Type-D ) allows connection to the DeviceNet Fieldbus to access many

More information

CONTENTS 1. BEFORE USE GENERAL DESCRIPTION POINTS OF CAUTION HARDWARE SPECIFICATIONS... 4

CONTENTS 1. BEFORE USE GENERAL DESCRIPTION POINTS OF CAUTION HARDWARE SPECIFICATIONS... 4 INSTRUCTION MANUAL COMMUNICATION CONTROLLER (DeviceNet) MODEL M2BD CONTENTS 1. BEFORE USE... 2 2. GENERAL DESCRIPTION... 2 3. POINTS OF CAUTION... 3 4. HARDWARE SPECIFICATIONS... 4 4.1. M2BD-x1 (suffix

More information

Installation and maintenance instructions

Installation and maintenance instructions Before installation these instructions must be fully read and understood Table of contents 1. Introduction... 1 2. Operation and storage... 1 3. Distinguish OLD/NEW models... 1 4. Installation... 3 4.1

More information

PACSystems* RX3i CANopen Master Module, IC695CNM001 Quick Start Guide, GFK-2837 March 2013

PACSystems* RX3i CANopen Master Module, IC695CNM001 Quick Start Guide, GFK-2837 March 2013 GE Intelligent Platforms Programmable Control Products PACSystems* RX3i CANopen Master Module, IC695CNM001 Quick Start Guide, GFK-2837 March 2013 Contents 1. User Features... 3 1.1. Overview... 3 1.2.

More information

MRUC-20 Modul-R CAN Bus Network

MRUC-20 Modul-R CAN Bus Network MRUC-20 Modul-R CAN Bus Network BALOGH This manual is based on information available at the time if its publication. Every effort has been made to provide accurate and up-to-date information. This document

More information

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication Remote I/O Scanner Catalog Number 1747-SN Installation Instructions 2 Remote I/O Scanner Important User Information Because of the variety of uses for the products described in this publication, those

More information

WRC-CANX CAN Bus Extender, Version 2 User s Manual

WRC-CANX CAN Bus Extender, Version 2 User s Manual WRC-CANX CAN Bus Extender, Version 2 User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject to change without

More information

I/O EXPANSION MODULES

I/O EXPANSION MODULES 4 Trio Motion Technology 4-2 Hardware Reference Manual General Description of I/O Modules Trio Motion Technology s range of digital and analogue input/output expansion modules are designed to enable simple

More information

PACSystems RX3i and Series IC694MDL916 and IC693MDL916 Output Module, Isolated Relay, N.O., 4 Amp, 16 Point

PACSystems RX3i and Series IC694MDL916 and IC693MDL916 Output Module, Isolated Relay, N.O., 4 Amp, 16 Point January 2010 PACSystems RX3i and Series 90-30 IC694MDL916 and IC693MDL916 Output Module, Isolated Relay, N.O., 4 Amp, 16 Point 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TB IC694MDL916 Q1 Q2 Q3 Q4 Q5 Q6 Q7

More information

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs. This Datasheet for the IC0BBA00 Block /8Vdc Analog Inputs / Outputs. http://www.qualitrol.com/shop/p--ic0bba00.aspx Provides the wiring diagrams and installation guidelines for this GE Series 90-0 module.

More information

GE Fanuc Automation Programmable Control Products. PACSystems RX3i. Serial Communications Modules. User s Manual, GFK-2460A.

GE Fanuc Automation Programmable Control Products. PACSystems RX3i. Serial Communications Modules. User s Manual, GFK-2460A. GE Fanuc Automation Programmable Control Products PACSystems RX3i Serial Communications Modules User s Manual, GFK-2460A March 2007 Warnings, Cautions, and Notes as Used in this Publication GFL-002 Warning

More information

Non-Isolated Analog Output Module with HART Communications, IC695ALG728-DC Non-Isolated Analog Output Modules, IC695ALG704-DC, IC695ALG708-DC

Non-Isolated Analog Output Module with HART Communications, IC695ALG728-DC Non-Isolated Analog Output Modules, IC695ALG704-DC, IC695ALG708-DC May 2017 PACSystems* RX3i Non-Isolated Analog Output Module with HART Communications, IC695ALG728-DC Non-Isolated Analog Output Modules, IC695ALG704-DC, IC695ALG708-DC Non-Isolated Analog Voltage/Current

More information

1782-JDA8 SmartMux-Lite / DeviceNet User s Manual

1782-JDA8 SmartMux-Lite / DeviceNet User s Manual 1782-JDA8 SmartMux-Lite / DeviceNet User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject to change without

More information

Operation Manual. Fieldbus system EX510-GDN1. DeviceNet Compatible GW unit

Operation Manual. Fieldbus system EX510-GDN1. DeviceNet Compatible GW unit Fieldbus system DeviceNet Compatible GW unit Operation Manual EX50-GDN URL http://www.smcworld.com Akihabara UDX 5F, --, Sotokanda, Chiyoda-ku, Tokyo 0-00, JAPAN Phone: +8-507-89 Fax: +8-598-56 Note: Specifications

More information

Remote I/O Scanner. Installation Instructions. (Catalog Number 1747-SN)

Remote I/O Scanner. Installation Instructions. (Catalog Number 1747-SN) Installation Instructions Remote I/O Scanner (Catalog Number 1747-SN) Inside...page Hazardous Location Considerations... 2 Environnements dangereux... 2 Overview... 3 Hardware Features... 4 Required Tools

More information

1782-JDC DeviceNet/Serial Gateway User s Manual

1782-JDC DeviceNet/Serial Gateway User s Manual 1782-JDC DeviceNet/Serial Gateway User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject to change without

More information

Series SD6 with DeviceNet (Addendum)

Series SD6 with DeviceNet (Addendum) Series SD6 with (Addendum) Watlow s Series SD6 with offers excellent control and application flexibly in a 1/16th DIN panel mount package. The Series SD6 with has been successfully tested for use with

More information

PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide

PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide GE Automation & Controls Programmable Control Products PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide GFK-3012 April 2017 g Contents

More information

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison DNETEXT-C CAN Bus Extender, Version 3 User s Manual Brad Harrison Although every effort has been made to insure the accuracy of this document, all information is subject to change without notice. Woodhead

More information

This Datasheet for the IC660BBD110. Block 115Vac Input 16 Circuits.

This Datasheet for the IC660BBD110. Block 115Vac Input 16 Circuits. This Datasheet for the IC660BBD110 Block 115Vac Input 16 Circuits http://www.cimtecautomation.com/parts/p-14435-ic660bbd110.aspx Provides the wiring diagrams and installation guidelines for this GE Series

More information

This Datasheet for the IC660BBR100. Block Relay Output Normally Closed 16 Circuits.

This Datasheet for the IC660BBR100. Block Relay Output Normally Closed 16 Circuits. This Datasheet for the IC660BB00 Block elay Output ormally Closed 6 Circuits http://www.qualitrol.com/shop/p-7-ic660bbr00.aspx Provides the wiring diagrams and installation guidelines for this GE Series

More information

SmartRail I/O Ethernet Base HE599ETX300

SmartRail I/O Ethernet Base HE599ETX300 MAN--EN Specifications / Installation SmartRail I/O Ethernet Base HE599ETX INTRODUCTION SmartRail I/O is a real-time, modular I/O system that supports a variety of Ethernet and Fieldbus Communication architectures.

More information

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for Version 1.0 16.05.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling MATERIAL HANDLING MANIFOLDS WITH DeviceNet INTERFACE 01348(N or G) MH** -- Material Handling 01351(N or G) MH** -- Material Handling Note: N = NPT ports G = BSPP ports SOL 14 SOL 12 Station #3 SOL 14 SOL

More information

This Datasheet for the IC697BEM721. I/O Link Interface Module for the Series

This Datasheet for the IC697BEM721. I/O Link Interface Module for the Series This Datasheet for the for the Series 90-70. http://www.cimtecautomation.com/parts/p-14754-ic697bem721.aspx Provides the wiring diagrams and installation guidelines for this GE Series 90-30 module. For

More information

GE Fanuc IC695ALG708. Rx3i PacSystem

GE Fanuc IC695ALG708. Rx3i PacSystem GE Fanuc IC695ALG708 http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/ic695alg708 Rx3i PacSystem Analog Output Module, 8 channels,that is configurable IC695A IC695AL IC695ALG 919-535-3180 sales@pdfsupply.com

More information

RSTI-EP Slice I/O. PROFINET Scanner EPXPNS001. GFK-2965C November 2017

RSTI-EP Slice I/O. PROFINET Scanner EPXPNS001. GFK-2965C November 2017 November 2017 Ethernet Ports PWR, SF, BF, MT, LINK 1, ACT 1, LINK 2, and ACT 2 LEDs Door for Micro USB Port PROFINET Scanner Power Supply LED RSTI-EP Slice I/O PROFINET Scanner The PROFINET Scanner is

More information

PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG

PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG September 2017 PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG Serial Communications Modules PACSystems* RX3i Serial Communications modules expand

More information

R7D-RR8 BEFORE USE... POINTS OF CAUTION. INSTRUCTION MANUAL REMOTE CONTROL RELAY CONTROL MODULE, 8 points MODEL. (DeviceNet)

R7D-RR8 BEFORE USE... POINTS OF CAUTION. INSTRUCTION MANUAL REMOTE CONTROL RELAY CONTROL MODULE, 8 points MODEL. (DeviceNet) INSTRUCTION MANUAL REMOTE CONTROL RELAY CONTROL MODULE, points (DeviceNet) MODEL BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined

More information

RSTI-EP Slice I/O Digital Input Modules EP-1214, EP-1218, EP-1318, EP-125F, EP-1804 Digital Input Module with Time Stamp EP-12F4

RSTI-EP Slice I/O Digital Input Modules EP-1214, EP-1218, EP-1318, EP-125F, EP-1804 Digital Input Module with Time Stamp EP-12F4 GFK-2975C August 2016 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Digital Input Module RSTI-EP Slice I/O Digital Input Modules EP-1214, EP-1218, EP-1318, EP-125F, EP-1804

More information

Flex Series User Guide

Flex Series User Guide User Programmable Current 4..20mA Digital RS485 Dual & Single Axis Up to 360º 2016 Flex Series User Guide Sensor Installation, Wiring, Flexware App Instructions Page 1 of 33 Page 2 of 33 Table of Contents

More information

Diagnostics (Logical) Diagnostics (Physical)

Diagnostics (Logical) Diagnostics (Physical) Enclosure Mounted Input/Output Stations In-Cabinet I/O IP 20 Protection Ideal for Retrofits Automatic Baud Rate Sensing FDN20-4S-4XSG FDN20-4S-4XSG-E* FDN20-4S-4XSG-DIN* * Not UL Electrical Operating Current:

More information

SMARTLINX INTERFACE MODULE

SMARTLINX INTERFACE MODULE SMARTLINX INTERFACE MODULE FOR DEVICE NET Instruction Manual PL-583 April 2001 R 33455830 Rev. 1.1 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others,

More information

PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide

PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide GE Automation & Controls Programmable Control Products PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide GFK-3012A June 2017 g Contents

More information

RSTI-EP Slice I/O. EtherCAT Network Adapter Module EPXETC001. GFK-2967B Septembery 2016

RSTI-EP Slice I/O. EtherCAT Network Adapter Module EPXETC001. GFK-2967B Septembery 2016 Septembery 2016 RSTI-EP Slice I/O EtherCAT Network Adapter Module PWR, BF, MT, L/A IN, L/A OUT, RUN, and ERROR LEDs Ethernet Ports Door for Micro USB Port EtherCAT Network Adapter Power Supply LED The

More information

FieldServer FS DeviceNet Master Adapter Driver

FieldServer FS DeviceNet Master Adapter Driver FieldServer FS-8700-114 DeviceNet Master Adapter Driver Driver Manual (Supplement to the FieldServer Instruction Manual) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after March 2017.

More information

CDN127 DeviceNet SPECIFICATIONS

CDN127 DeviceNet SPECIFICATIONS CDN127 DeviceNet SPECIFICATIONS Revision 1.6 04/01/01 Table of Contents Revision History...v Overview...1 Device Description...1 Switches...1 Indicators...2 Internal Jumpers...3 DeviceNet Interface...3

More information

CDN572-5 DEVICENET SPECIFICATIONS

CDN572-5 DEVICENET SPECIFICATIONS CDN572-5 DEVICENET SPECIFICATIONS TABLE OF CONTENTS Revision History...v CDN572-5 Overview...1 Hardware...1 Processor...1 DeviceNet Interface...1 Power Distribution...2 Switches and Indicators...2 MacID/BaudRate...3

More information

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO DeviceNet/PROFIBUS-DP Adapter - User Manual REV 4.0 SiboTech Automation Co., Ltd. Technical Support: +86-21-5102 8348 E-mail:gt@sibotech.net Table of Contents 1 ABOUT THIS DOCUMENT...2 1.1 GENERAL... 2

More information

This Datasheet is for the IC693CBL300. I/O Bus Expansion Cables.

This Datasheet is for the IC693CBL300. I/O Bus Expansion Cables. This Datasheet is for the IC6CBL00 I/O Bus Expansion Cables http://www.qualitrol.com/shop/p-45-ic6cbl00.aspx Provides the wiring diagrams and installation guidelines for this GE Series 0-0 module. For

More information

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018 September 2018 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Analog Input Module RSTI-EP Slice I/O Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664,

More information

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for Version 1.0 5.02.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

VersaMax IP Input Module

VersaMax IP Input Module Module is used to accept digital input signals. Module Specifications Housing dimensions (width x height x depth) Connection style Operating temperature Storage temperature Operating/storage humidity 60mm

More information

PACSystems* RX3i. RX3i Genius Communications Gateway IC695GCG001-DF. Important Product Information. Release History. Firmware Updates/Upgrades

PACSystems* RX3i. RX3i Genius Communications Gateway IC695GCG001-DF. Important Product Information. Release History. Firmware Updates/Upgrades GFK-2900G April 2018 PACSystems* RX3i RX3i Genius Communications Gateway IC695GCG001-DF Important Product Information General Product Documentation Product updated to resolve 3 issues: GCG configured at

More information

This Datasheet for the IC660BBD025. Block 5/12/24Vdc Sink I/O 32 Circuits.

This Datasheet for the IC660BBD025. Block 5/12/24Vdc Sink I/O 32 Circuits. This Datasheet for the IC0BBD02 Block /12/24Vdc Sink I/O 32 Circuits http://www.qualitrol.com/shop/p-14433-ic0bbd02.aspx Provides the wiring diagrams and installation guidelines for this GE Series 0-30

More information

Installation and Setup

Installation and Setup Installation and Setup 1 In This Chapter Installing the H PBC The Profibus Network Configuring the Controller Installing the H PBC Setting the Node Address Setting the Node Address Profibus DP is usually

More information

USER MANUAL 3170-INTB

USER MANUAL 3170-INTB USER MANUAL ProSoft Technology, Inc. Phone: 661-664-7208 9801 Camino Media Fax: 661-664-7233 Suite 105 E-mail: prosoft@prosoft-technology.com Bakersfield, CA 93311 http://www.prosoft-technology.com About

More information

This Datasheet for the IC660BBA101. Block 115Vac/125Vdc RTD Input 6 Channels.

This Datasheet for the IC660BBA101. Block 115Vac/125Vdc RTD Input 6 Channels. This Datasheet for the IC660BBA101 Block 115Vac/125Vdc RTD Input 6 Channels http://www.qualitrol.com/shop/p-14423-ic660bba101.aspx Provides the wiring diagrams and installation guidelines for this GE Series

More information

High Performance FieldBus cards

High Performance FieldBus cards Profibus card VLT 5000/6000... 2 Interbus card VLT 5000... 4 DeviceNet card VLT 5000... 6 Modbus+ card VLT 5000... 8 Lonworks cards VLT 5000/6000 Free Topology... 10 Lonworks cards VLT 5000/6000 78 kbps

More information

DeviceNet - CIP on CAN Technology

DeviceNet - CIP on CAN Technology The CIP Advantage Technology Overview Series DeviceNet - CIP on CAN Technology DeviceNet has been solving manufacturing automation applications since the mid-1990's, and today boasts an installed base

More information

PACSystems* RX3i. RX3i Genius Communications Gateway IC695GCG001-DE. Important Product Information. Release History. Firmware Updates/Upgrades

PACSystems* RX3i. RX3i Genius Communications Gateway IC695GCG001-DE. Important Product Information. Release History. Firmware Updates/Upgrades GFK-2900F January 2018 PACSystems* RX3i RX3i Genius Communications Gateway IC695GCG001-DE Important Product Information General Product Documentation Product updated to add support for Field Control, the

More information

GE Intelligent Platforms

GE Intelligent Platforms GE Intelligent Platforms Programmable Control Products PACSystems* RX3i IEC 61850 Ethernet Communication Module, IC695ECM850 Quick Start Guide, GFK-2851 February 2014 g Contents 1. User Features... 3 1.1.

More information

CDN067 DEVICENET SPECIFICATIONS

CDN067 DEVICENET SPECIFICATIONS CDN067 DEVICENET SPECIFICATIONS Revision History Revision Description Date 1.0 Initial Release Upgrade to DNet Rev. 2.0 07/20/98 Added support for status byte and status clear in poll Disallowed changing

More information

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. MCD Modbus Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE Order Code: 175G9000 1. Important User Information Observe all necessary safety precautions when controlling

More information

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1 YASKAWA Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1 YASKAWA MANUAL NO. SIBP C730600 01B Copyright 2004 YASKAWA ELECTRIC CORPORATION All rights reserved.

More information