1 Specifications/Instructions Infilex AC Air Handling Unit Controller for NC-bus Communication General Infilex AC Model WY5117C1XXX is a DDC controller for AHU. It is installed in a small space such as an AHU control panel. Infilex AC is equipped with inputs and outputs suitable for AHU control, and its software is freely editable in response to the applications. Operator interface and room user terminal are connectable to Infilex AC, supporting you in various situations to operate Infilex AC. Infilex AC also is networked with our BMS via our proprietary protocol NC-bus. Infilex AC sends operating status to the BMS and performs operating management in accordance with the commands sent from the BMS in order for you to integrally control and manage a whole building. The time scheduling function of Infilex AC, on the other hand, enables autonomous-distributed control. AHU: Air handling unit BMS: Building management system DDC: Direct digital control Features Compact design: Small sized body fits inside a control panel of a compact AHU. Wide range of input/output (I/O) combinations: Model with the I/O combination best-suitable for the air conditioning controls you desire, such as outdoor air cooling control, humidification, etc. is selectable. Increase in I/O points: An I/O module is added to Model WY5117C140X for increasing the I/O points. Operator interface (Operator Panel): Operator Panel (panel mount type/integral type) connected to Infilex AC allows you to change the settings of Infilex AC without accessing Infilex AC from the BMS. Room user terminals: User terminal (Neopanel or Neoplate) is connectable to Infilex AC, enabling the room occupants to turn on/off air conditioning unit and change temperature setting. Cooperation with BMS: Infilex AC is networked with our BMS to centrally monitor and control AHU. Autonomous distributed control: Even if a trouble occurs in the BMS, Infilex AC individually performs backup operation to distribute potential risks caused by malfunction of the BMS. Installation: Screwless push-in terminals for I/O reduce wiring workload. Additionally, either DIN rail mount or screw mount is selectable. CE Marking certified product: Infilex AC Model WY5117C conforms to all the applicable standards of CE Marking. DIN: Deutsches Institut fur Normung (German Institute for Standardization) Azbil Corporation All Rights Reserved.

2 Safety Instructions Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for ready reference. Usage Restrictions This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact our sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators. Caution for instrumentation design Considering unexpected failures and contingencies, be sure to design and check safety of the system and equipments. Warnings and Cautions WARNING CAUTION Alerts users that improper handling may cause death or serious injury. Alerts users that improper handling may cause minor injury or material loss. Signs Alerts users possible hazardous conditions caused by erroneous operation or erroneous use. The symbol inside indicates the specific type of danger. (For example, the sign on the left warns of the risk of electric shock.) Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside graphically indicates the prohibited action. (For example, the sign on the left notifies that disassembly is prohibited.) Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside graphically indicates the actual action to be carried out. (For example, the sign on the left indicates general instructions.) WARNING Be sure to ground the product with ground resistance of less than 100 Ω. Improper grounding might cause electric shock or malfunction. Detach the terminal cover only when wiring the product. Before detaching the terminal cover, be sure to turn off the power to the product and all the connected devices. After wiring, be sure to reattach the terminal cover. Failure to do so might cause electric shock. Before wiring and maintenance, be sure to turn off the power to the product. Failure to do so might cause electric shock. Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel) Failure to do so might cause electric shock. CAUTION (1/2) Install the product in a location that satisfies the operating conditions (temperature, humidity, power, vibration, shock, mounting direction, atmospheric condition, etc.) as listed in the specifications and use the product within the operating ranges as listed in the specifications. Failure to do so might cause fire or device failure. Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards. All wiring must comply with applicable codes and ordinances. Connect the cables to the product power supply terminals with the terminal lugs or an equivalent method to assure permanent connection. To connect the wires to the screw terminals, use crimp terminal lugs with insulation. Failure to do so might cause short circuit or electric shock. 2

3 CAUTION (2/2) Take anti-lightening measures based on regional and building characteristics. Lightening might cause fire or critical damage to the products without the anti-lightening measures. Take anti-noise measures if the product is installed in a location near electric noise sources. Failure to do so might cause malfunction or device failure. Be sure to provide a circuit breaker for the power to the product as the product does not have a power switch. Firmly tighten the terminal screws. Insufficient tightening of the terminal screws might cause fire or overheating. For wiring, strip each wire insulation for the length specified in this manual. If the strip length is longer than the specified, the stripped part of the wires will be exposed, causing electric shock or short circuit between adjacent terminals. If it is shorter, the stripped part will not contact the connector. Do not use unused/spare terminals on the product as relay terminals. Doing so might cause malfunction. Do not block the ventilation holes of this product. (Be sure to peel off the protective sheet after installation and wiring). Doing so might cause device failure. If more than the rated power voltage is applied to the product, replace the product with new one for your safety. Failure to do so might cause fire. Do not disassemble the product. Doing so might cause device failure. When replacing batteries, read the instructions hereinafter and correctly replace the product batteries. Failure to do so might cause overheating, burst, or leakage of the batteries. Dispose of the used batteries in accordance with your local regulations. Do not throw them in fire or in general garbage. Doing so might cause burst or ignition. Dispose of this product as industrial waste in accordance with your local regulations. Do not reuse all or a part of this product. 3

4 System Configurations For BMS and devices that are compatible to Infilex AC, ask our salesperson. BACnet IP BMS Client PC NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.) Infilex AC Model WY5117C Infilex AC Model WY5117C Infilex AC Model WY5117C Infilex AC Model WY5117C UT module Model RY5001Q UT module Model RY5001Q Operator Panel (Integral type) Model RY5001Q Operator Panel (Integral type) Model RY5001Q Operator Panel (Panel mount type) Model QY5100 Neoplate, Model QY7290 Operator Panel (Panel mount type) Model QY5100 Neopanel Model QY7205 Neopanel Model QY7205 Neoplate Model QY7290 Infilex ZM Model WY5122 Infilex GC Model WY5111 Infilex GD Model WY5110 Infilex ZM Model WY5122 Other connectable devices to NC-bus: DIF-II/Energy meter SC-bus (Max. 50 units and 1000 m) SC-bus (Max. 50 units and 1000 m) Infilex FC Model WY5205 Infilex FC Model WY5205 Infilex FC Model WY5205 Infilex FC Model WY5205 Infilex VC Model WY5206 Infilex VC Model WY5206 Infilex VC Model WY5206 Temperature sensor Neoplate Model QY7290 Temperature sensor Neopanel Model QY7205 Neopanel Model QY7205 Neopanel Model QY7205 Temperature sensor Temperature sensor Neopanel Model QY7205 Neopanel Model QY7205 Figure 1. System configuration example BMS: Building management system DIF-II: DGP (Data Gathering Panel) line interface-ii 4

5 Model Numbers Base model Temperature Power I/O Description number input WY5117 Infilex AC for NC-bus communication C 24 V AC 1 Fixed 1 Temperature input: 2 pts, voltage input: 2 pts, digital input: 4 pts, voltage output: 2 pts, relay output: 3 pts, 1 UT module or Operator Panel (integral type) connectable* 1, * 2 2 Temperature input: 2 pts, voltage input: 2 pts, digital input: 4 pts, voltage output: 3 pts, relay output: 4 pts, 1 UT module or Operator Panel (integral type) connectable* 1, * 2 3 Temperature input: 2 pts, voltage input: 2 pts, digital input: 6 pts, voltage output: 5 pts, relay output: 5 pts, 1 UT module or Operator Panel (integral type) connectable* 1, * 2 4 Temperature input: 2 pts, voltage input: 2 pts, digital input: 8 pts, voltage output: 6 pts, relay output: 6 pts, 1 UT module or Operator Panel (integral type) + 1 I/O module connectable* 1, * 2 00 RTD (Pt100) 0K RTD (Pt1000) Notes: *1 UT module, Operator Panel (integral type), and I/O module are optional. Separately order if needed. *2 Regarding I/O modules, UT module, and the integral type Operator Panel that can be assembled with Infilex AC basic unit, refer to AB-6527 Specifications/Instructions of Model RY50XX. Parts for Installation (Optional) Part number Screw tab DIN rail mounting bracket Description 5

6 Specifications Item Specification Power supply Rated voltage 24 V AC ± 15 %, 50 Hz/60 Hz Power shutdown Max V AC detection Power consumption 15 VA Leakage current 1 ma or less Environmental Rated operating Ambient temperature 0 C to 50 C conditions conditions Ambient humidity 10 %RH to 90 %RH (non-condensing) Altitude Max. 2,000 m Vibration Max. 5.9 m/s 2 (10 Hz to 150 Hz) Transport/ Ambient temperature -20 C to 60 C storage Ambient humidity 5 %RH to 95 %RH (non-condensing) conditions Vibration for storage Max. 5.9 m/s 2 (10 Hz to 150 Hz) Vibration for transport Max. 9.8 m/s 2 (10 Hz to 150 Hz) Installation Inside of control panel LED indication After Infilex AC is turned on, the LED operates as follows in response to the (Operating status LED) Infilex AC operating status. Power ON ON for several tens of seconds Power OFF OFF Major failure or initializing ON Minor failure Repetition of 1-second ON, 0.25-second OFF, 0.25-seccond ON, and 0.25-second OFF Engineering mode Repetition of 0.25-sec ON, 0.25-second OFF, 0.25-second ON, and 1.25-second OFF Data transmitting Repetition of 1-second ON and 1-second OFF NC-bus error Repetition of 0.25-second ON and 0.25-second OFF Backup in the event of power failure RAM* 1, RTC* 2 Lithium battery backup Data file Non-volatile memory (flash memory) backup Input Digital input Current 5 ma typ. Voltage 24 V DC typ. Connectable output Dry contact or open collector Allowable contact Max. 100 Ω ON-resistance Allowable contact Min. 100 kω OFF-resistance Allowable ON residual Max. 1 V DC voltage Temperature Input signal RTD (Pt100 (100 Ω/0 C), Pt1000 (1000 Ω/0 C)) input Measuring range -20 C to 80 C Voltage input Input voltage range 1 V DC to 5 V DC Input impedance 500 kω Output Relay output Output method Relay output N.O. contact (N.O. contacts share the same common line.) (N.O. contact) Contact rating Max. 24 V AC, 0.5 A (Inductive load: cosø = 0.4 or more) Max. 24 V DC, 0.5 A Minimum applicable load 5 V DC, 10 ma DC Relay output (N.O./N.C. Output method Relay output, N.O./N.C. contact (N.O./N.C. contact does not share the common line with N.O contact.) contact) Contact rating Max. 24 V AC, 0.5 A (Inductive load: cosø = 0.4 or more) Max. 24 V DC, 0.5 A Minimum applicable load 5 V DC, 10 ma DC Voltage output Output voltage range 2 V DC to 10 V DC / 0 V DC to 10 V DC Min. load resistance Min. 10 kω Communications NC-bus Transmission system Current transmission Transmission speed 4800 bps Transmission distance 500 m Weight 500 g Material (housing), color Modified PPE, light gray Terminal connection Power supply, ground M3 screw terminals (7.62 mm pitch between terminals) NC-bus communication, I/O Screwless push-in terminals PPE: Polyphenylene ether RAM: Random-access memory RTC: Real-time clock Notes: *1 RAM: A form of data storage that can be accessed directly in any random order. Stored data is erased when the power is turned off. RAM of Infilex AC is backed up by a lithium battery. *2 RTC: A computer clock that keeps track of the current time. RTC of Infilex AC is backed up by a lithium battery. (1/2) 6

7 Wire Specifications Item Wiring Wiring length* 1 Condition Power supply* 2 JIS IV2.0 mm 2 or JIS CVV 2.0 mm 2 or greater Ground* 2 JIS IV 2.0 mm 2 or JIS CVV 2.0 mm 2 or greater Ground resistance: Max. 100 Ω Digital input* 3 JIS IV, JIS CVV, or KPEV 0.9 mm 2, 1.25 mm 2 50 m Relay output* 3 JIS IV, JIS CVV, or KPEV 1.25 mm 2 50 m Max. 30 V AC/DC Temperature input* 3, 4 JIS IV, JIS CVV, or KPEV 1.25 mm 2 50 m Voltage input* 3 JIS IV, JIS CVV, or KPEV 0.9 mm 2, 1.25 mm 2 50 m Voltage output* 3 JCS CVV-S 1.25 mm 2 20 m Inverter output JIS IV, JIS CVV, or KPEV 1.25 mm 2 10 m Valve/damper JIS IV, JIS CVV, or KPEV 2.0 mm 2 20 m (for the system common wiring* 5 ) (from the relay terminal block) JIS IV, JIS CVV, or KPEV 1.25 mm 2 20 m Valve/damper Communication JCS IPEV-S 0.9 mm m (NC-bus)* 3 JCS: Japanese Electric Wire & Cable Makers' Association Standard JIS: Japanese Industrial Standards KPEV: Cable standard provided by Furukawa Electric Co., Ltd. Notes: *1 Wiring length shown above is the total wiring length from Infilex AC to a device in connection, including the wiring to and from an external terminal block. *2 Power supply and ground wires are connected to the M3 screw terminals. Crimp the terminal lugs on the wire ends. *3 Communication and input/output wires are connected to the screwless push-in terminals. Strip the wire sheath and connect the wires. Sheath strip length: 8 mm (Pin terminal cannot be used.) *4 RTD (Pt1000) temperature input is two-wire. Take the measuring error into account because the wire resistance causes measuring error. For instance, 1.25 mm 2 size wire causes approx. 0.1 C measuring error every 10 m. Correct the measuring error by setting Infilex AC. *5 When the valve/damper is connected for the system common wiring, the valve/damper operating current flows through the common line. Hence, the specification is as shown above. For a 20 m long IV 1.25 mm 2 cable, 4-wire connection is necessary to prevent the operating current from flowing through the common line. 7

8 Terminals Layout 24 V AC S S NC-bus I/O connection example* 1 Fan ON/OFF Fan ON/OFF Humidifier Outdoor air damper Relay output (for momentary only) (24 V AC/DC) Relay output (for momentary/maintained) (24 V AC/DC) Digital input Current: 5 ma Voltage: 24 V DC applied from Infilex AC I/O connection example* 1 Supply air fan status Supply air fan alarm Return air fan status Return air fan alarm Filter alarm Water-leak alarm General-purpose input General-purpose input Return air temperature Supply air temperature Return air humidity General-purpose voltage input Temperature input* 2 (-20 to 80 C) Voltage input (1 to 5 V) Voltage output (2 to 10 V/ 0 to 10 V) Hot water valve or Chilled/hot water valve Chilled water valve Outdoor air damper or Exhaust air damper Return air damper Fan inverter Fan inverter or Proportional humidifying Notes: *1 Other items that satisfy input/output specifications of Infilex AC are connectable as well. For available inputs and outputs of each Infilex AC model, refer to Table 1. *2 RTD (Pt100) temperature input is three-wire. Connect Pt100 temperature sensor to the terminals or RTD (Pt1000) temperature input is two-wire. Connect Pt1000 temperature sensor to the terminals 13 and 14 or 16 and 17. Figure 2. Terminals layout with I/O connection example Table 1. Applicable inputs/outputs for each model number Model number AI1 to AO1, DI1 to DI5, DI7, DO1, AO3 AO4 AO5 AO6 AI4 AO2 DI4 DI6 DI8 DO2 DO3 DO4 DO5 DO6 WY5117C110X WY5117C120X WY5117C130X WY5117C140X* Note: * For an I/O module that can be added to Model WY5117C1400, refer to AB-6527 Specifications/Instructions of Model RY50XX. 8

9 Dimensions Figure 3. Dimensions (mm) Parts Identifications Operating status LED Table 2. Indication and operation of the operating status LED LED indication LED operation Data transmitting Repetition of 1-second ON and 1-second OFF NC-bus error Repetition of 0.25-second ON and 0.25-second OFF Major failure / ON initializing Minor failure Repetition of 1-second ON, 0.25-second OFF, 0.25-second ON, and 0.25-second OFF Engineering mode Repetition of 0.25-second ON, 0.25-second OFF, 0.25-second ON, and second OFF Power OFF OFF Battery holder Figure 4. Parts identifications Data Setter connector (female) S1 switch Do not press the S1 switch. DIN rail mounting hook 9

10 Installation CAUTION Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards. Installation locations Install Infilex AC in a control panel. Do not mount Infilex AC under the conditions of high temperature and humidity. Leave at least 35 mm clearance between the top/bottom surface of Infilex AC and other devices. Mounting position Do not mount Infilex AC with the body tilted. Always mount it in the positions as shown in the figure below. No other mounting positions are allowed. Upright Do not tilt. Do not tilt. Vertical (upright) direction Sideway (allowed only when I/O module, UT module, or integral type Operator Panel is NOT assembled with the basic unit) Power supply terminals located on the lower corner of the front face Note: * Do not mount the Infilex AC basic unit sideway with the power supply terminals located upper corner, lying on its back, or lying face down. Figure 5 Mounting positions Vertical (upright) direction 10

11 DIN rail mount The following figure shows the mounting dimensions of Infilex AC on DIN rail. The width may vary depending on how many modules (I/O module, UT module, and integral type Operator Panel)* 1 are assembled with the Infilex AC basic unit. Width of Infilex AC = 60 mm* mm* 3 x n (quantity) Notes: *1 Regarding I/O modules, UT module, and the integral type Operator Panel that can be assembled with Infilex AC basic unit, refer to AB-6527 Specifications/Instructions of Model RY50XX. *2 Width of Infilex AC basic unit *3 Width of I/O module, UT module, or integral type Operator Panel Hatched area in the figure below shows the maintenance clearance n (60) (122.5)* 1 (132.5)* Infilex AC basic unit Cable duct *2 Infilex AC Cable duct Cable DIN rail holder duct DIN rail mounting brackets for bilateral sides (60) Part No Notes: *1 Pitch between upper/lower cable duct and the DIN rail. *2 Up to two modules (I/O module and/or UT module/integral type Operator Panel) can be assembled with the basic unit. *3 DIN rail position is shifted 5 mm downward from the center of Infilex AC. 5* 3 Figure 6. Mounting dimensions (mm): DIN rail mount Mount and fix Infilex AC on DIN rail so that it does not fall from the DIN rail. Check that the DIN rail holders of each module are pushed up and fixed on the DIN rail. Fasten the bilateral sides of Infilex AC with two DIN rail mounting brackets (Part No , separate order is required). (45) 35 (45) Cable duct DIN rail Hook Infilex AC 11

12 Direct screw mount The following figure shows the mounting dimensions of Infilex AC mounted directly on a mounting surface with screws. The width may vary depending on how many modules (I/O module, UT module, and integral type Operator Panel)* 1 are assembled with the Infilex AC basic unit. Width of Infilex AC = 60 mm* mm* 3 x n (quantity) Notes: *1 Regarding I/O modules, UT module, and the integral type Operator Panel that can be assembled with Infilex AC basic unit, refer to AB-6527 Specifications/Instructions of Model RY50XX. *2 Width of Infilex AC basic unit *3 Width of I/O module, UT module, or integral type Operator Panel Hatched area in the figure below shows the maintenance clearance. Screw tab Part No n 20 * See Note. Screw Infilex AC 7 15 Insert. Rear side To attach the screw tab, insert the screw tab into the slit provided on the rear side of Infilex AC DIN rail holder Pull down the DIN rail Note: * Up to two modules (I/O module and/or UT module/integral type Operator Panel) can be assembled with the basic unit. Figure 7. Mounting dimensions (mm): Direct screw mount To mount Infilex AC with screws, the screw tabs (Part No , with separate order required) are required. Mount and fix Infilex AC on the mounting surface with M4 8 screws. (One screw tab and two screws for one basic unit/module are required.) 12

13 Wiring WARNING Detach the terminal cover only when wiring the product. Before detaching the terminal cover, be sure to turn off the power to the product and all the connected devices. After wiring, be sure to reattach the terminal cover. Failure to do so might cause electric shock. Before wiring and maintenance, be sure to turn off the power to the product. Failure to do so might cause electric shock. CAUTION Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards. All wiring must comply with applicable codes and ordinances. Firmly tighten the terminal screws. Insufficient tightening of the terminal screws might cause fire or overheating. For wiring, strip each wire insulation for the length specified in this manual. If the strip length is longer than the specified, the stripped part of the wires will be exposed, causing electric shock or short circuit between adjacent terminals. If it is shorter, the stripped part will not contact the connector. Do not use unused/spare terminals on the product as relay terminals. Doing so might cause malfunction. Do not block the ventilation holes of this product. (Be sure to peel off the protective sheet after installation and wiring). Doing so might cause device failure. Precautions for wiring Tube marker: Since Infilex AC adopts the screwless push-in terminals, wires are connected without crimping terminal lugs. Therefore, if normal tube markers are used, they may come off when you disconnect the wires. To prevent this, use the following Flat Tube Marker. It is held on a wire by friction and thus does not come off easily. Flat Tube Marker Manufacturer Phoenix Contact Item number Model TMC-3 Applicable wire size 0.4 mm 2 to 2 mm 2 Package unit 200 m/roll 2 mm 2 cable running outside the control panel: Use an external terminal block to switch to 1.25 mm 2 cable inside the control panel. Two wires for one terminal: Use an external terminal block to aggregate the wires. Fan ON/OFF: Use a small-power circuit (max. 60 V operating voltage and 1.5 A operating current) to turn on and off fan. Signal wire for output to inverter: Use a shielded cable. Power supply wiring Crimp M3 terminal lugs with insulation on the wire ends, and connect the wires to the power supply terminals. Power supply wires Power supply terminals Connect. Figure 8. Power supply wiring 13

14 Wiring to I/O and NC-bus terminals The I/O and NC-bus wires are connected to the screwless push-in terminals of Infilex AC. Follow the procedure below for the I/O and NC-bus wiring. 1) Strip the wire sheath 8 mm. Note: * Scale for the strip length is indicated on the front surface of Infilex AC basic unit. If the insulation stripped part is longer than 8 mm, it may get exposed, causing electrical shock or short circuit between adjacent terminals. If it is shorter, it may not contact the terminal connector. 2) Make sure that no wire fiber goes out of the wire end. 3) Press the button on the terminal block deeply enough using a slotted screwdriver and insert the wire. (Maximum button-pressing force is 23 N.) Then, release the button. 4) Gently pull out the wire horizontally to make sure that it is completely held by the clamp and check no wire fiber being disconnected from the terminal. Note: * If you pull out the wire diagonally, it may be disconnected. Arrangement of the wires connected to Infilex AC LED Data Setter connector S1 switch Battery holder (Infilex AC mounted sideway with the power supply terminals located on the lower corner. Indication tag Notes: * Neatly place the wires using cable ties or the like so as not to hide LED, Data Setter connector, mark of Data Setter connector, S1 switch, battery holder, and indication tag. * Do not leave slack in the wires that run between the cable duct and Infilex AC. * Sideway mounting shown in the figure above is allowed only when I/O module, UT module, or integral type Operator Panel is NOT assembled with the basic unit. Do not mount the Infilex AC basic unit sideway with the power supply terminals located upper corner, lying on its back, or lying face down. Always install the basic unit assembled with an I/O module, and/or UT module/integral type Operator Panel in upright position. Figure 9. Arrangement of the wires connected to Infilex AC 14

15 Precautions for Wiring of Infilex AC and Devices System common wiring Ground line () is used as a common line for signal transmission to/from the field devices. For the system common, the common-mode power must be supplied to Infilex AC and each device (such as ACTIVAL ) via the wires connected to "~" and "" terminals of Infilex AC and each device. For the signal transmission between Infilex AC and each device, use "" wiring. Terminal block for branching Infilex AC ACTIVAL or damper actuator + - ACTIVAL or damper actuator + - Figure 10. Wiring example: System common wiring IMPORTANT: Use an isolation transformer. Do not ground the secondary side of the transformer. Provide a terminal block aright ahead of the transformer, and divide the line at the terminal block to connect to each device. (See Fig. 10.) Inverter 24 V AC From From Infilex AC Inverter + - Figure 11. Wiring example: Inverter IMPORTANT: Shielded cable must be single-point grounded on the inverter. 15

16 Humidity sensor Infilex AC Humidity sensor 24 V AC + - Figure 12. Wiring example: humidity sensor IMPORTANT: If Infilex AC and a humidity sensor are powered by a single transformer, the sensor might get damaged. Depending on the other connected devices and on the wiring condition, a short-circuit current may flow into the sensor and into the Infilex AC. Precautions for Use Before supplying the power Check that the all the wires are correctly connected. Remove the protective sheet from the top surface of Infilex AC. Note: * if some foreign objects possibly come inside Infilex AC from the ventilation holes on the side and bottom surfaces, cover the ventilation holes with sheets. 2) Tear off. 1) Peel off the adhesive area. Figure 13. Protective sheet Several tens of seconds are required for the Infilex AC normal operation after the power is turned on. During this time, the red LED on the front stays ON temporarily, but this does not indicate an error. 16

17 Connection of our engineering tool (Data Setter / PC-MMI) Connection of Data Setter Model QY5111B No conversion cable is required. Directly insert the male connector of the Data Setter into the female connector provided on the Infilex AC basic unit. At this time, hold the male connector with the mark facing left and insert it so that the mark points to the mark on the Infilex AC basic unit. Connection of Data Setter Model QY7211B Convert the D-SUB connector to the mini DIN connector with the conversion cable (Part No ). At this time, hold the male connector with the mark facing left and insert it so that the mark points to the mark on the Infilex AC basic unit. Insert the male connector as the two marks point to each other. Figure 14. Connection of our engineering tool System indication label for the controller number The indication tag has the system indication label on its back. Turn it over and fill in the controller number on the label. Turn over. Indication tag Figure 15. System indication label 17

18 Maintenance (Lithium Battery Replacement) CAUTION When replacing batteries, read the instructions hereinafter and correctly replace the product batteries. Failure to do so might cause overheating, burst, or leakage of the batteries. Dispose of the used batteries in accordance with your local regulations. Do not throw them in fire or in general garbage. Doing so might cause burst or ignition. IMPORTANT: Only authorized service personnel is allowed to replace the battery. Do not touch the power supply unit when replaceing the battery. Replace the lithium battery every 5 years if the product is always in use (in ON state). Since the remaining battery level cannot be checked by measuring the terminal voltage, be sure to replace the battery every 5 years. Replace the lithium battery with the power ON. If the product has never or hardly been operated (in OFF state) for a year, replace the lithium battery before the product operation. Battery replacement 1) Pull out the battery holder using a slotted screwdriver. 2) Disconnect the connector and detach the lithium battery from the battery holder. 3) Place a new lithium battery in the battery holder and connect the connector. 4) Insert the battery holder into the basic unit. 5) Fill in the date for next replacement (5 years after the replacement) on the indication tag using an oil-based pen. Lithium battery for backup 1) 4) 2) 3) Infilex AC basic unit 5) Battery holder Battery Connector Figure 16. Battery replacement 18

19 Blank page added for page editing purpose. 19

20 Install this product in a panel cabinet. This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive (EMCD) and the Restriction of the use of certain Hazardous Substances in Electrical and Electronic Equipment Directive (RoHSD). EMCD: EN Class A, Table 2 (for use in an industrial electromagnetic environment) RoHSD: EN ACTIVAL and Infilex are trademarks of Azbil Corporation in Japan or in other countries. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). AB-6438 Rev. 9.0 Jul

Infilex AC AHU Controller Model WY5317C

Infilex AC AHU Controller Model WY5317C Specifications/Instructions Infilex AC AHU Controller Model WY5317C General Infilex AC (Infilex: named for Infinity and Flexible ) Model WY5317C is a DDC (direct digital control) controller for AHU (air

More information

Infilex GC Multipurpose Controller Model WY5111

Infilex GC Multipurpose Controller Model WY5111 Specifications/Instructions Infilex GC Multipurpose Controller Model WY5111 General Infilex GC (Infilex: named for Infinity and Flexible ) Model WY5111 is a multipurpose controller designed to control

More information

Infilex GD Multipurpose Data Gathering Panel Model WY5310

Infilex GD Multipurpose Data Gathering Panel Model WY5310 Specifications/Instructions Infilex GD Multipurpose Data Gathering Panel Model WY5310 General Infilex GD (Infilex: named for Infinity and Flexible ) Model WY5310 is a multipurpose terminal data transfer

More information

Infilex GC Multipurpose Controller Model WY5311

Infilex GC Multipurpose Controller Model WY5311 Specifications/Instructions Infilex GC Multipurpose Controller Model WY5311 General Infilex GC (Infilex: named for Infinity and Flexible ) Model WY5311 is a multipurpose controller designed to control

More information

Intelligent Component Series Direct Coupled Damper Actuator Model MY8040A

Intelligent Component Series Direct Coupled Damper Actuator Model MY8040A Specifications/Instructions Intelligent Component Series Direct Coupled Damper Actuator Model MY8040A General Model MY8040A direct coupled damper actuator is a motorized actuator to open/close a damper.

More information

I/O Modules, User Terminal Module, and SAnet Interface Module

I/O Modules, User Terminal Module, and SAnet Interface Module Specifications/Instructions I/O Modules, User Terminal Module, and SAnet Interface Module for Infilex AC, Infilex GC, Infilex GD, PARAMATRIX 4, and Infilex BC I/O Control Unit General Model RY50XX series

More information

Infilex FC. Fan Coil Unit Controller for SC-bus Communication. Specifications/Instructions. Overview. Features AB-6567

Infilex FC. Fan Coil Unit Controller for SC-bus Communication. Specifications/Instructions. Overview. Features AB-6567 Specifications/Instructions Infilex FC Fan Coil Unit Controller for SC-bus Communication Overview Infilex FC Model WY5205W is a DDC controller for FCU. In addition to FCU ON/OFF operation, valve control,

More information

Advanced Remote I/O Module

Advanced Remote I/O Module Specifications/Instructions Advanced Remote I/O Module Overview This product ( RJ-1101W1600 or RJ-1102W1600) is a dedicated remote I/O module for Advanced Controller ( WJ-1101W0000). Up to 20 RJ-1 I/O

More information

BACnet Controller for General-purpose Building Applications

BACnet Controller for General-purpose Building Applications Specifications BACnet Controller for General-purpose Building Applications General Model WJ-1101 is the BACnet controller to be used for a wide range of building applications such as air-conditioning and

More information

PARAMATRIX 4 Chiller Controller

PARAMATRIX 4 Chiller Controller Specifications PARAMATRIX 4 Chiller Controller General PARAMATRIX 4 (often shortened to PMX-4) is a Direct Digital Controller (DDC) specifically designed only for sequential control of heating/cooling

More information

SCS (System Core Server) Model BCY44100M

SCS (System Core Server) Model BCY44100M Specifications General SCS (System Core Server) is a controller that integrates DDC (direct digital controller) and RS (remote station), such as PARAMATRIX -III and Infilex series controllers, into BMS

More information

Infilex VC Variable Air Volume Controller with Actuator for SC-bus Communication

Infilex VC Variable Air Volume Controller with Actuator for SC-bus Communication Specifications/Instructions Infilex VC Variable Air Volume Controller with Actuator for SC-bus Communication Overview Infilex VC (Infilex: named for Infinity and Flexible ) Model WY5206C is a VAV controller

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the

More information

(Thermoplate (Auxiliary part))

(Thermoplate (Auxiliary part)) Specifications/Instructions Neopanel Digital User Terminal for Infilex Series Controller (Thermoplate (Auxiliary part)) General Model QY7205 Neopanel is a digital user terminal for the controllers such

More information

Infilex VC Variable Air Volume Controller with Actuator for BACnet MS/TP Communication

Infilex VC Variable Air Volume Controller with Actuator for BACnet MS/TP Communication Specifications/Instructions Infilex VC Variable Air Volume Controller with Actuator for BACnet MS/TP Communication General Infilex VC Model WY5706C is our new VAV controller with an actuator that communicates

More information

PARAMATRIX -III Chiller Controller Model WY7400T

PARAMATRIX -III Chiller Controller Model WY7400T Specifications PARAMATRIX -III Chiller Controller Model WY7400T General PARAMATRIX-III (PMX-III) is a direct digital controller (DDC) specifically designed for sequential control of chiller plant units

More information

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Wired Remote Controller 7 Day Programmable Ductless Systems KSACN0401AAA (High Wall Models) KSACN0501AAA (Ducted/Cassette Models) INSTALLATION INSTRUCTIONS NOTE: Read the entire instruction manual before

More information

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

Communicative controller for VAV systems

Communicative controller for VAV systems FCR015 Communicative controller for VAV systems Summary FCR015 is a communicative controller for heating and cooling panels and a VAV (variable air volume) damper. It measures temperature and CO 2 concentration

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808R, UID-0808T, UID-1600,UID-0016R, UID-0016T Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1 IO-PT4 I/O Expansion Module 4 PT100 Inputs (-50 to 460 C) The IO-PT4 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 4 PT100 inputs

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UID-W1616R, UID-W1616T Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide

More information

Installation Manual INTELLIGENT SERVER. Model name: BMS-LSV6UL

Installation Manual INTELLIGENT SERVER. Model name: BMS-LSV6UL Model name: BMS-LSV6UL INTELLIGENT SERVER Thank you very much for purchasing this TOSHIBA INTELLIGENT SERVER. Please read this manual carefully beforehand for proper installation of the SERVER. NOTE This

More information

Twido Programmable Controllers Discrete I/O Modules

Twido Programmable Controllers Discrete I/O Modules Twido Programmable Controllers Discrete I/O Modules Hardware Guide 03/2007 www.telemecanique.com 2 Table of Contents Safety Information....................................5 About the Book.......................................9

More information

DIGITAL INPUT/OUTPUT RELAY INTERFACE BMS-IFDD01E

DIGITAL INPUT/OUTPUT RELAY INTERFACE BMS-IFDD01E INSTALLATION MANUAL DIGITAL INPUT/OUTPUT RELAY INTERFACE BMS-IFDD01E Thank you very much for purchasing this TOSHIBA Digital Input/Output Relay Interface. Please read this manual carefully beforehand for

More information

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005 Product and Applications Description Application Programs The application programs of the dimmer UP 525/01 consist of two elements: the actuating and the sensor program element. The tasks actuating program

More information

Analog Monitor Installation Manual

Analog Monitor Installation Manual Analog Monitor Installation Manual Part Number: 144-23919 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems and equipment.

More information

Non-communicating room controllers

Non-communicating room controllers 3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,

More information

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs The IO-DI8-TO8 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 digital inputs,

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

DC I/O Conversion Module FA-TB32XY

DC I/O Conversion Module FA-TB32XY DC I/O Conversion Module FA-TB32XY User's Manual Thank you for purchasing FA Goods product. Before using, please read this User s Manual and the relevant manuals carefully to ensure correct use. SAFETY

More information

V E1B Snap-in I/O Module

V E1B Snap-in I/O Module V200-18-E1B Snap-in I/O Module The V200-18-E1B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital

More information

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs Product and Applications Description Example of Operation dimmer UP 525/11 load circuit AC 230 V L1 N The dimmer UP 525/11 is a dimming actuator for mounting in box mounts (a.o. 60 mm Ø, 60 mm depth).

More information

V E2B Snap-in I/O Module

V E2B Snap-in I/O Module V200-18-E2B Snap-in I/O Module The V200-18-E2B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital

More information

Manual Control Unit GFC 32

Manual Control Unit GFC 32 Manual Control Unit 1400004_EN/05.2017 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Settings 6 7. Remote control

More information

Operating Instructions VEGAMET 381

Operating Instructions VEGAMET 381 Operating Instructions VEGAMET 381 in out Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6 2.1 Authorised personnel...

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Analog Input Installation Manual

Analog Input Installation Manual Analog Input Installation Manual August 2011 Part Number: 144-23917 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems

More information

B&W RearView Camera Installation & Operation

B&W RearView Camera Installation & Operation B&W RearView Camera Installation & Operation CA52 (Camera) FOR MORE INFORMATION WWW.STRATEGICVISTA.COM BEFORE OPERATING THIS SYSTEM, PLEASE READ THIS MANUAL THOROUGHLY AND RETAIN IT FOR FUTURE REFERENCE

More information

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A) Product and functional description also functions if the bus cable is not connected or if the bus communication fails. After a long push button action (> 2 s), the other valve group is selected. The yellow

More information

Operation Manual. Fieldbus system EX510-GPR1. PROFIBUS DP Compatible GW unit

Operation Manual. Fieldbus system EX510-GPR1. PROFIBUS DP Compatible GW unit Fieldbus system PROFIBUS DP Compatible GW unit Operation Manual EX50-GPR URL http://www.smcworld.com Akihabara UDX 5F, --, Sotokanda, Chiyoda-ku, Tokyo 0-00, JAPAN Phone: +8 3-507-89 Fax: +8 3-598-536

More information

PS/IO Circuit Board Retrofit

PS/IO Circuit Board Retrofit S&C 6800 Series Automatic Switch Controls PS/IO Circuit Board Retrofit Table of Contents Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet....

More information

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13 s 3 875 RXB Room controller Communicating room controller for fan-coil applications FC-13 RXB39.1 The RXB39.1 room controller is used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil

More information

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

Rhino Redundancy Module PSM24-REM360S. Operating Instructions Rhino Redundancy Module PSM4-REM360S Operating Instructions RHINO REDUNDANCY MODULE PSM4-REM360S Description With this module and two power supplies of the PSM series (78, 90, 56, 80 and 360 watt models),

More information

Extension module for lighting control

Extension module for lighting control s 3 842 DESIGO RXC Extension module for lighting control Extension to the RXC30 / RXC31 / RXC38 room controller RXC40.1 RXC40.5 The RXC40 extension module is used in conjunction with an RXC30, RXC31 or

More information

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02 s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808THS Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-TO8 and IO-DI8-TO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The

More information

MODEL: M5DY SEN TRONIC AG CURRENT LOOP SUPPLY. [2] POWER INPUT AC Power M: V AC (Operational voltage range V, Hz)

MODEL: M5DY SEN TRONIC AG CURRENT LOOP SUPPLY. [2] POWER INPUT AC Power M: V AC (Operational voltage range V, Hz) Super-mini Terminal Block Signal Conditioners M5-UNIT CURRENT LOOP SUPPLY Functions & Features Powering a 0 ma DC current loop Applicable to smart transmitters Isolation between the input and output Fast

More information

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display UC102 Communicative heating controller Summary UC102 is a communicative room heating controller with two inputs and one PWM output for control of a radiator or electrical heater. It can work autonomously,

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIS-04PTN Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

Wireless Remote Controller Kit

Wireless Remote Controller Kit INSTALLATION MANUAL Wireless Remote Controller Kit LS BRC4C8 Read these instructions carefully before installation. Keep this manual in a handy place for future reference. This manual should be left with

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UIS-WCB1 Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide as Uni-I/O

More information

Operation Manual. Fieldbus system EX510-GDN1. DeviceNet Compatible GW unit

Operation Manual. Fieldbus system EX510-GDN1. DeviceNet Compatible GW unit Fieldbus system DeviceNet Compatible GW unit Operation Manual EX50-GDN URL http://www.smcworld.com Akihabara UDX 5F, --, Sotokanda, Chiyoda-ku, Tokyo 0-00, JAPAN Phone: +8-507-89 Fax: +8-598-56 Note: Specifications

More information

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 UniStream HMI Panel Installation Guide USP-070-B10, USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for

More information

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual. The power behind competitiveness Delta Infrasuite Power Management Power Distribution Unit User Manual www.deltapowersolutions.com Save This Manual This manual contains important instructions and warnings

More information

DC I/O Conversion Module

DC I/O Conversion Module DC I/O Conversion Module,FA-TB32XYH User's Manual Thank you for purchasing FA Goods product. Before using, please read this User s Manual and the relevant manuals carefully to ensure correct use. SAFETY

More information

English. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM

English. Operating manual. Universal transmitter UT125.  Save for later reference. Companies / brands of GHM English Operating manual Universal transmitter UT125 Companies / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents page 1. Intended use (areas of application)... 3 1.1 Safety

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Vision OPLC V350-35-R34/V350-J-R34 Installation Guide The Unitronics V350-35-R34/V350-J-R34 offers the following onboard I/Os: 22 Digital Inputs, configurable via wiring to include 2 Analog and 3 HSC/Shaft-encoder

More information

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

QUICK START GUIDE. vau4/3. Frequency converter.   operating instructions /12 operating instructions QUICK START GUIDE Frequency converter vau4/3 28100241101 12/12 1 Safety information Warning of electrical shock! Danger to life! Electrical shock can cause serious injury or even

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIA-0402N Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

TOP - 1. Instruction Manual. Version 1.0 Produced in Jan. 2004

TOP - 1. Instruction Manual. Version 1.0 Produced in Jan. 2004 Version 1.0 Produced in Jan. 2004 Instruction Manual LCD monitor IV-08MP Thank you for purchasing the SHARP IV-08MP LCD monitor. Read this introductory instruction manual carefully to thoroughly familiarize

More information

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000 1 542 1542P03 1542P01 1542P02 QXA2001 QXA2000 AQX2000 Condensation Monitor QXA2000 QXA2001 The QXA2000 condensation monitor is used to avoid damage due to condensation on chilled ceilings and in HVAC plant.

More information

PROGRAMMABLE CONTROLLER. FP0 A/D Converter Unit. Technical Manual ARCT1F321E

PROGRAMMABLE CONTROLLER. FP0 A/D Converter Unit. Technical Manual ARCT1F321E PROGRAMMABLE CONTROLLER Technical Manual ARCT1F321E-2 2008.11 Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly,

More information

PAR-WT50R-E PAR-WR51R-E

PAR-WT50R-E PAR-WR51R-E Wireless Remote Controller and Receiver PAR-WT50R-E PAR-WR51R-E This manual explains installation of the PAR-WR51R-E wireless receiver and the PAR-WT50R-E wireless remote controller, and settings of these

More information

Touch-controller_IM_03943A_1_Co_EN.indd 오후 3:06:00

Touch-controller_IM_03943A_1_Co_EN.indd 오후 3:06:00 Touch-controller_IM_03943A_1_Co_EN.indd 2 2013-06-28 오후 3:06:00 Touch Centralized Controller MCM-A300N Air Conditioner installation manual This manual is made with 100% recycled paper. imagine the possibilities

More information

V E1B Snap-in I/O Module

V E1B Snap-in I/O Module V200-18-E1B Snap-in I/O Module The V200-18-E1B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital

More information

Manual Simatek Control Unit GFC 32

Manual Simatek Control Unit GFC 32 Manual Simatek Control Unit GFC 32 Original instructions 1400004_GB Ver. 2014.01.09 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections

More information

Manual Control Unit GFC 16

Manual Control Unit GFC 16 Manual Control Unit 1400003_EN/04.2017 Index 1. Main features 3 2. Tekniske data 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Settings 5 7. Remote 7 8. Shut down

More information

Non-communicating room controllers

Non-communicating room controllers 3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For

More information

MODEL: R2K-1 SEN TRONIC AG. R2K Series

MODEL: R2K-1 SEN TRONIC AG. R2K Series 1 MODEL: R2K-1 R2K Series /RS-485 CONVERTER Functions & Features Bidirectional converter between and RS-485 used when connecting Modbus RS-485 devices to a PC CE marking Standard: Conforms to, EIA Transmission

More information

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E Table of contents 1. INTRODUCTION...1 2. HARDWARE DESCRIPTION...2 3. INSTALLATION...6 4. CONNECTION...8 5. USER SAFETY AND PROTECTION OF THE EQUIPMENT...11

More information

High Speed Remote I/O Module

High Speed Remote I/O Module High Speed Remote I/O Module EXF-RC15 The Unitronics EXF-RC15 is a High Speed Remote I/O Module that offers three High Speed Counter inputs and four high speed outputs. Overall, the EXF-RC15 offers 9 digital

More information

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description SIL 3 coupling relay for safety-related switch on Data sheet 105818_en_01 PHOENIX CONTACT 2014-08-18 1 Description The PSR-PC50 SIL coupling relay can be used for power adaptation and electrical isolation

More information

TOUCH SCREEN CONTROLLER for Air Conditioning Control System

TOUCH SCREEN CONTROLLER for Air Conditioning Control System INSTALLATION MANUAL TOUCH SCREEN CONTROLLER for Air Conditioning Control System Model: BMS-TP064ACE BMS-TP064PWE BMS-TP52ACE BMS-TP52PWE Thank you very much for purchasing the TOSHIBA Touch Screen Controller.

More information

AB Axis Industries. Use

AB Axis Industries. Use AB Axis Industries PULSE ADAPTER ENCO PULSE The ENCO PULSE pulse adapter acquires and handles the pulses from consumption meters with pulse output and transmits the data to a network of AMR system. Use

More information

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3 Overview Safety notes 1 SITOP power supply Manual Description, device design, dimension drawing 2 Mounting/removal 3 Mounting position, mounting clearances 4 Installation 5 Technical data 6 Safety, approvals,

More information

Installation Job Aid for VSP 4850GTS

Installation Job Aid for VSP 4850GTS Installation Job Aid for VSP 4850GTS Notices Release 6.1.0.0 NN46251-308 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs describe

More information

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date: Documentation Fan cartridge for EtherCAT and Bus Terminals Version: Date: 1.5 2017-08-07 Table of contents Table of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety instructions...

More information

Vision OPLC V TR6/V350-J-TR6

Vision OPLC V TR6/V350-J-TR6 Vision OPLC V350-35-TR6/V350-J-TR6 Installation Guide The Unitronics V350-35-TR6/V350-J-TR6 offers the following onboard I/Os: 8 Digital Inputs, configurable via wiring to include 2 Analog (current/voltage)

More information

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER MODEL : ARC2020

USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER MODEL : ARC2020 USER MANUAL MULTI COLOR MODEL : ARC2020 ACCSYS ELECTRONICS 140/6B, GOLDEN INDUSTRIAL ESTATE, JAWAHARLAL NEHRU ROAD, GERUGAMBAKKAM, CHENNAI - 600122 Tel: 044 60505599 / 60505511 E-mail : sales@accsyselectronics.com

More information

CPCI-PS24 24V-Power Supply

CPCI-PS24 24V-Power Supply 24V-Power Supply Hardware Manual to Product I.2301.21 esd electronic system design gmbh Vahrenwalder Str. 207 30165 Hannover Germany http://www.esd.eu Phone: +49 (0) 511 3 72 98-0 Fax: +49 (0) 511 3 72

More information

Conductive Level Controller

Conductive Level Controller Conductive Level Controller 61F-D21T-V1 Ideal for level control for industrial facilities and equipment. Outputs can be set to self-hold at ON or OFF using self-holding circuits. Sensitivity adjustment

More information

F1000 User's Manual. (Version: V1.01)

F1000 User's Manual. (Version: V1.01) (Version: V1.01) Contents Chapter 1 Overview... 2 Chapter 2 Installation... 3 2.1 Installation guide... 3 2.1.1 Installation position... 3 2.1.2 NEMA4 standard installation... 3 2.1.3 Environment precautions...

More information

Instruction Sheet Board Style Low Water Cutoff

Instruction Sheet Board Style Low Water Cutoff Instruction Sheet Board Style Low Water Cutoff 102-305 SUPERSEDES: REVISION E DATED December 12, 2007 #5401173-REV F PLANT ID 001-3902 US Patents 6,904,800, 7,243,540, and 7,317,993 Other Patents Pending

More information

Dell Networking S4810 Open Networking (ON) Getting Started Guide

Dell Networking S4810 Open Networking (ON) Getting Started Guide Dell Networking S4810 Open Networking (ON) Getting Started Guide Regulatory Model: S4810 Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better use of your

More information

ASI Systems ML5740A Series

ASI Systems ML5740A Series ML5740A Series Electric Linear Valve Actuators Non-Spring Return APPLICATION The ML5740A series actuators operate standard ASI Systems valves in heating, ventilating and air conditioning (HVAC) applications.

More information

Communications & Networking

Communications & Networking 8-Point Source Input & 8-Point Transistor Sink Output odule () Key features include: Communicate with network 8-point source input and 8-point sink output module Removable terminal blocks Use as remote

More information

Model Number Structure

Model Number Structure Solid State Relays with Failure Detection Function G3PC CSM_G3PC_DS_E_1_1 Refer to Safety Precautions for All Solid State Relays. Detects failures in SSR used for heater temperature control and simultaneously

More information

Dell Networking S4100-ON Series. Set-Up Guide

Dell Networking S4100-ON Series. Set-Up Guide Dell Networking S4100-ON Series Set-Up Guide Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either

More information

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016 Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target

More information

External level devices for conductive point level switch

External level devices for conductive point level switch SENSORS FOR FOOD AND BIOPHARMA. Product Information VNV-2, ZNV-2 CONTROLS External level devices for conductive point level switch Application/Specified usage Point level detection of aqueous, conductive

More information