UniPak UP448 Bridge Input Isolating Signal Conditioner

Size: px
Start display at page:

Download "UniPak UP448 Bridge Input Isolating Signal Conditioner"

Transcription

1 6-wire Bridge Connection Excitation for to 350 Ω Load Cells 500 Volt (3-way) Isolation Excellent Accuracy (0.0%) DIP Switch Configuration Digital Input Tare Calibration RS85 Modbus RTU Superior Flexible Power: 0-0 VDC or 9-28 VAC (50-60 Hz) DIN Rail Mount (35 mm) Removable Terminal Blocks UniPak UP8 The UniPak model UP8 provides configuration for the most popular load cells and measurement spans commonly used: mv to 28 mv with a 5 V excitation. This translates to load cell sensitivity of 0.2 mv/v to 25.6 mv/v. The UP8 has a configurable DC current or voltage output. The UP8 also has a Digital I/O port that may be used as either a digital input (Tare) or output. The UP8 completes its unprecedented flexibility by including a standard serial communication protocol, Modbus RTU, via RS85 bus or direct via RS232. The UP8 may be a Modbus slave. PC Configuration software is available for enhanced operation and Modbus register configuration. LEDs on the front indicate status and power and provide feedback for the Modbus communications. Signal Conditioning flexibility and use made easy from ioselect, powered by Seneca (Z-SG). General Specification Input Digital Excitation Output Current Voltage Digital Power Power Consumption 2 W RS85 Interface 6-wire Bridge span mv to 28 mv Sensitivity of 0.2 mv/v to 25.6 mv/v 30 V Maximum Tare or Span Calibration 5 ~60 ma (87.5 Ω min) = Up to Four 350 Ω Bridges in Parallel -20 ma, V (600 Ω max) 0-5 V, ma (2 kω min) ma Maximum (external) 0 to 0 Vdc or 9 to 28 Vac 2-wires 200 to 5,200 baud ModBus RTU Slave Protocol Performance Specifications Isolation 500 Vac Accuracy 0.0% Calibration 0.0% Linearity % Thermal Coefficient Sampling Frequency 2.53 to 5.7 Hz = Response Time 6.6 ms to 80 ms Operating Temp Storage Temp -0 to 65 C ( to 50 F) -0 to 85 C (-0 to 85 F) Humidity 30 to 0 C (non-condensing) Weight Dimensions 0 g (.9 oz) 7.5 x 00 x 2 mm 0.69 x 3.9 x. in Mounting 35 mm DIN 6277 Ordering Information: IOS-UP-8 IOS- Z-SG Accessories: IOS-Z-NET3 Configuration Software Fax: (800) Ph: (877) 3GET IOS (33-867)

2 Installation Instructions UniPak UP8 / Z-SG Install on horizontally mounted TS 35 DIN rail. For optimum operation and product life make sure adequate ventilation is provided. Severe operating conditions are defined as follows: Power supply voltage > 30 Vdc or 26 Vac Input sensor powered from UP8 Output current sourced from UP8 Modules may need to be separated by at least 5 mm if: The panel temperature exceeds 5 C and one or more of the above conditions exist. The panel temperature exceeds 35 C and 2 or more of the above conditions exist. Wiring Diagrams Power Supply Digital Input Vac or 9-0 Vdc The upper limits must not be exceeded! Serious damage could result 7 8 V 2 Vdc Input and Output Configuration 6 Excitation Sense - Sense - Excitation Bridge Input Signal - Signal Wire The UP8 may be configured using a calibrator, the live load cell system (if control of the full scale is available), via a PC or via Modbus RTU protocol. There are 3 DIP-switches on the UP8: SW, SW2 and SW3. SW defines the baud rate and Modbus address for Modbus communications. SW3 should be ON if the UP8 is the last device on the serial communications bus. SW2 defines the use of the Digital I/O, sets the input range (aka: sensitivity), sets the output range and the function of the push button. The push button can be locked out so no inadvertent press will affect the settings. It may be used to define the tare (constant load) and full scale input (see the next page for details). The configurable digital I/O port is useful as an output to indicate a stable weight has been reached. When configured as an input the digital I/O port is useful to set the zero for the tare function. Enhanced functions are available using Modbus RTU or the configuration software (See the Modbus Register definitions). The Excitation is fixed at 5 Vdc. Digital Output Load V 2 Vdc Excitation Sense - Sense - Excitation Output Voltage Output Current 5 V -Wire Signal - Signal Baud Rate & Modbus Address Selection SW SW SW3 Bus Terminator 2 OFF ON Baud Address EEPROM Pin Connections. Digital Input/Output 2. Power 3. Power. Output 5. - Output 6. Digital Input/Output 7. Excitation 8. Sense 9 Signal 0. - Excitation. - Sense 2. - Signal Digital I/O, Output Range & Input Sensitivity SW2 Digital I/O Input Output SW2 Output Range 0-0 V 0-5 V 0-20 ma - 20 ma SW2 Sensitivity ± mv/v ± 2 mv/v ± mv/v ± 8 mv/v ± 6 mv/v ± 32 mv/v ± 6 mv/v ± 28 mv/v RS85 Connections ERR PWR RX TX COM Push Button Function SW2 Calibration Default Tare Full Scale Stored Legend = ON = N.A. Full Scale is the Excitation multiplied by the Sensitivity, e.g.: (Excitation = 5 V) 2 mv/v x 5 V = 0 mv (877) 3GET IOS (33-867)

3 Manual Calibration UniPak UP88 / Z-SG ) Set the DIP switches for the desired sensitivity and output ranges. Set SW2- = OFF and SW2-5 = ON. 2) Power the Z-SG, connect a multi-meter to the output and a millivolt calibrator to the Signal and -Signal terminals. 3) Using a calibrator set the input to the TARE (0% input) level. ) Press and hold the push-button until the yellow LED is flashing. The TARE value is stored. NOTE: Release the button within 5 seconds from the moment the LED begins to flash or the calibration process will end. 5) Using the calibrator introduce the TARE FULL SCALE (00% input) level to the input. 6) Set SW2- = ON (SW2-5 remains ON). 7) Press and hold the push button until the yellow LED is flashing (See NOTE above). 8) Press and hold the push button until the yellow LED stops flashing. The TARE FULL SCALE level is stored. 9) Confirm that input and output correspond as desired by setting the calibrator to TARE for 0% output. 0) Set input to TARE FULL SCALE to confirm output is 00%. Software Calibration During the entire procedure read the register ADC_LONG ( ) with a ms interval to maintain communication from the front jack. TARE Acquisition ) Set the DIP switches for the desired sensitivity and output ranges. Set SW2- & 5 = ON. 2) Connect the Z-SG to the PC and power. 3) Enter the password 0xFACB in the RESET register (0039). ) Introduce the TARE level to the Signal and -Signal terminals. Wait 5 seconds for stabilization. 5) Acquire 0 samples from the register ADC_LONG ( ) at intervals of 500 ms then calculate the mean value. 6) Save the mean value obtained in the long TARE register TARE_LONG ( ). 7) Provide the command for a Reset by entering the 0xABAC value in the register RESET (0039). FULL SCALE Acquisition ) Follow steps -5 above with the exception of using the FULL SCALE level in place of the TARE level. 2) Save the mean value in the long FULLSCALE variable. 3) Define the following long support value: NET=FULLSCALE - TARE. ) Save the net FULL SCALE value in the float variable: TECHN 5) Define the following support float variable: K_WEIGHT_FLOAT=TECHN/NET. 6) Save the long support variable value NET in the register: LONG ( ). 7) Save the support float variable value K_WEIGHT_FLOAT in the register: K_WEIGHT_FLOAT(00-005). 8) Save the support float variable value TECHN in the register: FL( ). 9) Provide the command for a Reset by entering the 0xABAC value in the register RESET(0039). Description of Operation The input's measured value is translated into an analog output signal (current or voltage). The input is available through Modbus RTU protocol upon query by RS85 bus and/or RS232 jack. Serial communication parameters can be made either by Modbus RTU or DIP switch. The Z-SG's various functions are described below. Retransmitted Output The analog output permits the retransmission of the net weight as follows: -At intermediate values, the progression is linear from 0 to 00%. -If the Net Weight in units of weight < 0, the output = 0% - If the Net Weight in units of weight > than the net full scale, the output = 00%. Digital Input/Output The Z-SG offers the ability to select either a digital input or a digital output. The selection is made only by DIP-switch. Digital Input The digital input permits the zeroing of the tare. Digital Output The output can be configured via Modbus for three different operating modes and switches to ON or OFF status (according to Modbus setting) whenever: ) The Net Weight exceeds the Net Full Scale. 2) The Weight is stable and the Net Weight exceeds the threshold. 3) The Weight is stable GET IOS ( ) RS232 Serial Port Cable Dimension Diagram

4 UniPak UP8 / Z-SG Description of Operation (continued) Stable Weight Function Informs the user of the precise moment the weight has stabilized. This information is available via Modbus register (see Register 0037: STATUS) and can also be signalled by digital output (after previous selection and programming by Modbus). This function is characterized by the two parameters: Weight and Time. The weight is considered stable whenever the net weight in Time has changed by a quantity lower than Weight. Remote Zero Setting of the Tare The UP8 permits the zeroing of the tare value by means of digital input (whenever enabled) or via Modbus register (see Register 0037: STATUS). Rejection at 50 and 60 Hz Rejection to interference at both 60 and 50 Hz can be enabled at the same time. See Appendix A for details on setting and optimization Calculation of Measurement Mean Value The mean value of a settable number of samples (NR_SAMPLINGS: to 27) can be calculated. In this way, the NetWeight displayed is the mean value calculated, and the period for which a new value is available is equal to NR_SAMPLINGS* Sampling period. Modbus Registers The UP8 has MODBUS 6 bits (words) registers, accessible by RS85 or RS232 serial communication. This means data can be acquired from a PC or a controller. The next paragraphs describe the supported MODBUS commands, and the functions of the registers. SUPPORTED MODBUS COMMANDS Code Function Description 03 * Read Holding Registers Read up to 6 word registers 0 * Read Input Registers Read up to 6 word registers 06 Write Singe Register Write a word register 6 Write Multiple Registers Write up to 6 word registers * The two functions have the same effect HOLDING REGISTERS The 6-bit Holding Registers have the following structure: Most Significant bit Bit Index Least Significant bit Word (6 Bits): MODBUS Register The Bit notation [x:y] shown in the table indicates all the bits from x to y. For example, Bit [2:] indicates bit 2 and bit, and illustrates the meaning of the various linked combinations of the values of the two bits. Remember that the MODBUS 3,, 6 and 6 single and multiple reading and writing functions can be executed on the following registers. The following indication (only readable or also writable) is provided for every register: R: Readable W: Writable R*: Always readable. Writable only in any of the three following cases: SW2-=OFF and SW2-5=ON, SW2-=ON and SW2-5=OFF, or whenever the correct password has been entered (during the set up phase). MSW = Most Significant Word; LSW = Least Significant Word GET IOS ( ) FLASH REGISTERS MACHINE ID Bit [5:8]: contain the module s ID: 23 (hexa- decimal: 0x7) Bit [7:0]: contain the firmware s revision. 000 R FW_CODE Firmware s Internal Code R HW_REL Instrument s Hardware Version 0003 R ADDR Set the Module s Address and Parity Control 000 R/W BAUDR Bit [5:8] Bit [7:0] Bit [5:8] Bit [7:0] TARE_LONG_H TARE_LONG_L FL_H FL_L Set the Module s Address. Permissible values from 0x00 to 0xFF (0-255). Default = Set the Parity Control: 0x00 = No Parity (Default) 0x0 = Even Parity 0x02 = Odd Parity Set the Baud Rate and the Response Delay Time Set the Baudrate: 0x00: 800 Baud 0x0: 9600 Baud 0x02: 9200 Baud 0x03: 3800 Baud (Default) 0x0: Baud 0x05: 5200 Baud 0x06: Not permitted 0x07: 200 Baud Set the response delay time in characters that represents the number of pauses of 6 characters to be entered between the end of the Rx and the start of the Tx message. Default = 0 tare value (long format, MSW) tare value (long format, LSW) Net measurement full scale in technical units (floating point format, MSW) Net measurement full scale in technical units (floating point format, LSW) Bit [5:0] Set the net measurement full scale in techni- cal units (kg, lbs, etc.) and serves to display the new weight in technical units (FLOAT WEIGHING) Default = LONG_H LONG_L K_WEIGHT_ K_WEIGHT_ THRES_ THRES_ WEIGHT_ net full scale value (long format, MSW) net full scale value (long format, LSW) Bit to unit of weight conversion value (float format, MSW) Bit to unit of weight conversion value (float format, LSW) Threshold in unit of weight (floating point format, MSW) Bit [5:0] If the new weight (WEIGHT_FLOAT: ) exceeds the threshold value set and the weight is stable, the digital output (when set in operating mode) is closed or opened Threshold in unit of weight (floating point format, LSW) Weight variation in technical units accepted for stable weight (float format, MSW) Bit [5:0] Together with Register 0020 ( TIME), per- mits the establishment of when the weight is stable. This represents the weight variation in units of weight accepted for stable weight. The weight is considered stable whenever the net weight in the Time has changed by a quantity lower than Weight. Default = 0005 R/W 0006 R* 0007 R* 0008 R* 0009 R* 000 R* 00 R* 00 R* 005 R* 006 R/W 007 R/W 008 R/W

5 UniPak UP8 / Z-SG FLASH REGISTERS WEIGHT_ TIME RAM REGISTERS ADC_LONG_H Raw A/D value at 2 bits (MSW) 0032 R ADC_LONG_L Raw A/D value at 2 bits (LSW) 0033 R WEIGHT_SHORT Contains the new weight value in ±0000 scale WEIGHT_ WEIGHT_ Bit [5:0] DIGITAL_OUT_ TYPE CONFIG Bit [5:8] Bit [7] Bit [6:0] Bit [5:0] GET IOS ( ) Net weight value in ±0000 scale which the mean value must be calculated. The WEIGHT_FLOAT is equal to the tare. Equal to 0000 when the WEIGHT_FLOAT is equal to the FL (Net Full Scale). Limited: -000 to 000. Net weight value in unit of weight (floating point format, MSW) Net weight value in unit of weight (floating point format, LSW) 003 R 0035 R 0036 R STATUS Status register 0037 R/W Bit [5:5] Bit [] Bit [3] Stable weight : Weight is stable Tare zero-setting request : The zero-setting of the tare is required. Bit [2] Weight 0 : Net Weight = 0 Bit [] Bit [0] Weight variation in technical units accepted for stable weight (float format, LSW) Time in units of 00 ms used to establish whether the weight is stable. This is the parameter that together with Weight establishes Stable Weight. It is expressed in units of 00 ms. Stable Weight occurs when the net weight in Time has change by a quantity lower than Weight. Default = (00 ms) Sets the shifting of the digital output - if enabled by DIP switch Defines the change of the output upon the appearance of the condition set by the Bit [6:0]: 0: The output is normally opened and closes upon the condition. : The output is normally closed and opens upon the condition. Defines the operation of the digital output. Changes state with any of the following: 0: The Net Weight exceeds the Net Full Scale (Default). : The Weight is stable and the Net Weight exceeds the threshold. 2: The Weight is stable Configuration register to set the rejection and sampling frequency Bit [5:0] Sets the sampling frequency and interfer- ence rejection (See Appendix A). Default = 20 (0x00D2) NR_SAMPLINGS Set the number of A/D samplings which the mean value will be calculated Bit [5:0] The number of samples which the mean val- ue must be calculated. The WEIGHT_FLOAT register provides the mean value calculated. Permissible value: -27. Default = 0. Net Weight Net Full Scale : Net Weight Net Full Scale 009 R/W 0020 R/W 002 R/W 0022 R/W 0023 R/W RAM REGISTERS STATUS_DIP- SWITCH Bit [5] Bit [] Bit [3] Bit [2] Bit [] Bit [0] Bit [9] Bit [8] Bit [7] Bit [6] Bit [5] Bit [] Bit [3] Bit [2] Bit [] Bit [0] APPENDIX A Configuration of Sampling Frequency, Measurement update Time and Rejection The table below provides the values that can be set in the Modbus register CONFIG (0022) together with the corresponding sampling frequency values and the net weight value update period. The latter depends on the number of samples for which the mean value will be calculated that has been set in the Register NR_SAMPLINGS (0023). In the table below, N indicates the number of samples value NR_SAMPLINGS while also indicating whether rejection is enabled at 50 or 60 Hz. Value of Register: CONFIG (0022) DIP-switch status display 0038 R Status of SW- Status of SW-2. Status of SW-3. Status of SW-. Status of SW-5. Status of SW-6. Status of SW-7. Status of SW-8. Status of SW2-. Status of SW2-2. Status of SW2-3. Status of SW2-. Status of SW2-5. Status of SW2-6. Status of SW2-7. Status of SW2-8. RESET Module reset control register 0039 R/W Bit [5:0] The command for reset is given by entering the code: 398 (0xABAC) Sampling Frequency (Hz) Measurement Update Time (S) Rejection: 50 Hz Rejection: 50 Hz N * NO NO N * 0.03 NO NO N * YES YES N * NO YES N * NO NO N * YES NO N * YES YES N * NO YES EN /2002 EN /2005 EN600-/200 EN6072 Pending ioselect, Incorporated P: , F: , info@ioselect.com

ioselect Z-NET Z-SG Bridge Input Isolating I/O Module

ioselect Z-NET Z-SG Bridge Input Isolating I/O Module -wire Bridge Connection Excitation for to 30 Ω Load Cells 00 Volt (3-way) Isolation Excellent Accuracy (0.0%) DIP Switch Configuration Digital Input Tare Calibration RS8 Modbus RTU Superior Flexible Power:

More information

USER MANUAL Z-SG / Z-SG-L

USER MANUAL Z-SG / Z-SG-L USER MANUAL Z-SG / Z-SG-L Strain gauge converter with ModbusRTU protocol MI002633 Page 1 Non è stata trovata alcuna voce d'indice. Seneca Z-PC Line modules: Z-SG / Z-SG-L The Z-SG / Z-SG-L modules allows

More information

Strain Gauge Converter

Strain Gauge Converter EN Z-SG General Description Module Z-SG is a strain gauge signal converter. Measurements taken using the 6-wires or 4-wires technique are available through Modbus-RTU serial protocol or the analog output.

More information

USER MANUAL Z-SG / Z-SG-L. Advanced Digital Strain gauge converter. Via Austria, PADOVA ITALY

USER MANUAL Z-SG / Z-SG-L. Advanced Digital Strain gauge converter. Via Austria, PADOVA ITALY USER MANUAL Z-SG / Z-SG-L Advanced Digital Strain gauge converter SENECA s.r.l. Via Austria, 26 35127 PADOVA ITALY Tel. +39.049.8705355 8705359 Fax. +39.049.8706287 Web site: www.seneca.it Technical assistance:

More information

LC0 DVP

LC0 DVP 2010-09-24 5012602300-2LC0.... DVP-1071070-01 POWER RUN ERROR L.V NET ZER O MAX MOTION NET ZER O MAX MOTION CH1 CH2 SHD SHD ENGLISH Thank you for choosing Delta s DVP series PLC. Delta releases DVP02LC-SL

More information

USER MANUAL Z-8NTC 8 CHANNELS NTC TEMPERATURE SENSOR CONVERTER WITH USB / RS485 PORT AND MODBUS RTU PROTOCOL

USER MANUAL Z-8NTC 8 CHANNELS NTC TEMPERATURE SENSOR CONVERTER WITH USB / RS485 PORT AND MODBUS RTU PROTOCOL USER MANUAL Z-8NTC 8 CHANNELS NTC TEMPERATURE SENSOR CONVERTER WITH USB / RS485 PORT AND MODBUS RTU PROTOCOL SENECA S.r.l. Via Austria 26 35127 Z.I. - PADOVA (PD) - ITALY Tel. +39.049.8705355 8705355 Fax

More information

UNIVERSAL CURRENT CONVERTER

UNIVERSAL CURRENT CONVERTER UNIVERSAL CURRENT / VOLTAGE CONVERTER AC/DC Current / Voltage Analyzer The is the first CURRENT / VOLTAGE CONVERTER & ANALYZER ALL IN ONE - of the market. It allow you to connect all isolated current sensors.

More information

Pen Drive USB Datalogger!

Pen Drive USB Datalogger! SINGLE PHASE POWER METER Isolated V/I converter -RS485 Modbus - Datalogger Single-phase power meter RMS, and Voltage/Current Isolated. Signal Converter 1000 VDC / 600 VAC, 10 A AC/DC, Variable frequency

More information

S SENECA. Installation Manual Z-TWS4. Z-PC Line. Web Multifunction Controller Straton / Linux

S SENECA. Installation Manual Z-TWS4. Z-PC Line. Web Multifunction Controller Straton / Linux S SENECA Z-PC Line EN Installation Manual Contents: - General specifications - Technical features - Modbus and CANopen connections - Installation rules - Electrical connections - LEDs signallings - Default

More information

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3 INSTALLATION MANUAL LC 200 Electronic Overload Guard Software versione PW0501 R 0.3 CONTENTS MAIN FEATURES LC 200 TECHNICAL FEATURES Page 2 SYMBOLS Page 3 WARNINGS Page 3 IDENTIFICATION DATA PLATE Page

More information

Characteristics and functioning

Characteristics and functioning Characteristics and functioning 1/1 enod4-t Characteristics and functioning 216702-C_NU-eNod4T-ETH-E-0314 2/2 enod4-t Characteristics and functioning 216702-C_NU-eNod4T-ETH-E-0314 1 ENOD4 PRODUCT RANGE...

More information

Characteristics and functioning

Characteristics and functioning Characteristics and functioning 1/27 enod4-c Characteristics and functioning NU-eNod4C-ETH-E-1014_216706-A 1 ENOD4 PRODUCT RANGE... 4 1.1 General presentation... 4 1.2 Versions and options... 4 1.2.1 Versions...

More information

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES Load Cell and Weighing Indicators A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES INDICATORS Ratiometric Measurement Tare and Auto Transducer Excitation

More information

DCS Series. Digital Counting Scale. Setup Manual

DCS Series. Digital Counting Scale. Setup Manual DCS Series Digital Counting Scale Setup Manual Revision 1.1 February 12, 1997 1996-1997 Transcell Technology, Inc. Contents subject to change without notice. Transcell Technology, Inc. 975 Deerfield Parkway

More information

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process and Ratiometric Signals Features Reads process signals from ±200 mv to ±600V or ±2 ma to ±5A full scale Ratiometric mode for bridges and

More information

DTM Distributed Transmitter Monitor

DTM Distributed Transmitter Monitor Distributed Transmitter Monitor 96 Communication Module The 96 functions as an RS232 to RS485 convertor and / or enables (32) modules to be networked together via Modbus. Combined with the -CFG configuration

More information

Copyright Extract from Conditions of Sale Safety Warning

Copyright Extract from Conditions of Sale Safety Warning KD420 User Manual Copyright 2004-2013 KK Systems Ltd. No reproduction of any part of this document, in any form, is allowed without prior written permission from KKSystems Ltd. All other copyrights and

More information

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-A8VI Installation Guide. The 2300 series stations are designed to

More information

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE POWER MONITORING INSTALLATION GUIDE H8030/8031 H8030/8031 Modbus Energy Meter Networked kw/kwh Transducer Product Identification Model Max Amps CT Size Enhanced Data Stream Meters H8030-0100- 100 H8030-0300-

More information

3 CH Analog Output module / CANopen

3 CH Analog Output module / CANopen 3 CH Analog Output module / CANopen Power Supply 1..4 Vdc, 19..28 Vac Isolation 1,5 kvac (5 way) Accuracy,5% A/D resolution 14 bit Channels 3 Voltage range 1 V Current range..2, 4..2 ma RPDO < 2 ms (-1%

More information

EMC ModWeigh MW61B. Mk2 & Mk3 Weigher System. Application. MW99 Weight Indicator. MW61B_Brochure_Issue_11b EMC INDUSTRIAL GROUP LTD

EMC ModWeigh MW61B. Mk2 & Mk3 Weigher System. Application. MW99 Weight Indicator. MW61B_Brochure_Issue_11b EMC INDUSTRIAL GROUP LTD EMC ModWeigh MW61B Mk2 & Mk3 Weigher System APPLICATIONS Silo/Tank weighing Batch weighing Platform scales FEATURES Digital high accuracy design (no pots or DIP switches) Excitation for up to 10 x 350Ω

More information

Vibration-Resistant Weighing Indicator

Vibration-Resistant Weighing Indicator Vibration-Resistant Weighing Indicator Powerful vibration-cancelling function (High Performance Digital Filter) High speed sampling (100 times/second)/high accuracy Circuits equipped with powerful noise

More information

KTA-250 Anemometer Alarm Card

KTA-250 Anemometer Alarm Card Connects to Davis Instruments DS7911 Anemometer Monitor both the wind speed and direction Interface to PLCs using the Modbus protocol Communicate via RS232 or 2-wire RS485 Interface to PLCs/Instruments

More information

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points) Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners WJ21 series Analog Signal to RS485/232 Converter (A/D Converter) Features: >> Analog signal acquisition, isolated RS-485/232 output >> 12-bit AD converter, testing accuracy>0.1% >> Can Program and calibrate

More information

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description Description LAUREL ELECTRONICS, INC. Features Laureate Digital Panel Meter for Load Cell & Microvolt Input 20, 50, 100, 250 & 500 mv ranges Span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999

More information

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX DOCUMENT NO: TDC 0550 MANUAL - 2 1.0) INTRODUCTION. PAGE 2 1.1) ABOUT THIS MANUAL. PAGE 2 1.2) INTRODUCTION. PAGE

More information

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. IQ300 Wall Mount Load Cell Indicator Data sheet English 1.01 Introduction The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. The high

More information

High Voltage DC Meter

High Voltage DC Meter High Voltage DC Meter Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

Features and Benefits. Certifications

Features and Benefits. Certifications iologik R1200 Series RS-485 remote I/O Features and Benefits Dual RS-485 remote I/O with built-in repeater Supports the installation of multidrop communications parameters Install communications parameters

More information

PENKO Engineering B.V. When Weighing Counts FLEX Multi Channel Extended

PENKO Engineering B.V. When Weighing Counts FLEX Multi Channel Extended SPECIFICATIONS FLEX Multi Channel For each individual weighing channel (channel 1-4) Wiring Full Wheatstone bridge with passive connections (6-wire system) Sense system Passive sense system Excitation

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners Analog Signal to RS485/232 Converter Signal Isolators & Conditioners (WJ21 series A/D Converter) Features: >> Analog signal acquisition, isolated RS-485/232 output >> 12-bit AD converter, testing accuracy>0.1%

More information

HIGH-VOLTAGE DC METER

HIGH-VOLTAGE DC METER HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website:

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: 805HP Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: www.anyload.com Email: info@anyload.com TABLE OF CONTENTS 1. Introduction and Product Features 3 2.

More information

LVX Control Unit. Features:

LVX Control Unit. Features: Date 2013-02-28 Control Unit Features: Most parameters can be defined as required for your interfaces. You decide which information is output and how. Fast cycle times, just a few µs/beam. Maximum beam-count

More information

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual. Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-RO4 Installation Guide. The 2300 series stations are designed to

More information

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. IQ240 Panel Mount Load Cell Indicator Data sheet English 1.01 Introduction The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. The high

More information

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS POWER MONITORING ENERCEPT Networked Power Transducer (Modbus RTU) DANGER US Patent No. 6,373,238 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in

More information

Enercept H8035/H8036 Modbus Energy Meter Networked kw/kwh Transducers

Enercept H8035/H8036 Modbus Energy Meter Networked kw/kwh Transducers POWER MONITORING INSTALLATION GUIDE Enercept H8035/H8036 Modbus Energy Meter Networked kw/kwh Transducers US Patent No. 6,373,238 Installer's Specifications Input Voltage 208 to 480 VAC Number of Phases

More information

S401 THE NEW STANDARD FOR MODBUS INDICATORS. Minimum wiring, maximum flexibility. Only 2 wires and 20 measures all in one display

S401 THE NEW STANDARD FOR MODBUS INDICATORS. Minimum wiring, maximum flexibility. Only 2 wires and 20 measures all in one display S401 THE NEW STANDARD FOR MODBUS INDICATORS Minimum wiring, maximum flexibility. Only 2 wires and 20 measures all in one display INDEX 1. Introduction 4 1.1 Interfaces and cabling 4 1.2 Graphics and visualization

More information

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website:

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: 805HP Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: www.anyload.com Email: info@anyload.com TABLE OF CONTENTS 1. Introduction and Product Features 3 2.

More information

Analog signal to RS485 or RS232 Converter, A/D Converter

Analog signal to RS485 or RS232 Converter, A/D Converter Analog signal to RS485 or RS232 Converter, A/D Converter Features: Analog signal acquisition, isolated RS-485/232 output 12-bit AD converter, testing accuracy>0.1% Can be remotely reconfigured for modules

More information

smart meters... 6 panel meters... 7 field displays... 8 display types loop powered displays TRANSMITTERS & CONVERTERS...

smart meters... 6 panel meters... 7 field displays... 8 display types loop powered displays TRANSMITTERS & CONVERTERS... 2 content DISPLAYS... 4 smart meters... 6 panel meters... 7 field displays... 8 display types... 10 loop powered displays... 12 TRANSMITTERS & CONVERTERS... transmitters... 15 converters... 18 serial data

More information

IP67 VERSION BOX (on request) 8+3 PG9 cable glands-plugs. 8+3 PVC fittings for sheath

IP67 VERSION BOX (on request) 8+3 PG9 cable glands-plugs. 8+3 PVC fittings for sheath Digital/analog weight transmitter suitable for back panel mounting on Omega/DIN rail or junction box for field mounting (on request box versions). Weighing system with 8 independent reading channels with

More information

EXCELL PRECISION CO., LTD.

EXCELL PRECISION CO., LTD. Excell Precision Limited 24. All rights reserved Worldwide. The information contained herein is the property of Excell Precision Limited and is supplied without liability for errors or omissions. No part

More information

805HP. Handheld Digital Weight Indicator User s Manual (v1703) Anyload Transducer Co. Ltd Website:

805HP. Handheld Digital Weight Indicator User s Manual (v1703) Anyload Transducer Co. Ltd Website: 805HP Handheld Digital Weight Indicator User s Manual (v1703) Anyload Transducer Co. Ltd Website: www.anyload.com Email: info@anyload.com TABLE OF CONTENTS 1. Introductions and Features 2 2. Safety Recommendations

More information

iopro Mirrored IO System

iopro Mirrored IO System Ph: (877) 343-8467 Fax: (800) 303-5381 Email: info@ioselect.com iopro Mirrored IO System Quick Start Guide (Ver. 6) www.ioselect.com Page 1 Introduction This document will cover how to use the iopro family

More information

NetBiter I/O Extender User Manual

NetBiter I/O Extender User Manual User Manual Part no. 0920-9999-009 IntelliCom Innovation AB Pilefeltsgatan 73 SE-302 50 Halmstad SWEDEN Phone +46 35 17 29 90 Fax +46 35 17 29 09 email info@intellicom.se www www.intellicom.se Revision

More information

C500 Series Data Sheet

C500 Series Data Sheet C500 Series Data Sheet - 16 x 350Ω load cells - AC and DC versions - Ethernet and USB host and slave standard - 10,000d @ 0.5 µv/d - 8 set points (option) - Analog module with 2 isolated outputs (option)

More information

TR150 Digital Readout Unit SL755. Impact Test Equipment Ltd & User Guide. User Guide

TR150 Digital Readout Unit SL755. Impact Test Equipment Ltd   &   User Guide. User Guide TR150 Digital Readout Unit SL755 Impact Test Equipment Ltd www.impact-test.co.uk & www.impact-test.com User Guide User Guide Impact Test Equipment Ltd. Building 21 Stevenston Ind. Est. Stevenston Ayrshire

More information

The LT1300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

The LT1300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. LT1300 Wall Mount Load Cell Indicator Datasheet English 1.00 Introduction The LT1300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. The high

More information

Y800 Plus Frequency, Rate & Period Meter With dual, independently field-scalable channels

Y800 Plus Frequency, Rate & Period Meter With dual, independently field-scalable channels Y800 Plus Frequency, Rate & Period Meter With dual, independently field-scalable channels Description Features Frequencies from 0.005 Hz to 1 MHz 6-digit resolution at update rates up to 25/s Selectable

More information

Wall-/Pipe Mounted Universal Process Indicator

Wall-/Pipe Mounted Universal Process Indicator Data Sheet SS/_8 Wall-/Pipe Mounted Universal Process Indicator High visibility LED display the clearest view of your process status 0.1% measurement accuracy precise indication of process measurement

More information

IPM650 Intelligent Panel-Mount Display

IPM650 Intelligent Panel-Mount Display Quick Start Guide IPM650 Intelligent Panel-Mount Display Sensor Solutions Source Load Torque Pressure Multi Component Calibration Instruments Software www.futek.com Getting Help TECHNICAL SUPPORT For more

More information

Gateway 1400 Reference Manual

Gateway 1400 Reference Manual Profibus-DP Gateway 1400 Reference Manual Copyright All Rights Reserved. No part of this document may be copied, reproduced, republished, uploaded, posted, transmitted, distributed, stored in or introduced

More information

Digital Indicator Solutions

Digital Indicator Solutions Digital Indicator Solutions Loop-Powered Attachable Compact Attachable Loop-Powered Smart Compact System Loop-Powered Compact Smart System Intelligent Smart System "Intelligent" Options Dual & Display

More information

CHAPTER 1. Introduction Introduction 3

CHAPTER 1. Introduction Introduction 3 Technical & User Manual Weight Indicator: SMIT-3015 Manufactured By: Samyak Instrumentation Pvt.Ltd. F-4, Memnagar Complex, Opp.Petrol Pump, Memnagar Village, Ahmedabad, India-380052. Phone: +91-79-27495500/5600,

More information

Process displays For current and voltage

Process displays For current and voltage Features Voltage input TRMS-AC/DC up to 600 V Current input AC/DC 1 A, 5 A and shunt (precision resistor) 60 or 100 mv With 2 or 4 limits Display range can be linearised Min, Max, Hold functions 4 20 ma

More information

RS 485 Mini Modbus 1AO

RS 485 Mini Modbus 1AO RS 485 Mini Modbus 1AO Version 1.0 14/08/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained

More information

S1MMmA500VM S1MMmA500VLM S1MMmA500VHM. Technical data. 3-phase energy meter with universal current input

S1MMmA500VM S1MMmA500VLM S1MMmA500VHM. Technical data. 3-phase energy meter with universal current input 3-phase energy meter with universal current input Equivalent to class 0,5S (KWh) of E6053- Equivalent to class 0,5S (KVARh) of E6053-4 Accuracy ±0,5% RDG Universal input for current measurement Energy

More information

TRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

TRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES Digital Panel Indicators A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input Analogue Output

More information

The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement Acquisition Measurement Control The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input

More information

C160 Wall-/Pipe Mounted Universal Process Indicator

C160 Wall-/Pipe Mounted Universal Process Indicator Data sheet DS/ EN Rev. I Wall-/Pipe Mounted Universal Process Indicator reliable process indicator, wherever it s needed High visibility LED display the clearest view of your process status 0.1% measurement

More information

FT2 View Instruction Manual

FT2 View Instruction Manual 399 Reservation Road, Marina, California U.S.A Ph: (831) 384-4300 Fax: (831) 384-4312 www.foxthermalinstruments.com 2006 Fox Themal Instruments, Inc. Introduction: The FT2 View application software is

More information

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual. Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-RTD6 Installation Guide. The 2300 series stations are designed to

More information

POWERWISE INDAC SETUP MANUAL

POWERWISE INDAC SETUP MANUAL POWERWISE INDAC SETUP MANUAL REVISION: 2.2 INDAC & EMONITOR GATEWAY An installation guide for the PowerWise indac. 2013 PowerWise, Inc. This manual may contain proprietary information about the product

More information

SY021 Portable Load/Force Meter User instructions

SY021 Portable Load/Force Meter User instructions SY021 Portable Load/Force Meter User instructions Relates to firmware version 5.2 INTRODUCTION The SY021 is a portable load meter, which can indicate the load present on any attached cell. A dual channel

More information

T1K MODBUS Base Controller Specifications

T1K MODBUS Base Controller Specifications Base Controller 1 2 In This Chapter.... Base Controller Setting the DIP Switches Setting the Rotary Address Switches Port Pin out and Wiring RJ12 Serial Port Pin out and Wiring 2 2 Base Controller General

More information

10 DIGITAL MICRO-PROCESS TOTALIZER METER with ALARMS / ANALOG OUTPUT / PULSE OUTPUT / RS-485. T Total Alarm x 1 + FRONT PANEL & KEY FUNCTIONS

10 DIGITAL MICRO-PROCESS TOTALIZER METER with ALARMS / ANALOG OUTPUT / PULSE OUTPUT / RS-485. T Total Alarm x 1 + FRONT PANEL & KEY FUNCTIONS 0 DIGITAL MICRO-PROCESS TOTALIZER METER with ALARMS / ANALOG OUTPUT / PULSE OUTPUT / RS-85 + FEATURES! Accuracy: + - 0.00% F.S. High brightness 0." LED; Rate of display range: 0~99999 Rate / Total decimal

More information

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION Revised Last Revised by Alex Messner This page was intentionally left blank. Table of Contents 1 Overview... 2 2 User Interface... 3 2.1 LEDs... 3 2.2 Buttons...

More information

ACTIONI/Q Q498. DC Powered DC Input Field Configurable Isolator with Math Functions

ACTIONI/Q Q498. DC Powered DC Input Field Configurable Isolator with Math Functions ACTIONI/Q Q498 DC Powered DC Input Field Configurable Isolator with Math Functions Q498-0000 Provides 2 Isolated Analog Inputs, 1 Analog Output & 1 Frequency Output, as well as a Discrete Input & Output

More information

Operating Manual. Dynisco /8 DIN Indicator Concise Product Manual

Operating Manual. Dynisco /8 DIN Indicator Concise Product Manual Dynisco 1490 1/8 DIN Indicator Concise Product Manual 59476-9 Operating Manual -1- CAUTION: Installation should be only performed by technically competent personnel. Local Regulations regarding electrical

More information

JSD81 series products are based on SCM's intelligent monitoring and control system, users set the calibration value,

JSD81 series products are based on SCM's intelligent monitoring and control system, users set the calibration value, 8-Channel Analog Signals to RS485/232 Converter(A/D Converter JSD81 series) Features: 8-CH analog signal acquisition/isolation,rs-485/232 output 24-bit AD converter, testing accuracy>0.05% Can Program

More information

Industrial 1-port RS422/485 Modbus Gateway IMG-110T

Industrial 1-port RS422/485 Modbus Gateway IMG-110T Industrial 1-port RS422/485 Modbus Gateway IMG-110T Presentation Outlines Product Positioning Applications Product Overview Comparison Product Benefits Appendix Product Features 2 / 43 Product Positioning

More information

/8 DIN Universal Process Indicator

/8 DIN Universal Process Indicator Data Sheet SS/_ High visibility LED display the clearest view of your process status.% measurement accuracy precise indication of process measurement Analog and relay outputs as standard alarm and retransmission

More information

TLB4 TLM8. ERDE-Elektronik AB - Spikgatan Vellinge TLM8den.

TLB4 TLM8. ERDE-Elektronik AB - Spikgatan Vellinge TLM8den. Digital/analog weight transmitter suitable for back panel mounting on Omega/DIN rail or junction box for eld mounting (on request box versions). Weighing system with 8 independent reading channels with

More information

LCp-100 Weight Indicator/Transmitter

LCp-100 Weight Indicator/Transmitter Precision Force and Weight Measurement Technologies LCp-100 Weight Indicator/Transmitter Process Applications: Mix Tanks Blenders Reactors Product Description Hardware Features 1 Million Count Resolution,

More information

BASE LOAD UNLOAD 3 PRODUCTS 6 PRODUCTS 14 PRODUCTS Multiprogram

BASE LOAD UNLOAD 3 PRODUCTS 6 PRODUCTS 14 PRODUCTS Multiprogram ATEX/IECEx version (on request) PVC end-fittings for sheath (on request) PROGRAM BASE LOAD UNLOAD 3 PRODUCTS 6 PRODUCTS 14 PRODUCTS Multiprogram External 8-relay modules included. ON REQUEST -B -C -S -3-6

More information

BASE LOAD UNLOAD 3 PRODUCTS 6 PRODUCTS 14 PRODUCTS Multiprogram

BASE LOAD UNLOAD 3 PRODUCTS 6 PRODUCTS 14 PRODUCTS Multiprogram PROGRAM BASE LOAD UNLOAD 3 PRODUCTS 6 PRODUCTS 14 PRODUCTS Multiprogram External 8-relay modules included W200 W200-C W200-S W200-3 W200-6 W200-14 ON REQUEST W200-MU CERTIFICATIONS OIML R76:2006, class

More information

WTX120. Legal-for-trade industrial weighing terminal. Special features. Data sheet

WTX120. Legal-for-trade industrial weighing terminal. Special features. Data sheet WTX120 Legal-for-trade industrial weighing terminal Special features - Connection of up to 8 SG load cells (350 ohm) via plug terminals - Display resolution up to 30,000, legal for trade up to 10,000e

More information

LD-RTD / LD-TC Temperature Controller

LD-RTD / LD-TC Temperature Controller 1 LD-RTD / LD-TC Temperature Controller Available in either an RTD model or a thermocouple model, these units accept all common temperature probe types, and offer a technically advanced, but cost effective

More information

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X Modular solution based on the combination of two units: VMU-E analysis unit and VMU-X universal power supply and RS485 communication unit.

More information

User Manual. cmt-svr Startup Guide

User Manual. cmt-svr Startup Guide User Manual cmt-svr Startup Guide Table of Contents Chapter 1 Overview... 1 1.1 Specification... 1 1.2 Dimensions... 2 1.3 Connector pin designations... 3 1.4 USB host port and SD card slot... 3 1.5 Ethernet

More information

EDX-10 Series. Compact Recording System

EDX-10 Series. Compact Recording System 3-51 EDX-10 Series Compact Recording System Compact & lightweight, with a simple configuration, all channels synchronous 20 khz high-speed sampling (For 4 channels) Control Unit EDX-10B A unit controls

More information

PT2060 Monitor. PT2060/91 SIM System Interface Module. Specifications. Electrical. Messtechnik

PT2060 Monitor. PT2060/91 SIM System Interface Module. Specifications. Electrical. Messtechnik PT2060/ System Interface Module ProvibTech s PT2060/ module is a communication and system interface module. This module is used to: module. The two phase reference channels can be used to provide phase

More information

K107A / K107B Half-duplex RS485 serial bus with 3-point insulation

K107A / K107B Half-duplex RS485 serial bus with 3-point insulation 0 0 K0 R THE INTERNATIONAL CERTIFICATION NETWORK EN K0A / K0B Half-duplex RS serial bus with -point insulation General Description The K0A and K0B modules are half duplex serial buses with -point insulation.

More information

Digital Bench Scale. Revision 1.2 September 14, 2000 Contents subject to change without notice.

Digital Bench Scale. Revision 1.2 September 14, 2000 Contents subject to change without notice. Digital Bench Scale Revision 1.2 September 14, 2000 Contents subject to change without notice. Salter Brecknell Weighing Products 1000 Armstrong Drive Fairmont, MN 56031 Tel (800) 637-0529 Tel (507) 238-8702

More information

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector. PM1000 SERIES PLUG-ON DISPLAY BRIGHT LED DISPLAY INDICATION RANGE -999 TO +9999 FITS TO DIN 43650 CONNECTOR PLUG-ON TO ANY TRANSMITTER WITH 4-20MA OUTPUT EASY TO SCALE ON SITE ROBUST DESIGN SET POINT OPTION

More information

/8 DIN Motorized Valve Controller

/8 DIN Motorized Valve Controller Data Sheet SS/_5 Boundless motorized valve controller no need for slidewire feedback; improves reliability Two sealed 5A control relays suitable for direct connection to the valve, reducing installation

More information

RS485 MODBUS Module 8I8O

RS485 MODBUS Module 8I8O Expansion Module 8 digital inputs, 8 digital outputs Version 2.2 12/01/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the

More information

User Manual. cmt-svr Startup Guide

User Manual. cmt-svr Startup Guide User Manual cmt-svr Startup Guide Table of Contents Chapter 1 Overview... 1 1.1 Specification... 1 1.2 Dimensions... 2 1.3 Connector pin designations... 3 1.4 USB host port and SD card slot... 3 1.5 Ethernet

More information

DXp-10 and DXp-15 Weight Transmitter

DXp-10 and DXp-15 Weight Transmitter Precision Force and Weight Measurement Technologies DXp-10 and DXp-15 Weight Transmitter Applica pplications: Inventory Weighing Process Weighing Web Tension Measurement Product Description l Microprocessor

More information

GS100P. Weighing Controller. Contents. Order Codes

GS100P. Weighing Controller. Contents. Order Codes GS100P Weighing Controller 1 This intelligent weighing controller comes precalibrated to suit either a 4-wire or a 6-wire strain gauge input, and has a number of advanced functions designed specifically

More information

FT2 View Instruction Manual

FT2 View Instruction Manual 399 Reservation Road, Marina, California U.S.A. Ph: (831) 384-4300 Fax: (831) 337-5786 www.foxthermalinstruments.com 2006 Fox Thermal Instruments, Inc. 07/19/13 Introduction: The FT2 View application software

More information

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND OleumTechTM TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND MUST BE FAMILIAR WITH LEVEL 1 TRAINING MATERIALS BEFORE MOVING FORWARD Doc ID# 80-6010-001b TABLE OF CONTENTS 1. WHAT IS NEW WRITE IMPORT

More information

Remote I/O Modules EH-RIO2 Series

Remote I/O Modules EH-RIO2 Series Remote I/O Modules EH-RIO2 Series Fieldbus adapter: ProfiNET, EtherCAT, Modubus TCP / RTU, Profibus-DP, DeviceNet Separation of electronics module and terminal block for easy installation and maintenance

More information

WTX110. Legal-for-trade industrial weighing terminal. Special features. Data sheet

WTX110. Legal-for-trade industrial weighing terminal. Special features. Data sheet WTX110 Legal-for-trade industrial weighing terminal Special features - Up to 8 SG load cells can be connected (350 ohms) - Stainless steel housing shapes for desktop and wall mounting or control cabinet

More information

LAUREL. Laureate Dual-Channel Pulse Input Totalizer With Two Independently Scalable Input Channels & Presets ELECTRONICS, INC. Features.

LAUREL. Laureate Dual-Channel Pulse Input Totalizer With Two Independently Scalable Input Channels & Presets ELECTRONICS, INC. Features. Description LAUREL ELECTRONICS, INC. Laureate Dual-Channel Pulse Input Totalizer With Two Independently Scalable Input Channels & Presets Features Frequencies up to 1 MHz Totals stored in non-volatile

More information

Trident and Trident X2 Digital Process and Temperature Panel Meter

Trident and Trident X2 Digital Process and Temperature Panel Meter Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products

More information

Digital Bench Scale. Revision 1.2 August 24, Contents subject to change without notice.

Digital Bench Scale. Revision 1.2 August 24, Contents subject to change without notice. Digital Bench Scale Revision 1. August 4, 000 Contents subject to change without notice. Salter Brecknell Weighing Products 1000 Armstrong Drive Fairmont, MN 56031 Tel (800) 637-059 Tel (507) 38-870 Fax

More information