Why Not Operate Data Centers & Telecom Central Offices at 400 VDC???

Size: px
Start display at page:

Download "Why Not Operate Data Centers & Telecom Central Offices at 400 VDC???"

Transcription

1 Why Not Operate Data Centers & Telecom Central Offices at 400 VDC??? Dennis P. Symanski Senior Project Manager 2009 IBM Power and Cooling Technology Symposium 20-21OCT2009 Rochester, MN

2 Data Center Energy Use in U.S. From: EPA Report to Congress on Server and Data Center Efficiency, It is estimated that this sector consumed about 61 billion kilowatthours (kwh) in 2006 (1.5 percent of total U.S. electricity consumption) for a total electricity cost of about $4.5 billion 2

3 Telecom Central Office Energy Consumption Country Network Energy Consumption % of Country Total Energy Consumption USA Verizon TWh 0.24% Japan NTT Group TWh 1% Italy Telecom Italia TWh 1% France France Telecom- Orange TWh 0.4% Spain Telefonica TWh 0.6% Global electricity consumption of telecom industry estimated at 1%: 164 billion kwh More than the total electricity consumption of Iran, Turkey or Sweden Enough to power 1.6 million homes million tons of CO2 (equivalent to the annual emissions of 29 million cars!) Source: Emerson Network Power and NTT 3

4 Heat Density Trends The Uptime Institute Reprinted with permission of the Uptime Institute Inc. from a white paper titled Heat Density Trends in Data Processing, Computer Systems, and Telecommunications Equipment. 4

5 Data Centers versus Telecom Central Offices Similarities Both installing lots of IT equipment Both adding new services & capabilities (Central Offices looking more & more like Data Centers) Both are running out of power & cooling & space Differences 200 to 240 VAC operation versus 48 VDC Commercial-grade equipment versus NEBS-certified equipment Modern newer installations versus old/downtown installations 5

6 400 VDC Data Center Demonstration (2006) EPRI participated in this 400 VDC data center demonstration showing 7% efficiency improvement over state-of-the-art AC power distribution 28% efficiency improvement over typical AC power distribution 6

7 State-of-the-Art 208 VAC versus 400 VDC 480V 3φ AC AC/DC DC/AC UPS PDU 208V 1φ AC Rack AC/DC Server PSU DC/DC 12V VR VR Fans Electr. loads 94% x 96% x 93% x 92% = 77% BLD 480V G PWR 3φ AC AC/DC UPS 400V DC PDU Rack 400V DC Server DC/DC PSU 12V VR VR Fans Electr. loads 97.5% x 100% x 95% x 92% = 85% Source: Delta Products Corp 7

8 Why do 400 VDC at all??? Increased Efficiency Already demonstrated Better Space Utilization Most equipment will be smaller Increased Reliability (Fewer Components) Expected & to be confirmed over time Decreased Cost (Fewer Components) Once volume is ramped up 8

9 400 VDC Power Distribution EPRI is developing a specification for DC power distribution with Intel and others. 9

10 400 VDC Power Supplies Power Supply Specification Exactly the same as the existing spec for 100 to 240 VAC or 200 to 240 VAC (Worldwide Safety & EMC Standards) EXCEPT Input voltage 300 to 400 VDC and Input connector rated at 400 VDC 10

11 400 VDC Facilities Power Distribution Facilities Specification Need Safety Agency (e.g. UL) listing on all new 400 VDC products (Rectifier/DC UPS/PDU/Busway/Fuse/Breaker/Power Strip/Connectors) +/- 200 VDC rating (400 VDC Center-Tapped) Operating tolerance: +0%, -25% All loads connected between +200 and -200 VDC No loads are to be connected +200 to ground or -200 VDC to ground 11

12 DC Voltage Why 400 VDC??? (Sweet Spot) IEC 900 BS (U.K.) 750 Ordinance (JPN) 600 NEC(U.S.) (192cell) 374 (168cell) 321 (144cell) 575 Validus 380 DC Demo (Sun) 300 NEDO PJ. (Sendai) Operating bulk - voltage 373(U.K.) 354(EU) 311(JPN) large Distribution efficiency Cable Distance 0 Law, Regulation, Code, and Stds. Distributied Telecom trends Gen. (Number of Cell) Demos (Reference) Rating voltage of parts and elements 186(U.S.) AC system voltages ( Peak ) small Benefit of HVDC system From NTT-Facilities Survey 12

13 400 VDC Components 13

14 400 VDC Components (Testing) Hole burnt through electrical contact point of female contact Damage distributed along wiping surface of male contact Anderson Power Products Hot Mating Test IEC 320 Plug and Receptacle 250 mating/disconnect cycles, VDC with 240 amp peak inrush current 14

15 400 VDC Components (Testing) The Anderson Power Products, Power Pole contact system is designed such that arcing damage is limited to sacrificial leading areas of the contact. The arcing damage does not compromise the integrity of the point of electrical contact once full connector mating is achieved. Damage at leading edge of contact Damage at leading edge of contact No damage at electrical contact point 15

16 400 VDC Components 16

17 400 VDC Components Fujitsu Component/NTT Facilities Rack Power Strip 17

18 Organizations Already Involved International Electrotechnical Commission (IEC) European Telecommunications Standards Institute (ETSI) International Telecommunications Union (ITU) Electric Power Research Institute Lawrence Berkeley National Lab The Green Grid DC Power Partners Photovoltaic Industry Electric Car Industry NTT/Orange-France Telecomm/Syracuse Univ/UC San Diego/Korea Telecom/--- 18

19 DC Power Partners 19

20 Together Shaping the Future of Electricity 20

380VDC Data Center Duke Energy Charlotte, NC

380VDC Data Center Duke Energy Charlotte, NC 380VDC Data Center Duke Energy Charlotte, NC Dennis P. Symanski EPRI - Senior Project Manager Silicon Valley Leadership Group 2011 Data Center Efficiency Summit 18NOV2011 IBM - San Jose, CA 380VDC Data

More information

380VDC Data Center At Duke Energy

380VDC Data Center At Duke Energy 380VDC Data Center At Duke Energy Dennis P. Symanski EPRI - Senior Project Manager Curtis Watkins Duke Energy - Senior Project Manager Emerging Technology (ET) Summit November 9, 2010 Sacramento, CA From

More information

DC Power Standards. Brian Fortenbery Energy Efficiency Group Power Delivery and Utilization Sector EPRI

DC Power Standards. Brian Fortenbery Energy Efficiency Group Power Delivery and Utilization Sector EPRI DC Power Standards Brian Fortenbery Energy Efficiency Group Power Delivery and Utilization Sector EPRI Data Center Power Delivery System UPS 85-92% Power Dist 98-99% Power Supply 68-72% DC/DC 78-85% The

More information

HVDC Innovation, XECHNO Power & Fresh HVDC

HVDC Innovation, XECHNO Power & Fresh HVDC 1 HVDC Innovation, XECHNO Power & Fresh HVDC Energy Saving Technology for the Data Center Green Consulting Business Unit Solution Business Division NTT DATA INTELLILINK Corp. Problems facing data centers:

More information

DC The Power to Change Buildings A Non-profit Alliance Driving Open Standards to Direct Current Power Distribution in Buildings

DC The Power to Change Buildings A Non-profit Alliance Driving Open Standards to Direct Current Power Distribution in Buildings DC The Power to Change Buildings A Non-profit Alliance Driving Open Standards to Direct Current Power Distribution in Buildings What is the EMerge Alliance? Not-for-profit 501c -Part 6 Open application

More information

Starline DC Solutions

Starline DC Solutions Starline DC Solutions 380vdc Revolution or Evolution? 380Vdc Data Center Architecture Advancements Timothy E. Martinson Universal Electric Director StarLine DC Solutions Division Emerge Alliance Chair

More information

Powering Compute Platforms in High Efficiency Data Centers. Annabelle Pratt, Pavan Kumar, Kevin Bross, Tomm Aldridge

Powering Compute Platforms in High Efficiency Data Centers. Annabelle Pratt, Pavan Kumar, Kevin Bross, Tomm Aldridge Powering Compute Platforms in High Efficiency Data Centers Annabelle Pratt, Pavan Kumar, Kevin Bross, Tomm Aldridge Agenda Defining a power-efficient efficient data center Improving power delivery efficiency

More information

High Voltage Direct Current Power Solutions for Data Centers

High Voltage Direct Current Power Solutions for Data Centers High Voltage Direct Current Power Solutions for Data Centers Professor: Dr. Danny Silver Acadia University Student Name: Jim Nasium Published: April 10 th, 2011 1. Introduction As the demand on data centers

More information

Extending Energy Efficiency. From Silicon To The Platform. And Beyond Raj Hazra. Director, Systems Technology Lab

Extending Energy Efficiency. From Silicon To The Platform. And Beyond Raj Hazra. Director, Systems Technology Lab Extending Energy Efficiency From Silicon To The Platform And Beyond Raj Hazra Director, Systems Technology Lab 1 Agenda Defining Terms Why Platform Energy Efficiency Value Intel Research Call to Action

More information

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; 4 0 0 V D C p o w e r f e e d s o l u t i o n Juha Klemola / HW Architect / Nokia Introduction to the challenge Datacenter

More information

System Specifications

System Specifications System s Environmental s, page 1 Switch Dimensions, page 1 Switch and Module Weights and Quantities, page 2 Transceiver and Cable s, page 2 Switch Power Input Requirements, page 2 Power s, page 3 Power

More information

Rack Centric - High Voltage Distribution

Rack Centric - High Voltage Distribution Rack Centric - High Voltage Distribution Randy Malik Senior Technical Staff Member Research Triangle Park Raleigh, North Carolina Email: Rmalik@us.ibm.com Data Center Application Typical Data Center Energy

More information

System Specifications

System Specifications Environmental s, on page 1 Switch Dimensions, on page 1 Switch and Module Weights and Quantities, on page 2 Transceiver and Cable s, on page 2 Switch Power Input Requirements, on page 2 Power s, on page

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

System Specifications

System Specifications System s Environmental s, page 1 Switch Dimensions, page 1 Switch and Module Weights and Quantities, page 2 Transceiver and Cable s, page 2 Switch Power Input Requirements, page 2 Power s, page 3 Power

More information

Addressing Data Center Efficiency Lessons Learned From Process Evaluations of Utility Energy Efficiency Programs

Addressing Data Center Efficiency Lessons Learned From Process Evaluations of Utility Energy Efficiency Programs Addressing Data Center Efficiency Lessons Learned From Process Evaluations of Utility Energy Efficiency Programs IEPEC Conference Session 16: Industrial Strength Evaluation June 10, 2010 AJ Howard Energy

More information

Pros and Cons of Various DC Distribution Architectures

Pros and Cons of Various DC Distribution Architectures Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification

More information

Server Technology Inc.

Server Technology Inc. Server Technology Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2011-Sept-22 Headquarters Server Technology, Inc. 1040 Sandhill

More information

LED Indicator. Class I

LED Indicator. Class I FWC100 Series 100 Watt ITE Desktop Power Supply High Efficiency: Level V High Power Density 4.2W/in3 Lifetime Expectation >5 years Hold up Time >48ms at full load Power Factor Correction EISA and CEC Compliant

More information

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working

More information

DATA CENTER MEETING ALL POWER REQUIREMENTS IN THE DATA CENTER

DATA CENTER MEETING ALL POWER REQUIREMENTS IN THE DATA CENTER DATA CENTER MEETING ALL POWER REQUIREMENTS IN THE DATA CENTER DO YOU HAVE THE POWER TO GROW YOUR DATA CENTER BUSINESS? Data center operation is a no compromise business. Customers are buying peace-of-mind

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Planning, Implementing and Application of Cabinet Power Distribution Units White Paper STI-100-007 Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United

More information

MSR 2400W. Multi purpose Power System for Telecom and Industrial Applications. Nominal Output Voltage. Voltage Setting Range

MSR 2400W. Multi purpose Power System for Telecom and Industrial Applications. Nominal Output Voltage. Voltage Setting Range MSR 2400W Multi purpose Power System for Telecom and Industrial Applications 2400 W modular system All voltages available 0 144VDC per module U and I adjustable from 0 to max value Hot-swap plug-in modules

More information

CPX8216 Series CompactPCI High Availability System

CPX8216 Series CompactPCI High Availability System CPX8216 Series CompactPCI High Availability System The Emerson CPX8216 system is a dual 8-slot, 12U, carrier-grade platform with a CompactPCI backplane. n Dual 8-slot backplane (CPX8216 models) or backplane

More information

Technical Specifications

Technical Specifications Technical s This appendix lists the technical specifications for the Cisco UCS 5108 server chassis and includes the following sections: KVM Cable, page 1 Chassis s, page 2 Environmental s, page 3 s for

More information

Dynamic Power Management in the Data Center

Dynamic Power Management in the Data Center Dynamic Power Management in the Data Center IBM Power and Cooling Symposium Raleigh, NC 04 October 2007 Bharat S. Shah Emerson Network Power Bharat.Shah@EmersonNetworkPower.com Agenda Power Management

More information

Aarlogic TER-GX910. Product description. Rev.9 17/03/2013

Aarlogic TER-GX910. Product description. Rev.9 17/03/2013 Aarlogic TER-GX910 Product description Rev.9 17/03/2013 Contents 1 Overview... 3 2 Hardware Interface Description... 3 2.1 Main features of the TER-GX910... 3 2.2 Hardware block diagram... 4 3 Interface

More information

GT- IRDM-9603 Product description Rev. 2 17/06/2014

GT- IRDM-9603 Product description Rev. 2 17/06/2014 GT- IRDM-9603 Product description Rev. 2 17/06/2014 1 1. Overview The GT- IRDM- 9603 is a complete Satellite Terminal solution for Satellite applications. Based on IRIDIUM 9603 module. 2. Hardware Interface

More information

Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices?

Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices? This is a photographic template your photograph should fit precisely within this rectangle. Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and

More information

LFWLP225 SERIES 225 Watt Open Frame Power Supply Measures: 4.00 x 2.00 x 1.00

LFWLP225 SERIES 225 Watt Open Frame Power Supply Measures: 4.00 x 2.00 x 1.00 Features 4 x 2 x 1 Inches Form factor 225 Watts with Forced Air Cooling Efficiencies upto 94% -40 to 70 degree operating temperature* 12V / 0.5A Fan Output, Thermal Shut-Down feature 3.37m Hours, Telcordia

More information

AC, DC and Custom Power Supplies

AC, DC and Custom Power Supplies AC, DC and Custom Power Supplies High Efficiency Power Solutions DC-DC CONVERTERS Range Power Amps Max / Outputs Input Range Output (VDC) Dimensions H x W x D mm (inches) F501 500W 40 36-75 48, 28, 24,

More information

Friedrich Smaxwil CEN President. CEN European Committee for Standardization

Friedrich Smaxwil CEN President. CEN European Committee for Standardization Friedrich Smaxwil CEN President CEN European Committee for Standardization www.cen.eu www.cencenelec.eu Friedrich Smaxwil, CEN President 1. Standards & standardization 2. CEN s role in European Standardization

More information

Compute Engineering Workshop March 9, 2015 San Jose

Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud

More information

EZ864 G. Telit Cellular GSM/UMTS Engine. Hardware guide Version: Update: 27. APR.2009 EZ864 G_Hardware Guide_V

EZ864 G. Telit Cellular GSM/UMTS Engine. Hardware guide Version: Update: 27. APR.2009 EZ864 G_Hardware Guide_V EZ864 G Telit Cellular GSM/UMTS Engine Hardware guide Version: 04.01 Update: 27. APR.2009 EZ864 G_Hardware Guide_V4. - 1 - Hardware Interface Description 1. Hardware Features of the EZ864 G Feature Implementation

More information

ENGINEERING SPECIFICATION 90 WATT POWER SUPPLY PART NUMBER PA P1

ENGINEERING SPECIFICATION 90 WATT POWER SUPPLY PART NUMBER PA P1 ENGINEERING SPECIFICATION 90 WATT POWER SUPPLY PART NUMBER PA-1900-32P1 EFFECTIVE DATE : Nov. 26, 2012 MODEL: PA-1900-32P1 SPECIFICATION REV :B PAGE 1 OF 13 REV. ITEM DESCRIPTIONS OF CHANGE CHANGED REF.

More information

Universal, Scalable Factorized Power Architecture for New Processors and Memory Loads

Universal, Scalable Factorized Power Architecture for New Processors and Memory Loads Universal, Scalable Factorized Power Architecture for New Processors and Memory Loads Uptime Institute, New York, NY, May 2010 Abstract: HPC (High Performance Computing) processors and memory loads continue

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Revision 1 Executive Summary A new approach to power distribution for high density

More information

PRODUCT FEATURES AND ADVANTAGES

PRODUCT FEATURES AND ADVANTAGES Flatpack2 24/1800 HE 24VDC Rectifier/Converter Modules The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out. With efficiency up to 96.2%, the losses have been

More information

Power Consumption in the Data Center. Green Concepts

Power Consumption in the Data Center. Green Concepts Power Consumption in the Data Center Green Concepts What is your Energy Saving Strategy? Buying Energy Efficient Equipment (EEE) 46% Say Yes to Green Technology Information Week Research Green Data Center

More information

Installation Job Aid for VSP 4450GTX-HT- PWR+

Installation Job Aid for VSP 4450GTX-HT- PWR+ Installation Job Aid for VSP 4450GTX-HT- PWR+ Notices Release 6.1.0.0 NN46251-305 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Installation Instructions

Installation Instructions Installation Instructions (Cat. No. 1794-TBN) 6 1 5 9 4 2 3 10 6 7 8 Component Identification 1 Female flexbus connector 2 Terminal base unit (1794-TBN) 3 Male flexbus connector 4 Keyswitch Set to the

More information

BC Hydro Power Smart Forum Introducing Canada s First Utility IT Energy Conservation Program

BC Hydro Power Smart Forum Introducing Canada s First Utility IT Energy Conservation Program BC Hydro Power Smart Forum Introducing Canada s First Utility IT Energy Conservation Program David Rogers IT Advisor, BC Hydro Power Smart November 17, 2008 IT Energy Management BC Hydro Power Smart Data

More information

Electrical Specifications. Input Current 115 VAC: 1 A max. 230 VAC: 0.5 A max.

Electrical Specifications. Input Current 115 VAC: 1 A max. 230 VAC: 0.5 A max. MLP75 Medical Features 3 x 2 x 1 Inches Form factor 75 Watts Convection Approval to EN60601 3 rd Edition Efficiencies upto 93% -40 to 70 degree operating temperature Dual fusing Thermal Shut-Down feature

More information

Innovative Data Center Efficiency Techniques. Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation

Innovative Data Center Efficiency Techniques. Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation Innovative Data Center Efficiency Techniques Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation 1 Alternate titles.. Crisis or opportunity? Never build a new data center! Improve

More information

6640A Series Single-Output, 200 W DC Power Supplies, GPIB

6640A Series Single-Output, 200 W DC Power Supplies, GPIB 6640A Series Single-Output, 200 W DC Power Supplies, GPIB Data Sheet Speed and accuracy for test optimization Fast, low-noise outputs Analog control of output voltage and current Fan-speed control to minimize

More information

LFWLP350 SERIES 350 Watt Open Frame Power Supply Measures: 5.00 x 3.00 x 1.00

LFWLP350 SERIES 350 Watt Open Frame Power Supply Measures: 5.00 x 3.00 x 1.00 Features 5 x 3 x 1 Inches Form factor 350 Watts with Forced Air Cooling & 200 Watts Convection Cooling Efficiencies upto 94% -40 to 70 degree operating temperature* 12V / 0.5A Fan Output, Thermal Shut-Down

More information

PS2328 Integrated Power. System

PS2328 Integrated Power. System PS2328 Integrated Power System 1 Power System consists of: CONTROL / EXPANSION MODULE One rack (Power Supply Housing). Two identical 48V @ 2000W (1+1 redundant) or Two identical 1500W (1+1 redundant) or

More information

MSR 2400R. Rugged Power System for Military and Heavy Duty Applications

MSR 2400R. Rugged Power System for Military and Heavy Duty Applications MSR 2400R Rugged Power System for Military and Heavy Duty Applications 2400 W modular power system Power supply or battery charging systems Parallel n+1 connection, up to 90A Series connection, up to 360VDC

More information

RAILWAY & METRO MEETING ALL POWER REQUIREMENTS ALONG THE TRACK

RAILWAY & METRO MEETING ALL POWER REQUIREMENTS ALONG THE TRACK RAILWAY & METRO MEETING ALL POWER REQUIREMENTS ALONG THE TRACK do you have the power to take your raıl servıce ınto the future? Safety, timeliness and efficiency are the hallmarks of high quality train

More information

GT- HE910-EUD. Product description Rev. 8 21/02/ Overview

GT- HE910-EUD. Product description Rev. 8 21/02/ Overview GT- HE910-EUD Product description Rev. 8 21/02/2013 1. Overview The GT-HE910-EUD is a complete Cellular Terminal solution for GSM/UMTS applications. Based on Telit HE910-EUD module. 1 Hardware Interface

More information

TELCO. Tomi Männikkö/HW Architect, Datacenter R&D/ Nokia

TELCO. Tomi Männikkö/HW Architect, Datacenter R&D/ Nokia TELCO EDGE SERVER AND CHASSIS Tomi Männikkö/HW Architect, Datacenter R&D/ Nokia Open edge chassis overview Key specifications 3U, 19 mountable (EIA-310 compatible) 130.6 x 440 x 430 mm (H x W x D) 1U and

More information

Albatros 2 Grid supervision module / PSU User manual. AVS76.39x/309. Infrastructure & Cities. Edition 2.1

Albatros 2 Grid supervision module / PSU User manual. AVS76.39x/309. Infrastructure & Cities. Edition 2.1 s Infrastructure & Cities Albatros 2 Grid supervision module / PSU User manual AVS76.39x/309 Edition 2.1 CE1U2331en_02 03.12.2012 Building Technologies Siemens Switzerland td Infrastructure & Cities Sector

More information

3299 Rack Mount. Product Highlights. Multifunctional BypassP 2 Segment. Switching Fabric

3299 Rack Mount. Product Highlights. Multifunctional BypassP 2 Segment. Switching Fabric 3299 Rack Mount The 3299 is part of the BypassP 2 product line, providing 1Gb bypass and active tap versatility and multi-functionality. Figure 1: Rackmount populated with two modules with dual fiber bypass

More information

KUANTECH (SHEN ZHEN) COMPANY LIMITED KSAFD W1UK

KUANTECH (SHEN ZHEN) COMPANY LIMITED KSAFD W1UK 1 GENERAL... 2 1.1 Description... 2 2 INPUT REQUIREMENTS... 2 2.1 Input Conditions... 2 2.2 AC Inrush Current... 2 3 OUTPUT REQUIREMENTS... 2 4 MECHANICAL... 3 4.1 Enclosure And Layout... 3 4.2 Input and

More information

LFMWLP225 SERIES 225 Watt Open Frame Power Supply Measures: 4.00 x 2.00 x 1.00

LFMWLP225 SERIES 225 Watt Open Frame Power Supply Measures: 4.00 x 2.00 x 1.00 Features 4 x 2 x 1 Inches Form factor 225 Watts with Forced Air Cooling Approval to EN60601 3 rd Edition Efficiencies upto 94% -40 to 70 degree operating temperature* Dual fusing 12V / 0.5A Fan Output,

More information

CAN enabled The retifier can be monitored and controlled through analogue signals. It is also equipped with a CAN signal bus.

CAN enabled The retifier can be monitored and controlled through analogue signals. It is also equipped with a CAN signal bus. D CAR0948TN -48V/850W rectifier Product Features High power density: 19.2W / inch delta; 1160W/L Constant output power Fits in 19 high, ETSI compliant Wide input range (90VAC 280VAC) Outdoor operating

More information

Energy efficiency management and environmental impact assessment for ICTs

Energy efficiency management and environmental impact assessment for ICTs http://eustandards.in/ Energy efficiency management and environmental impact assessment for ICTs Beniamino Gorini (ETSI TC-EE chairman) 2 Contents What is required to define sustainable ICT products/networks/services

More information

Prisma II Platform. Optoelectronics

Prisma II Platform. Optoelectronics Optoelectronics Prisma II Platform Description In optical transmission systems, the network platform forms the foundation of the product family. The Prisma II platform provides network operators with the

More information

HYDRO X Series 450W / 550W / 650W

HYDRO X Series 450W / 550W / 650W Introduction FSP Hydro X series power supplies are 80 PLUS Gold certified, unique ventilation hole design and built with premium components, to provide excellent cooling and quiet performance. With all

More information

CISCO AC/DC POWER SOLUTION FOR USE WITH CISCO OPTICAL PLATFORMS

CISCO AC/DC POWER SOLUTION FOR USE WITH CISCO OPTICAL PLATFORMS DATA SHEET CISCO AC/DC POWER SOLUTION FOR USE WITH CISCO OPTICAL PLATFORMS The Cisco AC/DC Power Solution provides a scalable platform for the delivery of DC power to equipment-installation sites that

More information

How Huawei s Solutions Address the Challenges of Powering ICT Network

How Huawei s Solutions Address the Challenges of Powering ICT Network How Huawei s Solutions Address the Challenges of Powering ICT Network www.huawei.com Environmental Protection Digital Divide Supply Chain Employee Community Support Reducing environmental impact throughout

More information

Green IT: reduce energy costs and improve service levels with virtualization Bob Good, Manager - Systems Engineers August 2009 MISA Fall Conference

Green IT: reduce energy costs and improve service levels with virtualization Bob Good, Manager - Systems Engineers August 2009 MISA Fall Conference Green IT: reduce energy costs and improve service levels with virtualization Bob Good, Manager - Systems Engineers August 2009 MISA Fall Conference Current State of the Data Center 2 Typical x86 Through

More information

Power Supply Options for Helium-Neon Lasers

Power Supply Options for Helium-Neon Lasers Power Supply Options for Helium-Neon Lasers www.lumentum.com Data Sheet All Lumentum helium-neon power supplies provide a highly regulated constant current output, allowing for excellent optical stability

More information

SLI 15 INVERTER SERIES, 1500 W

SLI 15 INVERTER SERIES, 1500 W SLI 15 INVERTER SERIES, 1500 W FEATURES DESCRIPTION New, compact design: 1U height x 19" width x 14.94" depth; 19" rack-mountable High efficiency: up to 93% True sine wave output Parallelable output with

More information

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters Applications Telecom IT Industrial Safety in compliance with IEC60950:1999, 3 rd edition; EN60950:2000; UL60950, 3 rd edition; CSA Standard C22.2 No.60950-00, 3 rd edition Features New, compact design:

More information

TMF SERIES: 1U HOT-SWAP POWER SYSTEM Single Output 400 Watt Modules with PFC

TMF SERIES: 1U HOT-SWAP POWER SYSTEM Single Output 400 Watt Modules with PFC Call U.S.: +1(954) 346-2442 sales@unipower-corp.com Call U.K.: +44(0) 1903 768200 info@unipower-europe.com TMF SERIES: 1U HOT-SWAP POWER SYSTEM Single 400 Watt Modules with PFC MODULE FEATURES Only 1U

More information

Cisco CRS 16-Slot Chassis Power Systems

Cisco CRS 16-Slot Chassis Power Systems This chapter includes the following sections: Power specifications are provided in Technical Specifications Power Systems Overview, on page 1 Power Component Information Common to the Two Types of Power

More information

Electrical Specifications VAC/390 VDC, Universal (Derate from 100% at 100V AC to 90% at 90V AC)

Electrical Specifications VAC/390 VDC, Universal (Derate from 100% at 100V AC to 90% at 90V AC) WLP350 Industrial Features 5 x 3 x 1 Inches Form factor 350 Watts with Forced Air Cooling & 200 Watts Convection Cooling Efficiencies upto 94% -40 to 70 degree operating temperature* 12V / 0.5A Fan Output,

More information

Installation Job Aid for VSP 4850GTS

Installation Job Aid for VSP 4850GTS Installation Job Aid for VSP 4850GTS Notices Release 6.1.0.0 NN46251-308 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs describe

More information

Safety Standards. Model Number:

Safety Standards. Model Number: 040APS Highlights & Features Compliant to IEC 60601-1 3rd edition IT and medical safety approvals Low earth leakage Current (

More information

QD V LED Tape DMX Driver

QD V LED Tape DMX Driver 4 320W output 1-16ch 24V 4x 5A HP SMD5050 60LED/M MP SMD3528 120LED/M SP SMD3528 60LED/M 60M 60M 20M 30M 60M 110-240VAC Input Voltage IP20 Ingress Protection 24V Output Voltage 4x 5A Max Output Current

More information

Power Supplies GLX40 GLX50 GLX60 GLX110-B GLX110-C GLX120 GLX140-C GLX140-CF GLX150-C GLX17Q-C GLX17S-C GLX200 GLX250-CEF GLX250-CF

Power Supplies GLX40 GLX50 GLX60 GLX110-B GLX110-C GLX120 GLX140-C GLX140-CF GLX150-C GLX17Q-C GLX17S-C GLX200 GLX250-CEF GLX250-CF 3 Power Supplies GL Series: Single & Multi Output Switchers The new GL series provides a broad range of AC/DC power supply solutions that covers power ratings from 25 watts to 500 watts for use in various

More information

040APS12 B MDS. MDS Medical AC-DC Open Frame 12Volt, 40Watt / MDS-040APS12 B ``` Highlights & Features. Safety Standards.

040APS12 B MDS. MDS Medical AC-DC Open Frame 12Volt, 40Watt / MDS-040APS12 B ``` Highlights & Features. Safety Standards. 040APS12 B Highlights & Features Safety Approvals to IEC 60601-1 3rd ed. & IEC 60950-1 Risk management report available Low touch current (

More information

FMP VDC RECTIFIER 42 Amps 2000 Watts

FMP VDC RECTIFIER 42 Amps 2000 Watts FMP20.48 48VDC RECTIFIER 42 Amps 2000 Watts DESCRIPTION The FMP20.48 rectifier incorporates resonant technology to reduce component stresses and provide increased system reliability. The rectifier features

More information

Electrical Specifications Input

Electrical Specifications Input 850 Watts Multi-Output Preliminary PDU RoHS 1 of 5 This is a 2U Power Supply Assembly (PSA) primarily for an ATX type product, comprising of one or two AC to 12V Power Supplies (PSU), and a Power Distribution

More information

FP-PS-4. Features. Installation

FP-PS-4. Features. Installation OPERATING INSTRUCTIONS FP-PS-4 FieldPoint Power Supply These operating instructions describe the installation, features, and characteristics of the FP-PS-4. Features The FP-PS-4 is a FieldPoint power supply

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Safety Standards. Model Number:

Safety Standards. Model Number: 040APS15 B Highlights & Features Safety Approvals to IEC 60601-1 3.1rd ed. & IEC 60950-1 Compliant with IEC 60601-1-2 4th Ed. Requirements Low touch current (

More information

Power Monitoring in the Data Centre

Power Monitoring in the Data Centre Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags

More information

500Watts Medical Single Output

500Watts Medical Single Output FEATURES Medical 60601-1 3 rd Edition approved U-Channel, End fan and Top fan types available Optional high efficiency OR-ing FET diode Current share function 2 year warranty ELECTRICAL SPECIFICATIONS

More information

Input Voltage Range AC Input. Input Frequency Range. Output Power natural convection. Operating Temperature Range. Model Selection

Input Voltage Range AC Input. Input Frequency Range. Output Power natural convection. Operating Temperature Range. Model Selection (877) 634-0982 www.digipwr.com DPMULP40 Series 40 Watt Medical Grade AC/DC Power Supply Product Specification Universal AC Input 3 x 2 x 0.75 Footprint Key Product Features Medical (BF) Safety Approved

More information

275 Watt Medical Ultra low profile

275 Watt Medical Ultra low profile 127 x 76 x 19 mm Form factor 275 Watts with Forced Air Cooling Approval to EN60601 3rd Edition Efficiencies upto 92% -40 to 70 degree operating temperature* Dual fusing Electrical Specifications 12V /

More information

400AUS24 B MDS AUS. MDS Medical AC-DC Open Frame 24Volt, 400Watt / MDS-400AUS24 B. General Description. Model Information. Model Numbering ```

400AUS24 B MDS AUS. MDS Medical AC-DC Open Frame 24Volt, 400Watt / MDS-400AUS24 B. General Description. Model Information. Model Numbering ``` 400AUS24 B Highlights & Features Safety Approvals to IEC 60601-1 3rd ed. & IEC 60950-1 Risk management report available Low touch current (

More information

Safety Standards. Model Number:

Safety Standards. Model Number: 150AAS12 F/B Highlights & Features Meet DOE Level VI and ErP Lot 7 Safety Approvals to IEC 60601-1 3.1rd ed. & IEC 60950-1 Compliant with IEC 60601-1-2 4th Ed. Requirements Low touch current (

More information

Electrical Specifications VAC/390 VDC, Universal (Derate from 100% at 100V AC to 77% at 80V AC)

Electrical Specifications VAC/390 VDC, Universal (Derate from 100% at 100V AC to 77% at 80V AC) 180 Watt Industrial Features 4 x 2 x 0.75 Inches Form factor 180 Watts with Forced Air Cooling Efficiencies upto 92% -40 to 70 degree operating temperature* 12V / 0.5A Fan Output, Thermal Shut-Down feature

More information

400AUS24 B MDS AUS. MDS Medical AC-DC Open Frame 24Volt, 400Watt / MDS-400AUS24 B. General Description. Model Information. Model Numbering ```

400AUS24 B MDS AUS. MDS Medical AC-DC Open Frame 24Volt, 400Watt / MDS-400AUS24 B. General Description. Model Information. Model Numbering ``` 400AUS24 B Highlights & Features Safety Approvals to IEC 60601-1 3.1rd ed. & IEC 60950-1 Compliant with IEC 60601-1-2 4th Ed. Requirements Low touch current (

More information

Large Frame IEC Contactors

Large Frame IEC Contactors Large Frame IEC Contactors Bulletin 100-E PUBLIC Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 1 Changing Applications for Contactors There are fewer and fewer traditional large motor starting

More information

EMC1600 Series Media Converter and Ethernet Extender Chassis

EMC1600 Series Media Converter and Ethernet Extender Chassis EMC1600 Series Media Converter and Ethernet Extender Chassis User s Manual Preface This manual describes how to install and use the 16-Bay Media Converter and Ethernet Extender Chassis. This chassis is

More information

Brocade ICX 6610 Switch

Brocade ICX 6610 Switch 6 May 2015 Brocade ICX 6610 Switch Technical Specifications 2015, Brocade Communications Systems, Inc. All Rights Reserved. ADX, Brocade, Brocade Assurance, the B-wing symbol, DCX, Fabric OS, HyperEdge,

More information

4 x 2 x 0.75 Inches Form factor. 180 Watts with Forced Air Cooling. Approved to EN/IEC Efficiencies up to 92% Standby Power < 0.

4 x 2 x 0.75 Inches Form factor. 180 Watts with Forced Air Cooling. Approved to EN/IEC Efficiencies up to 92% Standby Power < 0. The MBC180 Series of ultra low open frame medical power supplies feature a wide universal AC input range of 85 V 264 VAC, offering output power 180 W with 13 CFM of forced air cooling or up to 120 W with

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

DC a technology whose time has come again

DC a technology whose time has come again DC a technology whose time has come again How Direct-Current Microgrids are taking us back to the future November 8, 2012 Guy AlLee Research Scientist, Intel Chair Campus/Building Microgrid TSC, EMerge

More information

ABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends

ABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends ABB Automation & Power World: April 18-21, 2011 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing Trends May 10, 2011 Slide 1 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing

More information

The -3Ph extension on a product indicates a 3 Phase power product.

The -3Ph extension on a product indicates a 3 Phase power product. Power Terms Glossary 20-Amp Power Input Support: 20-amp Power Input Support. IEC320/C20 power inlet receptacles supports any power cord with IEC320/C19 power connector (PTCORD-XX). 24-Character Outlet

More information

RT12-240V/2.4kW Rectifier Specification

RT12-240V/2.4kW Rectifier Specification The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between

More information

Safety Standards. Model Number: Unit Weight:

Safety Standards. Model Number: Unit Weight: MEA-250A24C Highlights & Features Meet Efficiency Level VI Safety Approvals to IEC 60601-1 3.1 Ed. & IEC 60950-1 Compliant with IEC 60601-1-2 3 th and 4 th Ed. Requirements IP22 ingress protection rating

More information

PMT. Model Number: Model Number Input Voltage Range Output Voltage Output Current PMT-5V350W1A (Selectable by Switch)

PMT. Model Number: Model Number Input Voltage Range Output Voltage Output Current PMT-5V350W1A (Selectable by Switch) PMT Highlights & Features AC input range selectable by switch Full Aluminium casing for light weight and corrosion resistant handling Built-in automatic fan speed control circuit Wide operating temperature

More information

Pierre Sebellin. Systems Technical Officer International Electrotechnical Commission

Pierre Sebellin. Systems Technical Officer International Electrotechnical Commission Pierre Sebellin Systems Technical Officer International Electrotechnical Commission Introduction IEC is a global organization that publishes consensus-based international Standards and manages Conformity

More information

E3T Energy. Information Technology and Data Centers (Webinar 1) Emerging Technologies Showcase IT Equipment & Power Management

E3T Energy. Information Technology and Data Centers (Webinar 1) Emerging Technologies Showcase IT Equipment & Power Management Information Technology and Data Centers (Webinar 1) Showcase IT Equipment & Power Management November 20, 2013 Welcome. Today s webinar is being recorded and will be posted at: www.e3tnw.org www.conduitnw.org

More information