Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Size: px
Start display at page:

Download "Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power"

Transcription

1 Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

2 Agenda Issues facing the Data Center Managing the explosive growth Power consumption getting the attention of Governments Developing the right cooling strategy for today and into the future Examples of how the right cooling strategy can lower the Total Cost of Ownership Myth High Density computing is more costly 2

3 Managing High Density Servers Rack density trend when fully populated with the newest server technology How most sites are dealing with server density x 2U Servers 2kW Heat Load x 1U Servers 6kWw Heat Load Blade Centers 24kW Heat Load 2009 Rabid Blades 40kW Heat Load Heading Toward 50kW 3

4 Progression to High Density The average server replacement cycle is 3-4 years Rack kw 1kW 2kW 5kW 10 kw 15 kw 20 kw Issues facing the IT Manager Getting Air out of the Racks Hot air mixing with the inlet of other racks Diversity of loads in the Data Center Not aware that more Fans create heat Flexibility of On Demand Cooling 4

5 DCUG Survey Results What are the Biggest Issues facing the IT Manager 0% 10% 20% 30% 40% 50% Heat Density (Cooling) Space Constraints/Grow th Pow er Density Adequate Monitoring Capabilities Availability (Uptime) Technology Changes / Change Energy Costs / Equipment Efficiency Other Security (Physical or Virtual) Data Center Consolidations Data Storage Hardw are Reliability Regulatory Compliance Staffing/Training Limitations 8% 7% 7% 5% 4% 3% 2% 2% 1% 1% 0% 19% 18% 22% 5

6 Cooling Presents an Opportunity For Energy Savings Cooling About 37%- 45% Data Center Power Draws Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Sources of Energy Waste Fans / Blowers running on redundant units Lighting, etc. 3% Lack of air containment (cable openings, room leakage) Unnecessary cooling unit cycling on and off Lack of humidification control between units IT Equipment 50% Source: EYP Mission Critical Facilities Inc., New York Mixing of Hot and Cold air lowering the effectiveness of the cooling unit Excess Fan energy that turns into heat 6

7 US EPA Report Data Center Efficiency Public Law Energy consumed by servers & data centers has doubled in last 6 years and is expected to double again in next 5 years to > 100 Billion kwh State-of-the-Art technologies and best management practices could reduce electricity use by up to 55% Recommendations include: Standardized performance measurements for data centers and equipment Incentive programs Research and development Industry collaboration and partnerships tacenter_report_congress_final1.pdf 7

8 Understanding The Basics Heat generated is directly related to the server power (100%) As server power increases (kw), the airflow (CFM) through the rack increases proportionally Raised floor tiles are limited in airflow (about CFM) Higher entering air temperatures on a cooling unit will provide more capacity and increased efficiency Higher density servers will have a greater range of temperatures leaving the rack over time (larger swings of server load) Fan horsepower to move the air is significant and all the power turns into heat (100 kw Cooling unit uses typically a 10 HP motor that generates 8.5kW of heat) 8

9 Having The Right High Density Cooling Strategy Delivers... Cooling for High Density racks Increase servers per rack Increase number of racks per room Energy Efficiency Lower Operating Costs More power allocated for IT/Server loads Get more out of your existing facility 9

10 Planning for High Density requires A Systems Approach to the Cooling System Traditional Floor-Mount through the first w/sqft (or 4-5 kw per rack) and Supplemental Cooling above that level Computer Room / Data Center Provides high density sensible cooling at the source SUPPLEMENTAL COOLING TRADITIONAL Floor-Mount + Controls Humidity and Filtration Creates the base airflow distribution kw / Rack 10

11 Critical Requirements Of The Base Cooling Load Equipment Cooling units with Variable cooling capacity DX Compressors such as the Digital Scroll VFDs on the fans Controls so that units can work as a team Eliminate dehumidification/humidification fighting Balance the load Optimize the cooling performance High efficiency condensers Green Refrigerant products 11

12 Moving the Heat Room Servers Rack Chip Heat Sink Memory Other components Network Devices Power Supplies CRAH Chiller Heat Rejection Areas for Improvement Reduced server fan power Higher temperatures over cooling coils (room temperature / less mixing of hot and cold air) Reduced resistances lower fan power 12

13 Cooling Solutions to Meet the Higher Density Requirements Requires moving the cooling closer to the heat source to more precisely cool the specific load and not waste energy brute force cooling the whole room. Cooling coils may be in multiple locations External to the Rack Overhead, Back, Side In the Rack Under, Side Part of the Server Requires a fluid to be delivered to the cooling coils to transport the heat out of the Data Center Chilled Water (CW) Refrigerant (pumped low pressure) 13

14 Energy Efficiency Benefits for Cooling Closer to the Load Traditional Cooling Only Fan Power- 8.5kW per 100 kw of Cooling Average entering air temperature of F Cooling Unit Blower Resistances Liebert XD & Base Cooling Fan Power- 3.5 kw per 100 kw of Cooling 2 kw per 100kW) Average entering air temperature of F 65% less fan power Greater cooling coil effectiveness 14

15 Liquid Cooling Configurations with Building Chilled Water Building Chiller XDWP CW Building Chilled Water Valve Heat Exchanger CDU Tank Pump Pump 2nd Loop XDP Refrigerant 15

16 Open and Closed Architectures Open and Closed Architecture Systems as defined by ASHRAE The open architecture systems utilize cooling coils near the heat load either inside or outside the server rack and utilize the room air volume as a thermal storage to ride through short power outages. The closed architecture fully encloses the rack with the cooling coil inside. Other provisions are required for power loss ride through. 16

17 Secondary Fluid Comparisons Pumped Refrigerant System Advantages No Water in the DC or electrical hazards Micro-channel coil efficiency (+50%), lower air side pressure drop => lower operating costs Smaller piping requirements Cooling Modules can be located anywhere Scalable Capacity (2-3x to CW ) Disadvantages Small room scalability Higher Fluid Cost Chilled Water Based System Advantages Lowest Fluid Cost No limitation to room size Disadvantages Electrical Hazard Lower Operating Efficiency May require fluid treatment to prevent fouling Limited overhead cooling options 17

18 Flexibility - Extends Your Existing Infrastructure Investment On demand, plug-and-play flexibility to add additional capacity Cooling at the source of heat with advanced compact heat exchangers Multiple module configurations to meet any Data Center layout Works with any brand of racks Cooling fluid is a gas (no water) Self-regulating capacity 100% Sensible cooling Liebert XDO Hot Aisle Cold Aisle Configuration Hot Spots, Zones and Hot Rooms Liebert XDV Liebert XDH 18

19 Plug and Play Capacity on Demand 19

20 Liebert XD Energy Efficiency Benefits Cooling closer to the source Dramatically less fan power required to move the air Higher air temperature entering the coil results in increase performance Coil Technology Microchannel coils most efficient coil surface Sensible cooling All cooling module operate the coil at 5 degree F above the dew point in the room Does not unnecessarily dehumidify requiring additional humidification (value of 7% in efficiency) 20

21 The Traditional Way (120 8kw/rack) AC AC AC AC (12) 30 ton CW Air Handlers PDU PDU PDU PDU PDU PDU 10 operational for the load 2 stand by PDU PDU PDU PDU PDU PDU AC AC AC AC Floor space 4256 sqft PDU PDU PDU PDU PDU PDU Requires a raised floor of 48 PDU PDU PDU PDU PDU PDU AC AC AC AC 21

22 Liebert XD Solution (120 8kw/rack) AC AC (4) 20 ton CW Air Handlers XD XD XD PDU PDU PDU PDU PDU PDU PDU PDU PDU PDU PDU PDU 3 operational for the load 1 stand by (6) XDP with (96) XDV 5/80 operational 1/16 redundant XD PDU PDU PDU PDU PDU PDU XD Floor Space 3640 sqft XD PDU PDU PDU PDU PDU PDU AC AC 22

23 Total Room Load Calculations 120 Racks 8 kw per Rack Floor Mount AH Liebert XD & Floor Mount Rack Loads Fans(BHP) Room Latent Excess Latent PDU People Build Env Lights Liebert XD benefits Less Fan power 100% sensible Total (kw) Smaller load to size the Chiller 23

24 Summary of Equipment 120 Racks 8 kw per Rack Floor Mount AH Liebert XD & Floor Mount Chillers (3) 250 ton (3) 200 ton CW Pumps (3) 25 HP (3) 20 HP Liebert XD (vs traditional method) 20% less Chiller plant Floor Mount Units (12) 30 ton (4) 20 ton Liebert XD (96) XDV Floor Space (sqft) Raised Floor Height (in) Scalable Design 8kw 20kw 15% less floor space Scalable Platform 24

25 Annual Energy Consumption (kw) 120 Racks 8 kw per Rack Floor Mount AH Liebert XD & Floor Mount Prec Air Units XDV XDP Pumps CW Pumps Chiller Tower Fans Condenser Pumps Rehumidification Total Kw Operating Costs (@$.08/kw) $ 295,231 $ 204,571 Delta $ (90,660) -31% Cooling closer to the source is more efficient. 25

26 Capital Costs Total Impact 120 Racks 8 kw per Rack Floor Mount AH Liebert XD & Floor Mount Chiller $ 187,500 $ 150,000 Cooling Units $ 135,360 $ 258,015 Installation $ 322,860 $ 452,265 Floor Space $ - $ (123,200) Total (E,I,S) $ 645,720 $ 737,080 Delta $ 91,360 Operating Savings $ (90,660) Payback (yr) 1.0 Results Traditional 4256 sqft Liebert XD 3640 sqft (-616 ft²) Example at $200 / ft² Industry range $ / ft² 26

27 kw Chiller Capacity per kw of Sensible Heat Load Liebert XD Technology - Fluid Cooling at the Source Drives Down Operating Costs Chiller Capacity Latent Load Fan Load Sensible Load Traditional CW CRAC CW Enclosed Rack Refrigerant Modules 20% less capacity of the support equipment Chiller (s) Cooling Tower / Condensers Chiller water circulating pumps Emergency Generators Electrical Switch Gear kw power to cool 1 kw of sensible heat Annual Power Consumption 30% Lower Traditional CW CRAC CW Enclosed Rack Refrigerant Modules Fan Pump (CDU) Pump (CW) Chiller 27

28 Liebert XD Full Range of Opportunities XDO20 XDC or XDP Base Infrastructure (160 kw) Future pumping units of larger capacity XDV10 XDH20/32 Standard Cooling Modules 10-35kw +++ Embedded Cooling (microchannel intercoolers) Tested 35-60kw Developing up to 100kw Embedded & Chip Cooling (microchannel intercoolers and Cooligy chip cooling) Tested 50 kw (100% redundant) Capable over 100kw 28

29 Additional System Opportunities for Improved Cooling Efficiencies kw for cooling per kw of server heat load Data Center Best Practices Optimal 0.36 Enclosed Rack 2006/2007 Energy Savings driven by reduction in Fan Power (cooling system and server) plus Heat Transfer efficiency 0.31 XD Modules (10 35 kw) 2004/ % Egenera (10 20 kw) 2006/2007 Embedded Cooling (35 60 kw) Component Cooling (>50 kw) Future 45% Traditional Cooling Liebert XD Opportunities 29

30 Cooling Process Throughout The Range Of Rack Loads Cooling Process 30 Availability Flexibility TCO Availability Flexibility TCO Availability Flexibility TCO Availability Flexibility TCO Availability Flexibility TCO Availability Flexibility TCO Availability Flexibility TCO Availability Flexibility TCO Availability Flexibility TCO Chip/Component Cooling Embedded Rack - Refrigerant Rack Mounted - Refrigerant Rack Mounted - CW Traditional CRAH >0-5 >5-10 >10-15 >15-20 >20-25 >25-30 >30-35 >35-50 >50 Rack Load (kw)

31 Improving The Total Cost Of Ownership with the Liebert XD Cooling Systems How Cooling closer to the source of the heat makes the heat exchangers more efficient (higher entering air temperatures) Lower total Fan HP Sensible cooling eliminates wasted energy dehumidify unnecessarily and then having to re-humidify Less Chiller or DX infrastructure required Overhead cooling modules require no additional floor space Cooling solutions that meets the requirements to fill racks of high density servers Infrastructure for modules today and for future server / rack designs Results in More cooling capacity for energy consumed Less Power (energy consumed) Less Power (energy consumed) Less Power and Capital Equipment Less Floor Space consumed Less Floor Space consumed Extends your capital life 31

32 Lower Power For Cooling Provides More Power For IT Equipment 12% 26% Data Center Power Draws Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% 59% IT Equipment 50% For the same building power, you can allocate more power to the IT Equipment (18%) 32

33 Take Aways Cooling solutions for higher density will need to move closer to the load and will require a reliable fluid delivery means Cost effective cooling solutions exist that can be employed today that meet future needs Allow racks to be fully populated Cooling at the source of the heat load will actually lower your incremental energy consumption Less power for the cooling system provides more power for the IT equipment Results in more available Floor Space and Growth capability for the IT equipment 33

34 Thank You Contact: 34

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

Liebert XD. Cooling Solutions For High Heat Density Applications. Precision Cooling For Business-Critical Continuity

Liebert XD. Cooling Solutions For High Heat Density Applications. Precision Cooling For Business-Critical Continuity XD Cooling Solutions For High Heat Density Applications Precision Cooling For Business-Critical Continuity High Density. High Temperatures Today s data center technologies compound conventional cooling

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Liebert XD Flexible, Energy-Saving Cooling Solutions For High Heat Density Applications. Precision Cooling For Business-Critical Continuity

Liebert XD Flexible, Energy-Saving Cooling Solutions For High Heat Density Applications. Precision Cooling For Business-Critical Continuity Liebert XD Flexible, Energy-Saving Cooling Solutions For High Heat Density Applications Precision Cooling For Business-Critical Continuity Liebert XD Saves Significant Energy Today, more than ever, environmental

More information

The Energy. David L. Moss Dell Data Center Infrastructure

The Energy. David L. Moss Dell Data Center Infrastructure The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers TM PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that enable

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

Close Coupled Cooling for Datacentres

Close Coupled Cooling for Datacentres Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close

More information

Data Center Optimized Controls

Data Center Optimized Controls Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Chiller Replacement and System Strategy. Colin Berry Account Manager

Chiller Replacement and System Strategy. Colin Berry Account Manager Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit

More information

ENERGY EFFICIENT COOLING SOLUTIONS FOR DATA CENTERS. Introducing a Vertiv tool for evaluating cooling system total cost of ownership

ENERGY EFFICIENT COOLING SOLUTIONS FOR DATA CENTERS. Introducing a Vertiv tool for evaluating cooling system total cost of ownership ENERGY EFFICIENT COOLING SOLUTIONS FOR DATA CENTERS Introducing a Vertiv tool for evaluating cooling system total cost of ownership TWO STAGE POWER DISTRIBUTION ENERGY EFFICIENT COOLING SOLUTIONS FOR DATA

More information

Overcoming the Challenges of Server Virtualisation

Overcoming the Challenges of Server Virtualisation Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

Enabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific

Enabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific Enabling Business Critical Continuity for Unified Communications Andy Liu Product Manager, Asia Pacific Emerson Creating Technology and Solutions for a World in Action #1 AC & DC Power System #1 OEM Embedded

More information

Close-coupled cooling

Close-coupled cooling Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable

More information

DATA CENTER LIQUID COOLING

DATA CENTER LIQUID COOLING DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid

More information

Rack cooling solutions for high density racks management, from 10 to 75 kw

Rack cooling solutions for high density racks management, from 10 to 75 kw Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market

More information

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data

More information

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight LIEBERT icom THERMAL SYSTEM CONTROLS All for One, One for All Optimize a Single Cooling Unit With an Intelligent

More information

PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers

PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers TM PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that

More information

Precision Cooling. Precision Cooling Advantages

Precision Cooling. Precision Cooling Advantages Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

Server Room & Data Centre Energy Efficiency. Technology Paper 003

Server Room & Data Centre Energy Efficiency. Technology Paper 003 Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:

More information

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations

More information

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise TWO STAGE POWER DISTRIBUTION Executive Summary Today s data centers are changing rapidly, and it is more important than ever

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

DCIM Data Center Infrastructure Management Measurement is the first step

DCIM Data Center Infrastructure Management Measurement is the first step DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by

More information

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed

More information

Liebert PDX from 15 to 120 kw

Liebert PDX from 15 to 120 kw Liebert PDX from 5 to 0 kw The Thermal Management Solution for Small and Medium Data Centers Electronic Expansion Valve Efficiency Digital Scroll Partial Load icom Control TCO Optimization Integrated Solution

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Scalable, Secure. Jason Rylands

Scalable, Secure. Jason Rylands Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Energy Efficiency Solutions for Your Data Center

Energy Efficiency Solutions for Your Data Center Energy Efficiency Solutions for Your Data Center Chapter One: Cooling Assessments Click a section below You Know You Need a Cooling Assessment When Cooling Assessments Yield Benefits Now and in the Future

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Switch to Perfection

Switch to Perfection Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

Cooling Solutions & Considerations for High Performance Computers

Cooling Solutions & Considerations for High Performance Computers Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

DCIM Data Center Infrastructure Management

DCIM Data Center Infrastructure Management DCIM Data Center Infrastructure Management Part 2 Implementation Challenges & Strategic Advantages - Predictive Analysis August 8, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Implementation

More information

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell

More information