1 380VDC Data Center Duke Energy Charlotte, NC Dennis P. Symanski EPRI - Senior Project Manager Silicon Valley Leadership Group 2011 Data Center Efficiency Summit 18NOV2011 IBM - San Jose, CA
2 380VDC Data Center Activity Involved With Multiple 380VDC Demos Universities Electric Utilities Telecom Industry Harmonizing Multiple 380VDC Standards Efforts DC Power Partners Joining EMerge Alliance European Telecommunications Standards Institute International Electrotechnical Commission (SG4) NFPA 70:National Electrical Code (2011>>>2014) Working With Many Manufacturers IT Equipment As Well As Facility Equipment 2
3 DC powered 0perational/Demo Sites for ICT use Worldwide ~380VDC Demos US Syracuse Univ. 380VDC US Intel Corp. France Telecom 380 VDC Sweden UPN AB. 350/380 VDC China Telecom 380VDC KOREA 300&380VDC 400 VDC Japan US UCSD NTT Group 380VDC 380 VDC Japan Other Demos US Duke Energy 380 VDC Taiwan IT Manufacture 380 VDC New Zealand Telecom NZ 380 VDC 220 VDC 3
4 DC Voltage Distribution efficiency Cable Distance Why 380VDC? Sweet Spot IEC 900 BS (U.K.) High Long Ordinance (JPN) Server PS NEC(U.S.) (192cell) 374 (168cell) 321 (144cell) [to 48] Validus 380 US DC Demo 300 NEDO PJ. (Sendai) Operating bulk - voltage 373(U.K.) 354(EU) 324V (US 311(JPN) Low Short 0 Law, Regulation, Code, and Stds. Distr. Gen. Telecom (Number of Cells) Demos (Reference) Rating voltage of parts and elements AC ICT input voltages ( Peak ) Benefit of HVDC system ETSI Std. (draft) Edited from source: NTT FACILITIES, INC. 4
5 380VDC Data Center Demos EPRI/LBNL - Electric Power Research Institute Lawrence Berkeley National Lab, California Duke Energy data center in Charlotte, North Carolina Calit2 - California Institute for Telecommunications and Information Technology, UC San Diego 5
6 Duke Energy 380VDC Data Center Demo HP Servers IBM Servers EMC Storage Arrays Delta Rectifiers StarLine Busway Dranetz-BMI Metering 6
7 Standard 208VAC vs 380VDC Data Center 7
8 Duke Energy Data Center Set-Up Facilities Phase 1 Data Center 480V 3P 4W 380Vdc Bus HP Rack DC CB IBM Rack DC CB EMC 2 Rack DC CB 480V 3P 3W AC PDU MPU2 Delta Rectifier HP Rack IBM Rack EMC 2 Rack HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 EMC 2 CLARION CX4-960 UPS 300KVA 480V/480V 480V Conditioned Power Distribution Panel CB200A CB200A CB200A Delta 30kVA Rectifier Batteries AC 750W DC 750W HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 AC 750W DC 750W HP ProLiant DL380 G7 IBM POWER7 Server AC/DC PSUPower DC Supply PSU EMC 2 DAE AC PSU EMC 2 DAE AC PSU EMC 2 DAE AC PSU DC PSU DC PSU DC PSU EMC 2 SPE AC/DC PSUPower DC Supply PSU AC 750W DC 750W Ethernet Switch 208Vac to Racks 8
9 Duke Energy Data Center Metering Scheme RECTIFIER POWER INPUT Performance Calculation % POWER DIFFERENCE = 1 - RECTIFIER POWER INPUT CALCULATED POWER ACPSU DC Power Network AC Meter AC CALCULATED POWER ACPSU = AC Power Network UPS Rectifier AC Meter DC Meter Meter kw DC DC 4 Meter Meter 5 AC 6 7 kw 6 kw 7 ACPSU AGGREGATED KW UPS Efficiency X XFMR Efficiency AC Meter XFMR (PDU) AC Meter 8 9 kw 8 kw 9 UPS Efficiency = kw 7 kw 6 XFMR Efficiency = kw 9 kw 8 Meter 12 kw 12 AC Meter kw AC kw 10 Meter 10 HP Rack IBM Rack DC Meter EMC Rack ACPSU AGGREGATED KW = kw 10 + kw 11 + kw 12 9
10 Percentage Improvement over AC Networks 14.9% 15.0% 15.1% 15.3% 15.6% 15.8% AC vs DC Comparison Tests Test Average Percent Difference Between AC and DC Network 16.0% 15.8% Duke/EPRI DC Demonstration Comparison Test Results - All Tests Average Improvement Over Unconditioned Power Source Test % 15.6% Test % 15.4% Test % Test % Test % Test % Average 15.3% 15.2% 15.0% 14.8% 14.6% 14.4% 14.2% Test 1 Test 2 Test 3 Test 4 Test 5 Test 6 Tests Test 1 All servers and storage arrays on but idle (28 hours) Test 2 IBM and EMC on but idle (28 hours) Test 3 All servers and storage arrays running at 100% (8 hours) IBM (nstress), HP (Prime95), EMC (IOMeter) Test 4 All servers and storage arrays running at 50% (18 hours) Test 5 - All servers and storage arrays running at 100% (51 hours) Test 6 IBM and EMC on but idle (19 hours) 10
11 Delta Products - DC UPS Modular design Hot-swappable control module 20kW per power module 80kW 120kW 160kW 280kW Redundancy Configuration Facility Configuration Row Configuration + Batteries Batteries DC UPS Battery Room Servers Clusters 60+20kW DC UPS Servers 60+20kW DC UPS 11
12 Delta Products - Rectifier Module Spec Power Module capacity 20KW. Input voltage: 480/277V, 400/230V, 380/220V Input range: +15%~-20%of Nominal Voltage. Input power factor >0.99. Current Total Harmonic Distortion <5%. Output voltage 350/380/400Vdc (Nominal). Current balance accuracy < 3%. Output Voltage regulation < 1% Output short current limit: 75A. AC DC efficiency : 96%. Fully DSP based digital control. Delta patented topology for 3 phase buck boost PFC. Swappable power module design. Dimension: 129(H) x 219(W) x 700(D) mm. Weight: 16.1 Kg 12
13 Data Center DC Product Examples 380VDC Power Supplies, Interconnect Cables, Bus Ways, Outlet Strips, Breakers 13
14 Y/120 VAC System Cost Comparison Diagram 14
15 380 VDC System Cost Comparison Diagram (15% Less CAP-EX and 35% Less OP-EX) 15
16 ITI(CBEMA) VAC Operating Ranges 16
17 DC Volts 380VDC Operating Ranges 50 μsec 380 VDC Voltage Tolerance Curve msec Duration (Seconds) Upper Voltage Limits Nominal Voltage Lower Voltage Limits 410 VDC 380 VDC 360 VDC 260 VDC 17
18 380VDC Power Distribution NOTE: All loads are to be connected between L(+) and L(-). PE is not a power conductor. 18
19 Easier Integration Of Renewables Reference to Nextek Power Systems US Patent 7,872,375 18JAN
20 Benefits Summary Of 380VDC Higher Reliability Fewer Conversions/Fewer Points Of Failure Higher Efficiency Higher Efficiency Power Supplies & UPS No PDU Transformer Needed Smaller Size Better Power Quality Easier Integration Of Renewable Energy Easier Integration of Energy Storage 20
21 Other DC Applications 380VDC Uses Telecom Central Offices (Operating Today At 48VDC) Variable Speed Drives (Washers/Dryers/Air Cond) Other Home Appliances (Stoves/Ovens) Rapid Charger For Plug-in Electric Vehicles 24VDC Uses Lighting Consumer Electronics (TVs, PCs, Projectors) EMerge Alliance Members Working On Both Voltages 21
22 DC Challenges Standardizing on DC Voltages 380VDC looking like the leading candidate Safety Agency Approval/Listing (e.g. UL) DC & AC Products Both Need These Approvals Paradigm Shift Back To Some Of Thomas Edison s DC Ideas We Are Used To The AC World Today Vendor Selection More AC Vendors To Choose From...But DC Vendors Are Now Available 22
23 Together Shaping the Future of Electricity 23
380VDC Data Center At Duke Energy
380VDC Data Center At Duke Energy Dennis P. Symanski EPRI - Senior Project Manager Curtis Watkins Duke Energy - Senior Project Manager Emerging Technology (ET) Summit November 9, 2010 Sacramento, CA From
More informationDC Power Standards. Brian Fortenbery Energy Efficiency Group Power Delivery and Utilization Sector EPRI
DC Power Standards Brian Fortenbery Energy Efficiency Group Power Delivery and Utilization Sector EPRI Data Center Power Delivery System UPS 85-92% Power Dist 98-99% Power Supply 68-72% DC/DC 78-85% The
More informationWhy Not Operate Data Centers & Telecom Central Offices at 400 VDC???
Why Not Operate Data Centers & Telecom Central Offices at 400 VDC??? Dennis P. Symanski Senior Project Manager 2009 IBM Power and Cooling Technology Symposium 20-21OCT2009 Rochester, MN Data Center Energy
More informationStarline DC Solutions
Starline DC Solutions 380vdc Revolution or Evolution? 380Vdc Data Center Architecture Advancements Timothy E. Martinson Universal Electric Director StarLine DC Solutions Division Emerge Alliance Chair
More informationDC The Power to Change Buildings A Non-profit Alliance Driving Open Standards to Direct Current Power Distribution in Buildings
DC The Power to Change Buildings A Non-profit Alliance Driving Open Standards to Direct Current Power Distribution in Buildings What is the EMerge Alliance? Not-for-profit 501c -Part 6 Open application
More informationE f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n
E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; 4 0 0 V D C p o w e r f e e d s o l u t i o n Juha Klemola / HW Architect / Nokia Introduction to the challenge Datacenter
More informationPSMA Power Technology Roadmap 2013 Presentation September 6, 2012
PSMA Power Technology Roadmap 2013 Presentation September 6, 2012 Brian T. Patterson - Chairman Governing Member, EMerge Alliance General Manager, Armstrong World Industries Vision Standards Eco-system
More informationUPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications
INFINITE POWER Mission Critical Applications UPS UNINTERRUPTIBLE POWER SUPPLY centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw Rack-mountable modules designed for blades, data-center,
More informationHIGH RELIABILITY DC POWER DISTRIBUTION SYSTEM (HRDCPDS) FOR CRITICAL POWER ENVIRONMENTS (DC-UPS)
National Conference June 12-15 Boca Raton, FL HIGH RELIABILITY DC POWER DISTRIBUTION SYSTEM (HRDCPDS) FOR CRITICAL POWER ENVIRONMENTS (DC-UPS) A PATENT PENDING SYSTEM PRESENTATION Mark Baldwin - President
More informationDC a technology whose time has come again
DC a technology whose time has come again How Direct-Current Microgrids are taking us back to the future November 8, 2012 Guy AlLee Research Scientist, Intel Chair Campus/Building Microgrid TSC, EMerge
More informationZero Energy Buildings (ZEB) Buildings that produce as much energy as they use in a year
Zero Energy Buildings (ZEB) Buildings that produce as much energy as they use in a year What s likely to change in the approach to design/build? 1. Integrated design and operations planning 2. Site renewable
More informationThe 3-phase, 5-wire model name is PF LNM. The 3-phase, 4-wire model name is PF LNN.
The 12.5kW power shelf accepts 3-phase input power and provides stable DC output power (1000A at 12.5VDC). The OCP 21-inch power shelf includes a total of 5+5 high-power, hot-swappable PSUs in redundant
More informationValidus DC Systems. DC Power Distribution Solutions Serving: Mission Critical Applications Next Generation Data Centers Green IT Infrastucture
Validus DC Systems DC Power Distribution Solutions Serving: Mission Critical Applications Next Generation Data Centers Green IT Infrastucture Copyright Validus DC Systems, LLC AC vs. DC: A Quick Tutorial
More informationCisco CRS 16-Slot Chassis Power Systems
This chapter includes the following sections: Power specifications are provided in Technical Specifications Power Systems Overview, on page 1 Power Component Information Common to the Two Types of Power
More informationAPMTM UPS 18kW - 90kW The Flexpower Technology for mission critical applications
APM UPS 18kW - 90kW The Flexpower Technology for mission critical applications WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that enable
More informationRack Centric - High Voltage Distribution
Rack Centric - High Voltage Distribution Randy Malik Senior Technical Staff Member Research Triangle Park Raleigh, North Carolina Email: Rmalik@us.ibm.com Data Center Application Typical Data Center Energy
More informationServer Technology Inc.
Server Technology Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2011-Sept-22 Headquarters Server Technology, Inc. 1040 Sandhill
More information1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA
The SR series on line double conversion UPS with full time Digital Signal Processor control technology is the perfect solution for mission critical users who demand high reliability, availability and performance
More informationHVDC Innovation, XECHNO Power & Fresh HVDC
1 HVDC Innovation, XECHNO Power & Fresh HVDC Energy Saving Technology for the Data Center Green Consulting Business Unit Solution Business Division NTT DATA INTELLILINK Corp. Problems facing data centers:
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 100kW 3MW
PRODUCT BROCHURE Conceptpower DPA 500 480V UL Modular UPS 100kW 3MW 2 C O N C E P T P O W E R D PA 5 0 0 4 8 0 V M O D U L A R U P S Today s data centers require continuous uptime. That target is why ABB
More informationDC Power Distribution System Standards Next Generation Net Zero Energy Commercial Buildings
National Energy Efficiency Technology Summit Schedule Portland, Oregon Sep. 24-27, 2012 DC Power Distribution System Standards Next Generation Net Zero Energy Commercial Buildings From Chips, to Building
More informationSystem Specifications
System s Environmental s, page 1 Switch Dimensions, page 1 Switch and Module Weights and Quantities, page 2 Transceiver and Cable s, page 2 Switch Power Input Requirements, page 2 Power s, page 3 Power
More informationTechnical Specifications
Technical s This appendix lists the technical specifications for the Cisco UCS 5108 server chassis and includes the following sections: KVM Cable, page 1 Chassis s, page 2 Environmental s, page 3 s for
More informationR E C T I F I E R I N V E R T E R C O N V E R T E R MP7
Uninterruptible Power Supply Product Specifications Description The industrial UPS provides your critical equipment with uninterruptible 3 phase AC power. Using high frequency dual conversion technology,
More informationCompute Engineering Workshop March 9, 2015 San Jose
Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud
More informationSystem Specifications
Environmental s, on page 1 Switch Dimensions, on page 1 Weights for the Chassis, Modules, Fan Trays, and Power Supplies, on page 2 Power s, on page 4 Environmental s Environment Temperature Relative humidity
More informationproduct catalog Telecom / Network Datacom Medical Commercial / Industrial Powering Technology
product catalog 2012 Telecom / Network Datacom Commercial / Industrial Medical High Voltage Military / C.O.T.S. For Support call: North America: 954-346-2442 x1071 Europe: +44(0) 1903 768 200 www.unipowerco.com
More informationMP7. Uninterruptible Power Supply
Uninterruptible Power Supply PRODUCT SPECIFICATIONS Description The industrial UPS provides your critical equipment with uninterruptible 3 phase AC power. Using high frequency dual conversion technology,
More informationTechnical Data Sheets Uninterruptible Power Supply LP11 Series UPS kva
GE Critical Power Technical Data Sheets Uninterruptible Power Supply LP11 Series UPS 3 5 6 8 10 kva GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91
More informationModular and Scalable Power Converters in the UPS Industry
A-PDF Split DEMO : Purchase from www.a-pdf.com to remove the watermark Modular and Scalable Power Converters in the Industry Ian Wallace Eaton Corporation, Innovation Center 1 Eaton Overview Eaton Electric
More informationPowering Compute Platforms in High Efficiency Data Centers. Annabelle Pratt, Pavan Kumar, Kevin Bross, Tomm Aldridge
Powering Compute Platforms in High Efficiency Data Centers Annabelle Pratt, Pavan Kumar, Kevin Bross, Tomm Aldridge Agenda Defining a power-efficient efficient data center Improving power delivery efficiency
More informationPOWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA)
POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA) A55-00017 SEC PLUS 8-10 KVA MAREKTING SPECS REV. A 9/10 8kVA, 10kVA POWERVAR Isolated On-Line UPS Specifications Index 1.0 General
More informationEaton DC Power Solutions
Eaton DC Power Solutions 19 sub-rack Modular 3U and 6U options Up to 6 rectifier modules Pre-configured software High power density (24/48V: 300/250A, 6U, 19 ) Multiple AC option (1Ø, 3Ø, 2Ø) Fast on-line
More informationDACS ELECTROSYSTEMS PVT.LTD
DACS ELECTROSYSTEMS PVT.LTD Introduction of DACS DACS Electrosystems Pvt.Ltd is located in Pune (Mah), India Ever since it was established in 1981 it commenced with design, manufacturing and supply of
More informationSMARTONLINE E3 UPS SYSTEMS
SMARTONLINE E3 UPS SYSTEMS Extremely efficient protection for your most important equipment IDEAL OUTPUT POWER PROTECTS CRITICAL SYSTEMS On-line, double conversion operation continuously delivers precision-regulated,
More informationPRODUCT FEATURES AND ADVANTAGES
Flatpack2 24/1800 HE 24VDC Rectifier/Converter Modules The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out. With efficiency up to 96.2%, the losses have been
More informationHP Rackmountable 3 Phase Uninterruptible Power Systems Overview
Overview Crowded data centers and racks filled to capacity with storage devices, monitors, servers communications devices, and other equipment are driving the need for uninterruptible power with increased
More informationEP Series II UPS 230 V
EP Series II UPS 230 V 1000/2000/3000 VA Uninterruptible Power Supply (UPS) geindustrial.com Non-stop pure power Today s 24/7 business world depends on 24/7 power availability and demands zero down time.
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 20kW 600kW
PRODUCT BROCHURE Conceptpower DPA 120 208V UL Modular UPS 20kW 600kW 2 CONCEPTPOWER DPA 120 280V MODULAR UPS Today s data centers require continuous uptime. That target is why ABB s Conceptpower DPA 120
More informationProduct brochure. Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW
Product brochure Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW 2 Product brochure Conceptpower DPA 120 UL UPS Conceptpower DPA 120 The modular UPS for small and medium-sized data centers UPS
More informationHigh Voltage Direct Current Power Solutions for Data Centers
High Voltage Direct Current Power Solutions for Data Centers Professor: Dr. Danny Silver Acadia University Student Name: Jim Nasium Published: April 10 th, 2011 1. Introduction As the demand on data centers
More informationEnergy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices?
This is a photographic template your photograph should fit precisely within this rectangle. Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and
More informationPower Solutions Catalogue
Power Solutions Catalogue CONTENTS Uninterrupted Power Systems (UPS) T-4101 Series Range: 1-10kVA, Single Phase UPS (Transformer-less) 02 T-4101A Series Range: 3-10kVA, Single Phase UPS (Transformer-less)
More informationHigh-Voltage DC-DC Power Module Development. Public Review
High-Voltage DC-DC Power Module Development Public Review DC-DC Power Module Phase 1 (Spec Development) Project Problem statement: A modular DC-DC power supply is needed to provide low cost, higher efficiency
More informationRTCC SMART Series. Duke Energy s Coalition of the Willing. March 18, #RTCCSMARTSeries. Presented By: Program Sponsors:
RTCC SMART Series Duke Energy s Coalition of the Willing March 18, 2016 @Tricleantech #RTCCSMARTSeries Program Sponsors: Presented By: Research Triangle Cleantech Cluster: Who We Are Board of Directors
More informationQUINT-PS AC/24DC/10
Extract from the online catalog QUINT-PS-100-240AC/24DC/10 Order No.: 2938604 DIN rail power supply unit 24 V DC/10 A, primary switched-mode, 1- phase Commercial data EAN 4017918890537 Pack 1 Pcs. Customs
More informationthe Centric 300 An advanced modular UPS up to 1800kVA/kW
the Centric 300 An advanced modular UPS up to 1800kVA/kW 1 Gamatronic, Israel s Leading Power Electronics Company True to the exceptional reputation earned by Israeli technology companies, Gamatronic has
More informationAnue Net Tool Optimizer 5273
Anue Net Tool Optimizer 5273 Carrier-Grade, High-Availability Network Monitoring Switch High-Availability Features Overview Telecommunication and cable service providers face many challenges monitoring
More informationMODULAR DC POWER SUPPLY MODEL 62000B SERIES MODEL 62000B SERIES. Modular DC Power Supply. Ethernet. Key Features :
Modular DC Power Supply MODEL 62000B SERIES Key Features : Voltage range: 1 ~ 150V Current range: Up to 2000A (System) Power range up to 1.5KW per module up to 120KW per system High Power Density (464
More informationSocomec Netys PR RT U P S TOWER / RACK MOUNT
Socomec Netys PR RT Ideal solution for protecting small servers, networking devices and peripherals. Assures service continuity to critical applications. Designed for professional applications: the sinevawe
More informationPowerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM)
Powerware 9315 Hot Sync Parallel Capacity System Bypass Module (SBM) Modbus Profile 164950161 Rev B Read Input Status Modbus Function Code 02 Input registers start at 10000. Register 1 On Battery 0 BOOL
More informationSystem Specifications
Environmental s, on page 1 Switch Dimensions, on page 1 Switch and Module Weights and Quantities, on page 2 Transceiver and Cable s, on page 2 Switch Power Input Requirements, on page 2 Power s, on page
More informationMAJOR VA Power Inverter
MAJOR500-500 VA Power Inverter The Major500 is a highly reliable, telecom quality, DC to AC power inverter. The Major500 features full electronic protection, high efficiency and low output noise. The built-in
More informationServer Specifications
, page 1 Power Cord s, page 6 This appendix lists the physical, environmental, and power specifications for the server. Physical s, on page 1 Environmental s, on page 2 Power s, on page 2 Physical s The
More informationLiebert APM 30, 60, 90, 120, 150kVA UPS Adaptive Power Quality Solution for Critical Applications
AC Power For Business-Critical Continuity Liebert APM 30, 60, 90, 120, 150kVA UPS Adaptive Power Quality Solution for Critical Applications Tel: +852-2690-4118 Liebert APM Efficiency Without Compromise
More informationAC, DC and Custom Power Supplies
AC, DC and Custom Power Supplies High Efficiency Power Solutions DC-DC CONVERTERS Range Power Amps Max / Outputs Input Range Output (VDC) Dimensions H x W x D mm (inches) F501 500W 40 36-75 48, 28, 24,
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationSmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU6000RT3UHV 6000VA online 6U rack / tower UPS (3U Power Module + 3U Battery
More informationSystem Specifications
Environmental s, on page 1 Switch Dimensions, on page 1 Weights for the Chassis, Modules, Fan Trays, and Power Supplies, on page 2 Power s, on page 3 Environmental s Environment Temperature Relative humidity
More informationSmartOnline 240 & 120V 20kVA 18kW Double- Conversion UPS in 25U enclosure, Pre-installed Network Card, USB, DB9, Bypass, Hardwire
SmartOnline 240 & 120V 20kVA 18kW Double- Conversion UPS in 25U enclosure, Pre-installed Network Card, USB, DB9, Bypass, Hardwire MODEL NUMBER: SU20KRTHWTFASSM Highlights 20kVA / 20,000VA / 18,000W on-line
More informationSystem Specifications
System s Environmental s, page 1 Switch Dimensions, page 1 Switch and Module Weights and Quantities, page 2 Transceiver and Cable s, page 2 Switch Power Input Requirements, page 2 Power s, page 3 Power
More informationSmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial
SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial MODEL NUMBER: SU3000RTXL3UHV Highlights 3000VA / 3kVA / 2400 watt on-line double-conversion
More information24/48V Battery Bank Ah High Cycling Long Life
Outdoor Power Cabinets, 48V DC Free Cooled with Combined Air-Con. PreFactory assembled with 19 inch Power sub rack, 2 or 4 battery Shelf s, 3U DCAC Panel combined with rectifiers 2U or 4U Power Module
More informationGalaxy VX. From 500 to 1500 kw N+1 Parallel solutions up to 4000 kw 380V / 400V / 415V / 440V. schneider-electric.com/ups
Galaxy VX Highly efficient, scalable, three-phase power protection with flexible operating modes and ECOnversion for large facilities, data centers, and business-critical applications. From 500 to 1500
More informationCisco TelePresence MSE 8000
Data Sheet Cisco TelePresence MSE 8000 Figure 1. Cisco TelePresence MSE 8000 Product Overview The Cisco TelePresence MSE 8000 (MSE 8000) is a high-capacity voice and video conferencing media services engine.
More informationAC-DC Converter REC K10
Rectifier System for Telecom-, Industry- and Rail applications General Electrical Safety EN 60950, UL 94 Protection class 1 Pollution degree 2 Isolation primary secondary 3.75kVDC PFC Ventilation EN 6100-3-2,
More informationCISCO AC/DC POWER SOLUTION FOR USE WITH CISCO OPTICAL PLATFORMS
DATA SHEET CISCO AC/DC POWER SOLUTION FOR USE WITH CISCO OPTICAL PLATFORMS The Cisco AC/DC Power Solution provides a scalable platform for the delivery of DC power to equipment-installation sites that
More informationSmartOnline 208/120V or 240/120V 16kVA 11.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial
SmartOnline 208/120V or 240/120V 16kVA 11.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU16000RT4U Description Tripp Lite 16kVA SmartOnline
More informationExtending Energy Efficiency. From Silicon To The Platform. And Beyond Raj Hazra. Director, Systems Technology Lab
Extending Energy Efficiency From Silicon To The Platform And Beyond Raj Hazra Director, Systems Technology Lab 1 Agenda Defining Terms Why Platform Energy Efficiency Value Intel Research Call to Action
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1, 2N, 2(N+1) UPS topologies Large Free standing
More informationMUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application
MUST900 Modular UPS 30-300 kva modular UPS - up to 900 Datacenter & servers Internet centers Local Area Networks (LAN) Telecommunication devices Emergency application Smart Energy Solutions HOT SWAP 0.9
More informationEst FlexiPower Maxi UPS FPX Maxi kVA
Est.1968 FlexiPower Maxi UPS FPX Maxi 50 250kVA True modular UPS system for critical applications Designed and Published by Thycon. A UPS DESIGNED TO MEET THE NEEDS OF TODAY AND TOMORROW The FlexiPower
More informationSystem Specifications
Environmental Specifications, page 1 Switch Dimensions, page 1 Weights and Quantities for the Chassis, Modules, Fan Trays, and Power Supplies, page 2 Power Specifications, page 4 Environmental Specifications
More informationZP120N Online UPS. High Power Intensity. Flexibility. High efficiency with low heat dissipation. Smart Energy Solutions
Online UPS 1,2,3,6,10,20 kva single/single-phase and three/single-phase High Power Intensity STRONGEST PERFORMANCE Flexibility High efficiency with low heat dissipation EXTENDABLE AUTONOMY Smart Energy
More informationGAMATRONIC, A SolarEdge Division.
GAMATRONIC, A SolarEdge Division. 17 Hartum Street, POB 45029, Jerusalem 9777517,Israel Tel: +972-2-5888222 Fax: +972-2-5828875 e-mail: info@gamatronic.com www.gamatronic.com The Power+ Premium 60 is
More informationDC POWER SUPPLIES DNX 110/220 V
DC POWER SUPPLIES DNX 110/220 V ISO 9001 Power supply systems DNX are dedicated to supply the equipment which needs for its operation direct voltage 110 / 220, with emphasis on maximum reliability and
More informationPMC. Model Number: Model Number Input Voltage Range Output Voltage Output Current PMC-24V600W1BA Vac ( Vdc) 24Vdc 25.
PMC Highlights & Features Universal AC input range High PF > 0.99 @ 115Vac Power Boost of 200% for 5 seconds Meet Surge Immunity IEC 61000-4-5, Level 4 (CM: 4kV, DM: 2kV) Built-in fan speed control and
More informationProtected Power Supply for your Applications. Telecom Industrial Data Center
Protected Power Supply for your Applications Telecom Industrial Data Center The future is here. ELTEK Deutschland- Your partner for highly efficient power systems and services When it comes to power conversion
More informationDC POWER OVERVIEW BROCHURE Powerful Solutions for Critical Data and Telecom Applications
DC POWER OVERVIEW BROCHURE Powerful Solutions for Critical Data and Telecom Applications DC POWER OVERVIEW BROCHURE NETSURE APPLICATIONS yradio Base Station / Microwave Site ywireless & Wireline Access
More informationTME Modular Series UPS System kva/kw - 208/220 VAC
GE TME Modular Series UPS System 15-90 kva/kw - 208/220 VAC TME Modular Series UPS 15-90 kva/kw Highest Technology with Modular Design GE s TME Series UPS is one of the most reliable three-phase UL UPS
More informationSmartOnline 120V 3kVA 2.4kW Double- Conversion UPS, Tower, Extended Run, Network Card Options, USB, DB9 Serial
SmartOnline 120V 3kVA 2.4kW Double- Conversion UPS, Tower, Extended Run, Network Card Options, USB, DB9 Serial MODEL NUMBER: SU3000XL Highlights 3000VA / 3kVA / 2400 watt online double-conversion tower
More informationCPS VS UPS FOR POWERING DATA CENTERS
CPS VS UPS FOR POWERING DATA CENTERS HOW THE ADVANTAGES OF A NO BREAK CONVERGED POWER SYSTEM (CPS) PROVIDED BETTER POWER RELIABILITY, SYSTEM AVAILABILITY AND REDUCED COSTS OVER A UNINTERRUPTABLE POWER
More informationSLI 15 INVERTER SERIES, 1500 W
SLI 15 INVERTER SERIES, 1500 W FEATURES DESCRIPTION New, compact design: 1U height x 19" width x 14.94" depth; 19" rack-mountable High efficiency: up to 93% True sine wave output Parallelable output with
More informationBasic Methods for DTE Power Delivery
Basic Methods for DTE Power Delivery Ed Walker TI Technical Staff Analog Field Applications Cary, NC Design Example attempt to show Methods of implementation for power, isolation and output control leverage
More informationHuawei Embedded Power System
Huawei Embedded Power System HUAWEI TECHNOLOGIES CO., LTD. Contents Embedded DC Power System ETP483-A1... 1 ETP489-A2... 2 ETP4815-A3... 3 ETP482-C5A1... 4 Rectifier Module R4815G1... 5 R4815N1... 6 R483G1...
More informationPRODUCT BROCHURE. Cyberex PowerBuilt Industrial UPS Uninterruptible power supply system 10 80kVA
PRODUCT BROCHURE Cyberex PowerBuilt Industrial UPS Uninterruptible power supply system 10 80kVA 2 C Y B E R E X P O W E R B U I LT I N D U S T R I A L U P S The Cyberex PowerBuilt is a true online double-conversion
More informationModular three-phase UPS system. Conceptpower DPA kva True modular UPS system for critical applications
Modular three-phase UPS system Conceptpower DPA 10 250 kva True modular UPS system for critical applications A UPS designed to meet the needs of today and tomorrow The Conceptpower DPA is a high-power,
More informationSLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters
Applications Telecom IT Industrial Safety in compliance with IEC60950:1999, 3 rd edition; EN60950:2000; UL60950, 3 rd edition; CSA Standard C22.2 No.60950-00, 3 rd edition Features New, compact design:
More informationPower distribution solutions for the ProLiant DL580 G2 server
Power distribution solutions for the ProLiant DL580 G2 server Introduction... 2 Symbols in text... 2 Executive summary... 2 Glossary... 2 ProLiant DL580 G2 server power requirements... 3 Power distribution
More informationMSR 2400W. Multi purpose Power System for Telecom and Industrial Applications. Nominal Output Voltage. Voltage Setting Range
MSR 2400W Multi purpose Power System for Telecom and Industrial Applications 2400 W modular system All voltages available 0 144VDC per module U and I adjustable from 0 to max value Hot-swap plug-in modules
More informationon-line LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs industrial applications
ZP110 on-line UPS 1, 2, 3, 6, 10kVA single/single phase LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs Emergency Devices (Lights/Alarms) Electro-Medical Devices
More informationTHOR Modular. Modular UPS system. Online double-conversion Scalable Decentralized Parallel. Modular. 10, 20, 30, 40kVA modules kVA systems
Power Supplies Modular THOR Modular Modular UPS system Online double-conversion Scalable Decentralized Parallel Modular 10, 20, 30, 40kVA modules 10-520kVA systems Power factor 1.0 at 10/20kVA/kW modules
More informationSmartOnline V 10kVA 7kW Online, Double-Conversion UPS, 6U Rack/Tower, Extended Run, Pre-installed SNMP port, RS232, 3 Phase in-single Phase out
SmartOnline 200-240V 10kVA 7kW Online, Double-Conversion UPS, 6U Rack/Tower, Extended Run, Pre-installed SNMP port, RS232, 3 Phase in-single Phase out MODEL NUMBER: SU10KRT3/1X Highlights 10,000VA (10kVA)
More informationHP Uninterruptible Power Supplies Overview
NOTE: Additional information on these and additional HP UPS products at: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/index.html Description HP rack mountable UPSs, designed
More informationAP160N Online UPS compact
Online UPS compact Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs Emergency devices (light, alarm) Medical devices Telecommunication devices Rack-tower convertible
More informationPSL. Power Quality & Energy Monitoring. PQube power quality & energy analyzer. Low-Cost, High-Precision
Low-Cost, High-Precision Power Quality & Energy Monitoring PQube power quality & energy analyzer AC and DC Monitoring Lab-Grade Accuracy Modular & Embeddable Plug-and-Play Functionality Direct Remote Communication
More informationSafety Standards. Model Number: Unit Weight:
MEA-250A24C Highlights & Features Meet Efficiency Level VI Safety Approvals to IEC 60601-1 3.1 Ed. & IEC 60950-1 Compliant with IEC 60601-1-2 3 th and 4 th Ed. Requirements IP22 ingress protection rating
More informationRAILWAY & METRO MEETING ALL POWER REQUIREMENTS ALONG THE TRACK
RAILWAY & METRO MEETING ALL POWER REQUIREMENTS ALONG THE TRACK do you have the power to take your raıl servıce ınto the future? Safety, timeliness and efficiency are the hallmarks of high quality train
More informationSmartPro 120V 2.2kVA 1.6kW Line-Interactive UPS, Tower, Extended Run, Network Card Options, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.6kW Line-Interactive UPS, Tower, Extended Run, Network Card Options, USB, DB9 Serial MODEL NUMBER: SMART2200VSXL Highlights 2.2kVA / 2200VA line interactive tower UPS system 120V
More informationDATA CENTER MEETING ALL POWER REQUIREMENTS IN THE DATA CENTER
DATA CENTER MEETING ALL POWER REQUIREMENTS IN THE DATA CENTER DO YOU HAVE THE POWER TO GROW YOUR DATA CENTER BUSINESS? Data center operation is a no compromise business. Customers are buying peace-of-mind
More information