Replacement of the University of Missouri Research Reactor (MURR) Cooling Towers

Size: px
Start display at page:

Download "Replacement of the University of Missouri Research Reactor (MURR) Cooling Towers"

Transcription

1 Replacement of the University of Missouri Research Reactor (MURR) Cooling Towers Les Foyto, Associate Director John Fruits, Reactor Manager Carl Herbold, Assistant Reactor Manager

2 Overview MURR Facility Cooling Tower History Tower Design Project Background and Timeline The Big Snag The Big Lag Lessons Learned Q & A

3 History of MURR Located in Columbia, Missouri October 13, 1966 Facility established initial criticality and licensed to operate at 5 MWs July 18, 1974 Facility uprated to 10 MWs September 1, 1977 Facility starts a 10 MW, 150-hour-per-week operating schedule September 1, 2006 Facility submits 20-year license renewal application to the NRC

4 Key Reactor Parameters MURR is a pressurized, reflected, heterogeneous, open pool-type, which is light-water moderated and cooled Maximum thermal power 10 MW Peak flux in center test hole 6.0E14 n/cm 2 -s Core 8 fuel assemblies (775 grams of U-235/assembly) Control blades 5 total: 4 boral shim-safety, 1 SS regulating Reflectors beryllium and graphite Forced primary coolant flow rate 3,750 gpm (237 lps) Forced pool coolant flow rate 1,200 gpm (76 lps) Primary coolant temps 120 F (49 C) inlet, 136 F (58 C) outlet Primary coolant system pressure 85 psia (586 kpa) Pool coolant temps 100 F (38 C) inlet, 106 F (41 C) outlet Beamports three 4-inch (10 cm), three 6-inch (15 cm)

5

6 Reactor Core Assembly 3-D View 2-D View

7 Funding for the Project Amount ~$84K Source Global Threat Reduction Initiative (GTRI) Reactor Conversion Program through a Work Order from Argonne National Laboratory This funding is part of the HEU/LEU fuel conversion project: Funded temporary cooling tower tie-ins Funded thermal-hydraulic study for new cooling towers ~$1.29 mil Funded purchase of new cooling tower Funded demolition of old cooling tower and installation of the new cooling tower Funded installation, rent and removal of temporary cooling towers Funded installation of data acquisition system

8 Previous Cooling Tower History 1964/65 Original 2 Cell Cooling Tower Installed 1973/74 3rd Cell added for 10 MW Power Uprate Cooling Tower Refurbished Cooling Tower Refurbished 2004/05 Cooling Tower Electrical Upgrades 7

9 Project Background Activity GTRI lays groundwork via thermal design study and replacement cost estimate NEUP provides catalyst, which GTRI prepared us for University Campus Facilities provides project management, contracts designer and general contractor GTRI provides temporary tower connections University Procurement purchases new cooling towers University Procurement leases temporary towers

10 Tower Design

11 Tower Design

12 Tower Design Three cells Original Wood frame, induced-draft, cross-flow, PVC fill Concrete basin/sump Two-speed 40 HP fans Cools 4688 gpm (296 lps) From 104 deg-f (40 C) To 87 deg-f (31 C) At 77 deg-f (25 C) wet-bulb temperature Three cells Current Stainless Steel frame, induceddraft, cross-flow, PVC fill Elevated Stainless Steel basin Two-speed 40 HP fans Cools 5400 gpm (341 lps) From 115 deg-f (46 C) To 86 deg-f (30 C) At 80 deg-f (27 C) wet-bulb temperature

13

14 Date Activity Project Timeline 09/26/11 Commenced installation of temporary cooling towers 10/10/11 Placed temporary cooling towers on service 10/19/11 Commenced demolition of old cooling tower 10/24/11 Commenced Installation of new cooling tower 12/30/11 New cooling tower essentially complete 01/02/12 Placed new cooling tower on service 01/17/12 Commenced removal of temporary cooling towers 01/18/12 Temporary cooling towers removed

15

16

17

18

19

20

21

22

23

24 The Big Snag Week of October 10 th, 2011 Monday Thursday Friday-Sunday Placed temporary cooling towers on service Noted excess and growing volume of water in basement sump Noted excess water makeup on temporary cooling towers Secured temporary booster pumps to minimize losses DIG, DIG, DIG

25

26

27 The Big Lag Noted decrease in performance of the two parallel primary heat exchangers Frequent backflushing did not resolve or improve thermal performance **Reactor power was reduced for a period of weeks**

28 9/2006 8/2006 7/2007 9/2007 8/2007 7/2007 6/2008 7/2008 6/2008 5/2008 4/2009 6/2009 5/2009 4/2009 3/2010 5/2010 4/2010 3/2010 2/2011 4/2011 3/2011 2/2011 1/2012 2/2012 1/2012 0/2012 9/2013 Log Mean Temperature Difference The Big Lag 100% 90% Mechanical Cleaning on 503A 80% 70% 60% 50% 40% 30% 20% 10% 0% Installation of Temporary Towers 503B 503A 503 Average Plate Replacement on 503B

29 The Big Lag Roughly 240 lb (110 kg) of calcium scale was removed HX was reassembled and retested in 36 hours

30 Lessons Learned Don t replace your cooling tower

31 Lessons Learned Don t replace your cooling tower The one part of your system you have the least access to will be the part that breaks

32 Lessons Learned Don t replace your cooling tower The one part of your system you have the least access to will be the part that breaks Significant operational impacts from proper chemistry control

33 Lessons Learned Don t replace your cooling tower The one part of your system you have the least access to will be the part that breaks Significant impact to proper chemistry control Clear and knowledgeable communication on leased equipment

34 Thank You For Your Attention, Any Questions???

Measuring and Managing a Data Center Cooling Shutdown

Measuring and Managing a Data Center Cooling Shutdown Measuring and Managing a Data Center Cooling Shutdown Columbia University Information Technology - August 24, 2012 Table of Contents Overview Timeline Cricket Graphs What s being graphed Mechanical Electrical

More information

FLEX Implementation. Roy Harter RLH Global Services. SAMG-D course, IAEA, Vienna, Austria October

FLEX Implementation. Roy Harter RLH Global Services. SAMG-D course, IAEA, Vienna, Austria October FLEX Implementation Roy Harter RLH Global Services rlharter@aol.com SAMG-D course, IAEA, Vienna, Austria 19-23 October 2015 What is FLEX? US Nuclear Industry Response to NRC Mitigating Strategies Order

More information

LABVIEW APPLICATION: ENERGY LABORATORY UPGRADE

LABVIEW APPLICATION: ENERGY LABORATORY UPGRADE Session 3233 LABVIEW APPLICATION: ENERGY LABORATORY UPGRADE J. Howard Arthur Michael R. Sexton Mechanical Engineering Department Virginia Military Institute Lexington, VA 24450 Abstract This paper describes

More information

Indirect Adiabatic and Evaporative Data Centre Cooling

Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced

More information

update: HPC, Data Center Infrastructure and Machine Learning HPC User Forum, February 28, 2017 Stuttgart

update: HPC, Data Center Infrastructure and Machine Learning HPC User Forum, February 28, 2017 Stuttgart GCS@LRZ update: HPC, Data Center Infrastructure and Machine Learning HPC User Forum, February 28, 2017 Stuttgart Arndt Bode Chairman of the Board, Leibniz-Rechenzentrum of the Bavarian Academy of Sciences

More information

Rear Door Heat Exchanger

Rear Door Heat Exchanger Vinod Kamath Power and Thermal Engineering Sep 16, 2005 Problem Statement Rack Power loads are high due to increased compute density. The impact is seen in datacenters as high inlet air temperatures to

More information

Indirect Adiabatic and Evaporative Data Center Cooling

Indirect Adiabatic and Evaporative Data Center Cooling Indirect Adiabatic and Evaporative Data Center Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced technology

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

HIGH EFFICIENCY Central Chiller

HIGH EFFICIENCY Central Chiller Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,

More information

Chiller Replacement and System Strategy. Colin Berry Account Manager

Chiller Replacement and System Strategy. Colin Berry Account Manager Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit

More information

Radiation Center Strategic Plan Mission, Vision, Goals and Strategies for Activities and Operations

Radiation Center Strategic Plan Mission, Vision, Goals and Strategies for Activities and Operations Radiation Center Strategic Plan 2012 Mission, Vision, Goals and Strategies for Activities and Operations July 2012 Radiation Center Strategic Plan 2012 Mission, Vision, Goals and Strategies for Activities

More information

New Nuclear Technology. NuScale Power Safe. Clean. Economic. Simple Small Modular Reactors. Congressional Briefing February 25, 2013

New Nuclear Technology. NuScale Power Safe. Clean. Economic. Simple Small Modular Reactors. Congressional Briefing February 25, 2013 New Nuclear Technology NuScale Power Safe. Clean. Economic. Simple Small Modular Reactors Congressional Briefing February 25, 2013 Michael S. McGough Chief Commercial Officer NuScale Power, LLC 2012 NuScale

More information

Engine Control Workstation Using Simulink / DSP Platform (COOLECW) SENIOR PROJECT PROPOSAL

Engine Control Workstation Using Simulink / DSP Platform (COOLECW) SENIOR PROJECT PROPOSAL Engine Control Workstation Using Simulink / DSP Platform (COOLECW) SENIOR PROJECT PROPOSAL By: Mark Bright and Mike Donaldson Project Advisor: Dr. Gary Dempsey Date: Dec 11, 2008 1 Project Summary Cooling

More information

Contents. Rev. 2, 5/12/2016 1

Contents. Rev. 2, 5/12/2016 1 Answers to Frequently Asked Questions for CTI STD-201 Thermal Certification of Cooling Towers, Closed Circuit Coolers and Evaporative Refrigerant Condensers Contents What is CTI STD-201?... 3 To what equipment

More information

Silicon Valley Power Data Center Program Rebate Application

Silicon Valley Power Data Center Program Rebate Application Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account

More information

Comprehensive Energy Management & Utility Master Plan

Comprehensive Energy Management & Utility Master Plan Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach

More information

Saving Water and Operating Costs at NREL s HPC Data Center

Saving Water and Operating Costs at NREL s HPC Data Center Saving Water and Operating Costs at NREL s HPC Data Center Thomas P. Carter, P.E. Johnson Controls Thomas.P.Carter@jci.com David Sickinger National Renewable Energy Laboratory David.Sickinger@nrel.gov

More information

Chiller Plant Optimization: A Case Study

Chiller Plant Optimization: A Case Study Presentation of Chiller Plant Optimization: A Case Study Presented by Michael S. Conway The site Large pharmaceutical client 5 MW cogen 88,000 PPH of boiler capability 8,200 tons of chiller capability

More information

This standard sets forth a program. will certify that all models of a line of water cooling towers offered for sale by a specific

This standard sets forth a program. will certify that all models of a line of water cooling towers offered for sale by a specific STD-201 CERTIFICATION PURPOSE This standard sets forth a program whereby the Cooling Technology Institute will certify that all models of a line of water cooling towers offered for sale by a specific manufacturer

More information

Resolution 1 F (1 C) single point; degrees C or Calibration single or dual point Calibration F

Resolution 1 F (1 C) single point; degrees C or Calibration single or dual point Calibration F RMS Rainwater Harvesting Series 100 Controller Specifications Measurement Performance Contacting Conductivity ph Range 0-10,000 µs/cm Range -2 to 16 ph units Resolution 1 µs/cm Resolution 0.01 ph units

More information

Filter Fan Unit LIGHT

Filter Fan Unit LIGHT Filter Fan Unit LIGHT Type LIGHT EC Technical Concept Technical Concept Filter Fan Unit LIGHT Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean air to individual

More information

M. Middleton, R.E. Williams, Bryan Eyers and Dan Khan NIST Center for Neutron Research TRTR 2016 August 25, 2016

M. Middleton, R.E. Williams, Bryan Eyers and Dan Khan NIST Center for Neutron Research TRTR 2016 August 25, 2016 Lessons Learned using a PLC for Process Control M. Middleton, R.E. Williams, Bryan Eyers and Dan Khan NIST Center for Neutron Research TRTR 2016 August 25, 2016 Lessons Learned using a PLC for Process

More information

Installation of a Second CLICIT Irradiation Facility at the Oregon State TRIGA Reactor

Installation of a Second CLICIT Irradiation Facility at the Oregon State TRIGA Reactor Installation of a Second CLICIT Irradiation Facility at the Oregon State TRIGA Reactor Robert Schickler and Steve Reese Oregon State University, 100 Radiation Center Corvallis, OR, 97330 USA Corresponding

More information

Technical Concept. Filter Fan Unit LIGHT. Type LIGHT AC Type LIGHT EC

Technical Concept. Filter Fan Unit LIGHT. Type LIGHT AC Type LIGHT EC Technical Concept Filter Fan Unit LIGHT Type LIGHT AC Type LIGHT EC Filter Fan Unit LIGHT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean air

More information

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable

More information

MK SERIES CROSS FLOW COOLING TOWER

MK SERIES CROSS FLOW COOLING TOWER The Ultimate Cooling Machine MK SERIES CROSS FLOW COOLING TOWER CERTIFIED PERFORMANCE DURABLE ENERGY & SPACE SAVING MODEL DEFINITION FOR MK2348E-2BI MK 2348 E 2 B I CROSS FLOW TYPE BOX SIZE MOTOR SIZE

More information

Assembly and Maintenance

Assembly and Maintenance Assembly and Maintenance Assembly and Maintenance Test Pumps Pressure Test Pumps Tests all types of installations such as heating, compressed air and refrigeration systems, oil installations, fire lines

More information

Type. Facts. 441, 442 Full nozzle DIN. Flanged Safety Relief Valves spring loaded. The-Safety-Valve.com. Metric Units LWN E

Type. Facts. 441, 442 Full nozzle DIN. Flanged Safety Relief Valves spring loaded. The-Safety-Valve.com. Metric Units LWN E Type 441, 442 DIN Flanged Safety Relief Valves spring loaded Metric Units Facts The-Safety-Valve.com LWN 468.01-E DIN, ANSI 40 Cap H2 19 Lock nut 18 Adjusting screw with bushing 16 Upper spring plate 12

More information

Sputtering Sensor ADVANTAGES

Sputtering Sensor ADVANTAGES The INFICON is specifically designed for use in any sputtering process. The sensor body and cooling tubes are gold plated beryllium copper for maximum cooling efficiency in the sputtering environment.

More information

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1 00 01 10 Table of Contents DIVISION 00: PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 06.17.2014 00 21 13 Instructions to Bidders 11.08.2013 00 22 13 Supplementary Instructions

More information

Standard Circulating Pumps

Standard Circulating Pumps Product review Range: 1 1 3Q [ m³/h] Hz - North America 1 3 1 1 1.x1 1.x x x3 x 1 1 Q [ US gpm] >Single-head pumps: Seal-less circulator with flanged connection. Two speed, manually adjustable to match

More information

LADWP POWER INFRASTRUCTURE PLAN

LADWP POWER INFRASTRUCTURE PLAN LADWP 2017-18 POWER INFRASTRUCTURE PLAN Introduction LADWP has built a vast power generation, transmission and distribution system that spans five Western states, and delivers electricity to about 4 million

More information

UPGRADE PROGRAM. V250 Series Pumps vs V301 Series Pumps. Technical Memo

UPGRADE PROGRAM. V250 Series Pumps vs V301 Series Pumps. Technical Memo UPGRADE PROGRAM V250 Series Pumps vs V301 Series Pumps Technical Memo INDEX Outline drawings ISO100 3 Outline Drawing CFF6 5 Technical Specification 7 Notes 8 Accessories 8 Controller comparison 9 Outline

More information

98 Series Back Pressure. Valve Link. Features. Fisher Controls. August 1993 Bulletin 71.4:98

98 Series Back Pressure. Valve Link. Features. Fisher Controls. August 1993 Bulletin 71.4:98 Series Back Pressure and Type Relief VL000 Valves FIELDVUE Valve Link Fisher Controls August Bulletin.: The Series (figure ) is used for back pressure or relief applications in liquid, gas, air, and steam

More information

Example. Section: PS 709 Examples of Calculations of Reduced Hours of Work Last Revised: February 2017 Last Reviewed: February 2017 Next Review:

Example. Section: PS 709 Examples of Calculations of Reduced Hours of Work Last Revised: February 2017 Last Reviewed: February 2017 Next Review: Following are three examples of calculations for MCP employees (undefined hours of work) and three examples for MCP office employees. Examples use the data from the table below. For your calculations use

More information

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

Customer Responsibilities

Customer Responsibilities For Research Use Only. Not for use in diagnostic procedures. Thank you for purchasing the Agilent G5590A BenchCel Workstation. To get you started and to assure a successful and timely installation, please

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

1/28/2013. ASHRAE Standard ASHRAE Standard Aiming at 50% Energy Savings For ASHRAE Standard 90.

1/28/2013. ASHRAE Standard ASHRAE Standard Aiming at 50% Energy Savings For ASHRAE Standard 90. -203-203 Stephen V. Skalko, P.E. Chair SSPC 90. Aiming at 50% Energy Savings For 90.-203 ASHRAE Winter Meeting January 28, 203 AIA Objectives for the Session Develop basic understanding of different formats

More information

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH 1 Chilled and Hot Water Fan Coil Low Static 4-Pipe Nominal Size:

More information

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system Fair City Plaza Task: Diagnose problems, recommend improvements for small municipal district cooling system The Fair City Plaza district cooling system provides chilled water to five buildings in a downtown

More information

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED

More information

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

Data Center Trends and Challenges

Data Center Trends and Challenges Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to

More information

LAKEWOOD INSTRUMENTS MODEL 1575e WATER TREATMENT CONTROLLER

LAKEWOOD INSTRUMENTS MODEL 1575e WATER TREATMENT CONTROLLER LAKEWOOD INSTRUMENTS MODEL 1575e WATER TREATMENT CONTROLLER The Model 1575e uses the latest in microprocessor capability, giving the user a high level of application flexibility. A large illuminated graphics

More information

Excellent location for Data Center Campus in Hanko

Excellent location for Data Center Campus in Hanko Excellent location for Data Center Campus in Hanko CAMPUS LOCATION AND LOGISTICS Ideal Data Center site location Hanko Data Center campus is located in the City of Hanko, Southern Finland The site is ideal

More information

APC APPLICATION NOTE #126

APC APPLICATION NOTE #126 #16 Selection Procedure for Inow Chilled Water Products By Greg Uhrhan, P.E. and Scott Buell Abstract Proper selection of Inow chilled water cooling systems requires an engineer or technical salesperson

More information

Butterfly Control Valve. DMK/6 Series

Butterfly Control Valve. DMK/6 Series Butterfly Control Valve DMK/6 Series UL Listed for US and Canada UL 842 and ULc C125 & C842 File # MH 18741 Models DMK 707/6 (3/4 NPT) DMK 710/6 (1 NPT) DMK 712/6 (1 1/4 NPT) DMK 715/6 (1 1/2 NPT) DMK

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Blending Conveying Drying Process Cooling Heat Transfer Size Reduction GP SERIES Packaged Chillers Comprehensive Flexible Versatile Compact unitary designs available in a variety of configurations from

More information

Next Generation DCP Optimization using MV VSDs

Next Generation DCP Optimization using MV VSDs Next Generation DCP Optimization using MV VSDs Vivek Apte Regional Product Director Johnson Controls - Middle East Cell : +971506243059 IDEA 2016- Dubai 1 Central Plant Optimization Energy and operating

More information

+91-8048763833 Janani Enterprises, Coimbatore http://www.industrialcoolingequipments.com/ We are one of the leading Manufacturer, Wholesaler, Trader, Exporter and Importer of a wide range of Cooling Tower,

More information

Case Study: Energy Systems Integration Facility (ESIF)

Case Study: Energy Systems Integration Facility (ESIF) Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case

More information

OPTIONS FOR INFORMATION COMMUNICATION TECHNOLOGY (ICT) PROVISION AND SUPPORT CONTRACT

OPTIONS FOR INFORMATION COMMUNICATION TECHNOLOGY (ICT) PROVISION AND SUPPORT CONTRACT OPTIONS FOR INFORMATION COMMUNICATION TECHNOLOGY (ICT) PROVISION AND SUPPORT CONTRACT 1 PURPOSE OF REPORT 1.1 The Council contracts externally for the provision of ICT services and, with marginally in

More information

Virtual Temperature Cycle Test (TCT) for validation of indirect Charge Air Coolers and Exhaust Gas Recirculation Coolers

Virtual Temperature Cycle Test (TCT) for validation of indirect Charge Air Coolers and Exhaust Gas Recirculation Coolers Virtual Temperature Cycle Test (TCT) for validation of indirect Charge Air Coolers and Exhaust Gas Recirculation Coolers STAR Global Conference 2014 Vienna, March 17-19 G. Apostolopoulos, R. Stauch, C.

More information

Applications: Page 60. Chemical manufacturing / processing plants Paint manufacturing facilities Bulk truck terminals Refineries

Applications: Page 60. Chemical manufacturing / processing plants Paint manufacturing facilities Bulk truck terminals Refineries CSA - Class I Div. 1 - Groups C & D CSA - Class I Div. 2 - Groups A, B, C & D CSA - Class II Div. 1 & 2 - Groups E, F & G CSA - Class III UL 844 - Class I Div. 1 - Groups C & D UL 844 - Class I Div. 2

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Slide 1. Slide 2. Voisey s Bay Project Update

Slide 1. Slide 2. Voisey s Bay Project Update Slide 1 Slide 2 Voisey s Bay Project Update October 2003 Slide 3 Presentation Overview Project Components Mine and Concentrator Exploration Argentia Hydromet R&D Innovation Centre Expenditure Forecast

More information

ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS

ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS GLOBAL PRESENCE, LOCAL SERVICE WHERE WE MAKE IT WORK WHO WE MAKE IT WORK FOR ACCREDITATIONS i-chiller -10 C to 30 C 1.7 TO 505kW i-chiller COMPACT

More information

Saving Energy with Free Cooling and How Well It Works

Saving Energy with Free Cooling and How Well It Works Saving Energy with Free Cooling and How Well It Works Brent Draney HPC Facility Integration Lead Data Center Efficiency Summit 2014-1 - NERSC is the primary computing facility for DOE Office of Science

More information

Safety and Security a Single Entity at the JM-1 SLOWPOKE-2 Reactor Facility

Safety and Security a Single Entity at the JM-1 SLOWPOKE-2 Reactor Facility Safety and Security a Single Entity at the JM-1 SLOWPOKE-2 Reactor Facility RONMCCREA CUSHNIE JOHN PRESTON The International Centre for Environmental and nuclear sciences Overview Facility Overview Project

More information

Henderson Mill Road 48 Water Line Issue. Thursday, July 23, 2015 Monday, July 27, 2015

Henderson Mill Road 48 Water Line Issue. Thursday, July 23, 2015 Monday, July 27, 2015 Henderson Mill Road 48 Water Line Issue Thursday, July 23, 2015 Monday, July 27, 2015 Situation A grass cutting crew working in the area hit a fire hydrant on Henderson Mill Road The fire hydrant was directly

More information

DATA CENTER LIQUID COOLING

DATA CENTER LIQUID COOLING DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid

More information

COLOR MEGARAD Cameras

COLOR MEGARAD Cameras State of the art camera regarding image quality and radiation tolerance with 720 TV-lines horizontal resolution and perfect color reproduction. Special inspection in high radiation areas and spaces. IVVI

More information

Standard Circulating Pumps

Standard Circulating Pumps Product review Range: 1 1 3Q [ m³/h] Hz - North America 1 3 1 1 1.x1 1.x x x3 x 1 1 Q [ US gpm] >Single-head pumps: Circulating pumps with flanged connection > Applications: Drinking-water circulation

More information

COOLING SOLUTIONS BY LABTECH INNOVATION INSPIRED

COOLING SOLUTIONS BY LABTECH INNOVATION INSPIRED WATER CHILLERS COOLING SOLUTIONS COOLING SOLUTIONS BY LABTECH Even if water is one of the most precious and scarce resources, it is still largely used as coolant in many laboratories. Most of the water

More information

4" MULTISTAGE CENTRIFUGAL SUBMERSED PUMPS COMPLETE WITH MOTOR

4 MULTISTAGE CENTRIFUGAL SUBMERSED PUMPS COMPLETE WITH MOTOR NOCCHI SCM 4 PLUS Maximum rigidity and resistance to water hammer, Strong resistance to the abrasive action of sand, Excellent hydraulic efficiency SCM 4 PLUS submersible pumps consist of a multi-stage

More information

GENERATOR ADDENDUM TO MAGNOLIA GARDENS ASSISTED LIVING COMPREHENSIVE EMERGENCY MANAGEMENT PLAN

GENERATOR ADDENDUM TO MAGNOLIA GARDENS ASSISTED LIVING COMPREHENSIVE EMERGENCY MANAGEMENT PLAN Contact Person: Philip McCollum - Administrator Magnolia Gardens Assisted Living AL Lic# 10314 3800 62 nd Avenue North Pinellas Park, FL 33781 Phone: 727.489.6440 GENERATOR ADDENDUM TO MAGNOLIA GARDENS

More information

STD-201 CERTIFICATION PURPOSE

STD-201 CERTIFICATION PURPOSE STD-201 CERTIFICATION PURPOSE This standard sets forth a program whereby the Cooling Technology Institute will certify that all models of a line of water cooling towers offered for sale by a specific manufacturer

More information

XBR V4 INSTALLATION AND USER GUIDE

XBR V4 INSTALLATION AND USER GUIDE XBR V4 INSTALLATION AND USER GUIDE xbr V4 Installation and User Guide Page 1 of 18 Revision History Dash#/Rev Date Author Description 0.1 04/03/2013 Eric Anderson Initial draft 0.2 04/08/2013 Eric Anderson

More information

Performance Test of Core Protection and Monitoring System with DLL for SMART Simulator Implementation

Performance Test of Core Protection and Monitoring System with DLL for SMART Simulator Implementation 2014 KNS Spring Meeting in Jeju Performance Test of Core Protection and Monitoring System with DLL for Simulator Implementation BonSeung Koo, DaeHyun Hwang and KeungKoo Kim May 29-30, 2014 Korea Atomic

More information

FOX-50 Heat Flow Meter

FOX-50 Heat Flow Meter FOX-50 Heat Flow Meter Site Preparation Guide Revision A Issued June 2016 Page 1 Table of Contents Table of Contents... 1 Ideal Setup... 2 System Components... 3 Instrument Measurements... 4 Utility Requirements...

More information

Thermal Diffusivity Instruments DLF-2 with EM-1600

Thermal Diffusivity Instruments DLF-2 with EM-1600 Thermal Diffusivity Instruments DLF-2 with EM-1600 Site Preparation Guide Revision A Issued February 2017 Table of Contents Table of Contents... 1 Ideal Setup... 2-3 System Components... 3 Instrument Measurements...

More information

Isotemp. Bath Circulators. Improve the productivity. of your lab with solutions. from Fisher Scientific

Isotemp. Bath Circulators. Improve the productivity. of your lab with solutions. from Fisher Scientific Isotemp Bath Circulators Improve the productivity of your lab with solutions from Fisher Scientific I s o t e m p B a t h Isotemp Refrigerated and Heating Bath Circulators Three Controller Choices: Programmable,

More information

3D Galaxy II GH-WIU02. English User s Manual

3D Galaxy II GH-WIU02. English User s Manual 3D Galaxy II GH-WIU02 English User s Manual 3D Galaxy II Liquid Cooling System Caution 1. Before pouring liquid coolant into the tank to test the liquid cooling system, please reconfirm all the tubes have

More information

DMT PERFORMING UNDER PRESSURE DMT. All-Media Pressure Scanner Features. Applications. Description 1/8

DMT PERFORMING UNDER PRESSURE DMT. All-Media Pressure Scanner Features. Applications. Description 1/8 Features Low Pass Anti-aliasing Filter per Channel Up to ±0.05% System Accuracy EU Throughput Rates in excess of 100 Hz 10 BaseT Ethernet Interface, TCP & UDP Protocol Pressure Ranges from 5 psi (34 kpa)

More information

SERPENT Cross Section Generation for the RBWR

SERPENT Cross Section Generation for the RBWR SERPENT Cross Section Generation for the RBWR Andrew Hall Thomas Downar 9/19/2012 Outline RBWR Motivation and Design Why use Serpent Cross Sections? Modeling the RBWR Generating an Equilibrium Cycle RBWR

More information

The 5400A Series, Group D, end-of-line flame arrester is designed to prevent the propagation of flames into a storage vessel.

The 5400A Series, Group D, end-of-line flame arrester is designed to prevent the propagation of flames into a storage vessel. Varec 00A Series The 00A Series, Group D, end-of-line flame arrester is designed to prevent the propagation of flames into a storage vessel. Introduction Varec s have been the industry standard for over

More information

Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach

Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach Hiroshi Nagazono In recent years, IT devices such as servers have come to have high performance and be highly integrated

More information

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve the

More information

BIG BUTTON PHONE WITH ONE TOUCH DIALING AND

BIG BUTTON PHONE WITH ONE TOUCH DIALING AND FUTURE CALL LLC BIG BUTTON PHONE WITH ONE TOUCH DIALING AND 40db HANDSET VOLUME MODEL: FC-1507 USER MANUAL Please follow instructions for repairing if any otherwise do not alter or repair any parts of

More information

A 101 A B C. Variable flow-control valve, series DXC. Dynamic Flow Networking. Description. Content

A 101 A B C. Variable flow-control valve, series DXC. Dynamic Flow Networking. Description. Content 101 DX Variable flow-control valve, series DX Pressure independent variable flow-control Dynamic hydronic balancing in full load and part load Integrated flow and temperature measurement Power supply U

More information

Close-coupled cooling

Close-coupled cooling Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable

More information

XBR V3 INSTALLATION AND USER GUIDE Rev 03. xbr V3 Installation and User Guide Page 1 of 14. (preliminary)

XBR V3 INSTALLATION AND USER GUIDE Rev 03. xbr V3 Installation and User Guide Page 1 of 14. (preliminary) XBR V3 INSTALLATION AND USER GUIDE xbr V3 Installation and User Guide Page 1 of 14 Revision History Rev Date Author Description 01 07/03/2012 Eric Anderson Initial release 02 09/25/2012 Eric Anderson Clarification

More information

DOE EM Web Refresh Project and LLNL Building 280

DOE EM Web Refresh Project and LLNL Building 280 STUDENT SUMMER INTERNSHIP TECHNICAL REPORT DOE EM Web Refresh Project and LLNL Building 280 DOE-FIU SCIENCE & TECHNOLOGY WORKFORCE DEVELOPMENT PROGRAM Date submitted: September 14, 2018 Principal Investigators:

More information

WO P-NF-L-M-407c Spec Submittal

WO P-NF-L-M-407c Spec Submittal WO2-2-10000-2P-NF-L-M-407c Spec Submittal General Specifications WO2-2-10000(801304) Width: IN/CM 136.25/346.07 Height: IN/CM 84.5/214.63 Depth: IN/CM 41.7/105.92 Dry weight: LB/KG 4000/1814.37 Operational

More information

9861 Series. High Temperature Mass Flow Controllers/Meters. Overview. Product Description. Thermal Mass Flow

9861 Series. High Temperature Mass Flow Controllers/Meters. Overview. Product Description. Thermal Mass Flow DS-TMF-9861-Series-MFC-eng August, 2018 Data Sheet 9861 Series 9861 Series Mass Flow Controller/Meters Thermal Mass Flow High Temperature Mass Flow Controllers/Meters Overview Originally developed by Unit

More information

AB x 1 HDMI switch with 3D and 4K support

AB x 1 HDMI switch with 3D and 4K support AB7816 4 x 1 HDMI switch with 3D and 4K support EMXXX Product Title from CMS 2 ENGLISH Table of contents 1.0 Introduction... 2 1.1 Packing contents... 2 2.0 Panel description... 3 3.0 Frequently Asked

More information

shop online:

shop online: Process systems Liquid ring vacuum pumps Single stage pumps 8 Alpha series single stage liquid ring vacuum pumps 9 AL series single stage liquid ring vacuum pumps 97 Two stage pumps 00 SHR series liquid

More information

Overcoming the Challenges of Server Virtualisation

Overcoming the Challenges of Server Virtualisation Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement

More information

2013 AWS Worldwide Public Sector Summit Washington, D.C.

2013 AWS Worldwide Public Sector Summit Washington, D.C. Washington, D.C. How to Buy the Cloud Brett McMillen, Principal Doug VanDyke, General Manager Changing IT Acquisition Strategies Old World IT Price lock Vendor lock-in Rigid CLIN structure CapEx Budget

More information

REPORT TO THE BUSINESS ADMINISTRATION COMMITTEE

REPORT TO THE BUSINESS ADMINISTRATION COMMITTEE REPORT TO THE BUSINESS ADMINISTRATION COMMITTEE RECOMMENDATION TO AWARD A SOLE SOURCE CONTRACT FOR MAINTENANCE AND TECHNICAL SUPPORT OF THE CENTRAL HEATING AND COOLING PLANT S DISTRIBUTED CONTROL SYSTEM

More information

Closed-Loop Water-Cooled Enclosure GL840ES-3048-CLWCE. High Performance 30kW Closed-Loop Water-Cooled Enclosure COOL THE SERVERS, NOT THE ROOM!

Closed-Loop Water-Cooled Enclosure GL840ES-3048-CLWCE. High Performance 30kW Closed-Loop Water-Cooled Enclosure COOL THE SERVERS, NOT THE ROOM! High Performance 30kW Closed-Loop Water-Cooled Enclosure COOL THE SERVERS, NOT THE ROOM! 1 COOL THE SERVERS, NOT THE ROOM! Overcoming Data Center Challenges The Great Lakes Closed-Loop Water-Cooling System,

More information

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data

More information

CV activities on LHC complex during the long shutdown

CV activities on LHC complex during the long shutdown CV activities on LHC complex during the long shutdown Serge Deleval Thanks to M. Nonis, Y. Body, G. Peon, S. Moccia, M. Obrecht Chamonix 2011 Contents Maintenance Upgrade projects UW pumping upgrade Back

More information

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

Motivair MLC-SC Air-Cooled Scroll Chillers Tons INNOVATE DESIGN APPLY www.motivaircorp.com Motivair MLC-SC Air-Cooled Scroll Chillers 100 285 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Businesses who function in today s advanced

More information

Control systems for spallation target in China ADS systems

Control systems for spallation target in China ADS systems The 15th Intern. Conf. on Accelerator and Large Experimental Physics Control Systems (ICALEPCS15) Control systems for spallation target in China ADS systems Zhiyong He, Qiang Zhao,Wenjuan Cui,Yuxi Luo,

More information

Agenda Date: 8/23/17 Agenda Item: SB CLEAN ENERGY

Agenda Date: 8/23/17 Agenda Item: SB CLEAN ENERGY Agenda Date: 8/23/17 Agenda Item: SB STATE OF NEW JERSEY Trenton, New Jersey 08625-0350 www.nj.gov/bpu/ CLEAN ENERGY IN THE MATTER OF THE CLEAN ENERGY PROGRAM AUTHORIZATION OF COMMERCIAL AND INDUSTRIAL

More information

Computer Controlled Steam Turbine, with SCADA TTVC

Computer Controlled Steam Turbine, with SCADA TTVC Technical Teaching Equipment Computer Controlled Steam Turbine, with SCADA TTVC EDIBON SCADA System Teaching Technique used 2 Control Interface Box 5 Cables and Accessories 6 Manuals 3 Data Acquisition

More information

Installation Manual. 1.Included Accessories. System Controller SC-201-6M INT. Requests to Installers *SHA8754 C*

Installation Manual. 1.Included Accessories. System Controller SC-201-6M INT. Requests to Installers *SHA8754 C* System Controller SC-201-6M INT Installation Manual Potential dangers from accidents during installation and use are divided into the following two categories. Closely observe these warnings, they are

More information

Green IT Project: The Business Case

Green IT Project: The Business Case Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at

More information