Case Study: Energy Systems Integration Facility (ESIF)
|
|
- Juliet Lindsey
- 5 years ago
- Views:
Transcription
1 Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1
2 Case Study Roadmap Steve: NREL Introduction Steve: Performance Specs & Integrated Process Design Holistic approach to data center design and integration Peter: Cooling and Energy Recovery Steve: Preliminary (early) data All: Panel Discussion 2
3 NREL Snapshot Only National Laboratory Dedicated Solely to Energy Efficiency and Renewable Energy Leading clean-energy innovation for 37 years ~2300 total staff in world-class facilities Campus is a living model of sustainable energy ~34,000 visitors in FY2013. Located in Golden, Colorado Owned by the Department of Energy Operated by the Alliance for Sustainable Energy 3
4 Scope of Mission Energy Efficiency Renewable Energy Systems Integration Market Focus Residential Buildings Commercial Buildings Data Centers Personal and Commercial Vehicles Solar Wind and Water Biomass Hydrogen Geothermal Grid Infrastructure Distributed Energy Interconnection Battery and Thermal Storage Transportation Private Industry Federal Agencies Defense Dept. State/Local Govt. International 4
5 ESIF: Energy System Integration Facility New 185,000 s.f. research facility Office space for 220. High bay and laboratory space. Data center Integrated chips-to-bricks approach. Process: Design build with performance specs. LEED Platinum Significant achievement for building with large lab and data center load. Planning started in
6 National Renewable Energy Laboratory Steve Hammond NREL Data Center Showcase Facility 10MW, 10,000 s.f. Leverage favorable climate Use evaporative cooling, NO mechanical cooling. Waste heat captured and used to heat labs & offices. World s most energy efficient data center, PUE 1.06! High Performance Computing Petascale+ HPC Capability in year planning horizon 5 to 6 HPC generations. Insight Center Scientific data visualization Collaboration and interaction. Lower CapEx and lower OpEx. Leveraged expertise in energy efficient buildings to focus on showcase data center. Integrated chips to bricks approach.
7 Critical Data Center Specs Warm water cooling, 75F (24C) Water much better working fluid than air - pumps trump fans. Utilize high quality waste heat, 95F (35C) or warmer. +90% IT heat load to liquid. Up to 10% IT heat load to air. High power distribution 480VAC, Eliminate conversions. Think outside the box Don t be satisfied with an energy efficient data center nestled on campus surrounded by inefficient laboratory and office buildings. Innovate, integrate, optimize. Dashboards report instantaneous, seasonal and cumulative PUE values. National Renewable Energy Laboratory Steve Hammond
8 System Integration Designing for Energy Reuse HIGH PERFORMANCE COMPUTING DATA CENTER IT Load, Grows from 1 MW up to 10 MW Achieving Energy Efficiency Goals Requires: Evaporative Hydronic Cooling (Not Compressor Based) Maximize Direct Heat to Water, Minimize Use of Air for Cooling Maximize Energy Reuse in the Form of Low Grade Heating MUTUALLY BENEFICIAL RELATIONSHIP OFFICE SPACE and HIGH BAY LABORATORIES Require Large Volumes of Ventilation Air (Outside Air) Achieving Energy Efficiency Goals Requires: Maximize Evaporative Cooling, Minimize Compressor Use Utilize Energy Recovery to Reduce Operational Energy Use Provide for Static Pressure Reset & Exhaust Stack Velocity Turn-Down via Wind Anemometer Control. 8
9 COOLING AND ENERGY RECOVERY 9
10 Liquid Cooling Technologies Direct Contact Liquid Cooling TYPICAL SYSTEM CONFIGURATION A Cooling Distribution Unit (CDU) Isolates the Computer Cooling Liquid (Water) from the Central Building Systems The CDUs Circulate Water to Liquid-Cooled Local Heat Sinks (Multiple Each Server) Distribution Manifold Provides Brings Water to Each Server (Radiant Piping Technology) Supports Higher Density Solutions with a Minimal Amount of Air Cooling Required Water is in Direct Contact with Electronic Equipment (No Heat Pipe Interface) Higher Water Quality Requirements Higher Water Damage Risk Due to Multiple System Connections and Distribution Piping 10
11 Benefits of Liquid Cooling Thermal Stability DESIGN CONSIDERATIONS Due to the High and Variable Heat Loads within the Servers, Manufacturer s Favor a Stable, Consistent Temperature Profile Cooling Distribution Units (CDUs) Act as a Buffer to Central Building Systems and Give the User Control over Operating Set Points Dedicated Central Systems Serving the Data Center Need to BOTH Energy Efficiency & Temperature Stability 11
12 NREL Energy Systems Integration Facility Design Conditions and Capacity Liquid Cooling 100% total capacity 75 deg F chilled water supply Minimum 95 deg F return temp Design Capacity Day One: 1.0 MW IT load Final: 10 MW IT load Air Cooling 20% total capacity (Day One 10% capacity) 80 deg F inlet air / 25% RH minimum / 60% RH (42 deg f dp) maximum 100 deg f return temp
13 NREL Energy Systems Integration Facility
14 14
15 45 deg Chilled Water System 29% of the Year in Full Water Side Econmizer 15
16 75 deg Chilled Water System 100% of the Year in Full Water Side Econmizer 16
17 Cooling Load (kw, total) Cooling Load (kw, per rack) % Watercooled Supply Water Temp (F) Water delta T (F) Water press. Drop (PSI) Air Inlet/ Outlet Temp (F) System I % (100F RWT) 20 80/- System II % (85F RWT) 15 80/87 System III % (102.1F RWT) 21 80/96.5 System IV % /- 17
18 18
19 19
20 20
21 21
22 Heat of Vaporization & Evaporative Cooling 22
23 NREL Energy Systems Integration Facility Heat Recovery System Recovered Heat to Lab and Office AHUs
24 Annual Energy GWh/yr Heat MBtu NREL Energy Systems Integration Facility We want the bytes AND the btu s! 10 NREL-ESIF Data Center Energy Recovery at 1 MW IT Load Annual Heat Demand & Recovery 9 2, EUE 0.9 Energy Targets PUE 1.06 EUE 0.9 EUE 0.7 Current Design PUE 1.05 EUE 0.7 Data Center Equipment Load Thermal Energy Recovered 2,000 1,500 1, Recovered Heat Campus Hot Water Heat for Export to Campus Heat Recovered Energy Usage Effectiveness (EUE) = Total Data Center Annual Energy Total Energy Recovered Total IT Equipment Annual Energy
25 THE BOTTOM LINE 25
26 NORMAL POWER (PLUG) DATA CENTER PANEL SP3 NORMAL LIGHTING DATA CENTER PANEL SL3 EMERGENCY LIGHTING DATA CENTER Panel ESL2 COOLING TOWERS DATA CENTER CT-602A, CT-602B, CT-602C, CT-6O2D COOLING TOWER FILTRATION UNIT & TRACE HEATERS FOR PIPING TOWER WATER PUMPS DATA CENTER P-602A, P-602B ENERGY RECOVERY PUMPS P-604A, P-604B AIR-HANDLING UNITS AHU-DC1, AHU-DC2 MAKE-UP AIR-HANDLING UNIT, MAU-DC1 WITH EVAPORATIVE COOLING PUMP DISTRIBUTION BOARD DSB-DCU-1 HPC FLEX RACK #9 HPC FLEX RACK #10 HPC FLEX RACK #11 HPC FLEX RACK #12 POWER DISTRIBUTION UNIT, HPC PDU-DCU-1 POWER DISTRIBUTION UNIT, LEGACY PDU-DCU-2 POWER DISTRIBUTION UNIT, HPC PDU-DC4-1 POWER DISTRIBUTION UNIT, LEGACY PDU-DC4-2 DISTRIBUTION BOARD DSB-DC2-1 DISTRIBUTION BOARD DSB-DC2-2 DISTRIBUTION BOARD DSB-DC1-1 DISTRIBUTION BOARD DSB-DC1-2 STAND-BY LOAD ESIF HPC Datacenter PUE Calculation NREL ESIF DATA CENTER ENERGY EFFICIENCY METRICS ENGINE BLOCK & FUEL HEATERS STAND-BY GENERATOR STAND-BY POWER POWER USE EFFECTIVENESS (PUE) DATA CENTER ENERGY EFFICIENCY IS BENCHMARKED USING AN INDUSTRY STANDARD METRIC OF POWER USE EFFECTIVENESS (PUE). THE PUE IS DEFINED AS FOLLOWS: ENERGY USE EFFECTIVENESS (EUE) ENERGY USE EFFECTIVENESS (EUE) IS A METRIC OF RECOVERED ENERGY BENEFICIALLY USED OUTSIDE OF THE DATA CENTER (HEATING). THE EUE IS DEFINED AS FOLLOWS: CRH CALCULATED POWER BASED ON RUNTIME HOURS (TYPICAL) AUTOMATIC TRANSFER SWITCH, ATS-LS AUTOMATIC TRANSFER SWITCH, ATS-CPLE AUTOMATIC TRANSFER SWITCH, ATS-U1SB POWER USE EFFECTIVENESS = TOTAL FACILITY POWER TOTAL FACILITY POWER IT EQUIPMENT POWER = LIGHTING & PLUG POWER + COOLING LOADS + PUMP LOADS + HVAC LOADS + IT EQUIPMENT POWER ENERGY USE EFFECTIVENESS = TOTAL FACILITY ENERGY TOTAL FACILITY ENERGY RECOVERED ENERGY TOTAL FACILITY ENERGY = LIGHTING & PLUG ENERGY + COOLING LOADS + PUMP LOADS + HVAC LOADS + IT EQUIPMENT ENERGY DATA CENTER NORMAL POWER SERVICE ENTRANCE SWITCHBOARD NORMAL LOAD IT EQUIPMENT POWER = TOTAL POWER USED TO MANAGE, PROCESS, STORE, OR ROUTE DATA WITHIN THE DATA CENTER IT EQUIPMENT ENERGY = TOTAL ENERGY USED TO MANAGE, PROCESS, STORE, OR ROUTE DATA WITHIN THE DATA CENTER EPM UPS UPM1 & UPM2 EPM EPM EPM EPM DATA CENTER ELECTRICAL TRANSFORMER CENTRAL PLANT DISTRIBUTION BOARD DSB-CP MECHANICAL DISTRIBUTION BOARD, DSB-MS1 DISTRIBUTION BOARD DSB-DCU DISTRIBUTION BOARD DSB-DC4 DISTRIBUTION BOARD DSB-DC3 DISTRIBUTION BOARD DSB-DC2 DISTRIBUTION BOARD DSB-DC1 DSB-U1SB CENTRAL PLANT EMERGENCY DISTRIBUTION BOARD, DSB-CPE UPS DISTRIBUTION BOARD ATS-U1SB EPM EPM EPM EPM CRH EPM EPM EPM EPM ELECTRICAL POWER METER (TYPICAL) COOLING DISTRIBUTION RACK, CDU-1 COOLING DISTRIBUTION RACK, CDU-2 COOLING DISTRIBUTION RACK, CDU-3 COOLING DISTRIBUTION RACK, CDU-4 RECOVERED ENERGY BENEFICIALLY USED OUTSIDE DATA CENTER, HEAT EXCHANGER HX-605A COOLING DISTRIBUTION RACK, CDU-5 COOLING DISTRIBUTION RACK, CDU-6 RECOVERED ENERGY (TYPICAL FOR HPC RACKS) LIGHTING & PLUG POWER COOLING LOADS PUMP LOADS HVAC LOADS IT EQUIPMENT POWER
27 STRIBUTION UNIT, PDU-DCU-1 STRIBUTION UNIT, Y PDU-DCU-2 STRIBUTION UNIT, PDU-DC4-1 STRIBUTION UNIT, Y PDU-DC4-2 UTION BOARD SB-DC2-1 UTION BOARD SB-DC2-2 BUTION BOARD SB-DC1-1 BUTION BOARD SB-DC1-2 Preliminary ESIF HPC Datacenter PUE ERGY EFFICIENCY METRICS POWER USE EFFECTIVENESS (PUE) DATA CENTER ENERGY EFFICIENCY IS BENCHMARKED USING AN INDUSTRY STANDARD METRIC OF POWER USE EFFECTIVENESS (PUE). THE PUE IS DEFINED AS FOLLOWS: POWER USE EFFECTIVENESS = TOTAL FACILITY POWER IT EQUIPMENT POWER TOTAL FACILITY POWER IT EQUIPMENT POWER = LIGHTING & PLUG POWER + COOLING LOADS + PUMP LOADS + HVAC LOADS + IT EQUIPMENT POWER = TOTAL POWER USED TO MANAGE, PROCESS, STORE, OR ROUTE DATA WITHIN THE DATA CENTER ENERGY USE EFFECTIVENESS (EUE) ENERGY USE EFFECTIVENESS (EUE) IS A METRIC OF RECOVERED ENERGY BENEFICIALLY USED OUTSIDE OF THE DATA CENTER (HEATING). THE EUE IS DEFINED AS FOLLOWS: ENERGY USE EFFECTIVENESS = TOTAL FACILITY ENERGY IT EQUIPMENT ENERGY Evap Cooling Towers, 2 Lighting, Plug Load, Misc., 6 Pumps, 34 Fan Walls, 7 TOTAL FACILITY ENERGY RECOVERED ENERGY TOTAL FACILITY ENERGY = LIGHTING & PLUG ENERGY + COOLING LOADS + PUMP LOADS + HVAC LOADS + IT EQUIPMENT ENERGY = TOTAL ENERGY USED TO MANAGE, PROCESS, STORE, OR ROUTE DATA WITHIN THE DATA CENTER UPS UPM1 & UPM2 636 = 1.077! EPM EPM EPM EPM DISTRIBUTION BOARD DSB-DCU DISTRIBUTION BOARD DSB-DC4 DISTRIBUTION BOARD DSB-DC3 DISTRIBUTION BOARD DSB-DC2 IT Equipment, 636KW DISTRIBUTION BOARD DSB-DC1
28 Heat ESIF Offices, Labs, ventilation (save $200K / year) Green Data Center Bottom Line IT Load Energy Recovery NO Mechanical Chillers Evap. Water Towers Cost less to build Cost less to operate Comparison of ESIF PUE 1.06 vs efficient 1.3 data center. CapEx No Chillers Initial Build: 600 tons 10 Yr. growth: 2400 tons 10-year Savings: ($1.5K / ton) Savings No Chillers $.9M $3.6M $4.5M OpEx (10MW IT Load) PUE of 1.3 PUE of 1.06 Annual Savings 10-year Savings ($1M / MW year) Utilities $13M $10.6M $2.4M $24M (excludes heat recovery benefit)
29 What s Next - System Integration, DR, and Energy Mgmt MAXIMIZE ENERGY EFFICIENCY & REUSE Maximize Beneficial Daylighting, Minimize Lighting Loads Active Radiant (Chilled) Beams Perimeter Cooling & Heating Underfloor Air, Natural Ventilation, & Solar-Powered Relief Fans ENERGY Mgmt & Demand Response Go beyond power capping Energy Management Alter workload to meet opportunity. Alter workload minimize impact. 29
30 30
Saving Water and Operating Costs at NREL s HPC Data Center
Saving Water and Operating Costs at NREL s HPC Data Center Thomas P. Carter, P.E. Johnson Controls Thomas.P.Carter@jci.com David Sickinger National Renewable Energy Laboratory David.Sickinger@nrel.gov
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationCooling Solutions & Considerations for High Performance Computers
Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationNew ultra-efficient HPC data center debuts 12 March 2013, by Heather Lammers
New ultra-efficient HPC data center debuts 12 March 2013, by Heather Lammers Steve Hammond, director of NREL's Computational Science Center, stands in front of air-cooled racks in the high performance
More informationDATA CENTER LIQUID COOLING
DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationComprehensive Energy Management & Utility Master Plan
Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationGreen IT Project: The Business Case
Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationOptimizing Laboratory Controls through Fault Detection and Diagnostics Software. Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM
Optimizing Laboratory Controls through Fault Detection and Diagnostics Software Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM Overview What are EIS & FDD Tools? Data Connection Methods
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationSession 6: Data Center Energy Management Strategies
Session 6: Data Center Energy Management Strategies Data Center Energy Use and Opportunities: Applying Best Practices to meet Executive Order Requirements Dale Sartor, PE Lawrence Berkeley National Laboratory
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationCatch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable
Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable Urs Iten, Director Global Portfolio Management Data Center siemens.com/datacenters
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationEnergy Efficiency and WCT Innovations
Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data
More informationSaving Energy with Free Cooling and How Well It Works
Saving Energy with Free Cooling and How Well It Works Brent Draney HPC Facility Integration Lead Data Center Efficiency Summit 2014-1 - NERSC is the primary computing facility for DOE Office of Science
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationDEDICATED HEAT RECOVERY UNIT (DHRC)
DEDICATED HEAT RECOVERY UNIT (DHRC) AHRI CERTIFICATION Air-Conditioning, Heating, and Refrigeration Institute Multistack is AHRI Certified and continues to certify products as they are developed AHRI Certification
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationHigh Performance Computing (HPC) Data Center Proposal
High Performance Computing (HPC) Data Center Proposal Imran Latif, Facility Project Manager Scientific & Enterprise Computing Data Centers at BNL 10/14/2015 Quick Facts!! Located on 1 st floor in Building
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationEngineered Energy Solutions An Overview. Controls, Automation and Energy Conservation
Engineered Energy Solutions An Overview Controls, Automation and Energy Conservation Engineered Energy Solutions Independent Control System Integration and Engineering Firm specializing in the energy efficient
More informationEnergy Action Plan 2015
Energy Action Plan 2015 Purpose: In support of the Texas A&M University Vision 2020: Creating a Culture of Excellence and Action 2015: Education First Strategic Plan, the Energy Action Plan (EAP) 2015
More informationAchieving Operational Excellence
Achieving Operational Excellence Energy Efficient Operations in a Shrinking Budget Environment 2010 Energy/Facilities Connections Conference Innovative Approaches for a New Decade DID YOU KNOW? Nine out
More informationSYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC. February 17, 2010 Revised
SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC February 17, 2010 Revised SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BACKGROUND INFORMATION Syracuse University
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationFt Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work
Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive
More informationHybrid Warm Water Direct Cooling Solution Implementation in CS300-LC
Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement
More informationPLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy
PLAYBOOK F O R C H A N G E How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy The world is becoming more digital every day. The demand for feature-rich,
More informationDATA CENTER AIR HANDLING COOLING SOLUTIONS
DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner
More informationCase study on Green Data Center. Reliance Jio Infocomm Limited
Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationNREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions
NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationPhil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical
E n g i n e e r i n g W o r k s h o p : A d v a n c e d C o o l i n g S o l v i n g t h e E n e r g y C h a l l e n g e t h r o u g h I n n o v a t i o n s i n D a t a C e n t e r C o o l i n g 3m.com/immersion
More informationAlfonso Ortega Villanova University Site Director Associate Vice President Research and Graduate Programs James R. Birle Professor of Energy Technology Villanova University www.villanova.edu/es2 Villanova
More informationsystems integration R&D facility.
systems integration R&D facility. Unique Capabilites Hardware-in-the-Loop at Megawatt-scale Power Megawatt-scale power-in-the-loop allows researchers and manufacturers to conduct integration tests at full
More informationContinuous Commissioning at Sandia National Laboratories
Session: Why On going Commissioning Can Lead to Better Performing Buildings Continuous Commissioning at Sandia National Laboratories Jack Mizner Sandia National Laboratories August 10, 2016 Sandia National
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationT66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management
T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell
More informationTrane mytest Water-cooled Chiller Performance Validation What you spec is what you get *
Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get * Trane CenTraVac chillers: Designed and built to be the best; tested to prove it Ongoing innovation. Unmatched capabilities.
More informationM+W Group s Visionary Delta Datacenter
Region Central Europe M+W Germany GmbH A Company of the M+W Group 23 rd April 2014 M+W Group s Visionary Delta Datacenter IKS Data Center Design & Engineering Conference 2014 Moscow, Russia M+W Group at
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationNew Wisconsin Energy Code: What it Means for Me?
2018 Wisconsin Energy Efficiency Expo Hosted by the Wisconsin Association of Energy Engineers New Wisconsin Energy Code: What it Means for Me? May 17, 2018 Shana Scheiber, PE, LEED AP ID+C, WELL AP Building
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationMake the most of your Energy from Power Plant to Plug. Chris Simard, Regional Director Field Sales Group
Make the most of your Energy from Power Plant to Plug Chris Simard, Regional Director Field Sales Group We see six key challenges facing our world Connectivity Simplicity Globalization Demand For Energy
More informationREPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:
REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009
More informationChiller Replacement and System Strategy. Colin Berry Account Manager
Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit
More informationData Center Trends and Challenges
Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationΕΠΛ372 Παράλληλη Επεξεργάσια
ΕΠΛ372 Παράλληλη Επεξεργάσια Warehouse Scale Computing and Services Γιάννος Σαζεϊδης Εαρινό Εξάμηνο 2014 READING 1. Read Barroso The Datacenter as a Computer http://www.morganclaypool.com/doi/pdf/10.2200/s00193ed1v01y200905cac006?cookieset=1
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationData Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. TelecityGroup Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se
More informationRolf Brink Founder/CEO
Rolf Brink Founder/CEO +31 88 96 000 00 www.asperitas.com COPYRIGHT 2017 BY ASPERITAS Asperitas, Robertus Nurksweg 5, 2033AA Haarlem, The Netherlands Information in this document can be freely used and
More informationSTATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016
STATE DATA CENTER DRAFT PROPOSAL 1 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles MEETING GOALS
More informationOperation Guide CT100
Operation Guide CT100 PG 1 The CT100 communicating Z-Wave thermostat operates via a high-quality, easy-to-use touch screen. To set or adjust your CT100, simply touch your finger firmly to the screen. The
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationInnovative Data Center Energy Efficiency Solutions
Innovative Data Center Energy Efficiency Solutions Dr. Hendrik F. Hamann IBM T.J. Watson Research Center 2/8/2009 2007 IBM Corporation A holistic Challenge: Energy & Thermal Management Energy / thermal
More informationResults of Study Comparing Liquid Cooling Methods
School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September
More informationInnovative Data Center Efficiency Techniques. Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation
Innovative Data Center Efficiency Techniques Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation 1 Alternate titles.. Crisis or opportunity? Never build a new data center! Improve
More informationDesigning Ultra-Efficient Building Cooling Systems
Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,
More informationEnergy Efficiency for Exascale. High Performance Computing, Grids and Clouds International Workshop Cetraro Italy June 27, 2012 Natalie Bates
Energy Efficiency for Exascale High Performance Computing, Grids and Clouds International Workshop Cetraro Italy June 27, 2012 Natalie Bates The Exascale Power Challenge Where do we get a 1000x improvement
More informationWhy would you want to use outdoor air for data center cooling?
Dell Fresh Air 2.0: Frequently Asked Questions Achieve improved data center efficiency and powerful enterprise performance you have come to expect from Dell, by deploying Dell Fresh Air hardware. Competitively
More informationYour Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant
Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,
More informationEnergy Systems Integration
Energy Systems Integration Dr. Bryan Hannegan Associate Laboratory Director June 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated
More informationINSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE
INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE Dr Jon Summers Scientific Leader in Data Centers, RISE Adjunct Professor of Fluid Mechanics, Lulea University of
More informationMeasurement and Management Technologies (MMT)
IBM Systems Lab Services and Training Measurement and Management Technologies (MMT) Data Center Solutions for a Smarter Planet AGENDA IBM Energy Efficiency Program & Accomplishments IBM CO2 Reduction Commitment
More informationPerformance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report
Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationCompute Engineering Workshop March 9, 2015 San Jose
Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationPrecision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers
Precision Cooling for Business-Critical Continuity Liebert HPC-S Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S: Enhanced Efficiency Freecooling Chiller Higher energy costs, limited
More informationAquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.
Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling
More information7th Annual Statewide Energy Efficiency Forum Applying Building Technologies to Realize Savings June 16, 2016
. Lessons Learned - SMUD s East Campus Operations Center Jim Parks 7th Annual Statewide Energy Efficiency Forum Applying Building Technologies to Realize Savings June 16, 2016 Powering forward. Together.
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationRetro-Commissioning Report
10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism
More informationFLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities
UTILITIES ELEMENT NOTE: Unless otherwise noted, the goals, objectives and policies contained in this element shall guide development of the Main Campus and Southwest Campus in Tallahassee as well as the
More informationTopics. CIT 470: Advanced Network and System Administration. Google DC in The Dalles. Google DC in The Dalles. Data Centers
CIT 470: Advanced Network and System Administration Data Centers Topics Data Center: A facility for housing a large amount of computer or communications equipment. 1. Racks 2. Power 3. PUE 4. Cooling 5.
More information