Metal Debris Sensor Manual. Index. 1. Brief Introduction. 2. Main Technical Parameters

Size: px
Start display at page:

Download "Metal Debris Sensor Manual. Index. 1. Brief Introduction. 2. Main Technical Parameters"

Transcription

1 Metal Debris Sensor Manual YHY1-1 Series Index 1. Brief Introduction 2. Main Technical Parameters 3. Sensor Installation 3.1 Mechanical Installation 3.2 Electrical Connection 4. Wiring & Configuration 4.1 Wiring Definition 4.2 Wiring Notification 5. Notifications on Operation 6. Transportation & Storage 7. RS485 Communication 7.1 Transport Format 7.2 Frame Format 7.3 Communication Protocol Explanation 7.4 Communication Format Explanation 1. Brief Introduction YHY-1 Metal Debris Sensor is the advanced "Online Oil-Liquid Metal Detector", which is expert in detecting the Ferromagnetic Particle and the Non- Ferromagnetic Particle in the lubricating oil serving Mechanical Components (Bearing & Gears) YHY-1 Metal Debris Sensor is consisted of sensor and cable. The sensor is installed in the "Oil-Line". The sensor is connected with the upper device by cable. 1 / 5

2 2. Main Technical Parameters Particles Detected Min. Flow Rate Max. Flow Rate Max. Working Pressure Medium Working Temperature Storage Temperature Weight Power Supply Pipe Size Communication Protocol 100μm (Ferromagnetic Metal) 450μm (Non-Ferromagnetic Metal) 0.2 l/min 100 l/min 3.0 MPa Lubricating Oil -40~85 Deg. C (Available for Customization) -40~85 Deg. C (Available for Customization) 1.4 kg 18-30V, 200mA 12.7 mm RS Sensor Installation 3.1 Mechanical Installation Sensor Dimension could be referred as follows: - Process Connection Sensor-Pipe Inner Size is Ф 12.7mm, the inlet/outlet of the port is M18x1.5 female thread. Thread Depth is 17mm. Pipe Joint Connection is normally deployed, sealed by the "O" Ring or Adhesive Tape - Sensor Installation Dimension (mm) Sensor dimension is Length (148) x Width (125)x Height (102) The sensor could be fixed by the "Mounting-Hole (Ф 8.4mm)" in base-cover. Hole Center Distance is "103 x 92" Additional space should be reserved for sensor installation. 2 / 5

3 3.2 Electrical Connection The sensor could be connected with PC via Cable, as follows: 4. Wiring & Configuration 4.1 Wiring Definition Standard Sensor is available for "RS485 Sending Function (TX+, TX-)". "RS485 Receiving Function" could be customized. Standard /Default Sensor is equipped with "6-core Plug" (pluggable). 4.2 Wiring Notification Wire Sectional Area of the "Receiving-Signal Processing Unit" should meet 0.25mm 2 Communication Wire should apply "STP (Shielded Twisted Pair)". Communication Wires (RX+, RX-, TX+, TX-) should not be inversely connected. 4-wire communication wire and the power wire should be correctly wired. Otherwise, the communication convertor will be destroyed by high voltage. The Cable Length should be less than 500m, when the Baud Rate is bps 5. Notifications on Operation In case "Abnormal Situation" occurs, please cut-off the power supply. Please contact Tosilon if the fault cannot be solved. During the Transportation & Installation, the sensor should be handled with care. Before turn on power, make sure the wiring is correct. 6. Transportation & Storage During the transportation and un-packaged, the sensor should be avoid severe impact. Storage Environment should be clean, ambient temp. is -30~80 Deg. C; Humidity 95% (Non-condensate); Non-Corrosive 3 / 5

4 7. RS485 Communication When the particles are detected, the parameters will be sent to the Host via RS485 (Data Length: 51-Byte; Simplex / Duplex). Update Frequency is 1s 7.1 Transport Format Information Transmission adopt asynchronous mode in bytes. The contact information between the sensor and the host is based on 11-bit format. Parity Check Start Bit (1) Data Bits (8) Parity Bit (1) Stop Bit (1) 0 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 1 No Parity Start Bit (1) Data Bits (8) Stop Bit (1) Stop Bit (1) 0 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/ Frame Format When the Data-Frame reaches the host, it will be analyzed if there is no error during the data transmission. The Data-Frame consists Address Code, Data Field, Check Code. Address Code Data Field Check Code 8-Bits N 8-Bits 16-Bits Check: Data may have error caused by interference during the data transmission. It can inspect if the data has any error during the transmission to check the data and ensure the master PC does not response the wrong data. The checking uses CRC-16 redundant method. Below introduce the process. The concerned bytes in the frame are defined as a string of binary data (0, 1). The 16 th checksum is created as follows: the data steam times 216, divided by generator s polynomial (X16 + X15 + X2 + 1) that expressed with binary , the quotient is ignored, and the 16 bits remainder is the value of the CRC. The calculate process uses modulo two or XOR. And create checksum as follow steps: Omit the most Significant Bit of the generator, and reverse the bit, create a new polynomial or 1 hexadecimal data A Put all 1 or hexadecimal FFFF in 16 bit register. Carry out XOR calculate to the first data byte with the 16 bites register low order byte, and save the result to the 16 3 bits register. 4 Move register data one bite toward the right, if over flow bit is 1, turn to progress 5, otherwise turn to progress 6. 5 Carry out MOR calculate to 16 bits register with generator new polynomial and save the result to the register. 6 Repeat process 4, until the eight byte move. Carry out XOR calculate to next data byte with the 16 bites register low order byte, and save the result to the 16 bits 7 register. 8 Repeat the process 4-7, until all bite of the data has carried out XOR by the 16 bits register. 9 The data in the 16 bites register is CRC / 5

5 7.3 Communication Protocol Explanation Frame Head: Communication Data-Frame start with "0x55AA" Data Field: Data Length is not limited, Max. Length is 104 Bytes Error Check Filed: 16-Bit CRC check, occupy 2-byte. Frame check words, Big endian, Little endian. Frame End: Communication Data-Frame end with "0xEEEE" 7.4 Communication Format Explanation Description Meaning Data Word Length Type Byte Mark Frame Head Packet Start Bit 0x55AA 2 char 1~2 Fe Particular Data N Fe Particular Data Fe_100 Fe_200 Fe_300 Fe_400 Fe_500 Fe_600 Fe_700 0 ~ diameter less than Int32 3~5 0 ~ diameter 100~200 3 Int32 6~8 diameter 201~300 0 ~ Int32 9~11 diameter 301~400 0 ~ Int32 12~14 diameter 401~500 0 ~ Int32 15~17 diameter 501~600 0 ~ Int32 18~20 diameter larger than ~ Int32 21~23 Fe_800 Reserved 0 ~ Int32 24~26 Fe_1000 Reserved 0 ~ Int32 27~29 Total volume of above Fe_ALL interval Fe particular unit 0~ float 30~33 mm3/1000 Number of NFe diameter NFe_500 less than 500 Number of NFe diameter NFe_ ~700 NFe_100 Number of NFe diameter 0 larger than 700 Total volume of above NFe_ALL interval NFe particular 4 float unit mm3/1000 0x00 Indicating bit Reserved 0x01 0x02 1 char 47 0x041 CRC check bit Check data involving data packet 2 Int Ending- frame delimiter End bit of data packet 0xEEEE 2 char / 5

RS-FS-N01 Wind speed transmitter user's Guide (485type)

RS-FS-N01 Wind speed transmitter user's Guide (485type) RS-FS-N01 Wind speed transmitter user's Guide (485type) Issue: V1.0 1 2 Context 1. Introduction... 4 2. Installation instructions...5 3. Configure the software installation and use... 6 4. Communication

More information

RS-FX-N01 wind transmitter user's Guide (485type)

RS-FX-N01 wind transmitter user's Guide (485type) RS-FX-N01 wind transmitter user's Guide (485type) Issue:. V1. 0 1 2 Context 1. Introduction...4 2. Installation instructions... 5 3. Configure the software installation and use...7 4. Communication Protocol...

More information

SPM90 MODBUS PROTOCOL AND REGISTER LIST V1.0

SPM90 MODBUS PROTOCOL AND REGISTER LIST V1.0 SPM90 MODBUS PROTOCOL AND REGISTER LIST V1.0 目 录 1. Introduction... 1 1.1 Purpose of the Communication Protocol... 1 1.2 Version of Communication Protocol... 1 2. Detailed Description of the SPM90 Modbus

More information

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL v 1.0 Thanks for choosing the Intelligent temperature and humidity controller

More information

IFC 100 Supplementary instructions

IFC 100 Supplementary instructions IFC 100 Supplementary instructions Signal converter for electromagnetic flowmeters Description of Modbus interface Electronic Revision: ER 3.0.xx Modbus version: 1.0.xx KROHNE CONTENTS IFC 100 1 Important

More information

SPM33. MODBUS Protocol and register List V1.5

SPM33. MODBUS Protocol and register List V1.5 SPM33 MODBUS Protocol and register List V1.5 ZHUHAI PILOT TECHNOLOGY CO.,LTD 目 录 1. Introduction... 1 1.1 Purpose of the Communication Protocol... 1 1.2 Version of Communication Protocol... 1 2. Detailed

More information

TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL

TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL 1 2 CONTENTS 1. APPLICATION... 5 2. BASIC REQUIREMENTS, OPERATIONAL SAFETY... 5 3. INSTALLATION... 5 3.1. Assembly...5 3.2. Electrical Connections...7

More information

Product data sheet accessories control and regulation Accessories AIRWIN

Product data sheet accessories control and regulation Accessories AIRWIN Product data sheet accessories control and regulation BO-CT1 Continuous controller Item no. 6100101 Control of humidification performance BO-CT1 Option board 2 binary inputs Item no. 002212 Setpoint switching,

More information

CONFIGURATION: The Reader, LED Indicator, pin numbers for the 9-pin connector and the 25-pin adapter are shown in Figure 1-2.

CONFIGURATION: The Reader, LED Indicator, pin numbers for the 9-pin connector and the 25-pin adapter are shown in Figure 1-2. FEATURES: Major features of the Swipe Reader are as follows: Powered through the USB port no external power supply required Hardware Compatible with PC or any computer or terminal with an RS-232 interface

More information

Forcom Technology Co., Ltd. Intelligent RS-485/422 to RS-232 converter

Forcom Technology Co., Ltd. Intelligent RS-485/422 to RS-232 converter Forcom Technology Co., Ltd. Tel: +886-2-77296880 Fax: +8862-27055495 e-mail: info@forcomtech.com.tw URL: http://www.forcomtech.com.tw Intelligent RS-485/422 to RS-232 converter Model No.: R32TR1 AD-INT

More information

DCC-8 DIGITAL TO EIGHT CURRENT LOOP CONVERTER OPERATING MANUAL

DCC-8 DIGITAL TO EIGHT CURRENT LOOP CONVERTER OPERATING MANUAL DCC-8 DIGITAL TO EIGHT CURRENT LOOP CONVERTER OPERATING MANUAL 1 TABLE OF CONTENTS 1. MOUNTING INSTRUCTIONS 1.1 Standard DIN Rail mounting 1.2 Screw Mounting 2. FUSE REPLACEMENT 3. ASSEMBLING THE UNIT

More information

Interface Module XC Modbus Protocol Converter / User Manual

Interface Module XC Modbus Protocol Converter / User Manual Page 1 from 10 Bär Industrie-Elektronik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950 General The Interface Module XC Modbus is designed for use with the EMH LZQJ-XC and DMTZ-XC

More information

Carbon Monoxide Sensor - ModBus

Carbon Monoxide Sensor - ModBus Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read

More information

Temperature & Humidity LED Display Low Cost & Industrial Grade Cabinets

Temperature & Humidity LED Display Low Cost & Industrial Grade Cabinets Description This module has two displays Temperature and Humidity,suitable for environment monitor.the ambient temperature and relative humidity are measured using high performance DHT22 sensor which has

More information

IF96017 MODBUS COMMUNICATION PROTOCOL

IF96017 MODBUS COMMUNICATION PROTOCOL CONTENTS 1.0 ABSTRACT 04/07/14 Pagina 1 di 9 MULTIFUNCTION FIRMWARE 1.00 COMMUNICATION PROTOCOL IF96017 MODBUS COMMUNICATION PROTOCOL 2.0 DATA MESSAGE DESCRIPTION 2.1 Parameters description 2.2 Data format

More information

Two 16 Bit Registers, One for Integer Display One for Floating Point.

Two 16 Bit Registers, One for Integer Display One for Floating Point. Description Modbus Slave LED board allows PLCs and other automation equipment to display integer and floating point values over ModBus. The LED Board acts like a slave on the RS485 Bus. The baud rate and

More information

Installation and Operation Manual SPC1

Installation and Operation Manual SPC1 Installation and Operation Manual SPC1 BIA-SPC1 rev 5 Page 1 TABLE OF CONTENTS Page QUICK GUIDE DRAINAGE PUMP FLOATS CONNECTED TO PANEL 4-5 QUICK GUIDE DRAINAGE PUMP FLOAT CONNECTED TO PUMP 6-7 QUICK GUIDE

More information

MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS

MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS 18 channels for HART / Modbus RTU sensors 2 digital channels 16 math channels 4 relay outputs for alarm or control

More information

VersaMax IP Input Module

VersaMax IP Input Module Module is used to accept digital input signals. Module Specifications Housing dimensions (width x height x depth) Connection style Operating temperature Storage temperature Operating/storage humidity 60mm

More information

SPACEMOUSE SYNTHESIS OF JOYSTICK AND TRACKBALL. Technical DATA: Electrical DATA

SPACEMOUSE SYNTHESIS OF JOYSTICK AND TRACKBALL. Technical DATA: Electrical DATA SPACEMOUSE SYNTHESIS OF JOYSTICK AND TRACKBALL The high-precision SpaceMouse Module is ideally suited for D manipulation of industrial applications. Due to its compact dimensions the module can be easily

More information

Temperature controller Ducted systems

Temperature controller Ducted systems 2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master

More information

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

UC-2000 Installation Manual Unicorn Computers Technology Limited

UC-2000 Installation Manual Unicorn Computers Technology Limited UC2000 Installation Manual Copyright 2003. All rights reserved. Table of Contents Specifications 2 Enclosure for the UC2000 Controller 3 Unicorn Access Control System Configuration 4 UC2000 Controller

More information

HK-DID-MX-HDMI Product Name. Characteristic. Picture. Screen matrix switcher Describe

HK-DID-MX-HDMI Product Name. Characteristic. Picture. Screen matrix switcher Describe Product Name Screen matrix switcher Describe Matrix switcher is a high-performance intelligent matrix switch device designed for switching of audio and video signals. It switches all audio and video input

More information

Technical data. General specifications. Functional safety related parameters B 10d Electrical specifications Operating voltage U B

Technical data. General specifications. Functional safety related parameters B 10d Electrical specifications Operating voltage U B Model Number Cable pull rotary encoder with PROFI- NET interface Features Robust aluminum drum housing Drum travel when cable retracted using threaded spindle Bellows with steel tip Comprehensive accessories

More information

Ha-VIS econ 2000 Fast and Full Gigabit Ethernet Basic. Features

Ha-VIS econ 2000 Fast and Full Gigabit Ethernet Basic. Features 2000 Fast and Full Gigabit Ethernet Basic Commercial Temp.: / Industrial Temp.: Power Sourcing Equipment (PSE) with 4 Ports PoE+ (34.2 watts per port) General description Unmanaged Ethernet switches of

More information

TRANSDUCER T4311, T4411

TRANSDUCER T4311, T4411 TRANSDUCER T4311, T4411 Programmable temperature transducer for RTD Pt1000 sensor with serial output RS232 and RS485 Instruction manual Instruction Manual for use of transducer: T4311 (RS232), T4411 (RS485)

More information

JUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet

JUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet sales@jumo.co.uk info.us@jumo.net Page 1/9 JUMO PINOS L01 Calorimetric flow sensor Brief description The JUMO PINOS L01 flow sensor serves the measuring and monitoring of flow velocities of water and aqueous

More information

Page 1 MRK-D-0011, V2.0 Aeroqual SM50 User Guide

Page 1 MRK-D-0011, V2.0 Aeroqual SM50 User Guide Page 1 Table of Contents User Guide Revision History... 3 Description... 4 1. Operating Instructions... 4 1.1. Power... 4 1.2. Warm Up... 4 1.3. Standard Inputs and Outputs... 4 1.4. Using the Relay Output...

More information

DL-LN3X Series 2.4G Ad-hoc Network Wireless Communication Module

DL-LN3X Series 2.4G Ad-hoc Network Wireless Communication Module DL-LN3X Series 2.4G Ad-hoc Network Wireless Communication Module DL-LN3X series module is the wireless communication module independently developed. The module is designed specifically for the applications

More information

Communication Protocol Manual JOFRA ATC Copyright 2007 AMETEK Denmark A/S

Communication Protocol Manual JOFRA ATC Copyright 2007 AMETEK Denmark A/S Communication Protocol Manual JOFRA ATC Copyright 2007 AMETEK Denmark A/S Contents 1 Introduction...6 2 Protocol...7 2.1 Variables...7 2.2 Telegram structure...8 2.3 Packing and unpacking of telegrams...9

More information

T2314, T2414. Instruction Manual

T2314, T2414. Instruction Manual Atmospheric pressure transmitter T2314, T2414 with RS232 / RS485 serial output Instruction Manual Instruction Manual Device type Pressure Output Galvanic isolated output T2314 RS232 - T2414 RS485 Device

More information

Technical Documentation

Technical Documentation Technical Documentation FAFNIR Universal Device Protocol Edition: 02/2018 Version: 1.09 Article no.: 350052 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Tel.: +49 / 40 / 39 82 07 0 Fax: +49 / 40

More information

PowerLogic ION6200 Serial Communications Protocol and ION / Modbus Register Map

PowerLogic ION6200 Serial Communications Protocol and ION / Modbus Register Map 70022-05-XX PROTOCOL DOCUMENT 04/2007 PowerLogic ION6200 Serial Communications Protocol and ION / Modbus Register Map This document explains the Modbus protocol on the ION6200 meter. The ION6200 meter

More information

Industrial Media Converters

Industrial Media Converters Wireless AP Industrial s Introduction & Features Fiber s Ethernet s Serial s s Distance Extension With Higher Immunity Introduction The media converters have incorporated SUNIX advanced technologies such

More information

NEW product. Large digital pressure sensor 31series. Easily viewable LCD dual displays. High level visibility with 3-color display.

NEW product. Large digital pressure sensor 31series. Easily viewable LCD dual displays. High level visibility with 3-color display. NEW product No, NPPDF 6-01E-3 Large digital sensor 31series SEU-31 Easily viewable LCD dual displays. igh level visibility with 3-color display 2-Color indications depending on output. Main display : Pressure

More information

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections Data sheet 3379_en_B 1 Description PHOENIX CONTACT 2015-07-14 2 Features Media converters provide

More information

ABSOLUTE ROTARY ENCODER INTERBUS

ABSOLUTE ROTARY ENCODER INTERBUS Main Features - Compact and heavy duty industrial model - Interface: Remote-Bus - ENCOM-Profile: K (programmable) - Housing: 58 mm - Shaft: 6 or 10 mm, hollow- 15 mm - Resolution: max. 25 Bit =,554,42

More information

Solumetrix Toroidal Conductivity Sensors

Solumetrix Toroidal Conductivity Sensors Solumetrix Toroidal Conductivity Sensors Models: BKIN50, BKEX50, BEIN75, BEEX75 Conductivity: Dual range, 0-20.00 ms (Compensated), 0.1 us resolution 0-200.0 ms (Compensated), 1 us resolution Temperature

More information

K -B U S R. R S485/ K N X C onverter. U ser m anual-v er.1 BTPT-01/ KNX/EIB Intelligent Installation Systems

K -B U S R. R S485/ K N X C onverter. U ser m anual-v er.1 BTPT-01/ KNX/EIB Intelligent Installation Systems Guangzhou Video-star Electronics Industrial Co., Ltd K -B U S R R S/ K N X C onverter U ser m anual-v er.1 BTPT-01/.1 KNX/EIB Intelligent Installation Systems Contents 1. Summary ---------------------------------------------------------------------------------------------------------------------

More information

T2314, T2414. Instruction Manual

T2314, T2414. Instruction Manual Atmospheric pressure transmitter T2314, T2414 with RS232 / RS485 serial output Instruction Manual Instruction Manual Device type Pressure Output Galvanic isolated output T2314 RS232 - T2414 RS485 Device

More information

RS485/ KNX Bidirectional Converter K-BUS R. User manual-ver.1.3 BTPT-02/ KNX/EIB Intelligent Installation System

RS485/ KNX Bidirectional Converter K-BUS R. User manual-ver.1.3 BTPT-02/ KNX/EIB Intelligent Installation System Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R RS485/ KNX Bidirectional Converter User manual-ver.1.3 BTPT-02/485.1 KNX/EIB Intelligent Installation System Contents 1. Summary--------------------------------------------------------------------------------------------------------------------------3

More information

KNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS).

KNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS). PRODUCT NEWS Products News: New HC-A16KNX PAGE 1 / 8 Summary 1. This advanced product news introduces the new product HC-A16KNX. 2. The details are indicated in the description. Description 1. Applicable

More information

NEW product. Large digital pressure sensor 31series. Easily viewable LCD dual displays. High level visibility with 3-color display.

NEW product. Large digital pressure sensor 31series. Easily viewable LCD dual displays. High level visibility with 3-color display. NEW product No, NPPDF 6-01E Large digital sensor 31series SEU-31 Easily viewable LCD dual displays. igh level visibility with 3-color display 2-Color indications depending on output. Main display : Pressure

More information

F8008. Fiber Modem for up to 4E1 /8E1 +RS232+Ethernet. + optional V.35/QFXS/QFXO

F8008. Fiber Modem for up to 4E1 /8E1 +RS232+Ethernet. + optional V.35/QFXS/QFXO F8008 Fiber Modem for up to 4E1 /8E1 +RS232+Ethernet + optional V.35/QFXS/QFXO Description F8008 is a fiber optical multiplexer of new generation different from the traditional PDH, multiplexing 1 full

More information

Communication Protocol Manual JOFRA CTC, ITC, MTC, ETC and Compact Copyright 2008 AMETEK Denmark A/S

Communication Protocol Manual JOFRA CTC, ITC, MTC, ETC and Compact Copyright 2008 AMETEK Denmark A/S Communication Protocol Manual JOFRA CTC, ITC, MTC, ETC and Compact Copyright 2008 AMETEK Denmark A/S Contents 1 Introduction...5 2 Protocol...5 2.1 Variables...5 2.2 Telegram structure...6 2.3 Packing

More information

HuddleCamHD RS-232 Joystick Controller Model Number: HC-JOY

HuddleCamHD RS-232 Joystick Controller Model Number: HC-JOY HuddleCamHD RS-232 Joystick Controller Model Number: HC-JOY JOYSTICK KEYBOARD INSTALLATION & OPERATION MANUAL Rev 1.0 6/15 Easy pan, tilt & zoom controls for any RS-232 VISCA protocol camera! Controls

More information

ADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual

ADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual ADAM-510 RS-/RS-85 Repeater ADAM-510S Isolated RS-/85 Repeater ADAM-50 Isolated RS-/85 Converter Startup Manual Packing List Before you begin installing your module, please make sure that the following

More information

Appendix to the Operating Instructions RMx621 with ModBus Interface V Connection to ModBus-IDA System

Appendix to the Operating Instructions RMx621 with ModBus Interface V Connection to ModBus-IDA System Operating Instructions Appendix to the Operating Instructions RMx621 with ModBus Interface V3.03.00 Connection to ModBus-IDA System BA231R/09/en/08.09 71027031 MS Word Endress+Hauser 2 Contents 1 General...

More information

M15S OPERATION MANUAL

M15S OPERATION MANUAL M15S OPERATION MANUAL minikol ITALY www.minikol.com Index 1. Operation overview and general introduction... 1 2. Operation Modes... 2 2.1. Manual mode...2 2.2. Single mode...3 2.2.1. Setting target value...3

More information

4-port 10/100TX + 1 or 2-port 100FX Industrial Switch. User Manual

4-port 10/100TX + 1 or 2-port 100FX Industrial Switch. User Manual 4-port 10/100TX + 1 or 2-port 100FX Industrial Switch User Manual Rev.1.03 Sep-2010 FCC Warning This Equipment has been tested and found to comply with the limits for a Class A digital device, pursuant

More information

L P Linn-Pumpen GmbH. Electric-gear-pumps series FKM

L P Linn-Pumpen GmbH. Electric-gear-pumps series FKM Electric-gear-pumps series FKM Construction Self-priming electric-gear-pumps, bellhousing with foot-flange, pump-casing in cast iron. Gear-pumps series FKM with motor-power up to 1,5. Suction- and -ports

More information

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. MCD Modbus Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE Order Code: 175G9000 1. Important User Information Observe all necessary safety precautions when controlling

More information

T3311, T3313, T3411 T7310, T7410. Instruction Manual

T3311, T3313, T3411 T7310, T7410. Instruction Manual Programmable transmitter of temperature, relative humidity and other derived humidity values T3311, T3313, T3411 Programmable transmitter of atmospheric pressure, temperature, relative humidity and other

More information

PSI-MOS-PROFIB/FO 850 T

PSI-MOS-PROFIB/FO 850 T Extract from the online catalog PSI-MOS-PROFIB/FO 850 T Order No.: 2708261 FO converter with integrated optical diagnosis, alarm contact, for PROFIBUS up to 12 MBit/s, T-coupler with two FO interfaces

More information

List of Contents 1. INTRODUCTION DEFINITIONS AND ABBREVIATIONS REFERENCES TECHNICAL DATA GENERAL MODBUS RTU...

List of Contents 1. INTRODUCTION DEFINITIONS AND ABBREVIATIONS REFERENCES TECHNICAL DATA GENERAL MODBUS RTU... MAGX2 RTU User Guide -0- V1.5 23-01-2018 List of Contents 1. INTRODUCTION... 2 1.1 DEFINITIONS AND ABBREVIATIONS... 2 1.2 REFERENCES... 2 2. TECHNICAL DATA... 3 2.1 GENERAL MODBUS RTU... 4 3. COMMISSIONING...

More information

Installation and operation manual ReciFlow Gas

Installation and operation manual ReciFlow Gas Installation and operation manual ReciFlow Gas 1 1. Measurement principle... 3 2. Installation... 5 3. Operation... 7 4. Electrical interfaces... 11 5. Communication protocol... 14 6. Software update and

More information

Product Information. DCM Standard indoor stations TK IS A 514 A.. TK IS A 514 AD.. (Design)

Product Information. DCM Standard indoor stations TK IS A 514 A.. TK IS A 514 AD.. (Design) Product Information DCM Standard indoor stations TK IS A 514 A.. TK IS A 514 AD.. (Design) ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 58579 Schalksmühle Phone +49.2355.806-0 Fax +49.2355.806-189 E-Mail:

More information

Programmable transmitter of temperature, relative humidity and other derived humidity values with RS485 serial output Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with RS485 serial output Instruction Manual TRANSMITTER T3413, T3417 Programmable transmitter of temperature, relative humidity and other derived humidity values with RS485 serial output Instruction Manual Instruction Manual for use of temperature

More information

Tango. alpha nea. Thermometers and controllers with digital communication - Series AM

Tango. alpha nea. Thermometers and controllers with digital communication - Series AM Installed in Tango (standard) or alpha nea frames Modbus RTU communication over RS485 line Wide range of power supply Control knob for correction setting Can be installed in a multifunction frame Tango

More information

Electronics Single wire communication

Electronics Single wire communication Electronics Single wire communication Wilfrid Laurier University October 23, 2017 Single wire communication Single wire communication Parallel communication uses 4 or 8 bits plus control signals Single

More information

T1K MODBUS Base Controller Specifications

T1K MODBUS Base Controller Specifications Base Controller 1 2 In This Chapter.... Base Controller Setting the DIP Switches Setting the Rotary Address Switches Port Pin out and Wiring RJ12 Serial Port Pin out and Wiring 2 2 Base Controller General

More information

Communications guide. Line Distance Protection System * F1* GE Digital Energy. Title page

Communications guide. Line Distance Protection System * F1* GE Digital Energy. Title page Title page GE Digital Energy D90 Plus Line Distance Protection System Communications guide D90 Plus firmware revision:.9x GE publication code: 60-9070-F (GEK-3469) GE Digital Energy 650 Markland Street

More information

Fibre Modem - Single-mode

Fibre Modem - Single-mode Revision 1.0 November. 2006 1 - Single-mode P/N: : 995087 Model 3000 / Access 4000 Optically Isolated Interface INSTALLATION GUIDE OVERVIEW: The Inner Range Single-mode provides 2 separate, optically isolated

More information

USER MANUAL MBAR EX By JETI model s.r.o

USER MANUAL MBAR EX By JETI model s.r.o USER MANUAL MBAR EX By JETI model s.r.o. 14. 11. 2014 CONTENTS 1. INTRODUCTION...3 2. MAIN FEATURES...3 3. PLACEMENT OF MBAR EX SENSOR...3 4. CONNECTING THE MBAR EX SENSOR...4 5. SETTING VIA JETIBOX...5

More information

Absolute encoders - bus interfaces Solid shaft with clamping or synchro flange Optical multiturn encoders 13 bit ST / 12 bit MT, RS485

Absolute encoders - bus interfaces Solid shaft with clamping or synchro flange Optical multiturn encoders 13 bit ST / 12 bit MT, RS485 Optical multiturn encoders 1 bit ST / 12 bit MT, RS485 Features Encoder multiturn / RS485 Optical sensing method Resolution: singleturn 1 bit, multiturn 12 bit Clamping or synchro flange Fieldbus protocol

More information

Digi-Pas. Installation and Operation Guidelines for DWL5000XY, DWL5500XY and DWL5800XY Tilt Sensor Modules. Rev

Digi-Pas. Installation and Operation Guidelines for DWL5000XY, DWL5500XY and DWL5800XY Tilt Sensor Modules. Rev Installation and Operation Guidelines for DWL5000XY, DWL5500XY and DWL5800XY Tilt Sensor Modules Rev. 2.3 CONTENT 1. Introduction... 1 1.1. Overview... 1 1.2. Technical Specification...1 1.3. Dimension

More information

MU110-6U. Analog output module 6 channel. User guide

MU110-6U. Analog output module 6 channel. User guide MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)

More information

Installation and Operation Manual DPC1

Installation and Operation Manual DPC1 Installation and Operation Manual DPC1 BIA-DPC1 rev 5 Page 1 TABLE OF CONTENTS Page QUICK GUIDE DRAINAGE PUMPS FLOATS CONNECTED TO PANEL 4-5 QUICK GUIDE DRAINAGE PUMPS FLOATS CONNECTED TO PUMPS 6-7 QUICK

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction VEGASWING 71 A Contents Contents Safety information... 2 1 Product description 1.1 Function and configuration... 3 1.2 Functional principle... 3 1.3 Technical data...

More information

RFT(Robotous Force/Torque Sensor) Series

RFT(Robotous Force/Torque Sensor) Series RFT(Robotous Force/Torque Sensor) Series Installation and Operation Manual REVISION 1.1 1 Contents 1. Caution 4 1.1. Notices 4 1.2. Warning 4 2. Installation 5 2.1. Overview 5 2.2. Power Supply Specifications

More information

The information in this chapter will enable you to:

The information in this chapter will enable you to: C H A P T E R ➅ Hardware Reference The information in this chapter will enable you to: Environmental Specifications Use this chapter as a quick reference tool for most system specifications Use this chapter

More information

TOSVERT VF-S9 Communications Function Instruction Manual

TOSVERT VF-S9 Communications Function Instruction Manual TOSVERT VF-S9 Communications Function Instruction Manual Notice 1. Make sure that this instruction manual is delivered to the end user of the inverter. 2. Read this manual before first using the communications

More information

ADAM Fiber Optic to RS-232/422/485 Converter

ADAM Fiber Optic to RS-232/422/485 Converter ADAM-4542+ Fiber Optic to RS-232/422/485 Converter Overview Fiber optic transmission offers the benefits of wide bandwidth, immunity to EMI/RFI interface, and secure data transmission. The ADAM-4542+ can

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners 8-ch DI Switch Signal to RS485/232 Converters (WJ62 Series) Features: >> Eight channels switch signal acquisition,isolated RS-485/232 output >> Each input channel adopts optical isolation >> Can read level

More information

8 Channel USB to RS485/422 Converter USB-402 User s Manual Ver. 1.0 HuMANDATA LTD.

8 Channel USB to RS485/422 Converter USB-402 User s Manual Ver. 1.0 HuMANDATA LTD. 8 Channel USB to RS485/422 Converter USB-402 User s Manual Ver. 1.0 HuMANDATA LTD. Table of Contents Precautions... 1 Revision History... 2 Introduction... 2 1. Overview... 3 1.1. Power Supply... 4 1.2.

More information

DC BRUSHLESS MOTOR CONTROLLER BLSD-20/BLSD-50

DC BRUSHLESS MOTOR CONTROLLER BLSD-20/BLSD-50 1. Product designation DC BRUSHLESS MOTOR CONTROLLER BLSD-20/BLSD-50 with RS-485 interface Manual BLSD.20.50.001 Brushless controllers BLSD-20 and BLSD-50 are electronic devices to operate and control

More information

Data Sheet for Joysticks

Data Sheet for Joysticks Intuitive control of 3D-movements 6 degrees of freedom Optoelectronic sensors UART or USB interface The high-precision SpaceMouse Module is ideally suited for 3D manipulation of industrial applications.

More information

Supply voltage. Input current. Encoder supply. Memory SIMATIC S7-200, CPU 221 COMPACT UNIT, DC POWER SUPPLY 6 DI DC/4 DO DC, 4 KB CODE/2 KB DATA,

Supply voltage. Input current. Encoder supply. Memory SIMATIC S7-200, CPU 221 COMPACT UNIT, DC POWER SUPPLY 6 DI DC/4 DO DC, 4 KB CODE/2 KB DATA, Data sheet SIMATIC S7-200, CPU 221 COMPACT UNIT, DC POWER SUPPLY 6 DI DC/4 DO DC, 4 KB CODE/2 KB DATA, Supply voltage Rated value (DC) 24 V DC Load voltage L+ Rated value (DC) permissible range, lower

More information

Amphenol Advanced Sensors. SM-UART-04L Laser Dust Sensor. Application Note. Features. Applications

Amphenol Advanced Sensors. SM-UART-04L Laser Dust Sensor. Application Note. Features. Applications Application Note SM-UART-04L Laser Dust Sensor SM-UART-04L Laser Dust Sensor is designed to operate in a moderate environment and provides excellent performance. It s embedded optical design leverages

More information

Revision 1.2. July 24, COM Protocol Manual. for MDC and ADC N 11th St - San Jose CA

Revision 1.2. July 24, COM Protocol Manual. for MDC and ADC N 11th St - San Jose CA Revision 1.2 July 24, 2017 COM Protocol Manual for MDC and ADC www.mountztorque.com - 1080 N 11th St - San Jose CA 95112-408.292.2214 1 1 Overview and Communication Specifications 1.1 Overview If the PC

More information

Pressure sensors SPAW with display

Pressure sensors SPAW with display Key features At a glance 9 pressure ranges from 1 +1 bar up to 0 +100 bar 4-digit LED display, easy to read, robust Protection class IP67 320 rotatable display 1% accuracy, 0.15% repetition accuracy Temperature

More information

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND OleumTechTM TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND MUST BE FAMILIAR WITH LEVEL 1 TRAINING MATERIALS BEFORE MOVING FORWARD Doc ID# 80-6010-001b TABLE OF CONTENTS 1. WHAT IS NEW WRITE IMPORT

More information

Multi-axial miniature joystick based on Hall Effect technology

Multi-axial miniature joystick based on Hall Effect technology Joystick with grip Multi-axial miniature joystick based on Hall Effect technology J... + space-saving design + highly reliable and long lifetime due to contactless Hall Effect technology + integrated third

More information

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas technical datasheet technical datasheet MTL0 Displays Loop-powered indicators for hazardous areas Loop powered -0mA Field and panel mounting Environmental protection to IP7 Easy to configure Number of

More information

1 10/100TX FX w/ 1 PoE Injector Industrial Switch. User Manual

1 10/100TX FX w/ 1 PoE Injector Industrial Switch. User Manual 1 10/100TX + 1 100FX w/ 1 PoE Injector Industrial Switch User Manual CE Mark Warning This is a Class-A product. In a domestic environment this product may cause radio interference in which case the user

More information

FLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet

FLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet Fieldline Modular Device With Eight Digital Inputs Data Sheet 697000 02/2004 This data sheet is only valid in association with the FLS FLM SYS INST UM E user manual or the user manual for your bus system

More information

Technical Parameter... 4 Installation and Connection... 5

Technical Parameter... 4 Installation and Connection... 5 2 CONTENTS Technical Parameter... 4 Installation and Connection... 5 1. Indicator Diagram... 5 2. Loadcell Connection... 6 3. Serial Communication interface and Scoreboard... 7 Operation Instruction...

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

PSI-MOS-RS422/FO 850 T

PSI-MOS-RS422/FO 850 T Extract from the online catalog PSI-MOS-RS422/FO 850 T Order No.: 2708397 FO converter with integrated optical diagnosis, alarm contact, for RS-422/RS-485 4-wire/ INTERBUS to 2 Mbit/s, T-coupler with two

More information

8-port 10/100TX + 2-Port 10/100/1000T/100/1000 SFP Combo with 8 PoE Injectors Industrial Ethernet Switch User Manual

8-port 10/100TX + 2-Port 10/100/1000T/100/1000 SFP Combo with 8 PoE Injectors Industrial Ethernet Switch User Manual 8-port 10/100TX + 2-Port 10/100/1000T/100/1000 SFP Combo with 8 PoE Injectors Industrial Ethernet Switch User Manual FCC Warning This Equipment has been tested and found to comply with the limits for a

More information

Mini slides SLT/SLS/SLF

Mini slides SLT/SLS/SLF Mini slides SLT/SLS/SLF Precision, rigid guide Highly flexible Adjustable end position cushioning 03/10 Subject to change Products 04/05 1 / 1 Mini slides SLT/SLS/SLF Features SLS SLF SLT SLT/SLS/SLF SLT

More information

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2 Electronic pressure measurement Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2 WIKA data sheet PE 81.53 Applications Test bench construction Water jet

More information

Level sensor Stainless steel version Model RLT-1000, for industrial applications

Level sensor Stainless steel version Model RLT-1000, for industrial applications Level measurement Level sensor Stainless steel version Model RLT-1000, for industrial applications WIKA data sheet LM 50.02 Applications Level measurement of liquids in machine building Control and monitoring

More information

Compressed air quality meas. according to ISO 8573 Residual oil content - particles - moisture

Compressed air quality meas. according to ISO 8573 Residual oil content - particles - moisture Compressed air quality meas. according to ISO 8573 Residual oil content - particles - moisture Residual oil content measurement OIL-Check 400 For permanent and highly precise measurement of the vaporous

More information

Rev 1.3, Air-Farm User Manual. CO2 / Temperature / Humidity Transmitter

Rev 1.3, Air-Farm User Manual. CO2 / Temperature / Humidity Transmitter Rev 1.3, 2018-06 Air-Farm User Manual CO2 / Temperature / Humidity Transmitter Features CO2, Temperature and Humidity measurement Three high sensitivity sensors RS485(MODBUS) Communication Analog Voltage

More information

Error Detection Codes. Error Detection. Two Dimensional Parity. Internet Checksum Algorithm. Cyclic Redundancy Check.

Error Detection Codes. Error Detection. Two Dimensional Parity. Internet Checksum Algorithm. Cyclic Redundancy Check. Error Detection Two types Error Detection Codes (e.g. CRC, Parity, Checksums) Error Correction Codes (e.g. Hamming, Reed Solomon) Basic Idea Add redundant information to determine if errors have been introduced

More information

NIR Moisture Analyzer KB-30

NIR Moisture Analyzer KB-30 NIR Moisture Analyzer KB-30 Operation Manual Safety Precautions FPL950701 Improper use of the NIR moisture analyzer in violation of the following safety notes may result in death, injury or damage to property

More information

Golander Peristaltic Pump MODBUS Communication Instruction

Golander Peristaltic Pump MODBUS Communication Instruction Golander Peristaltic Pump MODBUS Communication Instruction 1 Introduction... 1 2 Modbus Protocol... 2 2.1 Modbus Protocol Model... 2 2.2 Byte Format... 2 2.3 MODBUS Message Timing... 2 2.4 Field... 3 2.5

More information

Ultrasonic Flow Meter Brochure

Ultrasonic Flow Meter Brochure Ultrasonic Meter Brochure Rev. 2011/06/10 www.sitelab.us.com Descriptions SL1168 Ultrasonic meter uses the latest digital technology and low-voltage broadband pulse transmission. The instrument is tolerant

More information