InterLink ECM20/ECL60 EC Series Installation and Operation Manual
|
|
- Arabella Owen
- 6 years ago
- Views:
Transcription
1 Commercial Refrigeration Parts InterLink ECM20/ECL60 EC Series Installation and Operation Manual
2 Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Contents User Interface 3 Keys and Led 3 Accessing and Using Menus 4 Basic Commands Menu 4 Basic Commands Edit Lock 4 Programming Menu 5 Copy Card 5 Password 6 Enabling Defrost Manually 6 Diagnostics 6 Alarms 7 Max and Min Temperature Mechanical Assembly 8 Elecctrical Wiring 8 Conditions of use 8 Liability and Residual Risk 8 Disclaimer 9 Technical Data 9 Parameters Table 10
3 ECM20/ECL60 Installation and Operation Manual Commercial Refrigeration Parts Electronic controllers for refrigerating units To activate the LOC function: - enter the Basic Commands menu by pressing - press the and keys within 2 seconds If the LOC function is active and you try to enter the Parameters menu, the word LOC appears. If this happens, the parameters are still displayed but cannot be edited. To disable the keypad lock, repeat the aforementioned procedure. * When switched on, the device performs a Lamp Test; the display and LEDs will flash for several seconds to check that they all function correctly. Keys and Leds UP Press and release Scrolls through menu items Increases values Press for at least 5 secs Activates the Manual Defrost function DOWN Press and release Scrolls through menu items Decreases values STAND-BY (ESC) Press and release Returns to the previous menu level Confirm parameter value Press for at least 5 secs Activates the STANDBY function (when outside the menus) SET (ENTER) Press and release Displays alarms (if active) Opens Basic Commands menu Press for at least 5 secs Opens the Programming menu Confirms commands Reduced Set/Economy LED Flashing: Reduced active Compressor LED Permanently on: Compressor Active Flashing: Delay, protection or blocked start-up. Defrost LED Permanently on: Defrost Active Flashing: Manual or D.I activation Fan LED Permanently on: Fans active Alarm LED Permanently on: Flashing: Aux LED Alarm on Alarm acknowledged Depending on model C LED Permanently on: C ting (dro = 0) F LED Permanently on: F ting (dro = 1) For friendly service and advice in New Zealand visit your local Heatcraft branch or call
4 Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Accessing and Using the Menus Resources are organised into menus which are accessed by briefly tapping the key ( Basic Commands menu) or by keeping the key pressed for more than 5 seconds ( Programming menu). Either do not press any keys for 15 seconds (time-out) or press the key once,to confirm the last value displayed and return to the previous screen. Basic Commands Menu Access the Basic Commands menu by pressing and releasing the key. If no alarms are active, the SEt label appears. By pressing the and keys you can scroll all folders in the Basic Commands menu: - AL: alarms folder (only visible if an alarm is active); - SEt: Set point ting folder. - Pb1: probe 1 folder; - Pb2: probe 2 folder **; - dit: interval between defrosts folder; - det: defrost timeout folder; - dst: defrost end temperature folder **; (** models ID971 and ECL60 only) Setting the Set point: To display the Set point value press the key when the SEt label is displayed.the Set point value appears on the display. To change the Set point value, press the and keys within 15 seconds. Press to confirm the modification. Change the value of the dit, det and dst defrost parameters in the same way. Displaying the probes: When the Pb1 or Pb2* label is displayed, press and the associated probe value will appear (* Pb2 is only present on models ID971 and ECL60). Basic Commands Edit Lock It is possible to disable the keypad on this device. The keypad can be locked by entering the Basic Commands menu using and pressing and within 2 seconds or by programming the LOC parameter (see dis label folder) With the keypad locked you can still access the Basic Commands menu by pressing to display the Set point and dit, det and dst parameters, but you cannot edit them. To disable the keypad lock, repeat the locking procedure. 4 For friendly service and advice in Australia visit your local Heatcraft branch or call
5 ECM20/ECL60 Installation and Operation Manual Commercial Refrigeration Parts Programming Menu To access the Programming menu hold down the key for more than 5 seconds. If specified, the PA1 access PASSWORD will be requested (see PASSWORD paragraph). Press the key to modify the values. The display will show the first folder in the menu (e.g.: the CP folder). By pressing the and keys you can scroll all folders in the Programming menu (Figure 1): 5 secs 5 secs Figure 1 Figure 2 Press the key beside the selected folder ( def in the example in figure 2) to view the first parameter contained. Select the desired parameter using the and keys. Press to see the current value of the selected parameter. Press and to change the value and then press to save it. NOTE: It is strongly recommended that you switch the device off and on again each time the parameter configuration is changed, in order to prevent malfunctioning of the configuration and/or ongoing timings Using the Copy Card The Copy Card is an accessory connected to the TTL serial USING port used for THE quick COPY programming CARD of the device parameters (upload and download a parameter The map Copy to Card one or is more an accessory devices of the connected same type). to Upload the TTL (label serial UL) and port copy used card formatting quick (label programming Fr) operations of should the device be performed parameters as explained (upload below: and download a parameter map to one or more devices of the same type). Upload (label UL) and copy card formatting (label Fr) operations should be performed as explained below: The FPr folder contains the commands necessary for use of the Copy Card. Press the key to open the Functions menu. Press the and The FPr keys folder to scroll contains through to the commands required function necessary (e.g. UL). for use of the Copy Card. Press the key to open the Functions Press menu. the Press key the to execute and the upload. keys If the to operation scroll is through successful, to the display required will show function y, if (e.g. not it UL). will show n. Press the key to execute the upload. If the operation is successful, the display will show y, if not it will show n. Upload (UL) This function uploads the programming parameters from the device. Upload (UL) This function uploads the programming parameters from the device. UPLOAD: device Copy Card UPLOAD: device Copy Card Format: (Fr) This command is used to format the copy card, an operation which is necessary when using the card for the first time. Format: (Fr) This command is used to format the copy card, an operation which is necessary when using the card Important: when the copy for card the has first been time. programmed, Important: the parameter when the Fr will copy delete card all has data been that have programmed, been entered. the This parameter operation cannot Fr be will cancelled. delete all data that have been entered. This operation cannot be cancelled. Download Download from re: from re: Connect Connect the copy the card copy when card the when device is the switched device off. is switched When the device off. When is the switched device on, the is download switched from on, the the copy download card will begin from automatically. the copy At card the end will DOWNLOAD of the begin lamp test, automatically. the display will At show the dly end of if the the operation lamp test, was successful the display and will dln if not. UPLOAD show dly if the operation was successful and dln if not. DOWNLOAD: DOWNLOAD: Copy Copy Card Card Device device NOTES: - after NOTES: the parameters have been downloaded, the device uses the downloaded parameter map tings. - see FPr - after folder the in parameters Parameter Table have and been Description downloaded, of Parameters. the device uses the downloaded parameter map tings. - see FPr folder in Parameter Table and Description of Parameters. 8 For friendly service and advice in New Zealand visit your local Heatcraft branch or call
6 Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Passwords The password PA1 allows access to the programming parameters. In the standard configuration the password is disabled (value = 0). To enable it (value 0) and assign the required value, enter the Programming menu, in the folder with the dis label. If the password is already enabled it will be required to access the Programming menu. To enter it: 5 secs If the password is incorrect, the display will show the PA1 label and you will have to repeat the entry procedure. Manual Defrost Cycle Activation To manually activate the defrost cycle, hold down the key for 5 seconds. If the defrost conditions are not satisfied - the parameter OdO 0 (Models ECM20, ID971 and ID974) - the evaporator probe Pb2 temperature is higher than the defrost end temperature (Models ID971 and ID974) the display will flash 3 times, to indicate that the operation will not be carried out. Diagnostics Alarms are always indicated by the buzzer (if present) and the alarm icon. To switch off the buzzer, press and release any key, the relative icon will continue to flash. NOTES: If alarm exclusion times have been (see AL folder in the parameters table) the alarm will not be signalled. A probe 1 (Pb1) malfunction alarm will appear directly on the display with the indication E1. Models ID971 and ID974: A probe 2 (Pb2) malfunction alarm will appear directly on the display with the indication E2. 6 For friendly service and advice in Australia visit your local Heatcraft branch or call
7 ECM20/ECL60 Installation and Operation Manual Commercial Refrigeration Parts Alarms Label Fault Cause Effects Remedy E1 Probe 1 faulty (cold room) measured values are outside operating range probe faulty/short-circuited/open Display label E1 Alarm icon permanently on Min/max alarm regulator disabled Compressor operation according to Ont parameter. check probe type NTC/PTC (H00) check the probe wiring replace probe E2 Probe 2 faulty (defrost) measured values are outside operating range probe faulty/short-circuited/open Display label E2 Alarm icon permanently on The Defrost cycle will end due to Time out (Parameter det ) check probe type NTC/PTC (H00) check the probe wiring replace probe AH1 Probe 1 HIGH temperature alarm value read by probe 1 > HAL after time of tao. (see MAX/MIN ALARMS table) Recording of label AH1 in folder AL No effect on regulation Wait until temperature value read by probe 1 returns below HAL AL1 Probe 1 LOW temperature alarm value read by probe 1 < LAL dopo tempo pari a tao. (see MAX/MIN ALARMS table) Recording of label AL1 in folder AL No effect on regulation Wait for the temperature value read by probe 1 to come back above LAL EA External alarm Digital input activated (H11 as external alarm) Recording of label EA in folder AL Alarm icon permanently on Regulation blocked if EAL = y to check and to remove the external cause which generate alarm on D.I. Opd Door open alarm Digital input activated (H11 as door switch) (for a longer time than tdo) Recording of label Opd in folder AL Alarm icon permanently on Regulator blocked close the door delay function defined by OAO 10 Max and Min Temperature Alarms Relative Temperature Value to point (Att=1) Absolute Temperature Value (Att=0) Off AFd AFd AFd AFd Setpoint - LAL Setpoint Setpoint + HAL LAL LAL + AFd LAL - AFd HAL Setpoint - LAL + AFd Setpoint + HAL - AFd Minimum temperature alarm Temp. Set+LAL * Temp. LAL (LAL with sign) Maximum temperature alarm Temp. Set+HAL ** Temp. HAL (HAL with sign) Returning from minimum temperature alarm Returning from maximum temperature alarm Temp. Setpoint + LAL + AFd Setpoint - LAL +AFd Temp. Setpoint + HAL - AFd Temp. Temp. LAL + AFd HAL - AFd * if LAL is negative, Set + LAL < Set ** if HAL is negative, Set + HAL > Set 11 For friendly service and advice in New Zealand visit your local Heatcraft branch or call
8 Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Mechanical Assembly The instrument is designed for panel mounting. Make a hole of 29x71 mm, insert the instrument and fix it using the brackets provided. Do not mount the instrument in humid and/or dirty places; it is suitable for use in ordinary polluted places. Ventilate the place in proximity to the instrument colling slits. 70mm 29mm 71mm 67mm 74mm 32mm Electrical Wiring Attention! Never work on electrical connections when the machine is switched on. The instrument is equipped with screw terminal boards for connection of electrical cables with a diameter of 2.5 mm2 (one conductor only per terminal for power connections). For the capacity of the terminals, see the label on the instrument. In the model ID 974 with Switching power supply only one voltage free relay output is present, on all other models on the contrary all relay outputs are voltage free. Do not exceed the maximum current allowed; in case of higher loads, use an appropriate contactor. Make sure the power supply voltage complies with the one required by the instrument. In 12V versions the power supply must be provided by a security transformer with the protection of a delayed 250 ma fuse. Probes have no connection polarity and can be extended using a regular bipolar cable (note that the extension of the probes affects the EMC electromagnetic compatibility of the instrument: pay extreme attention to wiring). Probe cables, power supply cables and the TTL serial cables should be distant from power cables. Conditions of Use Permitted Use For safety reasons the instrument must be installed and used according to the instruction provided and in particular, under normal conditions, parts bearing dangerous voltage levels must not be accessible. The device must be adequately protected from water and dust as per the application and must also only be accessible via the use of tools (with the exception of the frontlet). The device is ideally suited for use on household appliances and/or similar refrigeration equipment and has been tested with regard to the aspects concerning European reference standards on safety. It is classified as follows: according to its manufacture: as an automatic electronic control device to be incorporated by independent mounting; according to its automatic operating features: as a 1 B-type operated control type; as a Class A device in relation to the category and structure of the software. Unpermitted use Any other use other than that permitted is de facto prohibited. It should be noted that the relay contacts provided are of a practical type and therefore subject to fault. Any protection devices required by product standards or dictated by common sense due to obvious safety reasons should be applied externally. Liability and Residual Risks ELIWELL CONTROLS SRL shall not be liable for any damages deriving from: - installation/use other than that prescribed and, in particular, that which does not comply with safety standards anticipated by regulations and/or those given herein; - use on boards which do not guarantee adequate protection against electric shock, water or dust under the conditions of assembly applied; - use on boards which allow access to dangerous parts without the use of tools; - tampering with and/or alteration of the products; - installation/use on boards that do not comply with the standards and regulations in force. 8 For friendly service and advice in Australia visit your local Heatcraft branch or call
9 ECM20/ECL60 Installation and Operation Manual Commercial Refrigeration Parts Disclaimer This manual and its contents remain the sole property of Interlink CONTROLS SRL, and shall not be reproduced or distributed without authorization. Although great care has been exercised in the preparation of this document, Interlink CONTROLS SRL, its employees or its vendors, cannot accept any liability whatsoever connected with its use. Interlink CONTROLS SRL reserves the right to make any changes or improvements without prior notice. Technical Data Mechanical Caracteristics Front protection: IP65. Housing: PC+ABS UL94 V-0 resin plastic casing, polycarbonate glass, thermoplastic resin keys. Dimensions: front 74x32 mm, depth 59 mm. (excluding terminals). Mounting: panel mounting with 71x29 mm (+0.2/-0.1 mm) drilling template. Terminals: screw terminal for cable with a diameter of 2,5mm 2 Connectors: TTL for connection to Copy Card Temperature: Operating: C - Storage: C Humidity: Operating / Storage: % RH (not condensing). Electrical Caracteristics Power Supply: 230Va (+10% / -15%) 50/60 Hz Consumption: 3W max Display Range: NTC: 50.0 C C; PTC: C C (on display with 3 digit + sign) Accuracy: Better than 0.5% of full-scale +1 digit. Resolution: 0,1 C. Buzzer: YES (it depends from the model) Analogue Input: ECM20: 1 NTC (Default) / PTC input (programmable by parameter H00). ID971 e ECL60: 2 NTC (Default) / PTC input (programmable by parameter H00). Digital Input: 1 voltage-free digital input Digital Output: ECM20: 1 Compressor relay: IEC (2)A max 250Va UL Hp (8FLA - 48LRA) max 240Va ID971: 1 Defrost relay: N.O. 8(3)A - N.C. 6(3)A max 250Va 1 Compressor relay: IEC (2)A max 250Va UL Hp (8FLA - 48LRA) max 240Va ECL60: 1 Defrost relay: N.O. 8(3)A - N.C. 6(3)A max 250Va 1 Compressor relay: IEC (3)A max 250Va UL /2 Hp (5FLA - 29LRA) max 240Va 1 Fan relay: 5(2)A max 250Va Regulations Electromagnetic compatibility: This device complies with Directive 2004/108/EC and the harmonised standard EN Security: This device complies with Directive 2006/95/EC and the harmonised standard EN Food safety: This device complies with standard EN as follows: - suitable for storage - climate range A - measurement class 1 in the range from -35 C to 25 C (*) (* exclusively using Eliwell ntc probes) Voluntary marks/certifications: ENEC/UL (check on the device label). Classification: operating (not safety) device for integration. NOTE 1: switch the device off and on after modifying the ntc/ptc probe (par. H00). NOTE 2: check the power supply specified on the instrument label; for relay and power supply capacities,contact the Sales Office. NOTE:The technical data included in this document, related to measurement (range, accuracy, resolution, etc.) refer to the instrument itself, and not to its equipment such as, for example, sensors.this means, for example, that sensor(s) error(s) shall be added to the instrument s one. For friendly service and advice in New Zealand visit your local Heatcraft branch or call
10 Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Table of Parameters PAR. SEt dif HSE LSE OSP dod Ont don dof dbi OdO (!) dty TABLE OF PARAMETERS DESCRIPTION Temperature SEtpoint. COMPRESSOR REGULATOR (folder with CP label) differential. Relay compressor tripping differential. The compressor stops on reaching the Setpoint value (as indicated by the adjustment probe), and restarts at temperature value equal to the Setpoint plus the value of the differential. Note: the value 0 cannot be assumed. Higher SEt. Maximum possible point value. Lower SEt. Minimum possible point value. Off Set Point. Temperature Value to be added to the Set-Point if reduced is enabled (Economy function). digital (input) Open door. Digital input that allow you to switch off loads. Valid if H11 = ±4 (door microswitch). n = does not switch off loads; y = switch off loads COMPRESSOR PROTECTIVE DEVICE (folder with CP label) On time (compressor). Compressor activation time in the event of faulty probe. If Ont=0 the compressor is always off, while Ont>0 the compressor is always on. delay (at) On compressor. Delay time in activating the compressor relay after switch-on of instrument. delay (after power) OFF. Delay after switch off; the indicated time must elapse between switch-off of the compressor relay and the successive switch-on. delay between power-on. Delay between switch-ons; the indicated time must elapse between two successive switch-ons of the compressor. delay Output (from power) On. Delay time in activating the outputs after switch-on of the instrument or after a power failure. DEFROSTING REGULATOR (folder with def label) defrost type. Type of defrosting. 0 = electric defrost - compressor off (OFF) during defrosting; 1 = reverse cycle defrost (hot gas); compressor on (ON) during defrosting; 2 = Free defrost; defrosting independently of compressor. 16 dit dct doh det dst dpo FSt FAd Fdt dt dfd FCO Fod defrost interval time. Interval between the start of two successive defrosting operations. defrost Counting type. Selection of count mode for the defrosting interval. 0 = compressor operating hours (DIGIFROST method); Defrosting active only if compressor is on. 1 = Real Time - equipment operating hours; defrost counting is always active when the machine is on and start everytime the instrument switch on, 2 = compressor stop. Each time the compressor stops a defrosting cycle is performed according to parameter dty defrost Off Hour. Start-of-defrosting delay time from the call. defrost Endurance time. Defrosting time-out; determines duration of defrosting. defrost Stop temperature. Defrost stop temperature (defined by the evaporator probe). defrost (at) Power On. Determines if at the start-up the instrument must enter defrosting (if the temperature measured by the evaporator allows this operation). y = yes; n = no. FANS REGULATOR (folder with FAn label) Fan Stop temperature. Fan lock temperature; if the value, read by the evaporator probe, is higher than the value, fans stop. Fan differential. Fan starting differential (see par. FSt ). Fan delay time. Delay time in activating fans after a defrost operation. drainage time. Dripping time. defrost Fan disable. Allows to select the evaporator probes exclusion during defrost. y = yes (fan disable); n = no. Fan Compressor OFF. Allows to select compressor fans lock OFF (switched off). y = fans activated (with thermostat; based on the value read by the defrost probe, see parameter FSt ); n = fans off; dc = not used. Fan open door. Fans active when the door is open. Allows you to select the option of stopping the fans when the door is open, and re-starting the fans when door is closed (if they were active). n = fans stop; y = fans unchanged For friendly service and advice in Australia visit your local Heatcraft branch or call
11 ECM20/ECL60 Installation and Operation Manual Commercial Refrigeration Parts ALARMS (folder with AL label) Att Allow you to select if the parameters HAL and LAL will have absolute (Att=0) or relative (Att=1) value. AFd Alarm Fan differential. Alarm differential. HAL Higher ALarm. Maximum temperature alarm. Temperature value (in relative value) which if exceeded in an upward direction triggers the activation of the alarm signal. LAL Lower ALarm. Minimum temperature alarm. Temperature value (in relative value), which if exceeded in a downward direction, triggers the activation of the alarm signal. PAO Power-on Alarm Override. Alarm exclusion time after instrument switch on, after a power failure. dao defrost Alarm Override. Temperature alarm exclusion time after defrost. OAO Alarm signaling delay after digital input disabling (door close). Alarm is only for high-low temperature alarms. tdo time out door Open. Alarm activation delay time open door. tao temperature Alarm Override. Temperature alarm signal delay time. EAL External Alarm Clock. External alarm to lock loads (n = don t lock loads; y = lock loads). DISPLAY (folder with dis label) LOC LOCk. Basic Commands edit lock. However, you can enter parameter programming modify them along with the status of this parameter in order to allow unlocking. y = yes; n = no PA1 PAssword 1. When enabled (value other than 0) it constitutes the access key for level 1 parameters. ndt number display type. View with decimal point. y = yes; n = no CA1 CAlibration 1. Positive or negative temperature value added to the value read by probe 1. CA2 CAlibration 2. Positive or negative temperature value added to the value read by probe 2. ddl defrost display Lock. Viewing mode during defrosting. 0 = shows the temperature read by the room probe; 1 = locks the reading on the temperature value read by room probe when defrosting starts, and until the next time the Setpoint value is reached; 2 = displays the label def during defrosting, and until the next time the Setpoint value is reached. dro display read-out. Select C or F for displaying the temperature read by the thermostat probe. (0 = C, 1 = F). PLEASE NOTE: the switch between C and F DO NOT modify point, differential, etc. (for example =10 C become 10 F). 18 H00 (!) H08 H11 H25 H42 rel tab UL Fr CONFIGURATION (folder with "CnF" label) Probe type selection, PTC or NTC (Default). 0 = PTC; 1 = NTC. Stand-by operating mode. 0 = display switch off; 1 = display switch off, loads and alarms stopped; 2 = display with OFF label, loads and alarms stopped. Configurability digital inputs/polarity. 0 = disabled; ±1 = defrosting; ±2 = reduced ; ±3 = not used; ±4 = door microswitch; ±5 = external alarm; ±6 = Stand-by (ON-OFF). ATTENTION! Positive or negative values change the polarity. Enable/disable the buzzer. 0 = disabled; 4 = enabled; = not used. Evaporator probe present. n = not present; y = present. release firmware. Device version: read only parameter. table of parameters. Reserved: read only parameter. COPY CARD (folder with Fpr label) Up Load. Programming parameter transfer from instrument to Copy Card. Format. Erasing all data in the copy card. PLEASE NOTE: using Fr parameter (copy card formatting) the data within the copy card will be lost permenently. The operation cannot be cancelled. (!) WArnIng! If one or more of these parameters highlighted with (!) are modified, the controller must be switched off and switched on again to ensure correct operation. In any case, it is strongly recommended that you switch the controller off and switch it on again any time parameters have been changed to prevent malfunctioning on configuration and/or timing underway. For friendly service and advice in New Zealand visit your local Heatcraft branch or call
12 Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Parameters-Default Setting AL FAn def CP Parameters - Default Setting PAR. ECM20 ID961 ID971 ECL60 ID974 U.M. RANGE DEFAULT RANGE DEFAULT RANGE DEFAULT SEt -50, ,0 0,0-50, ,0 0,0-50, ,0 0,0 C/ F dif +0, ,0 2,0 +0, ,0 2,0 +0, ,0 2,0 C/ F HSE LSE ,0 LSE ,0 LSE ,0 C/ F LSE -58,0... HSE -50,0-58,0... HSE -50,0-58,0... HSE -50,0 C/ F OSP -30, ,0 0,0-30, ,0 0,0-30, ,0 0,0 C/ F dod n/y n n/y n n/y n flag Ont min don sec dof min dbi min OdO min dty /1/2 0 0/1/2 0 flag dit hours dct 0/1/2 1 0/1/2 1 0/1/2 1 flag doh min det min dst , ,0-50, ,0 C/ F dpo n/y n n/y n n/y n flag FSt , ,0 C/ F FAd , ,0 2,0 C/ F Fdt min dt min dfd n/y y flag FCO n/y/dc n flag Fod n/y n flag Att 0/1 1 0/1 1 0/1 1 flag AFd +1, ,0 2,0 +1, ,0 2,0 +1, ,0 2,0 C/ F HAL LAL ,0 +50,0 LAL ,0 +50,0 LAL ,0 +50,0 C/ F LAL -50,0... HAL -50,0-50,0... HAL -50,0-50,0... HAL -50,0 C/ F FPr CnF dis AL PAR. ECM20 ID961 ID971 ECL60 ID974 U.M. RANGE DEFAULT RANGE DEFAULT RANGE DEFAULT PAO hours dao min OAO hours tdo min tao min EAL n/y n n/y n n/y n flag LOC n/y n n/y n n/y n flag PA num ndt n/y y n/y y n/y y flag CA1-12, ,0 0,0-12, ,0 0,0-12, ,0 0,0 C/ F CA , ,0 0,0-12, ,0 0,0 C/ F ddl 0/1/2 1 0/1/2 1 0/1/2 1 num dro 0/1 0 0/1 0 0/1 0 flag H00 0/1 1 0/1 1 0/1 1 flag H08 0/1/2 2 0/1/2 2 0/1/2 2 num H num H num H n/y y n/y y flag rel / / / / / / / tab / / / / / / / UL / / / / / / / Fr / / / / / / / 12 For friendly service and advice in Australia visit your local Heatcraft branch or call
13 ECM20/ECL60 Installation and Operation Manual Commercial Refrigeration Parts Connections CONNECTIONS/ CONNESSIONI/ CONEXIONES/ ANSCHLUSS-PLAN/ CONNEXIONS/ ПОДКЛЮЧЕНИЕ N L N L N N L L ID961 PLUS ID961 PLUS (A) (A) ID961 ECM20 ID961 Supply 230Va Supply 3W max 230Va W 6 max Supply Supply 230Va 3W max 230Va W 6 max D.I. (thermostat) (thermostat) Pb1 Pb1 D.I. D.I. (thermostat) (thermostat) Pb1 (evaporator) D.I. TTL TTL A A CONNECTIONS/ CONNESSIONI/ CONEXIONES/ ANSCHLUSS-PLAN/ TERMINALS/ MORSETTI/ BORNES/ CONNEXIONS/ KLEMMEN/ BORNES/ ПОДКЛЮЧЕНИЕ РАЗЪЕМЫ defrost relay / relè sbrinamento relé descarche / relais abtauung ID971 ID961 ID974 relais dégivrage / реле ID971 размораживания ID974 compressor relay / relè compressore ID971 PLUS PLUS TTL relé compresor / Ausgangsrelais Kompressor TTL relais compresseur / реле компрессора (evaporator) Pb2 A Pb1 A Pb2 N-L A N L ID971 PLUS 1 ID971 Supply 230Va 3W max fan relay / relè ventole relé ventiladores / Ausgangsrelais Gebläse relais ventilateurs / реле крыльчаток Power Supply / Alimentazione / Alimentación Speisung / Alimentation / Питание TTL input / Ingresso TTL / Entrada TTL TTL-Eingang / Entrée TTL / Вход TTL D.I. (thermostat) Pb1 (evaporator) A Pb2 TTL ID974 PLUS ECL60 ID974 1 Supply 230Va 3W max A TTL N L (evaporator) (thermostat) D.I. Pb2 Pb1 For friendly service and advice in New Zealand visit your local Heatcraft branch or call
14 Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Technical Data TECHNICAL DATA (DATITECNICI) Mechanical Caracteristics (Caratteristiche Meccaniche) Front protection (Protezione frontale): IP65. Housing (Contenitore): PC+ABS UL94 V-0 resin plastic casing, polycarbonate glass, thermoplastic resin keys Dimensions (Dimensioni): front 74x32 mm, depth 59 mm. (excluding terminals) Mounting (Montaggio): panel mounting with 71x29 mm (+0.2/-0.1 mm) drilling template. Terminals (Morti): screw terminal for cable with a diameter of 2,5mm 2 Serial (Seriale): TTL for connection to Copy Card Temperature (Temperatura): Operating (Utilizzo): C - Storage (Immagazzinamento): C Humidity (Umidità): Operating (Utilizzo) / Storage (Immagazzinamento): % RH (not condensing) Electrical Caracteristics (Caratteristiche Elettriche) Power Supply (Alimentazione): 230Va (+10% / -15%) 50/60 Hz - Consumption (Consumo): 3W max Display range (Range di visualizzazione): NTC: 50.0 C C; PTC: C C (on display with 3 digits + sign) Accuracy (Accuratezza): Better than 0.5% of full-scale +1 digit. Resolution (Risoluzione): 0,1 C Buzzer (Buzzer): YES (it depends from the model) Analogue Input (Ingressi Analogici): ECM20: ID961: 1 NTC (Default) / PTC input (programmable by parameter H00*) ID971 e ID974: ECL60: 2 NTC (Default) / PTC input (programmable by parameter H00*) Digital Input (Ingressi Digitali): 1 voltage-free digital input Digital Output (Uscite Digitali) ECM20: ID961: 1 Compressor relay: IEC (2)A max 250Va UL Hp (8FLA - 48LRA) max 240Va ID971: 1 Defrost relay: N.O. 8(3)A - N.C. 6(3)A max 250Va 1 Compressor relay: IEC (2)A max 250Va UL Hp (8FLA - 48LRA) max 240Va ID974: 1 Defrost relay: N.O. 8(3)A - N.C. 6(3)A max 250Va 1 Compressor relay: IEC (3)A max 250Va UL /2 Hp (5FLA - 29LRA) max 240Va 1 Fan relay: 5(2)A max 250Va 14 For friendly service and advice in Australia visit your local Heatcraft branch or call
15 ECM20/ECL60 Installation and Operation Manual Commercial Refrigeration Parts Notes For friendly service and advice in New Zealand visit your local Heatcraft branch or call
16 InterLink is a registered trademark of Heatcraft Australia Pty Ltd, 286 Horsley Road, Milperra NSW ABN NOTE: The InterLink ECM20/ECL60 device is not sold for personal, domestic or household use and the standard Heatcraft Warranty Policy and Terms and Conditions of Sale apply to this device. InterLink ECM20/ECL60 is totally reliant on the GSM network to provide alarm notification and data reporting, these services may not be free from fault or interruption. Heatcraft accepts no liability for the use or misuse of its products under any circumstances, including provision of GSM network, GPS services, or device failure, for whatever reason. Heatcraft shall not be liable for any damages suffered or incurred by the user (including, but not limited to, general, special, consequential or incidental damages) arising from or in connection with the use or performance of the InterLink ECM20/ECL60 solution. To the maximum extent permitted by applicable law no warranties or guarantees are given as to the currency, availability, accuracy, security or quality of any information received or accessed using the Services and you are solely responsible for any reliance on or use of the information received or that is accessed when using this product/service. Prior to installing or using this product or any software, hardware or third party products and services, it is your responsibility to ensure that your airtime service provider has agreed to support all of their features. Heatcraft also reserves the right to change the specifications, functionality and instructions of its products and accessories, at any time without notification heatcraft.com.au heatcraft.co.nz
ENGLISH EW961/971/974
EN ENGLISH EW961/971/974 Electronic controllers for refrigeration units EN UP Press and release Scrolls through menu items Increases values Press for at least 5 secs Activates the Manual Defrost function
More informationID 974 DCC electronic controllers for forced air refrigeration units
cod. 9IS42075 rel. 4/06 -GB- *If the conditions for defrosting are not present, or if parameter OdO0, the display will blink three times, to indicate that the operation will not be performed. ID 974
More informationEZ-HT / EZ-MT / EZ-LT. Electronic controllers for refrigeration units
EZ-HT / EZ-MT / EZ-LT EN Electronic controllers for refrigeration units EZ-HT / EZ-MT / EZ-LT USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Activates the
More informationEWPLUS 902/961 EWPLUS 971/974
ENGLISH Electronic controllers for refrigeration units EN EWPLUS 902/961 EWPLUS 971/974 UP Press and release Scrolls through menu items Increases values Press for at least 5 secs Activates the Manual Defrost
More informationEWPlus 961 EO Dispenser
EWPlus 961 EO Dispenser Electronic controllers for refrigeration units NOTE: When the controller is powered on it performs a lamp test, during which time the display and LEDs will flash for several seconds
More informationIDPLUS 902/961/971/974. Electronic controllers for refrigeration units
IDPLUS 902/961/971/974 GB Electronic controllers for refrigeration units CONTENTS ID PLUS 902/961 USER INTERFACE (KEYS AND LEDS)... 4 ID PLUS 971/974 USER INTERFACE (KEYS AND LEDS)... 6 ID PLUS 902/961
More informationEMPlus 600. Electronic digital indicator
EMPlus 600 EN Electronic digital indicator USER INTERFACE UP Press and release Scroll menu items Increases values DOWN Press and release Scroll menu items Decrease values KEYS EMPlus 600 STAND-BY (ESC)
More informationIDPLUS 978. Electronic controllers for refrigeration units
IDPLUS 978 EN Electronic controllers for refrigeration units USER INTERFACE IDPLUS 978 UP Press and release Scroll menu items Increases values Press for at least 5 sec Activates the Manual Defrost function
More informationEWRC 300/500 NT QUICK START. Controllers for static and ventilated cold rooms. English
EWRC 300/500 NT Controllers for static and ventilated cold rooms QUICK START INTRODUCTION The Coldface EWRC 300/500 NT series controls the temperature of a static or ventilated cold room. The instrument
More informationICPlus 902. Electronic controller with 1 intervention point
ICPlus 902 EN Electronic controller with 1 intervention point USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Function can be configured by the user (H31)
More informationID985/V. Electronic controllers for ventilated refrigeration units with electronic expansion valve management
ID985/V GB Electronic controllers for ventilated refrigeration units with electronic expansion valve management SUMMARY MECHANICAL ASSEMBLY...3-GB ELECTRICAL CONNECTIONS...3-GB ELECTRICAL DIAGRAM...4-GB
More informationEWPC 901/A rel. 6/96 ing
EWPC 91A rel. 696 ing temperature controller with alarm output WHAT IT IS The EWPC 91A is a temperature controller specifically designed for refrigeration applications. The instrument includes a 1 Vdc
More informationEWPlus 961/971/974 EO LVD
EWPlus 961/971/974 EO LVD Versatile high-performance controllers thanks to the new Energy Saving algorithms for plug-in refrigerated cabinets. USER INTERFACE EWPLUS EO LVD NOTE When switched on, the device
More informationEWCH 485 Electronic Pulse Counter
Electronic Pulse Counter Technical Data Sheet INSTRUMENT DESCRIPTION GENERAL DESCRIPTION is a programmable microprocessor based counter with 1or 2 outputs. The instrument offers the possibility to program:
More informationID 985/S/E/CK - ID985/E LX electronic controllers for ventilated refrigeration units
cod. 9IS23080 rel. 4/08 -GB- ID 985/S/E/CK - ID985/E LX electronic controllers for ventilated refrigeration units with RS485 on board (ID985/S/E/CK) and remote display BUTTONS AND DISPLAY UP button Scrolls
More informationID 985/S/E/CK - ID 985/E LX
ID 985/S/E/CK - ID 985/E LX Electronic controllers for ventilated refrigeration units with RS485 on board (ID985/S/E/CK) and remote display BUTTONS Scrolls through the menu items Increases values Activates
More informationID974E electronic controllers for ventilated refrigeration units
cod. 9IS448- rel. 7-8 -GB- ID974E electronic controllers for ventilated refrigeration units USER INTERFCE The user has a displa and four kes for controlling status and programg of the instrument. KEYS
More informationICPlus 915. Electronic controller with 2 intervention points
ICPlus 915 EN Electronic controller with 2 intervention points USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Function can be configured by the user (H31)
More informationEWTS LX programmable electronic timers
cod. 9IS43096 rel. 7/06 -GB- EWTS 950-990 LX programmable electronic timers LEDs cnt slow flashing for parameter programming fast flashing when counting in progress permanently on when counting stopped
More information4-step Chiller and Heat Pump Controller
4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW
More informationIC 915 (LX) Alarm ON for active alarm; blinking when a silenced alarm is still present
IC 95 (LX) GB cod. 9IS37 rel. 4 electronic controller with points and differential point adjustment USER INTERFACE The user has a display and four buttons for controlling instrument status and programg.
More informationMECHANICAL INSTALLATION
Controllers for freezer cabinet and cold rooms with built-in compressor. Panel-mounted Energy Saving algorithms and optimised defrost control 8 preloaded applications efrost at single/double evaporator
More informationID-Digifrost Line ID-DIGIFROST LINE BROCHURE
IDDigifrost Line IDDIGIFRT LINE BRCHURE Table of Contents General Description Icon pecifications election Guide ID 96(), 96 L 3 ID 970, 970 L 4 ID 97, 97 L temperature (PtcNtc) 5 ID 974, 974 L 6 ID 975
More informationPROGRAMMING CONTROLLER ELIWELL IC-915 DUAL CONTROLLER
PROGRAMMING CONTROLLER ELIWELL IC-915 DUAL CONTROLLER Programming Manual Release Date: July 5, 2006 Publication Number: 33319INS Revision Date: April 03, 2014 Revision: C Visit the Cornelius web site at
More informationLOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E
LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E Table of contents 1. INTRODUCTION...1 2. HARDWARE DESCRIPTION...2 3. INSTALLATION...6 4. CONNECTION...8 5. USER SAFETY AND PROTECTION OF THE EQUIPMENT...11
More informationControllers for static or ventilated refrigeration units up to 2HP. Innovative Solutions for Cold Rooms. Technology & Evolution
Controllers for static or ventilated refrigeration units up to 2HP Innovative Solutions for Cold Rooms Technology & Evolution MasterCella is the new series of controllers for cold rooms that joins the
More informationField module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve
FKE003 Field module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve Features Operation of electronic expansion valves pulsed via integrated electronic
More informationOne Channel and Two Channel DALI Relay Device
Installation Guide DGOZ-RLY-10A-01 DGOZ-RLY-10A-02 One Channel and Two Channel DALI Relay Device REGISTERED DESIGN Designed in Australia to meet Australian Standards and installation conditions DIGINET.NET.AU
More informationSupplementary operating instructions for your air curtain system Controller TMC 500
Supplementary operating instructions for your air curtain system Controller TMC 500 (Translation of the original) Serial number: Year: Please quote this number when contacting customer service! Date 08.04.2016
More informationenglish S-5EC Potentiometer 5-step Operating Instructions Keep for reference! L-BAL-E265-GB 1608 Index 002
S-5EC english Potentiometer 5-step Operating Instructions Keep for reference! Content 1 General notes............................................ 3 1.1 Structure of the operating instructions....................
More informationE2KQ-X. Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster. Chemical-resistant Proximity Sensor. Ordering Information
Chemical-resistant Proximity Sensor E2KQ-X CSM_E2KQ-X_DS_E_4_3 Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster Excellent resistance against chemicals and oil with fluororesincoated case.
More informationNon-communicating room controllers
3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,
More information2-Way Wireless I/O Expander Installation Guide
2-Way Wireless I/O Expander Installation Guide For more detailed information please refer to the iconnect Installer Manual provided on our website: www.electronics-line.com Table of Contents 1. Introduction...
More informationE2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.
Flat Proximity Sensor EK-F CSM_EK-F_DS_E Flat Capacitive Sensor with a Thickness of Only mm Flat Sensor with excellent space efficiency. (Model with built-in Amplifier is only mm thick.) Direct mounting
More informationOperating instructions AC010S Compact AS-i E-STOP safety module
Operating instructions AC010S Compact AS-i E-STOP safety module Sachnr. 7390636_/00 05/2007 Contents Safety instructions............................. 3 Installation / Setup............................
More informationGCI-5K INSTALLATION AND OPERATOR S MANUAL
GCI-5K INSTALLATION AND OPERATOR S MANUAL Grid-tied inverter for wind Ningbo Ginlong Technologies 1 INTRODUCTION 2 SAFETY GUIDELINES AND WARNINGS 3 INSTALLATION 3.1 Selecting a location for the inverter
More informationOriginal operating instructions Fail-safe inductive sensor GF711S / / 2013
Original operating instructions Fail-safe inductive sensor GF7S 8528 / 5 / 23 Contents Preliminary note...3. Explanation of symbols...3 2 Safety instructions...4 2. Safety-related requirements regarding
More informationON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)
(ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET TCY-BH-T-U Wall controller with sensor TDC-BH-T-U Duct controller with sensor SOA-Tn10 Outdoor temperature sensor (Optional) OVERVIEW For wall applications
More informationDESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications
3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for
More informationTXM1.8U TXM1.8U-ML. Universal modules TX-I/O
8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility
More informationRoom unit with PPS2 interface
1 626 Room unit with PPS2 interface for use with: controllers with a PPS2 interface QAA88.3 Room temperature measurement Key buttons for adjustment of the room temperature setpoint Key buttons for operating
More informationSemi flush-mounted room temperature controllers with LCD
s 3 077 RDD310 RDE410 Semi flush-mounted room temperature controllers with LCD For heating systems RDD310 RDE410 RDD310 and RDE410 features: Operating voltage AC 230 V 2-position control with On / Off
More informationAC-115 Compact Networked Single-Door Controller Hardware Installation and Programming
AC-115 Compact Networked Single- Controller Hardware Installation and Programming Copyright 2013 by Rosslare. All rights reserved. This manual and the information contained herein are proprietary to REL,
More informationOriginal operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016
Original operating instructions Safety relay with relay outputs with and without delay UK G50S 803638 / 00 0 / 06 Contents Preliminary note...4. Symbols used...4 Safety instructions...5 3 Items supplied...6
More informationLEDsmart+ Slave Relay Device
Installation Guide MMSR Provides general purpose ON/OFF control via 2-wire trailing edge devices Compatible with Diginet MEDM Dimmer Diginet LEDsmart+ Dimmers (Rotary and Push Button versions) Diginet
More informationGREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26
E39.0.31.6C-02 Data logger for humidity temperature as of version V1.0 Operating Manual T-Logg 160 GREISINGER electronic GmbH D - 93128 Regenstauf, Hans-Sachs-Straße 26 +49 (0) 9402 / 9383-0 +49 (0) 9402
More informationOriginal operating instructions Safety relay with relay outputs G1501S / / 2016
Original operating instructions Safety relay with relay outputs G50S UK 8023637 / 00 02 / 206 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...5 3 Items supplied...6 4 Functions
More informationControllers for compressor racks with advanced energy saving. PN08 September 2016
page 1 / 16 XC400/600 for small/medium compressor rack management Dixell introduces the new compact parametric controllers for compressor rack with. Dixell presents the XC400/600 series, dedicated to the
More informationWING REFRIGERATION CONTROLLERS
SECTION INDEX FUNCTIONS MODELS - NT, MT AND LT APPLICATIONS COMPACT/SPLIT FORMAT Thermostats and off cycle defrost multifunction controllers XW10L - XW10V- - XW20L - XW20LS - XW20V - XW20VS Multifunction
More informationCustom Controller Installation Instructions
MODEL CUSTOM CONTROLLER HARDWARE CODE MAX ALLOWABLE AMBIENT TEMP: 70 C (158 F) THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: 1) THIS DEVICE MAY
More informationOrdering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel
I/O Relay CSM DS_E_4_4 Slim-styled I/O Relay Saves Space in Panel SPST-NO, SPST-NC, and SPDT contact forms available for output (SPST-NO only for input). Ultra-slim housing measuring 29 (W) x 0 (D) x 2
More informationRack Input Module Installation Instructions
Rack Input Module Installation Instructions DOC. #560105000 A 7/30/04 PRINTED IN U.S.A. Regulatory Compliance Safety This device has been tested and found to be in compliance with the requirements set
More informationIO-AO6X I/O Expansion Module 6 Isolated Analog Outputs
IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated
More informationXEV EX48 Superheat Controller
Instruction Sheet PA-00369 January 2014 XEV EX48 Superheat Controller XEV EX48 Superheat Controller with ModBus Communication Capability XEV EX48 Driver for Emerson EX4,5,6,7,8 Electronic Stepper Expansion
More informationEWCM Compact controller for compressor plants
EN EWCM 4120-4150-4180 e Compact controller for compressor plants 1 Summary INTRODUCTION - CHaracteristics...4 CONDITIONS OF USE...4 MECHANICAL ASSEMBLY...7 WIRING DIAGRAMS...7 CONNECTION DIFFERENCES BETWEEN
More informationMCX06C Programmable controller
Data sheet MCX06C Programmable controller MCX06C is an electronic controller that holds all the typical functionalities of MCX controllers in the 32x74 mm standard size: programmability connection to the
More informationRXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station
s 3 836 3836P01 Desigo TRA PL-Link IO Block Use with PXC3 series room automation station RXM39.1 The PL-Link IO Block contains the inputs and outputs controlled by a room automation station via PL-Link.
More informationLED W RGBA User Manual
LED- 245-1W RGBA User Manual Please read the instructions carefully before use CONTENTS 1. Safety Instructions...2 2. Technical Specifications...3 3. How To Set The Unit...4 3.1 Control Panel...4 3.2 Main
More informationProgrammable controller Type MCX06C
Programmable controller Type Danfoss range of universal MCX programmable controllers offers the functionality and reliability you need to get the best out of your heating, ventilation, air-conditioning
More informationGREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26
H20.0.34.6C-05 EASYBus-Sensor module for temperature from version V3.2 Operating Manual EBT 2R Content 1 INTENDED USE 2 2 GENERAL ADVICE 2 3 SAFETY INSTRUCTIONS 2 4 DISPOSAL NOTES 2 5 ASSIGNMENT 3 6 DIMENSION
More informationNon-communicating room controllers
3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For
More informationRefrigeration solutions Controllers for commercial refrigeration, food service and catering
Refrigeration solutions Controllers for commercial refrigeration, food service and catering PRIME WING Refrigeration solutions PRIME & WING Series are the innovative & aesthetical solution controllers
More informationXR-CHC and XRB-CHC Refrigeration controllers with Bluetooth connectivity
XR-CHC and XRB-CHC Refrigeration controllers with Bluetooth connectivity PN 13/18 September Dixell introduces its new XR-CHC and XRB-CHC controllers with Bluetooth connectivity for refrigerated applications.
More informationIO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs
IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-TO8 and IO-DI8-TO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The
More informationFS-21.doc Status Filter Control FS-21. EasyRange
Filter Control FS-21 EasyRange 1/27 1/28 Index 1 General Information...4 1.1 Equipment...4 2 Installation...5 2.1 Mechanical Installation...5 2.2 Electrical Installation...5 2.2.1 Connection Diagram...6
More informationRТTH DUAL ROOM SWITCH
DUAL ROOM SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS PRODUCT DESCRIPTION ARTICLE CODES INTENDED AREA OF USE TECHNICAL DATA
More informationProgrammable controller MCX06C
MAKING MODERN LIVING POSSIBLE Technical brochure Programmable controller MCX06C Danfoss range of universal MCX programmable controllers offers the functionality and reliability you need to get the best
More informationOriginal operating instructions Fail-safe inductive sensor GI711S / / 2010
Original operating instructions Fail-safe inductive sensor GI7S 704583 / 0 06 / 200 Contents Preliminary note 3. Explanation of symbols 3 2 Safety instructions 4 2. Safety-related requirements regarding
More informationCA-A480-A Elevator Controller. Reference & Installation Manual
CA-A480-A Elevator Controller Reference & Installation Manual TABLE OF CONTENTS INTRODUCTION.................................................................. 4 Introduction.............................................................................................
More informationTLZ10 DIGITAL ELECTRONIC THERMOCONTROLLER. toll-free 1(866) (603) ADVANCED THERMOELECTRIC PO Box 1003, WRJ, VT 05001
TLZ0 DIGITAL ELECTRIC THERMOCTROLLER ADVANCED THERMOELECTRIC PO Box 003, WRJ, VT 000 toll-free (8) -434 (03) 888-47 sales@electracool.com The Z3 Series became the replacement for the TLZ0 and TDH-0 Series
More informationESM-3711-CL 77 x 35 DIN Size, Minimum & Maximum Temperature Record, Digital, ON / OFF Cooling Controller
ESM-3711-CL 77x35 DIN Size Cooling Controller Internal Buzzer ESM-3711-CL 77 x 35 DIN Size, imum & imum Temperature Record, Digital, ON / OFF Cooling Controller - 3 Digits display - NTC input or, PTC input
More informationOEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers
OEM CLIMATIX TM Room unit QAA822 with2- wire interface For use with Climatix controllers Remote control of air conditioning unit Mandík Measurement of the room temperature Buttons for starting, setting
More informatione30v DIGITAL ELECTRONIC THERMOMETER OPERATING INSTRUCTIONS Index
e30v DIGITAL ELECTRONIC THERMOMETER OPERATING INSTRUCTIONS Vr. 01 (ENG) - 18/01 - cod.: ISTR-Me30V-ENG01 ASCON TECNOLOGIC S.rl. Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY Tel.: +39 0381 69871 -
More informationName No. of I/O points Model Safety inputs: 12, test outputs: 4
Safety I/O s DST1 Series CSM_DST1 Series_DS_E_7_3 Distributed Safety s That Reduce Wiring. Lineup includes four models to accommodate various I/O types and number of I/O points. Monitor the safety system
More informationThe Indicator with 3 Limit Contacts
A 1200 The Indicator with 3 Limit Contacts Format: Installation depth: 96x48 mm (1/8-DIN) 122 mm Description and Operating Manual ELOTECH Industrieelektronik GmbH Verbindungsstrasse 27 D 40723 HILDEN FON
More informationE2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.
Flat Proximity Sensor EK-F CSM_EK-F_DS_E Flat Capacitive Sensor with a Thickness of Only mm Flat Sensor with excellent space efficiency. (Model with built-in Amplifier is only mm thick.) Direct mounting
More informationSD1306. Speed Dome IP Camera. Quick User Guide
SD1306 Speed Dome IP Camera Quick User Guide Table of Contents I. Camera Introduction... 1 1. Package Contents... 1 2. Hardware Installation... 2 2.1 Factory Default... 6 3. SD card Compatibility List...
More informationQXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000
1 542 1542P03 1542P01 1542P02 QXA2001 QXA2000 AQX2000 Condensation Monitor QXA2000 QXA2001 The QXA2000 condensation monitor is used to avoid damage due to condensation on chilled ceilings and in HVAC plant.
More informationTemperature & Humidity Datalogger
R6030 Temperature & Humidity Datalogger Instruction Manual Table of Contents Introduction... 2 Product Quality... 3 Safety... 3 Features... 3 Included... 3 Specifications... 4 Instrument Description...
More informationMicro-Ohmmeter Model 6292
Micro-Ohmmeter Model 6292 Quick Start Guide ENGLISH www.aemc.com CHAUVIN ARNOUX GROUP Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated
More informationOperating Manual RISH DPM Hz
Operating Manual RISH DPM 72mm x 144mm 96mm x 96mm 48mm x 96mm 2-60-006-00-00512_Rev. B - 7/2016 DIGITAL MULTIFUNCTION INSTRUMENT Programmable Digital Panel Meter Installation & Operating Instructions
More informationElectronic controllers for small centralised air-conditioning units
FLEX Electronic controllers for small centralised air-conditioning units General Description Eliwell, a leading manufacturer for over a decade of control equipment for small and medium-size air conditioning
More informationMETREL test and measurement accessories: 3-phase AktivGT / Machine adapter A1322 Instruction manual Version 1.0, Code no.
METREL test and measurement accessories: 3-phase AktivGT / Machine adapter A1322 Instruction manual Version 1.0, Code no. 20 751 979 Distributor: Manufacturer: METREL d.d. Ljubljanska cesta 77 1354 Horjul
More informationMILLENIUM INSTALLATION MANUAL NTR 735 B/E. Simple Automation Control Module (MAS)
MILLENIUM /E Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 6 4. CONNECTION 7 5. USER SAFETY AND PROTECTION OF EQUIPMENT 10 1. Introduction The MILLENIUM series has been
More informationEVF305 Product specifications - Version 1.02 EVCO S.p.A. Evco S.p.A. Product specifications EVF305
Evco S.p.A. Product specifications EVF305 Digital controllers for the management of the rotisserie with capacitive type user interface Drawn-up by Name and surname Date November 2012 page 1 of 14 1. REVISIONS
More informationTemperature controller Ducted systems
2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master
More informationTC-8900 Controller Units with PM-8900 Power Modules
European Electronic Controls Catalogue Catalogue Section F Product Bulletin PM-8900 Issue date 06 2000 TC-8900 Controller Units with PM-8900 Power Modules Introduction TC-8900 is a family of analogue controllers,
More informationNumber of input channels
Safety Relay Unit (Sensor Connector Type) CSM DS_E_3_1 Less Wiring Required with Safety Light Curtain Sensor connector allows direct connection to OMRON 3SJ Safety Light Curtains with PNP outputs. Reduces
More informationFCA THE SOLLATEK FREOCOM
FCA THE SOLLATEK FREOCOM the Intelligent Controls Temperature control, energy saving and voltage protection for all fridges, freezers and coolers. As the problems associated with global warming become
More informationSMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015)
SMM Series 3G and GSM Modems Quick Start Guide Document Number: 0013-001-000272 () Documentation Control Generation Date: October 20, 2015 Cybertec Pty Limited All rights Reserved. No part of this publication
More informationTXM1.8U TXM1.8U-ML. Universal modules TX-I/O
s 8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility
More informationSeries SD-3PB Digital THERMOSTAT + TIMER
SD-3PB Thermostat and Interval Timer in one Unit. This microcomputer based controller consists of two sections: The Digital Timer and Digital Thermostat, working together to control the power switched
More informationDocumentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:
Documentation Fan cartridge for EtherCAT and Bus Terminals Version: Date: 1.5 2017-08-07 Table of contents Table of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety instructions...
More informationProduct and functional description
Product and functional description The RS 520/23 shutter / blind actuator is a KNX device with one relay output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The
More informationOP10. Pre-programmed, configurable controller for simple applications
revision 10 2013 OP10 Pre-programmed, configurable controller for simple applications The Optigo OP10 range of controllers can be set to handle everything from temperature or humidity control to control
More informationProduct and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs
Product and Applications Description Example of Operation dimmer UP 525/11 load circuit AC 230 V L1 N The dimmer UP 525/11 is a dimming actuator for mounting in box mounts (a.o. 60 mm Ø, 60 mm depth).
More informationE2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor
Aluminum-detecting Proximity Sensor EEY CSM_EEY_DS_E_5_1 A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Non-ferrous metals, such as aluminum and brass, are detected.
More informationDXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions
DUAL DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL
More informationRoom Temperature Controller
3 023 Room Temperature Controller for four-pipe fan coil units RCC30 Outputs for on / off valve actuators Outputs for three-speed fan Control depending on room or return air temperature Operating modes:
More informationRXTH DUAL ROOM SENSOR / SWITCH
DUAL ROOM SENSOR / SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE
More information