PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS CABLING RFP (TOTAL OF 1500 CAT6 DROPS)

Size: px
Start display at page:

Download "PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS CABLING RFP (TOTAL OF 1500 CAT6 DROPS)"

Transcription

1 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS CABLING RFP (TOTAL OF 1500 CAT6 DROPS) This is an RFP for Internal Connections (Cabling) for Prairie-Hills Elementary School District 144. This primary cabling will be for the new Prairie-Hills Junior High School in Markham, Illinois. REQUEST FOR PROPOSAL DESCRIPTION: STRUCTURED TELECOMMUNICATIONS CABLING AND ENCLOSURES PART 1 GENERAL 1.01 SECTION INCLUDES A. Voice Cabling B. Data Cabling C. Wireless Cabling D. Overhead Projector Data Cabling E. Video Conference Cabling F. Video Distribution over Data Cabling (Closed Circuit Video Distribution System) G. USB Cabling (Cat 6e and USB) H. Fiber Optic Cabling I. RGBHV Cabling J. HDMI Cabling K. 3.5mm Audio Cabling L. Classroom Audio M. Open Racks N. Four post server racks O. Distribution frames, cross-connection equipment, enclosures, and outlets RELATED REQUIREMENTS

2 A. Section Building Wire and Cable. B. Section Grounding and Bonding: Electrical system grounding and bonding. C. Section Conduit. D. Section Cable Trays E. Section Boxes. F. Section Closed Circuit Video Distribution System 1.03 COODRINATION OF WORK A. Contractor shall furnish and install all conduit/raceway as required for the structured cabling distribution system. This includes all raceway explicitly shown on plans or generically required for a complete, functional system. B. Contractor shall furnish and install all specialty backboxes for devices as required for the structured cabling distribution system. This includes all backboxes explicitly shown on plans or generically required for a complete, functional system. C. Contractor shall furnish and install all branch circuits required for the structured cabling distribution system as specified. This includes all circuits explicitly shown on plans or generically required for a complete, functional system. STRUCTURED TELECOMMUNICATIONS CABLING AND ENCLOSURES 1.04 REFERENCE STANDARDS A. ICEA S Category 3, 5, & 5e Individually Unshielded Twisted Pair Indoor Cable for Use in General Purpose and LAN Communications Wiring Systems; Insulated Cable Engineers Association; B. NFPA 70 - National Electrical Code; C. TIA FOTP-21 - Mating Durability of Fiber Optic Interconnecting Devices; Rev A, 1988(R 2002). D. TIA-492AAAB - Detail Specification for 50-um Core Diameter/125-um Cladding Diameter Class Ia Graded-Index Multimode Optical Fibers; 1998 (R 2002). E. TIA-492CAAA - Detail Specification for Class IVa Dispersion-Unshifted Single-Mode Optical Fibers; 1998 (R 2002).

3 F. TIA OFSTP-7 - Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant; G. TIA OFSTP-14 - Optical Power Loss Measurements of Installed Multimode Fiber Cable Plant; Rev A, 1998(R2003). H. TIA/EIA-568-B.1 - Commercial Building Telecommunications Cabling Standard - Part 1: General Requirements; Rev B, 2001; Addenda 1-7. I. TIA/EIA-568-B.2 - Commercial Building Telecommunications Cabling Standard - Part 2: Balanced Twisted Pair Cabling Components; Rev B, 2001; Addenda J. TIA/EIA-568-B.3 - Commercial Building Telecommunications Cabling Standard - Part 3: Optical Fiber Cabling Components Standard, and Addendum 1 - Additional Transmission Performance Specifications for 50/125 um Optical Fiber Cables; Rev B, 2000; Addendum 1. K. TIA Commercial Building Standard for Telecommunications Pathways and Spaces; L. TIA/EIA Administration Standard for the Telecommunications Infrastructure; Rev A, M. ANSI/J-STD Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications; Rev A, N. UL Communications Cables; Current Edition, Including All Revisions. O. UL Standard for Protectors for Paired-Conductor Communications Circuits; Current Edition, Including All Revisions. P. UL Reference Standard for Electrical Wires, Cables, and Flexible Cords; Current Edition, Including All Revisions. Q. UL Standard for Communications-Circuit Accessories; Current Edition, Including All Revisions SUBMITTALS A. Product Data: Manufacturer's data sheets on each product to be used, including: 1. Storage and handling requirements and recommendations. 2. Installation methods. B. Shop Drawings: Show compliance with requirements on isometric schematic diagram of network layout, showing cable routings, telecommunication closets, rack and enclosure layouts

4 and locations, service entrance, and grounding, prepared and approved by BICSI Registered Communications Distribution Designer (RCDD). C. Manufacturer Qualifications. D. Installer Qualifications. E. Test Plan: Complete and detailed plan, with list of test equipment, procedures for inspection and testing. Submit along with product data. F. Field Test Reports. G. Project Record Documents: Prepared and approved by BICSI Registered Communications Distribution Designer (RCDD). 1. Record actual locations of outlet boxes and distribution frames. 2. Show as-installed color coding, pair assignment, polarization, and cross-connect layout. 3. Identify distribution frames and equipment rooms by room number on contract drawings. H. Operation and Maintenance Data: List of all components with part numbers, sources of supply, and operation and maintenance instructions; include copy of project record documents QUALITY ASSURANCE A. Manufacturer Qualifications: At least 3 years experience manufacturing products of the type specified. B. Installer Qualifications: A company having at least 3 years experience in the installation and testing of the type of system specified, and: 1. Employing a BICSI Registered Communications Distribution Designer (RCDD). 2. Supervisors and installers factory certified by manufacturers of products to be installed. 3. Employing BICSI Registered Cabling Installation Technicians (RCIT) for all work DELIVERY, STORAGE, AND HANDLING A. Store products in manufacturer's unopened packaging until ready for installation. B. Keep stored products clean and dry WARRANTY

5 A. The installing Contractor shall provide from the prime data and voice wiring distribution equipment manufacturer a 25 year warranty. 1. Cable conductors shall have test data that includes sufficient information to fully identify the conductors or paired conductors according to the practices established in ANSI/TIA/EIA Telecommunication Building Wiring Standards. The test results must be provided on 3.5" DOS formatted diskettes, in one of the following file formats: a. ASCII File b. Manufacturer of hand-held tester formatted file 2. Installing Contractor shall be responsible (at installing Contractors expense) for satisfying all requirements necessary as stipulated by warranty provider. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Cabling and Equipment: 1. Cable Manufacturers a. Mohawk b. Berk-Tek c. Superior Essex 2. Modular Jack Manufacturers a. Hubbell b. Ortronics c. Leviton 2.02 SYSTEM DESIGN A. Provide a complete permanent system of cabling and pathways for voice and data communications, including cables, conduits and wireways, pull wires, support structures, enclosures and cabinets, and outlets. 1. Comply with TIA/EIA-568 and TIA/EIA-569, latest editions.

6 2. Entire system shall be Cat 6e certified and warranteed unless otherwise noted. All cabling is specified as Mohawk GigLAN or equal Berk-Tek or Superior Essex. 3. Provide fixed cables and pathways that comply with NFPA 70 and ANSI/J-STD-607 and are UL listed or third party independent testing laboratory certified. 4. In this project, the term plenum is defined as return air spaces above ceilings, inside ducts, under raised floors, and other air-handling spaces. B. Main Distribution Frame (MDF): Centrally located support structure for terminating backbone cables, functioning as point of presence to external service provider. 1. Locate main distribution frame as indicated on the drawings. 2. Capacity: As required to terminate all cables required by design criteria plus minimum 25 percent spare space. C. Intermediate Distribution Frames (IDF): Support structures for terminating horizontal cables that extend to telecommunications outlets. 1. Locate intermediate distribution frames as indicated on the drawings. D. Backbone Cabling: Cabling, pathways, and terminal hardware connecting intermediate distribution frames (IDF's) with main distribution frame (MDF), wired in star topology with main distribution frame at center hub of star. E. Cabling to Outlets: Specified horizontal cabling, wired in star topology to distribution frame located at center hub of star; also referred to as "links" PATHWAYS A. Conduit: As specified in Section 16131; provide pull cords in all conduit. B. Underground Service Entrance: PVC, Type EPC-40 conduit COPPER CABLE AND TERMINATIONS A. Voice Cabling 1. Backbone Voice a. Copper Backbone Cable: TIA/EIA-568 Category 3 solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 100 pairs formed into 25-pair binder groups; covered with gray

7 thermoplastic jacket and complying with all relevant parts of and addenda to latest editions of TIA/EIA-568 and ICEA S , and UL ) Provide NFPA 70 type CMP plenum-rated cable. 2) Provide cable having conductors twisted at minimum rate of two per foot; actual length and frequency of twists at manufacturer's option. 3) Color code conductors in accordance with ICEA S ) Each patch panel port shall have two pair terminated 5) Provide minimum 40% spare pairs 2. Horizontal Voice a. Cable 1) Copper Horizontal Cable: TIA/EIA-568 Category 6e solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 4 individually twisted pairs; covered with White jacket and complying with all relevant parts of and addenda to latest edition of TIA/EIA-568 and UL 444. (a) Provide NFPA 70 type CMP plenum-rated cable. (b) Mohawk GigaLAN or equal b. Jacks and Connectors 1) RJ-45, non-keyed, terminated with 110-style insulation displacement connectors; high impact thermoplastic housing; complying with same standard as specified horizontal cable and UL (a) Color: White (b) Performance: 500 mating cycles. (c) Voice Jacks: 4-pair, pre-wired to T568A configuration, with color-coded indications for T568B configuration. B. Data Cabling 1. Horizontal Data a. Cable

8 1) Copper Horizontal Cable: TIA/EIA-568 Category 6e solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 4 individually twisted pairs; covered with blue jacket and complying with all relevant parts of and addenda to latest edition of TIA/EIA-568 and UL 444. (a) Provide NFPA 70 type CMP plenum-rated cable. (b) Mohawk GigaLAN or equal b. Jacks and Connectors 1) RJ-45, non-keyed, terminated with 110-style insulation displacement connectors; high impact thermoplastic housing; complying with same standard as specified horizontal cable and UL (a) Color: Blue (b) Performance: 500 mating cycles. (c) Data Jacks: 4-pair, pre-wired to T568A configuration, with color-coded indications for T568B configuration. 2. Wireless a. Cable 1) Copper Horizontal Cable: TIA/EIA-568 Category 6e solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 4 individually twisted pairs; covered with Green jacket and complying with all relevant parts of and addenda to latest edition of TIA/EIA-568 and UL 444. (a) Provide NFPA 70 type CMP plenum-rated cable. (b) Mohawk GigaLAN or equal b. Jacks and Connectors 1) RJ-45, non-keyed, terminated with 110-style insulation displacement connectors; high impact thermoplastic housing; complying with same standard as specified horizontal cable and UL (a) Color: Green (b) Performance: 500 mating cycles. (c) Data Jacks: 4-pair, pre-wired to T568A configuration, with color-coded indications for T568B configuration.

9 3. Overhead Projector Data Cabling a. Cable 1) Copper Horizontal Cable: TIA/EIA-568 Category 6e solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 4 individually twisted pairs; covered with Yellow jacket and complying with all relevant parts of and addenda to latest edition of TIA/EIA-568 and UL 444. (a) Provide NFPA 70 type CMP plenum-rated cable. (b) Mohawk GigaLAN or equal b. Jacks and Connectors 1) RJ-45, non-keyed, terminated with 110-style insulation displacement connectors; high impact thermoplastic housing; complying with same standard as specified horizontal cable and UL (a) Color: Yellow (b) Performance: 500 mating cycles. (c) Data Jacks: 4-pair, pre-wired to T568A configuration, with color-coded indications for T568B configuration. 4. Video Conference Cabling a. Cable 1) Copper Horizontal Cable: TIA/EIA-568 Category 6e solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 4 individually twisted pairs; covered with Black jacket and complying with all relevant parts of and addenda to latest edition of TIA/EIA-568 and UL 444. (a) Provide NFPA 70 type CMP plenum-rated cable. (b) Mohawk GigaLAN or equal b. Jacks and Connectors 1) RJ-45, non-keyed, terminated with 110-style insulation displacement connectors; high impact thermoplastic housing; complying with same standard as specified horizontal cable and UL (a) Color: Black

10 (b) Performance: 500 mating cycles. (c) Data Jacks: 4-pair, pre-wired to T568A configuration, with color-coded indications for T568B configuration. 5. Video Distribution over Data Cable a. Cable 1) Copper Horizontal Cable: TIA/EIA-568 Category 6e solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 4 individually twisted pairs; covered with Orange jacket and complying with all relevant parts of and addenda to latest edition of TIA/EIA-568 and UL 444. (a) Provide NFPA 70 type CMP plenum-rated cable. (b) Mohawk GigaLAN or equal b. Jacks and Connectors 1) RJ-45, non-keyed, terminated with 110-style insulation displacement connectors; high impact thermoplastic housing; complying with same standard as specified horizontal cable and UL (a) Color: Orange (b) Performance: 500 mating cycles. (c) Data Jacks: 4-pair, pre-wired to T568A configuration, with color-coded indications for T568B configuration. 6. USB Cabling a. Horizontal USB - Cat 6 Connector 1) Cable (a) Copper Horizontal Cable: TIA/EIA-568 Category 6e solid conductor unshielded twisted pair (UTP), 24 AWG, 100 ohm; 4 individually twisted pairs; covered with Red jacket and complying with all relevant parts of and addenda to latest edition of TIA/EIA-568 and UL 444. (1) Provide NFPA 70 type CMP plenum-rated cable. (2) Mohawk GigaLAN or equal 2) Jacks and Connectors

11 (a) RJ-45, non-keyed, terminated with 110-style insulation displacement connectors; high impact thermoplastic housing; complying with same standard as specified horizontal cable and UL (1) Color: Red (2) Performance: 500 mating cycles. (3) Data Jacks: 4-pair, pre-wired to T568A configuration, with color-coded indications for T568B configuration. b. Horizontal USB - USB Connector 1) Cable (a) Custom terminated USB cable length as required (b) Terminated A-to-A 2) Jacks and Connectors (a) USB Pass through Connector (1) USB A-to-A (2) Color: Blue C. Patch Cords: 1. Patch cords are to be provided for all ports within patch panels and at user ports (i.e. office space or classroom). Cords to be miscellaneous lengths as required (verify with Owner and in field). Cords to be color to match system. 2. Patch cords shall be provided for all cabling to include but not limited to data, voice, wireless, overhead projectors, USB, video conference, video distribution, HDMI, 15 pin VGA, 3.5mm Audio and Coax with F connectors for video distribution. All patch cords are to be factory made. All patch cords will be stranded construction unshielded twisted pair and be constructed following all TIA/EIA 568A, TSB-36, TSB-40 standards. b. Contractor shall provide proper length patch cables to facilitate moves and changes. Final layout of wiring closets shall determine proper patchcord lengths. Example lengths are listed below. c. Patch cords shall be category (5e, 6, etc.) to match specified horizontal voice and data cabling.

12 2.05 FIBER OPTIC CABLE AND ADAPTORS A. Fiber Optic Backbone Cable: # as noted on drawings-fiber, multimode 50/125 um, complying with TIA-492AAAB; covered with orange cable jacket and complying with relevant portions of and addenda to latest edition of TIA/EIA Provide NFPA 70 type OFNP nonconductive-plenum-rated cable. 2. All fiber optic cables shall be run in (and protected by) plenum rated indoor corrugated innerduct. Contractor shall size innerduct as required. B. Fiber Optic Adapters and Connectors: Duplex SC, push-on-push-off type, multimode adaptors with zirconia ceramic alignment sleeves; complying with relevant parts and addenda to latest edition of TIA/EIA-568 and with maximum attenuation of 0.3 db at 1300 nm with less than 0.2 db change after 500 mating cycles when tested in accordance with TIA C. Fiber patch cords 1. Provide full complement of patch cords sized as required CROSS-CONNECTION EQUIPMENT A. Connector Blocks for Category 5e and Up Cabling: Type 110 insulation displacement connectors; capacity sufficient for cables to be terminated plus 25 percent spare. B. Patch Panels for Copper Cabling: Sized to fit EIA standard 19 inch wide equipment racks; 0.09 inch thick aluminum; cabling terminated on Type 110 insulation displacement connectors; printed circuit board interface. 1. Jacks: Non-keyed RJ-45, suitable for and complying with same standard as cable to be terminated; maximum 48 ports per standard width panel. 2. Capacity: Provide ports sufficient for cables to be terminated plus 25 percent spare. 3. Labels: Factory installed laminated plastic nameplates above each port, numbered consecutively; comply with TIA/EIA-606 using encoded identifiers. 4. Provide incoming cable strain relief and routing guides on back of panel. 5. Provide full height (min 2U) patch cord organizers for each patch panel a. Minimum 2U height b. Panel material: 16 ga cold-rolled steel

13 c. cover material: 16 ga cold-rolled steel d. Ring: 0.225" diameter steel road e. Black power coat f. Front and rear rings g. Front and rear cover 6. Patch Cords: Provide one patch cord for patch panel port. 7. Jack colors in patch panel shall match system wiring colors (ex, data - Blue, Voice - White, etc.) C. Patch Panels for Fiber Optic Cabling: Sized to fit EIA standard 19 inch wide equipment racks; 0.09 inch thick aluminum. 1. Adaptors: As specified above under FIBER OPTIC CABLING; maximum of 24 duplex adaptors per standard panel width. 2. Labels: Factory installed laminated plastic nameplates above each port, numbered consecutively; comply with TIA/EIA-606 using encoded identifiers. 3. Provide incoming cable strain relief and routing guides on back of panel. 4. Provide rear cable management tray at least 8 inches deep with removable cover. 5. Provide dust covers for unused adaptors. 6. Patch Cords: Provide one patch cord for each patch panel port RGBHV DISTRIBUTION SYSTEM A. Final wall mounted connector shall be female to female 15-pin pass through type. Coordinate cable connectors with face plate module. B. Cabling shall be preconnectorized type: One of the following (no substitutions) 1. Hubbell Plug-n-Play 2. Rapid Run C. Verify connection type/method and raceway capacity based upon submitted cables and jacks.

14 2.08 HDMI DISTRIBUTION SYSTEM A. Final wall mounted connector shall be female to female HDMI pass through type. Coordinate cable connectors with face plate module. B. Cabling shall be preconnectorized type: One of the following (no substitutions) 1. Hubbell Plug-n-Play 2. Rapid Run C. Verify connection type/method and raceway capacity based upon submitted cables and jacks mm Audio system A. Final wall/ceiling mounted connector 3.5mm Mini stereo jack 1. Stereo pair connectors shall be Red for right channel and White for left channel B. Audio cables shall be field terminated at each end to male RCA connectors. 1. Terminations shall be solder type C. Cable shall be 25AWG shielded low capacitance audio connecting cable 1. Single Channel Audio: Belden (or equal) 8421 shall be used. Two Channel Audio: Belden audio (or equal) D. Verify connection type/method and raceway capacity based upon submitted cables and jacks Classroom Audio - Solution B A. RDL TX-PA40D Audio Power Amplifier 1. Inputs: 10K ohm balanced 2. Input Level: 400 mv (RMS) minimum 3. Frequency Response: 35 Hz TO 30 khz 4. THD: less than.35% 5. Noise: less than -60 db 6. Output: 8 ohom balanced, 6 watts RMS

15 7. Power: 24 to mA B. Tannoy CMS601 DCEM Recessed Ceiling Speaker 1. Tile bridge for lay-in ceiling application 2. Plaster mud ring where required C. Altronix Power Supply VDC output 2. Number of circuits as required. One circuit per classroom 3. Total capacity as required (1.5A DC per RDL TX-PA40D) 4. Output fuses rated a 1.5 amp VAC Input 2.11 ENCLOSURES A. Backboards: Interior grade plywood without voids, 3/4 inch thick; UL-labeled fire-retardant. 1. Size: As indicated on drawings. 2. Do not paint over UL label. B. Racks and Cabinets: 1. Racks (Open bay): EIA-310-D standard 19 inch wide component racks. a. All data/network cabinets shall be open bay relay racks designed in accordance with EIA RS- 310c STANDARDS (19"). The racks shall be constructed of aluminum with durable black polyurethane or mill finish designed for 19" rack mount equipment. Racks shall be 84" high. 1) 16 gage steel construction with corrosion resistant finish; vertical and horizontal cable management channels, top and bottom cable troughs, and grounding lug. 2) Vertical U-channel 3) 6.5" channel depth (unless specified on drawing as 14" channel depth) 4) EIA hole pattern front and rear. 5) Vertical cable management rings

16 6) Floor and ceiling cable access for routing and management of distribution cables. 7) Cable support bracket kit for ladder rack. 8) Ladder rack shall be securely attached to top of cabinets and wall to provide cable raceway path and structural support. 9) All MDF racks shall be secured to floor through approved anchors. 10) Slotted ducts for cable management 11) Each rack shall include 1 prewired AL4000BC raceway with R duplex receptacles 2. 4 Post Server Rack a. Racks (Open bay): EIA-310-D standard 19 inch wide component racks. 1) All data/network cabinets shall be open bay relay racks designed in accordance with EIA RS- 310c STANDARDS (19"). The racks shall be constructed of aluminum with durable black polyurethane or mill finish designed for 19" rack mount equipment. Racks shall be 84" high. (a) 2' Wide X 3" Deep 4 Post (b) 16 gage steel construction with corrosion resistant finish; vertical and horizontal cable management channels, top and bottom cable troughs, and grounding lug. (c) EIA hole pattern front and rear. (d) Vertical cable management rings (e) Floor and ceiling cable access for routing and management of distribution cables. (f) Cable support bracket kit for ladder rack. (g) Ladder rack shall be securely attached to top of cabinets and wall to provide cable raceway path and structural support. (h) All MDF racks shall be secured to floor through approved anchors. (i) Slotted ducts for cable management (j) Each rack shall include 1 prewired AL4000BC raceway with R duplex receptacles 3. Hinged Wall Mount Rack: EIA-310-D standard 19 inch wide component racks.

17 a. Hinged wall mount racks designed to mount 19" equipment. Racks shall be minimum of 36" high and manufactured from 16-gauge steel with a durable black polyurethane finish. b. 8 gage aluminum brackets, hinged to allow access to back of installed components. c. High quality 16 Gauge CRS construction d. One set of fully adjustable (front to rear) 19" #12-24 tapped mounting rails e. Two hinge design to allow body section of cabinet to be opened for easy access to rear of equipment f. Door hinge which allows fully reversible design. g. Top and bottom cabinet knockouts h. Plexiglas door i. grilled bottom for ventilation j. Color as directed by architect k. Electric cooling fan l. Rack mounted power strip. 4. Security Boxes for Wireless Access Points a. Hubbell Wall box WBW10W b. Vented steel enclosure c. Durable powder coat d. Cable entray/exit: four 7/8" round knock-out openings on sides, top and bottom e. Cable entry/exit: one 1 3/8" knock-out on back. f. Accepts most standard, low voltage wireless access points to mount plate with VELCRO cable ties or welf tapping screws. PART 3 EXECUTION 3.01 INSTALLATION - GENERAL A. Comply with latest editions and addenda of TIA/EIA-568, TIA/EIA-569, ANSI/J-STD-607, NFPA 70, and SYSTEM DESIGN as specified in PART 2.

18 3.02 PATHWAYS A. Underground Service Entrance: Install conduit at least 18 inches below finish grade; encase in at least 3 inches thick concrete for at least 60 inches out from the building line. B. Install with the following minimum clearances: inches from motors, generators, frequency converters, transformers, x-ray equipment, and uninterruptible power systems inches from power conduits and cables and panelboards inches from fluorescent and high frequency lighting fixtures inches from flues, hot water pipes, and steam pipes. C. Conduit: 1. Do not install more than 2 (two) 90 degree bends in a single horizontal cable run. 2. Leave pull cords in place where cables are not initially installed. 3. Conceal conduit under floor slabs and within finished walls, ceilings, and floors except where specifically indicated to be exposed. a. Conduit may remain exposed to view in mechanical rooms, electrical rooms, and telecommunications rooms. b. Treat conduit in crawl spaces and under floor slabs as if exposed to view. c. Where exposed to view, install parallel with or at right angles to ceilings, walls, and structural members. d. Under floor slabs, locate conduit at 12 inches, minimum, below vapor retarder; seal penetrations of vapor retarder around conduit. D. Grounding and Bonding: Perform in accordance with ANSI/J-STD-607 and NFPA 70. E. Firestopping: Seal openings around pathway penetrations through fire-rated walls, partitions, floors, and ceilings. F. Cable Routing

19 1. All cabling to re routed within approved raceway or above lay-in ceiling. Cabling shall be hidden by ceiling or raceway in all locations of the building with the exception of IDF and MDF rooms or as otherwise noted on the drawings. a. Where cable tray is provided, route cabling within cable tray. b. Where conduit sleeve is provided, route cabling within conduit sleeve c. Above lay-in ceilings, where cable tray or conduit sleeves are not available: 1) Where raceway for cabling is not provided, Contractor shall run cabling through Erico Cablecat 2" J hooks. (a) J hooks shall be directly attached to building structure at a maximum of 4'-0" center-tocenter. (b) Additional J hooks will be added as necessary to limit the maximum cable catenary (cable sag) to 12" maximum. (c) Install tye-wraps around all J hooks upon completion of cable pulls. (d) J hook cable density shall not exceed 60% of the maximum cable count suggested by manufacture. If necessary, provide additional level of J hooks for high cable density runs. (e) Contractor shall provide all mounting hardware (threaded rod, unistrut, etc.) Necessary to solidly mounted, complete cable raceway system INSTALLATION OF EQUIPMENT AND CABLING A. Cabling: 1. Do not bend cable at radius less than manufacturer's recommended bend radius; for unshielded twisted pair use bend radius of not less than 4 times cable diameter. 2. Do not over-cinch or crush cables. 3. Do not exceed manufacturer's recommended cable pull tension. 4. When installing in conduit, use only lubricants approved by cable manufacturer and do not chafe or damage outer jacket. B. Service Loops (Slack or Excess Length): Provide the following minimum extra length of cable, looped neatly: 1. At Distribution Frames: 120 inches.

20 2. At Outlets - Copper: 12 inches. C. Copper Cabling: 1. Category 5e/6: Maintain cable geometry; do not untwist more than 1/2 inch from point of termination. 2. For 4-pair cables in conduit, do not exceed 25 pounds pull tension. 3. Copper Cabling Not in Conduit: Use only type CMP plenum-rated cable as specified. D. Fiber Optic Cabling: 1. Prepare for pulling by cutting outer jacket for 10 inches from end, leaving strength members exposed. Twist strength members together and attach to pulling eye. 2. Support vertical cable at intervals as recommended by manufacturer. E. Wall-Mounted Racks and Enclosures: 1. Install to plywood backboards only, unless otherwise indicated. 2. Mount so height of topmost panel does not exceed 78 inches above floor. F. Floor-Mounted Racks and Enclosures: Permanently anchor to floor in accordance with manufacturer's recommendations. G. Field-Installed Labels: Comply with TIA/EIA-606 using encoded identifiers. 1. Cables: Install color coded labels on both ends. 2. Outlets: Label each jack on its face plate as to its type and function, with a unique numerical identifier. 3. Patch Panels: Label each jack as to its type and function, with a unique numerical identifier. 4. Patch Cords: Label with jack identifier corresponding to initial installation FIELD QUALITY CONTROL A. Comply with inspection and testing requirements of specified installation standards. B. Visual Inspection: 1. Inspect cable jackets for certification markings. 2. Inspect cable terminations for color coded labels of proper type.

21 3. Inspect outlet plates and patch panels for complete labels. 4. Inspect patch cords for complete labels. C. Testing - Copper Cabling and Associated Equipment: 1. Test as required to support manufactures' system warranty 2. Test backbone cables after termination but before cross-connection. 3. Test backbone cables for DC loop resistance, shorts, opens, intermittent faults, and polarity between connectors and between conductors and shield, if cable has overall shield. 4. Category 3 Backbone: Perform attenuation test. 5. Category 5e/6 Links: Perform tests for wire map, length, attenuation, NEXT, and propagation delay. D. Testing - Fiber Optic Cabling: 1. Backbone: Perform optical fiber end-to-end attenuation test using an optical time domain reflectometer (OTDR) and manufacturer's recommended test procedures; perform verification acceptance tests and factory reel tests. 2. Multimode Backbone: Perform tests in accordance with TIA/EIA Method B. E. Final Testing: After all work is complete, including installation of telecommunications outlets, and telephone dial tone service is active, test each voice jack for dial tone. Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

22 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS INTERFACES RFP This is an RFP for Internal Connections (Interfaces) for Prairie-Hills Elementary School District 144. These interfaces will provide connectivity between network hardware and locations. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 2 Long wavelength SFP Fiber (single-mode) transceiver (example: Cisco GLC-LH-SM). 12 Short wavelength SFP Fiber transceiver (example: Cisco GLC-SX-MM). Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

23 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION NETWORK SWITCHES RFP This is an RFP for Internal Connections (Network Switches) for Prairie-Hills Elementary School District 144. These switches will provide connectivity for all district locations, including the new Prairie-Hills Junior High School. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: Network switches to be installed and utilized throughout the district including the new Prairie-Hills Junior High School. Here is the breakdown of the 149 units being requested: (2) Gigabit Core Switches (example: Cisco 6513). (60) 48-port Gigabit Switches (example: Cisco 3750). (21) 24-port Gigabit Switches (example: Cisco 3750). (64) 24-port Gigabit PoE Switches (example: Cisco 3750-E). (2) 8-port Gigabit Switches (example: Cisco WS-C3750G-12S-S). Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

24 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION RACKS RFP This is an RFP for Internal Connections (Racks) for Prairie-Hills Elementary School District 144. These racks will be installed in the main MDF at the new Prairie-Hills Junior High School and other locations throughout the district. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 8 total rack units to be used throughout the district including the new Prairie-Hills Junior High School. 44U, 4-post open frame rack units. An example would be the EIA-310-E, ROHS unit. Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

25 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION ROUTERS RFP This is an RFP for Internal Connections (Routers) for Prairie-Hills Elementary School District 144. These routers are to be installed and configured for the schools in the district including the new Prairie-Hills Junior High School, Markham Park, Highlands, Nob Hill, Fieldcrest, Chateaux, Mae Jemison, and Primary Academic Center. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 8 State-of-the-Art Routers with at least 2 Gigabit LAN ports to be used in all district buildings. There will be cross-communication between all of the units. An example of an applicable router would be the Cisco 3900 series. Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

26 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION SERVERS RFP This is an RFP for Internal Connections (Servers) for Prairie-Hills Elementary School District 144. These servers will be used for DNS, DHCP, , and Proxy services. In addition, switch servers are required for control and communication with existing as well as new servers. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 16 State-of-the-Art Servers with Dual-Processors, 8GB ECC RAM, RAID Controller, 3 or more SAS HDDs, 2 Gigabit LAN adapters (example: HP Proliant DL580 G7). 11 KVM switch with monitor (example: Belkin 19 Single Rail LCD Rack Console). Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

27 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION UNINTERRUPTABLE POWER SUPPLIES (UPS) RFP This is an RFP for Internal Connections (UPS) for Prairie-Hills Elementary School District 144. These UPS units will be utilized throughout the district in order to provide uninterruptable power to servers and network hardware. The units identified below are for the MDF and IDF rooms in the new Prairie-Hills Junior High School as well as existing locations. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 53 total UPS units to be configured and deployed throughout the district including the new Prairie-Hills Junior High School. The breakdown is as follows: (21) 3000VA 110V Rack Mount (example: APC SMART-UPS 3000VA RM 2U LCD 120V). (2) 1000VA 110V Rack Mount (example: APC SMART-UPS 1000VA USB & Serial RM 2U 120V). (27) 600VA 110V Rack Mount (example: APC SMART-UPS 750VA LCD RM 2U 120V) ( 2) VA 220V Rack Mount Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

28 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION VIDEO COMPONENTS AND VIDEO CONTENT STORAGE RFP This is an RFP for Internal Connections (Video Components and Video Content Storage) for Prairie-Hills Elementary School District 144. Both have been combined in this RFP to allow for a complete video distribution solution to the district. The required hardware will vary depending on the proposed solutions. REQUEST FOR PROPOSAL DESCRIPTION: Provide a for a video component/video content storage solutions using the following system requirements: IP Based System IPTV Digital TV Web-Based Central Management Console Content Neutral Content Storage and Cataloging Learning Standards Linked to Content Calendar Scheduling Video Content Creation Live Wireless Broadcasting Video on Demand, DVD Availability Reporting, Training Integrate with Existing Infrastructure for Video/Sound Desktop Video Conferencing, Bulletin Board Remote Control of Devices, Projector/DVD, Cameras, et cetera Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

29 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION VOIP RFP This is an RFP for Internal Connections (VoIP) for Prairie-Hills Elementary School District 144. The proposed solution should provide everything required for the VoIP system. The VoIP system will support the district including all schools as well as the district office. REQUEST FOR PROPOSAL DESCRIPTION: Provide a detailed solution and bid for the following: A hosted or hardware solution to provide VoIP services for the entire school district. Any solution needs to be able to utilize our interconnectivity between buildings (current service provided with AT&T OPT-E-MAN). While approximately 350 phones are currently being used, any solution should be able to accommodate an increase in phones. At this time, the district has 3 PRIs total. 2 PRIs are used for incoming and outgoing calls. 1 additional PRI is used for call forwarding. There are currently PoE connections wherever phones would be placed, the majority of those connections are on Cisco WS-CE500-24PC switches, but that may change. Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

30 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION WIRELESS ACCESS CONTROLLERS RFP This is an RFP for Internal Connections (Wireless Access Controllers) for Prairie-Hills Elementary School District 144. These wireless access controllers will need to be compatible to manage the existing Cisco Aironet 1250 units as well as new units proposed under the district s Wireless Access Points RFP. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 8 Wireless Access Controllers to manage access points at all district schools. As noted above, the controllers must be compatible with existing and future wireless access point hardware. Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

31 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION WIRELESS ACCESS POINTS RFP This is an RFP for Internal Connections (Wireless Access Points) for Prairie-Hills Elementary School District 144. These wireless access points will need to be controllable and work in conjunction with the existing Cisco Aironet 1250 units the district has. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 85 State-of-the-Art Wireless Access Points with Gigabit PoE LAN ports. 60 units will be configured and setup in the new Prairie-Hills Junior High School with the remaining being deployed throughout other schools in the district. An example would be the Cisco Aironet 3500 series of Wireless Access Points. Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

32 PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION BACKUP RFP This is an RFP for Internal Connections (Backup) for Prairie-Hills Elementary School District 144. This backup unit will be used to backup data from district servers. It will need to be accessible on the network and have the ability to perform data restoration. Provide a bid for the following hardware: REQUEST FOR PROPOSAL DESCRIPTION: 1 rack-mountable backup unit, at least 7TB in capacity with software for restoration of data. Prairie-Hills Elementary School District 144 reserves the right to accept or refuse any proposal based upon decisions that are in the best interest of the school district. Prairie-Hills Elementary School District 144 will utilize, but not be limited to, the following criteria in reviewing the bid submission: 1. Price 2. Overall responsiveness to the RFP 3. Vendor s experience and ability to perform 4. References

Tarleton State University. Specifications

Tarleton State University. Specifications Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication

More information

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6 Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12

More information

TIA/EIA 568A Sub-system HORIZONTAL CABLING

TIA/EIA 568A Sub-system HORIZONTAL CABLING TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

SECTION COMMUNICATIONS BACKBONE CABLING

SECTION COMMUNICATIONS BACKBONE CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED

More information

COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

Classroom WiFi Network Infrastructure Plan

Classroom WiFi Network Infrastructure Plan Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to

More information

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note

More information

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a

More information

Los Angeles Community College District Design Standards

Los Angeles Community College District Design Standards LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure

More information

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM 1993 SPECIFICATIONS CSJ 1685-05-068, ETC. & 1685-02-042 1.0 DESCRIPTION SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM THIS ITEM DESCRIBES THE OPERATION AND INSTALLATION OF AN ARTERIAL

More information

f) Telecommunications Equipment Rooms

f) Telecommunications Equipment Rooms SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

Communications. UNM IT/Telecommunications Guide Specification Communications

Communications. UNM IT/Telecommunications Guide Specification Communications The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

Division 27 Master Specification for

Division 27 Master Specification for Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor

More information

UNIVERSITY OF CALICUT (Purchase Division)

UNIVERSITY OF CALICUT (Purchase Division) No. 12831/PURCHASE-ASST-A1/2013/CU UNIVERSITY OF CALICUT (Purchase Division) Calicut University. P.O., Dated, 07.06.2013. TENDER NOTICE Sealed and competitive tenders are invited for the installation of

More information

Data Cabling / Low Voltage Technology Specifications

Data Cabling / Low Voltage Technology Specifications P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall

More information

Cisco ONS CL Shelf Assembly Hardware

Cisco ONS CL Shelf Assembly Hardware CHAPTER 1 This chapter provides a description of Cisco ONS 15310-CL shelf hardware. Instructions for installing equipment are provided in the Cisco ONS 15310-CL and Cisco ONS 15310-MA Procedure Guide.

More information

RCC45 ➁ Overview / /

RCC45 ➁ Overview / / RCC45 ➁ Overview 010.2936 More future and modularity Integration of POF and power Guaranteed modularity Long-term investment protection Flexible cabling solution Fast and convenient installation 1 010.2721

More information

Tender No: MUST/ 011/

Tender No: MUST/ 011/ MERU UNIVERSITY OF SCIENCE AND TECHNOLOGY NETWORK INFRASTRUCTURE ADDENDUM Tender No: MUST/ 0/207-208. SERVER ROOM The 30 kva UPS SOCOMEC and the 30 KVA AVR SOCOMEC makes should be provided. Concrete sealing

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Field-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red.

Field-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red. FM45 Connector Cat. 6 A IP20, 4P, TIA 568-A/B, 10x R815651 966704105 10 Stk. 090.7437 / ähnliche Abbildung Instruction manual Field-terminated connector with housing. Color housing: gray (RAL 7042). Color

More information

Plug & Play Universal Harness, SMF-28 Ultra Single-mode (OS2)

Plug & Play Universal Harness, SMF-28 Ultra Single-mode (OS2) Plug & Play Universal Systems Harnesses have a pinned (male) MTP connector on one end that connects to a Plug & Play Universal Systems trunk or extender trunk, while the other end is equipped with single

More information

Cabling Infrastructure

Cabling Infrastructure Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements

More information

3 Chapter Introduction. 3.2 Copper Cable

3 Chapter Introduction. 3.2 Copper Cable 3 Chapter 3 3.1 Introduction The Network Media is the device that physically carries the data from computer to computer. The three major types of network media are: Copper Cable Fiber-Optic Cable Wireless

More information

Design Guidelines for Facilities Construction:

Design Guidelines for Facilities Construction: Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,

More information

SPECIFICATION STANDARD

SPECIFICATION STANDARD PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and

More information

Termination for 568A and 568B pin configurations.

Termination for 568A and 568B pin configurations. 1 Termination for 568A and 568B pin configurations. The four twisted pairs in Unshielded Twisted Pair (UTP) cabling terminate in eight-pin modular jacks. There are two different pin configurations permitted

More information

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack PART 1 GENERAL 1.1 WORK INCLUDED Section 27 11 00 COMMUNICATION EQUIPMENT ROOM FITTINGS Section 27 11 23 Communications Cable Management and Ladder Rack A. Provide all labor, materials, and equipment for

More information

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist A. Targets Quantities meet DD9, applicable TC 5-, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC 5-,

More information

Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC.

Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC. Specifications for Modular Sound Shadow Sound Masking Sound Management Group, LLC. 1.01 General Requirements This section details general requirements for plenum sound masking installations. 1.1 Contract

More information

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA

Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA Panduit PreConfigured Industrial Distribution Frame (IDF) Installation Instructions Part Numbers ZDF48-RA and ZDF48-EA ZDF48-6RA and ZDF48-6EA Figure 1: Industrial Distribution Frame (IDF) Equipment Elevation

More information

Pretium EDGE HD Solutions A LANscape Pretium Solutions Product

Pretium EDGE HD Solutions A LANscape Pretium Solutions Product Pretium EDGE HD Solutions for Enterprise Data Centers and Storage Area Networks Corning Pretium EDGE HD solutions create a fiber optic tip-to-tip solution for data centers and storage area networks (SANs)

More information

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction

More information

ANSI/TIA-568-C Cat 6A Field Test Specifications

ANSI/TIA-568-C Cat 6A Field Test Specifications This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability

More information

Haworth Power Technical Sheets January 2018

Haworth Power Technical Sheets January 2018 Haworth Power Technical Sheets January 2018 Includes Accessories This page intentionally left blank. Table of Contents Desk Top Port Power Tap Cord Power Tap Conduit Enchanced Power Module Flip Top Unit

More information

Specifications PVS 200, PVS 300, PVS 400 Systems

Specifications PVS 200, PVS 300, PVS 400 Systems Specifications PVS 200, PVS 300, PVS 400 Systems Overall system UTP transmission... Optimal cable length is 50' - 75' (15 m - 23 m). Minimum = 15' (5 m) Maximum = 125' (38 m) NOTE: Distances were measured

More information

The 5500 Series from The Wiremold Company

The 5500 Series from The Wiremold Company 5500 Nonmetallic Raceway Multi-Channel Surface Nonmetallic Raceway Available Factory Prewired. The 5500 Series from The Wiremold Company provides wire and cable management for data, voice, video, and power

More information

Panduit Certified Installer. Fiber Certification Review

Panduit Certified Installer. Fiber Certification Review Panduit Certified Installer Fiber Certification Review 2 What does the cleave tool do? A. Breaks the glass cleanly B. Cuts the glass cleanly C. Scores the glass cleanly D. Shatters the glass cleanly Breaks

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before

More information

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside

More information

SECTION WIRING DEVICES

SECTION WIRING DEVICES SECTION 16141 WIRING DEVICES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation

More information

9/27/04 cci Cablecom Inc. 1

9/27/04 cci Cablecom Inc. 1 cci Cablecom Inc. 1 CCI Cablecom Inc. is a privately held, women owned corporation headquartered in Aurora, CO. We manufacture a variety of voice and datacom products. Cable applications Include: Local

More information

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120 DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified

More information

The six major components of a structured wiring system are:

The six major components of a structured wiring system are: OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.

More information

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE The Omega MPP enclosure is based on a 19" frame, with 4 empty module slots for MPP modules. Highly flexible : any mix between twisted pair and optical fiber modules.

More information

The 5400 Series Raceway from The Wiremold

The 5400 Series Raceway from The Wiremold 5400 Nonmetallic Raceway Nonmetallic Raceway with Twin Snap Cover System Available Factory Prewired The 5400 Series Raceway from The Wiremold Company provides wire and cable management for data, voice,

More information

Pretium EDGE Solutions Trunk Cable, 50 µm multimode (OM3)

Pretium EDGE Solutions Trunk Cable, 50 µm multimode (OM3) Pretium EDGE 133 Pretium EDGE Solutions Trunk Cable, 50 Pretium EDGE Solutions trunk cables utilize the MTP Connector, a 12 -fiber push/pull optical connector with a footprint similar to the SC simplex

More information

Addendum No. 1 January 7, 2015

Addendum No. 1 January 7, 2015 Addendum No. 1 January 7, 2015 DISTRICT-WIDE WIRELESS UPGRADE AND CABLING: INTERNAL CONNECTIONS E-RATE YEAR 18 - RFP NO. 14-15-103 Below is the list of questions received and clarifications. The color

More information

Total Amount Carried Forward To Bill summary Page

Total Amount Carried Forward To Bill summary Page BILL 1: GROUND FLOOR Supply, Deliver, Install, Set to Work and Commission the Following. 1.01 4 Pair, 24 AWG UTP cable, CAT 6, 305 metres per roll. As siemon or equal &approved equivalent 1.02 CAT 6 Face

More information

UNDERCARPET CABLING SYSTEM For Power and Communications

UNDERCARPET CABLING SYSTEM For Power and Communications UNDERCARPET CABLING SYSTEM For Power and Communications Linking Everything Together Power, Voice, and Data December 5, 2007 Undercarpet Cabling System Overview What is Undercarpet Cabling? Primary Applications

More information

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology

More information

Specifications PVS 200D and PVS 400D Digital Systems

Specifications PVS 200D and PVS 400D Digital Systems Specifications PVS 200D and PVS 400D Digital Systems Overall system STP transmission... Up to 150' (46 m) Standard included cable length is 35' (11 m) Shipping weight PVS 200D System... 53 lbs (24 kg)

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Voice Integration Overview

Voice Integration Overview Voice Integration Overview 010.2936 Intelligent voice integration Highest packing density Modular design Efficient and tool-free connection technique Comprehensive product range Ingenious labelling system

More information

SECTION PROJECTOR LIFTS AND MOUNTS. A. Refer to Section [ Submittal Procedures] [Insert section number and title].

SECTION PROJECTOR LIFTS AND MOUNTS. A. Refer to Section [ Submittal Procedures] [Insert section number and title]. (Specifier Note: The purpose of this guide specification is to assist the Specifier in correctly specifying AeroLift motorized projector lifts and their installation. The Specifier needs to edit these

More information

CONEC Industrial Ethernet Circular Sealed RJ45 Connector System consists of a RJ45 Plug Kit, a Receptacle Kit and a Protective Cover Assembly.

CONEC Industrial Ethernet Circular Sealed RJ45 Connector System consists of a RJ45 Plug Kit, a Receptacle Kit and a Protective Cover Assembly. Revised Sept-28-2009 Sealed Industrial Ethernet Circular IP67 Cat. 5e RJ45 Connector System Instructions CONEC Industrial Ethernet Circular Sealed RJ45 Connector System consists of a RJ45 Plug Kit, a Kit

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

Technology Standards

Technology Standards June 6, 211 Communications Infrastructure Cabling Services ITB Addenda #1 APPENDIX D, Revision 3.3, dated May 19, 26, is replaced in its entirety, with APPENDIX D, Revision 9, dated April 211, per the

More information

PHYSICAL INFRASTRUCTURE QUICK SKU FINDER

PHYSICAL INFRASTRUCTURE QUICK SKU FINDER PHYSICAL INFRASTRUCTURE QUICK FINDER Simplified Connectivity Simplified Connectivity combines our technical support services, products, and industry leading customer advocacy to create a comprehensive

More information

Family of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits

Family of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits SYSTIMAX Structured Cabling Systems Family of Cords Quality Stranded and Solid Cords That Connect Data and Voice Circuits Lucent Technologies Family of Stranded Cords includes 110 patch, modular and adapter

More information

UMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management

UMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management UMass Lowell October 1, 2011 Network and Voice Infrastructure Specifications Version 5.1 Prepared by Network Engineering and Network Project Management TABLE OF CONTENTS NETWORK AND VOICE INFRASTRUCTURE

More information

[0.057] 5.8 [0.23]

[0.057] 5.8 [0.23] Product Specification 7 March 13 Rev A1 SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used

More information

ANSI/TIA/EIA-568-B Cabling Standard NOTE

ANSI/TIA/EIA-568-B Cabling Standard NOTE 95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial

More information

SECTION WIRING DEVICES

SECTION WIRING DEVICES PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 1 1.4 REFERENCES... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 COORDINATION... 2 PART 2 - PRODUCTS... 2 2.1

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console 1993 Specifications CSJ 0598-01-057 1.0 Description SPECIAL SPECIFICATION ITEM 6398 Transportation Management Console This Item shall govern for the furnishing and installation of Transportation Management

More information

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled. 27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part

More information

Modular plugs, accessories and tooling

Modular plugs, accessories and tooling Modular plugs, accessories and tooling Introducing the new Cat 6A/6 modular plugs, slim-line boots and color clips CommScope modular plug portfolio CommScope offers a vast portfolio of Modular Plugs for

More information

InstaPATCH Cu Cabling Solutions for Data Centers

InstaPATCH Cu Cabling Solutions for Data Centers SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 InstaPATCH Cu Solution Specification 2 Harness Assembly Design 3

More information

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2 document Page 1 of 18 TECHKNOW, INC Kiosk Order Confirmation System INSTALLATION MANUAL Revision Date: July 11, 2012 Part # Version 3.2 Techknow, Inc. 393 Mayfield Road Duncan, SC 29334 www.gotechknow.com

More information

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide 2015 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T

More information

1/2 Introduction. SIMBOX LC 1/7 Introduction 1/8 Flush-mounting and surfacemounting. 1/9 Dimensional drawings

1/2 Introduction. SIMBOX LC 1/7 Introduction 1/8 Flush-mounting and surfacemounting. 1/9 Dimensional drawings Siemens AG 200 ALPHA SIMBOX Small Distribution Boards /2 Introduction /2 Introduction /3 Flush-mounting and hollow-wall distribution boards /4 Hood-type distribution boards /5 Accessories /6 Dimensional

More information

[0.057] 5.8 [0.23]

[0.057] 5.8 [0.23] Product Specification 7 June 13 Rev B SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used

More information

Cables and Connectors

Cables and Connectors Module 2 Cables and Connectors Twisted Pair Two wires that carry the data signals (one conductor carries a positive signal; one carries a negative signal). Two wires are twisted to reduce the effects of

More information

4188, 4288, 4288-S and 4688 Protected Entrance Terminals

4188, 4288, 4288-S and 4688 Protected Entrance Terminals 4188, 4288, 4288-S and 4688 Protected Entrance Terminals Instructions Underwriters Laboratories (UL) Listed January 1997 34-7041-3837-8 Revision A Contents: 1.0 General... 1 2.0 Accessories... 2 3.0 Protector

More information

Installing the Cisco 2524 and Cisco 2525 Routers

Installing the Cisco 2524 and Cisco 2525 Routers CHAPTER 3 Installing the Cisco 2524 and Cisco 2525 Routers This chapter guides you through the installation of the Cisco 2524 and Cisco 2525 routers and includes the following sections: Required Tools

More information

ALPHA SIMBOX Small Distribution Boards

ALPHA SIMBOX Small Distribution Boards ALPHA SIMBOX Small Distribution Boards /2 Introduction /3 Introduction /4 Flush-mounting and hollow-wall distribution boards /5 Surface-mounting and hood-type distribution boards /6 Accessories /7 Dimensional

More information

Contents. Structured Cabling Solutions. LAN Cables Patch Cords Connectors Patch Panels... 06

Contents. Structured Cabling Solutions. LAN Cables Patch Cords Connectors Patch Panels... 06 Contents Cat6 Structured Cabling Solutions U/UTP Cabling Solutions Structured Cabling Solutions LAN Cables... 03 Patch Cords... 04 Connectors... 05 Patch Panels... 06 U/FTP Cabling Solutions LAN Cables...

More information

Communication

Communication 27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and

More information

AT&T Switched Ethernet Service SM

AT&T Switched Ethernet Service SM Site Preparation Guide AT&T Switched Ethernet Service SM December 2016 2016 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered trademarks

More information

PANZONE ZONE CABLING SYSTEMS

PANZONE ZONE CABLING SYSTEMS PANZONE ZONE CABLING SYSTEMS PANDUIT provides a complete line of zone cabling products for open office architecture applications, telecommunication enclosures, data centers, wireless deployments and network

More information

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1993 Specifications CSJ s 0924-06-221,etc. & 0924-06-223 SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1. Description. This specification describes the minimum acceptable requirements for a weatherproof

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SNAP Compact Fiber Optic Patch Panel

SNAP Compact Fiber Optic Patch Panel SNAP Compact Fiber Optic Patch Panel Compact size perfect for limited space enclosures UL Listed 1863 Versatile surface or DIN-Rail mount capability Slide-hinged faceplate aids field termination Patch

More information

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide. .2 Loadcenters and Circuit Breakers Overview Product Selection Guide BR Loadcenters Description Service Single-phase, three-wire, 20/240 Vac Short-Circuit Current Rating 0 kaic: All single- and three-phase

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

*REQUIRED* 169 Main Street 700 Plaza Middlesex Middletown, CT T: F:

*REQUIRED* 169 Main Street 700 Plaza Middlesex Middletown, CT T: F: ADDENDUM COVER & RECEIPT CONFIRMATION SHEET 169 Main Street 700 Plaza Middlesex Middletown, CT 06457 T: 860-343-8297 F: 860-343-9504 www.wright-pierce.com DATE: 9/6/16 ADDENDUM CONSISTS OF (Including this

More information