1 SYSCO HOUSTON HOUSTON, TEXAS October, 2018 Infrared Inspection Report SYSCO Houston Inc Greens Crossing Blvd. Houston, Texas, Company Contact: Steve Moulder Project: CHARTER OAK DRIVE, LITTLE ROCK, AR PHONE: & FAX:

2 ORDER OF REPORT CONTENTS 1: Data To Facilitate Understanding & Utilizing Scan Report 2: Scan Results Overview & Action Taken Form 3: Identified Faulting Conditions, Information & Photographs 4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found DISCLAIMER This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not intended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility s condition, maintenance practices or correction of conditions indicated herein. By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, concerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.

3 Utilizing Report Contents Included in this report are Photographs and Thermographs of problem areas found during our recent Infrared Inspection of your facility. Each problem area picture is accompanied by: Date Location Information Temperature Calculations Color-coded Temperature Intensity and/or Condition Significance Data A Brief Comment Relating The Item In The Photograph To Its Corresponding Thermograph Suggested Corrective Recommendations. In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity. Thermal intensity is indicated by use of a color-coded data inserts that locate a fault s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows: INSERT Red Orange Yellow Green Temperature Range 70ºC/126ºF and higher above Ambient Operating Temp. 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp. 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp. *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp. ( * See page 4)

4 Determining Cost Effective Responses Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate. Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports. STANDARD ELECTRICAL FAULT FAILURE CURVE (Does Not Include Area In Blue) MINOR INTERMEDIATE SERIOUS CRITICAL DEVICE TEMP IS AMBIENT, BUT DEVICE IS EITHER FAULTY OR UNSAFE. 10ºC * 18ºF 25ºC 45ºF 40 C 72ºF 70 C 126ºF AMBIENT TEMP YEARS MONTHS MONTHS TO WEEKS WEEKS TO NOW FAULTY EQUIP Built In Trend Monitoring When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings. If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.

5 Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use Total Temperature: Total Temperature = Ambient Operating Temperature + Fault temperature Allows you, the customer, to evaluate possible damage to equipment. Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating. Contacts start to fail around 130ºC/266ºF Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes: Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet. If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault. Allows you, the customer, to determine if device will operate at intended amperage. Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine) If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip. 1. An intermittent high load. 2. A minor (Green) or intermediate (Yellow) fault. Report pages with photographs: PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph *AOT stands for Ambient Operating Temperature Both black & white and color infrared thermographs are presented to better depict the fault condition.

6 In addition to the corrective response time frame suggested below and the failure curve located on the previous page, you may want to consider using the military standard responses presented below. Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment: Temperatures rise above Ambient Operating Temperature: *10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label) 25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label) 40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected. (Orange Label) 70ºC/126ºF and above component failure imminent. Immediately inform the person responsible for continued operation of equipment. (Red Label) Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions. * Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind. Fault Correction Recommendation When Our Source Assessment Is Inaccurate: When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist. The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located. Example: If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp. in the lead holder lug.

7 SCAN RESULTS OVERVIEW PROMPT ATTENTION ITEMS: Because of: 1. The intensity or heat level indicated at the time of the scan. 2. Deterioration caused by excessive temperature not present at the time of the scan. 3. Physical condition irregularities observed at the time of the scan. We recommend that the following faults be given prompt attention: Faults: None Noted Items With Asterisks Have High Total or Ambient Operating Temperatures. United Spectrographics October, 2018

8 SUMMARY OF FINDINGS FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO. MINOR 0 0 INTERMEDIATE 1 1/72 SERIOUS 0 0 CRITICAL 0 0 SERIOUS 0 0 Number of items located at facility: 128 Number of faults: 1

9 ACTION TAKEN SYSCO Houston Houston, Texas October, 2018 Fault # Item # Category Repaired Monitor Date Name 1 72 Intermediate

10 PROJECT: CUST REP: SCAN REP: Daniel Clifton Hinze DATE: October 12, 2018 LOCATION: Maintenance Department 480/277 Volt Distribution Panel Labeled: HD2 Section 1 Left Side Breakers PH # 1 > ITEM: Breaker 41 SOURCE: TEMP: Line side buss stab contact area. Temp. of area indicating a faulting condition is: 60ºC / 140ºF Total Temp - 30ºC / 86ºF AOT = 30ºC / 54ºF above AOT. Note: Temp. may be higher as fault cannot be seen directly. TH # 1 > COMMENTS Abnormal heat is being generated in breaker component. See yellow arrows in PH#1 and TH#1. Loose and/or corroded contact area. Clean, inspect and re-secure. TH # 1 > TEMPERATURE ABOVE AOT 30 C / 54 F

11 AREA/EQUIPMENT LIST Following is a list of the electrical equipment located at the SYSCO Houston Inc, Houston, Texas,, facility and data relating to its operating condition at the time the scan was performed. NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection. No. Equipment Operating Visually Inspected EQUIPMENT LIST Fault # MAIN ELECTRICAL ROOM 1 ELA 208/120 Volt Distribution Panel X 2 EHA 208/120 Volt Distribution Panel X 3 Sq. D Motor Control X 4 LS 208/120 Volt Distribution Panel X 5 HS 480/277 Volt Distribution Panel X 6 HDF1 Sec 1 480/277 Volt Distribution Panel X 7 HDF1 Sec 2 480/277 Volt Distribution Panel X 8 HDF1 Sec 3 480/277 Volt Distribution Panel X 9 Overhead Transformer X 10 Overhead Transformer X 11 ATS-MSB2 Transfer Switch X 12 Mobile Generator Tap Box X 13 ASCO 480 Volt Switchgear Sec 1 Monitoring X 14 ASCO 480 Volt Switchgear Sec 2 52G2 Generator 1 Main X 15 ASCO 480 Volt Switchgear Sec 3 ATS-MSB1 Breaker X 16 ASCO 480 Volt Switchgear Sec 4 Fire Pump/ATS-MSB2 X 17 ASCO 480 Volt Switchgear Sec 5 ATS MSB1 X 18 Cutler Hammer Switchgear MSB1 (3 Sections) X 19 Cutler Hammer Switchgear MSB2 (3 Sections) X COMPRESSOR CONTROL ROOM 20 RMCC Control Cabinet (6 Doors) X 21 RMCC-2 Control Cabinet X

12 No. Equipment Operating Visually Inspected 22 SC-8 Control Cabinet X Fault # 23 Compressor 2 Control Cabinet X 24 Compressor 4 Control Cabinet X 25 Compressor 6 Control Cabinet X 26 Compressor 7 Control Cabinet X 27 Compressor 5 Control Cabinet X 28 Compressor 3 Control Cabinet X FIRE PUMP ROOM 29 Dry Air Pac Control Cabinet & Disconnect X 30 Fire Pump Control Cabinet X OUTSIDE 31 (2) Pole Mounted Fuse Disconnects X 32 (2) Pad Mounted Transformers (Fins Only) X ELECTRICAL ROOM 1035 (Break Room) 33 Unlabeled Cutler Hammer 480 Volt Switchboard X 34 HC 480/277 Volt Distribution Panel X 35 DPH1 Sec 1 480/277 Volt Distribution Panel X 36 DPH1 Sec 2 480/277 Volt Distribution Panel X KVA Transformer X 38 LC Sec 1 208/120 Volt Distribution Panel X 39 LC Sec 2 208/120 Volt Distribution Panel X 40 LC2 Sec 1 208/120 Volt Distribution Panel X 41 LC2 Sec 2 208/120 Volt Distribution Panel X 42 HD-1 480/277 Volt Distribution Panel X 43 HD-2 480/277 Volt Distribution Panel X 44 LD Sec 1 208/120 Volt Distribution Panel X 45 LD Sec 2 208/120 Volt Distribution Panel X 46 ELC 208/120 Volt Distribution Panel X

13 No. Equipment Operating Visually Inspected 47 EHC 208/120 Volt Distribution Panel X 48 EHD 480/277 Volt Distribution Panel X 49 EDPC 480/277 Volt Distribution Panel X 50 Overhead 30 KVA Transformer X 51 Overhead Transformer X 2ND FLOOR Office Electrical Room DPH2 Sec 1 480/277 Volt Distribution Panel X 53 DPH2 Sec 2 480/277 Volt Distribution Panel X 54 IGB Sec 1 208/120 Volt Distribution Panel X 55 IGB Sec 2 208/120 Volt Distribution Panel X 56 EHF 480/277 Volt Distribution Panel X 57 ELF 208/120 Volt Distribution Panel X KVA Transformer X 59 LF Sec 1 208/120 Volt Distribution Panel X 60 LF Sec 2 208/120 Volt Distribution Panel X 61 LF2 Sec 1 208/120 Volt Distribution Panel X 62 LF2 Sec 2 208/120 Volt Distribution Panel X 63 HF 480/277 Volt Distribution Panel X 64 (2) Overhead 45 KVA Transformer X Computer Room PDU1 Sec 1 208/120 Volt Distribution Panel X 66 PDU1 Sec 2 208/120 Volt Distribution Panel X 67 Liebert UPS (Out of Service) ELEVATOR ROOM Cab Light Disconnect X 69 Shunt Trip Breaker Disconnect X 70 Elevator Control Cabinet X MAINTENANCE DEPARTMENT 71 LD2 208/120 Volt Distribution Panel X Fault #

14 No. Equipment Operating Visually Inspected 72 HD2 Sec 1 480/277 Volt Distribution Panel X 1 73 HD2 Sec 2 480/277 Volt Distribution Panel X 74 Overhead 45 KVA Transformer X DRY DOCK 75 Mini Loader Control Cabinet (HK Systems) X 76 Eaton 30 KVA 3ø Transformer X 77 Unlabeled 208/120 Volt Distribution Panel X 78 Unlabeled 480/277 Volt Distribution Panel X ELECTRICAL ROOM Overhead 75 KVA Transformer X 80 LK-1 208/120 Volt Distribution Panel X 81 Unlabeled 208/120 Volt Distribution Panel X 82 HK 480 Volt Distribution Panel X 83 (Left) Unlabeled 208/120 Volt Distribution Panel X 84 (Right) Unlabeled 208/120 Volt Distribution Panel X 85 Cutler-Hammer KVA 3ø Transformer X 86 EF-2 Motor Control X 87 EF-1 Motor Control X COOLER DOCK 88 HK Systems Control Cabinet X 89 HB2 480/277 Volt Distribution Panel X 90 LB Sec 1 208/120 Volt Distribution Panel X 91 LB Sec 2 208/120 Volt Distribution Panel X kva Transformer X 93 HB Sec 1 480/277 Volt Distribution Panel X 94 HB Sec 2 480/277 Volt Distribution Panel X 95 HA Sec 1 480/277 Volt Distribution Panel X 96 HB Sec 2 480/277 Volt Distribution Panel X Fault #

15 No. Equipment Operating Visually Inspected 97 HA Sec 1 480/277 Volt Distribution Panel X 98 HA Sec 2 480/277 Volt Distribution Panel X 99 EHB 480/277 Volt Distribution Panel X BATTERY CHARGER AREA 100 LD4 208/120 Volt Distribution Panel X 101 HD4 Sec 1 480/277 Volt Distribution Panel X 102 HD4 Sec 2 480/277 Volt Distribution Panel X 103 HD3 480/277 Volt Distribution Panel X 104 Overhead 45 KVA Transformer X 105 BL 480/277 Volt Distribution Panel X TRANSPORTATION GARAGE 106 HVM1 Sec 1 480/277 Volt Distribution Panel X 107 HVM1 Sec 2 480/277 Volt Distribution Panel X 108 HVM2 480/277 Volt Distribution Panel X KVA Transformer X 110 LVM1 208/120 Volt Distribution Panel X 111 LVM2 208/120 Volt Distribution Panel X 112 Unlabeled Panel X ROOF 113 RTU 1 X 114 RTU 2 X 115 RTU 3 X 116 RTU 4 X 117 RTU 5 X 118 RTU 6 X 119 RTU 7 X 120 Kitchen Unit X 121 Penthouse Fan Disconnects X Cooling Tower Area 122 South Cooling Tower Disconnect X Fault #

16 No. Equipment Operating Visually Inspected 123 South Cooling Tower Water Pump Disconnect X Fault # 124 Center Cooling Tower Disconnect X 125 Center Tower Water Pump Disconnect X 126 North Cooling Tower Disconnect X 127 North Cooling Tower Water Pump Disconnect X 128 RTU 10 Control Cabinet X

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

(Project Name & Location)

(Project Name & Location) Accredited Thermographers 2014 Thermographic Inspection (Project Name & Location) Date: Issue: Ref: REPORT DETAILS Issued By: Thermographer: Thermal Imaging Services 8/139 Woolooware Rd Burraneer NSW 2230

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

1.0 Executive Summary

1.0 Executive Summary Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service

More information

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved

More information

2011 Thermographic Inspection ACME Industries Pacific Hwy, North Sydney Vol.6

2011 Thermographic Inspection ACME Industries Pacific Hwy, North Sydney Vol.6 Thermal Imaging Services 8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

MOBILE CONNECTOR - GEN 2 OWNER'S MANUAL

MOBILE CONNECTOR - GEN 2 OWNER'S MANUAL MOBILE CONNECTOR - GEN 2 OWNER'S MANUAL UNITED STATES Contents Safety Information... 2 Save These Important Safety Instructions... 2 Warnings...2 Cautions...3 General Information... 4 Mobile Connector

More information

Predictive Maintenance in a Mission Critical Environment

Predictive Maintenance in a Mission Critical Environment CSI 2130 Predictive Maintenance in a Mission Critical Environment This paper discusses the need to proactively protect mechanical and electrical support systems in data processing centers and data storage

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW) Product datasheet Characteristics ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/400...440V(7.5kW) Complementary Assembly style Function available Supply voltage limits Main Range of product

More information

Mitigating Arc Flash Hazards

Mitigating Arc Flash Hazards 1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash

More information

EHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ Phone: (609) Fax: (609)

EHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ Phone: (609) Fax: (609) EHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ 08691 Phone: (609) 259-4116 Fax: (609) 259-4119 6-Way RAMP Mobile Console Standard Features Are: 50/73/90 KVA Air Natural Transformer

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481200 VGD-100 Vari-Green Drive Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

TSC Schneider-PDI Agenda

TSC Schneider-PDI Agenda TSC Schneider-PDI Agenda General Electrical Power Layouts and Equipment Single Phase UPS s Three Phase UPS s Trends In Data Center Power Distribution Data Center Cooling Trends and Products Jim Tubbesing

More information

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:

More information

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Underground Warning Tape. 6. Lockout

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318 ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16

More information

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1

More information

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 574-294-2511 CANADA Dometic Corporation 46 Zatonski, Unit 3 Brantford, ON N3T 5L8 CANADA 519-720-9578 For Service Center

More information

Table of Contents List of Equipment General Information Safety Precautions Device Installation...

Table of Contents List of Equipment General Information Safety Precautions Device Installation... Table of Contents Table of Contents.... List of Equipment... 3. General Information... 4 3. Safety Precautions... 6 3. Device Installation... 7 6. Device Operation... 0 7. Statement of Limited Warranty...

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Delaware s Premier Suburban Office Park

Delaware s Premier Suburban Office Park IRON IRON HILL HILL CORPORATE CORPORATE CENTER CENTER Delaware s Premier Suburban Office Park WHITE WING 700 RED WING 750 BLUE WING 800 www.cbre.us/ironhill PROJECT SUMMARY White Wing Red Wing Blue Wing

More information

Delaware s Premier Suburban Office Park

Delaware s Premier Suburban Office Park IRON IRON HILL HILL CORPORATE CORPORATE CENTER CENTER Delaware s Premier Suburban Office Park WHITE WING 700 RED WING 750 www.cbre.us/ironhill PROJECT SUMMARY White Wing Red Wing Blue Wing Parking Garage

More information

Source-Transfer Application Guide

Source-Transfer Application Guide S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this

More information

Thermal Imaging Camera 220 x Instruction Manual

Thermal Imaging Camera 220 x Instruction Manual Thermal Imaging Camera 220 x 160 800201 Instruction Manual 1 TABLE OF CONTENTS INTRODUCTION... 3 FEATURES... 4 MATERIALS SUPPLIED... 4 FRONT PANEL DESCRIPTION... 5 LCD DISPLAY... 6 SET UP... 7 MEASUREMENT

More information

Panduit Basic Rack PDU

Panduit Basic Rack PDU Panduit Basic Rack PDU User Manual Release 1.0 Issue 1.0 Copyright 2014 Panduit Corp. All rights reserved. No part of this book shall be reproduced, stored in a retrieval system, or transmitted by any

More information

SUN2000P-375 W Smart PV Optimizer. User Manual. Issue 01. Date HUAWEI TECHNOLOGIES CO., LTD.

SUN2000P-375 W Smart PV Optimizer. User Manual. Issue 01. Date HUAWEI TECHNOLOGIES CO., LTD. Issue 01 Date 2017-08-01 HUAWEI TECHNOLOGIES CO., LTD. 2017. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of

More information

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions HP UPS R/T3000 ERM Installation Instructions Overview The ERM consists of two battery packs in a 2U chassis. The ERM connects directly to a UPS R/T3000 or to another ERM. Up to two ERM units can be connected.

More information

Operating instructions Evaluation system for flow sensors VS / / 2013

Operating instructions Evaluation system for flow sensors VS / / 2013 Operating instructions Evaluation system for flow sensors VS3000 7097 / 0 07 / 203 Contents Preliminary note...2 2 Safety instructions...3 3 Function and features... Mounting.... Mounting of the sensors...

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22D75S6U Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

Installation and Operation Manual SPC1

Installation and Operation Manual SPC1 Installation and Operation Manual SPC1 BIA-SPC1 rev 5 Page 1 TABLE OF CONTENTS Page QUICK GUIDE DRAINAGE PUMP FLOATS CONNECTED TO PANEL 4-5 QUICK GUIDE DRAINAGE PUMP FLOAT CONNECTED TO PUMP 6-7 QUICK GUIDE

More information

EHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ Phone: (609) Fax: (609)

EHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ Phone: (609) Fax: (609) EHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ 08691 Phone: (609) 259-4116 Fax: (609) 259-4119 6-Way Mobile Transformer Watlow AUTO Controllers Standard Features Are: 73KVA

More information

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22C17Q Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Pulse LED Instruction Guide

Pulse LED Instruction Guide PARTS LIST Light Fixture Aquarium Frame Mounts Instruction Guide WARNING: To guard against injury, basic precautions should be observed, including the following: A) READ AND FOLLOW ALL SAFETY INSTRUCTIONS.

More information

Equipment Operation & Maintenance

Equipment Operation & Maintenance Equipment Operation & Maintenance Many Facilities have: Very complex distribution systems. Many inter-locked backup power systems. Maintaining and troubleshooting the complex distribution system requires

More information

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only. Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 (440) 248-0400 Fax: (440) 248-6168 www.keithley.com Model 4200-RM Rack Mount Kit Packing List Introduction NOTE This 4200-RM Rack Mount

More information

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English Configurable Output Distribution 120V / 208V / 240V 60Hz User Manual English TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.......................... 1 GLOSSARY OF SYMBOLS....................................

More information

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN Deadbreak Apparatus Connectors MN650022EN COOPER POWER Effective March 2016 Supersedes S600-14-1 June 2010 SERIES 600 A U-OP visible break connector system operation instructions DISCLAIMER OF WARRANTIES

More information

Remote Control Thermal Imaging Camera System - 12V - Wireless or Wired Remote - 6" LCD Monitor

Remote Control Thermal Imaging Camera System - 12V - Wireless or Wired Remote - 6 LCD Monitor Remote Control Thermal Imaging Camera System - 12V - Wireless or Wired Remote - 6" LCD Monitor Part #: RCL-336 The Golight remote controlled thermal imaging infrared camera system with 6 inch LCD monitor

More information

TRENDS IN SWITCHGEAR SPECIFICATIONS

TRENDS IN SWITCHGEAR SPECIFICATIONS TRENDS IN SWITCHGEAR SPECIFICATIONS What changes are we seeing in equipment specifications? What s being discussed in client meetings? What s happening in the market to support these requests? EQUIPMENT

More information

AC4G-D User s Manual

AC4G-D User s Manual AC4G-D User s Manual Entire contents of this manual 2004 Active Cool Ltd. Ashkelon, Israel. Reproduction in whole or in part without permission is prohibited. Active Cool and AC4G-D are registered of Active

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Central Controller Operation & Installation Manual

Central Controller Operation & Installation Manual Central Controller Operation & Installation Manual YCZ-A004 CONTENT Function introduction of central controller... 1 Part info for central controller... 2 Page & Key Explanation... 4 Address Setting When

More information

MEGA DIAL PANEL Instructions

MEGA DIAL PANEL Instructions 2036 Fillmore Street Davenport, Ia. 52804 563-324-1046 www.racedigitaldelay.com MEGA DIAL PANEL Instructions WARRANTY AND DISCLAIMER DIGITAL DELAY ELECTRONICS INC. WARRANTS THE PRODUCTS IT MANUFACTURES

More information

QGV Units with G-120 Drives IMMEDIATE ACTION REQUIRED IMPORTANT PRODUCT SAFETY NOTICE

QGV Units with G-120 Drives IMMEDIATE ACTION REQUIRED IMPORTANT PRODUCT SAFETY NOTICE Service Alert Communications To: All Quincy Distributors From: Quincy Compressor Subject: Service Alert #389 Date: 02/01/2013 QGV Units with G-120 Drives IMMEDIATE ACTION REQUIRED IMPORTANT PRODUCT SAFETY

More information

ARCTIC AIR DC OLED. Digital Control Operations Manual

ARCTIC AIR DC OLED. Digital Control Operations Manual ARCTIC AIR DC OLED Digital Control Operations Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526 WWW.Microair.net Allentown NJ 08501 Fax (609) 259-6601 Before you start: 1. Applying power:

More information

EC Series. Safety Guide

EC Series. Safety Guide EC Series Safety Guide R5906018/02 01/07/2017 Barco Inc, Image Processing 3078 Prospect Park Drive, Rancho Cordova, CA, 95670, USA Phone: +1 916 859-2500 Fax: +1 916 859-2515 Support: www.barco.com/en/support

More information

Thermal cameras. Detect hot spots before they cause you trouble

Thermal cameras. Detect hot spots before they cause you trouble Thermal cameras Detect hot spots before they cause you trouble Thermal imaging Detect hot spots before they cause you trouble Using an SKF Thermal camera is a proactive way to help you detect problems

More information

SOLARIMMERSION IV Advanced Installation Manual v1.9

SOLARIMMERSION IV Advanced Installation Manual v1.9 SOLARIMMERSION IV Advanced Installation Manual v1.9 1 Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation

More information

Spring Test 5 due 4/26/2013

Spring Test 5 due 4/26/2013 Spring Test 5 due 4/26/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Where fixed multioutlet assemblies are employed, each feet or fraction thereof

More information

Power Quality of Commercial Buildings - Advanced

Power Quality of Commercial Buildings - Advanced Buildings - Advanced Hartford Steam Boiler One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: (800) 472-1866 www.munichre.com/hsb May 2017 Background Power quality is a general term used to describe

More information

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM Data Center Facility Analysis Project Final Presentation Wednesday, July 22, 2009 1:30 3:30 PM 1 Commonwealth Technology Center Conference Rooms 1 & 2 Enterprise Server Farm (ESF) Facility Data: 1 Technology

More information

5504 Thermocouple Analog Input Module

5504 Thermocouple Analog Input Module 550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime

More information

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN Padmounted switchgear MN285011EN Effective May 2017 Supersedes November 2004 (S285-10-4) Visible-Break switch accessory operation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

Operators Manual COFFEEPRO MOISTURE MAC PLUS Coffee & Cocoa M oisture Tester

Operators Manual COFFEEPRO MOISTURE MAC PLUS Coffee & Cocoa M oisture Tester Operators Manual COFFEEPRO MOISTURE MAC PLUS Coffee & Cocoa M oisture Tester Contents Page Components... 10-1 Error messages... 10-1 Operating conditions... 10-2 Screen and button Information... 10-3 Moisture

More information

Power System Vulnerabilities : AHCA 2016 Copyright (c) 2016 SSR, Inc. All rights reserved

Power System Vulnerabilities : AHCA 2016 Copyright (c) 2016 SSR, Inc. All rights reserved Training presentation for: AHCA Florida 2016 Annual Conference Finding & Managing Power System Vulnerabilities David Stymiest, CHFM, CHSP, FASHE, (PEin LA MS MA) Copyright 2016, Smith Seckman Reid, Inc.;

More information

CRITICAL INFRASTRUCTURE ASSESSMENTS

CRITICAL INFRASTRUCTURE ASSESSMENTS CRITICAL INFRASTRUCTURE ASSESSMENTS CRITICAL INFRASTRUCTURE ASSESSMENTS Critical Infrastructure Assessments Professional insight delivered by Vertiv experts will ensure that your infrastructure performs

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

DNG-200 LOW FOG GENERATOR USER MANUAL DNG-200 低煙機使用說明書

DNG-200 LOW FOG GENERATOR USER MANUAL DNG-200 低煙機使用說明書 DNG-200 LOW FOG GENERATOR USER MANUAL DNG-200 低煙機使用說明書 Read and save these insturctions 2008 Antari Lighting & Effects Ltd. User Manual Antari DNG-200 Low fog Generator Congratulations on the purchase

More information

Progressive Industries, Inc. EMS Electrical Management System

Progressive Industries, Inc. EMS Electrical Management System Progressive Industries, Inc. EMS Electrical Management System Complete Installation Guide and Operating Instructions for: Model EMS-LCHW50 Rated at 240V/50A Manufactured by: Progressive Industries, Inc.

More information

Series F75 Fail-Safe Module Installation, Operation and Maintenance Instructions

Series F75 Fail-Safe Module Installation, Operation and Maintenance Instructions WCAIM2029 (Part 16022) Series F75 Fail-Safe Module Installation, Operation and Maintenance Instructions CAUTION: Flowserve recommends that all products that must be stored prior to installation be stored

More information

Brasch Washdown Unit Heaters

Brasch Washdown Unit Heaters Brasch Washdown Unit Heaters Standard Features: Up to 48 KW Up to 400 Volts Disconnect switch with enclosure interlock Heavy-duty 304 stainless steel shroud Nema 4x non-metallic control panel 24-volt

More information

Converter SINAMICS G150. Type 6SL37102G

Converter SINAMICS G150. Type 6SL37102G Tests carried out on drives This documentation pertains to LV Umrichter E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Converter SINAMICS G150 Type 6SL37102G Edition 02/2019 www.siemens.com/drives

More information

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017 APPLICATION CONTROL GUIDELINES IntelliROL Power Supply PN 1176718 Revision Date: March 15, 2017 Table of Contents List of Tables...3 TGW Safety Recommendation...4 Warnings and Safety Instructions...5 Introduction...6

More information

ЗАО «БЕРГ АБ», (495) , Thermal cameras. Detect hot spots before they cause trouble

ЗАО «БЕРГ АБ», (495) ,  Thermal cameras. Detect hot spots before they cause trouble Thermal cameras Detect hot spots before they cause trouble Thermal imaging Detect hot spots before they cause trouble Since the dawn of the industrial age, temperature has been used to give an indication

More information

R-LB R-LX Series Installation, Operation & Maintenance Manual

R-LB R-LX Series Installation, Operation & Maintenance Manual Installation, Operation & Maintenance Manual WARNINGS Safety First Hazardous Voltage & Shock Hazard Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs

More information

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability 1910DB1207 By Hal Theobald, Product Marketing Manager, Schneider Electric Services Summary 1.0 Abstract...3 2.0 Introduction...3

More information

Power Quality of Commercial and Industrial Power Systems

Power Quality of Commercial and Industrial Power Systems Hanover Risk Solutions Power Quality of Commercial and Industrial Power Systems Power quality is a general term used to describe the quality of several different power-related characteristics. These characteristics

More information

MDM 011-Z1 Regen Resistor

MDM 011-Z1 Regen Resistor MDM 011-Z1 Regen Resistor Date of creation: 10.04.2017 Version date: 10.04.2017 Article number: 09-402-011-Z1-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

N+1 DC Power System with Battery Backup / Charging Function

N+1 DC Power System with Battery Backup / Charging Function MODULAR 24V DC POWER SUPPLY N+1 DC Power System with Battery Backup / Charging Function MODEL : SPS-2450B Please read this manual before operating your power supply. INSTALLATION & OPERATING MANUAL PROVIDES

More information

STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016

STATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016 STATE DATA CENTER DRAFT PROPOSAL 1 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles MEETING GOALS

More information

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET Description A Power Line Utilization Module (PLUM) is a device used to monitor the utilization and health parameters of

More information

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Regenerative Power Module And Common Bus RPM Panels Instruction Manual

Regenerative Power Module And Common Bus RPM Panels Instruction Manual Regenerative Power Module And Common Bus RPM Panels Instruction Manual Part Number September 2010 Copyright 2010 Magnetek Material Handling PRODUCT MANUAL SAFETY INFORMATION Magnetek, Inc. (Magnetek)

More information

Electrical Components and Equipment for General Use Self Inspection Checklist

Electrical Components and Equipment for General Use Self Inspection Checklist Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:

More information

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08

DNB Power and Control System Information and Interim Safety Procedures. Version draft 5/06/08 DNB Power and Control System Information and Interim Safety Procedures Version draft 5/06/08 DNB Power and Control System Information There are four sources of power for the DNB in the power supply and

More information

Sidewinder Pumps Inc. AC Timer/Controller

Sidewinder Pumps Inc. AC Timer/Controller Sidewinder Pumps Inc. AC Timer/Controller Page 1 of 12 Rev 032417 Table of Contents 1. Warnings-------------------------------------------------------------------------------------------------- 3 1.1.

More information

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22D47S6U Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina Progressive Industries Warranty Progressive warrants its products are free from defects in materials and workmanship for a period of three years. This is in lieu of all other warranties, obligations, or

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW) Characteristics soft starter-ats22-control 220V-power 230V(4kW)/400...440V(7.5kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component

More information

ADDENDUM NO. 1 ITB-DOT BAT. You are hereby notified that the above referenced Invitation to Bid (ITB) is modified as shown below:

ADDENDUM NO. 1 ITB-DOT BAT. You are hereby notified that the above referenced Invitation to Bid (ITB) is modified as shown below: ADDENDUM NO. 1 ITB-DOT-15-16-5002-BAT To: All Prospective Proposers From: Ashley Henning District Five Contractual Services Date: March 25, 2016 RE: ITB-DOT-15-16-5002-BAT ITS Battery Installation You

More information

SagFighter Active Voltage Conditioner / Sag Ride Through (SRT)

SagFighter Active Voltage Conditioner / Sag Ride Through (SRT) Utility Systems Technologies, Inc. P.O. Box 110 Latham, NY 12110 SagFighter Active Voltage Conditioner / Sag Ride Through (SRT) Overview The SagFighter is an industrial-grade, solid state, electronic voltage

More information

ASCO SERIES 300 Manual Transfer Switch Solutions

ASCO SERIES 300 Manual Transfer Switch Solutions ASCO SERIES 300 Manual Transfer Switch Solutions When power fails, businesses suffer. For some organizations, a permanent generator is too costly. Instead, permanent means for quickly connecting a portable

More information

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN Padmounted Switchgear MN285018EN Effective May 2017 Supersedes October 1994 (S285-80-1) COOPER POWER SERIES DC motor operator control installation and operation instructions DISCLAIMER OF WARRANTIES AND

More information

Infrared Thermal Imaging Camera

Infrared Thermal Imaging Camera The Electromagnetic Spectrum Gamma Rays X rays Ultraviolet (UV) Visible Light Infrared Microwaves Radio Waves UV Visible NIR SWIR MWIR LWIR 0.4µm 1.0µm 0.7µm 3.0µm 5.0µm 8.0µm 14.0µm Thermal Imaging Camera

More information

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC The PCI Series Phase Angle Fired SCR Power Controls 25-1200 AMPS 120-600 VAC Precise power control for complex SCR applications. ROBICON 1996 Distributed Worldwide by www.mcgoff-bethune.com Applications

More information

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel.

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel. LX Breaker Control Panels Installation and Setup Procedure Hubbell Building Automation, Inc. 9601 Dessau Road Building One Suite 100 Austin, Texas 78754 512-450-1100 512-450-1215 Fax www.hubbell-automation.com

More information

Thank you for your purchase of the Supa-Charger! Features Include:

Thank you for your purchase of the Supa-Charger! Features Include: Owner s Manual Thank you for your purchase of the Supa-Charger! The Supa-Charger is a High Performance Pedal Power Supply that will power any battery operated effect devices that require 9, 12 or 16 volts.

More information

ESV3000 ETDRS Illuminated Cabinet INSTRUCTION MANUAL

ESV3000 ETDRS Illuminated Cabinet INSTRUCTION MANUAL ESV000 ETDRS Illuminated Cabinet INSTRUCTION MANUAL ACTUAL SIZE LETTER FOOT METER SIZE 0 0 80 24 24M 6 50 40 2 25 20 16 19 15 12 9.5 7.5 6 4.8 Developed by Lea Hyvärinen, M.D. FOR TESTING AT FEET ( METERS)

More information

AIR COOLED MODULAR RECTIFIER

AIR COOLED MODULAR RECTIFIER CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:

More information