DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT
|
|
- Philip Newton
- 5 years ago
- Views:
Transcription
1 DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT
2 SCADA TO DG SITES
3 DIGESTER MW AND MVAR
4 INSTANTANEOUS READINGS FROM SEL 751 RELAY
5 TRASK SUBSTATION LOADING DO NOT WANT TO FEED INTO 115 KV
6 FAULT LOCATOR TOOL DEVELOPED BY GIS SPECIALIST
7 CAR HIT POLE EVENT ANALYSIS WILSON RIVER SUBSTATION EVENT ON
8 WILSON RIVER SUBSTATION, CIRCUIT 63 Misty Meadows Generation Olsen Rd. Recloser Car Pole Accident
9 SCADA ALARMS DURING EVENT NOTE: DEVICE TIMES ARE NOT SYNCHED Ckt 63 Recloser Locks Out Olsen Rd. Recloser Operations DG on adjacent circ Tripped Open
10 SOE FROM SUBSTATION RECLOSER
11 OLSEN RD. RECLOSER OPERATIONS
12 NEXUS 1500 METER ON SUBSTATION BUS
13 A PHASE CURRENT 2 OPERATIONS OF RECLOSER
14 3 RD INTERRUPTION MUCH HIGHER FAULT CURRENT
15 SEL 751 AT MISTY MEADOWS GENERATION 480 VOLT BUS
16 MAX FLT I = 3078 AMPS AT ACCIDENT SITE
17 SO HOW DID WE GET 4178 AMPS ON THE CIRCUIT 63 SEQUENCE OF EVENTS FILE?
18 SYNERGI PREDICTS A FAULT OF THIS MAGNITUDE SHOULD BE CLOSER IN TO THE SUBSTATION
19 THIS IS SECTION OF LINE THAT SYNERGI PREDICTED THE FAULT SHOULD BE IN
20 A SHARP EYED OPS SUPV. FOUND BURN MARKS IN THIS VICINITY. LONG SPANS DUE TO 115 KV UNDERBUILD
21 ELBOW FAILURE ON UG
22 SCADA ALARM AT 17:10 INDICATES FAULT ON NESTUCCA FEEDER 39
23 FIRST STEP IS TO CONNECT TO FORM 6 RELAY OVER ETHERNET SEQ COORD. MEANS ANOTHER DEVICE OPERATED
24 OSCILLOGRAPHIC FILE FROM THE FORM 6 RELAY PEAK CURRENT =1737 A 1737 X.707=1228 A RMS
25 FAULT LOCATION TOOL THAT GIS SPECIALIST MADE FLT I FROM SYNERGI PROTECTION STUDY
26 FAULT WAS ON SINGLE PHASE UG IN SUBDIVISION ELBOW FAILED
27 EXTENT OF FEEDER POSSIBLE LOCATIONS ON MULTIPLE BRANCHES
28 FIRST RAIN AFTER DRY SUMMER TILLAMOOK PEOPLE S UTILITY DISTRICT
29 FIRST INDICATION OF PROBLEM SCADA SHOWS FAULT ON CKT. 64
30 NEXUS 1500 ON SUB BUS
31 ZOOM IN ON PHASE A AND B CURRENTS
32 THE 3 PHASE CURRENTS ON CIRCUIT 64
33 COMPARE WAVEFORMS TO FORM 6 2 ND PHASE GETS INVOLVED
34 OUTAGE REPORT SHOWS INSULATOR FLASHED OVER
35 PROBLEMS AT TCCA BOILER TCCA=TILLAMOOK CHEESE FACTORY
36 FORM 6 OSCILLOGRAPH PEAK CURRENT = 3820 AMPS RMS CURRENT = 2700 AMPS
37 NEXUS 1500 ON SUB BUS
38 NEXUS FAULT CURRENT IS CLOSE TO FORM 6 VALUE = 3900A X.707=2757 A, NOTE DROP IN LOAD
39 FROM SYNERGI, FAULT CURRENT AT BOILER MATCHES MEASURED FAULT I
40 FAULT LOCATOR TOOL PRETTY CLOSE
41 TREE THROUGH LINE MOHLER CIRCUIT 91
42 RECLOSER AT SUB SHOWS 428 A FAULT CURRENT ON C PHASE
43 OSCILLOGRAPH FROM FORM 6 SHOWS FOUR CYCLES OF FAULT CURRENT 4 CYCLES =.066 SEC.
44 FAULT BLEW A 15 A FUSE AT FISH HATCHERY
45 TCC CURVE SHOWS THAT 15 A FUSE SHOULD BLOW IN.06 SEC. AT 425 AMPS
46 FAULT LOCATOR TOOL TURNED OUT TO BE FAIRLY ACCURATE Tree through Line Here Fuse Blew Here
47 SYNERGI PREDICTS 411 AMPS FAULT CURRENT AT THIS LOCATION
48 STARLING BRINGS DOWN BLUE HERON FAULT EVENT ON
49 TUESDAY MORNING AT 8:20 AM Public Relations called Operations to find out if a breaker operated at Wilson River Substation The Mill in town called to report a power dip SCADA showed that Circuit 61 had operated and Circuit 62 (Mill Feeder) saw current above Min Trip
50 ENGINEERING CONNECTED TO FORM 6 RECLOSER CONTROLS AT SUBSTATION VIA ETHERNET The Sequence of Events report from Ckt 61showed that the recloser tripped on Overcurrent, then reclosed and reset
51 ALSO DOWNLOADED OSCILLGRAPHY FILES FROM THE RECLOSERS Confirmed fault on Ckt 62
52 CONTINUATION OF WAVEFORM ON PRIOR SLIDE Note that second phase gets involved in fault in the last couple cycles before interruption
53 AFTER THE RECLOSER RECLOSED THE TRANSFORMER MAGNETIZING CURRENT WAS PRESENT After a few cycles, the magnetizing current decayed to below the minimum pickup value
54 NEXUS 1500 METER MONITORING THE TRANSFORMER BUS GIVES A BETTER PICTURE OF THE EVENT Note that 2 nd phase gets involved before breaker opens. And transformer inrush currents can be seen
55 ZOOMING IN TO PHASE B The recloser was open for 2010 ms (2 sec.)
56 PLUGGED FAULT CURRENTS INTO FAULT LOCATOR TOOL TO PREDICT LOCATION OF FAULT Area highlighted in red is most likely fault location
57 BLUE HERON RESTAURANT REPORTED HEARING A LOUD BANG DEAD STARLING WAS FOUND AT THE BASE OF A POLE NEAR THEM Blue Heron Dead Starling Predicted Fault Location
58 IT IS QUESTIONABLE THAT THE STARLING CAUSED THIS FAULT Usually takes a bigger bird to cause a phase-tophase fault Phase-to-phase fault current at location where starling was found did not match calculated fault current No burn marks from arcing were observed on the pole
59 A FAULT WAS SIMILAR TO THIS ONE AND NO CAUSE WAS FOUND (COMPARE TO SLIDE 36)
60 UG CABLE FAILURE LOCATION PREDICTION GOOD FLT I CONTRIBUTION FROM MILL MOTORS
61 SCADA ALARMS
62 INTERROGATE FEEDER BREAKERS Form 6 Recloser Controls did not show anything in Sequence of Events Files But they did capture Oscillographic waveforms The fault was on Circuit 63. The Form 6 on Ckt 63 showed two Oscillographic events First Event:
63 CIRCUIT 63 SECOND EVENT LINEMAN REFUSED THE RISER POLE
64 CIRCUIT 62 CONTRIBUTED FAULT CURRENT DUE TO LARGE MOTOR LOAD Note that current is going in the opposite direction as the current in Ckt 63
65 FROM PQ METER ON SUB BUS RMS VALUE OF FAULT CURRENT IS CLOSE TO WHAT THE FORM 6 SHOWS: 2165 A ON FORM 6, 2072 A ON NEXUS FAULT LASTED FOR 1.5 CYCLES =.0025 SEC
66 FAULT LOCATION PREDICTION NOT FAR OFF Fault on UG Cable
67 SYNERGI PROTECTION STUDY PREDICTS MAX SLG FAULT CURRENT TO BE 2292 A AT THIS LOCATION
68 30 A FUSE SHOULD BLOW IN.019 SEC. AT 2165 AMPS. 1.5 CYCLES =.025 SEC.
69 QUESTIONS? GAIL SHAW
WiAutoLink Frequently Asked Questions
Rev. 0 December 2014 Page 1 of 8 WiAutoLink Frequently Asked Questions December 2014 1 Rev. 0 December 2014 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the WiAutoLink Single Phase Electronic
More informationSmart Distribution Technology
Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications
More informationAdvanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Advanced Fuse-Saving Techniques T. ROUSAN Ameren Illinois USA J. JERMAKOWICZ S&C Electric
More information1. Coordination of series-rated devices is permitted where indicated on Drawings.
SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationImproving Fault Response with Real-time Fault Location Analysis through Combined Outage and Advanced Distribution Management
Improving Fault Response with Real-time Fault Location Analysis through Combined Outage and Advanced Distribution Management David Lyons Georgia Power Brad Williams Oracle Kevin Costin - Oracle Southern
More informationSacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,
Sacramento Municipal Utility District SMUD May 10, 2010 1 SMUD Facts and Figures 900 Sq. Miles Service Area 585,500 Customers 1.4 million Area Population 10 Bulk Substations 473 Miles of Transmission Lines
More information2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation
More informationSR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.
SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering
More informationASPEN Software - Introduction
ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical
More informationELG4125: System Protection
ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.
More informationSolid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3
www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated with
More informationUtility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations
Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations Michael. Duff City of College Station Payal Gupta, Dharmendra Prajapati, and Alex Langseth
More informationSECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY
SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices
More informationSmall Generator Interconnection System Impact Study Report. Completed For Q0047
Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection
More informationHigh-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY
S&C Remote Supervisory V ista Outdoor Distribution (15.5 kv through 38 kv) Electric utility customers are increasingly concerned about the frequency and duration of outages they are experiencing, and are
More informationCOOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN
Sectionalizers Catalog Data CA270001EN Supersedes 270-15 May 2014 COOPER POWER SERIES Types GN3E and GN3VE electronically controlled, manually closed sectionalizers Description A sectionalizer is an automatic
More informationProtection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW
SEL Distribution Substation Protection and Automation System Protection, Monitoring, and Control System for Distribution Substations Data Sheet SYSTEM ONE-LINE RELAY TARGETS ALARM HISTORY SYSTEM COMM.
More informationSpectra RMS Circuit Breakers with microentelliguard Trip Units
GE Energy Industrial Solutions Spectra RMS Circuit Breakers with microentelliguard Trip Units Greater system coordination, arc flash protection and reliability for new equipment and retrofit applications
More informationElectro Industries GaugeTech
Bakersfield Refining Company Ensures Productive Operations with Advanced Power Monitoring Bakersfield Refining Company is part of Equilon Enterprises LLC, a partnership between Shell and Texaco. Their
More informationRELT Reduced Energy Let Thru 2018
RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru Rick Schlobohm, P.E Senior Specification Engineer, There is an increasing concern in the electrical industry about arc flash energy levels
More informationLONG ISLAND POWER AUTHORITY INTERCONNECTION REQUIREMENTS FOR NEW DISTRIBUTED GENERATION GREATER THAN 300 KVA OPERATING IN PARALLEL WITH LIPA S RADIAL
LONG ISLAND POWER AUTHORITY INTERCONNECTION REQUIREMENTS FOR NEW DISTRIBUTED GENERATION GREATER THAN 300 KVA OPERATING IN PARALLEL WITH LIPA S RADIAL DISTRIBUTION SYSTEM Revised and Issued March 2003 I.
More informationENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.
ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser
More information1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output
More informationEnabling a Solid State Circuit Breaker
Enabling a Solid State Circuit Breaker USING SOLID-STATE CIRCUIT BREAKERS TO REVOLUTIONIZE POWER DISTRIBUTION Mike Harris Atom Power, Inc. Copyright 2019 Atom Power, Inc. All rights reserved. Enabling
More informationASPEN Software - Introduction
ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical
More informationDISTRIBUTION PROTECTION OVERVIEW
DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Mike Diedesch Avista Utilities Presented March th, 0 At the st Annual Hands-On Relay School Washington State University Pullman, Washington Table of Contents
More informationSACE Emax 2 Specification guide
SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or
More informationIED (Intelligent Electronic Device)
IED (Intelligent Electronic Device) Neopis IED (Intelligent Electronic Device) Intelligent Electronic Device Dynamic Characteristics PROMET 4300-F PROMET 4300-M Relay Type Setting Setting Range Setting
More informationENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1
ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated
More informationMiCOM P124 T&D. Self and Dual Powered Overcurrent Relays
PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can
More informationIdentify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements
Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence
More informationSolid Dielectric Switchgear Catalog S-trid13
Solid Dielectric Switchgear Providing load and fault interrupting switching for systems rated through 38kV, 800A continuous, 12.5 and 16kA symmetrical interrupting Vault or padmount designs Submersible
More informationSPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5
Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System
More informationElastimold Molded Vacuum Recloser - MVR
Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical
More informationMiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays
01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety
More informationBus Bar Protection Relay B-PRO 4000
Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation
More informationAwareness of the Situation
17/11/21 Situational Awareness UPDEA - Workshop Awareness of the Situation 25,623 Alarms in 8 ours 53 Alarms / min (average) 8% Are consequential Things 1 to keep in mind during a disturbance - Analog
More informationNU-LEC. Loop Automation. Reclosers & Sectionalizers
NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse
More informationTHE NEXT BIG THING IN DISTRIBUTION AUTOMATION
THE NEXT BIG THING IN DISTRIBUTION AUTOMATION Unrestricted Siemens Industry, Inc. 2017 usa.siemens.com/digitalgrid Siemens Distribution Feeder Automation (SDFA) Automatic Transfer Systems (ATS) Page 2
More informationCABLETROLL 3 CABLETROLL CABLETROLL CABLETROLL CABLETROLL LED-2 5 CABLETROLL CABLETROLL REMOTE INDICATION 7
CABLETROLL 3 CABLETROLL 2310 4 CABLETROLL 2320 4 CABLETROLL 2330 5 CABLETROLL 2350 5 LED-2 5 CABLETROLL 2410 6 CABLETROLL 2440 6 REMOTE INDICATION 7 The CableTroll indicators are fault current detectors
More informationUR Universal Relay Series
GE Digital Energy UR Universal Relay Series Revision 3.50 Release Notes GE ublication Number: GER-4432 Copyright 2009 GE Multilin Overview Summary GE Multilin issues the UR 3.50 release that introduces
More information.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical
Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of
More informationIMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS
IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS Armando Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA 99163 A reliable power system maintains frequency and voltage
More informationApplication Techniques CENTERLINE 2100 Motor Control Centers
POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product
More informationKarl Iliev, San Diego Gas & Electric Company
INTEGRATING DER THROUGH DISTRIBUTION SYNCROPHASORS Karl Iliev, San Diego Gas & Electric Company 2002 San Diego Gas and Electric Co. and Southern California Gas Company. All copyright and trademark rights
More informationMiCOM P521. Fast feeder differential protection
01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationFundamentals of Circuit Breaker Maintenance. AVO Training Institute, Inc. 2018
Fundamentals of Circuit Breaker Maintenance 1 AVO Training Institute, Inc. 2018 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation
More informationAuto-Sectionalizing Firmware Product Description, Information and Specification
g GE Energy Services Product Description, Information and Specification Document Number : PRPI-023 Version : 3.00 Revision : 2 Date : 03.02.10 Classification: GE Energy Services NOTICE OF COPYRIGHT & PROPRIETARY
More informationECNR/ECSR Class RK5 Dual-Element Time-Delay Fuses. Catalog Number ECNR (1-600A) 250Vac or Less Catalog Number ECSR (1-600A) 600Vac or Less
Catalog Number ECNR ( - 600A) 250Vac or Less Catalog Number ( - 600A) 600Vac or Less Amp Ratings ECNR 8 25 70 50 400 2 9 30 75 75 450 3 35 80 200 500 4 2 40 90 225 600 5 5 45 250 6 7.5 50 300 7 20 60 25
More informationUser Manual. AQ-F215 Simulator
User Manual AQ-F215 Simulator Instruction manual AQ-F215 Simulator 2 (28) Revision 1.00 Date 16.5.2014 Changes N/A Revision 1.01 Date 13.3.2018 Changes Updated visual look Readability improvements Instruction
More informationFree Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL
SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent
More informationMedium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks
66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks General NEPSI's activar, Medium
More informationSOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection
SOLKO-N (7S18) Feeder Differential Protection CLASSIFICATION OF UNIT TYPE POTECTION Summation Transformer, Circulating Current Protection B B 3 1 1 O O 3 1 1 SUMMATION TANSFOME SUMMATION TANSFOME O - Operating
More informationIssued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog
Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic
More information9926 Series Branch Rated Circuit Breakers AC Version
Branch Rated AC Version Hydraulic Magnetic Single pole and double pole versions 20/240 VAC, 50/60 Hz Up to 25A Just 3 mm wide Mounts on 35mm DIN-rail UL 489 listed, CSA C22.2 No. 5-02, CE VDE Ordering
More informationLightweight and flexible recloser control for single-phase applications
SEL-35S Kestrel Single-Phase ecloser Control Lightweight and flexible recloser control for single-phase applications Plug-and-work operation with popular single-phase reclosers simplifies new and retrofit
More informationSEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay
Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.
More informationRedundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc
Redundant Bus Protection Using High-Impedance Differential Relays Josh LaBlanc Purpose Discuss the configuration of the bus under study, and touch on the needs for redundant protection on the bus. Briefly
More informationRMS Product Presentation
RMS Product Presentation THE RELAY SPECIALISTS relay monitoring systems pty ltd www.rmpl.com.au Relay Monitoring Systems Pty Ltd 6 Anzed Court - Melbourne - Australia Manufacturing in Australia Company
More informationMiCOM P521. Fast Feeder Differential Protection
01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationSM100. On-Line Switchgear Condition Monitoring
On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring Introduction Weis is a specialist company with over 40 years of experience in the commissioning, testing & maintenance of
More informationBREAKER FAILURE PROTECTION
0 th Annual HANDS-ON RELAY SCHOOL March 11-15, 201 REAKER FAILURE PROTECTION brent.c@relayapplication.com OUTLINE Protection System Failures and reaker Failures Protection versus Relaying Relay Schemes
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationPower System Protection Training
Power System Protection Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Refresh your knowledge of
More informationHybrid STATCOM / SVC Workgroup 15 th May 2014
Hybrid STATCOM / SVC Workgroup 15 th May 2014 Place your chosen image here. The four corners must just cover the arrow tips. For covers, the three pictures should be the same size and in a straight line.
More informationS&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application
Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The
More informationwww. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES
Protective Relays Electrical Apparatus Capacitor Bank Protection Relay 165-440-900 Figure 1: Edison Idea Relay The capacitor bank protection relay is a member of Cooper Power Systems Edison Idea TM line
More informationWe will discuss two types of loss-of-potential (LOP) logic during this presentation:
1 We will discuss two types of loss-of-potential (LOP) logic during this presentation: Traditional LOP, which uses traditional voltage and current elements to detect an LOP condition. Advanced LOP, which
More informationMaximizing protection coordination with self-healing technology
Supersedes December 2011 Daniel P. Roth, Distribution Automation Technical Manager, Eaton s Cooper Power Systems Abstract Much of the Smart Grid initiative includes the installation of new recloser and
More informationMULTI 9 System Catalog UL Recognized C60N Supplementary Protectors
UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5
More informationISGS. Intelligent SwitchGear System The Flexible Solution
TM ISGS Intelligent SwitchGear System The Flexible Solution Multi-Function Flexibility At The Touch Of A Key Siemens introduces the ISGS Intelligent SwitchGear System a remarkable new development in switchgear
More informationBasic User and Installation Manual
HERON ELECTRIC COMPANY LTD Basic User and Installation Manual Mi-4 Mi-8 Mi-12 Mi-16 Mi-144 Multi -Wire Controller Doc ref. Mi Multi Wire Basic November 2008 TABLE OF CONTENTS 1. About This Controller...
More informationPG&E 500 kv Protection Standard Design and Development
PG&E 500 kv Protection Standard Design and Development Davis Erwin, Rafael Pineda, and Monica Anderson Pacific Gas and Electric Company Eric Udren Quanta Technology, LLC Jordan Bell and Neal Jones Schweitzer
More informationPrime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ).
S W I T C H G E A R Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ). Prime Engineering is a full service electrical engineering firm that specializes in medium and high voltage equipment
More informationCurrent Limiting Protector
CLiP Current Limiting Protector For systems rated 2.8-38kV, and continuous currents through 5000A Arc Flash and Arc Blast Reduction Network Protection SCADA Adaptable Indoor or Outdoor Application Professional
More informationBulletin 1489 Circuit Breakers. Selection Guide
Bulletin 1489 s Selection Guide Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options
More informationSource-Transfer Application Guide
S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this
More informationVIP 40/45 VIP 400/410
40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered
More informationThis webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB
This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,
More informationMicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Allis Chalmers Power Circuit Breakers
MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Allis Chalmers Power Circuit Breakers Easily replace electro-mechanical trip units with the latest electronic, digital trip unit technology Ensure
More informationSR750/760 Feeder Management Relay
G Digital nergy S750/760 Feeder Management elay Firmware Version 7.31 elease Notes G Publication Number: G-4364 Copyright 2010 G Multilin Summary Overview G Multilin issues the S750/760 Feeder Management
More informationA Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering
A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy Patrick Robinson Altelec Engineering Captured Arcing Fault Event Arc begins as phase A-C, 8ka peak, dies out then
More informationMG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD
United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL
More informationMEDIUM VOLTAGE FUSES. POWR-GARD Fuse Datasheet. 2,400-38,000 VAC Current-Limiting
MEDIUM VOLTAGE FUSES 2,400-38,000 VAC Current-Limiting Current-limiting E- and R-rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of
More informationAdvanced Protection and Control for a Power System Serving Industrial Customers
Advanced Protection and Control for a Power System Serving Industrial Customers Marco F. Jorge Iberdrola Energía Monterrey David Sánchez, Héctor J. Altuve, and Jorge L. Soto Schweitzer Engineering Laboratories,
More informationMONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES
MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity
More informationCommon Departures Interconnecting Facilities Requirements
Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low
More informationMaximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches
Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually
More informationBF
BE1-11i INTERTIE PROTECTION SYSTEM DEVICE FUNCTIONS The BE1-11i Intertie Protection System is a multifunction numeric relay providing the protection and control requirements outlined in IEEE 1547-2003
More information7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching
7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that
More information750/760 Feeder Management Relay Instruction Manual
GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario
More informationADDITIONAL INFORMATION MODBUS INSTRUCTION MANUAL. Request publication Request publication DNP 3.0 INSTRUCTION MANUAL
BE1-851E ENHANCED OVERCURRENT PROTECTION SYSTEM DEVICE FUNCTIONS 43 50 51 62 The BE1-851E is an enhanced overcurrent protection system based on the design of the BE1-851, a multifunction, numeric relay
More informationDNP Points List and Implementation
S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) DNP Points List and Implementation Table of Contents Section Page Section Page Introduction...1 Status Points...2
More information1 Description of Methodology for Volt / Var Optimization
Methodology for Volt / Var Optimization on a Substation Basis May 13th, 2011 Version 1.7 1 Methodology for Volt / Var Optimization (VVO) on a Substation Basis This use case discusses how the utility will
More informationNumerical Protective and Management Relays
Numerical Protective and Management Relays Presented at: The Institution of Engineers (India) Andaman and Nicobar State Centre Port Blair Dr. H. K. Verma Deputy Director and Professor of Electrical Engineering
More informationReclosers. Functional Specification Guide PS280026EN. Form 6 Rack/Yard-Mount Recloser Control
Reclosers Form 6 Rack/Yard-Mount Recloser Control Functional Specification Guide Functional specification for Form 6 rack/yard-mount recloser control 1. Scope 1.1. This specification describes the features
More informationC C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description
CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated
More informationMicrogrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids
Enrico Ragaini (ABB Low Voltage Products), Alexandre Oudalov (ABB Corporate Research), ISGT Europe 2012, Berlin Microgrids: Building Blocks of the Smart Grid Adaptive Protection Schemes for Microgrids
More informationSURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT
SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT ESTABLISHED SINCE 1985 Circuit Breaker Solid State Controls with RMS-2007AF LOGIC (All logics come with ARC FLASH as a standard) The SURE TRIP SOLID STATE
More informationSUB-CYCLE OVERCURRENT PROTECTION FOR SELF-CLEARING FAULTS DUE TO INSULATION BREAKDOWN INTRODUCTION
SUB-CYCLE OVERCURRENT PROTECTION FOR SELF-CLEARING FAULTS DUE TO INSULATION BREAKDOWN Ljubomir A. Kojovic Cooper Power Systems 11131 Adams Road PO Box 1 Franksville, WI 316-1 Charles W. Williams Jr. Florida
More information