ABB Network Partner. User s Manual SM/REx 500*2.0

Size: px
Start display at page:

Download "ABB Network Partner. User s Manual SM/REx 500*2.0"

Transcription

1 User s Manual SM/REx 500*2.0

2 This manual belongs to:

3 Contents Chapter Page About this manual 1 Introduction 3 Instructions 9 27 References 75 Customer feedback report 77 Software Registration Form 79 Index 81 1MRK UEN*2.0-00

4 1MRK UEN*2.0-00

5 About this manual This is a software manual for SM/REx 500 * 2.0 Document number: 1MRK UEN Version: 2.0 Revision: 00 Issue date: Data subject to change without notice We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted. This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify us as soon as possible. The data contained in this manual is intended solely for the product description and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards. As a result, it is possible that there may be some differences between the HW/ SW product and this information product. Author s address: ABB Network Partner AB S Västerås Tel: Fax: Internet: ABB Network Partner AB MRK UEN *

6 2 1MRK UEN *2.0-00

7 Introduction The chapter "Introduction" Introduction...5 Terminal parameter setting and supervision...6 1MRK UEN*

8 Introduction 4 1MRK UEN*2.0-00

9 Introduction Introduction Introduction Welcome to the SM/REx 500 version User s manual. SM/REx 500, version 2.0, is intended for parameter setting and supervision of the corresponding terminals: - REx 500 multi functional terminal - REL 501 line distance protection terminal - REL 511 line distance protection terminal - REL 521 line distance protection terminal - REL 531 line high speed distance protection terminal - REL 551 line differential protection terminal - REL 561 line differential and distance protection terminal - REB 551 breaker protection terminal - REC 561 control terminal version 2.0. The software runs on a PC system using the DOS operating system.! Note! The SM/REx 500, version 2.0 can not be used with previous versions than 2.0 of the terminals in the previous list. When REx 5xx terminal is mentioned in this User s manual, it is understood as the terminal type that were mentioned in the previous list. Once a terminal is installed, the user can change the text to the type of terminal, for example, after installing SM/REx 500, the text can be changed to REL 531, using the edit function. For more details, see Ref.2 in chapter 4: References. The SM/REx 500 software module is part of SMS 010, hereafter simply denoted SMS. The Station Monitoring System (SMS) consists of four functional parts: Parameter setting and supervision Disturbance recording evaluation Event handling Time synchronisation Before SM/REx 500 can be used, the platform program SMS-BASE must be installed on the PC system. 1MRK UEN*

10 Terminal parameter setting and supervision Introduction Introduction The SMS-BASE is the platform program always required to run SM/REx 500 and other SM/... software modules. When SM/REx 500 is installed, it will be integrated in the SMS-BASE software structure. The product can be considered as the library files required for SMS-BASE to communicate with REx 5xx. The REPORT program must also be installed if SMS is to be used for event and alarm handling of the REx 5xx terminal. To be able to make use of this document the user should be familiar with SMS-BASE. For more information regarding SMS-BASE functions, please refer to the SMS-BASE User s Guide (see Ref. 2 in chapter 4: References ). This software module is developed and manufactured by ABB Network Partner AB, Västerås, Sweden. 1 Terminal parameter setting and supervision Terminal parameter setting and supervision, sometimes also called protection/control monitoring, is a means for getting the same information on a PC as that available on the built-in HMI (Human-Machine-Interface) on the front of the terminal. In this case, even more information is available through the PC. This means that the SM/REx 500 program is a way to access information stored in the terminal that is not available on the built-in HMI of the terminal, e.g. time tagged disturbance reports and event functions settings. 1.1 Product overview The ABB Network Partner PANORAMA concept contains a full range of flexible and functional systems for monitoring, protection, and control of all parts in the power system. The terminals in the REx 5xx-series consist of several numerical highperformance terminals for medium and high voltage applications. Almost all information and settings available in the terminals can also be made available in a PC equipped with SMS programs. For the REx 5xx, the CAP 531 configuration tool is also required for configuration of the function blocks. Since SMS also supports communication via telephone modems this makes SMS a way to travel to the station by communication link, making physical presence in the station unnecessary. Besides the SM/REx 500 software module, there are other programs available for efficient use of the information stored in the terminals. 6 1MRK UEN*2.0-00

11 Terminal parameter setting and supervision Introduction Introduction SMS software available for REx 5xx terminal SMS-BASE - Platform program for all SMS applications. REPORT - Event and alarm handling program. The program is integrated with SMS-BASE. SM/REx 500- Software module for setting and monitoring of the REx 5xx terminal. The included FrontRECOM, which contains a part of RECOM, makes manual collection of disturbance recordings via the front port of the terminal possible. RECOM - Program for manual or automatic collection of disturbance recordings. REVAL - Program for manual evaluation of disturbances. 1MRK UEN*

12 Terminal parameter setting and supervision Introduction Introduction 8 1MRK UEN*2.0-00

13 Instructions The chapter "Instructions" Instructions...11 Installation...11 About the product...11 System requirements...12 At the REx 5xx terminal end:...12 At the PC end:...12 For communication via telephone modems:...13 The README file...13 Installation procedures...13 Installation of SMS-BASE...13 Installation of SM/REx The SMS directory structure...14 Installation of FrontRECOM...15 Installation procedures...15 Installation of REPORT...16 Communicating via the REx 5xx front port...17 Starting the SM/REx 500 program...17 Basic operation...18 Changing settings in a terminal...18 Presenting options...18 Read or Write multiple parameters to or from a terminal...19 Example of writing all settings to the terminal...20 Alternating between setting groups...21 Setting REx 5xx terminal time...22 Archive disturbance data...23 Using REPORT with SM/REx Configuration of Event and Alarm tables...24 Configuring logging tables MRK UEN*

14 10

15 Installation Instructions Instructions 1 Installation Before using SM/REx 500, the software must be installed on the local hard disk on a PC. 1.1 About the product SM/REx 500 is used for parameter setting and supervision of one of the corresponding REx 5xx terminals. It is delivered on two diskettes. One diskette contains the software module for SM/REx 500, which includes specific description files for communication with REx 5xx, and the second diskette contains FrontRECOM, for manual disturbance collection via the front port.! Note! The SM/REx 500 can only be used to communicate with the corresponding * 2.0 of REx 5xx terminals. Previous versions require SM-products corresponding to the terminal name, i.e. SM/REL 521 for terminal REL 521. The FrontRECOM program, however, can communicate with all existing REx 5xx terminals. The SM/REx 500 diskette contains the following files: INSTALL.EXE INSTALL.LAN PKUNZIP.EXE DEVICES MODULES MODULES.ZIP FUNCTION.ZIP README.TXT Installation program Language file for the installation Expansion software for MODULES.ZIP Additional file section to DEVICES already installed Empty file required by the installation program Compressed configuration files Compressed files for auxiliary functions Latest information The FrontRECOM diskette contains the following files: INSTALL.EXE FRONTINS.EXE README.TXT Installation program Compressed program files Latest information 1MRK UEN*

16 Installation Instructions Instructions 1.2 System requirements The following requirements must be fulfilled for the SM/REx 500 software module to operate (see also Ref. 2: SMS-BASE User's Guide in chapter 4: References ): At the REx 5xx terminal end: Alternative 1; Remote and/or local SPA-bus communication: Terminal REx 5xx with installed Remote communication SPA/IEC option. Optical fibre SPA-bus with opto/electrical converter.! Note! The settings for the SPA/IEC communication is made via local HMI. Alternative 2; Front communication: Terminal REx 5xx. Front connection cable for the REx 5xx-series. The software module SM/REx 500 enables the reading and setting of individual parameters, or switching between preset groups of parameters in one or several REx 5xx terminals. The authorization for remote setting are set on the local HMI of the terminal At the PC end: Computer; 100% IBM compatible PC Local disk space; 10 Mbyte + 8 Mbyte/terminal One serial port (RS232); COM1 or COM2 Parallel port; 1 port for the printer, LPT1, LPT2, or LPT3 Disk drive; 1 drive, 3.5 of type HD (1.44 Mbyte) Work memory; 500 kbyte unused Operating system; DOS 6.0 or higher Base program; SMS-BASE, version 2.1 or higher. If the REPORT program is used; version 2.0 or higher (used for event and alarm handling in SMS). If the RECOM program is used; version 1.4 or higher. A PC equipped with a 386 processor is sufficient for this type of SMS application. However, for better performance a more powerful PC is recommended. 12 1MRK UEN*2.0-00

17 Installation Instructions Instructions For communication via telephone modems: (see Ref 2. in chapter 4: References, SMS-BASE User s Guide, Appendix C) Public telephone network according to CCITT. Hayes compatible telephone modems that understand AT commands. For more details on building up the hardware, see Ref. 1 in chapter 4: References.). SMS communication with a REx 5xx terminal does not delay the protection/control function. The communication only affect the protection functions when new parameter settings are transmitted to the terminal. When new parameter settings (Settings, Configuration, Test, Event Masks) are downloaded, or when the active parameter setting group is changed, the terminal is blocked for typically 45 seconds. This will occur each time a data part containing settable parameters is transmitted to the terminal. 1.3 The README file The SM/REx 500 diskette and the FrontRECOM diskette both includes a README.TXT file. This file contains last minute news to be added to the User s manual, i.e. improvements made after the User s manual was printed. The README files are delivered in uncompressed format and should be read prior to installation. 1.4 Installation procedures Installation of the SM/REx 500 and the FrontRECOM programs is made by decompressing and copying files from the diskettes to the hard disk. This is normally designated C, but other disks can also be used. From here on, it is assumed that the installation procedure is carried out from disk drive A:. However, any other drive will of course be possible. In order to avoid problems, installation of the DOS-based programs is to be made directly in DOS, and not via MS Windows. It is also recommended not to have shell programs, like Norton Commander, active during the installation. When starting the SMS-BASE and SM/REx 500 for the first time after installation, follow the instructions in chapter Overview on page 29 and in chapter Handling SM/REx 500 on page Installation of SMS-BASE SMS-BASE must be installed on the PC before installation of SM/REx 500 can take place. SMS-BASE is delivered as a separate program and the installation is described in Ref Installation of SM/REx 500 Follow the steps described in the following to install from drive A to hard disk (C): 1MRK UEN*

18 Installation Instructions Instructions 1 Insert the SM/REx 500 diskette into drive A. Change the command line directory to drive A by typing a: and press <Enter>. 2 At the command line, type install and press <Enter>. Generally <F1> can be pressed in order to present a help text, and <Esc> to exit the installation procedure. The path of the SMS-BASE system is presented. This path can be edited. Note that the path is the location of the SMS-BASE system and not the position of the modules within the system. If the default path is to be used, press <Enter>. 3 Press <Enter> once more to confirm the path when the cursor is placed on Yes. The next screen displays the available unit on the diskette, i.e. REX500A V2.0. This unit is selected by pressing <Space> or <Enter> and is then marked with an X. Press <F2> to continue the installation procedure. 4 Press <Enter> once more to confirm the selected unit when the cursor is placed on Yes. 5 When the installation is completed (and the next diskette is to be asked for), press <Esc> to exit the installation procedure. The SM/REx 500 is now properly installed on the hard disk of the PC. If the default path is used, the hard disk should have the following directory structure after the installation: C:\SMS\BASE\ Home directory of the system SUPPORT\ Support programs for SMS MODULES\ Descriptions REX500A\ Description of the REx 5xx parts The SMS directory structure SM/REx 500 is a part of the SMS software structure. The SM/REx 500 module consists of a number of files and directories which are added to the SMS structure. The following file types are added into the directory C:\SMS\BASE\MODULES\REX500A: 14 1MRK UEN*2.0-00

19 Installation Instructions Instructions.SUP - Support files defining the programs to be called for a certain action..cnf - Configuration files defining all terminal parameters and data types..def - Initial values for terminal parameters..exe - General product support file..chn - Support file for the REPORT program..evn - Support file for the REPORT program..log - Support file for the REPORT program..sub - General product support file. 1.5 Installation of FrontRECOM A diskette called FrontRECOM is included in the SM/REx 500 package. It contains a part of RECOM, which enables manual collection of disturbance recordings via the front port of the terminal.! Note! FrontRECOM is to be installed before SM/REx 500 is used to add application elements in the SMS-BASE application structure.! Note! Installing FrontRECOM is only required if RECOM is not installed on the PC. If RECOM is to be installed on the PC, it must always be installed as the last diskette. This means that the installation must take place in the following order: 1 SM/REx FrontRECOM. Not necessary if RECOM is to be installed. 3 RECOM Installation procedures Follow the steps described in the following to install from drive A to hard disk (C): 1 Insert the FrontRECOM diskette into drive A. Change the command line directory to drive A by typing a: and press <Enter>. 1MRK UEN*

20 Installation Instructions Instructions 2 At the command line, type install and press <Enter>. If the SMS path is selected, C:\SMS is the default path. If another path is used, type install C:\realpath and press <Enter>. If a previous version of the FrontRECOM exists, the installation program will show the message An old installation of RECOM has been found on directory C:... and abort. To be able to install the new version of FrontRECOM, the previous version must be uninstalled. See below. The same is valid if RECOM is already installed on the PC. 3 Press <Any key> to confirm that the installation is to continue, or press <Ctrl> and <Break> to quit. 4 When the installation is completed, press <Any key> to continue. The temporary directory \recomtmp created during the installation, will now be deleted. FrontRECOM is now properly installed on the hard disk of the PC. Uninstallation of a previously installed version of the FrontRECOM program A previously installed version of the FrontRECOM program can be uninstalled using the uninstall command. All RECOM files are removed and the initialisation files in SMS-BASE are reset to original. To uninstall the program, do as follows: 1 Position to the RECOM directory by typing c: and press <Enter>, then type cd \sms\recom and press <Enter>. 2 Type uninstall and press <Enter>. The FrontRECOM program is now uninstalled.! Note! Follow the same procedure as described above if FrontRECOM version 1.4 is to be installed. This is also necessary if RECOM is to be installed on the PC. 1.6 Installation of REPORT The REPORT program is delivered as a separate program package with diskettes and a User s guide. For installation information, please refer to the REPORT User s Guide (Ref. 4). 16 1MRK UEN*2.0-00

21 Installation Instructions Instructions 1.7 Communicating via the REx 5xx front port The following steps must be followed to communicate via the front port of the REx 5xx terminal: 1 Connect a communication cable between the PC and the REx 5xx front port. 2 Start the PC. Now SMS-BASE can be started and run (see section 1.8 below), provided that the communication settings are correct. The settings for communication are made by selecting Alter application structure under the UTILITIES menu and then selecting Organisation, Station and Object. When the Object screen is shown, press C to open the screen for editing communication parameters. The important setting to check in this menu is Handshake, which has to be set to RTS-idle. This setting also works for remote communication with the terminal over modems via the rear ports. 3 Set the Baud rate for the front port communication correctly. Check the terminal baude rate setting using the local HMI, and set the PC to the same value. This setting is to be found under the local HMI menu: Configuration/SPA Comm/Front/... 4 Check that the Slave number is correct in all the data parts. Check the terminal slave number setting using the local HMI, and set the PC to the same value.this setting is also to be found under the local HMI menu: Configuration/SPA Comm/Front/... The list shown above is an example on how to set the communication parameters. All setting restrictions are set to OPEN on the front port, as described in chapter 3, paragraph Setting restrictions on page Starting the SM/REx 500 program SMS-BASE and SM/REx 500 is started from DOS in the following way: 1 Change the command line directory to C:\SMS\BASE by typing c: and then press <Enter>, type cd\sms\base and then press <Enter>. 2 Type smsbase and press <Enter> to start the program. 1MRK UEN*

22 Basic operation Instructions Instructions To start the SMS-BASE program from an MS Windows icon, please refer to paragraph Handling SMS under MS Windows on page 69.! Note! Once a terminal object is installed into the SMS-BASE application structure, the user may change the presented text. The type designation of the used control/protection terminal can be added. However, the module definition in the beginning of the text must not be changed. This part is used as reference by the SW Example: REX500A V2.0 C REL 511 Protection and Control terminal Bold: Not to be changed. Underlined:User defined text. For more details see Ref.2 in chapter 4: References. 2 Basic operation In this chapter the work flow for some typical tasks when using SM/REx 500, are described. 2.1 Changing settings in a terminal! Note! When changing parameter settings (Settings, Configuration, Test and Event Masks) or when changing active parameter setting group, the terminal will be blocked for typically 45 seconds Presenting options The terminals consist of many different functions, of which some are basic and some are options. After having installed a new REx 5xx terminal in the Application structure in SMS-BASE, it will be shown as if all options available for the terminal type are installed. But after having communicated with the terminal once (twice is needed in some cases), the screens will automatically be corrected to show only the functions that are currently installed. If you have prepared settings in advance, you must write them to the terminal first. 18 1MRK UEN*2.0-00

23 Basic operation Instructions Instructions Some parts of the SM/REx 500 only contain information belonging to one specific option. The first screen on such part will give information whether the option is installed or not. If not, it is recommended to remove the whole part, as described in paragraph Removing Parts of Unit from an installation on page 68, since it does not contain any relevant information Read or Write multiple parameters to or from a terminal All parameters for a Group (Disturbance Report, Service Report, Settings, Configuration and Event Masks) can be read or written to the terminal in one step. This will allow for monitoring or setting multiple parameters in several parts of SM/REx 500, by means of viewing and saving changes on the PC, instead of reading or writing data to or from the terminal each time a new part of SM/REx 500 is selected. This feature is especially valuable when setting a REx 5xx terminal for the first time, since the multiple write command will confirm to the user that all settings prepared in advance are downloaded to the terminal. 1MRK UEN*

24 Basic operation Instructions Instructions The multiple read or write function is available for: DRP--OVERReads all disturbance data (in parts DRP-INDC, DRP-EVEL, DRP-TRIP) from the terminal to the PC. SRV--ALL Reads all service values from the terminal to the PC. SET--ALL Reads or writes all settings from/to the terminal to/from the PC. CNF--ALL Reads or writes all configurations from/to the terminal to/from the PC. MSK--ALL Reads or writes all event masks from/to the terminal to/from the PC. Example of reading all settings from/to the terminal 1 Select the SET--ALL part under the group Settings. 2 Select Read ALL settings and press <Enter> The terminal data is now read to all SET-xxxx parts in the PC, in the same order as the parts are listed. The part currently executed is shown in the bottom left corner of the SMS-BASE screen. When the communication information box in the middle of the screen has disappeared and no current part is shown in the bottom left corner, all settings have been read and stored on the PC. All settings in each SET-xxxx part can be viewed by selecting Monitor PC-file information for each data part. 1 Select the SET-xxxx part containing the settings to be viewed. 2 Select Monitor PC-file information and press <Enter> Example of writing all settings to the terminal As the command Write ALL settings writes all settings from the PC to the terminal, all settings in each SET-xxxx part should first be changed to the desired value. If the settings stored in the terminal are to be modified, read first all settings to the PC as described in the previous section. 1 Select the SET-xxxx part containing the settings to be modified. Select Monitor PC-file information and press <Enter>. Change the settings, press <Esc> to leave the SET-xxxx part and press <Enter> twice to save the new settings. As all changes will be written to the terminal from the SET--ALL, it is not necessary to write the settings to the terminal, press <Esc> 20 1MRK UEN*2.0-00

25 Basic operation Instructions Instructions 2 Repeat the previous step for all SET-xxxx parts in which the settings should be modified. 3 Select the SET--ALL part. 4 Select the Write ALL settings You will now be asked if you want to write the selected group to the terminal. Press <Y> and then <Enter>. The PC-file information for all SET-xxxx parts is now written to the terminal in the same order as the parts are listed. The part currently executed is shown in the bottom left corner of the SMS-BASE screen. When the communication information box in the middle of the screen has disappeared and no current part is shown in the bottom left corner, all settings have been written to and stored in the terminal. The settings will be automatically read back to the PC for each SET-xxxx part, after the settings have been stored in the terminal. You can now verify the downloaded settings by selecting Monitoring PC-file information for each SET-xxxx part and check that the Present values stored in the terminal are the same as the New values that was entered in the PC.! Note! The write command that downloads ALL data parts is NOT password protected. Delete the xxx--all parts from the application structure if the ability to write ALL data parts without password is to be omitted. To uninstall the parts, see paragraph Removing Parts of Unit from an installation on page Alternating between setting groups 1 Select the SET-ACTI Change Active SetGroup part. 2 Select Read present group No. to PC-file to check which setting group is currently active. 3 Select Enter new group No. to monitor the active setting group and to enter the new one. On the top, the Remote change shows OPEN if change of active group is possible from SMS. 4 Select New group - Active setting group by pressing <Enter>, selecting the new group and the press <Enter> again. When the new group is entered, leave the editor with <Esc> and answer yes <Y> to the following questions by pressing <Enter> twice. 1MRK UEN*

26 Basic operation Instructions Instructions 5 Select Write new group No. to terminal and press <Enter>. 6 Enter the correct password and press <Enter>. 7 Press <Enter> again to proceed. When the active setting group is changed, the terminal will be blocked for typically 45 seconds. 2.3 Setting REx 5xx terminal time The terminal has an internal real time clock including full-time, i.e., date and time. The clock can be checked, and set from SM/REx 500 on a minute basis. The setting of the terminal time is not affected by the setting restrictions ( OPEN / BLOCKED ) in the terminal, i.e., it can always be changed. The format of the time is YY-MM-DD HH.MM:SS. Use the following work flow to check and, if necessary, set the REx 5xx terminal time: 1 Check and set the date and time of the PC (if necessary). 2 Read the internal time of the terminal by means of SET-TIME. Select Read terminal time to PC-file followed by Enter new time setting. 3 Compare the Terminal Time on screen 1 with the PC-file Time to check if the terminal time should be corrected. 4 Enter the full date and time. Add a few minutes to the time entry, e.g., if the time is when the string is entered, set the Terminal Time to When the new time is entered, leave the monitor mode immediately by pressing <Esc> and answer yes (Y) to the following questions by pressing <Enter> twice. 6 Select Write new time setting to terminal. 7 Enter the correct password and press <Enter>. Wait until Press <Enter> to leave the password function and to start the communication process. 9 Check the new REx 5xx terminal time by means of SET-TIME. Select Read terminal time to PC-file followed by Enter new time setting. Compare the read Terminal Time with the PC-file Time. For accurate setting of the terminal time it is recommended to utilise the local HMI, since the communication procedure in SMS makes accurate setting of the time difficult. 22 1MRK UEN*2.0-00

27 Basic operation Instructions Instructions! Note! It is only possible to change terminal time when no synchronisation source is configured. If a synchronisation source is configured, the time setting will be rejected by the REx 5xx terminal. 2.4 Archive disturbance data The easiest way to store disturbance data is to use the report facility and store the screens either on paper or in a text file. This facility is useful since only one disturbance at a time can be selected in the DRP-OVER part for detailed information in the other DRP-... parts. When storing information in a file the following procedure is to be followed: 1 Select one of the 10 disturbances in the DRP-OVER part for more detailed information. See also paragraph DRP-OVER Disturbance Overview on page Select, for example, the DRP-INDC part for information regarding the indications during the selected disturbance. 3 Select Read terminal data to PC-file and then Monitor PC-file information. 4 The selection F7 REPORT is given at the bottom of the screen. When pressing <F7> a selection list is presented as shown in the following figure. Fig. 1 Selection list obtained by pressing <F7>. 1MRK UEN*

28 Basic operation Instructions Instructions 5 Select Report all screens to file. All the information on the screens in the current Part of Unit will now be stored in a file given a name set by the date of the PC, and the extension SRP. 6 By selecting Start DOS-shell at file directory, the path to the directory where the file is stored is given. Information on the file can be accessed using, for example, the DOS-Edit editor, i.e. by typing edit _0.SRP at the DOS-prompt. For more information regarding these facilities, refer to the SMS-BASE User s Guide (see Ref. 2 in chapter 4: References ). 2.5 Using REPORT with SM/REx 500 The REPORT program is used for event, alarm and log reporting in the Station Monitoring System (SMS). The REPORT program is integrated with SMS-BASE and polls up to 16 defined stations in the application structure for events, alarms and log values. The result is presented to the user in form of logging files and screens. A complete REPORT system for an application comprises protection relays/terminals, a SRIO 500/1000 M or SACO 100M data communicator, a PC with SMS-BASE installed, REPORT and SM/... product/-s. REPORT communicates with the relays/terminals via the SRIO/SACO data communicator unit using the SACO 100M protocol. REPORT synchronises the operation of the entire system. To use REPORT for a REx 5xx terminal, the corresponding software module SM/REx 500 and SMS-BASE must be installed. SM/REx 500 contains the event, alarm and logging parameter tables for the REx 5xx terminal, necessary for handling REPORT data in the REPORT station. Only the parts that are specific for using SM/REx 500 together with REPORT is described in this User s manual. For installation, configuration and general use of the REPORT program, refer to Report User s Guide (see Ref. 4 in chapter 4: References) Configuration of Event and Alarm tables To configure the event, alarm and log handling for SM/REx 500, select Alter additional configurations in the UTILITIES menu. 24 1MRK UEN*2.0-00

29 Basic operation Instructions Instructions 1 Select Organization, Station, Object and then the Unit to configure. Press <Enter>. 2 Select Event/Alarm Tables, and press <Enter>.. Fig. 2 Selection of Event/Alarm Tables. 3 Select the first Part of Unit, TRM-OVER Terminal Overview, and press <Enter>. The following screen will appear: Fig. 3 Event/Alarm Tables for REx 5xx. The following events and alarms for the REx 5xx terminal can be configured in these 31 screens: Special SPA Events. All single events and double indications for Event Functions (i.e. Event Functions cannot be used together with the REPORT program). The settings in the event/alarm parameter table determine which events should be reported, which events that are defined as alarms, if audible alarms should be given and if SACO annunciators should be reset. Also event/alarm texts and the channel description can be edited. 1MRK UEN*

30 Basic operation Instructions Instructions Please refer to the REPORT User s Guide (see Ref. 4 in chapter 4: References ) for further information Configuring logging tables To configure the logging handling, enter the Logging Tables for the selected unit. Fig. 4 Selection of Logging Tables. 1 Select the first Part of Unit, TRM-OVER Terminal Overview, and press <Enter>. The following screen will appear: Fig. 5 Logging Tables. The following logging values for the REx 5xx terminal can be selected to be logged on these 6 screens. (Note that the logging parameter description cannot be edited.) SPABUS slave type and number. Primary mean values. Analog input phasors. Synchrocheck values. ma input values. Please refer to the REPORT User s Guide (see Ref. 4 in chapter 4: References ) for further information. 26 1MRK UEN*2.0-00

31 The chapter "" Extensive operation...29 Overview...29 Navigating through the SMS structure...30 Changing application structure...30 Altering application structure...30 Handling SM/REx Setting restrictions...30 Password handling...31 Configuring functions and logical elements...32 Parts of Unit in SM/REx Terminal Overview...33 Disturbance Report...33 Service Report...34 Settings...36 Terminal Report...39 Configuration...40 Test...41 Event Masks...41 General Display Layout...42 Screen layout for settable quantities...42 Contents Screens...43 Other examples...45 Terminal Overview...46 TRM-OVER...46 DRP-OVER Disturbance Overview...50 DRP-INDC Indications...55 DRP-EVEL 150 Events List...56 DRP-TRIP Trip values...58 DRP-CLRS Clears and Manual trig...61 RECOM REX5XXV1 Unit disturbance summary...62 Appendix...68 Diagnosing errors...68 Error messages during communication...68 Adopting PC to SMS programs...68 Removing Parts of Unit from an installation...68 Handling SMS under MS Windows...69 Error Messages...70 List of References MRK UEN*

32 28 1MRK UEN*2.0-00

33 Extensive operation 1 Extensive operation This chapter describes SM/REx 500 functions. The menus in the SM/REx 500 program are presented with explanations of the contents and how to use them. 1.1 Overview The following flow of activities is typical when using SM/REx 500: The user: Creates and maintains an application structure. Establish communication via telephone modems or direct connection. Selects from the application structure the terminal to work with. Orders data to be sent from the terminal to the PC, by selecting Read terminal data to PC-file. Observes the presented data by selecting Monitor PC-file information. Reads the information sent from the terminal. Orders new data to be sent from the PC to the terminal by selecting Write PCfile settings to terminal. A write procedure is automatically followed by a verification procedure, to ensure that the settings are changed correctly. The SMS-BASE program is a standard application run in DOS, consisting of the following parts: 1 Function keys: <Esc> EXIT from current menu. <F7> REPORT generation, i.e., printing of screens. <F8> Start DOS window. <PgDn> Display NEXT screen. <PgUp> Display PREVIOUS screen. <Enter> CHANGE value. 2 Menu items: The menus offer a number of functions which are explained in the SMS-BASE User s Guide (see Ref. 2 in chapter 4: References). When a terminal is selected on the unit level, a list of functional groups is shown. Each group contains the different parts of the terminal. The user selects a group by pressing <Enter>. The parts within the group are then shown. The user can select any of the parts by pressing <Enter>, and perform actions to display or modify information related to the selected part. The user can: 1MRK UEN*

34 Extensive operation Read settings and information from the terminal. Monitor settings and information stored in the PC. Write settings to the terminal. Generate and print reports. When data is written to the terminal, a password has to be entered by the user. The password check assumes one password common to all the units in one station. Communication to the terminals is performed through the SPA-bus protocol Navigating through the SMS structure The SELECT menu includes the application structure, either built with the Alter application structure function, or installed from a diskette. The application structure fulfils its task by means of mapping the real world hierarchy of Organization, Station, Object, Unit, Groups and Part of Unit into the directory structure. The user navigates through the structure using the <Arrow>, <Home>, <End>, <PgUp>, and <PgDn> keys. Press <Enter> to select an item in the structure. Press <Esc> to return from a selected item in the structure Changing application structure To change the application structure, select the Application structure path function in the SETUP menu. The path to the application structure is by default C:\SMS\DATA-EX Altering application structure To work with the application structure, select the Alter application structure function in the UTILITIES menu. A new application structure must be built when SMS-BASE is started for the first time, 1.2 Handling SM/REx 500 In this section the general handling of SM/REx 500 is described Setting restrictions Remote setting restrictions can be set on the REx 5xx local HMI, which disables the possibility to set parameters in the REx 5xx terminal from SMS. However, parameters and information can always be read. 30 1MRK UEN*2.0-00

35 Extensive operation The access rights have the following alternatives: Access rights on remote communication ports (rear) Switching between setting groups Setting of individual parameters Open or Blocked Setting made under Configuration/SPA/IEC Comm/Rear menu node Open or Blocked Setting made under Configuration/ SPAComm/Rear menu node The setting of the access rights can only be done via the local HMI. For communication on the front port of the terminal, no setting restrictions exist. For instructions on how to communicate via the front port, see paragraph Communicating via the REx 5xx front port on page 17. Access rights on front communication port Switching between setting groups Setting of individual parameters Open Open Password handling A password must be entered as an introduction to each activity that can change the settings of the protection terminal. The password is the same for all terminals in one station. This means that if the password is changed during communication with one terminal, the new password is valid for all terminals in that station. Remote setting activities are allowed according to the setting restrictions set via the local HMI on the REx 5xx terminal. The default password for a new station is 000.! Note! The SET--ALL, CNF--ALL and MSK--ALL parts have no password handling. This means that these parts can write data to the terminal without entering any password. To inhibit this function, the SET--ALL, CNF-ALL and MSK--ALL parts should be removed from the structure as described in paragraph Removing Parts of Unit from an installation on page 68 1MRK UEN*

36 Extensive operation Configuring functions and logical elements The terminal configuration of all application functions and logical elements is performed using the CAP 531 Configuration Tool (CAP/REx 500). No configuration of the application functions and logical elements is available in the SM/REx Parts of Unit in SM/REx 500 In this section an overview of all SM/REx 500 parts is given. Some data parts are described more thoroughly in the following chapters. Prior to the first communication session with the terminal, the information is presented as if all options were installed. The reason is that it must be possible to prepare all settings in advance. But after having communicated once with the terminal, the data entry fields belonging to options not installed will disappear. In the table below all parts of unit in SM/REx 500 are listed. For each data part a description together with the screen contents is presented. References: Technical reference manual for corresponding terminal REx 5xx * MRK UEN*2.0-00

37 Extensive operation Terminal Overview This section contains basic information on the terminal. It gives the same overview of the terminal front panel as a visitor gets when visiting the station. Screen contents Description TRM-OVER Terminal overview - HMI LEDs, Module This part gives the same overview of the terminal front panel that a visitor would have when visiting the station. Analogue Inputs, Communication Function Selectors See chapter Terminal Overview on page 46 in the chapter Disturbance Report The disturbance report menu gives the user all information recorded by the terminal for the last ten disturbances since the last clearing of the disturbance recorder memory. Screen contents DRP-OVER Disturbance overview Reporting Conditions DRP-INDC Indications Description This part contains information about the last 10 disturbances stored in the terminal. See paragraph DRP-OVER Disturbance Overview on page 50 in the chapter. Indications that appeared during the recorded disturbances, for each disturbance record separately. Indications recorded by the disturbance reporting unit are selectable during the configuration procedure. See paragraph DRP-INDC Indications on page 55 in the chapter for detailed information. DRP-EVEL 150 Event list Event DRP-TRIP Trip values Distance to fault Contains information on events during the disturbance selected in DRP-OVER. See paragraph DRP-EVEL 150 Events List on page 56 in the chapter for detailed information. The user gets information on the distance to the fault together with the fault loop that was used for calculation. Trip values are presented as phasors, value and phase angle of the currents and voltages, before and during the fault. See DRP-TRIP Trip values on page 58 in the chapter for detailed information. 1MRK UEN*

38 Extensive operation DRP-CLRS Clears and Manual trig RECOM REX5XXV1 Unit disturbance summary Manual triggering of a disturbance report is possible in this data part. Clears all the disturbances in the terminal and LEDs. See paragraph DRP-CLRS Clears and Manual trig on page 61 in the chapter for detailed information. This program makes it possible to collect the disturbance recordings stored in the terminal, to the PC. Contains the disturbance date and sequence number, the triggering signal, and if it is stored in the PC, or only in the terminal. See paragraph RECOM REx5xxV1 Unit disturbance summary on page 62 in chapter for detailed information Service Report Information on the operating conditions in question, for protected objects in the power system, as well as information on the terminal itself is available in this data part. All the service values are the currently measured values in the protection terminal at the time of communication with the terminal. Screen contents SRV--ALL Read ALL Service Values Upload routine. SRV-ALOG Primary values Synchrocheck values Secondary values Impedance values Directions Diff Values Diff Communication Analogue Inputs Trig Status Autorecloser Counters Description This part allows reading of all service reports data sequentially from the terminal. This does not include the SRV-CLRS part. Contains the service values for the analogue inputs and protection functions. All signals that are active will be marked with a square. Only the functions installed in the terminal will be shown. 34 1MRK UEN*2.0-00

39 Extensive operation SRV-CLRS Clear Counters SRV-FUN1 Additional Functions In this data part it is possible to clear the Autorecloser Counters presented in the SRV-ALOG part. Contains the service values for the logical signals and protection functions. All signals that are active will be marked with a square. Only the functions installed in the terminal will be shown. Additional Functions: - Internal Signals - Active Group - IO Error - Time - Test - MIM Error - Differential - Instant. over current - Time delayed ovecurrent- Breaker failure - Fuse failure - Broken conductor - Stub - Time delayed undervolt. - Time delayed overvolt. - Trip - Current transf. circuit supervision - Over load - Dead line detection - Loss off voltage - Earth fault 4-step - Earth fault comm. - Earth fault ComIRevWei - Time Delayed Earth fault SRV-FUN2 Impedance Contains the service values for the logical signals and protection functions. All signals that are active will be marked with a square. Only the functions installed in the terminal will be shown. SRV-FUN3 Synchrocheck 1..4 Autorecloser 1..6 Contains the service values for the logical signals and protection functions. All signals that are active will be marked with a square. Only the functions installed in the terminal will be shown. SRV--LOG Logical Gate Outputs Contains the service values for the logical elements. All signals that are active will be marked with a square. Only the functions installed in the terminal will be shown. SRV-MIMV ma Input Values SRV-IOnn (1..13) IOnn Binary Inputs and Outputs Contains the service values for the ma Input Module installed in the terminal. If the module is not installed, the fields for the module will be empty. For each module the slot position for where the module is installed is shown. This part contains the service values for the input and output signals of the I/O modules, maximum 13 modules, including MIM. The modules must be first installed in the terminal. 1MRK UEN*

40 Extensive operation SRV--RTC I/O Remote Terminal Communication Contains the service values for the input and output signals of the remote terminal communication Settings This data part is for the setting of different parameters within the built-in protection and automation functions, as well as for those in the disturbance reporting unit.! Note! If remote change of settings is blocked in the terminal, it will not be possible to change any parameter from SMS, even if new settings are sent to the terminal. The terminal will not accept them. Screen contents SET--ALL Write-Read ALL Settings SET-ACTI Change Active Set- Group SET-COPY Copy setting groups Description This part allows reading or writing of all settings to or from the terminal. The Read ALL settings and Write ALL settings do not include the SET-ACTI and SET-TIME parts. The Active Setting Group shows which setting group is currently active in the terminal and when it was activated. An identification string for each of the 4 setting groups is shown along with the data when the setting group was stored in the terminal. The identification string is set in SET-GRnA Screen 1. If a new string is set in SET-GRnA, it cannot be read in the SET-ACTI until it is transmitted to the terminal and read back with SET-ACTI. Copies all the defined settings from one group to the other. When several data parts exist for each setting group, all will be copied. This process does not include communication with the terminal, which means that to save these settings in the terminal, a write operation has to be performed. This can be done from the SET--ALL data part or from the SET-GRnX data part to which the settings were copied. 36 1MRK UEN*2.0-00

41 Extensive operation SET-GRnA Line Reference Differential Earth Fault Additional Functions SET-GRnB Impedance SET.GRnC Synchrocheck 1..4 Autorecloser 1..6 SET-DREP Recording Times, Fault Locator Binary Signals - Input Binary Signals - Input Binary Signals - Input Binary Signals - Input SET-ASIG Analogue signals -Trig Name and Transformer ratios Recording and Triggers All settings regarding the protective functions in the terminal are done in the SET-GRnX part. There are 3 different setting groups with the same contents. (X={A, B, C}) Settings of the basic disturbance reporting functions in the terminal are done in this part. The user can determine whether the disturbance reporting unit is to be active or not, by setting operation On or Off. Different recording times, e.g. pre-fault, post-fault and limit time, are settable in this submenu. The programming of the triggering functionality and the masking of the binary signals are to allow local man-machine communication. For the fault locator function, the user must define the unit in which a distance to fault will be presented. All settings of the analogue signals in the Disturbance recorder function in the terminal are done in this part. This means that if the Disturbance recorder function is not installed, the entire part can be removed. It is feasible to select the triggering mode (overfunction, underfunction and Off-mode) and the recording mode of up to ten analogue signals when necessary. 1MRK UEN*

42 Extensive operation SET-DAIn DA Voltage U1..U5 DA Current I1..I5 DA11 - Voltage U phase-phase DA12 - Current I, phase DA13 - Active Power, P DA14 - Reactive Power, Q DA15 - Frequency, f The settings of the analogue inputs in the Direct Analogue Input function in the terminal is done in this part. The Monitoring A/C Measurements function must be installed in the terminal. If not, the entire part can be removed as shown in paragraph Removing Parts of Unit from an installation on page 68 in the chapter. SET-MIMn ma Input Module n Operation, Sampling Rate Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 SET-PLSC Pulse Counter SET-TIME The settings of the ma Input Modules are done in this part. The ma Input Module must be installed in the terminal. If not, the entire part can be removed as shown in paragraph Removing Parts of Unit from an installation on page 68 in the chapter. The settings of the Pulse Counter 1 to 12 is done in this part. The function must be installed in the terminal. If not, the entire part can be removed as shown in paragraph Removing Parts of Unit from an installation on page 68 in the chapter Technical description. The terminal has an internal real time clock including full-time, i.e., date and time. The clock can be checked, and set from SMS on a minute basis. The settings of the Terminal Time are not affected by the setting restrictions ( OPEN/BLOCKED ) in the terminal, and can always be changed. 38 1MRK UEN*2.0-00

43 Extensive operation Terminal Report This menu gives the user information on the terminal itself. Screen contents TRM--REP InternalEvents - SelfSuperv Internal events Self supervision information Observed modules - Article number, revision Noted modules - Article number, revision Users Notes Description The self supervision facilities informs the user about faults detected in the terminal itself or within any of the built-in protection functions. The identity of the terminal consists of information on the terminal s serial number, ordering number and software and hardware versions of different software functions and hardware modules. See chapter TRM--REP InternalEvents - SelfSuperv on page 64 in the chapter for detailed information. Analogue Input TRM--INST Installed software functions Installed hardware units All software functions and hardware units installed in the terminal are listed, with ordering numbers as they appear in the ordering forms. 1MRK UEN*

44 Extensive operation Configuration This menu serves for the user-specific configuration of a terminal.! Note! The write command that downloads ALL configuration data parts is NOT password protected. Delete the CNF-ALL part from the application structure if the ability to write or read ALL data parts without password is to be omitted. To remove the part from the application structure see paragraph Removing Parts of Unit from an installation on page 68 in the chapter. Screen contents CNF-ALL Write-Read ALL Configurations Up/download routine. CNF-ALOG Analogue - I/O - Comm Identifiers- Analogue Input U, I, P, Q, f Analogue Input U1..U5, I1..I5, CTEarth I/O-Modules Time Synchronisation Source, SPABUS communication LON communication IEC-Com, Remote Terminal Communication CNF-BHMI Local HMI menus Disturbance Report and Service Report menus Settings and Terminal Informations Configuration, Test and Command menus Description This part allows reading or writing of all configuration data from or to the terminal. The configuration regarding the analogue inputs and I/O-modules is done in this part. Information about the communication and time synchronisation is also presented. The LON communication configuration and setting restrictions are shown in this data part. The configuration of the menus of the local HMI of the terminal is done in the CNF-BHMI part. 40 1MRK UEN*2.0-00

45 Extensive operation Test This menu serves for testing purposes. The user can block the sending of alarm signals to the control centre during the testing activities. It is possible to block the operation of the disturbance reporting unit so as not to overload the memory with operations caused by the secondary injection testing. Screen contents TST-MODE Test - Block functions Test Block Functions Configuration Mode Description All settings regarding the Test function are done in the TST-MODE part: Set the terminal in test mode Block selected functions during test mode Set the Disturbance report and the Disturbance summary to On or Off during test mode. Set the terminal in configuration mode. It can only be done from the terminal. This disables the logic tasks in the terminal Event Masks! Note! The write command that downloads ALL event mask data parts is NOT password protected. Delete the MSK--ALL part from the application structure if the ability to write or read ALL data parts without password is to be omitted. To remove the part from the application structure, see paragraph Removing Parts of Unit from an installation on page 68 in the chapter. Screen contents MSK--ALL Write-Read ALL Event Masks Description The part MSK--ALL allows reading or writing all Events Masks from or to the terminal. Up/download routine. 1MRK UEN*

46 Extensive operation MSK-EV03 Event function Report Set Event Functions reporting Event Function 1 Event Function 2 Event Function 3 MSK-EVnn The Event function reporting and the masking of Event functions for the SPA events polled by SCS and REPORT in SMS are done in the MSK-EVnn part The setting in the MSK-EVnn part is only valid for the SPA events and will therefore not affect the events in disturbance recording presented in the DRP-EVEL part. Event function nn..nn Event Function n MSK-ANEV Event Mask for Analogue Events ma Input Module 1..6 Direct Analogue Input Pulse Counter The masking of Analogue Events for the SPA events used by SCS, is done in the MSK-ANEV part. 1.4 General Display Layout Screen layout for settable quantities All the layouts of screens with settable quantities are designed similarly. They have four columns; Parameter name, Present values, New values and Unit. The Present values column shows the actual settings of the REx 5xx terminal at the time of the last reading from the terminal. The date and time stamp shows when the Present values were transmitted to the PC. The New values are the modifiable values. The user can change the values and send them to the terminal. The PC-file date and time stamp shows when the settings were last stored in the PC. The representation of time and date, i.e., PC-file time, depends on the specified country code in the CONFIG.SYS file in the PC. 42 1MRK UEN*2.0-00

47 Extensive operation For most settable parameters, an explanatory text is displayed at the bottom line of the screen. The help text gives the user a more detailed description of the parameter along with the setting range, if applicable. (The text is displayed when the user positions the cursor to the parameter field which has a defined text). The help text follows the cursor position. For some data parts, an alarm text can be displayed in the first screen, i.e. the contents screen. A warning text appears at the top left area of the screen giving information about errors and actual conditions in the terminal. If the Remote setting restrictions is blocked in the terminal, it will only be possible to monitor the settings from SMS. If the user tries to transfer new parameters to the terminal when remote settings are blocked, the terminal will not accept them. In each part where settings can be made, it is shown whether remote setting is OPEN or BLOCKED. Commands like Clear Disturbance Reports and Clear Counters are not affected by the Remote setting restrictions, i.e. they can always be executed Contents Screens The following applies to all the contents screens for the data parts: A list of contents is presented to inform about the contents on the following screens: Stat, Obj and Unit shows the station, object and unit numbers and associated label texts. Terminal Time shows the real time clock value of the terminal at the end of the last terminal reading of this data part. The format of the time is YY-MM-DD HH.MM. SelfSuperv presents a summarised status of the terminal. Normally it should indicate OK, but if the self supervision has detected any fault, WARNING or FAIL is shown. 1MRK UEN*

48 Extensive operation In the upper part of the screen Remote setting indicates whether remote change of the parameters is allowed ( OPEN ) or not ( BLOCKED ) on the connected channel. The restriction is set with the local HMI on the terminal and cannot be changed from the SMS. SM shows the SM-product version number. 44 1MRK UEN*2.0-00

49 Extensive operation In the first line the name of the terminal, the name of the data part and the performed function (read, monitor) are shown. Terminal identity Other examples Only the functions installed in the terminal will be shown. Additional information, like Module type and Slot number are shown in another box. Terminal Time shows the real time clock value of the terminal at the end of the last terminal reading of this data part. The format of the time is YY-MM-DD HH.MM:SS. 1MRK UEN*

50 Extensive operation The information is grouped in different functions. The information presented is the values that were valid at the moment of reading from the terminal. Stored Time is the time of last change when saving information in the terminal. PC file time is the time of the last saving of new values in the PC. Positioning the cursor in New values of a parameter shows a help line related with that parameter. 1.5 Terminal Overview TRM-OVER The TRM-OVER part contains basic information of the terminal. This part gives the same overview of the terminal front panel as a visitor would get when visiting the station. Since the amount of information being transferred from the terminal is limited, reading the terminal overview can be used as a fast check to verify that the communication with the terminal is working correctly. Note that it is not possible to set any parameter in the TRM-OVER part. Fig. 1 TRM-OVER Screen MRK UEN*2.0-00

51 Extensive operation Screen 2 - Information presented Fig. 2 TRM-OVER Screen 2 The product name REx 500 and the version number Version 2.0 are displayed together with the information on which setting group is active in the terminal. local HMI LEDs shows the status of the three LEDs on the local HMI of the terminal. The Green LED signifies: Ready which means that the terminal is in operation, or Fail if the internal fail signal is activated. The Yellow LED signifies: Start Disturbance Report triggered, or Test if the terminal is put in test mode, or - otherwise. The Red LED signifies: Trip Trip command issued from a protection function, or Conf if the terminal is in configuration mode, or - otherwise. If the terminal is in test mode, this will be indicated with the text WARNING TESTMODE ACTIVE. I/O-Modules shows a list of hardware slots and the installed I/O-module in each slot. 1MRK UEN*

52 Extensive operation Screen 3 - Information presented Fig. 3 TRM-OVER Screen 3 Terminal Time shows the real time clock value of the terminal at the end of the last terminal reading of this data part. The format of the time is YY-MM-DD HH.MM. FRONT COMMUNICATION shows the SPA configuration, i.e., slave number and baud rate of the front port on the terminal. REAR COMMUNICATION shows the SPA configuration, i.e., slave number and baud rate of the rear SPA port on the terminal or the IEC communication and the baud rate. The LON configuration is also shown, i.e. domain Id, subnet Id, node Id, neuron load status and location configuration. Setting Restrict OPEN = remote setting allowed, and BLOCKED = remote setting not allowed. These setting restrictions can only be set on the local HMI and are valid for both rear ports of the terminal. TIME SYNCHRONISATION SOURCE shows if LON or SPA is selected for synchronisation of the internal real time clock. Alternatively, the time synchronisation can be performed via a minute-pulse to a binary input of the terminal. The status of the time synchronisation source is shown and should indicate OK.! Note! If any function is not installed in the terminal, the corresponding part of the screen will be empty or show Not installed. 48 1MRK UEN*2.0-00

53 Extensive operation Screen 4 - Information presented Fig. 4 TRM-OVER Screen 4 Function Selectors and Optional Functions shows a list of functions that can be installed in the terminal. Installed functions are marked with a square to the left of the text. 1MRK UEN*

54 Extensive operation 1.6 Disturbance Report DRP-OVER Disturbance Overview The part DRP-OVER contains information about the 10 last disturbances stored in the terminal. In this part, the user also selects which disturbance to activate for more information in the other DRP-xxxx parts (DRP-INDC, DRP-EVEL and DRP-TRIP). Screen 1 - Information presented Fig. 5 DRP-OVER Screen 1 The No. of the recorded disturbance is a number running from 0 to 200, and then starting from 0 again. This is the primary disturbance identifier in the terminal, not to be mixed with the daily sequence number that is reset to zero each new date. This is also the number to be entered by the user in order to select a new disturbance to be loaded into the disturbance report memory in the terminal. By selecting a disturbance, the detailed information about the disturbance will be available for SMS. An overview of the stored disturbances is shown with information regarding the Date and Time of the recording, Outgoing TRIP, and Trig Signal causing the start of the recording. 50 1MRK UEN*2.0-00

55 Extensive operation Screen 1 - Select a new disturbance number The SMS and the terminal present detailed information about one disturbance at a time. This means that a disturbance must be selected before any detailed information about the disturbance can be accessed from the SMS. In order to get more detailed information on each of the recorded disturbances the user must select one of the listed disturbances by entering a disturbance number in the New No. field. 1 To select a disturbance, press <Enter>. 2 Enter the number of one of the disturbances listed to the left on the screen, and press <Enter> 3 Press <Esc> to leave the part and select Activate selected DistRep No.. This action will make the terminal load the selected disturbance into an active memory area accessible from SMS. When detailed presentation of data is selected from the SMS, the terminal will, on request, upload the data to the PC. 4 Finally select Monitor PC-file information in order to verify that the selected number is now presented in the Present No. field. 5 The selection of a new disturbance will make more information regarding the selected disturbance available to the SMS. The additional information is shown in the three parts DRP-INDC, DRP-EVEL, and DRP-TRIP provided that the required functions are installed in the terminal. It is also possible to select a disturbance and upload the data of the disturbance to the PC in one step. This will allow presentation of the data in the DRP-INDC, DRP-EVEL and DRP-TRIP parts by Monitoring PC-file information. To select a disturbance and upload the data: 6 Press <Enter> in DRP-OVER Screen 1. 7 Enter the number of one of the disturbances listed to the left on the screen, and press <Enter>. 8 Press <Esc> to leave the part and select Upload DistRep DPR-INDC-EVEL- TRIP. This action will make the terminal load the selected disturbance into an active memory area accessible from SMS and upload the disturbance data for DRP-INDC, DRP-EVEL and DRP-TRIP parts to the PC. 9 Select Monitor PC-file information in order to verify that the selected number is now presented in the Present No. field. The selection of a new disturbance and upload of data will make the information regarding the selected disturbance available to the SMS. As the information is already uploaded to the PC, the detailed information is available in the DRP-INDC, DRP- EVEL, and DRP-TRIP by selecting Monitoring PC-file information when opening these parts, provided that the required functions are installed in the terminal. 1MRK UEN*

56 Extensive operation Screen 1 - Disturbance numbering The terminal has a storage capacity of 10 disturbances, equivalent to approximately 1,5 Mb. On the local HMI these are numbered 1-10, while in SMS the index number is used. The reason for this is that after the user has read the DRP-OVER, and selected, for example, the last disturbance designated Disturbance 1, a new disturbance might occur in the terminal. This means that Disturbance 1 has changed contents. Instead, by using the index number 0-200, the number of the selected disturbance will be unique, and the situation described will never occur. HMI Select Disturbance HMI- Local reading area in database SELECT COPY Disturbance 1 Disturbance 2 Disturbance 10 SMS SMS- Local reading area in database Select Disturbance COPY SELECT Fig. 6 SMS and local HMI reading areas for disturbances. 52 1MRK UEN*2.0-00

57 Extensive operation Screen 1 - Information structure of disturbance functions Depending on the functions installed in the terminal, the information available for a disturbance varies. The indications event list, fault locator values, trip values and disturbance recording header are always available for the last 10 disturbances. The number of disturbance recordings containing oscillographic information depends on the recording times set in the terminal, and the harmonic contents of the signals. All information is accessed via SM/REx 500 and the disturbance recordings, which are available via FrontRECOM (or RECOM) and can be evaluated with REVAL. Disturbance No Overview (DRP-OVER) Select active disturbance No. (DRP-OVER) Disturbance No. 1 Indications (DRP-INDC) Event list (DRP-EVEL) Trip values (DRP-TRIP) Disturbance No. 2 Indications (DRP-INDC) Event list (DRP-EVEL) Trip values (DRP-TRIP) Disturbance No. 10 Indications (DRP-INDC) Event list (DRP-EVEL) Trip values (DRP-TRIP) Fault locator (DRP-TRIP) Fault locator (DRP-TRIP) Fault locator (DRP-TRIP) Disturbance Recording (RECOM, REVAL) Disturbance Recording (RECOM, REVAL) Disturbance Recording (RECOM, REVAL) Fig. 7 Information structure of disturbance reporting functions. 1MRK UEN*

58 Extensive operation Screen 2 - Information presented Fig. 8 DRP-OVER Screen 2 Disturbance report Operation shows if the disturbance reporting functions are active or not in normal mode and in test mode. These settings can be changed in the parts SET-DREP Disturbance Report Contents and TST-MODE Test - block functions. At the lower left part of the screen, the user is informed if the terminal is in Test- Mode or in NormalMode at the moment of communication. The Recorder shows if the Event Recorder function is installed in the terminal and if the Disturbance Recorder function is installed along with the amount of disturbance memory used by the Disturbance Recorder at the moment. The Daily Sequence No shows the status of the sequence number counter, i.e. the number the next recorded disturbance during the present day will get. The number is reset to 0 when a new day begins. The first report that day gets the number 0, the second number 1, etc. 54 1MRK UEN*2.0-00

59 Extensive operation DRP-INDC Indications The part DRP-INDC contains information on indications during the disturbance that was selected in the part DRP-OVER. Note that it is not possible to set any parameters in the DRP-INDC part. Screen 1 - Information presented Fig. 9 DRP-INDC Screen 1 If no disturbances are stored in the terminal this will be indicated with the text WARNING - NO DISTURBANCES STORED IN TERMINAL. If the disturbances were stored while the terminal was in test mode, this will be indicated with the text WARNING - RECORDING MADE IN TESTMODE. Disturbance information shows some basic information regarding the selected disturbance. Number is the same number as was selected in the part DRP-OVER. Date, Time is the time of the triggering of the disturbance report. Daily Sequence No shows the terminal sequence number of this specific disturbance report. The number is reset to 0 when a new day begins and the first report that day gets the number 0, the second number 1, etc. Trig Signal shows which signal triggered the disturbance reporting function. tpre, pre-fault shows the pre-fault time of the recording, i.e., the time recorded before the triggering signal was activated. ttotal shows the total recording time, i.e., pre-fault, fault, and post-fault times. Active Setting Grp shows which setting group was active during the disturbance. 1MRK UEN*

60 Extensive operation Screen 2 - Information presented Fig. 10 DRP-INDC Screen 2 At the top of the screen the No. of the disturbance, Date, Time and Trig Signal are shown. The 48 binary signals configured by the user are shown. The signals are presented with the user-defined names. All signals that were active during the disturbance, i.e. the signals that have changed state once or several times, are indicated with a square in front of the name DRP-EVEL 150 Events List The part DRP-EVEL contains information on events during the disturbance that was selected in the part DRP-OVER. Note that it is not possible to set any parameters in the DRP-EVEL part. The Event recorder function must be installed in the terminal in order to get an event list. If not, the event list will always be empty. In this case the whole part can be removed as shown in paragraph Removing Parts of Unit from an installation on page 68 in this chapter. 56 1MRK UEN*2.0-00

61 Extensive operation Screen 1 - Information presented Fig. 11 DRP-EVEL Screen 1 If no disturbances are stored in the terminal, this will be indicated with the text WARNING - NO DISTURBANCES STORED IN TERMINAL. If the disturbances were stored while the terminal was in test mode, this will be indicated with the text WARNING - RECORDING MADE IN TESTMODE. Disturbance information shows some basic information regarding the selected disturbance. Number is the same number as was selected in the part DRP-OVER. Date, Time is the time of the triggering of the disturbance report. Daily Sequence No shows the terminal sequence number of this specific disturbance report. The number is reset to 0 when a new day begins and the first report that day gets the number 0, the second number 1, etc. Trig Signal shows which signal triggered the disturbance reporting function. tpre, pre-fault shows the pre-fault time of the recording, i.e. the time recorded before the triggering signal was activated. ttotal shows the total recording time, i.e. pre-fault, fault, and post-fault time. Active Setting Grp shows which setting group was active during the disturbance. Stat, Obj and Unit shows the station, object and unit numbers and associated label texts. Event Recorder required shows if the Event recorder function is installed in the terminal or not. If not, it is recommended to remove the DRP-EVEL part as mentioned earlier. 1MRK UEN*

62 Extensive operation Screen 2 to 5 - Information presented Fig. 12 DRP-EVEL Screen 2 The events among the 48 binary signals selected by the user are shown along with the time tag. The events are presented with the user-defined signal names. The event list for each disturbance contains a maximum of 150 events presented on four screens. The first event on the first screen is the first event that occurred within the disturbance, and the following events are presented in chronological order DRP-TRIP Trip values The part DRP-TRIP contains information on trip values related to the disturbance that was selected in the part DRP-OVER. The Measurement 1A/5A function must be installed in the terminal in order to get any values. If not, all values always show 0. In this case, the whole part can be removed as shown in paragraph Removing Parts of Unit from an installation on page 68 in this chapter. 58 1MRK UEN*2.0-00

63 Extensive operation Screen 1 - Information presented Fig. 13 DRP-TRIP Screen 1 If no disturbances are stored in the terminal this will be indicated with the text WARNING - NO DISTURBANCES STORED IN TERMINAL. If the disturbances were stored while the terminal was in test mode, this will be indicated with the text WARNING - RECORDING MADE IN TESTMODE. Disturbance information shows some basic information regarding the selected disturbance. Number is the same number as was selected in the part DRP-OVER. Date, Time is the time of the triggering of the disturbance report. Daily Sequence No shows the terminal sequence number of this specific disturbance report. The number is reset to 0 when a new day begins and the first report that day gets the number 0, the second number 1, etc. Trig Signal shows which signal triggered the disturbance reporting function. Active Setting Grp shows which setting group was active during the disturbance. 1MRK UEN*

64 Extensive operation Screen 2 - Information presented Fig. 14 DRP-TRIP Screen 2 On the top of the screen No. of the disturbance, Date, Time and Trig Signal are shown. The phasors for the prefault conditions are shown on the left part of the screen along with the frequency. To the right, the phasors for the fault conditions are shown. 60 1MRK UEN*2.0-00

65 Extensive operation DRP-CLRS Clears and Manual trig In the part DRP-CLRS it is possible to clear LED indications and disturbances stored in the terminal. It is also possible to activate a manual trig that generates a disturbance report. Screen 1 - Performing a manual trig Fig. 15 DRP-CLRS Screen 1 By selecting Yes on the Manual Trig of a Recording all disturbance reporting functions available in the terminal is activated when the command is sent to the terminal. If 10 disturbances are stored in the terminal or if the disturbance memory is full, this action will overwrite the oldest disturbance. Screen 1 - Clearing information The HMI LEDs will be cleared if selecting Yes. This corresponds to pressing the C button on the local HMI. All disturbance reports, i.e. the information available in the different DRP-... parts and RECOM will be erased if selecting Yes. After this action the disturbance memory will be empty. Screen 1 - Note All desired settings have to be made each time since all actions set to Yes will be performed when selecting Write settings to terminal. For this reason, always start with the command Read terminal data to PC-file, as this action will set all answers to No. All actions in the DPR-CLRS part can be carried out even if remote setting is blocked in the terminal. However, a password is requested before any clearing activity can take place. 1MRK UEN*

66 Extensive operation RECOM REx5xxV1 Unit disturbance summary The RECOM REx5xxV1 part enables the PC to collect the disturbance recordings stored in the terminal. Presentation on the screen differs, depending on whether FrontRECOM or RECOM is installed in the PC. In this chapter, only FrontRECOM is described since it is included in the SM/REx 500 package. For more information regarding RECOM, refer to the RECOM User s guide. Ref. 3 in chapter 4: References. To get any information, the Disturbance recorder function must be installed in the terminal. On screen 4 of the TRM-OVER part, information is shown whether the Disturbance recorder function is installed or not. If not, the RECOM screen is always empty. In this case the whole part can be removed as shown in paragraph Removing Parts of Unit from an installation on page 68 in this chapter. Screen 1 - Information presented Fig. 16 RECOM REx 500 Screen 1 On top of the screen the names of Station, Object and Unit are shown. Note that these are the names entered in SMS-BASE. This means that it is not the names read from the terminal, which is the case in all other parts in SM/REx 500. On the upper right hand side DIRECT is shown, if direct communication connection is selected in the SMS-BASE communication setup. The list shows all disturbances stored in the terminal (up to 10) and all disturbances stored only in the PC, i.e. disturbances no longer available in the terminal. The first and second columns show the date and the daily sequence number. The first disturbance occurring each day will get the daily sequence number 000. The next will get the sequence number 001, and so on. Note that this number is not the same number as shown in the DRP-OVER part. In this case the number is an index running from 0 to 200 in order to give each disturbance in the terminal database an unique number. In the parts DRP-INDC, DRP-EVEL and DRP-TRIP both the index number and the daily sequence number are shown on the first screen. 62 1MRK UEN*2.0-00

67 Extensive operation The third and fourth columns indicate where the disturbance is stored. R stands for disturbance file, and H stands for header file. If the disturbance memory is full due to long recording times, the oldest disturbances might consist of the header only. There might also be disturbances that are only stored in the PC, because the whole recording has been deleted or overwritten in the terminal. Time shows when the trigger of the disturbance recorder was activated. Trig is the triggering signal, analogue or binary, or manual triggering.screen 1 - Uploading a disturbance to the PC Screen 1 - Uploading a disturbance to the PC To upload a disturbance to the PC, the disturbance of interest has to be highlighted by positioning the cursor with the <up arrow> and <down arrow> keys. Press <U> to upload all information, i.e. the header (H) and the disturbance file (R) from the terminal to the PC. This action will not delete the recording in the terminal. It will still be available for other users until it is manually deleted or overwritten by new disturbances. The uploaded disturbance will be stored in the same directory structure as the terminal settings, e.g. c:\sms\data\o001\s001\o001\u001. The name of the disturbance file will be, for example, RE*, where the first six digits are the date, YYMMDD, and the last two the sequence number. The file name extension is REV for the disturbance file and REH for the header file. When opening the file with the REVAL disturbance evaluation program, the same station and unit names as entered in SMS-BASE will be shown in order to simplify the handling. Screen 1 - Refreshing information on screen The refresh selection <R> updates the information on the screen, e.g. if a new disturbance has occurred.! Screen 1 - Deleting a disturbance from the PC The delete selection <D> deletes the current highlighted disturbance file in the PC. Note! It is only the PC-file containing the disturbance information that is deleted. Disturbances stored in the terminal are not affected. Screen 1 - Getting Help The help selection <E> presents a short help text for the handling of FrontRECOM. Screen 1 - Exiting FrontRECOM To exit the FrontRECOM Unit disturbance summary, press <Esc> or <X>. 1MRK UEN*

68 Extensive operation! Note! If the disturbance memory is full, and the oldest disturbance is uploaded at the same time as a new disturbance occurs, the information in the oldest disturbance will be lost. This will result in a disturbance that is only partly stored on the PC, and will not be possible to open by the REVAL disturbance evaluation program. The REVAL program then gives the indication Not readable. 1.7 TRM--REP InternalEvents - SelfSuperv The part TRM--REP consists of the status of the terminal, coming from the self supervision functions, and article numbers of the terminal and the included hardware modules. Screen 1 - Information presented Fig. 17 TRM--REP Screen 1 READ ERROR - THE CONTENTS CHANGED. READ AGAIN This warning is displayed if Internal Events shown on screen 2-3 has changed during the communication. To access an updated list, the data part must be read again by selecting Read terminal data to PC-file. 64 1MRK UEN*2.0-00

69 Extensive operation Screen 2 to 3 - Information presented Fig. 18 TRM--REP Screen 2 On these screens the internal events of the terminal are presented. The list mainly contains events from the internal self supervision signals. The list is a first-in-first-out list. All the events are presented with date and time. The latest event is always presented as the last event in the list. The events are presented in chronological order. Screen 4 - Information presented Fig. 19 TRM--REP Screen 4 On these screens, the current status of all self supervision signals, at the time of communication with the terminal, is presented along with a brief explanation. All activated self supervision signals in this list are also included in the internal event list on screen 2. 1MRK UEN*

70 Extensive operation Screen 5 to 6 - Information presented Fig. 20 TRM--REP Screen 5 Fig. 21 TRM--REP Screen 6 On this screen the article numbers of the included hardware modules are presented. The reason for this information is to give the user the correct identification number if a module is faulty and has to be replaced. The article numbers of all I/O-modules and the CPU-module are stored as a code on the module itself and will automatically be updated if the module is replaced. The terminal type and version number are presented together with a unique serial number of the terminal. The Ordering No. of the terminal is also presented. 66 1MRK UEN*2.0-00

71 Extensive operation Screen 7 - Settable parameters Fig. 22 TRM--REP screen 7 On this screen the notes made by the user are shown. After downloading, these notes are stored in the terminal and can be read by other users from other locations using the SMS. The user notes are intended to store information regarding, for example, additional hardware co-operating with the terminal, or the date of the last test or maintenance. This information can only be read from SMS. It is not available on the local HMI. The possibility to change the user notes is not affected by the setting restrictions ( OPEN / BLOCKED ) in the terminal, i.e. they can always be changed. The notes are changed when selecting Write User s Notes to terminal Screen 9 - Information presented Fig. 23 TRM--REP Screen 8 On this screen, the nominal values for the transformer inputs are shown. 1MRK UEN*

72 Appendix 2 Appendix 2.1 Diagnosing errors Check the technical requirements according to paragraph System requirements on page 12 in the chapter Instructions. Check the installation with reference to paragraph Installation procedures on page 13 in the chapter Instructions. The correct use of SM/REx 500 is presented in chapters 2 and 3. When errors occur, their type as well as a probable cause are shown in the lower part of the screen. Error messages normally have to be confirmed with <Enter>. The user is then brought back to the activity prior to the one that caused the error. See SMS-BASE User s Guide Ref. 2 in chapter 4: References for more information regarding error messages. 2.2 Error messages during communication When communication is bad using a telephone line, data is not transferred. After a number of unsuccessful attempts to transfer a quantity, the program asks the user to press <R> for a Retry or <Q> for Quit. Normally, select <Q> and terminate the call. Try to call again to get a better line. Both rear port channels on the terminal are normally served in parallel. However, during busy terminal situations, the service may be delayed and a busy signal (NAK 1) is sent by the terminal during read conditions and another busy signal (NAK 7) during write conditions. It is very important that the SMS user does not Skip any NAK messages. Either press Retry <R> or Quit <Q>. Otherwise, most likely the transmitted data is faulty or incomplete. 2.3 Adopting PC to SMS programs Sometimes when selecting Monitor PC-file information the text Not enough memory is shown on the screen. This means that less than the required 450 kb of work memory are available on the PC. One common problem is that other applications are resident in the same memory area in the PC. By removing these from the PC, memory is released and the requirement of 500 kb is fulfilled. 2.4 Removing Parts of Unit from an installation If any Part of Unit is not relevant for a terminal, for example SET-ASIG if the Disturbance recorder function is not installed, this part can be removed from the installation: 68 1MRK UEN*2.0-00

73 Appendix 1 Select the Alter application structure in the UTILITIES menu. 2 Go down the structure and select the terminal in question. 3 Select the part SET-ASIG and press <D>. 4 Answer yes <Y> to the question. This procedure can be repeated for any Part of Unit. The removal of parts due to the fact that some functions are not installed in a terminal is highly recommended in order to get a better overview. Also the removal of parts like SET--ALL or DRP-CLRS is highly recommended, if the philosophy of the user is that this action should not be possible from SMS. So, for each new instance of unit, the following work flow is recommended: 1 For each part select Read terminal data to PC-file. 2 Then select the Monitor PC-file information in order to check that the required function is installed, and if the part contains functionality that is of interest for the user. If not, the part should be removed according to the procedure above. 2.5 Handling SMS under MS Windows The SMS-BASE can be started as an icon in MS Windows as described in the SMS- BASE User s Guide Ref. 2. When starting SMS-BASE from Windows the PC will automatically open a DOS-Window in which SMS-BASE is run. It will then be possible to switch between different applications in Windows by pressing <Alt>+<Tab>. It will also be possible to reduce the DOS application to a smaller window, by pressing <Alt>+<Enter>. This means that the information in SMS can be overviewed at the same time as for example REVAL, as shown below. For more information regarding this facility refer to the MS Windows User s Guide. 1MRK UEN*

74 Appendix Fig. 24 SMS-BASE run as a small DOS window under MS Windows. 2.6 Error Messages Terminal blocked Internal fault: The internal supervision software of the terminal has detected an error, e.g. component malfunction. The input "block" of the trip function element is activated: By an activated input signal via I/O, internally connected/configured to the element. By another input signal e.g. "FIXED-ON" internally connected/configured to the element. By local HMI: In menu "Test" the alternative "Block Terminal" is On. The blocking must be released from the same menu by changing setting to Off. 70 1MRK UEN*2.0-00

User s Manual CAP 531*1.5 Configuration and Programming tool

User s Manual CAP 531*1.5 Configuration and Programming tool User s Manual CAP 531*1.5 Configuration and Programming tool This manual belongs to: Contents Chapter Page About this manual 1 Introduction 3 Technical descriptions 81 References 177 Customer feedback

More information

ABB Network Partner. User s Manual RECOM*1.4

ABB Network Partner. User s Manual RECOM*1.4 User s Manual RECOM*1.4 This manual belongs to: Contents Chapter Page About this manual 1 Introduction 3 Instructions 11 Technical description 21 References 77 Customer feedback report 79 Software Registration

More information

ABB Network Partner. User s Manual HV/RET 521*2.0

ABB Network Partner. User s Manual HV/RET 521*2.0 User s Manual HV/RET 521*2.0 This manual belongs to: Contents Chapter Page About this manual 1 Introduction 3 Installation 9 Technical description 41 References 65 Customer feedback report 67 Software

More information

ABB Network Partner. User s Manual CAP/REx 500*2.0

ABB Network Partner. User s Manual CAP/REx 500*2.0 User s Manual CAP/REx 500*2.0 This manual belongs to: Contents Chapter Page About this manual 1 Introduction 3 Instructions 7 References 15 Customer feedback report 17 Software Registration Form 19 Index

More information

Terminal tool box CAP 540*1.2

Terminal tool box CAP 540*1.2 Page 1 Issued: January 2003 Revision: A Data subject to change without notice Features Engineering tool box including disturbance upload, parameter setting, monitoring and configuration of REx 5xx transmission

More information

SM/SACO for SMS 010 User s Guide SMS 010 SACO library

SM/SACO for SMS 010 User s Guide SMS 010 SACO library 1MRS 750331-ESD Version B Replaces version A Issued 97-10-15 Checked P.S. Approved S.S. Data subject to change without prior notice SM/SACO for SMS 010 User s Guide SMS 010 SACO library This set of SM/SACO

More information

Installation and commissioning manual

Installation and commissioning manual ,QVWDOODWLRQDQG&RPPLVVLRQLQJPDQXDO (QJLQHHU,7 7HUPLQDOWRROER[ &$3 Installation and commissioning manual $ERXWWKLVPDQXDO,QVWDOODWLRQ0DQXDO Installing the CAP 540 Navigator...7 Installing PST...10 Installing

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

Communicate IT Software module DR-COM. Buyer s Guide

Communicate IT Software module DR-COM. Buyer s Guide Buyer s Guide Issued: April 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Periodical and automatic collection of recordings on substation level Manual collection

More information

Relay configuration and setting tool package

Relay configuration and setting tool package Issued: May 1999 Status: Updated Version: C/30.09.2002 Data subject to change without notice Features Function logic configuration tool according to IEC 61131-3 standard for ABB range of protection relays

More information

Relay Product Engineering Tools

Relay Product Engineering Tools Relay Product Engineering Tools CAP 505 Issued: May 1999 Status: Updated Version:D/16.09.2003 Data subject to change without notice Features Function logic configuration tool according to IEC 61131-3 standard

More information

User s Manual HV/Collect*3.1

User s Manual HV/Collect*3.1 User s Manual HV/Collect*3.1 This manual belongs to: Contents Chapter Page About this manual 3 Introduction 5 Instructions 11 Technical descriptions 17 References 35 Appendix 37 Index 47 2 About this manual

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Mounting kits for space-saving mounting in racks and cubicles and on walls IP54 protected mounting capability in cubicles

Mounting kits for space-saving mounting in racks and cubicles and on walls IP54 protected mounting capability in cubicles Page Revision: - Issued: December 00 Data subject to change without notice )HDWXUHV 0RXQWLQJNLWV 0RXQWLQJNLWV Mounting kits for space-saving mounting in racks and cubicles and on walls IP54 protected mounting

More information

Multifunction Protection and Switchgear Control Unit. Operator's manual

Multifunction Protection and Switchgear Control Unit. Operator's manual REF 542plus 1MRS755869 Issued: 01.11.2002 Version: C/31.05.2007 REF 542plus Contents Copyrights... 7 1. Introduction...9 1.1. This manual... 9 1.2. Use of symbols... 9 1.3. Intended audience... 9 1.4.

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

Relay setting toolbox

Relay setting toolbox Relay setting toolbox CAP 501 Issued: May 1999 Status: Updated Version B/06.11.2001 Data subject to change without notice Features General parameter setting support for ABB protection relays and terminales

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

SINUMERIK 840 C OEM Version Windows Remote Diagnostics Host for MMC, Viewer for SINUMERIK

SINUMERIK 840 C OEM Version Windows Remote Diagnostics Host for MMC, Viewer for SINUMERIK SINUMERIK 840 C OEM Version Windows Remote Diagnostics Host for MMC, Viewer for SINUMERIK Planning Guide Edition 05.96 Service documentation Brief description 1 Detailed description 2 SINUMERIK 840 C OEM

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

ATL20 ATL30 Automatic transfer switch controller

ATL20 ATL30 Automatic transfer switch controller I 194 GB 07 07 ATL20 ATL30 Automatic transfer switch controller REMOTE CONTROL SOFTWARE MANUAL Summary Introduction... 2 Minimum resources of the PC... 2 Installation... 2 Activation of the PC-ATL connection...

More information

MV Process Application Library LIB 510. Product Guide

MV Process Application Library LIB 510. Product Guide Issued: April 1999 Status: Updated Version: C/09.05.2006 Data subject to change without notice Features Application library for MV process applications built using ABB Substation Automation products Application

More information

IMO. ismart. Training Manual

IMO. ismart. Training Manual IMO ismart Training Manual automation@imopc.com IMO IMO Precision Controls 1000 North Circular Rd Staples Corner London NW2 7JP Tel: +44 (0) 208 452 6444 Fax: +44 (0) 208 450 2274 Email: sales@imopc.com

More information

Operating Instructions

Operating Instructions 33CS Comfort System Software CONTENTS Page GENERAL...1 OPERATION...1-11 Start-Up...1 Main Menu...2 CURSOR MOVEMENT AND FUNCTION SELECTION Initial Setup and Configuration...3 BASIC MODE EXPERT MODE MODEM

More information

PSM 505. Inform IT Power System Monitoring. Stand-alone Fault Analysis and Evaluation Tool. Technical Data. Introduction.

PSM 505. Inform IT Power System Monitoring. Stand-alone Fault Analysis and Evaluation Tool. Technical Data. Introduction. Page 1 Issued: July 2003 New Data subject to change without notice Introduction High-voltage transmission and distribution networks are the backbone of modern power generation and distribution systems.

More information

The TPU-2000R unit comes enclosed in a metal case. Follow the instructions and diagrams in this section to install the TPU-2000R.

The TPU-2000R unit comes enclosed in a metal case. Follow the instructions and diagrams in this section to install the TPU-2000R. Installation The TPU-2000R unit comes enclosed in a metal case. Follow the instructions and diagrams in this section to install the TPU-2000R. Receipt of the TPU-2000R When you receive the TPU-2000R, examine

More information

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation 111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities

More information

High impedance protection relay

High impedance protection relay High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted

More information

PRON NA60-CBA. IEC Communication Protocol User Guide PRON NA60-CBA. Version Page: 1 of 13 PRON NA60-CBA IEC

PRON NA60-CBA. IEC Communication Protocol User Guide PRON NA60-CBA. Version Page: 1 of 13 PRON NA60-CBA IEC IEC 870-5-103 Communication Protocol User Guide PRON NA60-CBA Page: 1 of 13 PRON NA60-CBA IEC 870-5-103 Contents Contents...2 1 IEC 870-5-103 Protocol...3 8.1 Physical Layer...3 8.1.1 Electrical Interface...3

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

GC-10 Wireless Control Box. User Guide

GC-10 Wireless Control Box. User Guide Wireless Control Box User Guide 1. Introduction This Installation and User Guide will assist you in installing and configuring the Brodersen SMS Alarm Unit. The guide covers the installation of the configuration

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

IDEA. User s Guide. Part No IDE02 Issue 1-0, April 1995 Printed in U.S.A. (183)

IDEA. User s Guide. Part No IDE02 Issue 1-0, April 1995 Printed in U.S.A. (183) IDEA User s Guide Part No. 17500IDE02 Issue 1-0, April 1995 Printed in U.S.A. (183) 4 FOREST PARKWAY, SHELTON, CONNECTICUT 06484 TEL: 203-926-5400 FAX: 203-929-0535 This manual has been developed by Nitsuko

More information

U90 Ladder Software Manual. Version 3.50, 6/03

U90 Ladder Software Manual. Version 3.50, 6/03 U90 Ladder Software Manual Version 3.50, 6/03 Table Of Contents Welcome to U90 Ladder... 1 Program Editors... 1 Project Navigation Tree...1 Browse Sequences...1 Printing Documentation...2 Interface Language...

More information

M2500 Engine Controller Configuration Manual

M2500 Engine Controller Configuration Manual M2500 Engine Controller Configuration Manual Revision: 08-04-2011 Page 1 Contents 1 Preface... 4 2 Configuration from front panel... 5 2.1 Engine Controller Configuration... 6 2.1.1 RPM settings... 6 2.1.2

More information

QUICK START. DevCom2000 User Manual

QUICK START. DevCom2000 User Manual QUICK START DevCom2000 uses Device Descriptions (DDs) to access data stored in the memory of the smart field device. These DDs are developed by the manufacturer for their products and, in turn, distributed

More information

Distributed busbar protection REB500 Operation Manual

Distributed busbar protection REB500 Operation Manual REB500 Substation Automation Products Operation Manual Document ID: 1MRK 500 121-UEN Issued: May 2015 Revision: - Product version: 8.10 Copyright 2015 ABB. All rights reserved Copyright This document

More information

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits 01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution

More information

DNP3 Communication User's manual

DNP3 Communication User's manual MV Network Management Fault tracking Monitoring and Control Merlin Gerin Easergy Range T200 P, T200 I DNP3 Communication User's manual Summary General...2 Functionnalities...2 Characteristics...2 Connection

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

PC100. Operating Manual. Enclosed Disk Art.-No.: Programming-Software for Compact-Encoder

PC100. Operating Manual. Enclosed Disk Art.-No.: Programming-Software for Compact-Encoder PC100 Operating Manual Programming-Software for Compact-Encoder Edition date/rev. date: 03.03.1999 Document no./rev. no.: TR-E-BA-GB-0007-02 Software version: V3.4 File name: TR-E-BA-GB-0007.DOC Author:

More information

CAP 505. User s Guide

CAP 505. User s Guide CAP 505 1MRS752292-MUM CAP 505 Issued: 04.10.2002 Version: L/05.01.2005 1. About this manual...7 1.1. Copyrights...7 1.2. Trademarks...7 1.3. General...7 1.4. Use of symbols...8 1.5. Abbreviations...8

More information

CAP 505 Relay Product Engineering Tools Installation and Commissioning Guide

CAP 505 Relay Product Engineering Tools Installation and Commissioning Guide CAP 505 Relay Product Engineering Tools Industrial IT enabled products from ABB are the building blocks for greater productivity, featuring all the tools necessary for lifecycle product support in consistent

More information

ADVANCED OPERATOR PANEL (AOP)

ADVANCED OPERATOR PANEL (AOP) ADVANCED OPERATOR PANEL (AOP) Operating Instructions Issue 04/02 English Contents 1 Warnings and Notes 3 1.1 Special Key Functions 4 2 Applications Examples 4 2.1 Single drive control using the AOP 4 2.2

More information

TFS 2100 Traveling Wave Fault Location System

TFS 2100 Traveling Wave Fault Location System Traveling Wave Fault Location System The most accurate overhead transmission and distribution line fault locator Accuracy: ±150m typical regardless the line length Unaffected by fault resistance Suitable

More information

The following steps will allow you to install and quickly begin using DevCom:

The following steps will allow you to install and quickly begin using DevCom: QUICK START DevCom uses Device Descriptions (DDs) to access data stored in the memory of the smart field device. These DDs are developed by the manufacturer for their products and, in turn, distributed

More information

VIPER MANUAL TM0019. TM0019 Page 1 of 48 Issue 2.01

VIPER MANUAL TM0019. TM0019 Page 1 of 48 Issue 2.01 VIPER MANUAL TM0019 TM0019 Page 1 of 48 Issue 2.01 PROPRIETARY RIGHTS NOTICE The information contained in this manual is the property of Kidde Fire Protection Services Limited and may not be reproduced

More information

Modular identification system

Modular identification system Modular identification system (xx00000675.tif).jpg Application To be able to locate a relay unit in a protective relay, the unit is identified with a unique item designation. Furthermore, the electrical

More information

Application of a modern control and protection system in an existing EHV substation in Maribor, Slovenia

Application of a modern control and protection system in an existing EHV substation in Maribor, Slovenia Station Automation & Protection Station Automation and Protection includes control, monitoring, and protection for power plant, transmission, and distribution applications. Solutions range from single

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

The following steps will allow you to install and quickly begin using DevCom:

The following steps will allow you to install and quickly begin using DevCom: QUICK START DevCom uses Device Descriptions (DDs) to access data stored in the memory of the smart field device. These DDs are developed by the manufacturer for their products and, in turn, distributed

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

Modbus Remote Communication Protocol for REM 54_. Technical Description

Modbus Remote Communication Protocol for REM 54_. Technical Description Modbus Remote Communication Protocol for REM 54_ 1MRS 750781-MUM Issued: 08.03.2002 Version: A/18.06.2002 Checked: ML Approved: AF Remote Communication Protocol for REM 54_ Modbus We reserve the right

More information

PHARO User Configuration Software UCS USER MANUAL Rev.0-15/07/ pharo.reer.it

PHARO User Configuration Software UCS USER MANUAL Rev.0-15/07/ pharo.reer.it PHARO User Configuration Software UCS USER MANUAL 8540588 - Rev.0-15/07/2004 www.reer.it pharo.reer.it This document is protected by the law of copyright, whereby all rights established therein remain

More information

IS2000. Administrative Operator s Guide. AOG-101 (07/2005) Software Version 7.45

IS2000. Administrative Operator s Guide.  AOG-101 (07/2005) Software Version 7.45 IS2000 Administrative Operator s Guide www.imron.com AOG-101 (07/2005) Software Version 7.45 Table of Contents INTRODUCTION...6 Overview...6 GENERAL INFORMATION...6 Logging On...7 Logging Off...9 Event

More information

[ ] INFOLOG. Hand-held terminal type PSION. Operating Manual. for SITRANS F US ultrasonic flowmeter type SONOCELL and SONO 3301 *085R9464*

[ ] INFOLOG. Hand-held terminal type PSION. Operating Manual. for SITRANS F US ultrasonic flowmeter type SONOCELL and SONO 3301 *085R9464* s Operating Manual INFOLOG Hand-held terminal type PSION for SITRANS F US ultrasonic flowmeter type SONOCELL and SONO 3301 [ ] SAP No. FDK-521H1200 SFIDK.PS.029.D1.02 *085R9464* 1. Introduction Contents

More information

CS3000 MMI SW-Version 6.1 Control and Configuration Software for FlexPak3000 V , GV3000 V and Liqui-Flo. Instruction Manual

CS3000 MMI SW-Version 6.1 Control and Configuration Software for FlexPak3000 V , GV3000 V and Liqui-Flo. Instruction Manual CS3000 MMI SW-Version 6.1 Control and Configuration Software for FlexPak3000 V2.0-4.3, GV3000 V2.0-6.0 and Liqui-Flo Instruction Manual Manual P/N: 899.05.84 Firmware P/N: 788.05.30 User Manual: 49 1307e

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Date 18/05/17. Operation and maintenance instructions for driver configurator QSet

Date 18/05/17. Operation and maintenance instructions for driver configurator QSet Operation and maintenance instructions 28 1. General recommendations The recommendations regarding safe use in this document should be observed at all times. Some hazards can only be associated with the

More information

MLP (Multi-Link Programming) SOFTWARE

MLP (Multi-Link Programming) SOFTWARE FOR REVISIONS 1.10 AND ABOVE Doc-6001005 Rev - 3380 USER'S GUIDE TO MLP (Multi-Link Programming) SOFTWARE CHATSWORTH, CALIFORNIA Multi-Link Programming software makes programming a chain of Sentex Infinity

More information

REX 521 Protection Relay Operator s Manual

REX 521 Protection Relay Operator s Manual REX 521 Industrial IT enabled products from ABB are the building blocks for greater productivity, featuring all the tools necessary for lifecycle product support in consistent electronic form. 1MRS 751107-MUM

More information

POWER VISION INSTRUCTION MANUAL

POWER VISION INSTRUCTION MANUAL NETWORK ANALYSIS SOFTWARE POWER VISION INSTRUCTION MANUAL (M98135801-03-11B) CIRCUTOR S.A. INDEX 1.- POWER VISION SOFTWARE INSTALLATION... 4 2.- INTRODUCTION TO POWER VISION... 12 3.- COMMUNICATIONS...

More information

IDM DATA ACQUISITION SYSTEM

IDM DATA ACQUISITION SYSTEM DATA ACQUISITION SYSTEM The a compact and economical multifunction data acquisition system Rendering all Unrivalled product profile Advanced multifunctional distributed data acquisition system Fully multitasking

More information

VAMP 221. Table of Contents

VAMP 221. Table of Contents 2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,

More information

180 Series Keypad. Handbook. Revision 2.1

180 Series Keypad. Handbook. Revision 2.1 180 Series Keypad Handbook Revision 2.1 Revision History Revision 1.0 Initial release Revision 2.0 Major update with addition of 180-40 Added 180-40 to document and various headings Note regarding unique

More information

MT8001 MP4.20 Management Terminal

MT8001 MP4.20 Management Terminal MT8001 MP4.20 Management Terminal Localisation guide Building Technologies Data and design subject to change without notice. Supply subject to availability Copyright by Siemens AG Building Technologies

More information

IBIS-E. Parameterization software for Contrans E SU. Short manual 42/28-37 EN Rev. 0.0

IBIS-E. Parameterization software for Contrans E SU. Short manual 42/28-37 EN Rev. 0.0 IBIS-E Parameterization software for Contrans E SU Short manual 42/28-37 EN Rev. 0.0 Contents Page Application and description... 3 Remarks on terminology The types of displays listed below are utilized

More information

Relay Setting Tools CAP 501 Operator s Manual

Relay Setting Tools CAP 501 Operator s Manual Relay Setting Tools CAP 501 Operator s Manual $%% 1MRS751271-MUM Issue date: 31.01.2000 Program revision: 2.0.0 Documentation version: B CAP 501 Relay Setting Tools Operator s Manual Copyright 2000 ABB

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

Manual SmartGraph for Humlog 10

Manual SmartGraph for Humlog 10 Manual SmartGraph for Humlog 10 State: 10.12.2001 Version: V1.0 1 1 INTRODUCTION TO SMARTGRAPH... 4 1.1 Manage, Configure... 4 1.2 The Programme Interface... 4 1.2.1 Graphs... 5 1.2.2 Table... 6 1.2.3

More information

Relion 670 series. Busbar protection REB670 Operator's manual

Relion 670 series. Busbar protection REB670 Operator's manual Relion 670 series Busbar protection REB670 Document ID: 1MRK 505 179-UEN Issued: June 2010 Revision: C Product version: 1.1 Copyright 2010 ABB. All rights reserved Copyright This document and parts thereof

More information

7SR11 and 7SR12 Settings and Instruments

7SR11 and 7SR12 Settings and Instruments 7SR11 and 7SR12 Settings and Instruments Document Release History This document is issue 2012/01. The list of revisions up to and including this issue is: 2012/01 Software Maintenance 2011/06 Software

More information

Analogue Signal Transmitter AST 3 From prog.name A001A140. Operating instructions, Quick installation

Analogue Signal Transmitter AST 3 From prog.name A001A140. Operating instructions, Quick installation GB Analogue Signal Transmitter AST 3 From prog.name A001A140 Operating instructions, Quick installation Operating instructions, Quick operation Contents Introduction... 1 Operating instruction General...

More information

Installation and commissioning manual REL 505-C1*2.3 Overcurrent protection terminal

Installation and commissioning manual REL 505-C1*2.3 Overcurrent protection terminal Installation and commissioning manual REL 505-C1*2.3 Overcurrent protection terminal About this manual DocID: 1MRK 506 094-UEN Issue date: June 2001 Status: New Version: 2.3 Revision: 00 ABB Automation

More information

2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM

2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM 2214 EVENT LOGGER MODULE FOR THE VX2200 SYSTEM CONTENTS PAGE Manual Introduction 3 Product Overview 3 Operation and Connection 3 RS232 Connection 3-4 RS485 Connection 3-4 2214 PCB layout 5 RS485 Bus Terminal

More information

READ THIS INFORMATION FIRST Product: Remote IO Manager Software Release Remote IO Manager w/ Cable. Remote IO Manager Branding Toolkit.

READ THIS INFORMATION FIRST Product: Remote IO Manager Software Release Remote IO Manager w/ Cable. Remote IO Manager Branding Toolkit. May 16, 2002 IMPORTANT PRODUCT INFORMATION READ THIS INFORMATION FIRST Product: Remote IO Manager Software Release 2.03 IC641CFG100E IC641CFG101E IC640CFG200E Remote IO Manager. Remote IO Manager w/ Cable.

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

Synchro-check relay. Application

Synchro-check relay. Application Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to

More information

100% electricity. Automatic transfer switch controllers ATL series

100% electricity. Automatic transfer switch controllers ATL series 100% electricity Automatic transfer switch controllers ATL series Automatic transfer switch controllers Keep control around the clock General characteristics Rated auxiliary power supply: 220-230-240VAC

More information

Installation / Set-up of Autoread Camera System to DS1000/DS1200 Inserters

Installation / Set-up of Autoread Camera System to DS1000/DS1200 Inserters Installation / Set-up of Autoread Camera System to DS1000/DS1200 Inserters Written By: Colin Langridge Issue: Draft Date: 03 rd July 2008 1 Date: 29 th July 2008 Page 1 of 25 Installation Instructions

More information

Installation and Programming Manual

Installation and Programming Manual IBSM Manual IBSM Installation and Programming Manual This Manual describes the IBSM InterBus-S Master, its uses and set up. It also describes the use of the IBSM configuration software. Effective: 12 June,

More information

SERVICE TOOL MAP110 USER MANUAL. Landis+Gyr. H c en

SERVICE TOOL MAP110 USER MANUAL. Landis+Gyr. H c en SERVICE TOOL Landis+Gyr MAP110 USER MANUAL H 71 0200 0332 c en Revision History Index Date Comments a 28.02.2005 First edition b 31.05.2005 Changes to release 1.1 c 22.09.2005 Changes to release 1.2 subject

More information

ACCESS 3000 COMPACT (RPE920 ENCODER) SUPERVISOR S GUIDE

ACCESS 3000 COMPACT (RPE920 ENCODER) SUPERVISOR S GUIDE Multitone Electronics plc 2005 ACCESS 3000 COMPACT (RPE920 ENCODER) SUPERVISOR S GUIDE Part No. 9261-7849 Issue 1 Access 3000 Compact Supervisor s Guide 9261-7849 Issue 1 Page 2 This guide is for use with

More information

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy Reyrolle Protection Devices 7SG117 Argus 7 Synchronising Relay Answers for energy 7SG117 Argus 7 Synchronising Relay Fig 1. Independent check & system synchronising settings Adjustable slip frequency,

More information

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology This manual is suitable for HGM9580 bus tie bus parallel unit only. Clarification of notation used within this publication. SIGN INSTRUCTION

More information

DS-4483 Standard Logger Program Quick Reference For Software Version: 4.06

DS-4483 Standard Logger Program Quick Reference For Software Version: 4.06 DS-4483 Standard Logger Program Quick Reference For Software Version: 4.06 Requires Firmware Version: VL/2.17+ Revision History: Version 1.00 02 February 2004 Preliminary release version Version 4.01 21

More information

PC CONFIGURATOR Model: 27HUCFG. Users Manual , Minamitsumori, Nishinari-ku, Osaka JAPAN Tel: Fax:

PC CONFIGURATOR Model: 27HUCFG. Users Manual , Minamitsumori, Nishinari-ku, Osaka JAPAN Tel: Fax: Model 27HU Universal Temperature Transmitter PC CONFIGURATOR Model: 27HUCFG Users Manual 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Tel: +81-6-6659-8201 Fax: +81-6-6659-8510 http://www.m-system.co.jp/

More information

/TLC. Additional Manual for TEX-LCD series and TEX-LIGHT series. Manufactured by

/TLC. Additional Manual for TEX-LCD series and TEX-LIGHT series. Manufactured by Additional Manual for TEX-LCD series and TEX-LIGHT series Manufactured by Italy File Name: 03_TLC_ING_1.0.indd Version: 1.0 Date: 01/02/2008 Revision History Date Version Reason Editor 01/02/2008 1.0 Prima

More information

F650 Firmware Release Notes / History (Rev 10)

F650 Firmware Release Notes / History (Rev 10) 1.00 2.00 First version of the product (Basic Model F1G0) Full protection scheme F650BABF1G0HI August 30 th 2002 1.11 2.00 New model F2G0 (inputs and outputs board type 2) F650BABF2G0HI October 14 th 2002

More information

AQTIVATE CONFIGURATION TOOL FOR AQ-300 DEVICES

AQTIVATE CONFIGURATION TOOL FOR AQ-300 DEVICES AQTIVATE CONFIGURATION TOOL FOR AQ-300 DEVICES AQtivate configuration tool for AQ-300 devices 2 (120) Revision 1.00 Date April 2011 Changes The first revision. Revision 1.01 Date 13.2.2015 Changes Added

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

Sostenuto 4.1 title page. System Management User s Guide

Sostenuto 4.1 title page. System Management User s Guide Sostenuto 4.1 title page System Management User s Guide Date: November 2013 All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, or stored in any

More information

LON bus communication devices 1MRS MBG Page 1 Issued: April 1999 Status: New Data subject to change without notice

LON bus communication devices 1MRS MBG Page 1 Issued: April 1999 Status: New Data subject to change without notice LON bus communication devices Page 1 Issued: April 1999 Status: New Data subject to change without notice Features The LonWorks Network is an open system adapted for various application areas Peer-to-peer

More information

Codesoft 6 Premier Overview Manual. Thermocode Series 2 (all Printers)

Codesoft 6 Premier Overview Manual. Thermocode Series 2 (all Printers) Thermocode Series 2 Codesoft Overview Manual. (Issue 4.1) 28 July 2003 Page No. - 1 - Open Date Equipment Ltd. Unit s 8 & 9 Puma Trade Park, 145 Morden Road, Mitcham, Surrey. CR4 4DG United Kingdom. Tel:-

More information

Distribution Management System Open++ Opera v.3.3. User Manual

Distribution Management System Open++ Opera v.3.3. User Manual Distribution Management System Open++ Opera v.3.3 User Manual 1MRS 751464-MUM Issued: 31.12.1999 Version: D/29.8.2003 Program Revision: 3.3D We reserve the right to change data without prior notice. User

More information

Norstar Voice Mail 3.0 Software Maintenance Manual

Norstar Voice Mail 3.0 Software Maintenance Manual This document was created with FrameBuilder 4.0.4 Norstar Voice Mail 3.0 Software Maintenance Manual Norstar is a trademark of Northern Telecom Copyright Northern Telecom 1997 1-800-4 NORTEL www.nortel.com/norstar

More information

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied:

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied: 1) IED Protection and Control Manager PCM 600 Tool (SEP-601) PCM 600 Introduction and Overview Application Configuration Tool (CAP 531) Signal Matrix Tool, SMT Graphical Display Editor, GDE Parameter Setting

More information