Influences of corner surface temperatures

Size: px
Start display at page:

Download "Influences of corner surface temperatures"

Transcription

1 Influences of corner surface temperatures 1 Research goal Risk of condensation and mould growth at interior construction surfaces are largely influenced by the relative humidity at the surfaces. Often the temperature of indoor corner surfaces against the façade is a bit lower than the mean wall surface temperature during heating season. Because lower temperatures result in higher relative humidity s, these corner surfaces could be risk areas for mould growth, as can be seen in Fig. 1. The goal of this study is to receive more insight in the temperature distribution by corner surfaces and the factors that influence this.

2 2 Theoretical background Beside visual and mechanical damage, condensation and mould growth can also lead to respiratory problems. Fungal spores contaminate the air and can cause health complaints when they are inhaled. Fig. 1 Corner surfaces with mould grow A rough criterion to prevent mould growth is that the monthly mean relative humidity at the surfaces must be lower than 80%. When this condition is met, the risk of mould growth is acceptable, but still not excluded. Because it is difficult or impossible in many cases to determine whether these conditions are met, a simplified standard to determine the risk of mould growth has been developed. The most obvious choice for a standard to prevent moisture problems would have been to make a standard for the lowest admissible surface temperature calculated with the standard climate. The Temperature Ratio is a dimensionless quantity, which is used in the Dutch building code. The calculated temperature ratio is a value between 0 and 1, this represents a scale between respectively high to low risk of moisture problems. The temperature ratio is defined as: With: f n = T si T e T a T e T si = T e = T a = lowest interior surface temperature [K or ⁰C]; effective outdoor temperature [K or ⁰C]; indoor air temperature [K or ⁰C]; The standard climate in the Netherlands is given as an effective outdoor temperature of 0⁰C and a reference indoor air temperature of 18⁰C (at 1,7m. above the floor in middle of the room). When the ratio f n >= 0.65, the risk of moisture problems is called acceptable. So the lowest surface temperature T si should be higher than 11,7⁰C. At the reference temperatures and an indoor relative humidity of 53%, this means that the R.H. at the surface is 80%. When the heat flow through the construction is one-dimensional, and the temperature ratio is known, the surface temperature can be easily determined for all different outdoor and indoor air 2

3 temperatures. Also when the thermal conductivity of the structure is known, the interior surface temperature can be calculated for all values of outdoor and indoor air temperatures, when indoor and outdoor surface heat coefficients are well estimated: With: R i R m R m T s = T R i + R e + T m R i + R i = T e + (T m R i + R i T e ) m T s = interior surface temperature [K or ⁰C]; T e = exterior air temperature [K or ⁰C]; T a = indoor air temperature [K or ⁰C]; R m = Total thermal resistance between the surface and exterior air [m 2.k /W]; R i = Surface heat transfer resistance at the inside [m 2.k /W]; Note that the surface temperature is strongly dependent on the indoor surface coefficient of heat transfer. Even though this coefficient is mostly considered as a constant value by heat loss calculations, it should not been done by evaluating risk of moisture problems. Especially in corners this coefficient differs from open surfaces due to a difference in radiation exchange, caused by an aberrant view factor with another (mostly lower) average ambient temperature. Also the airflow velocities near the corners differ from the mean intern airflow. These influences will be examined during this study. Besides the problem of uncertain surface coefficients of heat transfer at indoor corners, the heat flow through the construction is not one-dimensional and often adjacent to several external temperatures like: outside air, ground or adjacent room temperature. In this case we can use superposition to determine a general solution for the corner surface temperature at a certain position, for all different bordering temperatures. When there are n different bordering temperatures, we need n-1 different temperature-independent functions. Let a structure be bounded by n different bordering temperatures T e1, T e2,..,t en. Then: 1 k n λ k ( T ) n k = h ek (T ek T sk ) Suppose a k (x,y,z) T ek is the solution of the differential equations where, except for the surface, all bordering temperatures equal zero. From linearity of the equations with boundary conditions then follows that a k (x,y,z) is a solution of the equations with: T ek =1 and other boundary temperatures are 0. If we do this for all surfaces in a 3-dimensial case, the general solution is: n T(x, y, z) = a k (x, y, z) T ek k=1 The functions a i (x,y,z) are independent of the bordering temperatures. If T ek = T e for 1 i n then also: T(x,y,z)=T e, so: n a k (x, y, z) = 1 k=1 3

4 We have applied the superposition method on a practical example. We assumed an indoor corner whose construction is bordered to the outdoor temperature and an unheated room. The wall is only insulated on the outside. We use COMSOL Multiphysics to simulate this corner construction with exposition to four different ambient temperatures as can be seen in Fig. 2. We use the simulated corner surface temperatures of the first two simulation variants to calculate the a k (x,y,z) with superposition. After that, we use these constant values to calculate the corner surface temperature, which should apply for the ambient air temperatures as were simulated in variant 4. This calculated value which is obtained by superposition, will be compared with the simulation result of variant 4. Fig. 2 Simulation variants with used ambient air temperatures The construction properties we have applied to the simulations are: Concrete walls: Thickness= 20 cm Lambda λ= 2 W/m.K h e = 25 W/m 2.k Insulation material: (against outside wall) Thickness= 10 cm Lambda λ= 0,04 W/m.K h i = 7,7 W/m 2.k 4

5 In Fig. 3 the simulated construction temperatures were visualized, the concerning corner surface temperatures are also given. Fig. 4 shows also the corresponding heat flux streamlines. Fig. 3 Simulation results: construction and indoor corner surface temperature Fig. 4 Simulation results: construction temperature and heat flux streamlines For the superposition method we use only the first two simulated corner temperatures to determine the other concerning temperatures: Ts = a1 T e 1 + a2 T e 2 + a3 T e 3 Ts variant 1 = 1,62⁰C = a1 0 + a2 5 + a3 0 So: a2= 0,324 Ts variant 2 = 12,77⁰C = a a2 0 + a3 0 So: a1= 0,639 5

6 n a k (x, y, z) = 1 Thus: a3 = 1 a1 a2 = 1 0, ,324 = 0,038 k=1 Variant 3: Ts = a1 0 + a ,038 ( 10) = 0,38⁰C (Simulated temperature is 0,38⁰C) Variant 4: Ts = 0, , ,038 ( 10) = 14,02⁰C (Simulated temperature is 14,00⁰C) So the calculated values are in good agreement with the simulation results. As we mentioned before, the surface temperature is strongly dependent on the indoor surface coefficient of heat transfer. This coefficient is mostly considered as a constant value. In Fig. 5 the indoor and outdoor surface coefficients of heat transfer were shown, which were usually used for heat loss calculations in the Netherlands: Fig. 5 Surface heat transfer coefficients, used for heat loss calculations Fig. 6 also shows a table with surface coefficients of heat transfer. These were used for power calculations of thermal activated elements such as concrete core activation. The temperature difference between surface and air in all these cases is 5 ⁰C. Distinction is made in heating or cooling function and between ceiling, floor and wall elements. 6

7 Fig. 6 Surface heat transfer coefficients, used for thermal power supply calculations of thermal activated slabs [2] When we need more accurate values, the separate heat transfer coefficients for radiation and convection can be approached by the following formulas (isso-pub.48): Heat transfer coefficient by free convection Depend on the situation and direction of energy flow, Floor heating/ceiling cooling: h c = 2 T 0,31 Floor cooling /ceiling heating: h c = 0,54 T 0,31 Vertical slab, wall cooling/heating: With: h c = 1,6 T 0,31 T= [W/(m 2.K)] [W/(m 2.K)] [W/(m 2.K)] the temperature difference between surface in indoor air temperature. Where: With: Heat transfer coefficient by radiation h r = 4 C T 3 [W/(m 2.K)] C = the resulting radiation constant = ε 1 ε 2 σ [W/(m 2.K 4 )] ε 1 and ε 2 = the emission coefficients of respectively the considered slab and the other interior surfaces. σ = the Stefan-Boltzmann constant= 5,67*10-8 [W/(m 2.K 4 )] T= the mean temperature of the considered slab and other interior surfaces [k]. 7

8 This method is used for good approximations. When an even more accurate value is necessary, the radiation exchange between the considered slab and other interior surfaces should be calculated, taking into account the surface temperatures, view factors and emission factors. The simulations out of this study should give insight in the factors that influence temperature differences along internal construction surfaces. 3 Method We use the software program COMSOL Multiphysics 4.1 to make computer simulations of the heat flow problems. Herewith we try to find out which influence several factors have on the interior temperature difference between mean slab surface temperature and corner surface temperatures. The influence factors that were considered in this study are: Surface area ratio between inside and outside the corner. Because the one-room model is a cubic, the external surface areas are greater than the interior surfaces, because the construction elements have a certain thickness. We also simulate variants with the same effective intern and extern surface area. Simulations with constant surface transfer coefficients for convection and radiation. These constant coefficients were combined with a constant interior air temperature. Free convection caused by temperature differences. The air density depends on the air temperature and is entered by the ideal gas law. In case of free convection, a heating volume inside the room provides the energy to the air. Surface tot surface radiation between the construction elements (empty room). Surface to surface radiation between construction elements themselves and a warm internal surface. We use a sphere in the middle of the room, which propose the internal warm objects like furnishing. By introducing or leaving out these factors into the simulations, we should be able to derive the separate influences from the results. The simulations were done on a simple one-room building with dimensions (H,W,D) 3,4 x 4 x 4m. The construction elements are 20 cm thick and have a thermal resistance (Rc) of 2,5 m 2.K/W. Unfortunately, the simulations with CFD failed in this three-dimensional model. So we used a twodimensional model of this construction, to investigate the influence of free convection with the CFD module. 8

9 We assume that the outside room-model boundaries are everywhere adjacent to an outside air temperature of -10⁰C. So this factor should not result in surface temperature differences at the inside. More information about the models is given in the Model section. The different simulation variants in this study are visualized in Table 1: Table 1 Simulation variants in this study (total 19) Nr 2D or 3D Constant heat transfer coefficient hc (convection) hr (radiation) Free convection Radiation between: Construction And warm elements indoor surface Equal indoor/ outdoor surface area 1 2D X X X 2 2D X X 3 2D X 4 2D X X X X 5 2D X X X 6 2D X X 7 2D X X 8 2D X(different) X 9 2D X 10 2D X X X 11 2D X X 12 2D X X X X 13 2D X X X 14 3D X X X 15 3D X X 16 3D X 17 3D X X X X 18 3D X X X 19 3D X X 9

10 4 The model The physical modules in Comsol that are applied in this study to solve this heat problem are: Surface to surface radiation Heat Transfer in fluids and solids Non-Isothermal (laminar) Flow Geometry and mesh properties The symbol (*) means that the indicated property mentioned below is not applied in all the simulation variants. 2-D Model Dimensions [m]: Indoor air square (WxH) = 3,6x3,0 Thickness floor, ceiling and wall elements = 0,2 * Circle in middle of the of room (diameter) = 1 *Heat source Ellipses (semiaxis a x b ) = 0.1 x 0,3183 Fig. 7 visualizes the two-dimensional model of the one-room building. The colours in this picture indicate the different thermal conductivities of the materials. The red circle in the middle represents the warm interior surface, which exchanges radiated energy with the construction surfaces. The two white ellipses represent convective heat sources that supply warmth to the air. The air is indicated as the large blue area. The light blue rectangles on sides are the construction elements: walls, ceiling and floor. In some simulation variants, the edges of these elements are modified to high insulated material, to get the same effective outside surface area as on the inside for heat conduction. Fig. 7 Visualization of the 2D model 10

11 3-D Model Dimensions [m]: Indoor air block (WxDxH) = 3,6x3,6x3,0 Thickness floor, ceiling and wall elements = 0,2 *Sphere in middle the of room (diameter) = 1 Fig. 8 shows the three-dimensional model of the one-room building. The colours in the slice frames indicate the different thermal conductivities of the materials. The air is excluded because this model containts no CFD study. This is replaced by imitated boundary conditions. Fig. 8 Visualization of the 3D model Note that some properties, which are present in the pictures above, are not applicable for all the simulation variants. 11

12 Mesh settings: The mesh of the complete 2D construction consists of elements, and the 3D construction of elements. Fig. 9 shows the mesh statistics of the 2D model and the mesh geometry is visualized in Fig. 10. The statistics of the 3D model were present in Fig. 11: Fig. 9 Mesh statistics of the 2D model Fig. 10 Mesh geometry of the 2D simulation model Fig. 11 Mesh statistics of the 3D model Fig. 12 Mesh geometry of the 3D simulation model 12

13 Boundary Conditions Convective Cooling: Air temperature outdoor (outside boundaries) = K (outside boundaries) Surface heat transfer coefficient outside = 25 W/m 2.K (outside boundaries) *Constant Air temperature inside = 3D-Models: K; 2D-Models: K (Only in combination with constant surface heat transfer coefficients) *Constant surface heat transfer coefficients (inside wall and ceiling surfaces): h c +h r = 7,7 W/m 2.K (convection + radiation), h c = 3,0 W/m 2.K (only convection) *Constant surface heat transfer coefficients (inside floor surface): h c +h r = 6,0 W/m 2.K (convection + radiation), h c = 1,3 W/m 2.K (only convection) *Constant temperature (exclusive CFD variants) = K (surface circle/sphere) *Surface tot surface radiation (method: Hemicube): Between construction element surfaces and circle/sphere surface. Emissivity surfaces ε : = 0,9 Ambient temperature: = T *Non-isothermal Flow Laminar airflow Air volume boundary conditions = No slip Air Volume Force (density differences) = Total Volume heat sources = 190W per meter depth (2D model) (spread over one or more ellipses) Material Properties and Initial Condition Thermal conductivity k: Construction elements = 0,08 [W/m.K] *Indoor circle/sphere = 0,5 [W/m.K] *High insulation corner elements = [W/m.K] 13

14 *Air = E-4*(T)^ E-8*(T)^ E- 11*(T)^ E-15*(T)^4 [W/m.K] Density ρ: Construction elements = 2300 [kg/m 3 ] *Indoor circle/sphere = 1500 [kg/m 3 ] *High insulation corner elements = 500 [kg/m 3 ] *Air = nitf.pa*mw_a/(r_const*(t)) [kg/m 3 ] (nitf.pa = absolute pressure, Mw_a= molar mass=28.97[g/mol], R_const=general gas constant) Heat capacity at constant pressure C p : Construction elements = 840 [J/(kg*K)] *Indoor circle/sphere = 700 [J/(kg*K)] *High insulation corner elements = 300 [J/(kg*K)] Air = *(T)^ E - 4*(T)^ E-7 * (T)^ E-10 * (T)^4 [J/(kg*K)] P ref = 1 [atm.] Solver Settings Except the simulations that include CFD, all simulations were done with a stationary solver. 2-Dimensional Models, Time Dependent solver: Type of analysis: Non-isothermal flow (nitf) Relative tolerance: 0,01 Simulation time range: range(0,0.1,5) range(5,0,2,15) range(15,0,5,60) range(60,1,1000) range(1000,3,1800) range(1800,5,3600) range(3600,10,4*3600). 3-Dimensional Models, Stationairy solver: Type of analysis: Conjugate heat transfer (nitf) Relative tolerance: 0,001 14

15 5 Results In this result section a part of the total simulation results are presented. These results give a good representation of the influences caused by the separate factors to the surface temperature distribution. All the other results are presented in the appendix and some movies from the CFDsimulations are attached as digital appendix. Variant 16. This 3D variant is simulated with only a constant surface coefficient of heat transfer for convection (hc). The model has different inside and outside surface areas. Radiation and CFD is not included. Graphs 1 Surface temperatures variant 16; Ceiling (left) and Floor (right) 15

16 Variant 3. This 2D variant is simulated with only a constant surface coefficient of heat transfer for convection (hc). The model has different inside and outside surface areas. Radiation and CFD is not included. Graphs 2 Surface temperatures variant 3; Ceiling (left) and Floor (right) Variant 19. This 3D variant is simulated with only a constant surface coefficient of heat transfer for convection (hc). The model has different inside and outside surface areas. Radiation exchange between the construction elements is analyzed. CFD is not included. Graphs 3 Surface temperatures variant 19; Ceiling (left) and Floor (right) 16

17 Variant 11. This 2D variant is simulated with only a constant surface coefficient of heat transfer for convection (hc). The model has different inside and outside surface areas. Radiation exchange between the construction elements is analyzed. CFD is not included. Graphs 4 Surface temperatures variant 11; Ceiling (left) and Floor (right) Variant 18. This 3D variant is simulated with only a constant surface coefficient of heat transfer for convection(hc). The model has different inside and outside surface areas. Radiation exchange between construction surfaces themselves and the warm indoor surface is analyzed. CFD is not included. Graphs 5 Surface temperatures variant 18; Ceiling (left) and Floor (right) 17

18 Variant 13. This 2D variant is simulated with only a constant surface coefficient of heat transfer for convection (hc). The model has different inside and outside surface areas. Radiation exchange between construction surfaces themselves and the warm indoor surface is analyzed. CFD is not included. Graphs 6 Surface temperatures variant 13; Ceiling (left) and Floor (right) Variant 7. This 2D variant is simulated without radiation or constant surface coefficients of heat transfer. The model has the same outside surface area as the inside. Free convection is included. Graphs 7 Surface temperatures variant 7; Ceiling (left) and Floor (right) 18

19 Variant 8. This 2D variant is simulated without radiation or constant surface coefficients of heat transfer. The model has the same outside surface area as the inside. Free convection is included, but the air is heated in a different way than in the other simulation variants with CFD. Graphs 8 Surface temperatures variant 8; Ceiling (left) and Floor (right) 19

20 6 Conclusion & Discussion Conclusion Based on the simulation results we can conclude that all simulated influencing factors are visible on the inside surface temperatures. They also provide good information about the separate influences of the different factors in our 2D and 3D model. So the main cause of surface temperature difference is the surface area ratio between inside and outside. The larger outside surface area in the corners causes a larger heat flux in the construction near the inside corner surface, so the temperature drops until it is ca. 6⁰C beneath the surface temperature in the middle. When we look at the influence of radiation in an empty room, the simulations show that the temperature differences will be flattened. Due to the exchange of radiated energy between hot and cold surfaces the temperatures approach each other a bit. The cold corners and floor surfaces has a negative radiative heat flux, which implies that they absorb more radiated energy than they emit. So the surface temperatures in the corners and middle of the floor could rise up to ca. 2⁰C. The surface temperature in the middle of the ceiling decreases more than the surface temperature towards the borders of the ceiling, because the view factor to the cold floor is larger in the middle of the ceiling. The floor surface is colder, because the constant surface coefficient of heat transport by convection, that we have entered, is 2.7 W/m 2.K lower than for the ceiling and the walls. In the simulations that include CFD, the surfaces do not have such a constant coefficient, but the floor surface temperatures are also lower than the others because of the air temperature gradient and the cold construction element surfaces. Simulations with a warm surface (circle/sphere) in the middle of the room, with a temperature almost equal to the air temperature, are done to imitate the influence of warm indoor surfaces from e.g. furniture on construction surface temperatures. Because the view factor of this warm surface is larger to the middle of the construction elements than towards the corners, the radiation exchange is greater towards the middle. As result the temperature in the middle of the surface will increase up to ca. 0,5⁰C more than towards the corners of the surface. The influence of free convection on the surface temperatures is quite large. It causes peaks of temperature differences up to ca. 6⁰C. The temperature pattern is strongly dependent on the way the air is heated. In the discussion section the realization of those temperature profiles due to free convection will be further discussed. 20

21 Discussion Even though the simulation results give us good insight in the influence of the different factors, the effects in practice are still strongly dependent on building geometry, building physics properties and the way of air treatment. Also the interior of a room could have great influences on radiation exchange and the convective air streams. Unfortunately it was not possible to simulate the effect of free convection in the threedimensional model. This means that the results out the 2D-model only give information about the surface temperature difference near the corners of two perpendicular construction elements. It is likely that the differences are greater in corners of three perpendicular elements. Most likely the airflow will be lower in these 3D corners. Because the simulations with free convection (CFD) were not stationary and include heat sources in the room instead of a constant indoor air temperature, there is fairly large difference between the final air temperatures. This also influenced the construction surface temperature, so keep this in mind during comparing the simulation variants. Because we are mainly interested in the temperature differences along the surfaces, this is not a big problem. Comparing the surface temperatures out of simulation variants with constant surface coefficients of heat transfer (hc &hr) and surface temperatures out of the variants that include simulated radiation and free convection, we can conclude that the constant coefficients which we implemented are too high for our models. The constant coefficients that we have used are: - Ceiling and walls: h radiation = 4,7 W/m 2.K; h convection = 3,0 W/m 2.K - Floor: h radiation = 4,7 W/m 2.K; h convection = 1,3 W/m 2.K These constants were coupled with the constant air temperature. The radiation coefficient is possibly too high, because all surfaces have nearly the same temperature. In our models all construction elements border the cold outdoor air. In practice most rooms also contain warm indoor construction elements and more other warm surfaces when it is furnished etc. The total main surface temperature is than closer to the air temperature. Also the convective heat transfer is probably greater in practice, because the effect of natural and/or mechanical ventilation on the air velocity. The results show a recurring surface temperature pattern in the simulation variants with free convection. Temperature peaks arise toward the ceiling corners, which also collapse just before the corner, as we can see for example in Graphs 7. In the middle of the ceiling surface, there will also be a rise in temperature. This pattern probably arises because of the following phenomenon: The heat source in the air and the cold surfaces cause an ongoing circulation of the indoor air. The heated air rises up and displaces the local air downwards. The two main flow patterns how this is happen are shown in Fig. 14, Fig. 13 and Fig. 15. The warm airflow rises up from the middle or from the sides of the room and deflects near the ceiling. Note that the deflection point on the sides is a bit from the corner and that the airflow in the corner itself is lower. That would explain the decrease of temperature near the corner. 21

22 Fig. 14 Flow pattern from outside to inside Fig. 13 Flow pattern from inside to outside The temperature peaks near the sides of the floor surfaces can be explained by the displaced warm air from above, that drops down along the walls and deflects on the floor toward the heat source, as can be seen in the figures. The temperature peak on the floor surface does not drop down near the corner, because the wall temperature is higher than the floor temperature and the velocity in the lower corners is relative high compared the velocity elsewhere just above the floor. Fig. 15 Flow pattern from outside to inside with circle in the middle and two heat sources 22

23 Bibliography 1 M.h. de Wit, [2009]: Heat, air and moisture in building envelopes. Course book Eindhoven University of Technology: blz H.M. Bruggema, 2007; Vergelijking van systemen Betonkernactivering,klimaatplafonds, wand- en vloerverwarming. TVVL Magazine 3/

24 Annex 1: Simulation results with 2D-model 24

25 Variant 1. This 2D variant is simulated with constant surface coefficients of heat transfer (hc+hr) and with the same outside surface area as on the inside. Radiation and CFD is not included. The colors in the figure below indicate the temperature of the construction elements: Fig. 16 Temperature of construction elements The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 9 Ceiling surface temperature distribution (left); 25

26 Floor Surface: Graphs 10 Floor surface temperature distribution (left); Left Wall Surface: Graphs 11 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 12 Right wall surface temperature distribution (left); 26

27 Variant 2. This 2D variant is simulated with constant surface coefficients of heat transfer (hc+hr). The model has different inside and outside surface areas. Radiation and CFD is not included. The colors in the figure below indicate the temperature of the construction elements: Fig. 17 Temperature of construction elements The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 13 Ceiling surface temperature distribution (left); 27

28 Floor Surface: Graphs 14 Floor surface temperature distribution (left); Left Wall Surface: Graphs 15 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 16 Right wall surface temperature distribution (left); 28

29 Variant 3. This 2D variant is simulated with a constant surface coefficient of heat transfer for convection (hc) only. The model has different inside and outside surface areas. Radiation and CFD is not included. The colors in the figure below indicate the temperature of the construction elements: Fig. 18 Temperature of construction elements The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 17 Ceiling surface temperature distribution (left); 29

30 Floor Surface: Graphs 18 Floor surface temperature distribution (left); Left Wall Surface: Graphs 19 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 20 Right wall surface temperature distribution (left); 30

31 Variant 4. This 2D variant is simulated with a constant surface coefficient of heat transfer for convection (hc) only and with the same outside surface area as the inside. Also radiation exchange between construction themselves and warm indoor surface. CFD is not included. The colors in the figure below indicate the temperature of the construction elements: Fig. 19 Temperature of construction elements The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 21 Ceiling surface temperature distribution (left); 31

32 Floor Surface: Graphs 22 Floor surface temperature distribution (left); Left Wall Surface: Graphs 23 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 24 Right wall surface temperature distribution (left); 32

33 Variant 5. This 2D variant is simulated with a constant surface coefficient of heat transfer for convection (hc) only. The model has different inside and outside surface areas. Radiation exchange between construction themselves and warm indoor surface is analyzed. CFD is not included. The colors in the figure below indicate the temperature of the construction elements: Fig. 20 Temperature of construction elements The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 25 Ceiling surface temperature distribution (left); 33

34 Floor Surface: Graphs 26 Floor surface temperature distribution (left); Left Wall Surface: Graphs 27 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 28 Right wall surface temperature distribution (left); 34

35 Variant 6. This 2D variant is simulated with a constant surface coefficient of heat transfer for convection (hc) only. The model has different inside and outside surface areas. Radiation exchange between the construction elements is analyzed. CFD is not included. The colors in the figure below indicate the temperature of the construction elements: Fig. 21 Temperature of construction elements The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 29 Ceiling surface temperature distribution (left); 35

36 Floor Surface: Graphs 30 Floor surface temperature distribution (left); Left Wall Surface: Graphs 31 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 32 Right wall surface temperature distribution (left); 36

37 Variant 7. This 2D variant is simulated without radiation or constant surface coefficients of heat transfer. The model has the same outside surface area as the inside. Free convection is included. The colors in the figure below indicate the air temperature in the room: Fig. 22 Indoor air Temperature The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 33 Ceiling surface temperature distribution (left); 37

38 Floor Surface: Graphs 34 Floor surface temperature distribution (left); Left Wall Surface: Graphs 35 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 36 Right wall surface temperature distribution (left); 38

39 Variant 8. This 2D variant is simulated without radiation or constant surface coefficients of heat transfer. The model has the same outside surface area as the inside. Free convection is included, but the air is heated in a different way than in the other simulation variants with CFD. The colors in the figure below indicate the air temperature in the room: Fig. 23 Indoor air Temperature The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 37 Ceiling surface temperature distribution (left); 39

40 Floor Surface: Graphs 38 Floor surface temperature distribution (left); Left Wall Surface: Graphs 39 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 40 Right wall surface temperature distribution (left); 40

41 Variant 9. This 2D variant is simulated without radiation or constant surface coefficients of heat transfer. The model has different inside and outside surface areas. Free convection is included. The colors in the figure below indicate the air temperature in the room: Fig. 24 Indoor air Temperature The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 41 Ceiling surface temperature distribution (left); 41

42 Floor Surface: Graphs 42 Floor surface temperature distribution (left); Left Wall Surface: Graphs 43 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 44 Right wall surface temperature distribution (left); 42

43 Variant 10. This 2D variant is simulated without constant surface coefficients of heat transfer. The model has the same outside surface area as the inside. Radiation exchange between the construction elements is analyzed. Free convection is also included. The colors in the figure below indicate the air temperature in the room: Fig. 25 Indoor air Temperature The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 45 Ceiling surface temperature distribution (left); 43

44 Floor Surface: Graphs 46 Floor surface temperature distribution (left); Left Wall Surface: Graphs 47 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 48 Right wall surface temperature distribution (left); 44

45 Variant 11. This 2D variant is simulated without constant surface coefficients of heat transfer. The model has different inside and outside surface areas. Radiation exchange between the construction elements is analyzed. Also free convection is included. The colors in the figure below indicate the air temperature in the room: Fig. 26 Indoor air Temperature The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 49 Ceiling surface temperature distribution (left); 45

46 Floor Surface: Graphs 50 Floor surface temperature distribution (left); Left Wall Surface: Graphs 51 Left Wall surface temperature distribution (left); Right Wall Surface: Graphs 52 Right wall surface temperature distribution (left); 46

47 Variant 12. This 2D variant is simulated without constant surface coefficients of heat transfer. The model has the same outside surface area as the inside. Radiation exchange between construction themselves and warm indoor surface is analyzed. Free convection is also included. The colors in the figure below indicate the air temperature in the room: Fig. 27 Indoor air Temperature The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 53 Ceiling surface temperature distribution (left); 47

48 Floor Surface: Graphs 54 Floor surface temperature distribution (left); Left Wall Surface: Graphs 55 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 56 Right wall surface temperature distribution (left); 48

49 Variant 13. This 2D variant is simulated without constant surface coefficients of heat transfer. The model has different inside and outside surface areas. Radiation exchange between construction themselves and warm indoor surface is analyzed. Free convection is also included. The colors in the figure below indicate the air temperature in the room: Fig. 28 Indoor air Temperature The indoor surface heat fluxes and temperatures are shown in the following graphs: Ceiling Surface: Graphs 57 Ceiling surface temperature distribution (left); 49

50 Floor Surface: Graphs 58 Floor surface temperature distribution (left); Left Wall Surface: Graphs 59 Left wall surface temperature distribution (left); Right Wall Surface: Graphs 60 Right wall surface temperature distribution (left); 50

51 Annex 2: Simulation results with 3D-model 51

52 Variant 14. This 3D variant is simulated with constant surface coefficients of heat transfer (hc+hr) and with the same outside surface area as the inside. Radiation and CFD is not included. The colors in the figure below indicate the temperature of the indoor surfaces: Fig. 29 Temperatures of the indoor surfaces The temperatures of surface diagonals from ceiling and floor are shown in the graphs below: Graphs 61 Temperature of ceiling surface diagonals (left); Floor surface diagonals (right); 52

53 Variant 15. This 3D variant is simulated with constant surface coefficients of heat transfer (hc+hr). The model has different inside and outside surface areas. Radiation and CFD is not included. The colors in the two figures below indicate the temperature of the indoor surfaces: Fig. 30 Temperatures of the indoor surfaces 53

54 Fig. 31 Temperatures of the indoor surfaces The indoor temperatures of surface diagonals and borders from ceiling and floor are shown in the graphs below: Graphs 62 Temperature of ceiling surface diagonals and borders (left); Floor surface diagonals and borders (right); 54

55 Variant 16. This 3D variant is simulated with only a constant surface coefficient of heat transfer for convection (hc). The model has different inside and outside surface areas. Radiation and CFD is not included. The colors in the figure below indicate the temperature of the indoor surfaces: Fig. 32 Temperatures of the indoor surfaces The indoor temperatures of surface diagonals and borders from ceiling and floor are shown in the graphs below: Graphs 63 Temperature of ceiling surface diagonals and borders(left); Floor surface diagonals and borders (right); 55

56 Variant 17. This 3D variant is simulated without constant surface coefficients of heat transfer. The model has the same outside surface area as the inside. Radiation exchange between construction themselves and warm indoor surface is analyzed. CFD is not included. The colors in the two figures below indicate the temperature of the indoor surfaces: Fig. 33 Temperatures of the indoor surfaces 56

57 Fig. 34 Temperatures of the indoor surfaces The indoor temperatures of surface diagonals and borders from ceiling, floor and wall are shown in the graphs below: Graphs 64 Temperature of ceiling surface diagonals and borders (left), floor surface (middle) and wall surface diagonals (right); 57

58 The figures below visualize the net radiative heat flux and incoming irradiation of the inner surfaces: Ceiling Surface: Fig. 35 Radiative heat flux of the ceiling surface Fig. 36 Irradiation on the ceiling surface 58

59 Floor Surface: Fig. 37 Radiative heat flux of the floor surface Fig. 38 Irradiation on the floor surface 59

60 Wall Surface: Fig. 39 Radiative heat flux of the wall surface Fig. 40 Irradiation on the wall surface 60

61 Variant 18. This 3D variant is simulated with a constant surface coefficient of heat transfer for convection (hc) only. The model has different inside and outside surface areas. Radiation exchange between construction themselves and warm indoor surface is analyzed. CFD is not included. The colors in the two figures below indicate the temperature of the indoor surfaces: Fig. 41 Temperatures of the indoor surfaces 61

62 Fig. 42 Temperatures of the indoor surfaces The indoor temperatures of surface diagonals and borders from ceiling and floor are shown in the graphs below: Graphs 65 Temperature of ceiling surface diagonals and borders (left); Floor surface diagonals and borders (right); 62

63 The figures below visualizes the net radiative heat flux and incoming irradiation of the inner surfaces: Ceiling Surface: Fig. 43 Radiative heat flux of the ceiling surface Fig. 44 Irradiation on the ceiling surface 63

64 Floor Surface: Fig. 45 Radiative heat flux of the floor surface Fig. 46 Irradiation on the ceiling surface 64

65 Wall Surface: Fig. 47 Radiative heat flux of the floor surface Fig. 48 Irradiation on the wall surface 65

66 Variant 19. This 3D variant is simulated with a constant surface coefficient of heat transfer for convection (hc) only. The model has different inside and outside surface areas. Radiation exchange between the construction elements is analyzed. CFD is not included. The colors in the two figures below indicate the temperature of the indoor surfaces: Fig. 49 Temperatures of the indoor surfaces 66

67 Fig. 50 Temperatures of the indoor surfaces The indoor temperatures of surface diagonals and borders from ceiling and floor are shown in the graphs below: Graphs 66 Temperature of ceiling surface diagonals and borders (left); Floor surface diagonals and borders (right); 67

68 The figures below visualizes the net radiative heat flux and incoming irradiation of the inner surfaces: Ceiling Surface: Fig. 51 Radiative heat flux of the ceiling surface Fig. 52 Irradiation on the ceiling surface 68

69 Floor Surface: Fig. 53 Radiative heat flux of the floor surface Fig. 54 Irradiation on the floor surface 69

70 Wall Surface: Fig. 55 Radiative heat flux of the wall surface Fig. 56 Irradiation on the wall surface 70

Middle East Technical University Mechanical Engineering Department ME 413 Introduction to Finite Element Analysis Spring 2015 (Dr.

Middle East Technical University Mechanical Engineering Department ME 413 Introduction to Finite Element Analysis Spring 2015 (Dr. Middle East Technical University Mechanical Engineering Department ME 413 Introduction to Finite Element Analysis Spring 2015 (Dr. Sert) COMSOL 1 Tutorial 2 Problem Definition Hot combustion gases of a

More information

The benefits of FEM-SS-BES (Finite Element Method, State-Space, Building Energy Simulation) modeling exchange for building physics

The benefits of FEM-SS-BES (Finite Element Method, State-Space, Building Energy Simulation) modeling exchange for building physics The benefits of FEM-SS-BES (Finite Element Method, State-Space, Building Energy Simulation) modeling exchange for building physics A.W.M. (Jos) van Schijndel, R.P. (Rick) Kramer Department of the Built

More information

Free Convection in a Water Glass

Free Convection in a Water Glass Solved with COMSOL Multiphysics 4.1. Free Convection in a Water Glass Introduction This model treats free convection in a glass of water. Free convection is a phenomenon that is often disregarded in chemical

More information

TYPE 529: RADIANT SLAB

TYPE 529: RADIANT SLAB TYPE 529: RADIANT SLAB General Description This component is intended to model a radiant floor-heating slab, embedded in soil, and containing a number of fluid filled pipes. The heat transfer within the

More information

NUMERICAL CALCULATION OF MEAN RADIANT TEMPERATURE AND TEMPERATURE ASYMMETRY FOR COMPLEX ROOM GEOMETRY

NUMERICAL CALCULATION OF MEAN RADIANT TEMPERATURE AND TEMPERATURE ASYMMETRY FOR COMPLEX ROOM GEOMETRY Proceedings: Indoor Air 2 NUMERICAL CALCULATION OF MEAN RADIANT TEMPERATURE AND TEMPERATURE ASYMMETRY FOR COMPLEX ROOM GEOMETRY M Prek * University of Ljubljana, Faculty of Mechanical Engineering, Askerceva

More information

Convection Cooling of Circuit Boards 3D Natural Convection

Convection Cooling of Circuit Boards 3D Natural Convection Convection Cooling of Circuit Boards 3D Natural Convection Introduction This example models the air cooling of circuit boards populated with multiple integrated circuits (ICs), which act as heat sources.

More information

Non-Isothermal Heat Exchanger

Non-Isothermal Heat Exchanger Non-Isothermal Heat Exchanger The following example builds and solves a conduction and convection heat transfer problem using the Heat Transfer interface. The example concerns a stainless-steel MEMS heat

More information

Using the Discrete Ordinates Radiation Model

Using the Discrete Ordinates Radiation Model Tutorial 6. Using the Discrete Ordinates Radiation Model Introduction This tutorial illustrates the set up and solution of flow and thermal modelling of a headlamp. The discrete ordinates (DO) radiation

More information

CIBSE Application Manual AM11 Building Performance Modelling Chapter 6: Ventilation Modelling

CIBSE Application Manual AM11 Building Performance Modelling Chapter 6: Ventilation Modelling Contents Background Ventilation modelling tool categories Simple tools and estimation techniques Analytical methods Zonal network methods Computational Fluid Dynamics (CFD) Semi-external spaces Summary

More information

Comparison of Classic and Finned Piston Reciprocating Linear Air Compressor Using COMSOL Multiphysics

Comparison of Classic and Finned Piston Reciprocating Linear Air Compressor Using COMSOL Multiphysics Comparison of Classic and Finned Piston Reciprocating Linear Air Compressor Using COMSOL Multiphysics M. Heidari*, P. Barrade, and A. Rufer LEI, École Polytechnique Fédérale de Lausanne, Lausanne, Switzerland

More information

TUTORIAL#4. Marek Jaszczur. Turbulent Thermal Boundary Layer on a Flat Plate W1-1 AGH 2018/2019

TUTORIAL#4. Marek Jaszczur. Turbulent Thermal Boundary Layer on a Flat Plate W1-1 AGH 2018/2019 TUTORIAL#4 Turbulent Thermal Boundary Layer on a Flat Plate Marek Jaszczur AGH 2018/2019 W1-1 Problem specification TUTORIAL#4 Turbulent Thermal Boundary Layer - on a flat plate Goal: Solution for Non-isothermal

More information

Lab 9: FLUENT: Transient Natural Convection Between Concentric Cylinders

Lab 9: FLUENT: Transient Natural Convection Between Concentric Cylinders Lab 9: FLUENT: Transient Natural Convection Between Concentric Cylinders Objective: The objective of this laboratory is to introduce how to use FLUENT to solve both transient and natural convection problems.

More information

Heat Exchanger Efficiency

Heat Exchanger Efficiency 6 Heat Exchanger Efficiency Flow Simulation can be used to study the fluid flow and heat transfer for a wide variety of engineering equipment. In this example we use Flow Simulation to determine the efficiency

More information

Tutorial to simulate a thermoelectric module with heatsink in ANSYS

Tutorial to simulate a thermoelectric module with heatsink in ANSYS Tutorial to simulate a thermoelectric module with heatsink in ANSYS Few details can be found in the pictures attached. All the material properties can be found in Dr. Lee s book and on the web. Don t blindly

More information

Modelling of a Wall Inlet in Numerical Simulation of Airflow in Livestock Buildings

Modelling of a Wall Inlet in Numerical Simulation of Airflow in Livestock Buildings 1 Modelling of a Wall Inlet in Numerical Simulation of Airflow in Livestock Buildings B. Bjerg 1, K. Svidt 2, S Morsing 3, G. Zhang 3 and J. O. Johnsen 3 1 The Royal Veterinary and Agricultural University,

More information

First Steps - Conjugate Heat Transfer

First Steps - Conjugate Heat Transfer COSMOSFloWorks 2004 Tutorial 2 First Steps - Conjugate Heat Transfer This First Steps - Conjugate Heat Transfer tutorial covers the basic steps to set up a flow analysis problem including conduction heat

More information

Turbulent Premixed Combustion with Flamelet Generated Manifolds in COMSOL Multiphysics

Turbulent Premixed Combustion with Flamelet Generated Manifolds in COMSOL Multiphysics Turbulent Premixed Combustion with Flamelet Generated Manifolds in COMSOL Multiphysics Rob J.M Bastiaans* Eindhoven University of Technology *Corresponding author: PO box 512, 5600 MB, Eindhoven, r.j.m.bastiaans@tue.nl

More information

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data

More information

Chapter 13 RADIATION HEAT TRANSFER

Chapter 13 RADIATION HEAT TRANSFER Heat and Mass Transfer: Fundamentals & Applications Fourth Edition in SI Units Yunus A. Cengel, Afshin J. Ghajar McGraw-Hill, 2011 Chapter 13 RADIATION HEAT TRANSFER PM Dr Mazlan Abdul Wahid Universiti

More information

STAR-CCM+: Ventilation SPRING Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, 11 pm)

STAR-CCM+: Ventilation SPRING Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, 11 pm) STAR-CCM+: Ventilation SPRING 208. Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, pm). Features of the Exercise Natural ventilation driven by localised

More information

Computation of Velocity, Pressure and Temperature Distributions near a Stagnation Point in Planar Laminar Viscous Incompressible Flow

Computation of Velocity, Pressure and Temperature Distributions near a Stagnation Point in Planar Laminar Viscous Incompressible Flow Excerpt from the Proceedings of the COMSOL Conference 8 Boston Computation of Velocity, Pressure and Temperature Distributions near a Stagnation Point in Planar Laminar Viscous Incompressible Flow E. Kaufman

More information

Ashwin Shridhar et al. Int. Journal of Engineering Research and Applications ISSN : , Vol. 5, Issue 6, ( Part - 5) June 2015, pp.

Ashwin Shridhar et al. Int. Journal of Engineering Research and Applications ISSN : , Vol. 5, Issue 6, ( Part - 5) June 2015, pp. RESEARCH ARTICLE OPEN ACCESS Conjugate Heat transfer Analysis of helical fins with airfoil crosssection and its comparison with existing circular fin design for air cooled engines employing constant rectangular

More information

Influence of mesh quality and density on numerical calculation of heat exchanger with undulation in herringbone pattern

Influence of mesh quality and density on numerical calculation of heat exchanger with undulation in herringbone pattern Influence of mesh quality and density on numerical calculation of heat exchanger with undulation in herringbone pattern Václav Dvořák, Jan Novosád Abstract Research of devices for heat recovery is currently

More information

Microwell Mixing with Surface Tension

Microwell Mixing with Surface Tension Microwell Mixing with Surface Tension Nick Cox Supervised by Professor Bruce Finlayson University of Washington Department of Chemical Engineering June 6, 2007 Abstract For many applications in the pharmaceutical

More information

EN 10211:2007 validation of Therm 6.3. Therm 6.3 validation according to EN ISO 10211:2007

EN 10211:2007 validation of Therm 6.3. Therm 6.3 validation according to EN ISO 10211:2007 Therm 6.3 validation according to EN ISO 10211:2007 Therm 6.3 validation according to NBN EN ISO 10211:2007 eneral considerations and requirements for validation of calculation methods according to NBN

More information

NUMERICAL ANALYSIS OF WIND EFFECT ON HIGH-DENSITY BUILDING AERAS

NUMERICAL ANALYSIS OF WIND EFFECT ON HIGH-DENSITY BUILDING AERAS NUMERICAL ANALYSIS OF WIND EFFECT ON HIGH-DENSITY BUILDING AERAS Bin ZHAO, Ying LI, Xianting LI and Qisen YAN Department of Thermal Engineering, Tsinghua University Beijing, 100084, P.R. China ABSTRACT

More information

Modeling and Simulation of Single Phase Fluid Flow and Heat Transfer in Packed Beds

Modeling and Simulation of Single Phase Fluid Flow and Heat Transfer in Packed Beds Modeling and Simulation of Single Phase Fluid Flow and Heat Transfer in Packed Beds by:- Balaaji Mahadevan Shaurya Sachdev Subhanshu Pareek Amol Deshpande Birla Institute of Technology and Science, Pilani

More information

Computational Fluid Dynamics as an advanced module of ESP-r Part 1: The numerical grid - defining resources and accuracy. Jordan A.

Computational Fluid Dynamics as an advanced module of ESP-r Part 1: The numerical grid - defining resources and accuracy. Jordan A. Computational Fluid Dynamics as an advanced module of ESP-r Part 1: The numerical grid - defining resources and accuracy Jordan A. Denev Abstract: The present paper is a first one from a series of papers

More information

Coupled Analysis of FSI

Coupled Analysis of FSI Coupled Analysis of FSI Qin Yin Fan Oct. 11, 2008 Important Key Words Fluid Structure Interface = FSI Computational Fluid Dynamics = CFD Pressure Displacement Analysis = PDA Thermal Stress Analysis = TSA

More information

Tutorial 1. Introduction to Using FLUENT: Fluid Flow and Heat Transfer in a Mixing Elbow

Tutorial 1. Introduction to Using FLUENT: Fluid Flow and Heat Transfer in a Mixing Elbow Tutorial 1. Introduction to Using FLUENT: Fluid Flow and Heat Transfer in a Mixing Elbow Introduction This tutorial illustrates the setup and solution of the two-dimensional turbulent fluid flow and heat

More information

Laser speckle based background oriented schlieren measurements in a fire backlayering front

Laser speckle based background oriented schlieren measurements in a fire backlayering front Laser speckle based background oriented schlieren measurements in a fire backlayering front Philipp Bühlmann 1*, Alexander H. Meier 1, Martin Ehrensperger 1, Thomas Rösgen 1 1: ETH Zürich, Institute of

More information

Smoothing the Path to Simulation-Led Device Design

Smoothing the Path to Simulation-Led Device Design Smoothing the Path to Simulation-Led Device Design Beverly E. Pryor 1, and Roger W. Pryor, Ph.D. *,2 1 Pryor Knowledge Systems, Inc. 2 Pryor Knowledge Systems, Inc. *Corresponding author: 4918 Malibu Drive,

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0122 ISBN: 978-83-7947-232-1 Numerical Investigation of Transport and Deposition of Liquid Aerosol Particles in Indoor Environments

More information

Outline. COMSOL Multyphysics: Overview of software package and capabilities

Outline. COMSOL Multyphysics: Overview of software package and capabilities COMSOL Multyphysics: Overview of software package and capabilities Lecture 5 Special Topics: Device Modeling Outline Basic concepts and modeling paradigm Overview of capabilities Steps in setting-up a

More information

CFD MODELING FOR PNEUMATIC CONVEYING

CFD MODELING FOR PNEUMATIC CONVEYING CFD MODELING FOR PNEUMATIC CONVEYING Arvind Kumar 1, D.R. Kaushal 2, Navneet Kumar 3 1 Associate Professor YMCAUST, Faridabad 2 Associate Professor, IIT, Delhi 3 Research Scholar IIT, Delhi e-mail: arvindeem@yahoo.co.in

More information

SolidWorks Flow Simulation 2014

SolidWorks Flow Simulation 2014 An Introduction to SolidWorks Flow Simulation 2014 John E. Matsson, Ph.D. SDC PUBLICATIONS Better Textbooks. Lower Prices. www.sdcpublications.com Powered by TCPDF (www.tcpdf.org) Visit the following websites

More information

The viscous forces on the cylinder are proportional to the gradient of the velocity field at the

The viscous forces on the cylinder are proportional to the gradient of the velocity field at the Fluid Dynamics Models : Flow Past a Cylinder Flow Past a Cylinder Introduction The flow of fluid behind a blunt body such as an automobile is difficult to compute due to the unsteady flows. The wake behind

More information

An Introduction to SolidWorks Flow Simulation 2010

An Introduction to SolidWorks Flow Simulation 2010 An Introduction to SolidWorks Flow Simulation 2010 John E. Matsson, Ph.D. SDC PUBLICATIONS www.sdcpublications.com Schroff Development Corporation Chapter 2 Flat Plate Boundary Layer Objectives Creating

More information

Air Movement. Air Movement

Air Movement. Air Movement 2018 Air Movement In this tutorial you will create an air flow using a supply vent on one side of a room and an open vent on the opposite side. This is a very simple PyroSim/FDS simulation, but illustrates

More information

c Fluent Inc. May 16,

c Fluent Inc. May 16, Tutorial 1. Office Ventilation Introduction: This tutorial demonstrates how to model an office shared by two people working at computers, using Airpak. In this tutorial, you will learn how to: Open a new

More information

Building and HVAC system simulation with the help of

Building and HVAC system simulation with the help of Simbuild 2008 IBPSA US - 3 rd National Building Simulation Conference Berkeley, CA Building and HVAC system simulation with the help of an engineering equation solver S. Bertagnolio, G.Masy, P.André and

More information

COOL-COVERINGS. André Santos, The Netherlands Copyright Active Space Technologies

COOL-COVERINGS. André Santos, The Netherlands Copyright Active Space Technologies COOL-COVERINGS André Santos, The Netherlands 21-03-2012 Copyright Active Space Technologies 2004-2011 Young and competent company Started in 2007 in Germany, in 2004 in Portugal Role Support scientific

More information

solar energy. compared be able to with a low skyscrapers. buildings Solar The the room when the the sky, higher good view

solar energy. compared be able to with a low skyscrapers. buildings Solar The the room when the the sky, higher good view EVALUATION OF A SIMPLIFIE ED MODEL FOR FAÇADE COLLECTORS Thibault Pflug 1, Paolo Di Lauro 1, Tilmann Kuhn 1, Christoph C Maurer 1 1 Fraunhofer Institute for Solarr Energy Systems ISE, Freiburg, Germany

More information

INTEGRATED BUILDING ENERGY AND LIGHTING SIMULATION IN THE FRAMEWORK OF EU PV LIGHT PROJECT

INTEGRATED BUILDING ENERGY AND LIGHTING SIMULATION IN THE FRAMEWORK OF EU PV LIGHT PROJECT Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 INTEGRATED BUILDING ENERGY AND LIGHTING SIMULATION IN THE FRAMEWORK OF EU PV LIGHT PROJECT Milan Janak 1 and Reinhard Kainberger

More information

INTEGRATION OF BUILDING DESIGN TOOLS IN DUTCH PRACTICE

INTEGRATION OF BUILDING DESIGN TOOLS IN DUTCH PRACTICE INTEGRATION OF BUILDING DESIGN TOOLS IN DUTCH PRACTICE Wim Plokker & Luc L. Soethout TNO Building and Construction Research Department of Indoor Environment, Building Physics and Systems P.O. Box 49 NL-2600

More information

USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS

USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS Erin L. Hult 1, Gianluca Iaccarino 2, and Martin Fischer 2 1 Lawrence Berkeley National Laboratory, Berkeley, CA 2 Stanford

More information

Air curtain temperature measurement in an open refrigerated display cabinet by IR thermography

Air curtain temperature measurement in an open refrigerated display cabinet by IR thermography Air curtain temperature measurement in an open refrigerated display cabinet by IR thermography by S. Marinetti*, A. Rossetti*, F. Ferrari* and S. Minetto* * National Research Council, Construction Technologies

More information

Assignment in The Finite Element Method, 2017

Assignment in The Finite Element Method, 2017 Assignment in The Finite Element Method, 2017 Division of Solid Mechanics The task is to write a finite element program and then use the program to analyse aspects of a surface mounted resistor. The problem

More information

First Steps - Ball Valve Design

First Steps - Ball Valve Design COSMOSFloWorks 2004 Tutorial 1 First Steps - Ball Valve Design This First Steps tutorial covers the flow of water through a ball valve assembly before and after some design changes. The objective is to

More information

For this week only, the TAs will be at the ACCEL facility, instead of their normal office hours.

For this week only, the TAs will be at the ACCEL facility, instead of their normal office hours. BEE 3500 Homework Assignment 5 Notes: For this assignment, you will use the computational software COMSOL Multiphysics 5.3, available in Academic Computing Center Engineering Library (ACCEL) at the Carpenter

More information

Modeling External Compressible Flow

Modeling External Compressible Flow Tutorial 3. Modeling External Compressible Flow Introduction The purpose of this tutorial is to compute the turbulent flow past a transonic airfoil at a nonzero angle of attack. You will use the Spalart-Allmaras

More information

Autodesk Moldflow Insight AMI Cool Analysis Products

Autodesk Moldflow Insight AMI Cool Analysis Products Autodesk Moldflow Insight 2012 AMI Cool Analysis Products Revision 1, 22 March 2012. This document contains Autodesk and third-party software license agreements/notices and/or additional terms and conditions

More information

Computational Simulation of the Wind-force on Metal Meshes

Computational Simulation of the Wind-force on Metal Meshes 16 th Australasian Fluid Mechanics Conference Crown Plaza, Gold Coast, Australia 2-7 December 2007 Computational Simulation of the Wind-force on Metal Meshes Ahmad Sharifian & David R. Buttsworth Faculty

More information

Thermal experimental investigation of radiative heat transfer for the validation of radiation models

Thermal experimental investigation of radiative heat transfer for the validation of radiation models Computational Methods and Experimental Measurements XII 251 Thermal experimental investigation of radiative heat transfer for the validation of radiation models N. P. Lavery, M. R. Vujičić & S. G. R. Brown

More information

METHODOLOGY FOR NATURAL VENTILATION DESIGN FOR HIGH-RISE BUILDINGS IN HOT AND HUMID CLIMATE

METHODOLOGY FOR NATURAL VENTILATION DESIGN FOR HIGH-RISE BUILDINGS IN HOT AND HUMID CLIMATE 03-011 The 2005 World Sustainable Building Conference, METHODOLOGY FOR NATURAL VENTILATION DESIGN FOR HIGH-RISE BUILDINGS IN HOT AND HUMID CLIMATE P C Wong 1 D Prasad 2 M Behnia 3 1 Faculty of Built Environment,

More information

Introduction to ANSYS CFX

Introduction to ANSYS CFX Workshop 03 Fluid flow around the NACA0012 Airfoil 16.0 Release Introduction to ANSYS CFX 2015 ANSYS, Inc. March 13, 2015 1 Release 16.0 Workshop Description: The flow simulated is an external aerodynamics

More information

Problem description. Problem 65: Free convection in a lightbulb. Filament (Tungsten): Globe (Glass): = FSI boundary. Gas (Argon):

Problem description. Problem 65: Free convection in a lightbulb. Filament (Tungsten): Globe (Glass): = FSI boundary. Gas (Argon): Problem description This tutorial demonstrates the use of ADINA for analyzing the fluid flow and heat transfer in a lightbulb using the Thermal Fluid-Structure Interaction (TFSI) features of ADINA. The

More information

CFD validation of the thermal comfort in a room using draft rates

CFD validation of the thermal comfort in a room using draft rates CFD validation of the thermal comfort in a room using draft rates Authors: Mika Ruponen 1 and John A. Tinker 1 1 School of Civil Engineering, University of Leeds, UK Corresponding email: mika.ruponen@halton.com

More information

Application of Simulation Method for Analysis of Heat Exchange in Electronic Cooling Applications

Application of Simulation Method for Analysis of Heat Exchange in Electronic Cooling Applications Application of Simulation Method for Analysis of Heat Exchange in Electronic Cooling Applications D.Ramya 1, Vivek Pandey 2 Department of Mechanical Engineering, Raghu Engineering College 1 Associate Professor,

More information

How TMG Uses Elements and Nodes

How TMG Uses Elements and Nodes Simulation: TMG Thermal Analysis User's Guide How TMG Uses Elements and Nodes Defining Boundary Conditions on Elements You create a TMG thermal model in exactly the same way that you create any finite

More information

ACSON MDS Selection Software

ACSON MDS Selection Software ACSON MDS Selection Software Table of Content 1.0 What is MDS selection software. 3 2.0 Required information and results. 4 2.1 Required information. 4 2.2 Results. 6 3.0 Using this software. 7 3.1 Executing

More information

MATHEMATICAL ANALYSIS, MODELING AND OPTIMIZATION OF COMPLEX HEAT TRANSFER PROCESSES

MATHEMATICAL ANALYSIS, MODELING AND OPTIMIZATION OF COMPLEX HEAT TRANSFER PROCESSES MATHEMATICAL ANALYSIS, MODELING AND OPTIMIZATION OF COMPLEX HEAT TRANSFER PROCESSES Goals of research Dr. Uldis Raitums, Dr. Kārlis Birģelis To develop and investigate mathematical properties of algorithms

More information

Getting State-Space Models from FEM Simulations

Getting State-Space Models from FEM Simulations Getting State-Space Models from FEM Simulations A.W.M. (Jos) van Schijndel Eindhoven University of Technology P.O. Box 513; 5600 MB Eindhoven; Netherlands, A.W.M.v.Schijndel@tue.nl Abstract:. Finite element

More information

Thermal and Flow Modeling & Validation of an Exhaust Gas Particulate Matter Sensor

Thermal and Flow Modeling & Validation of an Exhaust Gas Particulate Matter Sensor Thermal and Flow Modeling & Validation of an Exhaust Gas Particulate Matter Sensor A. Lourdhusamy, B. Henderson, J. Steppan, V. Wang, J. Fitzpatrick, K. Allmendinger EmiSense Technologies, LLC Salt Lake

More information

Possibility of Implicit LES for Two-Dimensional Incompressible Lid-Driven Cavity Flow Based on COMSOL Multiphysics

Possibility of Implicit LES for Two-Dimensional Incompressible Lid-Driven Cavity Flow Based on COMSOL Multiphysics Possibility of Implicit LES for Two-Dimensional Incompressible Lid-Driven Cavity Flow Based on COMSOL Multiphysics Masanori Hashiguchi 1 1 Keisoku Engineering System Co., Ltd. 1-9-5 Uchikanda, Chiyoda-ku,

More information

Modeling Skills Thermal Analysis J.E. Akin, Rice University

Modeling Skills Thermal Analysis J.E. Akin, Rice University Introduction Modeling Skills Thermal Analysis J.E. Akin, Rice University Most finite element analysis tasks involve utilizing commercial software, for which you do not have the source code. Thus, you need

More information

Free Convection Cookbook for StarCCM+

Free Convection Cookbook for StarCCM+ ME 448/548 February 28, 2012 Free Convection Cookbook for StarCCM+ Gerald Recktenwald gerry@me.pdx.edu 1 Overview Figure 1 depicts a two-dimensional fluid domain bounded by a cylinder of diameter D. Inside

More information

GEOMATICS SYNTHESIS PROJECT SYMPOSIUM

GEOMATICS SYNTHESIS PROJECT SYMPOSIUM GEOMATICS SYNTHESIS PROJECT SYMPOSIUM Thursday 8 November, 2012 Oostserre, BKCity in association with GEOMATICS SYNTHESIS PROJECT SYMPOSIUM OVERVIEW 1. Introduction 2. Background 3. Site Description 4.

More information

Automotive Thermal Management for Full Vehicles

Automotive Thermal Management for Full Vehicles Automotive Thermal Management for Full Vehicles Concerning the thermal behavior of automotive vehicles it is pursued to accomplish simulations for the full complexity of a vehicle's geometry and transport

More information

Velocity and Concentration Properties of Porous Medium in a Microfluidic Device

Velocity and Concentration Properties of Porous Medium in a Microfluidic Device Velocity and Concentration Properties of Porous Medium in a Microfluidic Device Rachel Freeman Department of Chemical Engineering University of Washington ChemE 499 Undergraduate Research December 14,

More information

Room Fire. Figure 1. Room fire in this example. This tutorial demonstrates how to:

Room Fire. Figure 1. Room fire in this example. This tutorial demonstrates how to: 2018 Room Fire This is a more complex example. Although the geometry of the model is relatively simple, the fire is ignited by glowing particles that heat the sofa upholstery. The upholstery releases fuel

More information

Solid Conduction Tutorial

Solid Conduction Tutorial SECTION 1 1 SECTION 1 The following is a list of files that will be needed for this tutorial. They can be found in the Solid_Conduction folder. Exhaust-hanger.tdf Exhaust-hanger.ntl 1.0.1 Overview The

More information

On the numerical accuracy of particle dispersion simulation in operating theatres

On the numerical accuracy of particle dispersion simulation in operating theatres On the numerical accuracy of particle dispersion simulation in operating theatres Wiebe Zoon 1,*, Marcel Loomans 1 and Jan Hensen 1 1 Eindhoven University of Technology, Eindhoven, the Netherlands * Corresponding

More information

MATHEMATICAL MODELING OF SILICON SINGLE CRYSTAL INDUSTRIAL GROWTH

MATHEMATICAL MODELING OF SILICON SINGLE CRYSTAL INDUSTRIAL GROWTH MATHEMATICAL MODELING OF SILICON SINGLE CRYSTAL INDUSTRIAL GROWTH Dr. Andris Muižnieks, Dr. Andis Rudevičs, Dr. Armands Krauze, BSc. Vadims Suškovs, BSc. Kirils Surovovs, BSc. Kārlis Janisels 1. Introduction

More information

Applications of ICFD solver by LS-DYNA in Automotive Fields to Solve Fluid-Solid-Interaction (FSI) Problems

Applications of ICFD solver by LS-DYNA in Automotive Fields to Solve Fluid-Solid-Interaction (FSI) Problems Applications of ICFD solver by LS-DYNA in Automotive Fields to Solve Fluid-Solid-Interaction (FSI) Problems George Wang(1 ), Facundo del Pin(2), Inaki Caldichoury (2), Prince Rodriguez(3), Jason Tippie

More information

EVALUATION OF WIND-DRIVEN VENTILATION IN BUILDING ENERGY SIMULATION: SENSITIVITY TO PRESSURE COEFFICIENTS

EVALUATION OF WIND-DRIVEN VENTILATION IN BUILDING ENERGY SIMULATION: SENSITIVITY TO PRESSURE COEFFICIENTS EVALUATION OF WIND-DRIVEN VENTILATION IN BUILDING ENERGY SIMULATION: SENSITIVITY TO PRESSURE COEFFICIENTS R. Ramponi 1,2 ; D. Cóstola 1 ; A. Angelotti 2 ; B. Blocken 1, J.L.M. Hensen 1 1: Building Physics

More information

Strömningslära Fluid Dynamics. Computer laboratories using COMSOL v4.4

Strömningslära Fluid Dynamics. Computer laboratories using COMSOL v4.4 UMEÅ UNIVERSITY Department of Physics Claude Dion Olexii Iukhymenko May 15, 2015 Strömningslära Fluid Dynamics (5FY144) Computer laboratories using COMSOL v4.4!! Report requirements Computer labs must

More information

FEMLAB Exercise 1 for ChE366

FEMLAB Exercise 1 for ChE366 FEMLAB Exercise 1 for ChE366 Problem statement Consider a spherical particle of radius r s moving with constant velocity U in an infinitely long cylinder of radius R that contains a Newtonian fluid. Let

More information

Porous Reactor with Injection Needle

Porous Reactor with Injection Needle Porous Reactor with Injection Needle Introduction This model treats the flow field and species distribution in an experimental reactor for studies of heterogeneous catalysis. The model exemplifies the

More information

Visualization of three-dimensional incompressible flows by quasitwo-dimensional

Visualization of three-dimensional incompressible flows by quasitwo-dimensional Visualization of three-dimensional incompressible flows by quasitwo-dimensional divergence-free projections Alexander Yu. Gelfgat School of Mechanical Engineering, Faculty of Engineering, Tel-Aviv University,

More information

Abstract. Die Geometry. Introduction. Mesh Partitioning Technique for Coextrusion Simulation

Abstract. Die Geometry. Introduction. Mesh Partitioning Technique for Coextrusion Simulation OPTIMIZATION OF A PROFILE COEXTRUSION DIE USING A THREE-DIMENSIONAL FLOW SIMULATION SOFTWARE Kim Ryckebosh 1 and Mahesh Gupta 2, 3 1. Deceuninck nv, BE-8830 Hooglede-Gits, Belgium 2. Michigan Technological

More information

Solved with COMSOL Multiphysics 4.0a. COPYRIGHT 2010 COMSOL AB.

Solved with COMSOL Multiphysics 4.0a. COPYRIGHT 2010 COMSOL AB. Journal Bearing Introduction Journal bearings are used to carry radial loads, for example, to support a rotating shaft. A simple journal bearing consists of two rigid cylinders. The outer cylinder (bearing)

More information

Backward facing step Homework. Department of Fluid Mechanics. For Personal Use. Budapest University of Technology and Economics. Budapest, 2010 autumn

Backward facing step Homework. Department of Fluid Mechanics. For Personal Use. Budapest University of Technology and Economics. Budapest, 2010 autumn Backward facing step Homework Department of Fluid Mechanics Budapest University of Technology and Economics Budapest, 2010 autumn Updated: October 26, 2010 CONTENTS i Contents 1 Introduction 1 2 The problem

More information

Driven Cavity Example

Driven Cavity Example BMAppendixI.qxd 11/14/12 6:55 PM Page I-1 I CFD Driven Cavity Example I.1 Problem One of the classic benchmarks in CFD is the driven cavity problem. Consider steady, incompressible, viscous flow in a square

More information

EDSL Guide for Revit gbxml Files

EDSL Guide for Revit gbxml Files EDSL Guide for Revit gbxml Files Introduction This guide explains how to create a Revit model in such a way that it will create a good gbxml file. Many geometry issues with gbxml files can be fixed within

More information

MODELING PARTICLE DEPOSITION IN VENTILATION DUCTS

MODELING PARTICLE DEPOSITION IN VENTILATION DUCTS MODELING PARTICLE DEPOSITION IN VENTILATION DUCTS MR Sippola 1* and WW Nazaroff 1,2 1 Dept. of Civil and Environmental Engineering, University of California, Berkeley, CA, USA 2 Indoor Environment Dept.,

More information

Module 5: Video Modeling Lecture 28: Illumination model. The Lecture Contains: Diffuse and Specular Reflection. Objectives_template

Module 5: Video Modeling Lecture 28: Illumination model. The Lecture Contains: Diffuse and Specular Reflection. Objectives_template The Lecture Contains: Diffuse and Specular Reflection file:///d /...0(Ganesh%20Rana)/MY%20COURSE_Ganesh%20Rana/Prof.%20Sumana%20Gupta/FINAL%20DVSP/lecture%2028/28_1.htm[12/30/2015 4:22:29 PM] Diffuse and

More information

Developing a New Design to Improve Radiation Heat Transfer in an Oven-Like Cavity

Developing a New Design to Improve Radiation Heat Transfer in an Oven-Like Cavity HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Developing a New Design to Improve Radiation Heat Transfer in an Oven-Like Cavity Temel

More information

CFD in COMSOL Multiphysics

CFD in COMSOL Multiphysics CFD in COMSOL Multiphysics Christian Wollblad Copyright 2017 COMSOL. Any of the images, text, and equations here may be copied and modified for your own internal use. All trademarks are the property of

More information

McNair Scholars Research Journal

McNair Scholars Research Journal McNair Scholars Research Journal Volume 2 Article 1 2015 Benchmarking of Computational Models against Experimental Data for Velocity Profile Effects on CFD Analysis of Adiabatic Film-Cooling Effectiveness

More information

DESIGN SUPPORT SIMULATIONS FOR A DOUBLE-SKIN FAÇADE

DESIGN SUPPORT SIMULATIONS FOR A DOUBLE-SKIN FAÇADE DESIGN SUPPORT SIMULATIONS FOR A DOUBLE-SKIN FAÇADE Martin Barták (1), Terezie Dunovská (2) and Jan Hensen (1,3) (1) Czech Technical University in Prague Faculty of Mechanical Engineering, Dept. of Environmental

More information

LAMP /F2C4-FHNO/R23

LAMP /F2C4-FHNO/R23 1224-15/F2C4-FHNO/R23 Features High luminous power Typical chromaticity coordinates x=0.258, y=0.228 according to CIE1931 Bulk, available taped on Ammo. ESD-withstand voltage: up to 4KV The product itself

More information

CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN

CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN 146 CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN 5.1 INTRODUCTION In recent days, most of the buildings are equipped with insect proof screens to keep the insect not to enter inside

More information

Design, Modification and Analysis of Two Wheeler Cooling Sinusoidal Wavy Fins

Design, Modification and Analysis of Two Wheeler Cooling Sinusoidal Wavy Fins Design, Modification and Analysis of Two Wheeler Cooling Sinusoidal Wavy Fins Vignesh. P Final Year B.E.,Mechanical Mepco Schlenk Engineering College Sivakasi,India P. Selva Muthu Kumar Final year B.E.,

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Set No. 1 IV B.Tech. I Semester Regular Examinations, November 2010 FINITE ELEMENT METHODS (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions carry equal marks

More information

Udaan School Of Mathematics

Udaan School Of Mathematics Exercise 18.1 1. Find the lateral surface area and total surface area of a cuboid of length 80 cm, breadth 40 cm and height 0 cm. It is given that Cuboid length Breath b Height WKT, lb bh hl 40cm 0cm h

More information

Best Practices: Electronics Cooling. Ruben Bons - CD-adapco

Best Practices: Electronics Cooling. Ruben Bons - CD-adapco Best Practices: Electronics Cooling Ruben Bons - CD-adapco Best Practices Outline Geometry Mesh Materials Conditions Solution Results Design exploration / Optimization Best Practices Outline Geometry Solids

More information

Vehicle thermal safety with THESEUS-FE. Author: Dr. Daniel Koester

Vehicle thermal safety with THESEUS-FE. Author: Dr. Daniel Koester Author: Dr. Daniel Koester Date: September 4, 2014 Workflow for Underhood Simulations ANSA or other CAD/meshing software CAD cleanup and meshing: either CAD geometry description or NASTRAN-style FE meshes

More information

MDS Selection Software

MDS Selection Software User Manual UM-07-M03-MSS MDS Selection Software Engineered for flexibility and performance. TM 1 Table of Contents What is MDS selection software? Required information and results Using this software

More information