VISONIK Communication via Ethernet with VISONIK BPS V20.06 Documentation on basics

Size: px
Start display at page:

Download "VISONIK Communication via Ethernet with VISONIK BPS V20.06 Documentation on basics"

Transcription

1 s VISONIK Communication via Ethernet with VISONIK BPS V20.06 Documentation on basics CM110662en_ For internal use only Building Technologies

2 Siemens Switzerland Ltd Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel Fax Siemens Switzerland Ltd Subject to change 2 / 32 For internal use only Building Technologies

3 Table of contents 1 Revision history Introduction About this document Terms and abbreviations Purpose of BPS firmware V BPS hardware product range Configuration Overview General Hardware / Firmware identification Communication parameter settings TTY parameter settings Configuration as Net-BPS Hardware combinations Communication parameter settings Commissioning workflow Configuration as Net-ECU Hardware combination Communication parameter settings Commissioning workflow Configuration as Tele-BPS Hardware combinations Communication parameter settings Commissioning workflow Brief instructions for configuration on the DCS Configuration as Tele-ECU Hardware combinations Communication parameter settings Commissioning workflow Configuration as SDLC-BPS Hardware combinations Communication parameter settings Commissioning workflow P-bus and TX-I/O settings Network communication Overview Information on protocols Configure IP addresses Operate via network Operation via DCS Operation via Visotool Operation from another PS Programmed data exchange Exchange data with DEX (data exchange) Exchange data with MSG / REP (message / report) Exchange ASCII strings...29 For internal use only 3 / 32 Building Technologies Table of contents

4 1 Revision history Version Date Changes Section Pages New document 4 / 32 For internal use only Building Technologies Revision history

5 2 Introduction 2.1 About this document Purpose Target audience Prerequisites Content This document describes the new functions of BPS firmware V20.06 as compared to earlier versions. These primarily are an improved functionality of the ECU function along with adjustments of the reduced COM1 and COM2 insert product range to the new TX-I/O modules range. VISONIK system and service technicians. Knowledge of the VISONIK system and VISONIK BPS in particular. This document describes how to configure and apply the various BPS operating modes with regard to communication. The focus clearly is on communication via the Ethernet. This documents summarizes information from other documents such as Net-BPS, Ecu-BPS, and telephony in a clear and concise manner. For detailed information on telephony, the corresponding documents are referenced. Reference documents CM2T8332E CM110442en CM2P8307en Telephony with VISONIK BPS Documentation on basics. Net-BPS V2x.xx Documentation on basics, Ecu-BPS Documentation on basics. If there is conflicting information, the information in this document is valid. TX-I/O documentation See document CM "TX-I/O tool" for the new TX-I/O modules and how to integrate them in VISONIK. This document is available via STEP. For internal use only 5 / 32 Building Technologies Introduction

6 2.2 Terms and abbreviations The table below explains the terms and abbreviations used in this document. Term Network ECU ECU function Net-ECU Tele-ECU Net-BPS Tele-BPS SDLC-BPS PS DCS COM server DUART ASX protocol Attribute protocol ECU ring ECU slave LU P-bus BIM Explanation Stands for Ethernet network in this document. Abbreviation for Enhanced Communication Unit. BPS1.ECU function as gateway between process stations on an SDLC ring and partner stations on the Ethernet or modem connection (DCS / Net-BPS / Tele-BPS / notebook with Visotool). BPS1.ECU with active ECU function for Ethernet. BPS1.ECU with active ECU function for modem connections. BPS1.xx on Ethernet. BPS1.xx on modem. BPS1.xx on SDLC ring. Abbreviation for Process Station: BPS/PRV2/PRV1/EKL-X. Data Communication Server (VISONIK mgmt. station). Terminal server chip for Ethernet communication on COM1 inserts BPS1.C1/1E or BPS1.C1/1ES. Dual Universal Asynchronous Receiver Transmitter. Chip for two RS232 channels on COM1 inserts BPS1.C1/1E or BPS1.C1/1ES. Channel A is the modem interface, channel B is the connection to the COM Server. Application protocol to transmit COLBAS data. Application protocol to exchange VISONIK point parameters between PS and DCS. SDLC ring on an ECU. PS on an ECU ring. The ECU is the ring master. On the DCS, "daughter" rather than slave is used. P-bus load units. P-bus module interface. Gateway between P-bus and island bus for TX-I/O modules. Represents the connection TX-I/O modules as P-bus modules. 6 / 32 For internal use only Building Technologies Introduction

7 2.3 Purpose of BPS firmware V20.06 Migration from SDLC to Ethernet BPS firmware V20.06 primarily contains extensions and improvements of the ECU function to support step-by-step migration from SDLC ring operation to Ethernet communication. This, as a result, will replace the SDLC ring card in the mid-term. The drawing shows the planned migration path. Depending on topology and framework conditions, an entire ring (with max. 34 process stations) can be reconnected to a Net-ECU, or, individual process stations from the ring can be upgraded to Net-BPS and connected directly to the Ethernet. No restrictions apply to existing communication connections between process stations and the DCS. For internal use only 7 / 32 Building Technologies Introduction

8 2.4 BPS hardware product range This section provides an overview of currently available basic units, communication and program cards. Basic units COM1 cards for Ethernet ASN BPS1.00 BPS1.32 BPS1.64 BPS1.128 BPS1.ECU ASN BPS1.C1/1E BPS1.C1/1ES Description Basic unit without P-bus function for CFE applications. Basic unit with P-bus function for 32 / 64 / 128 load units. Basic unit for ECU function. Description COM1 card with DUART and COM Server. COM1 card with SDLC-ASIC, DUART and COM Server. RJ45 plug (COM Server output) for Ethernet. RS232 interface (output DUART channel A) for modem or terminal. Telephony function with C1/E cards SDLC-ASIC As the new product range no longer contains the old cards for telephony (PVC1.1ST or BPS1.C1/1ST), we adapted the BPS firmware V20.06 to ensure that the RS232 interface can be used for telephony. However, Ethernet access is blocked during telephony operation. BPS1.C1/ES is the only card with SDLC-ASIC that remains available as part of the new range. It allows you to configure a BPS1.xx as SDLC-BPS. Access to the Ethernet, however, is precluded in this operating mode. COM2 cards for TEC / Monogyr ASN BPS1.C2/1F BPS1.C2/1M Description COM2 card for TEC controllers (Profibus). COM2 card for Monogyr. Program card P-bus connection TX-I/O modules BPS1.ECU with P-bus The current program card is BPS1.M /E2-V20 with firmware version The P-bus ASIC and P-bus connection are located on the power supply card RG1.64 or PRG1.128 of the basic unit. You can operate the new TX-I/O modules via a P-bus BIM. See "P-bus and TX-I/O settings" on how to set up this operating mode. The operating mode as Tele-ECU or Net-ECU also now allows for operating the P- bus (with max. 64 load units). However, we recommend to use this option only for small applications to avoid performance problems. See "P-bus and TX-I/O settings" on how to set up this operating mode. 8 / 32 For internal use only Building Technologies Introduction

9 3 Configuration 3.1 Overview Operating modes This section shows how to configure the five operating modes of the BPS firmware: Net-BPS Net-ECU Tele-BPS Tele-ECU SDLC-BPS For each operating mode, the required hardware, communication parameter settings and commissioning workflows are described. 3.2 General Hardware / Firmware identification Basic unit and inserted cards are identified by the Boardident parameters. They are available in the Ethernet or ECU report (query ENREP or ECUREP). The firmware version is located in the report header. Check both boardident and firmware version only after initial hardware boot. Basic unit COM1 card COM2 card Program card If a COMx card is missing, boardident parameter is TCMx = 0. Current product range Boardident for the current product range. Device ASN Boardident Basic unit BPS1.00 /32 /64 /128 TMBD = 8/9/10/11 BPS1.ECU TMBD = 7 COM1 card BPS1.C1/1E TCM1 = 7 BPS1.C1/1ES TCM1 = 12 COM2 card BPS1.C2/1F TCM2 = 4 BPS1.C2/1M TCM2 = 5 Program card BPS1.M /E2-V20 TMEM = 14 For internal use only 9 / 32 Building Technologies Configuration

10 Old product range Compatibility of the product ranges Caution Boardidents for older, no longer available product ranges: Device ASN Boardident Basic unit PRV2.00 /32 /64 /128 TMBD = 1/2/3/4 PVC1/1ST TCM1 = 1 PVC1/1S TCM1 = 2 COM1 card PVC1/1T TCM1 = 3 BPS1.C1/1S TCM1 = 10 BPS1.C1/1ST TCM1 = 11 COM2 card PVC2.1F TCM2 = 1 PVC2.2M TCM2 = 2 Program card PVA3.01 TMEM = 6 PVA3.02 TMEM = 7 The new program card and the COM cards BPS1.C1/1E, BPS1.C2/1F, BPS1.C2/1M can also be plugged into old PRV2 basic units. Do not use old program cards PVA03 on BPS basic units Reason: Different timing of the RAM blocks may result in problems at extreme operating temperatures. EPROM set V20.06 can also be used on old program cards Communication parameter settings The communication parameters are also available in the Ethernet report (query ENREP). Check them after the initial hardware boot and set them for the selected operating mode. Enter the settings local and without connection to the DCS. Meaning of communication parameters in the IP-Address Setpoint communication medium (Ethernet / Modem connection / SDLC). Actual value communication medium (Ethernet / Modem connection / SDLC). Activate telephony package (for Ethernet and modem connection). Depending on communication medium (Ethernet / Modem connection / SDLC). Baud rate DUART channel B to COM Server or Baud rate DUART channel A to modem. IP configuration, relevant only for Net-BPS and Net-ECU. Value own PS number. Own system number. DCS number. DCS system number. 10 / 32 For internal use only Building Technologies Configuration

11 @BLN.SWAY The basic parameter for the operating mode SWAY Comm.medium Operating mode as 1 Ethernet Net-BPS 2 SDLC SDLC-BPS 3 Ethernet + SDLC Net-ECU 4 Modem connection. Tele-BPS 6 Modem connection + SDLC. Tele-ECU, SDLC-BPS with telephony. Caution Address is saved in the EEPROM of the program card. The factory setting regardless of COM1 card (operating mode as SDLC-BPS). For all other operating must be changed accordingly. The address parameters MPS and PPS(1) are critical for a successful connection between DCS via Ethernet or modem connection. The ASX protocol requires correct values for MSY and PSY(1). As long as data are not exchanged across system limits, we recommend to keep default value 0 for MSY and PSY(1) TTY Baud rate (telephony package active), parameters have no function. The RS232 interface (DUART channel A) is initialized directly by the firmware. With COM1 cards with Ethernet connection (RJ45 plugs), the parameters of do not have any function. The COM Server interface (DUART channel B) is initialized directly by the firmware. In both cases, the interface's baud rate is given For internal use only 11 / 32 Building Technologies Configuration

12 3.3 Configuration as Net-BPS Hardware combinations The table shows possible basic units and COM cards for Net-BPS operating mode. All combinations are possible. Device ASN Boardident Basic unit PRV2.00 /32 /64 /128 TMBD = 1/2/3/4 BPS1.00 /32 /64 /128 TMBD = 8/9/10/11 COM1 card BPS1.C1/1E TCM1 = 7 BPS1.C1/1ES TCM1 = 12 COM2 card Optional, all possible TCM2 = 0/1/2/4/ Communication parameter settings Parameter Desired value 1 1 No Yes IP-Address Subnet-Mask Project-specific Yes, via ENET$ No Project-specific Yes Enter PS IP-address Enter the IP address of the PS via COLBAS variable ENET, e.g.: ENET$:= "IP= ; SN= ; GW= " IP, SN (subnet) and GW (gateway) can be changed individually, e.g.: ENET$:= "IP= " ENET$:= "" (blank string) deletes the previous entry. All changes become effective only after RESET command (restart BPS). Changes automatically trigger a restart. The baud must match the baud rate set in the COM Server. The factory setting is 9600 baud. If the baud rates differ, communication is impossible. In this case, the Ethernet report reads the following under ACTUAL NET CONNECTION: 'No Link to COM Server' You can check and adjust the baud rate in the COM server only via Telnet: Enter telnet ip-address 1111 in the PC's command window. The COM server dialog box opens. SETUP port (serial), UART setup takes you to the baud rate. 12 / 32 For internal use only Building Technologies Configuration

13 3.3.3 Commissioning workflow Procedure Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Assemble hardware combination, carry out hardware boot. Connect Visotool to tool interface, check Boardident parameters in Ethernet report (query ENREP). Set the configuration parameters, enter RESET. After restarting, check the CONFIGURATION in the Ethernet report. The following must be displayed: Routing not active, Ethernet Mode active, Configuration parameters as per the settings. Check ACTUAL NET CONNECTION in the Ethernet report. After seconds, the following must be displayed: COM Server ok, No Net Access Plug in the connection cable for the Ethernet (RJ45 plug COM1 port). After seconds, the following must be displayed: COM Server ok, Net Access ok On the DCS, enter the corresponding data for the Net-BPS in the profile file Visoprf.prf, section [NET]. Example: [NET] $ps[11] = uwt After entering the data, the DCS starts to negotiate the protocol with the Net-BPS as soon as the physical connection is established. In the Ethernet report, the display in ACTUAL NET CONNECTION part changes from 'No Link to DCS' to 'DCS connection ok'. For internal use only 13 / 32 Building Technologies Configuration

14 3.4 Configuration as Net-ECU Hardware combination Device ASN Boardident Basic unit BPS1.ECU TMBD = 7 COM1 card BPS1.C1/1ES TCM1 = 12 COM2 card Not allowed TCM2 = 0 Program card Only BPS1.M /E2 TMEM = 14 Caution Operation as Net-ECU is possible only with this hardware combination Communication parameter settings Parameter Desired value 3 3 No / 9600 Yes IP-Address Subnet-Mask Project-specific Yes, via ENET$ No Project-specific Yes IP address entry See previous section "Configuration as Net-BPS". See comment in previous section " Configuration as Net-BPS". All connected ring slaves must have the same baud rate. For PRV1 and EKL-X, only 4800 bd are possible (max. baud rate). Number of slaves The max. number of slaves is 34. Although more than 34 slaves on the ring may be displayed in the ECU report, only 34 can communicate with the DCS. 14 / 32 For internal use only Building Technologies Configuration

15 3.4.3 Commissioning workflow Commissioning on the ring side: Step 1 Step 2 Step 3 Step 4 Assemble hardware combination, carry out hardware boot. Connect Visotool to tool interface, check Boardident parameters in Ethernet report (query ENREP). Set the configuration parameters, enter RESET. After restarting, check the CONFIGURATION in the Ethernet report. The following must be displayed: Routing active, Ethernet Mode active, Configuration parameters as per the settings. Connect the Net-ECU on the ring. Then check ring communication in the ECU report (query ECUREP). After a few seconds, the display under RING DIAGNOSTIC must show: Vicemaster: active SlaveCount: (Number of slave PS on ring) Slave Stations: (List of slave PS numbers) The yellow REM LED must flash at a 2 s bright, 1 s dark rhythm. Commissioning on the network side: Parameter LPS Same workflow as for commissioning the Net-BPS (from Step 5). After communication between the DCS and Net-ECU is established, the process stations on the ECU ring are identified automatically and entered as ECU slaves. Check with parameter LPS (link PS) in $xxbln point: Value of LPS = PS number of the ECU for all ECU slaves. For internal use only 15 / 32 Building Technologies Configuration

16 3.5 Configuration as Tele-BPS Hardware combinations The table shows possible basic units and COM cards for Tele-BPS operating mode. All combinations are possible. Device ASN Boardident Basic unit PRV2.00 /32 /64 /128 TMBD = 1/2/3/4 BPS1.00 /32 /64 /128 TMBD = 8/9/10/11 COM1 card PVC1.1ST TCM1 = 1 PVC1.1T TCM1 = 3 BPS1.C1/1E TCM1 = 7 BPS1.C1/1ST TCM1 = 11 BPS1.C1/1ES TCM1 = 12 COM2 card Optional, all possible TCM2 = 0/1/2/4/5 Caution Ring connection and Ethernet connection, if available, have no impact on this operating mode Communication parameter settings Parameter Desired value 4 4 No 1 / 2 Yes (value 2 : Tele-event Yes (max Yes No @BLN.PSY(1) PS number System number Partner 1 and 2 Yes Yes Yes Yes Telephony parameters Typical modem/dial-up sequences: To place a call from one partner device to another, a number of specific telephony parameters are required. The most important parameters are (text numbers as Text number for local modem Text number for dial-up sequence partner Text number for dial-up sequence partner Local modem Dial-up sequence partner Dial-up sequence partner = "1: Elsa 28.8 = "1: = "2: Teleprinter;C2= " (C2 = Partner modem phone number). For a detailed description of telephony, refer to CM2T8332E. 16 / 32 For internal use only Building Technologies Configuration

17 3.5.3 Commissioning workflow Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Assemble hardware combination, carry out hardware boot. Connect Visotool to tool interface, check Boardident parameters in ECU report (query ECUREP). Set the configuration parameters, enter RESET. After restarting, check the CONFIGURATION in the ECU report. The following must be displayed: Routing not active, Ethernet Mode not active, Configuration parameters as per the settings. Display all other telephony parameters and texts via: Check PHONE DIAGNOSTIC in the ECU report.. If no modem is connected, the following is displayed: PHON PHAS: Modem failure Connect and enable modem with RS232 interface (TTY1 / DUART channel A) and telephone plug. Set the following parameters for the initial function (log for opening connection (manual dial-up command to partner 1). Then change change from 0 to 1. Open call and monitor modem, i.e. connection initialization phases. In Step 7, a connection is established only if the partner is configured accordingly. The next section provides brief instructions for the DCS. Refer to document CM2T8332E for additional information. For internal use only 17 / 32 Siemens Communication viaethernet with VISONIK BPS CM110662en_01 Building Technologies Configuration

18 3.5.4 Brief instructions for configuration on the DCS Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Connect the modem to the COM or USB port. Check the COM port assigned to the modem in the Windows Device Manager. Define a terminal channel in profile file Visoprf.prf, section [PCV], for the COM port. Example (terminal channel $T3 for COM1):. $Tytype[3] = COMx $Tycomxname[3]= COM1 Generate a terminal channel with ctrl-p,pkg,gnp,$t3 and set the following parameters: DTYP = Modem MCAT = 1 (modem category, value range 1..7). MSEQ = 200 (number TXC clear text for modem sequence). BD = (baud rate for connection DCS modem, max bd). Set the following parameters in point $xxbln of the Tele-BPS: MCAT = 1 (link to terminal channel). MSEQ = 201 (number TXC clear text for dial-up sequence). Define the TXC clear text for modem sequence ($T3 MSEQ): ctrl-p,txc,aend,number: 200 Typical modem sequence on the DCS: C 0200= 1: Elsa 28.8 QT;C1=ATDT;IN=at&fs0=1. Define the TXC clear text for dial-up sequence ($xxbln MSEQ): ctrl-p, TXC, AEND, Number: 201 Typical dial-up sequence on the DCS: C 0201= 1: PS11;C2= (C2 = Partner modem phone number). Caution: Text numbers Always use different text numbers on BPS and DCS to make sure that the DCS does not overwrite the BPS texts. 18 / 32 For internal use only Building Technologies Configurati

19 3.6 Configuration as Tele-ECU Hardware combinations Device ASN Boardident Basic unit BPS1.ECU TMBD = 7 COM1 card BPS1.C1/1ST TCM1 = 11 BPS1.C1/1ES TCM1 = 12 COM2 card Not allowed TCM2 = 0 Program card Only BPS1.M /E2 TMEM = 14 Caution The Ethernet connection on BPS1.C1/1ES in this operating mode has no function. COM1 port PVC1.1ST cannot be used due to the processor clock frequency 24 MHz Communication parameter settings Parameter Desired value 6 6 No / 9600 Yes Set all other communication and specific telephony parameters identical to section "Configuration as Tele-BPS" Number of slaves All connected ECU slaves must have the same baud rate. For PRV1 and EKL-X, only 4800 bd are possible (max. baud rate). We recommend to limit the number of slaves to max Commissioning workflow Commissioning on ring side: Step 1 Step 2 Step 3 Step 4 Assemble hardware combination, carry out hardware boot. Connect Visotool to tool interface, check Boardident parameters in ECU report (query ECUREP). Set the configuration parameters, enter RESET. After restarting, check the CONFIGURATION in the ECU report. The following must be displayed: Routing active, Ethernet Mode not active, Configuration parameters as per the settings. Connect the Tele-ECU on the ring. Then check ring communication in the ECU report. After a few seconds, the display under RING DIAGNOSTIC must show: Vicemaster: active SlaveCount: (Number of slave PS on ring) Slave Stations: (List of slave PS numbers) The yellow REM LED must flash at a 2 s bright, 1 s dark rhythm. For internal use only 19 / 32 Building Technologies Configuration

20 Commissioning on the modem side Configuration on the DCS Same workflow as for commissioning the Tele-BPS. Same workflow as for configuring the Tele-BPS. In addition, check parameter LPS (link PS) in $xxbln point of the slaves: Value of LPS = PS number of the ECU for all ECU slaves. 3.7 Configuration as SDLC-BPS Hardware combinations The two tables show possible basic units and COM cards for SDLC-BPS operating mode. Mixing PRV and BPS product ranges does not work (incompatible SDLC- ASIC and processor clock frequency). BPS product range PRV product range Caution BPS1.C1/1ES Device ASN Boardident Basic unit BPS1.00 /32 /64 /128 TMBD = 8/9/10/11 BPS1.C1/1S TCM1 = 10 COM1 card BPS1.C1/1ST TCM1 = 11 BPS1.C1/1ES TCM1 = 12 COM2 card Optional, all possible TCM2 = 0/1/2/4/5 Device ASN Boardident Basic unit PRV2.00 /32 /64 /128 TMBD = 1/2/3/4 COM1 card PVC1.1ST TCM1 = 1 PVC1.1S TCM1 = 2 COM2 card Optional, all possible TCM2 = 0/1/2/4/5 COM1 card BPS1.C1/1ES continues to be available as the only card. The Ethernet connection on the in this operating mode has no function Communication parameter settings Two variants In operating mode SDLC-BPS, two variants are possible: SDLC stand-alone or SDLC + telephony (provided a card with modem interface is inserted). The telephony function in this only allows for transmitting ASCII strings to a teleterminal / teleprinter (e.g. send clear text messages via modem connection). Parameter Desired value Desired value Stand-alone SDLC + telephony No meaning Project-specific Max bd. In the case of SDLC + telephony, address and telephony parameters must be set as in the Tele-BPS configuration. 20 / 32 For internal use only Building Technologies Configuration

21 3.7.3 Commissioning workflow Commissioning on ring side: Step 1 Step 2 Step 3 Step 4 Assemble hardware combination, carry out hardware boot. Connect Visotool to tool interface, check Boardident parameters in ECU report (query ECUREP). Set the configuration parameters, enter RESET. After restarting, check the CONFIGURATION in the ECU report. The following must be displayed: Routing not active, Ethernet Mode not active, Configuration parameters as per Check based on the yellow REM LEDs if the BPS works as ring slave: Fast flashing on the ECU ring, irregular flashing on the DCS ring (image of current general query). Modem-side commissioning for SDLC + telephony Same workflow as for commissioning the Tele-BPS. For internal use only 21 / 32 Building Technologies Configuration

22 3.8 P-bus and TX-I/O settings The P-bus is supported as per the basic unit's ASN type. xx in PRV2.xx or BPS1.xx designates the max. number of P-bus load units (LU). The supply card PRG1.64 limits the LUs to 64. BPS1.ECU with P-bus TX-I/O integration Basic unit BPS1.ECU allows P-bus operation with firmware V20.06 for small applications (max. 64 load units). P-bus operation must be activated explicitly. This is possible with the following physical write command: PHYW(4008,0,LU) with LU=32 / 64 / 0 for switch-off. The factory setting is LU=0. The set number becomes effective after the next restart. The set number is saved to EEPROM and survives all restarts. It is read via PHYR(4008,0) BPS firmware V20.06 supports integration of TX-I/O modules via the P-bus BIM. The following functionality is available: Delayed startup of the P-bus driver after power up. Tolerance to response times of the P-bus-BIM. Set the delayed power up via the following physical write command: PHYW(4007,0,DT) with DT = Delay time in seconds. The recommended value is DT=30. After a hardware boot, DT=0. DT is saved to EEPROM and can be read any time via PHYR(4007,0). The parameters for tolerance are set by default. Change them in the event of problems only after consultation with Field Support or Development. See the TX-I/O manual on how to configure and commission the TX-I/O modules (part of the DESIGO V2.37 documentation on STEP). 22 / 32 For internal use only Building Technologies Configuration

23 4 Network communication 4.1 Overview This section discusses the various methods to exchange data between VISONIK devices via the Ethernet. VISONIK devices on the network The following topology shows the communication partners. Included: Process stations on the SDLC ring that can communicate via the network. 4.2 Information on protocols VISONIK knows two application protocols: Attribute protocol ASX protocol ASCII data The attribute protocol helps transmit VISONIK point parameters. With the attribute protocol, data can be exchanged only between PS and DCS. (The DCS maintains the central process image of all process stations in the system). ASX protocol to transmit COLBAS data. With the ASX protocol, data is interchanged between process stations and exchanged with the DCS (primarily to back up and restore COLBAS tasks, dispatcher, timeswitch programs, and text catalogs). There is no special application protocol to exchange COLBAS data between Visotool and the process stations via the network. Data is exchanged as pure ASCII strings (printable characters plus a few control characters such as LF, CR, NUL, Ctrl-E). The data is embedded in the underlying UDP/IP protocol to transport via Ethernet and not visible to users. Users do not handle the attribute protocol. However, users should be familiar with the overall concept from the ASX protocol to ensure correct programming in COLBAS. For internal use only 23 / 32 Building Technologies Network communication

24 ASX connections ASX client/server ASX services DUS (dialog with partner) DEX (data exchange) MSG (message) REP (report) ASX connections are temporary, logical channels between two partner stations to exchange COLBAS data. An ASX connection is established by a station to send an open command to a partner. Data is transferred after connection is established. The connection is again closed via a close command; or due to a timeout in exceptional cases. The ASX client is the partner station that opens the connection; the other station is the ASX server. The term client/server only refers to an individual ASX connection. The ASX protocol knows four application services: DUS (dialog with partner), DEX (data exchange), MSG (message), and REP (report). Each service is handled via a separate ASX connection. The connection is opened and closed via service-specific COLBAS commands or statements. With DUS, operator entries in a $Tn window of the DCS or a TTYn interface of a PS are sent transparent to a partner station and answered by the partner station. A DUS connection is opened via an immediate command DUS(US,SYS,WAY) and closed via Ctrl-E. DEX is used for programmed data exchange between two PS. A DEX connection is opened upon execution of statement OPEN CONNECTION and closed upon execution of CLOSE CONNECTION. The statements SEND, REQUIRE, TRANSMIT and RECEIVE are used to transfer data. The MSG service is used for programmed output of individual messages to a local interface TTYn of a partner station. The data transfer occurs upon execution of the PRINT statement. An MSG connection is opened and closed implicitly. The REP service is used for programmed output of reports to a local interface TTYn of a partner station. With standard reports (ALR, SYR), the REP connection is opened and closed explicitly. For own, programmed reports (with RES, PRINT statements and ENDRES), the REP connection is opened upon RES and closed upon ENDRES. ASX connections A BPS can have several open ASX connections to the same or different partner stations. 2 DUS connections, one as client, one as server. 2 DEX connections, one as client, one as server. 3 MSG or REP connections, either client or server. 24 / 32 For internal use only Building Technologies Network communication

25 4.3 Configure IP addresses For communication to work via the network, the communication partners must know each others address. IP addresses in the DCS IP addresses in Visotool IP addresses in Net-BPS / ECU Dynamic entries Planned entries On the DCS, enter the IP addresses of all partner stations on the network in the profile file visoprf.prf, section [NET]. Example: [NET] $ps[11] = uwt In Visotool, the IP addresses of the Net-BPS /ECU must be entered in register "Connection > Open via TCP/IP" and NetBPS selected. In a Net-BPS / ECU, all IP addresses of all partner stations on the network are managed in a so-called partner address table. In this table, the IP addresses are linked to the PS numbers. There are two different alarm entries: Dynamic entries carried out spontaneously by the BPS firmware upon receipt of the first telegram from a to date unknown partner. This includes an entry for the DCS and for a notebook with Visotool, but also entries carried out upon receipt of the initial open command of a to date unknown ASX client. Planned entries entered explicitly via COLBAS. A planned entry is required whenever an ASX connection is to be opened as client on the corresponding process station (as a user with DUS or upon programmed data exchange). Enter the planned entry with a C-text. = "pps[11] = = "pps[20] = ; Net-ECU for ring 2" Following the IP address, a comment may be appended for display in the Ethernet report following a semicolon ;. Text that does not match the required syntax is not entered in the partner address table, and there is no associated error message (handles as regular C-text entry). An existing, planned entry can be changed any time via the C-text or (the partner address table continues to display the old entry to avoid interruption of an open ASX connection). Display entries ENREP/P allows for checking the entries in the partner address table any time. Planned and dynamic entries differ by their text number indication and possible comments. ENREP/H (history) allows for checking all partners on the network with whom the BPS has exchanged data since the last RESET. The partner's port is also displayed in addition to PS number and IP address (8000 for Net-BPS/ECU, 8500 for DCS, 8501 for Visotool). Number of entries Max 40 entries can be planned. The table always offers space for at least 10 dynamic entries. For internal use only 25 / 32 Building Technologies Network communication

26 4.4 Operate via network Operation via DCS ctrl-p, DUS, $nn (station number) allows for reaching each PS in the earlier topology diagram (Net-BPS, Net-ECU, ECU slave). ctrl-e interrupts the DUS connection Operation via Visotool Every Net-BPS / Net-ECU can be reached via a Visotool connected to the network. In Visotool, the IP address of the Net-BPS /ECU must be entered in register "Connection > Open via TCP/IP" and NetBPS selected. DUS connections Follow-on connections with DUS are then possible: a) From a Net-ECU to an ECU slave. DUS (US=nn, SYS=0, WAY=2) nn=station number ECU slave. b) From a Net-BPS / Net-ECU to the DCS with DUS (US=nn, SYS=0, WAY=1) nn=system number DCS ($S,SYNR) c) From a Net-BPS / Net-ECU to another Net-BPS with DUS (US=nn, SYS=0, WAY=1) nn=station number Net-BPS For variant c), the Net-BPS to be reached must be entered in the partner address table of the first station (ASX client) along with its IP address. ctrl-e exits the DUS and returns to operation of the first station Operation from another PS Rather than via the network, Visotool can also be connected to a PS via a local I/O interface (normally TTY3). The above operating options of a partner device via DUS are identical. DUS from ECU slave If the PS is an ECU slave, DUS parameter WAY must always be 2 (communication medium SDLC). The DUS connection for a DUS connection from a ECU slave to a Net-BPS must be entered in the partner address table of the Net-ECU. 26 / 32 For internal use only Building Technologies Network communication

27 4.5 Programmed data exchange Task variable for communication For data to be exchanged with partner devices as programmed in a COLBAS task, the task variables for communication TSKWAY,TSKPPA,TSKUS,TSKSYS,TSKTTY must be initialized correctly. The corresponding value assignments must precede the instructions for data transfer. TSKWAY Variable TSKWAY must correspond to the communication medium. TSKWAY Comm.medium Partner type Protocol 0 Local interface Terminal ASCII 1 Ethernet PS / DCS ASX 2 SDLC ring PS / DCS ASX Caution TSKPPA TSKUS,TSKSYS Caution TSKSYS TSKTTY ASX client/server role With TSKWAY=1, enter TSKPPA=1 (historical reasons; a Net partner is handled the same as modem partner 1). For TSKWAY=0/2, function TSKPPA has no meaning. For TSKWAY>0, TSKUS=station number, TSKSYS=system number of the partner. For TSKWAY=0, TSKUS,TSKSYS have no meaning. To exchange data directly between process stations on the Ethernet or on the SDLC ring, the partner stations must have the same system number (TSKSYS=0 or TSKSY=@BLN.MSY). In the event of different system numbers, opening a connection via DCS is attempted. TSKTTY designates the I/O interface for message output via task. With TSKWAY=0, TSKTTY is the local TTYn interface. With TSKWAY>0, TSKTTY is the TTYn interface of the partner station. For data exchange DEX (data exchange), TSKTTY has no meaning. The station with the operating communication task always is the ASX client in the case of programmed data exchange. The partner station (TSKUS,TSKSYS) always is the ASX server Exchange data with DEX (data exchange) Permissible COLBAS statements for DEX: OPEN CONNECTION SEND, REQUIRE, TRANSMIT und RECEIVE CLOSE CONNECTION Troubleshooting COLBAS reference The programmed data exchange with DEX must have troubleshooting ON ERROR GOTO. In this case, it must be ensured that an open DEX connection is interrupted. The troubleshooting process must contain instruction CLOSE CONNECTION. Document CM110434en "COLBAS language description ( ), section 4.14 "Data exchange" contains detailed information on the COLBAS statements fro DEX. For internal use only 27 / 32 Building Technologies Network communication

28 DEX connections The following options are available for DEX connections: DEX from Net-BPS to Net-BPS /Net-ECU TSKWAY=1, TSKPPA=1, TSKUS=station number Net-BPS / Net-ECU. The ASX server (Net-BPS / Net-ECU) must be entered in the partner address table of the ASX client along with its IP address. DEX from Net-BPS via Net-ECU to ECU slave TSKWAY=1, TSKPPA=1, TSKUS=station number ECU slave. The ASX server (ECU slave) must be entered in the partner address table of the ASX client along with the IP address of the Net-ECU. Example: Net-ECU Station number 20, IP address ECU slave Station number 25, entry in the partner address = "pps[25] = " DEX from Net-ECU to Net-BPS TSKWAY=1, TSKPPA=1, TSKUS=station number Net-BPS. The ASX server (Net-BPS) must be entered in the partner address table of the ASX client along with its IP address. DEX from Net-ECU to ECU slave TSKWAY=2, TSKPPA=0, TSKUS=station number ECU slave. No entry in the partner address table of the Net-ECU. DEX from ECU slave to ECU slave/net-ecu TSKWAY=2, TSKUS=station number ECU slave / Net-ECU. DEX from ECU slave via Net-ECU to Net-BPS TSKWAY=2, TSKUS=station number Net-BPS. The ASX server (Net-BPS) must be entered in the partner address table of the Net- ECU along with its IP address. 28 / 32 For internal use only Building Technologies Network communication

29 4.5.2 Exchange data with MSG / REP (message / report) When TSKWAY>0, a PRINT statement opens an MSG connection. When TSKWAY>0, the COLBAS statements for standard reports (SYR,ALR,ERP...) as well as the RES statement (reservation of an I/O interface) open a REP connection. In the latter case, the REP connection must be closed explicitly with ENDRES; any number of PRINT statements can exist between RES and ENDRES, but no statements for standard reports. Variable TSKTTY MSG / REP connections Messages to the DCS For MSG / REP connections, the I/O interface for at the partner station must be defined via variable TSKTTY to output messages. MSG / REP connections offer the same possibilities as DEX connections. For the values TSKWAY,TSKPPA,TSKUS and the entries in the partner address table of the ASX client or the Net-ECU, the same process applies as for exchanging data with DEX. In addition, messages and reports can be sent to a $Tn window of the DCS. TSKTTY in this case stands for the $Tn window and TSKUS for the DCS number. The firmware enters the IP address of the DCS (ASX server) in the partner address table of the ASX client Exchange ASCII strings Setting the following variables in the Net-BPS: TSKWAY=0 TSKTTY=2 local I/O interface on the Ethernet Allows for programming data exchange via Visotool connected to the network. Prerequisite is a connection from Visotool to the corresponding Net-BPS. (See section "Configure IP addresses ). This operating mode e.g. allows for reading data processing profiles. For internal use only 29 / 32 Building Technologies Network communication

30 30 / 32 For internal use only Building Technologies Network communication

31 For internal use only 31 / 32 Building Technologies

32 Siemens Switzerland Ltd Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel Fax Siemens Switzerland Ltd Subject to change 32 / 32 For internal use only Building Technologies

Building Process Station

Building Process Station 8 302 VISONIK Building Process Station Overview This data sheet provides the following information: Overview of unit types, connections, and accessories for the VISONIK building process station(hereafter

More information

Use. Functions. VISONIK Building Process Station Overview

Use. Functions. VISONIK Building Process Station Overview 8 301 VISONIK Building Process Station Overview This data sheet provides the following information: Overview of unit types, connections, and accessories for the VISONIK Building Process Station (hereafter

More information

PXM20 Soft Remote-Diagnostic [Modem] PXM20-E-Soft Remote-Diagnostic [Modem] User's Guide. CM110751en_ Building Technologies

PXM20 Soft Remote-Diagnostic [Modem] PXM20-E-Soft Remote-Diagnostic [Modem] User's Guide. CM110751en_ Building Technologies s PXM20 Soft Remote-Diagnostic [Modem] PXM20-E-Soft Remote-Diagnostic [Modem] User's Guide CM110751en_02 2013-07-31 Building Technologies 2 / 8 Building Technologies 2013-07-31 Contents 1 Application...

More information

EQ7000. User Manual. Rev 1.00

EQ7000. User Manual. Rev 1.00 EQ7000 User Manual Rev 1.00 www.equustek.com Revision 1.00 February 27, 2009 Contents INTRODUCTION...4 ABOUT THIS MANUAL...4 INTENDED AUDIENCE...4 HARDWARE SPECIFICATIONS...5 PHYSICAL SPECIFICATIONS...5

More information

Quick Start Guide PROFINET Switch 4/8-port. Version. 1en.

Quick Start Guide PROFINET Switch 4/8-port. Version. 1en. Quick Start Guide PROFINET Switch 4/8-port Version 1en www.helmholz.de Contents 1. Introduction 3 2. Preparing the PROFINET switch 4 3. Project planning for PROFINET switch 4 4. Setting the port properties

More information

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Login for the first time, please use http://192.168.1.100 To key in user name and password is for identifying authorization. Default

More information

FACTORY AUTOMATION. MANUAL OHV-F230-B17 PROFINET Gateway for OHV Handheld

FACTORY AUTOMATION. MANUAL OHV-F230-B17 PROFINET Gateway for OHV Handheld FACTORY AUTOMATION MANUAL OHV-F230-B17 PROFINET Gateway for OHV Handheld R With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

Example for a VISONIK system configuration:

Example for a VISONIK system configuration: 85P0 85P0 8 577 PLD0.TOWER PLD0.RACK VISONIK PLD0.TOWER DCS Data and Communication Server PLD0.RACK Data and communication servers (DCS) are used as management stations in building automation and control

More information

MANUAL PCV Parameterization Tool

MANUAL PCV Parameterization Tool FACTORY AUTOMATION MANUAL Configuration software With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services

More information

# Byrne Rd, Burnaby, BC, V5J 3J1, Canada Phone: or

# Byrne Rd, Burnaby, BC, V5J 3J1, Canada Phone: or EQ7000 User Manual Rev 1.04 www.equustek.com Revision 1.04 Feb 20th, 2017 #286-5489 Byrne Rd, Burnaby, BC, V5J 3J1, Canada Phone: 888-387-3787 or 604-266-8547 www.equustek.com Page 1 Contents INTRODUCTION...4

More information

Connection of linked and third-party systems. Operation of building automation and control systems via networks.

Connection of linked and third-party systems. Operation of building automation and control systems via networks. 8 PLD9.TOWER 57 PLD9.RACK VISONIK DCS Data and communication server PLD9.TOWER PLD9.RACK Data and communication servers (DCS) are used as management stations in building automation and control (BAC). With

More information

M-bus configuration and readout software ACT531 User s guide

M-bus configuration and readout software ACT531 User s guide s M-bus configuration and readout software ACT531 User s guide 012_A6V10844345_en_c 2018-09-13 Building Technologies Published by: Siemens Switzerland Ltd. Building Technologies Division International

More information

RC001-NMS1 (REV.C) User Manual

RC001-NMS1 (REV.C) User Manual RC001-NMS1 (REV.C) User Manual Raisecom Technology Co., Ltd (08/2005) CONTENTS Chapter 1. System Overview...2 1.1 RC002-16 Chassis...2 1.2 RC001-NMS1 Master Network Management Module...2 1.3 RC001-NMS2

More information

FAQ 03/2014. How do I go online? SIMOTION & SINAMICS.

FAQ 03/2014. How do I go online? SIMOTION & SINAMICS. FAQ 03/2014 How do I go online? SIMOTION & SINAMICS http://support.automation.siemens.com/ww/view/de/22016709 This article is taken from Siemens Industry Online Support. The terms of use specified there

More information

Prizm Mux Monitor (PMon) User Manual. March 13, Rev. 2.1

Prizm Mux Monitor (PMon) User Manual. March 13, Rev. 2.1 Prizm Mux Monitor (PMon) User Manual March 13, 2009 Rev. 2.1 Moog Components Group Springfield Operations 750 West Sproul Road Springfield, PA 19064 E-Mail: mcg@moog.com URL: www.moog.com/components Tel:

More information

BAS Router BACnet Multi-Network Router

BAS Router BACnet Multi-Network Router BAS Router BACnet Multi-Network Router The BAS Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP thereby allowing the system integrator to

More information

Product Datasheet NK8231 CEI interface for a single subsystem

Product Datasheet NK8231 CEI interface for a single subsystem Product Datasheet NK8231 CEI interface for a single subsystem NK8000 MP4.40 The NK8231 CEI interface for a single subsystem is used to connect a local or distributed intrusion detection system to MM2000

More information

ACE PLUS CORP. APCON100 series Operation Manual RS-232 to Ethernet Converter

ACE PLUS CORP. APCON100 series Operation Manual RS-232 to Ethernet Converter APCON100 series Operation Manual RS-232 to Ethernet Converter Page 1 of 24 APCON100 series Operation Manual Index Chapter 1 Specifications 2 Chapter 2 Introduction 3 Chapter 3 Easy Installation 4 Chapter

More information

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007 RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007 RS007 is a universal data converter which support serial RS232, RS422 and RS485 to the TCP / IP intelligent communication converter, it offers RS485/RS422

More information

ETHM-2. Ethernet Module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel

ETHM-2. Ethernet Module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel Ethernet Module ETHM-2 Firmware version 1.0 ethm2_en 09/08 SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 info@satel.pl www.satel.pl SATEL's goal is to continually improve

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

Hotel Solution HMI User's guide

Hotel Solution HMI User's guide s Hotel Solution HMI User's guide CM2B6307en 12/15/2008 For internal use only Building Technologies Siemens Switzerland Ltd Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301

More information

HART / EtherNet/IP Gateway GT200-HT-EI User Manual V 1.0 REV A SST Automation

HART / EtherNet/IP Gateway GT200-HT-EI User Manual V 1.0 REV A SST Automation HART / EtherNet/IP Gateway GT200-HT-EI V 1.0 REV A SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 Product Overview... 4 1.1 Product Function...4 1.2 Product Features... 4 1.3 Technical

More information

Quick Start Guide PN/CAN Gateway Layer 2. Version. 2 en. ab FW

Quick Start Guide PN/CAN Gateway Layer 2. Version. 2 en. ab FW Version 2 en ab FW 1.02 Quick Start Guide PN/CAN Gateway Layer 2 www.helmholz.de Content 1. Introduction 3 2. Preparation of the PN/CAN Gateway 3 3. Configure PN/CAN Gateway 4 4. PN/CAN Gateway settings

More information

SHEET. BAS Portable Router BACnet Multi-Network Router. BAS Portable Router

SHEET. BAS Portable Router BACnet Multi-Network Router. BAS Portable Router BAS Portable Router d a t a SHEET BAS Portable Router BACnet Multi-Network Router The BAS Portable Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet

More information

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

CLIMATIX IC20 User manual

CLIMATIX IC20 User manual s Infrastructure & Cities CLIMATIX CLIMATIX IC20 User manual A6V10450042_en--_a 2014-10-07 Building Technologies Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division Gubelstrasse

More information

Product Family: Networking Hardware Number: AN-NH-012

Product Family: Networking Hardware Number: AN-NH-012 APPLICATION NOTE THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT These documents are provided by our technical support department to assist others. We do not guarantee that the data

More information

TCweb Application Note 1 April 2003, Revision A Tidal Engineering Corporation 2003

TCweb Application Note 1 April 2003, Revision A Tidal Engineering Corporation 2003 A Simple Local Area Network Setup for Connecting Multiple TCwebs Using a Low Cost Cable/DSL Router Figure 1 TCweb Thermocouple Monitor One of the powerful features of the TCweb Thermocouple Monitor is

More information

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH485Ex1 Doc No: PH485Ex1-UM-001 #1 RS-485 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

GW1000 User s Guide. Revision 1.04 Mar 30, 2008

GW1000 User s Guide. Revision 1.04 Mar 30, 2008 GW1000 User s Guide Revision 1.04 Mar 30, 2008 Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390 Table of Contents 1.0 GW1000 General Operation & Applications... 3 2.0 Hardware Specifications...

More information

BACnet/IP Web Interface

BACnet/IP Web Interface Desigo Control Point BACnet/IP Web Interface PXG3.W100-1, PXG3.W200-1 Web-based, graphical operation of BACnet automation stations using Desigo touch panels and devices with an HTML 5.0 web browser. Simultaneous

More information

STM-1 Mux SONET/SDH Multiplexer User Manual

STM-1 Mux SONET/SDH Multiplexer User Manual STM-1 Mux SONET/SDH Multiplexer User Manual [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document. Type the abstract of the document here. The

More information

FX Tools Software Package - FX CommPro N2 User s Guide

FX Tools Software Package - FX CommPro N2 User s Guide User s Guide FX CommPro N2 Issue Date September 25, 2008 FX Tools Software Package - FX CommPro N2 User s Guide FX Tools Software Package FX CommPro N2... 3 Introduction...3 Installation... 4 Installing

More information

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

modunet292: novanet-ethernet interface

modunet292: novanet-ethernet interface SAUTER EY-modulo 2 PDS 96.015 en Product Data Sheet EY-BU292 : - interface How energy efficiency is improved SAUTER EY-modulo 2 integrated into familiar IP technology Areas of application Parameterisation

More information

Installation and Operation Manual

Installation and Operation Manual ETC2002 Network Communicator Installation and Operation Manual BG0328 Rev. A7 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship

More information

ETOR-4 Ethernet/Serial Gateway ETOR-4. Ethernet/Serial Gateway USER MANUAL

ETOR-4 Ethernet/Serial Gateway ETOR-4. Ethernet/Serial Gateway USER MANUAL ETOR-4 Ethernet/Serial Gateway USER MANUAL 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...6 SECTION 2 INSTALLATION...9 2.1 Definitions on ETOR... 9 2.2 Configuring ETOR...10 2.3 Required Installations

More information

BlueBridge. Networking Reference Guide

BlueBridge. Networking Reference Guide BlueBridge Networking Reference Guide BB-1616DT BlueBridge DSP BlueBridge TSD-BB44 4 Channel Digital Signal Processor ETHERNET IP RESET BlueBridge GREEN = SIGNAL RED = PEAK INPUT 1 INPUT 2 INPUT 3 IP INPUT

More information

SK CU4-EIP-C Part number:

SK CU4-EIP-C Part number: SK CU4-EIP-C Part number: 275 271 519 EtherNet/IP Internal Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their

More information

SIMATIC NET. S7-CPs for PROFIBUS. CP Extended for PROFIBUS. Manual Part B4

SIMATIC NET. S7-CPs for PROFIBUS. CP Extended for PROFIBUS. Manual Part B4 SIMATIC NET S7-CPs for PROFIBUS Manual Part B4 CP 443-5 Extended for PROFIBUS 6GK7 443-5DX04-0XE0 Version 1 or higher (Firmware Version V6.1 or higher) for SIMATIC S7-400 / S7-400H Status and fault LEDs

More information

Manual. Profi-S-Link. Document 26/834; Edition EN

Manual. Profi-S-Link. Document 26/834; Edition EN Manual Profi-S-Link Document 26/834; Edition EN03 2013-10-17 Content 0 Content 0 Content 0.1 Document History... 0-2 0.2 About this manual... 0-2 0.3 Brands and trademarks... 0-2 0 1 Quickstart 1.1 Summary...

More information

SK CU4-PNT-C Part number:

SK CU4-PNT-C Part number: SK CU4-PNT-C Part number: 275 271 515 PROFINET IO Internal Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their

More information

Contents 1. Summary

Contents 1. Summary Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R KNX IP Router User manual-ver.1 BNIPR-00/00.1 KNX/EIB Intelligent Installation Systems Contents 1. Summary------------------------------------------------------------------------------------------------------------------------------

More information

RC-SV Configuration Guide (Rev 4)

RC-SV Configuration Guide (Rev 4) Kramer Electronics, Ltd. RC-SV Configuration Guide (Rev 4) Software Version 2.1.2.69 Intended for Kramer Technical Personnel or external System Integrators. To check that you have the latest version, go

More information

EtherSeries Modbus Gateway EMB-2 User s Guide

EtherSeries Modbus Gateway EMB-2 User s Guide EtherSeries Modbus Gateway EMB-2 User s Guide Revised March 25, 2004 Firmware Version 1.4 FCC Statement This device complies with the limits for a Class B digital device, pursuant to Part 15 of the FCC

More information

HDLC-USB. Portable Protocol Converter. Rev. Dec 25, Datasheet. Website:

HDLC-USB. Portable Protocol Converter. Rev. Dec 25, Datasheet.   Website: HDLC-USB Portable Protocol Converter Rev. Dec 25, 2017 HDLC-USB Datasheet Email: yacer@yacer.cn Website: www.yacer.cn 1 Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Applications... 3 1.4 Technical

More information

RS-422 Code-Operated Switches

RS-422 Code-Operated Switches JUNE 2000 SW421A-R2 SW422A-R2 RS-422 Code-Operated Switches COS/4 TEXT TRANSPARENT GRAPHICS MODE RESET ST LO CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S. 24 hours, 7 A.M. Monday to midnight

More information

SERVICE TOOL MAP110 USER MANUAL. Landis+Gyr. H c en

SERVICE TOOL MAP110 USER MANUAL. Landis+Gyr. H c en SERVICE TOOL Landis+Gyr MAP110 USER MANUAL H 71 0200 0332 c en Revision History Index Date Comments a 28.02.2005 First edition b 31.05.2005 Changes to release 1.1 c 22.09.2005 Changes to release 1.2 subject

More information

Desigo Insight Management station, V6.0 Getting started. CM110490en_ Building Technologies

Desigo Insight Management station, V6.0 Getting started. CM110490en_ Building Technologies Desigo Insight Management station, V6.0 Getting started CM110490en_08 2015-07-31 Building Technologies Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22

More information

Primary Setup Tool (PST) SIMATIC NET. Industrial Ethernet / PROFINET Primary Setup Tool (PST) Preface. Description. Software installation 2

Primary Setup Tool (PST) SIMATIC NET. Industrial Ethernet / PROFINET Primary Setup Tool (PST) Preface. Description. Software installation 2 Preface Description 1 SIMATIC NET Industrial Ethernet / PROFINET Software installation 2 Functions 3 Configuration Manual 07/2014 C79000-G8976-C204-06 Legal information Warning notice system This manual

More information

ez80190 Development Kit Quick Start Guide

ez80190 Development Kit Quick Start Guide Introduction Follow this guide to install and begin using your new ez80190 Development Kit from ZiLOG. The setup procedure guides the user through: Software installation and online registration Hardware

More information

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide VxI Power Ltd. IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide 01/12/2015 Document Number: 14970-020A Issue Number: 2 Contents 1.0 Device Overview... 2 2.0 Getting Started... 3 2.1 Connecting the Device...

More information

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2 NET101 RS232 / RS422 / RS485 to Ethernet Converter User s Manual Version 1.2 Copyright Information Copyright 2004-2005, Mega System Technologies, Inc. All rights reserved. Reproduction without permission

More information

Edition:2A ODM- 88. DVI Matrix Router USER MANUAL

Edition:2A ODM- 88. DVI Matrix Router USER MANUAL Edition:2A ODM- 88 DVI Matrix Router USER MANUAL ODM-88 Manual Page 2 ODM-88 Manual Page 3 Table of Contents 1 Introduction and Installation. 6 1.1 Key features... 6 1.2 ODM-88 Shipping Content... 6 1.3

More information

Welcome. Unleash Your Phone

Welcome. Unleash Your Phone User Manual Welcome Unleash Your Phone For assistance with installation or troubleshooting common problems, please refer to this User Manual or Quick Installation Guide. Please visit www.vonage.com/vta

More information

EQ-DCM User Manual Revision 1.02 Sep 10, 2013

EQ-DCM User Manual  Revision 1.02 Sep 10, 2013 EQ-DCM User Manual www.equustek.com Revision 1.02 Sep 10, 2013 Contents INTRODUCTION...5 ABOUT THIS MANUAL... 5 INTENDED AUDIENCE... 5 HARDWARE SPECIFICATIONS...6 PHYSICAL SPECIFICATIONS... 6 HARDWARE

More information

RC-SV Configuration Guide Revision 3

RC-SV Configuration Guide Revision 3 Kramer Electronics, Ltd. RC-SV Configuration Guide Revision 3 Software Version 2.1.2.32 Intended for Kramer Technical Personnel or external System Integrators. To check that you have the latest version,

More information

HDLC-ETH. Serial Ethernet Converter. Rev. Dec 20, Datasheet. Website:

HDLC-ETH. Serial Ethernet Converter. Rev. Dec 20, Datasheet.   Website: HDLC-ETH Serial Ethernet Converter Rev. Dec 20, 2017 HDLC-ETH Datasheet Email: yacer@yacer.cn Website: www.yacer.cn 1 Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Applications... 3 1.4 Technical

More information

Chapter 5: Communications 5 1 SR55 Communications Overview 5 2

Chapter 5: Communications 5 1 SR55 Communications Overview 5 2 Chapter 5 Table of Contents Chapter 5: Communications 5 1 SR55 Communications Overview 5 2 Modbus Serial Communications Overview 5 2 Modbus TCP Network Communications Overview 5 2 EtherNet/IP Network Communications

More information

SCADALink IP100 SCADA Terminal Server QUICK START GUIDE Revision 1.42 June 19, 2012

SCADALink IP100 SCADA Terminal Server QUICK START GUIDE Revision 1.42 June 19, 2012 SCADA Terminal Server QUICK START GUIDE Revision 1.42 June 19, 2012 www.scadalink.com INTRODUCTION Use this Quick Start Guide to configure a SCADALink IP100. Full documentation is found under the IP100

More information

tsh-700 Series User Manual

tsh-700 Series User Manual tsh-700 Series User Manual Tiny Serial Port Sharer Aug. 2017 Ver. 1.6 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery

More information

MicroTech BACdrop Setup Wizard Online User s Guide

MicroTech BACdrop Setup Wizard Online User s Guide MicroTech BACdrop Setup Wizard Online User s Guide BACnet -to-microtech Communications Gateway Contents Introduction System Requirements Starting the BACdrop Setup Wizard Working With the BACdrop Gateway

More information

HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation

HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 Product Overview... 4 1.1 Product Function...4 1.2 Product Features...

More information

QUICK START. DevCom2000 User Manual

QUICK START. DevCom2000 User Manual QUICK START DevCom2000 uses Device Descriptions (DDs) to access data stored in the memory of the smart field device. These DDs are developed by the manufacturer for their products and, in turn, distributed

More information

Profibus Gateway 3E V Technical Bulletin

Profibus Gateway 3E V Technical Bulletin Profibus Gateway 3E V1.0.0 Technical Bulletin TECHNICAL BULLETIN 2 Profibus Gateway 3E Liability for errors and misprints excluded. V1.0.0en/23.06.16 TECHNICAL BULLETIN Profibus Gateway 3E V1.0.0en/23.06.16

More information

The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages.

The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages. GV-I/O Box 16 Ports The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages. Key Features 16 inputs and 16 outputs are provided. Up to 9 pieces of GV-I/O

More information

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X EtherSeries EtherSeries CR-2 & CR-2-Opto User s Guide Revised October 7, 2013 Firmware Version 1.X TABLE OF CONTENTS SECTION 1 - DESCRIPTION... 2 SECTION 2 - SPECIFICATIONS... 4 SECTION 3 - INSTALLATION...

More information

Network Communications Controller. Quick Configuration Guide DN

Network Communications Controller. Quick Configuration Guide DN K T - N C C Network Communications Controller Quick Configuration Guide DN1656-0606 Purpose of this Document Reference Documents This Quick Setup Guide is intended for users who are already familiar with

More information

In-Circuit Emulator. UNetICE for ARM

In-Circuit Emulator. UNetICE for ARM In-Circuit Emulator UNetICE for ARM User Manual Version 1.0 Rorixwell Inc. Authorized distributor by Embest Info&Tech Tel: +1 (416) 757 0764 Fax: +1 (416) 757 0764 10 Electro Road, Toronto, ON, M1R 2A7,

More information

Web interface BACnet/IP

Web interface BACnet/IP s 9 294 DESIGO PX Web interface BACnet/IP PXG3.W100 Local or remote operation of one or multiple PX automation station(s) via Desigo Touch Panels (TP) and standard web browser Connection via Ethernet Central

More information

i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products

i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual (Version 1.01) PAGE:1

More information

User's Manual V 32.0

User's Manual V 32.0 User's Manual V 32.0 Trademark Acknowledgements Ford is a registered trademark of Ford Motor Company. Copyright Information DBS User s Manual. 2003, 2004 Ford Motor Company All rights reserved. The information,

More information

Serial to Ethernet Converter

Serial to Ethernet Converter Serial to Ethernet Converter User s Manual Version 1.1 2004 Infosystem Technology Corporation Disclaimers The information in this manual has been carefully checked and is believed to be accurate. Infosystem

More information

Building Technologies. Access Control SiPass networked - simple & networkable for everyday use

Building Technologies. Access Control SiPass networked - simple & networkable for everyday use Building Technologies Access Control SiPass networked - simple & networkable for everyday use SiPass networked Innovative access control SiPass networked is part of the SiPass product range for use in

More information

p N2 European Tool Set PRVCONF / PRVCODE User's Guide Version 3.42 Siemens Building Technologies Landis & Staefa Division CM2U8375E 06.

p N2 European Tool Set PRVCONF / PRVCODE User's Guide Version 3.42 Siemens Building Technologies Landis & Staefa Division CM2U8375E 06. p p F5 T p F4 F1 T F6 p N2 Y1 N1 B9 Y20 Q20 Q23 European Tool Set PRVCONF / PRVCODE User's Guide Version 3.42 CM2U8375E 06.1999 Siemens Building Technologies Landis & Staefa Division u8375e Contents 1.

More information

Monitor and Manage your Power System with Ease.

Monitor and Manage your Power System with Ease. People with Passion Best in Class Technology Power System Focus Monitor and Manage your Power System with Ease. TESLA 3000 Power System Recorder Accessing Multiple Remote Recorders on a Single Modem Call

More information

Site Book User s Guide

Site Book User s Guide Issue Date 11/01/01 USER S GUIDE...3 Introduction... 3 Key Concepts... 5 Related Documentation...5 Communications Options...5 N30 Supervisory Controller...5 Project Builder...6 N30 Upgrade Utility...6

More information

Sauter Systems

Sauter Systems 96.692/1 EYZ 292:, interface The is a interface for connecting the CASE Suite/ programming tools and the various novapro software on the management level to the EY3600 system with in a local area network

More information

I/A Series HARDWARE Product Specifications

I/A Series HARDWARE Product Specifications I/A Series HARDWARE Product Specifications I/A Series Station Computing Device (SCD) SCD5200 CPU OptoNet Power Supply Ethernet (COPE) Module/ SCD5200 CPU OptoNet Ethernet (COE) Module PSS 21H-8G3 B4 FEATURES

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

PROFIBUS Diagnostic Tools Release History

PROFIBUS Diagnostic Tools Release History Diagnostic Tools Release History Version: 2016-09-01 Content PC Software Diagnostics Suite (PB-DIAG-SUITE)... 2 Firmware Tester 5 (BC-700-PB)... 3 Firmware Tester 4 (BC-600-PB)... 4 Firmware Protocol Analyzers

More information

rbox610 Series Robust Din-rail Fanless Embedded System Web Configuration and App Software User s Manual

rbox610 Series Robust Din-rail Fanless Embedded System Web Configuration and App Software User s Manual rbox610 Series Robust Din-rail Fanless Embedded System Web Configuration and App Software User s Manual Disclaimers This manual has been carefully checked and believed to contain accurate information.

More information

Site Ethernet Interface Installation Manual

Site Ethernet Interface Installation Manual Site Ethernet Interface Installation Manual PK XXXX 10/03 1 of 22 Second Edition A publication of Kaba Ilco, Inc. 7301 Decarie Blvd. Montreal, Quebec Canada H4P 2G7 Printed in Canada, 2002 Copyright by

More information

ROCON RPC 116. SUBSTATION AUTOMATION Central unit for substation automation

ROCON RPC 116. SUBSTATION AUTOMATION Central unit for substation automation RPC 116 Central unit for substation automation RPC 116 offers an overall concept for substation system automation at Bay Level, Station Level and Control Center Level. RPC 116 is an embedded unit, which

More information

GW-USB-05. User's Guide. FW v1.07. IQRF USB Gateway MICRORISC s.r.o. User_Guide_GW-USB-05_ Page 1

GW-USB-05. User's Guide. FW v1.07. IQRF USB Gateway MICRORISC s.r.o.   User_Guide_GW-USB-05_ Page 1 FW v1.07 IQRF USB Gateway User's Guide 2016 MICRORISC s.r.o. www.iqrf.org User_Guide 160405 Page 1 Description is an IQRF gateway with USB connectivity. It is intended as an interface between IQRF network

More information

ETOR-4. Ethernet/Serial Gateway USER MANUAL

ETOR-4. Ethernet/Serial Gateway USER MANUAL ETOR-4 Ethernet/Serial Gateway USER MANUAL 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...6 SECTION 2 INSTALLATION...9 2.1 Definitions on ETOR... 9 2.2 Configuring ETOR...10 2.3 Required Installations

More information

Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366

Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366 Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366 AS-i master profile: M4 Firmware: from version RTS 3.0 onwards Target: from V.15 onwards for CoDeSys from

More information

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH232Ex1 Doc No: PH232Ex1-UM-001 #1 RS-232 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

BACnet/IP to BACnet MS/TP Router

BACnet/IP to BACnet MS/TP Router BACnet/IP to BACnet MS/TP Router Features Compact Size Routes between BACnet /IP and BACnet MS/TP networks 10/100Mbps Ethernet Auto-MDIX port Optically isolated MS/TP communications port MS/TP baud rates:

More information

Portable BASrouter BACnet Multi-Network Router

Portable BASrouter BACnet Multi-Network Router Portable BASrouter BACnet Multi-Network Router The Portable BASrouter is a compact BACnet multi-network router which provides versatile standalone routing between BACnet/IP, BACnet Ethernet (ISO 8802-3),

More information

USING THE XPERT2 / 9210B ON A TCP/IP NETWORK

USING THE XPERT2 / 9210B ON A TCP/IP NETWORK 1 USING THE XPERT2 / 9210B ON A TCP/IP NETWORK Prepared by: R&D January, 2009 Updated September 26, 2013 Sutron Corporation 22400 Davis Drive Sterling, Virginia 20164 TEL: (703) 406-2800 FAX: (703) 406-2801

More information

Products no longer available

Products no longer available Technical data sheet BKS24-.. MONICO-Controller BKS24-.. Forms an efficient fire protection system together with the motorisation sets BF(G)24MP Controller with application software for control and monitoring

More information

Ethernet Serial Server

Ethernet Serial Server Ethernet Serial Server Users Manual Eport-101, Eport-102, Eport-104, Eport108 1 INTRODUCTION... 1 1.1 FEATURES... 1 1.2 PRODUCT SPECIFICATIONS... 2 1.3 DEFAULT SETTINGS... 3 2 COMMUNICATION MODES... 4

More information

Contents. GV-I/O Box 8 Ports Key Features Compatible Software Packing List Overview DIP Switch...

Contents. GV-I/O Box 8 Ports Key Features Compatible Software Packing List Overview DIP Switch... Contents GV-I/O Box 8 Ports...2 1. Key Features... 2 2. Compatible Software... 2 3. Packing List... 2 4. Overview... 3 5. DIP Switch... 3 6. Connections to PC... 4 6.1 Installing USB Driver... 5 6.2 Assigning

More information

Extension module for BACnet over Ethernet / IP and graphic Web functions

Extension module for BACnet over Ethernet / IP and graphic Web functions s 9 265 9263p01 DESIGO PX Extension module for BACnet over Ethernet / IP and graphic Web functions Plugs into the modular automation stations, type PXC...-U PXA30-W2 For operation of the PXC -U automation

More information

Revision History. Version Date Changes Description of bridge mode settings via web interface Initial version

Revision History. Version Date Changes Description of bridge mode settings via web interface Initial version MANUAL ANAGATE CAN ANALYTICA GmbH Vorholzstrasse 36 Tel. +49 721 35043-0 E-mail: info@analytica-gmbh.de D-76137 Karlsruhe Fax: +49 721 35043-20 WWW: http://www.analytica-gmbh.de 1 2004-2006, Analytica

More information

Quick Start Guide PN/CAN-Gateway. Version. 1 en. from FW

Quick Start Guide PN/CAN-Gateway. Version. 1 en. from FW Quick Start Guide PN/CAN-Gateway Version 1 en from FW 1.00 www.helmholz.com Content 1. Introduction 3 2. Preparation of the PN/CAN-Gateway 3 3. Plan PN/CAN-Gateway 4 4. Configure PN/CAN-Gateway 5 5. Add

More information

HDLC-PCIE. Synchronous Serial Card. Rev. Dec 22, Datasheet. Website:

HDLC-PCIE. Synchronous Serial Card. Rev. Dec 22, Datasheet.   Website: HDLC-PCIE Synchronous Serial Card Rev. Dec 22, 2017 HDLC-PCIE Datasheet Email: yacer@yacer.cn Website: www.yacer.cn 1 Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Driver Support... 3 1.4 Applications...

More information

UPDATING THE FIRMWARE IN FRAME BASED MODULES...

UPDATING THE FIRMWARE IN FRAME BASED MODULES... 7700/7800 MultiFrame Manual TABLE OF CONTENTS 1. OVERVIEW... 1 1.1. REQUIREMENTS... 1 1.1.1. Requirements Serial Port Upgrade Method... 1 1.1.2. Requirements FTP Upgrade Method (For VistaLINK Capable Modules

More information