Smart Grid Standards. Dr.-Ing. Abdalkarim Awad Informatik 7 Rechnernetze und Kommunikationssysteme
|
|
- Delphia Shaw
- 5 years ago
- Views:
Transcription
1 Smart Grid Standards Informatik 7 Rechnernetze und Kommunikationssysteme
2 Some Smart Grid Related Standards IEC and DNP3: Substation IEC 61698/61970: Transmission and distribution IEC 61400: Wind Turbines IEEE : PMU OpenADR: Automated Demand Response ZigBee: Home Automation BACnet: Building Automation 2
3 Distributed Network Protocol DNP3 DNP3 becomes IEEE 1815 Set of communication protocols between data acquisition and control equipment It plays a crucial role in SCADA systems Used by control centers, RTU and IEDs It has five layers Master/slave Originally the physical layer used serial communication, but now Ethernet can be found user Application Transport Data Link Physical 3
4 IEC 61850: Substation IEC: International Electrotechnical Commission Communication Networks and Systems in Substations Was developed to provide inter-operability intelligent electronic devices (IEDs) for: Protection, Monitoring, Control and automation in substations Addresses Communications and Information modeling 4
5 IEC primary parts Part 6-1: Substation Configuration Language (SCL) Part 7-2: Abstract Communications Service Interface (ACSI) and base types Part 7-3: Common Data Classes (CDC) Part 7-4: Logical Nodes Part 8-1: Specific Communications Service Mappings (SCSM) -MMS & Ethernet Part 9-2: SCSM -Sampled Values over Ethernet Part 10-1: Conformance Testing 5
6 Three IEC61850 Protocols MMS (Manufacturing Message Specification) GOOSE (Generic Object Oriented Substation Event) SV (Sampled Values) 6
7 The Power Substation 7
8 The Power Substation Circuit Breaker (CB) 8
9 Intelligent Electronic Device (IED) Microprocessor-based controllers of power system equipment e.g. circuit breaker, protective relay... Receive digitalized data from sensors and power equipment Issue control commands in case of anomalies to maintain the desired status of power grid e.g. tripping circuit breakers 9
10 Example 10
11 IEC Standard in Substation Autmation MMS GOOSE Sampled Values 11
12 Example Source: esting.html 12
13 Industrial Ethernet Network 13
14 Prioritization In IEC control applications, it is required that the control message transfers occur within 3 ms. Faults can produce a data message storm. Strict priority. 14
15 Generic Substation Events (GSE) Generic Substation Events (GSE) Control model defined in IEC Provides a fast and reliable mechanism of transferring event data over the complete substation networks Multicast GSE subdivided into GOOSE (Generic Object Oriented Substation Events) GSSE (Generic Substation State Events). SV (Sampled Values) 15
16 GOOSE: Generic Object Oriented Substation Event GOOSE messages are sent when event occurs Publisher/Subscriber model Ethernet message (not TCP/IP) Multicast and priority tagging To guarantee delivery, GOOSE message is sent several times No ACK Examples of GOOSE messages : - Autoreclosing (between relay and BCU/CB) - Intertripping (between relay and relay) - Blocking (between relay and relay/bcu) - Interlocking (between BCU and BCU) 16
17 Sampled Values Similar to GOOSE Transmits high speed streams of data set samples encoded in multicast or unicast Ethernet frames. The protocol uses a publisher/subscriber model, in which a publisher transmits unacknowledged data to subscribers. Periodic (4000 sample per second) 17
18 Communication Stack of IEC Time Critical SV GOOSE SNTP MMS TCP/IP TCP/IP Ethernet Link Layer (with Priority, VLAN) Ethernet 100 MB/s Fiber 18
19 GOOSE and SV messages Application layer directly accesses link layer for speed no TCP/IP Uses Ethernet frame directly with Priority/VLAN 802.1Q tag Use priority 4 due to criticality or messages. VLAN use is optional. Fields in payload - source ID, status bits, analog values, time stamp, sequence number, time to live, quality bits, test modes. Typical packets bytes long. Preamble DA SA 1Q tag Type Payload FCS TPID PCP DEI VID 12 bit 3 bits 1 bit 12 bit TPID: Tag Protocol Identifier PCP: Priority Code Point DIE : Drop Eligible Indicator VID: VLAN identifier 19
20 Drivers for Wide Area Monitoring To avoid large area disturbances To improve usage of existing power transfer capacity To secure power system integrity 20
21 Wide Area Monitoring 21
22 Structure Data acquisition, carried by Phasor Measurement Units (PMU) Data delivery through wide area communication system to PDC-Phasor Data Concentrator Data Processing, through the system protection Center (SPC) Command delivery Command execution 22
23 Measures Voltage, Current, phase PMU1 IEEE C WAN PDC Historian Phasor Data Concentrator HMI App1 PMU2 APn Bay1 Bayn LAN e.g., DNP3 Modbus IEC60870 Substation Automation System WAN Command Data e.g., DNP3 Modbus IEC60870 PDC-Phasor Data Concentrator HMI -Human Machine Interface LAN -Local Area Network PMU -Phasor Measurement Unit Dr.- Ing. Abdalkarim Awad 23
24 Architecture SuperPDC PDC PDC PMU PMU PMU PMU PMU 24
25 Phasor Measurement Unit (PMU) The phasor measurement unit (PMU) is a power system device capable of measuring the synchronized voltage and current phasor in a power system. Synchronicity among phasor measurement units (PMUs) is achieved by same-time sampling of voltage and current waveforms using a common synchronizing signal from the global positioning satellite (GPS). The ability to calculate synchronized phasors makes the PMU one of the most important measuring devices in the future of power system monitoring and control 25
26 Synchronized Measurements A PMU at a substation measures voltage and current phasors: Very precise synchronization with μs accuracy. Compute MW/MVAR and frequency. Measurements are reported at a rate of times a second. Can track grid dynamics in real time Traditional SCADA refresh rate is seconds to minutes 26
27 Phasor Data Concentrator (PDC) Each utility has its own Phasor Data Concentrator (PDC) to: Aggregate/align data from various PMUs based on time tag Measurements from each utility s PDC is sent to the Central Facility: Where the measurements are synchronized across utilities 27
28 OpendPDC Complete set of applications for processing streaming time-series data in real-time Measured data is gathered with GPS-time from multiple input sources, time-sorted and provided to user defined actions, dispersed to custom output destinations for archival The openpdc implements a number of standard phasor protocols which can be used to receive data from devices. The supported protocols:ieee C37.118, IEEE 1344, BPA PDCstream, FNET, SEL Fast Message, 28
29 PMU for Wide Area Monitoring and Control Potential PMU Applications Wide-Area Visualization and Monitoring; Angle and Frequency Monitoring; Inter-area Oscillation Detection & Analysis; Proximity to Voltage Collapse; State Estimation; Fast Frequency Regulation; Transmission Fault Location Estimation; Dynamic Model Validation. 29
30 PMU Block Diagram Functional block diagram of the elements in a PMU. 30
31 Phasor: reminder A pure sinusoidal waveform can be represented by a unique complex number known as a phasor. A sinusoidal signal x( t) Xmcos( t ) The phasor representation of this sinusoid is given by Xm j Xm x( t) e (cos( ) sin( ))
32 Phasor: reminder Classical Definition of a Phasor The RMS cosine-reference voltage and current phasors are. 32 i j v j I e I I V e V V i v
33 Convention for synchrophasor representation 33
34 Phasor If the sinusoid is not a pure sine wave, the phasor is assumed to represent its fundamental frequency component. The most commonly used method of calculating phasors from sampled data is that of Discrete Fourier Transform (DFT). 34
35 Important of the Phasor Measurement P 1 V 2 * V 1 2 X L sin Bus1 XL Bus2 V1 PMU1 PMU2 V2 35
36 Compute MW & MVAR j v V V e V v v j i I I e I i i P VI cos( ) v i Q VI sin( ) v i 36
37 Synchronized Measurements Location 2 Location 1 Phase angular difference between the two buses can be determined if the two local clocks are synchronized. Synchronizing pulses obtained from GPS satellites. 37
38 Role of GPS Constellation of 24 satellites orbiting at 20,200 km Developed by US dept of defense Available for free for civilian use Beyond navigation use, it provides time reference: Protection systems derive usage of GPS from the timing signal 4 satellites are needed for knowing timing and location position Satellites have atomic clocks Provides coordinated universal time (UTC) which is international atomic time compensated for leap seconds for slowing of earths rotations can obtain accurate timing pulse every second with an accuracy of 1 microsecond 38
39 PMU Facts PMU uses discrete Fourier transform (DFT) to obtain the fundamental frequency components of voltage / current(half cycle or Full cycle) Data samples are taken over one cycle / multiple cycles. Resolution of the A / D converter is 16 bits. 39
40 Example Power Flow= 5 pu Frequency=50 The power is estimated using bus 1 and 2 (Φ1-Φ2) Error of time stamp at 1 is 0.1 ms and at bus2 is 0 Find the error in estimated power Bus1 j0.1 Bus2 V1=1.0 PMU1 PMU2 V2=1.0 40
41 Example 0.1 ms corresponds to: θ=(0.1ms/20ms)*2π = rad V1V 2 P sin( 1 2) X 10sin( ) Feq=50 Hz 41
42 Example P P V1V 2 sin( 1 2 X pu ) V1V X 2 sin( )
43 Signals with 50 and 51 Hz Blue: Cos(2*π*50*t) Red: Cos(2*π*51*t) 43
44 Table of synchrophasor values at a 10 fps reporting rate Fps: Frame per second 44
45 Relevant PMU Standards C A general transient data recording file format standard C a complete revision and dealt with issues concerning use of PMUs in electric power systems C Covers synchrophasor measurements for power systems Adds frequency & rate of change of frequency (ROCOF) and dynamic operation C Dr.-Ing. Defines Abdalkarim real-time Awad synchronized phasor measurement 45
46 C
47 Example of frame transmission order The SYNC word is transmitted first and CHECK word last. Two- and four-byte words including integer and floating-point numbers are transmitted most significant byte first (network or big endian order). All frame types use this same order and format. 47
48 Required PMU reporting rates 48
49 Word definitions common to all frame types 49
50 Word definitions common to all frame types 50
51 Sync (2 bytes) Frame synchronization word. Leading byte: AA hex Second byte: Frame type and Version, divided as follows: Bit 7: Reserved for future definition Bits 6 4: 000: Data Frame 001: Header Frame 010: Configuration Frame 1 011: Configuration Frame 2 100: Command Frame (received message) Bits 3 0: Version number, in binary (1 15), version 1 for this initial publication. 51
52 Word definitions common to all frame types 52
53 Example A PMU sent a packet that starts with following four bytes (decimal) 170,49,1,198 What is the 170? Determine the type of frame? Data Configuration Command header What is the size of the frame? 53
54 Example 170=0xAA (0x mean hexadecimal) It is the SYNC byte 49=0x31= b 0 (Bit 7: Reserved for future definition) 011: configuration frame : version 1 It is a configuration frame (Config-2) and the version (1) Then comes the two bytes size Size=198+1*256=
55 Configuration frame 55
56 Configuration frame 56
57 Word definitions unique to configuration frame 57
58 To send a value (e.g., voltage) It is possible to send it as a float or integer If Integer We need to scale it Example: to send as 16 bit integer Scale it e.g 1000*18.45=18450 At the receiver side: we convert it back using the same scale 18450/1000=18.45 In C37.118, PhasorMag=value*PHUNIT/
59 FORMAT (2 Bytes) Data format in data frames, 16-bit flag. Bits 15 4: Unused Bit 3: 0 = FREQ/DFREQ 16-bit integer, 1 = floating point Bit 2: 0 = analogs 16-bit integer, 1= floating point Bit 1: 0 = phasors 16-bit integer, 1 = floating point Bit 0: 0 = phasor real and imaginary (rectangular), 1 = magnitude and angle (polar) 59
60 Example Explain the following two bytes for FORMAT field First byte (MSB)= 0 Second byte=8 So we have Bits 15 4: Unused Bits 3 0: Bit 0=0 phasor real and imaginary (rectangular) Bit1=0 phasors 16-bit integer Bit2=0 analogs 16-bit integer Bit3=1 FREQ/DFREQ 32 bit float 60
61 PHUNIT (4 bytes) Conversion factor for phasor channels. Four bytes for each phasor. Most significant byte: 0 = voltage; 1 = current. Least significant bytes: An unsigned 24-bit word in 10 5 V or amperes per bit to scale 16-bit integer data. (If transmitted data is in floating-point format, this 24-bit value should be ignored.) 61
62 62
63 Data Frame Data frame organization 63
64 PHASORS(4/8) 16-bit integer values: Rectangular format: Real and imaginary, real value first 16-bit signed integers, range to Polar format: Magnitude and angle, magnitude first Magnitude 16-bit unsigned integer range 0 to Angle 16-bit signed integer, in radians 10 4, range to
65 PHASORS(4/8) 32-bit values in IEEE floating-point format: Rectangular format: Real and imaginary, in engineering units, real value first Polar format: Magnitude and angle, magnitude first and in engineering units Angle in radians, range π to +π 65
66 FREQ(2/4) Frequency deviation from nominal, in millihertz (mhz) Range nominal (50 Hz or 60 Hz) to Hz 16-bit integer or 32-bit floating point. 16-bit integer:16-bit signed integers, range to bit floating point: actual frequency value in IEEE floating-point format. 66
67 Example If the voltage is Determine the content of the PHASORS bytes for the same FORMAT in the previous example and the PHUNIT has the following 4 bytes (0,0,47,175) Based on the format field, we have to send the phasors as 16 bit Byte0=00 (most significant Byte) Byte1=00 Byte2= Byte3=175 PHUNIT=47* =
68 Example Vr= Vi=0 Before sending, we have to scale the value ScaledVr=Vr*100000/12207=20729 This value is 16 bit We have to send each byte ScaledVr=20729=0x50F9 ScaledVi=0=0x
69 Example We have to send the real part and then the imaginary part, therefore Fist byte=0x50=80 Second byte=0xf9=249 Third byte=0x00 Forth byte=0x00 The PDC will do 80* = *12207/ =
70 Cyclic redundancy codes (CRC) CRC-CCITT g(x) = x 16 + x 12 + x
71 Communication options: Serial IP protocol x message TCP/UDP header x message IP header TCP/UDP header x message Transp. header IP header TCP/UDP header x message Transp. trailer OPTIONS: TCP only, UDP only, TCP/UDP 71
72 Bibliography High Performance IEC GOOSE and Protection Relay Testing by Hachidai Ito and Kenichiro Ohashi, Toshiba Corporation, Japan IEEE C Standard Smart Grid: Technology and Applications, 2012, ISBN , Wiley, by Janaka Ekanayake, Kithsiri Liyanage, Jianzhong Wu, Akihiko Yokoyama, Nick Jenkins Smart Grid : Applications, Communications, and Security by Lars T. Berger and Krzysztof Iniewski Hamed Mohsenian-Rad, Communications & Control in Smart Grid (Slides) 72
C Dr.-Ing. Abdalkarim Awad Informatik 7 Rechnernetze und Kommunikationssysteme
C37.118 13.1.2016 Informatik 7 Rechnernetze und Kommunikationssysteme Measures Voltage, Current, phase PMU1 IEEE C37.118 WAN PDC Historian Phasor Data Concentrator HMI App1 PMU2 APn Bay1 Bayn LAN e.g.,
More informationCommunication In Smart Grid -Part3
Communication In Smart Grid -Part3 Dr.-Ing. Abdalkarim Awad 09.12.2015 Informatik 7 Rechnernetze und Kommunikationssysteme Zigbee General characteristics Data rates of 250 kbps, 20 kbps and 40kpbs. Star
More informationPAP13 - Harmonization of IEEE C with IEC and Precision Time Synchronization
PAP13 - Harmonization of IEEE C37.118 with IEC 61850 and Precision Time Synchronization 12 July 2010 Use Cases Related to Mapping IEEE C37.118 with IEC 61850 as Proposed for Draft IEC 61850-90-5 Synchrophasor
More informationChapter 6: DNP Introduction. 6.2 Features of the DNP The OSI/ISO model. 6.3 Basic topology
6.1 Introduction DNP3 (Distributed Network Protocol Version 3) is an open, intelligent, robust and efficient modern SCADA protocol designed to optimise the transmission of data acquisition information
More informationPG&E ARRA Synchrophasor Project
PG&E ARRA Synchrophasor Project End-to-End Testing June 9, 2011 Vahid Madani Proof of Concept Testing San Ramon 1 Proof of Concept Stage (POC) POC is a smaller scale synchrophasor system used to test,
More informationCommunication Networks
Communication Networks Nicholas Honeth (nicholash@ics.kth.se) Contents of the series Lecture 10 - Recap of the networks we ve seen so far - OSI model - Circuit and packet switching - Physical media Lecture
More informationJim McGhee, Utility Market Manager, RuggedCom Inc.
First Practical Experience with IEEE 1588 High Precision Time Synchronization in High Voltage Substation with IEC 61850 Process Bus Jim McGhee, Utility Market Manager, RuggedCom Inc. (JimMcGhee@RuggedCom.com)
More informationDeploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA
Deploying Digital Substations: Experience with a Digital Substation Pilot in North America Harsh Vardhan, R Ramlachan GE Grid Solutions, USA Wojciech Szela, Edward Gdowik PECO, USA SUMMARY Though IEC 61850
More informationLecture #11 Power system communication
KTH ROYAL INSTITUTE OF TECHNOLOGY Lecture #11 Power system communication Nicholas Honeth In this series Lecture #9 Communication protocol basics The OSI model Relationship between OSI and
More informationIEC Test Equipment Requirements
OMICRON K02 03 20060309 IEC 61850 Test Equipment Requirements Dr. Alexander Apostolov K02 03 20060309 Page: 1 Intelligent Substation Automation Systems OMICRON K02 03 20060309 Page: 2 Intelligent Sensor
More informationGRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM All rights reserved.
GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM 2014. All rights reserved. GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM 2014. All rights reserved. MEASUREMENT PRODUCT SOLUTIONS Reason RPV311 Digital fault recorder
More informationIEC Vaasa Seminar 21st October Contents
Ethernet In The Substation IEC 61850 Vaasa Seminar 21st October 2008 Contents IEC 61850 Environmental Conditions Communication Requirements Communication Protocols Security Summary Contents IEC 61850 Environmental
More informationIntroduction and Overview of IEC Communications. Schweitzer Engineering Laboratories, Inc.
Introduction and Overview of IEC 61850 Communications Schweitzer Engineering Laboratories, Inc. Copyright SEL 2009 SEL Provides Integration Best Practice & Stand-Alone IED Protocols SEL Suite SMART - SEL
More informationNovember 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer
ECE 421 Session 28 November 29, 2018 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,
More informationSimulation of Power System Substation Communications Architecture Based on IEC Standard
Simulation of Power System Substation Communications Architecture Based on IEC 61850 Standard Mohammad Golshani mohammad.golshani@brunel.ac.uk Gareth A. Taylor gareth.taylor@brunel.ac.uk Ioana Pisica ioana.pisica@brunel.ac.uk
More informationGlobal Synchronized Phasor Measurement Standards
Global Synchronized Phasor Measurement Standards Vahid Madani and Farnoosh Rahmatian March 30, 2011 i-pcgrid Workshop 2011 Phasor Measurement System GPS Timing standards IEEE 1588 PTP C37.238 Profile Communication
More informationDS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication
GE Grid Solutions DS Agile C264 Dual-bay Modular Substation Controller The DS Agile C264 substation controller is a sophisticated solution supporting multiple applications and functions for substation
More informationCOMMUNICATION NETWORKS. FOX615/612 TEGO1 IEC GOOSE Proxy Gateway interface module.
COMMUNICATION NETWORKS FOX615/612 TEGO1 IEC 61850 GOOSE Proxy Gateway interface module. 2 FOX615/612 TEGO1 IEC 61850 GOOSE GATEWAY INTERFACE MODULE INTRODUCTION 3 FOX615/612 multiplexing platform. Enabling
More informationIDM DATA ACQUISITION SYSTEM
DATA ACQUISITION SYSTEM The a compact and economical multifunction data acquisition system Rendering all Unrivalled product profile Advanced multifunctional distributed data acquisition system Fully multitasking
More informationChapter 2 State Estimation and Visualization
Chapter 2 State Estimation and Visualization One obvious application of GPS-synchronized measurements is the dynamic monitoring of the operating conditions of the system or the dynamic state estimation
More informationProcess Bus and Sampled Values Based Applications
Process Bus and Sampled Values Based Applications Dr. Alexander Apostolov Los Angeles, CA Page: 2 Analog Signal Processing in ISD Analog Input Module Function Module Rela Input Module Opto Input Module
More informationLessons Learned: Benefits of Using Standardized Protocols to Replace Substation Copper Field Wiring With Digital Communications
Lessons Learned: Benefits of Using Standardized Protocols to Replace Substation Copper Field Wiring With Digital Communications D. Dolezilek and A. Kalra Schweitzer Engineering Laboratories, Inc. Presented
More informationTrends in Station Bus and Process Bus Communications Via the Several IEC Protocols. Schweitzer Engineering Laboratories, Inc.
Trends in Station Bus and Process Bus Communications Via the Several IEC 61850 Protocols Schweitzer Engineering Laboratories, Inc. Copyright SEL 2009 Reduce Cost / Complexity of Field Wiring Yard House
More informationKyland Technology Co., Ltd. White Paper KT/ZY-RD Kyland Technology Co., Ltd. White Paper. High Precision Time Synchronization
Kyland Technology Co., Ltd. White Paper High Precision Time Synchronization I High Precision Time Synchronization Solution over Industrial Ethernet Network Keywords: IEEE1588, PTP Acronyms: Acronym PTP
More informationIEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China
IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China Real Time Communications Symposium Munich, January 2012 Maciej Goraj maciejgoraj@ruggedcom.com 1 Who is RuggedCom?
More informationMultilin P30 Phasor Data Concentrator
Multilin P30 Phasor Data Concentrator Secure high performance Phasor Data Concentrator (PDC) for wide area monitoring and dynamic disturbance analysis KEY BENEFITS Reduce deployment and operation cost
More informationA low-cost, economical solution for distribution feeder protection
SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status
More informationDigital Transformation of Power Delivery
Digital Transformation of Power Delivery Keynote Speech Professor Saifur Rahman, PhD Virginia Tech, USA IEEMA Engineer Infinite Conference, Delhi NCR, India, 14 March 2018 Traditional Electricity Delivery
More informationGrid Automation Controller COM600 How it fits into the Smart Grid?
ABB Oy Distribution Automation Grid Automation Controller How it fits into the Smart Grid? May 27, 2014 Slide 1 1MRS756763 E Content Technical Presentation May 27, 2014 Slide 2 Description Grid Automation
More informationSCE WASAS Combined Disturbance Fault Recorder (DFR) and Phasor Measurement Unit (PMU) Specifications. Anthony Johnson
SCE WASAS Combined Disturbance Fault Recorder (DFR) and Phasor Measurement Unit (PMU) Specifications Anthony Johnson Anthony.Johnson@SCE.com Summary Specifications for combined DFR/PMU to be used as part
More informationDigital Substation Overview of Technology, Industry
Digital Substation Overview of Technology, Industry Trends and Standardization Efforts 4th International Scientific & Technical Conference Actual Trends in Development of Power System Protection and Automation
More informationReviewed by CeemanB. Vellaithurai WSU ID:
Reviewed by CeemanB. Vellaithurai WSU ID: 11253840 Introduction Smart Grid Communication Infrastructure/Communication Architecture Data Assumptions Simulation Assumptions Good contributions Drawbacks Research
More informationProtection, Automation, and Control System. Combine subcycle line protection with complete substation bay control
Protection, Automation, and Control System Combine subcycle line protection with complete substation bay control Subcycle distance protection minimizes damage and expensive repairs on transmission lines.
More informationSynchrophasor Technology and Systems
PNNL-SA-106051 Synchrophasor Technology and Systems Jeff Dagle, PE Chief Electrical Engineer and Team Lead Electricity Infrastructure Resilience Pacific Northwest National Laboratory Richland, Washington
More informationIEC OBJECT MODELS OF MULTIFUNCTIONAL PROTECTION RELAYS
IEC 61850 OBJECT MODELS OF MULTIFUNCTIONAL PROTECTION RELAYS Alexander Apostolov AREVA T&D Automation Los Angeles, USA alexander.apostolov@areva-td.com Abstract The paper analyzes the functional hierarchy
More informationOctober 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer
ECE 421 Session 12 October 05, 2017 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,
More informationDiscover. BlackBox G4400. Outstanding Features. Designed for Your Needs. PQZIP Compression Technology. Elspec s Unique Technology
BlackBox G4400 Designed for Your Needs Discover Outstanding Features A comprehensive energy management and power monitoring program is the key to success for any energy provider/consumer, regardless their
More informationAnca Cioraca, Ilia Voloh, Mark Adamiak GE Grid Automation
Anca Cioraca, Ilia Voloh, Mark Adamiak GE Grid Automation In the beginning.rs-232 Migration to Ethernet in IEDs.circa 1997 Only invented in 1972.fast adoption for our industry Desire for Interoperability
More informationLearn IEC Configuration In 30 Minutes
Learn IEC 61850 Configuration In 30 Minutes Wei Huang ABB Inc. Lake Mary, FL, USA Wei.huang@us.abb.com Abstract the myth says IEC 61850 is too complicated to use with a steep learning curve. The traditional
More informationAutomate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control
Welcome to NovaTech Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control Paul Grabowski About the Author Paul Grabowski
More informationSynchrophasor Implementation Experience and Integration Challenges in Indian Grid
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Synchrophasor Implementation Experience and Integration Challenges in Indian Grid P.
More informationA Digital Implementation of Power System Metering and Protection
A Digital Implementation of Power System Metering and Protection Andreas Joachim Schmitt Thesis submitted to the faculty of the Virginia Polytechnic Institute and State University in partial fulfillment
More informationRTDMS CAISO TRAINING SESSION
Consortium for Electric Reliability Technology Solutions Real-Time Dynamics Monitoring System (RTDMS ) RTDMS CAISO TRAINING SESSION January 31, 2006 Manu Parashar & Jim Dyer Electric Power Group (EPG)
More informationTECHNICAL REPORT IEC/TR
TECHNICAL REPORT IEC/TR 61850-90-5 Edition 1.0 2012-05 Communication networks and systems for power utility automation Part 90-5: Use of IEC 61850 to transmit synchrophasor information according to IEEE
More informationSubstation to substation (ss2ss) GOOSE exchange for critical relay operations
CIGRÉ Canada 21, rue d Artois, F-75008 PARIS (CIGRE-130) Conference on Power Systems http : //www.cigre.org Vancouver, October 17-19, 2010 Substation to substation (ss2ss) GOOSE exchange for critical relay
More informationGrid Protection Alliance NYISO 2010 Smart Grid Vendor Forum. December 9, 2010
Grid Protection Alliance NYISO 2010 Smart Grid Vendor Forum December 9, 2010 1 Who is GPA? A not-for-profit corporation to support the utility industry The Grid Solutions Division of GPA is an open-source
More informationAutomation System Solutions
Automation System Solutions Automation Systems for Power Grid, Power Plant and Industries NR Electric Corporation Automation for Power Grid Substation Automation System Conventional Substation Automation
More informationCommunications guide. Line Distance Protection System * F1* GE Digital Energy. Title page
Title page GE Digital Energy D90 Plus Line Distance Protection System Communications guide D90 Plus firmware revision:.9x GE publication code: 60-9070-F (GEK-3469) GE Digital Energy 650 Markland Street
More informationDR. IR. J.L. RUEDA TORRES LAB INSTRUCTORS:
1. Introduction RTDS Training course of IEPG DAY 6: Application of GTNETx2 card COORDINATOR: DR. IR. J.L. RUEDA TORRES LAB INSTRUCTORS: dipl. ing Matija Naglic, msc. Arun Joseph March 8, 2018 The objective
More informationThe System for Power Automation
Basics 1 Tasks and solution The System for Automation The Tasks: Scalable system for Distributed process connection Process visualization Interface to control centre The Solution: Automation System PTD-SE-A2/
More informationA Case for Multi-Function PMU
A Case for Multi-Function PMU Harish I. Mehta Mehta Tech, Inc. www.mehtatech.com NASPI Chattanooga, TN Meeting PMU Definition PMU is generally defined as: IEEE C37.118 compliant device Time synchronized
More informationAdvanced distribution feeder solution with integrated protection, monitoring, and control
Protection System Advanced distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions. Keep track
More informationReal Time Requirements and Closed-Loop Testing of Wide Area Protection and Control Schemes
XIII SIMPÓSIO DE ESPECIALISTAS EM PLANEJAMENTO DA OPERAÇÃO E EXPANSÃO ELÉTRICA XIII SEPOPE 18 a 21 de Maio 2014 May 18 th to 21 st 2014 FOZ DO IGUAÇU (PR) - BRAZIL XIII SYMPOSIUM OF SPECIALISTS IN ELECTRIC
More informationOverview and Application
IEC 61850 Overview and Application Who am I? Rich Hunt Market Development Leader GE Grid Solutions Over 25 years in the power systems industry At GE for 10 years (almost) Member of IEEE PSRC, U.S. Representative
More informationAlmas, M., Vanfretti, L. (2014) Open Source SCADA Implementation and PMU Integration for Power System Monitoring and Control Applications.
http://www.diva-portal.org This is the published version of a paper presented at IEEE PES GM 2014. Citation for the original published paper: Almas, M., Vanfretti, L. (2014) Open Source SCADA Implementation
More informationSEL Real-Time Automation Controller (RTAC)
SEL Real-Time Automation Controller (RTAC) Product Family Rugged, deterministic, and reliable automation controllers for any environment 1 ms deterministic processing intervals support critical protection
More informationKarl Iliev, San Diego Gas & Electric Company
INTEGRATING DER THROUGH DISTRIBUTION SYNCROPHASORS Karl Iliev, San Diego Gas & Electric Company 2002 San Diego Gas and Electric Co. and Southern California Gas Company. All copyright and trademark rights
More informationECE4110 Internetwork Programming. Introduction and Overview
ECE4110 Internetwork Programming Introduction and Overview 1 EXAMPLE GENERAL NETWORK ALGORITHM Listen to wire Are signals detected Detect a preamble Yes Read Destination Address No data carrying or noise?
More informationImplementation of phasor measurement technology at Eskom
Implementation of phasor measurement technology at Eskom by Reshin Moodley and Brian Berry, Eskom The modern era of power delivery is faced with many challenges due to decreased reserves, increased use
More informationGraduate School of Fundamental Science and Engineering Computer and Communication Engineering. Waseda University. Master s Thesis
Graduate School of Fundamental Science and Engineering Computer and Communication Engineering Waseda University Master s Thesis TITLE The study of ICN based routing scheme for Power System Grid Communication
More informationEvolution of Control for the Power Grid
Evolution of Control for the Power Grid Anjan Bose Washington State University Pullman, Washington, USA University of Seville Seville, Spain June 17, 2016 THE INTERCONNECTED GRID Economics Transfer electric
More informationTR IEC Deterministic Networking
INTERNATIONAL ELECTROTECHNICAL COMMISSION TR IEC 61850-90-13 Deterministic Networking Maik Seewald IEC TC57, WG10 maseewal@cisco.com IEC 61850 in a nutshell Title: Communication networks and systems for
More informationPresentation to the TEXAS RENEWABLE ENERGY INDUSTRIES ASSOCIATION November 7, 2010
Presentation to the TEXAS RENEWABLE ENERGY INDUSTRIES ASSOCIATION November 7, 2010 SynchroTeq / SynchroTeq Plus: Point-on-wave switching RightWON: Modular remote automation platform for energy sites
More informationArchitecture for automatically generating an efficient IEC based communications platform for the rapid prototyping of protection schemes
Architecture for automatically generating an efficient IEC 61850-based communications platform for the rapid prototyping of protection schemes Steven Blair, Campbell Booth, Graeme Burt Institute for Energy
More informationExperience with a Digital Substation Pilot in North Ame rica
Experience with a Digital Substation Pilot in North Ame rica Wojciech Szela, Edward Gdowik PECO Harsh Vardhan, R. Ramlachan GE Grid Solutions 2018 Texas A&M Protective Relaying Conference IEC MDS 61850
More informationAdvanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating
Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage
More informationIEC GOOSE Communication and Its Impact on Substation Performance
IEC 61850-8-1 GOOSE Communication and Its Impact on Substation Performance Sunil Gupta Department of Electrical & Electronics Engineering, Maharaja Surajmal Institute of Technology, Delhi, India sunil.gupta_eee@msit.in
More informationDynamic Phasor Estimation in Electrical Power Systems Based on IEC61850 Process-Bus
SCHOOL OF ELECTRICAL AND ELECTRONIC ENGINEERING Dynamic Phasor Estimation in Electrical Power Systems Based on IEC61850 Process-Bus By Ahmed Abdolkhalig A thesis submitted in partial fulfillment of the
More informationReal-time Cyber-Physical Co-simulation of Power Grids. Vahid Jalili-Marandi, Ph.D., OPAL-RT Technologies, Montreal, Canada April 2018
Real-time Cyber-Physical Co-simulation of Power Grids Vahid Jalili-Marandi, Ph.D., OPAL-RT Technologies, Montreal, Canada April 2018 Overview About OPAL-RT Technologies Real-time simulation (RTS) concepts
More informationDr. Yi Hu, Dr. Damir Novosel Quanta Technology LLC
Brazil CIGRE B5 PDC Workshop Considerations and Requirements of PDCs for WAMPAC Systems Dr. Yi Hu, Dr. Damir Novosel Quanta Technology LLC Rio de Janeiro, Brazil April 6, 2010 Presentation Outline Global
More informationIEEE Standards Activities in the Smart Grid Space (ICT Focus) Overview
This document contains supplemental information referenced by the European Rolling Plan for ICT Standardisation. IEEE Standards Activities in the Smart Grid Space (ICT Focus) Overview IEEE s standardization
More informationIEC standard update
IEC 61850 standard update Christoph Brunner, Switzerland IEC 61850 Europe Conference Amsterdam September 27 28, 2017 Content IEC 61850 parts beyond Ed 1 scope Ongoing work related to IEC 61850 Improving
More informationApplication of synchronized monitoring for dynamic performance analysis. Monitoring Power System Dynamic Performance Using Synchronized Sampling
Application of synchronized monitoring for dynamic performance analysis Monitoring Power System Dynamic Performance Using Synchronized Sampling Mladen Kezunovic, Zheng Ce Texas A&M University College Station,
More informationAlarming and Operations of openpdc at ISO-NE
A U G 1 4, 2 0 1 3 A T L A N T A, G A Alarming and Operations of openpdc at ISO-NE Qiang Frankie Zhang, Patrick Pentz (Developer) Outline Project Overview Project Status Development Challenges Discussion
More informationApplying Intelligent Fast Load Shed Using IEC GOOSE
Applying Intelligent Fast Load Shed Using IEC 61850 GOOSE JC Theron, Steven Rowe GE Grid Solutions Troy Wilsey, Anthony Colonnese Ameresco Russell Gagner Civilian Naval Facilities Engineering Command 71
More informationPXM 4/6/8K DNP3 PXM 4/6/8K DNP3 Ethernet Communications User Manual
PXM 4/6/8K DNP3 PXM 4/6/8K DNP3 Ethernet Communications User Manual Contents Contents 1. INTRODUCTION... 1 2. DNP3 PROTOCOL PRIMER... 1 2.1 Why DNP3?...1 2.2 Link Layer Responsibility...5 2.3 Static and
More informationWide Area Monitoring and Control
Wide Area Monitoring and Control Schweitzer Engineering Laboratories André du Plessis Copyright SEL 2015 SEL Headquarters: WA US Manufacturing: ID, IL, WA Invent, Design, Build, and Support the Systems
More informationIEEE 1588/PTP: The Future of Time Synchronization in the Electric Power Industry
IEEE 1588/PTP: The Future of Time Synchronization in the Electric Power Industry Authors: Bernhard Baumgartner, Christian Riesch, Manfred Rudigier Authors affiliation: OMICRON electronics GmbH, Oberes
More informationSubstation Automation based on IEC Claes Rytoft ABB Power Systems
Substation Automation based on IEC 61850 Claes Rytoft ABB Power Systems BayNetworks Development of SA SA conventional MMI / Control Board NCC SA with interbay bus NCC SA with interbay & process bus NCC
More informationOvation Ethernet Link Controller Module Data Sheet
Ovation Ethernet Link Controller Module Features: Provides native Ethernet connectivity capability at the I/O level Enables faster, more efficient integration of robust data from third-party devices Dedicated
More informationDevelopment of a Smart Grid Test Bed and Applications in PMU and PDC Testing
Development of a Smart Grid Test Bed and Applications in PMU and PDC Testing Saugata S. Biswas, Student Member, IEEE, Jeong Hun Kim, Student Member, IEEE and Anurag K Srivastava, Senior Member, IEEE Abstract--The
More informationIEC 61850: From Paper to Operation
IEC 61850: From Paper to Operation Dr. Alexander Apostolov AREVA T&D Automation XVIII SNPTEE Curitiba, Brazil, 19 October 2005 Introduction IEC 61850 is now an approved international standard It allows
More informationTFS 2100 Traveling Wave Fault Location System
Traveling Wave Fault Location System The most accurate overhead transmission and distribution line fault locator Accuracy: ±150m typical regardless the line length Unaffected by fault resistance Suitable
More informationNumerical motor protection in medium voltage networks Motor Protection and Control REM620
Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,
More informationLecture 5 Substation Automation Systems. Course map
Lecture 5 Substation Automation Systems 1 Course map 2 1 Contents of the Lecture Part 1 Substation Automation Components Substation Automation Functions Communication within the Substation (Intro) Part
More informationTransmission Infrastructure Investment & Development in Vietnam
Transmission Infrastructure Investment & Development in Vietnam Presented by: Mr. Cao Duc Dung Expert of Technical Department National Power Transmission Corporation (NPT) 28 September, 2011 1 CONTENTS
More informationIEC Overview. Grant Gilchrist. Principal Consultant, Smart Grid Engineering November 2009
IEC 61850 Overview Grant Gilchrist Principal Consultant, Smart Grid Engineering November 2009 Traditional Power System Protocols Memory-mapped Register-based, like a filing cabinet. Anything could be in
More informationMODBUS Protocol for MiCOM P30 Series
MODBUS Protocol for MiCOM P30 Series Substation Protocols Technical Documentation This document does not replace the Technical Manual Version: MiCOM P30, MODBUS Index: B Release: 08 / 2011 MODBUS Protocol
More informationWAProtector Power System Wide Area Monitoring Protection and Control
WAProtector Power System Wide Area Monitoring Protection and Control Bojan Mahkovec, Dr. Tadeja Babnik ELPROS, Slovenia Flavio Rabello NOVAKOASIN, Brasil Brasil April 2010 1 Presentation outline Presentation
More informationElectrical Integration with Smart Communication
Electrical Integration with Smart Communication New possibilities with Industrial Ethernet ABB Group September 24, 2009 Slide 1 Unified Integration Approach MES and Business Systems Knowledge Portals as
More informationLecture #7 Substation Automation with IEC 61850
Lecture #7 Substation Automation with IEC 61850 Course map 1 Outline of the Lecture Recap of Substation Configurations Recap of Substation Automation Functions Recap of modern substation architectures
More informationMONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES
MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity
More informationAutomation Services and Solutions
Automation Services and Solutions Automate substation data acquisition and control to improve performance Maintain uninterrupted power services with proactive grid monitoring and controlling features.
More informationRelease 5.83 of the Universal Relay (UR) series introduces improvements for general and protection functions. Highlights of version 5.
GE Digital Energy UR Series Revision 5.83 Release Notes GE Publication Number: GER-4648A Copyright 2015 GE Multilin Inc. Overview Summary Release 5.83 of the Universal Relay (UR) series introduces improvements
More informationLecture #9 Introduction to communication networks
KTH ROYAL INSTITUTE OF TECHNOLOGY Lecture #9 Introduction to communication networks Nicholas Honeth In this series Lecture #9 Communication protocol basics Relationship between OSI and
More informationSmart Grid Architecture Committee (SGAC) Standard Review IEC Suite of Standards White Paper November 2011
Smart Grid Architecture Committee (SGAC) Standard Review IEC 61850 Suite of Standards White Paper November 2011 Standard Name IEC 61850 Suite of standards Communication networks and systems for power utility
More informationGOOSEING YOUR PARALLELING SCHEME
GOOSEING YOUR PARALLELING SCHEME Black & Veatch Holding Company 2017. 2011. All rights reserved. PREPARED FOR Power & Energy Automation Conference 31 JANUARY 2017 Power & Energy Automation Conference
More informationProgram. 5 Day IEC Seminar and Training. XXXX Automation & Information Systems XXXX
, 2010 Program 5 Day IEC 61850 Seminar and Training XXXX Automation & Information Systems XXXX 18.-22.01.2010 Notes: 1. Questions and discussions during and after each presentation are expected and welcome.
More informationTWFL - Travelling Wave Fault Location System
XC-2100E TWFL - Travelling Wave Fault Location System SCOPE is dedicated to the innovative use of electronics for Test & Measuring applications since 1988 for the Power Industry. Our approach of seeking
More informationJULIO OLIVEIRA, ABB POWER GRIDS GRID AUTOMATION, DECEMBER 01 ST ABB Ability - Digital Substations. FISE 7a Edición
JULIO OLIVEIRA, ABB POWER GRIDS GRID AUTOMATION, DECEMBER 01 ST ABB Ability - Digital Substations FISE 7a Edición Current challenges and changes facing utilities Aging infrastructure Legecy systems with
More information