8 Electrical Installation

Size: px
Start display at page:

Download "8 Electrical Installation"

Transcription

1 MOVIMOT Installation Guidelines Electrical Installation. MOVIMOT Installation Guidelines Connect Power Supply Lines The nominal voltage and frequency of MOVIMOT must correspond to the data for the supply system. Line cross-section: according to input current I in for rated power (see Technical Data). Permitted line cross-section of MOVIMOT terminals (does not apply to field distributor) Power terminals Control terminals.0 mm.0 mm ( x.0 mm) 0. mm.0 mm ( x 0. mm ) AWG AWG0 ( x AWG0) AWG AWG ( x AWG) Use conductor end sleeves without insulation collar (DIN Part, material E-CU) Install line safety at the beginning of the supply system cable behind supply bus junction (see the section "Connection of MOVIMOT Basic Unit," F/F/F). Use D, D0, NH or circuit breakers. The fusible rating should be selected in accordance with the cross-section of the cable. It is not permissible to use a conventional residual-current-operated circuit breaker as a protection device. Universal current-sensitive residual-current-operated circuit breakers (tripping current 00 ma) are permitted as a protective device. During normal operation of MOVIMOT, earth-leakage currents of >. ma can occur. Use contactor switch contacts to switch MOVIMOT from utilization category AC- according to IEC. SEW recommends using earth-leakage monitors with pulse-code measurement for power supply systems with non-grounded star point (IT systems). This step will prevent accidental triggering of the earth-leakage monitor by means of the grounding capacities of the inverter. 0 Altitude above 000 m MSL MOVIMOT drives with supply voltages of 0 to 00 V can be used at altitudes above 000 m MSL up to 000 m MSL under the following peripheral conditions. The rated continuous power is reduced based on the reduced cooling above 000 m (see the section Technical Data and Dimension Drawings). Above 00 m MSL, the air and creeping distances are only sufficient for overvoltage class. If the installation requires overvoltage class, an additional external overvoltage protection must be used to ensure that overvoltage surges are limited to. kv phase-to-phase and phase-to-ground. If safe electrical separation is required, it must be implemented outside the units at altitudes above 000 m MSL (presently, safe electrical separation is not specified by a standard outside the EU) The permitted rated supply voltage of x 00 V up to 000 m MSL is reduced by V for every 00 m to a maximum of x 0 V at 000 m MSL. 0. The maximum altitude is limited by creeping distances and flameproof components such as electrolytic capacitors. System Manual - Drive System for Decentralized Installation

2 MOVIMOT Installation Guidelines Connecting V DC supply Conventional Control (via Binary Commands) Control via RS- Interface Supply MOVIMOT either via external V DC or via the MLU..A or MLG..A options. Connect the required control leads (e.g. CW/Stop, CCW/Stop, f/f setpoint change) Use cables shielded as control cables and run separate from power cables. with bus master PLC, MLG..A, MBGA, MWAA option or MF... fieldbus interfaces Caution: Connect only one bus master. Use twisted pair shielded cables as control leads and route them separate from power current cables. Protection Devices MOVIMOT drives have integrated protection elements against overloads, external elements will not be necessary. UL-Compliant Installation Only use copper cables with the following temperature ranges as connection leads: Temperature range: 0 / C The permissible tightening torques of the MOVIMOT power terminals are:. Nm (. lb.in) MOVIMOT are suited for operation on voltage supply systems with grounded star (TN and TT systems) supplying a maximum supply current of,000 A AC and having a maximum rated voltage of 0 V AC (MM0B- to MMB-) or 00 V AC (MM0-0 to MM0B-0). The rating for the fuses is not to exceed the following values: MM0B-0 to MM0B-0: A/00 V MMB-0 to MM0B-0: A/00 V MM0B- to MMB-: A/0 V As external V DC voltage source use only tested units with a limited output voltage (V max = 0 V DC ) and limited output current (I A). UL certification does not apply to operation in voltage power systems with a nongrounded star point (IT systems). System Manual - Drive System for Decentralized Installation

3 Additional Installation Instructions for Fieldbus Interfaces, Field Distributors. Additional Installation Instructions for Fieldbus Interfaces, Field Distributors Current Carrying Capacity of Terminals Daisychaining V DC Supply Voltage for MFZ. Module Carrier: Cage clamp terminals X0 (gray): A maximum continuous current Screw terminals X, X (green): A maximum continuous current Additional Connection Options with MFZ. and MFZ. Field Distributor 0AXX Two M x studs are located on the connection part of the V DC supply. These studs can be used for daisychaining the V DC supply voltage. The studs have a current carrying capacity of A. 0AXX The connection part of the V DC supply comprises a X terminal block with two M x studs and a pluggable X0 terminal. The X terminal block can be used alternatively to X0 terminal for daisychaining the V DC supply voltage. The two studs are connected internally with the V connection on terminal X0. Terminal assignment: No. Name Function X V V power supply for module electronics and sensors (stud, jumpered with terminal X0/) 0V reference potential for module electronics and sensors (stud, jumpered with terminal X0/) The pluggable X0 terminal ("Safety Power") is intended for the external V DC supply of the MOVIMOT inverter via a safety reset device. Terminal assignment: No. Name Function X0 V V voltage supply for MOVIMOT for disconnection with safety reset device 0V reference potential for MOVIMOT for disconnection with safety reset device This allows a MOVIMOT drive to be used in safety applications. Corresponding information can be found in the documentation "Safe Disconnection for MOVIMOT." X/ and X0/ are factory-jumpered, so that the MOVIMOT inverter is supplied by the same V DC voltage as the fieldbus module. The current carrying capacity of the two studs is A. The current carrying capacity of screw terminal X0 is: 0 A. 0 0 System Manual - Drive System for Decentralized Installation

4 Additional Installation Instructions for Fieldbus Interfaces, Field Distributors Transfer Rates >. Mbps (in connection with MFP..D) With transfer rates >. Mbps it must be observed that the PROFIBUS connecting leads in the inside of the field distributor are kept as short as possible and have the same length for incoming and outgoing bus. Wiring Check Before connecting power to the system for the first time, it is necessary to perform a wiring check to prevent damage to persons, systems and equipment caused by wiring faults. Remove all bus modules from the connecting module. Disconnect all MOVIMOT inverters from the connecting module (only with MFZ.). Disconnect all plug connectors of the motor circuits (hybrid cable) from the field distributor. Perform an insulation test of the wiring in accordance with valid national standards. Check the grounding. Check whether supply system cable and V DC cable are insulated. Check whether supply system cable and communications cable are insulated. Check the polarity of the V DC cable. Check the polarity of the communications cable. Check the supply phase sequence. Ensure equipotential bonding between the fieldbus interfaces. After the Wiring Check Plug on and fasten all motor circuits (hybrid cable). Insert the bus modules and fasten screws. Plug on all MOVIMOT inverters and fasten screws (only with MFZ.). Install all terminal box covers. Seal plug connections not in use. 0 System Manual - Drive System for Decentralized Installation

5 Additional Installation Instructions for Fieldbus Interfaces, Field Distributors EMC Metal Cable Glands EMC metal cable glands supplied by SEW must be installed as follows: () 0 () Caution: Cut off insulation foil, but do not fold it back 0BXX 0 System Manual - Drive System for Decentralized Installation

6 RS- Connection of MOVIMOT Basic Unit. Connection of MOVIMOT Basic Unit L F/F/F Functions of the CW and CCW terminals under binary control V R L V R L K CW direction of CCW direction of rotation activated rotation activated Functions of f/f terminals L MOVIMOT V R L f/f V R L f/f M ~ BMG V supply DC CW/stop CCW/stop Setpoint switchover f/f Ready signal Contact closed = ready for operation K Setpoint f activated V V R R L L Setpoint f activated Functions of CW and CCW Terminals controlled via RS- interface / field distributor Both directions are enabled Only CW direction enabled. Setpoint selection for CCW rotation causes the drive to stop. red white blue BW braking resistor (only for MOVIMOT without brake) V = - R L f/f Ka Kb RS- RS V supply DC external or MLU../MLG..option. V V R R L L Only CCW direction enabled. Setpoint selection for CW rotation causes the drive to stop. Drive is inhibited or brought to a stop 0AEN System Manual - Drive System for Decentralized Installation

7 Connection of MLUA / MLUA Option. Connection of MLUA / MLUA Option YE (MLUA) / BN (MLUA) YE (MLUA) / BN (MLUA) L MOVIMOT L MLU..A V R L f/f Ka Kb RS- RS V BU 0BXX 0. Connection of MLGA / MLGA Option YE (MLGA) / BN (MLGA) L YE (MLGA) / BN (MLGA) MOVIMOT L MLG..A V RS RS- V R L f/f Ka Kb RS- RS () BU OG GN 0BXX 0 () Observe Enable of direction of rotation (see the section "Connection of MOVIMOT Basic Unit" Functions of terminals CW/Stop, CCW/Stop with controller via RS- interface) System Manual - Drive System for Decentralized Installation

8 Connection of MBGA Option. Connection of MBGA Option L MOVIMOT MBGA V R L f/f Ka Kb RS- RS V RS RS- () V DC () 0BXX. Connection of MWAA Option L V MOVIMOT R L f/f Ka Kb RS- RS V DC () V V R L 0V - 0 RS RS- MWAA () () () () Observe Enable of direction of rotation (see the section "Connection of MOVIMOT Basic Unit" Functions of terminals CW/Stop, CCW/Stop with controller via RS- interface) () EMC metal cable gland () Potentiometer with use of 0V reference voltage can be kω kω 0V - 0 MWAA Potential-free analog signal 0V - 0 0BXX MWAA System Manual - Drive System for Decentralized Installation

9 Connection of AS-i Binary Slave MLKA. Connection of AS-i Binary Slave MLKA L V MOVIMOT () R L f/f Ka Kb RS- RS AS-i - N.C. AS-i N.C. MLKA () 0V DI N.C. V DI WH BK/BU BK/ BK/WH BU () AS-i connection () Connection for external sensors. Connection RS- Bus Master 0AXX 0 L MOVIMOT RS- Busmaster (SPS / PLC) V R L f/f Ka Kb RS- RS RS- V DC () () () Observe Enable of direction of rotation (see the section "Connection of MOVIMOT Basic Unit" Functions of terminals CW/Stop, CCW/Stop with controller via RS- interface) () EMC metal cable gland () Potential compensation MOVIMOT / RS- master () () 0AXX 0 System Manual - Drive System for Decentralized Installation

10 Connection of MDGA Option.0 Connection of MDGA Option The diagnostic unit must be connected prior to the possible occurrence of a fault since the MOVIMOT fault messages are not saved and the information is lost when the V supply is disconnected. Connecting the MDGA to an RS- bus with several MOVIMOT is not permitted. The diagnostic unit can be used if the MOVIMOT is controlled via terminals (= address 0 [S/-S/ = OFF]). Using the diagnostic unit with setpoint setting via RS- interface is not permitted. L MOVIMOT MDGA V R L f/f Ka Kb RS- RS V RS RS- () 00BXX () EMC metal cable gland System Manual - Drive System for Decentralized Installation

11 Connection with PROFIBUS. Connection with PROFIBUS Connecting MFZ with MOVIMOT MFZ MFP... A B () MFZ (PROFIBUS) 0 A B D A 0 0 B PROFIBUS DP D VP D A B X0 V 0 V - V DC V RS RS- () V MOVIMOT R L f/f Ka Kb RS- RS () () 0AXX = Potential level 0 () For separate assembly of MFZ / MOVIMOT : Connect the shield of the RS- cable via an EMC metal cable gland on MFZ and MOVIMOT housing. () Ensure equipotential bonding between all bus stations. () Assignment of terminals - starting on page Terminal assignment X0 A Input PROFIBUS-DP data line A (incoming) B Input PROFIBUS-DP data line B (incoming) D - Data reference potential for PROFIBUS-DP (only for test purposes) A Output PROFIBUS-DP data line A (outgoing) B Output PROFIBUS-DP data line B (outgoing) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved VP Output V output (max. 0 ma) (only for test purposes) D - Reference potential for VP (terminal ) (only for test purposes) Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors V Output V power supply for MOVIMOT RS Output Communications link to MOVIMOT terminal RS RS- Output Communications link to MOVIMOT terminal RS- - 0V reference potential for MOVIMOT 0 System Manual - Drive System for Decentralized Installation

12 Connection with PROFIBUS Connecting MFZ Field Distributor with MFP... MFZ connection module with MFP, MFP fieldbus module and two separate V DC voltage circuits L L MFZ MFP MFP X L mm (AWG0). mm (AWG) mm (AWG0) X0 X 0 0 L x V DC A B V A B D VP A B PROFIBUS DP () () D D V V VI VI A B V V V 0AXX = Potential level = Potential level () EMC metal cable gland Terminal assignment X0 A Input PROFIBUS-DP data line A (incoming) B Input PROFIBUS-DP data line B (incoming) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved VP Output V output (max. 0 ma) (only for test purposes) A Output PROFIBUS-DP data line A (outgoing) B Output PROFIBUS-DP data line B (outgoing) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved 0 D - Reference potential for VP (terminal ) (only for test purposes) X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X/ - 0VV reference potential for actuators - 0VV reference potential for actuators System Manual - Drive System for Decentralized Installation

13 . Connection with PROFIBUS MFZ connection module with MFP, MFP fieldbus module and one common V DC voltage circuit L L MFZ MFP MFP x V DC A B V. mm (AWG) mm (AWG0) X0 X 0 0 A B D A B D res PROFIBUS DP () () X mm (AWG0) VP L L = Potential level = Potential level () EMC metal cable gland Terminal assignment X0 A Input PROFIBUS-DP data line A (incoming) B Input PROFIBUS-DP data line B (incoming) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved VP Output V output (max. 0 ma) (only for test purposes) A Output PROFIBUS-DP data line A (outgoing) B Output PROFIBUS-DP data line B (outgoing) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved 0 D - Reference potential for VP (terminal ) (only for test purposes) X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X/ - 0VV reference potential for actuators - 0VV reference potential for actuators D V V VI VI A B V 0AXX 0 0 System Manual - Drive System for Decentralized Installation

14 Connection with PROFIBUS MFZ connection module with MFP fieldbus module L L MFZ MFP X L L mm (AWG0). mm (AWG) mm (AWG0) X0 X 0 0 x V DC A B V A B D VP A B PROFIBUS DP () () D D V V A B V 0AXX = Potential level = Potential level () EMC metal cable gland Terminal assignment X0 A Input PROFIBUS-DP data line A (incoming) B Input PROFIBUS-DP data line B (incoming) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved VP Output V output (max. 0 ma) (only for test purposes) A Output PROFIBUS-DP data line A (outgoing) B Output PROFIBUS-DP data line B (outgoing) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved 0 D - Reference potential for VP (terminal ) (only for test purposes) X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors - - Reserved - - Reserved - - Reserved - - Reserved 0 System Manual - Drive System for Decentralized Installation

15 Connection with PROFIBUS Connecting MFZ, MFZ Field Distributor with MFP... MFZ, MFZ connection modules connected with MFP, MFP fieldbus module and two separate V DC voltage circuits L L MFZ MFZ MFP MFP () 0 X L L mm (AWG) mm (AWG0) X0 x V DC A B V () A B D A B PROFIBUS DP D () VP D V V VI VI A B V V V 0AXX 0 Terminal assignment = Potential level = Potential level () EMC metal cable gland () Assignment of terminals - starting on page X A Input PROFIBUS-DP data line A (incoming) 0 B Input PROFIBUS-DP data line B (incoming) D - Data reference potential for PROFIBUS-DP (only for test purposes) A Output PROFIBUS-DP data line A (outgoing) B Output PROFIBUS-DP data line B (outgoing) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved VP Output V output (max. 0 ma) (only for test purposes) D - Reference potential for VP (terminal ) (only for test purposes) Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X0/ - 0VV reference potential for voltage potential - 0VV reference potential for voltage potential 0 System Manual - Drive System for Decentralized Installation

16 Connection with PROFIBUS MFZ, MFZ connection module with MFP fieldbus module and one common V DC voltage circuit L L X L L mm (AWG0) 0 mm (AWG) MFZ MFP MFP 0 (). mm (AWG) 0 X0 MFZ 0 0 x V DC A B V A B D A B D PROFIBUS () DP () VP D V V VI VI A B V 0AXX = Potential level = Potential level () EMC metal cable gland () Assignment of terminals - starting on page Terminal assignment X0 A Input PROFIBUS-DP data line A (incoming) B Input PROFIBUS-DP data line B (incoming) D - Data reference potential for PROFIBUS-DP (only for test purposes) A Output PROFIBUS-DP data line A (outgoing) B Output PROFIBUS-DP data line B (outgoing) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved VP Output V output (max. 0 ma) (only for test purposes) D - Reference potential for VP (terminal ) (only for test purposes) Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X0/ - 0VV reference potential for voltage potential - 0VV reference potential for voltage potential System Manual - Drive System for Decentralized Installation

17 Connection with PROFIBUS MFZ, MFZ connection module with MFP fieldbus module L L X L L mm (AWG0) 0 mm (AWG) MFZ MFP 0 () 0. mm (AWG) X0 MFZ x V DC A B V A B D A B 0 0 D PROFIBUS () DP () VP D V V A B V = Potential level () EMC metal cable gland () Assignment of terminals - starting on page 0AXX 0 Terminal assignment X0 A Input PROFIBUS-DP data line A (incoming) B Input PROFIBUS-DP data line B (incoming) D - Data reference potential for PROFIBUS-DP (only for test purposes) A Output PROFIBUS-DP data line A (outgoing) B Output PROFIBUS-DP data line B (outgoing) D - Data reference potential for PROFIBUS-DP (only for test purposes) - - Reserved VP Output V output (max. 0 ma) (only for test purposes) D - Reference potential for VP (terminal ) (only for test purposes) Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI - Reserved VI - Reserved - - Reserved - Reserved 0 System Manual - Drive System for Decentralized Installation

18 Connection with InterBus (Copper Line). Connection with InterBus (Copper Line) Types of the InterBus Interface The MFI can be connected to the remote bus as well as the installation remote bus. The principal distinguishing feature between these types of interfaces can be found in the structure of the bus cable. Normal remote bus cables consist of -core cables twisted together in pairs for data transmission. In the installation remote bus, the wires for data transmission may be supplemented by the power supply for the MFI and active sensors. Remote Bus Connection The typical remote bus connection for IP0 units involves a -pin sub D plug. The following wiring examples show how MFIs are connected to units on the input or output end using -pin sub D plugs. INTERBUS Master max. 00 m (max.,00 ft.) MFI UL RC MFI INTERBUS BA TR max.. km (max. miles) max. 00 m (max.,00 ft.) SYS-F MFI MM UL RC MFI INTERBUS BA TR SYS-F MM MFI UL RC MFI INTERBUS BA TR SYS-F MM 00AEN System Manual - Drive System for Decentralized Installation

19 Connection with InterBus (Copper Line) Line Type D-MFI (-pin Sub D to MFI) Line Type MFI-D (MFI to - pin Sub D) The incoming remote bus is picked off from the preceding module using a -pin Sub D plug. The subsequent InterBus module is connected using a -pin Sub D socket. X0 MFZ (INTERB US) 0 0 () 0 0 GN YE PK GY BN GN YE PK GY BN - V DC () () () () DO /DO DI /DI COM () () DO /DO DI /DI COM () () 00AXX 0 () Incoming remote bus cable () Connect shield of incoming/outgoing remote bus cable with EMC metal cable gland at MFZ housing () Outgoing remote bus cable () Assignment of terminals - starting on page () -pole Sub-D connector () -pole Sub-D socket () Strain relief = Potential level System Manual - Drive System for Decentralized Installation 0

20 UL RC BA TR SYS-F UL RC BA TR SYS-F UL RC BA TR SYS-F Connection with InterBus (Copper Line) Installation Remote Bus Connection An -core cable is used for the installation remote bus. In addition to the strands for transmitting data, the cable also carries the V DC supply voltage for the MFI bus electronics and the active sensors. Incoming remote bus Installation remote bus max. 0m IBS IP CBK MFI MFI MFI Installation remote bus terminal MFI INTERBUS MFI INTERBUS MFI INTERBUS MM MM MM Outgoing/continuing remote bus V supply voltage 00AEN The maximum number of modules which can be connected to an installation remote bus terminal depends on the current consumption of the individual modules. Line Type CCO-I MFI (IP Round Connector MFI Terminals) A special InterBus installation remote bus terminal is required in order to open an installation remote bus segment. The installation remote bus can be connected to this bus terminal (e.g. type IBS IP CBK /F) using an IP round plug connector (type CCO-I). X0 MFZ (InterBus) 0 0 () 0 0 GN YE PK GY BN () () () DO /DO DI /DI COM RBST V 0V YE/GN BU 0AXX () IP round connector () incoming installation remote bus cable () Connect shield of installation remote bus cable with an EMC cable gland on the MFZ housing. () Assignment of terminals - starting on page = Potential level System Manual - Drive System for Decentralized Installation

21 Connection with InterBus (Copper Line) MFZA Connection with MOVIMOT (in combination with MFI, MFI, MFI) MFZ MFZ (INTERBUS) X0 () 0 0 () 0 0 V V V RS RS- V MOVIMOT R L f/f Ka Kb RS- RS MFI... /DO DO /DI DI COM /DO DO /DI DI COM - V DC () () 0AXX Terminal assignment = Potential level () For separate assembly of MFZ / MOVIMOT : Connect the shield of the RS- cable via an EMC metal cable gland on MFZ and MOVIMOT housing. () Ensure equipotential bonding between all bus stations. () Assignment of terminals - starting on page X0 /DO Input Incoming remote bus, negated data send direction (green) DO Input Incoming remote bus, data send direction (yellow) /DI Input Incoming remote bus, negated data receive direction (pink) DI Input Incoming remote bus, data receive direction (gray) COM - Reference potential (brown) /DO Output Outgoing remote bus, negated data send direction (green) DO Output Outgoing remote bus, data send direction (yellow) /DI Output Outgoing remote bus, negated data receive direction (pink) DI Output Outgoing remote bus, data receive direction (gray) 0 COM - Reference potential (brown) V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors V Output V power supply for MOVIMOT RS Output Communications link to MOVIMOT terminal RS RS- Output Communications link to MOVIMOT terminal RS- - 0V reference potential for MOVIMOT 0 System Manual - Drive System for Decentralized Installation 0

22 Connection with InterBus (Copper Line) Connecting Field Distributor MFZ with MFI... (Installation Remote Bus Connection) Line Type CCO-I MFI IP round connector MFI terminals A special InterBus installation remote bus terminal is required in order to open an installation remote bus segment. The installation remote bus can be connected to this bus terminal (e.g. type IBS IP CBK /F) using an IP round plug connector (type CCO-I). MFZ connection module with MFI/MFI fieldbus module L L MFI X mm (AWG0) MFZ V MFI YE/GN L L. mm (AWG) mm (AWG0) X0 X 0 0 /DO DO /DI DI COM /DO DO /DI DI COM V V VI VI V GN YE PK GY BN BU () () () DO /DO DI /DI COM RBST V 0V BU YE GN GY PK BN YE/GN () Kl./X Kl./X Kl./X0 Kl./X0 Kl./X0 Kl./X0 Kl./X0 () 0AXX = Potential level = Potential level () EMC metal cable gland () Incoming installation remote bus cable () Outgoing installation remote bus cable () IP round connector System Manual - Drive System for Decentralized Installation

23 Connection with InterBus (Copper Line) Terminal assignment X0 /DO Input Incoming remote bus, negated data send direction (green) DO Input Incoming remote bus, data send direction (yellow) /DI Input Incoming remote bus, negated data receive direction (pink) DI Input Incoming remote bus, data receive direction (gray) COM - Reference potential (brown) /DO Output Outgoing remote bus, negated data send direction (green) DO Output Outgoing remote bus, data send direction (yellow) /DI Output Outgoing remote bus, negated data receive direction (pink) DI Output Outgoing remote bus, data receive direction (gray) 0 COM - Reference potential (brown) X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X/ - 0VV reference potential for actuators - 0VV reference potential for actuators 0 System Manual - Drive System for Decentralized Installation 0

24 Connection with InterBus (Copper Line) MFZ connection module with fieldbus module MFI L L MFZ MFI YE/GN X. mm (AWG) L X0 X 0 0 L mm (AWG0) mm (AWG0) GN YE PK GY BU /DO DO /DI DI COM /DO DO /DI DI COM V V BN () () () DO /DO DI /DI COM RBST V 0V BU YE GN GY PK BN YE/GN () Kl./X Kl./X Kl./X0 Kl./X0 Kl./X0 Kl./X0 Kl./X0 () 0AXX = Potential level () EMC metal cable gland () Incoming installation remote bus cable () Outgoing installation remote bus cable () IP round connector 0 System Manual - Drive System for Decentralized Installation

25 Connection with InterBus (Copper Line) Terminal assignment X0 /DO Input Incoming remote bus, negated data send direction (green) DO Input Incoming remote bus, data send direction (yellow) /DI Input Incoming remote bus, negated data receive direction (pink) DI Input Incoming remote bus, data receive direction (gray) COM - Reference potential (brown) /DO Output Outgoing remote bus, negated data send direction (green) DO Output Outgoing remote bus, data send direction (yellow) /DI Output Outgoing remote bus, negated data receive direction (pink) DI Output Outgoing remote bus, data receive direction (gray) 0 COM - Reference potential (brown) X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors - - Reserved - - Reserved - - Reserved - - Reserved 0 System Manual - Drive System for Decentralized Installation 0

26 Connection with InterBus (Copper Line) Connecting MFZ, MFZ Field Distributor with MFI... (Installation Remote Bus Connection) Line type CCO-I IP round connector MFI terminals MFI A special InterBus installation remote bus terminal is required in order to open an installation remote bus segment. The installation remote bus can be connected to this bus terminal (e.g. type IBS IP CBK /F) using an IP round plug connector (type CCO-I). MFZ, MFZ connection modules with MFI/MFI fieldbus module L L MFZ MFI MFI YE/GN 0 X mm (AWG0) L L () 0. mm (AWG) X0 MFZ 0 0 V /DO DO /DI DI COM /DO DO /DI DI COM V V VI VI V GN YE PK GY BN BU () () () DO /DO DI /DI COM RBST V 0V BU YE GN GY PK BN YE/GN () Kl. Kl. Kl. Kl. Kl. Kl. Kl. () () EMC metal cable gland = Potential level () incoming installation remote bus cable () outgoing installation remote bus cable = Potential level () IP round connector () Assignment of terminals - starting on page 00AXX System Manual - Drive System for Decentralized Installation

27 Connection with InterBus (Copper Line) Terminal assignment X0 /DO Input Incoming remote bus, negated data send direction (green) DO Input Incoming remote bus, data send direction (yellow) /DI Input Incoming remote bus, negated data receive direction (pink) DI Input Incoming remote bus, data receive direction (gray) COM - Reference potential (brown) /DO Output Outgoing remote bus, negated data send direction (green) DO Output Outgoing remote bus, data send direction (yellow) /DI Output Outgoing remote bus, negated data receive direction (pink) DI Output Outgoing remote bus, data receive direction (gray) 0 COM - Reference potential (brown) V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X0/ - 0VV reference potential for actuators - 0VV reference potential for actuators 0 System Manual - Drive System for Decentralized Installation 0

28 Connection with InterBus (Copper Line) MFZ, MFZ connection modules with MFI fieldbus module L L X mm (AWG0) L L MFZ MFZ MFI YE/GN 0 0. mm (AWG) 0 0 () X0 GN YE PK GY BN BU /DO DO /DI DI COM /DO DO /DI DI COM V V () () () DO /DO DI /DI COM RBST V 0V BU YE GN GY PK BN YE/GN () Kl. Kl. Kl. Kl. Kl. Kl. Kl. () 0AXX = Potential level () EMC metal cable gland () Incoming installation remote bus cable () Outgoing installation remote bus cable () IP round connector () Assignment of terminals - starting on page System Manual - Drive System for Decentralized Installation

29 Connection with InterBus (Copper Line) Terminal assignment X0 /DO Input Incoming remote bus, negated data send direction (green) DO Input Incoming remote bus, data send direction (yellow) /DI Input Incoming remote bus, negated data receive direction (pink) DI Input Incoming remote bus, data receive direction (gray) COM - Reference potential (brown) /DO Output Outgoing remote bus, negated data send direction (green) DO Output Outgoing remote bus, data send direction (yellow) /DI Output Outgoing remote bus, negated data receive direction (pink) DI Output Outgoing remote bus, data receive direction (gray) 0 COM - Reference potential (brown) V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors - - Reserved - - Reserved - - Reserved - - Reserved 0 System Manual - Drive System for Decentralized Installation 0

30 RC TR RC TR RC RC TR TR RC TR Connection with InterBus (Fiber Optic). Connection with InterBus (Fiber Optic) Connection of Communication and V DC Supply InterBus and V DC supply are installed via rugged-line plug connector. 0AXX ) Fiber optic (InterBus remote bus) ) US/US voltage supply The cable connectors are not part of the SEW scope of delivery (manufactured by Phoenix-Contact). It is absolutely necessary to observe the project planning and installation guidelines for the rugged-line connection technology of Phoenix-Contact. Fitting the Bus Cable Connector The cable connectors can be connected to the bus module in four different ways (see the following figure). IB IB DIAG DIAG MFI INTERBUS INTERBUS RL RL () () RC US US DI0 DI0 DI DI DI DI TR US US FO FO DI DI DI DI DI DI FO FO IB IB DIAG DIAG MFI MFI INTERBUS INTERBUS RL RL RC US US DI0 DI0 DI DI DI DI TR US US FO FO DI DI DI DI DI DI FO FO SYS-F SYS-F Remote OUT (X) SYS-F SYS-F Remote OUT (X) Remote IN (X) Remote IN (X) () () IB IB DIAG DIAG MFI INTERBUS INTERBUS RL RL RC US US DI0 DI0 DI DI DI DI TR US US FO FO DI DI DI DI DI DI FO FO SYS-F SYS-F IB DIAG MFI INTERBUS INTERBUS RL RL IB DIAG US US DI0 DI0 DI DI DI DI US US FO FO DI DI DI DI DI DI FO FO Remote OUT (X) SYS-F SYS-F Remote IN (X) Remote OUT (X) Remote IN (X) 0AXX Cable connectors may only be connected with de-energized equipment. Do not use the clip of the cable connector to pull the connector into the correct position. Caution: Cable connectors not in use must be fitted with a dummy plug to ensure the enclosure! System Manual - Drive System for Decentralized Installation

31 Connection with InterBus (Fiber Optic) Assembly Switch off the voltage. Open the clip (.) and sufficiently insert the connector into the module electronics (.) Close the clip (.) Disassembly Switch off the voltage. Open the clip and pull the connector away from the module in the direction of the cables. Supply Voltage The two available supply voltages are used as follows: US: V DC supply of bus logic, sensors and MOVIMOT US: Supply of actuators (for current consumption see Technical Data) Contact Assignment MFI INTERBUS RL US FO FO US DI0 IB DIAG DIAG RC US TR US IB DIAG DIAG RC RC US MFI INTERBUS INTERBUS RL RL TR DI0 DI DI DI US DI0 DI0 DI DI DI TR US US FO DI DI DI DI DI FO SYS-F DI DI DI.. IB DIAG DIAG MFI MFI INTERBUS INTERBUS RL RL DI DI DI DI DI RC RC US US DI0 DI0 DI DI DI DI TR US FO FO SYS-F. 0AXX.eps 0 SYS-F US US US US US US US US US US US US US US US US 0 0AXX System Manual - Drive System for Decentralized Installation

32 Connection with InterBus (Fiber Optic) Cable Installation Cabling for the plug connectors requires maintaining a distance that is dependent upon the bending radius of the cable type being used (observe the project planning and installation guidelines for rugged-line connection technology from Phoenix-Contact). R min R min 0AXX Line Lengths < m Line lengths < of m are only permitted using the special pre-fabricated IBS RL CONNECTION-LK cable link (observe the project planning and installation guidelines for rugged-line connection technology from Phoenix-Contact). System Manual - Drive System for Decentralized Installation

33 Connection with InterBus (Fiber Optic) Sample Topology of an InterBus Design with Rugged-Line INTERBUS- Interface module MFI. B MFI. B Rugged-Line bus terminal Remote bus Dummy connector Remote bus (max.. km in copper and polymer fiber) Bus segment (max. 00 m in copper Max. m/0m in polymer fiber) Remote bus Remote bus Remote bus spur line MFI. B MFI. B MFI. B 0 Remote bus Dummy connector 000AEN If fiber optic cables are installed as permanent polymer fibers, a maximum distance of 0 m can be linked between two remote bus stations. If flexible polymer fibers are used, the maximum distance is m. System Manual - Drive System for Decentralized Installation 0

34 Connection with InterBus (Fiber Optic) MFZA Connection with MOVIMOT (in combination with MFI and MFI) MFZ (INTERB US) X0 () MOVIMOT 0 0 MFZ 0 0 V RS RS- V R L f/f Ka Kb RS- RS () MFI MFI () () 0AXX = Potential level () For separate assembly of MFZ / MOVIMOT : Connect the shield of the RS- cable via an EMC metal cable gland on MFZ and MOVIMOT housing. () Ensure equipotential bonding between all bus stations. () Assignment of terminals - starting on page Terminal assignment X0 - Reserved V Output V power supply for MOVIMOT RS Output Communications link to MOVIMOT terminal RS RS- Output Communications link to MOVIMOT terminal RS- 0V reference potential for MOVIMOT 0 System Manual - Drive System for Decentralized Installation

35 Connection with InterBus (Fiber Optic) Connecting MFZ Field Distributor with MFI MFI MFZ MFI MFI L X L. mm (AWG) mm (AWG0) X0 X 0 0 L mm (AWG0) L 0AXX = Potential level = Potential level Connecting MFZ, MFZ Field Distributor with MFI MFI MFZ MFZ MFI MFI L = Potential level = Potential level () Assignment of terminals - starting on page 0 () X X0 L L 0 0. mm (AWG) 0 mm (AWG0) L 0AXX 0 System Manual - Drive System for Decentralized Installation 0

36 UL UL UL UL UL UL Connection with DeviceNet. Connection with DeviceNet DeviceNet Connection Capabilities The MFD can be connected either via a multi-port or via a T-connector. If the connection with MFD is removed, the remaining stations will not be influenced, and the bus can remain active. MFD MFD MFD Bus terminating resistor MFI INTERBUS RC BA TR MFI INTERBUS RC BA TR MFI INTERBUS RC BA TR SYS-F SYS-F SYS-F T-connector T-connector T-connector MFD MFD MFD RC RC RC MFI INTERBUS BA TR MFI INTERBUS BA TR MFI INTERBUS BA TR SYS-F SYS-F SYS-F Bus terminating resistor 0 Multi-Port 00AEN System Manual - Drive System for Decentralized Installation

37 Connection with DeviceNet MFZ Connection with MOVIMOT (in combination with DeviceNet) MFZ MFD... X Terminal assignment () MFZ (DeviceNet) : DRAIN : V : V- : CAN_H : CAN_L = Potential level X0 V 0 V - V DC V RS RS- () () () () For separate assembly of MFZ / MOVIMOT : Connect the shield of the RS- cable via an EMC metal cable gland on MFZ and MOVIMOT housing. () Ensure equipotential bonding between all bus stations. () Assignment of terminals - starting on page X0 V- Input DeviceNet reference potential 0V CAN_L Input/output CAN_L data line DRAIN Input Equipotential bonding CAN_H Input/output CAN_H data line V Input DeviceNet power supply V - - Reserved - - Reserved - - Reserved - - Reserved Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors V Output V power supply for MOVIMOT RS Output Communications link to MOVIMOT terminal RS RS- Output Communications link to MOVIMOT terminal RS- - 0V reference potential for MOVIMOT V MOVIMOT R L f/f Ka Kb RS- RS 0AXX 0 0 System Manual - Drive System for Decentralized Installation

38 Connection with DeviceNet Connecting MFZ Field Distributor with MFD... MFZ connection module with MFD, MFD fieldbus module and two separate V DC voltage circuits L L MFZ MFD MFD X L mm (AWG0). mm (AWG) mm (AWG0) X0 X 0 0 L x V DC V V VI VI V V V V X : DRAIN : V : V- : CAN_H : CAN_L 000AXX = Potential level = Potential level Terminal assignment X0 V- Input DeviceNet reference potential 0V CAN_L Input/output CAN_L data line DRAIN Input Equipotential bonding CAN_H Input/output CAN_H data line V Input DeviceNet power supply V Reserved X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X/ - 0VV reference potential for actuators - 0VV reference potential for actuators System Manual - Drive System for Decentralized Installation

39 Connection with DeviceNet MFZ connection module with MFD, MFD fieldbus module and one common V DC voltage circuit L L MFZ MFD MFD x V DC X mm (AWG0) L L. mm (AWG) mm (AWG0) X0 X 0 0 V V VI VI V V 0 Terminal assignment = Potential level = Potential level X : DRAIN : V : V- : CAN_H : CAN_L X0 V- Input DeviceNet reference potential 0V CAN_L Input/output CAN_L data line DRAIN Input Equipotential bonding CAN_H Input/output CAN_H data line V Input DeviceNet power supply V Reserved X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X/ - 0VV reference potential for actuators - 0VV reference potential for actuators 000AXX 0 System Manual - Drive System for Decentralized Installation

40 Connection with DeviceNet MFZ connection module with MFD fieldbus module L L MFZ MFD X L L mm (AWG0). mm (AWG) mm (AWG0) X0 X 0 0 x V DC V V V V X : DRAIN : V : V- : CAN_H : CAN_L 000AXX = Potential level = Potential level Terminal assignment X0 V- Input DeviceNet reference potential 0V CAN_L Input/output CAN_L data line DRAIN Input Equipotential bonding CAN_H Input/output CAN_H data line V Input DeviceNet power supply V Reserved X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors Reserved System Manual - Drive System for Decentralized Installation

41 Connection with DeviceNet Connecting MFZ, MFZ Field Distributor with MFD MFZ, MFZ connection modules with MFD, MFD fieldbus module and two separate V DC voltage circuits L L MFZ MFZ MFD MFD () 0 X L L 0. mm (AWG) 0 0 mm (AWG0) X0 x V DC V V V VI VI V V V 0 X : DRAIN : V : V- : CAN_H : CAN_L 0AXX Terminal assignment = Potential level = Potential level () Assignment of terminals - starting on page X0 V- Input DeviceNet reference potential 0V CAN_L Input/output CAN_L data line DRAIN Input Equipotential bonding CAN_H Input/output CAN_H data line V Input DeviceNet power supply V Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuator (digital outputs) jumpered with terminal X0/ - 0VV reference potential for actuators - 0VV reference potential for actuators 0 System Manual - Drive System for Decentralized Installation

42 Connection with DeviceNet MFZ, MFZ connection modules with MFD, MFD fieldbus module and one common V DC voltage circuit: L L X mm (AWG0) 0 mm (AWG) L L MFZ MFD MFD () 0 0. mm (AWG) X0 MFZ 0 0 x V DC V V V VI VI V X : DRAIN : V : V- : CAN_H : CAN_L 0AXX Terminal assignment = Potential level = Potential level () Assignment of terminals - starting on page X0 V- Input DeviceNet reference potential 0V CAN_L Input/output CAN_L data line DRAIN Input Equipotential bonding CAN_H Input/output CAN_H data line V Input DeviceNet power supply V Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X0/ - 0VV reference potential for actuators - 0VV reference potential for actuators System Manual - Drive System for Decentralized Installation

43 Connection with DeviceNet MFZ, MFZ connection modules with MFD fieldbus module L L MFZ MFD 0 () X L L 0. mm (AWG) mm (AWG0) 0 mm (AWG) X0 MFZ x V DC 0 0 V V V V 0 X : DRAIN : V : V- : CAN_H : CAN_L 0AXX = Potential level () Assignment of terminals - starting on page Terminal assignment X0 V- Input DeviceNet reference potential 0V CAN_L Input/output CAN_L data line DRAIN Input Equipotential bonding CAN_H Input/output CAN_H data line V Input DeviceNet power supply V Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors Reserved 0 System Manual - Drive System for Decentralized Installation

44 UL UL UL UL UL UL Connection with CANopen open. Connection with CANopen CANopen Connection Capabilities MFO is connected via T connector. If the connection with MFO is removed, the remaining stations will not be influenced, and the bus can remain active. MFO MFO MFO () MFI INTERBUS RC BA TR MFI INTERBUS RC BA TR MFI INTERBUS RC BA TR SYS-F SYS-F SYS-F () () () MFO MFO MFO RC RC RC MFI INTERBUS BA TR MFI INTERBUS BA TR MFI INTERBUS BA TR SYS-F SYS-F SYS-F () () () () 00AXX () Bus terminating resistor 0 Ω () T connector 0 System Manual - Drive System for Decentralized Installation

45 Connection with CANopen MFZ Connection with MOVIMOT (in combination with CANopen) MFZ MFO... X Terminal assignment () MFZ (CANopen) : CAN_SHLD : CAN_V : CAN_ : CAN_H : CAN_L = Potential level X0 V 0 V - V DC V RS RS- () () () () For separate assembly of MFZ / MOVIMOT : Connect the shield of the RS- cable via an EMC metal cable gland on MFZ and MOVIMOT housing. () Ensure equipotential bonding between all bus stations. () Assignment of terminals - starting on page X0 CAN_ Input CANopen reference potential 0V CAN_L Input/output CAN_L data line CAN_SHLD Input Equipotential bonding CAN_H Input/output CAN_H data line CAN_V Input CANopen voltage supply V - - Reserved - - Reserved - - Reserved - - Reserved Reserved V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X0/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors V Output V power supply for MOVIMOT RS Output Communications link to MOVIMOT terminal RS RS- Output Communications link to MOVIMOT terminal RS- 0V reference potential for MOVIMOT V MOVIMOT R L f/f Ka Kb RS- RS 00AXX 0 0 System Manual - Drive System for Decentralized Installation

46 Connection with CANopen Connecting MFZ Field Distributor with MFO... MFZ connection module with MFO, MFO fieldbus module and two separate V DC voltage circuits L L MFZ MFO MFO X L mm (AWG0). mm (AWG) mm (AWG0) X0 X 0 0 L x V DC V V VI VI V V V V X : CAN_SHLD : CAN_V : CAN_ : CAN_H : CAN_L 00AXX Terminal assignment = Potential level = Potential level X0 CAN_ Input CANopen reference potential 0V CAN_L Input/output CAN_L data line CAN_SHLD Input Equipotential bonding CAN_H Input/output CAN_H data line CAN_V Input CANopen voltage supply V Reserved X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X/ - 0VV reference potential for actuators - 0VV reference potential for actuators System Manual - Drive System for Decentralized Installation

47 Connection with CANopen MFZ connection module with MFO, MFO fieldbus module and one common V DC voltage circuit L L MFZ MFO MFO x V DC X mm (AWG0) L L. mm (AWG) mm (AWG0) X0 X 0 0 V V VI VI V V 0 Terminal assignment = Potential level = Potential level X : CAN_SHLD : CAN_V : CAN_ : CAN_H : CAN_L X0 CAN_ Input CANopen reference potential 0V CAN_L Input/output CAN_L data line CAN_SHLD Input Equipotential bonding CAN_H Input/output CAN_H data line CAN_V Input CANopen voltage supply V Reserved X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors VI Input V power supply for actuators (digital outputs) VI Output V power supply for actuators (digital outputs) jumpered with terminal X/ - 0VV reference potential for actuators - 0VV reference potential for actuators 00AXX 0 System Manual - Drive System for Decentralized Installation

48 Connection with CANopen MFZ connection module with MFO fieldbus module L L MFZ MFO X L L mm (AWG0). mm (AWG) mm (AWG0) X0 X 0 0 x V DC V V V V X : CAN_SHLD : CAN_V : CAN_ : CAN_H : CAN_L 00AXX = Potential level = Potential level Terminal assignment X0 CAN_ Input CANopen reference potential 0V CAN_L Input/output CAN_L data line CAN_SHLD Input Equipotential bonding CAN_H Input/output CAN_H data line CAN_V Input CANopen voltage supply V Reserved X V Input V power supply for module electronics and sensors V Output V power supply (jumpered with terminal X/) - 0V reference potential for module electronics and sensors - 0V reference potential for module electronics and sensors Reserved System Manual - Drive System for Decentralized Installation

Compact Manual. Drive System for Decentralized Installation InterBus Interfaces and Field Distributors

Compact Manual. Drive System for Decentralized Installation InterBus Interfaces and Field Distributors Drive Technology \ Drive Automation \ System Integration \ Services Compact Manual Drive System for Decentralized Installation InterBus Interfaces and Field Distributors Edition 11/009 1676641 / EN SEW-EURODRIVE

More information

Manual. Fieldbus Interfaces / Field Distributors for Controlling MOVI-SWITCH. Edition 12/ / EN

Manual. Fieldbus Interfaces / Field Distributors for Controlling MOVI-SWITCH. Edition 12/ / EN Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services Fieldbus Interfaces / Field Distributors for Controlling MOVI-SWITCH Edition 1/006 11543019 / EN Manual SEW-EURODRIVE

More information

Drive System for Decentralized Installation PROFIBUS Interfaces and Field Distributors

Drive System for Decentralized Installation PROFIBUS Interfaces and Field Distributors Drive System for Decentralized Installation PROFIBUS Interfaces and Field Distributors Edition 04/2003 P R O F I PROCESS FIELD BUS B U S Manual 10564516 / EN SEW-EURODRIVE Contents 1 Valid Components...

More information

Manual. Drive System for Decentralized Installation PROFIBUS Interfaces, Field Distributors. Edition 07/2006 P R O F I B U S FC / EN

Manual. Drive System for Decentralized Installation PROFIBUS Interfaces, Field Distributors. Edition 07/2006 P R O F I B U S FC / EN Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services P R O F I PROCESS FIELD BUS B U S Drive System for Decentralized Installation PROFIBUS Interfaces, Field Distributors

More information

Manual. Drive System for Decentralized Installation AS-Interface Interfaces, AS-Interface Field Distributors. Edition 07/ / EN

Manual. Drive System for Decentralized Installation AS-Interface Interfaces, AS-Interface Field Distributors. Edition 07/ / EN Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services Drive System for Decentralized Installation AS-Interface Interfaces, AS-Interface Field Distributors Edition 07/2006

More information

Manual. Drive System for Decentralized Installation PROFIBUS Interfaces, Field Distributors P R O F B U S. Edition 11/ / EN

Manual. Drive System for Decentralized Installation PROFIBUS Interfaces, Field Distributors P R O F B U S. Edition 11/ / EN Drive Technology \ Drive Automation \ System Integration \ Services P R O F I PROCESS FIELD BUS B U S Drive System for Decentralized Installation PROFIBUS Interfaces, Field Distributors Edition 11/2008

More information

Operating Instructions

Operating Instructions Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services Explosion-Proof MOVIMOT Drives in Category 3D GC310000 Edition 12/2005 11407026 / EN Operating Instructions SEW-EURODRIVE

More information

Operating Instructions

Operating Instructions Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services MOVIMOT MM..C Edition 11/26 1144141 / EN Operating Instructions SEW-EURODRIVE Driving the world Contents 1 General Notes...

More information

Compact Manual. Drive System for Decentralized Installation EtherNet/IP Interfaces, Field Distributors * _1115*

Compact Manual. Drive System for Decentralized Installation EtherNet/IP Interfaces, Field Distributors * _1115* Drive Technology \ Drive Automation \ System Integration \ Services *22511466_1115* Compact Manual Drive System for Decentralized Installation EtherNet/IP Interfaces, Field Distributors Edition 11/2015

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Quick Start Guide. MOVIMOT MM..D With DRS/DRE/DRP AC Motor

Drive Technology \ Drive Automation \ System Integration \ Services. Quick Start Guide. MOVIMOT MM..D With DRS/DRE/DRP AC Motor Drive Technology \ Drive Automation \ System Integration \ Services Quick Start Guide MOVIMOT MM..D With DRS/DRE/DRP AC Motor Edition 02/2013 20099347 / EN SEW-EURODRIVE Driving the world General information

More information

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual. INTERBUS Inline Bus Coupler; Remote Bus Connections Via D-SUB Connectors REMOTE IN BA UL RD RC DSUB LD AUTOMATIONWORX Data Sheet 6362_en_03 PHOENIX CONTACT - 11/2007 REMOTE OUT Description The bus coupler

More information

Operating Instructions. MOVIMOT MM..D With AC Motor DRS/DRE/DRP. Edition 12/ / EN

Operating Instructions. MOVIMOT MM..D With AC Motor DRS/DRE/DRP. Edition 12/ / EN Drive Technology \ Drive Automation \ System Integration \ Services MOVIMOT MM..D With AC Motor DRS/DRE/DRP Edition 12/27 1167512 / EN Operating Instructions SEW-EURODRIVE Driving the world Contents Contents

More information

Edition. INTERBUS UFI11A Fieldbus Interface 06/2002. Manual / EN

Edition. INTERBUS UFI11A Fieldbus Interface 06/2002. Manual / EN INTERBUS UFI11A Fieldbus Interface Edition 06/2002 Manual 1052 5114 / EN 1 Overview of the System... 4 2 Unit Structure... 5 2.1 Front view... 5 3 Installation and Operation with Autosetup... 6 3.1 Installation

More information

IBS ST 24 BK-T INTERBUS-S. Data Sheet. Bus Terminal Module. Product Description

IBS ST 24 BK-T INTERBUS-S. Data Sheet. Bus Terminal Module. Product Description IBS ST 24 BK-T Data Sheet INTERBUS-S Bus Terminal Module Data Sheet Revision A 08/994 Product Description The IBS ST 24 BK-T bus terminal module is the head station for an INTERBUS ST compact station in

More information

High Performance FieldBus cards

High Performance FieldBus cards Profibus card VLT 5000/6000... 2 Interbus card VLT 5000... 4 DeviceNet card VLT 5000... 6 Modbus+ card VLT 5000... 8 Lonworks cards VLT 5000/6000 Free Topology... 10 Lonworks cards VLT 5000/6000 78 kbps

More information

RoHS. Shock / vibration resistant. Short circuit proof. Flexible. . XXXX e. . XXXX e

RoHS. Shock / vibration resistant. Short circuit proof. Flexible. . XXXX e. . XXXX e The Sendix multiturn encoders 5862 and 5882, with SSI or RS485 interface and combined optical and magnetic sensor technology, offer a maximum resolution of 25 bits. These encoders are programmable via

More information

This data sheet is only valid in association with the IL SYS INST UM E user manual.

This data sheet is only valid in association with the IL SYS INST UM E user manual. Inline analog input terminal, 4 inputs for connecting voltage signals Data sheet 8081_en_01_C01 PHOENIX CONTACT 2015-04-14 1 Description The terminal is designed for use within an Inline station. It is

More information

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma Data sheet 105597_en_01 PHOENIX CONTACT 2014-10-24 1 Description The module is designed for use within an ST station. It is

More information

IBS IL 24 BK RB-T-2MBD

IBS IL 24 BK RB-T-2MBD IBS IL 24 BK RB-T-2MBD INTERBUS Inline Terminal for Connecting a Remote Bus Branch Data Sheet 6766A 01/2003 $! $ * This data sheet is only valid in association with the "Configuring and Installing the

More information

Manual. MOVIMOT MM..D Functional Safety (including field distributor) * _0516*

Manual. MOVIMOT MM..D Functional Safety (including field distributor) * _0516* Drive Technology \ Drive Automation \ System Integration \ Services *22515062_0516* Manual MOVIMOT MM..D Functional Safety (including field distributor) Edition 05/2016 22515062/EN SEW-EURODRIVE Driving

More information

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink Characteristics variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink Main Range of product Altivar 32 Product or component type Product destination Product specific application

More information

MOVIDRIVE MDX61B INTERBUS DFI11B Fieldbus Interface

MOVIDRIVE MDX61B INTERBUS DFI11B Fieldbus Interface MOVIDRIVE MDX61B INTERBUS DFI11B Fieldbus Interface Edition 03/2004 Manual 1126 3717 / EN SEW-EURODRIVE 1 Important Notes... 4 2 Introduction... 5 3 Assembly / Installation Instructions... 7 3.1 Installing

More information

I/O Modules Active Stand-Alone: Interbus

I/O Modules Active Stand-Alone: Interbus I/O Modules Active Stand-Alone: Interbus Interbus a Fieldbus System Interbus is an internationally used fieldbus system. Since the first presentation of the system in 1987 the Interbus has been modified,

More information

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name Product data sheet Characteristics XPSMF3542 Preventa safety PLC compact - Profibus DP protocol Main Range of product Product or component type Safety module name Safety module application Nov 13, 2018

More information

ELR W1/ 6-24DC. Extract from the online catalog. Order No.:

ELR W1/ 6-24DC. Extract from the online catalog. Order No.: Extract from the online catalog ELR W1/ 6-24DC Order No.: 2982090 Illustration shows item ELR W1/ 6-24DC Electronic reversing load relay, for driving DC motors, with light indicator and protection circuit,

More information

PowerDRIVE-Box GEL 6505 Interface for controlling up to 5 positioning drives

PowerDRIVE-Box GEL 6505 Interface for controlling up to 5 positioning drives PowerDRIVE-Box GEL 6505 Interface for controlling up to 5 positioning drives Technical information Version 208-05 GEL 6505A: Box for top hat rail mounting, IP 20 variant General The PowerDRIVE-Box GEL

More information

Rotary Measuring Technology Absolute encoders, Multiturn, optional with incremental track

Rotary Measuring Technology Absolute encoders, Multiturn, optional with incremental track Electronic multiturn gear with intelligent sensing technology (IST) Integrative Technology Max. 4 programmable outputs* for the SSI version Programmable parameters include*: code type, resolution per revolution,

More information

Active Distributors AS-i Safety, Active Distributors AS-i

Active Distributors AS-i Safety, Active Distributors AS-i Active Distributors Safety, Active Distributors x connectors for Periphery connection via, M cable sockets or push in terminals (Figure similar) Figure Type Inputs Safety, SIL, Cat. x 9 mm, -channels Safety

More information

IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B

IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area Data Sheet 5764B 09/2000 # % $ This data sheet is only valid in association with the INTERBUS Inline System Manual IB IL SYS

More information

Operating Instructions

Operating Instructions Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services MOVIFIT FC Edition 02/2007 11574216 / EN Operating Instructions SEW-EURODRIVE Driving the world Contents 1 General Information...

More information

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors AUTOMATIONWORX Data Sheet 7119_en_02 PHOENIX CONTACT - 03/2007 Description The ILB IB 24 DO16-DSUB module

More information

ATV32HU75N4 variable speed drive ATV kw V - 3 phase - with heat sink

ATV32HU75N4 variable speed drive ATV kw V - 3 phase - with heat sink Characteristics variable speed drive ATV32-7.5 kw - 400 V - 3 phase - with heat sink Main Range of product Altivar 32 Product or component type Product destination Product specific application Function

More information

High Performance FieldBus cards

High Performance FieldBus cards Profibus card VLT 5000/6000...2 Interbus card VLT 5000... 4 DeviceNet card VLT 5000... 6 Modbus+ card VLT 5000...8 Lonworks card VLT 5000/6000 Free Topology... 10 Lonworks cards VLT 5000/6000 78 kbps and

More information

Operating Instructions

Operating Instructions Drive Technology \ Drive Automation \ System Integration \ Services Operating Instructions MOVIMOT MM..D With DRS/DRE/DRP AC Motor Edition 12/21 1717 / EN SEW-EURODRIVE Driving the world Contents Contents

More information

ILC 200 IB ILC 200 IB-PAC

ILC 200 IB ILC 200 IB-PAC ILC 200 IB ILC 200 IB-PAC Inline Controller with Programming Capabilities According to IEC 61131-3 Data Sheet 5883C04 07/2010 & & * ILC 200 IB and ILC 200 IB-PAC only differ in the scope of supply (see

More information

SUBCON-PLUS-PROFIB...

SUBCON-PLUS-PROFIB... Fast connector for PROFIBUS systems Data sheet 101610_en_10 PHOENIX CONTACT 2017-03-27 1 Description The SUBCON-PLUS-PROFIB... D-SUB series is specifically designed for use in PROFIBUS systems up to 12

More information

Operating Instructions

Operating Instructions Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ s Explosion-Proof MOVI-SWITCH Drives in Category 3D GC320000 Edition 09/2005 11212411 / EN Operating Instructions SEW-EURODRIVE

More information

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1.

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1. PSI-MODEM-/PB Broadband PROFIBUS extender, PROFIBUS leased line modem Data sheet 104396_en_03 1 Description PHOENIX CONTACT 2013-08-21 1.1 Features The PROFIBUS extender can be used to easily network PROFIBUS

More information

Operating instructions Evaluation system for flow sensors VS / / 2013

Operating instructions Evaluation system for flow sensors VS / / 2013 Operating instructions Evaluation system for flow sensors VS3000 7097 / 0 07 / 203 Contents Preliminary note...2 2 Safety instructions...3 3 Function and features... Mounting.... Mounting of the sensors...

More information

VersaMax IP Input Module

VersaMax IP Input Module Module is used to accept digital input signals. Module Specifications Housing dimensions (width x height x depth) Connection style Operating temperature Storage temperature Operating/storage humidity 60mm

More information

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output Product datasheet Characteristics XPSMF4000 Preventa safety PLC compact - Safe Ethernet Main Range of product Product or component type Safety module name Safety module application Preventa Safety automation

More information

IBS IL 24 RB-LK-2MBD:

IBS IL 24 RB-LK-2MBD: Inline Branch Terminal for an INTERBUS Remote Bus; Connections Using Fiber Optics RC D RD LD RB-LK FO AUTOMATIONWORX X2 X1 OUT Data Sheet PHOENIX CONTACT - 08/2005 Description The branch terminal is designed

More information

Compact Operating Instructions

Compact Operating Instructions Drive Technology \ Drive Automation \ System Integration \ Services Compact Operating Instructions MOVIMOT MM..D with AS-Interface and AC Motor DRS/DRE/ Edition 04/2010 16951611/ EN SEW-EURODRIVE Driving

More information

TM7NCOM16A CANopen interface block - IP67-16 I/O - M12

TM7NCOM16A CANopen interface block - IP67-16 I/O - M12 Characteristics CANopen interface block - IP67-16 I/O - M12 Main Range of product Product or component type Range compatibility Enclosure material Bus type [Ue] rated operational voltage Input/Output number

More information

Revision. Drive System for Decentralized Installation Fieldbus Interfaces, Field Distributors * _0717*

Revision. Drive System for Decentralized Installation Fieldbus Interfaces, Field Distributors * _0717* Drive Technology \ Drive Automation \ System Integration \ Services *23558857_0717* Revision Drive System for Decentralized Installation Fieldbus Interfaces, Field Distributors Edition 07/2017 23558857/EN

More information

ISOMETER isoev425/isoev425hc with coupling device AGH420

ISOMETER isoev425/isoev425hc with coupling device AGH420 with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles isoev425_d00126_04_d_xxen/06.2018 with coupling device AGH420 Insulation monitoring

More information

11 PROFIBUS Fieldbus Connector

11 PROFIBUS Fieldbus Connector 750-960 PROFIBUS Fieldbus Connector 634 54 mm> < < 45mm 5 < 36,7mm < 372 mm < 54 mm < 36 mm / 42 in < 5-6 mm / 022 in < 0 mm / 0394 in The fieldbus connector links a PROFIBUS device

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety Drive Technology \ Drive Automation \ System Integration \ Services Manual Control Cabinet Inverter MOVITRAC B Functional Safety Edition 05/2009 16811216 / EN SEW-EURODRIVE Driving the world Content Content

More information

ATV320U07M2C variable speed drive ATV kW V - 1 phase - compact

ATV320U07M2C variable speed drive ATV kW V - 1 phase - compact Characteristics variable speed drive ATV320-0.75kW - 200...240V - 1 phase - compact Main Range of product Product or component type Product specific application Device short name Format of the drive Product

More information

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description I/O extension module, eight digital transistor outputs Data sheet 105364_en_00 PHOENIX CONTACT 2013-03-26 1 Description The I/O extension module can be used in conjunction with Radioline wireless modules

More information

Motor controllers CMMO-ST

Motor controllers CMMO-ST q/w Worldwide: Superb: Easy: Festo core product range Covers 80% of your automation tasks Always in stock Festo quality at an attractive price Reduces procurement and storing complexity qready for dispatch

More information

Installation and Setup

Installation and Setup Installation and Setup 1 In This Chapter Installing the H PBC The Profibus Network Configuring the Controller Installing the H PBC Setting the Node Address Setting the Node Address Profibus DP is usually

More information

Rotary Measuring Technology Absolute encoders, Multiturn, DeviceNet

Rotary Measuring Technology Absolute encoders, Multiturn, DeviceNet High IP High shaft load capacity Shock/vibration resistant Short-circuit proof Reverse polarity protection Compact and Rugged: Minimal installation depth High shock and vibration values Very compact (only

More information

ATV320U04N4C variable speed drive ATV kW V - 3 phase - compact

ATV320U04N4C variable speed drive ATV kW V - 3 phase - compact Characteristics variable speed drive ATV320-0.37kW - 380...500V - 3 phase - compact Main Range of product Product or component type Product specific application Device short name Format of the drive Product

More information

ATV32H075M2 variable speed drive ATV32-0,75 kw V - 1 phase - with heat sink

ATV32H075M2 variable speed drive ATV32-0,75 kw V - 1 phase - with heat sink Characteristics variable speed drive ATV32-0,75 kw - 200 V - 1 phase - with heat sink Main Range of product Altivar 32 Product or component type Product destination Product specific application Function

More information

SK TU4-PBR Part number:

SK TU4-PBR Part number: SK TU4-PBR Part number: 275 281 100 PROFIBUS DP External Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their

More information

ATV32HU30N4 variable speed drive ATV32-3 kw V - 3 phase - with heat sink

ATV32HU30N4 variable speed drive ATV32-3 kw V - 3 phase - with heat sink Characteristics variable speed drive ATV32-3 kw - 400 V - 3 phase - with heat sink Complementary Line current Apparent power Prospective line Isc Nominal output current Maximum transient current Speed

More information

ATV61HU55M3 ATV61 5,5 kw 7,5HP 240V single phase EMC IP20

ATV61HU55M3 ATV61 5,5 kw 7,5HP 240V single phase EMC IP20 Product data sheet Characteristics ATV61HU55M3 ATV61 5,5 kw 7,5HP 240V single phase EMC IP20 Main Range of product Altivar 61 Product or component type Product specific application Component name Motor

More information

5 Fieldbus Technology

5 Fieldbus Technology 5 Fieldbus Technology Ex e / Ex i 10922E00 The s Ex e/ex i connect intrinsically safe Foundation Fieldbus H1 or Profibus PA field devices to a non-intrinsically safe / Ex e trunk. Up to four intrinsically

More information

MOVITRAC 31.. Frequency Inverter

MOVITRAC 31.. Frequency Inverter MOVITRAC 31.. Frequency Inverter PROFIBUS Fieldbus (FFP 31.. Option and Size 0/DP) Manual Edition 04/98 08/198/96 0922 6818 / 0498 Important Notes Read this User Manual carefully before you start installation

More information

Edition MOVI-SWITCH 08/2003. Operating Instructions / EN

Edition MOVI-SWITCH 08/2003. Operating Instructions / EN MOVI-SWITCH Edition 08/200 Operating Instructions 11210915 / EN SEW-EURODRIVE Contents 1 Important Notes... 2 MOVI-SWITCH Safety Notes... 5 Unit Design... 6.1 MOVI-SWITCH 1E... 6.2 MOVI-SWITCH 2S... 7.

More information

ATV61HC31Y variable speed drive ATV61-310kW - 690V - without EMC filter

ATV61HC31Y variable speed drive ATV61-310kW - 690V - without EMC filter Product data sheet Characteristics ATV61HC31Y variable speed drive ATV61-310kW - 690V - without EMC filter Main Range of product Altivar 61 Product or component type Product specific application Component

More information

SIMOCODE 3UF Motor Management and Control Devices

SIMOCODE 3UF Motor Management and Control Devices Technical specifications General data applicable to the basic units, current measuring modules, current/voltage measuring modules, expansion modules, decoupling module and operator panel Permissible ambient

More information

EPGG001. Fieldbus Gateway RS-232 to PROFINET. Industrial Communication. Technical Data. Part Number

EPGG001. Fieldbus Gateway RS-232 to PROFINET. Industrial Communication. Technical Data. Part Number Fieldbus Gateway RS-232 to PROFINET EPGG001 Part Number Easy handling Gateway from RS-232/422/485 interfaces to PROFINET With two Industrial Ethernet ports Technical Data Electrical Data Supply Voltage

More information

Motor units MTR-DCI, intelligent servo motors

Motor units MTR-DCI, intelligent servo motors -U- Type discontinued Motor units MTR-DCI, intelligent servo motors Key features General information The motor unit MTR-DCI is an innovative motor with integrated power electronics for positioning tasks.

More information

Operating displays for MC_40A (without fieldbus) [1] Operation LED V1 (three colors: green/red/yellow) Color Operating state Description

Operating displays for MC_40A (without fieldbus) [1] Operation LED V1 (three colors: green/red/yellow) Color Operating state Description Operating displays for MC_0A (without fieldbus) Operation. Operating displays for MC_0A (without fieldbus) The operating status of MOVIDRIVE compact MC_0A are displayed on LED V. [] Figure 0: MOVIDRIVE

More information

SK TU4-IOE-M12-C Part Number

SK TU4-IOE-M12-C Part Number SK TU4-IOE-M2-C Part Number 275 28 256 IO Extension Only qualified electricians are allowed to install and commission the module described below. An electrician is a person who, because of their technical

More information

IBS ST (ZF) 24 BK LB-T

IBS ST (ZF) 24 BK LB-T . - IBS ST (ZF) 24 BK LB-T Bus Terminal Module With Local Bus Branch Data Sheet 5049B 09/1999 5049B000 ' " # " % 1 6-4 * 7 5 7 4 + * ) * ) - -,, 4, 4 A? BEC K H= JE 7 5 * K I 6 A H E = " 8, + @ K A 1@

More information

VersaMax IP I/O Module

VersaMax IP I/O Module Module accepts four digital input signals and provides four digital outputs. It connects to a local bus that is interfaced to a Profibus-DP / PROFINET network by a Profibus Interface Unit (IC677PBI001)

More information

Communications & Networking

Communications & Networking 8-Point Source Input & 8-Point Transistor Sink Output odule () Key features include: Communicate with network 8-point source input and 8-point sink output module Removable terminal blocks Use as remote

More information

TROXNETCOM AS-i. Modules. Communication interface between a component and the controller. 06/2015 DE/en K

TROXNETCOM AS-i. Modules. Communication interface between a component and the controller. 06/2015 DE/en K .2 X X testregistrierung TROXNETCOM AS-i Communication interface between a component and the controller The module is used to connect the control system with the components Integral AS-Interface slave

More information

ISOMETER isoev425 with coupling device AGH420

ISOMETER isoev425 with coupling device AGH420 with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles Preliminary datasheet isoev425_d00126_02_d_xxde/09.2015 with coupling device

More information

EC07 EC63. Compatible actuators: ERL2 ESD2. How to order EC 07 B. Series. B Installation. method

EC07 EC63. Compatible actuators: ERL2 ESD2. How to order EC 07 B. Series. B Installation. method Controller EC07 EC63 Compatible actuators: ERL ESD Features Compact, light weight and thin (Body width 35mm) Can be set without manual Perfect installation compatibility with actuator PC software available

More information

ATV32HD11N4 variable speed drive ATV32-11 kw V - 3 phase - with heat sink

ATV32HD11N4 variable speed drive ATV32-11 kw V - 3 phase - with heat sink Product data sheet Characteristics ATV32HD11N4 variable speed drive ATV32-11 kw - 400 V - 3 phase - with heat sink Complementary Line current Apparent power Prospective line Isc Nominal output current

More information

FACTORY AUTOMATION QUICK START GUIDE IC-KP-*

FACTORY AUTOMATION QUICK START GUIDE IC-KP-* FACTORY AUTOMATION QUICK START GUIDE IC-KP-* IDENTControl units With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products

More information

over time. Improper wiring practices could result in drive malfunction due to loose terminal connections. Control Circuit Terminal Block Functions Dri

over time. Improper wiring practices could result in drive malfunction due to loose terminal connections. Control Circuit Terminal Block Functions Dri Figure 3.14 Main speed frequency reference. Multi-function programmable Safety input Forward run/stop Reverse run/stop External fault Fault reset Multi-step speed 1 main/aux switch Multi-step speed 2 Jog

More information

ATV32H055N4 variable speed drive ATV kw V - 3 phase - with heat sink

ATV32H055N4 variable speed drive ATV kw V - 3 phase - with heat sink Product datasheet Characteristics ATV32H055N4 variable speed drive ATV32-0.55 kw - 400 V - 3 phase - with heat sink Complementary Line current Apparent power Prospective line Isc Nominal output current

More information

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller),

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller), Fast connector with screw terminal block connection for fieldbus systems Data sheet 00287_en_02 PHOENIX CONTACT 207-04-2 Description The SUBCON-PLUS/... D-SUB series is specifically designed for use in

More information

Revision to the Operating Instructions

Revision to the Operating Instructions Drive Technology \ Drive Automation \ System Integration \ Services *21341397_1114* Revision to the Operating Instructions Decentralized Drive and Application Controller MOVIPRO ADC Edition 11/2014 21341397/EN

More information

ATV32HD11N4 variable speed drive ATV32-11 kw V - 3 phase - with heat sink

ATV32HD11N4 variable speed drive ATV32-11 kw V - 3 phase - with heat sink Product datasheet Characteristics ATV32HD11N4 variable speed drive ATV32-11 kw - 400 V - 3 phase - with heat sink Complementary Line current Apparent power Prospective line Isc Nominal output current Maximum

More information

ATV32HU30N4 variable speed drive ATV32-3 kw V - 3 phase

ATV32HU30N4 variable speed drive ATV32-3 kw V - 3 phase Product datasheet Characteristics ATV32HU30N4 variable speed drive ATV32-3 kw - 400 V - 3 phase - with heat sink Complementary Line current Apparent power Prospective line Isc Nominal output current Maximum

More information

ATV71QC16N4 variable speed drive ATV71Q - 160kW / 250HP V - IP20

ATV71QC16N4 variable speed drive ATV71Q - 160kW / 250HP V - IP20 Characteristics variable speed drive ATV71Q - 160kW / 250HP - 380...480V - IP20 Main Range of product Product or component type Device short name Product destination Product specific application Assembly

More information

SK TU4-CAO-C Part number:

SK TU4-CAO-C Part number: SK TU4-CAO-C Part number: 275 281 151 CANopen External Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their

More information

Installation Instructions Temperature transmitter TAA /00 06/2011

Installation Instructions Temperature transmitter TAA /00 06/2011 Installation Instructions Temperature transmitter TAA431 706042/00 06/2011 Contents 1 Functions and features...3 2 Installation...4 2.1 Addressing...4 2.2 Mechanical installation...4 2.3 Connection to

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input Safety + standard I/O in one module Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category IP20

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Active Distributors ASi Safety, IP67

Active Distributors ASi Safety, IP67 x connectors for profile cable Periphery connection via M8 cable sockets M cable sockets (Figure similar) Figure Type Inputs, SIL 3, Cat. 4 9 mm 9 mm 9 mm 9 mm channels channels channels channels Inputs

More information

Extension module for lighting control

Extension module for lighting control s 3 842 DESIGO RXC Extension module for lighting control Extension to the RXC30 / RXC31 / RXC38 room controller RXC40.1 RXC40.5 The RXC40 extension module is used in conjunction with an RXC30, RXC31 or

More information

Remote Process Actuation Control System AirLINE PHOENIX INLINE

Remote Process Actuation Control System AirLINE PHOENIX INLINE Remote Process Actuation Control System AirLINE PHOENIX INLINE Type 8644 can be combined with... Fully compatible with Phoenix Inline System Combination of Fieldbus, pilot valves and I/O modules High flexibility

More information

ATV61HC11N4 SPEED DRIVE 150 HP 460 V ATV61

ATV61HC11N4 SPEED DRIVE 150 HP 460 V ATV61 Product datasheet Characteristics ATV61HC11N4 SPEED DRIVE 150 HP 460 V ATV61 ATV61HC11N4 has not been replaced. Please contact your customer care centre for more information. Main Discontinued Range of

More information

AS-i 3.0 motor modules

AS-i 3.0 motor modules AS-i 3.0 4I/4O modules for two 4 V motorized rollers e.g. Interroll (EC00, EC300 or EC30) or RULMECA (RDR BL-) or Rollex (type 840) with binary and analog outputs Mixed input/output slave Speed setting

More information

vacon nx user manual basic i/o boards expander i/o boards adapter i/o boards ac drives

vacon nx user manual basic i/o boards expander i/o boards adapter i/o boards ac drives vacon nx ac drives basic i/o boards expander i/o boards adapter i/o boards user manual vacon 2 General information. GENERAL INFORMATION VACON NX range embodies a wide selection of expander and adapter

More information

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016 Original operating instructions Safety relay with relay outputs with and without delay UK G50S 803638 / 00 0 / 06 Contents Preliminary note...4. Symbols used...4 Safety instructions...5 3 Items supplied...6

More information

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ]

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ] CPX-Terminal Brief description CPX analogue I/O modules CPX-2AE CPX-4AE CPX-2AA English 8080173 2017-11e [8080175] Translation of the original instructions Documentation on the product For all available

More information

Manual. MOVIDRIVE Flying Saw Application. Edition 04/2004 A5.J / EN

Manual. MOVIDRIVE Flying Saw Application. Edition 04/2004 A5.J / EN Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services MOVIDRIVE Flying Saw Application A.J6 Edition 4/24 1122771 / EN Manual SEW-EURODRIVE Driving the world 1 Important Notes...

More information

ATV930U30M3 variable speed drive - ATV930-3kW - 200/240Vwith braking unit - IP21

ATV930U30M3 variable speed drive - ATV930-3kW - 200/240Vwith braking unit - IP21 Characteristics variable speed drive - ATV930-3kW - 200/240Vwith braking unit - IP21 Main Range of product Product or component type Device application Device short name Variant Product destination Mounting

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

IB IL 24 DI 16 IB IL 24 DI 16-PAC

IB IL 24 DI 16 IB IL 24 DI 16-PAC IB IL 24 DI 16 IB IL 24 DI 16-PAC Inline Terminal With 16 Digital Inputs Data Sheet 555302 06/2003 + Features This data sheet is only valid in association with the IB IL SYS PRO UM E User Manual or the

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information