1 April 07 Sheet 0.0- Lighting Control Systems Pow-R-Command Contents General Information Controller Features Panelboard Options System Options Pow-R-Command Panelboard Electronics and Controllable Circuit Breakers Controllers Controller Selection Externally Mounted Controllers Breaker Control Bus Controllable Circuit Breakers Master and Panelboards Master Panelboards and Powered Panelboards Master/ Panelboards SLAN Subnet Networks Ethernet RS MLAN Networks PRC Ethernet Interface Module (PRCEIM) Digital Switches and Low Voltage Switches Digital Switches Digital Switch Network Low Voltage Switches Switch Wallplates Connecting Field Wiring Control Devices Digital Inputs Analog Input Analog Outputs Analog I/O Module Switch Override Controller Software Lighting Optimization Software PC Central Software Recommended Minimum Computer Specifications PRC Advanced Controllers PRC Applications Typical Electric Room Layout Multi-Story Commercial Building Manual Occupant Light Level Control Automatic Daylight Harvesting Control Remote Mounted Analog Module Emergency Lighting Control Receptacle Control Integrated Metering Building Management System Integration and Interfacing Third-Party Modbus Master Control Connection Panelboard Pow-R-Command Retrofits Panelboard Ratings and Dimensions Pow-R-Command in Pow-R-Line a Construction Pow-R-Command in Pow-R-Line a Construction Series Ratings Specifications See Eaton s Product Specification Guide, available on CD or on the Web. CSI Format: Pow-R-Command Section 7D Section 09 CA0800E

2 .0- Pow-R-Command Family General Information April 07 Sheet 0 Pow-R-Command Pow-R-Command Pow-R-Command is a lighting control and energy management system that integrates branch circuit protection, control (switching and dimming) and metering into a single panelboard enclosure. The integrated design simplifies electrical distribution and control system design, and eliminates separate equipment enclosures and associated wiring. Other benefits include smaller equipment wall space requirement, reduced installation labor and lower total installed cost. Pow-R-Command systems are designed to meet or exceed ASHRAE, IECC and LEED requirements. Pow-R-Command Intelligent Panelboards use Eaton Pow-R-Line a and a lighting panelboard platforms to mount Pow-R-Command electronics and solenoid-operated controllable circuit breakers. Controller Features Pow-R-Command controllers are available in four different models (PRC750E, PRC000E, PRC500E and PRC000E). Controller features depend on the model number. Available features include: 5-day time clock Astronomical time clock with sunrise and sunset offsets Holiday and daylight savings time schedules Low voltage inputs for occupancybased and occupant override control Digital Switch Network (DSN) for connecting Pow-R-Command Digital Switches Analog inputs for connecting light level sensors Analog outputs provides manual dimming and automatic daylight harvesting control Backlit LCD touchscreen and Ethernet Maintenance Port for front panel programming, monitoring and override control Safe and easy access to low voltage field wiring by loosening two captive screws and folding display down Ethernet and RS-85 network communications Peer-to-peer controller communications protocol Master/ panelboard subnetwork (SLAN) communications Preconfigured web pages access from Maintenance Port and Ethernet network for system programming, monitoring and override control BACnet/IP communications protocol for integrating with building management systems notification of system alarms Modbus TCP pass-through mode for providing metering information Demand response logic Configurable source logic (OR, AND, XOR, NAND, LAST EVENT) Downloadable firmware for updating controller features System events logging Compatible with previous generation PRC systems See Table.- for controller selection chart. Panelboard Options Pow-R-Command panelboards are assembled using Eaton Pow-R-Line a and a lighting panelboards. Pow-R- Command panelboard options include: NEMA,, R and X enclosures Surface and flush mounting Column-width and Integrated Facility System (IFS) construction Main lug and main circuit breaker 00 A, A and 0 A panelboard interiors Interior sizes include 8-, -, -, 0-, 7- and 8-circuit configurations Service entrance label Retrofits into existing panelboard enclosures (consult factory) GHQRD single- and two-pole, 5 A, 0 A and A controllable circuit breakers suitable for 80Y/7 Vac loads GHQRDEL 5 A and 0 A emergency lighting controllable circuit breakers BABRSP single-pole 5 A, 0 A and A and two-pole 5 A, 0 A, A, A and 50 A controllable circuit breakers suitable for 08/0 Vac and 0/0 Vac loads Branch circuits series ratings Surge suppression devices IQ M panelboard meter and PXBCM Branch Circuit Monitor Consult factory for available options not listed above. See Page.9- for panelboard ratings and dimensions. System Options Pow-R-Command lighting control systems are used for a wide range of applications. The following system options are commonly used to meet control sequence, remote access and system maintenance requirements: Digital or low voltage switches Photosensors (outdoor, indoor, skylight and atrium) Low voltage input and analog I/O expansion modules Lighting Optimization Software (PRCLOS) provides system configuration, programming, override control and monitoring Ethernet Interface Module (EIM) connects PRC RS-85 network to dedicated PC or facility Ethernet network PRC5000 Advanced System Controller with optional custom building graphics Consult factory for system options not listed above. CA0800E

3 April 07 Sheet 0 Pow-R-Command Panelboard Electronics.- Pow-R-Command Panelboard Electronics and Controllable Circuit Breakers Controllers Pow-R-Command 5th generation E Series controller family includes PRC000E, PRC500E, PRC000E and PRC750E models. Specifiers select the controller to meet specific control and communication requirements. Controllers are shipped in two basic mounting configurations: integrated into Pow-R-Line a and a lighting panelboard or externally mounted in a controller cabinet. PRC-E Controller Controller standard features include: Color backlit high resolution LCD touchscreen for front panelboard programming, monitoring and override control Schedule, occupancy and override control logic Low voltage digital inputs to connect switches and occupancy sensors Local controller programming using Ethernet connection Maintenance Port to access controller Web pages or use Lighting Optimization Software (PRCLOS) Master panelboard to Panelboard SLAN sub-net network communications port Control and monitor up to 8 solenoid-operated circuit breaker poles Controller optional features include: Analog I/O to provide 0 0 Vdc dimming and daylight harvesting control Digital Switch Network (DSN) RS-85 serial network communications (CNET) Ethernet network communications Powerful peer-to-peer communications protocol to provide global commands BACnet/IP protocol for straightforward integration with building management systems Remote access to onboard Web pages over Ethernet network connection Controller low voltage compartment is located behind the LCD touchscreen display. Access is achieved by loosening the top two captive screws located at the top of each side of the display. Figure.- Controller Low Voltage Compartment A. Low voltage cables entry B. Digital inputs C. Universal inputs (digital or analog) D. Analog outputs E. External power source ( Vdc and PWR) F. BCB status LEDs G. Digital Switch Network auxiliary board (DSN) H. RS-85 controller network auxiliary board (CNET) I. SLAN connector J. Ethernet network connector K. RS-85 controller network connector (CNET) L. Digital Switch Network connector (DSN) M. LCD touchscreen display connector N. USB connector O. SD card connector P. Service connector factory use only Q. External power.0 A (Littelfuse Part #000) R. Internal fuse (Littelfuse Part #000) S. Status LEDs T. Maintenance Port (Ethernet) U. ON/OFF power switch V. Controller power connection (Vin) W. MLAN communications for connecting Analog Modules (PRCEAEM) and Modbus RTU compatible metering devices CA0800E

4 .- Pow-R-Command Panelboard Electronics April 07 Sheet 0 Controller Selection Table.- can be used to select the controller that includes features needed to meet application requirements. Table.- provides additional details to aid in controller selection. Table.-. Controller Selection Features PRC000E Master Panelboard PRC500E Master Panelboard PRC000E Master Panelboard PRC750E Master Panelboard Panelboard Schedule-based control Occupant override control Master/ SLAN Dimming/daylight harvesting control Digital Switch Network RS-85 network communications MLAN device expansion network Ethernet communications BACnet/IP protocol notification Modbus TCP Ethernet pass-through Access to controller Web server Modbus RTU communications Maintenance Port Ethernet Network Maintenance Port Only Maintenance Port Only Maintenance Port Only CA0800E

5 April 07 Sheet 05 Table.-. PRC-E Controller Features Pow-R-Command Panelboard Electronics.- Controller PRCEP PRC750E PRC000E PRC500E PRC000E Inputs Dry-contact inputs Universal inputs, configurable dry-contact or analog 0 0 Vdc Outputs Maximum number of controllable circuit breakers Analog outputs, 0 0 Vdc, 80 ma sink or ma source current Power supply to power external devices, 00 ma at Vdc/ Vac Power supply to power integrated Breaker Control Bus and SLAN V+ and V PRCEPP Inputs and Outputs Accessory Modules Analog Module (PRCEAEM) w/ 8 universal inputs configurable as 8 UI/8 AO 8 UI/8 AO 8 UI/8 AO maintained dry-contact or analog 0 0 Vdc, 8 analog outputs 0 0 Vdc at 80 ma sink or source current Switch Override Controller (PRCSOC) w/ 0 maintained dry-contact inputs, 0 I/ O 0 I/ O 0 I/ O optional card includes two-wire Vdc outputs for status LEDs Control Logic Panelboard configurations include 8,,, 0, 7 and 8 circuits Maximum number of control groups, 7 0 groups require PRCLOS software configuration day time clock Astronomical time clock with sunrise and sunset offsets Schedules Holidays Automatic daylight savings time Circuit breaker blink notice Override time switches Manual dimming and automatic daylight harvesting Configurable source logic (OR, AND, XOR, XNOR, NAND and LAST EVENT) Communications panelboard SLAN Maximum Breaker Control Bus (BCB) per SLAN Ethernet network BACnet/IP protocol notification, user configurable alarms Pow-R-Command RS-85 (CNET) Digital Switch Network (DSN) MLAN communications to Analog Module (PRCEAEM) MLAN communications to metering devices with Modbus RTU communications Modbus TCP pass-through metering mode Modbus RTU, Breaker Control Bus addresses Local Programming.-inch backlit color LCD touchscreen Front Maintenance Port (Ethernet) access to Web server 7 PRC Lighting Optimization Software (PRCLOS), Maintenance Port (Ethernet) access 7 Password protection Remote Programming Remote access to controller Web server via Ethernet connection PRC Lighting Optimization Software (PRCLOS) Password protection Memory SD card for logs and programming database (GB) Onboard capacitor to power clock chip during power outage (days) Refer to driver/ballast manufacturer specs to calculate maximum connected load. Connects to controller MLAN network. Requires PRCLOS configuration software. Maximum of seven PRCEAEM (PRC000E maximum one PRCEAEM) connected to MLAN network. 5 Connects to controller RS-85 CNET network. Maximum of eight meters with Modbus RTU communications. 7 Requires industry standard Ethernet patch cable. CA0800E

6 .- Pow-R-Command Panelboard Electronics April 07 Sheet 0 External Mounted Controllers External mounted controllers are available for retrofit and renovation projects when existing panelboards do not have required controller mounting space. External mounted controllers include controller and control power transformer mounted in a NEMA enclosure. Eaton Pow-R-Line a and a lighting panelboards can be converted to Pow-R-Command Panelboards (PRCEP) in the field by mounting Breaker Control Bus (BCB) and controllable circuit breakers directly to the interior. External mounted controllers are connected to the retrofitted PRCEP panelboard using the SLAN sub-net network communications. External Mounted Controller Table.-. External Mounted Controllers Controller Type Connected System Voltage Catalog Number PRC750E with display 0 Vac PRC750EECD-0 PRC750E with display 7 Vac PRC750EECD-7 PRC000E with display 0 Vac PRC000EECD-0 PRC000E with display 7 Vac PRC000EECD-7 PRC500E with display 0 Vac PRC500EECD-0 PRC500E with display 7 Vac PRC500EECD-7 PRC000E with display 0 Vac PRC000EECD-0 PRC000E with display 7 Vac PRC000EECD-7 PRCE Controller External Mounted Controller SLAN Alpha 0 AWG, conductor BCB # BCB # BCB # BCB # BCB #5 BCB # BCB #7 BCB #8 PRCEP PRCEP PRCEP PRCEP Figure.- External Mounted Controller SLAN Connection to Panelboards Note: For PRCE-SLAN-External Cabinet standard drawing references, visit Eaton.com/lightingcontrol. CA0800E

7 April 07 Sheet 07 Breaker Control Bus Pow-R-Command Panelboard Electronics Controllable Circuit Breakers Single- and two-pole solenoid operated controllable circuit breakers provide branch circuit protection and control of connected loads. Controllable circuit breakers are for electrical distribution systems up to 80Y/7 Vac. Controllable circuit breakers include status flag and temporary mechanical override. GHQRD Controllable Circuit Breakers.-5 Breaker Control Bus Breaker Control Bus (BCB) provides the electronic interface and power switching signal between the controller and solenoid-operated controllable circuit breaker. Each controller can be connected to a maximum of eight BCBs. Each BCB is connected to the controller by connecting SLAN sub-net network. BCB are installed and tested at the factory. Length of BCB is selected by the factory to fit the size of lighting panelboard being used. Available in 9-, 5- and -circuit lengths to match lighting panelboard configuration DIP switches to configure device SLAN sub-net network address between and 8 RUN, SLAN and PWR LEDs indicated operating status Factory mounted to panelboard interior rails and tested Breaker Control Bus (BCB) mounted Dual side Left side only or right side only Requires controlled loads to be located on the same side as BCB Reduces cost of installed equipment Field installs into existing Pow-R-Line a and a lighting panelboards Table.-. Breaker Control Bus Description Controlled Circuits Catalog Number 9-circuit breaker control bus 9 PRC000BCB-9R 5-circuit breaker control bus 5 PRC000BCB-5R -circuit breaker control bus PRC000BCB-R Single-Pole Two-Pole Table.-5. GHQRD Controllable Circuit Breakers Number of Poles Ampere Rating Interrupting Capacity (Symmetrical Amperes) Vac (50/0 Hz) 0 0/0 7 7/80 Catalog Number 5 5,000 5,000,000 GHQRD05 0 5,000 5,000,000 GHQRD00 5,000 5,000,000 GHQRD0 5 5,000 5,000,000 GHQRD05 0 5,000 5,000,000 GHQRD00 5,000 5,000,000 GHQRD0 Not recommended for existing PRC, PRC00, PRC750, PRC000 and PRC000 systems. GHQRSP controllable circuit breakers are compatible with these systems. CA0800E

8 .- Pow-R-Command Panelboard Electronics April 07 Sheet 08 GHQRDEL Emergency Controllable Circuit Breakers GHQRDEL controllable circuit breakers are designed to meet NEC 700.(F) for sources of power in unit equipment used for emergency lighting applications. The controllable circuit breaker includes both switched circuit for controlling lighting and standard non-switched circuit to provide power to the unit emergency charging and detection circuitry. Controllable circuit breaker includes a common handle tie and a common trip mechanism. Emergency Circuit Breaker Table.-. GHQRDEL Emergency Circuit Breaker Number of Poles Ampere Rating 5,000 GHQRDEL05 0,000 GHQRDEL00 Refer to Page.8- for typical field wiring drawing. BABRSP Controllable Circuit Breakers Table.-7. BABRSP Number of Poles Ampere Rating Interrupting Capacity (Symmetrical Amperes) Vac (50/0 Hz) 7 7/80 Single-Pole Two-Pole Interrupting Capacity (Symmetrical Amperes) Vac (50/0 Hz) 0 0/0 Catalog Number Catalog Number 5 0,000 BABRSP05 0 0,000 BABRSP00 0,000 BABRSP0 5 0,000 BABRSP05 0 0,000 BABRSP00 0,000 BABRSP0 0,000 BABRSP0 50 0,000 BABRSP050 BABRSPLC Plug Load Controllable Circuit Breakers Plug load controllable circuit breakers are used to meet new energy codes requiring 50% of receptacles to be switched ON and OFF using schedule- or occupancy-based control systems. The two-pole device includes a standard noncontrolled and controllable circuit breaker pole for connecting to split receptacles. The common handle tie disconnect meets 0 NEC 0. for multi-branch circuits with shared neutrals. Device includes common trip mechanism. Table.-8. BABRSPLC Number of Poles Ampere Rating BABRSPLC Interrupting Capacity (Symmetrical Amperes) Vac (50/0 Hz) 0 0/ Catalog Number 5,000 BABRSPLC05 0,000 BABRSPLC00 CA0800E

9 April 07 Sheet 09 Master and Panelboards.- Pow-R-Command Intelligent Panelboards are assembled in two basic configurations: Master Panelboard and Panelboard. Pow-R-Command systems are scalable using both Master and Panelboards to provide the right amount of control with reduced installed cost and system complexity. Master Panelboard Master Panelboards are designed for standalone and networked systems. Master Panelboard components include: PRC-E controller Low voltage power supply Breaker Control Bus (BCB) mounted Dual side Left side only or right side only Requires controlled loads to be located on the same side as BCB Reduces installed equipment cost Factory-installed SLAN cables Solenoid-operated controllable circuit breakers Option to add standard circuit breakers Option to add commonly used panelboard accessories, i.e., metering and surge protection devices Note: For PRCE-SLAN standard drawing references, visit Eaton.com/lightingcontrol. Controller with Power Supply Standard and Controllable Circuit Breakers Single- and Two-Pole Controllable Circuit Breakers Figure.-. Master Panelboard Breaker Control Bus Factory Installed SLAN Cable BCB BCB BCB BCB Controlled Side Controlled Side Controlled Side Controlled Side Dual Left Right Figure.-. Master Panelboard BCB Configurations CA0800E

10 .- Master and Panelboards System Configurations April 07 Sheet 0 Panelboard Panelboards (PRCEP) are designed to directly connect to Master Panelboard via controller SLAN sub-net network. Panelboard components include: Breaker Control Bus (BCB) Dual side Left side only or right side only Requires controlled loads to be located on the same side as BCB Reduces cost of installed equipment Factory-installed SLAN cables Solenoid-operated controllable circuit breakers Option to add standard circuit breakers Option to add commonly used panelboard accessories, i.e., metering and surge protection devices Note: For PRCE-SLAN standard drawing references, visit Eaton.com/lightingcontrol. Standard and Controllable Circuit Breakers Single- and Two-Pole Controllable Circuit Breakers Breaker Control Bus Factory Installed SLAN Cable Figure.-. Panelboard BCB BCB BCB BCB Controlled Side Controlled Side Controlled Side Controlled Side Dual Side Left Side Figure.-. Panelboard BCB Configurations Right Side CA0800E

11 April 07 Sheet Master and Panelboards System Configurations.- Powered Panelboard Powered Panelboards (PRCEPP) are designed to directly connect to Master Panelboard via controller SLAN sub-net network when the distance between the Master Panelboard and Panelboard exceeds 50 ft. Powered Panelboard components include: Low voltage power supply Breaker Control Bus (BCB) Dual side Left side only or right side only Requires controlled loads to be located on the same side as BCB Reduces cost of installed equipment Factory-installed SLAN cables Use Belden 05A shielded twisted pair cable to connect controller to Powered Panelboard BCB Solenoid-operated controllable circuit breakers Option to add standard circuit breakers Option to add commonly used panelboard accessories, i.e., metering and surge protection devices Powered Panelboards can be field converted to a Master Panelboard by installing the controller. Note: For PRCE-SLAN standard drawing references, visit Eaton.com/lightingcontrol. SLAN Connector Standard and Controllable Circuit Breakers Single- and Two-Pole Controllable Circuit Breakers Figure.-5. Powered Panelboard BCB Breaker Control Bus Mounting Bracket BCB XFMR BCB Mounting Bracket XFMR Power Supply with Mounting Bracket Factory Installed SLAN Cable Mounting Bracket BCB XFMR Controlled Side Controlled Side Controlled Side Controlled Side Dual Side Left Side Right Side Figure.-. Powered Panelboard BCB Configurations CA0800E

12 .- Master and Panelboards System Configurations April 07 Sheet Master Panelboard to Panelboard SLAN Sub-Net Network SLAN sub-net network is used to connect a single PRC-E controller to a maximum of eight Breaker Control Buses (BCB). The SLAN carries command signals from the controller to the appropriate BCB, which in turn, switches the solenoid-operated circuit breaker. Through the SLAN, the controller also polls BCB for status of the solenoid-operated circuit breakers. In addition to providing the communications path to the BCB, the SLAN wiring also provides a Vac from the control power transformer for powering the BCB and providing power to switch the solenoid-operated circuit breakers. SLAN connections SLAN+ and SLAN communications connections Power and Common power connections SLAN cable is specified ALPHA 0, 00 V, AWG, conductors Panelboard internal SLAN cables are factory installed Fiber-optic cable is recommended for outdoor, underground or between-structure applications VC + Alpha 0, AWG, Conductor VC Figure.-8. Breaker Control Bus-to-Breaker Control Bus Wiring Figure.-9. Breaker Control Bus SLAN Connector + Controller BCB # BCB # PRCE Controller VC + V C + To Next BCB, Maximum of 8 BCB # BCB # BCB # BCB # BCB #5 BCB # BCB #7 BCB #8 SLAN Alpha 0 AWG, conductor PRCE Master PRCEP PRCEP PRCEP Figure.-0. PRCE Master/ Panelboards SLAN Note: For PRCE-SLAN standard drawing references, visit Eaton.com/lightingcontrol. Figure.-7. Controller SLAN Connector CA0800E

13 April 07 Sheet Ethernet Networks PRC500E and PRC000E controllers include Ethernet network communications capabilities providing remote programming, monitoring and override functions. Using the Pow-R-Command peer-to-peer communications protocol, each controller connected to the Ethernet network can transmit and receive messages among the connected controllers. Not available in PRC750E and PRC000E controllers. PRC000E controller provides remote access to preconfigured Web pages to program, monitor and override the system over Ethernet network connection PRC000E controller may require PRCLOS software to program advanced features PRC500E controller requires PRCLOS software to remotely program, monitor and override the system Fiber-optic cable is recommended for outdoor, underground or between-structure applications Note: For PRCE-Ethernet standard drawing references, visit Eaton.com/lightingcontrol. Networks Ethernet Network Connector Figure.-. Controller Ethernet Network Connection Ethernet Master Personal Computer Master Figure.-. Remote Communications Over Ethernet Network Master.- Ethernet Personal Computer Personal Computer Patch Cable Connected to Maintenance Port Master Figure.-. Front Panel Connection to Ethernet Network Master Master CA0800E

14 .- Networks April 07 Sheet RS-85 CNET Networks PRC000E, PRC500E and PRC000E controllers include CNET RS-85 serial controller network communications capabilities providing remote programming, monitoring and override functions. Using Pow-R-Command peer-to-peer communications protocol, each controller connected to the CNET network can transmit and receive messages among the connected controllers. Not available in PRC750E controllers. CNET RS-85 serial network uses a two-wire, half-duplex network in a daisy-chained architecture. The connector provided in the controller low voltage compartment is for connecting the network in and out cables. The network operates independently of each controller, meaning that a controller can be powered down and the network will remain intact and operational. Up to 0 controllers and system accessories can be connected Requires daisy-chain network architecture Requires Belden 05A communications cable Maximum overall length of the RS-85 network should not exceed 00 feet When maximum length is exceeded, an RS-85 serial communications repeater may be required Fiber-optic cable is recommended for outdoor, underground or between-structure applications Peer-to-peer communications allows global commands between controllers Remote PC connection requires Ethernet Interface Module (PRCEIM) Front panel PC connection requires standard patch cable to connect to Maintenance Port PRCEIM provides master controller functions (refer to Page.- for details) PC connection to CNET requires Lighting Optimization Software (PRCLOS) Note: For PRCE-RS85-CNET standard drawing references, visit Eaton.com/lightingcontrol. RS-85 CNET Controller Figure.-. Controller RS-85 Serial Network Connection (CNET) PRCEIM Ethernet Master Personal Computer RS-85 Daisy Chain Twisted Pair with Shield Belden 05A or Equivalent Master Master Figure.-5. Remote Communications Over Ethernet to RS-85 Serial Network (CNET) Ethernet Personal Computer Dedicated PC Remotely Mounted PRCEIM Master RS-85 Daisy Chain Twisted Pair with Shield Belden 05A or Equivalent Master Master Figure.-. Dedicated PC Remote Communications Over RS-85 Serial Network (CNET) Personal Computer Patch Cable Connected to Maintenance Port Master RS-85 Daisy Chain Twisted Pair with Shield Belden 05A or Equivalent Master Master Figure.-7. Front Panel Communications to RS-85 Serial Network (CNET) CA0800E

15 April 07 Sheet 5 Networks.- MLAN Networks PRC000E, PRC500E and PRC000E controllers include MLAN RS-85 communications network for connecting a maximum of seven Analog Modules (PRCEAEM). Additionally, a maximum of eight meters equipped with Modbus RTU communications can be connected. MLAN is not available in PRC750E controllers. Connect maximum of seven Analog Modules (PRC000E maximum of one) PRC750E is not equipped with MLAN Connect maximum of eight metering devices equipped with Modbus RTU communications (PRC000E only), Modbus TCP pass-through mode implemented for providing metering information upon request from metering and monitoring systems Requires daisy-chain network architecture Requires Belden 05A shielded twisted pair communications cable Maximum 00 ft network length Network status available through controller Web pages Refer to Page.5- for Analog Module information Refer to Pages.8- and.8- for mains and branch circuit metering information Note: For MLAN network standard drawing references, visit Eaton.com/lightingcontrol. PRC000E/500E/000E Controller MLAN Modbus RTU PRCEAEM PRCEAEM RS-85 Daisy-Chain Twisted Pair with Shield Belden 05A or Equivalent PRCEAEM PRCEAEM PRCEAEM PRCEAEM MLAN Connections Figure.-8. Controller MLAN RS-85 Network Connection Meter Meter Meter Meter Meter Meter Meter PRCEAEM Meter Figure.-9. Controller MLAN RS-85 Network CA0800E

16 .- Networks April 07 Sheet PRC Ethernet Interface Module (PRCEIM) Pow-R-Command Ethernet Interface Module (PRCEIM) comes in a desktop enclosure and allows access to the Pow-R-Command controller RS-85 serial network (CNET). PRCEIM is recommended for remote access to PRC000E controllers. This device can be used as a master controller. Personal computer with Pow-R-Command Lighting Optimization Software (PRCLOS) is connected directly to the PRCEIM Ethernet port or connected over a facility Ethernet network. This device communicates at 0Base-T and must have a fixed IP address assignment on the Ethernet network. Connectors on the front of the PRCEIM are for Ethernet, CNET (RS-85 network, Belden 05A cable), and diagnostic network for local access to the device. PRCEIM is powered by using provided +5 Vdc power supply that plugs into any standard wall outlet. It also has an On/Off switch, power indicator LED and communication indicator LED. Used for remote access to controllers connected to CNET (RS-85 serial network) Connects to CNET using Belden 05A twisted-pair with shield, 0 ohm communications cable Recommended for systems using PRC000E controller Personal computer connected using Ethernet connection Requires fixed IP address Configured using Pow-R-Command Lighting Optimization Software (PRCLOS) Used to tunnel (PRCLOS) commands over CNET Can be configured to act as master scheduler 0 unique schedules and holidays Used to sync time clock of connected controllers Provides global alarm table Note: Refer to Figures.-5 and.- for connection architecture. Note: For PRCE-RS85-CNET standard drawing references, visit Eaton.com/lightingcontrol. Figure.-0. PRC Ethernet Interface Module (PRCEIM) RS-85 Serial Network Connection (CNET) CA0800E

17 April 07 Sheet 7 Digital and Low-Voltage Switches.- Digital and Low Voltage Switches Digital Switches Pow-R-Command Digital Switches (PRCDS) and Low Voltage Switches (PRCLS) provide local occupant override and light level scene control. Switches are available in -, - and -button configurations in white, black, almond and ivory colors. Switches are compatible with decorator-type wall plates and comply with NEMA WD- standards and sized to fit minimum NEMA wall box width dimension. Digital Switches (PRCDS) Pow-R-Command Digital Switches are used for occupant override and light level control. These devices are connected to the controller Digital Switch Network (DSN). PRC000E, PRC500E and PRC000E controllers include the DSN feature. PRCDS switches are not compatible with the PRC750E controller. Digital Switch comes standard with onboard memory to store all configuration and programming. This allows for the DSN to have distributed intelligence. This keeps the DSN from having a centralized break point. If one Digital Switch were to fail, the integrity of the network would not be compromised, and the remaining Digital Switches would still function properly. Connect to controller Digital Switch Network (DSN) using CAT AWG cable Each PRCDS includes two RJ-5 connectors for connecting the PRCDS switch DSN using a daisychain network architecture Up to 99 Digital Switches can be connected to a controller DSN Onboard rotary switches allow addresses (0 99) to be set in the field LED backlit buttons provide realtime breakers and/or groups status Onboard digital and analog I/O Onboard Vdc external power source -, - and -button configurations Black, white, almond and ivory colors Matching wallplates in single and multi-gang configurations PRCDS switches include onboard digital and analog I/O plus an external device power source. Field wired devices like occupancy sensors and photosensors can be directly wired to the PRCDS switch to eliminate the need for running field wiring to the electric closet. This feature saves installation time and provides lower installed system cost. Lighting equipped with 0 0 Vdc analog dimming control circuitry is also directly wired to the PRCDS switch. All ON/OFF and dimming control logic resides in the PRCDS switch. Analog input (AI) accepts 0 0 Vdc signal and is typically used to connect photosensor Digital input (DI) is typically used to connect occupancy sensor or other dry-contact input Note: Not available on -button Digital Switch. Analog output (AO) is used to directly control lighting equipped with 0 0 Vdc dimming circuitry Note: Maximum 0 ma current sink. Vdc/0 ma output (VOUT) power devices, i.e., occupancy sensors and photosensors Note: Higher than 0 ma current will disable operation of device. Engraved Digital Switch (-button shown) Addressing Switches Onboard I/O DSN Network Connections Figure.-. Digital Switch Hardware Overview CA0800E

18 .- Digital and Low-Voltage Switches April 07 Sheet 8 DSN from Previous Digital Switch or compatible PRC controller DSN Network AWG Cat Cable Vdc ( V) AO GND AI DI L N DSN to next Digital Switch *Note - for additional information on the DSN see drawing PRCE-DigitalSwitchNetwork Figure.-. Digital Switch Analog and Digital I/O Typical Wiring Table.-. Digital Switch Selection Number of Buttons BLK W Multiple Occupancy Sensors Require Switchpack Blue Blue SP0-## Color Black Black Black White White White Almond Almond Almond Ivory Ivory Ivory Consult factory for custom labeling. Note: For Switch Wallplates, refer to Table.-. P 0 0 Out In OR GY BK R BL Vdc AO GND AI DI P Catalog Number PRCDSB PRCDSB PRCDSB PRCDSW PRCDSW PRCDSW PRCDSA PRCDSA PRCDSA PRCDSV PRCDSV PRCDSV OR GY BK R BL VDC ( Vdc ext. device supply 0 ma max) Vdc ( V) AO AO (Analog Output- GND 0 0 V 0 ma max) AI GND Ground- I/O common DI AI (Universal Input- analog level or dry-contact) DI (Digital Input- Not avilable on the -button switch) Additional Occupancy Sensors. (See sensor manuals for further information) Vdc ( V) AO GND AI DI Vdc ( V) AO GND AI DI VDC (V) AO GND AI DI Dry-Contact Override Switch Table.-. Digital Switch I/O Configuration Pushbutton Configuration Analog Input 0 0 Vdc Note: For PRCE-DigitalSwitch-IO standard drawing references, visit Eaton.com/lightingcontrol. (+) (-) Photosensor w/ 0 to 0 V Signal Level LED Drivers and Fluorescent Ballasts 0 to 0 V Dimmable Dimming Circuit (+ -) To additional ballasts or LED drivers Maximum 0 ma Single Occupancy Sensor w/ Dry-Contact Input Digital Input 0 0 Vdc OR GY BK R Analog Output 0 0 Vdc Two-button Four-button Six-button Vdc Output 0 ma Maximum CA0800E

19 April 07 Sheet 9 Digital and Low-Voltage Switches.- Digital Switch Network (DSN) PRC000E, PRC500E and PRC000E controllers include the Digital Switch Network (DSN) feature. Digital Switches (PRCDS) are connected to the DSN using the designated RJ-5 connector located in the controller low voltage compartment using CAT AWG cable. All CAT connections are made using T-58B wiring standard to power the Digital Switch and establish communications with the controller. Digital Switch Network requires adding a PRC Power Injector (PRCDSNPI) when more than 5 Digital Switches are connected or total DSN cable length exceeds 500 feet. Digital Switch Network Splitter (PRCDSNS) is required when more than 50 Digital Switches are connected to the DSN. PRCDSNS splitter can also be used to reduce DSN field wiring. Maximum of 99 digital switches are connected to controller DSN DSN daisy-chain network architecture is configured using CAT AWG Digital Switch Network Power Injector (PRCDSPI) is required when more than 5 devices are connected to the DSN or maximum network length exceeds 500 feet Digital Switch Network Splitter is required when more than 50 digital switches are connected or when network flexibility is needed Digital Switch Network Connector DSN CAT AWG Address Switches SW SW SW SW SW SW Addressing 99 SW SW SW SW OUT Figure.-. Typical Digital Switch Network (DSN) Note: For PRCE-DigitalSwitchNetwork standard drawing references, visit Eaton.com/lightingcontrol. IN TB J OUT IN TB J OUT Digital Switches 5 DSN Power Injector Unswitched 0/7 Vac Supply IN OUT IN TB J Digital Switches OUT IN TB J CA0800E

20 SW SW TB OUT IN J SW SW TB OUT IN J SW SW TB J SW SW TB J SW SW TB J 7 SW SW TB OUT IN J 7 SW SW TB OUT IN J.- Digital and Low-Voltage Switches April 07 Sheet 0 Digital Switch Network Power Injector (PRCDSNPI) Digital Switch Network Power Injector (PRCDSNPI) may be required due to the current draw requirements of each Digital Switch and connected field devices like occupancy/ photo sensors and dimmable lighting equipped with 0 0 Vdc control circuitry, to operate correctly. The PRCDSNPI is required after each 5 PRCDS switches or when the DSN length exceeds 500 feet. DSN connections to the power injector are done in the exact same fashion as each Digital Switch. The PRCDSNPI includes a separate dual voltage 0/7 Vac power supply connection. Make sure to connect to an un-switched branch circuit. Used to boost low voltage power on the DSN Required after each 5 digital switches are connected or when DSN exceeds 500 feet Includes 0/7 Vac power supply for connecting to un-switched branch circuit DSN In Digital Switch Network Splitter (PRCDSNSP) Digital Switch Network Splitter (PRCDSNSP) is used as a convenient way to split the DSN into two legs to span in two directions. If there are more than 50 Digital Switches connected to a controller, a splitter is recommended. Consult factory for applications that may require this device. Used to split DSN into two directions May reduce the overall length of CAT AWG cable and installed cost Required for DSN with 50 or more digital switches OUT IN VAC ON OFF Reset Unswitched AC supply Vac Figure.-. Digital Switch Network Power Injector Wiring N Ground CAT AWG ON OFF DSN Out OUT DSN Out DSN Out OUT OUT IN CAT AWG IN IN DSN Out Figure.-5. Digital Switch Network Splitter Wiring Note: For PRCE-DigitalSwitchNetwork standard drawing references, visit Eaton.com/lightingcontrol. DS DS5 DS5 CA0800E

21 April 07 Sheet Digital and Low-Voltage Switches.-5 Low Voltage Switches (PRCLS) Pow-R-Command low voltage switches (PRCLS) are used for occupant override control. PRCLS switches are equipped with momentary dry-contact pushbuttons. These devices are connected to the controller digital inputs (DI DI8) and universal inputs (UI UI8). Pushbuttons do not include backlit feature. It is recommended that Digital Switches (PRCDS) be used for applications requiring backlit pushbuttons. Refer to Digital Switch information found on Page.-. A Switch Override Controller (PRCSOC) can be used when more than switch groups are required. Refer to Switch Override Controller information found on Page.5-. Connect to controller digital inputs DI DI8 and universal inputs UI UI8 (PRC750E DI DI) using 8 AWG wire, maximum of 500 feet -, - and -button configurations Black, white, almond and ivory colors Matching wallplates in single and multi-gang configurations Low Voltage Switch Low Voltage Switch Termination Board.75 (.98).7 (.) Pow-R-Command Low Voltage Switch Figure.-. Low Voltage Switch Connections Table.-. Low Voltage Switch Selection Color Number of Buttons Catalog Number Black White Almond Ivory SW0 SW0 SW0 SW05 Consult factory for custom labeling. Note: For Switch Wallplates, refer to Table.-. SW0 SW0 8 Ga Recommended Wire Size PRCLSB PRCLSB PRCLSB PRCLSW PRCLSW PRCLSW PRCLSA PRCLSA PRCLSA PRCLSV PRCLSV PRCLSV Note: For PRCE-Input/Output standard drawing references, visit Eaton.com/lightingcontrol. CA0800E

22 .- Digital and Low-Voltage Switches April 07 Sheet Switch Wallplates (PRCSWP) Pow-R-Command Switch Wallplates fit Digital Switch (PRCDS) and Low-Voltage Switch (PRCLS) devices. Screwless design provides easy installation. Available in black, white, almond and ivory for single and multi-gang designs. Switch Wallplate Table.-. Switch Wallplate Selection Color Number of Switches Catalog Number Black White Almond Ivory PRCSWPB PRCSWPB PRCSWPB PRCSWPW PRCSWPW PRCSWPW PRCSWPA PRCSWPA PRCSWPA PRCSWPV PRCSWPV PRCSWPV CA0800E

23 April 07 Sheet Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices.5- Connecting Field Wiring Control Devices Field control devices are connected to the controller digital inputs, analog inputs and analog outputs located in the low voltage compartment found behind the display. Easy access to these connections is accomplished by loosening the two captive screws found on each of the display top corners. Once screws are loosened, the display can be folded down using the hinge connection. Figure.5-. Controller Class Low Voltage Compartment Access Digital Switch Network Figure.5-. Controller Class Low Voltage Compartment Figure.5-. Low Voltage Wiring Connections Low Voltage I/O GND GND DI DI DI DI UI UI UI UI AO AO AO AO V PWR GND V V DI5 DI DI7 DI8 UI5 UI UI7 UI8 AO5 AO AO7 AO8 M+ M- Digital Inputs Controllers are equipped with eight digital inputs (DI DI8) and eight universal inputs (UI UI8). Universal inputs are configured as digital inputs when more than eight digital switch groups are required. Note: PRC750E controller includes digital inputs DI DI, no universal inputs. Digital inputs are designed for connecting low voltage momentary or maintained inputs and other devices equipped with dry-contact outputs, i.e., photo controllers, building management systems and security systems. Eight digital inputs (DI DI8) Eight universal inputs (UI-UI8) configurable to digital inputs when more than eight digital switch groups are required Digital inputs are connected using 8 AWG wire Maximum distance 500 feet between controller and input device Vac external power source used to power low voltage devices, i.e., occupancy sensors PRC750E controller includes digital inputs only (UI UI8 factory set to digital input configuration) GND Figure.5-. Maintained or Momentary Dry-Contact Input Connection GND DI or UI DI or UI V DI or UI Figure.5-5. Low Voltage Occupancy Sensor Note: For PRCE-InputOutput standard drawing references, visit Eaton.com/lightingcontrol. OR GY BK R GND DI or UI Line Neutral SP0-## P OR GY BK R BL P OR GY BK R BL Figure.5-. Multiple Low Voltage Occupancy Sensors with Switchpack CA0800E

24 .5- Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices April 07 Sheet Analog Inputs Controllers are equipped with eight universal inputs (UI UI8). Universal inputs are configured as 0 0 Vdc when analog light level sensors are used. Note: PRC750E controller does not include universal inputs feature. Eight universal inputs configurable to 0 0 Vdc analog inputs (UI UI8) Universal inputs are connected using 8 AWG wire Maximum distance 500 feet between controller and input device Vac external power source used to power low voltage devices, i.e., photosensors It is recommended to use photosensors found in Table.5- GND GND V UI UI Black Com Red Power Yellow Signal Black Com Yellow Signal Figure.5-7. Photosensor Connection Table.5-. Photosensors Description Red Power Indoor sensor V input, 0 0 V output, 50 to 750 fc Outdoor sensor V input, 0 0 V output, 50 to 750 fc Atrium sensor V input, 0 0 V output, 50 to 750 fc Skylight sensor V input, 0 0 V output, 000 to 750 fc Part Number C77G0 C77G0 C77G0 C77G07 Controller Analog Outputs Controllers are equipped with eight analog outputs (AO-AO8). Analog outputs provide 0 0 Vdc connection and control of lighting equipped with 0 0 Vdc dimming control circuitry. Note: PRC750E controller does not include analog outputs. Eight 0 0 Vdc analog outputs (AO-AO8) Analog outputs are connected using 8 AWG wire Maximum of 80 ma sink or ma source Maximum distance 000 feet between controller and luminaire GND DIM ( ) AO DIM ( ) DIM (+) DIM ( ) DIM (+) Figure.5-8. Analog Output Connection Additional ballasts or LED drivers Maximum 80 ma sink, ma source Note: For PRCE-Input/Output standard drawing references, visit Eaton.com/lightingcontrol. L L L L CA0800E

25 April 07 Sheet Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices.5- Analog I/O Module Analog Module (PRCAEM) PRCE Analog Module (PRCEAEM) is used when the quantity of either analog inputs or analog outputs exceeds the controller maximum number of eight. Compatible with PRC000E/500E/000E controller MLAN network. Not compatible with PRC750E controller. Each PRCEAEM includes eight 0 0 Vdc universal inputs and eight 0 0 Vdc analog outputs. Universal inputs can also be configured as maintained two-wire dry contact inputs for connecting external control devices. Analog outputs are used to connect LED and fluorescent lighting equipped with 0 0 Vdc dimming control circuitry. Maximum of 80 ma sink or source per analog output channel. PRCEAEM is connected to the controller MLAN network M+ and M connections in a daisy-chain network architecture using Belden 05A shielded twisted pair cable. It can be mounted near the controller or remotely to reduce field wiring. Maximum distance from the controller is,000 ft. Maximum of seven PRCEAEMs can be connected to the controller MLAN network. PRCEAEM is configured using Lighting Optimization Software (PRCLOS). Online status and I/O status is available through preconfigured Web pages. Outputs can be overridden and taken out-of-service using preconfigured Web pages. Device requires Vdc regulated power source. Factory assembled with NEMA enclosure controller, termination board and 0 Vac voltage power supply. Eight configurable universal inputs Connect photosensors when configured as 0 0 Vdc analog inputs Connect control devices equipped with maintained two-wire dry contact outputs Eight 0 0 Vdc analog outputs used to connect LED and fluorescent lighting equipped with 0 0 Vdc dimming circuitry Maximum 80 ma sink or source Maximum,000 ft distance using 8 AWG cable Maximum of seven PRCEAEM can be connected to the PRCE controller Connect to controller MLAN network M+ and M connections using a daisy-chain network architecture Belden 05A twisted pair with shield Maximum,000 ft distance from controller Configured using Lighting Optimization Software (PRCLOS) Online status and I/O status available through controller preconfigured Web pages Requires Vdc regulated power source Available in open style or in NEMA enclosure (includes 0 Vac control power transformer) Not compatible with PRC750E controller Table.5-. PRCE Analog Module (PRCEAEM) Selection Description Part Number Analog expansion module (open style) PRCEAEM One analog expansion module, NEMA enclosure PRCEAEME with 0 Vac power supply Two analog expansion modules, NEMA enclosure PRCEAEME with 0 Vac power supply Three analog expansion modules, NEMA enclosure PRCEAEME with 0 Vac power supply Four analog expansion module, NEMA enclosure PRCAEME with 0 Vac power supply Consult factory for non-standard configurations and enclosures. Note: For PRCEAEM I/O connections and controller MLAN network connection drawing references, visit Eaton.com/lightingcontrol. CA0800E

26 CH0 R0 L+ L - SH.5- Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices April 07 Sheet V UI Red Power Black Com Yellow Signal Photosensor w/ 0 to 0 V Signal Level GND V L+ L - SH AO AO AO AO AO5 AO AO7 AO8 UI Black Com Yellow Signal Red Power Dry-Contact Input Maintained Only UI UI 8 AWG 500 ft Maximum Distance Relay Contact from Other System Override Switch Contact GND V DC (Regulated) A L+ L - SH Module Addressing 0: : : : : 5: : 7: CH0 R0 AO AO UI UI AO AO Pow-R-Command PRCE Analog Module CAT#: PRCEAEM Part #: C5770G0 UI UI 0 0 Vdc 80 ma per Channel Dry- Contact or 0 0 V AO5 AO UI5 UI AO7 UI7 AO8 UI8 0 to 0 V Dimmable Fluorescent Ballast or LED Driver DIM ( ) L AO L *(See Caution) DIM ( ) DIM (+) DIM ( ) Additional Ballasts or LED Drivers DIM (+) Maximum 80 ma Sink, 80 ma Source Maximum of 80 ma Sink or Source Current 8 AWG,000 ft Maximum Distance Figure.5-9. PRCE Analog Module I/O Connections GND V Module Addressing N/A: : 5: 7: : : : 8: AO UI AO AO UI AO UI AO UI Pow-R-Command PRCE Analog Module CAT#: PRCEAEM Part #: C5770G0 A AO AO AO AO5 UI5 AO5 AO AO UI Vdc (Regulated) AO7 UI7 Figure.5-0. PRCE Analog Module 0 0 Vdc Dimming Outputs AO8 UI8 DIM(+) DIM( ) AO7 AO8 DIM(+) DIM( ) L L Additional LED Drivers Maximum 80 ma Source/Sink LED Dimming Zone DIM(+) DIM( ) DIM(+) DIM( ) L L L L DIM(+) DIM( ) UI UI L L DIM(+) DIM( ) UI UI Additional LED Drivers Maximum 80 ma Source/Sink Dimming Zone DIM(+) DIM( ) UI5 UI LED L L L LED L LED Dimming Zone 5 Dimming Zone Dimming Zone Additional LED Drivers Maximum 80 ma Source/Sink Notes: Analog Outputs (AO) used for 0 0 Vdc Dimming (8 available per module) 0 0 V Output Cables 8 AWG 000ft maximum Additional LED Drivers Maximum 80 ma Source/Sink DIM(+) DIM( ) Additional LED Drivers Maximum 80 ma Source/Sink Additional LED drivers Maximum 80 ma source/sink LED DIM(+) DIM( ) LED LED LED Dimming Zone 8 Dimming Zone 7 Dimming Zone L L L L UI7 UI8 Additional LED Drivers Maximum 80 ma Source/Sink Additional LED Drivers Maximum 80 ma Source/Sink L L CA0800E

27 CH0 R0 L+ L - SH CH0 R0 L+ L - SH JP CH0 R0 L+ L - SH April 07 Sheet 7 Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices.5-5 GND GND DI DI DI DI UI UI UI UI AO AO AO AO V PWR SLAN GND METER LAN DSN Controller-NET MLAN Belden 05A or equivalent. RS-85 0 Ohm Shielded Twisted Pair, Daisy-Chained MADE IN USA PWR BCB SLAN+ SLAN- V DI7 V DI5 DI8 DI UI5 UI8 AO AO7 UI UI7 AO8 AO5 M+ M- Controller Network SH - + Digital Switch Network PRCE Controller Low Voltage Compartment USB SD External Fuse A Internal Fuse A Diagnostic Override BCB/Ext. Power Controller Power F F SW 0 Ohm EOL resistor required at the last PRCEAEM. To additional PRCEAEM modules. 7 modules maximum per PRCE controller. GND V AO AO AO AO AO5 AO AO7 AO8 GND V AO AO AO AO AO5 AO AO7 AO8 GND V AO AO AO AO AO5 AO AO7 AO8 Module Addressing N/A: : 5: 7: : : : 8: Pow-R-Command PRCE Analog Module CAT#: PRCEAEM Part #: C5770G0 Vdc (Regulated) A UI UI UI UI UI5 UI UI7 UI8 Module Addressing N/A: : 5: 7: : : : 8: Pow-R-Command PRCE Analog Module CAT#: PRCEAEM Part #: C5770G0 Vdc (Regulated) A UI UI UI UI UI5 UI UI7 UI8 Module Addressing N/A: : 5: 7: : : : 8: Pow-R-Command PRCE Analog Module CAT#: PRCEAEM Part #: C5770G0 Vdc (Regulated) A UI UI UI UI UI5 UI UI7 UI8 Figure.5-. PRCE Analog Module Network, MLAN Network Connection CA0800E

28 .5- Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices April 07 Sheet 8 Switch Override Controller (PRCSOC) Pow-R-Command Switch Override Controller is generally used when the quantity of low voltage dry-contact inputs from field devices such as low voltage switches and occupancy sensors exceed the controller inputs. This device can also be remotely mounted in the space for local connection of low voltage inputs to reduce the number of wires needed to be pulled back to the Master Panelboard. PRCSOC controller is connected to the PRC controller RS-85 CNET network connection. Pow-R-Command Lighting Optimization Software (PRCLOS) is used to configure this device. PRCSOC is factory assembled in NEMA enclosure controller, termination board and 0/7 Vac dual voltage power supply. Four digital inputs (DI9 DI) Twelve universal inputs (UI UI) that can be configured as digital or analog inputs Sixteen Vdc low power digital outputs (GRP DO DO8 and GRP DO DO8) to power status LEDs (0 ma maximum) Optional Vdc low power digital outputs to power status LEDs (0 ma maximum) Three 0 0 Vdc analog outputs (80 ma maximum with required dimmer cable, part number 9CG0/consult factory during design phase) Termination board includes additional 8 digital inputs ( 8) recommended for maintained contact only. Consult factory for application support External 5 Vdc power source for powering occupancy and light level sensors and PRC auxiliary devices (00 ma maximum load) Digital and analog inputs are connected using 8 AWG wire Maximum distance of 500 feet from PRCSOC to input device Connects to controller CNET connection for RS-85 serial communications Factory assembled in NEMA enclosure with 0/7 Vac dual voltage power supply Configured using Lighting Optimization Software (PRCLOS) Not compatible with PRC750E controller Optional Vdc Digital Outputs Figure.5-. Switch Override Controller Table.5-. Switch Override Controller Selection Description PRC Switch Override Controller without power supply mounted in NEMA enclosure PRC Switch Override Controller with 0/7 Vac power supply mounted in a NEMA enclosure PRC Switch Override Controller with 0/7 Vac power supply, pilot output card mounted in a NEMA enclosure SOC Card Printed Circuit Board with Termination Points for 8 Inputs Catalog Number PRCSOCC PRCSOCEC PRCSOCECO CA0800E

29 April 07 Sheet 9 Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices.5-7 Reset 0 V Black Supply Power 0 V Vac Neutral Ground C 5 C 7 8 C 5 C 7 8 DI J Yellow/White Main Power J VAC N/C Yellow PRC SOC Controller DI TB Switch Inputs TB Switch Commons DI TB J Switch Inputs RS85 J RS85 JMP! + - S + - S IN OUT DIGITAL OUTPUTS Group Group C C 5 5 C C RS-85 Network (Belden 05A or equiv.) Figure.5-. Switch Override Controller Enclosure PRC000E, PRC500E or PRC000E Controllers To Additional PRC Network Devices RS-85 CNET Belden 05A 0 Ohm Shielded Twisted Pair Cable To Additional PRC Network Devices Main Power J J J JMP! J VAC N/C PRCSOC Controller + S IN + S OUT PRC 7X Chassis Board TB TB TB Switch Inputs Switch Commons Switch Inputs 8 Figure.5-. PRCE Controller to PRCSOC RS-85 Network Wiring CA0800E

30 .5-8 Lightning Control Systems Pow-R-Command Connecting Field Wiring Control Devices April 07 Sheet This page intentionally left blank. CA0800E

31 April 07 Sheet Software.- Lighting Optimization Software Lighting Optimization Software (PRCLOS) is recommended for Pow-R-Command system users. It is compatible with PRC750E, PRC000E, PRC500E and PRC000E controllers. PRCLOS allows users to configure, program and monitor their system. This basic software package is capable of recognizing and saving databases for a single site. Table.-. Lighting Optimization Software Description Catalog Number PRC Lighting Optimization Software PRCLOS Remote network connection not available. Requires direct connection to controller Maintenance Port. PRC750E connection requires industry standard patch cable. PC Central Software PC Central Software (PRCPCC) is recommended for field technicians responsible for maintaining Pow-R-Command systems. It is compatible with PRC750E, PRC000E, PRC500E and PRC000E systems. PRCPCC allows users to configure, program, monitor and override their system with the added features of advanced diagnostics and programming capabilities. This advanced software package is capable of recognizing and saving databases for single or multiple sites. Table.-. PC Central Software Description Catalog Number PC Central Software (single site) PRCPCC0 PC Central Software (0 sites) PRCPCC0 Remote network connection not available. Requires direct connection to controller Maintenance Port. PRC750E connection requires industry standard patch cable. Recommended Minimum Computer Specifications Although it is difficult to guarantee compatibility with all PC-compatible equipment, the basic installation is generally compatible with the following minimum specifications: Microsoft Windows operating system GHz processor or better Minimum GB RAM Hard drive with at least 00 MB of free space plus 50 MB for each site to be managed Ethernet network adapter Minimum 0 x 0 display Lighting Optimization Software and PC Central Software is compatible with the following operating systems: Windows 7 Windows Server 008 R Windows 8. Windows Server 0 Windows 0 CA0800E

32 .- Software April 07 Sheet This page intentionally left blank. CA0800E

33 April 07 Sheet PRC Advanced Controllers.7- PRC5000 Master Controller Enclosed PRC5000 Master Controller Pow-R-Command 5000 controller (PRC5000) is a microprocessor-based lighting and energy management controller. It is capable of communicating with other Pow-R-Command system devices for providing master scheduling control, load shedding and demand response, reporting, trend logging and implementing other control strategies. PRC5000 controller is commonly used to serve facility custom graphics via Web pages. Authorized users can log into the device using a standard Web browser for viewing custom graphics. System schedule changes and override controls can be made at the click of a button. Custom system performance and energy usage reports can be configured and automatically sent to the facility manager via notification. These reports may be used to measure and verify that equipment is performing as designed and delivering expected energy savings. Up to 5 individual local area networks (RS-85 serial network/cnet) can be coordinated through a single PRC5000. Of these 5 networks, a maximum of two may be wired directly to the PRC5000; the rest are connected via the facility s Ethernet network. Each of these CNET networks can accommodate up to 0 Pow-R-Command devices. Master scheduler (0 schedules) Load shedding and demand response logic control System alarms notification Custom reports Controls up to 5 local area networks, each with maximum of 0 Pow-R-Command devices Two RS-85 local area network connections Ethernet port for remote access to local area networks Option to serve custom building graphics Web pages Supplied in NEMA enclosure with 0 Vac convenience outlet Personal Computer PRC500E/ PRC000E Master Lighting Optimization Software (PRCLOS) System Configuration, Programming, Status and Control Ethernet Figure.7-. PRC5000 Master Controller Note: For PRCE-Ethernet standard drawing references, visit Eaton.com/lightingcontrol. PRC500E/ PRC000E Master Table.7-. PRCE5000 Master Controller Selection Description Part Number PRC5000 controller only PRC5000 PRC5000 controller in PRC5000E NEMA enclosure with 0 Vac convenience outlet Consult factory for non-standard configurations. PRC5000 Master Controller PRC500E/ PRC000E Master Master Controller Switching and Dimming Control Facility Custom Graphics (optional) CA0800E

34 .7- PRC Advanced Controllers April 07 Sheet This page intentionally left blank. CA0800E

35 April 07 Sheet Typical Electric Room Layout Typical Electric Closet Applications Layout Configuration Occupied Space.8- Network PRC-E Controller Analog Output 0 0 Vdc Dimming Conductor 8 AWG Analog Input 0 0 Vdc Conductor 8 AWG Digital Switch Network (DSN) CAT AWG Photosensor LED Dimming Lighting BCB # BCB # SLAN Alpha 0 Conductor 8 AWG Digital Switches Override Controls Master Lighting Control Receptacle Control Figure.8-. Typical Electric Room Layout Transformer CA0800E

36 .8- Applications April 07 Sheet Multi-Story Building Digital Switches rd Floor Master Ethernet Digital Switches nd Floor Master Analog Dimming Outputs Analog Photosensor Inputs Building Management System PRC000E/500E Controller Digital Switch Network PRC5000 Master Controller SLAN Digital Switches Personal Computer st Floor Master Figure.8-. Multi-Story Building Layout Note: For PRCE-Ethernet standard drawing references, visit Eaton.com/lightingcontrol. CA0800E

37 April 07 Sheet Applications Wiring Configuration.8- Manual Occupant Light Level Dimming Control Eight Analog Output 0 0 Vdc Dimming Channels (AO AO8) 80 ma Sink or ma Source Maximum 8 AWG 000 ft Maximum Cat ( AWG) Cable Digital Switch Network (DSN) GND GND DI DI DI DI UI UI UI UI AO AO AO AO V PWR SLAN DSN GND METER LAN Controller-NET Diagnostic PWR SLAN+ MADE IN USA BCB V DI7 V DI5 DI8 DI UI5 UI8 AO AO7 UI UI7 AO8 AO5 M+ M- Controller Network SH + Digital Switch Network USB JP SD External Fuse A Internal Fuse A Override BCB/Ext. Power Controller Power F F SW SLAN- PRC000E, PRC500E or PRC000E Controller Low Voltage Compartment 00% 00% 80% PRC Digital Switch (PRCDS) UP DWN 0% % OFF 0% OFF Incremental Control OFF, DN, UP, 00% Programmable Presets Figure.8-. Manual Occupant Light Level Control Note: For PRCE-Input/Output and PRCE-DigitalSwitch standard drawing references, visit Eaton.com/lightingcontrol. CA0800E

38 .8- Applications Wiring Configuration April 07 Sheet 8 Automatic Daylight Harvesting Dimming Control Eight Universal Inputs (UI UI8) (Analog 0 0 Vdc) 8 AWG 500 ft Maximum Primary Zone Eight Analog Output 0 0 Vdc Dimming Channels (AO AO8) 80 ma Sink or ma Source Maximum 8 AWG 000 ft Maximum Secondary Zone LED Secondary Dimming Zone LED Primary Dimming Zone GND GND DI DI DI DI UI UI UI UI AO AO AO AO V PWR SLAN DSN GND V DI7 V DI5 DI8 DI UI5 UI8 AO AO7 UI UI7 AO8 AO5 M+ M- METER LAN JP Controller-NET Diagnostic Override BCB/Ext. Power SW PWR SLAN+ MADE IN USA BCB Controller Network SH + Digital Switch Network USB SD External Fuse A Internal Fuse A Controller Power F F SLAN- PRC000E, PRC500E or PRC000E Controller Low Voltage Compartment Figure.8-. Automatic Daylight Harvesting Control Note: For PRCE-Input/Output standard drawing references, visit Eaton.com/lightingcontrol. Analog Module (PRCEAEM) available when controller analog output 0 0 Vdc channels are exceeded. See Page.5-. CA0800E

39 April 07 Sheet Applications.8-5 Remote Mounted Analog Module Electric Room Occupied Space MLAN Network Belden 05A Analog Output 0 0 Vdc Conductor 8 AWG Network PRC-E Controller Digital Switch Network (DSN) CAT AWG 0 0 Vdc Dimmable Lighting Photosensor Analog Module Analog Input 0 0 Vdc Conductor 8 AWG Digital Switch Override and Dimming Controls Master Figure.8-5. Remote Mounted Analog Module CA0800E

40 .8- Applications April 07 Sheet 0 Emergency Lighting Control GHQRDEL Emergency Lighting Controllable Circuit Breaker Emergency lighting control can be achieved by multiple methods. Commonly used methods include using an emergency lighting controllable circuit breaker, UL 9 relay and UL 9 Uninterruptible Power Supply (UPS). Pow-R-Command GHQRDEL emergency lighting controllable circuit breaker is a simple low cost device used to switch emergency lighting off when the space is unoccupied while maintaining power to the emergency detection circuit. This two-pole controllable circuit breaker includes a solenoid operated controllable pole and manually operated pole. Circuit breaker features also include handle-tie for common disconnect and internal common trip mechanism. GHQRDEL includes one phase connection to comply with the 00 National Electrical Code; Section 700.(F) for Sources of Power utilized in emergency lighting applications. Features GHQRDEL emergency lighting controllable circuit breaker features: Two-pole device with one phase connection to meet 00 NEC Section 700(F) single source of power requirement Solenoid operated pole for switching lighting off when the space is unoccupied Manually operated pole to provide continuous power to emergency detection circuit Handle-tie provides common disconnecting means Internal common trip mechanism Table.8-. GHQRDEL Controllable Circuit Breakers Number of Poles Ampere Rating Interrupting Capacity (Symmetrical Amperes) Vac (50/50 Hz) 0 7 Catalog Number 5 5,000,000 GHQRDEL05 0 5,000,000 GHQRDEL00 Not recommended for existing PRC, PRC00, PRC750, PRC000, PRC000 systems. GHQRSPEL controllable circuit breakers are compatible with these systems. GHQRDEL Uncontrolled (Feeds Emergency Detection Circuit) Remotely Operated Neutral Controlled (Turns Lighting ON/OFF) Normal Lighting Normal Lighting Normal Lighting Dual Purpose Lighting Normal/Emergency Figure.8-. Emergency Lighting Control Using GHQRDEL Emergency Controllable Circuit Breaker CA0800E

41 April 07 Sheet Applications.8-7 Remote Relay Unit (RRU-) Table.8-. Remote Relay Unit (RRU-) Description Catalog Number UL 9 remote relay unit 0 Vac UL 9 remote relay unit 7 Vac RRU--0V RRU--7V Remote Relay Unit (RRU-) The Remote Relay Unit (RRU-) is available in 0, 7 Vac input voltage configurations. The RRU- is designed to force all outputs in the Pow-R-Command panelboard to predetermined scene regardless of the controller programmed output status. This allows the override of outputs during loss of normal (grid) power to allow an alternate power source to drive the lighting loads. Once the RRU- senses the normal power returning, Pow-R-Command panelboard will return to the normal programmed operating mode. The RRU- provides a dry contact closure to a Pow-R- Command controller digital input when normal (grid) power is lost. When this digital input is programmed as priority override, this contact closure forces all controllable circuit breakers in the panelboard to the ON state. This priority override condition takes priority and will remain in effect until the contact closure from the RRU- is opened. Controller can also be programmed to force all dimmed loads equipped with 0 0 Vdc dimming circuitry to full ON. For emergency applications, Pow-R-Command Master Panelboard must be fed from an emergency power source. Pow-R-Command Controller RRU- Neutral = White NC Red Black 8 AWG Hot 0 Vac = Black Hot 7 Vac = Orange To Normal Power Source Note: For emergency applications, Pow-R-Command Master Panelboard must be fed from an emergency power source. Figure.8-7. RRU- Wiring to Pow-R-Command Controller C C DI GND CA0800E

42 .8-8 Applications April 07 Sheet Emergency Power Control (CEPC-) Emergency Power Control (CEPC-) The Emergency Power Control (CEPC) device allows the control of emergency lighting fed from a Pow-R-Command panelboard. The CEPC senses a local, single normal power circuit. The CEPC- is available in 0 Vac and 7 Vac input voltage configurations. As long as normal power is present, the CEPC permits normal and emergency switching of the lighting load from Pow-R-Command intelligent panelboards. If normal power is lost for any reason, the CEPC will force the connected emergency fixtures ON. This device includes a test switch for verifying proper functionality. CEPC- Features Eliminates energy waste by allowing emergency lighting to be switched Fail safe operation Visible emergency power LED Visible regular power LED Integral test switch Automatic diagnostic test feature Senses local circuit power loss Available in 0 Vac or 7 Vac UL 9 listed, meets NEC, OSHA and NFPA safety codes Table.8-. Emergency Power Control (CEPC-) Description Ratings Catalog Number Emergency control power non-dimmed loads Emergency control power 0 0 Vdc loads 0/7 Vac CEPC- 0/7 Vac CEPC--D Note: Consult factory for additional information. 0 A Emergency Panel 0 A Blue Blue/ White Pow-R-Command Normal Power Red CEPC Emergency Power Black/ Orange Yellow Blue/ White Emergency Lighting Load Figure.8-8. CEPC- Wiring Diagram for Non-Dimming Loads 0 A 7 EM Neutral Test Controlled Circuit 5 EM Hot Emergency Panel Blue (Violet 0 0 V) 0 A Pow-R-Command Normal Power Test Utility Power Figure.8-9. CEPC--D Wiring Diagram for 0 0 Vdc Dimming Loads White CEPC--D Emergency Power Test or Controlled Circuit Test Utility Power Regular Neutral Regular Line Hot (Sensing Circuit) Regular Neutral Regular Line Hot EM Load Red (Violet 0 0 V) Emergency Lighting Load Gray (0 0 V) CA0800E

43 April 07 Sheet UL 9 Uninterruptible Power Supply Applications Normal Power UPS Power.8-9 BCB BCB UL 9 Uninterruptible Power Supply UL 9 Uninterruptible Power Supply (UPS) can be used to provide 90 minutes of backup power for egress lighting loads when normal power is lost. Eaton's emergency lighting UPSs are UL 9 tested and certified, providing the industry's highest capacity and smallest footprint solution. Features Configured with external line and match battery cabinets to provide 90 minutes of backup time to meet UL 9 standard Manually operated test switch for conducting mandated equipment tests Protected test switch and interface protected from accidental operation and non-authorized users Enhanced communication capabilities for network connectivity and remote management applications UL 9 UPS Pow-R-Command Master Panelboard Figure.8-0. UL 9 UPS Connection to Pow-R-Command Note: For UL 9 UPS information, visit Eaton.com/UL9UPS. CA0800E

44 .8-0 Applications Wiring Configuration April 07 Sheet Receptacle Control Controllable Circuit Breaker Figure.8-. Plug Load Controllable Circuit Breaker (BABRSP) N A BABRSPLC B Handle Tie for Common Disconnect Temporary Override Controlled Uncontrolled (Split Receptacle or Quad Applications) N Figure.8-. Split Receptacle Control Using Controllable Load Control Circuit Breaker (BABRSPLC) Requires Handle Tie to Meet 0 NEC 0. for Shared Neutrals Controllable Circuit Breaker Standard Circuit Breaker Figure.8-. Split Receptacle Control Using Controllable Circuit Breaker (BABRSP) and Standard Circuit Breaker Figure.8-. Split Receptacle with Permanent Marking on Controlled Connection N CA0800E

45 April 07 Sheet 5 Applications.8- Integrated Metering Pow-R-Command intelligent panelboards can be configured to include IQ M mains meter or PXBCM branch circuit monitor. IQ M meter is used for metering mains only and includes meter, PTs and CTs with disconnect, and factory wiring. PXBCM branch circuit monitor can meter a maximum of 8 branch circuits in either singlesection or two-section panelboard configurations. IQ M Mains Meter IQ M Panelboard Mains Meter IQ M is a compact, affordable energy meter that combines exceptional performance and easy installation to deliver a cost-effective solution for energy and power monitoring applications, as well as submetering applications. Because of its compact size, the IQ M is an ideal solution for panelboard applications to monitor the main power coming into the panelboard. Use the IQ M for applications in lighting appliance and small power distribution panelboards up to 0 A. With the rapidly changing emphasis on LEED designs, the IQ M helps you to meet the Measurement and Verification points required by LEED and the U.S. Green Building Council. All models include pulse output and phase loss alarms for maximum versatility. The Modbus output option offers added flexibility for configuration, communication and data analysis. IQ M allows you to: Verify energy bills Make informed load shifting and shedding decisions Fairly and accurately allocate energy costs to users Identify wasteful practices Decrease unnecessary usage Produce an energy profile Secure the optimum utility rate structure Typical Applications Commercial submetering Energy management Industrial monitoring Cost allocation Features Economical and compact watthour meter with demand Backlit LCD display for local reading Compatible with PRC000E controller MLAN network, metering information is available over an Ethernet connection when using controller Modbus TCP pass-through mode; refer to MLAN networks on Page.- Compatible with the Power Xpert Gateway for remote monitoring Monitors: voltage, current, power factor, frequency Power: real, reactive and apparent Energy: real, reactive and apparent Optional data logging capability Optional serial communications (Modbus RTU) Revenue grade, ANSI C.0 0.5% accuracy, IEC 05- Class 0.5S User-enabled password protection On-board diagnostics Catalog Numbering System Table.8-. IQ M Catalog Numbering System Meter Series Not available with quadrant energy. IQM A Energy Type = Standard energy = quadrant energy Figure.8-5. Eaton Pow-R-Command Intelligent Panelboard Output Options = Pulse output only = Pulse output + Modbus = Pulse output + Modbus + data logging 5 = Pulse inputs + BACnet + data logging IQ M Meter CA0800E

46 .8- Applications April 07 Sheet PXBCM Branch Circuit Monitor PXBCM branch circuit monitor provides a means to monitor the main power coming into the panelboard and up to four additional three-phase meters. The PXBCM can be used in lighting appliance, small power distribution panelboards up to 0 A with branch breakers rated 00 A or below. The PXBCM can be used to meet the measurement and verification requirements. Requires -inch wide enclosure when integrated in a Pow-R-Command intelligent panelboard. With Modbus RS-85 and TCP output standard, the PXBCM offers flexibility for onboard configuration, as well as communication and data analysis through an integrated Web server or a number of building automation sources, including Eaton s Power Xpert and Foreseer products. Typical Applications Energy management Industrial monitoring Cost allocation Data center management Light commercial Industrial Institutions Features Power and energy readings at the branch circuit level Integrated Web server for remote monitoring and configuration Optional remote color touchscreen display for local reading Compatible with PRC000E controller MLAN network, metering information is available over an Ethernet connection when using controller Modbus TCP pass-through mode; refer to MLAN networks on Page.- Compatible with the Power Xpert gateway for remote monitoring Two basic panelboard configuration options: Main and branch devices Branch devices only PXBCM allows you to: Make informed load shifting and load shedding decisions Fairly and accurately allocate energy costs to users Identify wasteful practices Decrease unnecessary usage Produce an energy profile Main Metering CTs Metering CT Rail Main Metering Module Figure.8-. PXBCM Branch Circuit Monitor Requires -inch wide enclosure when integrated in a Pow-R-Command intelligent panelboard. CA0800E

47 April 07 Sheet 7 Applications.8- Building Management System Integration Pow-R-Command lighting control and plug load control systems are often connected to building management systems. There are two main methods of connecting to building management systems: Systems integration is where two systems are connected using communications. Systems that are integrated generally share more information and provide more control options, i.e., control and status Systems interfacing is where two systems are connected using dry-contacts. Systems that are interfaced may not provide status feedback between the systems PRC000E and PRC500E controllers provide a BACnet/IP communications protocol integration path to the building automation system. Controller status and control points are automatically mapped as BACnet objects. Both PRC-E controller and building management system need to be connected to the same subnet to establish communications between the two systems. Once connected, the building management system can auto discover the controller BACnet objects. BACnet objects include: Controllable circuit breaker group Individual controllable circuit breaker Digital inputs Analog inputs Analog outputs Personal Computer PRC500E or PRC000E Master Lighting Optimization Software (PRCLOS) System Configuration, Programming, Status and Control Ethernet PRC500E or PRC000E Master Figure.8-7. Typical Integration Network Architecture Refer to PRC-E Series Installation Manual MN00EN, Appendix C, BACnet Integration for more technical information. Integrated IQ M mains meter or PXBCM branch circuit monitor metering information is available via single Ethernet connection when using PRC000E controller Modbus TCP pass-through mode. Refer to MLAN networks on Page.-. Building Management System PRC500E or PRC000E Master BACnet/IP Communications Master Controller Switching and Dimming Control CA0800E

48 .8- Applications April 07 Sheet 8 Third-Party Modbus Master Control Connection Pow-R-Command Panelboards can be directly connected to a Modbus Master Controller using an RS-85 RTU network. This network functions the same as the Pow-R-Command SLAN sub-network. Controllable circuit breaker status and control is achieved by sending standard Modbus commands from the Modbus Master Controller to the Breaker Control Bus (BCB). A maximum of Breaker Control Bus can be connected to the network. Each BCB is assigned a unique address between BCB and BCB using onboard DIP switches. It is recommended that the first Pow-R-Command panelboard connected to the Modbus Master be configured as a Powered Panelboard (PRCEPP). This configuration includes a control power supply designed to provide power to Breaker Control Bus addressed between BCB and BCB8 and switch controllable circuit breakers. Another Powered Panelboard would be needed to power Breaker Control Bus between BCB9 and BCB. Refer to Third Party Modbus-SLAN drawing. Consult factory for Breaker Control Bus integration documentation. Note: For Third-Party Modbus-SLAN standard drawing references, visit Eaton.com/lightingcontrol. Control Power Supply Alpha 0 -Conductor AWG Third-Party Modbus RTU Building Management System SLAN Belden 05A Twisted Pair with Shield BCB # BCB # BCB # BCB # BCB #5 BCB # BCB #7 BCB #8 Powered Panelboard (PRCEPP) Figure.8-8. Third-Party Modbus Master Control Connection Panelboard (PRCEP) PRCEP PRCEP CA0800E

49 April 07 Sheet 9 Applications.8-5 Panelboard Pow-R-Command Retrofits Eaton PRLa and PRLa lighting panelboards can be retrofitted with Pow-R-Command electronics and controllable circuit breakers to provide lighting and plug load control. Breaker Control Bus (BCB) switching electronics are mounted to the existing panelboard interior rails using the single screw mounting tab found on both ends of the device. Only standard circuit breakers connected to loads designated to be controlled need to be replaced with controllable circuit breakers. When the panelboard is configured with BCB on each side, a factory-assembled BCB-to-BCB SLAN cable is used to interconnect the BCBs. With BCBs and controllable circuit breakers installed, the panelboard is now configured as a PRC Panelboard (PRCEP). Refer to Panelboard on Page.- to learn more about PRCEP panelboard configurations. Typically existing panelboards do not have the box height required to add the controller in the panelboard. External mounted controllers with control power supply are provided in NEMA enclosure and mounted near the Panelboards. Refer to External Mounted Controllers on Page.- to learn more about these devices. Retrofitted Panelboards and External Mounted Controllers are connected using the Master/ SLAN sub-net network by installing Alpha 0 cable with AWG, four conductors between the devices. Refer to Master Panelboard to Panelboard SLAN Sub-net Network on Page.-. Pow-R-Command retrofits into existing Eaton PRLa and a lighting panelboards Panelboards are converted to Pow-R-Command Panelboards (PRCEP) by installing Breaker Control Bus and controllable circuit breakers External Mounted Controller is mounted near the retrofitted PRCEP panelboard Factory-assembled BCB-to-BCB cables are used for panelboard interconnections between BCBs Controller and PRCEP are connected using SLAN sub-net network SLAN requires Alpha 0 cable with AWG, four conductors Breaker Control Bus Retrofit Kit Table.8-5. Breaker Control Bus Retrofit Kit Selection Description Catalog Number Breaker control bus (BCB) circuits retrofit kit Breaker control bus (BCB) 5 circuits retrofit kit Breaker control bus (BCB) 9 circuits retrofit kit BCB-to-BCB SLAN Cables PRC000BCB-R Table.8-. BCB-to-BCB Selection Description Catalog Number BCB-to-BCB / -circuit panelboard BCB-to-BCB / -circuit panelboard BCB-to-BCB / 8-circuit panelboard PRC000BCB-5R PRC000BCB-9R PRCSLANB PRCSLANB PRCSLAN8B PRCE Controller External Mounted Controller SLAN Alpha 0 AWG, conductor BCB # BCB # BCB # BCB # BCB #5 BCB # BCB #7 BCB #8 PRCEP PRCEP PRCEP PRCEP Figure.8-9. External Mounted Controller SLAN Connection to Retrofitted Panelboards Note: For PRCE-SLAN-External Cabinet standard drawing references, visit Eaton.com/lightingcontrol. CA0800E

50 .8- Applications April 07 Sheet 0 Industry standard lighting panelboards not manufactured by Eaton can be retrofitted with Pow-R-Command lighting and plug load controls. Eaton supplies standard panelboard interior with Breaker Control Bus (BCB) switching electronics and controllable circuit breakers. Interior is configured with required mains device and standard circuit breakers if required to power non-switched loads. Using customer supplied panelboard box dimensions a custom cover is supplied. Contractor simply bolts interior and cover to the box. Consult factory for retrofit panelboard take-off sheet. Typically existing panelboards do not have the box height required to add the controller in the panelboard. External mounted controllers with control power supply are provided in NEMA enclosure and mounted near the Panelboards. Refer to External Mounted Controllers on Page.- to learn more about these devices. Retrofitted Panelboards and External Mounted Controllers are connected using the Master/ SLAN sub-net network by installing Alpha 0 cable with AWG, four conductors between the devices. Refer to Master Panelboard to Panelboard SLAN Sub-net Network on Page.-. Pow-R-Command panelboard interiors retrofit into non-eaton panelboard boxes Panelboard interiors generally assemble as Panelboard (PRCEP) PRCEP includes Breaker Control Bus switching electronics, controllable and non-controlled branch circuit breakers and mains device External Mounted Controller is mounted near the retrofitted PRCEP panelboard Controller and PRCEP are connected using SLAN sub-net network SLAN requires Alpha 0 cable with AWG, four conductors Consult factory for retrofit panelboard take-off sheet Job Name Panel Specifications d Valid Control Groups: A thru P Panel Schedule Group c Ckt # Load Designation Note: Submit Panelboard Pictures (JPEG) with and without Cover # of Amps Poles Technical Support: Option lightingcontrol@eaton.com Take-off.xls 7/5/0 g h W e LUGS LUGS f a b Panelboard Take-off Worksheet D H Panelboard Designation Existing Pnlb Manufacturer Model/Series Number Main Device (MCB/MLO) Dimensions (inches) Smart C/B (Y/N) Voltage (08Y/0V, 80Y/7V) Ampacity Rating Short Circuit Rating Bus Material (AL/CU) Cable Entry (Top/Bottom) Panel Mount (Surface/Flush) Taken-off by Telephone Number Smart C/B (Y/N) # of Poles Figure.8-0. Panelboard Retrofit Take-Off Sheet (Consult Factory for Document) Date H W D a b c d e f g h Comments / Specials: Amps Load Designation Page Ckt # of Group CA0800E

51 April 07 Sheet Panelboard Ratings and Dimensions Pow-R-Line a.9- Pow-R-Command in Pow-R-Line a Construction Pow-R-Line a Panelboard Ratings Voltage 0 Vac maximum Main Lugs 00 0 A Main Breakers 00 0 A Branch Breakers 5 00 A (Bolt-on or plug-on chassis) Short-Circuit Current Ratings (Symmetrical) 0 Vac: 0 ka and ka fully rated 0 Vac: 00 ka series rated Service Three-phase, four-wire 08Y/0 V Single-phase, three-wire 0/0 V Suitable for service entrance applications when specified. Mains For available mains, refer to Table.9-. Branch Circuits For available branch devices, refer to Table.9-. Main Lugs Only The short-circuit rating of the MLO assembled panelboard will be fully rated based upon the lowest rated branch device or may be series rated with an approved upstream device. Main lugs only ampere ratings: 00, and 0. Main Circuit Breakers The short-circuit rating shown is that of the main breaker only. The shortcircuit rating of the assembled panelboard is the rating of the lowest fully rated main or branch device or the rating of an approved series rated combination. Table.9-. Branch Circuit Breakers Breaker Type BAB BAB BAB BAB-D BAB-C BABRSP BABRSP Ampere Rating Number of Poles,,,, Table.9-. Main Circuit Breakers QBGF, QBGFEP 5 50, 0 0 HID (High Intensity Discharge) rated breaker. Switching neutral breaker. Single-pole device requires two-pole space, two-pole device requires three-pole space. Solenoid operated breaker. 50 A is two-pole only. Series Rated Combinations Refer to series rating tables beginning on Page.9-7 for the approved series rated combinations available for the branch circuit breakers listed in Table.9-. Breaker Frame Amperes Breaker Type EHD FD, FDE HFD, HFDE FDC, FDCE EDB EDS ED EDH DK KD HKD KDC LHH Interrupting Rating (ka Symmetrical) at 0 Vac Interrupting Rating (ka Symmetrical) 0 Vac 0/0 Vac 0 Vac CA0800E

52 .9- Panelboard Ratings and Dimensions Pow-R-Line a April 07 Sheet Technical Data and Specifications Bussing 00 0 A: Tin-plated aluminum is standard, copper is available as an option. Boxes Boxes are made from code-gauge galvanized steel. Blank ends are supplied as standard, knockouts are available upon request. EZ Trim Trims are made from code-gauge steel and painted ANSI gray. All panelboards have door-in-door as standard with multi-point catch and lock, and concealed mounting hardware. Modifications Table.9-. Sub-Feed Lugs (Main Lugs Only) Ampere Rating 00 Table.9-. Through-Feed Lugs Ampere Information Rating 00 0 Panel Height Addition 0 Inches (0 mm) 0 Inches (0 mm) See Table.9- See Table.9- See Table.9- Table.9-5. Sub-Feed Breakers (One Per Panel) Ampere Rating Breaker Type 50 FDB FD HFD, HFDE FDC, FDCE EDB EDS ED EDH EDC DK KD HKD KDC Shunt Trips Shunt trips are available on breakers. BAB requires one additional pole space for shunt trip, i.e., single-pole is two-pole size, two-pole is three-pole size and three-pole is four-pole size. Ground Bar Standard bolted in box. Aluminum is standard, copper is available as an option. Enclosures Types,, R, and X. Interrupting Rating (ka Symmetrical) at 0 V Surge Protective Device (SPD) Integrated onto panelboard chassis. For complete product description and available ratings, refer to Tab. Box Sizing and Selection Box size for all Type panelboards are available from Table.9-. Instructions. Select the rating and type of mains required.. Count total number of branch circuit poles (including spaces) required in the panelboard. Do not count main breaker poles. Convert two- or three-pole branch breakers to single-poles, i.e., three-pole breaker, count as three poles. Note: For horizontal mounted mains (BAB Type), use main lug table, include space in branch section for mains.. Using correct table, type of mains and ampere rating per Step, find total number of poles. Note: Where total number of poles (Step ) fall between number in table, use the next higher number.. Read box size across columns to the right. Top and Bottom Gutters (Minimum) 5.50 inches (.7 mm). Side Gutters 0.00-inch (508.0 mm) wide box:.50 inches (5. mm). CA0800E

53 April 07 Sheet Panelboard Ratings and Dimensions Pow-R-Line a.9- Table.9-. Type Panelboards Dimensions in Inches (mm) Ampere Rating of Mains 00 A 00 A 5 Main lugs or main breaker 00 A 5 Main lugs or main breaker with 00 A through-feed lugs or sub-feed breaker A A Main lugs or main breaker A Main lugs or main breaker with A or 00 A sub-feed lugs or breaker 0 A 0 A Main lugs or main breaker 0 A Main lugs or main breaker with A or 00 A sub-feed lugs or breaker Main Breaker Type Mounting Position EHD, FDB, FD, FDE HFD, FDC, HFDE, FDCE Vertical EHD, FDB, FD, FDE HFD, FDC, HFDE, FDCE Vertical EDB, EDS, ED EDH, EDC FD, HFD, FDC, FDE, HFDE, FDCE Vertical EHD, FDB, FD, HFD, FDE FDC, EDB, EDS, HFDE, FDCE ED, EDH, EDC Vertical DK, KD, HKD, KDC, LHH Vertical DK, KD, HKD KDC, LHH Vertical EHD, FDB, FD HFD, FDC EDB, EDS, ED EDH, EDC Vertical Maximum Number of Branch Circuits Including Provisions Greater than branch circuit panelboards are available for jurisdiction governed by the 008 National Electrical Code. Smaller panelboard box sizes are available if required. Contact Eaton for application information. Add 8.00 inches (0. mm) for SPD..00-inch (7.) optional width is available for panelboards with high circuit counts. 5 For horizontal mounted mains (BAB Type), use main lug table, include space in branch section for mains. JD, HJD, JDC is same space requirement as 0 A DK, HKD, KDC Mains 8 Sub-feed breakers Box Dimensions Height Width Depth.00 (9.) 8.00 (9.) 8.00 (9.) 0.00 (5.0) 0.00 (5.0) 0.00 (5.0) 7.00 (8.8) 7.00 (8.8) 8.00 (9.) 8.00 (9.) 0.00 (5.0) 0.00 (5.0) 7.00 (8.8) 7.00 (8.8) 7.00 (8.8) (8.0).00 (9.) 8.00 (9.) 8.00 (9.) 0.00 (5.0) 0.00 (5.0) 0.00 (5.0) 7.00 (8.8) 7.00 (8.8) 8.00 (9.) 8.00 (9.) 0.00 (5.0) 0.00 (5.0) 7.00 (8.8) 7.00 (8.8) 7.00 (8.8) (8.0) 0.00 (5.0) 0.00 (5.0) 7.00 (8.8) 7.00 (8.8) 7.00 (8.8) 7.00 (8.8) (8.0) (8.0) 0.00 (5.0) 7.00 (8.8) 7.00 (8.8) (8.0) (8.0) (8.0) (8.0) CA0800E

54 .9- Panelboard Ratings and Dimensions Pow-R-Line a April 07 Sheet Pow-R-Command in Pow-R-Line a Construction Pow-R-Line a Panelboard Ratings Voltage 80Y/7 Vac maximum Note: PRLa panelboards are suitable for use on three-phase, four-wire 80Y/7 Vac service. Main Lugs 00 0 A Main Breakers 00 0 A Branch Breakers 5 00 A (bolt-on) Short-Circuit Current Ratings (Symmetrical) 0 Vac: 5 ka fully rated 0 Vac: 00 ka series rated 80Y/7 Vac: ka fully rated 80Y/7 Vac: 5 ka series rated Service Three-phase, four-wire 08Y/0 V and 80Y/7 V Single-phase, three-wire 0/0 V Suitable for service entrance applications when specified. Mains For available mains, refer to Table.9-7. The GHB main breaker is horizontally mounted, same as branch breakers. All other main breakers are vertically mounted. Branch Circuits For available branch devices, refer to Table.9-8. Main Lugs Only The short-circuit rating of the MLO assembled panelboard will be fully rated based upon the lowest rated branch device or may be series rated with an approved upstream device. Main lugs only ampere ratings: 00, and 0. Table.9-7. Main Circuit Breakers Breaker Frame (Amperes) Breaker Type GHB EHD 50 FDB FD, FDE HFD, HFDE FDC, FDCE ED DK KD HKD LHH KDC For use on 80Y/7 Vac systems only. Table.9-8. Branch Circuit Breakers Breaker Type GHB GHB GHQ HGHB GHQRD GHBGFEP Ampere Rating Number of Poles,, For use on 80Y/7 Vac systems only. Solenoid operated breaker. Series Rated Combinations Refer to series rating tables beginning on Page.9-7 for the approved series rated combinations available for the branch circuit breakers listed in Table.9-8. Main Circuit Breakers The short-circuit rating shown is that of the main breaker only. The short circuit rating of the assembled panelboard is the rating of the lowest fully rated main or branch device or the rating of an approved series rated combination. Interrupting Rating (ka Symmetrical) 80Y/7 Vac Interrupting Rating (ka Symmetrical) 0 Vac 0 Vac 7 Vac 80Y/7 Vac CA0800E

Pow-R-Command 1000 universal I/O module

Pow-R-Command 1000 universal I/O module Pow-R-Command 1000 universal I/O module Technical Data TD01412044E Effective February 2009 New Information Contents Pow-R-Command 1000 system......................... 2 General description.................................

More information

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.

More information

QUICK START. Installation & Programming Guide

QUICK START. Installation & Programming Guide QUICK START Installation & Programming Guide PRECAUTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. CAUTION - RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn off power at the circuit breaker

More information

Instruction Bulletin

Instruction Bulletin Instruction Bulletin 63249-401-200/A4 03/2005 POWERLINK TM G3 Controller NF1000G3 for use with POWERLINK G3 Systems Retain for future use. NOTICE Read these instructions carefully and look at the equipment

More information

i-3 Control Technology

i-3 Control Technology i-3 Control Technology Submittal Guide www.usa.siemens.com/i-3 Contents P1 Series Lighting Panel 4-6 i-3 Controller 7 SIPOD specifications 7-8 Inputs and Communications 9 Protocol Connections System Connections

More information

QSNE-2DAL-D Energi Savr Node QSTM 20 V. DALI Loop 2. seetouch QS Wallstation Energi Savr Node QS. QS Control Link

QSNE-2DAL-D Energi Savr Node QSTM 20 V. DALI Loop 2. seetouch QS Wallstation Energi Savr Node QS. QS Control Link LUTRON R Node TM NE-2DAL-D Fixture Controller NE-2DAL-D 09.0.09 Node TM The Node is a DIN-rail mounted controller for -compliant Digital Addressable loads. It provides bus power and control for two independent

More information

Model# CKM18 Model# CKM36 Model# CKM48 WARNING

Model# CKM18 Model# CKM36 Model# CKM48 WARNING Installation Instructions Model# CKM18 Model# CKM36 Model# CKM48 WARNING HAZARDOUS VOLTAGES. DISCONNECT FROM SUPPLY BEFORE REMOVING COVERS. NO USER SERVICEABLE PARTS INSIDE. SERVICE BY QUALIFIED PERSONNEL

More information

Lighting Control Panel

Lighting Control Panel Technical Data Lighting Control Panel Catalog# Project Comments Prepared by Date Type Overview Fifth Light s Lighting Control Panel (LCP) is used to control and operate all lighting devices using Digital

More information

SECTION DIGITAL LIGHTING CONTROLS

SECTION DIGITAL LIGHTING CONTROLS SECTION 26 09 25 PART 1 - GENERAL 1.1 SUMMARY A. Work included: 1. General Performance 2. Digital Wall or Ceiling Mounted Occupancy Sensor System 3. Digital Wall Switches 4. Handheld Remote Controls 5.

More information

Pegasus HC Lighting Control Panel

Pegasus HC Lighting Control Panel Overview The drives up to 32 relays, each rated 20 amps, with an integrated time clock and photocell input. Users can manually switch outputs on or off from a remote pushbutton controller, or create time

More information

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

clarity 3 Programmable Controller

clarity 3 Programmable Controller clarity 3 Programmable Controller BACnet General Purpose Controllers (B-AAC) DESCRIPTION Taco Clarity 3 FPC series controllers are designed to control building systems and HVAC equipment. The integrated

More information

Lighting Control Panel 16 and 24 INSTALLATION INSTRUCTIONS

Lighting Control Panel 16 and 24 INSTALLATION INSTRUCTIONS PRECAUTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. CAUTION: USE COPPER CONDUCTOR ONLY CAUTION: RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn off power at the circuit breaker before installing

More information

Table of Contents 1 ABOUT THIS GUIDE CONTACT INFORMATION ANTENNA INSTALLATION... 4

Table of Contents 1 ABOUT THIS GUIDE CONTACT INFORMATION ANTENNA INSTALLATION... 4 Table of Contents 1 ABOUT THIS GUIDE... 3 1.1 CONTACT INFORMATION... 3 2 ANTENNA INSTALLATION... 4 2.1 GENERAL INFORMATION... 4 2.2 SPECIFIC MOUNTING EXAMPLES... 5 2.3 CONNECTOR MOISTURE PROTECTION...

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

Wireless Fixture Adapter (WFA100-SN) Installation Instructions

Wireless Fixture Adapter (WFA100-SN) Installation Instructions Installation Instructions The Daintree Wireless Fiture Adapter () forms part of Daintree s Controlscope Manager (CSM) in commercial and industrial buildings. It transmits and receives messages over the

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 16 AND 24 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

LiteKeeper 8. Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION 1.02 DESCRIPTION OF WORK

LiteKeeper 8. Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION 1.02 DESCRIPTION OF WORK LiteKeeper 8 Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION The work covered in this section is subject to all of the requirements in the General Conditions

More information

Wireless Adapter (WA100-PM) i. Installation Instructions

Wireless Adapter (WA100-PM) i. Installation Instructions i. Installation Instructions The Daintree WA100-PM Wireless Adapter forms part of the Daintree ControlScope wireless controls solution for smart commercial and industrial buildings. It transmits and receives

More information

H704-42(H)(E), H704-42/1(H)(E)

H704-42(H)(E), H704-42/1(H)(E) POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (

More information

Basketball Shot Clock Set LX2180 Manual

Basketball Shot Clock Set LX2180 Manual Basketball Shot Clock Set LX2180 Manual 72 Industrial Boulevard Wrightsville, GA 31096 Phone: (800) 445-7843 Fax: (800) 864-0212 www.electro-mech.com LX2180 Revision 5 February 8, 2013 Table of Contents

More information

MICROFUSION FEATURES OPTIONS CERTIFICATIONS (PENDING) THREE PHASE SCR POWER CONTROLLERS

MICROFUSION FEATURES OPTIONS CERTIFICATIONS (PENDING) THREE PHASE SCR POWER CONTROLLERS MICROFUSION THREE PHASE SCR POWER CONTROLLERS FEATURES Auto-Ranging Input Voltage 24-600 VAC, 45-65 Hz AC Output 16, 32, 50, 80 Amps (@ 50 C 6000 ft) Control Features Microprocessor-based controller /

More information

IEI emerge MicroNode Install and Setup Guide. Contents

IEI emerge MicroNode Install and Setup Guide. Contents IEI emerge MicroNode Install and Setup Guide Contents Connecting power and the network to the MicroNode... 2 Using Power over Ethernet (PoE)... 3 or... 3 Using a 12 VDC power supply... 3 Connecting and

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

SEL-2414 Transformer Monitor

SEL-2414 Transformer Monitor SEL-2414 Transformer Monitor SEL-2414 Base Unit Vertical Chassis Front Panel Large LCD Display 4 Programmable Pushbuttons w/leds 7 Programmable LEDs Operator Control Interface EIA-232 Port Processor and

More information

Pow-R-Command 1000 Lighting Optimization Software

Pow-R-Command 1000 Lighting Optimization Software Pow-R-Command 1000 Lighting Optimization Software Technical Data TD01412035E Effective October 2007 New Information Contents General............................................... 2 Pow-R-Command 1000

More information

Quick Start Installation Guide

Quick Start Installation Guide apc/l Quick Start Installation Guide Version A2 Document Part Number UM-201 May 2010 OVERVIEW The apc/l is an intelligent access control and alarm monitoring control panel which serves as a basic building

More information

LiteKeeper 4. Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION 1.02 DESCRIPTION OF WORK

LiteKeeper 4. Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION 1.02 DESCRIPTION OF WORK LiteKeeper 4 Stand Alone Lighting Control Panel Technical Specifications PART 1. GENERAL 1.01 INTRODUCTION The work covered in this section is subject to all of the requirements in the General Conditions

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

9.3. Metering Devices, Protective Relays, Software and Connectivity

9.3. Metering Devices, Protective Relays, Software and Connectivity .3, Protective Relays, Software and Connectivity Product Eaton s IQ Multipoint Energy Submeter II is a revenue class electronic submetering device that can be mounted in panelboards or switchboards. When

More information

Pow-R-Command 2000 System Overview

Pow-R-Command 2000 System Overview Pow-R-Command 2000 System Overview Technical Data TD01412050E Effective January 2009 Contents Advanced Web Service Technology...................... 2 Pow-R-Command 2000 General Overview................

More information

Preparing for a Docking Drawer Slim Installation To prepare for a successful Docking Drawer Slim installation please ensure that the cable management

Preparing for a Docking Drawer Slim Installation To prepare for a successful Docking Drawer Slim installation please ensure that the cable management Docking Drawer Install Manual Docking Drawer Slim Series Applicable Models: 0290 00031(W) / 24 0290-00030(W) / 21 0290-00047(W) / 18 0230-00004. r6 1/19/2016 CAUTION READ CAREFULLY Failure to follow these

More information

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration Data Sheet Lighting Relay Panel Overview Leverage the Power of BAS Integration Exterior with Surface Mount Trim The Series UL Listed, Lighting Control Panel provides the capability to control high voltage

More information

D1V Rotary Control Panel D4S Button Panel PS Power Distribution Module USER MANUAL

D1V Rotary Control Panel D4S Button Panel PS Power Distribution Module USER MANUAL TM D1V Rotary Control Panel D4S Button Panel PS Power Distribution Module USER MANUAL General Cautions & Warnings! To prevent electrical shock or potential fire hazards, do not expose these products to

More information

GR 2400 PLANNING GUIDE. Important Note:

GR 2400 PLANNING GUIDE. Important Note: GR 2400 PLANNING GUIDE [ NEW CONSTRUCTION ] Planning Guide Index The Bus File................................... 2 Single Line Drawings.......................... 3 Multi-Bus Systems.............................

More information

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box

More information

SECTION ( ) LIGHTING CONTROL PANELBOARD

SECTION ( ) LIGHTING CONTROL PANELBOARD (26 24 16.02) LIGHTING CONTROL PANELBOARD PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install Lighting Control Panelboards as specified and as shown on the contract drawings. B. The Lighting

More information

Acuity Relay Panel User Guide

Acuity Relay Panel User Guide Acuity Relay Panel User Guide 1 of 26 Table of Contents Installation and Troubleshooting 1.1 - Powering Up the Panel... 3 1.2 - LED Blink Codes On Relay Control Card... 5 1.3 - Testing Relay and Dimming

More information

AB0602D ARCHITECTURAL BALLAST DRIVER. Version Date 06/25/2012

AB0602D ARCHITECTURAL BALLAST DRIVER. Version Date 06/25/2012 AB0602D ARCHITECTURAL BALLAST DRIVER Version 0.10 Date 06/25/2012 Page 2 of 10 DESCRIPTION AND FEATURES The AB-0602D is a 6 circuit, 2400 Watts per circuit ballast driver intended for dimmable fluorescent

More information

EISSBox OpenADR 2.0b

EISSBox OpenADR 2.0b Installation Instructions EISSBox EISSBox OpenADR.0b INS # Energy Interop Server & System (EISS ) EISSBox.0b Local Unit Installation Guide. IPKeys EISSBox is an OpenADR.0bcertified end point that is capable

More information

Instruction Bulletin. Fiber Optic Switch Packs. SLSPSP101 and SLSPSP102 for use with Luminaires INTRODUCTION CONTENTS OF THE BOX

Instruction Bulletin. Fiber Optic Switch Packs. SLSPSP101 and SLSPSP102 for use with Luminaires INTRODUCTION CONTENTS OF THE BOX Instruction Bulletin 63249-500-04A3 07/2010 Fiber Optic Switch Packs SLSPSP101 and SLSPSP102 for use with Luminaires INTRODUCTION SLSPSP101 Single Input Switch Pack SLSPSP102 Dual Input Switch Pack The

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new Controller.

More information

Installing Powerlink NF3500G4 Controllers

Installing Powerlink NF3500G4 Controllers Installing Powerlink NF3500G4 Controllers for Use with Powerlink Systems RETAIN FOR FUTURE USE Installing Powerlink NF3500G4 Controllers 63249-420-374A3 Instruction Bulletin 09/2015 2 2015 Schneider Electric.

More information

SCC Inc. TS Series. Technical Instructions. Document No. TS-2000 March 15, 2016

SCC Inc. TS Series. Technical Instructions. Document No. TS-2000 March 15, 2016 SCC Inc. TS-MS Master Lead/Lag Panels for Boiler Management, and Building Management System Interface Technical Instructions March 15, 2016 Description A TS-MS Series Master Lead/Lag Panel sequences and

More information

SEL-2411 Programmable Automation Controller

SEL-2411 Programmable Automation Controller SEL-2411 Programmable Automation Controller - Chassis - Processor and Communications Board - Front Panel - EIA-232 Port - LCD Display - IRIG-B Time Code - Operator Control Interface - Power Supply with

More information

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ONE ARTIS ZEEGO / ZEEGO.ZEN ARTIS ZEE MULTIPURPOSE SINGLE PLANE IECAX480V125A Main Disconnect Panel Bevco Engineering

More information

Compact, Low Profile High Rendering, 100% Diffusion

Compact, Low Profile High Rendering, 100% Diffusion SURFACE MT SERIES PRELIMINARY SPECIFICATION, SUBJECT TO CHANGE WITHOUT NOTICE MT Series Compact, Low Profile High Rendering, 100% Diffusion Trimless, No Visible Hardware Trimless appearance for recessed

More information

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers DECK All-In-One Enclosure Quick Installation Guide for Field Installers 1 Contents Legal Statement... 2 Preliminary Considerations... 2 Required Installation Tools and Materials... 2 Networking Information...

More information

Digital Lighting Systems, Inc.

Digital Lighting Systems, Inc. , Inc. PD402-DMX Four Channel Dimmer and Switch Packs 4 x 2.5 Amps @ 6VDC to 24 VDC DMX52 compatible DMX52 4 x 2.5 Amps Dimmer Pack C UL US LISTED Digital Lighting Systems, Inc. USER'S MANUAL User's Manual

More information

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis. A21 DIMMER CABINET SPECIFICATION. GENERAL. A.) Overview. 1.) The dimmer cabinets shall be fully digital, designed specifically for architectural and entertainment lighting applications, and shall consist

More information

Connecting a Cisco Output Module

Connecting a Cisco Output Module CHAPTER 5 Overview The optional Cisco Output Module (Figure 5-1) is attached to a Cisco Physical Access Gateway or Cisco Reader Module to provide additional connections for up to 8 outputs, each of which

More information

PS-4100 POWER SUPPLY MANUAL

PS-4100 POWER SUPPLY MANUAL PS-4100 POWER SUPPLY MANUAL Manual Part Number 180-0573 December 7, 2006 TABLE OF CONTENTS TITLE PAGE Table of Contents... 2 List Of Figures... 3 1. Introduction... 4 1.0. General... 4 1.1. Features...

More information

Specialized Lighting Solutions, Inc. SLS DALI CONTROLLERC

Specialized Lighting Solutions, Inc. SLS DALI CONTROLLERC DCP-A Panel Network DALI Control Panel for DALI Ballast, DALI Relays and DALI Dimmers 24 20 6 The DCP-A electronic network control panel with Clipsal DCDALCIP250-2 serial interfaces supports applications

More information

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service. PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA

More information

4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection...

4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection... .3 Product Description Drawout molded case circuit breaker switchboard Front accessible Front connected Through-the-door design drawout mechanism through 600A Insulated case UL 89 breakers up to 200A Visual

More information

POWER OVER ETHERNET. Technical Information. H.E. Williams, Inc. Carthage, Missouri

POWER OVER ETHERNET. Technical Information. H.E. Williams, Inc. Carthage, Missouri POWER OVER ETHERNET Technical Information PoE Technical Info Table of Contents PoE Lighting System Diagram...1 Example...1 PoE Gateway...2 Ordering Information...2 PoE Software & Service Packages...3 Ordering

More information

Active UTP Transceiver Hub with Integral Camera Power Installation Guide

Active UTP Transceiver Hub with Integral Camera Power Installation Guide Active UTP Transceiver Hub with Integral Installation Guide Models Include: HubWayLD8D HubWayLD16D - Eight (8) Channels - Sixteen (16) Channels HubWayLD82D HubWayLD162D - HubWayLD8D w/eight (8) HubWayAv

More information

Load D. Emergency. Line Voltage. to 3rd party device. Load C

Load D. Emergency. Line Voltage. to 3rd party device. Load C BAT= Sensor Configuration Load Config (PnL) Daylighting Config School - Classroom Best Practices A2.0E Indirect/Direct Pendant Lighting - With Lighting Occupancy sensing Manual control Single-zone daylight

More information

General Programming Tips

General Programming Tips nlight Relay Panel User & Programming Guide Installation & Troubleshooting Tips 1.1 - Powering Up Panel... 2 1.2 - LED Blink Codes On Relay Control Card... 3 1.3 - Testing Relay & Dimming Outputs... 4

More information

Pow-R-Command System Overview

Pow-R-Command System Overview July 2003 - System Overview Technical Data Table Of Contents System General 2 Applications for System 2 The Need For Lighting Control 2 Energy Costs 2 Software Control 2 Secure Network & Distributed Intelligence

More information

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM 1993 SPECIFICATIONS CSJ 1685-05-068, ETC. & 1685-02-042 1.0 DESCRIPTION SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM THIS ITEM DESCRIBES THE OPERATION AND INSTALLATION OF AN ARTERIAL

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

Dim levels for each system output may be controlled by any of the following methods:

Dim levels for each system output may be controlled by any of the following methods: Applied Electronics Bravo Series Dimming System Rack-Mount Architectural l SA12/2400A and l SA12/2400E Setup and Operation Instructions 1.0 Scope This document details the setup and operation requirements

More information

SEM3 - Embedded Micro Metering Module

SEM3 - Embedded Micro Metering Module SEM - Embedded Micro Metering Module Quick Reference Guide and Installation Instructions Scan QR Code for more information usa.siemens.com/sem Installation! DANGER Hazardous Voltage. Will cause death or

More information

SmartWire-DT In panel and on machine wiring solutions. Revolutionizing in-panel control wiring and on-machine connection of sensors and actuators

SmartWire-DT In panel and on machine wiring solutions. Revolutionizing in-panel control wiring and on-machine connection of sensors and actuators SmartWire-DT In panel and on machine wiring solutions Revolutionizing in-panel control wiring and on-machine connection of sensors and actuators SmartWire-DT Changing the way panels... Reduce cost throughout

More information

Control Your World. Lighting Control System

Control Your World. Lighting Control System Lighting Control System Control Your World Today s homes have a wide variety of lights, dimmers and switches, indoors and out. Lighting control provides convenience, cost savings and an extra measure of

More information

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Product Data Sheet Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ZEE BIPLANE IECAX480V225A Main Disconnect Panel Bevco Engineering Company, Inc. CONFIDENTIAL

More information

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157 PRODUCT DA TA SLC 150 110 Expansion Unit Catalog Nos. 1745-151, - 152, - 153, - 154, - 156, -E157 7 : The EXpdnSiQn Unit The SLC 150 expansion unit can be used with either the SLC 150 processor unit or

More information

MC CO MODBUS ADDRESSABLE SENSOR

MC CO MODBUS ADDRESSABLE SENSOR MC-4210 - CO MODBUS ADDRESSABLE SENSOR Manual Part Number 180-0545A March 31, 2003 PAGE 1 TABLE OF CONTENTS TITLE PAGE Table of Contents...2 List Of Figures...4 1. Introduction...5 1.0. General...5 1.1.

More information

Advanced Distribution Cable Junction Box For Spectra RMS Molded-Case Circuit Breakers with Advanced Feature microentelliguard TM Trip Units

Advanced Distribution Cable Junction Box For Spectra RMS Molded-Case Circuit Breakers with Advanced Feature microentelliguard TM Trip Units GE Energy Industrial Solutions GEH-704 Installation Instructions Advanced Distribution Cable Junction Box For Spectra RMS Molded-Case Circuit Breakers with Advanced Feature microentelliguard TM Trip Units

More information

Avtec, Inc. Lighting Systems

Avtec, Inc. Lighting Systems 6 Industrial Park Cahokia, IL 62206 Phone (618) 337-7800 Fax (618) 337-7976 E-Mail tech_info@avteclighting.com Report No. INSTALLATION OPERATION MAINTENANCE MANUAL, LED STRIP LIGHT, P/N 01-11-0007 P/N

More information

Provolt 0-10V Dimming Room Controllers (PRC)

Provolt 0-10V Dimming Room Controllers (PRC) (PRC) Easy-to-Install Self-Contained Lighting Control Solution Light Pipe DESCRIPTION The Leviton exclusive Provolt Room Controllers (PRC) offer high performance, code compliant, advanced room configuration

More information

6222 Two Door Module Technical Operations Manual

6222 Two Door Module Technical Operations Manual 6222 Two Door Module Technical Operations Manual TABLE OF CONTENTS Specifications...3 Overview...4 Operations...5 Custom Access Mode...5 Standard Access Mode...5 Offline Access Mode...5 Offline Memory...5

More information

Energi Savr Node for DALI QSNE-2DAL-D DALI Fixture Controller V. Photo

Energi Savr Node for DALI QSNE-2DAL-D DALI Fixture Controller V. Photo UTRO R UTRO R ode for E-2DA-D Fixture Controller ode for The ode unit is a DI-rail mounted controller for -compliant digital addressable loads. It provides bus power and control for two independent buses

More information

2U Congestion Alert Rack Insert for UK

2U Congestion Alert Rack Insert for UK 2U Congestion Alert Rack Insert for UK 2U Congestion Alert Rack Insert for UK The 2U congestion alert rack insert comes fully assembled, wired and ready to be installed in a rack. The rack provides communications,

More information

Modular Room Control (MRC) Series Expansion Board

Modular Room Control (MRC) Series Expansion Board Installation Instructions Issue Date December 13, 2002 Modular Room Control (MRC) Series Expansion Board Application The Modular Room Control (MRC) system has the ability to expand its input/output capabilities

More information

Allure EC-Smart-Comfort Series

Allure EC-Smart-Comfort Series Datasheet Allure EC-Smart-Comfort Series Communicating sensors with Smart-Light and Smart-Blind add-on modules Overview Features & Benefits The Allure EC-Smart-Comfort Series are versatile communicating

More information

Single Phase Systems-North American PC125/PC420 Series

Single Phase Systems-North American PC125/PC420 Series Single Phase Systems-North American PC125/PC420 Series Enclosure Power Distribution Units (epdu ) PC125-C Front RACK MOUNTED 19 x 3.4 (2U) x 8.5. Approximate shipping weight: 19 lbs. (12) NEMA OUTLETS

More information

LITETOUCH HYBRID WALL BOX DIMMER INSTALLATION INSTRUCTIONS

LITETOUCH HYBRID WALL BOX DIMMER INSTALLATION INSTRUCTIONS READ INSTRUCTIONS PRIOR TO INSTALLATION OF EQUIPMENT OR YOU MAY VOID THE WARRANTY! LITETOUCH INSTALLATION INSTRUCTIONS The LiteTouch Hybrid Wall Box Dimmer is a configurable lighting control device, that

More information

RXTH DUAL ROOM SENSOR / SWITCH

RXTH DUAL ROOM SENSOR / SWITCH DUAL ROOM SENSOR / SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE

More information

Rev CH Breaker Gateway Installation and Operation Manual

Rev CH Breaker Gateway Installation and Operation Manual 026-1710 Rev 1 05-15-07 CH Breaker Gateway Installation and Operation Manual 1640 Airport Road, Suite 104 Kennesaw, GA 31044 Phone: (770) 425-2724 Fax: (770) 425-9319 ALL RIGHTS RESERVED. The information

More information

PM Series Power Meter

PM Series Power Meter PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See

More information

Energi Savr Node with DALI for Quantum

Energi Savr Node with DALI for Quantum Energi Savr Node Digital Fixture Controller - CPN6916 Energi Savr Node with for Quantum 369794c 1 08.25.17 The Energi Savr Node family is a group of intelligent, modular products for the control of lighting

More information

Pow-R-Command 1000 System Overview

Pow-R-Command 1000 System Overview Pow-R-Command 1000 System Overview Instruction Leaflet IL01412008E Effective February 2009 Supersedes July 2006 Notes and Warnings............................... 2 Introduction......................................

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

GreenMAX Relay Control Panels

GreenMAX Relay Control Panels GreenMAX Relay Control Panels Smart Lighting Control Built By the Industry, For the Industry WHAT IS GreenMAX? GreenMAX is changing the industry standard for Relay Control Panels. A product that is built

More information

USER GUIDE. Stand-Alone Version

USER GUIDE. Stand-Alone Version USER GUIDE Version 2D-SA 1/1/06 Stand-Alone Version Class A FCC Device Statement Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void

More information

EA500. Installation Instructions Transponder

EA500. Installation Instructions Transponder EA500 EN Installation Instructions Transponder EA500 Installation Instructions 1.0 Overview EN 2 1.0 Overview The EA500 Transponder is the Security Escort module that provides communications between the

More information

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions. Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64

More information

Distributed Power Series

Distributed Power Series GENERAL INFORMATION The Room Controller offers a full power and control solution for standalone and integrated room controls. With up to eight zones of relay switching with 0-10V control fully rated at

More information

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide

Passive UTP Transceiver Hub with Integral Camera Power Installation Guide Passive UTP Transceiver Hub with Integral Installation Guide Models Include: HubWay8D HubWay16D - Eight (8) Channels - Sixteen (16) Channels HubWay82D HubWay162D - HubWay8 w/eight (8) HubWayAv - HubWay16

More information

GRX-3000 Control Units

GRX-3000 Control Units PRESET DIMMING CTROLS GRX-000 Control Units GRX-000 Control Units DESCRIPTI Cover (shown open) Base Zone Provide pushbutton recall of four preset lighting scenes. Control virtually any light source. Provide

More information

PHS Series. PowerHUBB Node - Satellite

PHS Series. PowerHUBB Node - Satellite PHS Series PowerHUBB Node - Satellite Project Name NETWORK Catalog No. Date The Hubbell Control Solutions' (HCS) PowerHUBB node provides power distribution architecture and data connectivity to create

More information

Allure EC-Smart-Comfort Series

Allure EC-Smart-Comfort Series Datasheet Allure EC-Smart-Comfort Series Communicating sensors with Smart-Light and Smart-Blind add-on modules Overview The Allure EC-Smart-Comfort series are versatile communicating sensor which provide

More information

EP/2 Installation Instructions

EP/2 Installation Instructions 1 2 3 4 7 ENTER 0 5 6 8 9 CLEAR + - LOGIC ONE EP/2 EP/2 Installation Instructions DOC. #569011000 A 7/30/04 PRINTED IN U.S.A. Regulatory Compliance Safety This device has been tested and found to be in

More information

Avtec, Inc. Lighting Systems

Avtec, Inc. Lighting Systems 6 Industrial Park Cahokia, IL 62206 Phone (618) 337-7800 Fax (618) 337-7976 E-Mail tech_info@avteclighting.com Report No. INSTALLATION OPERATION MAINTENANCE MANUAL, LED STRIP LIGHT, P/N 01-11-0010 P/N

More information

INTRODUCTION - DISPLAYS, DATA LOGGERS AND SOFTWARE

INTRODUCTION - DISPLAYS, DATA LOGGERS AND SOFTWARE INTRODUCTION - DISPLAYS, DATA LOGGERS AND SOFTWARE In times where energy conservation is a top priority for all progressive enterprises, the measurement of flow rates and consumption is becoming more and

More information

Occupancy and Vacancy Sensors ROOM CONTROLLER* DAYLIGHT SENSOR WPP-INT INSTALLATION GUIDE

Occupancy and Vacancy Sensors ROOM CONTROLLER* DAYLIGHT SENSOR WPP-INT INSTALLATION GUIDE Occupancy and Vacancy Sensors ROOM CONTROLLER* DAYLIGHT SENSOR WPP-INT INSTALLATION GUIDE 2 Part Number: WIR-3110 WARNING! SYSTEM MUST BE INSTALLED IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES

More information