7SA511 V2.2 Numerical Line Protection Relay

Size: px
Start display at page:

Download "7SA511 V2.2 Numerical Line Protection Relay"

Transcription

1 7SA511 V2.2 Numerical Line Protection Relay Operator Manual Power Blocked Manual No. SG

2

3 Table of Contents Table of Contents User Guide Chapter 1 Introduction Chapter 2 Product Description Chapter 3 Acceptance Tests Chapter 4 Installation Chapter 5 Programming the Relay Chapter 6 Displaying System and Relay Information Chapter 7 Commissioning the Relay Chapter 8 Maintenance Reference Guide Reference A. Method of Operation... A-1 Reference B. Hardware and Software... B-1 Reference C. Communications... C-1 Reference D. Specifications... D-1 Reference E. Reference F. Settings Calculations...E-1 Setting Worksheets...F-1 Reference G. Input/Output Functions... G-1 July 27, 1995 i

4 Table of Contents The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligation. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes, the matter should be referred to your local sales office. The contents of this manual should not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Energy & Automation, Inc. Any statements contained herein do not create new warranties or modify an existing warranty. ii July 27, 1995

5 Chapter 1 Introduction Table of Contents 1. Introduction Using This Manual Glossary of Terms and Abbreviations Relay Model Number List of Figures Figure 1-1. Reading the 7SA511 Relay Model Number July 27,

6 Introduction This page intentionally blank 1-2 July 27, 1995

7 Chapter 1 1. Introduction 1.1 Using This Manual This operator s manual is intended to provide you with all the information you need to install and operate the Siemens 7SA511 Numerical Line Protection Relay. In addition to describing the various tasks of operation, the manual offers general information about the functions and features of the relay. Several of the relay s functions and features are optional, depending on the model ordering number. This manual identifies all of the relay s options and frequently refers you to section 1.3, Relay Model Number, so you can determine which options your relay has. This manual is divided into two parts: The User Guide describes how to install, program, operate and maintain the relay, so you will need to read this part if you are to perform any of these tasks. General information about the relay s features and functions is also in this part of the manual. The Reference Guide includes the relay specifications, method of operation, relay setting calculations and worksheets, and information on the relay s hardware, software, and communications capabilities. If you are responsible for the application and setting calculation of the relay, you will need to read this part of the manual. Refer to Table 1-1 for help in finding the information you need in this manual. Table 1-1. Using This Manual. If you want to... Then read... learn more about the relay Chapter 2, Product Description Reference A, Method of Operation Reference B, Hardware & Software Reference C, Communications determine the optional function(s) Section 1.3, Relay Model Number available in your relay install the relay Chapter 4, Installation perform acceptance tests Chapter 3, Acceptance Tests program the relay Chapter 5, Programming the Relay Reference E, Setting Calculations Reference F, Setting Worksheets Reference G, Input/Output Functions check relay status, target history Chapter 6, Displaying System and Relay Information logs, and the event log place the relay in service or Chapter 7, Commissioning the Relay perform maintenance Chapter 8, Maintenance review relay specifications Reference D, Specifications July 27,

8 Introduction This manual assumes you are using the relay s operator panel to program, maintain, and operate the relay. If you are using DIGSI software or some other application to control the relay, refer to the appropriate user guide when instructions in this manual are insufficient. 1.2 Glossary of Terms and Abbreviations Following are definitions and descriptions of terms and abbreviations used in this manual that are unique to power systems and to Siemens relay technology in particular. Abbreviations and Acronyms A/D analog-to-digital AR automatic reclose CB circuit breaker C/O changeover CT current transformer CW codeword DAR delayed automatic reclose E earth or ground EEPROM electrically erasable, programmable read only memory E/F earth (ground) fault EPROM erasable, programmable read only memory FD fault detection; fault detector FNo function number I.T. inverse time LCD liquid crystal display (on the relay operator panel) LED light emitting diode (on the relay operator panel) LSA a substation (Siemens Localized Substation Automation system) m memorized M/C manual close mcb or m.c.b. miniature circuit breaker NC normally closed nm not memorized NO normally open O/C overcurrent PC personal computer pcb printed circuit board PCO parameter changeover PLC power line carrier POTT permissive overreach transfer trip (pilot protection scheme) PUTT permissive underreach transfer trip (pilot protection scheme) RAM random access memory RAR rapid automatic reclose ROM read only memory TT transmit time VT voltage transformer 1-4 July 27, 1995

9 Chapter 1 Terms annunciation 1. Activating the various relay outputs (LCD, LEDs, output relays) when events occurs. 2. Messages that appear on the operator panel LCD in the event log or target logs are also called annunciations. binary input block compensated (system) dead time drop-off drop-out earth fault loop forward high-set isolated (system) marshalling A relay input terminal that responds to the presence or absence of voltage on the terminal in a digital (on/off) manner. 1. Prevent normal operation or function. 2. Group of memory addresses. The neutral system point is inductively grounded to compensate for the distributed phase-to-ground system capacitance. Time allowed following fault clearance before attempting an automatic reclose. Drop-out (used in the LCD text). Return to a normal or no-fault state. Electrical ground. In phase-selective fault detection systems, this term describes the current path for phase-to-phase or phase-to-ground faults. For example, if a short circuit occurs between phase 1 (L1) and phase 2 (L2), the fault loop is L1-L2. The currents and voltages of the fault loop are decisive when calculating the distance to fault. Direction normally downstream towards the line or load (i.e., toward the protected component). An overcurrent protection element that operates independently of the definite time or inverse time elements and typically has a high pickup value and a small or zero (instantaneous) time delay. The neutral system point is purposely not connected to ground (ungrounded). Configuring the I/O units (LEDs, trip relays, etc.) July 27,

10 Introduction Terms pickup reclaim time reverse stage starpoint target trip Activation of a protection function either through detection of a fault or as a result of a binary input. The current and voltage levels or ratios that cause a protection element to pick up are called pickup values. The no-fault time period following automatic reclose that defines a successful reclose Direction normally upstream towards the bus or source (i.e. away from the protected object). A protection element; a group of protection parameters that, at a minimum, include pickup and time delay values. Common connection point in wye-connected electrical equipment; the neutral connection. System device to which a command or signal is directed. Activate a trip relay or open a circuit breaker. 1.3 Relay Model Number The model number for your 7SA511 relay is printed on the relay s nameplate, which is located on the operator panel (see Figure 2-1 in Chapter 2, Product Description ). As illustrated in Figure 1-1, you can read your relay s model number and determine the rated current, DC supply voltage, type of mounting (flush or surface), type of fault detection, and which optional functions your relay has. Using the model number allows you to verify that you have the correct relay for the application. This manual frequently refers you to the relay model number so you can determine whether or not a particular section is applicable to your relay and protected system. When the model number is used, the character(s) significant to the discussion is bold, and asterisks (*) are used to indicate that the character is irrelevant to the discussion. For example, model number 7SA511*-**A5*- **A/E* means the relay does not have the automatic reclose feature, so you can skip the sections on automatic reclose. 1-6 July 27, 1995

11 Chapter 1 Line Protection Relay Ratedcurrentat60/50HzAC 7SA511 A5 1A 5A Rated power supply voltage VDC , 48 VDC 60, 110, 125 VDC 220, 250 VDC Mounting construction Surface mounting Flush mounting Fault detection options B C Overcurrent fault detection Overcurrent, Voltage-controlled Overcurrent, and Polygonal Impedance fault detection Overcurrent and Voltage-controlled Overcurrent fault detection Ground fault detection input For grounded systems, ground current input for protected line only For ungrounded systems, without parallel line compensation For grounded systems, ground current input for parallel line compensation Communications interface (rear port) None Isolated, hard-wired Integrated fiber optic Automatic reclose (AR)/Parameter changeover (PCO) without AR with AR 3-pole with AR 1/3-pole without AR with AR 3-pole with AR 1/3-pole without PCO without PCO without PCO with PCO with PCO with PCO Power swing (PS)/High-resistance ground fault protection (GF) * A B C A B C E F G without PS with PS without PS with PS without GF without GF with GF with GF * The Power swing (PS) option is only applicable when the fault detection system selected is the polygonal impedance detector (code = 2). The High-resistance ground fault (GF) protection is only applicable for grounded systems, i.e., the ground fault detection Input code must be 0or2. Figure 1-1. Reading the 7SA511 Relay Model Number. July 27,

12 Introduction This page intentionally blank 1-8 July 27, 1995

13 Chapter 2 Product Description Table of Contents 2. Product Description About the Relay Relay Features Relay Setting Types Relay Setting Descriptions (by Address Block) Overview of Protection Functions Distance Protection Emergency Overcurrent Protection Power Swing Protection (optional) Pilot Protection High-Sensitivity Ground Fault Protection for Ungrounded Systems (optional) High-Resistance Ground Fault Protection (optional) Automatic Reclose (optional) Distance-to-Fault Location Additional Functions and Features of the Relay Secured Data Storage Serial Data Ports Multiple Parameter Sets (optional) July 27,

14 Product Description This page intentionally blank 2-2 July 27, 1995

15 Chapter 2 2. Product Description 2.1 About the Relay The 7SA511 line protection relay is a microprocessor-based relay designed to provide fast, reliable, and selective clearance of all kinds of ground and phase faults on overhead lines and cables being fed from one point or multiple points. The system can be radial, ring, or meshed topography. The system starpoint can be solidly grounded, compensated (resonant grounded), or isolated (ungrounded). This relay has 10 binary inputs, 5 trip relays, 11 signal relays, and 16 LED indicators. The relay can be flush or surface mounted and is easily programmed and operated using the controls and keypad on the operator panel. The LEDs on the operator panel continuously display relay status and target indication. When prompted, the LCD shows the system settings, configuration settings, protection settings, measured values, calculated values, setting options, event messages, and other operational information. The relay can be connected to a PC or to a substation control system, enabling the user to analyze data stored in the relay s memory and to monitor the relay s alarms and status signals. July 27,

16 Product Description 2.2 Relay Features Microprocessor-Based Technology Fully Numerical Design Five Distance Zones, Phase and Ground Polygonal Impedance Characteristic Selectable Forward, Reverse or Nondirectional Separate R-Setting for Phase and Ground Seven Independent Time Delays Fault Detector Options - Overcurrent - Voltage-Controlled Overcurrent - Impedance Pilot Logic Schemes - Permissive Overreach Transfer Trip (POTT) - Permissive Underreach Transfer Trip (PUTT) - Blocking - Unblocking - Directional Comparison - Directional Pilot Wire (requires 7PA5210) Weak Feed Echo Keying Logic Transient Blocking Zone Extension Scheme Reverse Interlock Bus Protection Single/Three-Pole Trip Single/Three-Pole Multi-Shot Reclosing Loss of Potential Block Overcurrent Protection as Backup for Distance Protection Power Swing Block/Trip Close-Onto-Fault Protection Isolated Ground Fault Detection Directional High Resistance Ground Fault Protection Nonvolatile Memory for Settings and Targets Programmable Binary Inputs, LEDs, Signal and Trip Relays Four Independent Setting Groups Fault Locating Parallel Line Compensation Option Fault Target Data Fault Waveform Capture (0.83 ms resolution for 60 Hz frequency) Operations Event Log Circuit Breaker Operations Counter Accumulated Circuit Breaker Interrupted Current (per pole) Real-Time Clock Circuit Breaker Trip Test Function Circuit Breaker Reclose Test Metering Functions (On-line) - Voltage - Current - Real Power (Watts) - Reactive Power (Vars) - Frequency - Impedances Two Serial Ports (one standard, one optional) IEC Communication Standard Self-Monitoring Draw Out Construction 2.3 Relay Setting Types The relay requires four types of settings. The settings, described below, determine how the relay recognizes and responds to operating conditions to protect your power apparatus equipment. Each relay is delivered with a set of parameters that are preprogrammed at the factory. All of the presettings are identified in Chapter 5, Programming the Relay. Operating settings define the conditions under which the relay will function. These include the setting of the real-time clock (time and date), choice of display language, and 2-4 July 27, 1995

17 Chapter 2 choice of the data transmission rate for the front port. The operating settings also identify what information is to be displayed in each of the two lines of the LCD for operational messages and for fault messages. The relay s Scope of Functions settings are also considered part of the operating settings. These settings indicate which functions are activated (EXIST) and deactivated (NON-EXIST). Operating settings also indicate how the optional functions automatic reclose and parameter changeover will operate. System settings identify the protected power system and switchgear. Information such as the system starpoint direction and condition, voltage transformer voltages, and current transformer rated current is required. The relay s distance protection and ground fault protection functions use this information to compute the system s protection requirements. When the parameter changeover feature is available (see section 2.5.3), system settings can vary between the parameter sets. Protection settings such as for distance protection, pilot protection, and overcurrent protection, specify the values that are used to identify fault conditions and are the majority of settings the 7SA511 relay requires. Depending on your relay model (see section 1.3.3), you may also need to indicate settings for power swing blocking protection or highresistance ground fault protection. When the parameter changeover feature is available (see section 2.5.3), protection settings can vary between the parameter sets. Relay configuration settings tell the relay how to process the input information and logically associate it with the output devices. If desired, you can reassign the binary inputs, annunciations, and the function of the relay s output signals, trip relays, and LEDs. Configuration is also referred to in this manual as programming or marshalling the relay Relay Setting Descriptions (by Address Block) Each relay input and output setting is assigned to a four-digit address number that you must access to display or change the setting. Address numbers are typically grouped in blocks according to their function. Table 2-1 describes all of the primary address blocks used in this relay. Your relay s configuration determines which addresses you will be able to access. Table SA511 Relay Primary Address Blocks. Address LCD Text Description 1000 PARAMETERS 1100 POWER SYSTEM DATA 1200 DIST. PROT. GENERAL SETTINGS 1300 DIST. PROT. INDEPEND. ZONES Program the protected system settings such as the system starpoint condition, voltage transformer data, and current transformer data. Also set the parameters for general line data. Indicate whether distance protection is on or off, program the direction of the distance protection directional elements, and set the trip delays for the fault detection zones (T4 or T5). Set the parameters for independent distance zones. Zone Z1 delay T1 Zone Z2 delay T2 Zone Z3 delay T3 July 27,

18 Product Description Address LCD Text Description 1400 DIST. PROT. Set the parameters for controlled (overreach) zones. CONTROLLED ZONES Zone Z1B delay T1B Zone Z1L delay T1L 1500 DIST. PROT. FAULT DETECTION Select the measurement control parameters for voltage-controlled overcurrent fault detection or impedance fault detection DIST. PROT. FAULT DETECTION Set the parameters for the fault detection program selected in address Also used to set all parameters for overcurrent detection only FAULT LOOP EARTHED NETWORK Set the parameters for determination of a fault loop in a grounded system 1800 FAULT LOOP NON-EARTHED NET Set the parameters for determination of a fault loop in isolated or compensated systems POWER SWING Select the type of power swing blocking protection (three options), and set the power swing polygon and vector values TELEPROTEC PERM. UNDERREACH Program the settings for pilot protection, permissive underreach transfer scheme TELEPROTEC PER. OVERREACH 2600 EMERGENCY OVERCURRENT PROT FAULT RECORDINGS Program the settings for pilot protection, permissive overreach transfer scheme. This includes setting the echo keying function on or off, the echo delay time, signal duration, and transient blocking time. Program the settings for emergency overcurrent protection, including turning the function on or off. Turn the waveform capture function on or off, select whether waveform capture is initiated by fault detection or by trip command, and indicate whether waveform records will be sent to a communications device connected to the front or to the rear port. Control the sensitivity of the measured values monitoring functions. Also program the settings for the fuse failure monitor, if used. Configure the relay for ground fault detection in systems with an isolated or compensated starpoint. Configure the relay for high-resistance ground fault protection in a grounded system. Configure directional comparison ground fault protection settings MEAS. VALUE SUPERVISION 3000 EARTH FAULT NON-EARTHED NET 3100 EARTH FAULT DIREC/NON-DIREC 3200 EARTH FAULT DIREC. COMPARISON 3300 EARTH FAULT Configure the relay for nondirectional ground fault protection. NON-DIRECTIONAL 3400 AUTO-RECLOS. Program how the auto-reclose function interacts with the protection FUNCTIONS functions, and set reclose cycle times FAULT Configure the fault location function. LOCATION 4000 TESTS 4200 DIRECTIONAL TEST Run the preprogrammed directional test of the individual measurement loops. All six measurement loops should indicate the correct direction of the load flow CB-TEST TRIP-CLOSE CYCLE 4400 CB TEST LIVE TRIP Run the preprogrammed trip-close test using the internal autoreclose function. Check the operation of the circuit breaker tripping function and the operation of the circuit breaker. This test is independent of the automatic reclose function. 2-6 July 27, 1995

19 Chapter 2 Address LCD Text Description 5000 ANNUNCIATIONS 5100 OPERATIONAL ANNUNCIATIONS Display operational and status events in chronological order beginning with the latest event. Operational messages include pickup and drop-out of enabled protections and alarms, pickup and drop-out of binary inputs, signal outputs, trips, relay diagnostics, and other relay operational information LAST FAULT Display the target history log for the most recent system fault, from fault detection until drop-out. The fault number, beginning fault time and time resolution display first, followed by the applicable annunciations. Fault annunciations are available for distance protection, emergency overcurrent protection, fault location, highresistance ground fault protection, and the internal auto-reclose function nd to LAST FAULT Display the target history log for the second to last fault. See address 5200 for available fault messages rd to LAST FAULT Display the target history log for the third to last fault. See address 5200 for available fault messages ISOLATED EARTH FLT DATA Display the annunciations generated for the last three ground faults for ungrounded systems (isolated or compensated) CB OPERAT. STATISTICS Display the circuit breaker operation statistics OPERATIONAL MEASURED VALUES Display the operational measured values, which are calculated based on the values entered for the protected system settings and on the relay rated frequency. The data displays in absolute primary values and in percent of the rated relay values. For ungrounded systems, this address displays the measured values that occurred during the last ground fault ISOL. E/F MEASURED VALUES 6000 MARSHALLING 6100 MARSHALLING Configure the binary inputs. BINARY INPUTS 6200 MARSHALLING Configure the signal relays. SIGNAL RELAYS 6300 MARSHALLING Configure the LEDs, including whether the indication is latched or LED INDICATORS unlatched MARSHALLING Configure the trip relays. TRIP RELAYS 6900 LSA CONFIGURATION Indicate whether the relay is part of a substation control system via the rear communications port OPERATING PARAMETERS Program the language selection, date format, substation identification numbers for the relay; select which operational messages to display, which fault event annunciations to display, etc SCOPE OF FUNCTIONS Indicate which protection and operating functions are available in the relay, e.g., emergency overcurrent protection, fault location detection, internal auto-reclose, etc. Also identify the rated frequency for the protected system DEVICE CONFIGURATION Program how the auto-reclose function interacts with the protection functions of the relay DEVICE CONTROL 8100 SETTING REAL TIME CLOCK Set the date and time for the real-time clock. You can also specify a difference time, which is primarily used to synchronize the relay s real-time clock with another reference. July 27,

20 Product Description Address LCD Text Description 8200 RESET Reset stored data including the LEDs, event log, and target log data PARAMETER CHANGE-OVER Select which parameter set is to be active, and copy parameter sets. 2.4 Overview of Protection Functions This section gives an overview of each of the 7SA511 relay protection functions, as listed below: Distance protection Emergency overcurrent protection Power swing protection (optional) Pilot protection Ground fault detection for ungrounded systems (optional) High-resistance ground fault protection for grounded systems (optional) Automatic reclose (optional) Distance-to-fault location You should read the relay s model number on the front of the operator panel to determine if your relay has the optional protection functions. section 1.3 in the Introduction section of this manual describes how to read and interpret the relay model number Distance Protection Distance protection is the main function of the 7SA511 relay. It is characterized by high measuring accuracy and flexible adaptation possibilities for the system characteristics. The distinguishing distance protection features of the 7SA511 relay are briefly discussed in the rest of this section. Feature Fault detection options Description Overcurrent fault detection (I ph >>). Use of this fault detection scheme depends on high short circuit currents. Voltage-controlled overcurrent (underimpedance) fault detection (V</I>). An overcurrent detection scheme in which the pickup value is voltage-controlled. The measured voltages, depending on the selected settings, may be the phase-to-ground or the phase-to-phase voltages. Polygonal impedance (dogbone) fault detection (Z<). This detection scheme uses calculated loop impedance values. 2-8 July 27, 1995

21 Chapter 2 Feature Ground fault detection Tripping characteristics and distance zones Directional measurement Trip delays Phase-selective tripping Automatic blocking of the distance protection function Fault location and clearance Description Ground faults are detected by ground current (I E )or displacement voltage (V E ). Either the impedance of the three phase-to-phase loops or three phase-to-ground loops are calculated depending on the ground fault detection. The effect of apparent impedance in unfaulted phases during ground faults is eliminated by a compensation method. The relay has polygonal tripping characteristics with separate settings for reactance and resistance. Separate settings are provided for the resistance for multi-phase and phase-to-ground faults. Five distance zones are provided, and they may be independently set in the forward direction, reverse direction, or nondirectional. Two of the zones may also be used for zone extension schemes. Directional measurement using sound phase voltages or voltage memory Seven independent trip delays are provided Phase-selective tripping is available for use with single-pole or single and three-pole automatic reclosing schemes To prevent incorrect distance measurement, automatic blocking of the distance protection function is provided following loss of measured voltages Fault location (distance-to-fault) is provided through calculation of the fault impedance. The distance-to-fault may be output in distance units (miles or kilometers), or percentage of line length. An optional parallel line compensation function is available. When a fault is detected, the relay initiates the following procedures for selective clearance of the fault: 1. Starts the delay times 2. Selects the measured values 3. Releases the impedance calculation and directional identification 4. Releases the trip command 5. Initiates other auxiliary functions 6. Indicates the faulty conductor(s) July 27,

22 Product Description Emergency Overcurrent Protection During periods when the line secondary voltage signal is not available, the relay can be used as a two-stage, definite-time, overcurrent protection device. You can also program the relay to automatically change over to the overcurrent mode for emergency service following detection of VT circuit failure. The VT failure is detected by the relay s internal monitoring and plausibility checks. External detection of VT failures may be input to the relay via a binary input Power Swing Protection (optional) Power swing protection is an optional function in 7SA511 relay models that use the polygonal impedance fault detection scheme (model number 7SA511*-**A52***1/3). There are two ways you can program the relay to respond to a detected power swing. 1. Blocking. The distance protection tripping function may be blocked for the duration of the power swing. 2. Tripping. Tripping may be initiated following the detection of a power swing outside the defined stability limits Pilot Protection The 7SA511 relay provides pilot protection for fast, selective clearance of faults over the complete line. You can choose from the following pilot protection schemes: Permissive underreach transfer tripping(putt) with nondirectional fault detection Permissive underreach transfer tripping with directional overreach zone Z1B) Permissive overreach transfer tripping (POTT)with overreach zone Z1B Directional comparison with fault detection Unblocking with zone Z1B Blocking mode with zone Z1B Directional pilot wire mode Reverse interlocking (bus protection) The pilot protection signal interface is implemented by assigning appropriate logical functions to a signal relay (transmitter) and a binary input (receiver) High-Sensitivity Ground Fault Protection for Ungrounded Systems (optional) In systems having an isolated neutral or a neutral grounded through an arc suppression coil, single-phase ground faults will not be detected by the short circuit protection function because of the minimal flow of ground fault current. The optional ground fault protection function for ungrounded systems recognizes, and when possible, locates the fault. Ground fault protection for ungrounded systems (relay models 7SA511*-**A5*-1***) includes the following functions. The relay detects (picks up) the ground fault by monitoring the displacement voltage. By measuring the phase-to-ground voltages, the relay determines the faulted phase. The direction of the ground fault (residual) current is determined by high accuracy, real, and apparent component measurement July 27, 1995

23 Chapter High-Resistance Ground Fault Protection (optional) High-resistance ground fault protection is another optional feature of the relay (models 7SA511*- **A5*-0/2**2/3) that is used for detection of ground faults in grounded systems where the fault path resistance can be extremely high (e.g., overhead lines without lightning protection conductors, or ground paths in sandy soils). In such cases, overcurrent and underimpedance elements do not always pick up, so phase selection for the distance measurement is not possible. You can select the high-resistance ground fault protection function to work in one of two ways: directional or nondirectional protection. Directional ground fault protection (definite time, overcurrent protection) incorporates nondirectional backup and standby protection. This function can be extended by integrated directional comparison logic so a carrier channel can be used for fast, selective tripping for high-resistance ground faults. Nondirectional fault detection using inverse time overcurrent, with adjustable characteristics, can be selected. This method is used most frequently for highly interlinked ground systems with high-resistance ground faults where the ends of the faulty line section carry the largest fault current and thus produce the shortest tripping time. When using impedance fault detection, ground fault impedances can occur which appear to lie outside the pickup characteristic of the relay. The high-resistance ground fault protection function of the 7SA511 relay also prevents this occurrence. July 27,

24 Product Description Automatic Reclose (optional) Automatic reclose (AR) is an optional relay function (relay models 7SA511*-**A5*- **B/C/F/G*). The automatic reclose function can minimize the system down time caused by temporary faults. The range of functions for automatic reclose include: Three-pole automatic reclose for all fault types Single-pole automatic reclose for single-phase faults, no reclose for multi-phase faults Single-pole automatic reclose for single-phase faults, and three-pole automatic reclose for multi-phase faults Single- or multi-shot reclose On/off control Selection of which protection elements can initiate automatic reclose Programmable reclaim time after - successful AR cycle - unsuccessful AR cycle - manual reclose of circuit breaker Integration with external automatic reclose equipment with communications via binary inputs and outputs Control of the automatic reclose function by an external protection scheme Blocking of automatic reclose - following manual reclose - on reverse direction fault detection (user-programmable) - on detection of evolving faults (user-programmable) Distance-to-Fault Location The distance-to-fault location function provides quick location of the fault point and repair of any resultant damage, which increases the availability of the line for energy transmission in the system. Distance-to-fault location is typically initiated by a trip command from the distance protection function, but it can also be initiated by a binary input. Working independently from the distance protection elements, distance-to-fault uses its own filter algorithms and measured values to recognize and locate the fault. The fault location calculation results in the following outputs: Short circuit loop from which the fault reactance is determined Reactance per phase in primary ohms Resistance per phase in primary ohms Distance to the fault in unit-of-length measure Distance to the fault in percent of total line length For accurate impedance measurements in parallel line systems, the optional ground fault detection function for parallel line compensation is required (relay models 7SA511*-**A5*-2***) July 27, 1995

25 Chapter Additional Functions and Features of the Relay The rest of this chapter gives a general description about the remaining functions and features of the 7SA511 relay, as listed below: Secured data storage Serial data ports Multiple parameter sets (optional) Secured Data Storage The 7SA511 relay provides all the data necessary to analyze the operational performance of the relay following a system fault. The recording functions, discussed below, are secured in case of a power interruption. Real-time clock. A real-time clock with battery backup may be synchronized via a binary input or through a serial data port (see section 2.5.2). All events are recorded with a date and time tag. Target history log. Operational records for the last three faults are recorded and stored in the relay s memory. These records include the fault type, interrupted current, distance-tofault, etc. Target history for ungrounded systems. Relays with the optional isolated system ground fault detection function record the details for the last three ground faults in a separate log. Tripping statistics. For each pole of a circuit breaker, it is possible to record the cumulative total of tripping operations and interrupted current Serial Data Ports A serial data port through which the relay can be programmed and operated is available on the operator panel. A second, optional port, used for data retrieval only, is available on the rear panel. In both cases, the data transmission protocol is in compliance with IEC Front Panel Port The port on the operator panel is intended to be used with a locally attached personal computer (PC). It is accessible through the 25 pin connector on the operator panel. The attached PC can run DIGSIÒ or other appropriate software to communicate and exchange information with the relay. This interface is not electrically isolated from the monitored system and conforms to the EIA RS-232-C specification. Rear Port The optional port on the rear panel of the relay is intended for remote data retrieval by a substation control system. It is available as an optical fiber or hard-wired interface (relay models 7SA511*-**A5*-*B/C**). Consult the factory for details on the use of this feature. July 27,

26 Product Description Multiple Parameter Sets (optional) Another optional feature of the 7SA511 relay is the ability to program multiple parameter sets (relay models 7SA511*-**A5*-**E/F/G*). This feature, called parameter changeover (PCO), provides four parameter sets identified as A, B, C, and D in addition to the original, default set. System settings and relay protection settings (addresses 1000 to 4000) can be uniquely defined for each parameter set. You can also copy data from one parameter set to another, including the original set. Only one parameter set is active at a time. You can change the active parameter set during relay operation (provided no protection functions are picked up) using the operator panel or through the binary inputs. If the relay is connected to a PC via the front port, you can use DIGSI software to change the active parameter set July 27, 1995

27 Acceptance Tests Acceptance Tests Table of Contents 3. Acceptance Tests Test Equipment Energizing the Relay Reading the Initial Display Verifying the Language Setting Relay Settings for Acceptance Tests Power Supply Test Metering Tests Binary Input Test LED Test Signal and Trip Relay Test Testing the Fault Detection Systems Overcurrent Fault Detection Test Voltage-Controlled Overcurrent Fault Detection Test (Optional) Impedance Fault Detection Test (optional) Testing the Distance Zones Independent Zones Z1, Z2, and Z Overreach Zones Z1B and Z1L Coordination Times Testing the Power Swing Blocking Function (Optional) Signal Transmission Test Permissive Underreach Transfer Trip (PUTT) Permissive Overreach Transfer Trip (POTT) Emergency Overcurrent Protection Test Initial Setup High-Set Overcurrent Definite Time Overcurrent Protection Overcurrent Test Procedure Isolated Ground Fault Detection Test (Optional) High-Resistance Ground Fault Protection Tests (Optional) Testing the Directional, Definite Time Ground Fault Protection Testing the Nondirectional Inverse Time Ground Fault Protection Testing the Automatic Reclose (AR) Function (Optional) End of Acceptance Testing List of Figures Figure 3-1. Voltage-Controlled Overcurrent Fault Detector Characteristic Figure 3-2. Polygonal Impedance Fault Detection Characteristic Figure 3-3. Distance Zone Characteristics July 27,

28 Acceptance Tests This page intentionally blank 3-2 July 27, 1995

29 Acceptance Tests 3. Acceptance Tests This section provides acceptance test procedures. Follow these procedures carefully to avoid possible injury and equipment damage. When testing the 7SA511 relay, you should be familiar with all applicable safety regulations from ANSI, IEC, NEC, and other pertinent standards. Be sure that you are using the correct tests for your relay configuration. If a test is not applicable to your relay model number and configuration do not attempt to perform the test. In the following chapters, the protection functions provided by the relay are referenced with the IEC designations shown in the list below. This nomenclature is used in the text, the tables and the LCD. The corresponding ANSI designations are also indicated. IEC ANSI I>> 50H/51H High-set emergency overcurrent protection element for phases I> 50/51 Definite time emergency overcurrent protection element for phases I E > 50G/51G/67G Time overcurrent element for high-resistance ground fault protection in grounded systems V E > Displacement voltage threshold for isolated ground fault detection AR 79 Automatic reclose 47 Phase sequence check 21 Distance protection with: I ph >> - Overcurrent fault detection V</I> - Voltage-controlled overcurrent fault detection Z< - Impedance fault detection 85 Pilot protection 78 Power swing/out-of-step protection For information on relay mounting and connection options, refer to the Installation section. July 27,

30 Acceptance Tests The acceptance tests described in the rest of this chapter verify the following are working: Power supply Metering capabilities Fault detection systems - Overcurrent - Voltage-controlled overcurrent (7SA511*-*CA52/3-****) - Polygonal impedance (7SA511*-*CA52-****) Distance zone schemes Pilot protection signal transmission functions Ground fault detection for ungrounded systems (7SA511*-*CA5*-1***) High-resistance ground fault protection for grounded systems (7SA511*-*CA5*-0/2**2/3) Automatic reclose (model number 7SA511*-*CA5*-**B/C/F/G*) Power swing function (model number 7SA511*-*CA52-***1/3) Binary inputs and LED operations Output contacts (signal and trip relays) 3.1 Test Equipment You will need the following items to perform the acceptance tests: DC power supply, 20W nominal minimum with a 1 millisecond peak load capability as indicated in Table 3-1. Table 3-1. Power Supply Rated Voltage (VDC) by Relay Model Number Relay Model Number Rated Voltage Inrush (peak) 7SA511*-2*A5*-**** 24/48 VDC 100 A 7SA511*-4*A5*-**** 60/110/125 VDC 50 A 7SA511*-5*A5*-**** 220/250 VDC 25 A Note: See section 1.3, Relay Model Number, for more information on how to read and interpret the relay model number. Timer with electrical start/stop contacts Multimeter DC voltage source adjustable between 0 V and 30 V Combination three-phase AC 60 Hz current and voltage source with adjustable: - Voltage between 0 V and 100 V - Current between 0 A and 20 A - Phase angle between voltage and current of 0 to 90 Note: Commercial test sets that include some or all of the above test tools are available and can be used in the following tests. 3-4 July 27, 1995

31 Acceptance Tests 3.2 Energizing the Relay DANGER Hazardous voltages in the equipment. This can cause severe personal injury and equipment damage. Testing should be performed only by qualified personnel. Follow all safety instructions contained herein. Do not insert or withdraw the module under power. Do not make wiring connections or changes under power. 1. Connect the relay to a DC power source that provides the rated relay voltage as described in Table If a protective cover is on the relay, remove the cover to access the operator panel. Refer to Installation section of this manual for step-by-step instructions on removing the relay protective cover. 3. Position the On/Off switch on the operator s panel to the On position. After energizing the relay, the green Power LED should light, and the Blocked LED will light up briefly then go out, which indicates the relay successfully completed its self-diagnostics tests. 4. Continue with section 3.2.1, Reading the Initial Display Reading the Initial Display When the relay is first energized, the text on the initial display will read as shown below: 0000z7SA511Vx.x 7SA511********** Instead of x.x appearing on the display, the relay firmware version, e.g., 2.1, will appear. The second line of the display shows the complete relay ordering number. The asterisks (*) shown here represent the characters that should appear in your relay s display. July 27,

32 Acceptance Tests Verifying the Language Setting The language setting cannot be determined from the initial display. To verify the language setting is English, follow this procedure: 1. Press the Direct Addr key. The display will appear as DIRECT ADDRESS (English) or DIREKTE ADRESSE (German) 3-6 July 27, 1995

33 Acceptance Tests If the display shows... Then... DIRECT ADDRESS the language setting is correct. You can continue to operate the relay and enter an address number, or type in 0000 and press Enter to return to the initial display. DIREKTE ADRESSE follow these steps to change the language parameter. a. Type in 7001 and press Enter z SPRACHE DEUTSCH will appear on the display. b. Press the Password key and enter password Each character ( 0 ) you type appears as symbol on the display. c. Press Enter. d. If your entry is correct, the message CW AKZEPTIERT appears on the display. Press Enter again. You return to address 7001, and the relay is in Programming mode. Go to step g. e. If your entry is not valid, the message CODEWORTEINGABE: CODEWORT FALSCH appears on the display. Begin again with step c. f. Press the No key. ENGLISH will appear on line 2 of the display. g. Press Enter to select the setting English. h. Press the key three times. The message CODEWORTBEREICH VERLASSEN? will appear on the display. i. Press the Yes key in response to the message and to save the language parameter. The NEW SETTINGS SAVED message will appear on the LCD. j. Press Enter to clear the message from the LCD and return to the initial 0000 address display. 3.3 Relay Settings for Acceptance Tests 1. Unless otherwise noted, the tests in this chapter assume that the relay presettings are used. Refer to the Setting Worksheets reference section of this manual for identification of all of the relay presettings in address number order. 2. Some tests in this chapter require you to change settings. After acceptance testing is complete, you will need to change the relay settings back to your settings. Refer to Chapter 5, Programming the Relay, for detailed instructions on how to change relay settings. 3. Using the programming procedures provided in Programming the Relay,ensure that the frequency parameter at address 7899 is set to 60 Hz. July 27,

34 Acceptance Tests Note: Inaccurate test results may indicate that the relay settings being used are incorrect. Always verify the relay settings for each test before beginning the test. If you repeatedly receive inaccurate test results and the relay settings are correct for the test, immediately contact the relay manufacturer. CAUTION Excessive test currents. Test currents larger than 4IN may damage the relay if applied continuously. Refer to the Specifications for overload ratings. CAUTION Excessive test voltage. Test voltages larger than 140 V may damage the relay if applied continuously. Refer to the Specifications for overload ratings. 3.4 Power Supply Test This procedure will check the power consumption of the 7SA511 and the alarm relay contacts. 1. Connect test equipment to the relay as indicated in the Table 3-2. Table 3-2. Power Supply Test Connections Relay Terminal Connections Test Equipment - Relay + (where applicable) - (where applicable) DC Power supply - Power input 4B1 4B2 Power Consumption Test A DC power supply is connected to the relay power input terminals. The input voltage is then varied over the allowed range and the current into the relay is checked to ensure that it is within the specified limits. 3-8 July 27, 1995

35 Acceptance Tests Test Procedure 1. Measure the input current while varying the input voltage between the limits indicated in the table below. The values should be within the Measured Current range for the corresponding entry in Table 3-3. Table 3-3. Power Consumption Test Test Voltage (V) Measured Current (A) Relay Model Number Rated Voltage Min. Max. Min. Max. 7SA511*-2*A5*-**** 24/48 V 19.2 V 56.0 V 0.12 A 0.63 A 7SA511*-4*A5*-**** 60/110/125 V 48.0 V V 0.04 A 0.25 A 7SA511*-5*A5*-**** 220/250 V V V 0.02 A 0.07 A Alarm Relay Contact Test The alarm relay contacts are tested for correct operation in both normal and failure modes. The failure mode is simulated by removing relay power. Test Procedure 1. Connect ohmmeters or other appropriate continuity checking devices to the relay terminals as indicated in the table below. 2. For the Power On/Off switch settings shown in Table 3-4 (supply or relay), the continuity reading should be as indicated. Table 3-4. Alarm Relay Contact Test Power On/Off Terminals 6A2-6A1 Terminals 6A1-6A3 Off W =0 W= On W= W=0 July 27,

36 Acceptance Tests 3.5 Metering Tests These procedures check the analog channels to the relay s microprocessor. Known values of current and voltage are connected to the current and voltage inputs, and the accuracy of the relay measurement is checked. Current and Frequency Metering Test This test uses a single-phase input and tests each current input separately. Test Procedure 1. Connect test equipment to the relay as indicated in Table 3-1. Table 3-5. Current and Frequency Metering Test Connections Relay Terminal Connections Test Equipment - Relay + (where applicable) - (where applicable) DC Power supply - Power input 4B1 4B2 1-phase current source - I L1 3A1 3A2 Notes: 1. The frequency of the test current must be the same as the relay s rated frequency (f N ), as defined at address The test current must match the relay s rated current, I N. Refer to the relay model number to determine the rated current as indicated in the following chart. Model No. 7SA5111-**A5*-**** 7SA5115-**A5*-**** IN 1 A 5 A 2. Using the operator panel, display the address corresponding to the terminal pair that has the current source connected (see Table 3-6). 3. Ensure that the displayed percentage is within the tolerance indicated in Table Move the current source to the next pair of terminals indicated in the table below. Repeat steps 2 through 4. Continue testing until all three pairs of current input terminals have been tested. Table 3-6. Current Metering Test Tolerance Current Input Connections Addr. No. LCD Text Min. Value Max. Value 3A1-3A2 (I L1 ) 5710 IL1[%] = 100% 98% 102% 2A1-2A2 (I L2 ) 5711 IL2[%] = 100% 98% 102% 1A1-1A2 (I L3 ) 5712 IL3[%] = 100% 98% 102% 5. Display address Ensure that the displayed value, f[%], is between 99.5% and 100.5% July 27, 1995

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear EMMS-T40013-01-4A00 SIERS Siemens integrated electrical racking system instruction manual usa.siemens.com/mvswitchgear SIERS Siemens Integrated Electrical Racking System Instruction Manual Hazardous voltages

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Using the Bitronics 70 Series to Improve Local Monitoring and Control Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application

More information

EDR-3000 Eaton Distribution Relay

EDR-3000 Eaton Distribution Relay EDR-3000 Eaton Distribution Relay Technical Data New Information Description Page 1. General Description.......................... 2 2. Applications............................... 2 3. Drilling Pattern.............................

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

750/760 Feeder Management Relay Instruction Manual

750/760 Feeder Management Relay Instruction Manual GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES BE1-50/51M TIME OVERCURRENT RELAY The BE1-50/51M Time Overcurrent Relay provides economical overload and fault protection for generators, transformers, lines and motors. ADVANTAGES Self powered from 50/60Hz

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

SIPROTEC. Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6. Preface. Introduction 1. Functions 2

SIPROTEC. Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6. Preface. Introduction 1. Functions 2 SIPROTEC Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6 V4.2 Manual Preface Introduction 1 Functions 2 Mounting and Commissioning 3 Technical Data 4 Appendix Literature Glossary

More information

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology This manual is suitable for HGM9580 bus tie bus parallel unit only. Clarification of notation used within this publication. SIGN INSTRUCTION

More information

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process Answers to Chapter 2 Review Questions 1. To accept signals from the machine or process devices and to convert them into signals that can be used by the controller 2. To convert controller signals into

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL Circuit Breaker Failure Relay Operating Principle Revision: 2 from 2005-02-25 Edition: 2005-02-25 _CBF-description_eng.doc Page 1 /14 Table of Contents: 1 GENERAL DESCRIPTION 4 2 FUNCTIONAL DESCRIPTION

More information

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL DRS-LIGHT Digital Unit Decoupling Relay Type DRS-LP824 Device Description Edition:09.05.2008 SLLR_LP824_e.doc Page 1 /10 CAUTION Installing, commissioning and operating of this product may be performed

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

Model 7705 Control Module

Model 7705 Control Module www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

BE1-BPR BREAKER PROTECTION RELAY ADVANTAGES

BE1-BPR BREAKER PROTECTION RELAY ADVANTAGES BE1-BPR BREAKER PROTECTION RELAY The BE1-BPR Breaker Protection Relay provides all the capabilities required for most breaker protection and monitoring functions. It incorporates a simple programming language

More information

FP5000. Refer to for the latest information on this constantly evolving product

FP5000. Refer to  for the latest information on this constantly evolving product FP5000 Refer to www.eatonelectrical.com for the latest information on this constantly evolving product FP5000 Product Overview Microprocessor design combines protection, metering and control into a single

More information

BITRONICS 878 DIOD Product Description BITRONICS 878 DIOD DISTRIBUTED INPUT/OUTPUT DEVICE

BITRONICS 878 DIOD Product Description BITRONICS 878 DIOD DISTRIBUTED INPUT/OUTPUT DEVICE BITRONICS 878 DIOD Product Description BITRONICS 878 DIOD DISTRIBUTED INPUT/OUTPUT DEVICE This page intentionally left blank 2 l BITRONICS 878 DIOD APPLICATION NOTE 878 Distributed Input/Output Device

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B SURGE PROTECTION PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) USER MANUAL Surge Protection Device B 01 156 9000 This Surge Protection Device is intended for professional use only Read this

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

SIPROTEC 4 7SA522 Distance Protection Relay for Transmission Lines

SIPROTEC 4 7SA522 Distance Protection Relay for Transmission Lines Distance Protection / 7SA522 SIPROTEC 4 7SA522 Distance Protection Relay for Transmission Lines Function overview Fig. /48 SIPROTEC 4 7SA522 distance protection relay LSP2309-afpen.tif Protection functions

More information

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH Industriefunkuhren Technical Manual Signal Converter for DIN Rail Mounting Series 4800xx-yy ENGLISH Version: 01.01-19.07.2007 2 / 23 Signal Converter 4800 - V01.01 INPORTANT NOTES Downloading Technical

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

output devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date:

output devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date: Class: Date: MECH1500Quiz1ReviewVersion2 True/False Indicate whether the statement is true or false. 1. The number and type of I/Os cannot be changed in a fixed PLC. 2. In a PLC system, there is a physical

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process Answers to Chapter 2 Review Questions 1. To accept signals from the machine or process devices and to convert them into signals that can be used by the controller 2. To convert controller signals into

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter 5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL 33309 3211 Fruitland Ave Los Angeles, CA 90058 SST7000 SST7100 Speed Switch / Transmitter Installation and Operation Manual Rev. C P/N145F-13112 PCO 00009270

More information

SIPROTEC. Differential Protection 7SD610. Preface. Table of Contents. Introduction 1. Functions 2. Installation and Commissioning 3 V4.

SIPROTEC. Differential Protection 7SD610. Preface. Table of Contents. Introduction 1. Functions 2. Installation and Commissioning 3 V4. Preface i SIPROTEC Differential Protection 7SD610 V4.2 Manual Table of Contents Introduction 1 Functions 2 Installation and Commissioning 3 Technical Data 4 Appendix v A Index Liability statement We have

More information

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations 2008 Many Changes in IEEE C37.2 IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations Major revisions first since 1995 Substantial additions 1 - New ten more

More information

THE INTEGRATED TESTING SOLUTION

THE INTEGRATED TESTING SOLUTION Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters THE INTEGRATED TESTING SOLUTION

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual Overcurrent and Earth-Fault Relay MRS75094-MUM Issued: 4.09.998 Version: D/4..2005 Overcurrent and Earth-Fault Relay Contents. About this manual...5.. Copyrights...5.2. Trademarks...5.3. Guarantee...5.4.

More information

SIPROTEC 4 7SD52/53 Multi-End Differential and Distance Protection in One Relay

SIPROTEC 4 7SD52/53 Multi-End Differential and Distance Protection in One Relay SIPROTEC 4 SD52/53 Multi-End Differential and Distance Protection in One Relay Function overview LSP213f.eps Fig. /41 SIPROTEC 4 SD52/53 differential protection relay Description The SD52/53 relay provides

More information

RMS Product Presentation

RMS Product Presentation RMS Product Presentation THE RELAY SPECIALISTS relay monitoring systems pty ltd www.rmpl.com.au Relay Monitoring Systems Pty Ltd 6 Anzed Court - Melbourne - Australia Manufacturing in Australia Company

More information

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 PC83 and PC830 series devices are designed to perform the relay protection functions and 6-154 kv networks automation, have different functionality

More information

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016 Interface Definition RISH EM 2340/1320/30/40 1 2-60-006-00-00494_Rev. D - 8/2016 2 Section DIGITAL MULTIFUNCTION INSTRUMENT Contents 1. Introduction Programmable Multi-function Energy Meter Installation

More information

DRTS 33. The new generation of advanced three phase relay test set

DRTS 33. The new generation of advanced three phase relay test set The new generation of advanced three phase relay test set Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Local control with color display Simultaneously available:

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS MAINTENANCE MANUAL EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS SPECIFICATIONS*... 2 INTRODUCTION... 3 DESCRIPTION...

More information

(1) Description of Operation 7SR224 Recloser Controller

(1) Description of Operation 7SR224 Recloser Controller (1) Description of Operation 7SR224 Recloser Controller DOCUMENTATION SET This document is part of a set. The full list of documents in the set, and the publication numbers under which they can be ordered,

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

7SR11 and 7SR12 Description of Operation

7SR11 and 7SR12 Description of Operation 7SR11 and 7SR12 Description of Operation Document Release History This document is issue 2012/02. The list of revisions up to and including this issue is: 2012/02 AC auxiliary power supply added 2012/01

More information

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318 ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16

More information

SIPROTEC 4 7SD61 Differential Protection Relay for Two Line Ends

SIPROTEC 4 7SD61 Differential Protection Relay for Two Line Ends Line Differential Protection / SD61 SIPROTEC 4 SD61 Differential Protection Relay for Two Line Ends Description The SD610 relay is a differential protection relay suitable for all types of applications

More information

Built for speed, security, and simplicity

Built for speed, security, and simplicity Time-Domain Line Protection Built for speed, security, and simplicity Traveling-wave-based and incremental-quantity-based line protection schemes as fast as ms with traditional pilot channels and over

More information

User s Guide REXA 103. General. 1MRK UEN Replaces UG E Version 1 August ABB Network Partner AB

User s Guide REXA 103. General. 1MRK UEN Replaces UG E Version 1 August ABB Network Partner AB User s Guide 1MRK 510 014-UEN Replaces UG03-8019E One to four shots, three-phase reclosing relay for transmission and subtransmission lines General Automatic high speed or delayed breaker reclosing after

More information

(1) Description of Operation. Autoreclose. 7SR224 Recloser Controller. (1) Description of Operation 7SR224 Appendix 2) Single/Triple Autoreclose

(1) Description of Operation. Autoreclose. 7SR224 Recloser Controller. (1) Description of Operation 7SR224 Appendix 2) Single/Triple Autoreclose (1) Description of Operation 7SR224 Appendix 2) Single/Triple Autoreclose (1) Description of Operation Appendix 2): 7SR224 Recloser Controller Single/Triple Autoreclose The copyright and other intellectual

More information

FP-5000 Feeder Protection

FP-5000 Feeder Protection Effective: April 2001 Page 1 New Information FP-00 Feeder Protection Contents Description Page FP-00 Description......... 2 Application Description...... 2 Features, Functions and Benefits..............

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Reyrolle Protection Devices 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Siemens Protection Devices Limited 2 7SR10 Argus Contents Contents Technical Manual Chapters 1. Description of Operation

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

ISGS. Intelligent SwitchGear System The Flexible Solution

ISGS. Intelligent SwitchGear System The Flexible Solution TM ISGS Intelligent SwitchGear System The Flexible Solution Multi-Function Flexibility At The Touch Of A Key Siemens introduces the ISGS Intelligent SwitchGear System a remarkable new development in switchgear

More information

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

SED2 Variable Frequency Drives with Electronic (E) Bypass Options SED2 Variable Frequency Drives with Electronic (E) Options Description The E- Options are companion packages for the family of SED2 Variable Frequency Drives (s). For information on the family of SED2

More information

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH) Surge-Trap STZ-R series Surge Protective Device (SPD) Danger Hazard of Electrical Shock, Explosion or Arc Flash Only qualified licensed electricians should install or service SPDs Verify that all power

More information

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager ABB Oy Distribution Automation Prashant Ganoo Regional Product Marketing Manager Feeder Protection REF615 Ver. 1.1 Technical Presentation 9/26/2008-1 - 1MRS756407 C Self Introduction Prashant Ganoo B.E.(ELECT),

More information

Power Xpert Meter 350 (PXM350) three-phased DIN-rail multifunction meter

Power Xpert Meter 350 (PXM350) three-phased DIN-rail multifunction meter Contents Description Page Product overview.... 2 Key features.... 2 Wide voltage range.... 2 Ordering information... 2 Additional features.... 2 functions comparison... 3 Metering.... 4 Specifications....

More information

Testing Instruments Manufactured by

Testing Instruments Manufactured by Circuit Breaker Dynamic Contact Resistance Meter HISAC Ultima Circuit Breaker Dynamic Test Set with up to Six Channel Dynamic Contact Resistance Meter 24 Binary Channels (4 Main + 4 PIR per Pole, 3 Poles

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

MRI1-IU - Voltage controlled time overcurrent relay

MRI1-IU - Voltage controlled time overcurrent relay MRI1-IU - Voltage controlled time overcurrent relay Contents 1 Introduction and application 2 Features and characteristics 3 Design 3.1 Connections 3.1.1 Analog input circuits 3.1.2 Output relays 3.1.3

More information

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics SIA-C Overcurrent and Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered Main characteristics The SIA-C is a overcurrent protection relay with self powered and dual powered (self

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.

More information

INSTRUCTION MANUAL FOR BREAKER FAILURE RELAY BE1-50BF. BE1-50BF BREAKER FAILURE RELAY Style No. XXX XXX XXXXX Serial No. HXXXXXXX

INSTRUCTION MANUAL FOR BREAKER FAILURE RELAY BE1-50BF. BE1-50BF BREAKER FAILURE RELAY Style No. XXX XXX XXXXX Serial No. HXXXXXXX INSTRUCTION MANUAL FOR BREAKER FAILURE RELAY BE1-50BF BE1-50BF BREAKER FAILURE RELAY Style No. XXX XXX XXXXX Serial No. HXXXXXXX P0048-40 Publication: 9190600990 Revision: G 01/10 *9190600990* INTRODUCTION

More information

high RESISTANCE STOPLIGHT Instruction Manual C-101EM

high RESISTANCE STOPLIGHT Instruction Manual C-101EM stoplight high RESISTANCE GROUNDING SYSTEM STOPLIGHT Instruction Manual C-101EM high resistance grounding protection The StopLight system uses a unique indicator light system to provide visual detection

More information

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control Protection, Automation, and Control System Combine subcycle line protection with complete substation bay control Subcycle distance protection minimizes damage and expensive repairs on transmission lines.

More information