Interface Manual Chemical Injection System
|
|
- Garry Haynes
- 5 years ago
- Views:
Transcription
1 1 Interface Manual Chemical Injection System SignalFire Numbers: CIJ-xLine (Local Modbus control) CIJ-xLine-Wireless (SignalFire radio) SignalFire Chemical Injection Controller Module The SignalFire Chemical Injection System (CIS) consists of the following: - SignalFire chemical injection controller in NEMA enclosure - Pre-assembled calibration and monitoring unit. Includes solenoid valve, calibration tube, and pressure sensor
2 2 SignalFire Chemical Injection System Diagram
3 Specifications 3 Power VDC (25mA average at 12V no outputs energized) Operating Temperature -40 C to +80 C Analog Inputs 0-10V max, 0-24mA max DC Output Drivers 12/24VDC, 12A max Pressure Sensor 1-5V interface, 0 to 48 H2O Solenoid Valve 12VDC Coil Radio Frequency MHz ISM band, FHSS radio, SMA connector
4 4 Connections and Components The Chemical Injection System provides screw terminals and terminal blocks for connections to the pump motor, solenoid valve, and pressure sensor. Power must be provided through the fused (15A) terminal block (10-30VDC, 12VDC nominal). The controller is designed to run standard 12VDC injection pumps that are controlled in an on/off manner. The antenna port is a standard SMA connector. Connect this port to a suitable 900MHz antenna. Installation The calibration and monitoring unit must be installed between the output of the tank and the input of the chemical injection pump. It must be installed so that the solenoid valve end is connected to the tank. All fittings are ½ NPT and a union is included to make installation easy. Care must be taken to ensure that the calibration tube is vertical to ensure accurate results. Mount the NEMA enclosure containing the chemical injection controller in a suitable location. Connect the solenoid valve, pressure sensor, and injection pump per the wiring diagram on the following page. Connect power to the system.
5 Wiring TERMINALS 5 12V TERMINALS FUSE - - Valve Motor + + VALVE 2 LED BATTERY VALVE+ BATTERY VALVE 1 LED RS232 CONFIG PORT VALVE+ PUMP 2 LED PUMP+ BATTERY Pressure Sensor 12V Valve 1 Valve 2 Chemical Injection Controller SIGNALFIRE wireless telemetry P Sensor IN Signal Power Ground STATUS LED PUMP+ BATTERY PUMP 1 LED TX LED RX LED Pump 1 Pump 2 ANALOG OUT DIG IN AUX OUTPUTS MODBUS RS485 POWER INPUT OUT2 BAT OUT1 BAT DIN2 DIN1 AO2 AO1 AIN2 AIN1 B A B A VDC Wiring Diagram for Single Well System
6 Status LEDs 6 The Chemical Injection System module has a green status LED which blinks indicating the module is running. If a radio is installed, the status LED also indicates the signal strength between the module and the gateway. In addition there are TX/RX LEDs to indicate radio messages to/from the module. The status LED will blink once a second if it is not connected to a gateway. If the module is connected to a gateway, it will blink a link quality code every 3 seconds. 3 Blinks = Strong Signal 2 Blinks = Good Signal 1 Blink = Weak Signal Each output driver also has a green LED which turns on while the relay is energized.
7 Operation The Chemical Injection System will do the following: - Report tank level - Automatically energize injection pump for configured/set amount of time - Slave chemical dosing rate to well production rate in automatic mode - Auto-calibrate the pump and report the calibration results - Report system parameters via a wireless link to the gateway or over a local RS485 Modbus connection - Real time clock for setting and measuring dosing amount over a contract 24-hour period - Automatic pump shut off on low fluid level ( < 2 in tank) 7 All configuration items may be set locally into the controller via RS485 Modbus RTU or over the wireless link from a PLC (or Totalflow, CygNet, etc.) for maximum flexibility.
8 8 Configuration Basic Configuration For the system to operate some basic configuration must be done at installation time. All configuration is done using the SignalFire ToolKit For accurate tank level measurements and calculated fluid volume pumped it is important to enter the specific gravity of the chemical being used. In addition if the pressure sensor is located above or below the bottom of the tank enter a sensor physical offset. For example of the sensor is located 6 below the bottom of the tank you would enter an offset of -6. A sensor mounted above the bottom of the tank would have a positive offset. The default pressure range of 0 to 48 is correct for the pressure sensor provided. The calibration tube diameter is 0.555, this is also pre-configured. The Modbus Slave ID must be configured to a unique address for use either with the SignalFire radio or for local Modbus control. In addition if the SignalFire radio is used the Radio Network and Radio Network Group must be set to match the SignalFire Gateway s settings.
9 The Chemical Injection System has 4 operational modes, listed below. Disabled The pump will be forced off and the valve will remain open (not energized). The system will ignore any commands to control the pump or the valve. 9 Manual In Manual Mode the pump and valve may be controlled either through the Toolkit (via a local connection) or remotely (via Modbus coil writes) through the gateway. This is the only mode that allows manual control. Calibrations can be initiated by the Toolkit or a Modbus coil write from the gateway only. Timed In timed mode, the pump will run based on the configured pump-on-time and pump-interval. In addition, automatic calibration will run if the calibration interval is a non-zero value. The pump-ontime range is 1 to 15 seconds and the pump-interval range is 30 to 180 seconds. Automatic In automatic mode, the pump-on-time and the pump-interval are automatically calculated based on the configured production rate, dosing PPM, and pump constant. Automatic calibration will run if the calibration interval is a non-zero value. In addition to properly configuring the level and sight tube ID parameters, automatic mode also requires the production rate and dosing PPM to be configured. At least one manual calibration must be performed so the Chemical Injection System has a valid calculated pump constant. In automatic mode the valid pumping times range from 2 seconds every 3 minutes to 15 seconds every 30 seconds. These are automatically calculated based on the pump calibration constant, the PPM dosing rate and the production rate. The pump time will automatically adjust if any of these three parameters change.
10 10 Calibration The automatic calibration takes place in the normal pumping schedule, that is, it does not pump chemical solely for the purpose of calibration. When the calibration interval is hit the system will close the solenoid valve for its normal pump on time and measure the volume pumped from the sight tube. The valve will then be opened until the next pump-on-time. This will repeat for the configured calibration run cycles. The calibration run cycles should be configured between 4 and 10 so that a large enough sample size is averaged for accurate calibration (the default is 5). Since the calibration is done in the normal pumping schedule it is possible to run the calibration often (once an hour) so that any voltage swing in the batteries due to solar charging/discharging is accounted for.
11 Error Status The status of the Chemical Injection System will be reported in register This register contains a bit masked set of error bits defined below. More than one error can occur at a 11 time. For example if a calibration fails the 0x01 bit will be set in addition to the reason the calibration failed. Bit Position Error Description 0x01 Latest calibration failed 0x02 Fluid in sight tube dropped below 2 during calibration 0x04 Failed to move > 2 of fluid in sight tube during calibration 0x08 Calibration configuration error, sight tube or calibration run cycles invalid 0x10 Low tank error. Tank level is < 2. Injection stopped 0x20 Over dosing error. Automatic calculated dose rate > 50% 0x40 Under dosing error. Automatic calculated dose rate < 1sec/3minutes 0x80 Configuration error. Parameter out of range. 0x100 Pump not calibrated. Calibration must be run for automatic mode operation
12 12 Modbus Register Mapping Register Address Coils (0xxxx) Register Number Description Data Type Pump energize Used in manual mode only Coil Valve energize Used in manual mode only Coil Aux. energize Used in any mode Coil Force Calibration Used in any mode Coil 05 Function Codes Operation Mode. 0 = disabled, 1 = manual, 2 = timed, 3 = auto Int 03, 04, 06, Pump on time (seconds) used in timed mode Int 03, 04, 06, Pump on interval (seconds) used in timed mode Int 03, 04, 06, Production Rate (barrels/hour) used in auto mode Int 03, 04, 06, Dosing Amount (PPM) used in auto mode Int 03, 04, 06, Error Status Bits (0 = no errors, 1 = calibration failed) Int 03, Calculated Automatic Pump on time (seconds 10) Int 03, Calculated Automatic Pump on interval (seconds 10) Int 03, Hours since last calibration Int 03, Internal temperature ( C) Int 03, Analog Input Value (μa) Int 03, Analog Input Value (mv) Int 03, Depth of fluid (inches) (high word) Float 03, Depth of fluid (inches) (low word) Float 03, Analog Input Scaled Reading (in. H 20) (high word) Float 03, Analog Input Scaled Reading (in. H 20) (low word) Float 03, Volume of fluid in tank (quarts) (high word) (Not Implemented) Float 03, Volume of fluid in tank (quarts) (low word) (Not Implemented) Float 03, Amount pumped this contract period (quarts) (high word) Float 03, Amount pumped this contract period (quarts) (low word) Float 03, Amount pumped previous contract period (quarts) (high word) Float 03, Amount pumped previous contract period (quarts) (low word) Float 03, Pump Relay state (1 = energized, 0 = de-energized) Int 03, Valve Relay state (1 = energized, 0 = de-energized) Int 03, Aux. Relay state (1 = energized, 0 = de-energized) Int 03, Pump Calibration Status (0 = not in cal, 1 = cal in process) Int 03, Auto-calibration interval (0 = disabled, hours) Int 03, 04, 06, Calibration run cycles (0 = disabled) (4 to 10 is valid) Int 03, 04, 06, Current Month (1-12) Int 03, 04, 06, Current Day (1-31) Int 03, 04, 06, Current Year (0 99, 0 = 2000) Int 03, 04, 06, Current Day of Week (0-6, 0 = Sunday) Int 03, 04, 06, Current Hour (0 23) Int 03, 04, 06, Current Minute (0 59) Int 03, 04, 06, Current Second (0 59) Int 03, 04, 06, 16
13 Start of Contract Period, Hour (0 23) Int 03, 04, 06, Start of Contract Period, Minute (0 59) Int 03, 04, 06, Asset ID Register 1 Int 03, 04, 06, Asset ID Register 2 Int 03, 04, 06, Asset ID Register 3 Int 03, 04, 06, Asset ID Register 4 Int 03, 04, 06, Asset ID Register 5 Int 03, 04, 06, Asset ID Register 6 Int 03, 04, 06, Asset ID Register 7 Int 03, 04, 06, Asset ID Register 8 Int 03, 04, 06, Calculated Pump Constant (quarts/hour 100) Int 03, Specific gravity ( 100) Int 03, 04, 06, Sight Tube diameter (ID in inches 1000) Int 03, 04, 06, Analog Input Scale Low ( 100) Int 03, 04, 06, Analog Input Scale High ( 100) Int 03, 04, 06, Sensor Physical Offset (inches 100) Signed Int 03, 04, 06, Calculated Pump Constant (quarts/hour) Float 03, Specific gravity Float 03, 04, Sight Tube diameter (ID in inches) Float 03, 04, Analog Input Scale Low (signed int, ex. 0 psi) Float 03, 04, Analog Input Scale High (signed int, 30 psi) Float 03, 04, Sensor Physical Offset (inches) (-36 to +36) Float 03, 04, Major revision number for the mainboard Int 03, Minor revision number for the mainboard Int 03, Major revision number for the radio Int 03, Minor revision number for the radio Int 03, High 16 bits of SFTS node address Int 03, Low 16 bits of SFTS node address (the radio ID) Int 03, Slave ID readback Int 03, Received signal strength of last packet from the slave Signed Int 03, Supply voltage of the CI controller, in millivolts Int 03, Minutes until the slave will time out, unless new data is received Int 03, Number of registers cached for this slave device Int 03, Remote device type Int 03, 04
WIRELESS REMOTE ASSET MONITORING & CONTROL
WIRELESS REMOTE ASSET MONITORING & CONTROL www.signal-fire.com info@signal-fire.com 978.212.2868 SIGNALFIRE TOOL KIT Free, easy to use PC configuration and diagnostics software. Supports wireless configuration
More informationWireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:
Wireless Transducer INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 2 Revision
More informationINSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.
INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,
More informationTRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND
OleumTechTM TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND MUST BE FAMILIAR WITH LEVEL 1 TRAINING MATERIALS BEFORE MOVING FORWARD Doc ID# 80-6010-001b TABLE OF CONTENTS 1. WHAT IS NEW WRITE IMPORT
More informationw w w. z i g s e n s e. c o m. a u
ZigSense is a line of low power wireless sensors utilizing ZigBee mesh network technology as its core communication channel. ZigSense systems contain a self healing network of wireless sensors designed
More informationProduct description for ED1600 generic Sigfox Module
Product description for ED1600 generic Sigfox Module The ED1600 Sigfox Module is mainly developed for container tracking purposes. To avoid the development of many different types of modules and just as
More informationMMT330 Series Moisture and Temperature Transmitters for Oil
MMT330 Series Moisture and Temperature Transmitters for Oil Features Continuous online measurement of moisture in oil Ball-valve installation no need to shut down the process or drain the oil Proven Vaisala
More informationMODEL SIB-V245 / V453
WILKERSON INSTRUMENT CO., INC INSTALLATION & OPERATION MANUAL SCADA INTERFACE BOARD MODEL SIB-V245 / V453 FOR MOTOROLA ACE3600 MIXED I/O MODULE RoHS Compliant UL/cUL Recognized Motorola is a registered
More informationSidewinder Pumps Inc. AC C1D2 Timer/Controller
Sidewinder Pumps Inc. AC C1D2 Timer/Controller Page 1 of 14 Rev 4/26/17 Table of Contents 1. Warnings --------------------------------------------------------------------------------------------------
More informationElectronic Control Options for Automatic Control Valves. Jody Malo Singer Valve
Electronic Control Options for Automatic Control Valves Jody Malo Singer Valve Control Chamber Restriction Manual Ball Valve Inlet Outlet Advantages: No power required Ease of use Been used for 80+ years
More informationJT400 Multivariable Transmitter
Product Specification Sheet JT400 Multivariable Transmitter Wireless Ultra Low Power Platform with Integrated, Chart Replacement Data Logging and I/O The industry s first, ultra-low power, multivariable
More informationPCS Ferguson 8000 Series Overview Manual. The PCS Ferguson 8000 Series brand is trademarked by PCS Ferguson.
The PCS Ferguson 8000 Series brand is trademarked by PCS Ferguson. These documents and materials are copyrighted by PCS Ferguson. 2016 All rights reserved. For information contact: PCS Ferguson 3771 Eureka
More informationPF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016
PF3107-00 MODBUS REGISTER MAP v1.4 Revised TRADEMARKS AND COPYRIGHT All content is subject to copyright and may not be reproduced in any form without the express written consent of the author. 2016 Profire
More informationTable of Contents 1 ABOUT THIS GUIDE CONTACT INFORMATION ANTENNA INSTALLATION... 4
Table of Contents 1 ABOUT THIS GUIDE... 3 1.1 CONTACT INFORMATION... 3 2 ANTENNA INSTALLATION... 4 2.1 GENERAL INFORMATION... 4 2.2 SPECIFIC MOUNTING EXAMPLES... 5 2.3 CONNECTOR MOISTURE PROTECTION...
More informationInstallation and Operating Instructions
Installation and Operating Instructions Modbus Terminal Board Form MTB IOI 4-12 1.0 DESCRIPTION 1.1 The Modbus Terminal Board is an RS-485, MODBUS RTU slave board capable of reading 33 channels. The first
More informationTrident and Trident X2 Digital Process and Temperature Panel Meter
Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products
More informationSidewinder Pumps Inc. AC Timer/Controller
Sidewinder Pumps Inc. AC Timer/Controller Page 1 of 12 Rev 032417 Table of Contents 1. Warnings-------------------------------------------------------------------------------------------------- 3 1.1.
More informationWIRELESS GATEWAY DUOS
WIRELESS GATEWAY DUOS REF.: PA160410210 / PA160411910 Wireless Gateway DUOS is an easy-to-use solution specially designed to create a network of physical data monitoring, such as: temperature and relative
More information12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)
4-20 ma & Relay Output Features 4-20 ma, ± 10 V, TC & RTD Inputs 12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 24 VDC @ 200 ma Transmitter Power Supply Options Type
More information5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA UM Channel Monitor.
5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL 33309 3211 Fruitland Ave Los Angeles, CA 90058 UM-600 6-Channel Monitor Version 2 Installation and Operation Manual Rev. G P/N145F-12990 PCO 00007462 (c)
More informationPF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner
PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION Revised Last Revised by Alex Messner This page was intentionally left blank. Table of Contents 1 Overview... 2 2 User Interface... 3 2.1 LEDs... 3 2.2 Buttons...
More informationEthernet Interface Module
Interface Manual 1 Ethernet Interface Module SignalFire Number: ENET-DIN The SignalFire Ethernet Gateway has the following features: - Wide range DC power input. 6 to 36VDC - Power Over Ethernet (POE)
More informationDMT340 Series Dewpoint and Temperature Transmitters for Very Dry Conditions
www.vaisala.com DMT340 Series Dewpoint and Temperature Transmitters for Very Dry Conditions The display shows measurement trends, real-time data, and measurement history. Features/Benefits Measures dew
More informationSC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703
SC1000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 8 Revision Date: 5-16-11 STATION
More informationSelf-Powered Wireless Instrumentation
Self-Powered Wireless Instrumentation Accutech Rapid deploy wireless instrumentation solutions for telemetry and remote SCADA Cost-Effective Solutions for Challenging Applications 03 Knowledge of your
More informationNetBiter I/O Extender User Manual
User Manual Part no. 0920-9999-009 IntelliCom Innovation AB Pilefeltsgatan 73 SE-302 50 Halmstad SWEDEN Phone +46 35 17 29 90 Fax +46 35 17 29 09 email info@intellicom.se www www.intellicom.se Revision
More informationINTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx
INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box
More informationSDM-8AO. Expansion Module 8 analog outputs. Manufactured for
Version 1.0 16.05.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have
More informationIntech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.
Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-A8VI Installation Guide. The 2300 series stations are designed to
More informationD5 SERIES WIRELESS SYSTEM
Our D5 series includes a range of radio s operate in the European free-use bands that differ in the type of interfaces and that communicate with each other directly or through repeaters. Available interfaces
More informationDMT345 and DMT346 Dewpoint Transmitters
DMT345 and DMT346 Dewpoint Transmitters for High Temperature Applications Features DMT345 measures humidity at temperatures up to 180 C (356 F) DMT346 measures humidity at temperatures up to 350 C (+662
More informationLineGuard Specification Sheet Issued 8/24/10 VA Revision 0. Valve Automation
LineGuard 2300 The LineGuard 2300 Electronic linebreak detection system monitors natural gas pipeline pressure and rate of pressure drop, and can provide manual or automatic control of a single valve actuator
More informationMicro Motion Model 7950 and Model 7951 Signal Converters
Product Data Sheet PS-001316, Rev. B April 2013 Micro Motion Model 7950 and Model 7951 Signal Converters Micro Motion Model 7950 and Model 7951 signal converters are the perfect complement to Micro Motion
More informationD7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES
11/17 D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES D7000 FEATURES Complete data acquisition systems. Analog and Digital I/O models available. RJ-45 Ethernet 10/100MB interface. Modbus TCP/IP Ethernet
More informationAnalogBridge Analog transmission system
AnalogBridge Analog transmission system Enclosure showing RTU Module and optional Power supply, External Relay User Guide Revision 1.4 Wireless Solutions at Work www.orbitcoms.com Page 1 Orbit Communications
More informationSC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703
SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 10 Revision Date: 1-9-12 STATION
More informationSPX-5000 Series. Operations Manual. Suprex Reader Extender - RF Wireless Interface. RPT GHz Repeater. SPX GHz
SPX-5000 Series Operations Manual Suprex Reader Extender - RF Wireless Interface SPX-5601 2.4GHz RPT-5651 2.4GHz Repeater SPX-5521 900 Mhz IOX-7621 2.4GHz EXP-2000 SPX-6601 2.4GHz SPX-5000_MAN_082112 This
More informationDigital Level Sensor. Consistent accuracy, unparalleled reliability. Answers for energy.
Digital Level Sensor Consistent accuracy, unparalleled reliability Answers for energy. 2 Consistent accuracy Unparalleled reliability The Siemens Digital Level Sensor (DLS) is an engineered solution for
More informationElectropneumatic miniature control valves Mounting Connectors Minisolenoid valves Indicators LED seals LED Valve modules Poppet 3/2 single pilot 4/2 s
ElectroPneumatic Miniature Control Valves Order/Technical Support Tel: (800) 6773 / FAX: (800) 677386 / www.crouzetusa.com /47 Electropneumatic miniature control valves Mounting Connectors Minisolenoid
More informationSCC Inc. TS-D Series. Technical Instructions. Document No. TS-3000 March 10, Deaerator, Surge and/or Condensate Control Panel.
Deaerator, Surge and/or Condensate Control Panel March 10, 2017 Description A TS-D series control system manages lead/lag operation of an individual deaerator (DA), surge, condensate, or a combination
More informationPS-4100 POWER SUPPLY MANUAL
PS-4100 POWER SUPPLY MANUAL Manual Part Number 180-0573 December 7, 2006 TABLE OF CONTENTS TITLE PAGE Table of Contents... 2 List Of Figures... 3 1. Introduction... 4 1.0. General... 4 1.1. Features...
More informationMODEL 8000MP LEVEL SENSOR
1 MODEL 8000MP LEVEL SENSOR INSTRUCTIONS FOR INSTALLATION, OPERATION & MAINTENANCE VISIT OUR WEBSITE SIGMACONTROLS.COM 2 SERIES 8000MP LEVEL SENSOR 1. DESCRIPTION The Model 8000MP Submersible Level Sensor
More informationRS 485 Mini Modbus 1AO
RS 485 Mini Modbus 1AO Version 1.0 14/08/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained
More informationiopro Mirrored IO System
Ph: (877) 343-8467 Fax: (800) 303-5381 Email: info@ioselect.com iopro Mirrored IO System Quick Start Guide (Ver. 6) www.ioselect.com Page 1 Introduction This document will cover how to use the iopro family
More informationHigh Voltage DC Meter
High Voltage DC Meter Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications
More informationWE CONNECT REAL WORLD STRUCTURAL MONITORING SMART SENSORS SOFTWARE CLOUD WIRELESS INTERFACE TO THE
WE CONNECT REAL WORLD TO THE STRUCTURAL MONITORING SENSORS WIRELESS INTERFACE SOFTWARE CLOUD Rev.10 del 3/10/017 Redatto da: R&D e MKT Approvato da: CEO Smart structural WIRELESS Interface NI00 devices
More information21 st Century Landfill Technology: Telemetry, Automation, and Alternative Power Sources
21 st Century Landfill Technology: Telemetry, Automation, and Alternative Power Sources Automation Automation provides for the starting and stopping of the operating system without the need of additional
More informationG303 RIO (REMOTE I/O) AND LOW END RTU
G3 TECHNOLOGIES, INC. G303 RIO (REMOTE I/O) AND LOW END RTU USER DOCUMENTATION / FUNCTIONAL SPEC. Introduction: The G303 is one of several RIO (Remote I/O) products from G3 Technologies designed to fill
More informationKTA-250 Anemometer Alarm Card
Connects to Davis Instruments DS7911 Anemometer Monitor both the wind speed and direction Interface to PLCs using the Modbus protocol Communicate via RS232 or 2-wire RS485 Interface to PLCs/Instruments
More informationHIGH-VOLTAGE DC METER
HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications
More informationCircuit Breaker Sentinel (CBS) for SF 6. power circuit breakers
Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers It is widely recognized that the concept of periodic equipment maintenance
More informationFamily of Water Cut Analyzers
Phase Dynamics Technology for Precision Measurements Phase Dynamics, Inc. 1251 Columbia Drive Richardson, TX 75081 USA E-Mail sales@phasedynamics.com Tel: 972-680-1550 Fax: 972-680-3262 Family of Water
More informationVersaMax Micro and Nano Technical Product Presentation
VersaMax Nano VersaMax Micro VersaMax Micro and Nano Technical Product Presentation Outline Introduction VersaMax Micro and Nano Product Strategy Future Products Product Description VersaMax Nano VersaMax
More information6-Channel Monitor. Installation and Operation Manual
3211 Fruitland Ave Los Angeles, CA 90058 Catalyst Monitor 6-Channel Monitor Version 2 Installation and Operation Manual Rev. H P/N145F-12964 PCO - 00009743 (c) Copyright 2015, Barksdale, Inc. All Rights
More informationIntech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.
Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-RTD6 Installation Guide. The 2300 series stations are designed to
More informationSS2200 Remote Controller
SS2200 Remote Controller General Purpose, DC Voltage General The SS2200 Remote Controller is a microprocessor-based programmable controller specifically designed to control single line and dual line centralized
More informationSC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:
SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14
More informationNEMA 4X. Wireless Technologies USA Witech USA Corp
R E M OT E O D OR A N T MO NI T O RI N G S Y S T E M Wireless Technologies USA Witech USA Corp ROS ROS (Remote Odorant Monitoring System) uses a proven electrochemical odorant sensor for THT or Mercaptan
More informationINTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL
INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:
More informationSMART SHOT CONTROLLER FLUID USERS GUIDE
SMART SHOT CONTROLLER FLUID USERS GUIDE Pg. 2 SMART SHOT CONTROLLER FEATURES 3 SMART SHOT CONTROLLER FEATURES 3 SMART SHOT CONTROLLER CONFIGURATIONS 4 FLOAT/SENSOR WIRING 5 TOP AND BOTTOM FLOAT/SENSOR
More informationRN-174. WiSnap M2 Super Module. Features. Description. Applications. ~ page 1 ~ rn-174-ds v1.1 6/1/2011
WiSnap M2 Super Module Features Development board containing the RN-171 module, status LEDs, power regulator Supports chip antenna (RN-174-C), PCB Trace antenna (RN-174-P), wire antenna (RN- 174-W) and
More informationCompressor Controller MAM 890
Compressor Controller MAM 890 OPERATION MANUAL Revision 1.0 04.08.2017 Notice Please read all the operation manual before operating the set and keep this manual for further reference. Installation of MAM
More informationTABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.
DIVERSIFIED HEAT TRANSFER SERIES 700 STEAM GENERATOR CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE AT SIGMACONTROLS.COM SERIES 700 DHT STEAM GENERATOR MANUAL 042514 2 TABLE OF CONTENTS INTRODUCTION.
More informationPROFIRE PF3100 Modbus Register Map PF
PF 3100 Modbus Register Map R 0.4 PF3100 Modbus Register Map PF3107-00 solutions@profireenergy.com Page 1 of 12 Table of Contents 1. Introduction... 3 General Information... 3 Configuration... 3 Communications...
More informationSINGLE-CHANNEL PROCESS INDICATOR series 8001
SINGLE-CHANNEL PROCESS INDICATOR series 8001 Analog Inputs - all inputs available in one unit - Pt100 RTD type DIN 43 760 or GOST 6651-78 (range from 0 to +600 C) - TC type: J - range from 0 to +600 C
More informationR & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.
R & D SPECIALTIES 2004, by R & D Specialties, Inc. All Rights Reserved. No part of this document may be copied or reproduced in any form or by any means without the prior written permission of R & D Specialties.
More informationSC100 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:
SC100 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 1 Revision Date: 4-2-18
More informationSuprex RF Series CYPRESS. Operations Manual. Suprex Reader Extender - RF Wireless Interface EXP SPX Mhz SPX-5521_MAN_0316
CYPRESS Suprex RF Series Operations Manual Suprex Reader Extender - RF Wireless Interface EXP-2000 SPX-5521 900 Mhz SPX-5521_MAN_0316 Cypress Suprex SPX-5521 Series Overview This manual covers the operation
More informationSpecification Manual
Document 010-0100002 Document version C Specification Manual SCADA Platform Griffin I'Net, Inc. Page 1 System Hardware Specifications General Specifications -40 to 75 degc ambient temperature range NEMA
More informationOperating Instructions. For. Level Control Module. Model SSR 1000
Operating Instructions For Level Control Module Model SSR 1000 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions before unpacking and commissioning.
More informationST-601 Inline ClO2 Concentration Monitoring Probe Instruction Manual
Pyxis Lab, Inc. ST-601 Inline ClO2 Concentration Monitoring Probe Instruction Manual Version 1.1 Pyxis Lab, Inc. 120 Jeffrey Ave Holliston, MA 01746 USA www.pyxis-lab.com service@pyxis-lab.com 1. Introduction
More information700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL
1 700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM 700 DPC MANUAL 072114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING
More informationPOWERWISE INDAC SETUP MANUAL
POWERWISE INDAC SETUP MANUAL REVISION: 2.2 INDAC & EMONITOR GATEWAY An installation guide for the PowerWise indac. 2013 PowerWise, Inc. This manual may contain proprietary information about the product
More informationoutput devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date:
Class: Date: MECH1500Quiz1ReviewVersion2 True/False Indicate whether the statement is true or false. 1. The number and type of I/Os cannot be changed in a fixed PLC. 2. In a PLC system, there is a physical
More informationWireless Irrigation Control System
Wireless Irrigation Control System General introduction: Automated irrigation becomes a trend with the development of smart agriculture. In order to send appropriate amount water in proper time to your
More informationOutput Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W
Differential Pressure Sensor (Air) Differential pressure transmitter with 8 selectable ranges 0 to 5/10 V, 4 to 20 ma outputs and Modbus functionality. NEMA 4X / IP65 rated enclosure. For monitoring the
More informationLAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description
Description LAUREL ELECTRONICS, INC. Features Laureate Digital Panel Meter for Load Cell & Microvolt Input 20, 50, 100, 250 & 500 mv ranges Span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999
More informationINTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS
INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS SHORT FORM 2002 SERIES D1000 Intrinsically Safe Galvanic Isolators SERIES D1000, for DIN Rail Mounting, provide the most simple and cost effective
More informationPRELIMINARY MANUAL. DC8-50-V3 Current measurement system
PRELIMINARY MANUAL DC8-50-V3 Current measurement system Firmware: v4 Last update: 16.9.2016 Table of contents Purpose of DC8-50 measurement board...3 DC8-50 advantages:...3 Connecting the power...4 Power
More informationNEMA 7. Wireless Technologies USA Witech USA Corp
R E M OT E O D OR A N T MO NI T O RI N G S Y S T E M Wireless Technologies USA Witech USA Corp ROS NEMA 7 ROS (Remote Odorant Monitoring System) uses a proven electrochemical odorant sensor for THT or
More informationDC3IOB Revision User Guide Updated 3/29/10. Overview
Revision 080910 User Guide Updated 3/29/10 Overview The is a three axis DC brush motor drive with an integrated PLC. A range of motor drive currents are selectable with jumper blocks. The integrated PLC
More informationLAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description
LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process and Ratiometric Signals Features Reads process signals from ±200 mv to ±600V or ±2 ma to ±5A full scale Ratiometric mode for bridges and
More informationRS485 MODBUS Module 8AO
Version 1.3 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have
More informationScanner 2000 microefm QuickStart. Installing the Scanner Remote Mount. Direct Mount NUFLO. Part No , Rev. A
NUFLO Part No. 30165024, Rev. A Scanner 2000 microefm QuickStart Installing the Scanner 2000 H L H L Flow Direct Mount To install the Scanner 2000 microefm using a direct mount to an orifice or cone meter
More informationEE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)
is dedicated for reliable monitoring of lubrication, hydraulic and insulation oils as well as diesel fuel. In addition to highly accurate measurement of water activity (a w ) and temperature (T), calculates
More informationPC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM
PC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM Modbus is a trademark of Modicon, Inc. Manual content copyright 2015 Extreme Telematics Corporation. All Rights Reserved. Ver 3.2 10/07/15
More informationCII: Current Input, Isolated
Safety 1. Application CII Driver Card 2. Installation 2.1 Services 2.2 Driver Card Installation 2.3 Driver Wiring 3. Configuration - Operation 3.1 Diagnostics 3.2 Calibration 4. Specifications Safety Electrical
More informationWireless Dry Contact Sensor
Wireless Dry Contact Sensor General Description The Wireless Dry Contact Sensor can be used to detect contact between two wired contact points, an external mechanical switch or a contact plate. Features
More informationPDW30 Point-To-Point Wireless Bridge
PDW30 Point-To-Point Wireless Bridge WIRELESS WIreless System FEATURES Wire Replacement in a Rugged, Industrial Housing Inputs and Outputs on Both Field Units Simple to Order, Configure, & Install 1 Mile
More informationFGRIO System User Manual
FGRIO System User Manual Version 1 FGRIO Master FGRIO Slave FGR2-IO Slave FGRIO-M FGRIO-S FGR2-IOS-CE-U UL Notification: This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D
More informationLS-RDIO0808 Modbus RTU
LS-RDIO0808 Modbus RTU Contact: Sunny QQ:2690803514 Whats app: 008613826574847 Skype: lensen-tech@outlook.com Email: sunny@lensen-tech.com Web:www.lensen-tech.com Add: Xixiang, Baoan, Shenzhen, China 1.
More informationPC-3000x PC-3000xC PUMP CONTROLLER. User Manual 844-4PRIMEX ( ) WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER
PC-3000x PC-3000xC PUMP CONTROLLER User Manual WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER 844-4PRIMEX (477-4639) WWW.PRIMEXCONTROLS.COM PRIMEX TABLE OF CONTENTS Warnings... 1 Introduction and Specifications...
More informationPENKO Engineering B.V. When Weighing Counts FLEX Multi Channel Extended
SPECIFICATIONS FLEX Multi Channel For each individual weighing channel (channel 1-4) Wiring Full Wheatstone bridge with passive connections (6-wire system) Sense system Passive sense system Excitation
More informationRST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions
Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND
More informationLTM IntelliGage Series Magnetostrictive Level Transmitters
LTM IntelliGage Series Magnetostrictive Level Transmitters Next-Generation Design LTM-350 IntelliGage Magtech introduces the world s smartest magnetostrictive level transmitter the LTM-350. The LTM-350
More informationDOCUMENT NAME DATE VERSION
Programming Manual RTU300/RTU400 RTU Series DOCUMENT NAME DATE VERSION MIKRODEV_SM_RTU_PM_EN 07 / 2018 1.6 CONTENT 1 LOGIC GATE BLOCKS...10 1.1 EDGE GATE...10 1.2 NOT GATE...14 1.3 OR GATE...15 1.4 NOR
More informationSpecification Sheet For electronically commutated motors
SC-VAV-N Specification Sheet For electronically commutated motors Used in constant pressure applications The SC-EFC is designed to control exhaust air in various building applications. The system includes
More informationTechnical specification
Technical specification EXPERT i/o extension modules Version 01.00.00 23-02-2017 This manual contains technical documentation which allows for easy installation and use of the i/o extension module product
More informationMTD75 Comprehensive cooling tower controller with all the functions required for dosing and control of cooling water
MTD75 Comprehensive cooling tower controller with all the functions required for dosing and control of cooling water Features Real time clock for accurate timed dosing Water meter input for volumetric/proportional
More informationAGROWtEK Technology to Help You Grow
Specifications Weather Station Sensor & Data Logger INSTRUCTION MANUAL SXW Power 24Vdc, ~5W Max Cable Distance 1000ft Aspirator 6cfm Fan with Foam Filter Temperature Range -20-60 C Temperature Accuracy
More information