1 Dynamic State Estimation Based Protection: Laboratory Validation Paul Myrda - EPRI & A.P. Meliopoulos and G. J. Cokkinides - Georgia Tech October 21, 2014, Houston, TX

2 Contents Background and Motivation Long Term Objectives & Vision Present Relaying Technology The Setting-less Protection Approach Implementation / Examples Applications Other Benefits Substation Based State Estimation Conclusions 2

3 Background and Motivation Protective Relay Setting has become Very Complex New Power Electronic Resource Interfaces Exhibit Fault Currents Comparable to Load Currents Detection and Locating of Some Faults is Difficult leading to Gaps in Protection. No Substation Level view of Protection Modeling Errors Play a Major Role in many Control Failures Wide Area Blackouts Asset Management is Painful NERC: #1 Root Cause of System Disturbances is Protective Relaying 3

4 Long Term Objectives / Vision Objective Vision Reduce Complexity Minimize the Coordination Role of the engineer Develop New Dynamic State Estimation Protection Method Establish a GateKeeper Device Transmits the Validated Model Upstream (other substations, control center, enterprise, etc.) Develop a fully automated protection, control and operation infrastructure 4

5 Present Relaying Technology Key Features Process Bus / Station Bus / Point to Point Mimic E/M Relays More Functions Increased Complexity Protection Dependability? Protection Security? Protection Gaps? NOTE: Protection Functions and Algorithms Mimic E/M Relays. New Technology Capabilities are Grossly Underutilized 5

6 The Setting-Less Protection Method In Search of Secure Protection: Setting-less Protection can be viewed as Generalized Differential protection Analytics: Dynamic State Estimation (systematic way to determine observance of physical laws) 6

7 Setting-less Protection Approach 1. Measure/Monitor as Many Quantities as Possible and Use Dynamic State Estimation to Continuously Monitor the State (Condition, Health) of the Zone (Component) Under Protection. Identify bad data, model changes, etc. 2. Act on the Basis of the Zone (Component) State (Condition, Component Health). 3. Advantage: No need to know what is happening in the rest of the system no coordination needed. 7

8 Implementation Overview The Component is represented with a set of Differential Equations (DE) The Dynamic State Estimator fits the Streaming Data to the Dynamic Model (DE) of the Component Object Oriented Implementation 8

9 Implementation Calculation Time Typical Sampling Rates t s = 0.1 ms to 0.5 ms Challenges 1. Perform the Analytics at time less than (2t s ) 2. Robust Operation of DSE requires accurate zone model 3. GPS Synchronized Measurements simplify Dynamic State Estimation (for linear zones it becomes a direct method) Example: Data Acquisition is performed 4 ks/s Dynamic State Estimation is performed 2,000 times per sec. 9

10 Capacitor Bank JCLINE3 LOAD04 Protection Zone 115 kv, 48 MVAr capacitor bank GUNIT2 G G XFMR2L XFMR2H YJLINE1 SOURCE1 SOURCE1-T LINETEE GEN YJLINE2 CAP1 LINE CAPBNK TXFMRHIGH 1 2 External Fault Capacitor Bank Internal Fault TXFMRLOW Event A single phase to ground fault at 2.2 seconds and duration 0.5 seconds at the location designated External Fault. An internal fault in the capacitor bank occurs at 3.0 secs (fault shorted cap cans of phase C, see figure). Fault changes the net capacitance of phase C from 4.8 μf to 2.4 μf. Relay Inputs (Measurements): Voltage of phase A-G Voltage of phase B-G Voltage of phase C-G Voltage at neutral point Current of phase A Current of phase B Current of phase C 10

11 Capacitor Bank External Fault Internal Fault kv kv Actual_Measurement_Voltage_CAPBANK_A (V) Actual_Measurement_Voltage_CAPBANK_B (V) Actual_Measurement_Voltage_CAPBANK_C (V) Estimated_Actual_Measurement_Voltage_CAPBANK_A 3Φ Voltage (V) Estimated_Actual_Measurement_Voltage_CAPBANK_B (V) Estimated_Actual_Measurement_Voltage_CAPBANK_C (V) A A Actual_Measurement_Current_CAPBANK_A (A) Actual_Measurement_Current_CAPBANK_B (A) Actual_Measurement_Current_CAPBANK_C (A) Estimated_Actual_Measurement_Current_CAPBANK_A 3Φ Current (A) Estimated_Actual_Measurement_Current_CAPBANK_B (A) Estimated_Actual_Measurement_Current_CAPBANK_C (A) Confidence-Level Confidence Similar Characteristics Trip Trip Signal No Trip Trip us Execution_time_average (s) Calculation Time us March 11, :46: March 11, :46:

12 Protection of multi-section Lines Internal Fault External Fault Protection Zone 500 kv Transmission Line (indicated as Monitored Line ) Event A phase A-C fault at 0.5 secs with duration of 0.5 secs at the location indicated as External Fault. A high impedance (2 kohms) phase A-G fault at 1.3 secs, at the location indicated as Internal Fault. Relay Inputs (Measurements) Three-phase voltages at both terminals Three-phase currents at both terminals 12

13 Protection of multi-section Lines External Fault Internal Fault ka ka kv kv Actual_Measurement_Current_TABL_A (A) Actual_Measurement_Current_TABL_B (A) Actual_Measurement_Current_TABL_C (A) Estimated_Actual_Measurement_Current_TABL_A (A) Estimated_Actual_Measurement_Current_TABL_B (A) Estimated_Actual_Measurement_Current_TABL_C (A) Actual_Measurement_Voltage_TABL_A (V) Actual_Measurement_Voltage_TABL_B (V) Actual_Measurement_Voltage_TABL_C (V) Estimated_Actual_Measurement_Voltage_TABL_A (V) Estimated_Actual_Measurement_Voltage_TABL_B (V) Estimated_Actual_Measurement_Voltage_TABL_C (V) Confidence-Level Trip No Trip Trip us Execution (s) us January 25, :08: January 25, :08:

14 Protection of Saturable Core Transformers FAULT Protection Zone G 1 2 SOURCE LINE XFMRH XFMRL 1-Ph LOAD 14.4/2.2kV, 1000 kva single-phase saturable-core transformer Event Inrush Current A 800kW load is connected at 0.72 secs to the transformer (generates inrush currents). A coil to ground fault at 1.52 secs. The fault location is 5% from neutral. Internal Turn-Ground Fault Relay Inputs (Measurements) Voltages at both sides Currents at both sides Temperature measurements at selected points 14

15 Protection of Saturable Core Transformers Inrush Current Internal Fault kv Actual_Measurement_Voltage_XFMRH_A (V) Estimated_Actual_Measurement_Voltage_XFMRH_A (V) kv A Actual_Measurement_Current_XFMRH_A (A) Estimated_Actual_Measurement_Current_XFMRH_A (A) A Confidence-Level p Trip or Not Trip Setting-Less Protection - No Trip Setting-Less Protection - Trip % Differential_Operation_Index (%) Differential Protection No Trip m% Differential Protection - Trip July 14, :36: July 14, :36:

16 Setting-less Protection Applications The following application have been successfully simulated in the lab environment: Capacitor Bank Protection Transmission Line Protection Transformer Protection Doubly Fed Induction Machine Protection Saturable Core Reactor Protection Distribution Line Protection 16

17 Laboratory Implementation Experimental Setup Block Diagram Experimental Setup PC with D/A Hardware Amplifiers (3) Hardfiber (2) PCIe Cards (2) Protection PC (1) 17

18 Laboratory Results Example 18

19 Other Benefits Protection is Ubiquitous Makes Economic Sense to Use Relays for Distributed Model Data Base Capability of Perpetual Model Validation A Ubiquitous System for Perpetual Model Validation 19

20 Vision: Substation Based State Estimation Control Center State Estimation Time Phasor Domain Transition Advantages Detection of Hidden Failures Overall Model Flow Substation Automation Centralized Substation Protection Automated Protection Coordination 20

21 Summary Setting-less Protection has been proven in a lab environment in six application areas Prototype installation at NYPA under a NYSERDA grant Multiple secondary benefits Model Validation Detection of Hidden Failures Distributed State Estimation Applications 21

22 Thank You! Together... Shaping the Future of Electricity

Update on DSE-Based Protection aka: Setting-less Protection Experience with Laboratory Testing

Update on DSE-Based Protection aka: Setting-less Protection Experience with Laboratory Testing Update on DSE-Based Protection aka: Setting-less Protection Experience with Laboratory Testing Sakis Meliopoulos George Cokkinides Georgia Tech Paul Myrda EPRI San Francisco, CA, March 26-28, 2014 1 Basic

More information

Dynamic State Estimation Based Protection (a.k.a. setting-less protection)

Dynamic State Estimation Based Protection (a.k.a. setting-less protection) Dynamic State Estimation Based Protection (a.k.a. setting-less protection) Sakis Meliopoulos, Ga Tech Bruce Fardanesh & George Stefopoulos, NYPA Paul Myrda, EPRI International Synchrophasor Symposium Atlanta,

More information

The Digital Substation: resilient and Cyber Secure Protection and Control

The Digital Substation: resilient and Cyber Secure Protection and Control The Digital Substation: resilient and Cyber Secure Protection and Control Sakis Meliopoulos Georgia Institute of Technology, Atlanta, Georgia USA PSERC Webinar, November 20, 2018 1 Presentation Outline

More information

Setting-less Protection: Basic Building Block for CSP

Setting-less Protection: Basic Building Block for CSP Setting-less Protection: Basic Building Block for CSP Sakis Meliopoulos, Georgia Tech & Paul Myrda, EPRI March 26, 2015 1 Driving Forces Present Numerical relays, rely on (typically) three currents and

More information

The Substation of the Future: A Feasibility Study

The Substation of the Future: A Feasibility Study The Substation of the Future: A Feasibility Study Final Project Report Power Systems Engineering Research Center Empowering Minds to Engineer the Future Electric Energy System Substation of the Future:

More information

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS Armando Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA 99163 A reliable power system maintains frequency and voltage

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Integrated Centralized Substation Protection

Integrated Centralized Substation Protection Proceedings of the 51 st Hawaii International Conference on System Sciences 2018 Integrated Centralized Substation Protection A. P. Meliopoulos Fellow, IEEE George Cokkinides Member, IEEE Hussain F Albinali

More information

Digital Protection Past, Present, and Future

Digital Protection Past, Present, and Future Digital Protection Past, Present, and Future Eric A. Udren Quanta Technology, LLC Pittsburgh, PA Presentation for CIGRÉ Grid of the Future Symposium Boston, MA October 22, 2013 eudren@quanta-technology.com

More information

Chapter 2 State Estimation and Visualization

Chapter 2 State Estimation and Visualization Chapter 2 State Estimation and Visualization One obvious application of GPS-synchronized measurements is the dynamic monitoring of the operating conditions of the system or the dynamic state estimation

More information

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68 The Challenges and Opportunities Faced by Utilities using Modern Protection and Control Systems - Paper Unavailable Trends in Protection and Substation Automation Systems and Feed-backs from CIGRE Activities

More information

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

A Case for Multi-Function PMU

A Case for Multi-Function PMU A Case for Multi-Function PMU Harish I. Mehta Mehta Tech, Inc. www.mehtatech.com NASPI Chattanooga, TN Meeting PMU Definition PMU is generally defined as: IEEE C37.118 compliant device Time synchronized

More information

Circuit Breaker Asset Management using Intelligent Electronic Device (IED) Based Health Monitoring

Circuit Breaker Asset Management using Intelligent Electronic Device (IED) Based Health Monitoring Circuit Breaker Asset Management using Intelligent Electronic Device (IED) Based Health Monitoring Carey Schneider Mike Skidmore Zak Campbell Jason Byerly Kyle Phillips American Electric Power October

More information

Transforming the Electric Grid

Transforming the Electric Grid Transforming the Electric Grid - ORNL s role in supporting DOE s mission January 6 th, 2005 Tom King Program Manager, Power Technologies Oak Ridge National Laboratory kingtjjr@ornl.gov 865-675-4390 Office

More information

About Georgia Transmission Corporation (GTC)

About Georgia Transmission Corporation (GTC) About Georgia Transmission Corporation (GTC) Transmission-only, not-for-profit cooperative Formed in March 1997 from the restructuring of Oglethorpe Power Corporation (OPC) GTC provides network transmission

More information

Synchrophasor Technology and Systems

Synchrophasor Technology and Systems PNNL-SA-106051 Synchrophasor Technology and Systems Jeff Dagle, PE Chief Electrical Engineer and Team Lead Electricity Infrastructure Resilience Pacific Northwest National Laboratory Richland, Washington

More information

SEL Time-Domain Link (TiDL ) Technology

SEL Time-Domain Link (TiDL ) Technology SEL Time-Domain Link (TiDL ) Technology The simple, fast, and secure digital secondary system solution Increase safety by removing high-energy cables from areas where personnel typically work. Reduce the

More information

Digital Transformation of Power Delivery

Digital Transformation of Power Delivery Digital Transformation of Power Delivery Keynote Speech Professor Saifur Rahman, PhD Virginia Tech, USA IEEMA Engineer Infinite Conference, Delhi NCR, India, 14 March 2018 Traditional Electricity Delivery

More information

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage

More information

Southern Company Smart Grid

Southern Company Smart Grid Southern Company Smart Grid Smart Grid Investment Grant Update July 25, 2011 Southern Company Southern Company is one of the nations largest generators of electricity Has 4.4 million retail customers across

More information

Digital Simulator Applications in Protective Relay Testing

Digital Simulator Applications in Protective Relay Testing Digital Simulator Applications in Protective Relay Testing D. Sevcik, H. DoCarmo CenterPoint Energy Houston, TX, USA M. Kezunovic Texas A&M University College Station, TX, USA T. Popovic Test Laboratories

More information

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Using the Bitronics 70 Series to Improve Local Monitoring and Control Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application

More information

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation 111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online): 2321-0613 Comparison of Shunt Facts Devices for the Improvement of Transient Stability of Two Machine

More information

Power System Network Simulator (PSNsim)

Power System Network Simulator (PSNsim) The PSNsim is hardware simulator that simulates all parts of power system from generation to utilization. The PSNsim is a scaled down model of the real power system that provides an experimental environment

More information

UR Universal Relay Series

UR Universal Relay Series GE Digital Energy UR Universal Relay Series Revision 5.90 Release otes GE Publication umber: GER-4401 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 5.90 release that introduces

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer ECE 421 Session 12 October 05, 2017 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

Commission Testing Methods for Protection Systems

Commission Testing Methods for Protection Systems Commission Testing Methods for Protection Systems Tom Ernst GE Grid Solutions Ken Sletten Minnesota Power Abstract Commission testing should be designed to assure that the protection system is set and

More information

Uses of Operational and Non-Operational Data

Uses of Operational and Non-Operational Data Mladen Kezunovic Texas A&M University http://www.ee.tamu.edu/~pscp/index.html Uses of Operational and Non-Operational Data Research Seminar Abu Dhabi, UAE, March 8, 2007 Outline Introduction Background:

More information

SDG&E s Accomplishments and Future Plans

SDG&E s Accomplishments and Future Plans SDG&E s Accomplishments and Future Plans Tariq Raman and Subbu Sankaran San Diego Gas & Electric Work Group Meeting October 23-24, 2018 San Diego Gas & Electric San Francisco SDG&E Los Angeles San Diego

More information

Modeling and Simulation in XENDEE

Modeling and Simulation in XENDEE Modeling and Simulation in XENDEE IEEE 34 Node Test Feeder Shammya Saha Graduate Research Assistant Electrical Engineering Ira A. Fulton School of Engineering Arizona State University shammya.saha@asu.edu

More information

Advanced Protection and Control Technologies for T&D Grid Modernization

Advanced Protection and Control Technologies for T&D Grid Modernization Advanced Protection and Control Technologies for T&D Grid Modernization i-pcgrid Workshop San Francisco, CA March 31, 2016 Jeff Shiles, Principal Manager Protection & Automation Engineering Southern California

More information

Load Flow Analysis. I Objectives

Load Flow Analysis. I Objectives EE342 Electrical Power Lab Experiment PS3 Load Flow Analysis I Objectives To demonstrate load flow concepts. To study system performance under different operating conditions. To experience the real feel

More information

EFFECTS OF GIC NEUTRAL BLOCKING DEVICES (NBDs) ON TRANSMISSION LINES PROTECTION PERFORMANCE AND POTENTIAL FOR RESONANCE.

EFFECTS OF GIC NEUTRAL BLOCKING DEVICES (NBDs) ON TRANSMISSION LINES PROTECTION PERFORMANCE AND POTENTIAL FOR RESONANCE. EFFECTS OF GIC NEUTRAL BLOCKING DEVICES (NBDs) ON TRANSMISSION LINES PROTECTION PERFORMANCE AND POTENTIAL FOR RESONANCE By Haytham Saeed Ahmed H. Eltom Professor of Engineering Committee Chair Abdelrahman

More information

MM35-DIN Series for High Power Inrush Current

MM35-DIN Series for High Power Inrush Current - Series for High Power Inrush Current Applications Page 1 of 7 Call Us: 775-884- 2434 Search for: Search Home Inrush Current Sensing Thermistor Tools About Video Library Blog Contact Us Inrush Current»

More information

SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD

SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD Tejpal P. Purohit 1, Prashant K. Bhavsar 2 Department of Electrical Engineering, Government Polytechnic Palanpur,

More information

Technology Innovation Delivering Value to BPA Organized, Disciplined, Focused

Technology Innovation Delivering Value to BPA Organized, Disciplined, Focused B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Technology Innovation Delivering Value to BPA Organized, Disciplined, Focused Keeping the Lights on for the Long Term The Basics Bonneville Power

More information

Practical Backup Fault Protection with Synchrophasors

Practical Backup Fault Protection with Synchrophasors Practical Backup Fault Protection with Synchrophasors Eric A. Udren Quanta Technology, LLC Pittsburgh, PA Presentation for Celebrating the visions of Synchrophasor Pioneers: A technical symposium in honor

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

Amsterdam 27 September 2017 David MacDonald

Amsterdam 27 September 2017 David MacDonald Operations & Maintenance facilitating condition based and predictive maintenance to support cost-efficient operation and maximum life-cycle of next generation IEC 61850 systems Amsterdam 27 September 2017

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

High impedance protection relay

High impedance protection relay High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted

More information

Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations

Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations Michael. Duff City of College Station Payal Gupta, Dharmendra Prajapati, and Alex Langseth

More information

November 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer

November 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer ECE 421 Session 28 November 29, 2018 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,

More information

SDG&E EPIC Program Overview

SDG&E EPIC Program Overview SDG&E EPIC Program Overview Presented by: Frank Goodman, SDG&E i-pcgrid Workshop March 30, 2018. All copyright and trademark rights reserved. Presentation overview SDG&E overview Project lists for three

More information

Concept of Automation in Management of Electric Power Systems Richard Joseph, Nerey Mvungi

Concept of Automation in Management of Electric Power Systems Richard Joseph, Nerey Mvungi Concept of Automation in Management of Electric Power Systems Richard Joseph, Nerey Mvungi Abstract An electric power system includes a generating, a transmission, a distribution, and consumers subsystems.

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

Smart Distribution Technology

Smart Distribution Technology Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications

More information

Small Generator Interconnection Tier 4 Facilities Study Report. Completed for. ( Interconnection Customer ) A Qualifying Facility Q0662

Small Generator Interconnection Tier 4 Facilities Study Report. Completed for. ( Interconnection Customer ) A Qualifying Facility Q0662 Small Generator Interconnection Tier 4 Facilities Study Report Completed for ( Interconnection Customer ) A Qualifying Facility Q0662 Proposed Interconnection Klamath Falls-Fishhole 69 kv line at approximately

More information

LPI SG + SS480 Spark Gap Surge Filters

LPI SG + SS480 Spark Gap Surge Filters LPI SG + Spark Gap Surge Filters Features High performance surge protector for an operating voltage of 220-277Vac Encapsulated spark gap and technology capable of operation under fault /overvoltage conditions

More information

Table of Issues and Directives Project Relay Loadability: Stable Power Swings

Table of Issues and Directives Project Relay Loadability: Stable Power Swings Table of Issues and Directives Project 2010-13.3 Relay Loadability: Stable Power Swings FERC Order 733 150. We will not direct the ERO to modify PRC-023-1 to address stable power swings. However, because

More information

Multi-Vendor Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization

Multi-Vendor Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization Multi-Vendor Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization Alan Lytz System Architect PPL Electric Utilities HQ: Allentown Pennsylvania USA 1.4 million customers 80,000

More information

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer ) Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original

More information

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems By Eng. Sameh Moustafa Mohamed Abd Elgowad Elbana A thesis submitted to The Faculty

More information

Data Attack Detection and Command Authentication via Cyber Physical Comodeling

Data Attack Detection and Command Authentication via Cyber Physical Comodeling Cyber Physical Systems Security and Privacy Data Attack Detection and Command Authentication via Cyber Physical Comodeling A. P. Sakis Meliopoulos, George Cokkinides, Rui Fan, and Liangyi Sun Georgia Institute

More information

Remote Real-Time Measurements of Voltage, Current and Energy

Remote Real-Time Measurements of Voltage, Current and Energy Remote Real-Time Measurements of Voltage, Current and Energy Chris Yakymyshyn Pam Hamilton Michael Brubaker yakymyshyn@fieldmetricsinc.com 727-319-0299 Slide 1 Outline Introduction FieldMetrics (FMI) Products

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

ABB static var compensator stabilizes Namibian grid voltage

ABB static var compensator stabilizes Namibian grid voltage Power ABB static var compensator stabilizes Namibian grid voltage factor! Rolf Grünbaum, Mikael Halonen, Staffan Rudin The spectacular dune landscapes of Namibia are a key factor in the country s booming

More information

Medium Voltage Metal-Enclosed Power Capacitor Banks

Medium Voltage Metal-Enclosed Power Capacitor Banks 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Power Capacitor Banks General Northeast Power System s (NEPSI's) medium

More information

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s) A. Introduction 1. Title: Verification and Data Reporting of Generator Real and Reactive Power Capability and Synchronous Condenser Reactive Power Capability 2. Number: MOD-025-2 3. Purpose: To ensure

More information

Modular Smart Grid Power Systems Simulators (Utilities)

Modular Smart Grid Power Systems Simulators (Utilities) Modular Smart Grid Power Systems Simulators (Utilities) AEL-MPSS SCADA Key features: Several Utilities and Final User options. Modular and scalable applications (from simple to advance complexity). Scalable

More information

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system SEL-451 Protection, Automation, and Bay Control System Advanced feeder protection and complete substation bay control in one economical system Customize distribution protection using multiple instantaneous,

More information

Micro physical simulation system of electric power systems

Micro physical simulation system of electric power systems International Journal of Smart Grid and Clean Energy Micro physical simulation system of electric power systems Xin Xu, Zongshuai Jin, Hengxu Zhang * Key Laboratory of Power System Intelligent Dispatch

More information

0 What: Time Synchronization, IEC Objects/IEEE C Harmonization (6.1.2, 6.2.2)

0 What: Time Synchronization, IEC Objects/IEEE C Harmonization (6.1.2, 6.2.2) 0 What: Time Synchronization, IEC 61850 Objects/IEEE C37.118 Harmonization (6.1.2, 6.2.2) 0.1 Abstract: IEC 61850 has been substantially developed for substations but is seen as a key standard for all

More information

3M Sensored Cable Accessories for Underground Medium Voltage Distribution System

3M Sensored Cable Accessories for Underground Medium Voltage Distribution System 3M Sensored Cable Accessories for Underground Medium Voltage Distribution System 3M Electronics & Energy Business 1 Introduction The focus on enhancing reliability and efficiency of the power grid has

More information

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4. Branch Procedure Document No. Issue No. : : CEOP8012 5 Approved By : Specialist Engineering NETWORK : Manager Approval Date Review Date : : 29/06/2018 29/06/2021 (Supersedes CEOP8012, Generation Connection:

More information

CMC 256plus. The High Precision Relay Test Set and Universal Calibrator

CMC 256plus. The High Precision Relay Test Set and Universal Calibrator CMC 256plus The High Precision Relay Test Set and Universal Calibrator CMC 256plus High Precision Relay Testing and The CMC 256plus is the first choice for applications requiring very high accuracy. This

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Study of Transient Stability Improvement of IEEE 9-Bus System by using SVC

Study of Transient Stability Improvement of IEEE 9-Bus System by using SVC Study of Transient Stability Improvement of IEEE 9-Bus System by using SVC Rathnasagar Rangu 1, Poonam Upadhyay 2 1 PG Student, VNR VJIET, Hyderabad, India 2 Professor, VNR VJIET, Hyderabad, India Abstract

More information

PG&E 500 kv Protection Standard Design and Development

PG&E 500 kv Protection Standard Design and Development PG&E 500 kv Protection Standard Design and Development Davis Erwin, Rafael Pineda, and Monica Anderson Pacific Gas and Electric Company Eric Udren Quanta Technology, LLC Jordan Bell and Neal Jones Schweitzer

More information

Medium Voltage Metal-Enclosed Harmonic Filter Systems

Medium Voltage Metal-Enclosed Harmonic Filter Systems 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Harmonic Filter Systems General NEPSI s armorvar, medium voltage metal-enclosed

More information

SDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager

SDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager SDG&E s EPIC Demonstration Projects on Emerging Communication Standards Frank Goodman, SDG&E EPIC Program Manager IEC 61850 Europe 2017 Conference September 26-28, 2017 2017 San Diego Gas & Electric Company.

More information

Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization with the PI System

Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization with the PI System Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization with the PI System Presented by Alan Lytz System Architect PPL Electric Utilities HQ: Allentown Pennsylvania USA 1.4 million

More information

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO PREPARED BY: System Management (WA) DOCUMENT REF: SO_OP_WA_3805 VERSION: 1.0 EFFECTIVE DATE: 13/10/2017 STATUS: DRAFT FOR CONSULTATION Approved

More information

Plats för bild på PST2291 med solpanel och en person

Plats för bild på PST2291 med solpanel och en person PST2200 POWER STATION AND TRANSMISSION LABORATORY PST2200 Power System Simulator with two generators Plats för bild på PST2291 med solpanel och en person PST2291 Solar Power Module General Introduction

More information

System Studies for American Transmission Co. s Benson Lake SVC Project

System Studies for American Transmission Co. s Benson Lake SVC Project Helping to keep the lights on, businesses running and communities strong System Studies for American Transmission Co. s Benson Lake SVC Project Adam Manty, Transmission Planning Engineer, ATC Outline Introduction

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection SOLKO-N (7S18) Feeder Differential Protection CLASSIFICATION OF UNIT TYPE POTECTION Summation Transformer, Circulating Current Protection B B 3 1 1 O O 3 1 1 SUMMATION TANSFOME SUMMATION TANSFOME O - Operating

More information

Modernizing Power Grids with Distributed Intelligence and Smart Grid-Ready Instrumentation

Modernizing Power Grids with Distributed Intelligence and Smart Grid-Ready Instrumentation 1 Modernizing Power Grids with Distributed Intelligence and Smart Grid-Ready Instrumentation Steve McAlonan, National Instruments Business Development Manager, Eastern US Energy Segment Roberto Piacentini,

More information

Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks

Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks General NEPSI's activar, Medium

More information

Transient stability of 11-bus system using SVC and improvement of voltage profile in transmission line using series compensator

Transient stability of 11-bus system using SVC and improvement of voltage profile in transmission line using series compensator American Journal of Electrical Power and Energy Systems 2014; 3(4): 76-85 Published online August 30, 2014 (http://www.sciencepublishinggroup.com/j/epes) doi: 10.11648/j.epes.20140304.12 ISSN: 2326-912X

More information

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District 5 WHAT IS A BUS? All connections are at the same voltage. WHAT IS A BUS? All

More information

Substation Secondary Asset Health Monitoring and Management System

Substation Secondary Asset Health Monitoring and Management System Substation Secondary Asset Health Monitoring and Management System Heng (Kevin) Chen and Lin Zhang Electric Power Group chen@electricpowergroup.com; zhang@electricpowergroup.com Oct. 23, 2018 Philadelphia,

More information

Phasor Technology Research Road Map to Improve Grid Reliability and Market Efficiency. Presented to TAC on April 5, 2005 and PAC on April 22, 2005

Phasor Technology Research Road Map to Improve Grid Reliability and Market Efficiency. Presented to TAC on April 5, 2005 and PAC on April 22, 2005 Phasor Technology Research Road Map to Improve Grid Reliability and Market Efficiency Presented to TAC on April 5, 2005 and PAC on April 22, 2005 Background Power Grid has evolved from a vertically integrated

More information

Automated Analysis of Digital Relay Data Based on Expert System

Automated Analysis of Digital Relay Data Based on Expert System Automated Analysis of Digital Relay Data Based on Expert System X. Luo, Student Member, IEEE, and M. Kezunovic, Fellow, IEEE Abstract Modern digital protective relays generate various files and reports

More information

T&D Technology Research Stem

T&D Technology Research Stem T&D Technology Research Stem Highlights of T&D Stem Activity (2000-2005) Mladen Kezunovic Former Stem Leader IAB Meeting Madison, June 1, 2006 1 Outline History Research Areas Projects Survey Initiatives

More information

Looking into the Future Protection, Automation and Control Systems

Looking into the Future Protection, Automation and Control Systems 1 Looking into the Future Protection, Automation and Control Systems, Power System Relaying Committee Substation Subcommittee Working Group K15 on Centralized Substation Protection and Control Presented

More information

Almas, M., Vanfretti, L. (2014) Open Source SCADA Implementation and PMU Integration for Power System Monitoring and Control Applications.

Almas, M., Vanfretti, L. (2014) Open Source SCADA Implementation and PMU Integration for Power System Monitoring and Control Applications. http://www.diva-portal.org This is the published version of a paper presented at IEEE PES GM 2014. Citation for the original published paper: Almas, M., Vanfretti, L. (2014) Open Source SCADA Implementation

More information

LPI SG + SST Spark Gap Surge Filter

LPI SG + SST Spark Gap Surge Filter LPI SG + SST Spark Gap Surge Filter Features High performance surge protector for an operating voltage of 220-240Vac Encapsulated spark gap and SST capable of sustaining fault and over-voltage conditions

More information

Geomagnetic Disturbances and High-Altitude Electromagnetic Pulse Research

Geomagnetic Disturbances and High-Altitude Electromagnetic Pulse Research Geomagnetic Disturbances and High-Altitude Electromagnetic Pulse Research Bob Arritt, Technical Executive Grid Operations and Planning, Electric Power Research Institute Grid Security Conference (GridSecCon)

More information

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus Non-conventional instrument transformers Advanced GIS substations with IEC 61850-9-2LE process bus Content Towards the digital GIS substations Optimized substation design NCIT for gas-insulated switchgears

More information

Wide Area Monitoring and Control

Wide Area Monitoring and Control Wide Area Monitoring and Control Schweitzer Engineering Laboratories André du Plessis Copyright SEL 2015 SEL Headquarters: WA US Manufacturing: ID, IL, WA Invent, Design, Build, and Support the Systems

More information