Surge Protection for Data & Signal Line Systems

Size: px
Start display at page:

Download "Surge Protection for Data & Signal Line Systems"

Transcription

1 Surge Protection for Data & Signal Line Systems 2016 CATALOG

2 About aycap aycap was founded in 1987 with a vision of creating and providing solutions that protect the world s infrastructures. From telecommunications to new and traditional energy networks, and from transportation systems to industrial applications of all types, aycap is there with solutions to ensure equipment uptime in spite of harsh electrical environments. The company strives to keep its customers sophisticated, mission-critical equipment running seamlessly and continuously, and is driven to make ongoing advancements in its surge protection technologies and product offerings. In October 2015 aycap acquired surge protection manufacturer and innovator Iskra Zaščite in Ljubljana Slovenia. Iskra Zaščite is a company with a long history of serving customers worldwide with best in class DIN rail surge protection solutions. Pairing Iskra Zaščite s wide product line with aycap s innovative Strikesorb technology and unmatched customer support culture offers aycap customers worldwide more complete solutions across applications in the industrial, telecommunications, transportation, and energy sectors.

3 Table of Contents Introduction 2 egulatory Standards 3 Quick Product Selection 4 Surge Protective Devices for Data & Signal Lines 13 Surge Protective Devices for Explosive Environments (Ex) 53 Surge Protective Devices for DC Power Systems 59 Surge Protective Devices for Local Area Networks (LAN) 65 Surge Protective Devices for Data Protocol 75 Various Data Surge Protective Devices 79 Surge Protective Devices for Coaxial/F Systems 85 Selection Guide 110 Typical Applications 113 Product Index 117 Table of Contents 1

4 Introduction Selection Table for ecommended Surge Protective Devices (SPDs) ecommended SPDs for use in zone interfaces according to IEC and IEC , based on correlation between standards IEC and IEC Lightning Protection Zones Test Class of SPD to IEC Category of SPD to IEC /1 Test Class 1 D1 1/2 Test Class 2 C2 2/3 Test Class 3 C1 Typical Components Used in SPDs Voltage-limiting and Current Limiting Devices Voltage-clamping Devices Varistor (MOV) A varistor is a bipolar, non-linear resistor with symmetrical voltage-current characteristics, where the resistance decreases with increasing characteristic curve. Transient Voltage Suppression (TVS) Diode A TVS diode is a clamping device that limits voltage spikes by the low impedance avalanche breakdown of the P/N junction. TVS diode contains a P/N junction similar to a Zener diode but with a larger cross section, which is proportional to its surge power rating. TVS diode has a very short response time, making it suitable for limiting fast rising transient voltages. Voltage-switching Devices Gas Discharge Tube () A is an arrangement of electrodes in a gas within an insulating, temperatureresistant ceramic or glass cylinder. Because of their switching characteristic and rugged construction, s exceed other components in current carrying capability. TSS Thyristor Surge Suppressor (TSS) Fixed Voltage Types A Thyristor surge suppressor is voltage-switching device, when above a certain breakdown current, the NPNP structure regenerates and switches to a low voltage condition. The multiple PN junctions of the TSS reduce the overall capacitance. Current Limiting Devices Positive Temperature Coefficient esistor (PTC esistor) PTC resistors are ceramic components whose electrical resistance rapidly increases when a certain temperature is exceeded. An overcurrent condition causes the devices to increase their resistance, thus reducing current flow. 2 SIGNALING NETWOK SEIES

5 egulatory Standards 1 IEC :2009 (VDE ) Low voltage surge protective devices Part 21: Surge protective devices connected to telecommunications and signaling networks Performance requirements and testing methods 2 IEC :2004 Low-Voltage Surge Protective Devices Part 22: Surge protection devices connected to telecommunications and signaling networks Selection and application principles 3 IEC/EN :2011 (VDE ) 4 IEC :2008 (VDE ) 5 IEC :2001 (VDE ) Surge protective devices connected to low voltage power distribution systems equirements and test methods Surge protective devices connected to low voltage power distribution systems Selection and application principles Electrical installation of buildings Part 5-53: Selection and erection of electrical equipment-isolation, switching and control 6 IEC PAS :2004 Surge arresters Part 7: Glossary of terms and definitions from IEC publications , , , , , , , , and IEC :2005 (VDE ) 8 IEC :2010 (VDE ) 9 IEC :2010 (VDE ) 10 IEC :2010 (VDE ) 11 IEC :2010 (VDE ) Electromagnetic compatibility (EMC) Part 4-5: Testing and measurement techniques Surge immunity test Protection against lightning Part 1: General principles Protection against lightning Part 2: isk management Protection against lightning Part 3: Physical damage to structures and life hazard Protection against lightning Part 4: Electrical and electronic systems within structures 12 ITU-T K.20:2008 Protection against interferences: esistibility of telecommunication switching equipment to overvoltages and overcurrent 13 ITU-T K.21:2008 Protection against interferences: esistibility of subscriber s terminal to overvoltages and overcurrent 14 ITU-T K.44:2011 Protection against interferences: esistibility test for telecommunication equipment exposed to overvoltages and overcurrent Basic ecommendation 15 IEC :1999 (VDE ) 16 IEC :2009 (VDE ) 17 IEC :2000 (VDE ) 18 IEC 60038:2009 (VDE ) Surge arresters Part 1: Non-linear resistor type gapped surge arresters for AC systems Surge arresters Part 4: Metal-oxide surge arresters without gaps for AC systems Surge arresters Part 5: Selection and application recommendations IEC standard voltages 19 UL 497B Protectors for data communication and fire-alarm circuits 20 IEC :2010 ailway applications Insulation coordination Part 2: Overvoltages and related protection 21 EN :2012 ailway applications Fixed installations DC surge arresters and voltage limiting devices Part 1: Surge arresters 22 EN :2003 ailway applications Fixed installations DC switchgear Part 5: Surge arresters and low-voltage limiters for specific use in DC systems 23 EN :1998 ailway applications Fixed installations Part 1: Protective provisions relating to electrical safety and earthing 24 IEC :2002 Electrical installations of buildings Part 7-712: equirements for special installations or locations Solar photovoltaic (PV) power supply systems 25 HD :2005 Electrical installations of buildings Part 7-712: equirements for special installations or locations Solar photovoltaic (PV) power supply systems 26 EN 61173:2001 Overvoltage protection for photovoltaic (PV) power generating systems guide 32. SIST EN :2006/A1:2011 Wind turbines Part 1: Design requirements (IEC :2005/A1:2010) 27 IEC T :2010 Wind turbine generator systems Part 24: Lightning protection 28 EN :2013 Low-voltage surge protective devices Surge protective devices for specific application including DC Part 12: Selection and application principles SPDs connected to photovoltaic installations 29 EN :2012 Low-voltage surge protective devices - Surge protective devices for specific application including DC Part 11: equirements and tests for SPDs in photovoltaic applications 30 IEEE 802.3at Power over Ethernet enhancements Introduction & egulatory Standards 3

6 Quick Product Selector Data & Signal Lines Product Page Description Connection/Signal aydat SLH-2 SMH-TC 14 Modular universal single-pair data SPD Coarse and fine protection -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL aydat SLH-4 SMH2-TC 16 Modular universal two-pair data SPD Coarse and fine protection -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL aydat SPH-2 18 Modular universal single-pair data SPD for balanced (symmetrical) lines Coarse and fine protection -20 ma current loop -Analog telephone line -Thermal probe PT 100, TTL aydat SPH-4 20 Modular universal two-pair data SPD for balanced (symmetrical) lines Coarse and fine protection -20 ma current loop -Thermal probe PT 100, TTL aydat SGH-3 SMH-SG 22 Modular single-pair data SPD with separated signal ground (S 232) Coarse and fine protection Insulation resistance to earth -Analog telephone line -S 232, S 485 -Thermal probe PT 100 aydat SBH-3 24 Modular single-pair data SPD with separated signal ground (S 232) Coarse and fine protection Insulation resistance to earth -CAN bus -Profibus DP -S 232/v.24, S 485 -Sinec L2 aydat SSH-3 SMH-SH aydat SH-2 SMH-C aydat SUI-4 SMI2 aydat SCH-2 NMH-TC aydat SCH-4 NMH2-TC aydat STD-2 IM-TD aydat SUHI-2 VMO aydat SU-2 SMH-TD 26 Modular universal single-pair data SPD for shielded cables Coarse and fine protection 28 Modular universal single-pair data SPD with remote contacts (C) Coarse and fine protection 30 Modular 2-pair SPD for exposed line Coarse and fine protection I imp =5 ka/pair 32 Universal compact single-pair data SPD Coarse and fine protection 34 Universal compact two-pair data SPD Coarse and fine protection 36 Modular single-pair data SPD Coarse and fine protection Overcurrent protection Various options available for base unit 38 Modular single-pair SPD Coarse and fine protection Lightning impulse current I imp =5 ka/pair 40 Modular single-pair SPD Coarse protection only Coordination elements -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL -20 ma current loop -Analog telephone line -S 232, S 422, V.11, S 485 -Thermal probe PT 100, TTL -Analog telephone line 4 SIGNALING NETWOK SEIES

7 U n V DC 5, 12, 15, 24, 30, 48, 60, 110 V U c V DC 6, 15, 18, 28, 33, 52, 64, 170 V I L at 25ºC A I n 8/20 ka I max 8/20 ka I imp 10/350 ka Frequency up to Housing IP DIN MHz Modular IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Modular IP mm 30, 230 V 33, 320 V MHz Modular IP mm 30 V 33 V MHz Modular IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Modular IP mm 5, 12, 30 V 6, 15, 33 V MHz Modular IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Modular IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Modular IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Modular IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Compact IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Compact IP mm 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V 0.145, MHz Modular IP 20 1TE 5, 12, 15, 24, 30, 48, 60, 110 V 6, 15, 18, 28, 33, 52, 64, 170 V MHz Modular IP 20 1TE 110 V 170 V MHz Modular IP mm Quick Product Selector 5

8 Quick Product Selector Data & Signal Lines Product Page Description Connection/Signal aydat SU-4 SMH2-TD 42 Modular two-pair SPD Coarse protection only Coordination elements -Analog telephone line aydat SLL-4 44 Modular two-pair SPD Fine protection suppressor diode only aydat SCL-1 IM-VF 46 Compact single-pair SPD Fine protection MOV only -20 ma current loop aydat SCL-2 IM-DF 48 Compact single-pair SPD Fine protection suppressor diode only -20 ma current loop aydat SUH-2 PS SMH-TC+PS 50 Modular SPD for DC power and data line in one (CAN bus) Coarse and fine protection Overcurrent protection -DC power system + data line -CAN bus Explosive Environments aydat Ex-2 SMH-Ex 54 Modular single-pair SPD for explosive environments (Ex) Coarse and fine protection Insulation resistance to earth -Hazardous areas aydat PLP Ex 56 Compact SPD for explosive environments (Ex) Coarse and fine protection Insulation resistance to earth -Hazardous areas DC Power Systems Protec DMD 20 aydat PSH-2 aydat PSC-2 SMH-PS 60 Modular SPD for DC/AC power systems Class III/Type 3/D U oc up to 6 kv emote contacts + LED status indicator 62 Modular universal single-pair SPD Coarse and fine protection Various options available for base unit -DC power systems -DC power systems Local Area Networks (LAN) aydat NET 6 LZ-NET 6 aydat NET 5 Series LZ-NET, LZ-NET PoE, LZ-NET STP aydat NET 5 19 LZ-24NET 19, LZ-24NET 19 PoE aydat NET 5 PS ZE 200 NET 66 LAN protector (1 way) All 4 pairs protected Frequency > 250 MHz, Cat 6 capable Termination: J45, shielded 68 LAN protector 1 way All 4 pairs protected Frequency >100 MHz, Cat 5 capable Termination: J45, Cat 5 connectors 70 LAN protector 19" rack patch panel up to 24 ports All 4 pairs protected Frequency > 100 MHz, Cat 5 capable Termination: J45, Cat 5 connectors 72 Combined POWE/LAN protector All 4 pairs in the UTB protected Frequency > 100 MHz, Cat 5 capable Termination: J45, Cat 5 connectors -LAN up to Cat 6 -LAN up to Cat 5 -LAN up to Cat 5 -LAN up to Cat 5 6 SIGNALING NETWOK SEIES

9 U n V DC U c V DC I L at 25ºC A I n 8/20 ka I max 8/20 ka I imp 10/350 ka Frequency up to Housing IP DIN V 170 V MHz Modular IP mm 30 V 33 V MHz Modular IP mm 12, 24 V 22, 28 V MHz Compact IP 20 6 mm 5, 12, 24, 60 V 6, 15, 28, 64 V , 0.25, MHz Compact IP 20 6 mm 24 V 28 V MHz Modular IP mm 12, 24 V 15, 28 V MHz Compact IP 20 6 mm 24, 48, 24/5 V 33, 54, 33/7.5 V MHz In-line IP 67 1/2 24, 48, 60, 120 V 34/44, 60, 75, 150 V AC/DC 1.2, 2.5, 2.5, 4 3,6,6,10 Modular IP 20 1TE 12, 24, 48 V 15, 28, 52 V Modular IP mm 48 V 50 V (Line-Line) 10 (Lines- Ground) MHz Compact IP mm 5, 48, 5 V 6, 58, 6 V 0.3 (Line-Line) 0.06 (Line-Line) 0.3 (Line-Line) MHz Compact IP 20 5, 48 V 6, 48 V 0.3 (Line-Line) 0.06 (Line-Line) 1, MHz Compact IP 20 5 V DC 230 V AC / 50 Hz 6 V DC 275 V AC / 50 Hz 0.3 (Line-Line) 3 (L(N)-PE, L-N) 10 (L+N-PE) 100 MHz Compact IP 20 Quick Product Selector 7

10 Quick Product Selector Data Protocols Product Page Description Connection/Signal aydat S 485 VM-S Compact single-pair data SPD Coarse and fine protection -S 422 -V.11 -S 485 Various Data Systems aydat PLP 24 PLP-24V aydat GD IM-GD Coaxial & F Systems 80 Single-pair SPD for 3/4 pipe installation Coarse and fine protection t A <1ns 82 OEM PCB module Single-pair SPD Coarse protection only Flying leads or screw terminals -20 ma current loop -Analog telephone line -xdsl -EIB Product Page Description Connection/Signal aycox BNC ZV-BNC 86 Coaxial BNC protector for analog video surveillance systems Coarse and fine protection Indirect shield earthing -Arcnet -Analog video aycox IEC, F ZV-1, ZV1-F 88 Coaxial protector for TV and cable TV Direct shield earthing -TV -Cable TV aydat CP BNC CCP-BNC aydat CP 7/16 CCP 7/16 aydat CP N CCP N aydat CP N-6G CCP N-6G aydat TNC-6G CCP TNC-6G 90 Coaxial protector for F antenna systems Frequency 2.6 GHz 92 Coaxial protector for base station F antenna systems Frequency 2.5 GHz 94 Coaxial protector for F antenna systems Frequency 2.6 GHz 96 Coaxial protector for F antenna systems Frequency 6 GHz 98 Coaxial protector for F antenna systems Frequency 6 GHz -Analog video -GSM, UMTS, LTE -GPS -adio systems -GSM, UMTS, LTE -GPS -adio systems -GSM, UMTS, LTE -GPS -adio systems -GSM, UMTS, LTE -GPS -adio systems 8 SIGNALING NETWOK SEIES

11 U n V DC U c V DC I L at 25ºC A I n 8/20 ka I max 8/20 ka I imp 10/350 ka Frequency up to Housing IP 5 V 6 V MHz Compact IP 20 2TE 24 V 28 V MHz In-line IP 55 3/4" 110 V 170 V MHz Compact IP 20 U n V DC U c V DC Max Peak Power W I L at 25ºC A I n 8/20 ka I max 8/20 ka Frequency up to Termination 10, 24 V 12, 28 V MHz BNC Type M-F, F-F 48, 48 V 66, 60 V 0.1, 0.1 5, 5 10, MHz IEC TV & F 70, 180, 280 V 40, 125, 300 W GHz BNC Type M-F, F-F 70, 180, 280 V 40, 125, 300 W GHz 7/16 Type M-F 70, 180, 280 V 40, 125, 300 W GHz N Type M-F, F-F 180 V 125 W GHz N Type M-F, F-F 180 V 125 W GHz TNC Type M-F, F-F Quick Product Selector 9

12 Quick Product Selector Coaxial & F Systems Product Page Description Connection/Signal aydat CP UHF CCP UHF 100 Coaxial protector for F antenna systems Frequency 600 MHz -adio systems aydat CP F75 CCP F aydat CP TV75 CCP TV aydat CP L/4-7/16 CCP L/4-7/ Coaxial protector for F antenna CCTV and CATV systems Frequency 2 GHz 104 Coaxial protector for F antenna CCTV and CATV systems Frequency 2 GHz 106 Coaxial protector for F antenna systems Frequency MHz, GHz -Cable TV -TV -GSM, UMTS, LTE aydat CP L/4-N CCP L/4-N 108 Coaxial protector for F antenna systems Frequency MHz, GHz -GSM, UMTS, LTE 10 SIGNALING NETWOK SEIES

13 U n V DC U c V DC Max. Peak Power W 70, 180, 280 V 40, 125, 300 W I L at 25ºC A I n 8/20 ka I max 8/20 ka Frequency up to Termination MHz UHF Type M-F, F-F 70, 180 V 40, 125 W GHz F Type M-F, F-F 70, 180 V 40, 125 W GHz TV Type M-F, F-F 500 W MHz L/4-7/16 Type M-F, F-F 500 W MHz L/4-N Type M-F, F-F Quick Product Selector 11

14 12 SIGNALING NETWOK SEIES

15 Modular & Compact Surge Protective Devices (SPDs) for Data & Signal Lines aydat products are universal data surge protective devices that contain both coarse and fine over voltage stages and provide longitudinal and transverse surge protection. aydat SH-2 products feature additional remote contacts. If the unit fails, the contacts change state. aydat SSH-3 Series is equipped with additional protection for cable shield. aydat SUI-4 Series was designed to withstand greater surge level [I imp =10 ka]. aydat SLH-4 Series is a universal data surge protective device (SPD) designed to protect two independent symmetrical data lines. aydat SLH-2 aydat SLH-4 aydat SPH-2 aydat SPH-4 aydat SGH-3 aydat SBH-3 aydat SSH-3 aydat SH-2 aydat SUI-4 aydat SCH-2 aydat SCH-4 aydat STD-2 aydat SUHI-2 aydat SU-2 aydat SU-4 aydat SLL-4 aydat SCL-1 aydat SCL-2 aydat SUH-2 PS Modular & Compact SPDs for Data/Signal Lines 13

16 Modular SPD for Single Pair aydat SLH-2 Series D1 C1 C2 C3 SMH-TC Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN These efficient overvoltage barriers contain both coarse and fine protection stages and provide longitudinal and a transverse surge protection. The initial protection stage comprises a three-pole gas discharge tube and is designed to divert the primary surge energy. The subsequent fine protection stage is carried out using fast bidirectional silicon avalanche diodes. Care is taken in the design of this fine protection stage to avoid capacitive line loading and thereby ensuring a low insertion loss and wide operating frequency range. Series line impedances ensure energy coordination between the coarse and a fine protection stages at all levels of the incident surge. To protect against the hazards of electric shock and fire which often results when power frequency contact occurs between power and communication lines, often called mains incursion, a thermo-clip is included on the primary protection stage to divert the power frequency current to ground. The plug-in module/base design facilitates replacement of a failed module without the need to remove system wiring. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SLH-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (Line-Ground) 7-10 V V V V V V V V (Line-Line) 7-10 V V V V V V V V esponse Time Overvoltage Protection t A < 1 ns Thermal Protection Yes Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path Ω Transverse Capacitance C 50 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2, 2.5 mm 2 Q Version Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SLH-2-xxx SLH-2-xxxQ (Quick Connect Terminals) SLH-2-xxxM (module) SIGNALING NETWOK SEIES

17 aydat SLH-2 Series Internal Configuration TC DB Legend DB Diode Block Gas Discharge Tube PG Protective Grounding esistor TC Thermo-clip 1 3 LINE PG EQUIP 2 4 & Packaging 90 SLH-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 52 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SLH-2-xxxM Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 24 g Packaging (Single Unit) mm 15 pieces 12 Quick Connect Terminals 90 SLH-2-xxxQ Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 54 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Bases with Quick Connect Terminals enable faster installation and have built-in contacts to enhance vibration resistance. Modular & Compact SPDs for Data/Signal Lines 15

18 Modular SPD for Two Pair aydat SLH-4 Series D1 C1 C2 C3 SMH2-TC Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN Like the aydat SLH-2 Series, the SLH-4 provides the same level of protection to two independent circuit pairs. A number of protection voltages are available to ensure the user is able to select the closest clamping voltage to the normal signal operation of the equipment being protected. The plug-in module/base design facilitates replacement of a failed module without the need to remove system wiring. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SLH-4 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 2 (4 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 5 ka esidual Voltage at 5 ka (8/20 µs) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (Line-Ground) 7-10 V V V V V V V V (Line-Line) 7-10 V V V V V V V V esponse Time Overvoltage Protection t A < 1 ns Thermal Protection Yes Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path Ω Transverse Capacitance C 50 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2, 2.5 mm 2 Q Version Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SLH-4-xxx SLH-4-xxxQ (Quick Connect Terminals) SLH-4-xxxM (module) SIGNALING NETWOK SEIES

19 aydat SLH-4 Series Internal Configuration DB TC DB 1 3 TC 2 4 Legend DB Diode Block Gas Discharge Tube PG Protective Grounding esistor TC Thermo-clip PG 5 7 LINE PG EQUIP 6 8 & Packaging 90 SLH-4 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 66 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SLH-4-xxxM Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 30g Packaging (Single Unit) mm 15 pieces 12 Quick Connect Terminals 90 SLH-4-xxxQ Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 66 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Bases with Quick Connect Terminals enable faster installation and have built-in contacts to enhance vibration resistance. Modular & Compact SPDs for Data/Signal Lines 17

20 Modular SPD for Single Pair aydat SPH-2 Series D1 C1 C2 C3 IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 30, 230 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SPH-2 Series of surge protective devices has been developed to protect a single pair loop, which could be ungrounded onto data, signal and communication circuits. It is intended for those applications where high ground potential rises may frequently occur, such as in locations close to electric railways. The circuit topology consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided by a three terminal gas discharge tube while fine protection is provided using a high speed silicon avalanche diode or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Both common (longitudinal) mode and differential (transverse) mode protection is provided. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SPH-2 Series 30 V 230 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 30 V 230 V Maximum Continuous Operating Voltage (DC) U c 33 V 230 V ated Load Current at 25ºC I L 1 A 5 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 80 V < 450 V ated Spark Overvoltage (Line-Ground) V V (Line-Line) V V esponse Time Overvoltage Protection (Line-Line) t A < 1 ns < 25 ns (Line-Ground) < 100 ns Insulation esistance of the Protection (Line-Ground) iso > 1 GΩ / 100 V (Line-Line) 33 MΩ 100 MΩ Serial esistance per Path Ω Transverse Capacitance (Line-Line) C 50 pf (Line-Ground) 50 pf Cut-off Frequency f G 10 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2, 2.5 mm 2 Q Version Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 30 V 230 V SPH-2-xxx SPH-2-xxxQ (Quick Connect Terminals) SPH-2-xxxM (module) SIGNALING NETWOK SEIES

21 aydat SPH-2 Series Internal Configuration TC DB TC MOV Legend DB Diode Block Gas Discharge Tube MOV Metal Oxide Varistor PG Protective Grounding esistor TC Thermo-clip 1 3 PG LINE PG EQUIP PG LINE PG EQUIP 2 4 SPH-2 30 V SPH V & Packaging 90 SPH-2 Series 30 V 230 V Weight per Unit 60 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SPH-2-xxxM Series 30 V 230 V 45 Weight per Unit Packaging (Single Unit) 26g mm 15 pieces 12 Quick Connect Terminals 90 SPH-2-xxxQ Series 30 V 230 V Weight per Unit 62 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Bases with Quick Connect Terminals enable faster installation and have built-in contacts to enhance vibration resistance. Modular & Compact SPDs for Data/Signal Lines 19

22 Modular SPD for Two Pair aydat SPH-4 Series D1 C1 C2 C3 IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 30 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SPH-4 Series of surge protective devices has been developed to protect two pair loops, which could be ungrounded onto data, signal and communication circuits. It is intended for those applications where high ground potential rises may frequently occur, such as in locations close to electric railways. The circuit topology consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided by a three terminal gas discharge tube while fine protection is provided using a high speed silicon avalanche diode or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Both common (longitudinal) mode and differential (transverse) mode protection is provided. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SPH-4 Series 30 V Electrical Lines Protected 2 (4 Conductors) Nominal Operating Voltage (DC) U n 30 V Maximum Continuous Operating Voltage (DC) U c 33 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 5 ka esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 80 V ated Spark Overvoltage (Line-Ground) V (Line-Line) V esponse Time Overvoltage Protection (Line-Line) t A < 1 ns (Line-Ground) < 100 ns Insulation esistance of the Protection (Line-Ground) iso > 1 GΩ / 100 V (Line-Line) 33 MΩ Serial esistance per Path Ω Transverse Capacitance (Line-Line) C 50 pf (Line-Ground) 5 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2, 2.5 mm 2 Q Version Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 30 V SPH-4-xx SPH-4-xxQ (Quick Connect Terminals) SPH-4-xxM (module) SIGNALING NETWOK SEIES

23 aydat SPH-4 Series Internal Configuration DB TC DB 1 3 TC 2 4 Legend DB Diode Block Gas Discharge Tube PG Protective Grounding esistor TC Thermo-clip PG 5 7 LINE PG EQUIP 6 8 & Packaging 90 SPH-4 Series Weight per Unit DIN Packaging (Single Unit) 30 V 60 g 2/3 TE mm 15 pieces SPH-4-xxM Series 30 V 45 Weight per Unit 26g Packaging (Single Unit) mm 15 pieces 12 Quick Connect Terminals SPH-4-xxQ Series 30 V Weight per Unit 62 g DIN /3 TE Packaging (Single Unit) mm pieces Bases with Quick Connect Terminals enable faster installation and have built-in contacts to enhance vibration resistance. Modular & Compact SPDs for Data/Signal Lines 21

24 SPD with Separated Signal Ground (S 232) aydat SGH-3 Series D1 C1 C2 C3 SMH-SG Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SGH-3 Series of surge protective devices has been developed to protect against the effects of induced voltages onto data, signal and communication circuits. It is intended for those applications where high ground potential rises may frequently occur, such as in locations close to electric railways. The circuit topology consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided by a three terminal gas discharge tube while fine protection is provided using a high speed silicon avalanche diode or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Both common (longitudinal) mode and differential (transverse) mode protection is provided. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SGH-3 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (SG-Ground) V (Line-Line), (Line-SG) 7-10 V V V V V V V V esponse Time Overvoltage Protection (Line-Line) t A < 1 ns (Line-Ground) < 100 ns Insulation esistance of the Protection (Line-Line) iso > 1 GΩ / 100 V (Line-Ground) 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path Ω Transverse Capacitance (Line-Line) C 50 pf (Line-Ground) 5 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SGH-3-xxx SGH-3-xxxM (module) SIGNALING NETWOK SEIES

25 aydat SGH-3 Series Internal Configuration Legend BD Bi-directional TVS Diode DB Diode Block Gas Discharge Tube esistor PG Protective Grounding SG Signal Grounding TC Thermo-clip TC DB LINE EQUIP 1 3 SG SG PG PG & Packaging 90 SGH-3 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 60 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SGH-3-xxxM Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 26g Packaging (Single Unit) mm 15 pieces 12 Modular & Compact SPDs for Data/Signal Lines 23

26 Modular SPD for Industrial Fieldbus Systems aydat SBH-3 Series D1 C1 C2 C3 IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 30 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SBH-3 Series of surge protective devices has been developed to protect fieldbus systems (CAN Bus, Profibus DP, S 232/V.24 m, S 485, Sinec L2). It is intended for those applications where high ground potential rises may frequently occur, such as in locations close to electric railways. The circuit topology consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided by a three terminal gas discharge tube while fine protection is provided using a high speed silicon avalanche diode or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Both common (longitudinal) mode and differential (transverse) mode protection is provided. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SBH-3 Series 5 V 12 V 30 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 30 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 33 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 22 V < 42 V < 80 V ated Spark Overvoltage (SG-Ground) V (Line-Line) 7-10 V V V esponse Time Overvoltage Protection (Line-Line) t A < 1 ns (Line-Ground) < 100 ns Insulation esistance of the Protection (Line-Ground) iso > 1 GΩ / 100 V (Line-Line) 6 KΩ 15 MΩ 33 MΩ Serial esistance per Path Ω Transverse Capacitance (Line-Line) C 50 pf (Line-Ground) 5 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-Strand 4 mm 2, 2.5 mm 2 Q Version Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 30 V SBH-3-xx SBH-3-xxQ (Quick Connect Terminals) SBH-3-xxM (module) SIGNALING NETWOK SEIES

27 aydat SBH-3 Series Internal Configuration Unprotected 1 3 DB 2 4 Protected Legend DB Diode Block Gas Discharge Tube PG Protective Grounding esistor PG PG & Packaging 90 SBH-3 Series 5 V 12 V 30 V Weight per Unit 60 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SBH-3-xxM Series 5 V 12 V 30 V Weight per Unit 26g Packaging (Single Unit) mm 15 pieces 12 Quick Connect Terminals 90 SBH-3-xxQ Series 5 V 12 V 30 V Weight per Unit 62 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Bases with Quick Connect Terminals enable faster installation and have built-in contacts to enhance vibration resistance. Modular & Compact SPDs for Data/Signal Lines 25

28 SPD for Shielded Cable aydat SSH-3 Series D1 C1 C2 C3 SMH-SH Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SSH-3 Series of surge protective devices has been developed to protect against the effects of induced voltages onto data, signal and communication circuits. The circuit topology consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided by a three terminal gas discharge tube while fine protection is provided using a high speed silicon avalanche diode or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Both common (longitudinal) mode and differential (transverse) mode protection is provided. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SSH-3 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (Shield-Ground) V (Line-Line), (Line-Ground) 7-10 V V V V V V V V esponse Time Overvoltage Protection (Shield-Ground) t A < 100 ns (Line-Line), (Line-Ground) < 1 ns Insulation esistance of the Protection (Shield-Ground) iso > 1 GΩ / 100 V (Line-Line), (Line-Ground) 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path Ω Transverse Capacitance (Shield-Ground) C 5 pf (Line-Line), (Line-Ground) 50 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SSH-3-xxx SSH-3-xxxQ (Quick Connect Terminals) SSH-3-xxxM (module) SIGNALING NETWOK SEIES

29 aydat SSH-3 Series Internal Configuration 1 3 TC DB 2 4 Legend DB Diode Block Gas Discharge Tube esistor PG Protective Grounding TC Thermo-clip 5 (SH) 7 LINE PG EQUIP 6 (SH) 8 & Packaging 90 SSH-3 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 60 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SSH-3-xxxM Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 26g Packaging (Single Unit) mm 15 pieces 12 Quick Connect Terminals 90 SSH-3-xxxQ Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 62 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Bases with Quick Connect Terminals enable faster installation and have built-in contacts to enhance vibration resistance. Modular & Compact SPDs for Data/Signal Lines 27

30 SPD with emote Contacts aydat SH-2 Series D1 C1 C2 C3 SMH-C Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SH-2 Series provides the same level of protection and technical performance as the SLH-2 Series, but also provides the feature of an additional set of voltage free contacts which can be used for remote signalization and monitoring of the device s status. If the unit fails, the contacts change state. These barriers provide both coarse and fine protection stages and offer longitudinal and transverse protection. The initial protection stage comprises a three-pole gas discharge tube and is designed to divert the primary surge energy. The subsequent fine protection stage is implemented using fast bidirectional silicon avalanche diodes. Special design techniques have been employed in the design of the fine protection stage to avoid capacitive line loading and thereby ensure a low insertion loss and wide operating frequency range. Series line impedance is used to ensure energy co-ordination between the coarse and fine protection stages irrespective of the magnitude of the incident surge. When power frequency contact occurs between power and communication lines, the hazard of electric shock and fire is increased. To prevent such risk, a thermoclip is included in the primary protection stage of this device to divert the power frequency current to ground. The plug-in module/base design facilitates replacement of a failed module without the need to remove system wiring. If the module is unplugged from the base, the through-connection is maintained, allowing continued operations while a replacement module is ordered. Technical Data SH-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (Line-Ground) 7-10 V V V V V V V V (Line-Line) 7-10 V V V V V V V V esponse Time Overvoltage Protection t A < 1 ns Thermal Protection Yes Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path Ω Transverse Capacitance C 50 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail emote Contacts atings AC 250 V/0.5 A, DC 50 V/1 A Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SH-2-xxx SH-2-xxxM (module) SIGNALING NETWOK SEIES

31 aydat SH-2 Series Internal Configuration 1 3 TC DB 2 4 Legend DB Diode Block Gas Discharge Tube PG Protective Grounding esistor C emote Control (NC) TC Thermo-clip LINE EQUIP 5 6 C C 7 8 PG PG & Packaging 90 SH-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 58 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SH-2-xxxM Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 24 g Packaging (Single Unit) mm 15 pieces 12 Modular & Compact SPDs for Data/Signal Lines 29

32 SPD for Two Pair Exposed Lines aydat SUI-4 Series D1 C1 C2 C3 SMI2 Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 20 ka, I max : 30 ka, I imp : 5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SUI-4 Series provides the same electrical performance as the SLH-4 Series but with a greater surge withstand level or impulse current 10 ka, 5 ka per line. It is intended for operation in electrical environments where higher exposure to the effects of direct or partially direct lightning currents may be experienced. These include wind turbines and PV installations where lightning exposures are more severe, but where protection of sensitive electronics, such as environmental sensors, is just as crucial. These barriers provide both coarse and fine protection stages and offer longitudinal and transverse protection. The initial protection stage comprises a three-pole gas discharge tube and is designed to divert the primary surge energy. The subsequent fine protection stage is implemented using fast bidirectional silicon avalanche diodes. Special design techniques have been employed in the design of the fine protection stage to avoid capacitive line loading and thereby ensure a low insertion loss and wide operating frequency range. Series line impedance is used to ensure energy coordination between the coarse and fine protection stages irrespective of the magnitude of the incident surge. When power frequency contact occurs between power and communication lines, the hazard of electric shock and fire is increased. To prevent such risk, a thermo-clip is included in the primary protection stage of this device to divert the power frequency current to ground. The plug-in module/base design facilitates replacement of a failed module without the need to remove system wiring. If the module is unplugged from the base, the through-connection is maintained, allowing continued operations while a replacement module is ordered. Technical Data SUI-4 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 2 (4 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 20 ka Maximum Discharge Current (8/20 µs) I max 30 ka D1 Impulse Current (10/350 µs) I imp 5 ka esidual Voltage at 5 ka (8/20 µs) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (Line-Ground) 7-10 V V V V V V V V (Line-Line) 7-10 V V V V V V V V esponse Time Overvoltage Protection t A < 1 ns Thermal Protection Yes Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path Ω Transverse Capacitance C 50 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SUI-4-xxx SUI-4-xxxM (module) SIGNALING NETWOK SEIES

33 aydat SUI-4 Series Internal Configuration DB TC DB 1 3 TC 2 4 Legend DB Diode Block Gas Discharge Tube PG Protective Grounding esistor TC Thermo-clip PG 5 7 LINE PG EQUIP 6 8 & Packaging 90 SUI-4 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 70 g DIN /3 TE Packaging (Single Unit) mm 15 pieces SUI-4-xxxM Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 30 g Packaging (Single Unit) mm 15 pieces 12 Modular & Compact SPDs for Data/Signal Lines 31

34 Compact SPD for Single Pair aydat SCH-2 Series D1 C1 C2 C3 NMH-TC Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: Up to 35 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Compact Design Compliance: IEC/EN These efficient overvoltage barriers contain both coarse and fine protection stages and provide longitudinal and a transverse surge protection. The initial protection stage comprises a three-pole gas discharge tube and is designed to divert the primary surge energy. The subsequent fine protection stage is carried out using multiple metal oxide varistors or with fast bi-directional silicon avalanche diodes. Care is taken in the design of this fine protection stage to avoid capacitive line loading and thereby ensuring a low insertion loss and wide operating frequency range. Care is taken to ensure energy coordination between the coarse and a fine protection stages at all levels of the incident surge. When power frequency contact occurs between power and communication lines, the hazard of electric shock and fire is increased. To prevent such risk, a thermo-clip is included in the primary protection stage of this device to divert the power frequency current to ground. Technical Data SCH-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (Line-Ground) 7-10 V V V V V V V V (Line-Line) 7-10 V V V V V V V V esponse Time Overvoltage Protection t A < 1 ns < 25 ns Thermal Protection Yes Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path 1cca. 1.0 Ω Transverse Capacitance C 30 pf 150 pf Cut-off Frequency f G 35 MHz 10 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SCH-2-xxx SIGNALING NETWOK SEIES

35 aydat SCH-2 Series Internal Configuration 1 3 DB 2 4 Legend D Diode DB Diode Block Gas Discharge Tube PG Protective Grounding esistor TC Thermo-clip PG LINE PG EQUIP & Packaging 89 SCH-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 54 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Modular & Compact SPDs for Data/Signal Lines 33

36 Compact SPD for Two Pair aydat SCH-4 Series D1 C1 C2 C3 NMH2-TC Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: Up to 5 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 5 ka Series Load Current: 0.8 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Compact Design Compliance: IEC/EN Like the aydat SCH-2 Series, the SCH-4 provides the same level of protection but in a compact enclosure which can provide protection to two independent circuits pairs. A number of protection voltages are available to ensure the user is able to select the closest clamping voltage to the normal signal operation of the equipment being protected. Technical Data SCH-4 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 2 (4 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 5 ka esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V < 450 V ated Spark Overvoltage (Line-Ground) 7-10 V V V V V V V V (Line-Line) 7-10 V V V V V V V V esponse Time Overvoltage Protection t A < 1 ns Thermal Protection Yes Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path 0.5 Ω Transverse Capacitance C 500 pf 250 pf Cut-off Frequency f G 3 MHz 5 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SCH-4-xxx SIGNALING NETWOK SEIES

37 aydat SCH-4 Series Internal Configuration Legend D Diode DB Diode Block Gas Discharge Tube L Inductor MOV Metal Oxide Varistor PG Protective Grounding esistor TC Thermo-clip PG LINE PG L L L L MOV MOV DB DB 2 4 EQUIP 6 8 & Packaging 89 SCH-4 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 64 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Modular & Compact SPDs for Data/Signal Lines 35

38 SPD with Overcurrent Protection aydat STD-2 Series D1 C1 C2 C3 IM-TD Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 145 ma (1 A for 110 V version) Safety: Internal Thermal unaway Disconnecter Indication: 2x End-of-life Status Flag Enclosure: DIN TE, DIN ail Mount Terminals: Stranded to 6 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat STD-2 Series of surge protective devices has been developed to protect against the effects of induced voltages onto data, signal and communication circuits. The circuit used is designed to minimize inter-capacitance, and shunt capacitance, thereby maximizing the operating frequency to 35 MHz in most cases. The circuit topology consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided by a three terminal gas discharge tube while fine protection is provided using a high speed silicon avalanche diodes or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Technical Data STD-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 145 ma 145 ma 145 ma 145 ma 145 ma 145 ma 145 ma 1 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) U res < 20 V < 39 V < 45 V < 65 V < 77 V < 135 V < 150 V < 450 V ated Spark Overvoltage (Line-Ground) V V V 3036 V V V V V (Line-Line) V V V 3036 V V V V V esponse Time Overvoltage Protection t A < 1 ns < 1 ns < 1 ns < 1 ns < 1 ns < 1 ns < 1 ns < 25 ns Thermal Protection (a,b) Thermal Disconnection Lines a & b Overcurrent Protection PTC esistors at A Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω cca. 1 Ω Transverse Capacitance C 7.0 nf 4.4 nf 3.3 nf 2.9 nf 2.1 nf 1.2 nf 1.0 nf 90 pf Cut-off Frequency f G 0.6 MHz 0.9 MHz 1.1 MHz 1.4 MHz 1.8 MHz 2.2 MHz 3.0 MHz 10 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 6 mm 2 Terminal Screw Torque 2.0 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Yellow; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail emote Contacts atings AC 250 V/0.5 A, DC 50 V/1 A Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V STD-2-xxx STD-2-xxxS (Base S ) STD-2-xxx (Base ) STD-2-xxxG (Base G) STD-2-xxxM (module) SIGNALING NETWOK SEIES

39 STD-2 Series Base Options Internal Configuration S Base: Where a coaxial shield is used and equipotential ground equalization is required. Base: Provides remote contacts to signify if an internal thermal disconnect has operated. G Base: Where a second ground terminal (in addition to the DIN rail ground strip) is provided for installations not utilizing DIN rail. STD-2 STD-2 STD-2 STD-2 Base S Base Base G Base TD PTC BD BD 1 BD 2 TD PTC 3 4 base STD PG TD PTC BD BD 1 BD 2 TD PTC 3 4 SG SG S base STD S PG TD PTC BD BD TD PTC BD 4 TD MOV 1 MOV MOV 2 TD 3 4 base STD PG TD MOV 1 MOV 2 TD MOV 3 4 SG SG S base STD-2-110S PG TD MOV 1 MOV MOV 2 TD 3 4 Legend BD Bi-directional TVS Diode Gas Discharge Tube MOV Metal Oxide Varistor PG Protective Grounding PTC Positive Temperature Coefficient esistor esistor SG Signal Grounding TD Thermal Decoupler TD 1 TD 3 PG C STD STD G PG PTC PTC PG BD BD base BD 2 4 G base PG C STD TD STD-2-110G base PG MOV 1 MOV MOV 2 TD 3 4 G base PG & Packaging 90 STD-2 Series STD-2-xxx STD-2-xxxS STD-2-xxx STD-2-xxxG Weight per Unit 88 g 96 g 92 g 96 g DIN TE Packaging (Single Unit) mm 12 pieces STD-2-xxxM Series 45 Weight per Unit Packaging (Single Unit) 32 g mm 24 pieces 17.5 Modular & Compact SPDs for Data/Signal Lines 37

40 SPD with Multi-Protection Modes aydat SUHI-2 Series D1 C1 C2 C3 VMO Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 2 2 terminal 1 3 Terminal Voltages: 5, 12, 15, 24, 30, 48, 60, 110 V DC Frequency ange: MHz Surge Discharge atings: I n : 20 ka, I max : 30 ka, I imp : 5 ka Series Load Current: 1 A Enclosure: DIN TE, DIN ail Mount Terminals: Stranded to 6 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SUHI-2 Series of surge protective devices has been developed to protect against the effects of induced voltages onto data, signal and communication circuits. It is intended for those applications where higher than normal surge discharge levels may be experienced. Coarse protection is provided by 2 two-terminal gas discharge tubes. A second stage of protection is provided using a three terminal gas discharge tube which assists in common mode protection. Fine protection is provided using a high speed silicon avalanche diodes or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Both common (longitudinal) mode and differential (transverse) mode protection is provided. Technical Data SUHI-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 18 V 28 V 33 V 52 V 64 V 170 V ated Load Current at 25ºC I L 1 A C2 Nominal Discharge Current (8/20 µs) I n 20 ka Maximum Discharge Current (8/20 µs) I max 30 ka D1 Impulse Current (10/350 µs) I imp 5 ka esidual Voltage at 5 ka (8/20 µs) U res < 20 V < 39 V < 45 V < 65 V < 77 V < 135 V < 150 V < 450 V ated Spark Overvoltage (Line-Ground) V V V V V V V V (Line-Line) V V V V V V V V esponse Time Overvoltage Protection t A < 1 ns < 25 ns Insulation esistance of the Protection iso 6 KΩ 15 MΩ 18 MΩ 28 MΩ 33 MΩ 52 MΩ 64 MΩ 170 MΩ Serial esistance per Path 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω 9-11 Ω cca. 2 Ω Transverse Capacitance C 7.0 nf 4.5 nf 3.3 nf 2.9 nf 2.1 nf 1.2 nf 1.0 nf 150 pf Cut-off Frequency f G 0.6 MHz 0.9 MHz 1.1 MHz 1.4 MHz 1.8 MHz 2.2 MHz 3.0 MHz 10 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 6 mm 2 Terminal Screw Torque 2.0 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Yellow; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V SUHI-2-xxx SUHI-2-xxxM (module) SIGNALING NETWOK SEIES

41 SUHI-2 Series Internal Configuration MOV MOV MOV BD BD 1 2 BD 3 4 Legend BD Bi-directional TVS Diode Gas Discharge Tube MOV Metal Oxide Varistor PG Protective Grounding esistor PG SUHI V base PG SUHI V base & Packaging 90 SUHI-2 Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 96 g DIN TE Packaging (Single Unit) mm 15 pieces SUHI-2-xxxM Series 5 V 12 V 15 V 24 V 30 V 48 V 60 V 110 V Weight per Unit 34 g Packaging (Single Unit) mm 15 pieces 17.5 Modular & Compact SPDs for Data/Signal Lines 39

42 SPD with Single Protection Mode aydat SU-2 Series D1 C1 C2 C3 SMH-TD Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltage: 110 V DC Maximum Operating Voltage 170 V DC Serial esistance per Path: 9-11 Ω Frequency ange: 16 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 300 ma Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SU-2 has been developed as a generic protector for use on data transmission circuits. Coarse protection is provided by a three terminal gas discharge tube. Internal thermal disconnectors are used to reduce the hazards of thermal runaway during fault conditions, or if mains incursion onto the low voltage data circuit occurs. To protect against the hazards of electric shock and fire which often results when power frequency contact occurs between power and communication lines, often called mains incursion, a thermo-clip is included on the primary protection stage to divert the power frequency current to ground. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SU-2 Series 110 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 110 V Maximum Continuous Operating Voltage (DC) U c 170 V ated Load Current at 25ºC I L 300 ma C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) U res < 500 V ated Spark Overvoltage (Line-Ground) V (Line-Line) V esponse Time Overvoltage Protection t A < 100 ns Thermal Protection Yes Insulation esistance of the Protection iso > 1 GΩ Serial esistance per Path 9-11 Ω Transverse Capacitance C 10 pf Cut-off Frequency f G 16 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 110 V SU-2-xxx SU-2-xxxM (module) SIGNALING NETWOK SEIES

43 aydat SU-2 Series Internal Configuration TC Legend Gas Discharge Tube PG Protective Grounding esistor TC Thermo-clip PG 1 3 LINE 3 1 PG 2 4 EQUIP 2 4 & Packaging 90 SU-2 Series Weight per Unit DIN Packaging (Single Unit) 110 V 52 g 2/3 TE mm 15 pieces SU-2-xxxM Series 110 V 45 Weight per Unit Packaging (Single Unit) 24 g mm 15 pieces 12 Modular & Compact SPDs for Data/Signal Lines 41

44 SPD for Two Pair with Single Protection Mode aydat SU-4 Series D1 C1 C2 C3 SMH2-TD Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltage: 110 V DC Maximum Operating Voltage 170 V DC Serial esistance per Path: 9-11 Ω Frequency ange: 16 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 5 ka Series Load Current: 300 ma Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SU-4 has been developed as a generic protector for use on data transmission circuits. Coarse protection is provided by a three terminal gas discharge tube. Internal thermal disconnectors are used to reduce the hazards of thermal runaway during fault conditions, or if mains incursion onto the low voltage data circuit occurs. To protect against the hazards of electric shock and fire which often results when power frequency contact occurs between power and communication lines, often called mains incursion, a thermo-clip is included on the primary protection stage to divert the power frequency current to ground. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SU-4 Series 110 V Electrical Lines Protected 2 (4 Conductors) Nominal Operating Voltage (DC) U n 110 V Maximum Continuous Operating Voltage (DC) U c 170 V ated Load Current at 25ºC I L 300 ma C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 5 ka esidual Voltage at 5 ka (8/20 µs) U res < 500 V ated Spark Overvoltage (Line-Ground) V (Line-Line) V esponse Time Overvoltage Protection t A < 100 ns Thermal Protection Yes Insulation esistance of the Protection iso > 1 GΩ Serial esistance per Path 9-11 Ω Transverse Capacitance C 10 pf Cut-off Frequency f G 16 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 110 V SU-4-xxx SU-4-xxxM (module) SIGNALING NETWOK SEIES

45 aydat SU-4 Series Internal Configuration TC 1 3 TC 2 4 Legend Gas Discharge Tube PG Protective Grounding esistor TC Thermo-clip PG 5 7 LINE PG EQUIP 6 8 & Packaging 90 SU-4 Series Weight per Unit DIN Packaging (Single Unit) 110 V 66 g 2/3 TE mm 15 pieces SU-4-xxxM Series 110 V 45 Weight per Unit 24 g Packaging (Single Unit) mm 15 pieces 12 Modular & Compact SPDs for Data/Signal Lines 43

46 SPD for Two Pair with Single Protection Mode aydat SLL-4 Series C1 C3 IEC/EN Category: C1/C3 Mode of Protection: Transverse Voltages: 30 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 250 A Series Load Current: 10 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SLL-4 has been developed to protect data transmission circuits or low voltage alarm circuits such as fire or security. The unit provides fine protection using a high speed, bi-directional, silicon stage. Where necessary, the aydat SLL-4 may be used with a higher energy coarse protection unit such as the SU Series. The plug-in module design facilities replacement of a failure module without the need to remove system wiring. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SLL-4 Series 30 V Electrical Lines Protected 2 (4 Conductors) Nominal Operating Voltage (DC) U n 30 V Maximum Continuous Operating Voltage (DC) U c 33 V ated Load Current at 25ºC I L 10 A C1 Nominal Discharge Current (8/20 µs) I n 250 A esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 80 V ated Spark Overvoltage (Line-Line) V (Line-Ground) V esponse Time Overvoltage Protection (Line-Line) t A < 1 ns (Line-Ground) < 1 ns Insulation esistance of the Protection (Line-Line) iso 33 MΩ (Line-Ground) 33 MΩ Serial esistance per Path 0.1 Ω Transverse Capacitance (Line-Line) C 50 pf (Line-Line) 50 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2, 2.5 mm 2 Q Version Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 30 V SLL-4-xx SLL-4-xxQ (Quick Connect Terminals) SLL-4-xxM (module) SIGNALING NETWOK SEIES

47 aydat SLL-4 Series Internal Configuration DB 1 DB LINE EQUIP 6 8 Legend DB Diode Block PG Protective Grounding PG PG & Packaging 90 SLL-4 Series Weight per Unit DIN Packaging (Single Unit) 30 V 56 g 2/3 TE mm 15 pieces SLL-4-xxM Series 30 V 45 Weight per Unit 22 g Packaging (Single Unit) mm 15 pieces 12 Quick Connect Terminals SLL-4-xxQ Series 30 V Weight per Unit 58 g DIN /3 TE Packaging (Single Unit) mm pieces Bases with Quick Connect Terminals enable faster installation and have built-in contacts to enhance vibration resistance. Modular & Compact SPDs for Data/Signal Lines 45

48 SPD with Single Protection Mode aydat SCL-1 Series C1 C3 IM-VF Series IEC/EN Category: C1/C3 Mode of Protection: Transverse Fine Protection: MOV Voltages: 12, 24 V DC Frequency ange: 0.5 MHz Surge Discharge atings: I n : 500 A Series Load Current: 10 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Compact Design Compliance: IEC/EN The aydat SCL-1 Series has been developed to protect data transmission circuits or low voltage alarm circuits such as fire or security. The unit provides fine protection using a MOV. Where necessary, the SCL-1 may be used with a higher energy coarse protection unit such as the SU Series. Technical Data SCL-1 Series 12 V 24 V Electrical Lines Protected 1 Conductor Nominal Operating Voltage (DC) U n 12 V 24 V Maximum Continuous Operating Voltage (DC) U c 22 V 38 V ated Load Current at 25ºC I L 10 A C1 Nominal Discharge Current (8/20 µs) I n 500 A esidual Voltage at I n (8/20 µs) U res < 48 V < 87 V ated Spark Overvoltage V V esponse Time Overvoltage Protection t A < 25 ns Insulation esistance of the Protection iso 1.5 MΩ 3.0 MΩ Serial esistance per Path <0.1 Ω Transverse Capacitance C <10 nf <6.0 nf Cut-off Frequency f G 0.5 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Stranded to 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Beige; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 12 V 24 V SCL-1-xx SIGNALING NETWOK SEIES

49 aydat SCL-1 Series Internal Configuration 1 2 PG MOV Legend MOV Metal Oxide Varistor PG Protective Grounding PG & Packaging 67.6 SCL-1 Series 12 V 24 V Weight per Unit 28 g DIN /3 TE Packaging (Single Unit) mm 40 pieces Modular & Compact SPDs for Data/Signal Lines 47

50 SPD with Single Protection Mode aydat SCL-2 Series C1 C2 C3 IM-DF Series IEC/EN Category: C1/C2/C3 (see Technical Data) Mode of Protection: Transverse Fine Protection: Bi-directional TVS Diode Voltages: 5, 12, 24, 60 V DC Frequency ange: Up to 1.4 MHz Surge Discharge atings: I n : up to 500 A Series Load Current: 10 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Compact Design Compliance: IEC/EN The aydat SCL-2 Series has been developed to protect data transmission circuits or low voltage alarm circuits such as fire or security. They only provide fine protection using a high speed, bi-directional, silicon stage. Where necessary, the SCL-2 may be used with a higher energy coarse protection unit such as the SU series. Technical Data SCL-2 Series 5 V 12 V 24 V 60 V Electrical Type per IEC/EN C1 / C2 / C3 C1 / C3 C1 / C3 C3 Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 5 V 15 V 24 V 60 V Maximum Continuous Operating Voltage (DC) U c 6 V 15 V 28 V 64 V ated Load Current at 25ºC I L 10 A Nominal Discharge Current (8/20 µs) I n 500 A 500 A 250 A 100 A esidual Voltage at I nv (8/20 µs) U res < 20 V < 39 V < 65 V < 150 V ated Spark Overvoltage (Line-Ground) 8-10 V V V V (Line-Line) V V V V esponse Time Overvoltage Protection t A < 1 ns Insulation esistance of the Protection iso 6 KΩ 15 MΩ 28 MΩ 64 MΩ Serial esistance per Path <0.1 Ω Transverse Capacitance C <7.0 nf <3.0 nf <1.0 nf <0.5 nf Cut-off Frequency f G 0.6 MHz 0.9 MHz 1.4 MHz 3 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Beige; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 5 V 12 V 24 V 60 V SCL-2-xx SIGNALING NETWOK SEIES

51 aydat SCL-2 Series Internal Configuration BD BD 4 PG Legend BD Bi-directional TVS Diode PG Protective Grounding PG & Packaging 67.6 SCL-2 Series 5 V 12 V 24 V 60 V Weight per Unit 26 g DIN /3 TE Packaging (Single Unit) mm 40 pieces Modular & Compact SPDs for Data/Signal Lines 49

52 SPD for DC Power Supply & Data aydat SUH-2 PS D1 C1 C2 C3 SMH-TC+PS Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal (Data Line) MOVs (PS Line) Voltages: 24 V DC (Data Line) 24 V AC (Power Line) Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.5 ka Series Load Current: 1 A (Data Line), 3 A (PS Line) Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat SUH-2 PS Series has been developed for protection of systems with one supply and one signal line (CAN bus, DeviceNet,...). This efficient overvoltage protective device is intended to protect line from overvoltage surges and electrostatic discharges created by switching transients in buildings. The signal line circuit is designed to minimize inter-capacitance, and shunt capacitance, thereby maximizing the operating frequency to 30 MHz. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data SUH-2 PS Data Line Power Supply Line Electrical Lines Protected 2 (1 Data Line + 1 Power Supply Line) Nominal Operating Voltage (DC) U n 24 V 24 V AC /30 V DC Maximum Continuous Operating Voltage (DC) U c 28 V 28 V AC /40 V DC ated Load Current at 25ºC I L 1 A 3 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20 µs) U res < 70 V < 100 V ated Spark Overvoltage (Line-Ground) V V (Line-Line) V V esponse Time Overvoltage Protection t A < 1 ns Insulation esistance of the Protection iso 28 MΩ 40 MΩ Serial esistance per Path Ω <0.2 Ω Serial Inductivity L 15 µh Transverse Capacitance C 50 pf 6.0 nf Cut-off Frequency f G 30 MHz 1 khz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 24 V SUH-2-xxPS SUH-2-xxPSM (module) SIGNALING NETWOK SEIES

53 aydat SUH-2 PS Internal Configuration TC DB TD L Legend BD Bi-directional TVS Diode DB Diode Block Gas Discharge Tube L Inductor MOV Metal Oxide Varistor PG Protective Grounding esistor TC Thermo-clip TD Thermal Disconnecter Power supply PG 5 7 Data 1 3 LINE MOV MOV BD L TD PG 2 4 EQUIP 6 8 & Packaging 90 SUH-2-xxPS Weight per Unit DIN Packaging (Single Unit) 24 V 72 g 2/3 TE mm 15 pieces SUH-2-xxPSM 24 V 45 Weight per Unit 34 g Packaging (Single Unit) mm 15 pieces 12 Modular & Compact SPDs for Data/Signal Lines 51

54 52 SIGNALING NETWOK SEIES

55 Modular Surge Protective Devices (SPDs) for Explosive Environments The aydat Ex Series is intended to provide protection to low voltage signal and data circuits located in potentially explosive environments. It is intended for use on inherently safe circuits in accordance with ATEX directive. The protection module should be located as close to the end-user equipment being protected as possible. aydat Ex-2 aydat PLP Ex aydat PLP2 Ex aydat PLP-24/5 Ex aydat PLP3L Ex Modular SPDs for Explosive Environments 53

56 SPD for Explosive Environments aydat Ex-2 Series D1 C1 C2 C3 SMH-xxEx Series IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 12, 24 V DC Maximum Operating Voltage: U c : 15, 28 V DC Frequency ange: 3 MHz Surge Discharge atings: I n : 5 ka, I max : 10 ka, I imp : 1 ka Series Load Current: 500 ma Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat Ex-2 Series is intended to provide protection to low voltage signal and data circuits located in potentially explosive environments. It is intended for use on inherently safe circuits in accordance with ATEX directive. The protection module should be located as close to the end-user equipment being protected, as possible. Input Power Pi Temperature Class Maximum Ambient Pi=1W T6 50 º C Pi=1.3W T5 55 º C Pi=2W T4 60 º C U o = U i I o =I i P o =P i Technical Data Ex-2 Series 12 V 24 V Type Intrinsic Safety Parameters Explosion Protected II 1G Ex ia IIC T* Ga (-40 º C Ta * C) IEC Type Examination Certificate Baseefa Baseefa 15ATEX0028X Ex IEC IECEx BAS X Maximum Input Voltage U i 16 V 29 V Maximum Input Current I i 500 ma Maximum Input Power P i 2 W Maximum Internal Capacitance C i 10 nf Maximum Internal Inductance L i 0.11 mh Number of Protected Pairs Electrical 1 (2 Conductors) Nominal Operating Voltage (DC) U n 12 V 24 V Maximum Continuous Operating Voltage (DC) U c 15 V 28 V ated Load Current at 25ºC I L 500 ma Nominal Discharge Current (8/20 µs) I n 5 ka Maximum Discharge Current (8/20 µs) I max 10 ka D1 Impulse Current (10/350 µs) I imp 1 ka esidual Voltage at 5 ka (8/20 µs) U res < 145 V ated Spark Overvoltage (Line-Line) V V (Line-Ground) V esponse Time Overvoltage Protection t A < 1 ns Insulation esistance at U c iso 15 MΩ 28 MΩ Insulation esistance at 500 V DC (Line-Ground) > 1 GΩ Serial esistance per Path <1 Ω Transverse Capacitance C <10 pf Cut-off Frequency f G 3 MHz Mechanical Terminal Cross Section Multi-strand 4mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Beige; Extinguishing Degree V-0 Mounting IEC/EN Order Information The circuit consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided using a three terminal gas discharge tube while fine protection is provided using a high speed bidirectional silicon stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. 35 mm DIN ail Order Code 12 V 24 V Ex-2-xx SIGNALING NETWOK SEIES

57 aydat EX-2 Series Internal Configuration F F L DB Legend DB Diode Block F Fuse Gas Discharge Tube L Inductor PG Protective Grounding esistor PG 1 3 LINE PG EQUIP 2 4 & Packaging 90 Ex-2 Series 12 V 24 V Weight per Unit 88 g DIN /3 TE Packaging (Single Unit) mm 15 pieces Modular SPDs for Explosive Environments 55

58 SPD for Explosive Environments aydat PLP Ex Series D1 C1 C2 C3 IEC/EN Category: D1/C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 24, 48, 24/5 V DC Maximum Operating Voltage: U c : 33, 54, 33/7.5 V DC Frequency ange: 30 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka, I imp : 2.0 ka Enclosure: Stainless Steel IP 67 Terminals: Connecting Cables 1 mm 2, 250 mm length Housing: In-line 1/2 Conduit Fitting Compliance: IEC/EN The aydat PLP Ex Series is intended to provide protection to low voltage signal and data circuits located in potentially explosive environments. It is intended for use on inherently safe circuits in accordance with ATEX directive. The protection module should be located as close to the end-user equipment being protected as possible. The circuit consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. Coarse protection is provided using a three terminal gas discharge tube while fine protection is provided using a high speed bidirectional silicon stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Technical Data PLPEx PLP-24Ex PLP2-24Ex PLP2-48Ex PLP 24/5Ex PLP3L-24Ex Type Intrinsic Safety Parameters IEC Type Examination Certificate Baseefa Baseefa 14ATEX0364X Ex II 1GD Ex ia IIC T6 Ga (-30 º C Ta 50 C) IEC IECEx BAS X Ex ia IIIC T85 º C Da (-30 º C Ta 50 C) Maximum Input Voltage U i 50 V Maximum Input Current I i 800 ma Maximum Input Power P i 2 W Maximum Internal Inductance L i 60 µh Electrical Nominal Operating Voltage (DC) U n 24 V 24 V 48 V 24 V/5 V 24 V Maximum Continuous Operating Voltage (DC) U c 33 V 33 V 54 V 33 V/7.5 V 33 V ated Spark Overvoltage (Line-Ground) V V V V V (Line-Line) V V V V, 9-13 V V Total Nominal Discharge Current (8/20 µs) I n 5 ka 10 ka 10 ka 10 ka 7.5 ka Total Discharge Current (8/20 µs) I max 10 ka 20 ka 20 ka 20 ka 15 ka Total Impulse Current (10/350 µs) I imp 1.0 ka 2.0 ka 2.0 ka 2.0 ka 1.5 ka esidual Voltage at I max (8/20 µs) (Line-Line) U res < 1.3 kv < 1.3 kv < 1.3 kv < 1.3 kv < 1.3 kv esponse Time Overvoltage Protection t A < 1 ns Insulation esistance of the Protection (Line-Line) iso > 32 MΩ > 32 MΩ > 32 MΩ > 32 MΩ/75 kω > 32 MΩ Insulation esistance at U(Line-Ground) = 500 V DC > 1 GΩ Transverse Capacitance C < 30 pf Cut-off Frequency f G 30 MHz Mechanical Ambient Temperature ange -30 º C < Ta < 60 º C Connection Cables D L 1 mm mm Degree of Protection IEC/EN IP 67 Housing Material Stainless Steel Dimension Length 78 mm 120 mm 120 mm 120 mm 120 mm Order Information Order Code PLP-24Ex PLP2-24Ex PLP2-48Ex PLP 24/5Ex PLP3LEx 1/2" NPT M G 1/2" (BSP 1/2 inch) SIGNALING NETWOK SEIES

59 aydat PLP Ex Series Internal Configuration 1(2) a DB 2(4) a DB b b c DB PLP-24Ex d Legend DB Diode Block Gas Discharge Tube 2(3) a DB PLP2-xxEx b DB c PLP3L-24Ex & Packaging PLP-24Ex PLP-24 Ex 1/2" NPT PLP-24 Ex M 20 1/2" PLP-24 Ex G 1/2" Weight per Unit 170 g Packaging (Single Unit) mm 6 pieces PLP2-xxEx PLP2-xx Ex 1/2" NPT PLP2-xx Ex M 20 1/2" PLP2-xx Ex G 1/2" Weight per Unit 290 g Packaging (Single Unit) mm 6 pieces PLP3L-24Ex PLP3L-24 Ex 1/2" NPT PLP3L-24 Ex M 20 1/2" PLP3L-24 Ex G 1/2" Weight per Unit 290 g Packaging (Single Unit) mm 6 pieces Modular SPDs for Explosive Environments 57

60 58 SIGNALING NETWOK SEIES

61 Modular & Compact Surge Protective Devices (SPDs) for DC Power Systems Surge protective devices for DC power systems have been designed to meet the unique requirements of protection used for telecommunication and railway applications. It provides both common and differential protection modes. Internal thermal disconnectors are used to eliminate the hazard of thermal runaway fault conditions. Protec DMD 20 aydat PSC-2 Modular & Compact SPDs for DC Power Systems 59

62 SPD for DC Power Systems Protec DMD 20 Series Class III POTEC DMD 20 Series IEC/EN Category: Class III/Type 3 Mode of Protection: L/N PE Location of Use: DC Power Systems Protection Element: MOV + Voltages: 24, 48, 60, 120 V AC Surge Discharge atings: I n : up to 4 ka, I max : up to10 ka Status Indication: emote Contacts + LED Enclosure: DIN TE, DIN ail Mount Terminals: Stranded to 6 mm 2 Housing: Modular Design Compliance: IEC : 2005, EN :2005 The Protec DMD Series has been designed to meet the unique requirements of protection of DC power systems found in Telepower and railway applications. Protec DMD Series provides both common and differential mode protection using high nominal discharge rating for extended operating life under DC conditions. Technical Data Protec DMD 20 Series 24 V 48 V 60 V 120 V Electrical Nominal Operating Voltage (AC) U n 24 V 48 V 60 V 120 V Maximum Continuous Operating Voltage (DC) U c 34 V / 44 V 60 V 75 V 150 V Open Circuit Voltage of Combination Wave Generator U oc 4 kv 4 kv 6 kv 6 kv Nominal Discharge Current (8/20 µs) I n 1.2 ka 2.5 ka 2.5 ka 4 ka Maximum Discharge Current (8/20 µs) I max 3 ka 6 ka 6 ka 10 ka Protection Level (L-N) U p < 180 V < 370 V < 400 V < 600 V (L-PE/N-PE) < 550 V < 650 V < 700 V < 850 V esponse Time Overvoltage Protection (L-N) t A < 25 ns (L-PE/N-PE) < 100 ns Thermal Protection Yes Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 6 mm 2 Terminal Screw Torque 2.0 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 24 V 48 V 60 V 120 V Protec DMD 20/xxx Protec DMD 20/xxxM (module) SIGNALING NETWOK SEIES

63 Protec DMD 20 Series Internal Configuration L (+) N (-) C Legend Gas Discharge Tube MOV Metal Oxide Varistor PE Ground esistor C emote Control (NC) MOV PE & Packaging 90 Protec DMD 20 Series 24 V 48 V 60 V 120 V Weight per Unit 96 g DIN TE Packaging (Single Unit) mm 12 pieces Protec DMD 20/xxx M 24 V 48 V 60 V 120 V 45 Weight per Unit Packaging (Single Unit) 32 g mm 15 pieces 18 Modular & Compact SPDs for DC Power Systems 61

64 SPD for DC Power Systems with Low esidual Voltage aydat PSC-2 Series C1 C2 C3 SMH-PS Series IEC/EN Category: C1/C2/C3 Mode of Protection: Longitudinal, Transverse Location of Use: DC Power Systems Coarse Protection: MOV Voltages: 12, 24, 48 V DC Surge Discharge atings: I n : 10 ka, I max : 20 ka Serial Inductivity: µh Series Load Current: 4 A Enclosure: DIN /3 TE, DIN ail Mount Terminals: Stranded to 4 mm 2 Housing: Modular Design Compliance: IEC/EN The aydat PSC-2 Series has been developed to protect power supplies. Coarse protection is provided by varistors, while fine protection is provided using a high-speed silicon stage. Internal thermal disconnectors are used to reduce the hazards of thermal runaway during fault conditions, or if mains incursion onto the low voltage data circuit occurs. If the module is unplugged out of the base, the connection lines remain enabled. Technical Data PSC-2 Series 12 V 24 V 48 V Electrical Lines Protected 1 (2 Conductors) Nominal Operating Voltage (DC) U n 12 V 24 V 48 V Maximum Continuous Operating Voltage (DC) U c 15 V 28 V 52 V ated Operating Current at 25 ºC I L 4 A C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at 5 ka (8/20 µs) U res < 32 V < 60 V < 135 V ated Spark Overvoltage (1, 2-PG) V V V (1, 2) V V V esponse Time Overvoltage Protection t A < 1 ns Thermal Protection Thermal Disconnection Insulation esistance of the Protection iso 15 MΩ 28 MΩ 52 MΩ Serial Inductance per Path L 10 14µH Transverse Capacitance C < 5nF < 3nF < 1.5nF Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 4 mm 2 Terminal Screw Torque 0.5 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code 12 V 24 V 48 V PSC-2-xx PSC-2-xxM (module) SIGNALING NETWOK SEIES

65 aydat PSC-2 Series Internal Configuration TD L TD L BD Legend Gas Discharge Tube MOV Metal Oxide Varistor PE Ground esistor C emote Control (NC) 1 3 PG LINE PG 4 EQUIP 2 4 & Packaging 90 PSC-2 Series 12 V 24 V 48 V Weight per Unit 64 g DIN /3 TE Packaging (Single Unit) mm 15 pieces PSC-2-xxM 12 V 24 V 48 V Weight per Unit 36 g Packaging (Single Unit) mm 15 pieces 12 Modular & Compact SPDs for DC Power Systems 63

66 64 SIGNALING NETWOK SEIES

67 Surge Protective Devices (SPDs) for Local Area Networks (LAN) The NET series is intended to protect Local Area Networks (LAN) from overvoltage surges and electrostatic discharges created by switching transients in buildings. LAN systems are particularly prone to such disturbances because of long cable lengths. aydat NET 6 aydat NET 5 aydat NET 5-19 aydat NET 5 PS aydat NET 5 Series is designed to protect Cat 5 Local Area Networks. They are available in standard, PoE and STP versions. aydat NET 6 is designed to protect Cat 6 Local Area Networks. It is suitable for protection of 1 Gbit/s lines and fully compatible with current PoE standards. aydat NET 5 xx-19 Series is designed to protect Cat 5 Local Area Networks. It is available in 8, 16 and 24 line versions. aydat Net 5 PS is combined protective device designed to protect Cat 5 Local Area Networks as well as the AC power port. SPDs for Local Area Networks 65

68 SPD for Category 6 LAN Networks aydat NET 6 LZ-NET 6 D1 C1 C2 C3 IEC/EN Category: D1/C1/C2/C3 Protection: All 4 Pairs Voltages: 48 V DC Maximum Operating Voltage: 50 V Frequency ange: 250 MHz, up to Cat 6, PoE Compatible Surge Discharge atings: I n : 10 ka, I imp : 1 ka Enclosure: UTB In-line Patch, DIN ail Mount Terminals: J45, Shielded Housing: Compact Design Compliance: IEC/EN The aydat NET 6 is intended to protect Local Area Networks (LAN) from overvoltage surges and electrostatic discharges created by switching transients in buildings. LAN systems are particularly prone to such disturbances because long cable lengths often behave like antennas to such atmospheric disturbances. It provides protection to all 4 lines in the UTP, STP and is Cat 6 capable. Ground potential equalization between signal and protective network or PC chassis ground is provided. Product is designed to fulfill all versions of PoE applications compatible with standards IEEE 802.3af and IEEE 802.3at. Technical Data NET 6 48 V Electrical Number of Protected Pairs 4 Pairs (8 Conductors) Nominal Operating Voltage (DC) U n 48 V Maximum Continuous Operating Voltage (DC) (Line-Line) U c 50 V (Pair-Pair) 72 V ated Load Current at 25ºC I L 1 A Nominal Discharge Current (8/20 µs) (Line-Line) I n 150 A C2 Total Discharge Current (8/20 µs) (Lines-Ground) I max 10 ka D1 mpulse Current (10/350 µs) I imp 1 ka Voltage Protection Level at I n (Line-Line) U p 150 V (Line-Ground) 550 V esponse Time Overvoltage Protection t A < 1 ns Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C Connection Type Input/Output: J45 Sockets Degree of Protection IEC/EN IP 20 Housing Material Metal Mounting IEC/EN mm DIN ail Order Information Order Code 48 V NET SIGNALING NETWOK SEIES

69 aydat NET 6 Internal Configuration Legend DB Diode Block Gas Discharge Tube PG Protective Grounding PG DB DB DB DB & Packaging 45.5 NET 6 48 V Weight per Unit 120 g DIN mm Packaging (Single Unit) mm pieces SPDs for Local Area Networks 67

70 SPD for Category 5 LAN Networks aydat NET 5 Series C1 C2 C3 LZ-NET 5 Series IEC/EN Category: C1/C2/C3 (see Technical Data) Protection: All 4 Pairs Voltages: 5, 48 V DC Maximum Operating Voltage: 6, 58 V DC Frequency ange: 100 MHz, Cat 5, PoE Compatible Surge Discharge atings: I n : up to 300 A per Line Enclosure: UTB In-line Patch Termination: J45, Cat 5 Connectors Housing: Compact Design Compliance: IEC/EN The aydat NET 5 Series is intended to protect Local Area Networks (LAN) from overvoltage surges and electrostatic discharges created by switching transients in buildings. LAN systems are particularly prone to such disturbances because long cable lengths often behave like antennas to such atmospheric disturbances. It provides protection to all 4 lines in the UTP and is Cat 5 capable. Ground potential equalization between signal and protective network or PC chassis ground is provided. PoE version aydat NET 5 PoE is designed to fulfill all versions of PoE applications compatible with standards IEEE 802.3af and IEEE 802.3at. Technical Data NET 5 NET 5 NET 5 PoE NET 5 STP Electrical Type per IEC/EN C1/C2/C3 C1/C3 C1/C2/C3 Number of Protected Pairs 4 Pairs (8 Conductors) Nominal Operating Voltage (DC) U n 5 V 48 V 5 V Maximum Continuous Operating Voltage (DC) U c 6 V 58 V 6 V C1 Nominal Discharge Current (8/20 µs) (Line-Line) I n 300A 60 A 300 A C2 Total Discharge Current (8/20 µs) (Lines-Ground) I max 1kA 250 A 1 ka Voltage Protection Level at I n (Line-Line) U p 35 V 150 V 35 V (Lines-Ground) 350 V 550 V 350 V esponse Time Overvoltage Protection t A < 1 ns Cut-off Frequency f G 100 MHz Mechanical Temperature ange -40 º C to +80 º C Connection Type Input/Output: J45 Sockets Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey, Extinguishing Degree V-0 Order Information Order Code NET 5 NET 5 PoE NET 5 STP NET 5 Series SIGNALING NETWOK SEIES

71 aydat NET 5 Series Internal Configuration Legend DB Diode Block Gas Discharge Tube PG Protective Grounding PG DB DB DB DB & Packaging 50.4 NET 5 NET 5 NET 5 PoE NET 5 STP Weight per Unit 56 g Packaging (Single Unit) mm 12 pieces SPDs for Local Area Networks 69

72 SPD for Multi-Port Category 5 LAN Networks aydat NET 5 19 Series LZ-xx NET 19 C1 C2 C3 IEC/EN Category: C1/C2/C3 (see Technical Data) Protection: All 4 Pairs Voltages: 5, 48 V DC Maximum Operating Voltage: 6, 58 V DC Frequency ange: 100 MHz, Cat 5, PoE Compatible Surge Discharge atings: I n : up to 300 A per Line Enclosure: 19" ack, Shielded, In-line Patch Termination: J45, Cat 5 Connectors Housing: Modular Design Options: 8, 16, 24 Port eplaceable 8 Port Module Compliance: IEC/EN The aydat NET 5 19 Series is intended to protect Local Area Networks (LAN) from overvoltage surges and electrostatic discharges created by switching transients in buildings. LAN systems are particularly prone to such disturbances because long cable lengths often behave like antennas to such atmospheric disturbances. It is designed to fit a 19 rack mount and can provide 8, 16 or 24 ports patching to UTP lines. PoE version aydat NET 5 19 PoE is designed to fulfill all versions of PoE applications compatible with standards IEEE 802.3af and IEEE 802.3at. Technical Data NET 5 19 NET 5 19 NET 5 19 PoE Electrical Type per IEC/EN C1/C2/C3 C1/C3 Number of Protected Ports 8, 16, 24 Ports Nominal Operating Voltage (DC) U n 5 V 48 V Maximum Continuous Operating Voltage (DC) U c 6 V 58 V C1 Nominal Discharge Current (8/20 µs) (Line-Line) I n 300A 60 A C2 Total Discharge Current (8/20 µs) (Lines-Ground) I max 1kA 250 A Voltage Protection Level at I n (Line-Line) U p 35 V 150 V (Lines-Ground) 350 V 350 V esponse Time Overvoltage Protection t A < 1 ns Cut-off Frequency f G 100 MHz Mechanical Temperature ange -40 º C to +80 º C Connection Type Input/Output: J45 Sockets Degree of Protection IEC/EN IP 20 Housing Material AI Mounting 19" ack Order Information Order Code NET 5 19 NET 5 19 PoE NET NET NET NET M (module) SIGNALING NETWOK SEIES

73 aydat NET 5 19 Series Internal Configuration PG POT1 IN POT DB DB DB DB DB DB DB DB Legend DB Diode Block Gas Discharge Tube PG Protective Grounding OUT & Packaging (19") NET 5 19 Series 8 Port 16 Port 24 Port Weight per Unit g g g Packaging (Single Unit) mm 1 pieces eplacement Surge Module for 8 Ports NET 5 19 M Series 8 Port 16 Port 24 Port Weight per Unit 146 g Packaging (Single Unit) mm 1 pieces NET 5 19 PoE Series 8 Port 16 Port 24 Port Weight per Unit g g g Packaging (Single Unit) mm 1 pieces eplacement Surge Module for 8 Ports NET 5 19 M PoE Series 8 Port 16 Port 24 Port Weight per Unit 146 g Packaging (Single Unit) mm 1 pieces SPDs for Local Area Networks 71

74 SPD for Combination Category 5 LAN & Power Networks aydat NET 5 PS Class III C1 C2 C3 ZE 200 NET The aydat NET 5 PS Series is intended to protect Local Area Networks (LAN) from overvoltage surges and electrostatic discharges created by switching transients in buildings. LAN systems are particularly prone to such disturbances because long cable lengths often behave like antennas to such atmospheric disturbances. IEC/EN/VDE Category: Class III/Type 3/C1/C2/C3 Protection: Power & Data Voltages: ± 5 V DC (data), 230 V AC (power) Maximum Operating Voltage: ± 6 V DC (data), 275 V AC (power) Frequency ange: 100 MHz, Cat 5 Compatible Surge Discharge atings: I n : 300 A per Line (data) I n : 3 ka L-N/L-PE (power) Enclosure: UTB In-line Patch, AC Power Outlet Termination: J45, Cat 5 Connectors (data) DIN CE(7) III, DIN CEE(7) IV (power) Housing: Compact Design Compliance: IEC/EN , It provides protection to all 4 lines in the UTP as well as protection to a 230 V AC power outlet. Equipotential equalization is provided between the LAN signal port and the AC power port. Technical Data NET 5 PS Power Data Electrical Type per IEC/EN , Class III/Type 3/D C1/C2/C3 Number of Protected Pairs 4 Pairs Nominal Operating Voltage (DC) U n 230 V AC / 50 Hz 5 V DC Maximum Continuous Operating Voltage (DC) U c 275 V AC / 50 Hz 6 V DC Nominal Discharge Current (8/20 µs) I n (L(N)-PE, L-N) 3 ka 300 A (Line-Line) Total Discharge Current (8/20 µs) I Total (L+N-PE) 10 ka 1 ka (Line-Ground) Open Circuit Voltage of Combination Wave Generator U oc (L(N)-PE, L-N) 6 kv (L+N-PPE) Voltage Protection Level at I n U p (L-N) < 1400 V 35 V (Line-Line) 10 kv (L(N)-PE) < 1750 V 350 V (Line-Ground) esponse Time Overvoltage Protection t A (L-N) < 25 ns < 1 ns (L(N)-PE) < 100 ns Cut-off Frequency f G 100 MHz Backup Fuse Mechanical Temperature ange Connection Type 16 A gl (needed when not present in network) DIN CE(7) III, DIN CEE(7) IV, Grounding Contact -40 º C to +80 º C Degree of Protection IEC/EN IP 20 Input/Output: J45 Sockets Housing Material Thermoplastic; Grey, Extinguishing Degree V-0 Status Indicator Order Information Order Code Disconnect Operation, Green & ed Light NET 5 PS SIGNALING NETWOK SEIES

75 aydat NET 5 PS Internal Configuration DB DB 6 4 Legend D Diode DB Diode Block Gas Discharge Tube MOV Metal Oxide Varistor esistor L N DB DB D ed MOV MOV & Packaging D D D D D D Green L N PE 47 NET 5 PS Weight per Unit 190 g Packaging (Single Unit) mm 12 pieces 72 SPDs for Local Area Networks 73

76 74 SIGNALING NETWOK SEIES

77 Surge Protective Devices (SPDs) for Data Protocols Data protocol SPDs were developed to protect different types of standard protocols. aydat S 485 aydat S 485 has been designed to protect all versions of S 485. It can be used for protection of S 422 and V.11 protocol as well. SPDs for Data Protocols 75

78 SPD for Data Protocols aydat S 485 VM-S 485 D1 C1 C2 C3 IEC/EN Category: D1/C1/C2/C3 Protection: Longitudinal, Transverse Coarse Protection: 2 2, 2 3 terminal Voltages: 5 V DC Maximum Operating Voltage: 6 V DC Serial esistance per Path: Ω per line Frequency ange: 1 MHz Surge Discharge atings: I n : 20 ka, I imp : 2.5 ka Enclosure: DIN TE, DIN ail Mount Terminals: Stranded mm 2 Housing: 16 Terminal, Compact Design Compliance: IEC/EN The aydat S 485 has been developed to protect 2 pair data transmission circuits using the S 485, S 422 and V.11 protocol. The circuit consists of two balanced pairs with equipotential equalization between them. Equipotential equalization is also provided between signal ground and protective ground to avoid equipment damage from ground potential rises during surge activity. Coarse protection is provided by a three terminal gas discharge tube while fine protection is provided using a high speed silicon stage, which provides both common (longitudinal) mode protection from each line to protective ground and differential (transverse) mode protection between each pair. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Technical Data S 485 Electrical Number of Protected Pairs 2(4 Conductors) Nominal Operating Voltage (DC) U n 5V Maximum Continuous Operating Voltage (DC) U c 6 V ated Load Current at 25ºC I L 500 ma C2 Nominal Discharge Current (8/20 µs) (Line-Line) I n 20 ka D1 Impulse Current (10/350 µs) I imp 2.5 ka esidual Voltage at 5 ka (8/20µs) (Line-Line) U res 20 V ated Spark Overvoltage (5, 6, 7 & 8-4, SG) 6.5 V 8.5 V (5-6 & 7-8) 6.5 V 8.5 V (5,6,7 & 8-2, PG) 78 V 116 V esponse Time Overvoltage Protection (5,6,7,8,SG) t A < 1 ns Thermal Protection (5,6,7,8) Yes Insulation esistance of Protection iso 6 kω Serial esistance per Path Ω Transverse Capacitance C < 2nF Cut-off Frequency f G > 1 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand mm 2 Terminal Screw Torque 2.0 Nm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Mounting IEC/EN mm DIN ail Order Information Order Code S SIGNALING NETWOK SEIES

79 aydat S 485 Internal Configuration 8 TC BD, 8 Legend BD Bi-directional TVS Diode Gas Discharge Tube PG Protective Grounding esistor SG Signal Grounding TC Thermo-clip SG, 4 3 PG, 2 TC BD BD, 7, 6, 5, SG, 4, 3, PG, 2 1, 1 & Packaging 90 S 485 Weight per Unit DIN Packaging (Single Unit) 114 g 2 TE mm 6 pieces SPDs for Data Protocols 77

80 78 SIGNALING NETWOK SEIES

81 Various Data Applications Surge Protective Devices (SPDs) The aydat PLP 24V surge protective device is intended for the protection of data circuits such as 4-20 ma current loops in industrial environments. aydat PLP 24 aydat GD The aydat GD is intended as a generic protector for data circuits. SPDs for Various Data Applications 79

82 Data Line Fitting SPD for Current Loops aydat PLP 24 C1 C2 C3 PLP-24V The aydat PLP 24 surge protective device is intended for the protection of data circuits such as 4-20 ma current loops, in industrial environments. The 3/4 inch pipe fitting makes this device ideal for applications such as the protection of field mount sensors, transducers and TUs. The unit can be configured in-line with the cable conduit and sensor terminals, or in a T configuration. The circuit consists of a multi-stage protector providing both common (longitudinal) mode and differential (transverse) mode protection. IEC/EN Category: C1/C2/C3 Mode of Protection: Longitudinal, Transverse Coarse Protection: 3 Terminal Voltages: 24 V DC Maximum Operating Voltage: 28 V DC Frequency ange: 3.0 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Serial esistance per Path: < 5 Ω per line Series Load Current: 145 ma Enclosure: 3/4 " Stainless Steel Fitting Conduit Terminals: Stranded to 2.5 mm 2 Housing: In-line 3/4 Conduit Fitting Compliance: IEC/EN Coarse protection is provided by a three terminal gas discharge tube, while fine protection is provided using a high speed silicon avalanche diode or metal oxide varistor stage. Care is taken to ensure coordination between these two stages without voltage or surge current blind spots occurring. Thermal protection is provided to reduce the hazards of thermal runaway should there be an inadvertent mains incursion fault. Technical Data PLP 24 PLP 24 V Electrical Number of Protected Pairs 1 (2 conductors) Nominal Operating Voltage (DC) U n 24 V Maximum Continuous Operating Voltage (DC) U c 28 V ated Load Current at 25ºC I L 145 ma C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at 5 ka (8/20 µs) (Line-Line) U res < 59 V ated Spark Overvoltage (Line-Ground) V (Line-Line) V esponse Time Overvoltage Protection t A < 1 ns Insulation esistance of the Protection iso 28 MΩ Serial esistance per Path < 5.0 Ω Transverse Capacitance C < 3 nf Cut-off Frequency f G 3 MHz Mechanical Temperature ange -40 º C to +80 º C Terminal Cross Section Multi-strand 2.5 mm 2 Degree of Protection IEC/EN IP 55 Housing Material Stainless Steel Mounting IEC/EN On pipe 3/4 inch Order Information Order Code PLP SIGNALING NETWOK SEIES

83 aydat PLP 24 Internal Configuration Legend DB Diode Block Gas Discharge Tube L Inductor MOV Metal Oxide Varistor PG Protective Grounding esistor LINE a PG b L L L MOV MOV L DB EQUIP, a, b & Packaging PLP 24 Weight per Unit Packaging (Single Unit) 324 g mm 8 pieces SPDs for Various Data Applications 81

84 SPD with Terminal Connection for Data Circuits aydat GD C1 C2 C3 IM-GD IEC/EN Category: C1/C2/C3 Mode of Protection: Transverse, Differential Voltages: 110 V DC Maximum Operating Voltage: 170 V DC Surge Discharge atings: I n : 5 ka, I max : 10 ka Series Load Current: 6 A Enclosure: PCB Hybrid Terminals: Flying Leads or Screw Terminals Housing: Compact Design Compliance: IEC/EN The aydat GD Series is intended as a generic protector for data circuits. It provides coarse protection via a three terminal gas discharge tube. An internal thermal disconnector provides protection during mains incursion. Technical Data GD Electrical Number of Protected Pairs 1 (2 conductors) Nominal Operating Voltage (DC) U n 110 V Maximum Continuous Operating Voltage (DC) U c 170 V ated Load Current at 25ºC I L 6 A C2 Nominal Discharge Current (8/20 µs) I n 5 ka Maximum Discharge Current (8/20 µs) I max 10 ka esidual Voltage at 5 ka (8/20 µs) U res < 700 V ated Spark Overvoltage (Line-Ground) V (Line-Line) V esponse Time Overvoltage Protection t A < 100 ns Thermal Protection Yes Insulation esistance of the Protection iso 1 GΩ Transverse Capacitance C < 1 pf Cut-off Frequency f G 30 MHz Mechanical Temperature ange -40 º C to +80 º C LIne Conductors Cross Section 0.5 mm 2 Ground Conductor Cross Section 0.75 mm 2 Connecting Conductor Length 150 mm Degree of Protection IEC/EN IP 20 Housing Material Thermoplastic; Grey; Extinguishing Degree V-0 Order Information Order Code GD SIGNALING NETWOK SEIES

85 aydat GD Internal Configuration TC Legend Gas Discharge Tube PG Protective Grounding TC Thermo-clip PG & Packaging GD Weight per Unit Packaging (Single Unit) 12 g mm 30 pieces SPDs for Various Data Applications 83

86 84 SIGNALING NETWOK SEIES

87 Surge Protective Devices (SPDs) for Coaxial & F Systems Coaxial protection devices are intended to protect TV sets, aerial amplifiers, CCTV/ CATV systems as well as F antenna systems and are suitable for frequencies up to 6 GHz. The careful design, low capacitance gas discharge arresters and high quality termination connectors, ensures a minimum of insertion loss throughout the frequency band. aycox BNC aycox IEC, F aydat CP BNC aydat CP 7/16 aydat CP N aydat CP N-6G aydat CP TNC-6G aydat CP UHF aydat CP F75 aydat CP TV75 aydat CP L/4-7/16 aydat CP L/4-N SPDs for Coaxial & F Systems 85

88 Coaxial SPD for Analog Video Surveillance Systems aycox BNC Series C1 C2 C3 ZV-BNC Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Voltages: 10, 24 V DC Maximum Operating Voltage: 12, 24 V DC Frequency ange: 100 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Series Load Current: 100 ma Enclosure: In-line Installation Termination: BNC Connectors Housing: Shielded Enclosure Compliance: IEC/EN The aycox BNC Series is intended to protect Arcnet computer networks and CCTV coaxial video signals. Both coarse and fine protection is provided in a shielded, impedance matched, compact in-line enclosure. Protection is provided by core-shield and shield-protective ground. The design ensures minimum of capacitance loading, thereby ensuring a high operating bandwidth while providing efficient clamping against transient voltages. Technical Data BNC BNC 5 BNC 12 Electrical Nominal Operating Voltage (DC) U n 10 V 24 V Maximum Continuous Operating Voltage (DC) U c 12 V 28 V ated Operating Current at 25ºC I L 100 ma C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at 5 ka (8/20µs) (Wire-Shield) U res < 35 V < 65 V ated Spark Overvoltage (Wire-Shield) 13.5 V 16.5 V 30 V 36 V (Shield-Ground) 72 V 108 V 72 V 108 V esponse Time Overvoltage Protection (Wire-Shield) t A < 10 ns (Shield-Ground) < 100 ns Insulation esistance of Protection (Wire-Shield) iso 10 MΩ 28 MΩ (Shield-Ground) 1 GΩ Serial esistance per Path 9 11 Ω Transverse Capacitance (Wire-Shield) C 30 pf (Shield-Ground) 1 pf Cut-off Frequency f G 100 MHz Transmission ate 16 Mbit/s Mechanical Temperature ange -40 º C to +80 º C Connection BNC Connector Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code BNC 5 BNC 12 BNC xx SIGNALING NETWOK SEIES

89 aycox BNC Series Internal Configuration C IN OUT BD Legend BD Bi-directional TVS Diode C Capacitor D Diode Gas Discharge Tube PG Protective Grounding esistor PG & Packaging BNC BNC 5 BNC 12 Weight per Unit 58 g Packaging (Single Unit) SPDs for Coaxial & F Systems 87

90 Coaxial SPD for TV & Cable TV aycox IEC 48, F 48 C1 C2 C3 ZV1, ZV1-F IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Voltages: 148 V DC Maximum Operating Voltage: 60 V DC Frequency ange: MHz Surge Discharge atings: I n : 5 ka, I max : 10 ka Series Load Current: 100 ma Termination: IEC TV or F Connectors Housing: In-line Installation, Shielded Enclosure Compliance: IEC/EN The aerial adapters aycox IEC 48 and F 48 are intended for the protection of TV sets, aerial amplifiers and cable television CATV. It should be connected to the aerial input of the TV set, with the coaxial cable from the aerial plugged into the other side. It should be grounded to the protective earth conductor of the housing installation. In the case of an individual aerial system with an individual aerial amplifier it is recommended to install an additional aerial adapter which should be connected in the same way as for the TV set. The aerial adapter is not suitable for outdoor installation or installation in very damp places. Technical Data IEC 48 F 48 Electrical Nominal Operating Voltage (DC) U n 48 V Maximum Continuous Operating Voltage (DC) U c 60 V ated Operating Current at 25ºC I L 100 ma C2 Nominal Discharge Current (8/20 µs) I n 5 ka Maximum Discharge Current (8/20 µs) I max 10 ka esidual Voltage at 5 ka (8/20µs) U res < 500 V ated Spark Overvoltage (Wire-Shield) 90 V 110 V esponse Time Overvoltage Protection (Wire-Shield) t A < 25 ns Insulation esistance of Protection (Wire-Shield) iso 6 MΩ Serial esistance per Path < 0.1 Ω Frequency ange f G MHz Mechanical Temperature ange -40 º C to +80 º C Connection TV Connector F Connector Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code IEC 48 F 48 XXX SIGNALING NETWOK SEIES

91 aycox IEC 48, F 48 Internal Configuration L LINE MOV MOV C EQUIP Legend C Capacitor L Inductor MOV Metal Oxide Varistor PG Protective Grounding PG & Packaging 17 IEC 48 F 48 Weight per Unit 32 g 78 Packaging (Single Unit) IEC F 48 SPDs for Coaxial & F Systems 89

92 In-line SPD for Coaxial & F Systems aydat CP BNC Series C1 C2 C3 CCP-BNC Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 70, 180, 280 V Maximum Peak Power: 40, 125, 300 W Frequency ange: DC 2.6 GHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 50 Ω Insertion Loss: < 0.4 db eturn Loss: > 20 db Termination: BNC Type (F-F, M-F) Housing: In-line Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP BNC Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to 2.6 GHz. It is designed as an in-line unit allowing ease of installation. The careful design, low capacitance gas discharge arresters and high quality BNC-type termination connectors, ensures a minimum of insertion loss throughout the frequency band. Transfer power is 40 W to 300 W continuous, depending on the coaxial cable protector voltage. The CP coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP BNC 70 V 180 V 280 V Electrical Maximum Continuous Operating Voltage U c 70 V 180 V 280 V Maximum Peak Power P max 40 W 125 W 300 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 600 V < 700 V < 900 V Impedance Z 50 Ω Insertion Loss I L < 0.4 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G GHz Mechanical Temperature ange -40 º C to +80 º C Connection BNC Female/Female BNC Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code 70 V 180 V 280 V CP BNC-FF-xxx CP BNC-MF-xxx SIGNALING NETWOK SEIES

93 aydat CP BNC Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging CP BNC-FF-xxx CP BNC-MF-xxx CP BNC 70 V 180 V 280 V 70 V 180 V 280 V 25 Weight per Unit 106 g 114 g Packaging (Single Unit) mm CP BNC-FF pieces 25 CP BNC-MF 57 SPDs for Coaxial & F Systems 91

94 In-line SPD for Coaxial & F Systems aydat CP 7/16 Series C1 C2 C3 CCP-7/16 Series The aydat CP 7/16 Series of coaxial surge protectors is intended to protect base station F antenna systems and is suitable for frequencies from DC to 2.5 GHz. It is designed for bulkhead or in-line installation. The careful design, low capacitance gas discharge arresters and high quality 7/16 - type termination connectors ensure a minimum of insertion loss throughout the frequency band. IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 70, 180, 280 V Maximum Peak Power: 40, 125, 300 W Frequency ange: DC 2.5 GHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 50 Ω Insertion Loss: < 0.2 db eturn Loss: > 20 db Termination: 7/16 Type (M-F) Housing: Bulkhead Installation, Shielded Enclosure Compliance: IEC/EN Transfer power is 40 W to 300 W continuous depending on coaxial cable protector voltage. The CP 7/16 coaxial cable protector is designed in accordance with the IEC : 2009 standards and regulations. is replaceable. The unit should be solidly mounted to the coaxial feed-through bulkhead, which should in turn present a low impedance path to ground for direct or partial lightning currents. Technical Data CP 7/16-MF 70 V 180 V 280 V Electrical Maximum Continuous Operating Voltage U c 70 V 180 V 280 V Maximum Peak Power P max 40 W 125 W 300 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 600 V < 700 V < 900 V Impedance Z 50 Ω Insertion Loss I L < 0.2 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G GHz Mechanical Temperature ange -40 º C to +80 º C Connection 7/16 Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code 70 V 180 V 280 V CP 7/16-MF-xxx SIGNALING NETWOK SEIES

95 aydat CP 7/16 Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging 32 CP 7/16-MF 70 V 180 V 280 V Weight per Unit 218 g Packaging (Single Unit) mm 100 pieces 70 SPDs for Coaxial & F Systems 93

96 In-line SPD for Coaxial & F Systems aydat CP N Series C1 C2 C3 CCP-N Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 70, 180, 280 V Maximum Peak Power: 40, 125, 300 W Frequency ange: DC 2.6 GHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 50 Ω Insertion Loss: < 0.4 db eturn Loss: > 20 db Termination: N Type (F-F, M-F) Housing: In-line Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP N Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to 2.6 GHz. It is designed as an in-line unit allowing ease of installation. The careful design, low capacitance gas discharge arresters and high quality N-type termination connectors, ensures a minimum of insertion loss throughout the frequency band. Transfer power is 40 W to 300 W continuous, depending on the coaxial cable protector voltage. The CP N coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP-N 70 V 180 V 280 V Electrical Maximum Continuous Operating Voltage U c 70 V 180 V 280 V Maximum Peak Power P max 40 W 125 W 300 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 600 V < 700 V < 900 V Impedance Z 50 Ω Insertion Loss I L < 0.4 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G GHz Mechanical Temperature ange -40 º C to +80 º C Connection N Female/Female N Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code 70 V 180 V 280 V CP N-FF-xxx CP N-MF-xxx SIGNALING NETWOK SEIES

97 aydat CP N Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging CP N-FF CP N-FF-xxx CP N-MF-xxx CP N 70 V 180 V 280 V 70 V 180 V 280 V Weight per Unit 138 g 142 g Packaging (Single Unit) mm 100 pieces 25 CP N-MF 60 SPDs for Coaxial & F Systems 95

98 In-line SPD for High Frequency Coaxial & F Systems aydat CP N-6G Series C1 C2 C3 CCP-N-6G Series The aydat CP N-6G Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to 6.0 GHz. It is designed as an in-line unit allowing ease of installation. The careful design, low capacitance gas discharge arresters and high quality N-type termination connectors, ensures a minimum of insertion loss throughout the frequency band. IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 180 V Maximum Peak Power: 125 W Frequency ange: DC 6.0 GHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 50 Ω Insertion Loss: < 0.4 db eturn Loss: > 20 db Termination: N Type (F-F, M-F) Housing: Bulkhead Installation, Shielded Enclosure Compliance: IEC/EN Transfer power is 125 W continuous. The CP N-6G coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP N-6G CP N-6G-FF CP N-6G-MF Electrical Maximum Continuous Operating Voltage U c 180 V Maximum Peak Power P max 125 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 700 V Impedance Z 50 Ω Insertion Loss I L < 0.4 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G GHz Mechanical Temperature ange -40 º C to +80 º C Connection N Female/Female N Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code CP N-6G-XX SIGNALING NETWOK SEIES

99 aydat CP N-6G Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging CP N-6G-FF CP N-6G CP N-6G-FF CP N-6G-MF Weight per Unit 132 g 130 g Packaging (Single Unit) mm 100 pieces CP N-6G-MF SPDs for Coaxial & F Systems 97

100 In-line SPD for High Frequency Coaxial & F Systems aydat CP TNC-6G Series C1 C2 C3 CCP-TNC-6G Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 180 V Maximum Peak Power: 125 W Frequency ange: DC 6.0 GHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 50 Ω Insertion Loss: < 0.4 db eturn Loss: > 20 db Termination: TNC Type (F-F, M-F) Housing: In-line Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP TNC-6G Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to 6.0 GHz. It is designed as an in-line unit allowing ease of installation. The careful design, low capacitance gas discharge arresters and high quality TNC-type termination connectors, ensures a minimum of insertion loss throughout the frequency band. Transfer power is 125 W continuous. The CP TNC-6G coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP TNC-6G CP TNC-6G-FF CP TNC-6G-MF Electrical Maximum Continuous Operating Voltage U c 180 V Maximum Peak Power P max 125 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 700 V Impedance Z 50 Ω Insertion Loss I L < 0.4 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G GHz Mechanical Temperature ange -40 º C to +80 º C Connection TNC Female/Female TNC Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code CP TNC-6G-XX SIGNALING NETWOK SEIES

101 aydat CP TNC-6G Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging 1/2"-28UNEF 7/16"-28UNEF 68±0.5 ø22.8 CP TNC-6G CP TNC-6G-FF CP TNC-6G-MF Weight per Unit 130 g 128 g Packaging (Single Unit) mm 100 pieces CP TNC-6G-FF 1/2"-28UNEF 7/16"-28UNEF 68±0.5 7/16"-28UNEF ø14.5 ø22.8 CP TNC-6G-MF SPDs for Coaxial & F Systems 99

102 In-line SPD for Coaxial & F Systems aydat CP UHF Series C1 C2 C3 CCP-UHF Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 70, 180, 280 V Maximum Peak Power: 40, 125, 300 W Frequency ange: DC 600 MHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 50 Ω Insertion Loss: < 0.4 db eturn Loss: > 20 db Termination: UHF Type (F-F, M-F) Housing: In-line Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP UHF Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to 600 MHz. It is designed as an in-line unit allowing ease of installation. The careful design, low capacitance gas discharge arresters and high quality UHF-type termination connectors, ensures a minimum of insertion loss throughout the frequency band. Transfer power is 40 W to 300 W continuous, depending on the coaxial cable protector voltage. The CP UHF coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP UHF 70 V 180 V 280 V Electrical Maximum Continuous Operating Voltage U c 70 V 180 V 280 V Maximum Peak Power P max 40 W 125 W 300 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 600 V < 700 V < 900 V Impedance Z 50 Ω Insertion Loss I L < 0.4 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G MHz Mechanical Temperature ange -40 º C to +80 º C Connection UHF Female/Female UHF Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code 70 V 180 V 280 V CP UHF-FF-xxx CP UHF-MF-xxx SIGNALING NETWOK SEIES

103 aydat CP UHF Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging CP UHF-FF CP UHF-FF-xxx CP UHF-MF-xxx CP UHF 70 V 180 V 280 V 70 V 180 V 280 V Weight per Unit 104 g 104 g Packaging (Single Unit) mm 100 pieces 25 CP UHF-MF 65 SPDs for Coaxial & F Systems 101

104 In-line SPD for Coaxial & F Systems aydat CP F75 Series C1 C2 C3 CCP-F Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 70, 180 V Maximum Peak Power: 40, 125 W Frequency ange: DC 2.0 GHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 75 Ω Insertion Loss: < 0.4 db eturn Loss: > 20 db Termination: F Type (F-F, M-F) Housing: In-line Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP F Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to 2.0 GHz. It is eminently suitable for the protection of USA CCTV and CATV systems. It is designed as an in-line unit allowing ease of installation. The careful design, low capacitance gas discharge arresters and high quality F-type termination connectors, ensures a minimum of insertion loss throughout the frequency band. Transfer power is 40 W to 125 W continuous, depending on the coaxial cable protector voltage. The CP F coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP F75 70 V 180 V Electrical Maximum Continuous Operating Voltage U c 70 V 180 V Maximum Peak Power P max 40 W 125 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 600 V < 700 V Impedance Z 75 Ω Insertion Loss I L < 0.4 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G GHz Mechanical Temperature ange -40 º C to +80 º C Connection F Female/Female F Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code 70 V 180 V CP F75-FF-xxx CP F75-MF-xxx SIGNALING NETWOK SEIES

105 aydat CP F75 Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging CP F75-FF CP F75-FF CP F75-MF CP F75 70 V 180 V 70 V 180 V Weight per Unit 80 g 84 g Packaging (Single Unit) mm 100 pieces 25 CP F75-MF 53 SPDs for Coaxial & F Systems 103

106 In-line SPD for Coaxial & F Systems aydat CP TV75 Series C1 C2 C3 CCP-TV Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Operating Voltage: 70, 180 V Maximum Peak Power: 40, 125 W Frequency ange: DC 2.0 GHz Surge Discharge atings: I n : 10 ka, I max : 20 ka Impedance: 75 Ω Insertion Loss: < 0.4 db eturn Loss: > 20 db Termination: TV Type (F-F, M-F) Housing: In-line Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP TV Series of coaxial surge protectors is intended to protect F antenna systems terminating in TV-type connections and is suitable for frequencies from DC to 2.0 GHz. It is eminently suitable for the protection of European CCTV and CATV systems. It is designed as an in-line unit allowing ease of installation. The careful design, low capacitance gas discharge arresters and high quality TV-type termination connectors ensures a minimum of insertion loss throughout the frequency band. Transfer power is 40 W to 125 W continuous, depending on the coaxial cable protector voltage. The CP TV coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP TV75 70 V 180 V Electrical Maximum Continuous Operating Voltage U c 70 V 180 V Maximum Peak Power P max 40 W 125 W C2 Nominal Discharge Current (8/20 µs) I n 10 ka Maximum Discharge Current (8/20 µs) I max 20 ka esidual Voltage at (1 kv/µs) U res < 600 V < 700 V Impedance Z 75 Ω Insertion Loss I L < 0.4 db eturn Loss L > 20 db Insulation esistance of Protection iso > 10 GΩ Frequency ange f G GHz Mechanical Temperature ange -40 º C to +80 º C Connection TV Female/Female TV Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code 70 V 180 V CP TV75-FF-xx CP TV75-MF-xx SIGNALING NETWOK SEIES

107 aydat CP TV75 Series Internal Configuration LINE LINE SHIELD SHIELD PE Legend Gas Discharge Tube & Packaging CP TV75-FF CP TV75-FF-xxx CP TV75-MF-xxx CP TV75 70 V 180 V 70 V 180 V Weight per Unit 80 g 82 g Packaging (Single Unit) mm 100 pieces 25 CP TV75-MF 50 SPDs for Coaxial & F Systems 105

108 In-line SPD for High Frequency Coaxial & F Systems aydat CP L/4-7/16 Series C1 C2 C3 CCP-L/4-7/16 Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Peak Power: 500 W Frequency ange: MHz, GHz Surge Discharge atings: I n : 15 ka, I max : 30 ka Impedance: 50 Ω Insertion Loss: < 0.2 db eturn Loss: > 20 db Termination: L/4-7/16 Type (F-F, M-F) Housing: Bulkhead Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP L/4-7/16 Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to MHz, GHz. It is designed for a bulkhead or in-line installation. The careful design, low intermodulation and high quality 7/16-type termination connectors ensures a minimum of insertion loss throughout the frequency band. Transfer power is 500 W continuous. The CP L/4-7/16 coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP L/4-7/16 CP L/4-7/16-FF CP L/4-7/16-MF Electrical Maximum Peak Power P max 500 W C2 Nominal Discharge Current (8/20 µs) I n 15 ka Maximum Discharge Current (8/20 µs) I max 30 ka Voltage Protection Level U p < 100 V Impedance Z 50 Ω Insertion Loss I L < 0.2 db eturn Loss L > 20 db Frequency ange f G MHz, GHz Mechanical Temperature ange -40 º C to +80 º C Connection L/4-7/16 Female/Female L/4-7/16 Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code CP L/4-7/16-XX SIGNALING NETWOK SEIES

109 aydat CP L/4-7/16 Series Internal Configuration /4 PE & Packaging 63 CP L/4-7/16 CP L/4-7/16-FF CP L/4-7/16-MF Weight per Unit 320 g 312 g Packaging (Single Unit) mm 100 pieces 29 CP L/4-7/16-FF CP L/4-7/16-MF SPDs for Coaxial & F Systems 107

110 In-line SPD for High Frequency Coaxial & F Systems aydat CP L/4-N Series C1 C2 C3 CCP-L/4-N Series IEC/EN Category: C1/C2/C3 Protection: Impedance Matched Maximum Peak Power: 500 W Frequency ange: MHz, GHz Surge Discharge atings: I n : 15 ka, I max : 30 ka Impedance: 50 Ω Insertion Loss: < 0.2 db eturn Loss: > 20 db Termination: L/4-N Type (F-F, M-F) Housing: Bulkhead Installation, Shielded Enclosure Compliance: IEC/EN The aydat CP L/4-N Series of coaxial surge protectors is intended to protect F antenna systems and is suitable for frequencies from DC to MHz, GHz. It is designed for bulkhead or in-line installation. The careful design, low intermodulation and high quality N-type termination connectors ensures a minimum of insertion loss throughout the frequency band. Transfer power is 500 W continuous. The CP L/4-N coaxial cable protector is designed in accordance with IEC : 2009 standards and regulations. A grounding stud is provided which should be connected to the system ground or coaxial feed-through bulkhead, as directly as possible. Technical Data CP L/4-N CP L/4-N-FF CP L/4-N-MF Electrical Maximum Peak Power P max 500 W C2 Nominal Discharge Current (8/20 µs) I n 15 ka Maximum Discharge Current (8/20 µs) I max 30 ka Voltage Protection Level U p < 100 V Impedance Z 50 Ω Insertion Loss I L < 0.2 db eturn Loss L > 20 db Frequency ange f G MHz, GHz Mechanical Temperature ange -40 º C to +80 º C Connection L/4-N Female/Female L/4-N Male/Female Degree of Protection IEC/EN IP 20 Housing Material Metal Order Information Order Code CP L/4-N-XX SIGNALING NETWOK SEIES

111 aydat CP L/4-N Series Internal Configuration /4 PE & Packaging CP L/4-N CP L/4-N-FF CP L/4-N-MF Weight per Unit 282 g 266 g Packaging (Single Unit) mm 100 pieces 74 CP L/4-N-FF CP L/4-N-MF SPDs for Coaxial & F Systems 109

112 Selection Guide Signal/Data Transmission Signal Type ecommended SPD Page 0-20 ma, 4-20 ma Current Loops SPH SGH SCH SUHI PLP ACNET aycox BNC 5 86 Binary Signals SPH SLH-2-5 SLH SLH-4-5 SLH SGH-3-5 SGH SSH-3-5 SSH SUI-4-5 SUI SCH-2-5 SCH SCH-4-5 SCH STD-2-5 STD BITBUS (IEEE-1118) SBH SLH SLH SGH SSH CAN Bus (Data Line) SBH SLH SLH SGH SSH CAN Bus (Power Line) PSC Protec DMD 20/24 60 CAN Bus (Data + Power Line) SUH-2-30PS 50 CCTV aycox BNC ControlNet aycox BNC Data Highway Plus SBH SLH SLH DeviceNet (Data Line) SBH SLH SLH SGH DeviceNet (Power Line) PSC Protec DMD 20/24 60 DeviceNet (Data + Power Line) SUH-2-30PS 50 EIB GD 82 Ex(i) Circuits Ex-2 54 PLP Ex 56 Ethernet CAT 5 NET 6 66 NET 5 68 NET 5 PS 72 NET Ethernet CAT 6 NET 6 66 FDDI, CDDI NET 6 66 NET 5 68 NET Signal Type ecommended SPD Page Fieldbus (Ex) Ex-2 54 PLP Ex 56 Genius Bus SLH SLH SSH Industrial Ethernet NET 6 66 INTEBUS Inline (emote) SBH SPH SLH SCH SCH SSH INTEBUS Inline (I/O) SLH SCH SUI SUHI INTEBUS Field Multiplexer SBH SGH KNX Bus GD 82 Local Operating Network (LON) SBH SLH SLH SGH Modbus SBH SLH SLH SGH SSH Opto Interface SPH SBH SLH SCH SSH STD SUHI SUI SSH Power Over Ethernet (PoE) NET 6 66 NET 5 PoE 68 NET 5 19 PoE 70 Power Supply (AC or DC) PSC-2-12 PSC Protec DMD 20/24 Protec DMD 20/ POFIBUS DP SBH SLH SLH SGH SSH SIGNALING NETWOK SEIES

113 Signal Type ecommended SPD Page POFIBUS PA SBH SPH SGH SLH SLH SSH POFIBUS PA (Ex) Ex-2 54 PLP Ex 56 S 232 SBH SGH S 422, V.11, X.21 SLH SCH S S 423A SLH SCH S S 485 SBH Synchronous Data Link Control (SDLC) SSH SLH SCH SUI S SLH SLH SGH SSH SINEC L1 SBH SLH SLH SGH SSH SINEC L2 SBH SLH SLH SGH SSH Suconet SLH S Voice Over IP (VoIP) NET 6 66 NET 5 PoE 68 NET 5 19 PoE 70 Temperature Measurement SBH SPH SGH SCH SUHI SUI PLP SSH Signal Type ecommended SPD Page Token ing NET 6 66 NET 5 68 NET TTL SGH SLH SSH SCH Telecommunications Signal Type ecommended SPD Page ADSL SLH SPH ADSL 2+ SLH SPH E1 NET 6 66 SPH SLH SUI G.703/G.704 NET 6 66 SPH SLH SUI HDSL SPH SLH SUI NET 6 66 ISDN S O SCH SUI NET 6 66 ISDN U O SLH SPH POTS STD SUHI SLH SPH SDSL SCH SUI NET 6 66 SHDSL SGH SLH SLH T-DSL SLH SPH VDSL SLH SPH Selection Guide 111

114 112 SIGNALING NETWOK SEIES

115 Applications Wastewater Management Level Measurement Equipment / POFIBUS PA PH Measurement Equipment / POFIBUS DP Flow Measurement Equipment / 4-20mA Temperature Measurement / Pt1000 SBH SPH SGH SLH SBH SLH SGH SSH SPH SGH SCH SUHI PLP SPH SGH SCH SUHI SUI PLP SSH Security Agencies Analog Video aycox BNC PoE Video NET 6 66 Voice Over IP (VoIP) NET 6 66 NET -5 PoE 68 NET 5 19 PoE 70 Industrial Automation Industrial Buses SBH-3-5 SBH SPH SLH-2-5 SLH SLH-4-5 SLH SGH-3-5 SGH SSH-3-5 SSH SUI-4-5 SUI SCH-2-5 SCH SCH-4-5 SCH STD-2-5 STD NET 6 66 Ethernet NET 6 66 NET 5 68 NET 5 PS 72 NET Industrial Ethernet NET 6 66 Typical Applications 113

116 Wind Systems Wind speed Measurement / 4-20mA SPH SGH SCH SUHI Temperature Measurement / Pt1000 SPH SUHI SGH SCH SUI Data Transmission / S 485 SSH SLH SCH SUI S Data Transmission / Ethernet NET 6 66 POTS / ISDN / DSL Line SLH SPH Photovoltaic Systems Wind Speed Measurement / 4-20mA SPH SGH SCH SUHI Temperature Measurement / Pt1000 SPH SGH SCH SUHI SUI SSH Data Transmission / S 485 SBH SLH SCH SUI S POTS / ISDN / DSL Line SLH SPH SIGNALING NETWOK SEIES

117 Telecommunication Transmitter Systems GSM, UMTS, LTE, GPS, adio Systems CP N-6G-MF 96 CP N-6G-FF 96 CP TNC-6G-MF 98 CP TNC-6G-FF 98 CP 7/16-MF 92 CP 7/16-FF 92 CP N-MF 94 CP N-FF 94 GMS, UMTS, LTE CP L/4-7/16-MF 106 CP L/4-7/16-FF 106 CP L/4-N-MF 108 CP L/4-N-FF 108 adio Systems CP UHF-MF 100 CP UHF-FF 100 Oil & Gas Industry; Biogas Plants Ex Zone Flow Measurement Ex PLP-24Ex 56 PLP2-24Ex 56 Pressure Measurement Ex PLP-24Ex 56 PLP2-24Ex 56 Level Measurement Ex PLP-24Ex 56 PLP2-24Ex 56 Outside Ex Zones Flow Measurement SGH SGH Pressure Measurement SGH SGH Level Measurement SGH SGH LAN Protection NET 6 66 Typical Applications 115

118 116 SIGNALING NETWOK SEIES

119 Product Index New Product Name New Order Code Product D1 C1 C2 C3 Modular and Compact SPD for Data/Signal Lines Legacy Product Names & Order Codes Order Code DIN aydat SLH SMH-TC 5V /3TE 14 aydat SLH SMH-TC 12V /3TE 14 aydat SLH SMH-TC 15V /3TE 14 aydat SLH SMH-TC 24V /3TE 14 aydat SLH SMH-TC 30V /3TE 14 aydat SLH SMH-TC 48V /3TE 14 aydat SLH SMH-TC 60V /3TE 14 aydat SLH SMH-TC 110V /3TE 14 aydat SLH-2-5M Module SMH-TC 5V /3TE 14 aydat SLH-2-12M Module SMH-TC 12V /3TE 14 aydat SLH-2-15M Module SMH-TC 15V /3TE 14 aydat SLH-2-24M Module SMH-TC 24V /3TE 14 aydat SLH-2-30M Module SMH-TC 30V /3TE 14 aydat SLH-2-48M Module SMH-TC 48V /3TE 14 aydat SLH-2-60M Module SMH-TC 60V /3TE 14 aydat SLH-2-110M Module SMH-TC 110V /3TE 14 aydat SLH-2-5Q /3TE 14 aydat SLH-2-12Q /3TE 14 aydat SLH-2-15Q /3TE 14 aydat SLH-2-24Q /3TE 14 aydat SLH-2-30Q /3TE 14 aydat SLH-2-48Q /3TE 14 aydat SLH-2-60Q /3TE 14 aydat SLH-2-110Q /3TE 14 aydat SLH SMH2-TC 5V /3TE 16 aydat SLH SMH2-TC 12V /3TE 16 aydat SLH SMH2-TC 15V /3TE 16 aydat SLH SMH2-TC 24V /3TE 16 aydat SLH SMH2-TC 30V /3TE 16 aydat SLH SMH2-TC 48V /3TE 16 aydat SLH SMH2-TC 60V /3TE 16 aydat SLH SMH2-TC 110V /3TE 16 aydat SLH-4-5M Module SMH2-TC 5V /3TE 16 aydat SLH-4-12M Module SMH2-TC 12V /3TE 16 aydat SLH-4-15M Module SMH2-TC 15V /3TE 16 aydat SLH-4-24M Module SMH2-TC 24V /3TE 16 aydat SLH-4-30M Module SMH2-TC 30V /3TE 16 aydat SLH-4-48M Module SMH2-TC 48V /3TE 16 aydat SLH-4-60M Module SMH2-TC 60V /3TE 16 aydat SLH-4-110M Module SMH2-TC 110V /3TE 16 aydat SLH-4-5Q /3TE 16 aydat SLH-4-12Q /3TE 16 aydat SLH-4-15Q /3TE 16 aydat SLH-4-24Q /3TE 16 aydat SLH-4-30Q /3TE 16 aydat SLH-4-48Q /3TE 16 aydat SLH-4-60Q /3TE 16 aydat SLH-4-110Q /3TE 16 aydat SPH /3TE 18 aydat SPH /3TE 18 aydat SPH-2-30M /3TE 18 aydat SPH-2-230M /3TE 18 aydat SPH-2-30Q /3TE 18 aydat SPH-2-230Q /3TE 18 aydat SPH /3TE 20 aydat SPH-4-30M /3TE 20 aydat SPH-4-30Q /3TE 20 Page Product Index 117

120 Product Index New Product Name New Order Code Product D1 C1 C2 C3 Modular and Compact SPD for Data/Signal Lines Legacy Product Names & Order Codes Order Code DIN aydat SGH SMH-SG 5V /3TE 22 aydat SGH SMH-SG 12V /3TE 22 aydat SGH SMH-SG 15V /3TE 22 aydat SGH SMH-SG 24V /3TE 22 aydat SGH SMH-SG 30V /3TE 22 aydat SGH SMH-SG 48V /3TE 22 aydat SGH SMH-SG 60V /3TE 22 aydat SGH SMH-SG 110V /3TE 22 aydat SGH-3-5M Module SMH-SG 5V /3TE 22 aydat SGH-3-12M Module SMH-SG 12V /3TE 22 aydat SGH-3-15M Module SMH-SG 15V /3TE 22 aydat SGH-3-24M Module SMH-SG 24V /3TE 22 aydat SGH-3-30M Module SMH-SG 30V /3TE 22 aydat SGH-3-48M Module SMH-SG 48V /3TE 22 aydat SGH-3-60M Module SMH-SG 60V /3TE 22 aydat SGH-3-110M Module SMH-SG 110V /3TE 22 aydat SBH /3TE 24 aydat SBH /3TE 24 aydat SBH /3TE 24 aydat SBH-3-5M /3TE 24 aydat SBH-3-12M /3TE 24 aydat SBH-3-30M /3TE 24 aydat SBH-3-5Q /3TE 24 aydat SBH-3-12Q /3TE 24 aydat SBH-3-30Q /3TE 24 aydat SSH SMH-SH 5V /3TE 26 aydat SSH SMH-SH 12V /3TE 26 aydat SSH SMH-SH 15V /3TE 26 aydat SSH SMH-SH 24V /3TE 26 aydat SSH SMH-SH 30V /3TE 26 aydat SSH SMH-SH 48V /3TE 26 aydat SSH SMH-SH 60V /3TE 26 aydat SSH SMH-SH 110V /3TE 26 aydat SSH-3-5M Module SMH-SH 5V /3TE 26 aydat SSH-3-12M Module SMH-SH 12V /3TE 26 aydat SSH-3-15M Module SMH-SH 15V /3TE 26 aydat SSH-3-24M Module SMH-SH 24V /3TE 26 aydat SSH-3-30M Module SMH-SH 30V /3TE 26 aydat SSH-3-48M Module SMH-SH 48V /3TE 26 aydat SSH-3-60M Module SMH-SH 60V /3TE 26 aydat SSH-3-110M Module SMH-SH 110V /3TE 26 aydat SSH-3-5Q /3TE 26 aydat SSH-3-12Q /3TE 26 aydat SSH-3-15Q /3TE 26 aydat SSH-3-24Q /3TE 26 aydat SSH-3-30Q /3TE 26 aydat SSH-3-48Q /3TE 26 aydat SSH-3-60Q /3TE 26 aydat SSH-3-110Q /3TE 26 aydat SH SMH-C 5V /3TE 28 aydat SH SMH-C 12V /3TE 28 aydat SH SMH-C 15V /3TE 28 aydat SH SMH-C 24V /3TE 28 aydat SH SMH-C 30V /3TE 28 aydat SH SMH-C 48V /3TE 28 aydat SH SMH-C 60V /3TE 28 aydat SH SMH-C 110V /3TE 28 aydat SH-2-5M Module SMH-C 5V /3TE 28 aydat SH-2-12M Module SMH-C 12V /3TE 28 aydat SH-2-15M Module SMH-C 15V /3TE 28 aydat SH-2-24M Module SMH-C 24V /3TE 28 aydat SH-2-30M Module SMH-C 30V /3TE 28 aydat SH-2-48M Module SMH-C 48V /3TE 28 aydat SH-2-60M Module SMH-C 60V /3TE 28 aydat SH-2-110M Module SMH-C 110V /3TE 28 Page 118 SIGNALING NETWOK SEIES

121 New Product Name New Order Code Product D1 C1 C2 C3 Modular and Compact SPD for Data/Signal Lines Legacy Product Names & Order Codes Order Code DIN aydat SUI SMI2 5V /3TE 30 aydat SUI SMI2 12V /3TE 30 aydat SUI SMI2 15V /3TE 30 aydat SUI SMI2 24V /3TE 30 aydat SUI SMI2 30V /3TE 30 aydat SUI SMI2 48V /3TE 30 aydat SUI SMI2 60V /3TE 30 aydat SUI SMI2 110V /3TE 30 aydat SUI-4-5M Module SMI2 5V /3TE 30 aydat SUI-4-12M Module SMI2 12V /3TE 30 aydat SUI-4-15M Module SMI2 15V /3TE 30 aydat SUI-4-24M Module SMI2 24V /3TE 30 aydat SUI-4-30M Module SMI2 30V /3TE 30 aydat SUI-4-48M Module SMI2 48V /3TE 30 aydat SUI-4-60M Module SMI2 60V /3TE 30 aydat SUI-4-110M Module SMI2 110V /3TE 30 aydat SCH NMH-TC 5V /3TE 32 aydat SCH NMH-TC 12V /3TE 32 aydat SCH NMH-TC 15V /3TE 32 aydat SCH NMH-TC 24V /3TE 32 aydat SCH NMH-TC 30V /3TE 32 aydat SCH NMH-TC 48V /3TE 32 aydat SCH NMH-TC 60V /3TE 32 aydat SCH NMH-TC 110V /3TE 32 aydat SCH NMH2-TC 5V /3TE 34 aydat SCH NMH2-TC 12V /3TE 34 aydat SCH NMH2-TC 15V /3TE 34 aydat SCH NMH2-TC 24V /3TE 34 aydat SCH NMH2-TC 30V /3TE 34 aydat SCH NMH2-TC 48V /3TE 34 aydat SCH NMH2-TC 60V /3TE 34 aydat SCH NMH2-TC 110V /3TE 34 aydat STD IM-TD 5V TE 36 aydat STD IM-TD 12V TE 36 aydat STD IM-TD 15V TE 36 aydat STD IM-TD 24V TE 36 aydat STD IM-TD 30V TE 36 aydat STD IM-TD 48V TE 36 aydat STD IM-TD 60V TE 36 aydat STD IM-TD 110V TE 36 aydat STD-2-5S IM-TD 5V S TE 36 aydat STD-2-12S IM-TD 12V S TE 36 aydat STD-2-15S IM-TD 15V S TE 36 aydat STD-2-24S IM-TD 24V S TE 36 aydat STD-2-30S IM-TD 30V S TE 36 aydat STD-2-48S IM-TD 48V S TE 36 aydat STD-2-60S IM-TD 60V S TE 36 aydat STD-2-110S IM-TD 110V S TE 36 aydat STD IM-TD 5V C TE 36 aydat STD IM-TD 12V C TE 36 aydat STD IM-TD 15V C TE 36 aydat STD IM-TD 24V C TE 36 aydat STD IM-TD 30V C TE 36 aydat STD IM-TD 48V C TE 36 aydat STD IM-TD 60V C TE 36 aydat STD IM-TD 110V C TE 36 aydat STD-2-5G IM-TD 5V 2GND TE 36 aydat STD-2-12G IM-TD 12V 2GND TE 36 aydat STD-2-15G IM-TD 15V 2GND TE 36 aydat STD-2-24G IM-TD 24V 2GND TE 36 aydat STD-2-30G IM-TD 30V 2GND TE 36 aydat STD-2-48G IM-TD 48V 2GND TE 36 aydat STD-2-60G IM-TD 60V 2GND TE 36 aydat STD-2-110G IM-TD 110V 2GND TE 36 Page Product Index 119

122 Product Index New Product Name New Order Code Product D1 C1 C2 C3 Modular and Compact SPD for Data/Signal Lines Legacy Product Names & Order Codes Order Code DIN aydat STD-2-5M Module IM-TD 5V TE 36 aydat STD-2-12M Module IM-TD 12V TE 36 aydat STD-2-15M Module IM-TD 15V TE 36 aydat STD-2-24M Module IM-TD 24V TE 36 aydat STD-2-30M Module IM-TD 30V TE 36 aydat STD-2-48M Module IM-TD 48V TE 36 aydat STD-2-60M Module IM-TD 60V TE 36 aydat STD-2-110M Module IM-TD 110V TE 36 aydat SUHI VMO 5V TE 38 aydat SUHI VMO 12V TE 38 aydat SUHI VMO 15V TE 38 aydat SUHI VMO 24V TE 38 aydat SUHI VMO 30V TE 38 aydat SUHI VMO 48V TE 38 aydat SUHI VMO 60V TE 38 aydat SUHI VMO 110V TE 38 aydat SUHI-2-5M Module VMO 5M TE 38 aydat SUHI-2-12M Module VMO 12M TE 38 aydat SUHI-2-15M Module VMO 15M TE 38 aydat SUHI-2-24M Module VMO 24M TE 38 aydat SUHI-2-30M Module VMO 30M TE 38 aydat SUHI-2-48M Module VMO 48M TE 38 aydat SUHI-2-60M Module VMO 60M TE 38 aydat SUHI-2-110M Module VMO 110M TE 38 aydat SU SMH-TD 110V /3TE 40 aydat SU-2-110M Module SMH-TD 110M /3TE 40 Page aydat SU SMH2-TD 110V /3TE 42 aydat SU-4-110M Module SMH2-TD 110M /3TE 42 aydat SLL /3TE 44 aydat SLL-4-30M /3TE 44 aydat SLL-4-30Q /3TE 44 aydat SCL IM-VF 12V /3TE 46 aydat SCL IM-VF 24V /3TE 46 aydat SCL IM-DF 5V /3TE 48 aydat SCL IM-DF 12V /3TE 48 aydat SCL IM-DF 24V /3TE 48 aydat SCL IM-DF 60V /3TE 48 aydat SUH-2-30PS SMH-TC+PS 24V /3TE 50 aydat SUH-2-30PSM Module SMH-TC+PS 24V /3TE SIGNALING NETWOK SEIES

123 New Product Name C1 C2 C3 Modular SPDs for Explosive Environments New Order Code Product Legacy Product Names & Order Codes Order Code DIN aydat Ex-2-12V SMH 12Ex TE 54 aydat Ex-2-24V SMH 24Ex TE 54 Page aydat PLP-24Ex 1/2 NPT PLP-24Ex 1/2 NPT aydat PLP-24Ex M PLP-24Ex M aydat PLP-24Ex G 1/ PLP-24Ex G 1/ aydat PLP2-24Ex 1/2 NPT PLP2-24Ex 1/2 NPT aydat PLP2-24Ex M PLP2-24Ex M aydat PLP2-24Ex G 1/ PLP2-24Ex G 1/ aydat PLP2-48 Ex 1/2 NPT PLP2-48 Ex 1/2 NPT aydat PLP2-48 Ex M PLP2-48 Ex M aydat PLP2-48 Ex G 1/2" PLP2-48 Ex G 1/2" aydat PLP-24/5 Ex 1/2 NPT PLP-24/5 Ex 1/2 NPT aydat PLP-24/5 Ex M PLP-24/5 Ex M aydat PLP-24/5 Ex G 1/ PLP-24/5 Ex G 1/ aydat PLP3L-24Ex 1/2 NPT PLP3L-24Ex 1/2 NPT aydat PLP3L-24Ex M PLP3L-24Ex M aydat PLP3L-24Ex G 1/ PLP3L-24Ex G 1/ Class III C1 C2 C3 Modular & Compact SPDs for DC Power Systems Protec DMD 20/24V Protec DMD 20/24V TE 60 Protec DMD 20/48V Protec DMD 20/48V TE 60 Protec DMD 20/60V Protec DMD 20/60V TE 60 Protec DMD 20/120V Protec DMD 20/120V TE 60 Module Protec DMD 20/24V Module Protec DMD 20/24V TE 60 Module Protec DMD 20/48V Module Protec DMD 20/48V TE 60 Module Protec DMD 20/60V Module Protec DMD 20/60V TE 60 Module Protec DMD 20/120V Module Protec DMD 20/120V TE 60 aydat PSC SMH-PS 12V /3TE 62 aydat PSC SMH-PS 24V /3TE 62 aydat PSC SMH-PS 48V /3TE 62 aydat PSC-2-12M Module SMH-PS 12M /3TE 62 aydat PSC-2-24M Module SMH-PS 24M /3TE 62 aydat PSC-2-48M Module SMH-PS 48M /3TE 62 D1 Class III C1 C2 C3 SPDs for Local Area Networks (LAN) aydat NET 6 PoE LZ-NET 6 48V aydat NET LZ-NET aydat NET 5 PoE LZ-NET PoE aydat NET 5 STP LZ-NET STP aydat NET LZ 8 NET aydat NET LZ 16 NET aydat NET LZ 24 NET aydat NET PoE LZ 8 NET 19 PoE aydat NET PoE LZ 16 NET 19 PoE aydat NET PoE LZ 24 NET 19 PoE aydat NET M LZ 8 NET 19M aydat NET M PoE LZ 8 NET 19M PoE aydat NET 5 PS ZE 200 NET Product Index 121

124 Product Index New Product Name D1 C1 C2 C3 SPDs for Data Protocols New Order Code Product Legacy Product Names & Order Codes Order Code DIN aydat S VM-S 48548V Page C1 C2 C3 Various Data SPDs aydat PLP PLP-24V aydat GD IM-GD C1 C2 C3 SPDs for Coaxial & F Systems aycox BNC ZV-BNC ±5V aycox BNC ZV-BNC ±12V aycox IEC ZV aycox F ZV1-F aydat CP BNC-FF CCP 70-BNC-FF aydat CP BNC-FF CCP 180-BNC-FF aydat CP BNC-FF CCP 280-BNC-FF aydat CP BNC-MF CCP 70-BNC-MF aydat CP BNC-MF CCP 180-BNC-MF aydat CP BNC-MF CCP 280-BNC-MF aydat CP 7/16-MF CCP 70-7/16-MF aydat CP 7/16-MF CCP 180-7/16-MF aydat CP 7/16-MF CCP 280-7/16-MF aydat CP N-FF CCP 70-N-FF aydat CP N-FF CCP 180-N-FF aydat CP N-FF CCP 280-N-FF aydat CP N-MF CCP 70-N-MF aydat CP N-MF CCP 180-N-MF aydat CP N-MF CCP 280-N-MF aydat CP N-6G-FF CCP 180-N-6G-FF aydat CP N-6G-MF CCP 180-N-6G-MF aydat CP TNC-6G-FF CCP 180-TNC-6G-FF aydat CP TNC-6G-MF CCP 180-TNC-6G-MF SIGNALING NETWOK SEIES

125 New Product Name C1 C2 C3 SPDs for Coaxial & F Systems New Order Code Product Legacy Product Names & Order Codes Order Code DIN aydat CP UHF-FF CCP 70-UHF-FF aydat CP UHF-FF CCP 180-UHF-FF aydat CP UHF-FF CCP 280-UHF-FF aydat CP UHF-MF CCP 70-UHF-MF aydat CP UHF-MF CCP 180-UHF-MF aydat CP UHF-MF CCP 280-UHF-MF aydat CP F75-FF CCP 70-F75-FF aydat CP F75-FF CCP 180-F75-FF aydat CP F75-MF CCP 70-F75-MF aydat CP F75-MF CCP 180-F75-MF aydat CP T75-FF CCP 70-TV75-FF aydat CP T75-FF CCP 180-TV75-FF aydat CP T75-MF CCP 70-TV75-MF aydat CP T75-MF CCP 180-TV75-MF aydat CP L/4-7/16-FF CCP L/4-7/16-FF aydat CP L/4-7/16-MF CCP L/4-7/16-MF Page aydat CP L/4-N-FF CCP L/4-N-FF aydat CP L/4-N-MF CCP L/4-N-MF Product Index 123

126 124 SIGNALING NETWOK SEIES

127

128 aycap Worldwide Locations Parkring Garching Munich Germany Telou & Petroutsou Maroussi Athens Greece Industrial Area of Drama Drama Greece 806 South Clearwater Loop Post Falls, ID United States of America Soseaua de Centura Chiajna Ilfov omania 46 Lefkosias Street Industrial Area of Dali 2540 Nicosia Cyprus Stegne 23 A 1000 Ljubljana Slovenia Block B, Phase II of New Sea Union No. 58 Heshun oad SIP, Suzhou Jiangsu Province China info@raycap.com 2016 aycap All rights reserved. G

Surge Protection for Low Voltage Power Systems

Surge Protection for Low Voltage Power Systems Surge Protection for Low Voltage Power Systems 2017 CATALOG Table of Contents About Raycap 3 Introduction 5 Regulatory Standards 6 Surge Protective Device Components & Terminology 8 Low Voltage Power Distribution

More information

Type Code No. Weight Packaging [g] [pcs]

Type Code No. Weight Packaging [g] [pcs] Surge arresters surge arresters are intended for protection of electrical installations and devices against overvoltage effects, which may occur in atmospheric discharges and switching overvoltages. The

More information

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing MULTI-POLE Lightning Current and Surge Arresters for PHOTOVOLTAIC SYSTEMS Class I / (B+C) and Class II / (C) COMPACT and MODULAR Housing 44 PV ISPRO BS(R) 12,5 The PV ISPRO BS(R) 12,5 series of over voltage

More information

Lightning & Surge Protection for Wind Turbine Systems

Lightning & Surge Protection for Wind Turbine Systems Lightning & Surge Protection for Wind Turbine Systems Product Selection Guide Table of Contents Technologies for Wind Turbine Protection 3 Protective Device Recommendations 4 Class I Strikesorb Surge Protection

More information

/60 ETITEC A 15/ /60 ETITEC A 15/440 Al/Fe connection*

/60 ETITEC A 15/ /60 ETITEC A 15/440 Al/Fe connection* surge arresters are intended for protection of electrical installations and devices against overvoltage effects, which may occur in atmospheric discharges and switching overvoltages. The main part of surge

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Overvoltage Protection Devices /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 and type 2 /7 5SD7 surge arresters, type 2 /10 5SD7 surge arresters, type

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2010 Overvoltage Protection Devices /2 Introduction /3 Lightning Arresters, Type 1 /5 Combination Surge Arresters, Type 1 and Type 2 /7 Surge Arresters, Type 2 /11 Surge Arresters, Type 3 /12

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2013 Overvoltage Protection Devices /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 and type 2 /7 5SD7 surge arresters, type 2 /10 5SD7 surge

More information

Leutron. Lightningand. Surge Protection for Power Net Systems (SPD) with EnerPro Combi-Devices. Seite 0 von14

Leutron. Lightningand. Surge Protection for Power Net Systems (SPD) with EnerPro Combi-Devices. Seite 0 von14 Leutron Lightningand Surge Protection for Power Net Systems (SPD) with EnerPro Combi-Devices Seite 0 von14 Novelties 2003 Combi Surge Protectors Leutron GmbH, 70771 Leinfelden-Echterdingen, Deutschland

More information

ETITEC - Lightning and Surge Arresters

ETITEC - Lightning and Surge Arresters ETITEC Lightning and Surge Arresters Overvoltage protection selection ETITEC selection Define system data: U max Uc > 1,2 x U max External lightning protection exist? NO Apply ETITEC C on string and on

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2014 Overvoltage Protection Devices /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 and type 2 /7 5SD7 combination surge arresters, type 1 / type

More information

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection CONTA-ELECTRONICS CONTA-PROTECT overvoltage protection When choosing the correct device for overvoltage protection, it is important to consider the regulations VDE 110-1, IEC 61643-1, EN 61643-11 and VDE

More information

Surge Protection Devices Ex9UE2

Surge Protection Devices Ex9UE2 Surge Protection Devices Ex9UE2 Surge Protection Devices Type 2 (Class II, T2, C) Tested according to EN 61643-11 Maximum continuous operational voltage U c from 275 V up to 440 V AC Versions with 1+0,

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 201 /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 + type 2 /7 5SD7 combination surge arresters, type 1 / type 2 /9 5SD7 surge arresters, type

More information

Surge Protection for Surveillance Systems

Surge Protection for Surveillance Systems Surge Protection for Surveillance Systems 1-in-1 Protection for Network Cameras 2-in-1 Protection for Power and Audio/Video Signals 3-in-1 Protection for Power, Audio/Video and PTZ Control Signals Application:

More information

Surge & Filter Protection Addressing your industrial power quality needs.

Surge & Filter Protection Addressing your industrial power quality needs. Surge & Filter Protection Addressing your industrial power quality needs. BULLETIN 983 INTRODUCING SURGE & FILTER PROTECTION SURGE & FILTER PROTECTION Rockwell Automation is pleased to introduce the Bulletin

More information

Ethernet Protection A Whole Solution Han Zou, ProTek Devices

Ethernet Protection A Whole Solution Han Zou, ProTek Devices Ethernet Protection ------ A Whole Solution Han Zou, ProTek Devices Introduction: As Ethernet applications progress from 10BaseT to 10Gigabit and beyond, IC components are becoming more complicated with

More information

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany Lightning and Surge Protection of Photovoltaic Installations 1 Lightning and Surge Protection for PV Installations 2 Safeguard from Risks Ups, that was the insurance policy of my house!! 3 Why Lightning

More information

Company Profile Surge Protective Devices

Company Profile Surge Protective Devices Company Profile Surge Protective Devices Who we are What we do SALTEK is a leading Czech based company specialising in the development and production of Surge Protective Devices. SALTEK offers a complete

More information

MODULES FOR SAFETY AND MONITORING

MODULES FOR SAFETY AND MONITORING MODULES FOR SAFETY AND MONITORING Woertz AG Hofackerstrasse 47, P.O. Box 948, CH-43 Muttenz, Switzerland Tel. ++4 6 / 466 33 33, Fax ++4 6 / 46 96 06 http://www.woertz.ch Woertz-USA 5 Discovery Drive,

More information

R3&A Limited, Cobourg, ON

R3&A Limited, Cobourg, ON R3&A imited, Cobourg, ON ightning and Surge Protection Devices for North America Easy Choice POWER SUPPY SYSTEMS Main distribution board (Category C) Class I ightning current arrester Subdistribution board

More information

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects of transient over voltages caused by

More information

Hazardous Area Protection

Hazardous Area Protection Hazardous Area Protection Global Solutions in Hazardous Area Surge and Lightning Protection Intrinsic Safety When instrumentation is installed in a potentially explosive environment steps must be taken

More information

Technical features OVR Surge Protective Devices Type 1 & Type 1+2

Technical features OVR Surge Protective Devices Type 1 & Type 1+2 Type 1 & Type 1+2 TECHNICAL FEATURES Technology Type 1 OVR T1 2 TS Triggered spark-gap Electrical features Standard IEC 61643-1 / EN 61643-11 Type / test class 1 / I Poles 1P - 1P -, 2P 2L 3P 3L 4P 4L

More information

BLITZDUCTOR XTU Universal lightning current / surge arrester

BLITZDUCTOR XTU Universal lightning current / surge arrester Pluggable DIN Rail Mounted SPDs Combined lightning current and surge arrester Max. discharge capacity for balanced data interfaces Capable of carrying lightning currents up to 10 ka (10/50 μs) For installation

More information

INFORMATION TECHNOLOGY SYSTEMS

INFORMATION TECHNOLOGY SYSTEMS Surge protection for INFORMATION TECHNOLOGY SYSTEMS SPDs for installations and equipment 131 Cross-reference Discontinued Products Alternatives Part No. Type Part No. Type Pluggable SPDs for DIN rail mounting

More information

HyperLink Brand Weatherproof PTZ Camera Lightning and Surge Protector Model: AL-VDP Series

HyperLink Brand Weatherproof PTZ Camera Lightning and Surge Protector Model: AL-VDP Series HyperLink Brand Weatherproof PTZ Camera Lightning and Surge Protector Model: AL-VDP Series Applications Pan-Tilt-Zoom (PTZ) analog video cameras Features Individual protection circuits for analog video

More information

2 Principle of lightning protection

2 Principle of lightning protection 2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical

More information

M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS

M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS G1 Outdoor Surge Protector for AC/Traction network VP range Dimensions (in mm) 19 M8 44 73 diam. 47 6 mm² Electrical

More information

INFORMATION TECHNOLOGY SYSTEMS SPDs FOR COAXIAL CONNECTION. DEHNgate Lightning current and surge arresters

INFORMATION TECHNOLOGY SYSTEMS SPDs FOR COAXIAL CONNECTION. DEHNgate Lightning current and surge arresters Lightning current and surge arresters Application-specific SPD designs SPD for use in satellite and cable TV systems with measuring output Combined lightning current and surge arrester for high discharge

More information

SPM Series Plug-in Surge Protection

SPM Series Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

Surge Protection Devices and Surge Protection Kit

Surge Protection Devices and Surge Protection Kit Surge and Surge Kit SPD s protect electrical and electronic equipment against transients, originating from lightning, switching of transformers, lighting and motors 3. Main protection - class 3 To cut-down

More information

Surge protection for transceiver systems

Surge protection for transceiver systems 162 PHOENIX CONTACT Surge protection for transceiver systems Main range 164 Features 166 Selection guide 168 Exposed antenna systems and outdoor cables that extend beyond a building are particularly at

More information

NEW Series SSH Output to 75A, 510 Vac with Diagnostics High Industrial Performance (HIPpak) Solid-State Relays

NEW Series SSH Output to 75A, 510 Vac with Diagnostics High Industrial Performance (HIPpak) Solid-State Relays FEATURES/BENEFITS Zero-cross models with system diagnostics Very low zero-cross turn-on voltage Input and output protection and control LED standard IP20 protection by flaps on terminals With double removable

More information

LPI SG + SST Spark Gap Surge Filter

LPI SG + SST Spark Gap Surge Filter LPI SG + SST Spark Gap Surge Filter Features High performance surge protector for an operating voltage of 220-240Vac Encapsulated spark gap and SST capable of sustaining fault and over-voltage conditions

More information

PT 3-PB-ST. Extract from the online catalog. Order No.:

PT 3-PB-ST. Extract from the online catalog. Order No.: Extract from the online catalog PT 3-PB-ST Order No.: 2858030 Surge protection plug for the base element, normal mode voltage coarse and fine protection for two floating signal wires in IT, common mode

More information

NEW surge protective devices

NEW surge protective devices NEW surge protective devices For use in low-voltage systems For overhead power lines and buildings Made in EU ABOUT COMPANY INTRODUCTION Company ELEKTROMEHANIKA & BB d.o.o. was established from recent

More information

Lightning Current Equipotential Bonding SPDs

Lightning Current Equipotential Bonding SPDs Lightning Current Equipotential Bonding SPDs Introduction Furse is a world leader in the design, manufacture, and supply of earthing and lightning protection systems. Over 100 years of experience makes

More information

SPM Series. Plug-in Surge Protection

SPM Series. Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

US Catalog March Surge protective devices (SPDs) UL range

US Catalog March Surge protective devices (SPDs) UL range US Catalog March 017 Surge protective devices (SPDs) UL range Surge protective devices (SPDs) UL range Introduction 1 1 OVR surge protective devices Joslyn surge protective devices Marketing tools 4 US

More information

NTS-protect. Description of GPS antenna and NTS time server connection via system lightning protector system /NTS-3000, NTS-4000, NTS-5000/

NTS-protect. Description of GPS antenna and NTS time server connection via system lightning protector system /NTS-3000, NTS-4000, NTS-5000/ NTS-protect Description of GPS antenna and NTS time server connection via system lightning protector system /NTS-3000, NTS-4000, NTS-5000/ SAFETY INSTRUCTIONS! This are the important Safety Instructions

More information

PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION

PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION INTERNAL PROTECTION systems PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION INDUSTRIAL INSTALLATIONS 2 1 2 5 5 7 2 2 2 2 4 6 6 7 3 OBJECT: Industrial premises, Industrial complexes, Hospitals, Public buildings

More information

Surge Protective Device

Surge Protective Device Surge Protective Device LED Light / Machine protection SPD Class 2 LT-C34G801W General Information LT-C and LT-HC series Surge Protective Devices are for protection of indirect lightning. They are designed

More information

wietap wietap Overvoltage Protection Tensions running high

wietap wietap Overvoltage Protection Tensions running high wietap wietap Overvoltage Protection Tensions running high 2 wietap wietap Overvoltage protection Important information on overvoltage The necessity of overvoltage protection on machines and systems as

More information

Surge Protection & Monitoring Solutions for Photovoltaic Systems

Surge Protection & Monitoring Solutions for Photovoltaic Systems Surge Protection & Monitoring Solutions for Photovoltaic Systems Raycap Products Provide the Ultimate Lightning Surge Protection for Photovoltaic Systems The remote locations, exposed surface areas and

More information

Surge Protection Devices Type 1+2

Surge Protection Devices Type 1+2 Surge Protection Devices Type 1+2 Description The combined surge protection devices offer as an all-in-one solution lightning and surge-voltage in one device. They are in accordance with the requirement

More information

Protection of PHOTOVOLTAIC SYSTEMS against LIGHTNING and OVERVOLTAGE. Surge Protection Device

Protection of PHOTOVOLTAIC SYSTEMS against LIGHTNING and OVERVOLTAGE. Surge Protection Device Protection of PHOTOVOLTAIC SYSTEMS against LIGHTNING and OVERVOLTAGE Surge Protection Device CHOICE OF SURGE PROTECTION DEVICES FOR PHOTOVOLTAIC APPLICATIONS General concept To achieve complete functionality

More information

ELPROMA NTSprotect Surge Protection

ELPROMA NTSprotect Surge Protection ELPROMA NTSprotect Surge Protection Rack 19 back panel with NTS-protect As the antenna is roof mounted (to have a clear view of the sky) it is likely to be exposed to lightning strikes. Protection against

More information

DBPApplication. PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL (0)

DBPApplication. PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL (0) DBP Series Data Protection Designed for business and industrial applications, these products provide protection for local area networks, CCTV/video equipment, computer serial communication interfaces and

More information

Lightning and surge protection for single-family houses

Lightning and surge protection for single-family houses Lightning and surge protection for single-family houses White Paper Contents Benefits of protecting an antenna by means of an isolated LPS instead of earthing the antenna Protection of the heat pump /

More information

Fundamentals of Thyristor Overvoltage Circuit Protection

Fundamentals of Thyristor Overvoltage Circuit Protection Fundamentals of Thyristor Overvoltage Circuit Protection Thyristor Surge Protection Technology The Problem of Overvoltages Electronic components have been designed to function properly when used within

More information

Contact protection relay

Contact protection relay Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts

More information

Signal Doublers. VariTrans A 20300

Signal Doublers. VariTrans A 20300 ProLine Interface Technology Signal Doublers Signal doublers with two switchable calibrated outputs in a 6 mm housing, also for applications with high output loads. The Task Isolation and transmission

More information

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester These modular distribution panel protectors for three phase power systems are designed to prevent damage to electrical distribution systems from mainsborne transient voltages which can occur as the result

More information

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications Power Circuit Control Circuit (External Source) Control Circuit (Internal Source) Short Circuit Current Rating (SCCR) Application Electrical Ratings Three-phase Number of Poles 3 Input Power Terminals

More information

Reliability in Surge Protection. Surge Protection. AC & DC Power Photovoltaic Coaxial Telecom Gas Discharge Tubes.

Reliability in Surge Protection. Surge Protection. AC & DC Power Photovoltaic Coaxial Telecom Gas Discharge Tubes. Reliability in Surge Protection Surge Protection AC & DC Power Photovoltaic Coaxial Telecom Gas Discharge Tubes www.citel.us CITEL Established in 1937, CITEL is the global leader in the development and

More information

Surge Protection & Monitoring Solutions for Photovoltaic Systems

Surge Protection & Monitoring Solutions for Photovoltaic Systems Surge Protection & Monitoring Solutions for Photovoltaic Systems Raycap Products Provide the Ultimate Lightning Surge Protection for Photovoltaic Systems The remote locations, exposed surface areas and

More information

LPI SG + SS480 Spark Gap Surge Filters

LPI SG + SS480 Spark Gap Surge Filters LPI SG + Spark Gap Surge Filters Features High performance surge protector for an operating voltage of 220-277Vac Encapsulated spark gap and technology capable of operation under fault /overvoltage conditions

More information

160 PHOENIX CONTACT Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA Main Office: (650) Outside Local

160 PHOENIX CONTACT Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA Main Office: (650) Outside Local 160 PHOENIX CONTACT Main range 162 Feature 164 Selection guide 166 Exposed antenna systems and outdoor cables that extend beyond a building are considered especially at risk, since they are directly exposed

More information

LPI SST Surge Filters

LPI SST Surge Filters LPI SST Surge Filters Features High performance surge protector for an operating voltage of 200-240Vac Designed to withstand fault and over-voltage conditions of up to 85Vac, as per IEC664 Impulse discharge

More information

Lightning and Surge Arresters

Lightning and Surge Arresters Lightning and Surge Arresters 5/4 Product overview 5/5 Lightning arresters, requirement category I (B) 5/6 Combined arresters, requirement category I (B) and II (C) 5/7 Single-pole surge arrester, requirement

More information

Extract from the online catalog SFP 1-5/120AC Commercial data Product description Technical data Standards

Extract from the online catalog SFP 1-5/120AC Commercial data Product description Technical data Standards Extract from the online catalog SFP 1-5/120AC Order No.: 2920667 Device surge protection filter to limit powerful surge voltages, mounting on NS 35. Commercial data EAN 4046356158558 Pack 1 pcs. Customs

More information

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment NTSA has developed the ultimate solution for protecting

More information

Deploying surge protective devices (SPDs) in photovoltaic systems. Technical Information

Deploying surge protective devices (SPDs) in photovoltaic systems. Technical Information Deploying surge protective devices (SPDs) in photovoltaic systems Technical Information 2 00/09.08 Preface Preface Damages caused by overvoltage s are not only responsible for expensive repair costs; they

More information

Zelio Control-modular measurement and control relays 1

Zelio Control-modular measurement and control relays 1 Presentation, description 1 106439 RM35 TM111MW Presentation Motor temperature measurement and 50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and

More information

TDS Transient Discriminating Surge Diverters

TDS Transient Discriminating Surge Diverters TDS Transient Discriminating Surge Diverters Surge Protection And Surge Ratings The stress, which an SPD will experience under surge conditions, is a function of many complex and interrelated parameters.

More information

MANUAL Surge Protectors

MANUAL Surge Protectors PROCESS AUTOMATION MANUAL Surge Protectors DP-LBF-I1.36.DE and DP-LBF- I1.36.IE With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

Voltage Transducer UMT516 / MT516

Voltage Transducer UMT516 / MT516 Voltage Transducer UMT516 / MT516 True RMS AC voltage measurements Voltage auto range measurements up to 600V # Wide frequency measurement range 16 400 Hz High accuracy class 0.2 (IEC-688), 0.1 on communication

More information

RMCN22BD Analog Converter ma - for Zelio Analog

RMCN22BD Analog Converter ma - for Zelio Analog Characteristics Analog Converter - 4..20 ma - for Zelio Analog Main Commercial Status Range of product Product or component type Analogue input type Analogue output type Commercialised Zelio Analog Voltage/Current

More information

Overvoltage Protection

Overvoltage Protection Overvoltage Protection OVR Range FRSOX 0100 03 GB ABB Lightning Protection Group 1 Main causes of transient overvoltages The solution: ABB OVR Surge Protective Device Range Lightning strike A lightning

More information

SPD Catalogue. SPD Catalogue. for AC applications

SPD Catalogue. SPD Catalogue. for AC applications SPD Catalogue SPD Catalogue for AC applications Eaton and Cooper united. Energizing a world that demands more. We deliver: Electrical solutions that use less energy, improve power reliability and make

More information

PV protective solutions

PV protective solutions PV SPD catalogue PV protective solutions for solar PV applications Eaton and Cooper united. Energizing a world that demands more. We deliver: Electrical solutions that use less energy, improve power reliability

More information

Circuit Protection Application Note TBU Electronic Current Limiter GR-1089 Port Type 2 and 4 Ethernet Protection

Circuit Protection Application Note TBU Electronic Current Limiter GR-1089 Port Type 2 and 4 Ethernet Protection Circuit Protection Application Note BU Electronic Current Limiter GR-1089 Port ype 2 and 4 Ethernet Protection About the Protection his application note details the BU device protection in an Ethernet

More information

PT 2X2-24DC-ST. Extract from the online catalog. Order No.:

PT 2X2-24DC-ST. Extract from the online catalog. Order No.: Extract from the online catalog PT 2X2-24DC-ST Order No.: 2838228 The illustration shows version PT 2x2-5DC-ST Protective plug PT with protective circuit for two 2-core floating signal circuits. Nominal

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/ DC - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type Time

More information

the data line series

the data line series the data line series 12-00131 OUTDOOR SINGLE PORT POE RJ45 SURGE ARRESTOR rev0-10/100/1000 Base-T CAT5e Protection - IEEE 802.3 A/F Power Mode B - Solid-state silicon-avalanche diodes with internal TVS

More information

Technical Specification

Technical Specification EMC TESTS, SEMINARS, HARD AND SOFTWARE Technical Specification No. E-MIG1206-3P.doc Revised: 10.March 2007 1 MIG Tester Type MIG1206-3P 1 MIG Tester Type MIG1206-3P 1 1.1 Introduction 1 2 General 2 2.1

More information

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13 Data sheet Thermistor motor protection relays CM-MSS.12 and CM-MSS.13 The thermistor motor protection relays CM-MSS.12 and CM-MSS.13 monitor the winding temperature of motors and protect them from overheating,

More information

Product Overview Surge Protective Devices

Product Overview Surge Protective Devices Product Overview Surge Protective Devices 2018 Who we are What we do SALTEK is a leading Czech based company specialising in the development and production of Surge Protective Devices. SALTEK offers a

More information

NEW NEW NEW NEW NEW NEW Electrical specification ESP SL06 ESP SL15 ESP SL30 ESP SL50 ESP SL110 ESP SL TN

NEW NEW NEW NEW NEW NEW Electrical specification ESP SL06 ESP SL15 ESP SL30 ESP SL50 ESP SL110 ESP SL TN Line Current rating In-line resistance Nottingham, NG EB, UK 0V 6.7V 750mA.0Ω 0kA 6V ESP SL Series Combined Category D, C, B tested protector (to BS EN 66) suitable for twisted pair signalling applications

More information

ITU-T Recommendations and the Resistibility of Telecommunication Equipment

ITU-T Recommendations and the Resistibility of Telecommunication Equipment ITU-T Recommendations and the Resistibility of Telecommunication Equipment Introduction WHITE PAPER The International Telecommunications Union (ITU-T) developed its ITU-T K Series Recommendations to help

More information

TT-ST-M-2-PE-24DC. Extract from the online catalog. Order No.:

TT-ST-M-2-PE-24DC. Extract from the online catalog. Order No.: Extract from the online catalog TT-ST-M-2-PE-24DC Order No.: 2858904 TERMITRAB, spring-cage modular terminal block with integrated surge protection and disconnect knives, for assembly on NS 35/7.5, voltage

More information

Revised Standards Provide Design Options for Primary and Secondary Protection TELECOM PROTECTION WHITE PAPER

Revised Standards Provide Design Options for Primary and Secondary Protection TELECOM PROTECTION WHITE PAPER TELECOM PROTECTION WHITE PAPER INTRODUCTION Telecommunications networks are subject to surges from lightning or power line faults, and the effects of these can be extremely detrimental to systems and equipment.

More information

Installation / Control Technique

Installation / Control Technique Installation / Control Technique Interface Relay, Interface Relay System Input-Output Interface Relay IK 3070, I_ 3070 0633 IK 3070 Circuit Diagrams IS 3070 According to IEC/EN 61 810-1 Relay, triac or

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

PT 2X2-HF-24 DC-ST. Extract from the online catalog. Order No.:

PT 2X2-HF-24 DC-ST. Extract from the online catalog. Order No.: Extract from the online catalog PT 2X2-HF-24 DC-ST Order No.: 2839729 The illustration shows the version PT 2x2-HF-12 DC-ST Protective plug PT with HF protective circuit for two 2-core floating signal

More information

Power supply CP-C 24/5.0

Power supply CP-C 24/5.0 2CDC 271 064 F0004 Features Supply voltage ranges: 85-264 V AC, 100-350 V DC Output voltage adjustable from 22-28 V DC, default setting 24 V DC 0,5 % 5 A output current Open-circuit, overload and continous

More information

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output Characteristics off-delay timing relay - control - 1 s..100 h - 24..240 V - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type

More information

AI561 Analog Input Module

AI561 Analog Input Module Ordering Data DATA SHEET AI561 Analog Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R1101 AI561, analog input module, 4 AI, U/I 1TNE 968 901 R3101 1TNE 968

More information

Systems which use a conventional POTS subscriber line to dial a compatible system and transfer digital data.

Systems which use a conventional POTS subscriber line to dial a compatible system and transfer digital data. PSTN Protection The demand for voice and data communications has never been greater. Today, virtually everyone in the developed world has access to a land-line telephone, which carries their voice or data

More information

TU531, TU532 Terminal Unit

TU531, TU532 Terminal Unit Ordering Data DATA SHEET TU531, TU532 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 217 200 R0001 1SAP 217 000 R0001 1SAP 417 000 R0001 TU531, terminal unit, 230 VAC,

More information

INFORMATION TECHNOLOGY SYSTEMS SOCKET OUTLET. DSM (RJ45) Surge Arrester. LAN fine protection for fixed installation

INFORMATION TECHNOLOGY SYSTEMS SOCKET OUTLET. DSM (RJ45) Surge Arrester. LAN fine protection for fixed installation SOCKET OUTLET (RJ5) Surge Arrester LAN fine protection for fixed installation Protection for all lines Shielded socket outlet, Category 5 Data socket outlet (Category 5) with integrated surge protection.

More information

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1 Manual PCD3.C90 Revision History Date Modification Asked by: Version 14.09.09 E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1 22.09.09 Added E/A Bus Connector PCD3.K116 Müller.R 1.2 06.01.10

More information

AO561 Analog Output Module

AO561 Analog Output Module Ordering Data DATA SHEET AO561 Analog Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1TNE 968 902 R1201 AO561, analog output module, 2 AO, U/I 1TNE 968 901 R3102 Terminal

More information

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers 2010-12-10 5011699201-PBB1 Eaton Logic Controller ELCB Controllers INSTRUCTION SHEET [Applicable Controllers] ELCB-PB10 ELCB-PB14 ELCB-PB20 ELCB-PB30 ELCB-PB40 IL05001005E 002-1310020-02 Thank you for

More information

S400 Series HIGH EFFICIENCY SURGE PROTECTIONS. For power supply For measurement and control devices For LAN / ICT Networks

S400 Series HIGH EFFICIENCY SURGE PROTECTIONS. For power supply For measurement and control devices For LAN / ICT Networks S400 Series HIGH EFFICIENCY SURGE PROTECTIONS For power supply For measurement and control devices For LAN / ICT Networks S400 Series High Efficiency Surge Protections High Efficiency Surge Protections

More information

Electronic timer CT-ARS.11

Electronic timer CT-ARS.11 2CDC 251 088 F0t07 Features Rated control supply voltage 24 240 V AC/DC Single function OFF delay timer without auxiliary voltage One device includes 7 time ranges (0.05 s 10 min) 1 c/o (SPDT) contact

More information

White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems

White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems White Paper AC Surge Protection Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems Richard Odenberg, Research & Advanced Applications, Founder of Transtector

More information