ESD, ESR, ESA, ESP, ESQ. Switching Units
|
|
- Erick Adams
- 5 years ago
- Views:
Transcription
1 ESD, ESR, ESA, ESP, ESQ Switching Units
2
3 Selection Table for ESR Units Safety Protection Bircher Category Class Inputs Outputs Voltage Redundancy Type 3 IP 30 30/5/4 x ESD 3 IP 30 30/5/4 ESR IP 30 30/5/4 ESR IP 30 30/5/4 ESR 3 IP30 4 x ESR 5 IP30 4 x ESR 6 IP 65 30/5/4 x ESA/ESP Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
4 Switching Units ESD3 DIN Housing Safety Category 3 according EN954- For contact mats acc. to EN 760- / for safety edges acc. to EN 760- Auto, External Reset Switching Units monitor tactile signal sensors such as safety mats, contact strips and bumper systems Function Connected s have a terminal resistance of 8. kohm and are monitored for changes in the continously flowing no-load current. In the non-activated condition both relays are energised. When one or more s are activated the total resistance sinks towards zero ohm if the value falls below the defined threshold (6. kohm) the relays are de-energised the yellow LED illuminates When a Error occurs in the circuit the total resistance rises towards infinity if the value rises above the defined threshold ( kohm) the relays are de-energised the red LED illuminates Type ESD-3 safety Category 3 according to EN954- self-monitoring double redundant signal evaluation automatic or external Reset fail-safe force guided relay Block Diagram and Connection * Upper Switching Threshold Nominal Resistance Lower Switching Threshold Signal Output Relay Contacts Resistance ~ kohm 8, kohm ~6, kohm Terminal Terminal Signal 9 Supply Voltage Signal 0 Supply Voltage 3 Signal 4 Signal Safety Output Relay 5 External Reset 3 Safety Output Relay 6 External Reset 4 7 Indication Relay 5 Safety Output Relay 8 Indication Relay 6 Safety Output Relay *Versions with automatic reset have this function integrated in the circuit Terminals type: x 8 pole plugable max. cross-section.5 mm Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
5 Variation Table The ESD3 variants are distinguished firstly by their reset function and secondly by the configuration of the status relay contact. This can be implemented off-load both as open and closed. It is not a safety contact, but is exclusively used for transmitting information. It is not monitored for failure and must never be used for safety shutdown in any form whatsoever. Each type is available in three voltage supply variants: 4 V AC/DC, 5 V AC, 30 V AC. Version Inputs Safety Relay Reset Status Relay Separation Auto External M SM C D 03 x x x x 04 x x x x 05 x x x x 06 x x x x 08 x x x x 09 x x x x 03C x x x x 05C x x x x Function Status Relay Contacts Type No voltage Error not operated operated (LED red) (LED yellow) Safety contact all Types O X O O Error Indication contact SM ESD3-03,-05 O X X O Error Indication contact C ESD3-03C,-05C X O O X Indication contact M ESD3-04,-06 O X O O Indication contact D ESD3-08,-09 X O X X Legend: O = Contact open X = Contact closed Reset Auto-Reset NO button on the front Reset electronically integrated External Reset NO button on the front external button (NC) Terminals 5,6 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)
6 Technical data Housing DIN ABS, red/black Isolation Class IP 30 (IEC 59) Protection Class IP54 Weight max. 50 gramm (depending on type) Power Supply 4 VACDC ±0% acc. to EN VAC ±0% (depending on type) 30 VAC ±0% Frequency Range 50/60 Hz (45 66 Hz) Power consumption max. 5 VA Duty Cycle 00% Fastening 35 mm mounting rail acc. to EN500 Safety Output Relay Utilization category AC-: 50V/ A / 500 VA acc.to EN * approx switchings DC-: 4V/ A/ 48W approx switchings Utilization category AC-5: 50V/ A / 500 VA acc.to EN * approx switchings (DC3: 6 switchings/ DC-3: 4V/ A/ 48W minute) approx switchings Contacts positively driven relays, AgCuNi Operating Life Mechanical 50 million switchings Fuse Protection A slow Dimension Sheet Stick-on labels in the following languages: en, fr, it, es, sv Drift Función Skyddskrets aktiv Givarfel Presencia Funzione Fallo del sensor ESD3 ESD3 Service Commutazione di sicurezza Anomalia periferica ESD3 Arrêt de sécurité Dérangement détecteur ESD3 Safety Stop Power Error ESD3 Error Signal Indicator Relay Switching Capacity 4VDC/A, resistive load 30 VAC/ A, resistive load Indicators LED 3 mm Operation Green Error Red (sensor resp. system error) Safety Switch-off Yellow (sensor) Reaction Time relay < 50 ms Temperature Range Operation 0 C to +55 C Storage 0 C to +80 C Humidity max. 80% relative (no condensation allowed) *If not mentioned ratings are required, ask for them at the manufacturer. For 4 VACDC supply voltage must be obtained from a safety trafo according to IEC74. The wiring must be protected against mechanical damage. Detailed assembly and operating information can be obtained from the Operating Instructions enclosed with the product Order Information e.g. Type ESD3-03 etc. see variation table Supply voltage 30 AC 5 AC 4 ACDC ESD AC Specifications are liable to change in accordance with product improvement. 4 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
7 Switching Units ESR-/-3 Safety Category, 3, according to CEN Bircher M3 Housing -pin Plug Large Selection Switching Units ESR Connected s are monitored for changes in the continously flowing no-load current. In the non-activated condition both relays are energised. When one or more s are activated the total resistance sinks towards zero ohm if the value falls below the defined threshold (6 kohm) the relays are de-energised theyellow LED illuminates Type ESR- ESR- Safety Category Two channel design Simple signal evaluation Recognition of Errors P F F Fa Fb When a Error occurs in the circuit the total resistance rises towards infinity if the value rises above the defined threshold ( kohm) the relays are de-energised thered LED illuminates (5) 3(8) 4(7) 34(9) A() A(0) F S F S 4(3) (4) () 3() (6) M M N without uxillary Contact with Auxillary Contact Upper Switching Threshold Nominal Resistance Resistance ~ kohm 8. kohm ESR- In addition to ESR- Simple signal evaluation per output Lower Switching Threshold ~6. kohm P F Signal Output Relay Contacts Connection (5) 3(8) 4(7) 34(9) A() A(0) F S F S 4(3) (4) () 3() (6) M F M F3 The maximum length of the with cable must not exceed 5 metres Maximum surface area 5 m Multiple s are to be connected in series The total resistance must not exceed 8. kohm N Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)
8 ESR-3 In addition to ESR- Error indication connection P N 74 F (5) 3(8) 4(7) 34(9) A() A(0) F S F S 4(3) (4) () 3() (6) ESR-3: Error indication relay. Contacts open when error ESR-3M: Error indication relay. Contacts closed when error Dimension Sheet Error collecting loop Error indication M F Technical data ESR- Housing Type M3, Material Red Noryl Isolation Class IP 30 (IEC 59) Weight max. 50 gramm (depending on type) Power Supply DC voltages are battery power only - Type ESR-. -4VADC 4-36VAC/4-48VDC (±0%) - Type ESR-. -5VAC (+0%/ 0%) with isolating transformer - Type ESR-. -30VAC (+0%/ 0%) with isolating transformer Frequency Range 50/60 Hz (45 66 Hz) Power consumption max. 3 VA Duty Cycle 00% ED Signal Output Relay/ Error Indication Relay - Switching Capacity 50 VAC/5 A (ohm) - Contact Material Hard silver - Operating Life Mechanical 00 million switchings Electrical switchings at 50 VAC/5 A - Fuse Protection 5 A slow Indicators LED 5 mm - Operation Green - Function Yellow -Error Red Reaction Time < 70 ms Temperature Range - Operation 0 C to +50 C - Storage 0 C to +80 C Humidity max. 80% relative 6 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
9 Switching Units ESR5/6 Pin Plugable Socket GS-BE-7 and ZH /494 -/-Channel General The difference between the ESR5 and ESR6 is that the ESR6 has two separate evaluation circuits. Function Connected sensors are monitored with a terminating resistance of 8. kohm to detect changes in the constant flowing zero-signal current. Both relays are energised in the non-active condition. If one or more sensors are activated the total resistance drops towards zero ohm when the resistance falls below the defined limit (approx. kohm) the relays de-energise the yellow LED illuminates Connection max. total length of sensor with cable 50 m max. total area of sensor 5 m multiple sensors are connected in series the total resistance must not exceed 8. kohm Important: The installed fuse is absolutely neccesary. It protects the relay contacts against «welding» when overloaded. Suppressors (0 Ohms/0. μf) are to be connected across the connected loads. Periodical function test are to be made. The designated test contacts are to be bridged (see Layout). The applied tests are to be documented. Further installation instructions can be obtained from the operators manual enclosed with the product. When a fault occurs in the sensor circuit (cable breakage, sensor defect ) the total resistance increases when the resistance exceeds the defined limit (approx. 9 kohm) the relays de-energise the red LED illuminates Terminal/Connections Terminal ESR5 ESR6 A,A (,0) Supply 4VACDC Supply 4VACDC,3 (5,8) -Input -Input 4,34 (7,9) -Input (or 8. kohm) -Input, (,6) Safety-Output Safety-Output,4 (3,4) Safety-Output 3 () Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)
10 Block Diagram Technical Data (5) 3(8) 4(7) 34(9) or 8.kOhm resistance Supply A() Voltage A(0) R R3 ESR5 two parallel sensor inputs safety output supply voltage 4VACDC redundant evaluation of the sensor Supply Voltage (5) 3(8) 4(7) 34(9) A() A(0) R R3 R R4 ESR6 two separate sensor inputs two separate safety outputs supply voltage 4VACDC redundant evaluation of both channels F F F () Drive Circuit (6) () Drive Circuit (6) 4(3) Drive Circuit (4) Housing NORYL, red Face Black Dimensions 85 x 74 x 36 mm Plug-socket -Pin Isolation Class IP30 Isolation Class IP54 Application area Temperature Range 0 C +55 C Power Supply 4 VACDC ±0% Frequency 50/60 Hz Power Consumption - ESR5 < 3 VA - ESR6 < 5 VA Input ESR5 - Reaction Value «Activated» <.3.5 kohm - Reaction Value «Interruption» > kohm Input ESR6 - Reaction Value «Activated» <.4.8 kohm - Reaction Value «Interruption» > kohm -ReactionTime max.ms Signal Output Relay A/50 VAC per channel Display LED 3 mm - Operation Green - Safety Switch-off Yellow - Error (Interruption) Red Test Specifications GS-BE-7 (April 98) and ZH /494 (Issue August 994) Overvoltage Category II (EN 600-) Contamination Grade (EN 600-) Protection Class 0 (EN and EN ) LED Status Supply Voltage Function Green Yellow Red Output Off Open On Ready Close On One sensor activated Open On Short-circuit or Test Open On Cable breakage Open 8 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
11 Layout Dimension Sheet ESR5 F REL3 REL J4 J LED Ordering Information ESR6 e.g. ESR5-4VACDC F REL REL3 F REL REL4 J3 J4 J J LED Type ESR5 ESR6 Supply Voltage 4ACDC LED5 LED6 LED, LED LED3, LED4 REL, REL3 REL, REL4 F F J J J3 J4 Operation Display (green) Operation Display (green) (only ESR6) Function Display (yellow) Error Display (red) Switching Circuit, Working contact switched in series Switching Circuit, Working contact switched in series (only ESR6) Fuse Amp slow Relay contact protection Fuse Amp slow Relay contact protection (only ESR6) Test Contact for REL Test Contact for REL4 (only ESR6) Test Contact for REL (only ESR6) Test Contact for REL3 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)
12 Switching Unit ESA 5 (A = Installation Housing) ESP 5 (P = Printed Circuit Board) IP65 Protection Class (ESA 5) Installation Housing Redundant signal evaluation Switching Units ESA Connected s are monitored for changes in the continously flowing no-load current. In the non-activated condition both relays are energised. ESAS 5, ESPS 5 / Stop-Restart Basic function as ESA 5/ESP 5 Additional when the is activated for sec. the third relay contact closes for.5 sec. (restart) ESA 5, ESP 5 When one or more s are activated the total resistance sinks towards zero ohm if the value falls below the defined threshold the relays are de-energised the yellow LED illuminates Safety Contact Restart ~s ~.5s Wiring Diagram For each sensor two redundant channels are available. The two output contacts are connected in series and protected with a fuse. 3 Safety Circuit 4 3 Drice Circuit 4 Supply 5 6 τ ~ = Restart 8 Supply 5 6 ~ = ESAS 5 / ESPS 5 ESA 5 / ESP 5 0 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
13 Connection The maximum length of the must not exceed 50 metres Maximum surface area 5 m Multiple s are to be connected in series The total resistance must not exceed 8. kohm Important: the installed fuse is absolutely necessary - to protect the relay contacts from «welding» when overloaded Suppressors (Type 0 Ohm/0. μf) are to be connected across inductive loads The assembly and operating instructions are described in the Assembly and Operating Manuals supplied with the product. Technical data ESA 5 ESP 5 Housing ABS grey transparent cover Dimensions 80 x 0 x x 94 - Protection Class IP65 IP00 - Cable gland 3 x PG9 Supply Voltage 30 VAC (+0/ 0%) with isolating trafo 5 VAC (+0/ 0%) with isolating trafo 4 VADC (+0/ 0%) Frequency Range 50/60 Hz Power Consumption max. 4 VA Inputs - Input resistance 5 kohm to V (internally) - Input voltage with 8.kOhm approx. 7.5 VDC Signal Output Relay - Switching Capacity A/50 VAC - Reaction time < 5 ms - Reaction time by interrupt < 5 ms Indicators LED 3 mm - Operation Green - Safety Shutdown Yellow ( off) - Error (interrupt) Red ( off) Temperature Range 0 C to 55 C Testing Basis GS-BE 7 and ZH /494 Additional Data Function «Restart» ESAS 5 ESPS 5 Housing see ESA Cable Gland x PG7, 3xPG9 Relay fro Restart Function - Switching Capacity A/50VAC - Time Delay.5sec - Impulse Time.5 sec Status LED Supply Function Green Yellow Red Output Off Not ready open On Ready closed On activated open On Short-circuit or test open On Cable breakage open Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
14 Dimension Sheets Print Version Installation Housing LED J LED LED4 J REL REL LED3 LED5 TR F = = PG7 PG7 PG9 ESA/ESP ESA 5 Terminals/Connection Layout: 3,4 Safety Circuit 5,6 Supply, LED J LED LED4 J REL REL3 REL LED3 LED5 F TR = = 70 PG7 PG9 ESAS Connections, Component Layout LED Operating indicator (green) LED, LED4 Function indicator (yellow) LED3, LED5 Error indicator (red) REL, REL Switching circuit, working contacts switched in series F Fuse A slow, relay contact protection J Test contact for REL J Test contact for REL ESAS/ESPS Terminals/Connection Layout: 3,4 Safety Circuit 7,8 Restart 5,6 Supply, Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
15 Overview ESA/ESP Total Programme OPEN ESA 5 ESA 5-R ESA 5-D ESAS 5 ESAS 5-R ESAS 5-D ESP 5 ESP 5-R ESP 5-D ESPS 5 ESPS 5-R ESPS 5-D ESZ-5 ESZ-5.D ESZS-5 ESZS-5-D Order Information e. g. ESPS 5-30 AC Type ESA Standard Unit ESP Standard Print Version ESAS Stop-Restart ESPS Stop-Restart Print Version ESZ plugable Supply Voltage 4VADC 5VAC 30VAC Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)
16 Switching Units ESQ GS-BE7 and ZH /494 4-channel Housing IP65 Redundant evaluation Connection General The ESQ is a electronic switching unit of the ES family. It controls sensors to a zero-signal current. Function Connected sensors are monitored with a terminating resistance of 8. kohm to detect changes in the constant flowing zero-signal current. All relays are energised in the non active condition. max. total length of one sensor system with cable 50 m max. total area of one sensor system 5 m multiple sensors are connected in series the total resistance must not exceed 8. kohm Important the installed fuse is absolutely necessary. It protects the relay contacts against «welding» when overloaded. Suppressors (0 Ohms/0. μf) are to be connected across the inductive loads. Periodical function tests are to be made (see Assembly, Commissioning, Periodical Tests) If one or more sensors are activated the total resistance of the sensor system drops towards zero ohm the resistance falls below the defined limit (.5 kohm) the safety relay de-energises the appropriate service relay de-energises (no safety output) the yellow LED illuminates according to the illustration «Status LED» When a fault occurs in a sensor circuite (cable breakage, sensor defect ) the total resistance of the appropriate sensor system increases the resistance exceeds the defined limit (9 kohm) the safety relay de-energises the appropriate service relay de-energises (no safety output) the red LED illuminates according to the illustration «Status LED» 4 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
17 Status LED safety edges service 3 4 safety safety edges ready activated cable breakage LED red on yellow on off outputs: (relays) closed open Terminal/Connections, -Input 3,4 -Input 5,6 -Input 3 7,8 -Input 4 9,0 Supply 4VACDC, Service-Output 3,4 Service-Output 5,6 Service-Output 3 7,8 Service-Output 4 9,0 Safety-Output Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)
18 Block Diagram Tecnical Data AT Housing ABS, gray, cover transparent Dimensions 0 x 00 x 75 mm Isolation Class IP65 Temperature Range 0 C to 55 C Power Supply 4 VACDC ±0% Frequency 50/60 Hz Power Consumption < 6 VA Reaction Time max. 5 ms Signal Output Relay - Safety A/50 VAC - Service A/50VAC per channel Display LED 3 mm - Operation green - Safety Switch-off yellow ( for status relay) - Error (Interruption) red ( per channel) - Service yellow ( per channel) Overvoltage II (EN 600-) Contamination Grade (EN 600-) Test Specifications GS-BE-7 (Aug. 94) and ZH /494 Protection Class 0 (EN and EN 60335) RED YELLOW four parallel sensor inputs one safety output four service outputs supply 4VACDC redundant evaluation of sensors 6 Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687
19 Layout Dimension Sheet LED3 J J J3 J4 J5 J6 J7 J8 LED LED LED3 LED4 LED6 LED7 LED8 LED9 LED LED LED3 LED4 LED6 LED7 LED8 LED9 LED5 LED0 LED LED LED5 LED0 REL REL REL 5 REL 6 REL 3 REL 4 F , , 60 red yellow LED, 4, 7, 9,, 4, 7, 9 LED, 3, 6, 8,, 3, 6, 8 LED5, 0, 5, 0 LED, LED3 REL,, 3, 4 REL5, 6 F Function sensor (yellow) Error (red) Function display relay Service (yellow) Function display relay Safety (yellow) Operation display (green) Service Safety Fuse Amp slow, Relay contact protection J, 3, 5, 7 Test contact for REL,, 3, 4 and REL5 J, 4, 6, 8 Test contact for REL6 Order Information ESQ5-4VACDC Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)
20 8 Note: Technical details and recommendations concerning our products are based on experience and are an aid for the orientation of the user. Details stated in our brochures and data sheets do not guarantee special properties of the products. This does not apply to special product properties confirmed in writing or individually on a case-by-case basis. Subject to technical alterations. Bircher Reglomat AG, Wiesengasse 0, CH-8 Beringen, Switzerland, Phone +4 (0)5 687, Fax +4 (0)5 687 D EN 0/0
Switching devices. ESD, ESR, ESA, ESP and EsGate. Simple, flexible, safe. Easy installation
ESD, ESR, ESA, ESP and EsGate Simple, flexible, safe Easy installation Can be configured for an extremely wide range of applications www.bircher.com High level of safety thanks to tried-and-tested technology
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationPositive-guided relay outputs: 4 safety contacts (N/O), instantaneous
ohne Abbildung Contact expansion module for increasing the number of available contacts Approvals PZE X4.1P with universal power supply Unit features Positive-guided relay outputs: 4 safety contacts (N/O),
More informationSafe monitoring relays
monitor for safe standstill monitoring Approvals Block diagram Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous LED indicator
More informationPositive-guided relay outputs: 4 safety contacts (N/O), instantaneous
Contact expander module for increasing the number of available contacts Approvals Unit features Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous LED indicator for: Switch status channel
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Block diagram Unit features Positive-guided relay outputs: 6 safety contacts (N/O), instantaneous 4 auxiliary
More informationE-STOP relay, safety gate monitor
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor output Connection options
More informationE-STOP relay, safety gate monitor
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor output Connection
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Unit features Positive-guided relay outputs: 7 safety contacts (N/O), instantaneous 2 auxiliary contacts (N/C),
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 2 safety contacts (N/O), delay-on de-energisation
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Two-hand control unit for press controllers and safety circuits Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous 1
More informationControl unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V
Innovative by tradition. Control unit SG-EFS 104/4L EN Operating instructions Version 2 1004128 SG-EFS 104/4L AC/DC 24 V Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY
More informationControl unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~
Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY
More informationSafety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E
EN 60204-1 Stop category 0 EN 954-1 Safety category 4 Basic device to EN 60204-1 and EN 954-1 single E-stop monitoring. Manual or automatic start Application up to safety category 2 and stop category 0
More informationSafety mats. sensing the future. Electrical surface switches for safe activation and deactivation of machines, devices and automatic doors
sensing the future Electrical surface switches for safe activation and deactivation of machines, devices and automatic doors Reliable, robust, low-maintenance System is simple to install Surface switch
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 5 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Connection
More informationSECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i
SECTION 16 VIPER Safety Relays Type: SCR-i (with added diagnostics) SAFETY RELAY FUNCTION: IDEM s VIPER SCR-i range of Safety Relays have been designed in accordance with EN60204-1 for safety circuits
More informationE-STOP relays, safety gate monitors
Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Reset button LED indicator for: Switch status channel 1/2 Supply voltage See
More informationE-STOP relays, safety gate monitors
E-STOP relays, safety gate monitors Up to Category 2, EN 954-1 Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Reset button
More informationPolymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3
Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 2 safety contacts (N/O), delay-on de-energisation
More informationPRSU/5 Safety Interface Controller
PRSU/5 Safety Interface Controller Installation Instructions 1. INTRODUCTION Tapeswitch PRSU/5 control units are designed to be used with Tapeswitch pressure sensitive sensors to form a complete safety
More informationPlug-in module SIRAX TV 808, 2 channels Isolating Amplifier unipolar/bipolar
Plug-in module SIRAX TV 808, channels For electrically insulating, amplifying and converting DC signals Application The purpose of the isolating amplifi er SIRAX TV 808 (Fig. ) is to electrically insulate
More informationOperating Instructions
Innovative by tradition. Operating Instructions Control Unit SG-RSV 239 Version 1 1003986 SG-RSV 239/24 24 V= 1005372 SG-RSV 239/36 36 V= 1003271 SG-RSV 239 50-150 V= Mayser GmbH & Co. KG Örlinger Straße
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O),
More informationVEO. V2UF230V10 Art.Nr.: TECHNICAL DATA
Continous voltage monitoring Mains fluctuation detection Detects voltage drop / short interruptions of at least 10ms Prevents undefined states in switching and control systems Generates reset pulse after
More informationFor full product information, visit Use the SpeedSpec code or scan the QR Code for quick access to the specific web page.
R Safety Monitoring Relays For full product information, visit www.sti.com. Use the SpeedSpec code or scan the QR Code for quick access to the specific web page. Dual-Channel Safety Monitoring Relay Power
More informationE-STOP relays, safety gate monitors
Unit features Safety gates Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided relay
More informationSafety relays PNOZsigma
Safety relays PNOZsigma Configuration guide, safety relays PNOZsigma Technical catalogue 3.2 November 2008 edition Why does Pilz offer more? Because the integrality of our business activities is what sets
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Unit features Safety features Gertebild ][Bildunterschrift_nur_Not-Halt Safety relay for monitoring E-STOP pushbuttons Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous
More informationContact protection relay
Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts
More informationTwo-hand control unit
Gertebild ][Bildunterschrift_Zweihand Two-hand control unit for press controllers and safety circuits Approvals Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous
More informationPolymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3
Operating Instructions Control Unit SGRST 153 Version 0.3 1004931 SGRST 153 Original instructions GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY Tel.: +49 731 20610 Fax: +49 731 2061222 EMail: info.ulm@mayser.com
More informationSafe timer relay/contact expansion modules
Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for unlocking an interlock with
More informationE-STOP relays, safety gate monitors
Unit features Positive-guided relay outputs: 2 safety contacts (/O), instantaneous Connection options for: E-STOP pushbutton Reset button LED indicator for: Switch status channel 1/2 Supply voltage See
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Gertemerkmale Positive-guided relay outputs:
More informationSNO 4062K SNO 4062KM SNO 4062 K / KM. Circuit diagram. Applications. Function. Function (Continued)
SNO 4062K SNO 4062 K / KM Basic unit for emergency stop and guard door applications Basic unit as per DIN EN 60204-1 and EN ISO 13849-1 for single or twin channel emergency stop monitoring. PL e and category
More informationE-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous Connection
More informationE-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous
More informationArticle no. BWU2045: AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input 1.23 NC
Safety + standard I/O in one module AS-i Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category
More informationChassis Power Supplies
PDC24 / PAC Chassis Power Supplies (PDC24 / PAC) Issue 3 October 2005 INTRODUCTION PURPOSE Two Power Supply Units (PSUs) provide a dual-redundant source of 5.4Vand 12Vdc onto the backplane for the modules
More informationPSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B
Safety Relay as a Contact Extension Block INTERFACE Data Sheet PHOENIX CONTACT - 05/2006 Description The PSR-...- 24DC/URM4/4X1/2X2/B safety relay can be used as a contact extension block in safety circuits
More informationsigno 727 SSI operating instructions
operating instructions signo 727 SSI Position-Indicator with/without limit values and SSI input from absolute encoder 1. Safety instructions This instrument has been built and tested in accordance with
More informationAS-i 3.0 motor module
3.0 motor module 3.0 motor module for two 4 V motorized rollers Itoh Denki (PM00ME/XE/XP, PM60ME/XE/XP) with 4 binary and analog outputs Mixed input/output slave Speed setting of parameter Protection category
More information02/11/2015
DIN Rail Mount 35 mm HSV Part number 84874320 Control of overspeed, underspeed, operating rate, stopping Measurement via discrete sensors - 3-wire PNP or NPN, Namur, voltage 0-30V or volt-free contact
More informationMultifunctional time delay relay MFT U31S, MFT U41SE
8 Functions, 8 time ranges Multivoltage: 24 Vac / dc 110... 240 Vac 2 output contacts MFT U31S Functions E Delay on E Delay on - version with control contact as opening contact A Delay off without auxiliary
More informationSIGUARD Safety Combinations and Safe Load Feeders. safety INTEGRATED
SIGUARD Safety Combinations and Safe Load Feeders safety INTEGRATED EMERGENCY Topmost priority protection of man, machine and the environment The topmost priority is to protect man, machine and the environment
More informationBNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS
BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS Safety Controller Suitable for use with Coded-Magnet Sensor Part Numbers below BNS250... BNS33... BNS303...
More informationAS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input
Safety + standard I/O in one module Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category IP20
More informationSafety Monitoring Relays
Safety Monitoring Relays Contents Selection Guide I-2 Safety Monitoring Relays G9SA I-6 SR101A I-12 SR103AM I-13 SR104P I-17 SR105E I-17 SR106ED I-21 SR108AD & SR109AD I-18 SR120MP I-21 SR125SMS45 I-22
More informationProduct and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING
Product and Applications Description Note If the application program is not loaded completely by the ETS, you had better interrupt the 24 V voltage supply of the I/O-module during the loading interval.
More informationPhase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details
Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE 1SVR 550 882 F 9500 CM-PBE Yellow LED - state of relay voltage and single-phase supply voltage for phase failure Monitoring of neutral
More informationE-STOP relays, safety gate monitors
Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Safety gate limit switch Reset button Light barriers LED indicator
More informationVEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA
Monitoring of phase sequence and phase loss Monitoring of asymmetry Supply voltage 208-480 V AC Supply circuit = measuring circuit 1 change-over contact Width 22,5 mm Control elements Asymmetry Status
More informationOriginal operating instructions Safety relay with relay outputs G1501S / / 2016
Original operating instructions Safety relay with relay outputs G50S UK 8023637 / 00 02 / 206 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...5 3 Items supplied...6 4 Functions
More information24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0
monitoring in conductive liquids 4 probe inputs for level monitoring Multifunction Adjustable sensor voltage Supply voltage 24-240V AC/DC Protective separation of measuring circuit 3 normally open contacts
More informationControl elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.
On-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status
More informationImmersion Temperature Sensors
1 782 1782P01 Symaro Immersion Temperature Sensors QAE2164 QAE2174 Active sensors for acquiring the water temperature in pipes and tanks Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V or
More informationRM35LM33MW liquid level control relay RM35-L V AC/DC
Characteristics liquid level control relay RM35-L - 24..240 V AC/DC Complementary reset time maximum switching voltage Main range of product product or component type relay type relay name relay monitored
More informationGS202 Encoder Switch
GS202 Encoder Switch 20:2 encoder switch 20 encoder inputs (TTL / RS422 standard) Input signals A, /A, B, /B, Z, /Z on each encoder input 2 x 6 control inputs (HTL / PNP) 2 encoder outputs (TTL / RS422
More informationMonitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064
Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window
More informationPSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1
PSR-SCP- DC/SSM/2X1 PSR-SPP- DC/SSM/2X1 Safety Relay With Downtime Monitoring INTERFACE Data Sheet PHOENIX CONTACT - 05/2006 Description The PSR-...- DC/SSM/2X1 safety relay can be used in safety circuits
More information4 C/O. Contact material AgNi AgNi gold-plated Nominal contact current Inrush current
Quattro-Relais Quattro Relay 4 Quattro Relay 4A4 Standard type / With LED and protection diode on request Quattro-Relais Order Code Order Code Quattro Relay 4 A 4 4 V DC N Type of relay Quattro Relay 4
More informationOriginal operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016
Original operating instructions Safety relay with relay outputs with and without delay UK G50S 803638 / 00 0 / 06 Contents Preliminary note...4. Symbols used...4 Safety instructions...5 3 Items supplied...6
More informationVEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA
4 time ranges 4 transition times Supply voltage 12-240V AC/DC 2 normally open contacts Width 22,5 mm Control elements Fine adjustment star contactor Setting of time range star contactor Transit time Status
More informationE-STOP relay, safety gate monitor
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 7 safety contacts (N/O),
More informationOperating instructions. Switching amplifier DN0210 DN / / 2015
Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5
More informationTime Counters mini "h", DC Version
Type 633-DC Time Counters mini "h", DC Version Type 633.0 Type 633.7 Type 633.8 High shock resistance Miniature dimensions Electrical connections in standard grid Suitable for PCB mounting Machine-solderable
More informationVital. Safety controller. Approvals: Control of: Features: Entire safety system based on the dynamic safety circuit.
Safety controller Vital Approvals: TÜV Nord Vital 1 TÜV Rheinland Vital and 3 Control of: Entire safety system based on the dynamic safety circuit. Features: Vital is based on a single channel safety concept
More informationBETRIEBSANLEITUNG TECHNICAL INSTRUCTION INTERFACE PSE2-SC-02 (24 V AC/DC) Version 1.4
Safety regulations - The unit should be installed and operated by persons, who are familiar with these instructions and the current regulations for safety at work and accident prevention. Follow local
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
More information02/11/2015
DIN Rail Mount 22.5 mm ETM2 Part number 84874023 Version ETM : Controls temperature of machines using built-in PTC probes Line break or probe short-circuit detection Version ETM2 / ETM22 : Fault latching
More informationInstallation Manual for D244X Series 24-volt Power Supplies
Installation Manual for D244X Series 24-volt Power Supplies D2441-B D2441-C D2443-B D2443-C D2445-B D2445-C D2400 Series 1A 24 volts 1A 24 volts 3A 24 volts 3A 24 volts 5A 24 volts 5A 24 volts Dycon Power
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Gertebild Bildunterschrift Two-hand control device for safety circuits Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary
More informationIndustrial Power Supplies
50-600 Watt Features Switch mode power supplies for DIN-rail mounting 6 power ranges with 2, 3, 6, 12, 20 and 24 A output current (24 VDC models) Selectable 115/ 230 VAC input Very low ripple and noise
More informationMODULES FOR SAFETY AND MONITORING
MODULES FOR SAFETY AND MONITORING Woertz AG Hofackerstrasse 47, P.O. Box 948, CH-43 Muttenz, Switzerland Tel. ++4 6 / 466 33 33, Fax ++4 6 / 46 96 06 http://www.woertz.ch Woertz-USA 5 Discovery Drive,
More informationDual Channel Monitor for Measurement of Speed and Ratio with SIL1 requirements Series D224.xx
D224 Dual Channel Monitor for Measurement of Speed and Ratio with SIL1 requirements Series D224.xx D224 Front View KEY FEATURES SIL1 / IEC 61508:2010 compliant Dual Channel Speed and Ratio Monitor with
More informationTechnical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):
Safety module CS AR-91, according to EN 81 Safety modules for the lift automatic floor levelling operation according to EN 81 Main functions For safety applications up to SIL 3 / PL e Choice between automatic
More informationSlim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations
Slim Relay G2RV The World's First Industrial Slim Relay Large plug-in terminals for reliable connection. LED indicator and mechanical flag to check operation. Transparent housing enables checking relay
More informationSafety controller unit B1 /
Version 1.0 Safety controller unit 470111B1 / For 2 to 16 safety sensors 470115B1 PL d in acc. with EN ISO 13849-1 / SIL CL 2 in acc. with EN IEC 62061 Two safety outputs and external contactor monitoring
More informationSafe monitoring relays
Unit features Unit description Gertebild ][Bildunterschrift_Stillstandswchter Standstill monitor for safe standstill monitoring Approvals Zulassungen Gertemerkmale Positive-guided relay outputs: 2 safety
More informationFaults on the system Proximity switch connection technology:
Speed monitor for connection to a base unit from the PNOZmulti modular safety system Approvals Unit features Monitoring of 2 independent axes Connection of 2 incremental encoders or 4 proximity switches
More informationPSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B
PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B Safety Relay for Emergency Stop and Safety Door Circuits INTERFACE Data Sheet 102858_02_en PHOENIX CONTACT - 12/2006 Description The PSR-...- 24DC/SDC4/2X1/B
More informationLENORD. +BAUER... automates motion. Tower oscillation monitor GEL 3011 for safety applications. Technical information Version General.
Tower oscillation monitor GEL 3011 for safety applications LENORD +BAUER... automates motion. Technical information Version 12.13 General 3-axis tower oscillation monitor in compact design Redundant system
More informationLCI User Manual mantracourt.com
LCI User Manual mantracourt.com LCI Load Cell Junction Box with Fault Monitor Contents Chapter 1 Introduction to the LCI... 2 Chapter 2 Installing the LCI... 3 Chapter 3 Setting up the LCI... 4 Sequence
More informationVEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA
Off-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5 mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status
More informationSafety Control Relay Product Catalog
Product Catalog Wall Mount for use with Safety Mats Safety Edges Safety Bumpers Safety Sensors 2 wire Safety Sensors 4 wire DIN Rail Mount Intrinsically Safe Explosion Proof Wall Mount Introduction The
More informationISOMETER isopv with coupling device AGH-PV
Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) for photovoltaic plants up to AC 793 V/DC 1100 V Vorläufiges Datenblatt IsoPV_D00024_02_D_XXEN/07.2018 ISOMETER with coupling
More informationDatasheet - SLB 200-C04-1R
14.02.2013-17:06:30h Datasheet - SLB 200-C04-1R Safety light barriers / Safety monitoring modules to monitor safety light barriers / SLB 200-C Up to 2 light barrier pairs SLB 200 can be connected 1 safety
More informationTwo-hand control unit
Unit features Safety features Gertebild ][Bildunterschrift_Zweihand Two-hand control unit for press controllers and safety circuits Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts
More informationSafe timer relay/contact expansion modules
Gertebild Bildunterschrift Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for
More informationPSR UC/ESAM4/3X1/1X2/B
Safety relay for emergency stop and safety door monitoring Data sheet 105318_en_02 PHOENIX CONTACT 2014-06-13 1 Description The safety relay can be used in safety circuits according to EN 60240-1 and IEC
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O),
More informationPSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description
SIL 3 coupling relay for safety-related switch on Data sheet 105818_en_01 PHOENIX CONTACT 2014-08-18 1 Description The PSR-PC50 SIL coupling relay can be used for power adaptation and electrical isolation
More informationOperating instructions. Standstill monitor A / / 2011
Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II
More informationPSR DC/ESP4/2X1/1X2
PSR-...- 24DC/ESP4/2X1/1X2 Safety relay for emergency stop and safety door monitoring Data sheet 100516_en_05 PHOENIX CONTACT 2013-11-21 1 Description The safety relay can be used for emergency stop and
More information120 WATT FLEX ATX TYPE WITH ACTIVE PFC
120 WATT FLEX ATX TYPE WITH ACTIVE PFC FXA120-W-F SERIES GENERAL SPECIFICATION This specification describes the performance characteristics of a grounded, with active PFC function, single phase, 120 watts,
More informationLVX Control Unit. Features:
Date 2013-02-28 Control Unit Features: Most parameters can be defined as required for your interfaces. You decide which information is output and how. Fast cycle times, just a few µs/beam. Maximum beam-count
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Kein Gerätebild vorhanden Gertemerkmale Positive-guided relay outputs:
More informationSafety control unit B1 / B1. for 2 to 16 machine safety sensors. Use. Types. + PLd according to EN ISO
Safety control unit for 2 to 16 machine safety sensors 470 121 B1 / 470 125 B1 + PLd according to EN ISO 13849-1 + two safety outputs and external contactor monitoring + for sensors with N.O./N.C. system
More information