1 VOLUME THREE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Cost of Owning a Chiller What is your bottom line? What Should You Consider? Understanding chiller energy consumption What is Chiller System Optimizer? Calculating the system part load... 3 Using Chiller System Optimizer to Help Optimization Can Save Time and Money Glossary of Terms Want to know more about system part load value? Call CARRIER and request the publication HVAC Analysis, Vol. 3, No. 3, written specifically for consulting engineers, or visit our website at System Part Load Value: A Case for Chiller System Optimization What Does It Cost to Own a Chiller? What does it cost to own two or three or four chillers installed in a central plant? The answer may not be what you think. Within the engineering community, there is an ongoing, behind-thescenes debate that may have a direct effect on your bottom line. The question centers on water chillers: how they are specified, and how they perform. The Air Conditioning and Refrigeration Institute (ARI) 1 develops and publishes technical standards that establish rating criteria and procedures for certifying equipment performance. 1 ARI is a national trade association representing manufacturers of more than 90% of the U.S. produced central air conditioning and commercial refrigeration equipment. In 1998, ARI revised their Standard 550/590, which defines the industry-accepted method of rating chiller performance. Since most chillers rarely operate at full load, the important criterion is how chillers perform at part load. The basic performance measure defined by ARI 550/ is the Integrated Part Load Value (IPLV). IPLV is a single number representation of part load performance calculated at standard operating conditions. For conditions other than standard, ARI 550/ also defines Non-Standard Part Load Value (NPLV) (see Glossary of Terms). The intent of IPLV (or NPLV) is to allow simple, uniform comparison of different chillers much the same as

2 Seasonal Energy Efficiency Ratio (SEER) is used for residential-type equipment. For instance, if choosing between two chillers, one with an IPLV of 0.50 kilowatts per ton, and a second with an IPLV of 0.54 kilowatts per ton, the apparent indication is that the first chiller is more efficient because it uses less electricity per ton of cooling. Unfortunately, this is not necessarily the case. Chilled water plants are complicated systems with different equipment types (i.e. chillers, pumps and cooling towers) that have interdependent performance relationships. These performance relationships are influenced by weather conditions, the building load profile, operating hours, the total number of chillers and other factors. In most cases then, real differences in energy consumption will not be what is indicated by the IPLV rating, because the IPLV specification used to buy the chiller is not representative of any particular project. It is based on only one chiller operating, average weather data, and an assumed building load profile. Indeed, ARI recommends that it is best to perform a comprehensive analysis that reflects the actual weather data, building load characteristics, number of chillers, operating hours and other factors unique to that specific project. What Is the Debate? When engineers specify electric water chillers, they define size, operating conditions, materials of construction, and the chiller s minimum efficiency. Efficiency has traditionally been expressed as maximum allowable kilowatts of energy consumption per ton of cooling (kw/ton). But, efficiency is elusive. Actual chiller efficiency will vary depending on a host of variables: whether the unit is operating 2 75% Energy and Maintenance SYNOPSIS at full load, minimum load or somewhere in between, the weather, and water temperatures. So, the great debate is how to define the minimum chiller performance. Using current standards, engineers specify chillers using IPLV, NPLV or full-load kw per ton. Some may even still use APLV 2. IPLV and NPLV are, at best, coarse indicators of anticipated performance at certain specific conditions. Full-load kw per ton is a meaningful performance indicator only for chillers that operate continuously at full load. Most chillers operate at part load more than 99% of the time. None of these performance gauges will assure you, as a Lifetime Cost of Chiller Ownership building owner, that you are buying chillers to best fit your needs. 24% Chiller and Installation Based on a new chiller installation. Installation includes the cost of piping, valves, insulation, pipe supports, electrical wiring and chiller foundation. 2 Application Part Load Value. APLV was eliminated from ARI Standard 550/590 in FIGURE 1 1% Engineering Design Why Should I Worry? If you are focused simply on minimizing first cost, it doesn t really matter. Have the engineer specify a chiller that seems reasonable on energy use, that fits the budget, and be done with it. But for most owners that s not enough. Today, most building owners and corporations are sophisticated in their approach to energy issues. Many have full-time energy managers and have established minimum energy standards to govern new construction. Every new building project has a construction budget and an operating budget; the informed owners recognize the need to consider economic trade-offs between both. Over the life of a chiller, energy and maintenance costs can total more than three to five times the original

3 cost to buy and install the chiller. Figure 1 shows a typical distribution of lifetime chiller costs for a new chiller installation. For a basic chilled water plant with two 500-ton centrifugal water chillers, the total lifetime cost can be about $1.8 million! Think about it. If you are preparing to make an asset purchase that will ultimately cost millions of dollars, do you want to use the same standardized single-digit decision method that a homeowner would use to buy a residential air conditioning unit? Probably not. Do you expect accurate, informed consultation from your engineer? You should. What Should My Engineer Do? The footnotes in ARI 550/ recommend performing a comprehensive analysis using actual weather data, building load characteristics, the number of chillers, actual operating hours, economizer capabilities, and the energy drawn by auxiliaries such as pumps and cooling towers. This is what you, as a building owner and a client, should require from your engineer. But, understand that a comprehensive analysis can be a lot of work. Many engineers, squeezed between schedules, architects and price competition, have not been able to get the fees it takes to do that much work. It is hard enough just getting the systems designed, drawn and specified in the time allotted, let alone perform a detailed, applicationspecific part-load analysis. There needs to be an inexpensive tool to significantly improve your decision-making information that can be made available with only marginal increase in engineering cost. That is why Carrier developed Chiller SystemOptimizer. What is Chiller System Optimizer? Chiller System Optimizer is a non-manufacturer specific software program that simplifies chilled water system analysis. Your engineer, working together with your local Carrier representative, can use the software to evaluate chiller performance by taking into consideration all of the system and location factors recommended by ARI. One of the program s unique features is that it calculates the System Part Load Value () as an alternative to ARI s standard IPLV and NPLV indicators. Like IPLV and NPLV, is a single numerical indicator of part-load chiller performance. The crucial difference is that it is calculated specifically for your project. This is important. is an accurate, representative indication of chiller performance operating under conditions unique to your project. So, How Does Chiller System Optimizer and Help? There is a misconception that chillers operate most efficiently at full load. People often then tend to think of a chiller s overall efficiency in terms of the full-load kw per ton. The truth is that a chiller can operate most efficiently wherever you want it to operate most efficiently. Manufacturers have at their FIGURE 2 Cooling Ton-hrs Per Year disposal huge assortments of compressor and heat exchanger combinations. For a given size of chiller, a manufacturer may have upwards of 10,000 different combinations of compressors, impellers, heat exchanger shells and tubes. If desired, a chiller can be selected to be most efficient at full load, 50% load, or anywhere in between. To make the best selection, it is necessary to first know where the most efficient point should be. That is a function of building load profile, hours of operation, the number of chillers operating at any given time, and the energy consumption of pumps, cooling towers and other auxiliaries. Figure 2 shows a typical building load profile overlaid with a plot of the system chiller profile. It can be seen Typical System Performance Profile Taken from Chiller System Optimizer Output Cooling Tons hrs Building Load % Chiller System kw/ton Chiller System kw/ton 3

4 that most of the time the building load is between 46 and 84% of full load. Conversely, the chiller efficiency varies, reaching its best efficiency during periods when the building load is at about 39% of full load. The weighted average operating point for both chillers is at about kw/ton. This is the. Chiller System Optimizer provides the project criteria necessary to specify chillers that are optimized for your specific project. When you receive bids from chiller manufacturers based on these criteria, the quoted figures will be accurate, dependable numbers. Your engineer can input the bids and quoted performance data into Chiller System Optimizer to reliably evaluate life cycle cost. In addition to the chillers, Chiller System Optimizer considers the energy use of pumps, cooling towers and other system auxiliaries. This allows the engineer to evaluate and select the best chillers, and design a truly optimized system assuring the lowest life cycle cost to you. What Does The Tell Me? In the example in Figure 2, the chillers modeled have a full-load energy consumption of kw per ton and an NPLV of kw/ton. In this system and location, the chiller s actual part-load energy consumption, the, is about kw per ton. This is over 19% better than the full-load measure and nearly 10% better than the NPLV measure. TABLE 1 BOSTON CHICAGO DALLAS MINNEAPOLIS ORLANDO SAN FANCISCO SEATTLE TUCSON Performance of a Typical Building System, Weather is the Only Factor Changed in Each City Minimum Maximum Variation Between Sites But Does It Really Make Any Difference? Competitor A (R123 Centrifugal) Chiller Full Load kw/ton Chiller NPLV We wondered the same thing, so we took an example project and made comparisons between eight different cities using the Chiller System Optimizer software. Table 1 shows the performance of a typical building system with a 1,000-ton load served by two 500-ton centrifugal chillers. The system is identical for each city shown: the same chillers, pumps, cooling towers and control sequence. Weather data was the only thing changed for each city. Also, two different makes of centrifugal chillers were compared in each city. The chillers were selected with identical full-load kw per ton ratings. To remain objective in this discussion, we did not include a Carrier chiller % Competitor B (R134a Centrifugal) Chiller Full Load kw/ton Chiller NPLV % Variation Between Chillers -4.55% -3.25% -0.59% -3.69% 0.57% % % -5.78% The results are surprising. If you take a specification prepared for a project in Orlando and use it for a project in San Francisco, the actual performance may vary by nearly 19%. Also, depending upon which make of chiller is selected, the variation in performance can be as much as 11% at the same site even if both chillers meet the specification with identical full-load kw per ton ratings. continued on page 5 4 SYNOPSIS

5 5 continued from page 4 So, What Does That Mean to Me? Let s look at the most pronounced example, San Francisco. If the engineer s specification defines the minimum chiller performance as simply kw per ton at full load, all things being equal, the actual performance will vary by more than 11% depending on the make of chiller selected. Also, note that the Competitor B chiller with the larger NPLV () will actually operate more efficiently than the Competitor A machine () when evaluated as part of the overall system using sitespecific information. Why? Because NPLV (and IPLV) is calculated at a very narrowly defined profile that is not often representative of what is actually happening in the system. If the Competitor B chiller is installed, it will operate at about kw/ton on average. This is nearly 17% better than the indicated NPLV and more than 25% better than the full-load rating. Is that what you expected? Is that what your engineer was expecting? Would you be surprised to know that, in spite of both chillers meeting the engineer s 3 Estimate of annual energy cost is based on electrical rates of $0.05 per kilowatt-hour and $7.50 per kilowatt demand, and includes the energy cost of pumps and cooling towers. specifications, if you buy the wrong chiller it will cost you more than $6,500 each year 3 in higher energy cost? Over the life of the chillers that adds up to an additional $163,000! Was that in the budget? Is it possible that you would like to be part of that life cycle decision? OK, But Doesn t Optimization Analysis Take a Lot of Time and Money? Not any more. In the old days, optimizing the chiller and system selections would take days of tedious calculations. Today, using Carrier s Chiller System Optimizer, the analysis to optimize chillers and system components for a specific project can be accomplished in a matter of hours. All your engineer needs to know is the peak load of your building and the load at one or two other points (e.g. the conditions where load equals zero). The program interpolates a load profile based on the actual anticipated facility operating hours. For special applications, the program allows you to define the actual building load profile. Other features: Weather is selected from actual weather data for 189 cities in the United States or 180 international locations. You can specify exact chiller performance from selections prepared by Carrier or other manufacturers. In addition, the program has performance templates of actual chillers from Carrier, Trane, York and McQuay. The computer model will also accept different combinations of chiller size, type (centrifugal, absorption, air-cooled, etc.) and manufacturer up to a total of 12 chillers, including chillers operating with variable speed drives. You can compare different chiller sequencing control options. Cooling tower performance can be approximated, or it can be accurately defined. Carrier has included a cooling tower performance algorithm in the software (provided by Baltimore Aircoil) to predict the actual tower performance. You are able to define specific economic criteria for your project: life cycle period, currency, different inflation rates for different items, energy rates for natural gas, electricity and steam, and the minimum rate of return. Costs for equipment, construction, maintenance, water treatment and other factors can be included. The program automatically performs the life cycle cost analysis between different options and systems that you define. When Should Chiller System Optimizer Be Used? Chiller System Optimizer fits into the design process in several locations. First, during preliminary design. When cooling loads have been approximated and the engineer is working with the architect to develop the building concept, Chiller System Optimizer can help determine the type of chilled water system to use. This allows the engineer to define space requirements for chillers, pumps and cooling towers. Second, during detailed design, Chiller System Optimizer can be used to define the exact criteria to be used

6 6 in the chiller specifications. Also, in retrofit projects, Chiller System Optimizer helps the engineer to specify chillers and equipment that will be truly optimized, providing the best return on investment for the project. Literally speaking, the time to use Chiller System Optimizer is now. Consider this: The time and expense of performing chilled water system optimization the old fashioned way has driven engineers into using simplified methods of specifying chilled water equipment. These methods are not indicative of true system performance, and leave you, the building owner, in the dark regarding operating cost. If you are uncertain about operating cost, then you are uncertain about 75% of the total cost of chiller ownership. Using Chiller System Optimizer, your engineer can prepare the meaningful analysis you need, simply and easily using inexpensive software that is not manufacturer specific. Chilled water systems are becoming more complex, and the options available to choose from are more varied and confusing than ever. The time for excuses is disappearing. Chiller System Optimizer is a tool available to your engineer through their local Carrier representative. APLV IPLV NPLV Application Part Load Value is a single number, part-load efficiency indicator* calculated using the ARI method referenced to selected conditions. APLV was introduced in ARI Standard , but deleted from the 1998 edition. Integrated Part Load Value is a single number, part-load efficiency indicator* calculated using the ARI method at standard rating conditions. Introduced in ARI Standard , the definition of IPLV was changed in ARI Standard 550/ to more closely reflect actual operating experience found in the field for a single chiller. Non-Standard Part Load Value is a single number, part-load efficiency indicator* calculated using the ARI method referenced to rating conditions other than ARI standard. The 1998 standard adopted NPLV for situations when a single chiller is not intended to operate at standard ARI rating conditions. Glossary of Terms System Part Load Value is a project-specific, single number, part-load efficiency indicator introduced by Carrier that is calculated using the equation form defined in ARI 550/ Unlike IPLV or NPLV, the factors used to calculate are project specific and consider multiple-chiller applications, actual operating hours, and project-specific operating conditions. * ARI Standard uses the term figure of merit. The word indicator is used as a clarification. The use of a single number performance value is to provide an indication of equipment performance relative to other equipment at defined conditions.

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM 1. Category (Check one and indicate New or Existing, if applicable) Commercial Buildings New or Existing Institutional Buildings: Educational Facilities New

More information

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system Fair City Plaza Task: Diagnose problems, recommend improvements for small municipal district cooling system The Fair City Plaza district cooling system provides chilled water to five buildings in a downtown

More information

where we are, where we could be, how we can get there. 12/14/2011

where we are, where we could be, how we can get there. 12/14/2011 Central Plant Optimization ASHRAE National Capitol Chapter - PES Wednesday, Nov 7, 2011 Dave Klee, LEED AP Director, Optimized Building Solutions Johnson Controls, Inc. 1 1 J o http://www.johnsoncontrols.com/cpo

More information

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get *

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get * Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get * Trane CenTraVac chillers: Designed and built to be the best; tested to prove it Ongoing innovation. Unmatched capabilities.

More information

Next Generation DCP Optimization using MV VSDs

Next Generation DCP Optimization using MV VSDs Next Generation DCP Optimization using MV VSDs Vivek Apte Regional Product Director Johnson Controls - Middle East Cell : +971506243059 IDEA 2016- Dubai 1 Central Plant Optimization Energy and operating

More information

Committed to Energy Efficiency

Committed to Energy Efficiency RESOLUTE Resolute Helps PNC Arena Reduce Energy Consumption and Costs While Improving Fan Comfort Lacking the visibility, real-time data and analytics needed to optimize facility performance and reduce

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

Air-Cooled Series R Chiller

Air-Cooled Series R Chiller Air-Cooled Series R Chiller The next generation of Air-Cooled Helical Rotary Chillers ANOTHER RELIABLE SOURCE OF CHILLED WATER FROM TRANE The new industry standard f The next generation of the air-cooled

More information

Air-Cooled Chillers. R134a. Performance Matters

Air-Cooled Chillers. R134a. Performance Matters TM Air-Cooled Chillers R134a Performance Matters The end of the air-cooled chiller compromise TM Get the benefits of an air-cooled design, plus energy efficiency and quiet operation When choosing between

More information

UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012

UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012 UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A 004 11 JUNE 2012 TABLE OF CONTENTS Abstract...3 Introduction...3 Methodology...4

More information

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants By: David Schurk DES., CEM., LEED AP., CDSM., SFP. Heat Transfer Solutions, Director of Healthcare Accounts The air-cooled

More information

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,

More information

Optimiz Chilled January 25, 2013

Optimiz Chilled January 25, 2013 Optimiz zing Existing Data Center Chilled Water Plants January 25, 2013 This White Paper describes factors to be consideredd when optimizing an existing data center chilledd water plant. Authored by Michael

More information

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers Engineering Data SED: 8012 Group: Centrifugal Chiller Date: March 2002 Supercedes: New Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers Model WSC/WDC 2002 McQuay International

More information

Silicon Valley Power Data Center Program Rebate Application

Silicon Valley Power Data Center Program Rebate Application Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account

More information

Precision Cooling. Precision Cooling Advantages

Precision Cooling. Precision Cooling Advantages Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing

More information

Achieving Operational Excellence

Achieving Operational Excellence Achieving Operational Excellence Energy Efficient Operations in a Shrinking Budget Environment 2010 Energy/Facilities Connections Conference Innovative Approaches for a New Decade DID YOU KNOW? Nine out

More information

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics

More information

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S FREE COOLING CHILLER Getting To A PUE Of 1.2 Free cooling data center chillers are designed to

More information

Data Center UPS Systems Why 1% Efficiency Matters

Data Center UPS Systems Why 1% Efficiency Matters Data Center UPS Systems Why 1% Efficiency Matters Harry Handlin Director Critical Power Applications, September 18, 2014 Key Questions / Problems Addressed: Why efficiency gains of as little as 1 percent

More information

The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER

The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER YZ MAGNETIC BEARING CENTRIFUGAL CHILLER YORK YZ Magnetic Bearing Centrifugal Chiller The YORK YZ Magnetic Bearing Centrifugal Chiller is a revolutionary

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

Setting New Standards for Ultra High Performance HVAC

Setting New Standards for Ultra High Performance HVAC Setting New Standards for Ultra High Performance HVAC WHITE PAPER What if your commercial HVAC system could operate as efficiently in 10 years as it did on the day it was commissioned? What if you could

More information

2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization

2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization 2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization Presented by: Steve Keppler, Senior Director Critical Systems Design Build Practice CLEAResult Deep Optimization Standard

More information

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS Capacity from 600 to 2,010kWr Engineered for flexibility and performance PRODUCT LEAFLET THE AWS SERIES OFFERS TOP EFFICIENCY, LOW SOUND LEVELS AND FLEXIBLE

More information

Constru January 15, 2013

Constru January 15, 2013 Use of Modula ar Design and its Relation to Energy Performance and Constru uction Costs January 15, 2013 The data center designerr and user now have a very wide range of modular options available with

More information

Designing Ultra-Efficient Building Cooling Systems

Designing Ultra-Efficient Building Cooling Systems Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,

More information

National Service Center

National Service Center UNITED TECHNOLOGIES CARRIER CORPORATION National Service Center MAXIMIZING PERFORMANCE AND LONGEVITY OF INDUSTRIAL CHILLERS Protection, Performance and Peace of Mind Because industrial chillers serve large

More information

Energy Performance Contracting

Energy Performance Contracting Energy Performance Contracting December 2017 Outlines Section One: Jonson Controls as an Energy Service Company (ESCO) Reasons behind investment in Energy Efficiency Section Two: Funding Options of Energy

More information

DEDICATED HEAT RECOVERY UNIT (DHRC)

DEDICATED HEAT RECOVERY UNIT (DHRC) DEDICATED HEAT RECOVERY UNIT (DHRC) AHRI CERTIFICATION Air-Conditioning, Heating, and Refrigeration Institute Multistack is AHRI Certified and continues to certify products as they are developed AHRI Certification

More information

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

DEEMED SAVINGS TECHNICAL ASSUMPTIONS Program: Description: Prescriptive rebates will be offered for new cooling equipment. Rebates may be dependent on equipment size or load that is offset and on meeting minimum efficiency requirements. Additional

More information

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer Large Tonnage Chillers Kingsley Hu Technical Support Engineer Chongqing Plant Chiller Products Reference Projects Manufacturing Facility Major Milestones Global R&D Talent Production Line introduction

More information

Trailblazer AGZ-E air-cooled scroll chillers

Trailblazer AGZ-E air-cooled scroll chillers Trailblazer AGZ-E air-cooled scroll chillers 30 to 240 tons with Variable Speed Condenser Fan Technology The right features, the right value, right now Intelligent Equipment AGZ-E 30 to 161 RapidRestore

More information

HVAC System Energy Savings Opportunities

HVAC System Energy Savings Opportunities HVAC System Energy Savings Opportunities Speaker Info M. Lant DuBose Energy Services ConEdison Solutions dubosem@conedsolutions.com (813)285-6340 Wholly owned subsidiary of ConEdison since 2007 Entered

More information

Developing an Action Plan: Building Energy Metering and Beyond

Developing an Action Plan: Building Energy Metering and Beyond Developing an Action Plan: Building Energy Metering and Beyond Angela Lewis, PE, PhD, LEED AP, FMP Project Manager Facility Engineering Associates (FEA) MANAGING CEUs AND CFM MAINTENANCE POINTS You are

More information

Unit 9, Lesson 1: What Influences Temperature?

Unit 9, Lesson 1: What Influences Temperature? Unit 9, Lesson 1: What Influences Temperature? Let s see if we can predict the weather. 1.1: Temperature Changes What factors or variables can influence the outside temperature? Make a list of different

More information

How To Draw Chiller Monsters Werewolves Vampires And Zombies

How To Draw Chiller Monsters Werewolves Vampires And Zombies How To Draw Chiller Monsters Werewolves Vampires And Zombies We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,

More information

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling CHILLER PLANT CONTROLS The challenges of producing chilled water are not the same as those a decade

More information

Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric

Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric Nomination title: Schneider Electric Prefabricated, Pre Assembled Data Centre Modules Schneider Electric has introduced a

More information

NEW FEATURES IN CARRIER BUILDING SYSTEM OPTIMIZER 1.40

NEW FEATURES IN CARRIER BUILDING SYSTEM OPTIMIZER 1.40 NEW FEATURES IN CARRIER BUILDING SYSTEM OPTIMIZER 1.40 Carrier Software Systems Carrier Corporation Syracuse, New York rev October 27, 2015 Copyright 2015 Carrier Corporation, All Rights Reserved Page

More information

FLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities

FLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities UTILITIES ELEMENT NOTE: Unless otherwise noted, the goals, objectives and policies contained in this element shall guide development of the Main Campus and Southwest Campus in Tallahassee as well as the

More information

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO 6 CASE STUDIES Brevard Community College: Florida Power & Light City of Miami Beach: Johnson Controls, Inc. Cape Canaveral Air Force Station: NORESCO Arbor Shoreline Office Park: Progress Energy Solutions

More information

Chiller Replacement and System Strategy. Colin Berry Account Manager

Chiller Replacement and System Strategy. Colin Berry Account Manager Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit

More information

Dykin Engineering Part & Services Sdn. Bhd.

Dykin Engineering Part & Services Sdn. Bhd. Dykin Engineering Part & Services Sdn. Bhd. CHILLED WATER SOLUTIONS Water chillers to custom air handlers to variable air volume terminal systems. We provide PM (Preventative Maintenance) and FM (Full

More information

Regional Seminar Series Orlando. Critical Facilities Update

Regional Seminar Series Orlando. Critical Facilities Update Regional Seminar Series Orlando Critical Facilities Update November 4, 2009 Robert Wheatley, OSIsoft Alexis Stobbe, OSIsoft Empowering Business in Real Time. Copyright 2009, OSIsoft, LLC. All rights Reserved.

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

The Green Imperative Power and cooling in the data center

The Green Imperative Power and cooling in the data center The Green Imperative Power and cooling in the data center An interview with Fred Miller, Product Line Manager, Eaton Data Center Solutions Expanding power demands. Increasing energy costs. Excessive heat.

More information

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER CLICK TO EDIT MASTER TITLE STYLE AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER GREEN CHILLER PLANT Energy Efficiency Superior system performance Less energy consumption versus similar size building Operation

More information

Construct Chiller Plant, Phase I

Construct Chiller Plant, Phase I Page 1 of 6 Construct Chiller Plant, Phase I project 1 of 1 Virginia Polytechnic Institute and State University (208) General Information Project Type: New Construction Project Code: 17657 Start Year:

More information

District Cooling Marches on in Dubai The Emirates Towers Case Study

District Cooling Marches on in Dubai The Emirates Towers Case Study District Cooling Marches on in Dubai The Emirates Towers Case Study RETROFITTING JUMEIRAH EMIRATES TOWERS with DISTRICT COOLING Presented by: Samer Khoudeir Chief Sales & Marketing Officer Empower Tariq

More information

Cleanroom Energy Benchmarking In High-Tech and Biotech Industries

Cleanroom Energy Benchmarking In High-Tech and Biotech Industries ACEEE 2001 Paper #66 Cleanroom Energy Benchmarking In High-Tech and Biotech Industries William Tschudi; Lawrence Berkeley National Laboratory Kathleen Benschine, Stephen Fok; Pacific Gas and Electric Company

More information

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell

More information

Effect of the Certification on Chillers Energy Efficiency

Effect of the Certification on Chillers Energy Efficiency Effect of the Certification on Chillers Energy Efficiency Yamina Saheb Eurovent Certification Paper presented at IEECB, April 2006, Frankfurt, Germany 4 Sulejman Becirspahic Eurovent Certification Jérôme

More information

Comprehensive Energy Management & Utility Master Plan

Comprehensive Energy Management & Utility Master Plan Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach

More information

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution CGWN/CCUN indoor liquid chillers The compact AquaStream² solution Plug and Play for unparalleled Certified performance Eurovent certification provides capacity and efficiency compliance, thus confirming

More information

Campus Energy Plant Tufts University. IDEA Microgrid Conference 2017 Optimizing the Economics of a Combined Heat and Power Project November 8, 2017

Campus Energy Plant Tufts University. IDEA Microgrid Conference 2017 Optimizing the Economics of a Combined Heat and Power Project November 8, 2017 Tufts University IDEA Microgrid Conference 2017 Optimizing the Economics of a Combined Heat and Power Project November 8, 2017 1 Overview Presentation Overview: Campus and Project Overview Economic Considerations

More information

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE 90.1-2016 Revisions to Waterside Economizer March 15, 2017 Stefan Gracik 510-663-2070 sgracik@integralgroup.com Agenda 1. Background

More information

Presentation. Guaranteed Energy Savings Performance Project

Presentation. Guaranteed Energy Savings Performance Project Presentation Guaranteed Energy Savings Performance Project Greg Spiro, PE, CEM, LEED-AP Georgia Institute of Technology Senior Mechanical Engineer Facilities Design & Construction 470-351-9867151 6th Street

More information

HOURLY ANALYSIS PROGRAM v5.00 and v5.01

HOURLY ANALYSIS PROGRAM v5.00 and v5.01 HOURLY ANALYSIS PROGRAM v and v5.01 Carrier Software Systems Carrier Corporation Syracuse, New York Rev. November 3, 2016 Copyright 2016 Carrier Corporation, All Rights Reserved Contents Chiller Features

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers White Paper 3 Revision 1 by Victor Avelar > Executive summary Part of data center planning and design is to align the power and cooling requirements

More information

Setting New Standards for Ultra High Performance HVAC

Setting New Standards for Ultra High Performance HVAC For more information about this Whitepaper and Optimum Energy, click here. Setting New Standards for Ultra High Performance HVAC What if you could guarantee that your commercial HVAC system would operate

More information

Energy Solutions for Buildings

Energy Solutions for Buildings Energy Solutions for Buildings Making energy safe, reliable, efficient, productive and green Make the most of your energy SM 1 Solutions to enable and sustain energy savings Technology is crucial to make

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Green IT Project: The Business Case

Green IT Project: The Business Case Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Compacts. Big New 8 screen

Compacts. Big New 8 screen Compacts NEW 4 Models: Cool The Affordable Dual Temp Chill or Heat Twin Higher Power Twin XP Extra Powerful, Compact World s Best Selling Ice Bath Systems. Now better then ever. Ice bath recovery Anywhere

More information

COMMERCIAL AIR CONDITIONERS Flooded Type Water Cooled Screw Chiller 2012

COMMERCIAL AIR CONDITIONERS Flooded Type Water Cooled Screw Chiller 2012 MCAC-2012-37 COMMERCIAL AIR CONDITIONERS 2012 Commercial Air Conditioner Business Units Midea Air Conditioning and Refrigeration Sector Add: West region of Midea commercial air conditioner department,

More information

Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation

Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation A cost model (See figure 1) has been created to provide the user a simplified method for directly comparing the energy cost of a

More information

Chiller Plant Optimization: A Case Study

Chiller Plant Optimization: A Case Study Presentation of Chiller Plant Optimization: A Case Study Presented by Michael S. Conway The site Large pharmaceutical client 5 MW cogen 88,000 PPH of boiler capability 8,200 tons of chiller capability

More information

Let s face it addressing the growing list of deferred

Let s face it addressing the growing list of deferred by L. Scott Turley Let s face it addressing the growing list of deferred maintenance projects is one of the most difficult challenges we have as campus facilities managers. Within Utility Operations, the

More information

High Resolution (1280x800) LCD Display Touchscreens are NEMA 4 IP66 rated (enclosure only) Pre-loaded with MCS-CONNECT

High Resolution (1280x800) LCD Display Touchscreens are NEMA 4 IP66 rated (enclosure only) Pre-loaded with MCS-CONNECT MCS-TOUCH-7 MCS-TOUCH-10.1 High Resolution (1280x800) LCD Display Touchscreens are NEMA 4 IP66 rated (enclosure only) Pre-loaded with MCS-CONNECT MCS-TOUCH-15.4 Vesa Mount or mount in an Enclosure MCS-MAGNUM-MLB-7

More information

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: 15000 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 10-26-11 - Minor revisions to Data Sheets 04-08-10 - Allowed use

More information

CGAM air-cooled scroll chiller. Highly efficient, yet extremely quiet

CGAM air-cooled scroll chiller. Highly efficient, yet extremely quiet CGAM air-cooled scroll chiller Highly efficient, yet extremely quiet Balancing energy efficiency and quiet operation Energy efficiency, sound, reliability, controls and service are all vitally important

More information

2018 Business Cooling Equipment Rebate Application

2018 Business Cooling Equipment Rebate Application 2018 Business Cooling Equipment Rebate Application LIMITED FUNDING: Contact your local Utility to confirm rebate availability. CUSTOMER INFORMATION Check here if you are applying for multiple Business

More information

RAPID CITY CALL CENTER 1400 TURBINE DRIVE RAPID CITY, SD FOR SALE / FOR LEASE OFFICE / CALL CENTER 133,102 SQ. FT.

RAPID CITY CALL CENTER 1400 TURBINE DRIVE RAPID CITY, SD FOR SALE / FOR LEASE OFFICE / CALL CENTER 133,102 SQ. FT. FOR SALE / FOR LEASE OFFICE / CALL CENTER 133,102 SQ. FT. PROPERTY OVERVIEW FOR SALE $12,000,000.00 FOR LEASE $12.50/SF NNN EST. NNN EXPENSES $6.33/SF BUILDING SIZE 133,102 SF LAND SIZE 15.01 acres (including

More information

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11 Table of Contents Executive Summary... 3 Site and Unit Background... 5 Chiller 1... 6 Chiller 2... 9 Appendix... 11 A Vidaris Company 2 Executive Summary New York Blood Center s facility in Long Island

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

Stratadyne Group Inc.

Stratadyne Group Inc. Stratadyne Group Inc. November 22, 2013 Mr. Phil Bowmile, CEO Enerfreeze Canada Inc. 5000 Yonge Street, Suite 1901 Toronto, Ontario M2N 7E9 Sent electronically: phil.bowmile@enerfreeze.ca Re: Chillers

More information

Magnitude magnetic bearing centrifugal chillers

Magnitude magnetic bearing centrifugal chillers Magnitude magnetic bearing centrifugal chillers 100-1500 tons Daikin Magnitude chillers Ahead of everything else Quiet operation To instill productivity and promote efficiency, commercial buildings today

More information

Energy Engineering: Tools and Trends

Energy Engineering: Tools and Trends Energy Engineering: Tools and Trends AEE Northeast Ohio Chapter Meeting March 27, 2008 1 Introduction Background and Experience Energy Engineer for Trane 20 years in HVAC Industry Equipment design and

More information

CARRIER edesign SUITE NEWS

CARRIER edesign SUITE NEWS Welcome Welcome to the premier issue of EXchange, offering timely, informative and interesting news on the Carrier edesign Suite of Software. Delivered quarterly, each issue will provide a wealth of information

More information

Roadmap to the Efficient Cloud: 3 Checkpoints for the Modern Enterprise

Roadmap to the Efficient Cloud: 3 Checkpoints for the Modern Enterprise Roadmap to the Efficient Cloud: 3 Checkpoints for the Modern Enterprise Roadmap for the Modern Enterprise As your AWS environment grows, the importance of instilling governance and following best practice

More information

Trading TCO for PUE? A Romonet White Paper: Part I

Trading TCO for PUE? A Romonet White Paper: Part I Trading TCO for PUE? A Romonet White Paper: Part I Executive Overview Most data center vendors claim to improve Power Usage Effectiveness (PUE). The problem with this is that focusing on reducing PUE makes

More information

BAS Chillers 8/15/2016. Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August 10, 2016

BAS Chillers 8/15/2016. Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August 10, 2016 Session 7: Building Automation and Operation Tools Outline Analytics Tools to Supplement BAS Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August

More information

Mexico Chiller Concessional Lending Pilot Project

Mexico Chiller Concessional Lending Pilot Project Mexico Chiller Concessional Lending Pilot Project World Bank UK Bilateral Current status: 1 st Phase completed Financial Agents Workshop, Washington D.C. 14, 15 April 2004 Project Objectives (i) Test various

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

ROI CASE STUDY IBM SPSS CITY OF LANCASTER. ROI: 1301% Payback: 1.5 months Average annual benefit: $1,344,338. Cost : Benefit Ratio 1 : 45.

ROI CASE STUDY IBM SPSS CITY OF LANCASTER. ROI: 1301% Payback: 1.5 months Average annual benefit: $1,344,338. Cost : Benefit Ratio 1 : 45. ROI CASE STUDY IBM SPSS CITY OF LANCASTER THE BOTTOM LINE The City of Lancaster, California needed to gain greater visibility into where Part I crimes were occurring and where they were expected to occur

More information

WATER-COOLED WATER-CHILLING AND HEAT PUMP WATER-HEATING PACKAGES USING THE VAPOR COMPRESSION CYCLE

WATER-COOLED WATER-CHILLING AND HEAT PUMP WATER-HEATING PACKAGES USING THE VAPOR COMPRESSION CYCLE WATER-COOLED WATER-CHILLING AND HEAT PUMP WATER-HEATING PACKAGES USING THE VAPOR COMPRESSION CYCLE AHRI WCCL OM JANUARY 2018 2111 Wilson Blvd, Suite 500 Arlington, Virginia 22201 (703) 524-8800 Sponsored

More information

AuraCool Economizer System

AuraCool Economizer System Page 1 Due to manufacturer's policy of continuous product improvement, the manufacturer reserves the right to make changes without notice. Drawings in this submittal are representations of the equipment

More information

Business Process Outsourcing

Business Process Outsourcing Business Process Outsourcing Copyright 2012-2014, AdminBetter Inc. LIST BUILDING SERVICES Table of Contents Introduction To List Building Services... 3 A Note On Ballbark Pricing... 3 Types Of List Building

More information

THE JOURNEY OVERVIEW THREE PHASES TO A SUCCESSFUL MIGRATION ADOPTION ACCENTURE IS 80% IN THE CLOUD

THE JOURNEY OVERVIEW THREE PHASES TO A SUCCESSFUL MIGRATION ADOPTION ACCENTURE IS 80% IN THE CLOUD OVERVIEW Accenture is in the process of transforming itself into a digital-first enterprise. Today, Accenture is 80 percent in a public cloud. As the journey continues, Accenture shares its key learnings

More information

Driving Proactive Facility Operations with Automated HVAC Diagnostics

Driving Proactive Facility Operations with Automated HVAC Diagnostics Driving Proactive Facility Operations with Automated HVAC Diagnostics Turn HVAC Data into Actionable Information AKA Monitoring Based Commissioning Ongoing Commissioning Automated Fault Detection & Diagnostics

More information

CENTRAL PLANT OPTIMIZATION. The heart of building efficiency

CENTRAL PLANT OPTIMIZATION. The heart of building efficiency CENTRAL PLANT OPTIMIZATION The heart of building efficiency This is one of the most efficient chillers in the world. What a waste. We re all more focused than ever on energy efficiency and selecting the

More information

Magnitude magnetic bearing centrifugal chillers

Magnitude magnetic bearing centrifugal chillers Magnitude magnetic bearing centrifugal chillers 75-1500 tons Better Air, Better Outcomes Magnitude magnetic bearing centrifugal chillers deliver the energy savings that building owners demand under all

More information

Variable Speed IPLV.36 kw/tr

Variable Speed IPLV.36 kw/tr ACEGWFVXR Series 50 Hz Energy Efficient Variable Speed Water-Cooled Screw Chillers 3 Range from 00 TR to 00 TR Variable Speed IPLV.36 kw/tr GREEN EFFICIENT SUSTAINABLE ACEGWFXR Series 50Hz Energy Efficient

More information

Software VIRTUAL BRIEFCASE REPORTING ENERGY DASHBOARDS ALARM/NOTIFICATION POINT VIEW CONSUMPTION VIEW

Software VIRTUAL BRIEFCASE REPORTING ENERGY DASHBOARDS ALARM/NOTIFICATION POINT VIEW CONSUMPTION VIEW Software The Entronix Energy Management software utilizes a stand-alone platform that does not require a control system for data acquisition. With this platform in place a user is able to access the software

More information