1
2 Table of Contents Executive Summary... 3 Site and Unit Background... 5 Chiller Chiller Appendix A Vidaris Company 2
3 Executive Summary New York Blood Center s facility in Long Island City, NY is a two-story 75,000 square foot building that serves as a blood bank as well as a processing laboratory. Two identical ton rooftop AAON aircooled chillers were comprehensively monitored for energy use to examine the immediate effectiveness of Ener.co s treatment process on condenser coil assemblies. The treatment process involves a thorough cleaning of the coil assembly, mechanical realignment of the fins (when necessary), preparing all coil surfaces for coating, and coating the coil-fin assembly with a ultra-thin layer of a proprietary anticorrosive chemical that claims to prevent an increase in energy consumption over time caused by the degradation of the coil surface. In order to differentiate between the effects of treatment with or without the coating, one chiller (chiller 1) underwent through the full Ener.co process while the other chiller (chiller 2) received a partial treatment where it received all the steps in the process mentioned above except that it was not coated with the anti-corrosive chemical. The results of the year-long before and after evaluation demonstrate that the full Ener.co treatment process can immediately reduce the energy use of a well-maintained five-year-old unit. Though the chillers run in a lead-lag sequence, chiller 1 has predominately served as lead in the past. While chiller 2 maintained its off-the-shelf performance, chiller 1 has been exposed to more wear and tear, and therefore posed a greater potential for improvement. Chiller 1 experienced the benefit of a 10% reduction in power draw (2.3 kw) while chiller 2 experienced a reduction of 4% (0.7kW) for similar weather conditions. Cooling capacity of each chiller was monitored alongside power draw and is expanded on in the next section. The findings are summarized in the following figures 1 and 2. The long-term benefits of the full treatment will be realized by the facility and verified by future monitoring of the two chillers. Figure 1 Using normal facility operation of chiller 1 alone and electricity cost of $0.22 per kwh in NYC, the expected first year energy savings will be approximately $4,000. A Vidaris Company 3
4 Further investigation was undertaken into the energy consumption of the compressors and fans of chiller 1 to disaggregate the unit s overall energy reduction and breakdown the savings to its constituent components. Of the total reduction of 10%, 89% of this was attributed to compressor power reduction and the other 11% to fan power reduction. Figure 2 A Vidaris Company 4
5 Site and Unit Background The New York Blood Center s facility in Long Island City, NY serves as a blood bank as well as a processing laboratory. The principal components in the system being evaluated are the two 2006, 60- ton AAON air-cooled glycol chillers (model number LL AA0A-000) serving assorted refrigeration loads throughout the facility. While only one chiller is operational at any given time, the second exists for system redundancy. Figure 3 The units were monitored from the fall of 2010 through the fall of The units were treated (again, with or without the coating) during the end of the summer of The lead-lag sequence of the chillers was swapped both before and after the Ener.co process to allow for the comparison of periods of operation for each unit during a wide range of outside weather conditions. True-power calibrated data loggers on each unit recorded the kilowatt use for five minute average sampling intervals. Based on the data observed, it appears that the system is oversized. Although each chiller has four 15- ton Copeland scroll compressors, one of these four was able to meet the cooling load throughout the vast majority of the monitoring period with frequent cycling. Warmer outside temperatures called for the operation of two compressors to meet the load, though this study focused on the operation of a single compressor for each chiller at a time. Unlike other Ener.co demonstration projects involving direct expansion coils, measuring the cooling capacity of the glycol chillers was more involved. The thermal inertia of a fluid cooler in this project (versus a direct expansion air cooler) and the frequent cycling of the compressor resulted in data indicating no conclusive effect on the units cooling capacity both before and after the treatment. Since, however, there was a sizeable reduction in power draw, the result was a clear improvement in chiller performance. Refer to the appendix for more information on the specific measurement methodology. A Vidaris Company 5
6 Chiller 1 The condenser coil assembly of chiller 1 was restored and treated. The following figures 4 and 5 depict the average reduction in power draw for chiller operation of two fans and one compressor during similar weather conditions: Figure 4 Catalog Before After % Reduction Total kw % Compressor kw % Fan kw % Controls kw Figure 5 It is observed that the energy savings of treatment are distributed between compressor and fan power with the compressor power responsible for the majority of the savings. A Vidaris Company 6
7 The following figures 6, 7, and 8 represent data points that have been filtered to show only steady-state operation during similar weather conditions with the periods of rain removed. There is a clear trend observed in the unit s total, compressor, and fan power across a wide array of outside air temperatures. Figure 6 A Vidaris Company 7
8 Figure 7 Figure 8 A Vidaris Company 8
9 Chiller 2 The condenser coil assembly of chiller was treated without the coating. The following figures 9 and 10 depict the average reduction in power draw for chiller operation during similar weather conditions: Figure 9 Catalog Before After % Reduction Total kw % Figure 10 The following figure 11 represent data points that have been filtered to show only stead-state operation during similar weather conditions with the periods of rain removed. There is a clear trend observed in the unit s total power across a wide array of outside air temperatures. A Vidaris Company 9
10 Figure 11 A Vidaris Company 10
11 Appendix Methodology The lead-lag sequencing of chillers 1 and 2 were swapped periodically over the course of one year starting on October 18 th 2010 through November 4 th, The treatment took place on the week of September 19 th, Ample performance data was collected both before and after the treatment for both chillers for a wide array of outdoor weather conditions. The following test instruments were installed on both units: One (1) DENT data-logging electric power test meter to measure and record the total true power draw for the entire chiller; using four (4) clip-on voltage probes, and two (2) current transformers. One (1) Hobo data-logger and two (2) remote, surface-type temperature sensors on the intake and discharge of chilled glycol piping. One (1) Hobo data-logger and two (2) remote temperature sensors to measure and monitor the air temperatures at the intake and discharge of the air-cooled condensers. The following test instruments were installed on only the unit being fully treated (chiller 1): Two (2) additional DENT data-logging electric power test meter to measure and record the total true power draw for the first two compressors; using four (4) clip-on voltage probes, and current transformerss on 2 of the 3 legs. Eight (8) Hobo data-loggers with fifteen (15) current transformers to measure and record the current draw on each of the three (3) legs for each of the two (2) remaining compressors and three (3) and condenser fans. For components with current transformerswhere only amperage was measured, true power was calculated based on the following equation: where power factor was measured with a handheld clamp-on meter at various times during the experiment. An additional two (2) Hobo data-logger temperature sensors monitored the ambient air temperature and R.H.. An ultrasonic flow meter was installed on a horizontal section of the chilled glycol piping common to both chillers within the facility s mezzanine mechanical equipment room. A Vidaris Company 11
12 Metrics Chiller 1: Total Unit o Volts o Amps o Kilowatts Compressors 1 and 2 o Volts o Amps o Kilowatts Compressors 3 and 4 o Volts o Amps o Powerfactor Condenser Fans 1, 2, and 3 o Volts o Amps o Power factor Intake and discharge temperatures across glycol/refrigerant evaporator Intake and discharge temperatures across the condenser coil assembly Chiller 2: Total Unit o Volts o Amps o Kilowatts Temperatures & R.H. o Intake and discharge across glycol/refrigerant evaporator Common to both Chillers: Ambient outdoor temperatures and R.H. Chilled glycol flow rate A Vidaris Company 12
13 Monitoring Devices Onset HOBO type U12 data loggers with external temperature sensors and current transformers DENT Instruments ELITEpro power data loggers with split-core current transformers GE Panametrics PT878 ultrasonic liquid data logging flow meter Amprobe ACD-41PQ 1000A power quality clamp meter The circuit panels of chiller 1 are seen below in figure 14, with DENT data loggers and split-core current transformers sub metering the chiller s electricity usage. Figure 12 A Vidaris Company 13
14 Below is a representative sample of the well-maintained condenser coil surface of both chillers before the treatment: Figure 13 The chillers (numbered below) are located on the center of the facility s rooftop: Figure 14 A Vidaris Company 14
15
16
17
18
Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers
Liebert HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S FREE COOLING CHILLER Getting To A PUE Of 1.2 Free cooling data center chillers are designed to
More informationFair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system
Fair City Plaza Task: Diagnose problems, recommend improvements for small municipal district cooling system The Fair City Plaza district cooling system provides chilled water to five buildings in a downtown
More informationMotivair MLC-SC Air-Cooled Scroll Chillers Tons
INNOVATE DESIGN APPLY www.motivaircorp.com Motivair MLC-SC Air-Cooled Scroll Chillers 100 285 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Businesses who function in today s advanced
More informationHOURLY ANALYSIS PROGRAM v5.00 and v5.01
HOURLY ANALYSIS PROGRAM v and v5.01 Carrier Software Systems Carrier Corporation Syracuse, New York Rev. November 3, 2016 Copyright 2016 Carrier Corporation, All Rights Reserved Contents Chiller Features
More informationMLC Air-Cooled Chillers MLC-FC Free-Cooling Chillers MLC-AD Adiabatic Chillers
INNOVATE DESIGN APPLY www.motivaircorp.com MLC Air-Cooled Chillers MLC-FC Free-Cooling Chillers MLC-AD Adiabatic Chillers 60-500 Tons OUR BUSINESS IS COOLING YOURS TM When commercial grade isn t enough
More informationCTC Low Temperature Process Chillers
INNOVATE DESIGN APPLY CTC Low Temperature Process Chillers 5-500 Tons OUR BUSINESS IS COOLING YOURS TM When commercial grade isn t enough When it comes to process cooling, every application is unique in
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationLiebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets
Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across
More informationMPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers
INNOVATE DESIGN APPLY www.motivaircorp.com MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers ½ - 100 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Motivair is a world-class
More informationWHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net
Digi-RTU WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve
More informationTrane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling
Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling CHILLER PLANT CONTROLS The challenges of producing chilled water are not the same as those a decade
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationGP SERIES Packaged Chillers
Blending Conveying Drying Process Cooling Heat Transfer Size Reduction GP SERIES Packaged Chillers Comprehensive Flexible Versatile Compact unitary designs available in a variety of configurations from
More informationHIGH EFFICIENCY Central Chiller
Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationRetro-Commissioning Report
10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationIT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw
IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationPrecision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers
Precision Cooling for Business-Critical Continuity Liebert HPC-S Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S: Enhanced Efficiency Freecooling Chiller Higher energy costs, limited
More informationEcoflair Air Economizers
Ecoflair Air Economizers Cooling to maximize value for the cloud schneider-electric.com/ecoflair Life is On Schneider Electric 1 Ecoflair takes data center efficiency to new heights 2 Imagine cooling your
More informationPrecision Cooling. Precision Cooling Advantages
Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing
More informationCHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM
CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM 1. Category (Check one and indicate New or Existing, if applicable) Commercial Buildings New or Existing Institutional Buildings: Educational Facilities New
More informationPrecision Cooling Mission Critical Air Handling Units
M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly
More informationStratadyne Group Inc.
Stratadyne Group Inc. November 22, 2013 Mr. Phil Bowmile, CEO Enerfreeze Canada Inc. 5000 Yonge Street, Suite 1901 Toronto, Ontario M2N 7E9 Sent electronically: phil.bowmile@enerfreeze.ca Re: Chillers
More informationTrailblazer AGZ-E air-cooled scroll chillers
Trailblazer AGZ-E air-cooled scroll chillers 30 to 240 tons with Variable Speed Condenser Fan Technology The right features, the right value, right now Intelligent Equipment AGZ-E 30 to 161 RapidRestore
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationWHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net
WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve the
More informationYour Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant
Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,
More informationCalculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers White Paper 3 Revision 1 by Victor Avelar > Executive summary Part of data center planning and design is to align the power and cooling requirements
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationDrives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
More informationAquaflair. BREC & BREF kW 380V/3ph/60Hz - 460V/3ph/60Hz. Air-cooled chillers and free-cooling chillers with double screw compressors
Aquaflair Air-cooled chillers and free-cooling chillers with double screw compressors BREC & BREF 350-1200kW 380V/3ph/60Hz - 460V/3ph/60Hz The all-in-one solution for your business need Combining cutting-edge
More informationAIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS
RAH 913 K AIR R-407C R-134a Series RAH... from 307 to 1879 kw - from 1 to 4 circuits The air cooled chillers of RAH series are extremely compact units so to reduce the installation spaces and weights.
More information110 East 59th Street Data Integrator Notes
110 East 59th Street Data Integrator Notes This site is a CHP system, operated by Office Power, LLC., which includes eight (8) Elliot TA-100 100 kw micro-turbine units. Thermal output from the units will
More informationCLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW. The indirect evaporative free-cooling Air Handling Unit
CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW The indirect evaporative free-cooling Air Handling Unit Flexible & Efficient 11 sizes from 30 kw up to 520 kw to fit your needs with maximum efficiency
More informationSUSTAINABLE SAUNDERS AC SHUTDOWN PROJECT
SUSTAINABLE SAUNDERS AC SHUTDOWN PROJECT a cooperative plan between the following partners: UH Manoa Facilities Management Office - Blake Araki, Chief Mechanical Engineer Hawaii Electric Company - Carlos
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationBuilding Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II
Building Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II Lesson 4: Sections Review of last class (0:20) Section 1: AHU: Discharge air temperature control (0:45) Break (0:10) Section 2: AHU: Heating
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationAuraCool Economizer System
Page 1 Due to manufacturer's policy of continuous product improvement, the manufacturer reserves the right to make changes without notice. Drawings in this submittal are representations of the equipment
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationLiebert. DSE Thermal Management System Free Cooling Economization Without Using Water
Liebert DSE Thermal Management System Free Cooling Economization Without Using Water LIEBERT DSE THERMAL MANAGEMENT SYSTEM Liebert DSE System Overview A Highly Efficient, Self-Optimizing Solution for Thermal
More informationCARRIER HOURLY ANALYSIS PROGRAM v5.0
CARRIER HOURLY ANALYSIS PROGRAM v5.0 Carrier Software Systems Carrier Corporation Syracuse, New York Rev. June 22, 2016 Copyright 2016 Carrier Corporation, All Rights Reserved Contents Air-Side Features
More informationHow To Draw Chiller Monsters Werewolves Vampires And Zombies
How To Draw Chiller Monsters Werewolves Vampires And Zombies We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,
More informationCollege Statement and Statistics Campus Site Map Five-Year Capital Plan Request FY through FY
Section Contents College Statement and Statistics Campus Site Map Five-Year Capital Plan Request FY 2013-14 through FY 2017-18 Project Funding Type Total ($ 000s) Replacement of Unit Ventilation System
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationNew Design Strategies for Energy Saving. Intelligent free-cooling
New Design Strategies for Energy Saving Intelligent free-cooling Intelligent New strategies for energy saving When designing mission critical systems for processing applications or highly technological
More informationWO P-NF-L-M-407c Spec Submittal
WO2-2-10000-2P-NF-L-M-407c Spec Submittal General Specifications WO2-2-10000(801304) Width: IN/CM 136.25/346.07 Height: IN/CM 84.5/214.63 Depth: IN/CM 41.7/105.92 Dry weight: LB/KG 4000/1814.37 Operational
More informationChiller Replacement and System Strategy. Colin Berry Account Manager
Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit
More informationIndirect Adiabatic and Evaporative Data Center Cooling
Indirect Adiabatic and Evaporative Data Center Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced technology
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationJUNXY Series DC Load Banks
JUNXY Series DC Load Banks It is really critical that your standby power system say UPS(uninterrupted power supply), battery bank, AC & DC generator, rectifier, transformers, inverter etc working in good
More informationAquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.
Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More information2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.
[Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL
More informationS 551 COMPRESSED AIR ANALYZER
The ideal data logger for energy analyzes (ISO 50001) and air audits (ISO 11011) Features Easy to use Just connect the sensor and start the recording, no configuration and programming required Easy operation
More informationIndirect Adiabatic and Evaporative Data Centre Cooling
Indirect Adiabatic and Evaporative Data Centre Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationDykin Engineering Part & Services Sdn. Bhd.
Dykin Engineering Part & Services Sdn. Bhd. CHILLED WATER SOLUTIONS Water chillers to custom air handlers to variable air volume terminal systems. We provide PM (Preventative Maintenance) and FM (Full
More informationMcQuay. Aircon Air-Cooled Condenser. APD Vintage C. Last Manufactured: Replacement Parts List No Revision A 05/2016
Replacement Parts List No. 046902400 Revision A 05/2016 McQuay Aircon Air-Cooled Condenser APD 005-140 Vintage C Last Manufactured: 1998 To find your Daikin Applied parts distributor, call 1-800-377-2787
More informationSupplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers
Engineering Data SED: 8012 Group: Centrifugal Chiller Date: March 2002 Supercedes: New Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers Model WSC/WDC 2002 McQuay International
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationAIR COOLED HEAT PUMPS WITH SCREW COMPRESSORS AND AXIAL FANS
PAH 2802 T K AIR R-407C R-134a Series PAH... T K from 205 to 778 kw - 2 circuits The air cooled heat pumps of PAH.T series are designed for outdoor installation and are particularly suitable for industrial
More informationIT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw
IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE
More informationSilicon Valley Power Data Center Program Rebate Application
Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account
More informationHigh Efficient Data Center Cooling
Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationWiring Diagrams INDEX. UNIT DESCRIPTION DRAWING NUMBER FIG. NO. 09DK Field Wiring 09DK DK054,064
09DK054-094 Air-Cooled Condenser Units 50/60 Hz Wiring Diagrams INDEX UNIT DESCRIPTION DRAWING NUMBER FIG. NO. 09DK054-094 Field Wiring 09DK500319 1 09DK054,064 Wiring Diagram and Component Arrangement
More informationFive Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
More informationOptimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC
Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics
More informationT66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management
T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell
More informationData Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationDesigning Ultra-Efficient Building Cooling Systems
Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,
More informationthat may have a direct effect on your bottom line. The question
VOLUME THREE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Cost of Owning a Chiller What is your bottom line?....... 1 What
More informationInstallation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment
Installation Service Statement of Work Start-up Service for Cooling Start-up - 1 - Service for Cooling Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0
More informationJ&M Fluidics, Inc. Company Product Overview
It s All about Building a Better Product for Our Clients! J&M Fluidics, Inc. Company Product Overview J&M Fluidics, Manufacturer of Air & Water-Cooled Process Chillers. Located in Telford, Pennsylvania
More informationSTULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling
STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued
More informationProduct Catalog. Belgium Tel.: +32 (0) The Netherlands Tel.: +31 (0)
Product Catalog Table of Contents NGR-30 Gateway ZEM-61 Wireless 3-Phase Electricity Monitor ZEM-30 Wireless Single Phase Electricity Monitor TES-11 / HTS-10 Wireless Temperature / Humidity Sensor TES-21
More informationLarge Tonnage Chillers. Kingsley Hu Technical Support Engineer
Large Tonnage Chillers Kingsley Hu Technical Support Engineer Chongqing Plant Chiller Products Reference Projects Manufacturing Facility Major Milestones Global R&D Talent Production Line introduction
More informationTechnology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach
Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach Hiroshi Nagazono In recent years, IT devices such as servers have come to have high performance and be highly integrated
More informationMOLLIER DIAGRAM CAN BE IMPROVED!
MOLLIER DIAGRAM CAN BE IMPROVED! IMPROVED BASIC COOLING CIRCUIT PERFORMANCE EFFICIENCY USING AN ECONOMISER Eng. Jonny Malachi, VP Operations, Mashav Refrigeration and Air Conditioning Engineering Ltd.
More informationMcQuay. Commercial Unitary Rooftop Cooling Only or with Electric Heat. LCA Design 1. Last Manufactured: 2004
Replacement s List No. 057111400 Revision A 08/2011 McQuay Commercial Unitary Rooftop Cooling Only or with Electric Heat LCA 180-240 Design 1 Last Manufactured: 2004 To find your Daikin Applied parts distributor,
More informationDATA CENTER AIR HANDLING COOLING SOLUTIONS
DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner
More informationREP N BANK ST. ENVIRONMENTAL NOISE STUDY Page 1 of 14
REP N45 852 BANK ST. ENVIRONMENTAL NOISE STUDY Page 1 of 14 2014-06-02 Robert Matthews, B.ARCH., O.A.A., A.A.N.B., R.A.I.C. N45 ARCHITECTURE INC. 2nd floor, 43 Eccles Street Ottawa, Ontario Canada K1R
More informationMcQuay Climate Control Singer. Incremental. NE, NH, NR Vintage A. TYA, TAA No Vintage. Last Manufactured: 1993
Replacement Parts List No. 055203200 Revision G 08/2017 McQuay Climate Control Singer Incremental NE, NH, NR 07-15 Vintage A TYA, TAA 007-015 No Vintage Last Manufactured: 1993 To find your Daikin Applied
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationLiebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability
Liebert AFC from 500 to 1700 kw The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw Vertiv Vertiv designs, builds and services mission critical technologies that
More informationglide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA
99 glide air cooled liquid chillers ND free cooling chillers glider 178 1328 Energy Class More efficient + B C D E F G Less efficient R134a CLSS SHELL C E C FREE COOLING 100 air cooled liquid chiller and
More information4-step Chiller and Heat Pump Controller
4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW
More informationi-accurate_gb_ High precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 kw
i-accurate_gb_07-2011 igh precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 Coming form 40 years experience in air conditioning and
More informationMeasuring and Managing a Data Center Cooling Shutdown
Measuring and Managing a Data Center Cooling Shutdown Columbia University Information Technology - August 24, 2012 Table of Contents Overview Timeline Cricket Graphs What s being graphed Mechanical Electrical
More information