Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC

Size: px
Start display at page:

Download "Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC"

Transcription

1 Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC

2 Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics of each equipment component of a chilled water plant Understand how the design characteristics and operation of each equipment component effects overall chiller plant efficiency Learn how to evaluate strategies to optimize chilled water plant performance based on existing chilled water plant design and operation Review actual operating data from central chilled water plants before and after implementation of optimization strategies 3/6/2014 2

3 Optimizing Chilled Water Plant Performance Benchmark the existing equipment Ensure proper preventive maintenance Optimize operation of existing equipment Evaluate possible capital retrofits 3/6/2014 3

4 A Typical Chiller Plant 3/6/2014 4

5 A Typical Chiller Plant What is the average total kw/ton for an existing chiller plant including chillers, cooling towers and pumps? Approx. 1.0 kw/ton What is an optimized total kw/ton for a chiller plant? Approx kw/ton (lower with capital investment) 3/6/2014 5

6 Benchmarking Pumps What is one of the most useful diagnostic tools for benchmarking pumps? The Pump Curve 3/6/2014 6

7 Benchmarking Pumps Example: TACO Model #TA1538 HP 75 GPM 1400 HD 140 IMP 12.5 RPM /6/2014 7

8 Benchmarking Pumps 3/6/2014 8

9 Benchmarking Pumps How can pump impeller size be confirmed? By deadheading the pump 3/6/2014 9

10 Benchmarking Pumps 3/6/

11 Benchmarking Pumps 3/6/

12 Benchmarking Pumps Why is it important to use the same gauge to measure suction and discharge pressures? To avoid gauge error since the differential pressure is needed 3/6/

13 Benchmarking Pumps Example: Measured Suction P: 9 psig Measured Discharge P: 58 psig Measured ΔP: 58 psig Measured ΔP: 134 head To convert psi to head, multiply by 2.31 Deadhead: 163 3/6/

14 Benchmarking Pumps 3/6/

15 Benchmarking Chillers Basic Formulas 1 ton = 12,000 Btuh GPM = Q / (500 x ΔT) Tons = GPM x ΔT / 24 3/6/

16 Benchmarking Chillers What ΔT is the basis of the rule of thumb of 2.4 GPM/ton for evaporator flow? ΔT = 10 degrees 3/6/

17 Benchmarking Chillers Tag # Manuf Model # Nom Tons #1 Trane CVHE090R #2 Trane CVHE090R #3 Trane CVHE 050 F BC 515 Evaporator GPM Ent Temp Lvg Temp Temp Diff 1, , Condenser GPM Lvg Temp Ent Temp Temp Diff 1, , , FLA kw kw/ton Refrig Charge Starts Hours R 123 1,111 34, R 123 1,131 25, R ,276 > /6/

18 Benchmarking Chillers Barrel Nom Tons Rated Flow Rated PD FT Rated Temp Diff Evap Cond 1, Meas Ent P Meas Lvg P Meas Diff P Meas PD FT Meas Flow ,543 Meas Ent T Meas Lvg T Meas Temp Diff Tons Amps kw kw/ton /6/

19 Benchmarking Chillers Measured Flow = Rated Flow * (Rated PD/Measured PD)^0.5 kw = (3)^0.5 *V * A * PF / /6/

20 Ensure Proper Maintenance Pumps Chillers Cooling Towers 3/6/

21 Optimize Pump Operation Over pumping results in: Flow problems Energy penalty 3/6/

22 Optimize Chiller Operation Lower condenser water temperature set point For every one degree drop in condenser water temperature, chiller efficiency will increase 2% Consider the trade off between lower compressor energy and increased cooling tower fan energy 3/6/

23 Optimize Chiller Operation What is the typical location of the differential pressure sensor controlling the pump variable speed drive? Somewhere along the chilled water supply and return piping What is the optimum location? 3/6/

24 Optimize Chiller Operation Relocate differential pressure sensor controlling pump variable speed drive Optimum location is across the chilled water supply and return piping at the farthest chilled water coil 3/6/

25 Evaluate Capital Retrofits Install variable speed drive on existing chiller(s) Significant energy savings in chiller energy use is possible (up to 30% in some applications) 3/6/

26 Optimizing Chilled Water Plant Performance Benchmark the existing equipment Ensure proper preventive maintenance Optimize operation of existing equipment Evaluate possible capital retrofits 3/6/

27 To download a copy of this presentation, go to 3/6/

Chiller Replacement and System Strategy. Colin Berry Account Manager

Chiller Replacement and System Strategy. Colin Berry Account Manager Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit

More information

How To Draw Chiller Monsters Werewolves Vampires And Zombies

How To Draw Chiller Monsters Werewolves Vampires And Zombies How To Draw Chiller Monsters Werewolves Vampires And Zombies We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,

More information

Next Generation DCP Optimization using MV VSDs

Next Generation DCP Optimization using MV VSDs Next Generation DCP Optimization using MV VSDs Vivek Apte Regional Product Director Johnson Controls - Middle East Cell : +971506243059 IDEA 2016- Dubai 1 Central Plant Optimization Energy and operating

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

Chiller Plant Optimization: A Case Study

Chiller Plant Optimization: A Case Study Presentation of Chiller Plant Optimization: A Case Study Presented by Michael S. Conway The site Large pharmaceutical client 5 MW cogen 88,000 PPH of boiler capability 8,200 tons of chiller capability

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

where we are, where we could be, how we can get there. 12/14/2011

where we are, where we could be, how we can get there. 12/14/2011 Central Plant Optimization ASHRAE National Capitol Chapter - PES Wednesday, Nov 7, 2011 Dave Klee, LEED AP Director, Optimized Building Solutions Johnson Controls, Inc. 1 1 J o http://www.johnsoncontrols.com/cpo

More information

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system Fair City Plaza Task: Diagnose problems, recommend improvements for small municipal district cooling system The Fair City Plaza district cooling system provides chilled water to five buildings in a downtown

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

AIR COOLED CONDENSERS

AIR COOLED CONDENSERS AIR COOLED CONDENSERS NQAC Quiet Line HNSQAC NQAC Quiet Line kw () Highly efficient external rotor fan motors give optimum performance with low noise levels Multiple fans (on all except smallest models)

More information

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation

More information

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

Motivair MLC-SC Air-Cooled Scroll Chillers Tons INNOVATE DESIGN APPLY www.motivaircorp.com Motivair MLC-SC Air-Cooled Scroll Chillers 100 285 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Businesses who function in today s advanced

More information

Presentation. Guaranteed Energy Savings Performance Project

Presentation. Guaranteed Energy Savings Performance Project Presentation Guaranteed Energy Savings Performance Project Greg Spiro, PE, CEM, LEED-AP Georgia Institute of Technology Senior Mechanical Engineer Facilities Design & Construction 470-351-9867151 6th Street

More information

What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering

What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,

More information

HVAC System Energy Savings Opportunities

HVAC System Energy Savings Opportunities HVAC System Energy Savings Opportunities Speaker Info M. Lant DuBose Energy Services ConEdison Solutions dubosem@conedsolutions.com (813)285-6340 Wholly owned subsidiary of ConEdison since 2007 Entered

More information

Pressure Drop Calculation

Pressure Drop Calculation Troubleshoot the following problem by using the information provided. The first 20 service technicians to fax the correct answer back to us will win $50. * Fax answers to: Jeff Cross @ (800) 783-5667 Troubleshooting

More information

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers INNOVATE DESIGN APPLY www.motivaircorp.com MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers ½ - 100 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Motivair is a world-class

More information

Designing Ultra-Efficient Building Cooling Systems

Designing Ultra-Efficient Building Cooling Systems Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Waterside Economizing in Data Centers: Design and Control Considerations

Waterside Economizing in Data Centers: Design and Control Considerations 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional reproduction,

More information

that may have a direct effect on your bottom line. The question

that may have a direct effect on your bottom line. The question VOLUME THREE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Cost of Owning a Chiller What is your bottom line?....... 1 What

More information

MLC Air-Cooled Chillers MLC-FC Free-Cooling Chillers MLC-AD Adiabatic Chillers

MLC Air-Cooled Chillers MLC-FC Free-Cooling Chillers MLC-AD Adiabatic Chillers INNOVATE DESIGN APPLY www.motivaircorp.com MLC Air-Cooled Chillers MLC-FC Free-Cooling Chillers MLC-AD Adiabatic Chillers 60-500 Tons OUR BUSINESS IS COOLING YOURS TM When commercial grade isn t enough

More information

PROCESS COOLING STUDY WORKSHEET

PROCESS COOLING STUDY WORKSHEET PROCESS COOLING STUDY WORKSHEET January, 0 December, 0 DIRECTIONS: Please save a copy of this form to your computer by selecting FILE/SAVE AS before entering text and numbers. Then fll in your information

More information

Siemens Demand Flow A unique and proven energy and operational cost saving application for water-cooled, central chilled water systems

Siemens Demand Flow A unique and proven energy and operational cost saving application for water-cooled, central chilled water systems Boston Green Tourism / Mandarin Oriental Hotel April 28, 2016 Siemens Demand Flow A unique and proven energy and operational cost saving application for water-cooled, central chilled water systems Answers

More information

Water cooled chiller plant (all-variable)

Water cooled chiller plant (all-variable) Data Center Water cooled chiller plant (all-variable) Design Envelope File No: 9.572 Date: november 14, 2014 Supersedes: 9.572 Date: september 22, 2014 design envelope s performance improvements are among

More information

32MP Gateway. Overview and Configuration Manual

32MP Gateway. Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual This document is the property of Carrier Corporation and is delivered on the express condition that it is not

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

Energy Management of the Refrigeration Systems at Zurich Airport. Burkhard Bein. Schaffhausen,

Energy Management of the Refrigeration Systems at Zurich Airport. Burkhard Bein. Schaffhausen, Energy Management of the Refrigeration Systems at Zurich Airport Burkhard Bein Schaffhausen, 29.06.18 Overview Content: General Information Refrigeration concept EMS program CS program Three projects for

More information

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers Engineering Data SED: 8012 Group: Centrifugal Chiller Date: March 2002 Supercedes: New Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers Model WSC/WDC 2002 McQuay International

More information

Air-Cooled Series R Chiller

Air-Cooled Series R Chiller Air-Cooled Series R Chiller The next generation of Air-Cooled Helical Rotary Chillers ANOTHER RELIABLE SOURCE OF CHILLED WATER FROM TRANE The new industry standard f The next generation of the air-cooled

More information

EVC INTERFACE TOOL OPERATION MANUAL EVC INTERFACE TOOL. Part No Part No Effective July 27, 2011 Revised December 18, 2012

EVC INTERFACE TOOL OPERATION MANUAL EVC INTERFACE TOOL. Part No Part No Effective July 27, 2011 Revised December 18, 2012 EVC INTERFACE TOOL OPERATION MANUAL EVC INTERFACE TOOL Part No. 8826824 Part No. 8826865 Effective July 27, 2011 Original English Version THE MILK COOLING SYSTEMS SPECIALISTS EVC INTERFACE TOOL OPERATION

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Blending Conveying Drying Process Cooling Heat Transfer Size Reduction GP SERIES Packaged Chillers Comprehensive Flexible Versatile Compact unitary designs available in a variety of configurations from

More information

Standard Circulating Pumps

Standard Circulating Pumps Product review Range: 1 1 3Q [ m³/h] Hz - North America 1 3 1 1 1.x1 1.x x x3 x 1 1 Q [ US gpm] >Single-head pumps: Seal-less circulator with flanged connection. Two speed, manually adjustable to match

More information

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants By: David Schurk DES., CEM., LEED AP., CDSM., SFP. Heat Transfer Solutions, Director of Healthcare Accounts The air-cooled

More information

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of

More information

Existing Building Energy Saving

Existing Building Energy Saving Existing Building Energy Saving Ir Cary Chan Executive Director, HK Green Building Council Aviation industry 1981 1971 1969 1930s 1903 2 3 4 5 6 7 A big gap to fill Convincing responses to your boss! Deliver!

More information

HIGH EFFICIENCY Central Chiller

HIGH EFFICIENCY Central Chiller Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,

More information

IBM - Energy Efficiency Recommissioning: Improving Buildings Systems Efficiency Jean-Pierre Boulianne, Pierre Lefèbvre, Yves Veilleux ICEBO 2013

IBM - Energy Efficiency Recommissioning: Improving Buildings Systems Efficiency Jean-Pierre Boulianne, Pierre Lefèbvre, Yves Veilleux ICEBO 2013 IBM - Energy Efficiency Recommissioning: Improving Buildings Systems Efficiency Jean-Pierre Boulianne, Pierre Lefèbvre, Yves Veilleux ICEBO 2013 IBM Bromont - Recommissioning IBM Manufacturing Plant Bromont,

More information

RBC-AMT32E / RBC-AMS41E

RBC-AMT32E / RBC-AMS41E Pocket Quick Reference Guide On the TOSHIBA RBC-AMT32E / RBC-AMS41E Remote Controllers Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large

More information

a) Provision of a chilled water supply b) Provision of electric power supply and other fuels

a) Provision of a chilled water supply b) Provision of electric power supply and other fuels 10.0 UTILITIES ELEMENT The purpose of this element is to ensure coordinated provision of utility services required to meet the future needs of the University, consistent with current efforts to address

More information

What is the Carrier ChillerVu series counterflow application?

What is the Carrier ChillerVu series counterflow application? Carrier ChillerVu 23XRV Series Counterflow Application Guide CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-578-01 4/5/2017 Verify that

More information

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller Pocket Quick Reference Guide On the TOSHIBA RBC-AMS51E Remote Controller Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity of data

More information

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,

More information

Identify the Right Applications

Identify the Right Applications providing insights for today s hvac system designer Engineers Newsletter volume 45 2 waterside economizers Keeping the "Free" In Free-Cooling This EN revisits the topic of a 2008 newsletter and provides

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Pressure switch KP. Data sheet

Pressure switch KP. Data sheet Data sheet Pressure switch KP The KP pressure switches can be used as safety switches against too low a suction pressure and / or too high a discharge pressure in refrigeration and air conditioning systems.

More information

Optimizing Laboratory Controls through Fault Detection and Diagnostics Software. Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM

Optimizing Laboratory Controls through Fault Detection and Diagnostics Software. Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM Optimizing Laboratory Controls through Fault Detection and Diagnostics Software Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM Overview What are EIS & FDD Tools? Data Connection Methods

More information

Trailblazer AGZ-E air-cooled scroll chillers

Trailblazer AGZ-E air-cooled scroll chillers Trailblazer AGZ-E air-cooled scroll chillers 30 to 240 tons with Variable Speed Condenser Fan Technology The right features, the right value, right now Intelligent Equipment AGZ-E 30 to 161 RapidRestore

More information

CENTRIFUGAL CONTROLS UPGRADE with Optional VFD control. MCS Total Solutions for all your HVAC\R Control Needs

CENTRIFUGAL CONTROLS UPGRADE with Optional VFD control. MCS Total Solutions for all your HVAC\R Control Needs MCS Total Solutions for all your HVAC\R Control Needs CENTRIFUGAL CONTROLS UPGRADE with Optional VFD control This brochure describes a standard upgrade package for a Centrifugal Chiller. Each Control upgrade

More information

AuraCool Economizer System

AuraCool Economizer System Page 1 Due to manufacturer's policy of continuous product improvement, the manufacturer reserves the right to make changes without notice. Drawings in this submittal are representations of the equipment

More information

DEDICATED HEAT RECOVERY UNIT (DHRC)

DEDICATED HEAT RECOVERY UNIT (DHRC) DEDICATED HEAT RECOVERY UNIT (DHRC) AHRI CERTIFICATION Air-Conditioning, Heating, and Refrigeration Institute Multistack is AHRI Certified and continues to certify products as they are developed AHRI Certification

More information

MOLLIER DIAGRAM CAN BE IMPROVED!

MOLLIER DIAGRAM CAN BE IMPROVED! MOLLIER DIAGRAM CAN BE IMPROVED! IMPROVED BASIC COOLING CIRCUIT PERFORMANCE EFFICIENCY USING AN ECONOMISER Eng. Jonny Malachi, VP Operations, Mashav Refrigeration and Air Conditioning Engineering Ltd.

More information

MICROCOMPUTER CONTROL CENTER

MICROCOMPUTER CONTROL CENTER OPERATION ROTARY SCREW LIQUID CHILLERS Supersedes: See Back Cover Form 160.47-O1.1 (197) MICROCOMPUTER CONTROL CENTER PART NO. 371-01112-001 or 371-01200-003 FOR MODEL YS BA BA S0 THRU YS FC FB S5 (STYLE

More information

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors. Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling

More information

Pressure switch KP. Data sheet

Pressure switch KP. Data sheet Data sheet Pressure switch KP The KP pressure switches can be used as safety switches against too low a suction pressure and / or too high a discharge pressure in refrigeration and air conditioning systems.

More information

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity ENVIRONMENTALLY SOUND REFRIGERANT C4H(5, 7) Product Specifications HIGH EFFICIENCY 15 and 17 TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 2, 3, 4, and 5 TONS SPLIT SYSTEM 208 / 230 Volt,

More information

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH 1 Chilled and Hot Water Fan Coil Low Static 4-Pipe Nominal Size:

More information

Dykin Engineering Part & Services Sdn. Bhd.

Dykin Engineering Part & Services Sdn. Bhd. Dykin Engineering Part & Services Sdn. Bhd. CHILLED WATER SOLUTIONS Water chillers to custom air handlers to variable air volume terminal systems. We provide PM (Preventative Maintenance) and FM (Full

More information

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies

More information

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

RGX COMMUNICATIONS GATEWAY

RGX COMMUNICATIONS GATEWAY RGX COMMUNICATIONS GATEWAY BTU Ventilation Corporation 47418 US Highway 10 Perham, Mn 56573 USA Phone (218) 346-7482 Fax (218) 346-7485 http:/// Manual ver 2.1 Copyright BTU Ventilation Corp 2008 RGX Communications

More information

Energy Efficiency Retrofit Technologies for RTUs

Energy Efficiency Retrofit Technologies for RTUs Energy Efficiency Retrofit Technologies for RTUs POTENTIAL RTU RETROFITS Retrofits proven to increase the energy efficiency and reduce operating costs Stated Goals of RTU Retrofit development (DOE): Optimize

More information

Case Study: Energy Systems Integration Facility (ESIF)

Case Study: Energy Systems Integration Facility (ESIF) Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case

More information

Communication Register Map - Uniflair Cooling

Communication Register Map - Uniflair Cooling DIGITAL 0 1 1 - - - - DIGITAL 1 2 2 System On (Fan) 0 or 1 boolean R DIGITAL 2 3 3 Compressor 1 0 or 1 boolean R DIGITAL 3 4 4 Compressor 2 0 or 1 boolean R DIGITAL 4 5 5 Compressor 3 0 or 1 boolean R

More information

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

DEEMED SAVINGS TECHNICAL ASSUMPTIONS Program: Description: Prescriptive rebates will be offered for new cooling equipment. Rebates may be dependent on equipment size or load that is offset and on meeting minimum efficiency requirements. Additional

More information

TacoNet For Windows Equipment Selection Version 7 October 2001 Taco, Inc Cranston St. Cranston, RI Phone:(800) FAX:(401)

TacoNet For Windows Equipment Selection Version 7 October 2001 Taco, Inc Cranston St. Cranston, RI Phone:(800) FAX:(401) TacoNet For Windows Equipment Selection Version 7 October 2001 Taco, Inc. 1160 Cranston St. Cranston, RI 02920 Phone:(800) 441-1969 FAX:(401) 942-2360 Copyright 1986-2001 All Rights Reserved. Foreword

More information

STANDARD MODELS MT 3/4 HP + LT 2.5 HP MT 1.0 HP + LT 2.5 HP. Other models available upon request

STANDARD MODELS MT 3/4 HP + LT 2.5 HP MT 1.0 HP + LT 2.5 HP. Other models available upon request PRODUCT DATA & SPECIFICATIONS Bulletin B40-BC-PDS Part # 1106712 PRODUCT SUPPORT web: b-rp.ca/bc email: multicompcu@b-rp.ca call: 1-844-893-3222 x524 scan: BC Combination Condensing Units Cooler/Freezer

More information

19XR CONTROLS UPGRADE with Optional VFD control

19XR CONTROLS UPGRADE with Optional VFD control MCS Total Solutions for all your HVAC/R Control Needs 19XR CONTROLS UPGRADE with Optional VFD control This brochure describes a standard upgrade package for the 19XR CHILLER. Each Control upgrade installation

More information

SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC. February 17, 2010 Revised

SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC. February 17, 2010 Revised SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC February 17, 2010 Revised SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BACKGROUND INFORMATION Syracuse University

More information

Liebert. PDX and PCW Compact Perimeter Cooling Solutions

Liebert. PDX and PCW Compact Perimeter Cooling Solutions PDX and PCW Perimeter Cooling Solutions LIEBERT PDX AND LIEBERT PCW Perimeter Cooling Solutions Introducing thermal management solutions that efficiently lower your operating costs and pack a lot of capacity

More information

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak Control

More information

New Design Strategies for Energy Saving. Intelligent free-cooling

New Design Strategies for Energy Saving. Intelligent free-cooling New Design Strategies for Energy Saving Intelligent free-cooling Intelligent New strategies for energy saving When designing mission critical systems for processing applications or highly technological

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to

More information

HIGH EFFICIENCY UP TO 19 SEER VARIABLE SPEED HEAT PUMP WITH OBSERVER

HIGH EFFICIENCY UP TO 19 SEER VARIABLE SPEED HEAT PUMP WITH OBSERVER HVH8 Product Specifications HIGH EFFICIENCY UP TO 19 SEER VARIABLE SPEED HEAT PUP WITH OBSERVER COUNICATING CONTROL SYSTE 2 THRU 5 TONS SPLIT SYSTE 208 230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Variable

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get *

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get * Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get * Trane CenTraVac chillers: Designed and built to be the best; tested to prove it Ongoing innovation. Unmatched capabilities.

More information

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER CLICK TO EDIT MASTER TITLE STYLE AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER GREEN CHILLER PLANT Energy Efficiency Superior system performance Less energy consumption versus similar size building Operation

More information

Standard Circulating Pumps

Standard Circulating Pumps Product review Range: 1 1 3Q [ m³/h] Hz - North America 1 3 1 1 1.x1 1.x x x3 x 1 1 Q [ US gpm] >Single-head pumps: Circulating pumps with flanged connection > Applications: Drinking-water circulation

More information

Saving Water and Operating Costs at NREL s HPC Data Center

Saving Water and Operating Costs at NREL s HPC Data Center Saving Water and Operating Costs at NREL s HPC Data Center Thomas P. Carter, P.E. Johnson Controls Thomas.P.Carter@jci.com David Sickinger National Renewable Energy Laboratory David.Sickinger@nrel.gov

More information

Model YLAA Air-Cooled Scroll Chillers Style A

Model YLAA Air-Cooled Scroll Chillers Style A FORM 0.-EG (709) Model YLAA Air-Cooled Scroll Chillers Style A 70 7 TON 7 kw 0 Hz R-0A Products are produced at a f a c i l i t y wh o s e qualitymanagement systems are ISO900 certified. Table of contents

More information

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution CGWN/CCUN indoor liquid chillers The compact AquaStream² solution Plug and Play for unparalleled Certified performance Eurovent certification provides capacity and efficiency compliance, thus confirming

More information

PEH-WSC CONTROLS UPGRADE with Optional VFD control

PEH-WSC CONTROLS UPGRADE with Optional VFD control MCS Total Solutions for all your HVAC/R Control Needs PEH-WSC CONTROLS UPGRADE with Optional VFD control This brochure describes a standard upgrade package for the PEH-WSC Chillers. Each Control upgrade

More information

HOURLY ANALYSIS PROGRAM v5.00 and v5.01

HOURLY ANALYSIS PROGRAM v5.00 and v5.01 HOURLY ANALYSIS PROGRAM v and v5.01 Carrier Software Systems Carrier Corporation Syracuse, New York Rev. November 3, 2016 Copyright 2016 Carrier Corporation, All Rights Reserved Contents Chiller Features

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

Aquaflair. BREC/F and BCEC/F kw

Aquaflair. BREC/F and BCEC/F kw Aquaflair Air-cooled chillers and free-cooling chillers with screw or oil-free centrifugal compressors equipped with adiabatic system BREC/F and BCEC/F 350-1350 kw Dualism for evolution: the combination

More information

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to

More information

CARRIER HOURLY ANALYSIS PROGRAM v5.0

CARRIER HOURLY ANALYSIS PROGRAM v5.0 CARRIER HOURLY ANALYSIS PROGRAM v5.0 Carrier Software Systems Carrier Corporation Syracuse, New York Rev. June 22, 2016 Copyright 2016 Carrier Corporation, All Rights Reserved Contents Air-Side Features

More information

Chilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP

Chilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP Chilled Water Distribution Design Considerations in Super Tall Buildings Dusan Mrdalj, Associate, ChapmanBDSP Dusan Mrdalj Bio - MSc Mechanical Engineering - Associate in ChapmanBDSP - 20 years of Professional

More information

U-Match Series DC Inverter Service Manual PRODUCT

U-Match Series DC Inverter Service Manual PRODUCT PRODUCT 1 PRODUCT 1 MODELS LIST 1.1 Outdoor Unit Name Product Code Power Supply (V, Ph, Hz) Appearance GUHD24NS3GO CF090W0800 220-240V~ 50/60Hz GUHD36NS3GO CF090W0860 220-240V~ 50/60Hz GUHD42NS3GO CF090W0870

More information

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11 Table of Contents Executive Summary... 3 Site and Unit Background... 5 Chiller 1... 6 Chiller 2... 9 Appendix... 11 A Vidaris Company 2 Executive Summary New York Blood Center s facility in Long Island

More information

KLP. Low Profile Evaporators CONTENTS PRODUCT DATA & INSTALLATION

KLP. Low Profile Evaporators CONTENTS PRODUCT DATA & INSTALLATION PRODUCT DATA & INSTALLATION Bulletin K30-KLP-PDI-16 Part # 1087150 PRODUCT SUPPORT web: k-rp.com/klp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: KLP Low Profile Evaporators Air, Electric, Hot

More information

APC APPLICATION NOTE #126

APC APPLICATION NOTE #126 #16 Selection Procedure for Inow Chilled Water Products By Greg Uhrhan, P.E. and Scott Buell Abstract Proper selection of Inow chilled water cooling systems requires an engineer or technical salesperson

More information

BACnet MS/TP Interface User s Guide

BACnet MS/TP Interface User s Guide PoolPak MPK with CommandPak Control System CPCS BACnet MS/TP Interface User s Guide DOCUMENT #: SVW07-BACNET-MSTP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak

More information

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S FREE COOLING CHILLER Getting To A PUE Of 1.2 Free cooling data center chillers are designed to

More information

Product Data. S Up to 19 SEER /13.0 EER / 11 HSPF S Microtube Technologyt refrigeration system Sound

Product Data. S Up to 19 SEER /13.0 EER / 11 HSPF S Microtube Technologyt refrigeration system Sound 25VNA8 Infinityr 18VS Variable Heat Pump with Puronr Refrigerant Product Data The Infinity 18VS heat pump offers high -efficiency variable speed performance in a remarkably small cabinet and provides up

More information

ACDU01A Communicating Service Tool

ACDU01A Communicating Service Tool Operation Manual 97B0106N02 Created: 10/1/12 Caution: These instructions are intended to be used by the installer or service personnel. End users are NOT advised to change or modify any of these settings.

More information

Product Data. S Up to 18 SEER /12.5 EER / 11 HSPF S Microtube Technologyt refrigeration system Sound

Product Data. S Up to 18 SEER /12.5 EER / 11 HSPF S Microtube Technologyt refrigeration system Sound 25VNA8 Infinityr 18VS Variable Heat Pump with Puronr Refrigerant 2 --- 5 Ton Product Data The Infinity 18VS heat pump offers high -efficiency variable speed performance in a remarkably small cabinet and

More information