WinPAC-5000 User Manual (WinCE Based, evc &.net)

Size: px
Start display at page:

Download "WinPAC-5000 User Manual (WinCE Based, evc &.net)"

Transcription

1 WinPAC-5000 User Manual (WinCE Based, evc &.net) Version 1.0.8, January 2014 Service and usage information for WP-5141 WP-5141-OD WP-5151 WP-5151-OD WinPAC-5000 Series User Manual, Version Page: 1

2 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, beginning from the date of delivery to the original purchaser. Warning ICP DAS assumes no liability for any damage resulting from the use of this product.icp DAS reserves the right to change this manual at any time without notice. The information furnished by ICP DAS is believed to be accurate and reliable. However, no responsibility is assumed by ICP DAS for its use, not for any infringements of patents or other rights of third parties resulting from its use. Copyright 2014 by ICP DAS Co., Ltd. All rights are reserved. Trademark The names used for identification only may be registered trademarks of their respective companies. Contact US If you have any problem, please feel free to contact us. You can count on us for quick response. service@icpdas.com WinPAC-5000 Series User Manual, Version Page: 2

3 Table of Contents 1. Introduction WinPAC-5000 Family WinPAC-5000 Naming Convention WinPAC-5000 Comparison Features Specifications Overview Dimension Companion CD Getting Started Mounting the Hardware Configuring the Boot Mode Changing the Language of the User Interface Using WinPAC Utility to Configure WinPAC Basic Functionality Using Backup Utility to Back up the Settings and Files Tools and Tasks Backup Utility Dconmcnfg Napopc_ce SendToCOM VCEP WinPAC_Utility Menu Bar Property Tabs Your First Program WinPAC-5000 Series User Manual, Version Page: 3

4 4.1. Preparing the Development Tools Installing WinPAC-5000 SDK Your First Program in C# Creating a New Project Adding the WinPAC-5000 Reference Adding the Control to the Form Adding the Event Handling to the Control Upload the Application to WinPAC Executing the Application on WinPAC Your First Program in VB.net Creating a New Project Adding the WinPAC-5000 Reference Adding the Control to the Form Adding the Event Handling to the Control Upload the Application to WinPAC Executing the Application on WinPAC Your First Program in embedded Visual C Creating a Forms-Based Project Configuring the Platform Specifying the Path of the WinPAC-5000 Reference Adding the Control to the Form Adding the Event Handling to the Control Upload the Application to WinPAC Executing the Application on WinPAC APIs and Demo Programs Demo Programs with C# C# Demo Programs for WinPAC Standard API C# Demo Programs for PAC I/O API Demo Programs with evc evc++ Demo Programs for WinPAC Standard API WinPAC-5000 Series User Manual, Version Page: 4

5 evc++ Demo Programs for PAC I/O API I/O Modules and SDK Selection WinPAC-5000 Updates OS Updates OS Updates Using Installation Package File OS Updates Using Eshell via Ethernet SDK Updates WinPAC SDK updates for C# or VB.net WinPAC SDK updates for evc Appendix A. Tips-How to A.1. How to add a User Account A.1.1. How to Use telnet to remote login the WinPAC from PC A.1.2. How to remove the user from the login list A.2. How to online debug WinPAC A.2.1. Debug WinPAC programs in EVC A.2.2. Debug WinPAC programs in Visual Studio 2005/ A.3. How to use the printer A.3.1. How to use network printer A.3.2. How to use printer via USB A.4. How to use services tool A.5. How to use ActiveSync through USB port A.6. How to automatically synchronize the WinPAC clock with an Internet Time Server Appendix B. XW-board Modules Appendix C. Revision History WinPAC-5000 Series User Manual, Version Page: 5

6 1. Introduction WinPAC-5000 Series is the new generation PAC (Programmable Automation Controller). It is equipped with a PXA270 CPU (520 MHz) running a Windows CE.NET 5.0 operating system, various connectivity (VGA, USB, Ethernet, RS-232/485) and I/O expansion bus. The WinPAC-5000 series has many advantages, including hard real-time capability, small core size, and fast boot speed, interrupt handling at a deeper level, achievable deterministic control and low cost. Using Windows CE.NET 5.0 gives it the ability to run PC-based control software such as Visual Basic.NET, Visual C#, Embedded Visual C++, SCADA software, SoftPLC. It gives users all of the best features of both traditional PLCs and Windows capable PCs. For hardware expansion, it also supports an I/O expansion bus. The I/O expansion bus can be used to implement various I/O functions such as D/I, D/O, A/D, D/A, Timer/Counter, UART, and other I/O functions. Nearly all kinds of I/O functions can be implemented by this bus. But the bus can support only one board. There are more than 10 boards available for WinPAC-5000 series which users can choose one of them to expand hardware features. WinPAC-5000 Series User Manual, Version Page: 6

7 1.1. WinPAC-5000 Family The WinPAC-5000 family is divided into two main types according to Audio port. WP-5141 (without Audio port) WP-5141-OD (with Audio port) WP-5151 (without Audio port) WP-5151-OD (with Audio port) WinPAC-5000 Naming Convention As you examine this manual, you ll notice there are many different models available. Sometimes it is difficult to remember the specifications for any given model. However, if you take a few minutes to understand the module naming conventions, it may save you some time and confusion. The figure below shows how the module naming conventions work for each WinPAC-5000 model. WinPAC-5000 Series User Manual, Version Page: 7

8 WinPAC-5000 Comparison The following table shows the comparison in all the features of WinPAC-5000 family. Model OS CPU Flash SDRAM Ethernet VGA Resolution RS-232/ RS-485 I/O Expansion Bus Audio Port WP /1 - WP-5141-OD WP-5151 CE5.0 PXA MHz 64 MB 128 MB x 600 Yes (for XW-board only) Yes - 1/2 WP-5151-OD Yes WinPAC-5000 Series User Manual, Version Page: 8

9 1.2. Features The key features of WinPAC-5000 include: Windows CE.Net 5.0 Supports PC based software: evc and VS.NET Web server, FTP server, Telnet server ISaGRAF version for IEC programming InduSoft version for SCADA solution Local I/O and Communication Expansion Board WinPAC-5000 series equip an I/O expansion bus to support one optional expansion board, called XW-board. It can be used to implement various I/O functions such as DI, DO, A/D, D/A, Timer/Counter and various communication interface, such as RS-232/422/485, CAN, FRnet, etc. WinPAC-5000 Series User Manual, Version Page: 9

10 Various Memory Expansions WinPAC-5000 provides various memory storage options, such as EEPROM and microsd. Customers can choose the memory based on their characteristics. 16 KB EEPROM: to store not frequently changed parameters. microsd/microsdhc: to implement portable data logging applications. Unique 64-bit Hardware Serial Number to Protect Your Program A unique 64-bit serial number is assigned to each hardware device to protect your software against piracy. Remote I/O Module and Expansion Unit With the built-in RS-485 and Ethernet port, the 5000 series can connect RS-485/Ethernet remote I/O units (RU-87Pn/ET-87Pn) or modules (I-7000/M-7000/ET-7000). With an XW-board, the 5000 series can have more communication ports or different interface to connect to other type of devices, for example: CANOpen devices, DeviceNet devices, or FRnet I/O modules. Plastic and Metal Casing The default case is plastic material, customers can choose metal case if they want. WinPAC-5000 Series User Manual, Version Page: 10

11 Multi-Communication Interface There are several of communication interfaces to expand I/O and connect to external devices: Small and Easy Installation WinPAC-5000 Series have a palm-size shape (91 mm x 132 mm x 52 mm) to be installed in a narrow space with DIN-Rail. Highly Reliable Under Harsh Environment Our WinPACs operate in a wide range of temperature and humidity. Operating Temperature: -25 ~ +75 C Storage Temperature: -30 ~ +80 C Humidity: 10% ~ 90% RH, non-condensing WinPAC-5000 Series User Manual, Version Page: 11

12 1.3. Specifications Models WP-5141 WP-5141-OD WP-5151 WP-5151-OD System Software OS Windows CE 5.0.Net Compact Framework 2.0/3.5 Embedded Service FTP server, Web server (supports VB script, JAVA script), Embedded SQL server SDK provided Dll for evc, Dll for Visual Studio.Net 2003/2005/2008 CPU Module CPU SDRAM Flash EEPROM Expansion Flash Memory RTC (Real Time Clock) 64-bit Hardware Serial Number Dual Watchdog Timers LED Indicator PXA270 or compatible (32-bit and 520 MHz) 128 MB 64 MB (32 MB for OS, 32 MB for System_Disk and System Registry) 16 KB Data Retention: 40 Years; 1,000,000 erase/write cycles microsd socket with a microsd card (support up to 16 GB microsd card) Provide second, minute, hour, date, day of week, month, year Yes Yes 3 LEDs (RUN/PWR, L1 ~ L2; RUN/PWR for status indications, L1 ~ L2 for user programmable) Rotary Switch Yes (0 ~ 9) VGA & Communication Ports VGA 640 x 480 or 800 x 600 Ethernet RJ-45 x 2, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators) USB 1.1 (client) 1 USB 1.1 (host) 1 Audio Port (Microphone-In and Earphone-Out) COM1 COM2 - Yes - Yes RS-232 (RxD, TxD and GND); Non-isolated RS-485 (D2+, D2-); 2500 V DC ; isolated COM3 RS-232 (RxD, TxD and GND); Non-isolated RS-485 (D3+, D3-); 2500 VDC; isolated WinPAC-5000 Series User Manual, Version Page: 12

13 Models WP-5141 WP-5141-OD WP-5151 WP-5151-OD I/O Expansion I/O Expansion Bus Yes, to mount one optional XW-board Mechanical Dimensions (W x L x H) Installation 91 mm x 132 mm x 52 mm DIN-Rail Mounting Environmental Operating Temperature -25 ~ +75 C Storage Temperature -30 ~ +80 C Ambient Relative Humidity 10 ~ 90% (non-condensing) Power Input Range +10 ~ +30 V DC Isolation 1 kv Consumption 4.8 W(0.2 6 W ( W (0.2 A 6 W ( V DC ) 24 V DC 24 V DC ) 24 V DC ) WinPAC-5000 Series User Manual, Version Page: 13

14 1.4. Overview Here is a brief overview of the components and its descriptions for module status. Front Panel The front panel includes programmable LED indicators. LED Indicators LED indicators provide a very convenient way of status indications for faster, easier diagnostics. LED Name RUN/PWR Color (ON State) Green Orange Meaning Power is on Power on and OS is running L1 Green User programmable control LED L2 Green User programmable control LED WinPAC-5000 Series User Manual, Version Page: 14

15 Tips & Warnings The LED indicators can be programmed with WinPAC API. If not necessary, do not use RUN that is assigned to the OS-status indicators. Top Panel The top panel includes a microsd socket, VGA port, USB client and rotary switch. microsd socket The microsd socket provides an easy way to expand the available storage with a microsd card up to 16 GB maximum. WinPAC-5000 Series User Manual, Version Page: 15

16 VGA port External VGA port provides an easy connection to a monitor or touch panel. USB Client USB Client is used to for ActiveSync application. An accessory USB cable is available to connect the client port with USB mini-b type to USB. Type A plug on a PC for ActiveSync application. Rotary Switch The rotary switch is used to select the operating mode. For more information about the operating mode, please refer to section 2.2. Configuring the Boot Mode. WinPAC-5000 Series User Manual, Version Page: 16

17 Bottom Panel The bottom panel includes a microphone, an earphone, a USB host, a connector and two Ethernet ports Microphone-in and Earphone-out (for WP-5141-OD/WP-5151-OD only) The microphone and an earphone jack to allow the input and the output of the audio system. Ethernet Port (LAN1 and LAN2) The Ethernet ports are the opening on WinPAC-5000 network equipment that Ethernet cables plug into. Ethernet ports accept cables with RJ-45 connectors. WinPAC-5000 Series User Manual, Version Page: 17

18 USB Host A USB host controller is a machine with a root hub which allows several input devices to be connected to it, such as mice and keyboards. Connector The pin assignments of the connector are as follows: WP-5141/WP-5141-OD Pin Signal Description 1 F.G Frame Ground 2 GND Power Input 3 PWR 4 TxD COM3: RS RxD 6 D- COM2: RS D+ 8 GND 9 TxD COM1: RS RxD WP-5151/WP-5151-OD Pin Signal Description 1 F.G Frame Ground 2 GND Power Input 3 PWR 4 D- COM3: RS D+ 6 D- COM2: RS D+ 8 GND 9 TxD COM1: RS RxD WinPAC-5000 Series User Manual, Version Page: 18

19 COM1 (3-Pins, RS-232) Note: CPU internal UART Baud Rate: 15200, 57600, 38400, 19200, 9600, 4800, 2400, 1200 bps Data Bits: 7, 8 Parity: None, Even, Odd Stop Bits: 1 FIFO: 1 byte COM2 (2-Pins, RS-485) Note: 16C550 compatible Baud Rate: 15200, 57600, 38400, 19200, 9600, 4800, 2400, 1200 bps Data Bits: 7, 8 Parity: None, Even, Odd, Mark (Always 1), Space (Always 0) Stop Bits: 1, 2 FIFO: 16 bytes COM3 (3-Pins, RS-232 for WP-5141/WP-5141-OD) Note: 16C550 compatible Baud Rate: 15200, 57600, 38400, 19200, 9600, 4800, 2400, 1200 bps Data Bits: 7, 8 Parity: None, Even, Odd, Mark (Always 1), Space (Always 0) Stop Bits: 1, 2 FIFO: 16 bytes WinPAC-5000 Series User Manual, Version Page: 19

20 COM3 (3-Pins, RS-485 for WP-5151/WP-5151-OD) Note: 16C550 compatible Baud Rate: 15200, 57600, 38400, 19200, 9600, 4800, 2400, 1200 bps Data Bits: 7, 8 Parity: None, Even, Odd, Mark (Always 1), Space (Always 0) Stop Bits: 1, 2 FIFO: 16 bytes WinPAC-5000 Series User Manual, Version Page: 20

21 1.5. Dimension All dimensions are in millimeters. WP-5141/WP-5151 WinPAC-5000 Series User Manual, Version Page: 21

22 WP-5141/WP-5151 with XW-board WinPAC-5000 Series User Manual, Version Page: 22

23 WP-5141-OD/WP-5151-OD WinPAC-5000 Series User Manual, Version Page: 23

24 WP-5141-OD/WP-5151-OD with XW-board WinPAC-5000 Series User Manual, Version Page: 24

25 1.6. Companion CD This package comes with a CD that provides drivers, software utility, all of the required documentations, etc. All of them are listed below. CD:\napdos wp-5000_ce50 Backup Backup files related to the documents, OS images, SDKs..., etc. Demo Demos related to WinPAC Document Document related to WinPAC Micro_SD Tools and drivers related to manage the microsd OS_Image OS_Image related to WinPAC PC_Tools Tools related to management WinPAC that install on PC SDK SDKs related to WinPAC System_Disk Tools and drivers related to System_Disk that install on WinPAC Update Installation packages related to WinPAC updates WinPAC-5000 Series User Manual, Version Page: 25

26 2. Getting Started If you are a new user, begin with this chapter, it includes a guided tour for basic overview of installation and configuration. In addition to Quick Start Guide, the package includes the following items, if any items are damaged or missing, please contact us. WinPAC Module WP-5141 WP-5141-OD WP-5151 WP-5151-OD A microsd Card and Software Utility CD Screw Driver a microsd/sd Adapter (1C016) 2.4 mm WinPAC-5000 Series User Manual, Version Page: 26

27 2.1. Mounting the Hardware Before installing the hardware, you should have a basic understanding of hardware specification, such as the size of hard drive, the usable input-voltage range of the power supply, and the type of communication interfaces. For complete hardware details, please refer to section 1.3. Specifications You also need to know the expansion capacities in order to choose the best expansion module for achieving maximal efficiency. For more information about expansion module that are compatible with the unit, please refer to WinPAC-5000 Series User Manual, Version Page: 27

28 Step 1: Mounting WinPAC-5000 The WinPAC-5000 can be mounted with the bottom of the chassis on the DIN rail, the wall or piggyback. To clean the unit, wipe it with a clean, dry cloth. Maintain the following conditions: Operating Temperature: -25 C to +75 C Storage Temperature: -30 C to +80 C Relative Humidity: 10% to 90%, non-condensing Mounting on DIN rail Removing from DIN rail DIN rail mounting The WinPAC-5000 has simple rail clips for mounting reliably on a standard 35 mm DIN rail. Piggyback mounting The WinPAC-5000 has two holes on both sides for piggyback mounting. WinPAC-5000 Series User Manual, Version Page: 28

29 Step 2: Connecting to a microphone, an audio, a PC, the USB device, and the power supply i. Connect the mouse or keyboard to the USB port. ii. Connect the microphone and earphone to the microphone-in and earphone-out (for WP-5141-OD/WP-5151-OD only) iii. Connect PC to the Ethernet port through a hub. iv. Connect the power supply (10 ~ 30 V DC ) to PWR and GND terminals. v. Connect the monitor to the VGA port. WinPAC-5000 Series User Manual, Version Page: 29

30 2.2. Configuring the Boot Mode The WinPAC-5000 has the following seven main operating modes, which can be selected by a rotary switch. Rotary switch position Modes of operation 0 Normal mode (Default) 1 Safe mode 2 Debug mode 3 OS update mode 4 Development mode 5 DCON_CE 6 VCEP 7 ~ 9 (For user) The following is an overview of the seven modes. Normal Mode (Default mode) Normal mode is the default mode of operation and the one you will use most of the time. Use this mode for more tasks and configurations. Programs also are executed in this mode. Safe Mode Safe mode is a trouble shooting. The mode loads the minimum required device drivers and system services to boot the WinPAC If you have malicious software or a program caused the WinPAC-5000 cannot be boot or run the normal mode, you can boot in safe mode to solve the problem. WinPAC-5000 Series User Manual, Version Page: 30

31 Debug Mode Debug mode is a special environment in which program debug functions can be used in addition to normal system functions. Debug mode is unsupported. OS Update Mode OS update mode is a way used to update OS. For more information on updating the WinPAC-5000 OS image, please refer to section 6.1. OS updates Development Mode DCON_CE In this mode, the DCON_CE will be run automatically, and other settings are same as the normal mode. For more information about the VCEP, please refer to section 3.3. DCON_CE. VCEP In this mode, the VCEP will be run automatically, and other settings are same as the normal mode. For more information about the VCEP, please refer to section 3.5 VCEP. User Mode The positions 7, 8, 9 of rotary switch are reserved for user s applications. When WinPAC-5000 is boot with one of these positions, it is boot at normal mode. User s application can check the rotary switch position to run at different mode. WinPAC-5000 Series User Manual, Version Page: 31

32 2.3. Changing the Language of the User Interface The WinPAC-5000 is a Windows CE-based operating system which provides multilingual user interface and the user interface can be set to one of multi languages. Step 1: Open the Control Panel Step 2: Run the Regional Settings Step 3: Choose the display language, and then click OK WinPAC-5000 Series User Manual, Version Page: 32

33 Step 4: Run the WinPAC Utility Step 5: On the File menu, click Save and Reboot Step 6: Click Yes to reboot the WinPAC-5000 WinPAC-5000 Series User Manual, Version Page: 33

34 2.4. Using WinPAC Utility to Configure WinPAC Basic Functionality WinPAC Utility is a tool that provides ability to configure the WinPAC-5000 services. For more information on how to use the WinPAC Utility, please refer to section 3.6. WinPAC Utility. WinPAC-5000 Series User Manual, Version Page: 34

35 2.5. Using Backup Utility to Back up the Settings and Files After saving the configuration settings for a WinPAC device following the first use, it is recommended to use the Backup utility to back up all the data (settings and files). Step 1: Run the Backup Utility on the WinPAC The Backup Utility is located at: \System_Disk\tools\Backup_utility\ Step 2: Click the Backup menu Step 3: Select the options that you want to backup, enter text annotations and then click the Start backup button WinPAC-5000 Series User Manual, Version Page: 35

36 Step 4: Confirm the backup options and then click Yes button Step 5: Choose the folder that you want to save backup file and click the Ok button Step 6: Wait for process to finish WinPAC-5000 Series User Manual, Version Page: 36

37 3. Tools and Tasks Following tools has been installed on WinPAC CD:\Napdos wp-5000_ce50 System_Disk Tools Backup_Utility Dcomcnfg DCON_CE DCON_Utility_CE5 ISQLW35 Modbus modbus_master_tool NAPOPC_CE5 Quicker RegistryEditor RegistryViewer Remote_display_application SendToCOM TaskMgr VCEP WinPAC_Utility WinPAC-5000 Series User Manual, Version Page: 37

38 Backup_Utility The Backup_Utility is a system backup/restore tool used to backup/restore all the data (OS, settings and files) from/to the WinPAC/ViewPAC device. Dcomcnfg dcomcnfg.exe for Windows CE to configure your DCOM settings. NTLMUser.exe for Windows CE to create local NTLM accounts on the Windows CE Device. DCON_CE With Host PC running the DCON Utility, on the WinPAC, the DCON_CE program allows user to view and monitor the status of the DCON Utility. ISQLW35 The ISQLW35 implements SQL server compact 3.5 Query Analyzer. Modbus The Modbus provides various applications of Modbus protocol for configuring the WinPAC. NAPOPC_CE5 NAPOPC_CE5 is an integrated omnibus software package, it allows user to quickly establish a DCS control system. Registry Editor The Registry Editor allows user to editor the registry value of Windows CE Operating System. WinPAC-5000 Series User Manual, Version Page: 38

39 Remote display application The remote display application allows user to view the display remotely of the WinPAC on a Host PC. SendToCOM The SendToCOM allows user to send/receive data to/from the expansion module via serial port. TaskMgr The TaskMgr provides details about programs and processes running on the WinPAC. VCEP The VCEP allows user to manage the WinPAC remotely on a Host PC. WinPAC Utility The WinPAC Utility provides various useful functions such as configuring Ethernet settings, monitoring system settings and FTP services for easy and quick management. WinPAC-5000 Series User Manual, Version Page: 39

40 3.1. Backup Utility Backup Utility is an application program for backing up data. With this utility, you can easily back up not only the files and folders you have created on your WinPAC-5000 but also the entire partition(s) including your WinPAC-5000 operating environment and its settings and dictionaries. Below are the step-by-step procedures to use the Backup utility to back up data. Step 1: Run the Backup Utility on the WinPAC The Backup Utility is located at: \System_Disk\tools\Backup_utility\ Step 2: Click the Backup menu Step 3: Select the options that you want to backup, enter text annotations and then click the Start backup button WinPAC-5000 Series User Manual, Version Page: 40

41 Step 4: Confirm the backup options and then click Yes button Step 5: Choose the folder that you want to save backup file and click the Ok button Step 6: Wait for process to finish WinPAC-5000 Series User Manual, Version Page: 41

42 3.2. Dconmcnfg DCOMCNFG is a utility included with Microsoft Windows CE operating system and is used to configure various DCOM-specific settings in the registry. You can use the registry to specify default permissions for objects on the system, such as Access, Launch, and Configuration. WinPAC-5000 Series User Manual, Version Page: 42

43 3.3. Napopc_ce5 NAPOPC_CE5 DA Server is a free OPC DA Server (The "OPC" stands for "OLE for Process Control" and the "DA" stands for " Data Access") working on WinPAC, ViewPAC & WinCon controllers provided by ICP DAS Ltd. The first standard (originally called simply the OPC Specification and now called the Data Access Specification) resulted from the collaboration of a number of leading worldwide automation suppliers working in cooperation with Microsoft. Originally based on Microsoft's OLE COM (component object model) and DCOM (distributed component object model) technologies, the specification defined a standard set of objects, interfaces and methods for use in process control and manufacturing automation applications to facilitate interoperability. NAPOPC_CE5 DA Server integrates OPC, Modbus TCP Slave and Modbus RTU Slave three kind Slave services, as well as integrates Modbus TCP Master, Modbus RTU Master and DCON three kind Master communication protocols. It also provides one advanced function Rule Script for use in the I/O integration and transformation, and some conditional Logic operation. Any version before of the NAPOPC_CE5 was named Quicker WinPAC-5000 Series User Manual, Version Page: 43

44 3.4. SendToCOM The SendToCOM uses the serial port to communicate with expansion module. To use the SendToCOM, you can send data to expansion module through the serial port, and receive data from other device through the serial port. For more information about these commands for communicating with expansion module, please refer to: CD:\Napdos\io_module\87k_high_profile_modules.htm WinPAC-5000 Series User Manual, Version Page: 44

45 3.5. VCEP ICPDAS VCEP is designed for managing your WinPAC anywhere. No matter where you are, ICPDAS VCEP provides a convenient environment on the Desktop PC and allows you control your WinPAC remotely. ICPDAS VCEP is composed of two main components: The Server which runs on WinPAC. The Client" which runs on a Desktop PC. Once a connection is established between the client and server (initiated by the client), the client will periodically send requests for screen updates and send mouse/key click information to the server to simulate. Each video frame is inter-compressed against the previous frame and then intra-compressed with a modified LZW scheme to minimize the amount of data transmitted from server to client. For more detailed information on VCEP application, please refer to ftp://ftp.icpdas.com.tw/pub/cd/winpac/napdos/wp-8x4x_ce50/pc_tools/vcep_ / WinPAC-5000 Series User Manual, Version Page: 45

46 3.6. WinPAC_Utility The WinPAC Utility is a tool which is designed to quickly control and manage the WinPAC. WinPAC-5000 Series User Manual, Version Page: 46

47 Menu Bar The WinPAC Utility includes the following function menu. All functions menu will be explained later. File Menu Help Menu Configuration Menu WinPAC-5000 Series User Manual, Version Page: 47

48 File Menu The menu commands Save Use to Save the settings into Flash. The new settings don t take effect until the WinPAC restart. Save and Reboot Save the settings into Flash and restart the WinPAC. The new settings will take effect after the WinPAC restart. Reboot Without Save Restore Default Settings Restarts the WinPAC without save the settings into Flash. Restarts the settings of WinPAC to its factory default values. The settings include configuration setting, network setting, auto execution, etc. Exit Exits the WinPAC Utility. WinPAC-5000 Series User Manual, Version Page: 48

49 Help Menu The menu commands Reset System to Default Use to Resets the system interrupt status to default. The operation used in the situation when the interrupt crash. You can select this operation to reset the interrupt status without rebooting the device. Release Notes About Checks out what s new and the know issues. Displays a dialog box with information about WinPAC Utility, including the current version and copyright information. WinPAC-5000 Series User Manual, Version Page: 49

50 Configuration Menu The menu commands Import Registry Key Use to Backs up a sub-key of registry by using a registration entry (.reg) file. How to use: Step 1: Select the Import Registry Key, then the Open dialog box will appear Step 2: On the Open dialog box, select a specific.reg file to import Warning: 1. The.reg file which should be saved by Export Registry Key. 2. It will not save automatically after import a.reg file. Export Registry Key Makes a backup of a registry sub-key How to use: Step 1: Select the Export Registry Key, then the Export Registry box will appear Step 2: Select a specific root key Step 3: Input a specific path of sub-key Step 4: Push the OK button, then the Save As dialog box will appear prompting you to WinPAC-5000 Series User Manual, Version Page: 50

51 The menu commands Use to select a location where you want to save this exported file Warning: The export operation will export all the sub-keys of the specific key which you input. Store All Registry Setting Stores all registry setting to flash from.das file which is saved by Dump All Registry Setting. How to use: Step 1: Select the Store All Registry Setting, then the Open dialog box will appear Step 2: On the Open dialog box, select a specific.das file to store Warning: 1. The.das file which should be saved by Dump All Registry Setting. 2. It will save automatically after store.das file. Dump All Registry Settings Dump all registries setting to.das file. How to use: Select the Dump All Registry Setting, then the Save As dialog box will appear prompting you to select a location where you want to save this exported file. WinPAC-5000 Series User Manual, Version Page: 51

52 Property Tabs The WinPAC Utility includes the following property tabs, all property tabs will be explained later. System Settings System Settings2 Ethernet Settings Network Settings System Information Auto Execution Multi-serial port wizard System Memory Setting WinPAC-5000 Series User Manual, Version Page: 52

53 System Settings Tab The System Settings tab provides functions to configure the task bar. The tab use to Adjust the size of the desktop Lock or Auto-Hide the taskbar How to use Select a display resolution from the Resolution list. Auto-Hide: Select the Auto Hide check box Lock: Select the Always On Top check box. Change the HTTP directory path Automatic synchronization of system time Enter a new path in the Change HTTP document root directory \windows\www\wwwpub to field, and then press the Setting button. Refer to the Appendix A.6 How to configure the service for automatically synchronizing with the internet time server * The battery initial voltage should be around 2.8~3.0V, when below 2.1V, the WinPAC/ViewPAC Utility will show the low power warning. When below 1.5V, the data in the RTC (real time clock) and 512KB SDRAM will be lost. Proceed to replace the PCs battery. The battery type: BR1225. WinPAC-5000 Series User Manual, Version Page: 53

54 System Settings2 Tab The System tab provides functions to set the name of the MicroSD card and the USB hard disk. The tab use to Set the name of the MicroSD card ant the USB hard disk How to use Enter the name of the MicroSD card and the USB hard disk in the relevant fields, and then press the Set button WinPAC-5000 Series User Manual, Version Page: 54

55 Ethernet Settings Tab The Ethernet Settings tab provides functions to configure either DHCP (Roaming) or manually configured (Static) network settings and to monitor the MAC address. Generally, DHCP is the default settings, but if you don t have a DHCP server, you must configure the network settings by using manual configuration. The tab use to Configure the network settings How to use Obtaining an IP address automatically from DHCP: Select the Use DHCP to get IP address option. Manually assign an IP address: Select the Assign IP address option. Monitor the MAC address See the MAC Address 1 and MAC Address 2 fields that display the physical address of LAN1 and LAN2. WinPAC-5000 Series User Manual, Version Page: 55

56 Network Settings Tab The Network Settings tab includes three tabs, FTP Setting, HTTP directory path, Users and Password and File Server Settings. The FTP settings tab provides functions to enable/disable the FTP access, enable/disable anonymous FTP access, and configure the FTP directory path. FTP Settings tab The tab use to Enable or disable the FTP access How to use Enable: Select the Enable check box in the FTP field. Disable: Select the Disable check box in the FTP field. Enable or disable anonymous FTP access Enable: Select the Enable check box in the Allow Anonymous field. WinPAC-5000 Series User Manual, Version Page: 56

57 The tab use to How to use Disable: Select the Disable check box in the Allow Anonymous field. Enable or disable anonymous FTP upload Enable: Select the Enable check box in the Allow Anonymous Upload field. Disable: Select the Disable check box in the Allow Anonymous Upload field. Change the FTP directory path FTP/Telnet authentication Enter a new path in the Change FTP default download directory field, and then press the Setting button. Refer to the Appendix A.1 WinPAC-5000 Series User Manual, Version Page: 57

58 Users and Passwords tab The tab use to Add a user account How to use Fill in the User name and Password field of your user account, press the Add button, and then press the Setting button Delete a user Choose a user name from the user account list, the user account account that you select will display in the User name and Password filed, press the Delete button, and then press the Setting button * The maximum number of the user accounts is 5. * The maximum of the string length of the user name and password fields must be less than 20 charachters. Please refer the document w2-022_how_to configure_the_file(smb)_server to use the File Server Settings tab. WinPAC-5000 Series User Manual, Version Page: 58

59 System Information Tab The System Information tab provides functions to monitor necessary system information of the WinPAC. The system information is the most important note of version control for upgrading system. Tips & Warnings The XW-board series are for upac-5000, LP-5000, and WP-5000 series. One PAC can only plug only one XW-board. The System Information tab show the module name for XW-board. WinPAC-5000 Series User Manual, Version Page: 59

60 Auto Execution Tab The Auto Execute tab provides functions to configure programs running at WinPAC startup, it allows users to configure ten execute files at most. Tips & Warnings The allowed file types are.exe and.bat, and they are executed in order of program 1, program 2, etc. The tab use to Configure programs running at startup How to use Press the Browse button to select the execute file which you want, and then press the Setting button. WinPAC-5000 Series User Manual, Version Page: 60

61 Multi-Serial Port Wizard Tab The Multi-serial port provides functions for installation of the XW-board driver. The table below shows the expansion communication modules that are compatible with the WinPAC RS-232/422/485, DI, DO Boards Model Serial Port Type Ch Wire DI DO Isolation XW506 RS wire - - XW507 RS-422/RS /2-wire XW508 RS wire XW509 RS wire XW511i RS wire Vrms XW514 RS wire For more detailed information about these support modules, please refer to WinPAC-5000 Series User Manual, Version Page: 61

62 System Memory Setting Tab The System Memory Setting tab provides functions to adjust and monitor the unused RAM. The tab use to Adjust display How to use Move the slider left to release more memory running programs or move the slider right to release more storage room, and then press the Setting button WinPAC-5000 Series User Manual, Version Page: 62

63 4. Your First Program When you learn every computer programming language you may realize that the first program to demonstrate is "Hello World", it provides a cursory introduction to the language's syntax and output. Before writing your first program, ensure that you have the necessary development tools and the corresponding WinPAC-5000 SDKs are installed on your system. WinPAC-5000 Series User Manual, Version Page: 63

64 4.1. Preparing the Development Tools WinPAC-5000 is a Windows CE-based unit. Windows CE is a mature embedded operating system which supports rapid development. Two standard development tools are list as follows which are highly integrated, with comprehensive support for developing applications of Windows CE-based WinPAC Visual Studio Visual Studio WinPAC-5000 has.net Compact Framework 2.0 installed. Visual Studio takes full advantage of the.net Compact Framework, which uses public Internet standards to enable integration with new and existing applications running on any platform. Supported languages include Visual C#, and Visual Basic.NET. Microsoft Embedded Visual C++ embedded Visual C++ embedded Visual C++ is a standalone integrated development environment (IDE) that brings a new level of productivity to Windows CE development without compromising flexibility, performance, or control. WinPAC-5000 Series User Manual, Version Page: 64

65 4.2. Installing WinPAC-5000 SDK The PACSDK is a Software Development Kit (SDK) that contains C header files, C libraries and documents. Step 1: Insert the CD into your CD-ROM drive Step 2: Execute the PAC270_SDK_YYYYMMDD.msi The PAC270_SDK_YYMMDD.msi can be obtained from: CD:\Napdos\wp-5000_ce50\SDK\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/sdk/ The installation program for the latest version of the WinPAC Platform SDKs can be obtained from: File name: pac270_sdk_yyyymmdd.msi yyyymmdd: Platform SDK released date Tips & Warnings The released date of the installation program SDK installation package that provides the PACSDK library must be later than or equal to 2012/10/15, such as PAC270_SDK_ msi Step 3: Follow the prompts until the installation is complete WinPAC-5000 Series User Manual, Version Page: 65

66 Understanding the PACSDK The PACSDK includes several application programming interfaces (APIs) that allows you perform various supporting tasks when developing WinPAC. Requirements The PACSDK only supports.net Compact Framework 2.0 or above. Installation Path After installing the PACSDK, a number of functions can be installed on the Host PC, and this installation puts the header files, libraries into the following public places so they are easily changed by update the PACSDK. Header files: C:\Program Files\Windows CE Tools\wce500\PAC270\Icpdas\Include\ARMV4I\ Libraries: C:\Program Files\Windows CE Tools\wce500\PAC270\Icpdas\Lib\ARMV4I\ PACSDK Reference For full usage information regarding the description, prototype and the arguments of the functions, please refer to the PAC Standard API Manual located at: For WP-5000 series CD:\Napdos\wp-5000_ce50\Document\SDK_Document\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/document/sdk_docum ent/ WinPAC-5000 Series User Manual, Version Page: 66

67 4.3. Your First Program in C# Here we will demonstrate how to create a C# program running on WinPAC-5000 with the C# development tool, which including the following topics: 1. Create a new project 2. Add WinPAC-5000 reference 3. Add the control to the form 4. Add the event handling for the control 5. Upload the application to WinPAC Execute the application on WinPAC-5000 In this tutorial, we will assume that you have installed WinPAC-5000 SDK on PC and used the Visual Studio 2005/2008 for application development. WinPAC-5000 Series User Manual, Version Page: 67

68 Creating a New Project The Visual C# project template is a composite control that you use in this example creates a new project with this user control. Step 1: Start Visual Studio 2005/2008 Visual Studio 2005/2008 Step 2: On the File menu, point to New, and then click Project WinPAC-5000 Series User Manual, Version Page: 68

69 Step 3: In the Project types pane, expand Visual C#, and then click Window CE5.0 Step 4: In the Templates pane, click Device Applications Step 5: Type a name in the Name field, and then click OK Here we will enter the name systeminfo and a different location for the project if you wish WinPAC-5000 Series User Manual, Version Page: 69

70 Adding the WinPAC-5000 Reference The WinPAC-5000 SDKs provides a complete solution to integrate with WinPAC Compatible with Visual C#, Visual Basic.net and C++. In order to use a component in your application, you must first add a reference to it. Step 1: In Solution Explorer, right-click the References node and click Add Reference on the shortcut menu The Add Reference dialog box appears. Step 2: Click the Browse tab, and then select PACNET.dll The PACNET.dll file can be obtained from: CD:\Napdos\wp-5000_ce50\SDK\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/sdk/ or CD:\Napdos\wp-8x4x_ce50\sdk\winpacnet\pacnet ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-8x4x_ce50/sdk/winpacnet/p acnet/ Step 3: Click OK to close the Add Reference dialog box WinPAC-5000 Series User Manual, Version Page: 70

71 Adding the Control to the Form You can drag various controls from the Toolbox onto the form. These controls are not really "live"; they are just images that are convenient to move around on the form into a precise location. After you add a control to your form, you can use the Properties window to set its properties, such as background color and default text. The values that you specify in the Properties window are the initial values that will be assigned to that property when the control is created at run time. Step 1: From the Toolbox, drag a Button control onto the form Step 2: Right-click the Button control, and then click Properties WinPAC-5000 Series User Manual, Version Page: 71

72 Step 3: In the Properties window, type Check the OS version, and press ENTER to set the Text property WinPAC-5000 Series User Manual, Version Page: 72

73 Adding the Event Handling to the Control You have finished the design stage of your application and are at the point when you can start adding some code to provide the program's functionality. Step 1: Double-click the button on the form The Code Editor opens with the cursor positioned in the event handler. Step 2: Inserting the following code into the header area using PACNET; Tips & Warnings The PACNET of using PACNET is case- sensitive. WinPAC-5000 Series User Manual, Version Page: 73

74 Step 3: Inserting the following code MessageBox.Show(PACNET.Sys.GetOSVersion()); MessageBox.Show(Sys.GetOSVersion()); WinPAC-5000 Series User Manual, Version Page: 74

75 Upload the Application to WinPAC-5000 WinPAC-5000 provide FTP server service, you can upload files to WinPAC-5000 or download files from a public FTP server.... Step 1: On the Build menu, click Build Solution Step 2: Open the browser and type the IP address of WinPAC-5000 WinPAC-5000 Series User Manual, Version Page: 75

76 Step 3: Upload the systeminfo.exe application and the corresponding PACNET.dll file to the WinPAC-5000 Tips & Warnings For applications programming in C# and VB.net with.net compact framework, when executing these application on the WinPAC-5000 controller, the corresponding PACNET.dll file must be in the same directory as the.exe file. WinPAC-5000 Series User Manual, Version Page: 76

77 Executing the Application on WinPAC-5000 After uploading the application to WinPAC-5000, you can just double-click it on WinPAC-5000 to execute it. WinPAC-5000 Series User Manual, Version Page: 77

78 4.4. Your First Program in VB.net Here we will demonstrate how to create a VB.net program running on WinPAC-5000 with the VB.net development tool, which including the following topics: 1. Create a new project 2. Add WinPAC-5000 reference 3. Add the control to the form 4. Add the event handling for the control 5. Upload the application to WinPAC Execute the application on WinPAC-5000 In this tutorial, we will assume that you have installed WinPAC-5000 SDK on PC and used the Visual Studio 2005/2008 for application development. WinPAC-5000 Series User Manual, Version Page: 78

79 Creating a New Project The VB.net project template is a composite control that you use in this example creates a new project with this user control. Step 1: Start Visual Studio 2005/2008 Visual Studio 2005/2008 Step 2: On the File menu, point to New, and then click Project WinPAC-5000 Series User Manual, Version Page: 79

80 Step 3: In the Project types pane, expand Visual Basic, and then click Window CE5.0 Step 4: In the Templates pane, click Device Applications Step 5: Type a name in the Name field, and then click OK Here we will enter the name systeminfo and a different location for the project if you wish WinPAC-5000 Series User Manual, Version Page: 80

81 Adding the WinPAC-5000 Reference The WinPAC-5000 SDKs provides a complete solution to integrate with WinPAC Compatible with Visual C#, Visual Basic.net and C++. In order to use a component in your application, you must first add a reference to it. Step 1: In Solution Explorer, right-click the References node and click Add Reference on the shortcut menu. The Add Reference dialog box appears. Step 2: Click the Browse tab, and then select PACNET.dll The PACNET.dll file can be obtained from: CD:\Napdos\wp-5000_ce50\SDK\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/sdk/ or CD:\Napdos\wp-8x4x_ce50\sdk\winpacnet\pacnet ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-8x4x_ce50/sdk/winpacnet/p acnet/ Step 3: Click OK to close the Add Reference dialog box WinPAC-5000 Series User Manual, Version Page: 81

82 Adding the Control to the Form You can drag various controls from the Toolbox onto the form. These controls are not really "live"; they are just images that are convenient to move around on the form into a precise location. After you add a control to your form, you can right-click the control and select Properties to set its properties, such as background color and default text. The values that you specify in the Properties window are the initial values that will be assigned to that property when the control is created at run time. Step 1: From the Toolbox, drag a Button control onto the form Step 2: Right-click the Button control, and then click Properties WinPAC-5000 Series User Manual, Version Page: 82

83 Step 3: In the Properties window, type Check the OS version, and press ENTER to set the Text property WinPAC-5000 Series User Manual, Version Page: 83

84 Adding the Event Handling to the Control You have finished the design stage of your application and are at the point when you can start adding some code to provide the program's functionality. Step 1: Double-click the button on the form The Code Editor opens with the cursor positioned in the event handler. Step 2: Inserting the following code 1. Imports PACNET 2. MessageBox.Show(PACNET.Sys.GetOSVersion()) MessageBox.Show(Sys.GetOSVersion()) 1 2 Tips & Warnings The PACNET of using PACNET is case- sensitive.. WinPAC-5000 Series User Manual, Version Page: 84

85 Upload the Application to WinPAC-5000 WinPAC-5000 provide FTP server service, you can upload files to WinPAC-5000 or download files from a public FTP server.... Step 1: On the Build menu, click Build Solution Step 2: Open the browser and type the IP address of WinPAC-5000 WinPAC-5000 Series User Manual, Version Page: 85

86 Step 3: Upload the systeminfo.exe application and the corresponding PACNET.dll file to the WinPAC-5000 Tips & Warnings For applications programming in C# and VB.net with.net framework, when executing these application on the WinPAC-5000 controller, the corresponding PACNET.dll file must be in the same directory as the.exe file. WinPAC-5000 Series User Manual, Version Page: 86

87 Executing the Application on WinPAC-5000 After uploading the application to WinPAC-5000, then you can just double-click it on WinPAC-5000 to execute it. WinPAC-5000 Series User Manual, Version Page: 87

88 4.5. Your First Program in embedded Visual C++ Here we will demonstrate how to create an evc++ program running on WinPAC-5000 with the evc++ development tool, which including the following topics: 1. Create a new Forms-Based project 2. Configure the platform 3. Specify the path of the WinPAC-5000 reference 4. Add the control to the form 5. Add the event handling for the control 6. Upload the application to WinPAC Execute the application on WinPAC-5000 In this tutorial, we will assume that you have installed WinPAC-5000 SDK on PC and used the embedded Visual C for application development. WinPAC-5000 Series User Manual, Version Page: 88

89 Creating a Forms-Based Project The evc++ project template is a composite control that you use in this example creates a new project with this user control. Step 1: Start embedded Visual C++ embedded Visual C++ Step 2: On the File menu, and then click New Step 3: Click the Projects tab, and then select WCE Application Step 4: Select the CPUs that WinPAC-5000 is supported on from the CPUs list box WinPAC-5000 Series User Manual, Version Page: 89

90 Tips & Warnings Ensure that Win32 (WCE ARMV4I) is selected in the CPUs list box and click OK. Step 5: Click OK to start the wizard Step 6: On the first page of the wizard, click Dialog based and then click Next, as shown in the following illustration WinPAC-5000 Series User Manual, Version Page: 90

91 Step 7: On the next page of the wizard, leave all the options as they are, and then click Next, as shown in the following illustration Step 8: On the next page of the wizard, click Next, as shown in the following illustration WinPAC-5000 Series User Manual, Version Page: 91

92 Step 9: On the next page of the wizard, Click Finish, as shown in the following illustration Step10: When the summary appears, click OK to complete the wizard, as shown in the following illustration WinPAC-5000 Series User Manual, Version Page: 92

93 Configuring the Platform When developing applications by using embedded Visual C++, you must configure the Platform to indicate what platform and device you intend to download the application to. Before you deploy your project, check the platform. On the Win32 [WCE ARMV4I] Debug configuration toolbar, select Win32 [WCE ARMV4I] Release, as shown in the following illustration. WinPAC-5000 Series User Manual, Version Page: 93

94 Specifying the Path of the WinPAC-5000 Reference The WinPAC-5000 SDKs provides a complete solution to integrate with WinPAC Compatible with Visual C#, Visual Basic.net and C++. In order to use a component in your application, you must first add a reference to it. Step 1: On the Tools menu, and then click Options The Options dialog box appears. WinPAC-5000 Series User Manual, Version Page: 94

95 Step 2: On the Directories tab, in the Show directories for list, select Include files Step 3: Under Directories, type the path of the heard file The specified include path of the header file is default located at: C:\Program Files\Windows CE Tools\wce500\PAC270\Icpdas\Include\ARMV4I\ Click this button to specify the path of the header file WinPAC-5000 Series User Manual, Version Page: 95

96 Step 4: In the Show directories for list, select Library files Step 5: Under Directories, type the path of the library file The specified include path of the header file is default located at: C:\Program Files\Windows CE Tools\wce500\PAC270\Icpdas\Lib\ARMV4I\ Click this button to specify the path of the Library files Step 6: On the Project menu, and then click Settings The Project Settings dialog box appears. WinPAC-5000 Series User Manual, Version Page: 96

97 Step 7: On the Link tab, type the PACSDK.lib in the Object/library module field, and then click OK WinPAC-5000 Series User Manual, Version Page: 97

98 Adding the Control to the Form You can drag various controls from the Toolbox onto the form. These controls are not really "live"; they are just images that are convenient to move around on the form into a precise location. After you add a control to your form, you can use the Properties function to set its properties, such as background color and default text. Step 1: Click Resource View in the Project Workspace pane and expand the resources tree by opening the top level folder Step 2: Open the Dialog folder and then double-click the dialog resource name IDD_SDKINFO_DIALOG The resource editor appears in the right pane. Step 3: From the Toolbox, drag a Button control onto the form WinPAC-5000 Series User Manual, Version Page: 98

99 Step 4: Right-click the Button control, and then click Properties The Push Button Properties dialog box appears. Step 5: Type Check the OS version in the Captions field, and then click WinPAC-5000 Series User Manual, Version Page: 99

100 Adding the Event Handling to the Control You have finished the design stage of your application and are at the point when you can start adding some code to provide the program's functionality. Step 1: Double-click the button on the form The Add Member Function dialog box appears. Step 2: Type the onbtncheckos in the Member function name field, and then click OK The Code Editor opens with the cursor positioned in the event handler. WinPAC-5000 Series User Manual, Version Page: 100

101 Step 3: Insert the following code char OS[32]; TCHAR buf[32]; pac_getosversion(os); pac_ansitowidestring(os, buf); MessageBox(buf,0,MB_OK); Step 4: Insert the following code into the header area #include PACSDK.h WinPAC-5000 Series User Manual, Version Page: 101

102 Upload the Application to WinPAC-5000 WinPAC-5000 provide FTP server service, you can upload files to WinPAC-5000 or download files from a public FTP server.... Step 1: On the Build menu, click Build SDKinfo.exe WinPAC-5000 Series User Manual, Version Page: 102

103 Step 2: Open the browser and type the IP address of WinPAC-5000 Step 3: Upload the systeminfo.exe application WinPAC-5000 Series User Manual, Version Page: 103

104 Executing the Application on WinPAC-5000 After uploading the application to WinPAC-5000, then you can just double-click it on WinPAC-5000 to execute it. WinPAC-5000 Series User Manual, Version Page: 104

105 5. APIs and Demo Programs There are several APIs and demo programs that have been designed for WinPAC You can examine the APIs and demo source code, which includes numerous functions and comments, to familiarize yourself with WinPAC-5000 APIs and quickly develop your own applications quickly by modifying these demo programs. WinPAC-5000 Series User Manual, Version Page: 105

106 5.1. Demo Programs with C# The following C# demos have been designed to demonstrate the various features of the WinPAC C# Demo Programs for WinPAC Standard API The table below describes the WinPAC-5000 demos that have been designed to demonstrate the standard operation features of the WinPAC System Information Interrupt Memory Access Watchdog UART Registry Micro SD System Operation WinPAC-5000 Series User Manual, Version Page: 106

107 Folder Demo Explanation system systeminfo Retrieves information about the OS version, CPU version, SDK version, etc. memoryaccess memory Shows how to read/write date values from/to EEPROM battery_backup_sram Shows how to read or write to the battery backup watchdog watchdog Displays how the watchdog operate microsd microsd_management Shows how to enables/disables Micro SD registry registry Shows how to read/write date values from/to registry uart diag Shows how to read the name of local I/O modules via UART For C# application, these demo programs can be obtained from: CD:\Napdos\wp-5000_ce50\Demo\WinPAC5000\DOTNET\C#.NET\Standard\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/demo/winpac5000/dotnet /c%23.net/standard/ WinPAC-5000 Series User Manual, Version Page: 107

108 C# Demo Programs for PAC I/O API The table below describes the WinPAC-5000 demos that have been designed to demonstrate the expansion I/O module features of the WinPAC WinPAC-5000 Series User Manual, Version Page: 108

109 Folder Demo Explanation GPIO GPIO Shows how to connect and control XW107 XW107_demo the XW-board series modules. XW506 XW507 XW509 XW511i XW304 XW310 XW310C XW506_demo XW507_demo XW509_demo XW511i_demo XW304_demo XW310_demo XW310C_demo For C# application, these demo programs can be obtained from: CD:\Napdos\wp-5000_ce50\Demo\WinPAC5000\DOTNET\C#.NET\PAC_IO\ XWBoard\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/demo/winpac5000/dotnet /c%23.net/pac_io/xwboard/ WinPAC-5000 Series User Manual, Version Page: 109

110 5.2. Demo Programs with evc++ The following evc++ demos have been designed to demonstrate the various features of the WinPAC evc++ Demo Programs for WinPAC Standard API The table below describes the WinPAC-5000 demos that have been designed to demonstrate the standard operation features of the WinPAC System Information Interrupt Memory Access Watchdog UART Registry Micro SD System Operation WinPAC-5000 Series User Manual, Version Page: 110

111 Folder Demo Explanation system systeminfo Retrieves information about the OS version, CPU version, SDK version, etc. memoryaccess memory Shows how to read/write date values from/to EEPROM battery_backup_sram Shows how to read or write to the battery backup watchdog watchdog Displays how the watchdog operate microsd microsd_management Shows how to enables/disables Micro SD registry registry Shows how to read/write date values from/to registry uart diag Shows how to read the name of local I/O modules via UART For evc application, these demo programs can be obtained from: CD:\Napdos\wp-5000_ce50\Demo\WinPAC5000\eVC\Standard\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/demo/winpac5000/evc/st andard/ WinPAC-5000 Series User Manual, Version Page: 111

112 evc++ Demo Programs for PAC I/O API The table below describes the WinPAC-5000 demos that have been designed to demonstrate the expansion I/O module features of the WinPAC WinPAC-5000 Series User Manual, Version Page: 112

113 Folder Demo Explanation GPIO GPIO Shows how to connect and control XW107 XW107_demo the XW-board series modules. XW506 XW507 XW509 XW511i XW304 XW310 XW310C XW506_demo XW507_demo XW509_demo XW511i_demo XW304_demo XW310_demo XW310C_demo For evc application, these demo programs can be obtained from: CD:\Napdos\wp-5000_ce50\Demo\WinPAC5000\eVC\PAC_IO\XWBoard\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/demo/winpac5000/evc/pa c_io/xwboard/ WinPAC-5000 Series User Manual, Version Page: 113

114 6. I/O Modules and SDK Selection This chapter describes how to select a suitable I/O expansion module and the corresponding SDK library to be used for developing programs on WinPAC-5000 series devices. Choosing a SDK Library for an I/O Module RS-485 WinPAC-5000 Series User Manual, Version Page: 114

115 RS-485 (I-7K series and M-7K series) I-7000, M-7000, RU-87Pn and high profile I-87K series modules connect to ViewPAC series devices via a twisted-pair, multi-drop, 2-wire RS-485 network. I-7K series I/O modules Module Native SDK.NET CF SDK I-7K series PACSDK.dll PACNET.dll I-7K series + I-7088(D) PACSDK_PWM.dll PACNET.dll For full details regarding I-7K series I/O modules and its demos, please refer to: bled_demo_for_7k_module.pdf M-7K series I/O modules Module Native SDK.NET CF SDK M-7K series Modbus Demo Modbus Demo For more detailed information about M-7K series modules using Modbus protocol and its demos, please refer to: RU-87Pn + I-87K series I/O modules Module Native SDK.NET CF SDK RU-87Pn + I-87K Refer to local I/O Refer to local I/O Other specified I/O modules Module Native SDK.NET CF SDK Others PACSDK.dll PACNET.dll WinPAC-5000 Series User Manual, Version Page: 115

116 Ethernet (ET-7K series) The Ethernet I/O devices available include ET-7000, I-8KE4/8 and I-8KE4/8-MTCP, and support either the DCON or the Modbus/TCP communication protocol. Module Native SDK.NET CF SDK ET-7K Modbus Demo Modbus Demo For more detailed information about ET-7K series modules using Modbus protocol and its demos, please refer to: WinPAC-5000 Series User Manual, Version Page: 116

117 7. WinPAC-5000 Updates ICP DAS will continue to add additional features to WinPAC-5000 SDK and OS in the future, so we advise you to periodically check the ICP DAS web site for the latest updates. WinPAC-5000 updates services can be divided into the following two main categories: CD: \Napdos wp-5000_ce50 os_image 1. OS updates eboot update_from_eshell update_from_file SDK 2. SDK updates IO_Modules Modbus NAPOPC_CE5 WinconSDK WinPacNet WinpacSDK WinPAC-5000 Series User Manual, Version Page: 117

118 7.1. OS Updates The updates files of OS image are located on: CD:\Napdos\wp-5000_ce50\OS_Image\ CD: \Napdos wp-5000_ce50 os_image eboot update_from_eshell update_from_file There are two ways to update the OS: 1. Update from file (Please refer to section 6.1.1) (We recommend that you use this one for more quicker and easier to update) 2. Update from Eshell (Please refer to section 6.1.2) OS_image Update_from_files Update_from_eshell Upgrade LAN1 Upgrade WinPAC-5000 Series User Manual, Version Page: 118

119 The WinPAC-5000 OS supports multi-language: 1. en - English 2. sc - Simplified Chinese 3. tc - Traditional Chinese os_image update_from_file update_from_eshell en sc tc en sc tc WinPAC-5000 Series User Manual, Version Page: 119

120 OS Updates Using Installation Package File Installation package is easier to upgrade OS image, you just copy the package file (.exe) and the corresponding AutoInit.bat file to WinPAC-5000, and then double-click installation package file to run it Upgrade Installation package file & AutoInit.bat file Step 1: Get the latest version of the installation package file and the corresponding AutoInit.bat file uploading to WinPAC-5000 The latest version of the installation package file and the corresponding AutoInit.bat file can be obtained from: CD:\Napdos\wp-5000_ce50\OS_image\update_from_file\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/os_image/update_fr om_file/ The corresponding AutoInit.bat file can be obtained from the same folder. There are several ways to upload these files to WinPAC-5000: i. Upload files via Ethernet. ii. Upload files via a USB storage device, the removable Micro SD card or FTP server WinPAC-5000 Series User Manual, Version Page: 120

121 Step 2: Run the installation package file and then click OK to make sure you receive the important notice of this procedure will ease flash memory Step 3: Select or clear the Retain the correct registry at next reboot check box to keep or remove the current registry settings at next reboot, and then click Update Now to start updating the WinPAC-5000 WinPAC-5000 Series User Manual, Version Page: 121

122 This installation procedure will perform the following tasks: i. Backup System_Disk Important Warnings Be careful, if the boot loader broken off in this step and cannot restart in safe mode, you have to send it back to us. ii. Erase flash disk iii. Install OS image iv. Set and save registry Tips & Warnings This procedure will reset the registry settings to their default settings, and all of your settings will be lost. During this time, do not turn off the WinPAC If the update is cancelled before completion, the WinPAC-5000 may become damaged and may require servicing or exchange. Besides, we recommend that you turn off all other applications before starting to upgrade the OS. WinPAC-5000 Series User Manual, Version Page: 122

123 Step 4: Configure the boot mode in normal mode, and then Click OK After completing the above-mentioned tasks, the Warning! dialog box will appear as follow, before clicking OK button, you must first turn the rotary switch to the 0 position Tips & Warnings If you have selected the Retain the correct registry at next reboot check box, after the installation has been completed, and then rebooting the WinPAC-5000 in normal mode, the Warning! dialog box will appear as follow, click OK button to reboot the WinPAC-5000 WinPAC-5000 Series User Manual, Version Page: 123

124 Step 5: Check the OS version of WinPAC-5000 Start the WinPAC Utility, and then select the System Information tab to check the current OS version. Check the OS version WinPAC-5000 Series User Manual, Version Page: 124

125 OS Updates Using Eshell via Ethernet By default, the OS updates via LAN1. Therefore, to update the OS image, make sure LAN1 is connected to the PC. LAN1 Upgrade Step 1: Get the latest version of the WinPAC-5000 OS image The latest version of the WinPAC OS image can be obtained from: CD:\Napdos\wp-5000_ce50\OS_image\update_from_Eshell\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/os_image/updat e_from_eshell/ Step 2: Run the registry clear.exe The registry clear.exe can be obtained from: CD:\Napdos\wp-5000_ce50\PC_Tools\ ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp -5000_ce50/pc_tools/ WinPAC-5000 Series User Manual, Version Page: 125

126 Step 3: Configure the boot mode in OS update mode Turn the rotary switch to 3, and then reboot the WinPAC. The Select Device dialog box appears. Step 4: Select the device which you want to update the OS image, and then click OK Select the device name which you want to update the OS image from the list. Step 5: Select the downloaded OS image file, and then click Open WinPAC-5000 Series User Manual, Version Page: 126

127 Step 6: Configure the boot mode in normal mode, and then click OK After completing the above-mentioned tasks, the Warning! dialog box will appear as follow, before clicking OK button, you must first turn the rotary switch to the 0 position Step 7: Run the WinPAC Utility Step 8: On the File menu, click Save and Reboot WinPAC-5000 Series User Manual, Version Page: 127

128 Step 9: Click Yes to reboot the WinPAC-5000 Step 10: Check the WinPAC OS version Start the WinPAC Utility, and then select the System Information tab to check the current OS version. Check the OS version WinPAC-5000 Series User Manual, Version Page: 128

129 7.2. SDK Updates The updates files of SDKs are located on: CD:\Napdos\wp-5000_ce50\SDK\ CD: \Napdos wp-5000_ce50 SDK IO_Modules Modbus NAPOPC_CE5 WinconSDK WinPacNet WinpacSDK By evc and dotnet development tools, the WinPAC SDK installation is divided into the following two parts: i. WinPAC SDK updates for dotnet (Please refer to section 6.2.1) ii. WinPAC SDK updates for embedded Visual C++ (Please refer to section 6.2.2) WinPAC-5000 Series User Manual, Version Page: 129

130 WinPAC SDK updates for C# or VB.net To determine the SDK version that is compatibly running on the WinPAC, you can read the Release Note which is located under each SDK folder, these files provides important updated information for what we fixed and added. Step 1: Get the latest version of the C# or VB.net components The latest version of the C# or VB.net components can be obtained from: ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-5000_ce50/sdk/winpacnet/ Step 2: Copy the latest version of DLL to Host PC and WinPAC The DLL files on Host PC are located at anywhere only the solution can reference it. The DLL files on WinPAC are located at the same directory as the.exe file. WinPAC-5000 Series User Manual, Version Page: 130

131 WinPAC SDK updates for evc++ To determine the SDK version that is compatibly running on the WinPAC, you can read the Release Note which is located under each SDK folder, these files provides important updated information for what we fixed and added. Step 1: Get the latest version of the evc++ components The latest version of the evc++ components can be obtained from: ftp://ftp.icpdas.com/pub/cd/winpac/napdos/wp-8x4x_ce50/sdk/winpacsdk/ Step 2: Copy the latest version of header files and libraries to Host PC The header files are located at: C:\Program Files\Windows CE Tools\wce500\PAC270\Icpdas\Include\ARMV4I\ The libraries are located at: C:\Program Files\Windows CE Tools\wce500\PAC270\Icpdas\Lib\ARMV4I\ Step 3: Copy the latest version of DLL files to WinPAC The DLL files are located at: \System_Disk\ICPDAS\System WinPAC-5000 Series User Manual, Version Page: 131

132 Appendix A. Tips-How to Here we will guide you through some very useful tips to customize your WinPAC-5000 There are more FAQ documents on ftp://ftp.icpdas.com.tw/pub/cd/winpac/napdos/wp-8x4x_ce50/document/faq/faq _index.htm. WinPAC-5000 Series User Manual, Version Page: 132

133 A.1. How to add a User Account To establish a new telnet and FTP account, please perform the following steps: Step 1: Run the WinPAC Utility Step 2: On the Login tab of the FTP Setting tab, type the user name and password, and then press Add button 2 1. Type the User name and Password WinPAC-5000 Series User Manual, Version Page: 133

134 Step 3: The user has been added to the allowed under the remote login and included in the following list, and then press setting button Step 4: Press OK to store the settings WinPAC-5000 Series User Manual, Version Page: 134

135 A.1.1. How to Use telnet to remote login the WinPAC from PC Step 1: On the PC, open a MS-DOS command prompt 2. Type cmd 3 Step 2: At the command prompt, type telnet (IP address) 1 WinPAC-5000 Series User Manual, Version Page: 135

136 Step 3: The connection has been set up, and then type the name and password Step 4: The remote login has been completed WinPAC-5000 Series User Manual, Version Page: 136

137 A.1.2. How to remove the user from the login list Step 1: Click a user from the list which you want to remove 2 1. The user will display in the field Step 2: The user will display in the field, and then press Delete to delete the user from the login list WinPAC-5000 Series User Manual, Version Page: 137

138 A.2. How to online debug WinPAC Debugging is a process that you use to find and resolve errors, or bugs, in a program. A.2.1. Debug WinPAC programs in EVC++ Step 1: On the Tools menu, click Configure Platform Manager WinPAC-5000 Series User Manual, Version Page: 138

139 Step 2: On the Windows CE Platform Manager Configuration dialog, click Properties Step 3: On the Device Properties dialog, click Configure WinPAC-5000 Series User Manual, Version Page: 139

140 Step 4: On the TCP/IP Transport Configuration dialog, select Fixed port check box, and then click the OK Step 5: On the Windows CE Platform Manager Configuration dialog, click Test WinPAC-5000 Series User Manual, Version Page: 140

141 Step 6: The Manual Server - Action dialog will appear displaying a command line, before click OK to close dialog, turn to the WinPAC controller side to do the next two-steps Step 7: On the WinPAC, select the menu, and then click Run WinPAC-5000 Series User Manual, Version Page: 141

142 Step 8: On the Run dialog, type the command which displays in step 6 and then click OK Step 9: Return to the Host PC side, and click OK on the Manual Server Action dialog WinPAC-5000 Series User Manual, Version Page: 142

143 Step 10: On the Testing Device Connection dialog, click OK Step 11: On the Device Properties dialog, click OK WinPAC-5000 Series User Manual, Version Page: 143

144 Step 12: On the Windows CE platform or device to configure dialog, click OK Step 13: On the Build menu, point to Start Debug, and then click Go WinPAC-5000 Series User Manual, Version Page: 144

145 Step 14: The Manual Server - Action dialog will appear displaying a command line, before click OK to close dialog, turn to the WinPAC controller side to do the next two-steps Step 15: On the Microsoft embedded Visual C++ dialog, click OK WinPAC-5000 Series User Manual, Version Page: 145

146 Step 16: Connection established. Then you can debug on line. Tips & Warnings If you want to quit the debugger and return to editing, you can click the Stop Debugging button from Debug menu WinPAC-5000 Series User Manual, Version Page: 146

147 A.2.2. Debug WinPAC programs in Visual Studio 2005/2008 Debugging in Visual Studio 2005/2008 are provided by WinPAC OS image V or later. Step 1: Make sure the following file are listed with the matching version numbers Path C:\Program Files\Common Files\Microsoft Shared\CoreCon\1.0\Bin File 1. ActiveSyncBootstrap.dll 2. ConMan2.dll 3. ConManPS.dll 4. DesktopDMA.dll 5. edbgtl.dll 6. TcpConnectionC.dll C:\Program Files\Common Files\Microsoft Shared\CoreCon\1.0\Bin\1033 C:\Program Files\Common Files\Microsoft Shared\CoreCon\1.0\Target\wce400\armv4i conmanui.dll 1. DeviceDMA.dll 2. edbgtl.dll 3. TcpConnectionA.dll 4. clientshutdown.exe 5. CMAccept.exe 6. ConmanClient2.exe Step 2: If the version matches correctly and the entire file are there, copy the WinPAC-5000 Series User Manual, Version Page: 147

148 following files to WinPAC:\ System_Disk\ICPDAS\System folder Clientshutdown.exe ConmanClient2.exe CMaccept.exe edbgtl.dll TcpConnectionA.dll Step 3: On the Project menu, click [Project Name] Properties WinPAC-5000 Series User Manual, Version Page: 148

149 Step 4: On the SystemInfo* tab, unselect Deploy the latest version of the.net compact Framework (including Service Packs) check box Step 5: On the Tools menu, click Options WinPAC-5000 Series User Manual, Version Page: 149

150 Step 6: On the Options dialog, select PAC 270 from the Show devices platform list, and then click Properties Step 7: On the PAC50- ARMV4:ARMV4I_Release Properties dialog, click Configure WinPAC-5000 Series User Manual, Version Page: 150

151 Step 8: On the Configure TCP/IP Transport dialog, select the Use specific IP address option and type the IP address of WinPAC, and then click OK Step 9: On the PAC50- ARMV4:ARMV4I_Release Properties dialog, click OK WinPAC-5000 Series User Manual, Version Page: 151

152 Step 10: On the Options dialog, click OK Step 11: On the WinPAC, run the CommanClient2 and the CMAccept.exe applications which is located at: \System_Disk\ICPDAS\System WinPAC-5000 Series User Manual, Version Page: 152

153 Step 12: On the Tools menu, click Connect to Device Step 13: On the Connect to Device dialog, select PAC 270 from Platform list and then click Connect WinPAC-5000 Series User Manual, Version Page: 153

154 Step 14: On the Tools menu, click Connect to Device Step 15: Connection established. Then you can debug on line FAQ: If the connection fails shown as follow, return to step 11 to do the action below WinPAC-5000 Series User Manual, Version Page: 154

155 Open the command prompt, run the CommanClient2.exe/transport:tcpconnectiona.dll/property:port=5000/id:Con at: \System_Disk\ICPDAS\System, and then run the CMAccept.exe WinPAC-5000 Series User Manual, Version Page: 155

156 A.3. How to use the printer WinPAC have ability to access the printer, you can connect to the printer via Ethernet network or USB. Tips & Warnings WinPAC only supports HP Laser Jet Printers which support PCL6 driver. The following printer support is released by HP HP LaserJet 4000 series/hp LaserJet 4100 series HP LaserJet 2100 series/hp LaserJet 2200 series HP LaserJet 1200 HP LaserJet 3200/HP LaserJet 3300 HP LaserJet 4200 series/hp LaserJet 4300 series HP LaserJet 5000 series/hp LaserJet 5100 series HP LaserJet 8000 series HP LaserJet 9000 series printers If you need the latest support of HP PCL6 printer, you can refer to following link jsp?objectid=bpl04568 WinPAC-5000 Series User Manual, Version Page: 156

157 A.3.1. How to use network printer To use a shared network printer, please perform the following steps: Step 1: On the Host PC, check the name of the Host PC and the shared printer WinPAC-5000 Series User Manual, Version Page: 157

158 Step 2: On the WinPAC, open a WordPad format file Step 3: Set up the printer 1. Printer: PCL Laser 2. Port: Network 3. Net Path: \\ServerName\PrinterName The ServerName is your PC s name or IP. The PrinterName is your printer s shared name of your PC 4. Paper Size: Select the paper size WinPAC-5000 Series User Manual, Version Page: 158

159 A.3.2. How to use printer via USB To use a shared network printer via USB, please perform the following steps: Step 1: On the WinPAC, open a WordPad format file Step 2: Set up the printer 1. Printer: Hewlett-Packard LaserJet 2. Port: LPT1 3. Paper Size: Select the paper size WinPAC-5000 Series User Manual, Version Page: 159

160 A.4. How to use services tool The services tool can help you turn on, turn off and monitor the WinCE services. Step 1: Open a MS-DOS command prompt Type cmd WinPAC-5000 Series User Manual, Version Page: 160

161 Step 2: List all services [Syntax] services list Step 3: Type the commands to configure service [Syntax] services stop <services name> For example, turn on the FTP service: services stop FTP0: WinPAC-5000 Series User Manual, Version Page: 161

162 Tips & Warnings For more information about using services tool, you just type services help WinPAC-5000 Series User Manual, Version Page: 162

163 A.5. How to use ActiveSync through USB port ActiveSync helps you to synchronize the files on your host PC with the WinPAC. Step 1: On the PC, install the Microsoft ActiveSync software The Microsoft Active Sync software can be obtained from Microsoft website. Step 2: Run the Microsoft ActiveSync You can run Microsoft Active Sync from the Start menu WinPAC-5000 Series User Manual, Version Page: 163

164 Step 3: On the File menu, click Connection Settings Step 4: Make sure the Allow USB connections are selected, and then click Connect WinPAC-5000 Series User Manual, Version Page: 164

165 Step 5: Click Next to get connected Step 6: Wait a while until the connection is established After the connection is established, the color of the ActiveSync icon will change to green. Disconnected Black & Write Connected - Green WinPAC-5000 Series User Manual, Version Page: 165

166 Step 7: Click Yes, and then click Next to set up a partnership Step 8: Select the type of information you want to synchronize, and then click Settings WinPAC-5000 Series User Manual, Version Page: 166

167 Step 9: Click Finish to complete the setup Step 10: Click Sync to synchronize the information WinPAC-5000 Series User Manual, Version Page: 167

168 Example: Synchronize a file between the PC and WinPAC-5000 Step 1: Follow the above-mentioned procedures to synchronize a file folder, and then double-click the Files Step 2: Under the Synchronized files, click Add to select the synchronized files or add the file to the synchronization folder, and then click OK The path of the synchronization folder. WinPAC-5000 Series User Manual, Version Page: 168

169 Step 3: Check the synchronization status After clicking OK, the synchronization will be performed. The synchronization folder on PC The synchronization folder on WinPAC-5000 WinPAC-5000 Series User Manual, Version Page: 169

170 A.6. How to automatically synchronize the WinPAC clock with an Internet Time Server Step 1: Run the WinPAC Utility Step 2: On the System Settings tab, press Configure WinPAC-5000 Series User Manual, Version Page: 170

171 Step 3: Select the domain name in the Server drop down list, and then enter a value in the Autoupdate Frequency field Step 4: Check the Automatically synchronize with an internet time server check box Step 5: On the File menu, click Save and Reboot Step 6: The WinPAC will automatically synchronize with an internet time server regularly Step 7: Press Update Now to synchronize WinPAC clock immediately. WinPAC-5000 Series User Manual, Version Page: 171

WinPAC-8000 User Manual (Standard series solution)

WinPAC-8000 User Manual (Standard series solution) WinPAC-8000 User Manual (Standard series solution) Version 2.0.2, April 2010 Service and usage information for Model: WP-8131 Model: WP-8431 Model: WP-8831 Model: WP-8141 Model: WP-8441 Model: WP-8841

More information

VP-23W1 VP-25W1 VP-4131

VP-23W1 VP-25W1 VP-4131 ViewPAC (WinCE-Based) User Manual Version 1.0.13, July 2017 Service and usage information for VP-23W1 VP-25W1 VP-4131 Written by Sean Edited by Anna Huang Warranty All products manufactured by ICP DAS

More information

VP-23W1/VP-25W1 User Manual

VP-23W1/VP-25W1 User Manual VP-23W1/VP-25W1 User Manual Version 1.01 beta1, June 2009 Service and usage information for VP-23W1 VP-25W1 ---------------------------------- Written by Hans Chen Edited by Anna Huang ViewPAC-23W1/ViewPAC-25W1

More information

8.2. WinPAC-5000 Series

8.2. WinPAC-5000 Series WinPAC-5000 Series.. WinPAC-5000 Series Overview The WP-5000 series is equipped an ARM CPU and running a windows CE.NET 5.0/7.0 operating system. Compared to μpac-5000, WP-5141 series has a VGA port to

More information

XP-8000-CE6 Series User Manual

XP-8000-CE6 Series User Manual XP-8000-CE6 Series User Manual (for WinCE 6.0 Based XPAC) V1.0.1, March 2017 XP-8x31-CE6/XP-8x41-CE6/XP-8x41-Atom-CE6 Written by Sean Hsu Edited by Anna Huang Warranty All products manufactured by ICP

More information

VP-x231-CE7 Series User Manual

VP-x231-CE7 Series User Manual VP-x231-CE7 Series User Manual Version 1.0.1 May 2016 Service and usage information for VP-1231-CE7/VP-4231-CE7/VP-6231-CE7 Written by Tunglu Yu Edited by Anna Huang Warranty All products manufactured

More information

2.4. LinPAC-8000 Series

2.4. LinPAC-8000 Series .. LinPAC-000 Overview Compared with the first generation LinCon-000, not only is the CPU performance improved have been added (from 0 MHz to 0 or 00 MHz) and uses an upgraded OS from Linux kernel. to

More information

WinPAC 8000 User Manual

WinPAC 8000 User Manual WinPAC 8000 User Manual Version 1.0 beta, May 2008 Service and usage information for WP-8041 WP-8441 WP-8141 WP-8841 Written by Hans Chen Edited by Anna Huang WinPAC 8000 User Manual, Version 1.0 beta,

More information

InduSoft PAC Quick Start. Version 1.0.0, 2016/05/06

InduSoft PAC Quick Start. Version 1.0.0, 2016/05/06 InduSoft PAC Quick Start Version 1.0.0, 2016/05/06 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, beginning from the date of delivery

More information

I-8KE4-MTCP I-8KE8-MTCP ET-7000 ET-7000 NS-205. RU-87Pn I-7000 M CAN/CANopen Devices I-7530 I-8KE4-MTCP NS-205 M-7000.

I-8KE4-MTCP I-8KE8-MTCP ET-7000 ET-7000 NS-205. RU-87Pn I-7000 M CAN/CANopen Devices I-7530 I-8KE4-MTCP NS-205 M-7000. Programmable Automation Controller Products Highlight Information Runtime InduSoft Web Studio Inside ISaGRAF Ver. SoftLogic Inside (IEC 6111-) VP-2W6 VP-25W6 PXA270 CPU (2-bit & 520 MHz) 12 MB SDRAM &

More information

IWS-2201-CE7 IWS-3201-CE7 IWS-4201-CE7

IWS-2201-CE7 IWS-3201-CE7 IWS-4201-CE7 IWSPAC-x201-CE7 Quick Start (CE7 Based IWSPAC) Version 1.0.0, March 2015 Usage information for IWS-2201-CE7 IWS-3201-CE7 IWS-4201-CE7 IWS-5201-CE7 IWS-6201-CE7 Written by Ian Chien Warranty All products

More information

UA-5000 Series User Manual

UA-5000 Series User Manual ICP DAS CO., LTD. UA-5000 Series User Manual IIoT Communication Server ICP DAS CO., LTD. All Rights Reserved. www.icpdas.com Warranty All products manufactured by ICP DAS are under warranty regarding defective

More information

XP-8346-CE6 XP-8346-CE6-PRO

XP-8346-CE6 XP-8346-CE6-PRO XP-000-CE Series Highlight Information Windows Embedded CE.0 Integrated with InduSoft Web Studio XP-0-CE XP-0-CE-PRO XP--CE XP--CE-PRO Integrated with ISaGRAF SoftLogic IIS, ASP.NET,.NET Framework. VS.NET

More information

XP-8000-CE6 User Manual, version Last Revised: February 2010 Page: 1

XP-8000-CE6 User Manual, version Last Revised: February 2010 Page: 1 XP-8000-CE6 User Manual, version 1.0.6. Last Revised: February 2010 Page: 1 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, beginning

More information

Win-GRAF ViewPAC. Features. Introduction. Windows Embedded Compact 7. Win-GRAF. Win-GRAF ViewPAC Series

Win-GRAF ViewPAC. Features. Introduction. Windows Embedded Compact 7. Win-GRAF. Win-GRAF ViewPAC Series Series VP-408-CE7 Introduction VP-08-CE7 Features 7", 10.4" TFT LCD AM5/AM54, 70 MHz/1 GHz CPU CE7 (Windows Embedded Compact 7) Embedded Win-GRAF SoftLogic (IEC 6111-) Hard Real-Time Capability PoE (Power

More information

2.2. WinPAC-8000 Series

2.2. WinPAC-8000 Series Programmable Automation Controller Products.. WinPAC-8000 Series Overview WinPAC-8000 is the new generation PAC of ICP DAS. It is equipped a PXA70 CPU (50 MHz) running a Windows CE.NET 5.0 operating system,

More information

I/O Expansion Units. 5.1 I/O Expansion Units Overview P Overview P RS-485 I/O Expansion Unit P5-2-1

I/O Expansion Units. 5.1 I/O Expansion Units Overview P Overview P RS-485 I/O Expansion Unit P5-2-1 .1 Overview P-1-1 Overview P-1-1.2 RS-48 I/O Expansion Unit P-2-1 RU-87P1/87P2/87P4/87P8 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - P-2-3.3 Ethernet I/O Expansion Unit P-3-1 ET-87P2/87P4/87P8

More information

tsh-700 Series User Manual

tsh-700 Series User Manual tsh-700 Series User Manual Tiny Serial Port Sharer Aug. 2017 Ver. 1.6 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery

More information

UA-5200 IIoT Communication Server

UA-5200 IIoT Communication Server UA-5200 Series UA-5200 IIoT Communication Server Features OPC UA Server and MQTT Client Service MQTT Broker Inside AM3354, 1 GHz 256 MB RAM and 512 MB Flash Linux kernel 3.2.14 OS Real-Time Capability

More information

TouchPAD TPD/VPD Series HMI Device User Manual

TouchPAD TPD/VPD Series HMI Device User Manual TouchPAD TPD/VPD Series HMI Device User Manual Version 1.1.0, Jul. 2015 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of

More information

I-7560U/7561U/7563U. User Manual WARRANTY WARNING COPYRIGHT TRADEMARKS CONTACT US

I-7560U/7561U/7563U. User Manual WARRANTY WARNING COPYRIGHT TRADEMARKS CONTACT US I-7560U/7561U/7563U User Manual USB tto RS--232//422//485 Converrtterrss Verr.. 1..0,, Decc.. 2013 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of

More information

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0. ECAN-240 (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.0 Page: 1 Table of Contents Table of Contents -----------------------------------------------------------------------------2

More information

5.3. Ethernet I/O Expansion Unit

5.3. Ethernet I/O Expansion Unit .. Introduction The ET-87Pn series remote I/O expansion unit is designed to acquire and control remote I/O through connections. It comprises A CPU module with none-volatile memory to backup/restore I/O

More information

DL-10. User Manual. RS-485 Remote Temperature and Humidity. English Ver. 1.0, Jul. 2017

DL-10. User Manual. RS-485 Remote Temperature and Humidity. English Ver. 1.0, Jul. 2017 DL-10 User Manual RS-485 Remote Temperature and Humidity English Ver. 1.0, Jul. 2017 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from

More information

TPM-4100/TP-4100/TP-2070/ TP-3080/TP-5120/TP-6150/ TP-7170 Touch Panel Monitor User Manual

TPM-4100/TP-4100/TP-2070/ TP-3080/TP-5120/TP-6150/ TP-7170 Touch Panel Monitor User Manual TPM-4100/TP-4100/TP-2070/ TP-3080/TP-5120/TP-6150/ TP-7170 Touch Panel Monitor User Manual Touch Panel Monitor User Manual, version 1.1.0, Last Revised: December 2015 Page: 1 Warranty All products manufactured

More information

WinCon Programmable Automation. Controller

WinCon Programmable Automation. Controller Programmable Automation WinCon- Controller Introduction The WinCon- is a leading edge embedded platform with Intel Strong ARM CPU running the Windows CE.NET operating system. When compared to the standard

More information

Win-GRAF ViewPAC VP-1238-CE7. Features. Introduction. Windows Embedded Compact 7. Win-GRAF 5.7" TFT LCD. Win-GRAF ViewPAC Series 5.

Win-GRAF ViewPAC VP-1238-CE7. Features. Introduction. Windows Embedded Compact 7. Win-GRAF 5.7 TFT LCD. Win-GRAF ViewPAC Series 5. Series Introduction 5.7" TFT LCD VP-18-CE7 Features 5.7" TFT LCD Cortex-A8 CPU (-bit & 1 GHz) Windows CE.NET 7.0 Inside Embedded Win-GRAF SoftLogic (IEC 6111-) Hard Real-Time Capability Slots for High

More information

Win-GRAF ViewPAC VP-4238-CE7 VP-6238-CE7 VP-1238-CE7. Features. Introduction. Windows Embedded Compact 7. Win-GRAF. Win-GRAF ViewPAC Series

Win-GRAF ViewPAC VP-4238-CE7 VP-6238-CE7 VP-1238-CE7. Features. Introduction. Windows Embedded Compact 7. Win-GRAF. Win-GRAF ViewPAC Series Series VP-18-CE7 Introduction VP-48-CE7 VP-68-CE7 Features 5.7"/10.4"/15" TFT LCD Cortex-A8 CPU (-bit & 1 GHz) Windows CE.NET 7.0 Inside Embedded Win-GRAF SoftLogic (IEC 6111-) Hard Real-Time Capability

More information

2.2. XP-8000 Series. Overview. XP-8000 Series. Compact PAC. XP-8000 Series XP-8000 IPC+I/O Cards

2.2. XP-8000 Series. Overview. XP-8000 Series. Compact PAC. XP-8000 Series XP-8000 IPC+I/O Cards XP-000 Series.. XP-000 Series Overview XP-000 Series The XP-000 combines the functionality and openness of PC, the reliability of a programmable logic controller (PLC), and the intelligence of I/O modules.

More information

DCON Utility Pro User s Manual Version 1.1, May 2015

DCON Utility Pro User s Manual Version 1.1, May 2015 DCON Utility Pro User s Manual Version 1.1, May 2015 Written by Martin Hsu Edited by Hans Chen Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period

More information

(XP-8048-CE6/XP-8348-CE6/XP-8748-CE6)

(XP-8048-CE6/XP-8348-CE6/XP-8748-CE6) Win-GRAF XPAC-8000-CE6 Series XP-8048-CE6 XP-8348-CE6 XP-8748-CE6 Features LX800, 500 MHz CPU Windows CE 6.0 R3 Core Embedded Win-GRAF SoftLogic (IEC 63-3) Hard Real-Time Capability VGA Port Output Modbus

More information

256 MB RAM. 256 MB 32 bits RISC Cortex-A8 600MHz SD Card Slot. N/A USB Host. N/A USB Client

256 MB RAM. 256 MB 32 bits RISC Cortex-A8 600MHz SD Card Slot. N/A USB Host. N/A USB Client User Manual V1.0.0 Table of Contents Overview... 1 1.1. Specification... 1 1.2. Dimensions... 2 1.3. Connector pinouts... 3 1.4. Restoring factory default... 3 1.5. LED indicator... 3 1.6. CR1225 battery...

More information

EZ Touchscreen CE Computer. User Manual

EZ Touchscreen CE Computer. User Manual EZ Touchscreen CE Computer User Manual Page 1 of 27 7/22/2005 Using EZ Touchscreen CE Computer The EZ Touchscreen CE Computer (or EZ-CE for short) can be used by any one who is familiar with using of Windows

More information

Arm-based DIN-rail industrial computers with 4 serial ports, 2 LAN ports, 8 DI/DO, and VGA. Features and Benefits. Certifications

Arm-based DIN-rail industrial computers with 4 serial ports, 2 LAN ports, 8 DI/DO, and VGA. Features and Benefits. Certifications IA260 Series Arm-based DIN-rail industrial computers with 4 serial ports, 2 LAN ports, 8 DI/DO, and VGA Features and Benefits Cirrus Logic EP9315 Arm9 CPU, 200 MHz 128 MB RAM onboard, 32 MB flash disk

More information

Warranty. Warning. Copyright. Contact Us

Warranty. Warning. Copyright. Contact Us M-6026U-32 16-channel Universal Input and 16-channel Universal Output Version: 1.0.0 Date: Dec. 2017 Edited by Horse Chien M-6026U-32 User Manual Version 1.0.0 Dec. 2017-1 - Warranty All products manufactured

More information

NetBiter Serial Server User Manual

NetBiter Serial Server User Manual User Manual IntelliCom Innovation AB Linjegatan 3D SE-302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 17 29 09 email info@intellicom.se web www.intellicom.se Revision List Revision Date Author

More information

WP-8137 WP-8437 WP-8837 WP-8847 WP-8757

WP-8137 WP-8437 WP-8837 WP-8847 WP-8757 WP-8137 WP-8437 WP-8837 Features PXA70, 50 MHz CPU Windows CE 5.0 ISaGRAF Ver.3 SoftLogic Inside (IEC 61131-3) Hard Real-Time Capability VGA Port Output Modbus RTU/TCP (Master, Slave) Support Soft-GRAF

More information

Matrix-605 WinCE ARM9 Industry Box Computer User Guide

Matrix-605 WinCE ARM9 Industry Box Computer User Guide Matrix-605 WinCE ARM9 Industry Box Computer User Guide Version 1.1 Copyright Artila Electronics Co., Ltd. All Rights Reserved. Table of Contents 1. Introduction... 1 1.1 Features... 1 1.2 Packing List...

More information

UA Series IIoT Communication Server

UA Series IIoT Communication Server UA Series - IIoT Communication Server UA Series IIoT Communication Server UA-5231 UA-5231M UA-5231M-3GWA UA-5231M-4GE UA-5231M-4GC Features OPC UA Server MQTT Client Service MQTT Broker Inside ARM CPU,

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

XP 8X4X-Atom CE6 OS Release Note, Version [Mar., 18, 2011]

XP 8X4X-Atom CE6 OS Release Note, Version [Mar., 18, 2011] XP 8X4X-Atom CE6 OS Release Note, Version 1.0.0.0 [Mar., 18, 2011] OS Key Features: Features Supported Description Language of OS Windows CE 6.0 Multi-language edition English German Russian French Spanish

More information

VP-4147 VP IT and Instrumentation for industry. Features. Introduction. ISaGRAF Features

VP-4147 VP IT and Instrumentation for industry. Features. Introduction. ISaGRAF Features -000/4000/5000 Series ISaGRAF Based WinCE VP-W7 VP-5W7 Features PXA70, 50 MHz CPU Windows CE 5.0 ISaGRAF Ver. SoftLogic Inside (IEC 6111-) Hard Real-Time Capability I/O Slots IP65 Compliant Front Panel.5

More information

2.5. ipac-8000 Series

2.5. ipac-8000 Series .. Overview of connecting I/O either through its own dual backplane bus or alternatively through remote I/O units and remote I/O modules. The unit comprises a main control unit with a range of standard

More information

User Manual. cmt-svr Startup Guide

User Manual. cmt-svr Startup Guide User Manual cmt-svr Startup Guide Table of Contents Chapter 1 Overview... 1 1.1 Specification... 1 1.2 Dimensions... 2 1.3 Connector pin designations... 3 1.4 USB host port and SD card slot... 3 1.5 Ethernet

More information

(XP-8137-CE6/XP-8337-CE6/XP-8737-CE6)

(XP-8137-CE6/XP-8337-CE6/XP-8737-CE6) XP-837-CE6 Features x86 CPU,.0 GHz, dual-core Windows CE 6.0 Embedded ISaGRAF Ver.3 SoftLogic (IEC 63-3) Hard Real-Time Capability VGA Port Output Modbus RTU/TCP (Master, Slave) Support elogger Support

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

Serial to Ethernet Converter

Serial to Ethernet Converter Serial to Ethernet Converter User s Manual Version 1.1 2004 Infosystem Technology Corporation Disclaimers The information in this manual has been carefully checked and is believed to be accurate. Infosystem

More information

ZigBee Converter User s Manual

ZigBee Converter User s Manual ZigBee Converter User s Manual Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser. Warning

More information

Lantech LSC-1102B SERIAL TO TCPIP CONVERTER. User Manual

Lantech LSC-1102B SERIAL TO TCPIP CONVERTER. User Manual Lantech LSC-1102B SERIAL TO TCPIP CONVERTER User Manual V1.0 Sep 2016 Table of Contents 1. Introduction 3 Overview 4 Product Specifications 8 2. Description & Installation 10 Product Panel Views 10 LED

More information

USB Keyboard Mouse. VGA Compact Flash

USB Keyboard Mouse. VGA Compact Flash Compact Embedded Controller RISC CPU 206MHz EEPROM/Flash/SDRAM Real-Time Clock Watchdog Timer Hardware Unique S/N Reset Key USB Keyboard Mouse Parallel Bus I/O Expansion Slot LED Indicator FRnet(Option)

More information

Wireless Network Video Recorder

Wireless Network Video Recorder LD2R/LD2R500 Wireless Network Video Recorder User Guide Version 1.0 PREFACE Thank you for purchasing the Wireless Network Video Recorder, an IP based device that installed on your network, which can be

More information

ViewPAC ViewPAC Overview P3-1-1

ViewPAC ViewPAC Overview P3-1-1 .1. Overview P-1-1 Overview - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - P-1-1 Features - - - - - - - - - - - - - - - - - - - - - - -

More information

2.1. XP-8000 and XP-8000-Atom Series

2.1. XP-8000 and XP-8000-Atom Series XP-8000, XP-8000-CE6, XP-8000-Atom and XP-8000-Atom-CE6 Series.. XP-8000 and XP-8000-Atom Series Overview Standard 009 The XP-8000-Atom combines the functionality and openness of PC, the reliability of

More information

8S RS232/422/485 Combo to USB2.0 Module Box Installation Guide

8S RS232/422/485 Combo to USB2.0 Module Box Installation Guide Installation Guide Congratulation on your purchasing this high performance 8-port RS232/422/485 Combo to USB2.0 Module Box. The product includes a metal module box and a USB cable. Each box has an upstream

More information

RS-485 Products. ICP Electronics Australia Pty Ltd Communication Cards for PC/IPC P 2-1

RS-485 Products. ICP Electronics Australia Pty Ltd Communication Cards for PC/IPC P 2-1 2.1 Communication Cards for PC/IPC P 2-1 2.2 Communication Modules for PAC P 2-2 2.3 Converter/Repeater/Hub/Splitter P 2-3 2.4 Termination Resistor/DC Bias Voltage P 2-5 2.5 I/O Modules P 2-6 2.6 I/O Units

More information

WP-8847 WP-8447 WP-8147

WP-8847 WP-8447 WP-8147 WinPAC-8x47 Series WinCE 5.0 ISaGRAF PAC ISaGRAF Ver.3 SoftLogic Inside Support IEC 61131-3 Standard Windows CE 5.0 Inside.NET Compact Framework 2.0 Support Microsoft Visual Basic.NET 2003/2005/2008, Visual

More information

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

WP 5000 CE 5.0 OS Release Notes

WP 5000 CE 5.0 OS Release Notes WP 5000 CE 5.0 OS 1.3.2.0 Release Notes Release Date: 03/10/2014 Key Features: Features Windows CE 5.0 Core OS Supported Description Yes OS Language Yes WP-5000-EN: Multi-language - English - German -

More information

EX-6014WI RS232 to WiFi Wireless Adapter, w/ Mounting Kit

EX-6014WI RS232 to WiFi Wireless Adapter, w/ Mounting Kit EX-6014WI RS232 to WiFi Wireless Adapter, w/ Mounting Kit Thank you for purchasing this RS232 to WiFi Wireless Adapter (hereinafter referred to as WiFi-Adapter ), it is designed to communicate with RS232

More information

Matrix-710. Linux-Ready Cortex-A5 Industry IoT Gateway. Hardware Guide. Version: Nov.

Matrix-710. Linux-Ready Cortex-A5 Industry IoT Gateway. Hardware Guide. Version: Nov. Matrix-710 Linux-Ready Cortex-A5 Industry IoT Gateway Hardware Guide Version: 1.01 2017 Nov. Copyright Artila Electronics Co., Ltd. All Rights Reserved Trademarks The Artila logo is a registered trademark

More information

**Please contact your local agent to get a legal license to upgrade: W-8031/8331/8731 to W- 8037/8337/8737 or W-8039/8339/8739 to W-8036/8336/8736 **

**Please contact your local agent to get a legal license to upgrade: W-8031/8331/8731 to W- 8037/8337/8737 or W-8039/8339/8739 to W-8036/8336/8736 ** Upgrading Your WinCON s ISaGRAF Driver This manual outlines the steps to install & upgrade your WinCON s drivers. (8037/8337/8737 & W-8036/8336/8736) **Please contact your local agent to get a legal license

More information

XP-8147-Atom-CE6. XP-8347-Atom-CE6. XP-8747-Atom-CE6

XP-8147-Atom-CE6. XP-8347-Atom-CE6. XP-8747-Atom-CE6 Features XP-8x47-CE6: LX800, 500 MHz CPU XP-8x47-Atom-CE6: Atom Z50,. GHz CPU Windows CE 6.0 R3 Core XP-8047-CE6 XP-847-Atom-CE6 Embedded ISaGRAF Ver.3 SoftLogic (IEC 63-3) Hard Real-Time Capability VGA

More information

FR-2057iT. 16-channel Sink Type Isolated Output Module With Isolated Communication line. User Manual

FR-2057iT. 16-channel Sink Type Isolated Output Module With Isolated Communication line. User Manual FR-2057iT 16-channel Sink Type Isolated Output Module With Isolated Communication line User Manual Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of

More information

I/O Expansion Units I/O Expansion Units Overview P RS-485 I/O Expansion Unit P Modbus TCP I/O Expansion Unit P6-3-1

I/O Expansion Units I/O Expansion Units Overview P RS-485 I/O Expansion Unit P Modbus TCP I/O Expansion Unit P6-3-1 .1. Overview P-1-1.2. RS-485 I/O Expansion Unit P-2-1 RU-87P1/87P2/87P4/87P8 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - P-2-2.3. Modbus TCP I/O Expansion Unit P-3-1 ip-8441-mtcp/ip-8841-mtcp

More information

VirtualSCADA VSU-485G USB to RS422/485 Isolated Converter User Manual

VirtualSCADA VSU-485G USB to RS422/485 Isolated Converter User Manual VirtualSCADA USB to RS422/485 Isolated Converter User Manual Revision 1.01.00 Page 1 (15) Table of contents Warranty and support... 3 Product return... 3 1 About the VirtualSCADA USB to RS422/485 Converter...

More information

3.1 Updating Web Package Updating OS... 16

3.1 Updating Web Package Updating OS... 16 User Manual V1.0.0 Table of Contents Chapter1. Overview... 1 1.1. Specification... 1 1.2. Dimensions... 2 1.3. Connector pin designations... 4 1.4. Restoring factory default... 4 1.5. LED indicator...

More information

User Manual. cmt-svr Startup Guide

User Manual. cmt-svr Startup Guide User Manual cmt-svr Startup Guide Table of Contents Chapter 1 Overview... 1 1.1 Specification... 1 1.2 Dimensions... 2 1.3 Connector pin designations... 3 1.4 USB host port and SD card slot... 3 1.5 Ethernet

More information

Industrial Tri-band 3G Modem GTM-201-3GWA Series. User Manual

Industrial Tri-band 3G Modem GTM-201-3GWA Series. User Manual Industrial Tri-band 3G Modem GTM-201-3GWA Series User Manual Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to

More information

Industrial Quad-band GPRS/GSM Modem GTM-201 Series. User Manual

Industrial Quad-band GPRS/GSM Modem GTM-201 Series. User Manual Industrial Quad-band GPRS/GSM Modem GTM-201 Series User Manual Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery

More information

Internet Camera Quick Installation Guide

Internet Camera Quick Installation Guide Internet Camera Quick Installation Guide Rev. 01 (Dec, 2001) Q20011203 Printed In Taiwan Table of Content INTRODUCTION...2 SYSTEM REQUIREMENT...3 INTERNET CAMERA... 3 Network:...3 Recommended PC or Notebook

More information

KinCon-8000 QUICK START GUIDE (Version 1.03)

KinCon-8000 QUICK START GUIDE (Version 1.03) KinCon-8000 QUICK START GUIDE (Version 1.03) Warranty All products manufactured by ICPDAS Inc. are warranted against defective materials for a period of one year from the date of delivery to the original

More information

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2 NET101 RS232 / RS422 / RS485 to Ethernet Converter User s Manual Version 1.2 Copyright Information Copyright 2004-2005, Mega System Technologies, Inc. All rights reserved. Reproduction without permission

More information

ABLELink. Modbus Gateway MB5000 Series User s Manual

ABLELink. Modbus Gateway MB5000 Series User s Manual ABLELink MB5000 Series User s Manual Version 1.1 Updated in March, 2010 TEL: 886-3-5508137 FAX: 886-3-5508131 http://www.atop.com.tw Table of Contents Table of Contents... 2 Introduction... 4 Features...

More information

GTM-204M-4G Industrial 4G LTE Modem User s Manual V1.0 High Quality, Industrial Data Acquisition, and Control Products

GTM-204M-4G Industrial 4G LTE Modem User s Manual V1.0 High Quality, Industrial Data Acquisition, and Control Products GTM-204M-4G Industrial 4G LTE Modem User s Manual V1.0 High Quality, Industrial Data Acquisition, and Control Products Warranty All products manufactured by ICP DAS are warranted against defective materials

More information

DCON Utility User s Manual Version 1.1, April 2006

DCON Utility User s Manual Version 1.1, April 2006 DCON Utility User s Manual Version 1.1, April 2006 ICP DAS, Co., LTD www.icpdas.com DCON Utility User s manual, April 2006, Version 1.1 ----- 1 Table of Contents Chapter1. Introduction...3 Chapter2. The

More information

Industrial 2-port RS422/485 Modbus Gateway

Industrial 2-port RS422/485 Modbus Gateway 2-port RS422/485 Serial Interface Two RS422/485 ports with 5-contact terminal block Cost effective for RS422/ to Fast Ethernet 10/100BASE- TX application Supports 4-wire RS422 or 2-wire with 5-contact

More information

Features. :. Introduction. :. Leader 5000 Appearance. Ethernet-Based Block I/O System

Features. :. Introduction. :. Leader 5000 Appearance. Ethernet-Based Block I/O System Features 10/100Mbps Ethernet full duplex Auto Negotiation Support C++/C Modbus/TCP drivers and OPC server Support configuration via built-in Web browsing, (HTML), Device Finder and I/O configuration utilities

More information

Product Manual. USB BAY-4 Port Serial DB- 9 RS-232 Adapter with FTDI Chipset. Coolgear, Inc. Version 1.1 September 2017 Model Number: USBG-BAY4

Product Manual. USB BAY-4 Port Serial DB- 9 RS-232 Adapter with FTDI Chipset. Coolgear, Inc. Version 1.1 September 2017 Model Number: USBG-BAY4 USB BAY-4 Port Serial DB- 9 RS-232 Adapter with FTDI Chipset Product Manual Coolgear, Inc. Version 1.1 September 2017 Model Number: USBG-BAY4 2 USBG-BAY4 Product Manual Revision History Revision Date Author

More information

SST-2450 Wireless Modem User s Manual

SST-2450 Wireless Modem User s Manual SST-2450 Wireless Modem User s Manual Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser.

More information

I-7570 Serial To HART Converter

I-7570 Serial To HART Converter I-7570 Serial To HART Converter User s Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original

More information

MGate MB3000 Modbus Gateway User Manual

MGate MB3000 Modbus Gateway User Manual MGate MB3000 Modbus Gateway User Manual Sixth Edition, July 2012 www.moxa.com/product 2012 Moxa Inc. All rights reserved. MGate MB3000 Modbus Gateway User s Manual The software described in this manual

More information

ET-7X00/PET-7X00 Series User Manual

ET-7X00/PET-7X00 Series User Manual Version 1.1.2, February 2014 Industrial Computer Products Data Acquisition Systems ET-7X00/PET-7X00 Series User Manual ET-7000/ET-7200 Series (Ethernet I/O) PET-7000/PET-7200 Series (PoE I/O) Warranty

More information

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual First Edition, June 2009 www.moxa.com/product 2009 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. MGate EIP3000

More information

3.1 I-7560 Pin Assignment and Specifications: Introduction

3.1 I-7560 Pin Assignment and Specifications: Introduction 3.1 I-7560 Pin Assignment and Specifications: Introduction The I-7560 adds a Windows serial Com port via its USB connection and is compatible with new & legacy RS-232 devices. USB Plug and Play allows

More information

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

Arm-based palm-sized industrial computers with 2 serial ports and 2 LAN ports. Features and Benefits. Certifications

Arm-based palm-sized industrial computers with 2 serial ports and 2 LAN ports. Features and Benefits. Certifications UC-7100 Series Arm-based palm-sized industrial computers with 2 serial ports and 2 LAN ports Features and Benefits MOXA ART Arm9 32-bit 192 MHz processor 16 or 32 MB RAM 8 or 16 MB Flash ROM Dual or single

More information

User s Guide. Ethernet Module for Barcode Printer

User s Guide. Ethernet Module for Barcode Printer User s Guide Ethernet Module for Barcode Printer 1. ETHERNET MODULE... 2 1-1. Functions... 2 1-2. General Specifications... 2 2. ETHERNET MODULE INSTALLATION... 3 2-1. Ethernet Module Installation for

More information

3-7 Tiny Serial-to-Ethernet Device Server & Modbus Gateway

3-7 Tiny Serial-to-Ethernet Device Server & Modbus Gateway Tiny Serial-to-Ethernet Device Server & Modbus Gateway - Tiny Serial-to-Ethernet Device Server & Modbus Gateway tds-00 Series tds-12 tds-00 series tdsm-12 Tiny Serial-to-Ethernet Device Server Features

More information

WISE-52xx Intelligent IIoT Concentrator

WISE-52xx Intelligent IIoT Concentrator - Web Inside, Smart Engine Features Runs on browsers, no extra software tool is required No more programming, Web pages provided for control logic editing IF-THEN-ELSE logic rules execution ability Support

More information

i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products

i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual (Version 1.01) PAGE:1

More information

Machine TV Interface. mtv-100. Memory Processor. I/O Port RTC. Power. Specification. Certificate Software

Machine TV Interface. mtv-100. Memory Processor. I/O Port RTC. Power. Specification. Certificate Software Machine TV Interface Features HD 720p High Resolution HDMI Output One Gigabit Ethernet Port Compact Design and DIN-rail Mountable Built-in 256MB Flash Memory SD Card Slot for Extension of Storage One USB

More information

WLAN Products 2.1 Overview P WLAN Remote Maintenance Device P WLAN Converter P Applications P2-4-1

WLAN Products 2.1 Overview P WLAN Remote Maintenance Device P WLAN Converter P Applications P2-4-1 WLAN Products.1 Overview P-1-1. WLAN Remote Maintenance Device P--1.3 WLAN Converter P-3-1.4 Applications P-4-1 Overview.1. Overview WLAN Products Overview 1 WLAN (Wireless Local Area Network) links devices

More information

Related Products. Ethernet Modbus LED Display

Related Products. Ethernet Modbus LED Display Related Products. LED Display P-- Modbus LED Display P-- LED Display.. LED Display Related Products LED Display Introduction Display Message Easily EKAN-MD04 Modbus LED Display EKAN-MD04 Modbus LED Display

More information

Matrix-700 Linux-Ready Cortex-A5 Industry IoT Gateway Hardware Guide

Matrix-700 Linux-Ready Cortex-A5 Industry IoT Gateway Hardware Guide Matrix-700 Linux-Ready Cortex-A5 Industry IoT Gateway Hardware Guide Version: 1.12 2018 Jan. Copyright Artila Electronics Co., Ltd. All Rights Reserved. Matrix-700 Hardware Guide Trademarks The Artila

More information

User Manual A08. User Manual

User Manual A08. User Manual A08 TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 2 1.1. Key Features... 3 1.2. OS Requirement... 4 1.3. Specification... 4 1.4. Packing List... 4 2. OVERVIEW... 5 2.1. LED Definition...

More information

MGate MB3000 Modbus Gateway User s Manual

MGate MB3000 Modbus Gateway User s Manual User s Manual Seventh Edition, May 2013 www.moxa.com/product 2013 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

TOUCH CONTROLLER CUWIN

TOUCH CONTROLLER CUWIN TOUCH CONTROLLER CUWIN User Manual 1 1.0 Introduction The CUWIN combines a graphic display and touch interface with a high efficiency industrial controller. It is equipped with Microsoft Windows CE 5.0

More information

WISE I/O Modules Overview P10-1-1

WISE I/O Modules Overview P10-1-1 .1. Overview P-1-1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Application Stories - - - - - - - - - - - - - - - - - - - - - -

More information

VP-23Wx-SC: Simplified Chinese VP-23Wx-TC: Traditional Chinese.NET Compact Framework 2.0.NET Compact Framework 3.5

VP-23Wx-SC: Simplified Chinese VP-23Wx-TC: Traditional Chinese.NET Compact Framework 2.0.NET Compact Framework 3.5 VP-23Wx OS 2.4.3.0 Release Notes Release Date: 09/18/2014 Key Features: Features Supported Description OS Language Yes VP-23Wx-EN: Multi-language including : - English - German - Russian - French - Spanish

More information

USER MANUAL FOR GS100/GS1003G

USER MANUAL FOR GS100/GS1003G USER MANUAL FOR GS100/GS1003G 1 Table of Contents 1. INTRODUCTION... 3 2. FEATURES... 3 3. OPERATION... 3 4.CONNECTION DETAILS... 4 5.CONFIGURATION... 5 5.1 Hyper Terminal Setting... 5 5.2 GS100 Configuration...

More information