1 PI ProcessBook 2015 User Guide

2 OSIsoft, LLC 777 Davis St., Suite 250 San Leandro, CA USA Tel: (01) Fax: (01) Web: PI ProcessBook 2015 User Guide by OSIsoft, LLC. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, photocopying, recording, or otherwise, without the prior written permission of OSIsoft, LLC. OSIsoft, the OSIsoft logo and logotype, PI Analytics, PI ProcessBook, PI DataLink, ProcessPoint, PI Asset Framework (PI AF), IT Monitor, MCN Health Monitor, PI System, PI ActiveView, PI ACE, PI AlarmView, PI BatchView, PI Coresight, PI Data Services, PI Event Frames, PI Manual Logger, PI ProfileView, PI Web API, PI WebParts, ProTRAQ, RLINK, RtAnalytics, RtBaseline, RtPortal, RtPM, RtReports and RtWebParts are all trademarks of OSIsoft, LLC. All other trademarks or trade names used herein are the property of their respective owners. U.S. GOVERNMENT RIGHTS Use, duplication or disclosure by the U.S. Government is subject to restrictions set forth in the OSIsoft, LLC license agreement and as provided in DFARS , DFARS , FAR , FAR , as applicable. OSIsoft, LLC. Version: Published: 14 July 2015

3 Contents Introduction... 1 What's new in PI ProcessBook PI ProcessBook essentials... 3 What can you view with PI ProcessBook... 3 Start PI ProcessBook... 3 Servers and connections...4 Workspace...7 Run mode and Build mode...8 Add-ins... 9 Load add-ins...9 Menus and toolbars Command menus Customize toolbars...10 Toolbar buttons Browser toolbar Browse ProcessBooks and displays View browsing history...12 Set a Home Page Bookmarks and browser history...12 Keyboard shortcuts Assign a keyboard shortcut Remove a keyboard shortcut Preference settings General preferences Table of Contents preferences Display Window preferences Trend preferences...21 Trend Elements preferences Print Page Setup for printing...25 Print Preview Set up printer Change the language used for PI ProcessBook About PI ProcessBook Work with a ProcessBook Basic steps to build a ProcessBook Create a new ProcessBook Add ProcessBook entries Create a text or display entry Linked display entry...32 Linked ProcessBook entries Operating system command entry Arrange ProcessBook entries...36 Book View...37 Outline View Copy and paste an entry PI ProcessBook 2015 User Guide iii

4 Contents Remove an entry Save and close a ProcessBook Open an existing ProcessBook...43 Work with multiple ProcessBooks...43 Properties...43 Summary information in ProcessBook...44 PI ProcessBook file properties PI ProcessBook display properties Import files to a ProcessBook File sharing capability...48 Moving a ProcessBook to another PC Work with a display...49 Overview of display elements...49 Static symbols Dynamic symbols Buttons...50 OLE objects Manage displays and independent display files...50 Open a display Zoom display size Use Full Screen mode Search for a display...53 Reduce a display to an icon to save space Save a display Display Settings window...55 Display scrolling properties Status bar indicators Drawing tools Organizing symbols Drawing area Drawing grid...59 Formatting Editable formatting attributes Set font Set line color...61 Set fill color Set background color...63 Set line weight...63 Set line style Set line ends Set formatting paintbrush ToolTip Statistics window Time Range and Playback toolbar Scroll Options window...68 Scroll period Display range Time Range toolbar Revert time range Change the time range Use the scrolling time range Use time forward and back buttons...73 Set time range for future trends...74 iv PI ProcessBook 2015 User Guide

5 Contents Layers within displays...74 Create layers Assign symbols to layers Layers and composite symbols...77 Active Layers status bar Migrating displays to another PI Data Archive server AF Modeler and AF Display Builder displays...79 Disable the AF Display Builder add-in Symbols in a PI ProcessBook display Trends Create a trend...82 Edit a trend Define Trend window...87 Configure Trend Scale Trend analysis tools Change time range How trends refresh Trend appearance Ad hoc trends OpenVMS trends and graphics Add AF attributes to trends XYPlots Draw an XYPlot Linear regression by least squares Correlation coefficient Interpreting an XYPlot Zoom and Revert functions Change time range feature XYPlot cursors Bad status indicators Out of range indicators Too many points Examples of XYPlots Additional dynamic symbols Values Button Bars Multi-state symbols Create dynamic multi-state symbols Static symbols Text symbol Line symbol Rectangle, square, arc, ellipse, and circle symbols Polygon symbol Polyline symbol Graphic symbol Symbol Library Work with symbols Details and annotations Details window PI annotations maintenance PI ProcessBook 2015 User Guide v

6 Contents Data Favorites add-in Select a default symbol for data favorites Search for data favorites Favorites panel Select and move a symbol Select multiple symbols Rotate a symbol Flip a symbol Delete a symbol Stacking order Move a symbol forward or backward in the stack Align multiple symbols Connectors Connect symbols Connection points Attach a symbol to a connector Connectors window Detect connections and attachments Reroute a connector path Item Definition button Display or change item definition Status report for dynamic symbols Status flags for data Create composite symbols Group, ungroup, or regroup symbols Modify composite symbols Analyze symbols in PI Coresight AF-based symbols Connect to a PI AF database Assign symbols to AF element templates Assign symbols to AF elements Verify AF-based symbol assignment Build displays with AF-based symbols Find AF elements and attributes in displays Element Relative Display (ERD) PI System data About PI data PI tags (PI points) PI AF assets PI AF attributes Time series data Calculated data Contextual data Future data PI time PI time abbreviations PI time expressions Time-stamp specification Time-interval specification PI tags (PI points) PI Data Archive and PI ProcessBook Updates to PI data vi PI ProcessBook 2015 User Guide

7 Contents PI Tag Search window View PI point attributes PI Data Archive data types Data sets PI Calculation data sets ODBC data sets Custom data sets Placeholders Verify a data set is in use Data set details Add a data set to a trend Time intervals for plotting tags and data sets Refresh a trend containing a data set Add data sets to bars or values in a display Run PI ProcessBook when data sets are included Edit a data set Delete a data set Copy a data set to another ProcessBook Loading custom data sets Configure a symbol with an AF attribute Configure the AF ODBC ODBC Driver Manager ODBC drivers ODBC data sources ODBC data access Open ODBC Data Source Administrator Prepare for ODBC Configure the ODBC data source Use MS Query to build data sets Assumptions about time stamps and data sets Stored procedures in queries Troubleshoot ODBC data sets Trace ODBC calls Delete an ODBC driver Delete an ODBC data source Edit an ODBC data source AF elements View AF element properties Configure display settings in AF Browser Toggle panes for AF elements in PI ProcessBook PI Notifications in PI ProcessBook Start PI Notifications Notifications window in PI ProcessBook Receive notifications Filter notifications Open displays associated with a notification Work with notifications Contacts window Open Contacts window Notification Contacts panel MS Office Communicator Contacts panel PI ProcessBook 2015 User Guide vii

8 Contents Work with contacts Contacts presence Embedding and Linking Overview of Microsoft OLE compound documents OLE Automation in PI ProcessBook Embedded objects Embed in PI ProcessBook Edit the contents of an embedded object Share ProcessBook displays with other applications Linked objects Link a file to a display Dynamic and manual updates of a linked object Edit, update, or break links How links are stored Select a new source link Edit the contents of a linked object Link a ProcessBook to another application Should you link or embed? Example of embedded and linked objects in a ProcessBook display Add an Active X control Work with OLE objects Icons versus graphics Windows drag and drop Edit the appearance of an OLE object Commands that ignore OLE objects Placement of OLE objects OLE object colors Edit contents of OLE objects Delete an OLE object from a display OLE container or server Visual Basic for Applications in PI ProcessBook VBA commands ActiveX Automation What you can do with ActiveX Automation in PI ProcessBook Automation vocabulary System administrator notes Installation System requirements bit operating systems Upgrade from a previous version of PI ProcessBook Compatibility with other PI System client products Silent installation Installation test Installed files Configuration settings for high availability Recommended setting for connection preference MDB to PI AF migration Module Relative Display Add-in Considerations for multiple versions of Installing PI ProcessBook 2012 uninstalls MRD add-in. or PI ProcessBook viii PI ProcessBook 2015 User Guide

9 Contents Matrix of display behavior Migrate a Module Relative Display (MRD) to an Element Relative Display (ERD) Default settings for the Playback toolbar DEP security Read and write data access for users Machine address PROCBOOK.INI Startup section ProcessBook View section Conversion section Data Manager section Trend Definition section Colors section Time Range Scroll section ProcessBook Level section Display Colors section XYPlot Definition section View-only mode Macro protection INI security IMPPIGP.INI SETUPProcessBook.LOG Troubleshooting tips Display cannot find data Trend cursor does not appear Trend legend does not appear Cannot change or save a display Is an XYPlot updating? Is an OLE object in a display linked or embedded? Linked object data is not updating Missing ODBC trace Missing ODBC data sources Technical support and other resources PI ProcessBook 2015 User Guide ix

10 Contents x PI ProcessBook 2015 User Guide

11 Introduction PI ProcessBook is an easy-to-use graphical display interface to the PI System that enables you to: Efficiently display current and historical data residing in the PI System and other sources Create interactive graphical displays that can be saved and shared Quickly switch between view and configuration modes Create dynamic, interactive displays and populate them with live data Write scripts that automate displays and trends using Microsoft Visual Basic for Applications, which is integrated into PI ProcessBook Use OSIsoft add-ins to perform PI Batch and other analyses What's new in PI ProcessBook 2015 Support for the new tag type in PI Server 2015 that stores data values into the future. PI ProcessBook handles these tags on trends by polling for new values at regular intervals upon updating displays. Additional enhancements and bug fixes are described in the Release Notes. PI ProcessBook 2015 User Guide 1

12 Introduction 2 PI ProcessBook 2015 User Guide

13 PI ProcessBook essentials Topics in this section What can you view with PI ProcessBook Start PI ProcessBook Add-ins Menus and toolbars Browser toolbar Keyboard shortcuts Preference settings Print Change the language used for PI ProcessBook About PI ProcessBook What can you view with PI ProcessBook A PI ProcessBook display entry may contain PI System data from any or all of the following sources: PI Data Archive servers PI Asset Framework (PI AF) Servers Calculations from PI data Databases with ODBC connectivity Databases with custom interfaces to PI ProcessBook Spreadsheets, documents, schematics, graphics, photos, and other Windows applications through OLE linking and embedding VBA code ProcessBook displays may be linked to other displays within the same ProcessBook, or to displays in a separate ProcessBook. You can also include buttons that launch other applications. Start PI ProcessBook 1. Launch the application. 2. Connect to a PI Data Archive server. 3. Open a ProcessBook file or display. PI ProcessBook 2015 User Guide 3

14 PI ProcessBook essentials Topics in this section Servers and connections Workspace Run mode and Build mode Servers and connections See the PI SDK Controls and Dialogs User Help to find comprehensive and up-to-date information on connecting PI ProcessBook to a PI Data Archive server. You can access this Help from the Help menu in the Connections window (File > Connections). Topics in this section Connect to a PI Data Archive server Network errors Displays and connection failure Node identifiers for multiple PI Data Archive servers Connect to a PI Data Archive server Use the PI Connection Manager window to manage connections to PI Data Archive servers. 1. Click File > Connections. The PI Connection Manager window appears. The window lists the configured servers to which you can connect. It also shows the server you have chosen as the default server. A selected checkbox next to a server name in the Connections window indicates an open connection to the PI Data Archive server. 4 PI ProcessBook 2015 User Guide

15 PI ProcessBook essentials 2. Manage connection settings: Click to select a check box and open a connection to a PI Data Archive server in the list. Clear a check box to close a connection. Select a PI Data Archive server in the server pane to access connection settings. If you select more than one server, the application tries to connect to each server using the same user ID and password. If it fails, a new PI Server Login window appears. If you already are logged in to the server from a different PI application, such as PI DataLink, the application uses the user ID and password with which you logged in. See the PI SDK Controls and Dialogs User Help for more detail. PI Data Archive security PI ProcessBook is designed to support whatever security is configured on the PI Data Archive server. When PI ProcessBook attempts to connect to a PI Data Archive server, the application first attempts to pass your Windows login credentials. The PI SDK will try to use them directly or find a Trust for the user, domain, application or machine (per Trust configurations). If all attempts to login to the PI Data Archive server using Windows credentials or other machine-related information fail, then you must have a PI user account (not Windows security-based). In this case, the PI SDK attempts to use the default PI user account PI ProcessBook 2015 User Guide 5

16 PI ProcessBook essentials configured for the Server (you can see this in the Connections window in PI ProcessBook). See Connect to a PI Data Archive server. If the default PI user account does not require a password, then you are automatically logged in. If the default account does require a password, a login window appears, which expects the PI user account and password. For more detailed information on PI Data Archive server security see PI Data Archive Security Configuration Guide, which is available on the OSIsoft Technical Support website. As of PI Server , the server can be configured to take advantage of significantly enhanced security options. Network errors Network errors update the Status Report window, rather than displaying error messages on your monitor. When a display is opened but the server is not available, only one Select New Node window appears. The window appears once for each server that is not available. See Status report for dynamic symbols and Displays and connection failure. Displays and connection failure If the connection to your data is not successful, the display is still drawn, but data in dynamic elements are replaced with indicators signifying that no data is available. Trends are labeled Invalid and no information is plotted. Values are replaced with pound signs (###) and the message Disconnected appears. Bar graphs are drawn using hash marks (//////). Multi-State symbols show the configured color for bad data. If a server has been disconnected, and/or cannot be reached, the Select New Node window appears. Click Connections to launch the PI Connection Manager window. From there you can choose a new server from the drop-down list of connected servers. 6 PI ProcessBook 2015 User Guide

17 PI ProcessBook essentials Node identifiers for multiple PI Data Archive servers A node identifier is stored with each tag name used in a display to point to the correct server. If you define PI Data Archive server nodes in the PI Connection Manager window, the identifiers are the same on each PC on the network as long as the node names for the PI System are the same. Workspace When you start PI ProcessBook, it appears as an open window or workspace on the desktop. Depending on your settings, you may initially see an empty workspace, or an open ProcessBook in either Book View or Outline View view. Within the PI ProcessBook workspace you can open a ProcessBook or independent display. Topics in this section ProcessBook (.piw) Display Create a new ProcessBook or display ProcessBook (.piw) In PI ProcessBook a ProcessBook is the container for the information and analysis of the process you are monitoring. A ProcessBook may appear as either a tabbed book - Book View, or an outline - Outline View, and is saved as a separate file with a.piw extension. A ProcessBook is a collection of individual displays of data and analysis. Use a ProcessBook to organize data from the PI System and other sources so that you can analyze the processes you monitor or the tasks you perform. A ProcessBook and its displays are stored in a single file. Display The main unit for creating presentations of data in PI ProcessBook is the display. A display can stand on its own (.pdi or.svg), or it can be part of a ProcessBook (.piw). A display contains all the symbols used to represent an operational environment using real-time, production data from the PI System as well as data from other sources. In addition to containing this collection of data elements, the display has its own set of features and properties that affect the collection of data elements. Displays can show a variety of elements, such as a schematic representation of a production line, a plot of readings taken from a production line, or a comparison of lab data and batch specifications. Displays can also be linked to other ProcessBooks, displays in other ProcessBooks, or other applications. Create a new ProcessBook or display Use the New window to create new ProcessBook, add ProcessBook entries, or open a display. PI ProcessBook 2015 User Guide 7

18 PI ProcessBook essentials 1. Click File > New to launch the New window, See Create a new ProcessBook, Add ProcessBook entries, or Open a display Run mode and Build mode When you work with a ProcessBook or an independent display, you work in one of two operating modes, Run mode or Build mode. Build mode Most of the functions that you use when you create or modify a ProcessBook require the Build mode pointer. Use Build mode to add, remove, or move symbols on a display, to add, remove, or organize entries in a ProcessBook, and for access to symbol definitions and formatting tools. Run mode Run mode is used to open entries and execute commands after a ProcessBook is built. You can make some changes to a display while in Run mode; however, working in Run mode keeps you from accidentally making permanent changes to items in a display. You switch between modes by clicking the Run mode pointer or the Build mode pointer, which are located on the Tools menu and the Drawing toolbar. Your preferred mode of operation is set as a default in your Preference settings. You can choose Build or Run mode as your preferred mode of operation by clearing or selecting the Prefer Run Mode check box in the General preferences tab of the ProcessBook Preferences window. This is a helpful preference if you spend most of your time building or editing displays. 8 PI ProcessBook 2015 User Guide

19 PI ProcessBook essentials Add-ins By default, PI ProcessBook installs with the following add-in components. You can load or unload these and other add-in components by using the Add-In Manager. AF 2.x Data Set Browser toolbar Data Favorites add-in Details window Element Relative Display (ERD) PI Notifications in PI ProcessBook ProcessBook SVG File Converter Enables you to save displays as SVG files, which can then be used by PI WebParts. Time Range and Playback toolbar ToolTip Statistics window See Load add-ins. You can install other add-ins with PI ProcessBook, but they do not become available until you add additional applications: PI BatchView Load add-ins The Add-In Manager lists the add-ins available in your PI ProcessBook installation. Use this window to control whether the add-ins are loaded whenever you use PI ProcessBook. 1. Click Tools > Add-in Manager. The Add-In Manager window appears. 2. Click an available add-in from the Available Add-Ins list. A description of what the add-in does appears in the Description box. 3. Under Load Behavior, select the appropriate check boxes: Loaded/Unloaded Loads or unloads the selected add-in. The add-in's current status appears in the Load Behavior column at the top. Load on Startup Loads the selected add-in on startup of PI ProcessBook. The add-in's current status appears in the Load Behavior column at the top. Command Line PI ProcessBook 2015 User Guide 9

20 PI ProcessBook essentials Loads the selected add-in when PI ProcessBook is started from the command prompt or from a script. 4. Click OK to complete the action and close the window. If the add-in is unloaded and then reloaded, you must click the Revert toolbar button to re-synchronize any symbols using the add-in. Menus and toolbars Topics in this section Command menus Customize toolbars Toolbar buttons Command menus The active components of menu bars change depending on the active window and current selections. There are five different collections of menu commands. Menu Bar Default Book Display View-Only Book View-Only Display Function Displays when no documents are active Displays when a PI ProcessBook workbook is active Displays when a PI ProcessBook display document is active Displays when PI ProcessBook is running in noedit mode and a PI ProcessBook workbook is active. Displays when PI ProcessBook is running in noedit mode and a display or workbook document is active. Customize toolbars Toolbars may be displayed or omitted. 1. Click View > Toolbars. The Toolbars tab of the Customize window opens. 2. Check the toolbars you wish to display, and click OK. Click the Commands tab to see what buttons appear on each toolbar. 3. To move a toolbar, click on the double vertical bar at the left end and drag to the new location. 10 PI ProcessBook 2015 User Guide

21 If the toolbar has no move handle, click on the title bar instead. 4. To reshape a floating toolbar (one without move handles), grab one of its edges and drag to a new shape. Toolbar buttons PI ProcessBook essentials Many of the menu commands in PI ProcessBook can be selected by clicking a button on a toolbar. To determine the use of a button on a toolbar, hover the mouse pointer over the button to display a tooltip. You can configure toolbars to display as view-only to omit unnecessary buttons. View-only toolbars and others can be specified in procbook.ini. See PROCBOOK.INI for details. Add buttons to toolbars You can change the icons that appear on the toolbars or create your own custom toolbar. 1. Click View > Toolbars. 2. From the Commands tab of the Toolbars window, you can select a particular toolbar in the window and drag buttons to existing toolbars in your PI ProcessBook window. 3. While the Commands tab is open, you can also drag buttons off of a toolbar to remove them from your window. Browser toolbar The Browser add-in provides a toolbar that resembles the controls of a typical web browser. The toolbar is automatically loaded when you install PI ProcessBook, and allows you to navigate recently-used ProcessBooks and displays. Topics in this section Browse ProcessBooks and displays View browsing history Set a Home Page Bookmarks and browser history Browse ProcessBooks and displays 1. Click View > Toolbars. 2. In the Toolbars list, make sure the Browser Toolbar and Time Range and Playback Toolbar are selected. These toolbars are open by default when you first launch PI ProcessBook. PI ProcessBook 2015 User Guide 11

22 PI ProcessBook essentials 3. From the Browser toolbar, click either the Forward or Back buttons to view previously opened ProcessBooks or displays. Only displays opened during the current session of PI ProcessBook are included in this navigation. 4. You can also use the Address box to open ProcessBooks and displays. a. Click the arrow to the right of the Address box to see the last ten valid file paths you entered. The last entry in the list is Browse. b. Click Browse to launch an Open File window where you can browse for a file. You can also enter a URL to open a file. View browsing history 1. Click the small black arrow to the right of the Back or Forward buttons to see a drop-down box that lists the last ten ProcessBooks and/or displays that you visited during the current session. 2. Click an entry to return to that item. The final entry in the list is History. 3. Click History to open the History tab of the Organizer window, from where you can find an alphabetical list of all ProcessBooks and displays visited during the current session. Set a Home Page See History tab and Bookmarks and browser history for details. The Home Page is the startup file that is defined in PI ProcessBook preferences. It can be a.pdi (display),.piw (ProcessBook), or a display entry. 1. On the Browser toolbar, click the small arrow next to the Home button. 2. From the drop-down menu, select one of the following: Use Default to make PIDemo.piw your default file. Use Current to set the start file to the current, active ProcessBook or display. Bookmarks and browser history The Organizer is a docking window that allows you to organize and use bookmarks and the current session's history. By default this window is hidden. Click the Bookmarks button on the Browser toolbar to make it appear. See Browser toolbar for details. 12 PI ProcessBook 2015 User Guide

23 PI ProcessBook essentials The Organizer window has two tabs: Browser and HIstory. Topics in this section Bookmarks tab History tab Add or edit bookmarks Bookmarks tab New bookmarks are automatically added to the root level of the bookmarks tree. You can organize the entries into a hierarchical tree structure by dragging and dropping entries. Bookmarks are stored in %USERPROFILE%\AppData\Roaming\PISystem\PI-ProcessBook \OSIsoft.PB.ToolBars.Browser.Bookmarks.xml. This file is saved when PI ProcessBook is closed. Right-click the Bookmarks tab to select one of the following from the menu: New Folder inserts a new folder at the top level of the tree or as a subfolder of a selected folder. Rename makes the entry name of the selected entry editable. Edit opens a window where you can enter a new name and file path for the selected bookmark. Select All selects every entry. Deselect All clears every entry. Send To File opens a Save File window for the location to store the list of bookmarks. Bookmarks are saved as XML and can be subsequently imported. Only files or folders that are selected (checked) in the tree are exported. Send To opens a pre-populated Outlook with the selected bookmarks ready to be sent as an attachment with the same format as the Send to File option. Only files or folders that are selected (checked) in the tree are exported. PI ProcessBook 2015 User Guide 13

24 PI ProcessBook essentials The Send To options are only visible if at least one entry is checked or when rightclicking an item. Import opens an Open File window where you can select a bookmarks file to import. History tab The History tab contains an alphabetical list of all ProcessBooks and displays you have visited during the current session. From there you can click an entry to return to that item. The icon of the entry indicates its file type. Hover over an entry to see its full path in a tooltip. Add or edit bookmarks 1. On the Browser toolbar click the Bookmark button to open the Bookmark tab of the Organizer window. From there you can browse, modify, or delete stored file locations. 2. Click to add a bookmark. 3. Click to edit a bookmark. If the active file is already bookmarked, the same icon appears as the Edit Bookmark icon. Click this button to edit the bookmark's label and file path. Keyboard shortcuts A keyboard shortcut is a combination of keystrokes to use for frequent actions. Several of these are already assigned in PI ProcessBook. They appear to the right of the corresponding menu command on the drop-down menus. PI ProcessBook lets you assign new combinations of keystrokes or change existing ones. For example you can: Assign a keyboard shortcut for inserting symbols with one command. Assign more than one keyboard shortcut to a specific action. Change an existing shortcut, such as Ctrl+S, to another sequence you prefer. Topics in this section Assign a keyboard shortcut Remove a keyboard shortcut 14 PI ProcessBook 2015 User Guide

25 PI ProcessBook essentials Assign a keyboard shortcut 1. Click View > Assign Shortcuts. The Shortcut Keys window appears. 2. Under Select a macro, click the appropriate macro (menu item). The description for that item and its assigned shortcuts, if any, appears. 3. Click the Create Shortcut button. The Assign Shortcut window appears. 4. In the Press new shortcut key box, type the key you wish to use for the shortcut. 5. Click OK. If you choose a combination already in use, the current assignment appears in the window. If you click OK, the previous assignment is voided. The new shortcut appears in the Assigned shortcuts box. If you want to reset all the keyboard shortcuts to their original positions when PI ProcessBook was installed, click the Reset All button, and then the OK button. PI ProcessBook 2015 User Guide 15

26 PI ProcessBook essentials Remove a keyboard shortcut 1. In the Shortcut Keys window, under the Select a macro list, select the appropriate macro (menu item command). The description for that item and its assigned shortcuts, if any, appears. 2. Under Assigned shortcuts, select the shortcut you want to remove, and then click the Remove button. 3. Click OK. Preference settings You can reach the ProcessBook Preferences window by clicking Tools > Preferences. Preference settings determine how the ProcessBook entries look, what colors are available when you draw, and whether your ProcessBook opens in Book View or Outline View. Preference settings are stored in the file procbook.ini. Before you change the Preference settings, consider creating a back-up copy of procbook.ini so that you can restore PI ProcessBook to the original settings. Topics in this section General preferences Table of Contents preferences Display Window preferences Trend preferences Trend Elements preferences General preferences Click Tools > Preferences > General tab to configure application-wide settings. These settings are stored in and retrieved from the [STARTUP] section of your procbook.ini file. See PROCBOOK.INI for details. 16 PI ProcessBook 2015 User Guide

27 PI ProcessBook essentials Author Determines the name used as the creator of new files and the person who last edited the file. See Summary information in ProcessBook for more information. This field is blank by default when PI ProcessBook is first installed on a computer. Startup File The file name and path in this field determine which, if any, file is automatically opened when the application is launched. The default value when PI ProcessBook is first installed is <installation path>\procbook\pidemo.piw. Library File The file name and path in this field determine which, if any, file is opened when the original symbol library command is used. The default value when PI ProcessBook is first installed is <installation path>\procbook\symlibry.piw. PI ProcessBook 2015 User Guide 17

28 PI ProcessBook essentials Prefer Run Mode Determines whether ProcessBook starts up in Run mode or Build mode by default. By default, this option is enabled when PI ProcessBook is first installed on a computer. Create Backup Files Determines whether backup files (with a.bak extension) are automatically created when a PI ProcessBook file is opened. By default, this option is turned off when PI ProcessBook is first installed on a computer. Keep snapshot values on updating plots Determines whether the archive event pipe is used for updating trends, discarding any snapshot values between stored, archive values. This setting is stored as PB2TraceCompatibility in the [STARTUP] section of your procbook.ini. By default, this option is turned off when PI ProcessBook is first installed on a computer. Future Data Refresh Interval The number of seconds between retrieving future data from the PI Data Archive server. Date and Time Format Settings in this area determine how time is displayed in PI ProcessBook. Previews of each format are shown to help you select the desired option. The Use local Windows format option uses the current Regional Options settings in the Windows Control Panel on the client machine to determine how dates and times are displayed. Dates are shown using the currently configured Short Date format and Times are shown using the current time format settings. The Use PI Time Format option displays time stamps in the default PI format of dd-mmmyy HH:mm:ss.ssss, where dd is the day of the month, mmm is a the short text abbreviation of the month name (e.g., Jan for January), yy is the two digit year, HH is the hour in 24-hour format, mm is the minute and ss.sss is the second, including sub-seconds, if present. Default Time Zone Determines whether time stamps reflect the time zone of the PI Data Archive server used to retrieve data (PI Server time zone), or the time zone of the local computer (Client machine time zone), when a new display is created. By default, the PI Data Archive server option is selected when PI ProcessBook is first installed on a computer. This setting can also be changed and is stored with each display. If this setting is changed while a display is active and the client and the server are in different time zones, all absolute times (not based on now like '*-8 hours') will not be translated to the new time zone. This setting is saved with the display. Table of Contents preferences Click Tools > Preferences > Table of Contents to configure the default view of Table of Contents windows for ProcessBook(PIW) files, as well as the font applied to each level of entry in those files. These settings are stored in and retrieved from your procbook.ini file. See PROCBOOK.INI. 18 PI ProcessBook 2015 User Guide

29 PI ProcessBook essentials Default View Settings in this area determine how ProcessBook entries are displayed by default. The default is Book view. Font Settings The controls in this area determine the font settings applied to each entry level in a ProcessBook. The font settings control the display of entry names in Table of Contents windows. Preview This read-only field displays font settings for each level in a ProcessBook. Each of the 10 possible entry levels is listed and displayed with its current font name, and style settings. PI ProcessBook 2015 User Guide 19

30 PI ProcessBook essentials Display Window preferences Click Tools > Preferences > Display Window tab to set options that apply to display windows. These settings are stored in and retrieved from your procbook.ini file. See PROCBOOK.INI. Preserve Aspect Ratio on resize Determines whether display element sizes change in proportion to the window size when a window is resized. When the check box is selected, the aspect ratio is preserved and the display element sizes change in proportion to the window size. Show Symbol ToolTips Determines whether ToolTips are displayed on display symbols. ToolTips appear for toolbar buttons regardless of this setting's value. By default, this option is turned on when PI ProcessBook is first installed on a computer. 20 PI ProcessBook 2015 User Guide

31 Show Value Attributes Determines whether icons are displayed for Value Attribute flags (Questionable, Substituted or Annotated) on PI data. This option is turned on when PI ProcessBook is first installed on a computer. Run mode scrolling Determines the scroll bar behavior of display windows in Run mode. Build mode scrolling Determines the scroll bar behavior of display windows in Build mode. PI ProcessBook essentials On Off Automatic Display contains scroll bars all the time. Scroll bars never appear. Scroll bars appear when needed (this is the default setting). Color Palette These fields present the 16 colors selected for use throughout the application as the basic colors for the color well control. Use the Modify button to launch the Color window, where you can select additional colors. Use the Reset button to return the Color Palette to system default values. Default Display Background Color Determines the default color used for new displays. The color well control is used to select a color. This color is also set when the Background color of the current display is changed. Symbol Defaults Contains fields to set the default formatting values for new symbols. These defaults are also changed when the Formatting controls are used and no symbols are selected. Trend preferences Click Tools > Preferences > Trend tab to set default settings for new trend symbols. These settings also apply to instant trends. PI ProcessBook 2015 User Guide 21

32 PI ProcessBook essentials Display Check or uncheck these options to configure what information a trend displays by default. AutoScale Select this check box if you want trends to be scaled as tag values change over time. If you do not select this check box, then trends use the Database scale for each tag. Plot Title Select this check box if you want a title to display. Vert. Scale Ins. Axis(Vertical Scale Inside Axis) Select this check box to display the numeric scale inside the axis. If you do not select this check box the scale displays outside the axis. Note that the value scale is drawn horizontally when the trend orientation is vertical. Grids Select to display grid lines. See Grid lines and labels. 22 PI ProcessBook 2015 User Guide

33 PI ProcessBook essentials Multiple Scales Add a value scale for each data point when selected. When the check box is cleared, only a single value scale appears. See Single and multiple scales for the vertical axis. Markers Select the Markers check box if you want markers to indicate data points on the trend. If you do not select the Markers check box three markers display on each line. These markers help you match a line to a tag. Show All When Trend Maximized Select this check box if you want to see all legend options appear when you maximize a trend. Clear this check box if you prefer to only see traces on a maximized trend. Legend Select or clear these options to configure what information appears in the trend legends. The information that can fit in the legend is determined by the size of the trend. Consequently, not all of the information in the legend may be visible: If the width of the legend is more than the width of the trend the legend does not appear. If the height of the text in the legend is longer than the total height of the trend, items are removed in this order: engineering units, tag name, then value. Options include: Tag Name Server Name (for PI tags) Value Sample Description Eng Units Use this display area to view a preview of selected trend preferences. Trend Elements preferences Click Tools > Preferences > Trend Elements tab to set what colors, line styles, and so on are used in individual traces gridlines, text, or the background. These settings also apply to instant trends. PI ProcessBook 2015 User Guide 23

34 PI ProcessBook essentials Multi-State on Ad Hoc Select this check box to include data from multi-stated symbols when creating an ad hoc (instant) trend. When this option is cleared, data from a multi-state configuration is not included on instant trends. Traces per Ad Hoc Trend Select the number of traces to have per plot on an ad hoc (instant) trend. The default is 3, the maximum is 8. Once this number is reached, additional plots are created to show the remaining tags selected for the instant trend. Plot Elements Use the drop down list to select from pens, text, grids, and background. For each plot element, select a Marker Type, Line Style, Line Weight, and Color. 24 PI ProcessBook 2015 User Guide

35 PI ProcessBook essentials Sample You may select one of several line styles for each trace. You can also specify the line thickness. Select none to omit a grid line. See your changes previewed in the Sample area at the bottom of the window. Print When you print from a ProcessBook, you can: In Outline view, print a list of the ProcessBook contents or selected displays. In Book view, print a list of the entire book or a selected tab section. Print the entire contents of a display or selected items from that window. You can also set various printing options, such as the number of copies. Each topic in the help file may be printed separately or you can print them all at once. The Print command is accessible from the File menu, CTRL+P, or the print button. You can print the contents of the active window or if you select items within a display before you open the Print window, then you can choose to print only those items. On a non-color printer, symbols are printed in shades of gray, but trends are printed in black and white. On some printers, when you print a trend with cursors, the value and time stamp boxes of the cursor does not hide the information beneath them. However, other trend cursors and the trend time scale may show through the trend cursor boxes, making the values hard to read. Topics in this section Page Setup for printing Print Preview Set up printer Page Setup for printing You can select the particular printer, the orientation of the paper, the paper size, and the source within the printer of the paper. Use the Properties button to fine-tune the quality of output or the performance of the printer. The settings you choose in Page Setup become the defaults for all your printing. PI ProcessBook 2015 User Guide 25

36 PI ProcessBook essentials PI ProcessBook supports dot matrix, HP PCL (LaserJet), Postscript, and color printers. However, all Windows print drivers may not be compatible. If you are not sure if your printer is supported or you observe any printing problems, contact OSIsoft Technical Support. Print Preview Print Preview displays your selection as it will look when it is printed. Note that the Print Preview shows colors even though you may be using a black and white printer. After you select the item you want to preview, click File > Print Preview. Zoom in or out of the selection by clicking on the selection with the magnifier cursor or by clicking the Zoom buttons. To print the selection, click the Print button. Set up printer Select Print Setup to choose a printer, page orientation, and paper size. In addition, you can fine-tune the quality of output or the performance of your printer. The settings you choose in Print Setup become the defaults for all your printing. 1. Click File > Page Setup. The Print Setup window appears. 2. Select the printer, orientation, and paper size and source. PI ProcessBook supports dot matrix, HP PCL (LaserJet), Postscript, and color printers. However, all Windows print drivers may not be compatible. If you are not sure if your printer is supported or you observe any printing problems, contact OSIsoft Technical Support. 3. Click the Properties button to select printer-specific options. Refer to your printer documentation for additional information about these options. Change the language used for PI ProcessBook You can change the language for the application on your machine if you have a PI ProcessBook Language Pack and the desired language resources installed. The language setting is per user locale, so if others want to use the application on the same machine under a different login, they can use different language resources if available. 1. Run the PI ProcessBook Language Pack and select the language resources you want to install, if they are not already available. 2. Click Tools > Preferences. 26 PI ProcessBook 2015 User Guide

37 PI ProcessBook essentials The ProcessBook Preferences window appears. 3. On the General tab, click the Language Settings button to launch the language selection tool. This button is only active if you have language resources installed. 4. Select the target language and click OK. 5. Quit and restart the application. PI ProcessBook now appears in the specified language. Note that users who log in with the same account see the same language, but the language does not change for those logging in to the machine with different accounts. About PI ProcessBook You can launch the About PI ProcessBook window by clicking Help > About PI ProcessBook. The window provides detailed version and build information, as well as a link to the OSIsoft Technical Support website. Click Copy Info to copy the contents of the list to your Windows clipboard where it can be pasted into a spreadsheet or text editor. This can be useful to share with OSIsoft Technical Support engineers if you have a problem. Click System Info to launch the Microsoft System Information window. This information can also be useful when troubleshooting issues through OSIsoft Technical Support. PI ProcessBook 2015 User Guide 27

38 PI ProcessBook essentials 28 PI ProcessBook 2015 User Guide

39 Work with a ProcessBook Topics in this section Basic steps to build a ProcessBook Create a new ProcessBook Add ProcessBook entries Arrange ProcessBook entries Open an existing ProcessBook Properties Import files to a ProcessBook File sharing capability Moving a ProcessBook to another PC Basic steps to build a ProcessBook There are five basic steps to create a new ProcessBook. 1. Create and save a ProcessBook. 2. Add, organize, and edit entry titles. 3. Design a detailed display for each display entry title, using the drawing tools to create schematics or other drawings with trends, bars, and values. To import outside data, add OLE objects and values from data set queries. 4. Format trends and make other adjustments to each display to present your data in the most useful manner. 5. Save the completed ProcessBook and install it wherever it is needed. In some installations, the system administrator might set your PI ProcessBook to View-only mode mode. If so, you cannot create and save new ProcessBooks. Create a new ProcessBook Before you create a ProcessBook, you should consider planning an organizational structure and a naming convention for the ProcessBook and the entries within it. When you create and save a new ProcessBook, the application initially gives it the title Book1, where 1 represents the number of ProcessBooks created during the current session. PI ProcessBook also creates a file name for the new ProcessBook. It suggests the first word from your title and an extension of.piw. For example, PI ProcessBook may suggest Filtrat1.PIW. If you plan to build an entire set of ProcessBooks, you might choose to modify PI ProcessBook 2015 User Guide 29

40 Work with a ProcessBook it in Windows Explorer to sort your set of ProcessBooks in some meaningful order, such as 05FiltrP.PIW. 1. In Build mode, click File > New. The New window appears. 2. Select ProcessBook (.piw) File. 3. In the ProcessBook Name box, type a name for the new book. 4. Click OK. A new ProcessBook appears. If you typed a name in the ProcessBook Name box, then the name appears on the ProcessBook title bar. If you did not type a name, then the default title Book1 appears on the title bar. Add ProcessBook entries After creating a ProcessBook, the next step is to add individual entries. By arranging and combining displays and other entry types, you can create a complete working environment for plant personnel. You can add entry titles to a ProcessBook and then complete the detailed design of the entries later. There are five specific types of entries: Text Provides headings or static information. See Create a text or display entry. Display Opens a display. See Create a text or display entry. Linked displays Links to an independent display file. See Linked display entry. Linked ProcessBook Links to an entry in another ProcessBook. See Linked ProcessBook entries. Operating system (OS) command Opens another application. See Operating system command entry. 30 PI ProcessBook 2015 User Guide

41 Work with a ProcessBook When you add entries to a ProcessBook in either Outline or Book View, the entries are arranged hierarchically. Subentries are indented under main entries. The name you give each new entry is the name that shows in the ProcessBook. When you create a new entry, it is placed in the ProcessBook just before the selected entry. If no entries are selected, the new entry appears at the end of the current tab section in Book View or at the end of the Outline View. The first entry on a book tab is normally a Level 2 item (Level 1 is used as the tab label). All Level 3 through 10 items are listed below a level 2 item and indented the same. In Outline View, all levels are indented according to their level. Topics in this section Create a text or display entry Linked display entry Linked ProcessBook entries Operating system command entry Create a text or display entry Use text entries to add labels and clarify text in a ProcessBook table of contents. Display entries represent a display in a ProcessBook. 1. Click File > New. The New window appears. 2. Under Type, select ProcessBook Entry. 3. Click OK. The Define ProcessBook Entry window appears. 4. In the Label window, type a name. The label must be 244 characters or less in length. PI ProcessBook 2015 User Guide 31

42 Work with a ProcessBook 5. For the Type, select Text or Display. 6. In the Level list, click the level at which you want to position the entry in the ProcessBook hierarchy of entries, or Type a number between 1 and Click OK. If you are creating the first entry in the ProcessBook, the level is automatically set to 1 and cannot be changed. This entry is used as the first tab label. The entry is added to the ProcessBook. If the entry is at Level 1 and you are in Book view, a tab is created using the name of the entry. 8. Click the Save button on the toolbar, or Click File > Save. Linked display entry A linked display allows you to use a display name to link to an entry elsewhere in the ProcessBook or in another ProcessBook or independent display file. This means that you create and store only one copy of the display. You can then access the same entry from several different locations in one ProcessBook. Or, while you are in one ProcessBook, you can open an entry from another one without having to close the first ProcessBook. The linked entry is not a copy; it is a way of opening the original, similar to using a Windows shortcut. The Book View or Outline View shows the title of the linked entry, but the actual display window shows the title of the original entry. If you edit the original from any linked entry, the original is updated and automatically appears updated in all the ProcessBooks that are linked to it. To prevent unexpected updates, you can restrict access to an entry so that only the original entry can be edited and all others to which it is linked are read-only. If the entry resides on a server, you can write-protect the file on the server. If you need more information on restricting access to files, see your system administrator. Before you create a link to an original entry in a different ProcessBook, the ProcessBook that contains the original (target) entry must be open. Once the link is established, you only need to open the ProcessBook with the Linked Entry. If you want to link to an entry in a second ProcessBook, open the second book or use the Display Search window. If you want to link to an entry in the current ProcessBook, create the original display entry first, save the file, and then create the linked entry. The target display must be in a file that has been saved so that its path can be determined. Create a linked display entry 1. Click File > New. 32 PI ProcessBook 2015 User Guide

43 Work with a ProcessBook The New window appears. 2. Under Type, select ProcessBook Entry. 3. Click OK. The Define ProcessBook Entry window appears. 4. In the Label window, type a name. The label must be 244 characters or less in length. 5. For the Type, select Link/OS Command. 6. Click the Browse button, or Click the Browse arrow to see more search options. The Open window appears. 7. To link to an independent display file, locate and select the display file (.pdi) to which you want to link and then click the Open button. The display name appears in the Action box. 8. To link to another ProcessBook, locate and select the processbook file (.piw) to which you want to link and click the Open button. The file name appears in the Action box. 9. To link to a display in a ProcessBook, select the Display Search option from the Browse drop-down and enter criteria to locate the display you want within the open files. If the display you want is not in a file that is open, select a different option in the Look in field. When the display is listed in the Display Search window, select it and click OK. The name appears in the Action box. 10. In the Level list, click the level at which you want to position the entry in the ProcessBook hierarchy of entries, or Type a number between 1 and 10. If you are creating the first entry in the ProcessBook, the level is automatically set to 1 and cannot be changed. 11. Clear the Options check box if you want the absolute path to the file checked first. 12. Click OK. By default, ProcessBook attempts to open a linked display from its relative path first. If the relative path fails, then the absolute path is checked. Clearing the Use relative path check box reverses the order in which the paths are resolved. For new displays, this option is checked by default. A linked display entry icon is added to the outline and book view of the ProcessBook you are developing. 13. Click the Save button. PI ProcessBook 2015 User Guide 33

44 Work with a ProcessBook If you need to move the original entry to another directory or ProcessBook, you must redefine the link between the ProcessBooks. If you move both the original and the linked item and the relationship between the two file paths is unchanged, you do not need to relink. Linked ProcessBook entries Similar to a linked display, a linked ProcessBook entry is a link to a different ProcessBook. When you open a linked ProcessBook entry, another ProcessBook is opened. You may open any of the entries in that ProcessBook. Using a linked ProcessBook entry is the same as opening a ProcessBook using the Open command on the File menu. The same rules apply to linked ProcessBook entries as to linked entries. Move linked entries If you move a linked pair of displays or ProcessBooks to another location and if this move changes the relationship of the two file paths, you need to relink the items. Operating system command entry An operating system command is used to start another application, such as Microsoft Excel, in addition to PI ProcessBook. Essentially, any command that you can execute with the Windows Run command can be used as an operating system command entry in a ProcessBook. For example, you can use an operating system command to link to PI DataLink reports or calculations. You can also create links to CAD drawings, modeling packages, or statistics packages. Links to displays saved as.svg files are treated as operating system command entries. When you have reports created on a different system, you can convert them to ASCII and, using an operating system command, create a link to Notepad to read the reports. If your company has online help files for certain procedures, you can create a link to those help files or other documents. Your computer must have enough memory to run the applications you want to use in addition to PI ProcessBook. The applications also must be installed on your system. If you do not know whether or not your computer has enough memory, contact your system administrator. Topics in this section Create an operating system command entry Working directory for operating system commands Create an operating system command entry 1. Click File > New. 34 PI ProcessBook 2015 User Guide

45 Work with a ProcessBook The New window appears. 2. Under Type, select ProcessBook Entry. 3. Click OK. The Define ProcessBook Entry window appears. 4. In the Label window, type a name. The label must be 244 characters or less in length. 5. For the Type, select Link/OS Command. 6. Click the Browse button to the right of the Action box, or Click the Browse arrow and then click Applications. The Open window appears. 7. Browse and locate the file to which want to link, and then click the Open button. The application's path/name appears in the Action box. If you know the name of the.exe file for the application, such as C:\excel \Excel.exe for Excel or the path and name of a data file, such as C:\document \report.xls, then you can type the path directly in the Action box. You can use most commands that execute successfully in the Windows Start menu Run window. 8. If you need to specify the location of the executable for the application, click the Browse button to the right of the Working folder box. The Browse for Folder window appears. 9. Locate and select the folder that you want to specify for this operating system command, and click OK. If you know the name of the working folder for this application, then you can type it directly in the Working folder box. 10. In the Level list, click the level at which you want to position the entry in the ProcessBook hierarchy of entries, or Type a number between 1 and 10. If you are creating the first entry in the ProcessBook, the level is automatically set to 1 and cannot be changed. 11. If the file specified in the Action box is associated with one application and you want to open it with another, select the Ignore the default shell command for recognized file types check box. This option is normally only used with files such as displays saved as SVG so that they can be opened in PI ProcessBook instead of the associated Viewer application. PI ProcessBook 2015 User Guide 35

46 Work with a ProcessBook 12. Click OK. If the file type is supported by ProcessBook (either natively or through an add-in), then it is opened directly when this option is selected for a Link or OS command entry. For example, an.svg file is opened using the SVG File Converter in ProcessBook, even if you have Adobe SVG Viewer installed. Clearing this check box disables this behavior, so the default shell command is used to open the file instead. An icon for the program you are launching is added to the outline and book view of the ProcessBook and the application opens. Close the application. 13. Click the Save button. Any path entered in the Action field is considered absolute. If the display with this entry is moved, the path is not changed from the original entry. If the Action is entered and saved as a relative path, the system attempts to open the command using that relative path. In this case, if you need to move the original entry to another directory or ProcessBook, you may have to redefine the link between the ProcessBooks. If you move both the original and the linked item and the relationship between the two file paths is unchanged, you do not need to relink. Working directory for operating system commands The Define ProcessBook Entry window has a text box where you can enter the working directory. The command line recognizes file extension associations. For example, in the past you needed to enter a command like: C:\EXCEL\EXCEL.EXE C:\MYWORK\MINE.XLS Now you can use a command like: C:\MYWORK\MINE.XLS In other words, if the string works for the Run command under the File menu of the Program Manager, it will work in PI ProcessBook. Some applications that you can access with an operating system command, such as MS Excel, allow only one copy of the application to open, even if you execute the command several times. Arrange ProcessBook entries Once you have created your entry titles, it is a good idea to consider how they are arranged in your ProcessBook. Each ProcessBook gives two possible views of your entry titles, Book View and Outline View. Whether you are in Outline View or Book View, you can edit and rearrange entries, or delete entries altogether. Some functions are performed the same regardless of the view in which you are working. Book View is a useful organizational tool when your ProcessBook has only a few dozen displays. If your ProcessBook is large and contains many displays, Outline View is faster and easier to use. 36 PI ProcessBook 2015 User Guide

47 Work with a ProcessBook Topics in this section Book View Outline View Copy and paste an entry Remove an entry Save and close a ProcessBook Book View In Book View, the ProcessBook displays as a loose-leaf binder. Tabs indicate major divisions in the ProcessBook. Each tab section has a heading, which may be any ProcessBook entry. The entry title is used as the tab name. A tab section may contain several pages of entries representing different types of information. There is no limit to the number of tabs you can have in a Book. However, as you add tabs or reduce the size of the ProcessBook, the tabs are stacked to the right of the Book. This might make the ProcessBook difficult to read in Book View. When you create a first-level entry in Book View, the name becomes the label for the section tab. If the entry is the first entry you have added to the ProcessBook, the entry level is automatically set at 1. Subsequent sub-entries are listed below the main entry. When you select another first level entry, a new page is created with a new tab. You can have up to 10 levels of entries in a ProcessBook, but levels 3 to 10 are displayed in Book View as though they were at the same level. Displays within a tab section are typically arranged in a hierarchical fashion. For example, a display that includes a boiler, a condenser, and a pump may be at the top level of a tab section. The boiler, the condenser, and the pump may be separate displays that are arranged underneath the summary display. Each of these displays can have several displays for their components. PI ProcessBook 2015 User Guide 37

48 Work with a ProcessBook Book View Topics in this section Turn pages in Book View Resize a ProcessBook Entries in Book View Turn pages in Book View 1. Click View > Book to view a ProcessBook in Book View. Notice the top right corner of the page is divided into two small triangles. 2. Click the upper triangle to move forward one page, or Click the lower triangle to move backward a page. A dark gray triangle indicates there are no more pages in that direction. 3. Click the tabs along the right-hand side to move quickly between sections of a ProcessBook. Resize a ProcessBook 1. Click and drag on the frame of a ProcessBook until the window is the size you want. 38 PI ProcessBook 2015 User Guide

49 As you make a window smaller, the ProcessBook is resized so you can still see all of the tabs. If the window becomes too small to display all the members of a group of displays, the displays are moved to new pages. If the ProcessBook window becomes too small, all the tabs behind the first tab are collapsed into one tab labeled More. 2. Click the More tab to display a pop-up list of the other tab sections. Work with a ProcessBook Entries in Book View When you create a first level entry in Book View, the name becomes the label for the section tab. If the entry is the first entry you have added to the ProcessBook, the entry level is automatically set at 1. Subsequent sub-entries are listed below the main entry. When you select another first level entry, a new page is created with a new tab. Topics in this section Change the name of an entry in Book View Change the level of an entry in Book View Change the name of an entry in Book View 1. Click View > Book to view a ProcessBook in Book View. 2. In Build mode, double-click the entry you want to change. The Define ProcessBook Entry window appears. 3. In the Label text box, type a new name. 4. Click OK. Change the level of an entry in Book View 1. Click View > Book to view a ProcessBook in Book View. 2. In Build mode, double-click the entry you want to change. The Define ProcessBook Entry dialog appears. 3. In the Level list, click the level at which you want to reposition the entry in the ProcessBook hierarchy of entries, or Type a number between 1 and Click OK. Outline View In Outline View, ProcessBook displays are arranged hierarchically on a page. Click View > Outline to display a ProcessBook as an outline. When you are in Outline View, a set of buttons is added to the active ProcessBook window to collapse or expand the outline. PI ProcessBook 2015 User Guide 39

50 Work with a ProcessBook You may need to resize the window so all the buttons are visible. Use the horizontal and vertical scroll bars to see all entries in the outline. Hierarchies of entries may be revised by dragging entries from one location to another, or by promoting and demoting entries. Outline View Topics in this section Collapse or expand Outline View Rearrange entries in Outline View Change the name of an entry in Outline View Change the level of an entry in Outline View Collapse or expand Outline View You can collapse or expand sections of the outline to view the list of displays in a meaningful manner. 1. Click View > Outline to view a ProcessBook in Outline View. 2. Click the black plus sign to the left of an entry to expand it. This shows additional displays that are subordinate to the selected display. Collapsed View: 40 PI ProcessBook 2015 User Guide

51 Work with a ProcessBook -or- Click the transparent plus sign to collapse the list of subordinate displays. Expanded View: You can change the font for each level in Outline View in the Preference Settings window. See Preference settings. Rearrange entries in Outline View In Build mode, click and drag the entry name up or down (not sideways) to a new location. A dotted line indicates the location of the entry you are moving. Alternatively, you can use the four buttons at the top left of the window as follows: Promote highlighted entry Demote highlighted entry Move highlighted entry up Move highlighted entry down Change the name of an entry in Outline View 1. Click View > Outline. 2. In Build mode, click the entry you want to change. 3. Click Edit > Selected Item. The Define ProcessBook Entry window appears. 4. In the Label box, type a new name. 5. Click OK. Change the level of an entry in Outline View 1. Click View > Outline. 2. In Build mode, click the entry you want to change. PI ProcessBook 2015 User Guide 41

52 Work with a ProcessBook 3. Click Edit > Selected Item. The Define ProcessBook Entry window appears. 4. In the Level list, click the level at which you want to reposition the entry in the ProcessBook hierarchy of entries. -or- Type a number between 1 and Click OK. Copy and paste an entry 1. Click on the Build mode pointer and select the entry. 2. Click the Copy button. This copies the selection to the clipboard. 3. If it is not already open, open the ProcessBook where you want to paste the entry. 4. Click the Paste button. This copies the contents of the clipboard to your ProcessBook. A copy of the original entry is created, not a link to the original. If you highlight an entry first, the new entry is placed above the highlighted entry. Remove an entry 1. In Build mode, select an entry title in either Book View or Outline View. 2. Press the DELETE key. The entry is removed from the ProcessBook. If you accidentally delete the wrong entry click Edit > Undo. Save and close a ProcessBook After creating a ProcessBook, it is a good idea to name the file and save it immediately. It is also important to save a ProcessBook periodically while you are working in it. When you save a ProcessBook, all changes to all entries and to the organizational structure are stored permanently. The ProcessBook remains open in your workspace so you can continue working. 1. To save a ProcessBook for the first time, click File > Save or Save As. 42 PI ProcessBook 2015 User Guide

53 Work with a ProcessBook The Save As window appears. 2. Type a name for the ProcessBook file. A.piw extension is automatically added. 3. Select the drive and directory where you want to save it. 4. Click OK. Open an existing ProcessBook 1. Click File > Open, or On the standard toolbar, click the Open button. The Open window appears. 2. Click the specific ProcessBook file (.piw) you want to open. 3. Click OK. Depending on the settings in the ProcessBook Preferences window, a default ProcessBook may open automatically when you start PI ProcessBook. PI ProcessBook keeps track of the four most recently opened ProcessBooks or independent display files. Instead of using File > Open, you may select a file name from the bottom of the File menu. Work with multiple ProcessBooks You can work in multiple ProcessBooks and/or independent display files at the same time. Use the File menu to create new or open existing ProcessBooks. Use the Windows menu to select the ProcessBook title and switch among them. Click inside a ProcessBook window to make it active. Switch among the open windows by pressing CTRL+F6. Properties Topics in this section Summary information in ProcessBook PI ProcessBook file properties PI ProcessBook display properties PI ProcessBook 2015 User Guide 43

54 Work with a ProcessBook Summary information in ProcessBook Click File > Properties to display the Summary Information window for a file. The Summary Information window you see is the same for the ProcessBook as a whole or for the individual displays. The following table describes the fields in the Summary Information window: Field Name Author Title Subject Keywords Comments Properties button Description Extracted from the Author field on the General tab in the ProcessBook Preferences window at the time the ProcessBook is first saved. You can change the Author field in either the Summary Information window or the ProcessBook Preferences window. Name of the ProcessBook (extracted from the original creation of the ProcessBook). Can be used to explain the title more fully. Can be added at any time. Can be used for any text entry. You can revise this field at any time. Clicking the Properties button displays the PI ProcessBook Properties window, which gives information about the view currently in the active window. See PI ProcessBook file properties. PI ProcessBook file properties 1. Click File > Properties to display the Summary Information window. 2. Click the Properties button. The PI ProcessBook Properties window appears. 44 PI ProcessBook 2015 User Guide

55 Work with a ProcessBook If you click the Properties button while a display is open, you launch the Display Properties window. The following table describes the fields in the PI ProcessBook Properties window: Field Name Title Created Created By Last Saved Last Saved By Revision System Commands Description Extracted from the Summary Information window. Original date and time the ProcessBook was saved. If the ProcessBook file is moved to another machine, the original date and time will be preserved, however Windows Explorer shows the date and time the file arrived on the present machine. Extracted from the Author field on the General tab in the ProcessBook Preferences window. Shows the original author, unless the author s name has been modified in the Summary Information window. Most recent revision date and time. Name of the person who saved the ProcessBook most recently. (Extracted from the Author field on the General tab in the ProcessBook Preferences window.) If this field is blank, the PC login name of the author is used. This is useful for tracking who made which revisions. Number of times the ProcessBook has been revised and saved. Total number of operating system command entries in the ProcessBook. Modify a ProcessBook title You can change the name of a ProcessBook at any time. PI ProcessBook 2015 User Guide 45

56 Work with a ProcessBook 1. In either Build mode or Run mode, click File > Properties. The Summary Informationwindow appears. See Summary information in ProcessBook. 2. In the Title box, type a new title. 3. Click OK. The ProcessBook title is different from the file name established in the New window when you created the new ProcessBook. The title bar on the ProcessBook window displays the file name, which ends in.piw, rather than the title. PI ProcessBook display properties 1. With a display window selected, click File > Properties to display the Summary Information window for a display. See Summary information in ProcessBook. 2. Click the Properties button. The Display Properties window appears. The following table describes the fields in the Display Properties window: Field name Title Created Description Extracted from the Summary Information window. Original date and time the ProcessBook was saved. If the ProcessBook file is moved to another machine, the original date and time will be preserved, however Windows Explorer shows the date and time the file arrived on the present machine. 46 PI ProcessBook 2015 User Guide

57 Work with a ProcessBook Field name Created By Last Saved Last Saved By Revision Total Symbols Tags Dynamic Symbols Static Symbols Servers Required Description Extracted from the Author field on the General tab in the ProcessBook Preferences window. Shows the original author, unless the author s name has been modified in the Summary Information window. Most recent revision date and time. Name of the person who saved the ProcessBook most recently. (Extracted from the Author field on the General tab in the ProcessBook Preferences window.) If this field is blank, the PC login name of the author is used. This is useful for tracking who made which revisions. Number of times the ProcessBook has been revised and saved. Total number of symbols in the display. Total number of unique PI Points used in the display. The number of display symbols that are dynamic symbols. The number of display symbols that are static symbols. The number of different PI Data Archive servers referenced in the display. Import files to a ProcessBook 1. To import PIDisDiff or PI-Graphics files into a ProcessBook, start PI ProcessBook. 2. Open an existing ProcessBook into which you want to import the files, or create a new ProcessBook. 3. In Build mode, click File > Import. The Import Files window appears. 4. Select the file type. 5. Select the drive and directory where the file resides, or Type the path and file name in the File Name box. You can select more than one file at a time. 6. Click the Open button. The status bar displays each file as it is imported. When completed, a message displays the number of files successfully imported. If errors occurred during the import process, a message box is displayed at the end of the import process showing the number of errors. You can check the message log from the Status Report icon at the bottom of your display. Depending on the size, some files may take several minutes to import. PI ProcessBook 2015 User Guide 47

58 Work with a ProcessBook When a trend is successfully imported, a new Text display showing the full file name is added to the ProcessBook. Each trend is added as a subordinate display and retains its original trend name. For graphics, the OpenVMS display name becomes the Display name. Once converted, graphics and trends can be edited like any other display. File sharing capability Several users may access the same ProcessBook file at the same time. However, if one person makes changes to a particular display entry and saves the changes, then other users are blocked from saving changes in that display. This protects against accidental saving conflicts. If a user has already changed a display, the second user who wishes to make changes to the display receives an error message explaining that someone else has already edited and saved the display. The second user then has two options: Save the changes under a different ProcessBook name, thus creating two ProcessBooks, -or- Close the ProcessBook and reopen it so that the new version of the display is shown. Then make changes and save again. Open the Summary Information window to view the name of the person who has made changes and saved the file most recently. See Summary information in ProcessBook. Moving a ProcessBook to another PC If you decide to move a ProcessBook to another PC, you might experience some differences in display entry appearance on the new PC: When the number of colors is different between the original PC and new PC, PI ProcessBook uses the closest color when drawing an entry. This is true for any graphics you may have included in an entry. If an entry calls for a font that is not available on the new PC, PI ProcessBook substitutes a similar font. If a ProcessBook includes links to other entries, ProcessBooks, or applications, PI ProcessBook may not be able to locate them if the path on the new PC is not the same as the old one. Node names (for PI Data Archive servers) must be identical. Different monitors have different resolutions, which may distort the appearance of an existing ProcessBook. PI ProcessBook records both the absolute and relative paths for Linked displays and Linked ProcessBooks. This means you can copy ProcessBooks to new directories without breaking links as long as either all the linked files are placed in a similar directory tree or all the drive, directory, and file names remain the same. 48 PI ProcessBook 2015 User Guide

59 Work with a display PI ProcessBook provides tools for manipulating and analyzing the information shown in a display. For example, you can: Display the point attributes of a tag Change the time range that is used for values, bars, trends, XYPlots, SQC plots, and Multi- State symbols Use a Trend Cursor to see the value of plotted tags at a specific point in time Create an instant trend Topics in this section Overview of display elements Manage displays and independent display files Drawing tools Formatting ToolTip Statistics window Time Range and Playback toolbar Time Range toolbar Layers within displays Migrating displays to another PI Data Archive server AF Modeler and AF Display Builder displays Overview of display elements Displays contain a variety of individual items, including static elements, buttons, OLE objects, and dynamic elements. Topics in this section Static symbols Dynamic symbols Buttons OLE objects Static symbols Static symbols are symbols that do not automatically change as time passes, such as an image, process diagram, or descriptive text. PI ProcessBook 2015 User Guide 49

60 Work with a display Static symbols include all items in a display that do not connect to the PI Data Archive server or other application to retrieve data, and do not start any application. Text labels and flow lines are examples of static symbols. Other types include rectangles, circles, arcs, and images. Dynamic symbols Buttons Dynamic symbols are values, bars, trends, XYPlots, SQC charts, and multi-state symbols (such as a pump image tied to temperature data) that change over time, and are based on the value of a tag in the PI Data Archive server. If you wish to see how a dynamic symbol was defined, select it and click the Item Definition button on the Drawing toolbar. Dynamic symbols may also report data from outside databases through queries. If you rest your mouse on a dynamic symbol, you can see a ToolTip with the current value, tag name, and time stamp. Icons for questionable, substituted, and annotated PI data can also appear on your displays. Most point types (see PI Data Archive data types) can be used with any dynamic symbol. There are some restrictions on string and timestamp data. Buttons are elements that create a link to other applications, such as a calculator or word processor, or other ProcessBooks or displays. You can also use buttons to execute a script. For example, if you find you work in a particular display and frequently need to update a report with the information you are monitoring, you can add a button that automatically opens a spreadsheet program. You also can use a button to perform common actions using a script, like printing a display, or connect to related displays, ProcessBooks, or Web sites. OLE objects OLE objects include information from outside applications, such as text, spreadsheets, or graphics. This information may be configured to update dynamically. OLE objects may be either linked or embedded or into displays. See Link a file to a displayand Embed in PI ProcessBook for details. Manage displays and independent display files Topics in this section Open a display Zoom display size Use Full Screen mode Search for a display Reduce a display to an icon to save space Save a display 50 PI ProcessBook 2015 User Guide

61 Work with a display Display Settings window Display scrolling properties Status bar indicators Open a display Use any of these procedures to open a display from either Book View or Outline View of a ProcessBook. Click on the display title, then on the New button to open the selected display in a new window. Click on the display title, then on the Open button to open the display into the last display window you used. If none are open, a display window opens. With the Run Mode pointer, double-click the display. The display opens and appears within an existing window, if possible. Click and drag the display title to an unused area in the application workspace and release the mouse. This opens a new display in addition to already opened displays. If you drag the display on top of an open display, it closes that display while opening the dragged display. To use the keyboard instead of the mouse, use CTRL+F6, to select the ProcessBook, then use the up or down arrow keys to select the display title. Press Enter. If you have more than one display open, it replaces the open display with the new display. Pressing CTRL+N is the same as clicking the New button. Results If the display is a display, linked display, or linked ProcessBook, the display is opened and the contents are displayed on your workspace. If the display is an operating system command, the command is executed or the application is started. If you click on an operating system command more than once in the same session, it might run the application repeatedly. This depends on the application and how it has been set up. Displays re-open in the same position, size, and shape as when they were last saved. Topics in this section Open several displays at one time Manage multiple open displays Open independent display files PI ProcessBook 2015 User Guide 51

62 Work with a display Open several displays at one time In addition to the procedures for opening a display, you can also open multiple displays simultaneously. 1. Press SHIFT while highlighting the displays you want to open in Outline view. 2. Click the New button at the bottom of the list of displays. Each display or linked display is opened in your workspace. Manage multiple open displays Just as you can work with multiple ProcessBooks, you can have multiple displays open in the work area. To make a display active, click in the display window or press CTRL+F6 to toggle between open displays. To improve viewing when there are multiple open displays, choose: Window > Cascade The titles of all open displays and ProcessBooks appear in a cascaded list down the screen. Window > Tile All open displays and ProcessBooks appear in a tiled view. Window > <display title> The selected display is active. Open independent display files Independent display files use a.pdi extension in the file name. 1. Double-click on a display file in Windows Explorer. A copy of the PI ProcessBook application installed on your PC opens, just as it would if you double-clicked on a.piw file. The independent display appears inside the application. Zoom display size Use the Zoom command to change the size of the drawing within a display window. a. Click View > Zoom. 52 PI ProcessBook 2015 User Guide

63 Work with a display The Zoom window appears. b. Click a percentage, or Type a number in the Custom text box to enlarge or reduce the drawing. The Custom text box displays the current Scale Factor. Typing a number greater than the current Scale Factor enlarges the drawing; typing a number less than the current Scale Factor reduces it. c. Select Fit all symbols to resize all the symbols in a display to fit within the window. If you want only specific symbols to fit within the display window, select the symbols, and then select Fit Selected Symbols. The items in the display resize and take up the entire window. OLE objects are not included. d. Click OK to accept your changes. You must save the display before closing it for your zoom settings to appear the next time you open it. Use the Maximize and Minimize buttons in the upper right hand corner of your display window to adjust your display size. When you maximize a display, all open display windows are maximized. You can also drag the edge or corner of the window to the desired size. If you have your Preference setting for Preserve Aspect Ratio check box selected, the contents of the display resize as you resize the window. If this option is not enabled, the size of each element in the display does not change as you change the window size. Use Full Screen mode 1. Click the Full Screen button on the Full Screen toolbar. Other toolbars vanish and the display enlarges to fit the screen. 2. Click the Full Screen button again to restore your toolbars. A default keyboard shortcut of F11 also toggles between Full Screen and Normal presentations. You can customize the Full Screen toolbar to contain other buttons to use with a Full Screen display. Search for a display 1. Open the ProcessBook you want to search. See Open an existing ProcessBook. 2. Click Tools > Display Search & Run. PI ProcessBook 2015 User Guide 53

64 Work with a display The Display Search window appears. 3. In the Name box, type one or more of the letters of the display name. 4. In the Look in drop-down list, click the location you want to search. -or- In the drop-down list, click Browse, and then locate the appropriate folder. 5. Optional: Select the Look in subfolders check box. 6. Click the Search button. The search results are displayed under Results. 7. Under Filename, click the display you want to open and then click OK. Reduce a display to an icon to save space If you find your work area cluttered with many open displays, you can reduce a display to an icon by clicking its Minimize button. Even though the display is minimized, it continues to be updated with information from the PI Data Archive server, however the results are not shown until the window is restored. When you want to use the display, double-click the icon. Save a display A display may be saved within a ProcessBook or as an independent file (.pdi). 1. Click File > Save or Save As. 2. From the Save as type drop-down box, select one of the following six formats. The default is.pdi:.pdi 54 PI ProcessBook 2015 User Guide

65 Display file. If you select this format your display becomes an independent file that updates under certain circumstances..svg SVG file for Web use. PI ProcessBook 3.0 or higher only supports version 3.0 or higher of the SVG add-in. See the SVG add-in release notes for more information. The last four file types are graphics formats and do not update. If you choose one of the graphic formats, the display in focus is unchanged by the Save-As operation. The display is left open and remains in the same mode (Run or Build)..jpg JPG-JPEG-JFIF compliant.bmp 32-bit Bitmap.wmf Windows Metafile.png Portable Network Graphics Display Settings window To edit display properties, click Edit > Display, or double-click the Time Zone setting in the Status bar. The Display Settings window appears. Work with a display PI ProcessBook 2015 User Guide 55

66 Work with a display Background Color The color applied to the area of the display where there are no symbols. This field uses a color well control to provide color choices. The color selected in this field also becomes the default background color for new displays. Time Zone This field determines whether the local computer or PI Data Archive server time zone is used for interpreting dates and times for this particular display. Connectors If this setting is changed while a display is active and the client and the server are in different time zones, all absolute times (not based on now such as '*-8 hours') will not be translated to the new time zone. This setting is saved with the display. The Enable Connector Attachments check box allows a symbol dragged and dropped on a Connector symbol to be attached to that Connector. Clearing the check box disables this functionality for the Display. Note that even if this feature is disabled for the display, you can still use the Connectors window to attach Symbols to Connectors. Enable Scripting 56 PI ProcessBook 2015 User Guide

67 When displays have many symbols on them, the performance of PI ProcessBook may be affected. One way to improve the situation is to disable the ability to code the majority of those symbols. In order to disable scripting and improve performance, you can take the following actions: OK In the Enable Scripting section, clear the Automatically Enable Scripting check box. This adds new symbols to the display without the overhead of enabling scripting if it isn't needed. If the display already has many enabled symbols on it, click the Disable Scripting for All Symbols button in the Enable Scripting section. This button removes the scripting capability for all existing symbols to help improve performance. Clicking this button accepts the changes made and closes the window. These settings are saved as part of the display object. Display scrolling properties Work with a display Run Mode scrolling determines the scroll bar behavior of display windows in Run mode. Build Mode scrolling determines the scroll bar behavior of display windows in Build mode. On Off Automatic Display contains scroll bars all the time. Scroll bars never appear. Scroll bars appear when needed. Status bar indicators The following appear on the PI ProcessBook status bar: Image Name Time Zone. See Display Settings window. Layers. See Layers within displays. Troubleshooting icons. See Status report for dynamic symbols. PI ProcessBook 2015 User Guide 57

68 Work with a display Image Name Displays the current default color for symbol line, fill, and background color. Keyboard Numeric Lock is on. Keyboard Scroll Lock is on. Drawing tools PI ProcessBook includes a drawing environment with features that allow you to create symbols and graphics within an entry. You can use the drawing tools to: Create ellipses, polygons, rectangles, arcs, lines, and polylines Add dynamic elements such as values, bars, and trends Add buttons and graphic files Add ActiveX controls The Drawing toolbar contains a set of buttons used for creating drawings and the Draw menu contains the corresponding commands. To use the drawing tools, click the appropriate button. When you draw a line or other shape, the tool uses the current formatting attribute preferences. Each of these objects is considered a symbol by PI ProcessBook. In Build mode, when you select a symbol by clicking it with your mouse, you see small squares around the bounding rectangle of the symbol. These are called selection handles and allow you to resize the symbol. For arcs, polygons, and polylines, there are also reshaping handles at the intersection of the line segments. Each symbol has a name, reflecting the order in which it was added to the display, such as Rectangle1, Rectangle2, etc. In Build mode (or VBA Design mode), an identifying tooltip appears whenever your mouse hovers over a symbol. If you are d rawing multiple objects, press the CTRL key while selecting the drawing tool. This lets you continue to work with that tool until you select a different tool. Topics in this section Organizing symbols Drawing area Drawing grid 58 PI ProcessBook 2015 User Guide

69 Work with a display Organizing symbols PI ProcessBook provides several tools to help you organize your drawings. These tools include a drawing grid, flip and rotate capabilities, and the ability to change the order in which objects overlap each other. You can move and resize drawing objects. You can also divide a display into layers so that you can segregate various elements. For example, you might separate HVAC elements from Electrical elements in a display. Any of these functions can be performed on a single screen element or group of them. For information on grouping objects, see Group, ungroup, or regroup symbols. Make sure you have selected the item or items with the Build Mode pointer. OLE objects behave somewhat differently; their behavior is discussed under Commands that ignore OLE objects. Drawing area The drawing area of a display is actually much larger than your monitor. There are scroll bars on the display window for moving around this area. You should plan to set a few options before you begin drawing: Consider turning on snap-to grid and setting the grid size, font style, and default colors of lines, backgrounds, and fills before you begin. It is usually easier to work with a grid when laying out a display. Symbols in your drawing automatically align themselves with the grid lines or the intersections of grid lines. Grid lines not only make it easier to place objects in the drawing, but it helps keep the objects proportional. You can start with one grid size and then modify it as your work gets more detailed. Select a font and font size for any values, trends, or text boxes you might add to the drawing. Select colors for lines, fills, and backgrounds that are easy on the eyes. For example, if you are projecting on a large video screen, a black background with colored lines is better, but if you are printing, a white background is better. While you are drawing, you can use the zoom feature to zoom in on an area that requires more attention. Zoom out if the drawing is larger than your monitor. Drawing grid The grid is a system of vertical and horizontal lines spaced at regular intervals on the drawing area. Dots are placed at the intersection of the grid lines. The grid helps you align drawing objects. When you move an object to a location on the drawing area, the corners or edges of the object are aligned with the closest grid intersection. This is called snap-to-grid or grid snap. When you turn off grid snap, you can move an object to any location within the drawing area. You determine the interval at which you want the grid lines to be spaced by setting the grid size. PI ProcessBook 2015 User Guide 59

70 Work with a display Set grid size and grid snap 1. In Build mode, open a display. 2. On the Arrange menu, click Grid Size. The Grid Size window appears. 3. In the Lines per Screen Unit box, type or select the number of grid lines per unit of drawing space. The size of a unit as displayed on your monitor varies according to the monitor's resolution and driver software. 4. Select the Snap to Grid check box. Once grid snap is on, any symbols you draw are automatically aligned to the grid. 5. Click OK. Formatting The Snap to Grid command also appears on the Arrange menu. Each symbol you draw and place on a display has attributes that determine how the symbol looks. The fill and line attributes that are currently selected on the Display Window tab of the ProcessBook Preference window are applied to any new drawing symbol. You may configure these attributes for individual symbols or for all selected symbols as a group. See Display Window preferences for details. The Symbol Formatting toolbar contains buttons for formatting fonts, colors, and line styles. PI ProcessBook also includes the older Formatting toolbar to support backwards compatibility. Topics in this section Editable formatting attributes Set font Set line color Set fill color Set background color Set line weight Set line style Set line ends Set formatting paintbrush 60 PI ProcessBook 2015 User Guide

71 Work with a display Editable formatting attributes The following table shows the editable attributes for each symbol. Colors Line Styles Line Fill Background Style Weight Ends Line X X X X Rectangle X X X X Text X X Ellipse X X X X Arc X X X X Value X X Polygon X X X X Polyline X X X Bar X X X X Trend X X X X XYPlot X X X X SQC X X X X Set font To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. 1. In Build mode, open a display, and click the symbol(s) whose font you want to change. 2. On the Symbol Formatting toolbar, click a name in the Font box. When choosing fonts, plan to use fonts that other PI ProcessBook users are likely to have. If another user does not have the fonts you used, PI ProcessBook attempts to match the font to an existing font. However, the match may make it difficult for another user to read the entry. 3. Type or click a point size in the Font Size box. Set line color To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. PI ProcessBook 2015 User Guide 61

72 Work with a display Set fill color 1. In Build mode, open a display, and click the symbol(s) whose line color you want to change. 2. On the Symbol Formatting toolbar, click the Line Color button. Depending on the symbol type, the following elements change to the color displayed on the button. Symbols that display text use the line color to determine the color of the text within the symbol Symbols that have lines (such as ellipses) use the line color to change lines in the symbol 3. Click the arrow on the right side of the Line Color button to display the color palette. 4. Choose from the 16 colors available or click on one of these two buttons: Custom Color Opens the Color window where you can choose additional colors from a color well of options None Disables line color. Setting the line color to None for Pen elements on a trend hides the trace and its associated markers To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. 1. In Build mode, open a display, and click the symbol(s) whose fill color you want to change. 2. On the Symbol Formatting toolbar, click the Fill Color button. The interior color of the selected symbol(s) changes. The Fill Color button is disabled if the selected symbol does not support this property. 3. Click the arrow on the right side of the Fill Color button to display the color palette. 4. Choose from the 16 colors available or click on one of these two buttons: Custom Color Opens the Color window where you can choose additional colors from a color well of options None Disables fill color. Setting the fill color to None shows the display background color. 62 PI ProcessBook 2015 User Guide

73 Work with a display Set background color To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. 1. In Build mode, open a display, and click the symbol(s) whose background color you want to change. 2. On the Symbol Formatting toolbar, click the Background Color button. The background of the selected symbol changes. The Background Color button is disabled if the selected symbol does not support that property. 3. Click the arrow on the right side of the Background Color button to display the color palette. 4. Choose from the 16 colors available or click on one of these two buttons: Custom Color Opens the Color window where you can choose additional colors from a color well of options None Set line weight Disables background color. Setting the background color to None shows the display background color. To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. 1. In Build mode, open a display, and click the symbol(s) whose line weight you want to change. 2. On the Symbol Formatting toolbar, click the Line Weight button. A list of six line weight options appears below the button. 3. Select a line weight. Set line style The thickness of the selected symbol's line weight changes. To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. PI ProcessBook 2015 User Guide 63

74 Work with a display 1. In Build mode, open a display, and click the symbol(s) whose line style you want to change. 2. On the Symbol Formatting toolbar, click the Line Style button. A list of six line style options appears below the button. Options include solid, dash, dot, dash-dot, dash-dot-dot, and none. Selecting None for a trend Pen element hides the trace line, but not the marker. 3. Select a line option. Set line ends The symbol's line pattern changes. To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. 1. In Build mode, open a display, and click the symbol(s) whose line ends you want to change. 2. On the Symbol Formatting toolbar, click the Line Ends button. A list of four line ends options appears below the button. These options determine whether arrows appear at the end of lines. 3. Select a line ends option. The selected symbol's line pattern changes. Set formatting paintbrush To determine what type of formatting is applicable for each symbol, refer to the table of Editable formatting attributes. 1. In Build mode, open a display, and click the symbol(s) whose font, color, or line formatting you want to replicate. 2. On the Symbol Formatting toolbar, click the Formatting Paintbrush button. Double clicking the Formatting Paintbrush button allows you to apply formatting to more than one symbol. To turn off the Formatting Paintbrush selection, click the button again or press ESC. 3. Click another symbol. The formatting of the first symbol is copied to the selected symbol(s). 64 PI ProcessBook 2015 User Guide

75 Work with a display ToolTip Statistics window In Run mode, hover your mouse over a point on a dynamic symbol to display a tooltip with summary statistics. Engineering units are shown next to the value followed by the timestamp paired with the value. If you hover your mouse over a point where there is more than one trace, each trace's data is shown on a separate line. Click Tools > ToolTip Statistics to open the ToolTip Statistics window, where you can select what type of data you want to see when viewing tooltips. The options under Summary Statistics to Show do not affect tooltips for XYPlots. Tooltip statistics are shown for any dynamic symbol that has PI data. The effective time range of the display is used to aggregate the data for these statistics. Time Range and Playback toolbar The Time Range and Playback toolbar allows you to play, pause, loop, and manually scroll a display through a pre-set time period. You can move backwards and forwards in time, alter the display range duration, and revert to the original symbol definitions. Playing back a display can be useful for showing the conditions of various systems and analyzing conditions leading up to a specific time frame or event. The Time Range and Playback toolbar is enabled for the active display and disabled if there is no active display. You can right-click anywhere in the PI ProcessBook toolbar area and show or hide the toolbar from the context menu. The toolbar contains a time tracker that shows the display range, the scroll period that shows the start and end time for the entire playback session, and the following controls: Revert Click the Revert button to restore all the active displays to their configured time ranges. This button is available only when playback is not active. PI ProcessBook 2015 User Guide 65

76 Work with a display Back or Forward One Time Period Click the One Time Period or One Time Period Forwards to adjust the display range back or forward one time period for the active display or all active displays, if synchronized. See Display range for details. When you use these buttons to move beyond the start or end time of the scroll period, the scroll period expands to contain the display range. These buttons are available only when playback is not active. Time tracker The time tracker shows the Display range and available Scroll period. Go to Current Time Click the Go to Current Time button current time (*). to move the display range so that its end time is the This action does not change the dimensions of the display range. This button is available only when playback is not active. Change the Display Range Click the Change Display Range button or double-click the display range to open the Change Display Range window and change the time range of the PI ProcessBook display. See Change Display Range window for details. Synchronize Click the Synchronize button to enable synchronization when one or more PI ProcessBook displays are open. When synchronization is enabled, time-related actions that you perform through the Time Range and Playback toolbar affect every display that is currently open and every new display that you open. Synchronization is disabled by default. Once on, synchronization remains enabled even if you close all displays. Time range actions that you make from the PI ProcessBook Time Range toolbar or a button on the standard toolbar are not synchronized. Only symbols that are already on the active display are synchronized. Symbols that you add to the display are not synchronized until the next time the display range changes. Synchronization is temporarily suspended during playback. The displays are resynchronized when playback is paused or stopped. 66 PI ProcessBook 2015 User Guide

77 Work with a display Repeat Click the Repeat button Scroll period. Stop Click the Stop button to make the playback repeat each time it reaches the end of the to end playback. This action resets the position of the Time Tracker to the far left and changes the Pause/Play icon to Play. Pause/Play The Pause/Play button drives the playback feature. ThePlay button changes to the pause icon when a display is in playback mode. When playback is paused, the button shows the play button. The playback rate is reduced if PI ProcessBook cannot retrieve display data quickly enough to keep up with the desired playback speed. When this occurs an information icon appears on the right side of the time tracker. Fast Forward Click the Fast Forward button to accelerate the rate of playback. Each successive click of Fast Forward doubles the rate at which the display plays back. The first click doubles playback speed, then advances to 4x, 8x, 16x, and 32x the playback speed. An additional click returns the playback to the default playback speed. Click Play to resume normal speed playback. The playback continues from the current position rather than starting from the beginning. Options Click the Options button to open the Scroll Options window. Calendar Hover at either end of the scroll period to see the Calendar icon. Click the scroll range while the calendar icon is displayed to open a calendar to set that end of the scroll period. The calendar accepts any time string format supported by PI and returns dates and times using Windows time configured with the current regional settings of the client computer. Topics in this section Scroll Options window Scroll period Display range PI ProcessBook 2015 User Guide 67

78 Work with a display Scroll Options window Use the Scroll Options window to set the default behavior settings for the Time Range and Playback toolbar. These defaults apply to the active display or all displays, if synchronization is on. The defaults are retained when PI ProcessBook is closed and re-opened on a per user basis. The following settings are controlled through this window: Display Range Use any accepted PI time input parameter to set the length of the display range. See PI time and Display range for details. Scroll Period Use the spin box or calendar controls to select start and end dates and times. See Scroll period. Refresh Rate select the number of seconds between updates of the display that is being played. Speed Select the rate at which the display plays back. The speed is expressed in units per second. Speed can be expressed as milliseconds, seconds, minutes, hours, days, and months, and must be smaller than the display range. Scroll period The scroll period marks the earliest and latest time for which you can manipulate or playback a display. 68 PI ProcessBook 2015 User Guide

79 Work with a display Topics in this section Scroll period constraints Scroll period time format Change the scroll period Scroll period constraints The scroll period must be larger than the display range. The scroll period end time must be after the scroll period start time. An error icon appears to the far right of the time tracker if you violate either of these conditions. Scroll period time format The displayed time format of the scroll period depends on its duration. If the scroll period is less than 24 hours, then the start and end time is shown in hours and minutes. If the scroll time is 24 hours or more, then the start and end time is shown as a date. The time zone of PI ProcessBook determines whether the time is shown in the client time zone or the server time zone. Change the scroll period There are several ways to change the scroll period. Hover the mouse next to the left or right arrow of the scroll period to change the mouse icon to a calendar icon. Click the icon to open the calendar where you can modify the dates. Click the Scroll Options button window for details. to open the Scroll Options window. See Scroll Options Display range The display range represents the time duration shown on the trend symbols, or for a bar or value, the end time of the display range is the symbol time. The display range must be shorter than the scroll period. Topics in this section Change the display range Change Display Range window Move the display range during playback PI ProcessBook 2015 User Guide 69

80 Work with a display Change the display range There are several ways to change the display range. Click the Change Display Range button or double-click the display range to open the Change Display Range window. See Change Display Range window. Double-click anywhere in the display range to open the Change Display Range window. Click and drag one of the display range thumbs. Click the display range and rotate the mouse wheel. Click the Playback Options button Options window. to open the Scroll Options window. See Scroll Click the display range and use the up and down arrow keys to change the size of the display range. Results A display must be reverted to re-establish any build time configuration time ranges for individual symbols. Change Display Range window Use the Change Display Range window to specify the display range. Rules for time settings: The start and end time boxes support all time string formats recognized by PI. You can edit the times manually. The dynamic time strings, such as *-1h, that you set are added to the drop-down list. Static time strings, such as 1-Jan-2009, are not added to the list. Each drop down list saves the ten most recently used values. Settings are stored per user. This button is available only when playback is not active. 70 PI ProcessBook 2015 User Guide

81 Work with a display Move the display range during playback The location of the display range on the scroll bar tracks the time of the playback on the display. The display range always advances from left to right from its initial start position while playing. There are several ways to move the display range while you play back a display. Use the Time Tracker arrow keys to move the display range current position. Click the scroll bar on either side of the display range to move the display range to the position where you click. Click anywhere in the display range and use the left and right arrow keys to move the display range back and forward across the scroll period. Time Range toolbar The Time Range toolbar is used for working with dynamic symbols. This toolbar is hidden by default for new installations of PI ProcessBook 2012 and later. We recommend you use the Time Range and Playback toolbar to manage time in a display. In general, the commands on this toolbar affect only the symbols selected on the display. If no symbols are selected, all symbols are affected. This toolbar, which must be used in Run mode, contains three buttons: Revert Returns the trend or other dynamic symbol to its original setting. Change Time Range Opens a window to set new, temporary start and end times. For Bars, Values, and Multi- State symbols you can only set an end time. Scroll Bar Scrolls through time values. Topics in this section Revert time range Change the time range Use the scrolling time range PI ProcessBook 2015 User Guide 71

82 Work with a display Use time forward and back buttons Set time range for future trends Revert time range Discard any of the changes you have made to the time range of a trend or the effective time of a Bar, Value, or Multi-State symbol and return it to its saved setting. In Run mode, click View > Revert, or Click the Revert button. Change the time range The Time Range command lets you enter new starting and ending times for dynamic symbols. When you specify a time range for a single-time dynamic element, such as a Multi-State symbol, bar or value, only the end time is used. The time represented on your display is the time relative to the PI Data Archive server, unless you have selected the client time zone setting for your display. If the PI Data Archive server to which you are connected is in a different time zone, time on your display represents the server time zone, not the local one. 1. In Run mode, select the dynamic symbol or symbols for which you want to change the time range. If no symbols are selected, the time range change affects all dynamic symbols on the display. 2. Click the Time Range button on the Time Range toolbar, or Click View > Time Range. The Change Time Range window opens, allowing you to change the time span for a trend or plot, or the effective time for a bar, value, or Multi-State symbol. 3. Select new starting and ending times from the drop-down lists or define your own starting and ending times. 72 PI ProcessBook 2015 User Guide

83 Work with a display Time ranges can be relative, absolute, or combined. 4. Click OK. The selected elements change to reflect the new time range. Use the scrolling time range 1. In Run mode, select the dynamic symbol or symbols for which you want to change the time range. If no symbols are selected, the time range change affects all dynamic symbols in the display. 2. On the Time Range toolbar, click the forward or backward Scroll Time button, or Click and drag the Scroll Time slider, or Click the space on either side of the Scroll Time slider to increment or decrement by a time span. If the slider is dragged, a tooltip is updated with the end time that is applied when you release the mouse button. 3. Release the mouse button. Selected symbols are refreshed with the new time range. You can scroll the time for all items in a display or selected items. If no trend is included in the selected items, the scroll buttons are disabled. Use time forward and back buttons Use the time backward and forward buttons to scroll the time range forward or backward. 1. Click on the desired symbols with the Run Mode pointer. 2. Click the Time Forward or Time Backward button. Trends scroll by the time range specified in the trend definition. When you select multiple trends, each trend maintains its time range as it is scrolled. If you select a trend and a dynamic element such as a value, the non-trend symbol scrolls by the time range specified in the first trend's definition. For example, if the trend displays data from 1:00 to 4:00 (three hours) and the value has a timestamp of 5:00, scrolling backward shows trend data from 10:00 to 1:00. The value's timestamp also changes by three hours (2:00). PI ProcessBook 2015 User Guide 73

84 Work with a display Run mode pointer Use the Run mode pointer for opening and executing displays and their associated commands. To obtain a Run mode pointer, on the Drawing toolbar, click the Run button, > Run. The mouse cursor appears in the shape of a small arrow., or click Tools You can choose Run mode as your preferred mode of operation by selecting the Prefer Run Mode check box in the General of the ProcessBook Preferences window. This is a helpful preference if you spend most of your time observing or analyzing displays rather than building them. See General preferences for details. Set time range for future trends To set trends with an end date in the future, enter an end time of the present (*) plus an amount of time, such as 4 hours or 8 days. These trends update if they are less than the maximum update time range limit. The default update time range limit is 7 days, but you can change that setting in the procbook.ini file. See PROCBOOK.INI for details. A trend can also be scrolled into the future using the time range buttons, but then it does not update. Layers within displays You can divide a display into layers containing one or more symbols. This feature could be useful in building a complex display with several systems depicted (electrical, HVAC, etc.). If you separate systems by layer, you can view any one of the layers by making the other layers invisible. Before creating a display you should determine how you might implement layers. When a display has no layers, all new symbols are added to the base layer of the display, thus removing the control afforded by using a layers-based strategy. A layer can be visible or invisible in Run mode. Layers are always visible in Build mode. You can move symbols between layers or remove them from a layer. Add, make visible, restack, and lock layers while ProcessBook is in either Run mode or Build mode. Delete layers only when ProcessBook is in Build mode. Topics in this section Create layers Assign symbols to layers Layers and composite symbols Active Layers status bar 74 PI ProcessBook 2015 User Guide

85 Work with a display Create layers 1. Open a display. 2. Click the Layers toolbar button, or Double-click the Layers icon in the status bar, or Click View > Layers. The Layers window appears. 3. Click the New Layer button to open the New Layer window. A default name comprised of the word Layer prefixed to the layer number appears. The layer number does not necessarily match the index number; it is simply the next unused integer in the list. A new layer is added to the end of the collection. Its index is one higher than the previous high index number. All symbols added to this layer are displayed over symbols on lower indexed layers. 4. Click OK to return to the Layers window. Index Specifies the index number of the layer. The index is used in determining the display order (Z Order) of overlapping symbols. A layer with a lower index number is lower in PI ProcessBook 2015 User Guide 75

86 Work with a display the stack than one with a higher number. Higher layers may obscure symbols in lower levels. Count This is a read-only value that contains the number of symbols on a layer. A composite symbol is counted once and each of its subordinate individual symbols is also counted. Up/down arrows Buttons at the right side of the window box are used to move the relative position of one layer to another within a display. As a layer is moved down the list, its index number becomes larger, and vice versa. Symbols on layers with higher index numbers may hide or cover symbols with lower-index numbers. Locked layers cannot be reordered. 5. Select the appropriate check boxes: Visible Makes the elements in the layer visible in Run mode. New layers are visible by default. Active Accepts all new symbols as you add them to the display. Inactive prevents symbols from being added automatically. New layers are Active by default. Locked Prevents you from adding symbols to a layer. Existing symbols on locked layers cannot be cut, copied, pasted, deleted, or moved. New layers are not locked by default. 6. Repeat steps 3-5 as needed. 7. Click OK to accept changes and close the Layers window. Assign symbols to layers If you have at least one layer in a display, you can assign symbols to it. 1. Select a symbol, right-click, and select Assign Layers. The Assign Layers window appears and displays all of your existing layers. 76 PI ProcessBook 2015 User Guide

87 Work with a display 2. Select or clear the checkbox next to a layer name to add or remove the selected symbol from a layer. If a layer name is grayed out, the layer is locked and you cannot add or remove symbols. You may add the same symbol to more than one layer. 3. Click OK. Layers and composite symbols To link symbols and create composite symbols click Arrange > Group, or click the Group button on the Layout toolbar. The symbols may be on different layers when they are grouped. Assign a composite symbol to any layer(s) regardless of its component symbols. You can not group symbols on locked layers into a composite symbol, but the layers may be locked after the symbols are grouped. You can not delete a composite symbol that contains symbols on locked layers, however, you can delete an unlocked layer. Normally, a symbol existing only on one layer is deleted if the layer is deleted, but when the symbol is inside a composite symbol it is not deleted. It stays in the composite symbol. If a composite symbol is hidden, all its parts are hidden. If the composite symbol is visible its individual parts may still be hidden if the layers they are assigned to are hidden. Because you can not individually select the parts of a composite symbol you must first use the Ungroup button to separate them in order to change their layer assignments individually. Active Layers status bar The Layers icon on the status bar shows whether or not the display has more than one layer. This icon appears in the status bar at the bottom of your application, indicating one or more layers in the display currently in focus. Double-clicking the icon displays the Layers window. PI ProcessBook 2015 User Guide 77

88 Work with a display If no layers have been defined, the icon appears with a slash through it. Hovering the mouse over the icon displays a tooltip with the names of any active layers, beginning with the top layer. Active Layers Status Bar Area (with Tooltip) Migrating displays to another PI Data Archive server When you want to use an existing tag with a different PI Data Archive server, PI ProcessBook attempts to locate the correct tags. Each ProcessBook saves the tag information for all of the symbols it contains. Beginning with PI SDK 1.3.6, when you use a PI ProcessBook symbol with a PI Data Archive server other than the one for which it was created, the PI Data Archive server is added automatically if it is discoverable on the network. If the PI Data Archive server is not discoverable, then PI ProcessBook prompts you to select a new PI Data Archive server. Once the new PI Data Archive server is selected, PI ProcessBook searches the database for a matching tag ID. If a match is found, PI ProcessBook retrieves the tag name associated with the tag ID and compares the tag name with the saved tag name. If the tag names are the same, the value is shown in the entry. If the tag names are different, PI ProcessBook searches the database for the tag ID of the saved tag name. If a match is found, the value is shown in the entry. If a match is not found, PI ProcessBook uses the tag ID saved with the ProcessBook regardless of the different tag names. If no tag ID or tag name is found in the database, PI ProcessBook displays a message informing you of the missing tag. This behavior is governed by the value of PB2TagResolution, located in the procbook.ini file's Data Manager section. PB2TagResolution can take the following values: 0 1 [Default] the Point ID is used to match a missing tag before the stored point name Uses the tag name before checking Point ID. This mimics behavior of older version of PI ProcessBook that are based on the PI API. See PROCBOOK.INI for information on procbook.ini. 78 PI ProcessBook 2015 User Guide

89 Work with a display AF Modeler and AF Display Builder displays Previous versions of PI ProcessBook used the AF Modeler add-in for building displays using AF elements. The AF Modeler add-in only worked with AF 1.x servers. PI Processbook used the AF compatibility layer for the AF Modeler with AF 2.x and later, which slowed performance. PI ProcessBook 2014 introduces the AF Display Builder add-in, which provides new features for building AF displays. The AF Display Builder add-in does not require the compatibility layer; however, it only works with AF 2.x and later servers. To use the AF Display Builder, you must have read/write access to the AF database and the AF elements or element templates that you will associate with AF-based symbols in PI ProcessBook. In PI ProcessBook 2014 and later, if you open a display that was made with the AF Modeler, that display is automatically converted to use the AF Display Builder add-in. This conversion removes the dependency compatibility and improves performance. You can then use the AF Browser and the AF Properties pane to create and add AF-based symbols for your displays. If you do not want to convert your AF Modeler displays to the new functionality, disable the AF Display Builder add-in before you open the displays in PI ProcessBook. See Disable the AF Display Builder add-in. Save the converted display to add it to newer versions of PI AF. PI ProcessBook 2014 does not save displays created using AF Modeler to newer versions of PI AF. Once you have saved a converted display, you cannot revert to the AF Modeler format. Disable the AF Display Builder add-in The AF Display Builder add-in was introduced in PI ProcessBook By default, this add-in is enabled. If you do not want your AF Modeler displays converted to the AF Display Builder format, then disable the AF Display Builder add-in before opening your display. Leaving the AF Display Builder enabled will cause your AF Modeler displays to be automatically converted when you open them. A display cannot be reverted to the AF Modeler format after you save the converted display. 1. In the ProcessBook toolbar, choose Tools > Add-In Manager. The Add-in Manager window opens. 2. In the list of available add-ins, select AF Display Builder Add-in. 3. In the Load Behavior area, clear the Loaded/Unloaded check box and then click OK. PI ProcessBook 2015 User Guide 79

90 Work with a display 80 PI ProcessBook 2015 User Guide

91 Symbols in a PI ProcessBook display Trends Symbols are the building blocks of a PI ProcessBook display. Dynamic symbols allow you to view live data in your display. These symbols are updated in real time as PI ProcessBook receives updates from your PI Data Archive server. The maximum number of dynamic symbols per display is 278,343. Static symbols allow you to embed graphics, text, lines, and other images in a display. Topics in this section Trends XYPlots Additional dynamic symbols Multi-state symbols Static symbols A trend is a dynamic symbol that lets you view values plotted against time. Trends can show the value of one or more data items over a time period. Trends are typically used to display time series data, though they may also include non-time series data as well. Some components of trends include: Traces Lines drawn on a trend to represent a series of data points from a data item. Pens Formatting components used to determine the presentation of data lines (traces) on trends. Plot Title The title of the trend being configured. The plot title can be blank, but a title is supplied by default. Grid lines Used to mark intervals along the time and value scales. If the Plot Time continues through the current time, the trend updates as information changes, unless the length of the overall time period exceeds the limit set by your System Administrator. The default limit is 7 days. This value is configurable. Topics in this section Create a trend PI ProcessBook 2015 User Guide 81

92 Symbols in a PI ProcessBook display Edit a trend Define Trend window Configure Trend Scale Trend analysis tools Change time range How trends refresh Trend appearance Ad hoc trends OpenVMS trends and graphics Add AF attributes to trends Create a trend 1. Open a display. 2. On the Drawing toolbar, click the Trend button, or Click Draw > Trend. The mouse pointer changes to the Trend pointer. 3. Click in the display where you want to add the trend and drag the pointer to form a rectangle into which the trend will be placed. When you release the mouse button, the Define Trend window appears. See Define Trend window. 82 PI ProcessBook 2015 User Guide

93 Symbols in a PI ProcessBook display 4. In the Plot box, type a name. 5. (Optional) Click the New Plot button if you want to build a trend with multiple plots. 6. In the Tags in Plot box, type the name of the tag, or Click the Tag Search button to locate a tag, or Click the Tag Search arrow to see more search options: Tag Search PI Calculation (data set) ODBC (data set) AF2- launches the Select AF Attribute window, from which you can search an AF database for elements and attributes. Element Relative - launches the Element Search window from which you can search an AF database for elements. Your selections for tags, data sets, or attributes appear under Tags in Plot. 7. If you manually enter tag names, select the appropriate PI Data Archive server from the Server drop-down list. Normally, the default PI Data Archive server is listed. 8. You can rearrange, add to, or delete the selected tags by clicking one of the buttons above the Tags in Plot box. If you have an ODBC dataset column with a PI Tag placeholder or a PI Summary dataset column selected for the plot, the Custom Placeholder button is enabled. PI ProcessBook 2015 User Guide 83

94 Symbols in a PI ProcessBook display 9. Click the Custom Placeholder button to change the PI Tag used as the placeholder for the selected trace. PI ProcessBook allows you to create custom placeholders for a symbol based on a summary data set or a PI tag placeholder in an ODBC data set. Placeholders are not allowed for expression data sets. The Custom Placeholders button in symbol definition windows allows you to specify different PI tags for a PI Summary data set or ODBC data set with a PI tag placeholder. The change applies only to the configured symbol. See Add or edit placeholders for details. 10. Under Scale, select Single Scale or, if you have more than one trace, you may select Multiple Scales. The multiple scales option shows a value range for each trace. There is only one time scale. 11. Consider checking the following check boxes: Logarithmic to display the data in a logarithmic scale. If you have multiple scales, you may set this option differently for each trace. This option is disabled for digital tags. You may use logarithmic and non-logarithmic scales for traces in the same trend when you select Multiple Scales. In this case, the minor grid lines associated with a logarithmic plot may confuse the plot. You can turn off the minor grid lines by setting the vertical minor grid color or line style to none. Regression Line determines whether a regression line is drawn for a selected trace. 12. In the Max and Min drop-down lists, select Autorange or Database or enter the values to determine the value scale range. Min Settings: Autorange The trend displays with the value scale starting at the closest available major axis. If the minimum is Autorange and the maximum is not, the scale starts at the lowest data value in the trace (not on a major axis) and ends on the closest major axis. Database The tag's Zero attribute is used to specify the minimum plot value. This value can be negative is the value of the tag is negative. 0 (absolute value) The value you type is used as the first value on the value scale. Max Settings: Autorange The trend displays with the value scale ending at the closest available major axis. If the maximum is Autorange and the minimum is not, the plot starts on the minimum value and ends on the largest trace value (neither min nor max will be on a major axis). Database 84 PI ProcessBook 2015 User Guide

95 The tag's Zero + Span attributes are used to specify the maximum plot value. 0 (absolute value) The value you type is used as the value scale maximum. 13. From the Format drop-down list, select the number format for the scale. Database is the default format. This number format is also applied to legend, cursor, and tooltip numbers. Database Database format uses the displaydigits PI Point attribute to determine how many decimal places to show. If the length of the number exceeds the displaydigits value, scientific notation is used. PI ProcessBook trims trailing zeroes that follow a decimal point. The Database format option is intended for use with PI Tags only. General Shows all significant digits for a number except trailing zeros. If the absolute value of the value is greater than 1e+7 or less than 1e-5, the format will switch to use scientific notation. Scientific Most useful with very large numbers. The scientific format used for trends displays in the format: 0.00E+00. Custom (#,##0.00, 0%) Allows you to enter your own number format. See the Table of Format Values for examples. 14. Under Plot Time, from the Start and End drop-down lists, select a time. An asterisk (*) represents the current time. You can also manually enter a valid PI Time string. 15. In the Style drop-down list, select Full time stamp, Partial time stamp, or Relative time stamp to indicate how time is displayed on the time axis. 16. Click OK. PI ProcessBook allows you to create custom placeholders for a symbol based on a summary data set or a PI tag placeholder in an ODBC data set. Placeholders are not allowed for expression data sets. The Custom Placeholders button in symbol definition windows allows you to specify different PI tags for a PI Summary data set or ODBC data set with a PI tag placeholder. The change applies only to the configured symbol. See Add or edit placeholders for details. Topics in this section Build a trend with multiple plots Move a plot Delete a plot within a trend Using logarithmic scales in trends Build a trend with multiple plots Symbols in a PI ProcessBook display For new trend symbols, you can add multiple plots at the same time so that many trends are created, configured and placed on the display without dragging additional symbols on the PI ProcessBook 2015 User Guide 85

96 Symbols in a PI ProcessBook display display. Once the plots are created they are no longer associated in any way and are configured, moved, and sized individually. 1. Follow the steps to Create a trend. 2. To create additional plots, click the New Plot button and select tags. Repeat as necessary. To view the tags you have selected, you can select each plot name in the Plot box. 3. To adjust the arrangement matrix for the plots you are creating, click the Layout tab (see Layout tab). These matrix options are available only when you create the trend and cannot be edited later. However, you can revise the traces and other trend properties on each plot individually. Move a plot If you have created more than one plot in the trend, you can move each plot separately. 1. In Build mode simply click the plot you want to move. 2. Selection handles appear around the plot. Use these handles to drag the plot to its new location. Delete a plot within a trend 1. In the Define Trend window, click the General tab. 2. In the Plot drop-down list, select the plot you want to delete, and then click the Delete Plot button. This button is only available while the symbol is being created. After you have drawn a trend, and you want to delete a plot, you can select the plot and then press DELETE. Using logarithmic scales in trends In the Define Trend window, there is a checkbox for logarithmic scales. This option is disabled for digital, timestamp and integer tags. If the scale is Single, the option is disabled if any digital or integer tag is present. If the scale is Multiple, the option is only disabled for digital and integer tags. See Define Trend window. Use logarithmic and non-logarithmic scales for traces in the same trend when "Multiple Scales" is selected. In this case, the minor gridlines associated with a logarithmic plot may confuse the 86 PI ProcessBook 2015 User Guide

97 Symbols in a PI ProcessBook display plot. You can turn off the minor gridlines by setting the vertical minor grid color to none. This is discussed in Trace Format tab. The log of zero and negative values is plotted similarly to bad data. The graph shows an X where the invalid log values begin. A cursor running over the negative values displays Invalid Log. If the current trace value is zero or less, the legend displays Invalid Log as the current value. Edit a trend Use the Define Trend window (see Define Trend window) to edit an existing trend. To launch this window do one of the following. In Build mode, double click a trend Select a trend and click the Item Definition toolbar button Select a trend and click Edit > Selected Item Define Trend window In the Define Trend window, you can specify tags; the colors and line styles for traces, legends, and backgrounds; and how much tag information is displayed with a trend. Use the Formatting toolbar to make color or line formatting or font changes. Trends are formatted according to certain defaults. Using the Trend preferences, you can create your own default format for new trends. You can set options like line colors, background, and marker shapes, and you can set the types of point information included with a trend. The Define Trend window has a General tab where you create a trend, and the following additional tabs for formatting and layout: Display Format Options for the elements to be included in the trend. Trace Format Orovides an alternate way to choose colors and line styles for each trace (plot line) as well as the axes, background, and text. Layout Options determine the arrangement of rows and columns for multiple plot trends. This tab only appears when you first create a trend symbol. Topics in this section Display Format tab Trace Format tab Layout tab PI ProcessBook 2015 User Guide 87

98 Symbols in a PI ProcessBook display Display Format tab Legend group box Select or clear check boxes for displaying the tag name, server name, description, value, and engineering units. Your choices are reflected in the sample trend at the bottom of the window. The information that can fit in the legend is determined by the size of the trend. Consequently, not all of the information in the legend may be visible. If the width of the legend is more than 50 percent of the width of the trend, the legend does not display. If the length of the text in the legend is longer than the total height of the trend, the items on the bottom are not shown. Display group box Select or clear the following check boxes. The sample trend reflects the changes you make. 88 PI ProcessBook 2015 User Guide

99 Symbols in a PI ProcessBook display Plot Title Vertical Scale Inside Axis Draws the value scale inside the plot area Grids Shows grid lines on the trend Markers When selected, markers indicate data points on the trend. If the Markers box is not selected, three markers appear on each line to help you match a line to a tag. Trend orientation Select one of the three options at the top of the window: End Time at right (horizontal), End Time at top (vertical), or End Time at bottom (vertical). This feature allows you to orient your trend in a horizontal or vertical direction. Trace Format tab Use the buttons on the Symbol Formatting toolbar to configure plot elements such as pens, traces, text, and background. See Formatting and Traces for details. The Trace Format tab gives you an alternate way to update formatting changes. PI ProcessBook 2015 User Guide 89

100 Symbols in a PI ProcessBook display Plot Element drop-down box Select from a list of available traces and other plot elements. Element Format group box Select formatting options for the selected plot element. Your choices are reflected in the sample trend at the bottom of the window. Layout tab The plot arrangement in a multi-plot trend is established by setting up the number of rows and columns of plots in the Layout tab. The Layout tab only appears when you initially create a trend (see Create a trend). After the layout is set, you cannot revise it because the plots are no longer associated when the symbol is created. However, individual plots can be moved on the display in Build mode. To revise the proposed plot arrangement matrix: 90 PI ProcessBook 2015 User Guide

101 Symbols in a PI ProcessBook display Under Plot Arrangement, select the number of rows and columns you want. The following example shows four plots, to be arranged in 2 rows of 2 columns each. Tab past the matrix to see the sample of your new selection display in the Preview area. Configure Trend Scale The Trend Scale window provides easy access to the value scale settings for each tag in a trend, SQC chart or XYPlot. If the plot uses a data set, only the Autorange and Absolute options are available for the Maximum and Minimum scale settings. PI ProcessBook 2015 User Guide 91

102 Symbols in a PI ProcessBook display 1. In Run mode, double-click the plot's value scale to open the Trend Scale window. In PI ProcessBook you can also click View > Trend Scale. This menu object is not available in PI ActiveView. 2. Click Single Scale or Multiple Scales. 3. If you are using multiple scales, then select the tag for which to set the scale options from the Tags drop-down list. 4. Select Autorange, Database, or Absolute options for the Maximum and Minimum values of the scale. Autorange Sets the value scale using the minimum and maximum tag values between the trend start time and end time. Database Sets the value scale using the tag attribute values in the Point Database. Zero is the minimum. Zero + Span is the maximum. See the PI Data Archive Reference Guide for more information on tag attributes. Absolute Allows you to enter a custom value for the value scale of a tag. Enter the value in the adjacent box. 5. If you have selected the Absolute option, then type in the Maximum and Minimum values of the scale in the adjacent boxes. 6. Click OK. Modifications made to a trend through use of this window do not affect the stored settings of the trend. To return the trend scale to its original settings, click Revert on the context menu. Trend analysis tools PI ProcessBook provides a number of tools for analyzing or monitoring the data in a trend, SQC chart, or XYPlot. Trend Zoom Lets you use the mouse to drag a box around the data you would like to see more detail. SeeReduce or enlarge a trend time range. Trend Expand Temporarily expands a trend symbol so that it occupies the entire display window. See Expand a trend. Trend Cursor Shows the value of the plotted tags at a specific point in time. SeeTrend cursor. 92 PI ProcessBook 2015 User Guide

103 Symbols in a PI ProcessBook display Topics in this section Drag Zoom Reduce or enlarge a trend time range Expand a trend Trend cursor Drag Zoom Drag Zoom lets you contract the time scale of a trend. 1. With the Run mode pointer, click an area in the trend at which you want a closer look. 2. Drag the pointer diagonally to create a rectangle. 3. When you release the mouse, the trend displays the data within the rectangle. Reduce or enlarge a trend time range To reduce or expand a time range, click to zoom in or out by a factor of 2. For example, if your PI ProcessBook trend time range is 8 hours, zoom in to divide the time range by 2 to display the trend with a 4-hour time range. Zoom out to multiply the time range by 2, which displays the trend for a 16-hour time period. Click Revert to remove the time range. The zoom in and out buttons might not appear on a small trend. Double-click a trend to expand its size and display hidden buttons. If there are no trend cursors, the Trend Zoom 2x command zooms in or out of the last portion of the time period. For example, if the initial time range is 60 minutes and you select Trend Zoom 2x In, the trend displays the last 30 minutes. Trend Zoom 2x Out displays 120 minutes, adding 60 minutes to the beginning of the trend. When a trend cursor is displayed, the command uses the trend cursor as the center of the zoomed trend. If several cursors are used, the last one set is used as the center of the zoomed trend. Expand a trend Double-click a trend in Run mode to redraw the trend so that it occupies the entire display window. Double-click again to reduce the trend to its original size. PI ProcessBook 2015 User Guide 93

104 Symbols in a PI ProcessBook display While the trend is expanded, the Drawing toolbar is disabled. If you switch to another display, the Drawing toolbar will work there. All descriptive information (title, tag descriptor, tag value) is shown on an expanded trend. Trend cursor A trend cursor lets you read tag values for a particular time. When you select a trend cursor, a vertical line indicates the cursor position. The box at the top of the line indicates the value and status. The box at the bottom displays the time and date of the value. On vertically-oriented trends the cursor is horizontally oriented. You may display several trend cursors at one time. A trend does not update while trend cursors are visible. If the trend is too small, the Trend Cursor command is disabled and the mouse pointer does not change when you move over the left axis. You can expand the trend by double-clicking it. Trend cursors can be automated. Topics in this section Add a trend cursor Remove a trend cursor Add a trend cursor 1. Notice whether the time scale appears at the bottom and the time stamp appears at the upper right. If not, the trend rectangle may be too small to use trend cursor. Enlarge the trend. If the time stamp does not appear, reformat the display format to show it. 2. With the Run mode pointer, click the Trend Cursor button. A cursor appears at the right edge of the trend. When the mouse pointer changes to a double-headed arrow over the trend cursor, click the vertical line and drag left to position the trend cursor, or Click View > Trend Cursor. An indented icon in front of the command indicates that trend cursors are on. 3. Move the mouse pointer over the left axis of the trend. The pointer changes to a trend cursor symbol. As you drag to the right, a new trend cursor is added to the trend. 4. Move the trend cursor back and forth across the trend by dragging it. As you move it, the time stamp, status, and value appear in a box at the top right of the trend. 94 PI ProcessBook 2015 User Guide

105 When you release the cursor, the values appear in boxes at the top and bottom of the cursor. You can add additional cursors by grabbing the trend cursor icon at the left axis. Remove a trend cursor Symbols in a PI ProcessBook display Click the Trend Cursor button, -or- Click View > Trend Cursor, -or- Revert the trend. To remove one trend cursor but not all of them, click the trend cursor and drag it to the left or right until it moves off of the trend. Change time range Scroll time ranges directly on a trend by using the Step Forward or Backward buttons on the time scale. These time changes are not saved with the symbol. Use the Revert button configured settings., located next to the time scale, to return the trend to its If the trend is too small these buttons may not appear. Expand the trend's size to display hidden buttons. You can also use buttons on the Time Range toolbar to modify time configurations settings. How trends refresh If the end time of the trend is current (*) or future (for example, *+1h), and trend cursors are off, then the trend updates whenever information is sent from the machine instrumentation to the PI Data Archive server at a configurable update rate (5 seconds by default). A dashed line on the plot time grid of the trend indicates the current time and that the plot is updating. If the information has not changed at the instrumentation sensor, the trend shows a flat line from the last update to the current time (the dotted line). You can force a refresh by clicking the Revert button. If desired, a PI System Manager can change the seven-day updating time range limit to another interval on your computer. PI ProcessBook uses an algorithm to identify the peaks and valleys of data values so that no information is lost when the trend time range is large. It ensures that the plot is not under- or over-sampled and that the correct amount of information is sent from the PI Archive. PI ProcessBook 2015 User Guide 95

106 Symbols in a PI ProcessBook display Unlike data from a PI Data Archive server, data from an ODBC data set refreshes according to a configured refresh rate. Trend appearance A trend appears according to the format established in the Trend Preferences. Click the Trend Formatting button to override this format. Typically, the title of the trend appears at the upper left, and the current timestamp appears at the upper right. The selected tag names, current or end value, and engineering units appear in the legend opposite the value scale. Topics in this section Grid lines and labels Value scale grid lines Single and multiple scales for the vertical axis Time scale grid lines Traces Markers Grid lines and labels Trends are formatted according to certain defaults. Use the Trend Elements tab in the ProcessBook Preferences window to create default formats for new trends. You can set options like line colors and marker shapes, and set the types of point information included with a trend. See Trend Elements preferences. Topics in this section Grid lines Grid line labels Grid lines Horizontal and vertical grid lines align with even units (whole numbers) on the scales. Grid lines for the value scale line up with whole numbers at intervals of 1, 2, 5, 10, or powers of 10 times those intervals. Grid lines for the time scale line up with time intervals such as weeks, days, hours, minutes, and so on. The traces then scroll as time passes on an updating trend. Grid line labels Configure the labels for the value scale using single or multiple scales. You can place these labels on either the inside or outside of the value axis: Single Scale Multiple Scales The union of the ranges for all traces appears in the label. The range for each trace in the trend appears in the label. 96 PI ProcessBook 2015 User Guide

107 Symbols in a PI ProcessBook display Configure the labels for the time axis using a full time stamp, partial time stamp, or a relative time stamp: Full timestamp Partial timestamp Relative timestamp Displays a complete time stamp for the start and end times. The time range of the trend is in the middle of the time axis. Labels most grid lines in the units of the time range. Displays the full time stamp for the end time of the trend at the top right edge of the plot. Displays the offset from the end time limit in weeks, days, hours, and so on. and the full time stamp for the end time of the trend at the top right edge of the plot. Labels for the grid lines appear unless the trend rectangle is too small. Value scale grid lines Grid lines are shown in value scale intervals of 1, 2, 5, 10, or powers of 10 times those intervals. The value axis minimum and maximum are set using one of four methods. Topics in this section Autorange scale Database scale Logarithmic scale Manually defined scale Autorange scale The value scale is determined by a calculation based on minimum and maximum values in the trend. As new data are received from the server, the high and low values may change, and the scale is recalculated accordingly. For example, if the original scale ranged from 5 to 100, but the new data has a high of 103, then the new plot shows a range from 5 to 105 (the nearest number divisible by 5 and larger than the high value). If more than one tag is plotted on a single scale, the value scale is calculated from the highest and lowest values for all the tags. Database scale If the scale is set to Database, the range is the same as the limits for the point on the server. The minimum value is termed zero, and the maximum value is the sum of the zero value plus the span value. For example, suppose the tag attributes for a point are Zero = 3 and Span = 6. The plot range therefore is based on making the minimum and maximum values 3 to 9. PI ProcessBook 2015 User Guide 97

108 Symbols in a PI ProcessBook display Logarithmic scale If you prefer a logarithmic scale, select this option. This option is disabled for digital, string, or time stamp tags. Manually defined scale When the scale is configured, an arbitrary minimum and maximum scale value can be entered. Single and multiple scales for the vertical axis Value scales are labeled whenever there is enough room. Configure these labels with either single or multiple scales. For a single scale label, the union of the ranges for all traces appears. For multiple scale labels, the range for the first trace appears next to the value axis. Ranges for the other traces appear in increasing distance from the axis in the order the tags are listed in the trend legend. On a single scale trend, traces that contain only one value (a flat line) or have no data are governed by special scaling rules. When a trend is composed of only flat or no data traces, the default value scale range is inflated to prevent showing a flat plot area. These default ranges are not applied if the trace in question is on a single scale trend that contains other visible traces that do not fall into either of the aforementioned categories. A single scale trace containing one flat trace with a constant value of PI ProcessBook 2015 User Guide

109 Symbols in a PI ProcessBook display A single scale trend containing a flat trace and a non-flat trace. The default range for the flat trace is not applied. Time scale grid lines Grid lines for the time scale line up with whole units of time, such as days, hours, minutes, and so on. On a trend that receives updates, traces scroll as time passes. For an updating trend, the current time is indicated by a dotted vertical line. Configure labels for the time axis in one of three ways: Full Timestamp Labels the start and end time limits with the date and time. When space permits, the elapsed time between these lines is also shown. Partial Timestamp Labels each grid line in whole units, such as hours. For example, the grid lines might be labeled 9:00, 10:00, and 11:00. A full time stamp showing the plot end time is shown at the upper right. Relative Timestamp Labels each grid line with the amount of time preceding the end time limit in days, hours, minutes, or seconds. For example, the grid lines might be labeled -4, -3, - 2, -1, meaning 4, 3, 2, and 1 hours before the end time. A full time stamp for the end time is shown at the upper right. Traces A trace is a single line on a trend. When a trace is continuous, a line is drawn from measurement to measurement. When a trace is discrete, the value is propagated forward until a new value is recorded in the database. This results in horizontal and vertical lines for the tag (staircase trace). Digital points are discrete type measurements, producing staircase traces. For digital points, the offset from the starting digital state code is plotted. Staircase traces are used for points from a PI Data Archive server that have a Step Flag set to TRUE. PI ProcessBook 2015 User Guide 99

110 Symbols in a PI ProcessBook display ODBC queries may produce either curved or staircase traces, depending on the Stepped Plot check box setting in the ODBC Data Set window. Hide traces You can hide one or more traces on the trend in Run mode so that an area of concern is more easily viewed. 1. Open a trend in Run mode. 2. Hover your mouse pointer over the trend's legend. The mouse pointer changes to a hand cursor 3. Click on the legend item to hide or show the trace on the plot., and the trace in the trend is highlighted. If the trace has a regression line configured, the regression line is also hidden. When a trace is hidden: the trace name is dimmed in the legend and the description, value, and engineering units are hidden (if they were shown before). the space reserved on the legend for the description, value, and engineering units collapses so that the trace under the hidden trace is moved. This clearly shows the visible traces on the legend, especially on a trend with many traces. on a multi-scale trend, the scale associated with the hidden trace is hidden. on a single scale trend, the minimum and maximum values shown on the scale may be adjusted. Results You can show hidden traces by clicking their names a second time in the legend, or by clicking the Revert button. All hidden traces are shown in Build mode. You can also right click on a trend and select Show All or Hide All to make traces visible or invisible. Markers Markers indicate data points and allow you to differentiate between traces on a trend. There are three types of markers. At least three markers are shown on a trace, unless the plot is too small. Topics in this section Actual data markers Trace markers X markers 100 PI ProcessBook 2015 User Guide

111 Symbols in a PI ProcessBook display Actual data markers Actual data markers plot each value stored in the database. The color of the trace and of the marker is the same. You can select the shape of the marker, such as diamonds, circles, squares, or triangles, which can be helpful for color- blind users and for monochrome monitors. Trace markers If there are too many values to plot based on the size of the trend, the display resolution and the density of the plotted data, actual data markers do not appear and trace markers are used instead. Trace markers are also used if the trend configuration does not specify markers. Trace markers help you identify the legend information for each trace; they do not indicate actual plot values. Up to three trace markers are used per trace. X markers When a value is outside the limits defined for the trend, it is plotted as over- or under-range. When a value is out of range or has a bad value, it is not shown on the plot. An X marker is placed on the trend at the beginning and end of the time when data are not plotted. When the data are missing, (for example, not connected to a server) they are given the value No Data and are not plotted. Ad hoc trends Create a trend on an ad hoc basis for tags represented by dynamic symbols in a display within a ProcessBook. Ad hoc trends are like any other trends in that you can scroll the time forward and backward, view cursors, zoom, view point attributes, use multiple scales, or change the time range. To create an ad hoc trend, use either: Trend tool to add a trend to an existing display pre-configured with data from other symbols on the display. Trend Display tool data from symbols on the original display. to create a separate, new display with a trend pre-configured with You can build a trend display before you open any displays. If you create an ad hoc trend display and then choose to save it for future use, it appears on the Book or Outline View as subordinate to the original display. Topics in this section Create an ad hoc trend Save an ad hoc trend display PI ProcessBook 2015 User Guide 101

112 Symbols in a PI ProcessBook display Create an ad hoc trend Create an ad hoc trend for a specific tag or tags. 1. In Run mode, select the dynamic symbol(s) with the data you want to trend, such as a bar, value, or Multi-State symbol. To select more than one dynamic symbol, hold down the Shift key while you click them. 2. Click the Trend Display button. A new display window opens, and a trend is created automatically for the selected symbols using the default format and time range. It is given the unique name Trend Display#, where # is a number. The plot title is Ad Hoc Trend. - or - Click the Trend button. The mouse pointer changes to a trend pointer. Click in the display and drag to create a rectangle. It is given the name Ad Hoc Trend. The trend appears in the rectangle, using the default format. If you select more tags than the default set in your Preference settings, usually 3, then you will have more than one plot in your trend or trend display. Save an ad hoc trend display If you create an ad hoc trend display and wish to save it for future use, then you must use the Save or Save As command before you close the instant trend. There are several options. Save an ad hoc trend display as an independent display by clicking it and using the Save As command with a.pdi filename extension. If you had a display entry from a ProcessBook open when the instant trend was created, the instant trend can be saved as a subordinate of the display by using the Save command. You can save an ad hoc trend as another file type, such as a bitmap (.bmp) file, using Save As. You cannot save an ad hoc trend from view-only mode. OpenVMS trends and graphics PI ProcessBook allows you to convert your existing OpenVMS trend and graphic files for use within a ProcessBook. Specifically, the following types of files are supported: PIDisDIFF files 102 PI ProcessBook 2015 User Guide

113 Contain trend graphs built using the PI Data Trending Package. You can convert horizontal, vertical, composite, and overview trends. PI-GP files Graphic files built using the PI-GP Graphics Builder. Before you can convert your trend files (PIDisDIFF), you must convert them as ASCII text files on the VAX and then download them to your PC. Once the files are on the PC, you can import them to a ProcessBook. Trends are formatted based on the settings on the Trend Elements tab on the ProcessBook Preference window. Topics in this section Convert OpenVMS trends Convert OpenVMS graphics Convert OpenVMS trends This process is used to convert OpenVMS graphics for use with a PC. 1. On the VAX or Alpha at the DCL prompt, type $ Run PISysExe:PIDisDIFF 2. Select option 1 List Master Display Library from the PI Display Data Interchange File Format Builder. 3. Direct the output to a file. 4. Enter a file name. If your file name is more than 8 characters and a 3-character extension (xxxxxxxx.xxx), the name is truncated during the download process. 5. Accept the defaults for display mask, group numbers and unit numbers (*). 6. Select the trend display types you are importing. For optimum performance select only options 1 (horizontal), 2(vertical), 3 (composite), and 8 (overview). 7. Quit the PIDisDIFF application (option Q). 8. Transfer the file from the VAX or Alpha to the PC using any ASCII text file transfer program you have available. Convert OpenVMS graphics This process is used to convert OpenVMS graphics for use with a PC. On the OpenVMS computer, copy a graphic file to your working directory. Graphic files are named PISysDat:PIGP_xxxxxxxxxx.dat, where xxxxxxxxxx is the display name. 1. At the DCL prompt, type Symbols in a PI ProcessBook display PI ProcessBook 2015 User Guide 103

114 Symbols in a PI ProcessBook display $ RUN PISysExe:GPAB 2. Select option 1 Convert Binary to ASCII from the PI Graphics Package ASCII/Binary File Conversion menu. 3. Type the display name of the graphic you want to convert and press Enter. Repeat for each file you want to convert. 4. Select option Q to quit the application. 5. Transfer the file from the VAX or Alpha to the PC using any ASCII text file transfer program you have available. Your PI ProcessBook Install disks include an OpenVMS command file which performs Steps 1-5 for all graphics. The file is named GPPBConv.com. Add AF attributes to trends XYPlots You can use values of AF element attributes in PI ProcessBook trends. Before you start To add attributes to trends, you must open PI ProcessBook and verify that the AF Browser and the AF Property pane are open and that you are connected to a PI AF server. You must have access to an AF element that includes attributes. 1. Open a display and select Build mode. 2. Select the trend to which you want to add AF attributes. 3. Select an AF element from the list in the AF Browser. The AF Property pane displays the attribute information. 4. Drag and drop an attribute from the AF Property pane into the empty trend plot. The attribute data is added to the trend. An XYPlot shows a correlation between one or more paired sets of data. On an XYPlot (also called a scatter plot), the X scale shows possible values for one of the items in the pair and the Y scale shows the value of the other item in the pair. A basic scatter plot looks like the following: 104 PI ProcessBook 2015 User Guide

115 Symbols in a PI ProcessBook display Uncorrelated data This case plotted 10-minute intervals of two points, A and B, for the last hour. Point A had 12 point values; Point B had 16 point values. The number of points plotted equals the number of pairs. Since A had fewer point values, the plot shows only 12 point pairs. The extra data from point B is ignored. You can configure the method by which pairing occurs. Correlation is a measure of the strength of the relationship between two variables. Correlation is indicated graphically by the spread of the data points around a fitted straight line (for example, a straight line that indicates the trend of the data). In general, the closer the points are to the fitted line, the stronger the correlation. The two PI tags shown in figure 1 are not strongly correlated. Another plot shows perfectly correlated data: Perfectly correlated A third plot is somewhat correlated: PI ProcessBook 2015 User Guide 105

116 Symbols in a PI ProcessBook display Somewhat correlated In the case of the third plot, a regression line with a slope (M) of 1 and an offset (B) of 0 drawn diagonally across the plot would show all points lying close to the line, some above it, some below it. This line formula is appropriate in this case because both scales are the same and the points appear to have values very close to each other. In other cases, one value may be two or three times the other value (for example) and the regression line would fall on a different slope, depending upon how the scales are configured. If the scales are the same, the slope of the line determines the relationship between the points. If the scales are not the same, the slope is insignificant. Topics in this section Draw an XYPlot Linear regression by least squares Correlation coefficient Interpreting an XYPlot Zoom and Revert functions Change time range feature XYPlot cursors Bad status indicators Out of range indicators Too many points Examples of XYPlots Draw an XYPlot 1. In Build mode, click Draw > XYPlot, -or- 106 PI ProcessBook 2015 User Guide

117 Symbols in a PI ProcessBook display On the Drawing toolbar, click the XYPlot button. 2. Drag a rectangle on the display to create the boundaries. 3. Release the mouse button. The Define XYPlot window opens with the General tab open. 4. Use the tabs as follows: General tab Select tags to be plotted. Display Format tab Choose what to show in the Legend and on the display. Plot Format tab Select how to color and style the plot elements, such as trace pens and background. 5. Click OK. The XYPlot appears. To revise an existing XYPlot, select Build mode and double-click the XYPlot. The Define XYPlot window appears. Make your changes and click OK. Click Undo to restore your original plot. Topics in this section General tab Display Format tab Plot Format tab Ad hoc XYPlots View XYPlot or SQC symbol statistics General tab Use the General tab to select data items to plot. PI ProcessBook 2015 User Guide 107

118 Symbols in a PI ProcessBook display Plot Title Enter a plot title. Change it later if you wish. Tags in Plot Select the tags or data sets you want to plot. Click the Tag Search button to locate a tag, or Click the Tag Search arrow to see more search options: Tag Search PI Calculation (data set) ODBC (data set) AF2- launches the Select AF Attribute window, from which you can search an AF database for elements and attributes. Element Relative - launches the Element Search window from which you can search an AF database for elements. Your selections for tags, data sets, or attributes appear under Tags in Plot. An Options radio button appears next to each tag name. Select Options to choose the X-axis tag. Unselected tags are Y-axis tags. If a tag that is selected as the X-axis is deleted, the first tag in the list becomes the X-axis tag. 108 PI ProcessBook 2015 User Guide

119 Use the four toolbar buttons on the title bar to rearrange this list. They are, in order, Add, Delete, Up Arrow, and Down Arrow. Server Enter or select a PI Data Archive server name. This field is only used when a PI Tag name is typed directly into the list. PI ProcessBook allows you to create custom placeholders for a symbol based on a summary data set or a PI tag placeholder in an ODBC data set. Placeholders are not allowed for expression data sets. The Custom Placeholders button in symbol definition windows allows you to specify different PI tags for a PI Summary data set or ODBC data set with a PI tag placeholder. The change applies only to the configured symbol. See Add or edit placeholders for details. Topics in this section Configure pairings Scale Box Plot time Add a data set to an XYPlot Element search symbol Configure pairings Once the tags are listed in the Tags in Plot list, configure the method for pairing values between X and Y in the Data Retrieval Methods box. X Tag Choose either Recorded or Interpolated for the retrieval method. Interpolated An interval may be entered in the Plot Time section. Interpolated is the default for tags and is disabled for ODBC and Custom data sets. This method retrieves interpolated values for the specified time range in regular intervals. For example, if the time range is *-1h to * and the Interval is 10m, then six values spaced 10 minutes apart are returned. This option provides a way to get evenly sampled data. Recorded Retrieves archive values between the specified start and end time. Y Tag(s) The Y tag data retrieval method applies to individually selected tags in the Tags in Plot list (unless the Use for all Y tags check box is selected). The default data retrieval method for Y tags is Synchronize. Y Tags, paired by position in the list Symbols in a PI ProcessBook display To use multiple time ranges, select Recorded or Interpolated. In this case, data is paired by position in the point list. If Interpolated is selected for the X tag as well, the interval value for the Y tag defaults to the one for the X tag. PI ProcessBook 2015 User Guide 109

120 Symbols in a PI ProcessBook display When Recorded is the retrieval mechanism, the results are not skewed by minor time stamp differences Y Tags, paired by timestamps To pair values by time, rather than by list position, choose one of these retrieval methods: Synchronize Synchronizes data found for X with data for Y using the time stamps for the X data. This may result in interpolated data values for Y. Match Find the event for Y corresponding to the exact time stamp as X. If no matching event is found, no match is made for that X value. Match or Previous Fnd the event for Y corresponding to the exact time stamp as X. If there is none, find the event that is the closest but earlier in time. Match or Next Find the event for Y corresponding to the exact time stamp as X. If there is none, find the event that is the closest, but later in time. Synchronize and Match use different PI SDK value retrieval methods. Synchronize uses TimedValues. Match uses RecordedValues and then uses the values where the time stamps match. Synchronize is disabled for ODBC and Custom data sets. If you select Synchronize or any of the Match options, the start and end times for that tag are set the same as for the X tag and cannot be changed. The XYPlot supports ODBC data sets that don't contain time stamps. This type of entry must be plotted as a Y-tag, and data values must be retrieved using the Recorded retrieval method. If a tag is changed from a Y tag to an X tag and has a value for Retrieval Method that is only valid for Y tags, the method is changed to Interpolated. If the tag is a data set, the method is changed to Recorded. In all cases, if a pair is not made, the unmatched X or Y events are ignored. Use for all Y tags Selecting this check box indicates that the Y-tags data retrieval mechanism applies for all Y- tags. If one of the tags is a Custom or ODBC data set and the selection mechanism is Interpolated or Synchronize, the selection mechanism will be Recorded or Match respectively for that tag only. Scale Box In the Scale Box, set the scale ranges for all tags. Single Y Scale 110 PI ProcessBook 2015 User Guide

121 combines all Y tag value ranges onto one scale. Multiple Y Scales Provides a separate scale for each Y tag. This choice does not change the scale min and max values, but allows them to be configured independently by selecting each Y tag and making changes. Regardless of your selection, you may independently configure the X scale tag. Max Autorange uses the maximum value plotted. You may enter an absolute value here as well. Default is Autorange. Database uses the zero plus span value of the tag in the PI Data Archive server to determine the max. Database with a data set plot uses the maximum value plotted. Min Autorange uses the minimum value plotted. You may enter an absolute value here as well. Default is Autorange. Database uses the zero value of the tag in the PI Data Archive server to determine the min. Database with a data set plot uses the minimum value plotted. Format Selects the number format of the Y scale, legend entries, cursor values, and tooltip values: Database Database format uses the displaydigits PI Point attribute to determine how many decimal places to show. If the length of the number exceeds the displaydigits value, scientific notation is used. PI ProcessBook trims trailing zeroes that follow a decimal point. The Database format option is intended for use with PI Tags only. General Shows all significant digits for a number except trailing zeros. If the absolute value of the value is greater than 1e+7 or less than 1e-5, the format will switch to use scientific notation. Scientific Most useful with very large numbers. The scientific format used for trends displays in the format: 0.00E+00. Custom (#,##0.00, 0%) Allows you to enter your own number format. See the Table of Format Values for examples. Table of format values The following number formats are available in PI ProcessBook. The characters used for the decimal and grouping are based on the Regional Settings on the computer where PI ProcessBook is installed. Format Value Result General #,## ,733 #,## , (#,##0) (1,733) (#,##0.00) (1,732.87) Symbols in a PI ProcessBook display PI ProcessBook 2015 User Guide 111

122 Symbols in a PI ProcessBook display Format Value Result 0% % 0.00% % Scientific E+00 Database Uses the Display Digits attribute for the tag from the PI System. The following table describes how to create a custom number format mask. Symbol Explanation # Placeholder for a digit. Leading and decimal zeros are not displayed 0 Placeholder for a digit. Leading and decimal zeros are displayed. Plot time You can set the time for each tag as it is highlighted in the Tags in Plot box. If a Y tag is selected and its selection mechanism is not Recorded or Interpolated, then these boxes are disabled. Start The start time of the selected tag. The list includes *-1h (minus one hour), *-4h, *-8h, *-1d, *-7d. The default is *-8h. End The end time of the selected tag. The list includes *, *-1h, *-4h, *-8h, *-1d, *-7d. The default is * (current time). Interval This field is enabled when the retrieval method is Interpolated. It provides a sampling interval for data. When you have completed configuring the fields on the General tab, click the Display Format tab. Add a data set to an XYPlot 1. In Build mode, click Draw > XYPlot, -or- On the Drawing toolbar, click the XYPlot button. 2. Drag a rectangle on the display to create the boundaries. 3. Release the mouse button. The Define XYPlot window opens with the General tab open. 4. Click the arrow next to the Tag Search button. 112 PI ProcessBook 2015 User Guide

123 Symbols in a PI ProcessBook display 5. Select ODBC or PI Calculation to see the corresponding Dataset Details or PI Calculation Data configuration window. 6. When you have completed the configuration, click OK to exit the configuration window. The data set name appears in the Tags in Plot box. 7. In the Define XYPlot window, click OK to see the plot. Element search symbol 1. Connect to an AF System. 2. Specify search criteria for the elements. 3. View the Search results. Display Format tab Use the Display Format tab to select options to show for an XY Plot legend and display. PI ProcessBook 2015 User Guide 113

124 Symbols in a PI ProcessBook display Legend Tag Name Lists the entries in Tags in Plot. Selected by default. Srvr Name Select this check box to prepend the tag name with the server name. Cleared by default. Description The tag description may be displayed on the legend. Selected by default. Value The last value of the tag plotted may be displayed. For digital and string tags, a string value is shown. Selected by default. Engineering Units Selected by default. If the tag does not report units, they are not shown on the legend for that tag. Correlation Coefficient When selected, indicates that the correlation coefficient should be calculated and displayed on the legend. Selected by default. Display Plot Title 114 PI ProcessBook 2015 User Guide

125 Symbols in a PI ProcessBook display Selected by default. Vertical Scale Inside Axis Select this check box to show the vertical scale to the right of the Vertical Axis, inside the plot area. Selected by default. Grids Select this check box to include vertical and horizontal grid lines. Selected by default. On the Plot Format window, you can configure the appearance of the major and minor grid lines. Linear Correlation Line Select this to show a linear regression line. The default is cleared, which does not draw a line. Connecting Lines Select this check box to show the paired points connected with straight lines in the order they are plotted. Selected by default. Clear the check box to configure a scatter plot with points only, no lines. The Sample area displays a sample XYPlot with the options you have selected. When you have completed the Display Format window, click the tab for the Plot Format window. Plot Format tab Use the Plot Format tab of the Define XYPlot window to select colors and styles for the various elements of your plot. PI ProcessBook 2015 User Guide 115

126 Symbols in a PI ProcessBook display Plot Element Drop-down list of the elements you can configure, such as major and minor gridlines, background colors, text font, etc. Pens correspond to the X-and Y tags listed in the order in the Tags in Plot box on the General tab. Element Format After you select an element in the Plot Element drop-down, available formatting options appear. A drop-down arrow is grayed out if the option is not configurable. For example, text has color but no line style options. Line Style Determines the line style for the selected element. Line Weight Determines the line weight for the selected element. If the selected element does not have a line weight property, this field is disabled. Marker Shape Determines the marker shape for pen elements. Color Determines the color for the selected element. Pen elements apply the color to the line and marker. Last Marker Color Allows selection of a different color for the last marker for a pen. If Match Trace is true (selected), this field is disabled. If the selected element does not have a marker, this field is disabled. Next To Last Marker Color Allows selection of a different color for the second-to-last marker for a pen. If Match Trace is true (selected), this field is disabled. If the selected element does not have a marker, this field is disabled. Match Trace Determines whether all marker colors match the trace color (true) for a pen. If set to false, the Last Marker Color and Next To Last Marker Color fields are enabled so the marker color can be changed for those two plotted pairs. By default, this field is selected (true). If the selected element does not have a marker, this field is disabled. Sample Provides a preview of your formatting changes. Ad hoc XYPlots You can draw an XYPlot in Run mode on an ad hoc basis. Click the XYPlot button and follow the steps described in Draw an XYPlot to begin, 116 PI ProcessBook 2015 User Guide

127 Symbols in a PI ProcessBook display View XYPlot or SQC symbol statistics To view and export raw data values and statistics, such as the mean and standard deviation of data for each PI point: 1. Double-click an XYPlot or SQC symbol. The Statistics window appears. 2. In the Options drop-down list, select Raw Data or Statistics. PI ProcessBook 2015 User Guide 117

128 Symbols in a PI ProcessBook display 3. (optional) To save this data to a text file, click Save Data to File. The data is saved to the file in the following format: Tag, <tag name> Start Time, <start time> End Time, <end time> Count, < number of points paired> Mean, <mean> STDEV, <standard deviation> Data Type, <data type> Index, Time, Value, Status <index>, <time>, <value>, <status> <index>, <time>, <value>, <status> Tag, <tag name> Start Time, <start time> End Time, <end time> Count, < number of points paired> Mean, <mean> STDEV, <standard deviation> Correlation, <correlation coefficient> Slope, <slope> Intercept, <intercept> Data Type, <data type> Index, Time, Value, Status <index>, <time>, <value>, <status> <index>, <time>, <value>, <status> You can also view these statistics in the Details window. 118 PI ProcessBook 2015 User Guide

129 Symbols in a PI ProcessBook display Linear regression by least squares The best-fit linear regression line is a straight line that attempts to summarize the trend of the plotted pairs. This line may be shown on the XYPlot. The best-fit line has the formula: Where m is the slope and b is the offset. To calculate m, we use the following equation: To calculate b, the following equation is used: Once m and b are known, the value of y that intersects the best-fit line can be calculated. Correlation coefficient The correlation coefficient (r) varies between -1 and +1. Positive values indicate that as X increases, Y also increases. Negative values indicate that as X increases, Y decreases. A value of zero indicates no correlation in the way the sets of values vary. The correlation coefficient for a set of points is calculated using the following formula: (n is the number of points, s is the standard deviation). You can display the correlation coefficient in the plot legend. Bad data points are not included in this calculation. Standard deviation(s) is calculated using the following formula: The mean is the arithmetic average. PI ProcessBook 2015 User Guide 119

130 Symbols in a PI ProcessBook display Interpreting an XYPlot In PI ProcessBook the XYPlot is a dynamic symbol. It has specialized characteristics, such as its statistical calculations, which are described in the following paragraphs. Point Properties Data can be retrieved from PI Data Archive or from independent data sets. Use the Tag Properties button or the right mouse menu Properties item to determine the attributes of the points in your XYPlot. Scroll Feature Scrolling is available from the ProcessBook toolbar. When time scrolling is used on an XYPlot symbol, all tags time ranges are changed to support the scroll duration. Plot Values In a typical XYPlot, the current name for the X tag appears below the plot. The current names for the different Y tags appear at the upper right. Below each one is the correlation coefficient for that XY pair. The dots and lines on the plot are colored to match the tag names. Plotted pair values appear in a ToolTip over the plot when the mouse cursor is hovering over an actual plotted point pair. The following illustration shows an example. In the figure above, if there had been more than one Y tag, each one would be displayed on a different line. The X tag information is placed at the bottom. For digital or string tags, the text value is displayed in the ToolTip. You can also view plot values by double-clicking the title bar and choosing the Raw Data option, rather than the Statistics option in the Statistics window. Zoom and Revert functions You can enlarge a portion of an XYPlot by using the Zoom feature. Topics in this section Enlarge the whole plot to fill the display window Enlarge a small area of the plot Revert 120 PI ProcessBook 2015 User Guide

131 Symbols in a PI ProcessBook display Enlarge the whole plot to fill the display window 1. In Run mode, double-click the plot. 2. To reduce the plot to its original size, double-click it again. It does not update while enlarged. Enlarge a small area of the plot 1. Place the mouse cursor on the upper left corner of the area to be zoomed. 2. Hold the left mouse button down while dragging a rectangle to cover the appropriate area. When you release the mouse, this area is enlarged to the borders of the original plot. PI ProcessBook 2015 User Guide 121

132 Symbols in a PI ProcessBook display The zoom area must be smaller than the plot area and cannot include the outer 20 percent of the plot. If the mouse is dragged past the plot boundary, the zoom rectangle stops at the border until the mouse reappears within the boundary. If the mouse is dragged off the plot symbol boundary, the zoom is canceled. Revert 1. Click Undo to return the plot to its state directly before the zoom occurred. 2. Click the Revert button to return the plot to its configured appearance. Change time range feature 1. Click View > Time Range. -or- On the Time Range toolbar, click the Change Time Range button. The Change Time Range window opens. 2. Enter new values in the Time Span box. All tags are affected when you change the range in this window. 3. Click the Revert button on the Time Range tool bar to return the plot to its configured appearance. 122 PI ProcessBook 2015 User Guide

133 Symbols in a PI ProcessBook display XYPlot cursors The cursor for an XYPlot includes both a horizontal and a vertical line. The mouse cursor is at the cross point of both cursor lines. You must be in Run mode to use the XYPlot cursor. To create a cursor, place the mouse very close to either the X- or Y-axis. Drag the cursor onto the plot. In the XYPlot below, you can see an XYPlot cursor at the Y axis that is not yet intersecting any points on the plot. You can also see an XYPlot cursor that was dropped on a point. The X and Y values appear in small boxes outside the axes. Using the mouse, you may position and release the cursor over any pair on the XYPlot. If the cursor is dropped on an area that contains no points, the cursor snaps to the nearest pair. Move the XYCursor from point to point AFter you have dropped an XYCursor on a point, use the arrow keys to move from point to point in time order. For example, pressing the right arrow key moves the cursor to the pair that is plotted immediately after the current pair in the same series. The left arrow moves the cursor to the pair that is plotted immediately before the current pair in the same series. The up arrow moves the cursor to the first pair in the previous series. The down arrow moves the cursor to the first pair in the next series. The cursor looks the same when it is dropped. The information on the XYCursor point pair is shown in a box on each axis. If the tags are digital or string, the text value is shown in the box rather than a numeric value. Placing the mouse cursor over one of the cursor boxes shows the time of the event. Bad status indicators If a single point of a pair contains a bad status, an X appears on the axis of the good point at its value. If both points of a pair contain bad statuses, an X appears at the origin of the plot. The XYPlot symbol supports Questionable, Annotated, and Substituted indicators. PI ProcessBook 2015 User Guide 123

134 Symbols in a PI ProcessBook display Out of range indicators When a point on the XYPlot falls above or below the X or Y scale range, it is not visible. This may be because the plot is zoomed or because the scales have been set within a certain range that does not cover the actual data. In order to indicate there is a point outside of the visible area, an X is used. By default, a straight line connects the points in the order that they are plotted. This line attempts to connect hidden points as well. An X is placed at each position where this line crosses the top or bottom of the plot area. Too many points When an X Tag has too many points to show on the plot, you receive and error message and no points are shown. The maximum number is 10,000 points. Examples of XYPlots For these examples, the X-axis represents one of the values in the pair and the Y-axis represents the other. The configuration of these axes regarding minimum and maximum values and interval (or unit) settings is left to you. Topics in this section Example 1: Create an XYPlot on a display in PI ProcessBook to compare values for two PI tags Example 2: Compare different tags to help optimize equipment performance Example 3: Lab comparisons Example 4: Comparing a batch run to a standard Example 5: Comparing two time ranges Example 1: Create an XYPlot on a display in PI ProcessBook to compare values for two PI tags 1. On the Drawing toolbar, click the XYPlot button and drag to form the bounding rectangle for the plot. The Define XYPlot window appears. 2. Enter a title for the plot and select 2 tags to be entered in the Tags in Plot list. 3. Click an option button to select one tag to be the X tag. 4. Use the default settings for time range, scale, and retrieval method. 5. Click the Display Format tab and check the box for the regression line. 6. Select the Plot Format tab and accept the default values. 7. Click OK and the plot appears. 124 PI ProcessBook 2015 User Guide

135 Symbols in a PI ProcessBook display Example 2: Compare different tags to help optimize equipment performance For example, suppose an engineer has just completed some optimization work on Boiler1, one of the four boilers in the plant. He wants to optimize the other three boilers (Boiler2, Boiler3, and Boiler4) so that they perform at the same level. After adjusting the three boilers, he wants to see how closely they perform to the optimized Boiler1. Assume that all four boilers run identical processes. 1. Plot the temperature of Boiler1 (the B1Temp tag) on the X-axis of an XYPlot and the temperatures of the other three boilers (B2Temp, B3Temp and B4Temp) on the Y-axis. 2. Use the same time range for all four tags. 3. Select a single scale so that the Boilers 2, 3 and 4 are compared directly against Boiler1. 4. Configure the plot to show the correlation co-efficient for each of the boilers. By viewing how far from the regression line each of the boilers falls, you can determine how closely their performance matches and which boilers you should continue to adjust. When all three boilers have an acceptable correlation coefficient, you know the work is complete. Example 3: Lab comparisons An engineer wants to compare lab results from his lab to those of another lab for the same sample of material. The plant's quality assurance lab has instituted some new testing procedures. In order to gauge the validity of the new testing procedures, an engineer wants to compare results from the new process against data from an outside lab that is known to have valid testing procedures. 1. Put the results from the in-house lab into a data set. 2. Place the results for the same test from the other lab into another data set. 3. Selects each data set as a tag in the plot, and select which one to be the X-axis. 4. Choose Recorded as the retrieval mechanism for each data set so that the results are not skewed by minor timestamp differences. If the XYPlot shows the results from the new process are well correlated with the outside lab's data, the new test procedure is validated. Example 4: Comparing a batch run to a standard An engineer wants to compare sample measurements taken from one Batch run and compare them to a fixed set of measurements he knows to be desirable. 1. Select the fixed set of measurements by choosing the appropriate tag or data set and indicating it is to be used for the X-axis. 2. Select the appropriate tags for the comparison batches, entering their specific time ranges. 3. Use Recorded values for all retrieval mechanisms. PI ProcessBook 2015 User Guide 125

136 Symbols in a PI ProcessBook display The data points are paired according to their position in the events list. The XYPlot shows how closely the results are correlated by how closely the pairs fall on a linear regression line. Pairs that fall outside this line may indicate problems with the batch run. Example 5: Comparing two time ranges An engineer wants to compare the performance of a Boiler unit over two time ranges. He needs to determine whether a boiler's performance has degraded over time or whether there are specific problems with the equipment. To do this, he creates an XYPlot that compares the temperature tag data from two different time ranges. 1. Enter the tag twice and assign one instance as the X tag. 2. Enter separate time ranges for each tag. 3. Set the match mechanism to be recorded or interpolated so that values are paired by their position in the list. If the pairs fall close to a linear regression line, you can assume the boiler's performance is at least steady. If some pairs are far from the line, it may indicate that the equipment has a specific problem. Additional dynamic symbols Topics in this section Values Button Bars Values A Value is the reading obtained for a data stream at the end time of a display. It is shown as a number or a digital state string. The tag name and time stamp can also be shown. The time stamp is the time stamp from the PI System that matches the event value shown. Add a dynamic value 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Value button. -or- Click Draw > Value. The mouse pointer changes to the Value pointer. 126 PI ProcessBook 2015 User Guide

137 Symbols in a PI ProcessBook display 3. Click in the display where you want the value to be placed. When you release the mouse button, the Define Value window is displayed. 4. In the Server drop-down list, select the PI Data Archive server to use. If a tag name is manually entered in the Tag box, it is expected to be on the selected server. If both server and tag name are entered in the Tag box, this field is updated with the entered server name. This field has no effect for non-pi data. 5. In the Tag box, type the name of the tag you want to display in the value box. -or- Click the Tag Search button to locate a tag, or Click the Tag Search arrow to see more search options: Tag Search PI Calculation (data set) ODBC (data set) AF2- launches the Select AF Attribute window, from which you can search an AF database for elements and attributes. Element Relative - launches the Element Search window from which you can search an AF database for elements. The Sample area shows how the value will look. PI ProcessBook 2015 User Guide 127

138 Symbols in a PI ProcessBook display 6. In the Format drop-down list, select a number format: Database Database format uses the displaydigits PI Point attribute to determine how many decimal places to show. If the length of the number exceeds the displaydigits value, scientific notation is used. PI ProcessBook trims trailing zeroes that follow a decimal point. The Database format option is intended for use with PI Tags only. General Shows all significant digits for a number except trailing zeros. If the absolute value of the value is greater than 1e+7 or less than 1e-5, the format will switch to use scientific notation. Scientific Most useful with very large numbers. The scientific format used for trends displays in the format: 0.00E+00. Custom (#,##0.00, 0%) Allows you to enter your own number format. See the Table of Format Values for examples. 7. In the Tag drop-down list, select the location of the tag name in the value box (None, Left, Right, Top, or Bottom). 8. In the Time stamp drop-down list, select the location of the time stamp in the value box (None, Left, Right, Top, or Bottom). 9. Click OK to add the value to the display. PI ProcessBook allows you to create custom placeholders for a symbol based on a summary data set or a PI tag placeholder in an ODBC data set. Placeholders are not allowed for expression data sets. The Custom Placeholders button in symbol definition windows allows you to specify different PI tags for a PI Summary data set or ODBC data set with a PI tag placeholder. The change applies only to the configured symbol.see Add or edit placeholders for details. Button You can add a button to your drawing that: Opens an independent display (.pdi) Opens a ProcessBook (.piw) Executes an operating system command For example: Create a drawing that shows the first part of a general process and add a button that opens a more detailed process in a separate display. Create a link to a related display in a different ProcessBook. Create a drawing and add a button that opens a PI DataLink spreadsheet to show a report. Create a drawing and add a button that opens an independent PI ProcessBook display (.pdi file) on a web site. You need to enter the URL (Uniform Resource Locator) address that points to the location of the specific.pdi file on a web server. 128 PI ProcessBook 2015 User Guide

139 Symbols in a PI ProcessBook display You can add a button to your drawing that: Executes a VBA script For example: Create a VBA script called AddTrend that inserts a trend on a display. Add a button to the display and configure it to use the AddTrend script (macro) as its Action. Add a button 1. In Build mode, open a display. On the Drawing toolbar, click the Button button, or Click Draw > Button. The mouse pointer changes to the Button pointer. 2. Click in the display where you want to add the button and drag the pointer to form a rectangle into which the button will be placed. When you release the mouse button, the Define Button window appears. 3. In the Text box, type the name of the button. The name should be no more than one or two words, and should describe the action the button performs when clicked. 4. Click the Browse button, or Click the Browse arrow to see more options. The Open window appears. 5. Browse and locate the item that you want to be the button action and then click the Open button. If you know the file or macro name, then you can type this directly in the Action box. The name of the selected item is displayed in the Action box. 6. Click the Browse button to the right of the Working folder box. The Working folder box allows you to specify the working folder for operating system commands. It is ignored if the Action refers to a document type supported by ProcessBook. If you know the name of the working folder for this application, then you can type this directly in the Working folder box. The Browse for Folder window appears. 7. Browse and locate the folder that you want to specify for the operating system command, and then click OK. 8. Leave the appropriate Options check box selected if you want to: Open a linked display in a new window. This option is selected by default. Use the relative path before the absolute path. PI ProcessBook 2015 User Guide 129

140 Symbols in a PI ProcessBook display By default, ProcessBook attempts to open a linked display from its relative path first. If the relative path fails, then the absolute path is attempted. Clearing this box reverses the order in which the paths are resolved. For new displays, this option is checked by default. Ignore the default shell command for recognized file types (for example, SVG). 9. Click OK. If the file type is supported by ProcessBook (either natively or through an add-in), then it is opened directly. For example, an.svg file is opened using the.svg File Converter in ProcessBook, even if you have Adobe SVG Viewer installed. Clearing this check box disables this behavior, so the default shell command is always used to open a file. The button is added to your display. Bars A Bar shows the current value of a tag as compared to a specified range of values. For example, a bar may be used to create the effect of a vessel filling and emptying, as the value changes. The range of values can be the maximum and minimum values specified in the point attributes, or, a bar can be designed to show a specific range of values. For example, if a tag s specified value is between 0 and 100 but it typically falls between 0 and 30, a bar can designed to show that range. However, if the value is outside the range of the bar, the bar will appear the same as a value right at one of the limits of the bar. The start of the bar may be within the limits of the bar. This lets you display deviations from a standard or target value. Bad values are shown with hash marks across the entire bar. Topics in this section Add a dynamic bar Bar scales Add a dynamic bar Creating a bar for a value allows you to see how the current value compares to the possible range of values. Since bars are dynamic, they are updated as the information changes from the PI Data Archive server. Bars may also be used to display the result of a data set query. String and timestamp data is not supported on Bar symbols. You can draw a bar using the current line style, line color, and fill attributes. 130 PI ProcessBook 2015 User Guide

141 Symbols in a PI ProcessBook display 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Bar button, or Click Draw > Bar. The mouse pointer changes to the Bar pointer. 3. Click in the display where you want to add the bar and drag the pointer to form a rectangle into which the bar will be placed. When you release the mouse button, the Define Bar window appears. 4. In the Server drop-down list, select the server to use for manually entered tags. If the server and tag name are both entered in the Tag box, this field is updated to show the new server name. This field is ignored for non-pi data. 5. In the Tag box, type the name of the tag you want to display on the bar, or Click the Tag Search button to locate a tag, or Click the Tag Search arrow to see more search options: PI ProcessBook 2015 User Guide 131

142 Symbols in a PI ProcessBook display Tag Search PI Calculation (data set) ODBC (data set) AF2- launches the Select AF Attribute window, from which you can search an AF database for elements and attributes. Element Relative - launches the Element Search window from which you can search an AF database for elements. 6. From the Upper and Lower drop-down lists, select the maximum and minimum values you want to use for the bar. Enter a constant, or choose Tag Zero() or TagZero()+TagSpan() for either or both values. If you choose a maximum value that is too small, the bar will be fully colored but there will be no warning that it has exceeded the maximum. 7. From the Start drop-down list, select the point on the bar from which you want to start drawing the bar. Enter a constant, or select TagZero()+TagSpan() or Tag Zero(). 8. Under Orientation, select one of the options to display the bar either vertically or horizontally. The Upper and Lower drop-down lists are renamed Right and Left when you select Horizontal orientation. The Sample area shows how the bar will look. 9. Under Scales, select Show Scales to show data values and scale tick marks on the bar symbol. When you select Scales, the Scales Inside and Number Formats are enabled. See Bar scales for information on working with scales. 10. Click OK to add the bar to the display. PI ProcessBook allows you to create custom placeholders for a symbol based on a summary data set or a PI tag placeholder in an ODBC data set. Placeholders are not allowed for expression data sets. The Custom Placeholders button in symbol definition windows allows you to specify different PI tags for a PI Summary data set or ODBC data set with a PI tag placeholder. The change applies only to the configured symbol. See Add or edit placeholders for details. Bar scales The options under Scales control how the bar symbol shows scales. Topics in this section Defaults Compatibility Tick marks 132 PI ProcessBook 2015 User Guide

143 Symbols in a PI ProcessBook display Format appearance Defaults The default is to show scales inside the bar symbol in General number format for symbol bars created with PI ProcessBook 2012 or later. For earlier versions of PI ProcessBook, Show Scales is not selected, and scales do not appear on the symbol bar. The scale values for the bar symbol are the Upper and Lower or Right and Left values in the Define Bar window for both tags and datasets, including AF. The default font is the font of the display. Digital tags show the value of the digital state rather than the numeric value of the state. Compatibility Bars created in PI ProcessBook 2012 are backward compatible with previous versions of PI ProcessBook. When a PI ProcessBook 2012 file is opened in a previous version, bar symbols appear as they did in the previous version. If the display is saved and reopened in a newer version, the scale settings are retained. A display created in version 3.2 or earlier of PI ProcessBook defaults to ShowScales not selected. Tick marks For vertical bars, the tick marks and values are shown on the left hand side of the symbol. For horizontal bars, the tick marks and values are shown on the bottom of the symbol. You can draw the scales inside or outside the bar symbol. Vertical Bar with scales (outside and inside) PI ProcessBook 2015 User Guide 133

144 Symbols in a PI ProcessBook display Horizontal Bar with scales (outside and inside) The lengths of major and minor tick marks is a percentage of the height or width of the bar, depending on the bar orientation, as described in the following table. Horizontal Vertical Minor Tick 4% of Height 4% of Width Major Tick 8% of Height 8% of Width For vertical bars, the tick marks and values are automatically turned off if the height of the bar becomes less than two times the height of the text used to write the scale values, or if the width is less than the width of the longest text used to write the scale value plus a small offset. For horizontal bars, the tick marks and values are automatically turned off if the width of the bar becomes less than two times the width of the longest text used to write the scale value, or if the height is less than the height of the text used to write the scale values plus a small offset. For both bar orientations, given the range of scale values, the scale increment values are rounded numbers, as close to integers as possible. The maximum number of major tick marks is nine; eleven counting the maximum and minimum values. The number of tick marks shown is a function of the size of the font and the size of the bar symbol. The number of major tick marks decreases as the size of the bar is decreases. The minor tick marks are shown at the half way point between major tick marks. There are major tick marks for each digital state, if the string value for the digital states fits in the width of the bar. There are no minor tick marks for digital tags. Format appearance To change the appearance of the bar symbol, right-click the bar. Click Format Font to change the font for the bar symbol. Click Format Color to change the color of the bar symbol. The color for the tick marks and values is the same as the bar s line color. Click Format Line Style to change the style of line for the bar symbol. Multi-state symbols 134 PI ProcessBook 2015 User Guide

145 Symbols in a PI ProcessBook display Some symbols support a multi-state configuration, which allows their colors to be altered based on a dynamic data value. Colors are assigned to ranges of values to create conditional formatting states. Any symbol except a trend, XY Plot, graphic, button, or OLE object can have a Multi-State configuration. String and timestamp data cannot be used to configure multi-state behavior. You determine the number of value ranges, the maximum for each range, and the colors assigned to each range. As the value of the tag changes, the Multi-State symbol changes color to reflect the current value state. You can make a symbol seem to disappear by setting a state color to the background color or to a color of none. For alarms or other purposes, you can set a state color to blink. For example, you may have a symbol showing two states. State 1 has a value range from 0 to 50 and a color of blue assigned to it. State 2 may have a range from 50 to 100 and have red assigned to it. When the reading is 50 or below, the symbol appears blue. Above 50, the symbol appears red. A color and sometimes a blinking attribute are assigned for data in bad status (for example, the interface becomes disconnected). For digital point types, a different color may be assigned to each digital state. The following symbols support multi-state formatting: Value Bar Rectangle Ellipse Line (or Connector) Text Polygon Polyline Arc Symbol Library Create dynamic multi-state symbols You can create a multi-state symbol after you have drawn a symbol or copied one from the Symbol Library window. 1. In Build mode, open a display. 2. Click the symbol that you want to use for creating a Multi-State symbol. On the Formatting toolbar, click the Multi-State Symbol button Click Edit > Multi-State. The Multi-State Symbol window appears., or PI ProcessBook 2015 User Guide 135

146 Symbols in a PI ProcessBook display 3. In the Server drop-down list, select the server to use for entered tags. If a server and tag are both entered in the Tag box, this field is updated with the new server name. This box does not apply to non-pi data. 4. In the Tag box, type the name of the tag you want to assign, or Click the Tag Search button to locate a tag, or Click the Tag Search arrow to see more search options: PI Tag Search window PI Calculation data sets (data set) ODBC data sets (data set) Configure a symbol with an AF attribute Opens the Select AF Attribute window, from which you can search an AF database for elements and attributes. Element search symbol Opens the Element Search window from which you can search an AF database for elements. 5. In the Number of States box, select the number of states to use. If the number of states is not entered, the number defaults to 2. (For digital tags, the number of states is automatically set to the number of defined states for that tag.) 6. From the Color for Bad Data drop-down color palette, select a color that will be used when the information is in bad status. You may also select the Blink check box to call attention to the symbol when data is bad (optional). 136 PI ProcessBook 2015 User Guide

147 Symbols in a PI ProcessBook display 7. In the State box, select In the Values box, type in a new maximum value for the state. The Values boxes display a range of values for each state. The total range of the tag is automatically divided by the number of states. For digital tags, the state name is displayed in these boxes. For other tag types, an estimate is made based on the span of values for the tag. 9. From the Color drop-down color palette, select a color that will be used for the state. You may also select the Blink check box (optional). 10. Repeat Steps 8 and 9 for each state in the symbol. Your choices and the relative range of values are displayed on the bar at the bottom of the window. 11. Click OK. You can remove a multi-state symbol definition by clicking the Convert to Static button, which breaks the link between the symbol and the multi-state configuration. PI ProcessBook allows you to create custom placeholders for a symbol based on a summary data set or a PI tag placeholder in an ODBC data set. Placeholders are not allowed for expression data sets. The Custom Placeholders button in symbol definition windows allows you to specify different PI tags for a PI Summary data set or ODBC data set with a PI tag placeholder. The change applies only to the configured symbol. See Add or edit placeholders for details. Static symbols Topics in this section Text symbol Line symbol Rectangle, square, arc, ellipse, and circle symbols Polygon symbol Polyline symbol Graphic symbol Symbol Library Text symbol The text symbol allows you to put one line of text on a display. Multiple lines of text are not supported. When this symbol is first added to the display, a text box with a blinking text cursor is displayed. PI ProcessBook 2015 User Guide 137

148 Symbols in a PI ProcessBook display You can add or edit text by double-clicking the Text symbol while in Build mode, which provides the text cursor. Unlike most other ProcessBook symbols, this symbol is not sized by dragging an area on the display. Instead, the symbol is sized to accommodate the text within. When text is added, the symbol grows in size and when text is removed the symbol size shrinks. The size of the font used also affects the size of the symbol. You can format the text symbol for font and color. Text symbols have all the functionality of other static symbols except rotating and flipping. Topics in this section Add text to a display Edit a text box Move a text block Add text to a display Use the Text tool to add text to a display. 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Text button, or Click Draw > Text. The mouse pointer changes to a text pointer. 3. Click in the display where you want to add the text. 4. Type the text in the text block. (You can only type the text on one line. The text will not wrap.) Text block refers to the text area associated with a shape that appears when you click the shape with the text tool or select it with the pointer tool. 5. When you finish typing, press ESC or click outside the text block. Edit a text box 1. In Build mode, open a display and double-click the text block you want to edit. 2. Click where you want to add or edit text. 3. Type to add text or edit the text. 4. When you finish typing, press ESC or click outside the text block. 138 PI ProcessBook 2015 User Guide

149 Symbols in a PI ProcessBook display Move a text block 1. In Build mode, open a display. 2. Click the text block you want to move, drag it to the new location, and then release the mouse button. Line symbol Lines within a drawing can be diagonal, horizontal, or vertical. Attributes you can change include line color and whether a line is dotted or dashed, thick or thin, and with or without arrowheads. Draw a line 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Line button, or Click Draw > Line. The mouse pointer changes to the line pointer. 3. Point to where you want to start the line. 4. Drag to draw the line. Press the SHIFT key while drawing to constrain the line to a horizontal or vertical line. Rectangle, square, arc, ellipse, and circle symbols Using the drawing tools, you can create these simple shapes: Rectangle, Square Arc Ellipse, Circle PI ProcessBook 2015 User Guide 139

150 Symbols in a PI ProcessBook display Draw a rectangle, square, arc, ellipse, or circle 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Rectangle, Arc, or Ellipse button, or Click the appropriate tool. The mouse pointer changes to a tool pointer. The appearance of the pointer indicates the type of tool you have chosen. 3. Click the display to place the upper left corner of the shape, and drag down and to the right to create a shape of the desired size. Press SHIFT while drawing to constrain the object to a square, circle, or circular arc. 4. Release the mouse button to complete a rectangle, square, ellipse, or circle. -or- 5. If you used the arc tool, one quarter of the shape is drawn. Click on it and resize it to the desired shape. Click and drag the end of the arc to change the angle. Press SHIFT to change the angle in 15-degree increments. When the arc is first drawn, the handle for reshaping the angle is just inside the resize handle. Polygon symbol The Polygon tool draws irregular shapes. When you select the polygon tool the mouse pointer changes to a polygon pointer. Polygons are drawn using the current color and line style attributes. 140 PI ProcessBook 2015 User Guide

151 Symbols in a PI ProcessBook display Draw a polygon 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Polygon button, or Choose Draw > Polygon. The mouse pointer changes to the Polygon pointer. 3. Click inside the display where you want to start drawing the first point of the polygon (point "a" in the example below). 4. Drag to create the first side (point "a" to point "b" in the example below). 5. Release the mouse button to position the second point of the polygon (point "b" in the example below). 6. Click at each of the remaining points of the polygon (points "c" through "g" in example below). Lines are drawn between the clicks. 7. To close and fill the polygon, double-click to place the last point in the polygon (point "g" in the example below). This action draws a line from the last point to the first point (point "g" to point "a" in the example below). Polyline symbol A Polyline is a set of line segments that you can draw using the Polyline tool. It uses the current line style attributes. Once you add a Polyline symbol, you can edit it in the same manner as the existing Polygon symbol. You can move or resize the entire symbol, as well as move the individual endpoints to create any desired arrangement. PI ProcessBook 2015 User Guide 141

152 Symbols in a PI ProcessBook display Draw a polyline 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Polyline button. The mouse pointer changes to the Polyline pointer. 3. Click inside the display where you want the starting point of the first line segment. 4. Drag to the location of the second point to make the first line. Each time you click the mouse button again, a new line is drawn from the location of the previously plotted point to the current location of the mouse pointer. 5. To finish the Polyline drawing, double-click. Press ESC to cancel the line altogether. Press the Shift key while you draw to create Right Angle Polylines. Similarly, pressing Shift while editing manipulates a point orthogonally in relation to the next endpoint. Graphic symbol In PI ProcessBook you can: Include a graphic file from another application, such as Microsoft Visio or CorelDRAW. Use a drawing or picture as the background for your display, then add symbols to it. This can reduce the amount of time you take to create a drawing. Rotate or flip a picture. Add an illustration to a display, and store it within the display or link it to the original graphic file. (Linking means that if the original graphic is edited or moved, it affects the appearance of the display as well.) Load an image in one file format and later save it in a different format. A drawing is display-resolution dependent, which means that it might look different from one monitor to another. Test the drawing on each monitor to see how it will look. PI ProcessBook supports the following image formats. Note that PI ProcessBook draws using raster graphics, so vector graphic formats might not appear exactly as expected. BMP CUR Windows Bitmap file; standard, non-compressed bitmapped graphic A file that contains an image that defines the shape of a cursor on the screen. 142 PI ProcessBook 2015 User Guide

153 Symbols in a PI ProcessBook display EMF ICO JPEG PNG TIFF, TIF WMF Enhanced Metafile Format; 32-bit Microsoft Windows Metafile vector format that also supports raster images. A file that contains a graphic to be used as an icon. Joint Photographic Experts Group - Refers both to the standard for storing compressed images and a graphic stored in that format. Note that this format is prone to lose resolution when it is repeatedly saved. Portable Network Graphics - graphic image format that utilizes lossless compression. Tag Image File Format graphic image. The Windows Metafile Format - the original 16-bit native vector file format for the Microsoft Windows operating environment. Add a graphic 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Graphic button, or Click Draw > Graphic. The mouse pointer changes to a graphic pointer. 3. Click in the display where you want to add the image and drag the pointer to form a rectangle into which the graphic will be placed. When you release the mouse button, the Define Graphic window appears. 4. Click the Browse button to locate the graphic drawing. -or- PI ProcessBook 2015 User Guide 143

154 Symbols in a PI ProcessBook display In the File Name box, type the path and file name of the graphic you want to insert. 5. Under Image Location, select: Embed if you want to update the graphic within the display file. Link if you want to store the graphic separately from the display file. 6. Under Format, select the appropriate option. 7. Click OK. Stretching the image to fit the bounding rectangle may distort the appearance of the graphic. A copy of the graphic is added to the display. Symbol Library A large selection of images is available in the Symbol Library. Many of these images have characteristics such as color, fill type, orientation, or background, which you can modify. On the installation CD, OSIsoft provides several other commonly used images in the ProcessBook file SYMLIBRY.PIW. You can cut and paste these images into a display. You can also add frequently used drawing components (for example, company logos) to this PIW file for later reuse. This file is usually installed here: C:\Program Files\ProcessBook\ProgramFiles\pipc\Procbook\SYMLIBRY.PIW Topics in this section Add an image from the Symbol Library Symbol Properties Add an image from the Symbol Library 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Symbol Library button. -or- On the Draw menu, click Symbol Library. The mouse pointer changes to the Symbol Library pointer. 3. Click in the display where you want to add the image and drag the pointer to form a rectangle into which to place it. When you release the mouse button, the Symbol Library window appears. 4. Under Categories, click the type of image you want to use, such as Boilers, Controllers, Valves, etc. 144 PI ProcessBook 2015 User Guide

155 Symbols in a PI ProcessBook display 5. Click Options to modify the image. See Configure Symbol Library options. 6. Click OK to add the image to your display. Configure Symbol Library options 1. In the Symbol Library window, a selection of images is displayed in the right-hand side of the window, click the appropriate symbol, and then click the Options button. -or- Right-click the image and click Symbol Options. The Symbol Options window appears. 2. Configure the following options: Fill Mode Controls the way the image is drawn. Options include Original, Shaded, Solid or Hollow. Fill Color PI ProcessBook 2015 User Guide 145

156 Symbols in a PI ProcessBook display Click the color box to change the fill color. Flip Select Horizontal, Vertical, or Both to change the orientation of the image. The default setting is None. This setting returns the image to its original position. Rotation Select 90, 180, or 270 to turn the image by 90 degree increments. The default setting is 0. This setting returns the image to its original position. Transparent Check this box if you want a transparent background. Background Color If the Transparent check box is not selected, you can click the color box to change the background color. Change the image fill and background color directly on a display by using the Fill Color and Background Color buttons on the Symbol Formatting toolbar. 3. Click the Defaults button if you want to revert to the default settings. 4. Click OK to accept the changes and return to the Symbol Library window. Symbol Properties If you right-click an image in the Symbol Library, the focus box at the upper left reflects that image. A small window appears; you can choose either Symbol Options or Properties. If you choose Properties, you see a Symbol Properties window, which displays the Symbol description, Data size, Type, and Handle information. This information could be used in VBA automation of PI ProcessBook. 146 PI ProcessBook 2015 User Guide

157 Work with symbols Topics in this section Details and annotations Data Favorites add-in Select and move a symbol Select multiple symbols Rotate a symbol Flip a symbol Delete a symbol Stacking order Align multiple symbols Connectors Item Definition button Status report for dynamic symbols Status flags for data Create composite symbols Analyze symbols in PI Coresight AF-based symbols Details and annotations The Details docking window is available to show data from dynamic symbols. The window is only available in Run mode and initially appears along the right side of your ProcessBook window; however, you can click and drag it anywhere inside the PI ProcessBook application. The PI Annotations editor is located at the bottom of the Details window. Topics in this section Details window PI annotations maintenance Details window To view data in the Details window, click a symbol in your display. Moving a plot cursor changes the rows highlighted to show the range of data around the cursor time. By default, the window remains open when a different display symbol is selected. The Details window is hidden when you switch to Build mode. You cannot open the Details window while in Build mode. PI ProcessBook 2015 User Guide 147

158 Work with symbols The Details window contains the following components: Data Item This field allows you to choose a data item, including datasets and PI tags in the selected symbol (by default, the first trace or main data source for the selected symbol is shown). The Show All entry shows data for all the data sources in the selected symbol. Option The Show All option only displays the first 3,500 values. This value can be increased by adding the registry key HKCU\Software\PISystem\PI - ProcessBook \DetailsAddin\MaxPoints (type DWORD) and setting it to the maximum number of points desired. This field allows you to toggle among three different types of information about your data source. Data Shows recorded values for a selected symbol's time range. By default the table is sorted on the timestamp column in descending order. Questionable (Q) The event value is unreliable or the circumstances under which it was recorded are suspect. Annotated (A) An annotation has been made to the event to include further information or commentary. You can add annotations to PI tags using PI ProcessBook, if you have permission to write to that tag on the PI Data Archive. Substituted (S): The event value has been changed from the original archived value. Statistics Shows a table of available summary values available, for example, Average, Minimum, and Maximum. Selecting this option disables the PI Annotation Maintenance controls. Available statistics vary for each symbol type. Point Attributes 148 PI ProcessBook 2015 User Guide

159 Shows an alphabetized list of PI point attribute values. This option is only available for PI tags. Selecting this option disables the PI Annotation Maintenance controls. See PI point attributes for details. Each view option provides the following controls: <Symbol Name> The name of the symbol selected on the display is shown above the data table. Refresh Work with symbols Refreshes data in all tables. Data shown does not automatically change after a symbol is first selected. You must use refresh to view any updates in the Details window. Enlarge/Shrink Font Makes the text size bigger or smaller. This may reduce the number of visible rows. Copy to Clipboard Allows you to copy the data table to your clipboard. You can then paste this data into another location such as a Microsoft Excel spreadsheet. Use the pin icon to lock the docking window to your screen. Click the pin icon again to unpin the window and minimize it along the border of your PI ProcessBook window. When a docking window is unpinned, a button appears along the side of the screen. Hover over it to re-expand the window. Open Details window Click View > Details to display the Details window. Alternatively, you can select the Show Details and Annotations command from the Context Display Menu. The Details window is only available in Run mode. PI annotations maintenance Annotations allow you to associate related information (such as text comments and other binary data) with any archive value. The PI Annotation Maintenance group at the bottom of the Details window allows you to easily annotate values on your dynamic symbols. PI ProcessBook 2015 User Guide 149

160 Work with symbols Annotations can be added, edited or viewed, provided that: The selected data item points to a PI Tag The target PI Data Archive server can read and write annotations You have permission to write annotations on the target PI Data Archive server A row representing an event is selected in the Data table If the target PI Data Archive server (or collective) is unavailable or cannot accept edits from the current user, the control is disabled. If the PI Data Archive server becomes unavailable while you are entering an annotation and you then click the Save button, you will receive an error. If you select Show All from the Data Source drop-down box on the Details window, the Value and Value Type fields in the PI Annotation Maintenance group are disabled. Add annotations 1. Open the Details window. 2. In Run mode, select a dynamic symbol on your display. 3. Select the event of interest in the Data table. 4. Click inside the Value text box and enter the information you wish displayed in your annotation. 5. Select a value from the Value Type drop-down box. 6. Click the Save button at the top of the PI Annotations Maintenance group. An annotation icon appears on the dynamic symbol if it is showing the annotated event. Hover over this icon to read your annotation. A record of the annotation also appears on the Details window when the Data option is selected. Data Favorites add-in The Data Favorites add-in provides a way to configure symbols by dragging a PI tag name (or other data item) from a list onto the symbol. 150 PI ProcessBook 2015 User Guide

161 Work with symbols The add-in can be unloaded or set not to load at startup by changing the options in the Add-in Manager window. When the Data Favorites add-in is first loaded, its window appears in the upper left corner of the PI ProcessBook application window. The window is only accessible in Build mode. If the window is closed, in Build mode, click View > Data Favorites. See Load addins for details. There are two panels within the Data Favorites window: Search Favorites Each panel can be collapsed if it is not needed. Topics in this section Select a default symbol for data favorites Search for data favorites Favorites panel Select a default symbol for data favorites The Default Symbol button dropped on an empty area of the display. controls which symbol is created when data items are To set the default symbol, click the Default Symbol button and select an option from the drop-down list. Available symbols: Bars Trends Values XYPlots If the selected symbol type does not support the data type of the dropped data item, a value symbol is drawn instead. Search for data favorites PI ProcessBook 2015 User Guide 151

162 Work with symbols Use the Search panel to search for PI tags and other data items. 1. To search for data items, use the Search Mask text box or click the Tag Search button to launch the Tag Search window. Tags selected using the Tag Search window automatically populate the Data Favorites Search list. The Search Mask field searches for tags matching the entered string on your default PI Data Archive server. 2. To save a data item to your Favorites, either drag and drop it into your Favorites list, or right click the data item in the Search list and click Add to Favorites. Use the pin icon to lock the docking window to your screen. Click the pin icon again to unpin the window and minimize it along the border of your PI ProcessBook window. When a docking window is unpinned, a button appears along the side of the screen. Hover over it to re-expand the window. Favorites panel The Favorites panel provides controls for manipulating the list of data favorites. The Favorites list is saved per user, so when a different user opens PI ProcessBook on the same machine, their list may be different. Topics in this section Use favorites Import or export data favorites Drag data between PI ProcessBook and other applications Use favorites 1. In Build mode, click View > Data Favorites to launch the Data Favorites docking window. 2. Select a default symbol for Data Favorites. Any favorites dragged onto a display take the form of this symbol. 3. In the Favorites panel, drag and drop any listed favorite to an existing trend or XYPlot symbol, or to a blank area of a display. The data item is permanently added once the display is saved. 152 PI ProcessBook 2015 User Guide

163 Work with symbols If the dropped selection contains multiple data items (for example, multiple tags) and the Bar or Value symbol is selected, a symbol is created for each one, slightly offset from each other, in cascading layout. Import or export data favorites Import data favorites: a. Right-click in the Datasource list in the Favorites panel, and click Import Favorites. b. Select a text file to import. Export data favorites: a. Right-click in the Datasource list in the Favorites panel, and click Export Favorites. The Save as window appears. b. Name the export file to save. Drag data between PI ProcessBook and other applications The Data Favorites add-in supports dragging a list of tag names in the following formats: One row of tags separated by either a semi-colon or tab delimiter Multiple rows (row delimited by a new line) of at least two columns which are delimited by either a tab or a semi-colon. Only one delimiter is used, and while there can be more than two columns in the dragged rows, only the first two columns are used. The first column must be the tag name, the second column may be an optional tag descriptor. Drags can come from any application that supports the text clipboard format, for example, Microsoft Word or Excel. Select and move a symbol Before you can apply commands to display objects you must select them. You can select single or multiple items on a display. 1. In Build mode, open a display. 2. Click a symbol in your display. Small squares appear around the bounding rectangle of the symbol. 3. If you want to move the symbol, drag the symbol to the desired location within your display. Press the Tab key to toggle among different symbols in your display once a symbol is selected. When you press the Tab key you deselect the current object and select the next object in the tabbing order. The tabbing order follows the stacking order on the display (by default, the order in which objects were added to the display). PI ProcessBook 2015 User Guide 153

164 Work with symbols To cancel a selection on any one object press SHIFT while clicking the object to deselect. To cancel selection of all objects on a display, click on the display background (in a spot where there are no symbols). ActiveX controls on the display do not react to tab order like other ProcessBook symbols because they are treated as separate windows within the display. Select multiple symbols You can perform many of the editing and organizing functions on more than one symbol at a time. For example, once selected, you can move multiple symbols to a new location, edit the color of lines and fill for multiple symbols, or even flip and rotate multiple symbols. 1. In Build mode, open a display. 2. Do one of the following: To select all of the symbols in a drawing area, click Edit > Select All. To select individual symbols, press SHIFT while clicking each symbol. Selection handles display around each selected item. To select several symbols at the same time, click near a symbol, and then drag to create a rectangle that includes all the symbols you want to select. To select symbols that are stacked on top of each other, click the top symbol. Selection handles appear. Continue clicking the top symbol to select symbols located under the top symbol. 3. Click the symbols you want to change or move. The selected symbols display handles. Rotate a symbol You can rotate a drawing symbol in 15 or 1 increments. You cannot rotate text, graphics, or OLE objects. Symbol Library images can only be rotated in 90 increments. 1. Select the symbol you want to rotate. 2. Click Arrange > Rotate. A rotation object appears in the center of the symbol. 3. Click a selection handle and drag in the direction that you want to rotate the symbol. The symbol is rotated in 1 increments. -or- Press SHIFT while dragging to rotate in 15 increments. 154 PI ProcessBook 2015 User Guide

165 Work with symbols Flip a symbol You can create a mirror image of a symbol by flipping it. You cannot flip text, graphics, or OLE objects. 1. Select the symbol you want to flip. 2. Click Arrange > Flip > Horizontal to flip the symbol from right to left or Vertical to flip the symbol from top to bottom. Delete a symbol 1. Select a symbol or multiple symbols that you want to delete. 2. Press DELETE, -or- Click Edit > Clear. Stacking order Each symbol you add to a drawing occupies its own space in the drawing. The layers, and therefore the symbols, are stacked on top of each other. By default, the first symbol you draw is at the bottom of the stacking order and the last symbol you draw is at the top of the stacking order. Using the stacking commands, you can move a symbol forward or backward within the stack. Depending on the number of objects between top and bottom, you may need to repeat a stacking command several times to move the symbol to the desired location within the stack. PI ProcessBook 2015 User Guide 155

166 Work with symbols Move a symbol forward or backward in the stack 1. Select the symbol you want to order. 2. On the Arrange menu, choose the direction you want to move the symbol: Click Forward to move it up one level (on top of something else). Click Backward to move it down one level (below something else). Click Bring to Front to move it to the top of the stack (on top of everything). Click Send to Back to move it to the bottom of the stack (below everything). Align multiple symbols You can align drawing symbols with each other. Use this feature to align symbols along their tops, bottoms, sides, or centers (either vertically or horizontally). The first symbol you select is the symbol to which others are aligned. When two or more value symbols are aligned, the text justification for each matches the alignment rule: left, center, or right. 1. Select the symbols you want to align. 2. Click Arrange > Align. The Align submenu appears. 156 PI ProcessBook 2015 User Guide

167 Work with symbols 3. Click the alignment options you want. All the selected symbols are aligned to the symbol you first selected, along the axis you specify. Connectors Topics in this section Connect symbols Connection points Attach a symbol to a connector Connectors window Detect connections and attachments Reroute a connector path Connect symbols Connect two symbols to each other using the connector symbol. A connector remains attached to other symbols regardless of how you move them. A connector is intended for modeling and automation purposes. Connection points on each symbol define where a connection occurs. You can add, delete, or move connection points on a symbol. Connectors try to avoid objects as they are being connected between two symbols. As connectors are drawn, they are orthogonal to the display, meaning that they go horizontally or vertically. There are no diagonal connectors. PI ProcessBook 2015 User Guide 157

168 Work with symbols Each end of a connector attaches to a connection point on another symbol. If you have not already created a connection point on a symbol, a connection point is built automatically as you draw the connector across a bounding line of the symbol. 1. Click the Connector button. -or- Click Draw > Connector. 2. Click the first symbol, called the source, and drag the mouse into the second symbol, called the destination. The connector arrow has a flow direction from the source to the destination. Connection points appear on both symbols. We recommend that you not move connectors by dragging and dropping them. Instead, use the Connectors window to rearrange connectors. You can use the Undo and Redo commands with connectors. Connection points Connection points on each symbol define where a connector may connect. Connection points are visible in Build mode only and appear on symbols as small x marks. When you select one with your cursor, it changes to an x within a bounding circle. A connection point is created automatically when a connector is dragged into a symbol. This point is created at the midpoint of the nearest edge of the bounding rectangle of the symbol. The end of the connector is moved to the connection point. You may add connection points and move them to specific locations. A connection point can be used for either the start of the flow or the end of a flow. The same connection point can be used for both. A flow can be bi-directional. If a second connector is dragged over a symbol, it either moves to the existing connection point or creates a new one. For irregular figures, connection points are placed near the midpoint of the side of the bounding rectangle of the figure, as shown in the illustration below, rather than inside the figure itself. You can adjust the position of the connection point to touch the actual figure. 158 PI ProcessBook 2015 User Guide

169 Work with symbols Connector with Connection Point on the Bounding Rectangle If a symbol is placed in front of another, the connection points on the hidden symbol cannot be selected. You can solve this problem by placing the two symbols on different layers of the display. Topics in this section Add connection points Disconnect a connection point Delete connection points Move connection points Determine the identifying number of a connection point Add connection points 1. In Build mode, select the symbol. 2. Click Edit > Connection Points > Add. A point appears at the upper left of the symbol. 3. Optional: Drag the new connection point to a different location. After you select one connection point, you can press C on the keyboard to cycle through any additional connection points on that symbol. Disconnect a connection point 1. In Build mode, click the connector connected to the connection point you want to disconnect. 2. Move your pointer over the connection point you want to disconnect. The point turns into a Click and drag the + sign to disconnect the connection point. PI ProcessBook 2015 User Guide 159

170 Work with symbols Delete connection points 1. Select the connection point. 2. Click Edit > Connection Points > Delete. Move connection points Connection points can be moved to a new position within a symbol. To do this, click a connection point in Build mode and drag it. For very fine adjustments, you can move connection points on a symbol. 1. In Build mode, click on a connection point. 2. Click Edit > Connection Points > Move. The Connection Point Placement window appears, where you can edit the width and height ratios in comparison to the X and Y axes of the symbol. Determine the identifying number of a connection point In Build mode, if you place your mouse over a connection point, a ToolTip shows the connection point number. The following illustration refers to connection point 2 on Rectangle 1. Connection point numbers are used on the Connectors window. Connection Point Numbering In other words, connection points have identifying names that are derived from the symbol name. For example, for a rectangle named Rectangle2, two connection points would be named <Rectangle2 : 1> and <Rectangle2 : 2>. 160 PI ProcessBook 2015 User Guide

171 Work with symbols If you are using a symbol from the Symbol Library, the connection point is named <TBSymbolx : n>, where TBSymbolx represents the specific name of the symbol. Attach a symbol to a connector You can attach a symbol, such as a text box or a meter, to a connector. Attaching is different from connecting. An attached symbol moves with a connector but does not account for flow direction. 1. Click Edit > Display to open the Display Properties window. 2. Be sure the Enable Connector Attachments option is selected. Click OK. 3. Create the subordinate symbol and drag and drop it across the connector. The subordinate attachment is attached to the connector. The placement is snapped either left/right or top/bottom depending upon the orthogonal direction of the connector at the position where the attachment has been placed. To remove an attached symbol from a connector, click the symbol and drag it away from the connector. Attach a symbol as an adjunct to another symbol You might want to attach two or more symbols so that they move together but do not become a composite symbol. For example, you might attach a text label symbol to a pump symbol. The text symbol is subordinate to the pump symbol and follows the pump symbol if the latter is moved. The advantage of this method of attachment is that each symbol in the group retains its identity and can be acted on individually for automation purposes. 1. Select at least two symbols. This enables the Symbol Attachments icon. 2. Click the Symbol Attachments icon, or Click Edit > Symbol Attachments, or On the right-click menu, click Symbol Attachments. The Symbol Attachments window appears. The symbols you selected appear as master or subordinate symbols. The first symbol selected becomes the master, the subsequent ones are subordinates. PI ProcessBook 2015 User Guide 161

172 Work with symbols 3. Select the Master Symbol. As you change the master, the title of the window changes also. 4. Place a check mark for the subordinate symbol or symbols and click OK. 5. Repeat the process for each master symbol. The Detach All bar at the top can be used to remove all attachments from the currently selected symbol in the Master box. To detach only one attachment, clear its check box. 6. Click OK. When you move a master symbol, any subordinates move with it. Connectors window Use the Connectors window to rearrange connections. To reach this window: Click the Connectors toolbar button. Click Edit > Connectors. -or- -or- On the right-click menu, click Connectors. The Connectors window affects connector symbols only. It cannot be used to attach one symbol to another symbol without a connector. The Connectors window has two tabs, Flow and Attachments. Each connector is identified by a unique name, which is revealed by a tooltip in 162 PI ProcessBook 2015 User Guide

173 Work with symbols your display. See Configure the flow of a connector and Configure attachments to a connector for details. Topics in this section Configure the flow of a connector Configure attachments to a connector Configure the flow of a connector The Connectors window, Flow tab specifies the source and destination of each connector from one symbol's connection point to another symbol's connection point. The window is available whenever a Connector exists on a display. The Flow tab shows two tree diagrams, Source and Destination, where you can change the connection points for the connector shown in the Connector drop-down box. There is also a Flow Direction drop-down box associated with the connector that appears in the Connector drop-down box. The Auto Avoid option is selected as a default, so that connectors route around other objects in the display. 1. In Build mode, open the Connectors window. The Flow tab is in focus. PI ProcessBook 2015 User Guide 163

174 Work with symbols Hover over any symbol or connector on a display for a tooltip to identify the connector you wish to rearrange. 2. In the Connector drop-down box, select a Connector. Connection points for the selected connector appear highlighted in the Source and Destination boxes. 3. Optional: Modify the Flow Direction. 4. Click a new Connection Point on the Source tree to change the source connection point. 5. Click a Connection Point on the Destination tree to change the destination connection point. 6. Click Apply. As you adjust connection points in the Connectors window, the corresponding connector in your display also provides visual indicators to help you see how your changes will appear. This changes the display. 7. Repeat these steps for all connectors on the display that you wish to modify. 8. Click OK. Configure attachments to a connector For very complex displays, it may be helpful to attach or arrange connector attachments through the Attachments tab on the Connectors window. 164 PI ProcessBook 2015 User Guide

175 Work with symbols 1. In Build mode, create a connector. See Connect two symbols. 2. Create the auxiliary symbol to be added to the connector. 3. Open the Connectors window, and select the Attachments tab. 4. Choose a connector from the Connector drop-down box. Unattached symbols on the display are listed in the Unattached Symbols box. Symbols that are already attached to the connector appear in the Currently Attached box. Existing source and destination symbols that are connected to connectors are not listed. 5. Highlight a symbol in the Unattached Symbols box that you want to add and click Add. The symbol now appears in the Currently Attached box. The Unattached Symbols box does not include Connectors or symbols attached to other symbols. 6. Adjust the position and placement of the attached symbol as needed. To move the symbol closer to one end of the connector, double-click the specified % and change it. To move the symbol from the top of the connector to another placement, double-click the default Top and choose Left, Right, or Bottom. 7. Click Apply and select another connector to adjust. PI ProcessBook 2015 User Guide 165

176 Work with symbols 8. If you need to remove an attachment, highlight the attachment in the Currently Attached box and click Remove. 9. When you are finished adjusting, click OK. Connect two symbols As connectors are drawn, they are orthogonal to the display, meaning that they go horizontally or vertically. There are no diagonal connectors. Each end of a connector attaches to a connection point on another symbol. If you have not already created a connection point on this symbol, a connection point is built automatically as you draw the connector across a bounding line of the symbol. Connectors and connection points have unique numbers to help you manipulate them in the Connectors window. You can open the Connectors window once you draw a connector; even if it is not attached to any symbols. Do not manipulate connectors by dragging and dropping them. Use the Connectors window to rearrange them. 1. Click the Connector button. -or- Click Draw > Connector. 2. Click on the first symbol, called the source, and drag the mouse into the second symbol, called the destination. The connector arrow has a flow direction from the source to the destination. Connection points appear on both symbols. If your mouse does not touch a symbol, you do not see a connection point. Do not adjust the connector manually. If you do not see connection points on both symbols, delete the connector and draw it again. You can use the Undo and Redo commands with connectors. Detect connections and attachments To see whether connectors or attached symbols exist for a particular symbol click the symbol or connector and hold down the mouse button. If there are existing connectors, all connectors with attached symbols for that symbol are highlighted and display in a different color (for example, white for black or yellow for blue). If there are no connectors, nothing happens. 166 PI ProcessBook 2015 User Guide

177 Work with symbols Reroute a connector path When you move a symbol, its connectors shift automatically to stay connected to the moved symbol and avoid overlapping other symbols in the display. Connectors can overlap each other. If a drawing becomes complex, you can request that all connectors be rerouted by clicking the Reroute button. If you select specific connectors and click Reroute, only those connectors are rerouted. Connectors crossing each other may be unavoidable but should be minimized. Do not move connectors manually. The object avoidance feature in PI ProcessBook can either ignore or take connectors into account when looking for the shortest path from the source to a destination. This behavior is controlled by the ConnectorsAvoidConnectors setting in ProcBook.ini. Object avoidance does not occur after you drag and drop a connector s line segment. If you modify the position of a connector manually, the center point and end points on the connector change from green to red, indicating that automatic object avoidance is turned off and you are responsible for all further updates to that connector. Rerouting can consume significant system resources (CPU and memory) to solve complex problems. Factors that can increase complexity include: A very large display Large numbers of Connectors on a single display Large numbers of symbols to be avoided A high number of "Lines per Screen Unit" (set in "Arrange", "Grid Size ", "Lines per Screen Unit" 1 equals the largest cell size; 30 gives the smallest cell size) Routing multiple displays on the same PC Item Definition button Use the Item Definition button in either Build or Run mode when you want to see what tags and formatting options were used in any symbol that uses a window for basic configuration. It is the same as double-clicking on the item with the Build mode pointer. If the symbol does not have a definition window, the button is dimmed. You can change the selections and save the new definition. This button does not open any of the formatting windows (for example, Font or Color). Display or change item definition 1. In either Build or Run mode, open a display. 2. Double-click the dynamic symbol whose definition you would like to change (such as a value, bar, trend, or button). PI ProcessBook 2015 User Guide 167

178 Work with symbols -or- Click the symbol, then on the Formatting toolbar, click the Item Definition button. If the Item Definition button appears dimmed, the symbol you selected might not have a definition window. A definition window displays that corresponds to the symbol you selected. 3. In the appropriate window, make your changes to the item's definition, and then click OK. These changes are saved with the symbol. Status report for dynamic symbols The status bar at the bottom of the PI ProcessBook application shows whether dynamic symbols in a display are updating normally. The Status icon is a green circle when there are no errors. It is a blue circle containing a question mark (?) if the display shows questionable data or a yellow arrow for substituted data. It contains an X in a red circle if a dynamic symbol is reporting bad data (or shutdown status). As you shift focus from one display to another, the icon might change. If you shift back to the Table of Contents, the status icon remains from the last display in focus. or The Status Report window appears when you have a display in focus and double-click the Status icon. This report lists all the symbols in a display that have data associated with them. You see the tag to which the symbol is connected and, if there is an issue, the error message appears. You can sort the list by any of the column headings. For troubleshooting purposes, the Message Log button shows you the SDK Log file. 168 PI ProcessBook 2015 User Guide

179 Work with symbols You can save this report as a.csv file by using the Save to File button. The status bar can be displayed or hidden from the View Status Bar item on the View menu. Status flags for data In addition to the Error indicator shown in the status bar, PI ProcessBook has three types of flags to indicate that the data is valid but additional information is available. Each dynamic symbol can display an icon when there is additional status information available. When move your pointer over a flagged symbol, a tooltip appears with the status message. In trends, status messages appear to the right of the tag values in the legend if the status is associated with the last value on the plot. The icons are shown below: Questionable Indicates that there is some reason to doubt the accuracy of the value. Substituted Used to indicate that the value has been changed from its original value. This value is set only by the PI Data Archive server when an existing value is changed. Annotated Indicates that there is a comment about a value. Text annotations are shown in symbol tooltips. Use the Details window to view and add annotations. If a tag has more than one flag, the highest priority status will be shown. The priority from high to low is: Questionable, Substituted, Annotated. To view all the flags associated with a PI Tag on the display, use the Details window, Data option. If you clear the Show Value Attributes check box in your Start Preferences, you do not see these icons. Consider disabling the icons to improve ProcessBook performance if you have very high speed sub-second data. See Status report for dynamic symbols Create composite symbols Composite symbols are created from the symbols in the drawing tools library. After you create a composite symbol, you can assign it to an asset in your AF database to create an AF-based symbol. 1. Click File > New to open a new display. 2. Select Build mode. 3. Using the drawing tools, add symbols to the display. 4. Click Arrange > Group to include all the elements into a group. PI ProcessBook 2015 User Guide 169

180 Work with symbols You can now assign the composite symbol to create an AF-based symbol. Topics in this section Group, ungroup, or regroup symbols Modify composite symbols Group, ungroup, or regroup symbols When creating or manipulating complex shapes, it is sometimes easier to combine individual symbols into one. You can group two or more symbols together, or you can group several groups. Once grouped, any commands that you apply affect the composite symbol as if it were a single symbol. If you want a group of symbols to remain together, but you need to continue modifying the components separately, you can attach the symbols instead of grouping them. 1. Select the symbols you want to group and from the Arrange menu choose one of the following: Group The symbols combine into one composite symbol with selection handles around the entire group. Ungroup The group is disassembled into its component symbols. Regroup You do not need to re-select all the components to regroup a previously grouped set of symbols. This command is only enabled when it applies. Modify composite symbols You can change one or all symbols within a composite symbol. When you are modifying an AFbased symbol, changes only take effect after you assign it to an asset in the AF database. Before you start To work with AF-based symbols, you must open PI ProcessBook and verify that the AF Browser is open and that you are connected to a PI AF server. 1. Open a display in Build mode and then locate and select the AF-based symbols. 2. Optional: If you have a composite symbol and you only want to change one of the grouped symbols, select the composite symbol and then click Arrange > Ungroup. This action separates the grouped symbols so that you can select symbols individually. 3. To change the symbol, right-click the symbol and then click Change Symbol. 170 PI ProcessBook 2015 User Guide

181 Work with symbols You must right-click directly on the symbol you want to change. The Change Symbol window opens. 4. Select the type for the new symbol and click OK. 5. When you are finished with your modifications, save the display file. The changes you made to any symbols in the display are saved only within the PI ProcessBook file and not updated in the AF database. To assign the modified symbol to an AF element template, see Assign symbols to AF element templates. To assign the modified symbol to an AF element, see Assign symbols to AF elements. Analyze symbols in PI Coresight You can launch a PI Coresight analysis directly from a PI ProcessBook display. This feature only works with Internet Explorer 10 and later. The PI Coresight add-in does not support datasets (including ODBC datasets), but does support element relative and module database tags that resolve to PI tags. Before you start To use the PI Coresight add-in, you must have read access to the default PI AF server. The configuration database of the default PI AF server must specify the PI Coresight server in the Coresight URL attribute (the path to this attribute is OSIsoft\PI Coresight Coresight URL). The PI Coresight installation program creates this attribute. If the attribute does not exist, you must create the attribute for the PI Coresight add-in to work properly. The Coresight URL attribute requires the following configuration: Field Value Type Data Reference Value Setting String <None> URL to the PI Coresight server, such as WebServerName/Coresight 1. Open the display and select the symbol you want to use in a PI Coresight analysis. You can select single or multiple symbols within the display, or include all the symbols in the display. 2. Click the Explore in PI Coresight button. AF-based symbols AF-based symbols are those symbols in PI ProcessBook that you assign to a PI Asset Framework element template or element. You can use them to create customized, reusable symbols that represent your AF elements within displays. PI ProcessBook 2015 User Guide 171

182 Work with symbols AF-based symbols can be: Individual symbols taken from the drawing tools library Composite symbols made up of grouped symbols from the drawing tools library Either static or dynamic symbols Assignments are used to define the association between AF-based symbols and AF elements. You can make assignments in two ways: Assign the AF-based symbol to an AF element template, element, or attribute. This assignment is saved in an AF database and makes the AF-based symbol a reusable object that is added when you drag and drop the AF elements from the AF Browser into your display. Assign an AF element in your display to an AF-based symbol. This assignment is saved only in the PI ProcessBook display file and does not affect the element definition within the AF database. Topics in this section Connect to a PI AF database Assign symbols to AF element templates Assign symbols to AF elements Verify AF-based symbol assignment Build displays with AF-based symbols Find AF elements and attributes in displays Element Relative Display (ERD) Connect to a PI AF database Use the Select Database window to find and connect to PI AF databases. 1. Click File > PI Systems. The Select Database window appears. 172 PI ProcessBook 2015 User Guide

183 Work with symbols 2. Use the System drop-down list to connect to a PI AF server that contains a PI AF database you wish to use. The (...) button launches the Systems window, where you can connect to other PI AF servers. 3. Once you select a PI AF server, search for a PI AF database using the Databases search box. 4. Select a database and click OK. The database you select is used by the Element Relative Display (ERD) add-in, where you can populate symbols with PI AF elements from the database. Assign symbols to AF element templates You create AF-based symbols by assigning them to an asset in the AF database so that users can drag and drop them from the AF Browser into displays. The AF-based symbol will be saved to the AF database that you are connected to when you make the assignment. Before you start To work with AF-based symbols, you must open PI ProcessBook and verify that the AF Browser is open and that you are connected to a PI AF server. 1. Open a display and select the symbol you want to assign to an AF element template. 2. Right-click the symbol and then click Assign Symbol to Template. The Assign Symbol to AFElementTemplate window opens. PI ProcessBook 2015 User Guide 173

184 Work with symbols 3. In the PI System field, verify that you are connected to the AF server that contains the AF element template you want. 4. In the Database field, verify the name of the AF database that contains the AF element template you want. 5. Select the AF element template from the Element Template list. 6. Optional: To keep the default setting that synchronizes your active display with the updated assigned AF-based symbols, leave the Re-Sync all Symbols checkbox selected. 7. Click OK to save. If the AF element template already had an AF-based symbol assigned to it, click OK in the Overwrite Confirmation window to confirm that you want to overwrite the existing assignment. Results All AF elements based on this AF element template are updated to include the AF-based symbol assignment within their element definitions, unless the individual AF element has an AF-based symbol assigned to it. AF element-level assignments take precedence over AF element template-level assignments. When you drag and drop elements with this AF-based symbol assigned to them into your PI ProcessBook display, you see the AF-based symbol in your display. Assign symbols to AF elements You create AF-based symbols by assigning them to an asset in the AF database so that users can drag and drop them from the AF Browser into displays. The AF-based symbol will be saved to the AF database that you are connected to when you make the assignment. Before you start To work with AF-based symbols, you must open PI ProcessBook and verify that the AF Browser is open and that you are connected to a PI AF server. 1. Open a display and select the symbol you want to assign to an AF element. 2. Right-click the symbol and then click Assign Symbol to Element. The Assign Symbol to AFElement window opens. 3. In the PI System field, verify that you are connected to the AF server that contains the AF element you want. 4. In the Database field, verify the name of the AF database that contains the AF element you want. 5. Select the AF element from the Element list. 6. Optional: To keep the default setting that synchronizes your active display with the updated assigned AF-based symbols, leave the Re-Sync all Symbols checkbox selected. 7. Click OK to save. 174 PI ProcessBook 2015 User Guide

185 If the AF element already had an AF-based symbol assigned to it, click OK in the Overwrite Confirmation window to confirm that you want to overwrite the existing assignment. Results Work with symbols The AF element is updated to include the AF-based symbol within its element definition. When you drag and drop the element into your PI ProcessBook display, you see the AF-based symbol in your display. Verify AF-based symbol assignment If you want to know whether or not an AF element has an AF-based symbol assigned to it, you can view the AF-based symbol properties of the AF element in an open PI ProcessBook display. Before you start To work with AF-based symbols, you must open PI ProcessBook and verify that the AF Browser is open and that you are connected to a PI AF server. 1. Open a display in Build mode and locate and select the element in an open display. To use a search to find AF elements in displays, see Find AF elements and attributes in displays. Open the AF Properties pane and click the Extended Properties link in the General tab. If the AF element is assigned an AF-based symbol, you can view the file path it in the Extended Properties window. If there is no assigned AF-based symbol, the file path field is empty. Drag and drop the AF element into the display to view its AF-based symbol. If the AF element has no AF-based symbol, you will see an empty square with the name of the AF element in the display. Build displays with AF-based symbols Once AF-based symbols have been created and saved in the AF database, you access them through PI ProcessBook to use when you build displays. Before you start To work with AF-based symbols, you must open PI ProcessBook and verify that the AF Browser is open and that you are connected to a PI AF server. You must be connected to the AF database where the AF-based symbols are saved. 1. To add an AF element that has an assigned AF-based symbol to a display, open your display in Build mode and select an AF element from the Elements tab. You can add multiple AF-based symbols to a display. 2. Drag and drop the AF element into the display. The AF element is shown as the AF-based symbol in the display. PI ProcessBook 2015 User Guide 175

186 Work with symbols If the AF element has no assigned AF-based symbol, you will only see a square with the AF element name in the display. 3. Optional: Create and modify AF-based symbols while you build displays. Changes made to AF-based symbols within a display are not saved to the AF database when you save the PI ProcessBook file. To make AF-based symbols available for reuse in displays, you must assign the AF-based symbols to AF elements or element templates. 4. Optional: Change the sub-element and attribute display and label preferences. Click Tools > Display Builder Preferences to open the AF Display Builder Preferences window. Options include: Include all sub-element symbols when adding AF-based symbols to a display Include name labels and attribute values for symbols Determine label positions relative to the symbol Assign display elements to symbols You can build or update your display using symbols, and assign an AF element used in the display to a symbol that is not assigned to an asset in the AF database. This is helpful in cases when you are working with large displays and want to use the symbol to locate AF elements across the display, or when you want to build displays with AF-based symbols before saving them in an AF database. 1. Have your display open and in Build mode, and select the symbol you want to use. 2. Right-click the symbol and then click Assign Element to Symbol. The Assign Element window opens. 3. Locate and select the AF element you want to assign to the symbol. Hide Sub-Elements and Show Unassigned Elements Only change which AF elements are listed in the AF Browser. 4. Click OK. The AF element you assigned to the symbol will now appear as the symbol when you use it in your display. You can click Edit > Find Next to find multiple instances of the AF element in the display. Results The AF element is assigned to the symbol within the display, but this assignment does not apply to the AF element template used by the display element, or other instances where this AF element is used in other displays. To assign the symbol to an AF element template, see Assign symbols to AF element templates. To assign the symbol to an AF element, see Assign symbols to AF elements. 176 PI ProcessBook 2015 User Guide

187 Work with symbols Find AF elements and attributes in displays You can search for AF elements and AF attributes within a display. Before you start Open PI ProcessBook and verify that the AF Browser is open and that you are connected to a PI AF server. 1. To search the display for an AF element, open the display and click Edit > Find AF Element. The Element Search window opens. a. Enter the search criteria for the AF element and click Search. b. Select the AF element you want from the search results and click OK. The display element that uses the AF element is highlighted. You can click OK again to highlight the next instance of the AF element in the display. 2. To search the display for an AF attribute, open the display and click Edit > Find AF Attribute. The Attribute Search window opens. a. Enter the search criteria for the AF attribute and click Search. b. Select the AF attribute you want from the search results and click OK. The display element that uses the AF attribute is highlighted. You can click OK again to highlight the next instance of the AF attribute in the display. Element Relative Display (ERD) Element Relative Display (ERD) is an add-in that replaces the hierarchical, Module Database (MDB)-based Module Relative Display add-in from earlier versions of PI ProcessBook with an asset store based on PI AF elements and their associative attributes. This approach allows you to organize and structure PI System and other data according to objects users are most familiar with, and then visualize that data in a PI ProcessBook display. PI ProcessBook allows you to search a PI AF database for elements and their attributes. You can then add these data items to dynamic symbols to graphically display this data in real-time. For more information on PI AF and elements, see About PI data, and the PI AF User Guide. To convert a legacy module relative display to an element relative display you must first migrate modules in the Module Database to elements in the PI AF database. MDB to PI AF migration is handled upon upgrade to PI Server See the PI MDB to AF Transition Guide for further details. Topics in this section Add element relative data to a dynamic symbol PI AF context path PI ProcessBook 2015 User Guide 177

188 Work with symbols Change PI AF element context Add element relative data to a dynamic symbol Use the Select Attributes window to add PI AF elements and PI AF attributes as data items to dynamic symbols on a display. 1. In Build mode, double-click a dynamic symbol. This opens the Define <symbol> window. 2. Click the arrow next to the Tag Search button. A drop-down menu appears. If you plan to work with an element that does not have multiple contexts you can instead click AF2. This brings up the Select AF Attribute window, and gives you another way of searching for AF data. 3. Click Element Relative. The Select Attributes window appears. 178 PI ProcessBook 2015 User Guide

189 The active elements in the Elements of Interest pane on the Element Relative Display docking window appear in the top pane of this window under Current Element of Interest. If an element has attributes, those attributes are available to add to a dynamic symbol. If there are no active elements in the Elements of Interest pane, the Element Search window appears instead of the Select Attributes window, allowing you to do a new search to populate the Elements of Interest pane. 4. Click attribute names to select from the Attributes for the selected element list. 5. Click the button to add the selected attributes to the Selected Attributes list. Work with symbols Apply the following option if desired: UOM Allows you to select a unit of measure for a given attribute. 6. Optional: Click the Add Element Name button to add the element name of the current context to the symbol. Select the Use Full Path check box to show the full path of the current context instead of just the element name. 7. Click OK to add the selected attribute(s) to your dynamic symbol. PI AF context path A context path relates a PI AF attribute to a parent element within a PI AF database. An attribute added as a data item to a dynamic symbol can point to different underlying PI points, depending on its context path. Use context paths to drive displays created in PI ProcessBook. Displays that use context paths in this manner are referred to as element-relative. This means that the data displayed for the attribute depends, at any time, on the context path that links the attribute to a parent element. Context paths are used most frequently to change the data displayed by a symbol based on user selection. For example, based on the selection of PI AF elements or attributes that represent assets in a plant, a display may present data from similar assets in a single plant or in different locations. For example, assume Tanks 1-5 in a plant are all described by the same measurement attributes of temperature and pressure. Each tank is represented as an element in the PI AF database with corresponding temperature and pressure attributes. A display that references the temperature attribute could display data for each tank in turn by allowing the user to specify the context path to any particular tank element. This allows you to use one display to view data for any one of the five tanks simply by selecting the desired tank from a list. Change PI AF element context Configure a dynamic symbol with element relative data by adding attributes from a specific element to a display. You can dynamically change the context for the selected element on your symbols by clicking an element name in the Elements of Interest pane on the Element Relative Display window. The attribute data that appears on your dynamic symbol corresponds to the active element you choose. If the attributes you select are not available for a selected element, you see No Data on the display when that element is selected. PI ProcessBook 2015 User Guide 179

190 Work with symbols 1. Click View > Element Relative Display. The Element Relative Display window appears. 2. In the Search Mask text box enter a search query, and click the green arrow, or a. Click the Element Search button to launch the Element Search window, where you can use advanced search fields. b. Enter your search query and click the Search button. The Search results list is populated with your results. c. Click any element(s) from the Search results list. d. Click OK. Any new items are added to the Elements of Interest list in the Element Relative Display docking window. 3. Search results appear in the Elements of Interest pane. Click a column heading to sort results by that heading. Use the Filter text box to filter out unwanted entries. Access previously used filter expressions by clicking the small triangle at the end of the text box. Select the Group by check boxes to group your search results by template. Hover over an element to display a tooltip that show the element's full path. 4. Click an item from the Elements of Interest pane. 180 PI ProcessBook 2015 User Guide

191 Work with symbols If there is a corresponding attribute in your display, that attribute's data will refresh with the new element context. Use the pin icon to lock the docking window to your screen. Click the pin icon again to unpin the window and minimize it along the border of your PI ProcessBook window. When a docking window is unpinned, a button appears along the side of the screen. Hover over it to re-expand the window. PI ProcessBook 2015 User Guide 181

192 Work with symbols 182 PI ProcessBook 2015 User Guide

193 PI System data PI ProcessBook allows you to view PI System data from a variety of sources, including PI points, PI AF element attributes, and PI Calculation data sets (expression or summary). Topics in this section About PI data PI time PI tags (PI points) Data sets ODBC AF elements About PI data You can retrieve and visualize data from your PI System and other systems that support different business functions and provide access to diverse information. You will likely work with PI data stored in: PI Data Archive PI Asset Framework (PI AF) You will typically use these items to specify the information you want to see: PI Tags (PI Points) PI AF Assets PI AF Attributes Different types of data perform different functions: Time series data Calculated data Contextual data PI tags (PI points) A PI point is a stream of real-time data from a defined source, and is described by a corresponding tag name and other attributes. PI points are frequently referred to as PI tags, and the terms are used somewhat interchangeably. However, a tag is simply a reference name for a PI point. Topics in this section PI Data Archive and PI ProcessBook Updates to PI data PI ProcessBook 2015 User Guide 183

194 PI System data PI AF assets PI Tag Search window View PI point attributes PI Data Archive data types PI AF assets are the building blocks of PI AF (like modules in MDB) and can represent either physical or logical entities in your process, such as a physical device, piece of equipment, storage container, or representative section of a process. PI AF attributes PI AF attributes represent data that is associated with an element. They can contain configuration information for the element, or measured or calculated process data that provides the information necessary for getting and setting its value to and from a data stream. Conceptually, a PI AF attribute replaces the PI aliases and PI properties that were used in the PI Module Database. PI AF attributes are children of PI AF elements. Time series data PI Data Archive data is collected and stored in the form of points, each of which represents a time-series data stream from a particular source, such as a temperature or pressure sensor. A tag is a reference name for a PI point. Calculated data Statistical calculations allow you to view Averages, High and Low values, and measures of variance. These all provide critical information about data events over a period of time. Contextual data Contextual data is a method of associating PI points and their properties with their business use, location, service or role. A content creator can configure contextual data to reflect the structure of the information, making data and its presentation more logical and accessible. A PI point tag name is an example of contextual data. PI points also have various configurable properties associated with the data, called point attributes. However, this information is presented largely in language relevant to data processing, not in measurements or standard business terms that are easily accessible to users outside the Operations department. PI AF provides a holding place for contextual representations of all data used in your PI System. Elements and attributes can reference PI points and attributes or data in other systems, including relational databases and web services. 184 PI ProcessBook 2015 User Guide

195 PI System data Future data With PI Server 2015, you can store data with a timestamp in the future (up to January 2038) in a new type of PI point, called a future PI point. In some ways, data from future PI points looks and behaves differently than historical data. By default, future PI points have their step attribute turned on (step=1) and compression turned off (compression=0). This is because most future PI points store discontinuous signals (for example, a series of discrete predictions) for which linear interpolation cannot be assumed. With the step attribute turned on, trends show a staircase pattern. All dynamic symbols support future data and updating displays continue to update when you set the display range into the future. Trends show a dotted vertical now line so that when you pan into the future to see your forecast data stored in future PI points there is a visual indicator to help you track where you are in time. The following example demonstrates some of these features: Traces for future PI points show a staircase pattern, because the step attribute is turned on. The historic PI point, CDT158, has no data beyond the now line (which is in the center of the display). The trend cursor, set at a time in the future, shows values for both future PI points, but not for the historic PI point. PI time You can use a special syntax, called PI time, to specify inputs for time stamps and time intervals. PI time uses specific abbreviations, which you combine to create time expressions. Topics in this section PI time abbreviations PI time expressions PI ProcessBook 2015 User Guide 185

196 PI System data Time-stamp specification Time-interval specification PI time abbreviations When specifying PI time, you can use specific abbreviations that represent time units and reference times. Time-unit abbreviations Abbreviation s m h d mo y w Time unit second minute hour day month year week To specify time units, you can specify the abbreviation, the full time unit, or the plural version of the time unit, such as s, second, or seconds. You must include a valid value with any time unit. If specifying seconds, minutes, or hours, you can specify a fractional value, such as 1.25h. You cannot specify fractional values for other time units. Reference-time abbreviations Abbreviation Full version Reference time * Current time t today 00:00:00 (midnight) of the current day y yesterday 00:00:00 (midnight) of the previous day sun 1 sunday 00:00:00 (midnight) on the most recent Sunday jun 2 june 00:00:00 (midnight) on the current day in June of the current year dec DD december DD 00:00:00 (midnight) on the DDth day of December in the current year YYYY 00:00:00 (midnight) on the current day and month in year YYYY M-D or M/D 00:00:00 (midnight) on the Dth day of month M in the current year DD 00:00:00 (midnight) on the DDth day of the current month 1 : Use the first three letters as an abbreviation for any day of the week: sun, mon, tue, wed, thu, fri, or sat. 2 : Use the first three letters as an abbreviation for any month of the year: jan, feb, mar, apr, may, jun, jul, aug, sep, oct, nov, or dec. 186 PI ProcessBook 2015 User Guide

197 PI System data PI time expressions PI time expressions can include fixed times, reference-time abbreviations, and time offsets. A time offset indicates the offset direction (either + or -) and the offset amount (a time-unit abbreviation with a value). Valid PI time expressions might include: Only a fixed time, such as 24-aug :50:00 Only a reference-time abbreviation, such as t Only a time offset, such as +3h A reference-time abbreviation with a time offset, such as t+3h Include at most one time offset in an expression. Including multiple offsets can lead to unpredictable results. For example, the following time expressions are not valid: *+1d+4h t-1d+12h Time-stamp specification To specify inputs for time stamps, you can enter time expressions that contain: Fixed times A fixed time always represents the same time, regardless of the current time. Input Meaning 23-aug-12 15:00:00 3:00 p.m. on August 23, sep-12 00:00:00 (midnight) on September 25, 2012 Reference-time abbreviations A reference-time abbreviation represents a time relative to the current time. Input Meaning * Current time (now) 3-1 or 3/1 00:00:00 (midnight) on March 1 of the current year :00:00 (midnight) on the current month and day in the year :00:00 (midnight) on the 25th of the current month t y tue 00:00:00 (midnight) on the current date (today) 00:00:00 (midnight) on the previous date (yesterday) 00:00:00 (midnight) on the most recent Tuesday Reference-time abbreviations with a time offset When included with a reference-time abbreviation, a time offset adds or subtracts from the specified time. Input *-1h t+8h Meaning One hour ago 08:00:00 (8:00 a.m.) today PI ProcessBook 2015 User Guide 187

198 PI System data Input y-8h mon+14.5h sat-1m Meaning 16:00:00 (4:00 p.m.) the day before yesterday 14:30:00 (2:30 p.m.) last Monday 23:59:00 (11:59 p.m.) last Friday Time offsets Entered alone, time offsets specify a time relative to an implied reference time. The implied reference time might be the current clock time or another time, depending on where you enter the expression. Input Meaning -1d One day before the current time +6h Six hours after the current time Time-interval specification Time-interval inputs define intervals for collecting or calculating values during a time period. For example, you might specify a 60-minute interval to compute an hourly average over a 12- hour period. To specify time-interval inputs, enter a valid value and time unit: Positive values define intervals that begin at the earlier time in the period and that finish at or before the later time in the period. Start time 2:00:00 End time 3:15:00 Time interval 30m Returned intervals 2:00:00 to 2:30:00 2:30:00 to 3:00:00 Negative values define intervals that finish at the later time in the period and that begin at or after the earlier time in the period. Start time 2:00:00 End time 3:15:00 Time interval -30m Returned intervals 2:15:00 to 2:45:00 2:45:00 to 3:15:00 PI tags (PI points) A PI point is a stream of real-time data from a defined source, and is described by a corresponding tag name and other attributes. PI points are frequently referred to as PI tags, and the terms are used somewhat interchangeably. However, a tag is simply a reference name for a PI point. Topics in this section PI Data Archive and PI ProcessBook 188 PI ProcessBook 2015 User Guide

199 PI System data Updates to PI data PI Tag Search window View PI point attributes PI Data Archive data types PI Data Archive and PI ProcessBook PI Data Archive is a time-series database that collects, stores, and retrieves numerical and string data. PI Data Archive resides on a host computer and is connected to PI ProcessBook through your network. When you open a display containing dynamic symbols, PI ProcessBook retrieves data from the PI Data Archive server. PI ProcessBook also notifies the PI Data Archive server that it would like to receive data whenever the readings for the dynamic symbols change. Each time a reading changes for points in the display, the information is recorded in the PI Data Archive server. This new information is sent to your displays and all the new values are added to trend traces. This is true even if you Reduce a display to an icon to save space. Updates to PI data You open a display, current values of PI tags are used for dynamic elements other than trends and XY plots. For trends and XY plots, the time scale is configurable on a plot-by-plot basis. Displays are updated whenever values change. Every five seconds, PI ProcessBook displays any new values for tags in open displays from each PI Data Archive server. You can modify the update rate in the procbook.ini file. For trends, new values are added to the trend traces. This update by exception algorithm has two benefits: Values that do not change are not sent over the network at every update. This can be a significant efficiency improvement over traditional scanning. Values that change more than once within five seconds are shown accurately on trends because all of the changes are delivered to PI ProcessBook. Values from PI calculations and custom data sets are also updated dynamically. PI Tag Search window The Tag Search window is used to locate PI tags. To open this window: On the Standard toolbar, click the Tag Search button, or Click the Tag Search button in any of the following windows: Define Value Define Bar PI ProcessBook 2015 User Guide 189

200 PI System data Define XYPlot Multi-State Symbol Define Trend The Tag Search window provides three types of searches: Basic Search allows you to create a tag mask by specifying PI point attributes. The mask is used to find a list of tags on the server with matching attributes. Advanced Search provides a query-building interface with access to more point attributes for complex searches. Alias Search provides a logical tree view of a PI Data Archive server through the PI Module Database, which you can use to select tags by their descriptive aliases. 1. Click a tab to choose a Basic, Advanced or Alias search. 2. Enter the required search criteria and click Search. Use '*' or '?' as wildcard characters to search for tag names and attributes. For example, the tag mask Tem* returns all point names that start with Tem while Tem? returns only points that start with Tem and end with another single character. All point mask fields are case insensitive. You can also click Favorites to access previous searches. 190 PI ProcessBook 2015 User Guide

201 Tags returned from a search appear listed in a search results panel. 3. Select the desired tags in the results panel, and click OK. Click column headers in the search results panel to sort the results. Ctrl-click or Shift-click to select multiple tags. Results PI System data For more information on PI tags, click the Help button from any Tag Search window in PI ProcessBook to launch the PI SDK Controls and Dialogs user help. View PI point attributes The configuration information for a PI point is stored as a list of attributes. You can display this list of properties for any dynamic symbol. See PI point attributes for a complete list of attributes and their descriptions. The Point Attributes window displays the attributes and snapshot values of PI points. 1. Using either the Run mode or Build mode pointer, click a dynamic symbol. 2. On the standard toolbar click the Tag Properties button, or click the Pt. Attr. (Point Attributes) button if you are in the Tag Search window, or in Run mode, click Tools > Point Attributes. The Point Attributes window appears. Results You can also view Point Attributes in the Details window. The tag for which the properties are displayed is shown in the Point Name drop-down list at the top of the window. If a trend has several tags, select each tag from the drop-down list or use the up and down arrows on your keyboard to scroll through the tags. The Point Properties window contains the Categorized tab and the Alphabetic tab. The Categorized tab displays the attributes categorically. The following categories are always displayed: Archive Classic Display Overview Security System These categories include all the attributes from the Base point class. The Base point class attributes are common to all PI points. If the PI point that is being displayed is not from the PI ProcessBook 2015 User Guide 191

202 PI System data Base point class, there is one additional category. This category is given the name of the point class to which the displayed PI point belongs. The point class-specific attributes are displayed in this category. The Alphabetic tab displays the attributes alphabetically. PI point attributes Attribute Descriptor Exdesc typicalvalue Units Zero Span digstartcode Explanation 26-character tag descriptor 80-character extended tag descriptor Typical value Engineering unit string Zero Span Code for the first digital state string for the tag dignumber Number of digital states minus 1 pointtype pointsource Point type character Point source character location1 Location parameter 1 location2 Location parameter 2 location3 Location parameter 3 location4 Location parameter 4 location5 Location parameter 5 filtercode squareroot scan excdev excmin excmax archiving compressing Res compdev compmin compmax totalcode convers displaydigits instrumenttag Filter code Square root flag Scan flag Exception deviation in percent of span Exception minimum time in seconds Exception maximum time in seconds Archiving flag Compression flag Resolution code Compression deviation in percent of span Compression minimum time in seconds Compression maximum time in seconds Totalization code Conversion factor for post-processed points Controls the format of numeric values on terminalbased PI screens Tagname for value in another system; used by some interfaces 192 PI ProcessBook 2015 User Guide

203 PI System data Attribute sourcept taglong tagshort creator createdate changer changedate pointnumber pointid Explanation Tagname for output to other systems; used by some interfaces Long tagname (up to 80 characters) 12 character tagname Creator of the tag Creation date of the tag User who modified the tag's attributes Change date of the tag ID number reused upon deletion of a point Unique internal ID number not reused upon deletion of a point PI Data Archive data types PI ProcessBook handles a full range of PI Data Archive data types, as shown in this table: Point type How it is used PI ProcessBook support Digital Int16 Int32 Float16 Used for points whose value can only be one of several discrete states, such as ON/OFF or Red/ Green/Yellow. Nearest equivalent to the PI 2.x Digital type. PI ProcessBook supports these as integers. Used for points whose values are 15-bit unsigned integers (0 to 32767). Nearest equivalent to the PI 2.x Integer type. Negative integer values are supported. Used for points whose values are 32-bit signed integers ( to ). PI reserves some values. Used for floating point values, scaled. The accuracy is one part in Nearest equivalent to the PI 2.x Real type. Supported Supported Supported for positive and negative Integer values Supported Use the displaydigits attribute to determine the precision to display. Float32 Float64 Used for single-precision floating- point values, not scaled. Used for double-precision floating- point values, not scaled. Supported Use the displaydigits attribute to determine the precision to display. Supported PI ProcessBook 2015 User Guide 193

204 PI System data Point type How it is used PI ProcessBook support String Blob Timestamp Each string event represents an ad- hoc state in a series. Used to store string data of up to 976 characters. Binary large object Used to store any type of binary data up to 976 bytes. Plotted as seconds over a given range. Not supported for logarithmic traces. Used to store values of type Timestamp. Any Time/Date in the Range 1- jan-1970 to 1-Jan-2038 On plots, each string event represents an ad-hoc state in a series; not supported on logarithmic traces, multi-state configurations, or bar symbols. Not supported Plotted as seconds over a given range. Not supported for logarithmic traces, multi-states, or bar symbols. Data sets In PI ProcessBook you can build dynamic symbols using data retrieved from data sets just as you can from specific points in PI Data Archive. A data set is basically the set of results of a query that addresses a specific data source. You can use placeholders to link PI tags and ODBC data within a query. Data sets are defined at the Book level so that they can be defined once and then shared among different displays within that ProcessBook. If you create an independent display (a.pdi file), the data set is defined only for that display. Trends including data sets can be manipulated, saved, moved, and copied in the same fashion as other trends. Whenever a display is updated, if a trace or value using a data set is configured using relative times, then the trace or value is updated. No updates occur if the data set is configured using absolute times. You can edit an existing data set, either from the Tools menu or from a symbol that uses the data set. However, if you have attached the data set to more than one symbol, editing the data set affects all the symbols. If you move a PI ProcessBook display containing a data set to another machine, you may need to reconfigure the data set or the machine's connection to the data source. 194 PI ProcessBook 2015 User Guide

205 PI System data Three types of data sets are available to provide data to displays: PI Calculation data sets (including PI Expression and PI Summary data sets) from PI Data Archive servers using PI Performance Equation syntax. These expressions provide summary data, such as averages, minimums, maximums, etc., or calculations such as the sum of two PI point values. ODBC data sets (Open Database Connectivity) data sets obtained from a relational database. Custom data sets built as COM objects supplied by Visual Basic or C++ programs as Add-Ins to PI ProcessBook. Topics in this section PI Calculation data sets ODBC data sets Custom data sets Placeholders Verify a data set is in use Data set details Add a data set to a trend Time intervals for plotting tags and data sets Refresh a trend containing a data set Add data sets to bars or values in a display Run PI ProcessBook when data sets are included Edit a data set Delete a data set Copy a data set to another ProcessBook PI ProcessBook 2015 User Guide 195

206 PI System data Loading custom data sets Configure a symbol with an AF attribute Configure the AF2 PI Calculation data sets PI Calculation data sets include PI Summary data sets and PI Expression data sets. These are drawn from the PI Data Archive server and plotted dynamically. Use the PI Calculation window to create, edit, or delete data sets. You can select predetermined calculations or create your own expressions. A similar window is used to configure ODBC data sets. PI Summary data sets PI Summary data sets enable you to use pre- determined functions to retrieve aggregated PI data for a tag. The AVG function calculates the average of the tag values for each interval. The Count function is the sum of event count over the time range when calculation basis is event-weighted, sum of event time duration over the time range when calculation basis is time-weighted. The MIN function selects the minimum of the tag values for each interval. A timestamp associated with the minimum value is also available. The MAX function selects the maximum of the tag values for each interval. A timestamp associated with the maximum value is also available. The PCTGOOD function determines the percentage of time for each interval, when the tag s archived values are good (that is without errors, such as out of range errors or shutdown flags). It is not applicable for digital tags. The PSTDEV function calculates the population or sample standard deviation of two or more values. The RANGE function calculates the difference between the tag s maximum and minimum values for each interval. The STDEV function calculates the population Standard Deviation of the tag values for each interval. The Total function is the total over the given time range. These functions are fully described in the "Performance Equations" chapter of the PI Data Archive Applications User Guide. PI Expression data sets PI Expression data sets enable you to create your own function or expression in PI Performance Equation syntax. These expressions can include tag variables with mathematical and logical operations as described in the "Performance Equations" chapter of the PI Data Archive Applications User Guide. This syntax is also documented on the OSIsoft Technical Support Web site, under the hierarchy Support > Downloads > Documentation for PI Data Archive. 196 PI ProcessBook 2015 User Guide

207 PI System data Topics in this section Create a PI Calculation data set Intervals and time value Plot a moving average in a trend Create a PI Calculation data set 1. Click Tools > Data Sets. The Data SetsData sets window appears. You can also create a PI Calculation data set by clicking the drop-down arrow next to the Tag Search button in the Define dynamic symbol windows. By accessing the PI Calculation Data window this way, you have the additional option of selecting a previously created PI Calculation data set, as well as the ability to create a new one as outlined below. 2. Click New > PI Calculation. The PI Calculation Data window appears. PI ProcessBook 2015 User Guide 197

208 PI System data 3. Enter values for the following fields: Server Select a PI Data Archive server. Name Enter a name for your data set. The name must be unique for the current.piw or.pdi file. PI Tag or Expression Enter a tag name or a PI expression. Use the button to search for PI Tags. If you choose to type an expression, be sure to use PI Performance Equations syntax, such as one of these: sinusoid * 2 ( cdt158 + sinusoid )/2 log( cdt158 ) ( sinusoid )/tagspan( sinusoid ) 4. Click OK to save your changes. The data set name must be unique for the current.piw or.pdi file. The node name and tag name must be valid. 198 PI ProcessBook 2015 User Guide

209 PI System data The interval must be a valid PI time. The sync time must be a valid PI time. Your new data set appears in the Data Sets window. Intervals and time value The calculated value for each interval is plotted at the start of the interval. For example, if the tag t_min has the following time-value pairs in a 10 minute interval, then the calculated value for this interval would be plotted at time 1:00:00. Time 1:00:00 1 1:01:00 2 1:02:00 3 1:03:00 4 1:04:00 5 1:05:00 6 1:06:00 7 1:07:00 8 1:08:00 9 1:09: :10:00 11 Value Because the AVG, STDEV, and PCTGOOD functions are time-weighted, their calculated values include the tag value at the lower interval boundary time but exclude the tag value at the upper interval boundary time. For the example above, the tag value 11 at time 1:10:00 is excluded in the function calculation; therefore the calculated value for AVG is 5.5 and the calculated value for STDEV is The calculated values for the MIN, MAX and RANGE, which are event-weighted functions, include the tag values of both the lower and upper interval boundary times. For the example above, the calculated value for MIN is 1, the calculated value for MAX is 11, and the calculated value for RANGE is 10. Plot a moving average in a trend You can plot additional statistics in a trend using data sets derived from PI tags. For example, you can plot both a tag and its moving average to show a smoothed version of the same curve. The moving average is built from the source tag using a data set that recalculates an average point value over recurring intervals. 1. In Build mode, double-click on the trend to open the Define Trend window. 2. Click the Tag Search arrow and choose PI Calculation to create a data set based on a tag. 3. Click New to add the data set and specify a Name and Description for the data set that calculates the moving average. PI ProcessBook 2015 User Guide 199

210 PI System data 4. Click Tag Search and select the tag you want to use as the basis for the calculation. 5. In the Interval field, choose the calculation period for the average. A new average tag value is computed at each interval over the plotted time range. 6. Click Average in the Columns panel to select an average calculation, and click OK. 7. Click OK to close the Define Trend window. ODBC data sets PI ProcessBook uses the term ODBC data set for the concept of an ODBC query that retrieves data from a relational database outside of the PI System to produce a group of data values organized into rows and columns and used to build a trend or other element in a ProcessBook display. A data set is identified within a ProcessBook by a unique name. The data set name refers to the combination of an SQL query statement and an ODBC data source with which to execute the query. The results of the SQL query are organized into rows and columns. You may select any column of the results for a display. For example, in a trend, each column in the data set that you select appears as a different trace. A SQL query statement may be written so that it executes based on other data in a display, such as PI tags or the start or end time. This is done using SQL placeholders (parameters); a tag, time, or text string is then substituted for each placeholder at run time. Create an ODBC data set 1. Click Tools > Data Sets. The Data Sets window appears. 2. Click the New button, then select ODBC. The ODBC Data window appears. 200 PI ProcessBook 2015 User Guide

211 PI System data 3. In the Name box, type a name for the data set. 4. In the Description box, type a description if you like. This text is displayed in the Description legend for the trace, if configured. 5. In the Refresh Interval list, enter the interval at which you want to automatically update the data set. -or- Type a number between 0 and 999. The default for the Refresh Interval is zero minutes. This means the data set only refreshes when the trace is first drawn or when you click the Revert Time Ranges button on the standard toolbar. If a tag placeholder is used, the Refresh Interval box list is disabled and the data is refreshed whenever the PI Tag value changes. 6. From the Data Source drop-down list, click the appropriate ODBC data source. If you do not already have an ODBC Data Source configured on your computer (using the Control Panel), click the Setup button to create or modify one. 7. Click the Design button. The Microsoft Query application is displayed. If Microsoft Query is not installed, then the Design button is disabled. You can key in the query manually. You can also copy and paste a query from another query building tool. 8. Choose your ODBC data source and design your query. PI ProcessBook 2015 User Guide 201

212 PI System data Click the Help button, if necessary, and follow Microsoft's instructions for completing the query. 9. Click OK to return to the ODBC Data window. To verify if the query can be understood by the ODBC data source, click the Check Syntax button. 10. Click OK. 11. If you want to use placeholders in the query, enter the appropriate WHERE clause, use question marks (?) to denote the location of placeholders, and click the Placeholders button. Placeholders are defined in the order in which they are encountered in the SQL statement. Clicking the Placeholders button causes the syntax of the query to be checked. If the syntax is not valid, the invalid query message is displayed. 12. Click OK. Custom data sets A custom data set is one provided through a VBA add-in to PI ProcessBook. It is a COM object or a.net object with a COM wrapper that acts as an interface between PI ProcessBook and the custom data provider. The source of data could be a data store (like MS SQL Server) or a data calculation engine. PI ProcessBook requests updates to the data every few seconds and adjusts its display accordingly. Before you can access custom data sets in a display, the Data Set add-in must be installed and loaded through the Add-In Manager window. Later, as you build a display, you select the data set and column to be used for a symbol on a display through the symbol definition windows. Once a custom dataset is loaded, it is available throughout the application. These data sets are not display- or ProcessBook-specific. Information on building a custom data set is beyond the scope of this user guide. It is discussed in Creating a Custom Data Set, a white paper available through the OSIsoft Technical Support Web site, or on the PI Developers Club web page. Placeholders A placeholder in an SQL query identifies a value that is to be provided when the query is run. You can validate a query before the actual values are provided. The standard SQL placeholder character is (?). Placeholders are numbered in their order of appearance, from left to right, in the query statement. For example, the following query statement has two placeholders, one for a text string for a sample ID and the other for a sample time. Select value, sample_time from Lab_data where sample_id=? and sample_time>? PI ProcessBook allows text, start times, end times, or tag values as substitutes for placeholders. Topics in this section Processing of placeholder queries 202 PI ProcessBook 2015 User Guide

213 PI System data Designing placeholder queries Add or edit placeholders Processing of placeholder queries Text placeholder values are substituted into a query when it is run. Start and End times are determined when a display is opened and are substituted into queries at execution. PI tag placeholder queries You can also use PI tag values as placeholders. With a PI tag placeholder, a join is processed between the ODBC data source and the PI data source. When a display is opened, PIProcessBook obtains PI tag values between the start and end time and substitutes these values into the SQL query, one at a time (in effect, executing the query for each PI tag value returned). The use of a tag placeholder is shown in the SQL query statement below: Select target from specs where product_code=? In this example, the values of the tag in the PI System that records the current product code are retrieved. The result set of the ODBC query is built by executing the query once for each placeholder value. In the case of this example, that would be one query execution for each product code found between the start and end times of the symbol. Designing placeholder queries Placeholders can be customized for a symbol. You can create an ODBC data set with a set of default placeholders. When that data set is attached to a specific symbol, the query s placeholders can be customized for that symbol without affecting the placeholders defined for any other symbol using that data set. Add or edit placeholders To open the Placeholders window, click the Placeholders button in the ODBC Data Sets window, or click the Custom Placeholders button on a symbol definition window. See Create an ODBC data set for details. In this window, you can rename placeholders, change their type or specify values. PI ProcessBook allows you to create custom placeholders for a symbol based on a summary data set or a PI tag placeholder in an ODBC data set. Placeholders are not allowed for expression data sets. The Custom Placeholders button in symbol definition windows allows you to specify different PI tags for a PI Summary data set or ODBC data set with a PI tag placeholder. The change applies only to the configured symbol. PI ProcessBook 2015 User Guide 203

214 PI System data 1. In the Placeholder Name box, select the parameter you want to configure. The parameters are in the same order as found in the data set query. The list is limited to the number of parameters found in the query. 2. In the Placeholder Properties group, select the Type for the selected parameter. There are four possible types, Text, PI Tag, Start Time, and End Time. You can optionally change the name of the placeholder to make its purpose clear. 3. Selecting a type transforms the window to allow you to enter the settings for the selected type, if any. If the query uses: Text input Type the replacement text value in the Text field. Tag values Type a node ID and tag name or click the Tag Search button to open the Tag Search window. Start and/or end times No additional configuration is used. 4. Click the Set button. 5. To configure another parameter, select it and repeat the previous steps. 6. Click OK. 204 PI ProcessBook 2015 User Guide

215 PI System data Verify a data set is in use Before you modify a data source or data set, it is important to determine whether it is being used in another display or symbol. PI Calculation data sets and ODBC data sets are established for an entire ProcessBook (or an independent display). Custom data sets are installed with the PI ProcessBook application and are available to any display that you open. 1. Click Tools > Data Sets. The Data Sets window appears. 2. Under Data Sets, click the data set name, then click the Show Use button. The Data Set Use window appears and displays where the data set is being used. Data set details Each data set is initially determined from a data source that must already be configured. If the data source you need is not listed, click the Setup button to add it. Once the Data Source is selected, add the query. If the Design button is unavailable you must type in the query. If MS Query is installed correctly, the Design button will not be unavailable. Click it to design the query. You can check syntax after you add the query. Including question marks (?) in the query allows placeholders to be defined. If you wish to use placeholders from PI in your query, establish them by clicking the Placeholder button and completing the process on the Placeholder window. Add a data set to a trend Just as you would add PI tags in defining a trend, you can add columns chosen from a data set. Each column is plotted as a separate trace, however, the data set columns that appear on your trend do not appear in the Point Properties window. You can manipulate trends containing data from data sets just as you would other trends, by using functions such as: Trend Zoom Scrolling Trend Cursor Time Range Revert Time Ranges Autorange Markers PI ProcessBook 2015 User Guide 205

216 PI System data 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Trend button. 3. Click in the display where you want to add the trend and drag the pointer to form a rectangle into which the trend will be placed. When you release the mouse button, the Define Trend window appears. 4. Click the Tag Search arrow, and then click PI Calculation. The PI Calculation Data window appears. If you want to display the ODBC Data window instead of the PI Calculation Data window, then click the Tag Search arrow, and then select ODBC. 5. Under Saved Data Sets, click the data set you want to add to the trend. 6. Under Data Set Columns, select a column(s) to be plotted in the trend (use the SHIFT or CTRL keys to select more than one column). Value Value of the expression for the calculation interval and type as of the timestamp. In the case of summary data sets, this column holds the value of the tag. Total The totalized value (time integral) of a tag over a given time, according to values stored in the archive. Average Average value of the expression for the calculation interval and type. Minimum Minimum value of the expression for the calculation interval and type. Maximum Maximum value of the expression for the calculation interval and type. PctGood The time percentage, over a given range, when a tag's archived values are good (not digital states). Range The difference between a tag's maximum and minimum values during a given time, according to values stored in the archive. StdDev The time-weighted standard deviation of a tag over a given time, according to values stored in the archive. PStDev 206 PI ProcessBook 2015 User Guide

217 The standard deviation of two or more arguments, where those arguments represent the whole population. Count The number of events for a point over a given time. 7. Click OK. Until you select a data set and at least one column, the OK button is dimmed. The selected data set/column(s) is now listed under Tags in Plot in the Define Trend window. 8. Select tags as desired and format the trend. If you wish to see or edit the definitions of placeholders, click the Custom Placeholders button in the Define Trend window. 9. Click OK. Data displays on the trend. PI System data If you select the Description check box, on the Display Format tab in the Define Trend window, then the description of the data set is taken from the PI Calculation Data window and repeated for each column that is plotted. There are usually no engineering units for a data set column. Time intervals for plotting tags and data sets The Start and End plot times on the Define Trend window are used to determine the time range for plotting tags. However, a data set may have different time boundaries than the plot time start and end for the tags. If the time range for the data set starts later than the time range for the tags, the data set traces begin with Xmarks. See Define Trend window for details. Refresh a trend containing a data set In a display containing only data from data sets, the data is refreshed based on the Data Set Refresh Interval, which is configured in the data set. The trend does not update again until the Data Set Refresh Interval has expired, at which time it requests another set of values and redraws itself. A PI tag in a display, on the other hand, receives exception notifications from the PI System and is updated on the display whenever the polling period elapses (every five seconds by default). If both PI and data set data are to be plotted on the same trend, then the latest data set value is continued toward the end time axis with changing PI exception data points until the refresh interval expires and new data are received from the data set. If a data set has a PI tag placeholder, then the data set is refreshed every time a new value is received for the PI tag placeholder. Add data sets to bars or values in a display A single value from a data set may be added to a display as either a Value or a Bar. PI ProcessBook 2015 User Guide 207

218 PI System data In general, queries can return many rows of results. The Value or Bar uses only the data from the last row of the results for the column you select; the rest of the results are discarded. In many cases, you can use an order by clause to control which rows are returned first. For example, the following query guarantees the most recent sample appears in the ProcessBook Value field: Select lab_val from Lab_Data where last_id = BW Order by Sample_time asc Run PI ProcessBook when data sets are included When you start PI ProcessBook and open an updating display, it connects to your PI System and remains connected until you close PI ProcessBook. If you have configured data sets in a ProcessBook, PI ProcessBook connects to a data source as soon as you open a display using data set results. The first time you use a particular data source, the external database may ask you for login information through a login window. After a successful connection, PI ProcessBook retains this information for use throughout the session. When you close the session, PI ProcessBook does not store your password locally because it would be a security risk to store a password locally. If your data source is configured to use Windows Authentication, then your network credentials are used to gain access to the data and you are unlikely to be prompted. Edit a data set You may change the Data Source, the Data Set Refresh Interval, the Description, or the query. However, when you change a data set, you might affect other queries that use the same data set. 1. Click Tools > Data Sets. The Data Sets window appears. See Data sets for details. 2. Under Data Sets, click the data set you want to edit, and then click the Edit button. 3. Either the PI Calculation Data window or the ODBC Data window displays depending upon the data set you selected. 4. If the PI Calculation Data window displays, then make your changes in the appropriate fields. 5. If the ODBC Data window displays, then do the following: To determine if Microsoft Query is installed, the application checks your MS-DOS path for the existence of msquery.exe) If the Design button is enabled, then: i. Click the Design button. 208 PI ProcessBook 2015 User Guide

219 An instance of Microsoft Query is started using the current data source and query. ii. Edit the data set in the MSQuery environment. iii. Click File > Return to ProcBook when you are finished. Microsoft Query cannot edit query statements that contain placeholders. If the Design button is disabled, then: If Microsoft Query is not installed, the Design button is disabled; however, you can type the query in the query text box. You can also copy and paste a query from another query building tool. i. Add or edit the appropriate WHERE clause in the query to edit a placeholder data set or existing placeholders (question marks represent placeholders in the query statement). ii. Click the Placeholders button. This action causes the syntax of the query to be checked. If the syntax is valid, then the Placeholders window displays with the current placeholders. If the syntax is invalid, then an invalid query message is displayed. iii. Click the Check Syntax button, to complete a syntax check of your query. The status of the query is returned. iv. When you have finished modifying the data set, click OK. If the data set is in use in a display, the Confirm Data Set Modification window displays. v. If you wish to proceed, click Continue. The Data Sets window appears. vi. Select the column(s) to be used and click OK to return to the window. PI System data Delete a data set Before you can remove a data set from the PI ProcessBook list, you must remove it from any symbols that use it. If the Data Set is a custom data set, which is a COM object, remove it through Add-in Manager window. Otherwise, use the following steps to delete a data set first from all displays in which it is used and then from the ProcessBook altogether. 1. Click Tools > Data Sets. The Data Sets window appears. See Data sets for details. 2. Under Data Sets, click the data set name, and then click the Show Use button to determine if any display or symbol is using the data set. 3. Close the Data Sets window. 4. Open each display in which a data set is being used and delete the data set from the appropriate window, such as the Define Trend or Define Value window. 5. Save each display. PI ProcessBook 2015 User Guide 209

220 PI System data 6. Reopen the Data Sets window. 7. Under Data Sets, click the data set you want to delete, and then click the Delete button. The data set is removed from under Data Sets in the Data Sets window. If the data set is in use, then the Can't Delete Data Set window appears. Copy a data set to another ProcessBook While data sources are configured for a computer, data sets are established for only one ProcessBook or independent display file. 1. Open the new or target ProcessBook or independent display file. 2. Open the old or source ProcessBook or independent display file. 3. From the Tools menu, select Data Sets. The Data Sets window appears. See Data sets for details. 4. Under Data Sets, click the data set you want to copy, and then click the Copy button. The Copy Data Sets window appears. 5. From the To Open Workbook drop-down list, select the correct target, and then click OK. Loading custom data sets Before you can access a custom data set in a display, you must create a data set add-in and install it on your computer. Then you must select it through the PI ProcessBook Add-ins Manager window. See Load add-ins. Configure a symbol with an AF attribute The AF2.x data set provides access to the AF database allowing you to configure a PI ProcessBook symbol with an AF attribute. From any symbol definition window, click the Tag Search button and select AF2 to open the Select AF Attribute window. If AF2 is not in the drop down list, it might not be loaded. Load it from Tools > Add-In Manger. 210 PI ProcessBook 2015 User Guide

221 PI System data 1. Connect to an AF database. 2. Select an AF element. 3. Select an AF attribute from the drop down list or click Search to search in the AF database. 4. Select a unit of measure in which to display the attribute. Configure the AF2 1. Click Tools > Data Sets to open the Data Sets window. 2. Select AF2 dataset from the list. 3. Click Edit to open the AF 2.x DataSet Configuration window. 4. Enter a Refresh Interval. 5. Select Do not retrieve AF Data in Build Mode to prevent data refresh while in build mode. Retrieving data might have a negative impact on performance while you are configuring a PI ProcessBook symbol. PI ProcessBook 2015 User Guide 211

222 PI System data ODBC ODBC client capability means that without writing vendor-specific code, you can access data from certain relational databases outside the PI System and include that data in your PI ProcessBook displays. The outside data source must be ODBC-compliant; for example, it must provide an ODBC Driver. An outside ODBC data source might include laboratory results, cost tables, or other sets of information that can be obtained through SQL queries. Since access to ODBC sources is configured on a particular computer, moving a display file that uses an ODBC data set may require the data source to be configured on the new computer. The data source has to have the same name on the new computer, or the data set will need to be reconfigured in the display. Topics in this section ODBC Driver Manager ODBC drivers ODBC data sources ODBC data access Open ODBC Data Source Administrator Prepare for ODBC Configure the ODBC data source Use MS Query to build data sets Assumptions about time stamps and data sets Stored procedures in queries Troubleshoot ODBC data sets Trace ODBC calls Delete an ODBC driver Delete an ODBC data source Edit an ODBC data source ODBC Driver Manager PI ProcessBook sends queries to a standardized interface from Microsoft called the ODBC Driver Manager. The Driver Manager forwards ODBC queries to appropriate vendor-provided drivers, which access the outside databases and return the requested data to your ProcessBook display. ODBC drivers Each DBMS (database management system), such as Microsoft SQL Server, requires a specific ODBC driver, provided by the vendor of the DBMS or a third party. Each driver is a dynamic link library (.dll) that implements a set of subroutine calls to retrieve data from a particular database. 212 PI ProcessBook 2015 User Guide

223 PI System data The Microsoft ODBC Driver Manager is included as a part of PI ProcessBook installation. ODBC data sources An ODBC data source identifies a database a user wants to access and the information needed to connect to that data. Examples of ODBC data sources are: A SQL Server database, the server on which it resides, and the network protocol used to access that server. An Excel spreadsheet on a file server. A directory containing a set of dbase files you want to access. ODBC data sources have an explicit name, are configured for a particular computer, and may be used by any ODBC- compliant application installed on that computer. ODBC data access PI ProcessBook stores relational queries in data sets within ProcessBook files. The data sets are created, stored, and accessed by name. PI ProcessBook symbols can then access the data sets. The columns in the data set make up the items that can be assigned to the trend, value, or bar. The SQL needed to retrieve data for PI ProcessBook can be configured once and used by many displays and symbols. PI ProcessBook must return a time and value pair(s) for display within a symbol (trend, value, or bar). Placeholders act as parameters to an SQL function call. They are evaluated at run time. Placeholders can take three forms: text, start/end times, or a PI tag name. Use the start and end time placeholders when the time limits of the query should be determined from the trend symbol where the query is used. The PI tag name placeholder can be used to join PI data with relational database data. A PIValue is retrieved for the PI tag and then substituted into the query. Using ODBC requires that you install the Microsoft ODBC Driver Manager and drivers (most operating systems already have the Driver Manager and some standard drivers installed). You must then configure data sources for ProcessBook and define individual queries, called data sets. Open ODBC Data Source Administrator 1. On the Windows Start menu, point to Settings, click Control Panel, double-click Administrative Tools, and then double-click Data Sources (ODBC). The Microsoft ODBC Data Source Administrator window appears or Click Tools > Data Sets. The Data Sets window appears. See Data sets. 2. Click the New button, and then click ODBC. The ODBC Data Sets window appears. PI ProcessBook 2015 User Guide 213

224 PI System data 3. Click the Data Source drop-down list to see what ODBC data sources you have already configured, if any. 4. Click the Setup button. The Microsoft ODBC Data Source Administrator window appears. Prepare for ODBC To use ODBC within your ProcessBook, you must install an ODBC driver and configure the corresponding ODBC data source on your computer. Open ODBC Data Source Administrator and click the Drivers tab to view the ODBC drivers that are already installed on your system. See your system administrator if you require additional ODBC drivers. Configure the ODBC data source Once any necessary ODBC drivers are installed, you need to configure the ODBC data sources available to the computer. 1. Open ODBC Data Source Administrator. 2. On the User DSN tab, under User Data Sources group, click the name of the ODBC data source you plan to use and then click the Configure button. The Setup window for the data source you selected appears. 3. Add the ODBC data source. 214 PI ProcessBook 2015 User Guide

225 PI System data Click the Help button, if necessary, and follow Microsoft's instructions for entering information onto the window. 4. When you have completed configuring the data source, click OK to return to the Microsoft ODBC Data Source Administrator window. To create data sources for any user of the computer, use the System DSN tab instead of the User DSN tab. You can set up data sources on the System DSN tab that are available to all users on the computer, but you must have elevated permissions on the computer. Use MS Query to build data sets You can use Microsoft Query (MS Query) for writing queries. It is not distributed with PI ProcessBook, but if you click the Design button in the ODBC Data window, then PI ProcessBook searches the registry in your computer to locate MSQry32.exe when the ODBC data sets window is opened. The MS Query application does not work with an ODBC query that includes placeholders. Consequently, the Design button in the ODBC Data window may be disabled. Assumptions about time stamps and data sets When a trend receives data from an ODBC data source, it receives the data as a Time / Value pair. The Value is generated by the query. The Time, however, might be obtained in one of two ways: If a Tag placeholder is used, then the time will be the time returned by the Tag. This time will supersede any time stamps returned by the query. One or more of the columns returned by the query may contain a date and/or time. If more than one time stamp column is returned, the first one as ordered by the SQL query is used. Stored procedures in queries Stored procedures can be used in ODBC data sets. They may contain placeholders as long as your database accepts the stored procedures call as a text string. The common syntax for this is: execute procname ('arg', 22,?) Check the documentation of your database management system for details. Stored procedures generally return results in rows and columns, just as a normal SQL query does. The only way to determine the columns returned by a stored procedure is to perform a test execution. When you are building the data set, because ProcessBook needs to know the columns returned, it executes the procedure. If the procedure call includes placeholders, the following defaults are used: PI ProcessBook 2015 User Guide 215

226 PI System data Text StartTime EndTime Tag 0 Actual text placeholder string Current time Current time An ODBC data set is created with a set of default placeholders. When it is attached to a specific symbol, the query's placeholders can be customized for that symbol, without affecting the placeholders defined for other symbols using that data set. For example, you can create a query for a database of laboratory data using a text placeholder for the sample name. You can then use a different sample name for every trend, bar, or value, rather than defining a new data set query for each sample name. Troubleshoot ODBC data sets Data sets can be added, deleted, copied, or edited by selecting the New, Delete, Edit, or Copy buttons in the Data Sets window. Columns are defined by the data set query. To see the columns returned by the query, select the data set when configuring a symbol to use it. The window shown from the Data Sets window opened from the Tools menu does not show the columns. The Show Use button opens a window that indicates what displays and symbols include data from this data set. Trace ODBC calls The ODBC Driver Manger provides an option for recording a log of all calls to the Driver Manager from all ODBC clients. The default options for ODBC are set to omit tracing and logging ODBC calls. If you choose to trace ODBC calls, you may suffer some degradation in system performance. Initiate call tracing 1. Click Tools > Data Sets. The Data Sets window appears. 2. Click New. Click ODBC. The ODBC Data window appears. 3. Click Setup. The ODBC Data Source Administrator window appears. 4. Select the Tracing tab. 5. To change the file where tracing is logged, choose a new file path in the Log File Path text box. Use the Browse button to search for files. 6. To initiate tracing, click the Start Tracing Now button. 216 PI ProcessBook 2015 User Guide

227 The label changes from Start Tracing Now to Stop Tracing Now, and the Log File Path text box becomes unavailable. 7. To stop tracing, click the Stop Tracing Now button. PI System data Delete an ODBC driver If you have deleted all data sources using a particular driver, you may uninstall it from your system. To do this, you must use the setup program for the ODBC driver. If you delete the wrong driver you need to reload it from the vendor. Delete an ODBC data source If you remove data sources while they are in use, displays that use them fail to retrieve data. Consequently, before you remove a data source, remove all data sets in which it is being used. PI ProcessBook cannot prevent users from removing a needed data source from the computer. 1. Open ODBC Data Source Administrator. 2. On the User DSN tab, under User Data Sources, click the name of the ODBC data source you want to delete and then click the Remove button. A confirmation message is displayed. 3. Click the Yes button to delete the data source. 4. Click OK to close the Microsoft ODBC Data Source Administrator window, then close the ODBC Data window. The data source is removed from under Data Sets in the Data Sets window. Edit an ODBC data source Occasionally you might want to use a different computer to access an existing ProcessBook display. If the display contains data from a PI Calculation Data Set, the display works correctly unless the new machine does not point to the same PI Data Archive server as the previous one. If this display contains data from an ODBC data set, you will need to reconfigure the correct ODBC data source on the new computer. Essentially this means establishing the same ODBC data source name that was used on the original computer. Follow the steps under Configure the ODBC data source. If the display contains data from a custom data set, then you must install that PI ProcessBook add-in on the new machine. AF elements You can access AF elements in PI ProcessBook through the AF Browser, which lets you browse for elements within your PI Asset Framework. PI ProcessBook 2015 User Guide 217

228 PI System data AF-based symbols that are assigned to AF elements are stored in an AF database, as part of the AF element definition. When you want to work with AF elements and AF-based symbols, you must be connected to the AF server and AF database where they are saved. Within PI ProcessBook, you can: View AF element properties. Configure how AF elements are displayed in the AF Browser. Customize your PI ProcessBook window settings for the AF Browser and the AF Property pane. Topics in this section View AF element properties Configure display settings in AF Browser Toggle panes for AF elements in PI ProcessBook View AF element properties You can view AF element properties directly from PI ProcessBook. Details for AF elements are displayed in the AF Property pane. Before you start To view AF element properties in PI ProcessBook, you must open PI ProcessBook and verify that the AF Browser is open and that you are connected to the PI AF server that stores the AF element. 1. Open a display and select Build mode. 2. Click View > AF Property. The AF Property pane opens. 3. Select an AF element from the AF Browser. You can view AF element properties in the AF Property pane. You can right-click the AF element in the AF Browser to open the Element Properties window. This window has multiple tabs that describe element details. You can right-click an AF attribute in the AF Property pane and then click Properties to open the Attribute Properties window. This window has general information about the AF attribute. Configure display settings in AF Browser You can view and change settings that determine how AF elements and the AF database are displayed in the AF Browser. 1. Open a display and right-click on an element in the AF Browser. 2. Choose one of the enabled options. 218 PI ProcessBook 2015 User Guide

229 Find Disabling an option in the AF Browser applies to all displays in PI ProcessBook. View and change search settings for particular AF objects, if they apply. Available AF objects are: Parent elements, Models, Layers, Connections, and Analyses. Make Root Node Change the view of the AF database to make the selected AF element the root node in the AF Browser. You can revert to the original AF database view by right-clicking the AF element and then clicking Reset Root Node. Refresh Refresh the values of the AF attributes for the selected AF element. Show History Show the history of the AF element. Security View the security settings for the selected AF element. The Permissions window lists the names of the groups or users and their permissions for that AF element. Properties Open a standalone Element Properties window that shows the same AF element properties information as the AF Browser. PI System data Toggle panes for AF elements in PI ProcessBook You can configure your window settings in PI ProcessBook to toggle both the AF Browser and the AF Property pane. The settings for how you display these GUI elements are saved separately for Build and Run mode, based on the settings from the last session in PI ProcessBook. 1. To toggle the AF Browser, open a display and click View > AF Browser. 2. To toggle the AF Property pane, open a display and click View > AF Property. PI ProcessBook 2015 User Guide 219

230 PI System data 220 PI ProcessBook 2015 User Guide

231 PI Notifications in PI ProcessBook PI Notifications provides PI System users the ability to configure rules that deliver notifications by and other delivery channels when certain conditions are met. These conditions are configurable and are normally dependent on a number of data inputs. Additionally, PI Notifications can be configured to deliver various content types to the notification contact, such as an attached PDI file or a path to a PDI file. For further information, see the PI Notifications User Guide. PI ProcessBook includes a PI Notifications add-in that retrieves notifications subscribed to from your PI System, and lists them in a window. This add-in also supports viewing and managing Contacts, which allows users to communicate and collaborate with other users from within PI ProcessBook without having to launch a separate application. Topics in this section Start PI Notifications Notifications window in PI ProcessBook Contacts window Start PI Notifications The add-in only loads in PI ProcessBook if the appropriate PI Notifications client software is already installed separately. 1. Click View > Notifications to manually open the Notifications window. The Notifications window is automatically opened at startup if it was left open when you previously shutdown PI ProcessBook. You can also launch PI ProcessBook to view a notification by opening a PDI file attached to a notification . Notifications window in PI ProcessBook The Notifications window provides controls for viewing PI Notifications in PI ProcessBook. PI ProcessBook 2015 User Guide 221

232 PI Notifications in PI ProcessBook The title bar displays the number of active, open notifications. This number appears in parentheses to the right of the Notifications window title, for example Notifications(2). Use the controls at the top of the Notifications window to receive notifications and view notifications. A notification rule is a set of conditions that leads to the creation of notifications. Notification rules and their associated notifications appear in the bottom half of the Notifications window. For more information on how to create notification rules, see the PI Notifications User Guide. Use the pin icon to lock the docking window to your screen. Click the pin icon again to unpin the window and minimize it along the border of your PI ProcessBook window. When a docking window is unpinned, a button appears along the side of the screen. Hover over it to re-expand the window. The size and position of the Notifications window is saved so that it opens the same way the next time you open PI ProcessBook. Topics in this section Receive notifications Filter notifications Open displays associated with a notification Work with notifications 222 PI ProcessBook 2015 User Guide

233 PI Notifications in PI ProcessBook Receive notifications To receive notifications in PI ProcessBook you need to connect to a PI System where notification rules are established. To change the default PI System connection in PI ProcessBook, click File > PI System. Use the icons at the top of the Notifications window to begin, pause, or resume receipt of notifications. Play icon indicates that incoming notifications are halted. Pause icon indicates that you are receiving notifications. Click this icon to stop receiving new notifications. For more information on configuring notifications, see the PI Notifications User Guide. Filter notifications PI Processbook only shows notifications for which you are subscribed. These are shown in the Notifications window. You can filter this list with the controls available at the top of this window. 1. In the View Notifications drop-down list, click one of the following options: Active Displays all open notifications. You only receive new notifications when this option is selected. Timerange Select either the Start Time or End Time text box and enter a PI time string. Click the corresponding drop-down arrow to launch a calendar to help you find a specific date. Recent Enter a time period to search within the last x-number of seconds, minutes, hours, or days. 2. Click the Go button to view your list of filtered notifications. Open displays associated with a notification Do one of the following: Click the Open Display icon in the Notifications window. Right click a notification and click Open Associated Display(s). This opens or creates displays for the content associated with the notification(s) selected in the list. The displays are opened and have the union of the selected time ranges applied to each symbol contained therein. This button is enabled if the selected notification items do PI ProcessBook 2015 User Guide 223

234 PI Notifications in PI ProcessBook not have all their associated content already open in PI ProcessBook; otherwise it is disabled. Work with notifications Click a notification in the Notifications to have its time range applied to the active display. Right click a notification to see a context menu providing the following options: Acknowledge Instance to acknowledge that action has been taken regarding the notification, and that no further escalation is needed. Acknowledge Subscription to acknowledge receipt of a notification you are subscribed to. Add Comment to comment on a notification. Show Contact Events to toggle the display of contact events for each notification. Show TimeSelector to toggle the display of filter options. Expand All/Collapse All to expand or collapse a notification grouping. View Notification Rule Summary to display the properties of the notification rule that triggered a selected notification. Set Time for All Displays sets the time range of all open displays to the time range of a selected notification, or union of time ranges for multiple selected notifications. Set Time for Associated Displays sets the time range of displays associated with the notification rule to the time range of the notification. Open Associated Display(s) opens the displays corresponding to the selected notifications and applies the union of the selected time ranges to each. Contacts window The Contacts window allows you to view and manage contacts from within PI ProcessBook. It is split into two panes and provides the following: Notification contacts MS Office Communicator contacts You do not need PI AF or PI Notifications to use most features of Contacts. However, to view the Contacts window you must have Office Communicator installed and be logged in at the time you launch PI ProcessBook. See the Microsoft Office Communicator home page for further information. Use the pin icon to lock the docking window to your screen. Click the pin icon again to unpin the window and minimize it along the border of your PI ProcessBook window. When a docking window is unpinned, a button appears along the side of the screen. Hover over it to re-expand the window. 224 PI ProcessBook 2015 User Guide

235 PI Notifications in PI ProcessBook Topics in this section Open Contacts window Notification Contacts panel MS Office Communicator Contacts panel Work with contacts Contacts presence Open Contacts window Click View > Contacts to open the Contacts docking window. The Contacts toolbar is located at the top of the window and displays: User Status Displays your full user name and current availability. This field cannot is not editable from within PI ProcessBook. Connection button Displays your connection state to Office Communicator. Notification Contacts panel The Notification Contacts panel displays the list of contacts that are subscribed to the notification you have selected in the Notifications window. Contacts are grouped according to type: Escalation Team, Group, and Individual. The group heading displays the icon associated with its type in PI AF. This contact list is not sorted, but appears in the order listed in PI AF to preserve the escalation order for an escalation team. The first entry in the escalation list has the highest priority. A contact's presence is shown with an icon to the left of the contact name. PI ProcessBook 2015 User Guide 225

236 PI Notifications in PI ProcessBook MS Office Communicator Contacts panel The MS Office Communicator Contacts panel displays your contacts from Microsoft Office Communicator. Groups are sorted alphabetically. Contacts are sorted alphabetically within groups. Offline contacts are placed at the end. A contact's presence is shown with an icon to the left of the contact name. Filter Microsoft Office Communicator contacts 1. Enter text in the Contacts Filter text box to search for contacts. Filter results appear in this panel. 2. Click the Clear button to clear your filter parameters. Work with contacts Right click a contact to display a menu that enables you to: View calendar availability (not available with MS Office Communicator 2005) Send an instant message Send Sort contacts View contact information Topics in this section Send an instant message to a contact Send to a contact Sort contacts View contact information Send an instant message to a contact Right click a contact in the Contacts window and click Send Instant Message. This opens an MS Office Communicator conversation window with the selected contact(s). Multiple contacts are not supported with Office Communicator Send to a contact Right click a contact in the Contacts window and click Send . A new message for the selected contact is composed. 226 PI ProcessBook 2015 User Guide

237 PI Notifications in PI ProcessBook A submenu provides the following options: No attachments Creates a blank . Display Screen Capture Attaches a screen capture of the active display. Any changes made to the display while it has been open are included in the screen capture; you do not need to save the file first. You must have Microsoft Outlook XP or greater installed on your machine to send to a contact. Sort contacts Right click a contact in the Contacts window and click Sort. A submenu provides the following options: Alphabetically By Availability Sorts contacts by contacts' presence. Selected by default. View contact information Right click a contact in the Contacts window and click View Contact Card. The Office Communicator Contact Card window appears where you can view contacts from MS Office Communicator. Contacts presence The PI ProcessBook PI Notifications add-in allows you to view personalized presence attributes from Office Communicator while working in PI ProcessBook. For more information on presence, see the Microsoft Office Online Help. PI ProcessBook 2015 User Guide 227

238 PI Notifications in PI ProcessBook 228 PI ProcessBook 2015 User Guide

239 Embedding and Linking PI ProcessBook provides the capability to use Microsoft's OLE linking and embedding technology. You can embed or link OLE objects from other Windows applications into a ProcessBook display. The data might be derived from a wide variety of OLE-compliant applications, such as spreadsheets, documents, and graphics. Topics in this section Overview of Microsoft OLE compound documents OLE Automation in PI ProcessBook Embedded objects Linked objects Should you link or embed? Add an Active X control Work with OLE objects Overview of Microsoft OLE compound documents ActiveX is Microsoft technology used for developing reusable object oriented software components. Container applications are those that can contain ActiveX objects. Compound documents are documents that contain parts from more than one application. The parts may be spreadsheets, word processing documents, ProcessBook displays, and so on. A compound document consists of a container document plus sub-documents that are 'served' by other applications. PI ProcessBook compound document functionality has two aspects: ProcessBook displays can be containers for objects from other applications, such as databases, spreadsheets, or documents. ProcessBook displays can be used to exhibit dynamic data within other container applications. In this case, the ProcessBook or display is considered an object. OLE Automation in PI ProcessBook OLE Automation of PI ProcessBook means that an application or program outside PI ProcessBook can manipulate PI ProcessBook objects such as displays or symbols. Currently, applications with OLE capability include Microsoft Excel, Access, and Visual Basic (VB), among others. A specific set of properties and methods are associated with each object type. Data from PI ProcessBook can be retrieved or manipulated according to scripts originating outside PI ProcessBook. For example, with the proper scripts in place, you could: PI ProcessBook 2015 User Guide 229

240 Embedding and Linking Obtain a PI ProcessBook object, such as a display, from PI ProcessBook and print it in an Excel spreadsheet. In fact, you can write the script to retrieve the display only when certain tag values or other conditions are met. Write a Visual Basic program to start PI ProcessBook, assess a particular display, and then alter it in some way. Click a button in ProcessBook to make an Excel spreadsheet show the average and raw data of the current trend in ProcessBook. Then you could change the time range of the ProcessBook, click the button again, and see the Excel spreadsheet update with the new time range. Although Automation scripts are not required to use a dialect of Visual Basic, at the present time, that is the most common approach. OSIsoft is using Visual Basic as the standard testing language for OLE Automation. For more information on how to write Visual Basic scripts for use with PI ProcessBook, click Help > PI Processbook VBA Language Reference. Embedded objects Embedded objects are copied from an existing file or created and then stored as an integral part of the container application, such as PI ProcessBook. Using an embedded object increases the file size of a ProcessBook significantly. Formats not natively supported by PI ProcessBook, such as Windows metafiles, can be pasted from the Windows clipboard as objects in a ProcessBook display. When you paste an object into a display it becomes embedded. To change the contents of an embedded file, double-click it. The source application software is invoked, and you can edit the object with the source application's commands. PI ProcessBook is a time-based application. When a ProcessBook is used as an embedded object, it updates dynamically whenever you double-click it. If you rename a ProcessBook or move it to another directory, drive, or PC, you can still change any embedded objects in displays as long as your system can locate the appropriate source application software. Topics in this section Embed in PI ProcessBook Edit the contents of an embedded object Share ProcessBook displays with other applications Embed in PI ProcessBook Objects may be created within a PI ProcessBook display by the source application and then stored as embedded objects. Alternatively, you may create objects from existing files or parts of files. In addition, you can embed an object by dragging or pasting it from another application. You must be in Build mode in order to insert a new object. 230 PI ProcessBook 2015 User Guide

241 Embedding and Linking Click Insert > Object to open the Insert Object window. Topics in this section Embed an existing file in a display Embed a new file in a display Embed an existing file in a display You can also embed images by using PI ProcessBook's graphic symbol. The graphic symbol is a built-in symbol that is specifically designed to display images, and therefore may offer you more control then embedding an OLE object. 1. Open the display. 2. In Build mode, click Insert > Object. The Insert Object window appears. 3. Select Create from File. 4. Click the Browse button. The Browse window appears. 5. Browse and locate the file you want to embed and then click the Open button. The file name is displayed in the File box, or In the File box, type the path where the file is located. 6. If you want to display an icon rather than a graphic, click the Display as Icon check box. 7. Click OK. PI ProcessBook 2015 User Guide 231

242 Embedding and Linking The object appears on your display. Embed a new file in a display 1. Open the display. 2. In Build mode, click Insert > Object. The Insert Object window appears. 3. Leave Create New selected (the default position). 4. Under Object Type, click the type of object you want to embed. 5. Click OK. If you want to display an icon rather than a graphic, select the Display as Icon check box. The object appears on your display. 6. Adjust the size and positioning of the object. 7. Commands for the source application are available on the menus. Create the contents of the new object and click elsewhere on the display to return to ProcessBook. 8. Save the display. Edit the contents of an embedded object You cannot edit an embedded object by opening the source application first because the embedded object is not a separate file. Instead, open the source application from within the embedded object in the PI ProcessBook display. Share ProcessBook displays with other applications You can embed a display within another OLE application, or you can link an entire ProcessBook. In embedding, the display is called a PI Display Document. Although applications with OLE functionality use similar commands, they are not exactly alike. The following general procedure uses examples from an Excel spreadsheet. Topics in this section Embed an existing display in another OLE application Embed a new display in another OLE application Embed an existing display in another OLE application 1. Open the display you want to embed. 2. Open the container application. 232 PI ProcessBook 2015 User Guide

243 For example, open a spreadsheet and select a cell in which you want to place a ProcessBook display. 3. In Build mode, click Edit > Select All, and drag the objects in the display into the other application. 4. Save the file. Embedding and Linking When you activate the dragged contents, the entire original display is drawn, regardless of which objects were dragged to the new container. Embed a new display in another OLE application 1. Open the container application. For example, open a spreadsheet and select a cell in which you want to place a display. 2. Click Insert > Object. The Object window appears. 3. On the Create New tab, under Object type, click PI Display Document. 4. Click OK. If you want to display an icon rather than a graphic, select the Display as icon check box. The display is embedded in the container application. Linked objects Linked object information is not stored as a part of the destination application. Instead, the destination file stores only the location of the linked source file. No matter how many links it has, only one version of the linked file is stored and maintained. Using a linked file increases the file size of a ProcessBook less than using an embedded object. In establishing an OLE link, you may update the: Contents of the object dynamically whenever the source file changes Update the object only by manual command To change the data in a linked file, such as which tags you have selected, you switch to the source application and open the file. Changes are then reflected in the container display according to the update method you selected. Alternatively, if you double-click the object, the source application and the actual file open, allowing you to edit the object. If the source application supports in-place activation, you can edit within the container window; otherwise a source application window opens. If you rename a ProcessBook or move it to another directory, drive, or PC, any links from displays to source files can break. These broken links need to be re-established if you wish to continue using them. PI ProcessBook 2015 User Guide 233

244 Embedding and Linking Topics in this section Link a file to a display Dynamic and manual updates of a linked object Edit, update, or break links How links are stored Select a new source link Edit the contents of a linked object Link a ProcessBook to another application Link a file to a display You can create a link from a ProcessBook display to an existing file. The linked object appears in a rectangle within your display. It is updated whenever the source file changes, unless you change the link setting from Automatic to Manual. You must be in Build mode to insert a linked object, however you may move or resize linked objects in either Build or Run mode. You may also edit the contents of a linked object, but you are actually editing the original source file, not simply the image in the ProcessBook display. 1. Open the display. 2. In Build mode, click Insert > Object. The Insert Object window appears. 3. Select Create from File. 4. Click the Browse button. The Browse window appears. 5. Browse and locate the file you want to embed and then click the Open button. The file name appears in the File box, or In the File box, type the path where the file is located. If you want to display an icon rather than a graphic, select the Display as Icon check box. 6. Select the Link check box. 7. Click OK. The object appears on your display. 8. Adjust the size and positioning of the object. Dynamic and manual updates of a linked object The default setting for a link is automatic updates, meaning that whenever the source data are changed, the data in your display changes. 234 PI ProcessBook 2015 User Guide

245 Embedding and Linking You can change this updating frequency to manual through the Links window. Manual updates are also initiated through this window. Edit, update, or break links If you have created an automatic link to another object, it updates whenever you open the entry. If you have created a manually updated link, use the Update Now button on the Links window to update your linked object. When you move a display, you may need to change the sources for linked objects by breaking the links and re-establishing them. 1. Open the display. 2. In Build mode, click Edit > Links. The Links window appears. 3. Click the link you want to change. You can select several links at once by pressing the CTRL key and clicking each link. 4. Choose one of the following options: Select Manual Updates the linked data manually Click Update Now Updates the linked data immediately Click Open Source Edits the linked data Click Break Link Permanently breaks the link. The object is converted to a picture (metafile). 5. Click OK. How links are stored When you establish a link between a ProcessBook display and a source file, the link is stored in two ways, the relative path for the link, and the absolute path for the link. The relative path is the relationship between the location of the source file and the location of the target file in the directory tree. The absolute path includes the drive, directory, and file name of the source file. Select a new source link When you move a ProcessBook or display that contains links to source files, if both the absolute and the relative paths change, you need to reestablish the links. PI ProcessBook 2015 User Guide 235

246 Embedding and Linking 1. Open the display. 2. In Build mode, click Edit > Links. The Links window appears. 3. Click the Change Source button. The Change Source window appears. Edit the contents of a linked object To edit the contents of a linked object, either double-click the object or open the source application and make changes. These are immediately reflected in the ProcessBook display if it is open; otherwise the changes appear the next time you open the ProcessBook display. When editing a linked object file, remember that the file may also be an object in other applications besides PI ProcessBook. In addition, you can reach the source application through the Links window. 1. Click Edit > Links. The Links window appears. 2. Click the appropriate link. 3. Click the Open Source button to open the source file. Link a ProcessBook to another application 1. Open the container application. For example, open a spreadsheet and select a cell in which you want to place a display. 2. Click Insert > Object. The Object window appears. 3. Click the Create from File tab. 4. Do one of the following to enter the file name and path: In the File name box, type the path. Click the Browse button and locate the ProcessBook file (.piw) that you want to link to. 5. Select the Link to File check box. 6. Click OK. The ProcessBook icon is displayed in your application. 236 PI ProcessBook 2015 User Guide

247 Embedding and Linking If you select the Display as Icon check box, then the Object Packager icon is used by default, rather than the ProcessBook icon. Should you link or embed? Embed If you want to update the object data within the target document or if you want to store all the source data within the container application. This option is also better if you plan to link files to different locations. Link If you want the data to update dynamically or when you need to minimize file size. The source application and linked files must continue to be available. When you link to a ProcessBook container, there is a risk of accidentally changing the source file. Example of embedded and linked objects in a ProcessBook display In the example below, a ProcessBook display includes a process schematic, an embedded list of equipment parts, and a link to lab results. The equipment parts list is stored with the ProcessBook display. If your PC has an installed copy of Microsoft Word, you can peruse or modify the list at any time simply by doubleclicking it. The lab results are stored by the source application, not in the ProcessBook display. The display can be set to update lab data dynamically whenever the results in the source application changed, or it can be set to update lab data when you click an Update Now button on the Edit Links window. PI ProcessBook 2015 User Guide 237

248 Embedding and Linking Add an Active X control You can insert ActiveX controls that are installed on your PC into PI ProcessBook displays. If you move the displays to other machines, then you must also install the controls there. Some ActiveX controls are self-contained and will work without further scripting. Most require additional VBA code before they function correctly. 1. In Build mode, open a display. 2. On the Drawing toolbar, click the Control button, or Click Draw > Control. The mouse pointer changes to a control pointer. 3. Click in the display where you want to add the control and drag the pointer to form a rectangle into which the control will be placed. When you release the mouse button, the Insert Control window appears. 4. Under Controls, click the appropriate control, and then click OK. For example, if you add a calendar control to a display, it might look like this: In Run mode, a user could change the month and date. A programmer could incorporate the calendar into scripts associated with the display. Work with OLE objects Topics in this section Icons versus graphics Windows drag and drop Edit the appearance of an OLE object Commands that ignore OLE objects Placement of OLE objects OLE object colors Edit contents of OLE objects Delete an OLE object from a display 238 PI ProcessBook 2015 User Guide

249 Embedding and Linking OLE container or server Icons versus graphics You can choose to have embedded or linked objects displayed either as graphic representations or as icons. An icon uses the minimum area of your display and would be appropriate for reference material, such as definitions. The icon for the source application appears unless you select another one. Choosing an icon to represent a linked file results in a slightly smaller ProcessBook file size. Choosing icons for embedded objects does not reduce ProcessBook file size. Convert graphic representations to icons To save space on a ProcessBook display for a linked object use an icon, rather than a graphic representation of the data. You may select to display an icon when you are creating the object by selecting the Display as Icon check box in the Insert Object window. Later, you can switch between an icon and a graphic representation of the object, as described below. If you have made the graphic representation other than a square shape, the icon may be distorted. 1. Open the display. 2. In Build mode, click the object you want to change. 3. Click Edit > Object (at the bottom of the menu) > Convert. The Convert window appears. 4. Select the Display As Icon check box. 5. Click OK. The object switches from a graphic to an icon. To switch from an icon to a graphic, clear the Display as Icon check box. 6. To select the icon to use, click the Change Icon button. The Change Icon window appears. PI ProcessBook 2015 User Guide 239

250 Embedding and Linking If you want to return to the default icon, then select Default. If you want to select a new icon from the available group, select From File and choose a new icon. If you want to select a new file to provide the icon, click the Browse button. If you want to change the name of the label that displays beneath the icon, then type the new name in the Label box. 7. Click OK to return to the Convert window. 8. On the Convert window, click OK. Windows drag and drop Use the Windows drag and drop feature to move or copy an object from another OLE application or display into a ProcessBook display or vice versa. To move an object, simply drag it. To copy an object, press CTRL and drag it. PI ProcessBook must be in Build mode to successfully have an object dragged or dropped. If you open a display and drag an object elsewhere, the display is permanently changed, regardless of whether you save it or simply close it. Edit the appearance of an OLE object Once an OLE object appears in a display, you can resize it, move it around on the display, or copy it. There are, however, a few differences in how OLE objects respond to PI ProcessBook commands, compared to native objects such as symbols. Although you must be in Build mode to insert an OLE object or edit links, you can edit OLE objects from either Run mode or Build mode. When you select an OLE object, switching modes does not cancel the selection. It is not possible to disable the ability to move, resize, edit, or copy an OLE object. This behavior is built into the underlying Microsoft OLE technology, and not governed by PI ProcessBook. 240 PI ProcessBook 2015 User Guide

251 Embedding and Linking Commands that ignore OLE objects Command Location Action Select All Edit menu Does not include OLE objects. Zoom/Fit All Symbols View menu Ignores OLE objects. Align Arrange menu Does not work because you cannot select more than one OLE object at a time. Forward Arrange menu Does not work because you cannot select more than one OLE object at a time. Backward Arrange menu Does not work because you cannot select more than one OLE object at a time. Group Arrange menu Does not work because you cannot select more than one OLE object at a time. Rotate Arrange menu Does not work with OLE objects. Flip Arrange menu Does not work with OLE objects. Placement of OLE objects OLE objects appear to obscure other elements of the display, such as text or symbols, if the OLE objects were created before the native symbols. The most recently created OLE object appears on top of older OLE objects and native symbols. Active X controls and OLE objects are not really part of a display, but rather sit on top of it. They therefore do not participate in the regular Z-order of display items. This fact also limits the ability to use the Tab key to select OLE objects in a display. OLE object colors You might want to use a background within an OLE object in a contrasting color to the display. To change the colors used in an OLE object, go to the source application. ProcessBook Color Preferences do not apply to OLE objects. Edit contents of OLE objects Some source applications permit in-place activation, which means that if you double-click the OLE object, the source application opens, displays its menus and commands through the ProcessBook menu bar, and permits you to edit the object in place within PI ProcessBook. Other source applications open a new window for editing when you double-click the OLE object. PI ProcessBook 2015 User Guide 241

252 Embedding and Linking 1. Open the display. 2. In Build mode, double-click the OLE object you want to edit. 3. Refer to the following table: If The source application permits in-place activation, menus and commands for the source application appear on your screen, temporarily replacing ProcessBook menus. The source application does not permit in-place activation, a new window containing the source application appears. Then a. Edit the object. b. Save it if it is a linked file. c. Click elsewhere on the display to return to ProcessBook or press the ESC key. a. Edit the object. b. Save it if it is a linked file. c. Close the window and return to ProcessBook. Delete an OLE object from a display 1. In Build mode, click the OLE object you want to delete. 2. Click Edit > Clear. OLE container or server A ProcessBook display can be shown in another application. For example, you could include an updating trend in an incident report produced in a word processing application such as Microsoft Word. Or, you could prepare a presentation for a group by using Microsoft PowerPoint to prepare slides and including embedded displays from PI ProcessBook. To do this, use the Insert Object command in the second application and insert an object of type PI Display Document. 242 PI ProcessBook 2015 User Guide

253 Visual Basic for Applications in PI ProcessBook OSIsoft licenses Visual Basic for Applications (VBA) from Microsoft in order to provide an integrated development environment. This is the same VBA that is used in Microsoft Office, Visio, AutoCAD, Great Plains Dynamics, and many other applications. In PI ProcessBook, each display has a VBA project associated with it. You can write scripts that execute in response to events in PI ProcessBook, either from user actions or data updates. Also use VBA to automate routine tasks or to cause changes in a display when data changes. The Visual Basic toolbar includes three command buttons: Visual Basic Editor, Run Macro, and Design Mode. Use of VBA in PI ProcessBook is documented in the VBA language reference. Click Help > PI ProcessBook VBA Language Reference to open this reference guide. You can find existing custom VBA scripts, and other related resources available at the PI Developers Club Web site. Topics in this section VBA commands ActiveX Automation What you can do with ActiveX Automation in PI ProcessBook Automation vocabulary VBA commands Access VBA through the VBA toolbar, or by clicking Tools > Macro: Visual Basic Editor Run Macros Design Mode Switches to VBA Editor window Opens the Macros window, which provides a way to select, debug, and run existing VBA scripts Stops any scripts that may be running or may start running. Useful for debugging ActiveX Automation ActiveX Automation refers to the technology of placing ActiveX controls (independent software modules) within applications and using scripts to manipulate the application and/or the controls. What you can do with ActiveX Automation in PI ProcessBook Data from PI ProcessBook can be retrieved or manipulated according to scripts originating either within or outside PI ProcessBook. For example, with the proper scripts in place, you could: PI ProcessBook 2015 User Guide 243

254 Visual Basic for Applications in PI ProcessBook Obtain a PI ProcessBook object, such as a display, from PI ProcessBook and print it in an Excel spreadsheet. In fact, you can write the script to retrieve the display if and only if certain tag values or other conditions are met. Write a VB program to start PI ProcessBook, access a particular display, and then alter it in some way. Click on a command button in ProcessBook to make an Excel spreadsheet show the average and raw data of the current trend in ProcessBook. Then you change the time range of the ProcessBook, click the button again, and see the Excel spreadsheet update with the new time range. Use a mouse click within a PI ProcessBook display to initiate updates or adjustments in the display. Update a PI ProcessBook display by typing new tag names into a spreadsheet. Although Automation scripts are not required to use a dialect of Visual Basic, at the present time, that is the most common approach. Automation vocabulary Understanding OLE Automation requires some technical vocabulary. Terms used in the PI ProcessBook VBA Language Reference Guide are defined below. Automation ActiveX Automation Server ActiveX Automation Container Object Property Method Event Accessing an object in an application and changing it or using it without using the user interface. The application that provides data. PI ProcessBook is an OLE Automation Server. It provides access to its internal objects from other applications. The application that initiates changes through scripts. PI ProcessBook is an Automation container, as are Microsoft Excel, Microsoft Access, and a few other commercial products. A specific item that may be manipulated by a script. For example, a ProcessBook, a display, or a symbol may be the object of a VB or VBA script. An attribute of an object. An object with read-write properties can have variable information assigned to it by the script. A read-only property cannot be changed. An action that can be performed on an object and may or may not return a value. Sometimes called a function. A procedure that executes whenever a particular action occurs, such as a mouse click. 244 PI ProcessBook 2015 User Guide

255 System administrator notes Topics in this section Installation Configuration settings for high availability MDB to PI AF migration Default settings for the Playback toolbar DEP security Read and write data access for users Machine address PROCBOOK.INI IMPPIGP.INI SETUPProcessBook.LOG Installation Detailed information on installing PI ProcessBook is available in the PI ProcessBook Release Notes, which are available on the OSIsoft Tech Support site. Topics in this section System requirements 64-bit operating systems Upgrade from a previous version of PI ProcessBook Compatibility with other PI System client products Silent installation Installation test Installed files System requirements For up-to-date system requirements, go to the OSIsoft Tech Support Products page ( techsupport.osisoft.com/products/). Click the product link to see information about the product, including the current system requirements. 64-bit operating systems PI ProcessBook is a 32-bit Windows application that runs on either 32- or 64-bit Windows operating systems. For 64-bit operating systems please note the following: PI ProcessBook 2015 User Guide 245

256 System administrator notes The default install location for OSIsoft 32-bit applications: C:\Program Files (x86) Registry settings are located under the Wow6432Node branch. For example references to:...\software\pisystem\pi ProcessBook\... can be found under:...\software\wow6432node\pisystem\pi ProcessBook\... Upgrade from a previous version of PI ProcessBook If you have a previous version of PI ProcessBook installed on your computer, you should upgrade that version rather than uninstall it. During the installation of PI ProcessBook, your previous version of PI ProcessBook is removed; however,.ini file settings are retained. If you have created or edited displays and ProcessBooks with other versions of PI ProcessBook, those files will still work. If your existing version is significantly older, you may need to migrate the displays through intermediate versions to ensure successful migration. Compatibility with other PI System client products If you have other client products, such as PI DataLink, the same root path is used for installation, often C:\Program Files\PIPC. Otherwise, incompatibilities in the.dll files shared by the applications could occur. If you have PI BatchView installed on your system, the setup program for PI ProcessBook installs a PI ProcessBook Batch group symbol that is compatible with the current version of PI ProcessBook. You can also install PI BatchView after installing PI ProcessBook, and the correct Batch Trend symbol is loaded. PI SQC is installed with PI ProcessBook. Silent installation You can install this software with the Windows silent installation feature. Sometimes called an unattended installation, silent installation requires no feedback during the setup process. System administrators with an automated software distribution application might use silent installation to deploy software automatically to large numbers of corporate desktops. To launch a silent installation, type: Setup.exe f silent.ini The silent.ini file is included in the setup kit. You can make site-specific alterations to the file as needed. See the silent.ini file for further information and descriptions of available arguments. Installation test You can view the results of the installation process by examining the setup log: PIPC\DAT\SetupProcessBook.log 246 PI ProcessBook 2015 User Guide

257 System administrator notes This log also contains information pertaining to the directory structure, node,.dlls, user name, and installation of various PI ProcessBook files. If the log file is not found in the \PIPC \Dat folder, look in the root directory of your system drive (for example, C:\). After you install PI ProcessBook, you can see the words PI System on the Windows Start menu under Programs. At this point, you are ready to use PI ProcessBook. If you experience problems with your software, contact OSIsoft Technical Support through the OSIsoft Technical Support website ( Installed files Upon completion, Setup installs PI ProcessBook under the root directory \PIPC. Setup also installs online help files and Release Notes. See the Release Notes (readme.htm) for a complete list of files. The Release Notes are normally installed at: C:\Program Files\PIPC\procbook\en\ProcessBook.pdf You can look at SetupProcessBook.log in the Dat directory of your PI ProcessBook installation to see a list of files installed by PI ProcessBook's Setup on your computer. SetupProcessBook.log does not show the files installed by VBA. Configuration settings for high availability On workstations where PI ProcessBook is used to write data or access data that is not available on secondary members of a collective, a configuration setting has been provided that modifies the default connection preference. By editing the procbook.ini file you can configure the preference for a particular collective. Entries of the form <collective name>=<preference> in the [COLLECTIVE PREFERENCE] section of the procbook.ini file control how ProcessBook establishes a connection to a server in a particular collective. The value represented above by <collective name> represents the name listed for the collective in the PI Connection Manager. The value represented above by <preference> must be one of the following values: PreferPrimary The primary server in the collective is preferred but not required RequirePrimary The primary server is required Any Any server in the collective is acceptable For PI ActiveView, connection preferences are configured in acview.ini. In general, if the advanced feature requires a primary server to operate correctly, specifying PreferPrimary connects you to the primary member whenever it is available. When the primary is unavailable, a secondary server is used and all features of ProcessBook that don't require the primary server continue to function. If the use of ProcessBook on a workstation PI ProcessBook 2015 User Guide 247

258 System administrator notes requires access to the primary, then specifying RequirePrimary forces the application to only connect to a primary member and fail when such a connection cannot be completed. Recommended setting for connection preference Most ProcessBook displays do not write data to PI Data Archive and therefore work equally well against primary and secondary member servers. A setting of Any is sufficient and supports the static load balancing configured in the PI SDK. A setting of PreferPrimary also works well but does not allow the workstation to participate in load balancing when running ProcessBook. If you use RequirePrimary, and the primary is unavailable, the application behaves as it did without high availability when the server is unreachable. When this occurs during the opening of a display, the error returned by the connection attempt is displayed in the Status Report window for each tag on the server. Typically, the message reads: The requested server in not currently available. Primary. Dynamic symbols on the display are presented in the same manner as any other symbol attached to a disconnected server, though there is no recovery unless the primary server comes back online. Status Report Window If this occurs after the display is already open, ProcessBook detects the loss of connection, as described previously, and tries to reconnect to the server. This call fails, generates the same error as in the previous case (The requested server in not currently available, Primary), and updates the Status Report window. 248 PI ProcessBook 2015 User Guide

259 System administrator notes MDB to PI AF migration PI ProcessBook 2012 converts Module Relative Displays (MRD) created with earlier versions of PI ProcessBook into displays that are compatible with PI AF. The first time you open an MRD display in PI ProcessBook 2012, it is automatically upgraded to an Element Relative Display (ERD) in memory. If you save the display, you cannot revert the display to an MRD. PI ProcessBook does not migrate data from the Module Database (MDB). The data migration is a separate process that occurs when you upgrade to PI Server 2010 or later. OSIsoft recommends that you: Upgrade to PI Server 2010 or later, which automatically converts your MDB data to PI AF Back up all of your displays before upgrading to PI ProcessBook 2012 Allow PI ProcessBook 2012 to automatically upgrade MRD displays to use the ERD instead Topics in this section Module Relative Display Add-in Considerations for multiple versions of Installing PI ProcessBook 2012 uninstalls MRD addin. or PI ProcessBook Matrix of display behavior Migrate a Module Relative Display (MRD) to an Element Relative Display (ERD) Module Relative Display Add-in The Module Relative Display Add-in, included in PI ProcessBook v3.2 and earlier, allows you to show data from a Module Database module on dynamic symbols in PI ProcessBook. This feature does not support PI AF data and is discontinued in PI ProcessBook Installing PI ProcessBook 2012 uninstalls MRD add-in. You must use an earlier release of PI ProcessBook or download and install the MRD add-in from the Technical Support Web site to view the following: MDB data from earlier versions of PI Data Archive Batch displays MRD displays Considerations for multiple versions of Installing PI ProcessBook 2012 uninstalls MRD add-in. or PI ProcessBook You must take special precautions when your PI System includes more than one version of Installing PI ProcessBook 2012 uninstalls MRD add-in. or more than one version of PI ProcessBook. Consider that: PI ProcessBook 2015 User Guide 249

260 System administrator notes PI ProcessBook 2012 does not automatically support MRD displays. You must download and install the MRD add-in to access data in MRD displays from PI ProcessBook 2012 even if you have earlier versions of Installing PI ProcessBook 2012 uninstalls MRD add-in.. When you attempt to open an MRD display that references an older server with PI ProcessBook 2012, you get an upgrade error and no data is displayed. You can use PI ProcessBook 3.2 or earlier to view MRD displays from earlier versions of Installing PI ProcessBook 2012 uninstalls MRD add-in. and PI Server PI Server 2010 has a synchronization feature that allows you to view data with MDB-based tools. After you upgrade a PI ProcessBook display from MRD to ERD, the display will only show data in PI ProcessBook 3.2 or later. Matrix of display behavior The following table describes what happens with MRD displays and ERD displays depending on the version of PI System and the version of PI ProcessBook. PI ProcessBook 2012 PI ProcessBook previously installed MRD add-in PI ProcessBook 3.2 PI Server 2010 or later Pre PI Server 2010 The first time you open an MRD display in PI ProcessBook 2012 the ERD add-in attempts to upgrade it. Symbols on converted displays receive data from PI AF. Installing PI ProcessBook 2012 uninstalls MRD add-in. PI ProcessBook 3.2 supports both MRD and ERD. You must manually uninstall the MRD Add-in from the computer to migrate exiting MRD displays to ERD. PI ProcessBook 3.2 supports both MRD and ERD. See tech support article on When to use MRD and ERD. Attempt to open MRD fails with Element Not Found or Attribute Not Found error messages. Installing PI ProcessBook 2012 uninstalls MRD add-in. You can continue to open MRD displays. Pre- PI ProcessBook 3.2 ERD is not available. PI Server 2010 supports MRD though a two-way synchronization that makes PI AF elements available as Modules. This is not the recommended path forward. We recommend that you upgrade to PI AF. You can continue to open MRD displays. 250 PI ProcessBook 2015 User Guide

261 System administrator notes Migrate a Module Relative Display (MRD) to an Element Relative Display (ERD) When an MRD is opened in PI ProcessBook 3.2 or higher, the ERD add-in attempts to map the stored MDB paths to the new paths in PI AF created by migration to a PI Server 2010 or later. Any errors are reported in the Migration Status window. After this upgrade, if you have saved the display, it is no longer compatible with earlier versions of PI ProcessBook, which do not have ERD. 1. In PI ProcessBook, open an MRD display. The display is shown and the migration process occurs at the point where the display would normally retrieve data. Once the migration process is complete, the ERD docking window appears with a status icon in the title bar notifying you whether or not the migration completed successfully. The display successfully migrated. The display successfully migrated, but there were some issues. The display was not migrated and will not work. In the case of a partially successful migration, the symbols and/or contexts that could not be migrated are left the way they were. If you save your display and then reopen it, the migration is reattempted. Following a successful migration you might see a dynamic symbol display No Data. This occurs when the Module database is migrated to a PI AF database, but the element corresponding to the module cannot be found on the PI AF database. 2. Click the icon to display the Migration Results window. PI ProcessBook 2015 User Guide 251

262 System administrator notes 3. Optional: Click the Save to File button to save the results as a tab-delineated file that can be exported into a spreadsheet such as Microsoft Excel. This file contains additional migration information. Default settings for the Playback toolbar The values for Scroll Period, Display Range, and Speed default to the settings they had when you closed PI Processbook. Default settings do not change from display to display. Start time, end time, and display range values default based on the user and locale. This avoids issues when a user enters a locale-dependent dynamic time string such as *-8 stunde that would only be recognized by the PI System when running under the same locale. Units for speed in the Playback Options window are localized for region. DEP security Data Execution Prevention (DEP) is a setting introduced with Windows XP SP2 and is available in subsequent Windows operating systems. The setting prevents malicious code attacks. PI ProcessBook works correctly when this setting is enabled. Read and write data access for users Although most data features in PI ProcessBook require read-only access (writing annotations from the Details add-in being one notable exception), the PI System administrator can configure a user's setup for read-only, read/write, or no access. For more information, refer to PIBuild:PIServer.txt on your Installing PI ProcessBook 2012 uninstalls MRD add-in. server node. If you want to restrict read and/or write access to PI data, make changes in the CLIENTACCESS section of the file pisysdat:piserver.dat. For example: 252 PI ProcessBook 2015 User Guide

PI ProcessBook 2012 User Guide

PI ProcessBook 2012 User Guide PI ProcessBook 2012 User Guide OSIsoft, LLC 777 Davis St., Suite 250 San Leandro, CA 94577 USA Tel: (01) 510-297-5800 Fax: (01) 510-357-8136 Web: http://www.osisoft.com OSIsoft Australia Perth, Australia

More information

PI DataLink MUI Language Pack

PI DataLink MUI Language Pack PI DataLink MUI Language Pack Version 2015 (5.2.0) 2015 OSIsoft, LLC. All rights reserved Table of Contents Overview Fixes and Enhancements Known Issues Setup Operating Systems System Prerequisites Server

More information

Installing PI AF with SQL Server 2012 AlwaysOn Availability Group Feature. Version 1.0

Installing PI AF with SQL Server 2012 AlwaysOn Availability Group Feature. Version 1.0 Installing PI AF with SQL Server 2012 AlwaysOn Availability Group Feature Version 1.0 OSIsoft, LLC 777 Davis St., Suite 250 San Leandro, CA 94577 USA Tel: (01) 510-297-5800 Fax: (01) 510-357-8136 Web:

More information

OSIsoft Release Notes

OSIsoft Release Notes OSIsoft Release Notes PI OPC DA Server 2017 Version 2.2.1 2017 OSIsoft, LLC. All rights reserved Table of Contents Overview... 1 Fixes and Enhancements... 1 Fixes... 1 Enhancements... 2 Known Issues...

More information

FactoryLink 7. Version 7.0. Client Builder Reference Manual

FactoryLink 7. Version 7.0. Client Builder Reference Manual FactoryLink 7 Version 7.0 Client Builder Reference Manual Copyright 2000 United States Data Corporation. All rights reserved. NOTICE: The information contained in this document (and other media provided

More information

Historian SE PROCESSBOOK USER S GUIDE

Historian SE PROCESSBOOK USER S GUIDE Historian SE PROCESSBOOK USER S GUIDE PUBLICATION HSEPB-UM020A-EN-E September 2007 Contact Rockwell Customer Support Telephone 1.440.646.3434 Online Support http://support.rockwellautomation.com Copyright

More information

PI Connector for Ping 1.0. User Guide

PI Connector for Ping 1.0. User Guide PI Connector for Ping 1.0 User Guide OSIsoft, LLC 777 Davis St., Suite 250 San Leandro, CA 94577 USA Tel: (01) 510-297-5800 Fax: (01) 510-357-8136 Web: http://www.osisoft.com PI Connector for Ping 1.0

More information

Recent Productivity Enhancements to PI ProcessBook

Recent Productivity Enhancements to PI ProcessBook Recent Productivity Enhancements to PI ProcessBook Laurie Dieffenbach, Product Manager Andre Downey, Development Lead OSIsoft Operational Data Analysis and Collaboration PI ProcessBook provides operational

More information

GE Fanuc Automation. CIMPLICITY HMI Plant Edition. Trend and XY Chart. CIMPLICITY Monitoring and Control Products.

GE Fanuc Automation. CIMPLICITY HMI Plant Edition. Trend and XY Chart. CIMPLICITY Monitoring and Control Products. GE Fanuc Automation CIMPLICITY Monitoring and Control Products CIMPLICITY HMI Plant Edition Trend and XY Chart Operation Manual GFK-1260H July 2001 Following is a list of documentation icons: GFL-005 Warning

More information

PI Web Services 2012 SP1 Release Notes

PI Web Services 2012 SP1 Release Notes PI Web Services 2012 SP1 Release Notes 1.3.1.0 2013 OSIsoft, LLC. All rights reserved Table of Contents Overview... 1 Fixes and Enhancements... 1 Fixes... 1 Enhancements... 1 Known Issues... 1 Setup...

More information

2016 OSIsoft TechCon. Condition-Based Maintenance with PI AF

2016 OSIsoft TechCon. Condition-Based Maintenance with PI AF 2016 OSIsoft TechCon Condition-Based Maintenance with PI AF 2016 TechCon Session OSIsoft, LLC 777 Davis St., Suite 250 San Leandro, CA 94577 USA Tel: (01) 510-297-5800 Web: http://www.osisoft.com 2015

More information

IHS Enerdeq Desktop International Training Guide

IHS Enerdeq Desktop International Training Guide IHS > Decision Support Tool IHS Enerdeq Desktop International Training Guide May 2009 Version 1.5.2 2009 IHS, All Rights Reserved. All trademarks belong to IHS or its affiliated and subsidiary companies,

More information

Basic Concepts. Launching MultiAd Creator. To Create an Alias. file://c:\documents and Settings\Gary Horrie\Local Settings\Temp\~hh81F9.

Basic Concepts. Launching MultiAd Creator. To Create an Alias. file://c:\documents and Settings\Gary Horrie\Local Settings\Temp\~hh81F9. Page 1 of 71 This section describes several common tasks that you'll need to know in order to use Creator successfully. Examples include launching Creator and opening, saving and closing Creator documents.

More information

Designer Reference 1

Designer Reference 1 Designer Reference 1 Table of Contents USE OF THE DESIGNER...4 KEYBOARD SHORTCUTS...5 Shortcuts...5 Keyboard Hints...5 MENUS...7 File Menu...7 Edit Menu...8 Favorites Menu...9 Document Menu...10 Item Menu...12

More information

PI Web API 2014 R2 Update 1 Release Notes

PI Web API 2014 R2 Update 1 Release Notes PI Web API 2014 R2 Update 1 Release Notes Application Version 1.3.1 2014 OSIsoft, LLC. All rights reserved Table of Contents Overview... 1 Fixes and Enhancements... 1 Fixes... 1 Enhancements... 1 Setup...

More information

Numbers Basics Website:

Numbers Basics Website: Website: http://etc.usf.edu/te/ Numbers is Apple's new spreadsheet application. It is installed as part of the iwork suite, which also includes the word processing program Pages and the presentation program

More information

For more tips on using this workbook, press F1 and click More information about this template.

For more tips on using this workbook, press F1 and click More information about this template. Excel: Menu to ribbon reference To view Office 2003 menu and toolbar commands and their Office 2010 equivalents, click a worksheet tab at the bottom of the window. If you don't see the tab you want, right-click

More information

2015 OSIsoft TechCon. Building Displays with the new PI ProcessBook and PI Coresight

2015 OSIsoft TechCon. Building Displays with the new PI ProcessBook and PI Coresight 2015 OSIsoft TechCon Building Displays with the new PI ProcessBook and PI Coresight 1 P a g e Table of Contents Contents Table of Contents... 1 Introduction... 2 Objectives... 2 Setup... 2 Approach...

More information

Creating Interactive PDF Forms

Creating Interactive PDF Forms Creating Interactive PDF Forms Using Adobe Acrobat X Pro for the Mac University Information Technology Services Training, Outreach, Learning Technologies and Video Production Copyright 2012 KSU Department

More information

Policy Commander Console Guide - Published February, 2012

Policy Commander Console Guide - Published February, 2012 Policy Commander Console Guide - Published February, 2012 This publication could include technical inaccuracies or typographical errors. Changes are periodically made to the information herein; these changes

More information

Press the Plus + key to zoom in. Press the Minus - key to zoom out. Scroll the mouse wheel away from you to zoom in; towards you to zoom out.

Press the Plus + key to zoom in. Press the Minus - key to zoom out. Scroll the mouse wheel away from you to zoom in; towards you to zoom out. Navigate Around the Map Interactive maps provide many choices for displaying information, searching for more details, and moving around the map. Most navigation uses the mouse, but at times you may also

More information

User Guide. FTR Reporter For more information, visit

User Guide. FTR Reporter For more information, visit FTR Reporter 5.7.1 For more information, visit www.fortherecord.com TABLE OF CONTENTS INTRODUCTION... 5 Overview... 5 About This Document... 5 GETTING STARTED... 6 Installation... 6 Starting Reporter...

More information

End User Guide. 2.1 Getting Started Toolbar Right-click Contextual Menu Navigation Panels... 2

End User Guide. 2.1 Getting Started Toolbar Right-click Contextual Menu Navigation Panels... 2 TABLE OF CONTENTS 1 OVERVIEW...1 2 WEB VIEWER DEMO ON DESKTOP...1 2.1 Getting Started... 1 2.1.1 Toolbar... 1 2.1.2 Right-click Contextual Menu... 2 2.1.3 Navigation Panels... 2 2.1.4 Floating Toolbar...

More information

HBS Training - IT Solutions. PlanWeb. Intermediate

HBS Training - IT Solutions. PlanWeb. Intermediate HBS Training - IT Solutions PlanWeb Intermediate CONTENTS Logging on to the system...3 The PlanWeb Window...5 The Tool Bar...6 The Status Bar...6 The Map Window...6 The Information Window...7 Changing

More information

Unit III: Working with Windows and Applications. Chapters 5, 7, & 8

Unit III: Working with Windows and Applications. Chapters 5, 7, & 8 Unit III: Working with Windows and Applications Chapters 5, 7, & 8 Learning Objectives In this unit, you will: Launch programs and navigate the Windows task bar. Perform common windows functions. Customize

More information

Acrobat X Professional

Acrobat X Professional Acrobat X Professional Toolbar Well Page Navigations/Page Indicator Buttons for paging through document Scroll Bar/box page indicator appears when using the scroll button to navigate. When you release

More information

Chapter 7 Inserting Spreadsheets, Charts, and Other Objects

Chapter 7 Inserting Spreadsheets, Charts, and Other Objects Impress Guide Chapter 7 Inserting Spreadsheets, Charts, and Other Objects OpenOffice.org Copyright This document is Copyright 2007 by its contributors as listed in the section titled Authors. You can distribute

More information

User Guide. Web Intelligence Rich Client. Business Objects 4.1

User Guide. Web Intelligence Rich Client. Business Objects 4.1 User Guide Web Intelligence Rich Client Business Objects 4.1 2 P a g e Web Intelligence 4.1 User Guide Web Intelligence 4.1 User Guide Contents Getting Started in Web Intelligence 4.1... 5 Log into EDDIE...

More information

Collaborate in Qlik Sense. Qlik Sense February 2018 Copyright QlikTech International AB. All rights reserved.

Collaborate in Qlik Sense. Qlik Sense February 2018 Copyright QlikTech International AB. All rights reserved. Collaborate in Qlik Sense Qlik Sense February 2018 Copyright 1993-2018 QlikTech International AB. All rights reserved. Copyright 1993-2018 QlikTech International AB. All rights reserved. Qlik, QlikTech,

More information

Sage Getting Started Guide. September 2017

Sage Getting Started Guide. September 2017 Sage 100 2018 Getting Started Guide September 2017 2017 The Sage Group plc or its licensors. All rights reserved. Sage, Sage logos, and Sage product and service names mentioned herein are the trademarks

More information

WINDOWS XP. iii. Contents

WINDOWS XP. iii. Contents C O N T E N T S Preface INTRODUCTION TO 1 Chapter 1 Navigating Windows XP 3 Launching Windows 3 Working with the Mouse 4 Moving the Mouse 4 Clicking 6 Double-clicking 6 Right-clicking 6 Dragging and Dropping

More information

Managing Content with AutoCAD DesignCenter

Managing Content with AutoCAD DesignCenter Managing Content with AutoCAD DesignCenter In This Chapter 14 This chapter introduces AutoCAD DesignCenter. You can now locate and organize drawing data and insert blocks, layers, external references,

More information

OpenForms360 Validation User Guide Notable Solutions Inc.

OpenForms360 Validation User Guide Notable Solutions Inc. OpenForms360 Validation User Guide 2011 Notable Solutions Inc. 1 T A B L E O F C O N T EN T S Introduction...5 What is OpenForms360 Validation?... 5 Using OpenForms360 Validation... 5 Features at a glance...

More information

Impress Guide. Chapter 11 Setting Up and Customizing Impress

Impress Guide. Chapter 11 Setting Up and Customizing Impress Impress Guide Chapter 11 Setting Up and Customizing Impress Copyright This document is Copyright 2007 2013 by its contributors as listed below. You may distribute it and/or modify it under the terms of

More information

IMAGE STUDIO LITE. Tutorial Guide Featuring Image Studio Analysis Software Version 3.1

IMAGE STUDIO LITE. Tutorial Guide Featuring Image Studio Analysis Software Version 3.1 IMAGE STUDIO LITE Tutorial Guide Featuring Image Studio Analysis Software Version 3.1 Notice The information contained in this document is subject to change without notice. LI-COR MAKES NO WARRANTY OF

More information

MS Publisher County of Henrico Public Libraries

MS Publisher County of Henrico Public Libraries MS Publisher 2013 I. About Publisher A. What is it? Publisher is a desktop publishing program that assists you in designing and producing professional documents that combine text, graphics, illustrations,

More information

SAP BusinessObjects Live Office User Guide SAP BusinessObjects Business Intelligence platform 4.1 Support Package 2

SAP BusinessObjects Live Office User Guide SAP BusinessObjects Business Intelligence platform 4.1 Support Package 2 SAP BusinessObjects Live Office User Guide SAP BusinessObjects Business Intelligence platform 4.1 Support Package 2 Copyright 2013 SAP AG or an SAP affiliate company. All rights reserved. No part of this

More information

Microsoft PowerPoint 2013 Beginning

Microsoft PowerPoint 2013 Beginning Microsoft PowerPoint 2013 Beginning PowerPoint Presentations on the Web... 2 Starting PowerPoint... 2 Opening a Presentation... 2 File Tab... 3 Quick Access Toolbar... 3 The Ribbon... 4 Keyboard Shortcuts...

More information

Getting Started. In This Chapter

Getting Started. In This Chapter Getting Started In This Chapter 2 This chapter introduces concepts and procedures that help you get started with AutoCAD. You learn how to open, close, and manage your drawings. You also learn about the

More information

Libraries. Multi-Touch. Aero Peek. Sema Foundation 10 Classes 2 nd Exam Review ICT Department 5/22/ Lesson - 15

Libraries. Multi-Touch. Aero Peek. Sema Foundation 10 Classes 2 nd Exam Review ICT Department 5/22/ Lesson - 15 10 Classes 2 nd Exam Review Lesson - 15 Introduction Windows 7, previous version of the latest version (Windows 8.1) of Microsoft Windows, was produced for use on personal computers, including home and

More information

Chapter 4 Working with Arena

Chapter 4 Working with Arena Chapter 4 Working with Arena What We ll Do... User interface Menus (including Running) Toolbars Help Model windows Drawing Printing Running Building the simple processing model Simulation with Arena Chapter

More information

VisualPST 2.4. Visual object report editor for PowerSchool. Copyright Park Bench Software, LLC All Rights Reserved

VisualPST 2.4. Visual object report editor for PowerSchool. Copyright Park Bench Software, LLC All Rights Reserved VisualPST 2.4 Visual object report editor for PowerSchool Copyright 2004-2015 Park Bench Software, LLC All Rights Reserved www.parkbenchsoftware.com This software is not free - if you use it, you must

More information

AutoCAD 2009 User InterfaceChapter1:

AutoCAD 2009 User InterfaceChapter1: AutoCAD 2009 User InterfaceChapter1: Chapter 1 The AutoCAD 2009 interface has been enhanced to make AutoCAD even easier to use, while making as much screen space available as possible. In this chapter,

More information

Chapter 2 Using Slide Masters, Styles, and Templates

Chapter 2 Using Slide Masters, Styles, and Templates Impress Guide Chapter 2 Using Slide Masters, Styles, and Templates OpenOffice.org Copyright This document is Copyright 2007 by its contributors as listed in the section titled Authors. You can distribute

More information

Microsoft How to Series

Microsoft How to Series Microsoft How to Series Getting Started with EXCEL 2007 A B C D E F Tabs Introduction to the Excel 2007 Interface The Excel 2007 Interface is comprised of several elements, with four main parts: Office

More information

Security Explorer 9.1. User Guide

Security Explorer 9.1. User Guide Security Explorer 9.1 User Guide Security Explorer 9.1 User Guide Explorer 8 Installation Guide ii 2013 by Quest Software All rights reserved. This guide contains proprietary information protected by copyright.

More information

Desktop Studio: Charts. Version: 7.3

Desktop Studio: Charts. Version: 7.3 Desktop Studio: Charts Version: 7.3 Copyright 2015 Intellicus Technologies This document and its content is copyrighted material of Intellicus Technologies. The content may not be copied or derived from,

More information

Using Online Help. About the built-in help features Using Help Using the How To window Using other assistance features

Using Online Help. About the built-in help features Using Help Using the How To window Using other assistance features Using Online Help About the built-in help features Using Help Using the How To window Using other assistance features About the built-in help features Adobe Reader 6.0 offers many built-in features to

More information

Guide to User Interface 4.3

Guide to User Interface 4.3 Datatel Colleague Guide to User Interface 4.3 Release 18 June 24, 2011 For corrections and clarifications to this manual, see AnswerNet page 1926.37. Guide to User Interface 4.3 All Rights Reserved The

More information

Impress Guide Chapter 11 Setting Up and Customizing Impress

Impress Guide Chapter 11 Setting Up and Customizing Impress Impress Guide Chapter 11 Setting Up and Customizing Impress This PDF is designed to be read onscreen, two pages at a time. If you want to print a copy, your PDF viewer should have an option for printing

More information

Creating Reports in Access 2007 Table of Contents GUIDE TO DESIGNING REPORTS... 3 DECIDE HOW TO LAY OUT YOUR REPORT... 3 MAKE A SKETCH OF YOUR

Creating Reports in Access 2007 Table of Contents GUIDE TO DESIGNING REPORTS... 3 DECIDE HOW TO LAY OUT YOUR REPORT... 3 MAKE A SKETCH OF YOUR Creating Reports in Access 2007 Table of Contents GUIDE TO DESIGNING REPORTS... 3 DECIDE HOW TO LAY OUT YOUR REPORT... 3 MAKE A SKETCH OF YOUR REPORT... 3 DECIDE WHICH DATA TO PUT IN EACH REPORT SECTION...

More information

Discovering Computers & Microsoft Office Office 2010 and Windows 7: Essential Concepts and Skills

Discovering Computers & Microsoft Office Office 2010 and Windows 7: Essential Concepts and Skills Discovering Computers & Microsoft Office 2010 Office 2010 and Windows 7: Essential Concepts and Skills Objectives Perform basic mouse operations Start Windows and log on to the computer Identify the objects

More information

Getting Started with Windows XP

Getting Started with Windows XP UNIT A Getting Started with Microsoft, or simply Windows, is an operating system. An operating system is a kind of computer program that controls how a computer carries out basic tasks such as displaying

More information

Excel 2013 Intermediate

Excel 2013 Intermediate Excel 2013 Intermediate Quick Access Toolbar... 1 Customizing Excel... 2 Keyboard Shortcuts... 2 Navigating the Spreadsheet... 2 Status Bar... 3 Worksheets... 3 Group Column/Row Adjusments... 4 Hiding

More information

ABBYY FineReader 14. User s Guide ABBYY Production LLC. All rights reserved.

ABBYY FineReader 14. User s Guide ABBYY Production LLC. All rights reserved. ABBYY FineReader 14 User s Guide 2017 ABBYY Production LLC All rights reserved Information in this document is subject to change without notice and does not bear any commitment on the part of ABBYY The

More information

Introduction to 9.0. Introduction to 9.0. Getting Started Guide. Powering collaborative online communities.

Introduction to 9.0. Introduction to 9.0. Getting Started Guide. Powering collaborative online communities. Introduction to 9.0 Introduction to 9.0 Getting Started Guide Powering collaborative online communities. TABLE OF CONTENTS About FirstClass...3 Connecting to your FirstClass server...3 FirstClass window

More information

Beyond 20/20. Browser - English. Version 7.0, SP3

Beyond 20/20. Browser - English. Version 7.0, SP3 Beyond 20/20 Browser - English Version 7.0, SP3 Notice of Copyright Beyond 20/20 Desktop Browser Version 7.0, SP3 Copyright 1992-2006 Beyond 20/20 Inc. All rights reserved. This document forms part of

More information

WINDOWS NT BASICS

WINDOWS NT BASICS WINDOWS NT BASICS 9.30.99 Windows NT Basics ABOUT UNIVERSITY TECHNOLOGY TRAINING CENTER The University Technology Training Center (UTTC) provides computer training services with a focus on helping University

More information

IBM Rational Rhapsody Gateway Add On. User Guide

IBM Rational Rhapsody Gateway Add On. User Guide User Guide Rhapsody IBM Rational Rhapsody Gateway Add On User Guide License Agreement No part of this publication may be reproduced, transmitted, stored in a retrieval system, nor translated into any

More information

Technical Documentation Version 7.3 Output

Technical Documentation Version 7.3 Output Technical Documentation Version 7.3 Output These documents are copyrighted by the Regents of the University of Colorado. No part of this document may be reproduced, stored in a retrieval system, or transmitted

More information

Getting Started. Microsoft QUICK Source 7

Getting Started. Microsoft QUICK Source 7 Microsoft QUICK Windows Source 7 Getting Started The Windows 7 Desktop u v w x u Icon links to a program, file, or folder that is stored on the desktop. v Shortcut Icon links to a program, file, or folder

More information

Funasset Limited Foundry House Foundry Road Taunton Somerset TA1 1JJ. Tel: +44 (0) Fax: +44 (0) mailmarkup.com funasset.

Funasset Limited Foundry House Foundry Road Taunton Somerset TA1 1JJ. Tel: +44 (0) Fax: +44 (0) mailmarkup.com funasset. Funasset Limited Foundry House Foundry Road Taunton Somerset TA1 1JJ Tel: +44 (0)1823 365864 Fax: +44 (0)1823 277266 mailmarkup.com funasset.com Copyright 2012 Funasset Limited. All rights reserved. Products

More information

PDF Creator Plus 6.0. Version 6.0. User Guide. PEERNET Inc.

PDF Creator Plus 6.0. Version 6.0. User Guide. PEERNET Inc. Version 6.0 User Guide PEERNET Inc. Copyright 2004-2012 Updated: 12/12/2012 Table of Contents Welcome... to PDF Creator Plus 1 Legal... Notices 2 System... Requirements 3 Typographic... Conventions 4 Activating...

More information

Sending image(s) to report Click Send Snapshot on any screen in Dolphin3D and choose the Send to Report option

Sending image(s) to report Click Send Snapshot on any screen in Dolphin3D and choose the Send to Report option Dolphin 3D Reports Sending image(s) to report Click Send Snapshot on any screen in Dolphin3D and choose the Send to Report option Creating a report step by step 1. Generate the desired images in Dolphin3D

More information

Desktop Studio: Charts

Desktop Studio: Charts Desktop Studio: Charts Intellicus Enterprise Reporting and BI Platform Intellicus Technologies info@intellicus.com www.intellicus.com Working with Charts i Copyright 2011 Intellicus Technologies This document

More information

USER GUIDE MADCAP CAPTURE 7. Getting Started

USER GUIDE MADCAP CAPTURE 7. Getting Started USER GUIDE MADCAP CAPTURE 7 Getting Started Copyright 2018 MadCap Software. All rights reserved. Information in this document is subject to change without notice. The software described in this document

More information

NiceLabel Designer Standard User Guide

NiceLabel Designer Standard User Guide NiceLabel Designer Standard User Guide English Edition Rev-1112 2012 Euro Plus d.o.o. All rights reserved. Euro Plus d.o.o. Poslovna cona A 2 SI-4208 Šenčur, Slovenia tel.: +386 4 280 50 00 fax: +386 4

More information

3.2 Circle Charts Line Charts Gantt Chart Inserting Gantt charts Adjusting the date section...

3.2 Circle Charts Line Charts Gantt Chart Inserting Gantt charts Adjusting the date section... / / / Page 0 Contents Installation, updates & troubleshooting... 1 1.1 System requirements... 2 1.2 Initial installation... 2 1.3 Installation of an update... 2 1.4 Troubleshooting... 2 empower charts...

More information

Aurora Multi-image System Control Software. User Manual

Aurora Multi-image System Control Software. User Manual Aurora Multi-image System Control Software User Manual Product Information Model: Aurora Controller Software Version: V010200 Release Date: January 18th, 2017 Company OSEE TECHNOLOGY CO., LTD. Contact

More information

CA Output Management Web Viewer

CA Output Management Web Viewer CA Output Management Web Viewer User Guide Release 12.1.00 This Documentation, which includes embedded help systems and electronically distributed materials, (hereinafter referred to as the Documentation

More information

SURVEYOR/400. Users Guide. Copyright , LINOMA SOFTWARE LINOMA SOFTWARE is a division of LINOMA GROUP, Inc.

SURVEYOR/400. Users Guide. Copyright , LINOMA SOFTWARE LINOMA SOFTWARE is a division of LINOMA GROUP, Inc. SURVEYOR/400 Users Guide Copyright 1996-2013, LINOMA SOFTWARE LINOMA SOFTWARE is a division of LINOMA GROUP, Inc. Surveyor/400 version: 4.0.0 Publication date: August 7 th, 2013 Table of Contents SURVEYOR/400

More information

[Not for Circulation] This document provides a variety of shortcuts for working in PowerPoint 2007.

[Not for Circulation] This document provides a variety of shortcuts for working in PowerPoint 2007. PowerPoint Shortcuts This document provides a variety of shortcuts for working in PowerPoint 2007. Using Slides from Other Presentations To add a slide from an existing presentation to the current presentation,

More information

HBS Training - IT Solutions. PlanWeb. Introduction

HBS Training - IT Solutions. PlanWeb. Introduction HBS Training - IT Solutions PlanWeb Introduction CONTENTS Logging on to the system...3 The PlanWeb Window...5 The Tool Bar...6 The Status Bar...6 The Map Window...6 The Information Window...7 Changing

More information

Table of Contents. Logos Imaging Application User s Manual Version Page 1

Table of Contents. Logos Imaging Application User s Manual Version Page 1 Table of Contents About... 4 System Requirements... 5 Uninstall Previous Versions... 5 Install LIA 6.0... 6 Install the Device Drivers... 13 Register... 14 Getting Help... 14 Technical Support... 14 Workspace

More information

IBM Rational Rhapsody Gateway Add On. User Manual

IBM Rational Rhapsody Gateway Add On. User Manual User Manual Rhapsody IBM Rational Rhapsody Gateway Add On User Manual License Agreement No part of this publication may be reproduced, transmitted, stored in a retrieval system, nor translated into any

More information

GraphWorX64 Productivity Tips

GraphWorX64 Productivity Tips Description: Overview of the most important productivity tools in GraphWorX64 General Requirement: Basic knowledge of GraphWorX64. Introduction GraphWorX64 has a very powerful development environment in

More information

ADOBE DRIVE 4.2 USER GUIDE

ADOBE DRIVE 4.2 USER GUIDE ADOBE DRIVE 4.2 USER GUIDE 2 2013 Adobe Systems Incorporated. All rights reserved. Adobe Drive 4.2 User Guide Adobe, the Adobe logo, Creative Suite, Illustrator, InCopy, InDesign, and Photoshop are either

More information

User Guide. BlackBerry Workspaces for Windows. Version 5.5

User Guide. BlackBerry Workspaces for Windows. Version 5.5 User Guide BlackBerry Workspaces for Windows Version 5.5 Published: 2017-03-30 SWD-20170330110027321 Contents Introducing BlackBerry Workspaces for Windows... 6 Getting Started... 7 Setting up and installing

More information

Podium Plus Data Analysis Software. User Manual. SWIS10 Version

Podium Plus Data Analysis Software. User Manual. SWIS10 Version SWIS10 Version Issue 1.10 February 2005 Contents 1 Introduction 6 1.1 What is Podium Plus? 6 1.2 About This Manual 6 1.3 Typographical Conventions 7 1.4 Getting Technical Support 7 2 Getting Started 8

More information

WinView. Getting Started Guide

WinView. Getting Started Guide WinView Getting Started Guide Version 4.3.12 June 2006 Copyright 2006 Mincom Limited All rights reserved. No part of this document may be reproduced, transferred, sold or otherwise disposed of without

More information

A QUICK TOUR OF ADOBE ILLUSTRATOR CC (2018 RELEASE)

A QUICK TOUR OF ADOBE ILLUSTRATOR CC (2018 RELEASE) A QUICK TOUR OF ADOBE ILLUSTRATOR CC (2018 RELEASE) Lesson overview In this interactive demonstration of Adobe Illustrator CC (2018 release), you ll get an overview of the main features of the application.

More information

Enterprise Architect Tips & Tricks Compilation - 1

Enterprise Architect Tips & Tricks Compilation - 1 Enterprise Architect Tips & Tricks Compilation - 1 Sparx Systems India In this article we have complied all the tips and tricks which we discovered from our day to day usage of Enterprise Architect. In

More information

Introducing Gupta Report Builder

Introducing Gupta Report Builder Business Reporting Chapter 1 Introducing Gupta Report Builder You can use Report Builder to design reports. This chapter describes: Our approach to building reports. Some of the reports you can build.

More information

SharePoint: Fundamentals

SharePoint: Fundamentals SharePoint: Fundamentals This class will introduce you to SharePoint and cover components available to end users in a typical SharePoint site. To access SharePoint, you will need to log into Office 365.

More information

Using Help Contents Index Back 1

Using Help Contents Index Back 1 Using Online Help Using Help Contents Index Back 1 Using Online Help About the built-in help features Adobe Reader 6.0 offers many built-in features to assist you while you work, including the Help window

More information

Solo 4.6 Release Notes

Solo 4.6 Release Notes June9, 2017 (Updated to include Solo 4.6.4 changes) Solo 4.6 Release Notes This release contains a number of new features, as well as enhancements to the user interface and overall performance. Together

More information

PowerPoint 2010 Level 1 Computer Training Solutions Student Guide Version Revision Date Course Length

PowerPoint 2010 Level 1 Computer Training Solutions Student Guide Version Revision Date Course Length Level 1 Computer Training Solutions Version 1.2 Revision Date Course Length 2012-Feb-16 6 hours Table of Contents Quick Reference... 3 Frequently Used Commands... 3 Manitoba ehealth Learning Management

More information

MockupScreens - User Guide

MockupScreens - User Guide MockupScreens - User Guide Contents 1. Overview...4 2. Getting Started...5 Installing the software... 5 Registering... 9 3. Understanding the Interface...11 Menu Bar... 11 Tool bar... 14 Elements... 14

More information

Help us make this document better smarttech.com/docfeedback/ SMART Ink 3.1 USER S GUIDE FOR WINDOWS OPERATING SYSTEMS

Help us make this document better smarttech.com/docfeedback/ SMART Ink 3.1 USER S GUIDE FOR WINDOWS OPERATING SYSTEMS Help us make this document better smarttech.com/docfeedback/170830 SMART Ink 3.1 USER S GUIDE F WINDOWS OPERATING SYSTEMS Trademark notice SMART Ink, SMART Notebook, SMART Meeting Pro, Pen ID, smarttech,

More information

Excel 2016 Basics for Windows

Excel 2016 Basics for Windows Excel 2016 Basics for Windows Excel 2016 Basics for Windows Training Objective To learn the tools and features to get started using Excel 2016 more efficiently and effectively. What you can expect to learn

More information

Installation and Configuration Manual

Installation and Configuration Manual Installation and Configuration Manual IMPORTANT YOU MUST READ AND AGREE TO THE TERMS AND CONDITIONS OF THE LICENSE BEFORE CONTINUING WITH THIS PROGRAM INSTALL. CIRRUS SOFT LTD End-User License Agreement

More information

PI OPC DA Server User Guide

PI OPC DA Server User Guide PI OPC DA Server 2017 User Guide OSIsoft, LLC 1600 Alvarado Street San Leandro, CA 94577 USA Tel: (01) 510-297-5800 Fax: (01) 510-357-8136 Web: http://www.osisoft.com PI OPC DA Server 2017 User Guide 1992-2017

More information

DYMO ID User Guide BC

DYMO ID User Guide BC DYMO ID User Guide BC Copyright 2015 Sanford, L.P. All rights reserved. Revised: 4/28/2015 No part of this document or the software may be reproduced or transmitted in any form or by any means or translated

More information

Collaborate in Qlik Sense. Qlik Sense April 2018 Copyright QlikTech International AB. All rights reserved.

Collaborate in Qlik Sense. Qlik Sense April 2018 Copyright QlikTech International AB. All rights reserved. Collaborate in Qlik Sense Qlik Sense April 2018 Copyright 1993-2018 QlikTech International AB. All rights reserved. Copyright 1993-2018 QlikTech International AB. All rights reserved. Qlik, QlikTech, Qlik

More information

KYOCERA Net Viewer User Guide

KYOCERA Net Viewer User Guide KYOCERA Net Viewer User Guide Legal Notes Unauthorized reproduction of all or part of this guide is prohibited. The information in this guide is subject to change without notice. We cannot be held liable

More information

OnPoint s Guide to MimioStudio 9

OnPoint s Guide to MimioStudio 9 1 OnPoint s Guide to MimioStudio 9 Getting started with MimioStudio 9 Mimio Studio 9 Notebook Overview.... 2 MimioStudio 9 Notebook...... 3 MimioStudio 9 ActivityWizard.. 4 MimioStudio 9 Tools Overview......

More information

KMnet Viewer. User Guide

KMnet Viewer. User Guide KMnet Viewer User Guide Legal Notes Unauthorized reproduction of all or part of this guide is prohibited. The information in this guide is subject to change for improvement without notice. We cannot be

More information

Piping & Instrumentation Diagrams

Piping & Instrumentation Diagrams Page 1 Piping & Instrumentation Diagrams Preface Using This Guide What's New? Getting Started Entering the Workbench Setting up Working Units and Grid Placing Components Routing a Piping Line or I & C

More information

Manual. empower charts 6.4

Manual. empower charts 6.4 Manual empower charts 6.4 Contents 1 Introduction... 1 2 Installation, updates and troubleshooting... 1 2.1 System requirements... 1 2.2 Initial installation... 1 2.3 Installation of an update... 1 2.4

More information

The walkthrough is available at /

The walkthrough is available at   / The walkthrough is available at https://downloads.openmicroscopy.org/presentations/2018/gbi-sydney / Description We will demonstrate a number of features of the OMERO platform using an OMERO server based

More information