Figure 1. ELSP Current-Limiting Backup Fuse. INSTALLATION

Size: px
Start display at page:

Download "Figure 1. ELSP Current-Limiting Backup Fuse. INSTALLATION"

Transcription

1 Fusing Equipment Current-Limiting Backup Fuse Electrical Apparatus - GENERAL The Cooper Power Systems Current-limiting Backup Fuse is used in series with low current primary protection devices such as a Bay-O-Net Fuse or MagneX Interrupter. The fuse is designed for use in transformer oil, Envirotemp FR3 fluid, or an approved equivalent. The fuse s highly efficient currentlimiting section minimizes the effects of high fault current stresses on equipment and the distribution system. Its minimum interrupting rating is coordinated with that of a low current interrupter to avoid undesirable low current operation; yet its maximum interrupting rating will clear the highest fault currents likely to occur. Higher continuous current ratings can be achieved by connecting two fuses in parallel. APPLICATION The fuse is used in transformers to protect and isolate faulted equipment. When connected in series with a low current primary protection device, the fuse becomes an element of a twopart protection system that gives a full range of fault protection. This two-part system provides low current protection with the replaceable expulsion fuse or resettable MagneX Interrupter, and it adds the energylimiting protection of a current-limiting fuse. Together, they coordinate easily with upstream and downstream devices. Figure 1. Current-Limiting Backup Fuse. INSTALLATION No special tools are required. The fuse is liquid immersed, mounted as near as possible to the incoming primary bushing to which it is connected. Normal liquid dielectric clearances should be used. Refer to Installation Instructions Sheet S--1 for details. PRODUCTION TESTS Tests are conducted on percent of production in accordance with Cooper Power Systems requirements. Physical Inspection I t Testing Resistance Testing Helium Mass Spectrometer Leak Testing TABLE 1 Electrical s and Characteristics Fuse Type Backup (Partial Range) C Rated Maximum Interrupting Current,000 A rms symmetrical* *See Table for fuses with ratings other than,000 A rms symmetrical May 007 Supersedes /07 Printed in U.S.A. 1

2 Current-Limiting Backup Fuse HIGH PURITY SILICA SAND FILLER Specific particle size, purity, and compaction gives the heat-absorbing and arc-quenching properties necessary for consistent clearing and low energy let-thru levels. MICA SPIDER Provides stable winding support without generating gas and pressure buildup during fuse operation. A B C SOLID COPPER END CAPS Brass inserts are tapped for attachment of a 1 /4 inch - 0 x 1 / inch lead hardware. DOUBLE SEALING SYSTEM Buna-N rubber gasket and epoxy sealant ensures seal performance and integrity. FIBERGLASS HOUSING Provides strength and maintains integrity of fuse during any interruption, from minimum melt current to maximum rated current of ka. INDELIBLE IDENTIFICATION LABEL Easy-to-read voltage and current ratings and catalog numbers. PURE SILVER ELEMENT Stable under current cycling and thermal stress, providing consistent melt characteristics. The ribbons effectively control and minimize peak arc voltage levels resulting from high current interrup tions. During inter rup tion, the element effectively controls and limits both current and energy (l t) let-thru levels. Figure. diameter Current-Limiting Back-up Fuse cutaway shows design characteristics. Note: Dimensions given are for reference only. TABLE Interrupting s Continuous Current Minimum Interrupting Capacity 8.3 kv kv 3 kv 3 Minimum Melt I Maximum t (A Clear I Minimum Minimum t s) (A Interrupting Melt I Maximum t s) Capacity (A Clear I Minimum Minimum t s) (A Interrupting Melt I t s) Capacity (A s) Maximum Clear I t (A s) 1,00 5,800 1,00 7, ,00 10,0 15 1,800 8,00 1 1,800 11, ,800 15, 1 4, 16,0 00 4, 3, , 34,0 0 6,00 6, ,00 33, ,00 38, ,600 4,900 9,600 5, ,600 68,0 3 17, 6, , 93, , 11, ,0 97,800 0,0 15,700 0,0 149, , , ,900 16, , , ,600 45, ,600 7,0 ** 800 1, , ,000 8, , , 0** 0 175, , , , , ,000 3** ,0 875, ,0 88,000 Notes: 1. The 8.3 kv, A through A ratings have been tested and approved for application at 9.9 kv. The maximum interrupting capacity for the A through A ratings at 9.9 kv is 18 ka.. The 15.5 kv, through 15 A and A ratings have been tested and approved for application at 17. kv. The maximum interrupting rating for the 15.5 kv fuse, A through 15 A at 17. kv is 43 ka. For the 15 kv, A fuse at 17. kv the maximum interrupting rating is 1 ka. 3. The maximum interrupting rating for the 3 kv fuse, 80 A through 1 A, 0 A and 3 A, is ka. For the 3 kv, A fuse the maximum interrupting rating is 1 ka. ** Parallel Fuses

3 - B C Figure 3. 3 diameter Current-Limiting Backup Fuse cutaway shows design characteristics. Note: Dimensions given are for reference only. TABLE 3 Dimensional Information Voltage (kv) Current A Dim. in/ (mm) - 7. (183) (44) (77) (47) (356) (414) (33) (49) 1-1 n/a B Dim. in/ (mm) 6.0 (15) 8.4 (14) 9.7 (47) 8.5 (16) 1.8 (35) 15.1 (384) 11.5 (9) 15.6 (396) 18.9 (480) C Dim. in/ (mm) (76) Ref. Figure 3 ORDERING INFORMATION To order an current-limiting fuse, de ter mine the am per age and voltage ratings of the ap pli ca tion and specify the fuse required from Table 4. For parallel fusing, order two fuses. TABLE 4 Back-Up Fuse Catalog Numbers Catalog Number Current 8.3 kv 15.5 kv 3 kv 354M61M 354M61M 354M61M 354M61M 354M61M 354M61M 354M61M 354M61M 354M61M 354M61M 354M61M 354M61M M71M 35480M71M M71M 3543M71M 3544M71M 3545M71M M71M M71M M71M M71M 35441M71M 35451M71M M71M N/A 35451M71M * M71M M71M M71M 0* 35431M71M 35441M71M 35451M71M 3* 35431M71M N/A 35451M71M * Parallel fuse application (ORDER TWO FUSES) Method A CORRELATION INFORMATION Use the correlation information in Tables 5, 6 and 7 to determine the amperage and voltage ratings of the fuse combination required for the application. Then use Table 4 to determine the appropriate fuse catalog number. Correlation is based on IEEE Standard C57.9 Loading Guide and IEEE Standard C Through-Fault Guide, and the Fuse Application Guide CP766A. Tables 5, 6 and 7 indicate the rec om mend ed Bay-O-Net fuse link or MagneX Interrupter and combination for each application. To order a current sensing Bay-O- Net Fuse, complete catalog number To order a dual sensing Bay-O-Net Fuse, complete catalog number To order a dual element Bay-O-Net Fuse, complete catalog number To order a High Ampere Overload Bay-O-Net Fuse, complete catalog number Examples: To order an and dual element Bay-O-Net fuse combination for a single-phase, 7. kv phase-to-ground, kva transformer, specify: 1 A Fuse 354M61M 1 Bay-O-Net Fuse 38108C07 3

4 Current-Limiting Backup Fuse TABLE 5 Recommended Single-Phase Transformer Bay-O-Net and Combinations 8.3 kv Nominal Single-Phase Voltage (KV) Phase-to-Ground Single- Phase Transformer (KVA) and Current Sensing Bay-O-Net Fuse Combinations a C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C17 and Dual Sensing Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C1 1.9 C C C C C C C1 1.9 C C C C C C and Dual Element Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C C C C C C C C C C1.0 C C C High Amp Overload Bay-O-Net/ Combinations C03CB C04CB**.6 1 C03CB C05CB*** C04CB C05CB C03CB** C05CB*** C04CB** Indicates parallel fuse application Notes: The following tables show minimum recommended fuse ratings. Recommended backup fuse will coordinate with protecting fuse and melt only on internal transformer faults. Rec om mended Bay-O-Net fuses meet inrush criterion of 1 times transformer full load current for 0.1 second. If a different transformer impedance is used, a different Fuse rating may be required. If a larger % is used, a smaller may coordinate. a. Current sensing Bay-O-Net fuse is selected to melt at 3 to 4 times transformer full load in 0 seconds. b. Dual sensing and Dual element Bay-O-Net fuses are selected to limit transformer load to approximately 160% for 7 hours and 00% for hours with the trans former initially carrying 75% of rated load at ambient temperature of 35 C. ** The use of these fuses will provide 175% of rated load for hours and 1% of rated load for 7 hours. The use of the next larger fuse is recommended for greater overload capacity. Contact your Cooper Power Systems representative for specific overload capability. *** The specified fuse provides slightly less than 175% of rated load for hours and 1% of rated load for 7 hours. Contact your Cooper Power Systems representative for specific overload capability. 4

5 - TABLE 5 (Continued) Recommended Single-Phase Transformer Bay-O-Net and Combinations 15.5 kv 3 kv Nominal Single-Phase Voltage (kv) Phase-to-Ground Single-Phase Transformer (kva) and Current Sensing Bay-O-Net Fuse Combinations a C C C C C C C C C C C C C C C C C C C C C C C C C C C C06.0 C08.0 C08.0 C08.0 C C10.6 C10.6 C10.6 C C1 4.0 C1 4.0 C C C C1 5.0 C C C C C C14 and Dual Sensing Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C C C C C C C C C C C C C C C C05.0 C08.0 C08.0 C08.0 C C10.6 C10.6 C10.6 C C C1 4.0 C C C C C1 5.0 C C C c C C10 and Dual Element Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C C C C C C C C C C C C C C C C C09.0 C07.0 C07.0 C C C09.6 C07.6 C C C C1 5.0 C High Amp Overload Bay-O-Net/ Combinations C03CB C03CB Indicates parallel fuse application Note: Table shows minimum recommended fuse ratings. Recommended backup fuse will coordinate with protecting fuse and melt only on internal transformer faults. Recom mended Bay-O-Net fuses meet inrush criterion of 1 times transformer full load current for 0.1 second. a. Current sensing Bay-O-Net fuse is selected to melt at 3 to 4 times transformer full load in 0 seconds. b. Dual sensing and Dual element Bay-O-Net fuses are selected to limit transformer load to approximately 160% for 7 hours and 00% for hours with the trans former initially carrying 75% of rated load at ambient temperature of 35 C. c. Use 3.0 kv rated fuse for this application. (See Table, note, page of this catalog section). 5

6 Current-Limiting Backup Fuse TABLE 6 Recommended Three-Phase Transformer Bay-O-Net and Combinations 8.3 kv Nominal Three-Phase Voltage (KV) Phase-to-Phase Three- Phase Transformer (KVA) and Current Sensing Bay-O-Net Fuse Combinations a C C C C C C C1 1.8 C C C C C C C C C C C C C C C C and Dual Sensing Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C C C C C C and Dual Element Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C C High Amp Overload Bay-O-Net/ Combinations C03CB C04CB C04CB** C03CB C03CB C05CB*** C04CB** C04CB C05CB*** C04CB C05CB Indicates parallel fuse application Note: Table shows minimum recommended fuse rating. Recommended backup fuse will coordinate with protecting fuse and melt only on internal transformer faults. Recommended Bay-O-Net fuses meet inrush criterion of 1 times transformer full load current for 0.1 second. a. Current sensing Bay-O-Net fuse is selected to melt at 3 to 4 times transformer full load in 0 seconds. b. Dual sensing and Dual element Bay-O-Net fuses are selected to limit transformer load to approximately 160% for 7 hours and 00% for hours with the trans former initially carrying 75% of rated load at ambient temperature of 35 C. ** The use of these fuses will provide 175% of rated load for hours and 1% of rated load for 7 hours. The use of the next larger fuse is recommended for greater overload capacity. Contact your Cooper Power Systems representative for specific overload capability. *** The specified fuse provides slightly less than 175% of rated load for hours and 1% of rated load for 7 hours. Contact your Cooper Power Systems representative for specific overload capability. 6

7 - TABLE 6 (Continued) Recommended Three-Phase Transformer Bay-O-Net and Combinations 15.5 kv Nominal Three-Phase Voltage (kv) Phase-to-Phase d 4.9d Three-Phase Transformer (kva) and Current Sensing Bay-O-Net Fuse Combinations a C C C C C C C C C C C C C08.0 C08.0 C06.0 C C C C C C C C C C1 4.0 C1 4.0 C C C C C C C C C C C C C C C C C16 and Dual Sensing Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C08.0 C08.0 C05.0 C C C C C C C C C C C1 4.0 C C C C C C C C C C C C C14 and Dual Element Bay-O-Net Fuse Combinations b C C C C C C C C C C C C C07.0 C07.0 C06.0 C C C C C C C C C C1 4.0 C C C C C C C C C High Amp Overload Bay-O-Net/ Combinations C03CB C04CB C03CB C04CB** 5.75 C04CB C03CB C03CB C05CB*** 5.75 C05CB 5.75 C04CB 5.75 C04CB C05CB*** 5.75 C05CB*** 5.75 C04CB** 5.75 C04CB Indicates parallel fuse application Note: Table shows minimum recommended fuse rating. Recommended backup fuse will coordinate with protecting fuse and melt only on internal transformer faults. Recommended Bay-O-Net fuses meet inrush criterion of 1 times transformer full load current for 0.1 second. a. Current sensing Bay-O-Net fuse is selected to melt at 3 to 4 times transformer full load in 0 seconds. b. Dual sensing and Dual element Bay-O-Net fuses are selected to limit transformer load to approximately 160% for 7 hours and 00% for hours with the trans former initially carrying 75% of rated load at ambient temperature of 35 C. c. 3 kv delta primary transformer connection. d. Recommended fuse is limited to gnd Y/gnd Y transformer with no more than % delta connected secondary load and with neutral internally grounded. Phase-to-ground rated fuses are frequently recommended for gnd Y-gnd Y connections. ** The use of these fuses will provide 175% of rated load for hours and 1% of rated load for 7 hours. The use of the next larger fuse is recommended for greater overload capacity. Contact your Cooper Power Systems representative for specific overload capability. *** The specified fuse provides slightly less than 175% of rated load for hours and 1% of rated load for 7 hours. Contact your Cooper Power Systems representative for specific overload capability. 7

8 Current-Limiting Backup Fuse TABLE 6 (Continued) Recommended Three-Phase Transformer Bay-O-Net and Combinations 3 kv Nominal Three-Phase Voltage (KV) Phase-to-Phase 3 c 7.6 d 34.5 d Three- Phase Transformer Rat- Rat- Rat- (KVA) ing ing ing and Current Sensing Bay-O-Net Fuse Combinations a C C C C C C C C C C06.0 C06.0 C C C C C C C C C C C C C C C C C C C C C C14 and Dual Sensing Bay-O-Net Fuse Combinations b C C C C C C C C C C05.0 C05.0 C C C C C C C C C C C C C C C C C C C C14 and Dual Element Bay-O-Net Fuse Combinations b C C C C C C C C C C05.0 C04.0 C C C C C C C C Indicates parallel fuse application Note: Table shows minimum recommended fuse rating. Recommended backup fuse will coordinate with protecting fuse and melt only on internal transformer faults. Recommended Bay-O-Net fuses meet inrush criterion of 1 times transformer full load current for 0.1 second. a. Current sensing Bay-O-Net fuse is selected to melt at 3 to 4 times transformer full load in 0 seconds. b. Dual sensing and Dual element Bay-O-Net fuses are selected to limit transformer load to approximately 160% for 7 hours and 00% for hours with the trans former initially carrying 75% of rated load at ambient temperature of 35 C. c. 3 kv delta primary transformer connection. d. Recommended fuse is limited to gnd Y/gnd Y transformer with no more than % delta connected secondary load and with neutral internally grounded. Phase-to-ground rated fuses are frequently recommended for gnd Y-gnd Y connections. 8

9 - TABLE 7 Recommended MagneX Interrupter and Current-Limiting Fuse Combinations Nominal Single Phase (kv Phase-to-ground) 10 kva % = kva. % = kva % = kva % = 1.9 kva % = kva % = 1.9 kva % = kva % = E5 1 E 1 E - 1 E 1 E - E1 15 E5 1 E 1 E 8.3 kv 15.5 kv 3 kv Notes: The MagneX Interrupter recommendations are based on: Deration factor of 0.5% per C above 5 C. Allowable loading greater than 1% for four hours in accordance with IEEE Standard C guide for Loading Distribution Transformers, Table 6. If using a MagneX Interrupter equipped without emergency overload, a smaller rating may be used. E1 15 E5 1 E E1 15 E5 1 E E1 15 E5 1 E 1 E E01 E1 E01 E E01 E1 E01 E01 E1 9

10 Current-Limiting Backup Fuse See the Following Catalog Sections for Additional Information: Fuse Holder Section -53 Bay-O-Net Fuse Holder Assembly Section - Current Sensing Bay-O-Net Fuse Section -45 Dual Sensing Bay-O-Net Fuse Section -46 Dual Element Bay-O-Net Fuse Section -48 High Ampere Overload Bay-O-Net Fuse Section -49 MagneX Interrupter Section -34 (previously 800-) Contact your Cooper Power Systems representative for further in for ma tion or other applications. Method B TIME CURRENT CURVES To determine or confirm the fuse that will coordinate with up stream and downstream system requirements, use the time-current characteristic curves and specify the fuse in di cated from Table 4. For full size TCC curves R (8.3 kv), R-91-7 (15.5 kv), and R (3.0 kv), contact your Cooper Power Systems rep re sen ta tive. 10

11 - 11

12 007 Cooper Power Systems, Inc., or its affiliates MagneX, Envirotemp, and FR3 are registered trademarks of Cooper Power Systems, Inc., or its affiliates IEEE Standard C57.9, IEEE Standard C57.91 and IEEE C are trademarks of the Institute of Electrical and Electronics Engineer, Inc Hickory Street Pewaukee, WI 57 USA

COOPER POWER SERIES. Fusing Equipment Catalog Data CA132064EN. Effective February 2018 Supersedes January 2014 (240-50)

COOPER POWER SERIES. Fusing Equipment Catalog Data CA132064EN. Effective February 2018 Supersedes January 2014 (240-50) Fusing Equipment Catalog Data CA132064EN Supersedes January 2014 (240-50) COOPER POWER SERIES Table of contents Attention....3 Eaton is in the process of updating part numbers and technical data due to

More information

ELSP current-limiting backup fuse

ELSP current-limiting backup fuse Catalog Data CA132013EN Supersedes TD132002EN October 2014 COOPER POWER SERIES current-limiting backup fuse General Eaton offers its Cooper Power series current-limiting backup fuse that is used in series

More information

ELSP current-limiting backup fuse

ELSP current-limiting backup fuse Supersedes May 2018 COOPER POWER SERIES General Eaton offers its Cooper Power series current-limiting backup fuse that is used in series with low current primary protection devices such as a Bay-O-Net

More information

Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test

Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test Surge Arresters VariSTAR Type AZU Heavy-duty Distribution Class Under-oil MOV Arrester Electrical Apparatus 235-64 GENERAL The Cooper Power Systems VariSTAR Type AZU under-oil MOV arrester is designed

More information

35 kv Class M.O.V.E. DirectConnect elbow arrester

35 kv Class M.O.V.E. DirectConnect elbow arrester Surge Arresters Catalog Data CA3506EN Effective February 017 Supersedes November 015 COOPER POWER SERIES 35 kv Class M.O.V.E. DirectConnect elbow arrester General Eaton's Cooper Power series M.O.V.E. DirectConnect

More information

Ferraz Shawmut TPMOV Principles and Operation

Ferraz Shawmut TPMOV Principles and Operation TPMOV Origin Due to recent changes in the Underwriters Laboratories Standard for Safety for Surge Protective Devices UL 1449 additional requirements have been instituted to maintain listings of Surge Protective

More information

TRANS-GUARD EXT CURRENT-LIMITING BACKUP FUSE 46KV - 138KV SYSTEMS

TRANS-GUARD EXT CURRENT-LIMITING BACKUP FUSE 46KV - 138KV SYSTEMS TRANS-GUARD EXT CURRENT-LIMITING BACKUP FUSE 46KV - 138KV SYSTEMS Minimize Energy Let-Through. Maximize Equipment Protection. Commonly used on 34.5kV and lower systems to enhance protection, external -Limiting

More information

L50QS SERIES HIGH-SPEED ROUND BODY FUSES

L50QS SERIES HIGH-SPEED ROUND BODY FUSES 00 Vac/dc -0 A Traditional Round Body Bolted Style HF Specifications Voltage Rating Amperage Rating Interrupting Rating Time Constant Material Approvals Environmental Country of Origin AC: 00V DC: 00V

More information

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters. Surge Arresters Storm Trapper H.E. (High Energy) Low-Voltage Distribution-class MoV Surge Arrester Electrical Apparatus 235-16 GEnErAL Cooper Power Systems Storm Trapper H.E. (High Energy), lowvoltage

More information

MEDIUM VOLTAGE FUSES. POWR-GARD Fuse Datasheet. 2,400-38,000 VAC Current-Limiting

MEDIUM VOLTAGE FUSES. POWR-GARD Fuse Datasheet. 2,400-38,000 VAC Current-Limiting MEDIUM VOLTAGE FUSES 2,400-38,000 VAC Current-Limiting Current-limiting E- and R-rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of

More information

File Ref: CP No.: CP1205 Rev. 0 Page: 1 of 25 CERTIFIED TEST REPORT. Cooper Power Systems. 28 kv Class 600 Amp 16.2 / 28.

File Ref: CP No.: CP1205 Rev. 0 Page: 1 of 25 CERTIFIED TEST REPORT. Cooper Power Systems. 28 kv Class 600 Amp 16.2 / 28. CP No.: CP1205 Rev. 0 Page: 1 of 25 CERTIFIED TEST REPORT Cooper Power Systems 28 kv Class 600 Amp CLĒĒR TM LOADBREAK SEPARABLE CONNECTOR SYSTEM REV. 0 DATE May 3, 2012 ORIGINAL REPORT DATE: May 3, 2012

More information

CABLE PROTECTORS /SPECIAL PURPOSE

CABLE PROTECTORS /SPECIAL PURPOSE CABLE PROTECTORS Ferraz Shawmut Cable Protectors are special purpose limiters which are crimped or bolted to cables to clear and isolate faults quickly, increasing the reliability of service entrance and

More information

Special Purpose Fuses

Special Purpose Fuses Ferraz Shawmut CP are special purpose limiters which are crimped or bolted to cables to clear and isolate faults quickly, increasing the reliability of service entrance and distribution runs. They are

More information

Section Overview. Table of Contents

Section Overview. Table of Contents Section Overview Littelfuse is your source for a fast replacement of - and R-rated medium voltage fuses. Our emergency service gets you the fuses you need quickly to minimize downtime of your critical

More information

JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B. R-Rated Fuses For Motor Circuit Protection Medium Voltage.

JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B. R-Rated Fuses For Motor Circuit Protection Medium Voltage. R-Rated medium voltage fuses are back-up current limiting fuses used in conjunction with medium voltage motors and motor controllers. The JCK-A, JCL-A, & JCR-A are supplied with Cutler- Hammer Ampgard

More information

CERTIFIED TEST REPORT

CERTIFIED TEST REPORT CP No.: CP1120 Rev. 1 Page: 1 of 24 CERTIFIED TEST REPORT Cooper Power Systems 15 kv Class 600 Amp CLĒĒR TM LOADBREAK SEPARABLE CONNECTOR SYSTEM REV. 1 DATE September 1, 2011 ORIGINAL REPORT DATE: July

More information

Special Purpose Fuses

Special Purpose Fuses Cable Protectors CP & CPH Ferraz Shawmut CP Cable Protectors are special purpose limiters which are crimped or bolted to cables to clear and isolate faults quickly, increasing the reliability of service

More information

AMP-TRAP Form 101 A15QS

AMP-TRAP Form 101 A15QS AMP-TRAP Form 0 AQS SEMICONUCTOR PROTECTION FUSES AQS Amp-trap Form 0 Semiconductor Protection fuses were designed for the specific protection of diodes and other semiconductor devices rated VAC/C. The

More information

Annexure-1 (CC no )

Annexure-1 (CC no ) Annexure-1 (CC no. 77627) TECHNICAL SPECIFICATIONS OF EXISTING LIGHTNING ARRESTORS S. No. Description Parameter 1. Type Station class heavy duty zinc oxide gapless 2. Applicable standard IEC-60099-4 /

More information

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary switched power supply, 1-phase, output current: 5 A ITERFACE Data Sheet 103349_en_00 1 Description PHOEIX COTACT - 05/2008 Features TRIO POWER is the DI-rail-mountable power supply unit with basic

More information

PRM MODEL TABLE. (1) Measured at 115V a-c source.

PRM MODEL TABLE. (1) Measured at 115V a-c source. SERIES PRM These units are modular ferroresonant voltage stabilizers which obtain their source-isolated, overload-protected output from Kepco s proprietary transformer, Flux-O-Tran. This design lends itself

More information

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary switched power supply, 3-phase, output current: 40 A INTERFACE Data Sheet 102782_01_en PHOENIX CONTACT - 06/2007 Description TRIO POWER is the rail mountable 24 V power supply unit with basic functions.

More information

10 SEC TIME DELAY (AT 500 PERCENT RATED LOAD), DUAL ELEMENT

10 SEC TIME DELAY (AT 500 PERCENT RATED LOAD), DUAL ELEMENT 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 AllenWatson@elliottelectric.com Catalog Number Manufacturer Description Weight per unit Product Category Features Characteristics

More information

L CV1050 Constant Voltage LED Driver, 24Vdc, 25W L1K1MID024V-25E

L CV1050 Constant Voltage LED Driver, 24Vdc, 25W L1K1MID024V-25E L05032-24CV1050 Constant Voltage LED Driver, 24Vdc, 25W L1K1MID024V-25E Engineered for Best Fixture Performance Fulham LumoSeries LED drivers are designed to efficiently power and control LED solutions

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation /

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation   / 5kA rms - 8kA DC Fluxgate current transducer Features DC 8000A AC 5000A rms Maximum gain error DC to 1kHz - 0.1% Transducer core optimized for high level of immunity against external magnetic fields Operating

More information

STEP-PS/1AC/24DC/1.75

STEP-PS/1AC/24DC/1.75 Primary-switched power supply, 1 AC, output current 1.75 A INTERFACE Data Sheet 103506_en_00 1 Description PHOENIX CONTACT - 05/2008 Features STEP POWER power supply units for building automation The new

More information

FLQ SERIES MIDGET (10x38mm) FUSES

FLQ SERIES MIDGET (10x38mm) FUSES 500 Vac Time-Delay 1 / 10-30 A Description The FLQ series 500 Vac time-delay fuses provide excellent supplemental protection of control power transformers, solenoids, and circuits with high inrush currents.

More information

SERIES SD3800 / SD3810 SPECIFICATION

SERIES SD3800 / SD3810 SPECIFICATION SERIES SD3800 / SD3810 SPECIFICATION SOLID DIELECTRIC SINGLE SIDED 15 KV & 25 KV PADMOUNTED VACUUM LOAD INTERRUPTERS AND VACUUM FAULT INTERRUPTERS WITH VISIBLE DISCONNECTS MANUALLY OPERATED / REMOTELY

More information

Purpose of High Voltage Circuit Switchers

Purpose of High Voltage Circuit Switchers Purpose of High Voltage Circuit Switchers Vertical interrupter circuit switcher without integral disconnect switch (Figure 2) Three-phase Interruption and Protection Circuit switchers have been developed

More information

L05055 LED Driver 60W, Vdc, mA L05059 LED Driver 60W, Vdc, mA L1M S-60E L1M S-60E

L05055 LED Driver 60W, Vdc, mA L05059 LED Driver 60W, Vdc, mA L1M S-60E L1M S-60E LED Driver 60W, 22-46 Vdc, 400-2000mA LED Driver 60W, 18-60 Vdc, 700-1400mA L1M1230200S-60E L1M1230140S-60E Engineered for Best Fixture Performance Fulham LumoSeries drivers are all built on core engineering

More information

Telephony Multi-Taps. 9000T-TP Series

Telephony Multi-Taps. 9000T-TP Series 9000T-TP Series The 9000T-TP series 1 GHz twisted-pair power multi-tap taps off part of its input RF and AC, but lets the rest pass through. It divides the tapped-off signal and power into multiple outputs,

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

DX 3 MCB A / 16 ka 80 A to 125 A (1,5 module per pole)

DX 3 MCB A / 16 ka 80 A to 125 A (1,5 module per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

AIR COOLED MODULAR RECTIFIER

AIR COOLED MODULAR RECTIFIER CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:

More information

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply for building automation INTERFACE Data sheet 103505_en_02 1 Description PHOENIX CONTACT - 08/2009 Features STEP POWER power supply units for building automation The new STEP

More information

Relays & Sockets. RSC Series. RSC Series Solid State Relays. Part Number Selection Specifications

Relays & Sockets. RSC Series. RSC Series Solid State Relays. Part Number Selection Specifications RSC Series RSC Series Solid State Relays Key features of the RSC series include: Slim design allows for DIN rail or panel mounting Built-in heat sink maximizes current output capability Epoxy-free design

More information

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary switched power supply, 1-phase, output current: 5 A ITERFACE Data Sheet 102777_en_03 1 Description PHOEIX COTACT - 05/2008 Features TRIO POWER is the DI-rail-mountable power supply unit with basic

More information

Limitor - PD Back-up Fuses without Controlled Power Dissipation

Limitor - PD Back-up Fuses without Controlled Power Dissipation Limitor - PD Back-up Fuses HIGH VOLTAGE IEC FUSES DIN HV BACK-UP FUSES FOR TRANSFORMERS FEATURES & BENEFITS Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear

More information

Ferrule fuse-links 14x51 am 500 to 690VAC

Ferrule fuse-links 14x51 am 500 to 690VAC Ferrule fuse-links 4x am 0 to 690VAC Ferrule fuse-links 4x am 0 to 690VAC LOW VOLTAGE IEC FUSES IEC CYLINDRICAL FUSE-LINKS FEATURES & BENEFITS Reduced size Striker version available for remote indication

More information

Ferrule fuse-links 22x58 am 500 to 690VAC

Ferrule fuse-links 22x58 am 500 to 690VAC Ferrule fuse-links 22x8 am 0 to 690VAC Ferrule fuse-links 22x8 am 0 to 690VAC LOW VOLTAGE IEC FUSES IEC CYLINDRICAL FUSE-LINKS FEATURES & BENEFITS Reduced size Striker version available for remote indication

More information

NTC thermistors for inrush current limiting

NTC thermistors for inrush current limiting NTC thermistors for inrush current limiting Summary NTC thermistors for inrush current limiting, as all NTCs, are made of polycrystalline mixed oxide ceramics. They suppress high inrush current surges,

More information

Ferrule fuse-links 10x38 gg 400 to 690VAC

Ferrule fuse-links 10x38 gg 400 to 690VAC Ferrule fuse-links x8 gg 400 to 690VAC Ferrule fuse-links x8 gg 400 to 690VAC LOW VOLTAGE IEC FUSES IEC CYLINDRICAL FUSE-LINKS FEATURES & BENEFITS Reduced size Full range protection Visual indication of

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

SPXI SERIES IN-LINE SOLAR FUSE

SPXI SERIES IN-LINE SOLAR FUSE 00 Vdc.-0 A Description The Littelfuse SPXI solar fuse is designed to integrate into an in-line assembly within a wire harness. The fuse provides photovoltaic (PV) protection that meets UL - for photovoltaic

More information

S&C Scada-Mate Switching Systems Outdoor Distribution (14.4 kv through 34.5 kv)

S&C Scada-Mate Switching Systems Outdoor Distribution (14.4 kv through 34.5 kv) Outdo Distribution (14.4 kv through 34.5 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution switching system shall confm to the following specification. 1.02 The loadbreak

More information

ECNR/ECSR Class RK5 Dual-Element Time-Delay Fuses. Catalog Number ECNR (1-600A) 250Vac or Less Catalog Number ECSR (1-600A) 600Vac or Less

ECNR/ECSR Class RK5 Dual-Element Time-Delay Fuses. Catalog Number ECNR (1-600A) 250Vac or Less Catalog Number ECSR (1-600A) 600Vac or Less Catalog Number ECNR ( - 600A) 250Vac or Less Catalog Number ( - 600A) 600Vac or Less Amp Ratings ECNR 8 25 70 50 400 2 9 30 75 75 450 3 35 80 200 500 4 2 40 90 225 600 5 5 45 250 6 7.5 50 300 7 20 60 25

More information

R Rated Motor Fuses. DD mm. Dimensions - Standard. Dimensions - B bolt-in. Other Medium Voltage Products. Head Office

R Rated Motor Fuses. DD mm. Dimensions - Standard. Dimensions - B bolt-in. Other Medium Voltage Products. Head Office imensions - Standard.. max R Rated Motor Fuses.. max. 0mm imensions - B bolt-in.. max. X. Slots (. c.t.c.)..mm. max. mm. mm Front view. mm imensions - GE Tags imensions for GE tags are dictated by the

More information

COOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN

COOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN Sectionalizers Catalog Data CA270001EN Supersedes 270-15 May 2014 COOPER POWER SERIES Types GN3E and GN3VE electronically controlled, manually closed sectionalizers Description A sectionalizer is an automatic

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

3 Series Thumbwheel Switches

3 Series Thumbwheel Switches Features/Benefits Most complete product offering in the industry Spacers available to fit most panel cutouts Front or rear mounting options Illuminated models available Typical Applications Test & measurement

More information

L05065 LED Driver 150W, 24-60Vdc, mA L1M1MLT400S-150E

L05065 LED Driver 150W, 24-60Vdc, mA L1M1MLT400S-150E L05065 LED Driver 150W, 24-60Vdc, 700-4000mA L1M1MLT400S-150E Engineered for Best Fixture performance Fulham LumoSeries drivers are all built on core engineering design principles for exceptional standards

More information

Han PCB termination. Han-Fast Lock PCB adapter for Han DD PCB adapter for Han DDD module

Han PCB termination. Han-Fast Lock PCB adapter for Han DD PCB adapter for Han DDD module Han termination Contents Page Han-Fast Lock... 20.11 adapter for Han DD... 20.13 adapter for Han DDD module... 20.16 adapter for Han 40 A Axial module... 20.18 adapter for Han E... 20.20 adapter for Han

More information

For the State of Washington SMALL GENERATOR INTERCONNECTION REQUEST (Tier 1 [Non-Net Meter], Tier 2, Tier 3) (Application Form)

For the State of Washington SMALL GENERATOR INTERCONNECTION REQUEST (Tier 1 [Non-Net Meter], Tier 2, Tier 3) (Application Form) Electrical Company: PacifiCorp For the State of Washington SMALL GENERATOR INTERCONNECTION REQUEST (Tier 1 [Non-Net Meter], Tier 2, Tier 3) (Application Form) Designated Contact Person: Robin Moore Address

More information

Current Limiting Protector

Current Limiting Protector CLiP Current Limiting Protector For systems rated 2.8-38kV, and continuous currents through 5000A Arc Flash and Arc Blast Reduction Network Protection SCADA Adaptable Indoor or Outdoor Application Professional

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

Equipment Short-Circuit Current Rating and Available Fault Current

Equipment Short-Circuit Current Rating and Available Fault Current Equipment Short-Circuit Current Rating and Available Fault Current Dan Neeser Field Application Engineer Eaton s Bussmann Business Dan.Neeser@CooperIndustries.com Agenda Interrupting Rating & Series Rating

More information

CUS150M1 Instruction Manual

CUS150M1 Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before using this product. Incorrect usage could

More information

Magnetic Circuit Protectors 153. Multi-Pole Circuit Protectors 154. APL/UPL, 205/295 Barriers 155. Configurations 156. Operating Characteristics 158

Magnetic Circuit Protectors 153. Multi-Pole Circuit Protectors 154. APL/UPL, 205/295 Barriers 155. Configurations 156. Operating Characteristics 158 Magnetic Circuit Protectors 53 Multi-Pole Circuit Protectors 54 APL/UPL, 205/295 Barriers 55 Configurations 56 Operating Characteristics 58 Delay Curves 59 Specifications 64 APL/UPL Decision Tables 70

More information

Engineered for Best Fixture Performance. Product features

Engineered for Best Fixture Performance. Product features L1MLT082S-12E24 (L05020-1224825) LED Driver 12W, 3-20 Vdc, 600/825 ma L1MLT050S-12E40 (L05020-1240500) LED Driver 12W, 3-30 Vdc, 400/500 ma L1MLT070S-12E40 (L05020-1240700) LED Driver 12W, 3-34 Vdc, 350/700

More information

LED Driver 12W, 3-24 Vdc, 600/825 ma LED Driver 12W, 3-34 Vdc, 350/700 ma

LED Driver 12W, 3-24 Vdc, 600/825 ma LED Driver 12W, 3-34 Vdc, 350/700 ma 12W L1MLT082S-12E24 L1MLT070S-12E40 (L05020-1224825) (L05020-1240700) LED Driver 12W, 3-24 Vdc, 600/825 ma LED Driver 12W, 3-34 Vdc, 350/700 ma Engineered for Best Fixture Performance Fulham LumoSeries

More information

APL/UPL, 205/295 Series Magnetic Circuit Protectors

APL/UPL, 205/295 Series Magnetic Circuit Protectors APL/UPL, 205/295 APL/UPL, 205/295 Series Magnetic Circuit Protectors Introduction 68 Single & Multi-Pole 69 Barriers 7 Configurations 72 Operating Characteristics 74 Delay Curves 75 Specifications 80 Decision

More information

AE/CE Series Industrial Control Transformers

AE/CE Series Industrial Control Transformers 5 AE/E Series Industrial ontrol Transformers SETION TA AE/E SERIES SERIES OPEN ORE INDUSTRIAL & OIL INDUSTRIAL ONTROL ONTROL TRANSFORMERS The Acme Electric AE and E Series Industrial ontrol Transformers

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1 Power Supply, Primary Switch Mode, arrow Design -PS-100-240AC/24/1 POWER provides: Extra narrow widths of 22.5, 45, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide range input A high

More information

Engineered for Best Fixture Performance. Product features. Certificates and standards. 5 year warranty. Classifications. Engineered for Performance

Engineered for Best Fixture Performance. Product features. Certificates and standards. 5 year warranty. Classifications. Engineered for Performance L05021(E) LED Driver mains dimmable 12W, 3-32Vdc, 350/700mA L1E1230070S-12E(Z) L05021-40250 LED Driver mains dimmable 10W, 20-40Vdc, 200/250mA L1E1230025S-10E L05021-40300 LED Driver mains dimmable 12W,

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

Package (4) Control Logic (3)

Package (4) Control Logic (3) Features Regulated Converters 2:1 Voltage Range 1.6kV Isolation UL Certified Efficiency up to 88% Six-Sided Continuous Shield Fixed Operating Frequency Description The series / converters are certified

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

4:1 Wide Input Voltage Range 1.6kVDC Isolation UL Certified Efficiency up to 84% Fixed Operating Frequency Six-Sided Continuous Shield

4:1 Wide Input Voltage Range 1.6kVDC Isolation UL Certified Efficiency up to 84% Fixed Operating Frequency Six-Sided Continuous Shield Features Regulated Converters 4:1 Wide Voltage Range 1.6kV Isolation UL Certified Efficiency up to 84% Fixed Operating Frequency Six-Sided Continuous Shield Description The series wide input range / converters

More information

Central Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date

Central Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date Last Amended on 31.07.2015 Page 1 of 11 I. SWITCHGEAR EQUIPMENT 1. High Voltage switchgear & control gear and AB switches Ratings upto 1200 kv system Switching Impulse Voltage (Dry & Wet) Power Frequency

More information

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157 PRODUCT DA TA SLC 150 110 Expansion Unit Catalog Nos. 1745-151, - 152, - 153, - 154, - 156, -E157 7 : The EXpdnSiQn Unit The SLC 150 expansion unit can be used with either the SLC 150 processor unit or

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A POWER DISTRIBUTION JK Series Solid State Starters Medium Voltage 200-400-600-720A SOLID STATE STARTER JKSSS4+ Series The JKSSS Series of motor starter is the result of extensive research and development.

More information

Motor Controllers AC Semiconductor Motor Controller Type RSHR MIDI

Motor Controllers AC Semiconductor Motor Controller Type RSHR MIDI otor Controllers AC Semiconductor otor Controller Type RSHR IDI Soft starting and stopping of 3-phase induction squirrel cage motors 2-phase control with integral bypassing of semiconductors Low inrush

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

L LED Driver 40W, 60Vdc, 1050mA, Dimmable L1M1MLT105S-40E L ND LED Driver 40W, 60Vdc, 1050mA L1MLT105S-40E

L LED Driver 40W, 60Vdc, 1050mA, Dimmable L1M1MLT105S-40E L ND LED Driver 40W, 60Vdc, 1050mA L1MLT105S-40E L05049-601000 LED Driver 40W, 60Vdc, 1050mA, Dimmable L1M1MLT105S-40E L05049-601000-ND LED Driver 40W, 60Vdc, 1050mA L1MLT105S-40E Engineered for Best Fixture Performance Fulham LumoSeries drivers are

More information

Specifications. S&C Loadbuster Disconnect Switches Outdoor Distribution (14.4 kv through 34.5 kv)

Specifications. S&C Loadbuster Disconnect Switches Outdoor Distribution (14.4 kv through 34.5 kv) Outdoor Distribution ( kv through 34.5 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: INCLUSIONS: All

More information

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II Reclosers Form 4C Microprocessor-Based Recloser Control KME4-88-1 (120V) and KME4-88-2 (240V) Analog Current Metering Accessory Design II Service Information S280-77-6 961015, 961016 Figure 1. Kyle KME4-88

More information

Level 2, 3 and 4 Interconnection Application for Certified, Inverter Based Generating Facilities Not Greater than 2MW

Level 2, 3 and 4 Interconnection Application for Certified, Inverter Based Generating Facilities Not Greater than 2MW Level 2, 3 and 4 Interconnection Application for Certified, Inverter Based Generating Facilities Not Greater than 2MW The Customer Generator applicant ("Applicant") hereby makes application to the T &

More information

Technical specifications for 5 ka, normal-duty distribution 4.5 kv and 5

Technical specifications for 5 ka, normal-duty distribution 4.5 kv and 5 Surge Arresters Technical Data TD235028EN Supersedes January 2012 (TD-231) COOPER POWER SERIES Technical specifications for 5 ka, normal-duty distribution 4.5 kv and 5 kv VariSTAR Mov disks Ø32.7 ±0.28

More information

Motor Controllers AC Semiconductor Motor Controller Type RSHR MIDI

Motor Controllers AC Semiconductor Motor Controller Type RSHR MIDI otor Controllers AC Semiconductor otor Controller Type RSHR IDI Soft starting and stopping of 3-phase induction squirrel cage motors 2-phase control with integral bypassing of semiconductors Low inrush

More information

Dynamic Arc Flash Reduction System

Dynamic Arc Flash Reduction System www.usa.siemens.com/mcc Dynamic Arc Flash Reduction System and its application in motor control centers White Paper Author: Pablo Medina Product Manager, tiastar MCC Executive Summary The risk of Arc Flash

More information

4:1 Wide Input Voltage Range 1.6kVDC Isolation UL Certified Efficiency up to 88% Over Current and Over Voltage Protection No Minimum Load Required

4:1 Wide Input Voltage Range 1.6kVDC Isolation UL Certified Efficiency up to 88% Over Current and Over Voltage Protection No Minimum Load Required Features Regulated Converters 4:1 Wide Voltage Range 1.6kV Isolation UL Certified Efficiency up to 88% Over Current and Over Voltage Protection No Minimum Load Required Description The wide range input

More information

Medium Voltage Fuses. Medium Voltage Fuses 64. R Rated Medium Voltage Fuses E Rated Medium Voltage Fuses 69-73

Medium Voltage Fuses. Medium Voltage Fuses 64. R Rated Medium Voltage Fuses E Rated Medium Voltage Fuses 69-73 64 R Rated 65-68 Rated 69-73 Rated Potential Transformer Fuses 74 Live Parts 75 2,400-38,000 VAC General Information Current-limiting and R rated fuses are equipped with a mechanical indicator or striker

More information

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC The PCI Series Phase Angle Fired SCR Power Controls 25-1200 AMPS 120-600 VAC Precise power control for complex SCR applications. ROBICON 1996 Distributed Worldwide by www.mcgoff-bethune.com Applications

More information

9926 Series Branch Rated Circuit Breakers AC Version

9926 Series Branch Rated Circuit Breakers AC Version Branch Rated AC Version Hydraulic Magnetic Single pole and double pole versions 20/240 VAC, 50/60 Hz Up to 25A Just 3 mm wide Mounts on 35mm DIN-rail UL 489 listed, CSA C22.2 No. 5-02, CE VDE Ordering

More information

Electrical Plan Review

Electrical Plan Review Electrical Plan Review Overcurrent Protection and Devices, Short-Circuit Calculations, Component Protection, Selective Coordination, and Other Considerations Table of Contents Part I: Overcurrent Protection

More information

What is a Deadfront and Separable Arrester

What is a Deadfront and Separable Arrester What is a Deadfront and Separable Arrester ArresterFacts 025 What are Deadfront and Separable Arresters Photo ArresterWorks Separable Arrester sketch Courtesy Tyco Electronics Deadfront Arrester Photo

More information

Engineered for Best Fixture Performance. Product features. 5 year warranty. Certificates and standards. Classifications. Dimming L1M1MLT105S-20E

Engineered for Best Fixture Performance. Product features. 5 year warranty. Certificates and standards. Classifications. Dimming L1M1MLT105S-20E L05011i LED Driver 20W, 3 33Vdc, 350-1050mA L1M1MLT105S-20E Engineered for Best Fixture Performance Fulham LumoSeries drivers are all built on core engineering design principles for exceptional standards

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Solid State Relays Industrial, 1-Phase ZS (IO) w. LED Types RAM1A, RAM1B

Solid State Relays Industrial, 1-Phase ZS (IO) w. LED Types RAM1A, RAM1B Solid State Relays Industrial, 1-Phase ZS (IO) w. LED Types RAM1A, RAM1B Zero switching (RAM1A) or instant-on switching (RAM1B) AC Solid State Relay Direct copper bonding (DCB) technology LED indication

More information

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions Service Information S270-30-1 Figure 1. Kyle Type TVS Time-Voltage Sectionalizer. Contents 010032KM

More information

CROWN LINE Power Bus Bar Distribution System

CROWN LINE Power Bus Bar Distribution System COWN LINE Power Bus Bar Distribution System COWN LINE Power Bus Bar Distribution System The pluggable bus bar system Currents up to 300 Amps Up to 2 meters in length Pluggable breakers VDE finger proof

More information

Distinctive Characteristics

Distinctive Characteristics Distinctive Characteristics Full face, bright LED illumination in choice of red, green, and amber for visible status indication. 9-amp or 6-amp electrical capacity in compact body. Interior shield prevents

More information

General Purpose Transformers 6

General Purpose Transformers 6 General Purpose Transformers 6 Description Dry-type transformers (en cap su lat ed, ventilated or non-ventilated), 600 Volt Class, isolation type, single and three phase, through 500. Indoor and outdoor

More information

Electrical Components Catalog Universal MATE-N-LOK Connector System

Electrical Components Catalog Universal MATE-N-LOK Connector System Introduction Product Facts Pins and sockets can be intermixed in the same housing Positive polarization Rear cavity identification Contacts completely enclosed in housings Positive locking housings Insulation

More information

Micro Contactor MA Series

Micro Contactor MA Series Relay-sized contactor, making it the world s smallest >3mm contact clearance acc. to IEC 60335-1 for Safety Applications Reversing contactor with mechanical interlock 3 Pole and 1 Aux. Contact NO or NC

More information

24 Input/8 Output AC Block I/O Module

24 Input/8 Output AC Block I/O Module 4 Input/8 Output AC Module Cat. No. 79-4A8 Series B Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air to

More information