Medium Voltage Fuses. Medium Voltage Fuses 64. R Rated Medium Voltage Fuses E Rated Medium Voltage Fuses 69-73

Size: px
Start display at page:

Download "Medium Voltage Fuses. Medium Voltage Fuses 64. R Rated Medium Voltage Fuses E Rated Medium Voltage Fuses 69-73"

Transcription

1 64 R Rated Rated Rated Potential Transformer Fuses 74 Live Parts 75

2 2,400-38,000 VAC General Information Current-limiting and R rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of the fuse. This provides visual identification of a blown fuse and can be used as a trigger for external devices. Note: xtension distance 1 /2 min; extension force 2lb. min The terms Medium Voltage and High Voltage have been used interchangeably by many people to describe fuses operating above 600 volts. Technically speaking, medium voltage fuses are those intended for the voltage range from 2,400 to 38,000 VAC. High voltage fuses are for circuits carrying voltages greater than 38,000 VAC. rated fuses are considered to be general purpose fuses and can be used to protect against low and high values of fault current. R rated fuses are designed for back-up protection. They must be used in series with other devices such as motor overload relays in order to achieve both overload and short-circuit protection. Littelfuse now offers a complete selection of and R rated medium voltage fuses for the protection of trans formers, potential transformers, feeders, and motor circuits. Single, double, and triple barrel designs are available to cover a wide range of current, voltage, and interrupting ratings. Conventional ferrule type, clip lock, and bolt-in mounting configurations are now available for virtually any application. Hermetically sealed fuses for use in hazardous environments are also offered. Contact the factory or your local Littelfuse representative for additional fuse ratings or custom mounting configurations. Medium voltage fuses are not intended to provide overload protection in the same sense as fuses rated 600 volts or less. Medium voltage fuse current ratings do not have the same meanings as the ampere ratings of low voltage fuses. All medium voltage fuses are limited in their ability to interrupt low value overcurrents, especially those between 100% and 200% of the fuse s continuous current rating. They are designed to carry their rated current without exceeding the temperature rise permitted by NMA and ANSI standards. Additional application data can be found in the Fuse Application section of this catalog. 24 Hour mergency Service is available. Call Applications Power Transformer Protection Potential Transformer Protection Motor Controller Back-up Protection Fused Switches Feeder Circuits Bolt-in Mount Fuses 64

3 R Rated Features R rated fuses provide required short-circuit protection for medium voltage motors, motor controllers and associated circuitry. These components have limited ability to absorb the energy of large shortcircuit currents. Medium voltage motor controllers contain overload relays which provide both overload protection and locked rotor protection to the motor. The controllers are also intended to interrupt low value short-circuits within the capability of the motor controller. This protects the medium voltage fuse from sustained overcurrents which are less than their minimum interrupting rating. Characteristics Voltage Rating: Current Range: Options 2,400 volts 8,250 volts 2R 36R Hermitically sealed for use in hazardous locations (add S suffix to part number) Bolt-in mounting configurations NMA Standards for R rated medium voltage power fuses require they operate within seconds when subjected to an rms current 100 times the R rating. For example, a fuse with a 2R rating will open within 15 to 35 seconds on an applied current of 2 x 100 = 200 amperes. Part System 130-4R-1C-5.5 Max Voltage (KV) Style (C-Cartridge) No. of Barrels Rating (size) Continuous Current Hookeye Feature* * For hookeye attachment; add W suffix to part number 3"DIA 6.38" 9.75" Clip Center D DD DDD R Rated 2.75 KV Old Size Maximum Continuous 40 deg C. Dim. A Dim. B Min. Interrupting Rating RMS Amps Max Interrupting Rating RMS Asym 70-2R-1C-2.75 LCK 2R 2R 70 7" " , R-1C-2.75 LCK 3R 3R 100 7" " , R-1C-2.75 LCK 4R 4R 130 7" " , R-1C-2.75 LCK 5R 5R 150 7" " , R-1C-2.75 LCK 6R 6R 170 7" " , R-1C-2.75 LCK 9R 9R 200 7" " , R-1C-2.75 LCK 12R 12R 230 7" " , R-2C-2.75 LCK 18R 18R 390 7" " , R-2C-2.75 LCK 24R 24R 450 7" " ,000 2 Add w suffix to part number for hookeye attachment. 65

4 R Rated 3"DIA 6.38" 9.75" (Clip Center) R Rated 5.5 KV 5.5 KV 14 Clip Centers Old Size Maximum Continuous 40 Degrees C Dim. A Dim. B Min. Interrupting Rating RMS Amps Max Interrupting 70-2R-1C-5.5 LCL 2R 2R 70 12" " , R-1C-5.5 LCL 3R 3R " " , R-1C-5.5 LCL 4R 4R " " , R-1C-5.5 LCL 5R 5R " " , R-1C-5.5 LCL 6R 6R " " , R-1C-5.5 LCL 9R 9R " " , R-1C-5.5 LCL 12R 12R " " , R-2C-5.5 LCL 18R 18R " " , R-2C-5.5 LCL 24R 24R " " , R-2C R " " , R-2C R " " , R-2C R " " , R-2C R " " , R-3C R " " , R-3C R " " , R-3C-5.5 LCL 36R 36R " " , R-1C-5.5X 2R 70 14" " , R-1C-5.5X 3R " " , R-1C-5.5X 4R " " , R-1C-5.5X 5R " " , R-1C-5.5X 6R " " , R-1C-5.5X 9R " " , R-1C-5.5X 12R " " , R-2C-5.5X 18R " " , R-2C-5.5X 24R " " , R-2C-5.5X 30R ,000 5 R Rated 8.25 KV Old Size Maximum Continuous 40 Degrees C Dim. A Dim. B Min. Interrupting Rating RMS Amps Max Interrupting 70-2R-1C R 70 12" " , R-1C R " " , R-1C R " " , R-1C R " " , R-1C R " " , R-1C R " " , R-1C R " " , R-2C R " " , R-2C R " " ,000 5 Add w suffix to part number for hookeye attachment. 66

5 R Rated Littelfuse POWR-GARD medium voltage fuses are available in several bolt-in mounting configurations. Contact factory for custom configurations. B BI IB Bolt mount Bolt-In mount Inverted-Bolt mount Refer to illustrations for mounting dimensions. Indicator (2).34" X.660 Slots 1.38" Apart 3" Dia. Indicator Indicator 3" Dia. Indicator (2).34" Holes 1.38" Apart Bolt Mount B Inverted-Bolt IB R Rated 2.75 KV Bolt Mount B 2.75 KV Inverted Bolt IB Old Size Maximum Continuous Degrees C Dim. A Dim. B Min. Interrupting Max Interrupting Rating RMS Amps 70-2R-1B R " 13" , R-1B R " 13" , R-1B R " 13" , R-1B R " 13" , R-1B R " 13" , R-1B R " 13" , R-1B R " 13" , R-2B R " 13" , R-2B R " 13" , R-1IB R 70 13" , R-1IB R " , R-1IB R " , R-1IB R " , R-1IB R " , R-1IB R " , R-1IB R " , R-2IB R " , R-2IB R " ,

6 R Rated.44" X.91" Slots (1.53" c.t.c.) 3"Dia. Indicator Indicator Bolt-In Mount BI R Rated 5.5 KV Bolt In Mount BI 5.5 KV Bolt Mount B 5.5 KV Inverted Bolt IB 8.25 KV Bolt-In Mount BI Old Front View Size Maximum Continuous 40 C. Dim. A Dim. B Min. Interrupting Max Interrupting Rating RMS Amps 70-2R-1BI-5.5 2R " , R-1BI-5.5 3R " , R-1BI-5.5 4R " , R-1BI-5.5 5R " , R-1BI-5.5 6R " , R-1BI-5.5 9R " , R-1BI R " , R-2BI R " , R-2BI R " , R-2BI R " , R-2BI R " , R-2BI R " , R-2BI R " , R-3BI R " 80, R-3BI R " 80, R-3BI R " 80, R-3BI R " 80, R-1B-5.5 2R " , R-1B-5.5 3R " , R-1B-5.5 4R " , R-1B-5.5 5R " , R-1B-5.5 6R " , R-1B-5.5 9R " , R-1B R " , R-2B R " , R-2B R " , R-2B R " , R-2B R " , R-2B R " , R-1IB-5.5 2R 70 18" , R-1IB-5.5 3R " , R-1IB-5.5 4R " , R-1IB-5.5 5R " , R-1IB-5.5 6R " , R-1IB-5.5 9R " , R-1IB R " , R-2IB R " , R-2IB R " , R-2IB R " , R-2IB R " , R-2IB R " , R-1BI R " , R-1BI R " , R-1BI R " , R-1BI R " , R-1BI R " , R-1BI R " , R-1BI R " , R-2BI R " , R-2BI R " ,

7 Rated Rated fuses have time current characteristics designed to provide current-limiting protection for power transformers, potential transformers, power centers, feeder centers, and unit sub stations. When properly applied, they can protect against high and low fault currents. NMA Standards for rated medium voltage fuses require that fuses rated 100 or less open within 300 seconds (5 minutes) when subjected to an RMS value of % of the fuse continuous current rating; and fuses with an rating larger than 100 must open within 600 seconds (10 minutes) when subjected to an RMS current of % of the fuse s continuous current rating. These values establish one point on the time-current curve. Characteristics Voltage Rating: 2,400 volts 38,000 volts Current Range: Options Hermetically sealed for use in hazardous locations (add S suffix to part number) Clip-lock (CL) and bolt-in styles available. Application Note: Since these fuses are used for the protection of general purpose circuits which may contain transformers, motors, and other equipment producing in-rush and/or overload currents, fuses should generally be rated at 140% of the normal full load current, and circuits should be analyzed to ensure that system load currents will not exceed the current rating of the fuse. (Clip Center) 3"DIA 6.38" 9.75" Rated Old Size Dim. A Dim. B Max Interrupting 2.75 Max. KV 10-1C-2.75 LCX " " 80, C " " 80, C " " 80, C " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C " " 80, C " " 80, C " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C " " 80, C-2.75 LCX " " 80, C-2.75 LCX " " 80, C " " 80, C-2.75 LCX " " 80, C " " 80,

8 Rated Rated Old Size Dim. A Dim. B Max Interrupting Diagram 10-1C " " 80, C " " 80, C " " 80, C " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C " " 80, C " " 80, C " " 80, C " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C-5.5 LCY " " 80, C " " 80, C " " 80, C " " 80, Max. KV 5.5 Max. KV 5NL " 80, NL " 80, NL " 80, NL " 80, NL-30 LCU " 80, NL-40 LCU " 80, NL-50 LCU " 80, NL-65 LCU " 80, NL-80 LCU " 80, NL-100 LCU " 80, NL-125 LCU " 80, NL-150 LCU " 80, NL-175 LCU " 80, NL-200 LCU " 80, NL " 80, NL2-250 LCU " 80, NL2-300 LCU " 80, NL2-350 LCU " 80, NL2-400 LCU " 80, NL2-450 LCU " 80,

9 Rated Rated Old Size Dim. A Dim. B Max Interrupting Diagram 10-1C " " 80,000, C " " 80, C " " 80, C " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ " " 80, C-8.25 LDZ 350Z " " 80, C " " 80, Max. KV 8.25 Max. KV 8NL " " 80, NL " " 80, NL " " 80, NL " " 80, NL-30 LCZ " " 80, NL-40 LCZ " " 80, NL-50 LCZ " " 80, NL-65 LCZ " " 80, NL-80 LCZ " " 80, NL-100 LCZ " " 80, NL2-100 LCZ " " 80, NL2-125 LCZ " " 80, NL2-150 LCZ " " 80, NL2-200 LCZ " " 80, NL " " 80, Rated Old Size Dim. A Dim. B Max Interrupting 10-1C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C " " 80, C " " 80, C " " 80, C " " 80, C-15.5 LDN " " 80, C-15.5 LDN " " 80, C " " 80, C " " 80, C " " 80, C " " 80, Max. KV 71

10 Rated Rated Old Size Dim. A Dim. B Max Interrupting 15GS " " 60, GS " " 60, GS " " 60, GS " " 60, GS " " 60, GS " " 60, GS " " 60, Max. KV 15.5 Max. KV 15NL " " 60, NL " " 60, NL " " 60, NL " " 60, NL-30 LCN " " 60, NL-40 LCN " " 60, NL-50 LCN " " 60, NL-65 LCN " " 60, NL-80 LCN 80S 80 20" " 60, NL-100 LCN 100S " " 60, NL2-80 LCN " " 60, NL2-100 LCN " " 60, NL2-125 LCN 125X " " 60, NL2-150 LCN " " 60, NL " " 60, NL2-200 LCN 200D " " 60, NL " " 60, NL " " 60, NL " " 60, NL " " 60, Rated Old Size Dim. A Dim. B Max Interrupting 15-1C " " 40, C " " 40, C " " 40, C " " 40, C " " 40, C " " 40, C " " 40, C " " 40, C " " 40, Max. KV Rated Old Size Dim. A Dim. B Max Interrupting 3-1C " " 20, C " " 20, C " " 20, C " " 20, C " " 20, C " " 20, C " " 20, C " " 20, C " " 20, C " " 20, C " " 20, Max. KV 72

11 Rated Clip Lock Design The clip lock type designs ensures a positive contact between the fuse and the connection cam. The fuse s clip lock tab slides in between the clip casting and the cam to prevent the fuse from slipping or blowing out of the holder. This positive contact improves heat dissipation and allows fuses to run cooler. Rated Old Size Dim. A Dim. B Max Interrupting 10-1CL " 15.13" 80, CL " 15.13" 80, C " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 15.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, Max. KV Clip Lock Rated Old Size Dim. A Dim. B Max Interrupting 10-1CL " 16.13" 80, CL " 16.13" 80, C " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, CL " 16.13" 80, Max. KV Clip Lock Rated Old Size Dim. A Dim. B Max Interrupting 10-1CL " 18.1" 60, CL " 18.1" 60, CL " 18.1" 60, CL " 18.1" 60, CL " 18.1" 60, CL " 18.1" 60, CL " 18.1" 60, CL " 21.13" 60, CL " 21.13" 60, CL " 21.13" 60, CL " 19.1" 60, CL " 19.1" 60, CL " 19.1" 60, CL " 19.1" 60, CL " 19.1" 60, CL " 19.1" 60, CL " 19.1" 60, Max. KV Clip Lock A B

12 Rated Potential Transformer Fuses Potential Transformer (PT) fuses are current-limiting fuses with high interrupting ratings designed for the protection of potential transformers. Application Note: When applying fuses for the protection of transformers, the magnetizing current in-rush must be considered. The characteristics of the in-rush, which can be matched with a fuse time-current curve, should be available from the transformer manufacturer. Characteristics Voltage Rating: 600VAC 25,500 VAC Current Range: 1/2 10 B A Rated Old Size Length Dim. A Diameter Dim. B Max Interrupting Rating RMS (Sym) 3-4PT , PT , PT , PT , Volt 2.75 Max. kv 2.75 Max.KV 500-4PT-2.4 1/ , PT-2.4 LCD , PT-2.4 LCD , PT , PT , PT , PT , PT , PT , Max. kv 5.5 Max. kv 8.25 Max. kv 15.5 Max. kv 25.8 Max. kv 1-5PT-4.8 LC , PT-4.8 LC ,000 1/2-6PT-5.5 1/ , PT , PT , PT , PT ,000 1/2-8PT-5.5 LCQ.5 1/ , PT-5.5 LCQ , PT-5.5 LCQ , PT-5.5 LCQ , PT-5.5 LCQ , PT-5.5 LCQ ,000 1/2-8PT / , PT , PT , PT ,000 1/2-11PT-15.5 LCT.5 1/ , PT-15.5 LCT , PT-15.5 LCT , PT-15.5 LCT , PT , PT ,000 1/2-16PT-25.5 LCJ 1-4 1/ , PT-25.5 LCJ ,500 74

13 Live Parts Live parts are available for mounting, R, and PT single, double, and triple barrel fuses. Mounting clips are available for ferrule type and clip lock style fuses. All clips are sold in pairs. Contact factory for additional live parts. Part : * System : Z For use with 1-9 / 16" to 1-5 /8 (1.625 ) diameter PT fuses. Part : * System : Z For use with 3" diameter fuses Part : * System : Z For use with all 13 / 16" (.8125 ) diameter PT fuses..08 Part : * System : Z For use with all 3" diameter fuses " HOLS Part : CL* System : ZXCL Clip Lock Design (For CL-14) Mounting Details for Clip Lock 3.63 TRIPL BARRL 3.63 DOUBL BARRL Bottom Lever In Closed Position * One Pair. Dimensions for reference only. Blown Fuse Indicator TOP VIW Top Lever in Open Position SINGL BARRL 1.00 A Dia. (2) Holes For Mounting Cable/Bus.44 DIA. (2) HOLS 75

MEDIUM VOLTAGE FUSES. POWR-GARD Fuse Datasheet. 2,400-38,000 VAC Current-Limiting

MEDIUM VOLTAGE FUSES. POWR-GARD Fuse Datasheet. 2,400-38,000 VAC Current-Limiting MEDIUM VOLTAGE FUSES 2,400-38,000 VAC Current-Limiting Current-limiting E- and R-rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of

More information

Section Overview. Table of Contents

Section Overview. Table of Contents Section Overview Littelfuse is your source for a fast replacement of - and R-rated medium voltage fuses. Our emergency service gets you the fuses you need quickly to minimize downtime of your critical

More information

JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B. R-Rated Fuses For Motor Circuit Protection Medium Voltage.

JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B. R-Rated Fuses For Motor Circuit Protection Medium Voltage. R-Rated medium voltage fuses are back-up current limiting fuses used in conjunction with medium voltage motors and motor controllers. The JCK-A, JCL-A, & JCR-A are supplied with Cutler- Hammer Ampgard

More information

ECNR/ECSR Class RK5 Dual-Element Time-Delay Fuses. Catalog Number ECNR (1-600A) 250Vac or Less Catalog Number ECSR (1-600A) 600Vac or Less

ECNR/ECSR Class RK5 Dual-Element Time-Delay Fuses. Catalog Number ECNR (1-600A) 250Vac or Less Catalog Number ECSR (1-600A) 600Vac or Less Catalog Number ECNR ( - 600A) 250Vac or Less Catalog Number ( - 600A) 600Vac or Less Amp Ratings ECNR 8 25 70 50 400 2 9 30 75 75 450 3 35 80 200 500 4 2 40 90 225 600 5 5 45 250 6 7.5 50 300 7 20 60 25

More information

TRADITIONAL HIGH-SPEED FUSES

TRADITIONAL HIGH-SPEED FUSES TRDITIONL HIGH-SPEED FUSES 10/20/00/600/700 Vac Very Fast-cting 1-1200 Ordering Information s L1S: 10 Vac/dc (1 60 ) 10 Vac (70 1000 ) 100 Vdc (70 1000 ) L2S: 20 Vac/dc (1 200 ) 20 Vac (22 800 ) 200 Vdc

More information

R Rated Motor Fuses. DD mm. Dimensions - Standard. Dimensions - B bolt-in. Other Medium Voltage Products. Head Office

R Rated Motor Fuses. DD mm. Dimensions - Standard. Dimensions - B bolt-in. Other Medium Voltage Products. Head Office imensions - Standard.. max R Rated Motor Fuses.. max. 0mm imensions - B bolt-in.. max. X. Slots (. c.t.c.)..mm. max. mm. mm Front view. mm imensions - GE Tags imensions for GE tags are dictated by the

More information

10 SEC TIME DELAY (AT 500 PERCENT RATED LOAD), DUAL ELEMENT

10 SEC TIME DELAY (AT 500 PERCENT RATED LOAD), DUAL ELEMENT 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 AllenWatson@elliottelectric.com Catalog Number Manufacturer Description Weight per unit Product Category Features Characteristics

More information

L50QS SERIES HIGH-SPEED ROUND BODY FUSES

L50QS SERIES HIGH-SPEED ROUND BODY FUSES 00 Vac/dc -0 A Traditional Round Body Bolted Style HF Specifications Voltage Rating Amperage Rating Interrupting Rating Time Constant Material Approvals Environmental Country of Origin AC: 00V DC: 00V

More information

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0 170 ADM 850 10 10 to 60 VDC Module Base / 170 ADO 830 30 6 Pt. Relay Out Module Base Version 1.0 31005197 00 Safety Information NOTICE Read these instructions carefully, and look at the equipment to become

More information

Installation Instructions

Installation Instructions Installation Instructions (1771-ODD Series B) Use this document as a guide when installing the catalog number 1771-ODD series B output module. The ac isolated output module is shipped in static-shielded

More information

TeSys IEC Contactors and Overload Relays

TeSys IEC Contactors and Overload Relays TeSys IEC Contactors and Overload Relays Making High-Fault Short-Circuit Current Ratings Simple Schneider Electric is an industry leader in IEC contactors and overload relays, and is recognized as the

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Ferrule fuse-links 10x38 gg 400 to 690VAC

Ferrule fuse-links 10x38 gg 400 to 690VAC Ferrule fuse-links x8 gg 400 to 690VAC Ferrule fuse-links x8 gg 400 to 690VAC LOW VOLTAGE IEC FUSES IEC CYLINDRICAL FUSE-LINKS FEATURES & BENEFITS Reduced size Full range protection Visual indication of

More information

AMP-TRAP Form 101 A15QS

AMP-TRAP Form 101 A15QS AMP-TRAP Form 0 AQS SEMICONUCTOR PROTECTION FUSES AQS Amp-trap Form 0 Semiconductor Protection fuses were designed for the specific protection of diodes and other semiconductor devices rated VAC/C. The

More information

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY The BE1-51 Series of Time Overcurrent Relays is microprocessor-based to provide versatile overload and fault protection on 50Hz or 60Hz systems. ADVANTAGES

More information

FLQ SERIES MIDGET (10x38mm) FUSES

FLQ SERIES MIDGET (10x38mm) FUSES 500 Vac Time-Delay 1 / 10-30 A Description The FLQ series 500 Vac time-delay fuses provide excellent supplemental protection of control power transformers, solenoids, and circuits with high inrush currents.

More information

ELSP current-limiting backup fuse

ELSP current-limiting backup fuse Catalog Data CA132013EN Supersedes TD132002EN October 2014 COOPER POWER SERIES current-limiting backup fuse General Eaton offers its Cooper Power series current-limiting backup fuse that is used in series

More information

Ferrule fuse-links 14x51 am 500 to 690VAC

Ferrule fuse-links 14x51 am 500 to 690VAC Ferrule fuse-links 4x am 0 to 690VAC Ferrule fuse-links 4x am 0 to 690VAC LOW VOLTAGE IEC FUSES IEC CYLINDRICAL FUSE-LINKS FEATURES & BENEFITS Reduced size Striker version available for remote indication

More information

Ferrule fuse-links 22x58 am 500 to 690VAC

Ferrule fuse-links 22x58 am 500 to 690VAC Ferrule fuse-links 22x8 am 0 to 690VAC Ferrule fuse-links 22x8 am 0 to 690VAC LOW VOLTAGE IEC FUSES IEC CYLINDRICAL FUSE-LINKS FEATURES & BENEFITS Reduced size Striker version available for remote indication

More information

H704-42(H)(E), H704-42/1(H)(E)

H704-42(H)(E), H704-42/1(H)(E) POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (

More information

Metering Devices IQ 300

Metering Devices IQ 300 Effective: May 2001 Page 1 New Information Contents Description Page General Description......... 2 Specifications.............. 3 Field Wiring Connections.... 4 Page 2 Effective: May 2001 Applications

More information

MOUNTING BASE AQB-A402 PLAN VIEW OF MOUNTING BLOCK & CIRCUIT BREAKER AQB-A802 CIRCUIT BREAKER MOUNTING BLOCK 2.50 MOTOR OPERATOR 25.

MOUNTING BASE AQB-A402 PLAN VIEW OF MOUNTING BLOCK & CIRCUIT BREAKER AQB-A802 CIRCUIT BREAKER MOUNTING BLOCK 2.50 MOTOR OPERATOR 25. Weights & Dimensions 4 1/8 4 5/16 4 1/8 4 5/16 Weights & Dimensions 5 1/16 6 1/2 15 1/2 17 15/16 A C A C 6 3/16 MOUNTING ASE MOUNTING ASE 5 1/16 6 3/16 MOUNTING ASE DIMENSIONS DESCRIPTION A C SINGLE ASE,

More information

Protistor size 2x72 and 2x73 ar 550 to 1250VAC (IEC)

Protistor size 2x72 and 2x73 ar 550 to 1250VAC (IEC) Protistor size 2x72 and 2x73 ar SEMICONDUCTOR PROTECTION FUSES SQUARE BODY HIGH-SPEED FUSE-LINKS AC PROTECTION FEATURES & BENEFITS Multiple body sizes and terminals or blades combination ar Class according

More information

Figure 1. ELSP Current-Limiting Backup Fuse. INSTALLATION

Figure 1. ELSP Current-Limiting Backup Fuse. INSTALLATION Fusing Equipment Current-Limiting Backup Fuse Electrical Apparatus - GENERAL The Cooper Power Systems Current-limiting Backup Fuse is used in series with low current primary protection devices such as

More information

Voltage Dip-Proofing Inverter

Voltage Dip-Proofing Inverter Voltage Dip-Proofing Inverter DPI54S / 54L Series Models 120V & 208/230 50/60Hz Contents: Introduction...3 Theory of operation...3 Specifications...5 Up-time considerations...6 Installation Guide...7 Test

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options

More information

Cert.Record No _0_000, Class No , DQD No 557 Rev SUPPLEMENTARY PROTECTORS COMPONENT ACCEPTANCE PROGRAM

Cert.Record No _0_000, Class No , DQD No 557 Rev SUPPLEMENTARY PROTECTORS COMPONENT ACCEPTANCE PROGRAM Seite 1 von 6 ACCEPTANCE RECORD File No: Class No: 016186_0_000 321530 SUPPLEMENTARY PROTECTORS COMPONENT ACCEPTANCE PROGRAM SUBMITTOR 4544043 E-T-A Circuit Breakers Limited 100 Leek Cr, Unit 11 Richmond

More information

Functional configuration Rated input voltage Power ratings Output voltage Output current Part number Non-PFC

Functional configuration Rated input voltage Power ratings Output voltage Output current Part number Non-PFC Switching Power Supply DIN-Rail Mount Power Supply With Capacity Up to 240 W for General or Industrial Applications Wide power range: 15 to 240 W 15 W and PFC Models with Universal voltage of 100 to 230

More information

ELSP current-limiting backup fuse

ELSP current-limiting backup fuse Supersedes May 2018 COOPER POWER SERIES General Eaton offers its Cooper Power series current-limiting backup fuse that is used in series with low current primary protection devices such as a Bay-O-Net

More information

COOPER POWER SERIES. Fusing Equipment Catalog Data CA132064EN. Effective February 2018 Supersedes January 2014 (240-50)

COOPER POWER SERIES. Fusing Equipment Catalog Data CA132064EN. Effective February 2018 Supersedes January 2014 (240-50) Fusing Equipment Catalog Data CA132064EN Supersedes January 2014 (240-50) COOPER POWER SERIES Table of contents Attention....3 Eaton is in the process of updating part numbers and technical data due to

More information

WMS SUPPLEMENTARY PROTECTORS

WMS SUPPLEMENTARY PROTECTORS WMS Supplementary Protectors Overview WMS SUPPLEMENTARY PROTECTORS Product Specification The WMS Supplementary Protector is a dual-rated product for both AC and DC supplies, in accordance with UL 1077

More information

Sensing and Control the Interactive Catalog.

Sensing and Control the Interactive Catalog. Interactive Catalog Supplements Catalog PDFs If you need detailed product information, or help choosing the right product for your application, see our Interactive Catalog Use the Interactive Catalog to

More information

K-Line Mini - Contactors, Overload Relays and Accessories

K-Line Mini - Contactors, Overload Relays and Accessories K-Line Mini - Contactors, Overload Relays and Accessories Class 8502 CONTENTS Description...................................................... Page General Information...............................................

More information

high RESISTANCE STOPLIGHT Instruction Manual C-101EM

high RESISTANCE STOPLIGHT Instruction Manual C-101EM stoplight high RESISTANCE GROUNDING SYSTEM STOPLIGHT Instruction Manual C-101EM high resistance grounding protection The StopLight system uses a unique indicator light system to provide visual detection

More information

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The

More information

Digital I/O Modules. Installation Instructions. (Catalog Number 1746 Series)

Digital I/O Modules. Installation Instructions. (Catalog Number 1746 Series) Installation Instructions Digital I/O Modules (Catalog Number 1746 Series) Input Module Catalog Numbers: 1746-IA4, -IA8, -IA16, -IB8, -IB16, -IC16, -IG16, -IH16, -IM4, -IM8, -IM16, -IN16, -ITB16, -ITV16,

More information

PGM-8325 MANUAL NEUTRAL GROUNDING MONITOR

PGM-8325 MANUAL NEUTRAL GROUNDING MONITOR POWR-GARD Supplemental Monitoring PGM-8325 SERIES Neutral Grounding Monitor PGM-8325 MANUAL NEUTRAL GROUNDING MONITOR JULY 2, 2009 REVISION 10 F 1 CT1 CT2 A B L1 L2 GROUND FAULT 1.0 RESET RESISTOR FAULT

More information

209/219/229 Multi-Pole Circuit Protectors 202 branch circuit applications such as EDP, air conditioners, panel boards

209/219/229 Multi-Pole Circuit Protectors 202 branch circuit applications such as EDP, air conditioners, panel boards The 29, E-Frame circuit breaker combines power switching with accurate, reliable circuit protection 29/29/229 Magnetic Circuit Protectors 99 in a compact single or multipole 249 Power Selector Breaker

More information

170 ADI VDC - 16 Pt. Discrete Input Module Base

170 ADI VDC - 16 Pt. Discrete Input Module Base 24 VDC - 16 Pt. Discrete Input Module Base 11 At a Glance Purpose This chapter describes the 170 ADI 340 00 TSX Momentum I/O base. In This Chapter This chapter contains the following sections: For This

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North

More information

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors B Curve NC100H Supplementary Protectors Rating 1P 2P 3P 4P 80 MG27164 MG27175 MG27186 MG27197 MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors C Curve NC100H Supplementary Protectors

More information

Voltage Dip-Proofing Inverter

Voltage Dip-Proofing Inverter Voltage Dip-Proofing Inverter DPI53S / 54L Series Models 120V & 208/230 50/60Hz LEADERS IN VOLTAGE DIP-PROOFING Contents: Introduction...3 Theory of operation...3 Specifications...5 Up-time considerations...6

More information

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A POWER DISTRIBUTION JK Series Solid State Starters Medium Voltage 200-400-600-720A SOLID STATE STARTER JKSSS4+ Series The JKSSS Series of motor starter is the result of extensive research and development.

More information

TOKISTAR LIGHTING INSTRUCTION MANUAL 24 VDC or 24 VAC

TOKISTAR LIGHTING INSTRUCTION MANUAL 24 VDC or 24 VAC TokiLux TM Series TOKISTAR LIGHTING INSTRUCTION MANUAL 24 VDC or 24 VAC General Description Tokistar's TokiLux Series may be operated at 24 VDC or 24 VAC. Light Bars are installed end-to-end within the

More information

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime

More information

Specifications. S&C Regulator Bypass Switches Type XL (Sequenced) and Type NL (Nonsequenced) Outdoor Distribution (14.

Specifications. S&C Regulator Bypass Switches Type XL (Sequenced) and Type NL (Nonsequenced) Outdoor Distribution (14. Type XL (Sequenced) and Type NL (Nonsequenced) Outdoor Distribution (14.4 kv and 25 kv) Specifications Conditions of Sale STANDARD: The seller s standard conditions of sale set forth in Price Sheet 150

More information

Han PCB termination. Han-Fast Lock PCB adapter for Han DD PCB adapter for Han DDD module

Han PCB termination. Han-Fast Lock PCB adapter for Han DD PCB adapter for Han DDD module Han termination Contents Page Han-Fast Lock... 20.11 adapter for Han DD... 20.13 adapter for Han DDD module... 20.16 adapter for Han 40 A Axial module... 20.18 adapter for Han E... 20.20 adapter for Han

More information

Miniature Circuit Breakers and Supplementary Protectors. Contents

Miniature Circuit Breakers and Supplementary Protectors. Contents . Optimum and Efficient Protection for Every Application Product Overview Features Optimum product quality, tested reliability and safety stand for best protection of personnel, installations and plant.

More information

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv) Outdo Distribution (15.5 kv and 27 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault interrupting system shall confm to the following specification. 1.02 The

More information

170 ADO VDC - 32 Pt. Discrete Output Module Base

170 ADO VDC - 32 Pt. Discrete Output Module Base 31001697 9/2010 170 ADO 350 00 24 VDC - 32 Pt. Discrete Output Module Base 27 Overview This chapter describes the 170 ADO 350 00 TSX Momentum I/O base. What's in this Chapter? This chapter contains the

More information

MINI-BEAM SM2A312CV and SM2A312CV2

MINI-BEAM SM2A312CV and SM2A312CV2 MINI-BAM M2A312CV and M2A312CV2 elf-contained AC-operated ensors Compact, modulated, self-contained convergent mode sensors for 24-24V ac operation Produces a precise 1.3 mm (.5 in) diameter sensing spot

More information

Installation Instructions

Installation Instructions Installation Instructions This document provides information on: important pre-installation considerations power supply requirements installing the module connecting the wiring using the indicators for

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 9 DIN Rail Miniature Circuit Breakers Product Overview................................................ Product Selection................................................ Accessories.....................................................

More information

NH fuse-links gg VAC with striker size 0, 1, 2, 3, 4

NH fuse-links gg VAC with striker size 0, 1, 2, 3, 4 NH fuse-links gg - 690VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions according to DIN 43 620 Parts 1 to 4 Lead free contact blades 0% cadmium APPLICATIONS gg: General purpose

More information

8 Submersible Motors Standard

8 Submersible Motors Standard Applications These motors are built for dependable operation in vertical 8 diameter or larger water wells. Basic Features Double Flanged NEMA mounting design Stainless steel splined shaft StatorShield

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 489 DIN Rail Miniature Circuit Breakers Product Overview................................................ 2 Product Selection................................................ 4 Accessories.....................................................

More information

NETRONICS HS3500 CONTROLLER

NETRONICS HS3500 CONTROLLER NETRONICS HS3500 CONTROLLER CUSTOMER NAME CONTROLLER SERIAL # CONTROLLER PART # PERSONALITY SWITCH SETTINGS BULLET PRESS CONFIGURATION DELIVERY DATE Contact the factory for help setting up your application.

More information

4. CIRCUIT BREAKERS. Functional Emergency Switching

4. CIRCUIT BREAKERS. Functional Emergency Switching 4. CIRCUIT BREAKERS The circuit breaker/disconnector fulfils all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist. As shown in table H2-19 the circuit

More information

PG Softstarter Installation Manual for 5A, 9A and 16A Controllers

PG Softstarter Installation Manual for 5A, 9A and 16A Controllers PG Softstarter Installation Manual for 5A, 9A and 16A Controllers Important User Information The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many

More information

IELR Series

IELR Series IELR Series Rail-Mount Magnetic Circuit Protectors Introduction Poles Specifications Operating Characteristics Delay Curves Approvals Decision Tables 6 62 63 64 65 69 70 IELR Series Rail-Mount Hydraulic

More information

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP) Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units Reference Number SPS 30 - (RIC Standard: SC 09 10 07 00 SP)

More information

User Manual. JS-ICON 624 PACK Portable Dimmer Pack. JOHNSON SYSTEMS INC. Spring

User Manual. JS-ICON 624 PACK Portable Dimmer Pack. JOHNSON SYSTEMS INC. Spring User Manual JS-ICON 624 PACK Portable Dimmer Pack JOHNSON SYSTEMS INC. Spring 2007 Table of Contents JS-ICON 624 DMX JS-ICON 624 CC 6-2.4kW Dimming Strip JS-ICON 624 ND 6-2.4kW Relay Strip Introduction...3

More information

Distributed Power System SA3100 Drive Configuration and Programming

Distributed Power System SA3100 Drive Configuration and Programming Distributed Power System SA3100 Drive Configuration and Programming Instruction Manual S-3056-1 Throughout this manual, the following notes are used to alert you to safety considerations:! ATTENTION: Identifies

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) DNP Points List and Implementation Table of Contents Section Page Section Page Introduction...1 Status Points...2

More information

Discrete Output Modules IC697MDL740

Discrete Output Modules IC697MDL740 55 1 IC697MDL740 (IC697MDL740) datasheet Features 16 Points - Four isolated groups of 4 points each 2 amp capacity per point High inrush capacity (10x rated current) Functions The 24/48 Volt DC 2 Amp Output

More information

CERTIFIED TEST REPORT

CERTIFIED TEST REPORT CP No.: CP1120 Rev. 1 Page: 1 of 24 CERTIFIED TEST REPORT Cooper Power Systems 15 kv Class 600 Amp CLĒĒR TM LOADBREAK SEPARABLE CONNECTOR SYSTEM REV. 1 DATE September 1, 2011 ORIGINAL REPORT DATE: July

More information

802B Compact, Precision and Small Precision

802B Compact, Precision and Small Precision 02B Compact, Precision and Small Precision Compact Precision Small Precision Description Bulletin 02B consists of different body styles: compact, precision and small precision. Each style has been designed

More information

EDR-3000 Eaton Distribution Relay

EDR-3000 Eaton Distribution Relay EDR-3000 Eaton Distribution Relay Technical Data New Information Description Page 1. General Description.......................... 2 2. Applications............................... 2 3. Drilling Pattern.............................

More information

Supplement to Instruction Manual

Supplement to Instruction Manual Supplement to Instruction Manual Compact Inverter 0 V series: FRN0001 to 00C2S-2U 400 V series: FRN0002 to 0011C2S-4U Single-phase 0 V series: FRN0001 to 0012C2S-7U Thank you for purchasing our FRENIC-Mini

More information

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions Service Information S270-30-1 Figure 1. Kyle Type TVS Time-Voltage Sectionalizer. Contents 010032KM

More information

Spring Test 5 due 4/26/2013

Spring Test 5 due 4/26/2013 Spring Test 5 due 4/26/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Where fixed multioutlet assemblies are employed, each feet or fraction thereof

More information

Instruction Manual HPH-8

Instruction Manual HPH-8 Specifications HPH-8 Trigger cable 120-volt, Nema 1-15 Main Power 50-amps @ 240-volt AC Power receptacles (4) Nema 5-15 or 6-15 Maximum HID wattage 8000 watts (on 240-volt) 4800 watts (on 120-volt) Maximum

More information

60103 Circuit Breaker

60103 Circuit Breaker 6003 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Circuit Breaker Type: Standard

More information

Switching Power Supply S8E1. Ordering Information. Compact and Economical Switching Power Supply

Switching Power Supply S8E1. Ordering Information. Compact and Economical Switching Power Supply Switching Power Supply Compact and Economical Switching Power Supply Models range from 10 to 50 W Open-frame and covered types Wide range of output voltage: 5-, 12-, 15- and 24-V models UL, CSA approved

More information

RAIN BIRD RC-4Bi, RC-7Bi, RC-1260Bi SERIES INSTRUCTION MANUAL

RAIN BIRD RC-4Bi, RC-7Bi, RC-1260Bi SERIES INSTRUCTION MANUAL RAIN BIRD RC-4Bi, RC-7Bi, RC-1260Bi SERIES INSTRUCTION MANUAL DESCRIPTION OF CONTROLS Refer to Figure 1 Figure 1 A. HOUR DIAL with 23 CYCLE START PINS The HOUR dial contains 23 pins for rescheduling automatic

More information

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS MAINTENANCE MANUAL EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS SPECIFICATIONS*... 2 INTRODUCTION... 3 DESCRIPTION...

More information

ICS Regent. AC Guarded Digital Output Module 110 VAC (T3464) PD-6021

ICS Regent. AC Guarded Digital Output Module 110 VAC (T3464) PD-6021 ICS Regent PD-6021 AC Guarded Digital Output Module 110 VAC (T3464) Issue 1, March, 06 AC Guarded digital output modules provide guarded switching of user-supplied 110 AC voltages to a maximum of sixteen

More information

IC693PWR331 High Capacity Power Supply, 24 VDC Input

IC693PWR331 High Capacity Power Supply, 24 VDC Input IC693PWR331 High Capacity Power Supply, 24 VDC Input The Series 90-30 DC input High Capacity power supply (IC693PWR33) is a 30 watt wide range supply designed for 24 VDC nominal inputs. For applications

More information

S66 Series Electronic Fan Speed Control

S66 Series Electronic Fan Speed Control FANs 121, 125, 1628.3 Product/Technical Bulletin S66 Issue Date 0918 S66 Series Electronic Fan Speed Control The S66 Series Electronic Fan Speed Control is designed to modulate the speed of single-phase,

More information

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD Molded Case Circuit Section Tri-Break Line Integrally Fused Thermal Magnetic Circuit Integrally Fused Magnetic Circuit Integrally Fused Molded Case Switches These breakers are available in three types.

More information

1.3. Miniature Circuit Breakers and Supplementary Protectors. Contents. WMZS Circuit Breaker. UL 1077 DIN Rail Supplementary Protectors

1.3. Miniature Circuit Breakers and Supplementary Protectors. Contents. WMZS Circuit Breaker. UL 1077 DIN Rail Supplementary Protectors . Miniature Circuit Breakers and Supplementary Protectors UL 077 DIN Rail Supplementary Protectors WMZS Circuit Breakers Contents Description WMZS Circuit Breaker Standards and Certifications................

More information

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL

More information

IELR Rail-Mount Series Magnetic Circuit Protectors

IELR Rail-Mount Series Magnetic Circuit Protectors IELR Rail-Mount IELR Rail-Mount Series Magnetic Circuit Protectors Introduction 92 Single Pole 93 Specifications 94 Operating Characteristics 95 Delay Curves 96 Approvals & Decision Tables 200 IELR Series

More information

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC The PCI Series Phase Angle Fired SCR Power Controls 25-1200 AMPS 120-600 VAC Precise power control for complex SCR applications. ROBICON 1996 Distributed Worldwide by www.mcgoff-bethune.com Applications

More information

SECTION 12. Miscellaneous. AEMC Electro Industries EMM, Inc. Graphic Controls Osaki Yokogawa (YCA) Woertz

SECTION 12. Miscellaneous. AEMC Electro Industries EMM, Inc. Graphic Controls Osaki Yokogawa (YCA) Woertz SECTION Miscellaneous (Terminal Blocks, Demand Meters, Recorders, Data Loggers, Chart Paper) AEMC Electro Industries EMM, Inc. Graphic Controls Osaki Yokogawa (YCA) Woertz Miscellaneous products from the

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protectors Specifications Bulletin Number 1492, 1692

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protectors Specifications Bulletin Number 1492, 1692 Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protectors Specifications Bulletin Number 1492, 1692 Topic Page 1489-M Miniature Circuit Breakers 1 1492-SP Supplementary Protectors

More information

PACSystems* RX3i IC695PSA040

PACSystems* RX3i IC695PSA040 August 2012 PACSystems* RX3i IC695PSA040 Power Supply, 120/240VAC or 125VDC, 40 Watts The PACSystems * RX3i power supply IC695PSA040 is a 40-Watt supply that operates from an input voltage source in the

More information

WiAutoLink Frequently Asked Questions

WiAutoLink Frequently Asked Questions Rev. 0 December 2014 Page 1 of 8 WiAutoLink Frequently Asked Questions December 2014 1 Rev. 0 December 2014 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the WiAutoLink Single Phase Electronic

More information

ELECTROSÓN. ZA Series. Features. Radial Lead Metal-Oxide Varistors for Low to Medium Voltage Operation. [ /Title (ZA Series) /Subject

ELECTROSÓN. ZA Series. Features. Radial Lead Metal-Oxide Varistors for Low to Medium Voltage Operation. [ /Title (ZA Series) /Subject Data Sheet July 999 File Number 84.6 [ /Title (ZA Series) /Subject (Radial Lead Metal Oxide Varistors for Low to Mediu m Voltage Operation) /Autho r () /Keywords (Littelfuse, Inc., Suppression Products,

More information

SMALL GENERATOR INTERCONNECTION REQUEST. (Application Form)

SMALL GENERATOR INTERCONNECTION REQUEST. (Application Form) Attachment 2 Transmission Provider: SMALL GENERATOR INTERCONNECTION REQUEST Designated Contact Person: Address: Telephone Number: (Application Form) An Interconnection Request is considered complete when

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

Products :: Circuit Protection :: Hydraulic/Magnetic Circuit Breakers

Products :: Circuit Protection :: Hydraulic/Magnetic Circuit Breakers Products :: Circuit Protection :: Hydraulic/Magnetic Circuit Breakers Miniature Hydraulic/Magnetic Circuit Breaker M-Series M-Series PDF elibrary The M-Series miniature hydraulic/magnetic circuit breakers

More information

Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks

Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks General NEPSI's activar, Medium

More information

Product Guide. UL 489 DIN rail miniature circuit breakers

Product Guide. UL 489 DIN rail miniature circuit breakers Product Guide UL 489 DIN rail miniature circuit breakers UL 489 DIN rail miniature circuit breakers Product Overview................................................ 2 Product Selection WMZT 10 kaic at

More information

low voltage GLOBAL CATALOGUE RANGE Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters

low voltage GLOBAL CATALOGUE RANGE Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters CTLOGUE GLOBL RNGE 2. Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters 2. 2. Product Overview. 2.2 Overload Relay Setting Range 2. - 2.8 Product Specifications 2.9-2. Contactor

More information

LDN Series Laser Diode Drivers

LDN Series Laser Diode Drivers The New LDN series laser diode drivers are the second generation of precision CW/Pulsed diode drivers offered by Lumina Power. Building on more than a decade of experience in laser diode driver technology

More information

Electrical Plan Review

Electrical Plan Review Electrical Plan Review Overcurrent Protection and Devices, Short-Circuit Calculations, Component Protection, Selective Coordination, and Other Considerations Table of Contents Part I: Overcurrent Protection

More information