Inside the Data Center: Opportunities for Energy Efficiency
|
|
- Ginger Lloyd
- 5 years ago
- Views:
Transcription
1 Pacific Gas and Electric Company Presented to Technologies and Practices for Efficient & Reliable Data Centers Inside the Data Center: Opportunities for Energy Efficiency Mark Bramfitt Sunnyvale, California December 11, 2006
2 Why Look In The White Room? It s where the energy use is located! 2
3 Energy Multiplier Effect Saving energy in the data center space can result in equivalent savings at the cooling plant level. Depending on the type of cooling system, a kwh of heat load in the center drives an additional 0.75 to 1.25 kwh of cooling system energy use. 3
4 Spectrum of Energy Efficiency Measures Computing Equipment Servers Data Storage Power Distribution and Conditioning UPS Direct Current Inside The Room Cooling CRAC s Airflow Management and Control Direct Liquid Cooling Equipment Cabinets 4
5 Computing Equipment Premium-efficiency equipment Servers Data storage devices Others On-board power supplies 80+ Virtualization/Consolidation Servers Data storage 5
6 Premium Efficiency Equipment It is very challenging for: Customers to select equipment PG&E to develop incentive program Why? Equipment makers list performance metrics (zero to 60, max speed) but not energy performance (mpg) 6
7 Who Has Premium Equipment? 7
8 What To Do? The industry is hashing out standard performance tests and reporting, through SPEC committee. PG&E has, can, and will pay incentives for rip&replace/refresh projects, based on a calculation model. PG&E will look to debut a deemedsavings program in
9 Computing Equipment Power Supplies PG&E has provided funding for a project to extend the 80+ power supply program into the data center computing equipment market. Program will pay equipment manufacturers directly to specify high performance power supplies in their equipment. 9
10 Virtualization! Wow! In layman s terms a primarily softwarebased technology that allows for much higher equipment utilization rates, leading to equipment consolidation and even energy management of remaining equipment. 10
11 Virtualization Typically involves a survey of equipment and utilization rates using a software tool Recommends strategies for migrating platforms/applications/workloads to virtual machines hosted on consolidated computing equipment 11
12 Virtualization - Incentives Complete an audit of the following: existing equipment prediction of remaining equipment Calculate energy savings based on de-rated nameplate data PG&E provides a calculation spreadsheet for vendors and customers 12
13 Virtualization Calculator Predicts energy savings from equipment consolidation Can work for servers and/or data storage consolidation Predicts savings from reduced cooling load Predicts impacts to UPS Available from HTEE Team 13
14 Power Distribution & Conditioning Premium-efficiency UPS Direct current power distribution 14
15 Premium-Efficiency UPS Consider moving from: Standard-efficiency double-conversion to premium-efficiency or Delta conversion (APC) or Rotary Consider: Systems with modular configuration to match loads Be cognizant of: Loading and efficiency curves 15
16 Direct Current Distribution Eliminate stages of DC/AC/DC power conversion by delivering direct current from the UPS directly to the racks Demonstrated by LBNL and industry partners Potential savings of 10% to 20% of overall power conversion/delivery losses 16
17 Cooling Inside the Data Center CRAC s Efficiency, VFD fans Controls End-of-row, integrated Airflow Management and Control Adaptive cooling control Cabinets and directed airflow Retro-commissioning measures Liquid Cooling 17
18 CRAC s Specify new or replacement CRAC s with SEER ratings higher than equivalent Title 24 standards. Specify new or retrofit existing CRAC s with VSD fans to allow for better airflow management. Some manufacturers promoting CRAC s with closer proximity to racks. 18
19 Airflow Management Several companies is offering new adaptive airflow control systems. Generally taking temperature readings at the equipment level and applying an algorithm to control CRAC s PG&E/QuEST DCCCP HP s Dynamic Smart Cooling IBM s CoolBlue 19
20 Airflow Management - Physical Consider a variety of technologies to manage airflow: Ducted cabinets, with or without integral fans and/or cooling coils End-of-row air containment Direct ducting of airstreams 20
21 Airflow Management - RCx Variety of low- and no-cost measures: Reorienting equipment to hot aisle/ cold aisle configuration Fixing holes in raised floor Under floor cable management Floor grate tile relocation 21
22 Airflow Management - Incentives Key challenge: Accurately calculate predicted energy savings from any single measure or package of measures Solution: Pre- and post-measurement of direct energy savings The Real Solution: Adaptive airflow control systems to the rescue 22
23 Technical Support Dependent on your commitment, PG&E can provide technical assistance to evaluate the energy impacts of measures you are considering of implementing. 23
24 Financial Incentives Key points: You must file an application and get approval before you start your project. Application and supporting calculation needed. Before and after metering is an alternative route. PG&E reserves the right to inspect before and after conditions. New construction 24
25 Financial Incentives - Limits Generally 8 cents per kwh of annual energy savings for computing equipment savings, up to 14 cents per kwh for cooling system upgrades. Limited to no more than half of project cost. $4MM annual per site (meter) cap! 25
26 On the Horizon Deemed savings approach for premium efficiency computing equipment, based on industry standards Variety of liquid cooling strategies: cabinet level and component level Thin-client systems for distributed computing Demand response strategies using IT scheduling software Self generation directly feeding DC side of UPS! 26
27 PG&E Support Technical assistance to scope out energy impacts of projects you are considering Support for completing financial incentive applications How to access? Contact your: PG&E Account Representative PG&E High Tech Energy Efficiency Team 27
28 Closing PG&E has significantly expanded the scope of product and service offerings for data centers, particularly in the realm of inside-the-data-center energy efficiency measures. On the basis of market interest, we have reserved program funding of ~$25M for for this segment. 28
29 Stay Up-To-Date The skeleton of our new website is completed. We re adding content every week. Check out our new website: 29
30 Inside the Data Center Have a suggestion or a question? Contact: 30
Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationTen Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42
Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationGreen IT Project: The Business Case
Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at
More informationCost Model Energy Benefits DirectAire & SmartAire Overview & Explanation
Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation A cost model (See figure 1) has been created to provide the user a simplified method for directly comparing the energy cost of a
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationOvercoming the Challenges of Server Virtualisation
Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationSession 6: Data Center Energy Management Strategies
Session 6: Data Center Energy Management Strategies Data Center Energy Use and Opportunities: Applying Best Practices to meet Executive Order Requirements Dale Sartor, PE Lawrence Berkeley National Laboratory
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationInternational 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase
International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations
More informationComEd Retro-Commissioning and Monitoring-Based Commissioning
ComEd Retro-Commissioning and Monitoring-Based Commissioning Rick Tonielli Sr. Program Manager C O N F I D E N T I A L Territory profile ComEd is an electric delivery company providing service to 3.8 million
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationData Center Infrastructure Management (DCIM) By Jesse Zhuo
Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationE e n rgy g y St S ud u y y Pr P og o r g ams December 2011
Energy Study Programs December 2011 1 Agenda Energy Study Programs Overview Recommissioning Engineering Studies Data Center Studies Custom Rebates What makes a good energy study? 2 Energy Study Program
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationDCIM Data Center Infrastructure Management Measurement is the first step
DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by
More informationPartner Introduction
P R E S E N T S Partner Introduction September 16, 2013 Today s Agenda The Market Opportunity The Cooling Capacity Factor (CCF) New service Benefits to Upsite Partners How to Sell Launch Plan & Support
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationEnergy Action Plan 2015
Energy Action Plan 2015 Purpose: In support of the Texas A&M University Vision 2020: Creating a Culture of Excellence and Action 2015: Education First Strategic Plan, the Energy Action Plan (EAP) 2015
More informationREPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:
REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationNew York State Energy Research and Development Authority
New York State Energy Research and Development Authority What is NYSERDA? Established in 1975, NYSERDA is a public benefit corporation helping New York State meet its goals to: Reduce energy consumption
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationData Centers. Powerful Solutions That Put You in Control. Energy Management Solutions. Where your energy dollars are used. 1
Energy for What s Ahead SM Energy Management Solutions Data Centers Powerful Solutions That Put You in Control Ready to take a byte out of your data center energy use and become more cost-effcient? Data
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationMonitoring-Based Commissioning (MBCx) Early Results from a Portfolio of University Campus Projects
2006 National Conference on Building Commissioning Early Results from a Portfolio of University Campus Projects Karl Brown Deputy Director, California Institute for Energy and Environment University of
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationWho is NYSERDA? IT Greening
Agenda NYSERDA Overview NYSERDA and Data Centers NYSERDA Programs Participation FlexTech Industrial and Process Efficiency (IPE) How to get started Q&A Who is NYSERDA? New York State Energy Research and
More informationDesigning the Next Generation Embedded Data Center. Silicon Valley Leadership Group
Designing the Next Generation Embedded Data Center Silicon Valley Leadership Group November 5, 2014 Agenda 1. Background 2. Solution setting overview 3. Market interventions 4. Cloud panel 5. Next steps
More information1.0 Executive Summary
Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More informationAvoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms
Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationA New Paradigm for Retrocommissioning: Moving Building Science to Green Collar Trades
A New Paradigm for Retrocommissioning: Moving Building Science to Green Collar Trades Presented by: Keith Forsman,PE Pacific Gas & Electric Company August 17, 2010 .From Building Science to Green Collar
More informationApplication of TileFlow to Improve Cooling in a Data Center
Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationAchieving Energy Efficiency in Data Centers
Achieving Energy Efficiency in Data Centers This document was specifically prepared to aid utility account managers who are working with C&I customers. Any other use of this material (in whole or in part)
More informationsurvey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.
:: In a recent Uptime Institute survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. 2 Maintain Assess Control ROI Monitor Optimize The Need for a Better Approach
More informationCRAH Retrofit and Energy Savings Project
CRAH Retrofit and Energy Savings Project Danny Johnson Director, Technical Operations Silicon Valley Leadership Group - Data Center Efficiency Summit October 24, 2012 2260 E. El Segundo Boulevard - A Digital
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationFt Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work
Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationCRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS
CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS Peter Klock, P.E., President ESC Engineering Services Company peter@escengineering.com Bill Henry, P.E., Consulting Mechanical
More informationEP s approach to Power & Energy efficiency in DCs & paradigms
DG for Innovation and Technological Support EP s approach to Power & Energy efficiency in DCs & paradigms Presentation Presentation subtitle subtitle or lead-in or lead-in that says that what says what
More informationGreen Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex
Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,
More informationEcolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001
Ecolibrium OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Cloud control Keeping data centres cool. COVER FEATURE Cloud control Such is the growth in data centres globally
More informationSmartAisle. SmartAisleTM. Energy-efficient use of existing cooling power in data centers to
SmartAisleTM SmartAisle TM Energy-efficient use of existing cooling power in data centers 1.50 to 1.58 1.49 Emerson Network Power Smart Aisle TM The consistent physical separation of cold zones from warm
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationTaking The Heat Off University of East Anglia Data Centre
Taking The Heat Off University of East Anglia Data Centre University of East Anglia delivers data centre to match corporate green credentials The University of East Anglia (UEA) is one of the leading green
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationAPC by Schneider Electric Elite Data Centre Partner
Data Centre Solutions...energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration
More informationPrescriptive Program Rebate Application
Prescriptive Program Internal use only Xcel Energy OID Check the appropriate program box for your rebate. Cooling Data center efficiency FSO (Fluid System Optimization) Foodservice equipment Heating Lighting
More informationRetro-Commissioning Report
10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism
More informationCannon T4 Modular Data Center (MDC)
SOLUTIONS Cannon T4 Modular Data Center (MDC) Cannon T4 Modular Data Centers are part of Cannon T4 Data Center Solutions Cannon T4 Data Center Solutions Overview T4 Data Centers T4 Mini Data Centers T4
More informationPower Monitoring in the Data Centre
Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags
More informationImproving Data Center Efficiency
Improving Data Center Efficiency Controlling Bypass Airflow in your Data Center Bypass airflow can have a significant impact on the cooling capacity and efficiency of any data center. One key part of
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationBC Hydro Power Smart Forum Introducing Canada s First Utility IT Energy Conservation Program
BC Hydro Power Smart Forum Introducing Canada s First Utility IT Energy Conservation Program David Rogers IT Advisor, BC Hydro Power Smart November 17, 2008 IT Energy Management BC Hydro Power Smart Data
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationData Center Design: Power, Cooling & Management
Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1, 2N, 2(N+1) UPS topologies Large Free standing
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationEstimating Data Center Thermal Correlation Indices from Historical Data
Estimating Data Center Thermal Correlation Indices from Historical Data Manish Marwah, Cullen Bash, Rongliang Zhou, Carlos Felix, Rocky Shih, Tom Christian HP Labs Palo Alto, CA 94304 Email: firstname.lastname@hp.com
More informationAdvanced RTU Campaign Technical Resources: Evaluating Performance December 10, 2013
Advanced RTU Campaign Technical Resources: Evaluating Performance December 10, 2013 Agenda Overview of the Advanced RTU Campaign Resources for RTU Evaluation RTU Evaluation Application RTU Upgrade Case
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More information10 TECHNIQUES FOR IMPROVING DATA CENTER POWER EFFICIENCY
NETAPP VISION PAPER 10 TECHNIQUES FOR IMPROVING DATA CENTER POWER EFFICIENCY Dan Hoffman November 2007 WP-7030-1107 IMPROVE POWER EFFICIENCY IN YOUR DATA CENTER USING TODAY S TECHNOLOGIES NetApp is completely
More informationCisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project
Cisco Lab Setpoint Increase Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify key technology, policy and
More informationServer Room & Data Centre Energy Efficiency. Technology Paper 003
Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends
ABB Automation & Power World: April 18-21, 2011 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing Trends May 10, 2011 Slide 1 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing
More informationPros and Cons of Various DC Distribution Architectures
Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification
More informationSilicon Valley Power Data Center Program Rebate Application
Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account
More informationSmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity
SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.
More informationData Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More information