R-Gaïa Free-Cooling and Meteorological conditions

Size: px
Start display at page:

Download "R-Gaïa Free-Cooling and Meteorological conditions"

Transcription

1 R-Gaïa Free-Cooling and Meteorological conditions Jean-Yves Clément December 2012 Copyright International Business Machines Corporation All rights reserved. IBM and its logo are trademarks of IBM Corporation. This document may not be reproduced in whole or in part without the prior written permission of IBM. Please consider the environment before printing this document

2 Agenda Free-cooling design choices Weather analysis Operation example IT specifications ASHRAE

3 Agenda Free-cooling design choices Weather analysis Operation example IT specifications ASHRAE

4 Light structure Real Estate and Site Operations 4

5 Heavy structure Real Estate and Site Operations 5

6 Heavy structure principal 6

7 Light structure principal 7

8 Cold air aisle is more efficient: Heat exchange is better shared with all CRAC s Less expensive (non return air plenum) Heat exchange with building structure are optimized T ext = 15 C and below Delta T Cold aisle = 15 C Delta T Hot aisle = 5 C Favorable to Cold aisle T ext = 25 C Delta T Cold aisle = 5 C Delta T Hot aisle = - 5 C Favorable to Cold aisle T ext = 35 C and above Delta T Cold aisle = - 5 C Delta T Hot aisle = - 15 C Favorable to Cold aisle Cold aisle Hot aisle 8

9 Humidification: steam time is over! 9

10 Humidification: steam time is over! Cold vapor generation High pressure Centrifugation Compressed air Piezo 10

11 Humidification: steam time is over! 11

12 Agenda Free-cooling design choices Weather analysis Operation example IT specifications ASHRAE

13 Montpellier Airport Temperatures 2008 DATE C Mean 00h-06h C Mean 07h-18h C Mean 19h-23h janv.-00 févr.-00 avr.-00 mai-00 juil.-00 sept.-00 oct.-00 déc.-00 févr

14 Grenoble Temperatures

15 Agenda Free-cooling design choices Weather analysis Operation example IT specifications ASHRAE

16 Air specification to apply to IT : ASHRAE 2008 was an improvement for air containment efficiency: Temperature of cold air (25 C) blown under the raised floor is a limiting factor during summer. 5,5 C dew point is too strict compared with IT specification Proposed solution Extent humidity working range to IT specifications Control hygrometry in DC and adjust blowing temperature with AMU 16

17 ASHRAE IT 2008 ASHRAE 2008 Allowable (Class 1) ASHRAE 2008 Recommended 17

18 Weather example 18

19 Weather example: too hot during 2h30 19

20 Weather example: too dry during 23h30! 20

21 12,5 C and 60% RH is too dry for ASHRAE! 21

22 Agenda Free-cooling design choices Weather analysis Operation example IT specifications ASHRAE

23 IT Requirements X3550 Supported environment: Air temperature: Server on: 10 to 35 C (50.0 to 95.0 F); altitude: 0 to m (3,000 ft). Humidity: Server on: 20 to 80%, maximum dew point 21 C, maximum rate of change 5 C/h 23

24 IT Requirements ZSeries S/390 z196 24

25 IT Requirements Environmental and shipping specifications for tape cartridges 25

26 IT Requirements: worst case hygrometry 26

27 Weather limit for air blowing at T=21 c and Hr=20% in DC 27

28 Water weight evolution during October 8 th 28

29 November 6 th to 11 th humid period outside air 29

30 ASHRAE Real Estate and Site Operations Free-cooling design choices Weather analysis Operation example IT specifications ASHRAE

31 ASHRAE 2011 Real Estate and Site Operations 31

32 ASHRAE 2011 Real Estate and Site Operations 32

33 ASHRAE 2011 Real Estate and Site Operations 33

34 ASHRAE IT Equipment Environment Corrosion Data corruption Reduced life Cycle Electrostatic discharge 34

35 ASHRAE humidity limit vs IT specification la spécification de l'air soufflé dans les data centres doit être conforme au cadre pointillé vert de la page 29 de la présentation jointe, c'est à dire t=18 C à 27 C et hr= 80% à 20%. Ceci implique que l'air extérieur présentant des températures même très inférieurs à 15 C doit être utilisé du moment que son poids d eau permet d être en spécification une fois réchauffé dans le data center. Plus largement l efficacité du FreeCooling sera améliorée si l AMU (Air Mixing Unit) permettre de balayer toute la plage de température autorisée de manière à utiliser au mieux les caractéristiques de l air extérieur. De ce fait les jours ou l air extérieur est froid et sec, une température de soufflage de 15 C donnera le meilleur résultat. La température extérieure remonte en cour de journée de 8 C à 10 C en 8heurs. Ceci respecte les 5 C/h de variation demandées dans les spécifications des équipements IT. 35

36 ASHRAE humidity limit vs IT specification Only solution to use Free-Cooling in winter No risk for IT No energy lost with humidification system Reduce condensation risk 36

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

GETTING STARTED WITH IN-WALL RELAY SWITCH

GETTING STARTED WITH IN-WALL RELAY SWITCH GETTING STARTED WITH IN-WALL RELAY SWITCH This document is the property of Webee L.L.C. The data contained here, in whole or in part, may not be duplicated, used or disclosed outside the recipient for

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

RO 051 S-DIAS Relay Output Module

RO 051 S-DIAS Relay Output Module RO 051 S-DIAS Relay Output Module Date of creation: 10.08.2015 Version date: 18.10.2017 Article number: 20-064-051-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/6274/4321-18

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

A separate CRAC Unit plant zone was created between the external façade and the technical space.

A separate CRAC Unit plant zone was created between the external façade and the technical space. Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure

More information

ISE 021 S-DIAS Interface Module RS232 / RS485

ISE 021 S-DIAS Interface Module RS232 / RS485 ISE 021 S-DIAS Interface Module RS232 / RS485 Date of creation: 23.04.2014 Version date: 31.01.2018 Article number: 20-101-021-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321

More information

Planning a Green Datacenter

Planning a Green Datacenter Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data

More information

SI 021 S-DIAS SSI Interface Module

SI 021 S-DIAS SSI Interface Module SI 021 S-DIAS SSI Interface Module Date of creation: 16.06.2014 Version date: 18.10.2017 Article number: 20-022-021-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/6274/4321-18

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

ICA 012 S-DIAS Interface Module CAN

ICA 012 S-DIAS Interface Module CAN ICA 012 S-DIAS Interface Module CAN Date of creation: 06.09.2016 Version date: 25.06.2018 Article number: 20-102-012-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax:

More information

ControlLogix Redundant Power Supply Chassis Adapter Module

ControlLogix Redundant Power Supply Chassis Adapter Module Installation Instructions ControlLogix Redundant Power Supply Chassis Adapter Module Catalog Number 1756-PSCA Use this publication as a guide when installing the ControlLogix 1756-PSCA chassis adapter

More information

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat B. Keith Dunnavant, P.E. Manager, Data Center Cooling Solutions Munters Corporation Founded in 1955 Manufacturing & Sales Locations

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER Applications in Diverse Climates within Europe, Middle East and Africa Freecooling, Evaporative and Adiabatic Cooling Technologies

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

1769 Compact I/O Communication Bus Expansion Cables

1769 Compact I/O Communication Bus Expansion Cables 1769 Compact I/O Communication Bus Expansion Cables (Cat. No. 1769-CRR1, 1769-CRR3, 1769-CLL1, 1769-CLL3, 1769-CRL1, 1769-CRL3) Installation Inside... For More Information... 2 Hazardous Location Considerations...

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across

More information

IPv6 Protocol (RFC 2460 DS)

IPv6 Protocol (RFC 2460 DS) IPv6 Protocol (RFC 2460 DS) Copy Rights This slide set is the ownership of the 6DISS project via its partners The Powerpoint version of this material may be reused and modified only with written authorization

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

Aquaflair. BREC/F and BCEC/F kw

Aquaflair. BREC/F and BCEC/F kw Aquaflair Air-cooled chillers and free-cooling chillers with screw or oil-free centrifugal compressors equipped with adiabatic system BREC/F and BCEC/F 350-1350 kw Dualism for evolution: the combination

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

DK UL. Ref. Certif. No. Date: Signature:

DK UL. Ref. Certif. No. Date: Signature: DK-54446-UL IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME SYSTEME CEI D'ACCEPTATION MUTUELLE DE CERTIFICATS D'ESSAIS DES EQUIPEMENTS ELECTRIQUES (IECEE)

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Additional Information on page 2.

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Additional Information on page 2. DK-68856-M1-UL IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME CB TEST CERTIFICATE Product Switching Power Supply for Building In Name and address of the

More information

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Switching Power Supply for Building In

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Switching Power Supply for Building In DK-68856-M1-UL IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME CB TEST CERTIFICATE Product Switching Power Supply for Building In Name and address of the

More information

About Transferring License Rights for. PL7 V4.5 and Unity Pro V2.3 SP1 Software

About Transferring License Rights for. PL7 V4.5 and Unity Pro V2.3 SP1 Software Page 1 of 38 Click here to access the English Cliquez ici pour accéder au Français Klicken Sie hier, um zum Deutschen zu gelangen Premete qui per accedere all' Italiano Pulse acquì para acceder al Español

More information

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market

More information

COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS

COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS Dr Jon Summers Scientific Leader in Data Centers Part-time Academic in Thermofluids at the

More information

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Additional Information on page 2

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Additional Information on page 2 DK-69361-UL IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME CB TEST CERTIFICATE Product Switching Power Supply for Building In Name and address of the

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 1 Environmental Data Center Management and Monitoring A White Paper from aritan 2 Table of Contents Introduction... 3 Sensor Design Considerations... 3 Temperature and Humidity Sensors... 4 Airflow Sensor...5

More information

HVAC DESIGN REQUIREMENTS FOR DATA CENTERS

HVAC DESIGN REQUIREMENTS FOR DATA CENTERS Bulletin of the Transilvania University of Braşov CIBv 2015 Vol. 8 (57) Special Issue No. 1-2015 HVAC DESIGN REQUIREMENTS FOR DATA CENTERS C.G. POPOVICI 1 Abstract: One of the things definitive for the

More information

Art and Science of Building NUS Data Centres

Art and Science of Building NUS Data Centres Art and Science of Building NUS Data Centres DATA CENTRE @ NUS Contents I. Nostalgia II. III. IV. Science of Elements in a Data Centre NUS DC Live Migration the Art and Challenges Milestones in Pictures

More information

Some advises for insulating a new. l isolation d un nouveau laboratoire. Arusha, January 2012

Some advises for insulating a new. l isolation d un nouveau laboratoire. Arusha, January 2012 Some advises for insulating a new cotton testing laboratory Quelques conseils techniques pour l isolation d un nouveau laboratoire d analyse du coton GOURLOT J.-P. PAYET L. Arusha, January 2012 Plan of

More information

C-DIAS Analogue Output Module CAO 082 for eight ±10V DC respectively eight 0 20mA DC outputs

C-DIAS Analogue Output Module CAO 082 for eight ±10V DC respectively eight 0 20mA DC outputs C-DIAS Analogue Output Module CAO 082 for eight ±10V DC respectively eight 0 20mA DC outputs This analogue output module is used for driving components capable of being analogue driven (e.g. proportional

More information

LVB-2 INSTRUCTION SHEET. Leakage Current Verification Box

LVB-2 INSTRUCTION SHEET. Leakage Current Verification Box LVB-2 INSTRUCTION SHEET Leakage Current Verification Box V 1.02 1.2018 DECLARATION OF CONFORMITY Manufacturer: Address: Product Name: Model Number: Associated Research, Inc. 13860 W. Laurel Dr. Lake Forest,

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

WASP Wireless Acceleration Sensor Puck USER MANUAL

WASP Wireless Acceleration Sensor Puck USER MANUAL WASP Wireless Acceleration Sensor Puck USER MANUAL VERSION 3.20 15/07/2016 WASP is a registered trademark owned by BossPac Engineering & Technology WASP is a PATENT PENDING technology owned by BossPac

More information

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Additional Information on page 2

IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME. Additional Information on page 2 DK-69327-UL IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME CB TEST CERTIFICATE Product Switching Power Supply for Building In Name and address of the

More information

INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE

INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE Dr Jon Summers Scientific Leader in Data Centers, RISE Adjunct Professor of Fluid Mechanics, Lulea University of

More information

Five Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide

Five Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide Five Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide Table of Contents Introduction Five Best Practices for Enterprise Data Center Design 1.

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing

More information

Stacking Module. Installation Guide AT-MCF2000S. PN Rev A

Stacking Module. Installation Guide AT-MCF2000S. PN Rev A Stacking Module AT-MCF2000S Installation Guide PN 613-000708 Rev A Copyright 2007 Allied Telesis, Inc. All rights reserved. No part of this publication may be reproduced without prior written permission

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

Evolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development

Evolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development Evolution of Facebook s data center design Veerendra Mulay, PhD Strategic Engineering and Development Agenda 1 Introduction 2 Electrical design 3 Mechanical design 4 Design evolution 5 RDDC Introduction

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,

More information

VLANs. Commutation LAN et Wireless Chapitre 3

VLANs. Commutation LAN et Wireless Chapitre 3 VLANs Commutation LAN et Wireless Chapitre 3 ITE I Chapter 6 2006 Cisco Systems, Inc. All rights reserved. Cisco Public 1 Objectifs Expliquer le rôle des VLANs dans un réseau convergent. Expliquer le rôle

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

2201 Rack Chassis User Manual

2201 Rack Chassis User Manual 2201 Rack Chassis User Manual CAUTION! This product may contain a laser diode operating at a wavelength of 1300 nm - 1600 nm. Use of optical instruments (e.g., collimating optics) with this product may

More information

VI 021 S-DIAS VARAN Control Module

VI 021 S-DIAS VARAN Control Module VI 021 S-DIAS VARAN Control Module Date of creation: 11.06.2013 Version date: 18.10.2017 Article number: 20-003-021-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/s6274/4321-18

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

Why would you want to use outdoor air for data center cooling?

Why would you want to use outdoor air for data center cooling? Dell Fresh Air 2.0: Frequently Asked Questions Achieve improved data center efficiency and powerful enterprise performance you have come to expect from Dell, by deploying Dell Fresh Air hardware. Competitively

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

WaterStopper User Instruction Setup and Troubleshooting guide

WaterStopper User Instruction Setup and Troubleshooting guide WaterStopper User Instruction Setup and Troubleshooting guide Thank you for purchasing the newest, most exciting development in home automation. WatersStopper is an affordable state of the art, purpose

More information

ZTE ZXCR Series DX In-Row Air Conditioning Product Description

ZTE ZXCR Series DX In-Row Air Conditioning Product Description ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase

More information

Sun Fire V125 Server Getting Started Guide

Sun Fire V125 Server Getting Started Guide Sun Fire V125 Server Getting Started Guide Sun Microsystems, Inc. www.sun.com Part No. 819-7423-10 September 2006, Rev. A Submit comments about this document at: http://www.sun.com/hwdocs/feedback Copyright

More information

LM910 Bluetooth 4.0 (Classic + LE) HCI Compact USB SMT Module Dual-Mode with 110m Estimated Max. Distance with Integrated Antenna

LM910 Bluetooth 4.0 (Classic + LE) HCI Compact USB SMT Module Dual-Mode with 110m Estimated Max. Distance with Integrated Antenna TECHNOLOGIES Bluetooth 4.0 (Classic + LE) HCI Compact USB SMT Module Dual-Mode with 110m Estimated Max. Distance with Integrated Antenna OSX XP Vista 7 8 Product Part No 910-0630 Revised 04/APR/2016 10

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

Internet Scale Infrastructure Innovation

Internet Scale Infrastructure Innovation Compute Summit Internet Scale Infrastructure Innovation Open Compute Summit 2011 James Hamilton VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com web: mvdirona.com/jrh/work blog:

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

Trading TCO for PUE? A Romonet White Paper: Part I

Trading TCO for PUE? A Romonet White Paper: Part I Trading TCO for PUE? A Romonet White Paper: Part I Executive Overview Most data center vendors claim to improve Power Usage Effectiveness (PUE). The problem with this is that focusing on reducing PUE makes

More information

ASHRAE Data Center Standards: An Overview

ASHRAE Data Center Standards: An Overview Mission Critical Facilities ASHRAE Data Center Standards: An Overview 10012 North Dale Mabry Highway Suite 109 Tampa, FL 33618 813-792-6009 www.pergravis.com Presenter: Steve Ritzi, CDCE Pergravis is a

More information

RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink

RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink INDUSTRIAL INTERNET IN ACTION CASE STUDY RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink CLIENT PROFILE CenturyLink Technology Solutions is the second largest telecommunications

More information

ECOBAY: Closed loop water cooled server cabinet for data centers

ECOBAY: Closed loop water cooled server cabinet for data centers ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical

More information

1. Getting to know the gimbal

1. Getting to know the gimbal 1. Getting to know the gimbal Roll Motor Mounting Screw Containing Bracket Mode Button Joystick LED Light Power Button Shutter Button Thank you for choosing YI products 2. How to use the gimbal 1) Charging

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise TWO STAGE POWER DISTRIBUTION Executive Summary Today s data centers are changing rapidly, and it is more important than ever

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

User Manual 318BT. Phantom Powered Bluetooth Audio Receiver

User Manual 318BT. Phantom Powered Bluetooth Audio Receiver User Manual 318BT Phantom Powered Bluetooth Audio Receiver Contents Product brief 3 Getting started 4 Regular use 6 Troubleshooting 7 Specifications 8 FCC Compliance 9 Canada- IC 10 Warranty 11 318BT Phantom

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

APC APPLICATION NOTE #114

APC APPLICATION NOTE #114 APPLICATION NOT #4 Using the Rack Air Containment System with the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC00 and ACSC0) is a self-contained air conditioner for server

More information

Rack cooling solutions for high density racks management, from 10 to 75 kw

Rack cooling solutions for high density racks management, from 10 to 75 kw Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.

More information

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

brightsolid Data Hall 1 Keysource Technical Specifications

brightsolid Data Hall 1 Keysource Technical Specifications brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements

More information

ABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends

ABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends ABB Automation & Power World: April 18-21, 2011 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing Trends May 10, 2011 Slide 1 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing

More information

Implications of Current Thermal Guidelines

Implications of Current Thermal Guidelines Copyright 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission from ASHRAE Journal/High Performing Buildings. This material may not be copied

More information

WIRELESS ENVIRONMENTAL MONITORS

WIRELESS ENVIRONMENTAL MONITORS Packet Powers compact wireless Environmental Monitors makes it easy and affordable to monitor all environmental conditions in your facility. From installation to monitoring in minutes 1 Place wireless

More information