Stratus ftserver T Series: Site Planning Guide

Size: px
Start display at page:

Download "Stratus ftserver T Series: Site Planning Guide"

Transcription

1 Stratus ftserver T Series: Site Planning Guide Stratus Technologies R001L-02

2 Notice The information contained in this document is subject to change without notice. UNLESS EXPRESSLY SET FORTH IN A WRITTEN AGREEMENT SIGNED BY AN AUTHORIZED REPRESENTATIVE OF STRATUS TECHNOLOGIES, STRATUS MAKES NO WARRANTY OR REPRESENTATION OF ANY KIND WITH RESPECT TO THE INFORMATION CONTAINED HEREIN, INCLUDING WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PURPOSE. Stratus Technologies assumes no responsibility or obligation of any kind for any errors contained herein or in connection with the furnishing, performance, or use of this document. Software described in Stratus documents (a) is the property of Stratus Technologies Bermuda, Ltd. or the third party, (b) is furnished only under license, and (c) may be copied or used only as expressly permitted under the terms of the license. Stratus documentation describes all supported features of the user interfaces and the application programming interfaces (API) developed by Stratus. Any undocumented features of these interfaces are intended solely for use by Stratus personnel and are subject to change without warning. This document is protected by copyright. All rights are reserved. No part of this document may be copied, reproduced, or translated, either mechanically or electronically, without the prior written consent of Stratus Technologies. The Stratus Technologies logo, the ftserver logo, Stratus 24 x 7 with design, The World s Most Reliable Servers, The World s Most Reliable Server Technologies, ActiveService, ftgateway, ftmemory, ftmessaging, ftstorage, Selectable Availability, XA/R, SQL/2000, and The Availability Company are trademarks of Stratus Technologies Bermuda, Ltd. The registered trademark Linux is used pursuant to a sublicense from the Linux Mark Institute, the exclusive licensee of Linus Torvalds, owner of the mark on a worldwide basis. NEBS is a trademark of Telcordia Technologies, Inc. All other trademarks are the property of their respective owners. Manual Name: Stratus ftserver T Series: Site Planning Guide Part Number: R001L Revision Number: 02 ftserver System Software for the Linux Operating System Release Number: 3.0 Publication Date: December 2005 Stratus Technologies, Inc. 111 Powdermill Road Maynard, Massachusetts Stratus Technologies Bermuda, Ltd. All rights reserved.

3 Contents Preface ix 1. Site Planning for ftserver T Series Systems 1-1 Site Planning Overview 1-2 Site Planning for Fault-Tolerant Systems 1-3 Site Planning Checklist 1-4 System Documentation Cabinet and Monitor Requirements 2-1 Cabinet Requirements 2-1 Cabinet Requirements for All ftserver T Series Systems 2-2 Additional Cabinet Requirements for ftserver T 60 AC Systems 2-5 Additional Cabinet Requirements for ftserver T 30 Systems 2-5 Monitor Requirements Space Planning 3-1 Room Requirements 3-1 Planning for Cables Electrical Power Planning 4-1 Redundant Power Sources 4-1 Grounding Requirements 4-1 DC-Powered Systems 4-2 DC Power Connection Information 4-2 DC Operation Power Service Requirements 4-5 AC Power Service Requirements 4-5 DC Power and Ground Cables 4-6 AC-Powered Systems 4-7 AC Operation Power-Service Requirements 4-7 Contents iii

4 Contents AC Power-Outlet Requirements 4-10 Connecting a System Directly to Two Separate AC Power Sources 4-11 AC Power Cords Supplied by Stratus 4-13 ftserver T 60 AC System-Power Cords 4-14 ftserver T 30 AC System-Power Cords 4-14 PDU Power Cords 4-15 Monitor, Tape-Drive, and Storage Enclosure AC Power Cords 4-16 External Modem Power Cords Network and Telephone Line Planning 5-1 Network Cable Requirements 5-1 Telephone Line Requirements ftserver T Series Rack Configuration Planning 6-1 Determining Rack Space Usage 6-1 Appendix A. System Specifications A-1 ftserver T 60 AC System Specifications A-2 ftserver T 30 AC System Specifications A-6 ftserver T 30 CO System Specifications A-9 DC-to-AC Inverter Specifications A-13 Peripheral and Storage Components A-14 Appendix B. Electrical Circuit and Wiring Information B-1 DC-Powered ftserver T 30 CO Systems B-1 Fault Protection B-2 Grounding Considerations B-2 Circuit Wiring Diagrams B-4 DC Power Cables and Connectors B-5 AC-Powered ftserver T 60 AC and T 30 AC Systems B-5 Grounding Considerations B-5 Circuit Wiring Diagrams B-6 Electrical Power Connectors B-14 Appendix C. Standards Compliance C-1 iv Stratus ftserver T Series: Site Planning Guide (R001L)

5 Contents Index Index-1 Contents v

6 Figures Figure 2-1. Rail Clearance 2-4 Figure 4-1. AA-P86600 Inverter DC Input Cabling Diagram 4-2 Figure 4-2. AC Output Cabling Diagram 4-4 Figure 4-3. ftserver T 30 AC System Connected Directly to AC Power 4-12 Figure 4-4. ftserver T 60 AC System Connected Directly to AC Power 4-13 Figure A-1. ftserver T 60 AC System - Front View A-2 Figure A-2. ftserver T 60 AC System - Rear View A-3 Figure A-3. ftserver T 30 AC System - Front View (Bezel Removed) A-6 Figure A-4. ftserver T 30 AC System - Rear View A-7 Figure A-5. ftserver T 30 CO System - Front View (Bezel Removed) A-9 Figure A-6. ftserver T 30 CO System - Front View with Bezel Filter A-10 Figure A-7. ftserver T 30 CO System - Rear View A-11 Figure B-1. AA-P86600 DC-to-AC Inverter - Rear View B-2 Figure B-2. Star Ground Example B-3 Figure B-3. DC System Wiring B-4 Figure B-4. Star Ground Example B-6 Figure B-5. Power Input Labeling B-7 Figure B-6. Single-Phase, 120-Volts AC Circuit Connection B-8 Figure B-7. Single-Phase, 240-Volts AC Circuit Connection B-9 Figure B-8. Split-Phase, 120/240 Volts AC Circuit Connection B-10 Figure B-9. Three-Phase, 208-Volts AC, Y-, or -Source Circuit Connection, Phase-to-Neutral B-11 Figure B-10. Three-Phase, 208-Volts AC, Y-, or -Source Circuit Connection, Phase-to-Phase B-12 Figure B-11. Three-Phase, 380-Volts AC, Y-, or -Source Circuit Connection, Phase-to-Neutral B-13 vi Stratus ftserver T Series: Site Planning Guide (R001L)

7 Tables Table 1-1. ftserver T Series Documents 1-7 Table 3-1. Cables Supplied by Stratus 3-3 Table 4-1. Tape Drive: External AC Power Requirements 4-5 Table 4-2. DC Power and Ground Cables 4-6 Table 4-3. ftserver T 30 AC Systems: AC Power-Service Table 4-4. Requirements 4-7 ftserver T 60 AC Systems: AC Power-Service Requirements 4-8 Table 4-5. Optional Components: AC Power-Service Requirements 4-8 Table 4-6. Worksheet: Determining A-Side Power Requirements 4-9 Table 4-7. Worksheet: Determining B-Side Power Requirements 4-10 Table 4-8. Table 4-9. Worksheet: Determining External Component Power Requirements 4-10 Worksheet: Determining A-Side Power-Outlet Requirements 4-11 Table Worksheet: Determining B-Side Power-Outlet Requirements 4-11 Table ftserver T 60 AC System-Power Cords: Volts AC and Hz 4-14 Table ftserver T 30 AC System-Power Cords: Volts AC and Hz 4-14 Table ftserver T 30 AC System-Power Cords: Volts AC and 50 Hz 4-14 Table ftserver T 30 AC System Power Cords: Volts AC and Hz 4-15 Table PDU Power Cords to AC Power 4-15 Table System Power (Jumper) Cables to a PDU 4-16 Table Power Cords for Monitors and Tape Drives 4-16 Table External Modem Power Cords 4-18 Table 5-1. Customer-Supplied Ethernet Cables 5-2 Table 6-1. Rack Space Usage Calculation 6-1 Table A-1. ftserver T 60 AC Cabinet Dimensions A-4 Table A-2. ftserver T 60 AC System Specifications A-4 Table A-3. ftserver T 30 AC System Specifications A-7 Table A-4. ftserver T 30 CO System Specifications A-11 Table A-5. AA-P86600 Environmental Specifications A-13 Table A-6. AA-P86600 Mechanical Specifications A-13 Table A-7. AA-P86600 Input Voltage, Current, and Power A-13 Tables vii

8 Tables Table A-8. AA-P86600 AC Output Specifications A-14 Table B-1. Connectors for AC Power Outlets B-14 Table C-1. EMI Standards C-1 Table C-2. Immunity Standards C-2 Table C-3. Safety Standards C-2 Table C-4. Noise Standards C-2 viii Stratus ftserver T Series: Site Planning Guide (R001L)

9 Preface Purpose of This Manual Audience The Stratus ftserver T Series: Site Planning Guide (R001L) documents the site requirements and customer responsibilities related to preparing a site for the installation of ftserver T 30 and T 60 systems. This manual is intended for those responsible for preparing a site for the installation of ftserver T 30 and T 60 systems. Revision Information This manual is a revision. This revision incorporates the following changes: It documents information about the AA-P86600 DC-to-AC power inverter. It documents the D548 storage enclosure and the U532 Fibre Channel PCI Adapter. It documents new tape-drive options. Notation Conventions This document uses the notation conventions described in this section. Warnings, Cautions, and Notes Warnings, cautions, and notes provide special information and have the following meanings:! WARNING A warning indicates a situation where failure to take or avoid a specified action could cause bodily harm or loss of life. Preface ix

10 Preface! CAUTION A caution indicates a situation where failure to take or avoid a specified action could damage a hardware device, program, system, or data. NOTE A note provides important information about the operation of an ftserver system. Typographical Conventions The following typographical conventions are used in ftserver documents: Getting Help The bold font emphasizes words in text or indicates text that you type, the name of a screen object, or the name of a programming element. For example: Before handling or replacing the clock card, make sure that you are properly grounded by using a grounded wrist strap. In the System Properties dialog box, click the Hardware tab. The italic font introduces new terms and indicates programming and command-line arguments that the user defines. For example: Many hardware components are customer-replaceable units (CRUs), which can be replaced on-site by system administrators with minimal training or tools. copy filename1 filename2 If you have a technical question, you can find the latest technical information at the Stratus Technical Support Web site: If you are unable to resolve your questions with the help available at this online site and the ftserver T Series system is covered by a service agreement, you can contact the Stratus Customer Assistance Center (CAC) or your authorized Stratus service representative. For information about how to contact the CAC, see the following Web address: Regulatory Notice All regulatory notices are provided in Appendix C, Standards Compliance. x Stratus ftserver T Series: Site Planning Guide (R001L)

11 Chapter 1 Site Planning for ftserver T Series Systems1- ftserver T Series systems are fault-tolerant systems designed specifically for telecommunications service providers. In addition to its fault-tolerant system architecture, Stratus provides fault-hardened device drivers, which enhance application reliability and availability. For an overview of the information you need to know and the tasks you need to perform to prepare a site for ftserver T Series systems, see: Site Planning Overview Site Planning for Fault-Tolerant Systems Site Planning Checklist System Documentation For detailed site planning information, see: Chapter 2, Cabinet and Monitor Requirements Chapter 3, Space Planning Chapter 4, Electrical Power Planning Chapter 5, Network and Telephone Line Planning Chapter 6, ftserver T Series Rack Configuration Planning Appendix A, System Specifications Appendix B, Electrical Circuit and Wiring Information Appendix C, Standards Compliance Site Planning for ftserver T Series Systems 1-1

12 Site Planning Overview Site Planning Overview Site planning for fault-tolerant systems includes: Space planning Provide adequate space for the system or cabinet and for a desk or table to accommodate components outside a cabinet. Also provide enough space for servicing the systems and components. Purchasing an appropriate cabinet and monitor If you do not purchase a cabinet from Stratus, ensure that the cabinet you plan to use meets the system s requirements. If you do not purchase a monitor from Stratus, make sure that the monitor you plan to use meets ftserver T Series system requirements. Electrical (DC) power planning For DC-powered ftserver T 30 CO systems, provide a nominal input voltage of 48 VDC. The input voltage should be at least VDC and no more than 56.7 VDC. Electrical (AC) power planning For AC-powered ftserver T 30 AC and T 60 AC systems, determine AC power requirements as shown in AC-Powered Systems on page 4-7. Stratus does not supply or support uninterruptible power supplies (UPS) for ftserver T Series systems. Network and telephone line planning Provide sufficient network and analog telephone lines. Use the Site Planning Checklist on page 1-4 to ensure that you prepare your site properly for your ftserver T Series system and to track your site-preparation progress. For a list of other documents related to your ftserver T Series system, see System Documentation on page 1-7. During the site planning and preparation processes, work closely with your facilities group or contractor to determine space, power, and environmental requirements. Enlist their help to provide a suitable location with sufficient power, HVAC capabilities, and network and telephone connections. 1-2 Stratus ftserver T Series: Site Planning Guide (R001L)

13 Site Planning for Fault-Tolerant Systems If your system is covered by a service agreement and you need help with site planning, contact the Customer Assistance Center. If you have contracted with the CAC for installation of the system, contact them after you have prepared the installation site and moved the system to the site. For more information about the CAC, see Getting Help in the Preface or the CAC web site at: Refer to Appendix A, System Specifications, for ftserver T Series system specifications and to the Stratus ftserver Systems Peripherals Site Planning Guide (R582) for specifications of other components. Site Planning for Fault-Tolerant Systems In addition to the usual site planning tasks, such as planning sufficient DC electrical power and providing network connections, consider the following specific fault-tolerant features of ftserver T Series systems: Lockstep technology in ftserver T Series systems means that the systems contain redundant hardware. In the event of a component malfunction, the partner component is an active spare that continues normal operation. The failed component can then be removed and replaced without loss of data or service. In addition to planning for the duplicated power supplies, fans, and disk drives, often supplied by other servers, plan for replicated core system components including motherboards, processors, memory, I/O buses, and PCI adapters. Consequently, site planning includes planning for two CPU enclosures and for pairs of: I/O enclosures Ethernet network ports PCI adapters DC power inverters Power receptacles ftserver T Series systems can connect to the Stratus ActiveService Network (ASN). Connecting a system to the ASN allows the CAC to remotely diagnose, troubleshoot, and resolve problems online. Site Planning for ftserver T Series Systems 1-3

14 Site Planning Checklist To enable connectivity to the ASN, which allows the CAC to remotely manage the system, the system contains an external modem. With an external modem, ASN connectivity is only possible if the operating system is operational. Site Planning Checklist Referring to the information in this document, answer the questions in the following sections. Planning for ActiveService Network Connectivity Do you have an external analog telephone line available for the external modem to connect to the Stratus ASN? NOTE A dedicated phone line provides the most reliable service. ASN calls routed through a PBX might be slow due to load on the PBX, or might not complete successfully due to disconnections. If you must use a PBX, do not route the telephone extension through a switchboard; instead, provide a direct-dial analog number. Do you have an additional telephone line and telephone near the operator s station for voice communications when calling for support? Planning for Optional Components Does your system include any of the following optional PCI adapters for network communications or external storage connectivity? If so, indicate how many of each and plan network connections accordingly. Adapter Number of Adapters U574 Dual-Port Fiber Gigabit Ethernet Adapter U575 Dual-Port Copper Gigabit Ethernet Adapter U918 Four-Port T1/E1 PCI Adapter U532 Fibre Channel PCI Adapter Will you supply your own monitor, or will you use a monitor supplied by Stratus? Is the monitor rack-mountable, or do you need to provide a table or desk? Do you require a keyboard and mouse? 1-4 Stratus ftserver T Series: Site Planning Guide (R001L)

15 Site Planning Checklist NOTE Use only the USB keyboard and mouse supplied by Stratus. Does your system include any D548 storage enclosures? Does your system include any external tape drives? Do you need to provide a table or desk? Each core I/O enclosure in an ftserver T Series system contains an external SCSI port that you can use to connect the system to tape drives. The system supports up to three tape drives per core I/O enclosure. Planning Power for ftserver T 30 CO Systems For ftserver T 30 CO systems, provide a nominal input voltage of 48 VDC. The input voltage should be at least VDC and no more than 56.7 VDC. If you have an optional tape drive, you must provide an external AC power source for it at the site. What are the lengths and types of the power cables provided with your system? What are the lengths and types of the ground cables provided with your system? Will you use a tape drive, D548 storage enclosures, or other optional, AC-powered components? Planning Power for ftserver T 30 AC and T 60 AC Systems What optional, AC-powered components will you use? What are the AC power requirements of your system? Is the AC power service wired properly? What are the lengths and types of the power cords provided with your system? Planning Space for Your System Will your system and its external components fit where you plan to place them? What is the height of the cabinet you will use, and what is the total height of the systems and components that will be installed in the cabinet? How many systems and optional components will be housed in the cabinet? What components will be located outside the cabinet? What are the lengths and types of all interface and communication cables provided with your system? Have you created a sketch of how the system will be arranged at the installation site? Consider the available cable lengths, the placement of external devices, and the location of network and voice communication connections. Site Planning for ftserver T Series Systems 1-5

16 Site Planning Checklist On the sketch, show the following: Location of the system and its external components Power cords, and telephone and interface cables Locations of DC and AC power receptacles, phone jacks, Ethernet jacks, switches, and/or hubs NOTE Make sure that all cords and cables are long enough to reach between their respective components and connectors. Route all cables out of the way of foot traffic. Working with Other Groups Have you provided your facilities group and/or contractors with the sketch and copies of the following? DC Operation Power Service Requirements on page 4-5 or AC Operation Power-Service Requirements on page 4-7 Table 4-6 through Table 4-8, which provide worksheets for determining AC power requirements Table 4-9 and Table 4-10, which provide worksheets for determining power outlet requirements Appendix B, Electrical Circuit and Wiring Information Any notes you have taken about site planning Have you reviewed and discussed the requirements with the facilities personnel and/or contractors to ensure that all site modifications are understood and implemented? If you have any questions about the number and types of components, contact your Stratus account executive or distributor. 1-6 Stratus ftserver T Series: Site Planning Guide (R001L)

17 System Documentation System Documentation When you receive your system, you will receive the following printed documents: Either a Stratus ftserver T 60 Systems: Installation Guide (R011L) or a Stratus ftserver T 30 Systems: Installation Guide (R002L) The warranty for your system You will also receive a system documentation CD-ROM containing the documents in Table 1-1. The documents are in Adobe Acrobat PDF format. Table 1-1. ftserver T Series Documents (Page 1 of 2) Document Stratus ftserver T Series: Site Planning Guide (R001L) Stratus ftserver T 30 Systems: Installation Guide (R002L) or Stratus ftserver T 60 Systems: Installation Guide (R011L) Task Prepare a site for installation of a system Install a system, including mounting the system in a cabinet Find the part number of a customer-replaceable unit (CRU) Start the system for the first time Stratus ftserver System Administrator s Guide for the Linux Operating System (R003L) Install, update, and restore Linux operating system software and ftserver System Software for the Linux Operating System (ftsss) Update firmware and hardware Install, replace, and extend system hardware Manage data storage, SCSI, and serial devices Set up and administer a system Install and maintain Linux packages Install and configure simple network management Troubleshoot ftserver T Series systems Site Planning for ftserver T Series Systems 1-7

18 System Documentation Table 1-1. ftserver T Series Documents (Page 2 of 2) Document Stratus ftserver T 30 Systems: Operation and Maintenance Guide (R004L) or Stratus ftserver T 60 Systems: Operation and Maintenance Guide (R012L) Release Notes: Stratus ftserver System Software for the Linux Operating System (R005L) Task Start up, shut down, and operate a system Troubleshoot system hardware Remove and replace CRUs Learn the contents of the latest ftsss release Learn the latest information about the product Learn about significant known problems and how to work around or avoid the problems Read Me First: Unpacking an ftserver T 30 System (R006L) or Read Me First: Unpacking an ftserver T 60 System (R010L) Stratus D540 and D548 Storage Enclosure Connection Guide (R554) Inspect and unpack ftserver T Series hardware Connect a D548 storage enclosure to an ftserver T Series system Learn how to use a D548 storage enclosure with an ftserver T Series system Stratus ActiveService Network Configuration Guide (R013W) Stratus ftserver Systems Peripherals Site Planning Guide (R582) Use the ActiveService Manager (ASM) to create an ASN configuration file for your ftserver T Series system Prepare a site for the installation of system peripherals. Ordering Additional Printed Documentation To order additional copies of the ftserver T Series system documentation, customers in North America can call the CAC at (800) or (800) , 24 hours a day, 7 days a week. Customers outside North America can contact the nearest Stratus Sales office, CAC office, or distributor. Orders will be forwarded to Order Administration. 1-8 Stratus ftserver T Series: Site Planning Guide (R001L)

19 System Documentation Commenting on the Documentation Stratus welcomes any corrections and suggestions for improving its documentation. Send your feedback by to If it is possible, please include the book title and page numbers. This information will assist Stratus Publications in making any needed changes to the ftserver T Series documentation. Your assistance is appreciated. Site Planning for ftserver T Series Systems 1-9

20 System Documentation 1-10 Stratus ftserver T Series: Site Planning Guide (R001L)

21 Chapter 2 Cabinet and Monitor Requirements2- If you are supplying your own cabinet and monitor for use with ftserver T Series systems, see the following requirements: Cabinet Requirements Monitor Requirements If you are not supplying your own cabinet and monitor go to Chapter 3. Cabinet Requirements If you are providing your own cabinet for the ftserver system, make sure the cabinet contains a 19-in. wide rack that meets the Electronic Industries Association (EIA) 310-D standard. For system cabinet requirements, refer to one of the following sections: Cabinet Requirements for All ftserver T Series Systems Additional Cabinet Requirements for ftserver T 60 AC Systems Additional Cabinet Requirements for ftserver T 30 Systems The following considerations apply to systems in cabinets. Elevated Operating Ambient Temperature- If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer. Reduced Air Flow - Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised. Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading. Circuit Overloading - Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might Cabinet and Monitor Requirements 2-1

22 Cabinet Requirements have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern. Cabinet Requirements for All ftserver T Series Systems Use a cabinet that is either 24U or 38U high. One U equals 1.75 inches (4.45 cm). A cabinet depth of 1000 mm ensures that you can close the rear door. Make sure that: The cabinet contains two front and two rear vertical EIA rails, one in each corner of the cabinet, that have the EIA universal square-hole pattern as defined in the EIA 310-D specification. NOTE ftserver T Series systems do not support the EIA wide square hole pattern. The front vertical rails extend at least 0.5 in. (1.27 cm) beyond the inside edge of the accessory leg, if present, to allow the mounting rails to be fitted. See Figure 2-1. The distance between the front vertical rails and the inside of the front door is at least 3.0 in. (7.62 cm). The distance between the rear of the system chassis and the inside of the rear door is at least 6.0 in. (15.24 cm). The vertical mounting rails are plated, or some other method is used to ensure continuity for grounding between installed equipment. Cable-management brackets are provided to support and constrain data and power cords so that the cables do not interfere with air flow out of the rear of the enclosures, and so that the connectors do not disconnect or break. The cabinet provides enough stability so that system components pass Telcordia GR-63-CORE Section 4.4 regulations for earthquake vibration (Zone 4), operation vibration, and transport vibration. To prevent stray voltages, all components are grounded together through the vertical mounting rails to the cabinet frame, and then to ground and also to local building ground. To ensure signal quality, use a grounding cable provided by Stratus for local building ground. There is a plan for maintaining cables and wires to the cabinet by either running them under the floor or placing them overhead in a power bus. Air flows through the cabinet from front to back. Air does not recirculate within the cabinet. Filler panels cover any unused rack space to prevent air recirculation. 2-2 Stratus ftserver T Series: Site Planning Guide (R001L)

23 Cabinet Requirements Blockers are installed between the vertical mounting rails and the side panels at the rear of the cabinet. Vents are evenly distributed on the front and rear doors and comprise at least 63% of the surface area. Door frame width must be kept to a minimum to maximize the available open area. NOTE If your cabinet does not have vented front and rear doors, remove the doors from the cabinet while the ftserver system is operating. The final installation conforms to all emission, immunity, safety, and other applicable regulations. Figure 2-1 shows the required rail clearance between the front vertical rails and the inside edge of an accessory leg. Cabinet and Monitor Requirements 2-3

24 Cabinet Requirements Figure 2-1. Rail Clearance 0.5-inch (1.27-cm) minimum 0.5-inch minimum msys182 1 Front vertical EIA rail 2 Accessory leg 3 Front of cabinet 2-4 Stratus ftserver T Series: Site Planning Guide (R001L)

25 Monitor Requirements Additional Cabinet Requirements for ftserver T 60 AC Systems The ftserver T 60 AC system consists of a 10U system, rack mountable in a customer-supplied cabinet. Make sure that: A 24U cabinet can support at least 900 lb (410 kg) to support allowed configurations and components for a 24U cabinet. A 38U cabinet can support at least 1100 lb (500 kg) to support allowed configurations and components for a 38U cabinet. The distance between the front and rear vertical rails is 27 in. (68.58 cm). The vertical mounting rails accept 10/32 screws. Additional Cabinet Requirements for ftserver T 30 Systems The ftserver T 30 system consists of a 6U system, rack mountable in a customer-supplied cabinet. Make sure that: The distance between the front and rear vertical rails is between 24.5 in. and 30 in. (62.23 cm and cm). The vertical mounting rails accept M-5 cage nuts and mounting hardware. Monitor Requirements If you are using a monitor that is not supplied by Stratus, make sure that: The monitor accepts universal VAC, Hz power. The VGA-compatible SVGA connector has a 15-pin D-sub connector at the cable end. The power cord for the monitor is long enough to reach the power source. The plug type on the power cord is compatible with the external power source at the site. NOTE Use the keyboard and mouse provided by Stratus. Cabinet and Monitor Requirements 2-5

26 Monitor Requirements 2-6 Stratus ftserver T Series: Site Planning Guide (R001L)

27 Chapter 3 Space Planning3- For information about planning sufficient space for your ftserver T Series system, see: Room Requirements Planning for Cables Room Requirements To ensure that the installation site provides a properly equipped, cooled, and sized environment, make sure that the site: Provides clearances for air circulation and servicing the system Locate the front and rear of the system at least 2.5 ft. (0.76m) away from walls and other obstructions. Maintains reasonable temperature and humidity levels and has a thermometer and humidistat to monitor room temperature and humidity Is as free of dust as possible Dust buildup in the system can impede air circulation and heat transfer, causing components to become less reliable as the ambient temperature rises. Provides a table or desktop for external devices such as a telephone, tape drives, and an external monitor or LCD display, keyboard, and mouse Provides cutouts in the floor for routing cables, if the site has an elevated floor! CAUTION Do not place the system in an area of high electrostatic discharge. Static electricity may damage components. Do not locate components near transformers or other electromagnetic devices. Space Planning 3-1

28 Planning for Cables Planning for Cables To accommodate cables from the ftserver T Series system, make sure to provide: Two telephone lines: One telephone line for use when calling for service One telephone line for the ASN connection to the modem Modem placement within 39 in. (1m) of the ftserver T Series system, unless you provide your own AC power and signal cables Ethernet jacks, switches, or hubs as needed For DC-powered ftserver T 30 CO systems, provide a nominal input voltage of 48 VDC. The input voltage should be at least VDC and no more than 56.7 VDC NOTE DC power cables generally have a wider diameter than AC cables. Be sure to leave enough space for the wider curves these cables require. For AC power: sources as required NOTE Stratus does not provide uninterruptible power supply (UPS) units for ftserver T Series systems. For optional components: AC wall outlets within reach of the power cords from the components, or use PDUs 3-2 Stratus ftserver T Series: Site Planning Guide (R001L)

29 Planning for Cables Make sure that any cables you plan to connect to the system are long enough to reach between the system and external components or connections. Table 3-1 lists the cables Stratus supplies and, for space planning, specifies the lengths of each cable. Table 3-1. Cables Supplied by Stratus Component Cable Description Length 1U LCD display Table-top LCD display, keyboard, and mouse BHFCA-EY, T521, or T522 rack-mounted tape-drive enclosure Second tape drive in a BHFGA-EY or T522 tape-drive enclosure ER-SL1AA-YF or ER-SL2AA-YF SuperLoader 3 tape-drive enclosure D548 storage enclosure External modem Cabinet ground-leakage cable One VGA cable attached to the LCD display and that connects to the VGA port in the I/O panel One USB cable attached to the LCD display and that connects to another USB cable, which is connected to the system One VGA cable attached to the LCD display and that plugs into the VGA port in the I/O panel One USB cable attached to the keyboard and that plugs into a USB port in the I/O panel One USB cable attached to the mouse and that plugs into the keyboard USB hub One SCSI-3 high-density cable with one 0.8 mm VHDC connector and 68-pin SCSI-3 connector, which connects to the SCSI port on the back of the I/O enclosure One SCSI-3 daisy-chain cable with a 68-pin SCSI-3 connector at each end One SCSI-3 high-density cable with one 0.8 mm VHDC connector and 68-pin SCSI-3 connector, which connects to the SCSI port on the back of the I/O enclosure Two Fibre Channel optical cables One modem extension cable Global adapters are provided in the localization kit. 10AWG ground-leakage cable with 1/4 in. (6.35 mm) and M8 ring lugs 72 in. (183 cm) 72 in. (183 cm) 72 in. (183 cm) 72 in. (183 cm) 72 in. (183 cm) 10 ft. (305 cm) 30 ft. (915 cm) 3 ft. (91.5 cm) 10 ft. (305 cm) 30 ft. (915 cm) 6.5 ft. (2m) 39 in. (1m) 15 ft. (4.6m) Space Planning 3-3

30 Planning for Cables 3-4 Stratus ftserver T Series: Site Planning Guide (R001L)

31 Chapter 4 Electrical Power Planning4- Stratus ftserver T 30 central office (CO) systems connect to DC power sources. ftserver T 30 AC and ftserver T 60 AC systems connect to AC power sources. For information about planning appropriate electrical power for your ftserver T Series systems, see: Redundant Power Sources Grounding Requirements DC-Powered Systems AC-Powered Systems AC Power Cords Supplied by Stratus Redundant Power Sources All ftserver T Series systems require at least two separate and independent electrical power sources. Think of them as the A-side power source and the B-side power source. Either side must be capable of continuing to provide power if power to the other side is lost. DC-powered systems require two DC power sources, and AC-powered systems require two AC power sources. Grounding Requirements The ftserver T Series system obtains an earth reference ground via independent ground connections to the cabinet frame. Ensure that a high-integrity safety-ground conductor is installed as part of the wiring system (in accordance with Bellcore standards).! WARNING Incorrect grounding can cause severe personal injury and extensive equipment damage. See Grounding Considerations in Appendix B for a more complete discussion of ftserver T Series grounding. Electrical Power Planning 4-1

32 DC-Powered Systems DC-Powered Systems You must provide two separate DC power sources to supply power to two DC-to-AC power inverters. Both inverters supply AC power to the ftserver T 30 CO systems. One of the sources must also provide power for the ASN modem and a V128 monitor unit, if purchased. The inverter units contain no user serviceable parts. This section includes the following topics: DC Power Connection Information DC Operation Power Service Requirements AC Power Service Requirements DC Power and Ground Cables DC Power Connection Information Stratus supplies power cables to connect each inverter s DC input cable to the CO power supply. Figure 4-1 shows the DC input and ground cables on the rear of the DC inverter assemblies. Figure 4-1. AA-P86600 Inverter DC Input Cabling Diagram tlc043a 1 B-side DC inverter 4 A-side DC inverter 2 A-side DC input cable 5 Chassis ground cable 3 B-side DC input cable 4-2 Stratus ftserver T Series: Site Planning Guide (R001L)

33 DC-Powered Systems NOTE User-supplied DC power cables that connect directly from the CO supply to the DC inverter s DC input cable must use an Anderson Power Products connector (Anderson part number SBS50BLU#6-BK) and two contacts (Anderson part number 1339G2-BK) at the inverter end. User-supplied DC power cables that connect directly from the CO supply to the rear of the DC inverter must use a FCI- Burndy ring lug connector (Burndy part number YAV6CL2TC14FX) at the inverter end. Each inverter provides AC power to the system components through AC output Y cords. One end of each Y cord provides AC power to one side of the system. The other end provides AC power to external components. One cord has a T-plug adapter to provide one additional AC outlet. Figure 4-2 shows how the AC output cables and splitters are connected to an ftserver T 30 CO system. NOTE The AC output cord T-plug adapter can be connected to either the A-side AC output cord or the B-side AC output cord. The DC power inverters support only the ftserver T 30 CO system s CPU, I/O, monitor, and modem units. Only attach monitors supplied by Stratus to the DC inverters.! CAUTION Do not connect tape drives, D548 storage enclosures, customer-supplied monitors, or other AC-powered components to the DC power inverters. Doing so may damage the inverters and the attached components. Connect the tape drive directly to an AC wall outlet. The D548 storage enclosure requires two separate power sources. Connect the two power cords from the storage enclosure directly to two electrically separate AC wall outlets. Electrical Power Planning 4-3

34 DC-Powered Systems Figure 4-2. AC Output Cabling Diagram tlc063a 1 B-side AC output Y cord 2 Extra AC output connector (not for tape drive) 3 System backplane B-side receptacle 4 System backplane A-side receptacle 5 AC output connector 6 AC output cord T-plug adapter 7 Monitor receptacle 8 Modem jumper cord 9 A-side AC output Y cord! WARNING Wiring must meet ftserver T 30 system needs and comply with local safety codes and requirements. 4-4 Stratus ftserver T Series: Site Planning Guide (R001L)

35 DC-Powered Systems DC Operation Power Service Requirements For DC-powered ftserver T 30 CO systems, provide a nominal input voltage of 48 VDC. The input voltage should be at least VDC and no more than 56.7 VDC. The DC inverters provide AC power to the backplane, monitor, and modem. See Appendix B, Electrical Circuit and Wiring Information for electrical circuit and wiring information.! WARNING Wiring must comply with local safety codes and requirements. AC Power Service Requirements The D548 storage enclosure and tape-drive units cannot be connected to any of the AC outputs from the DC inverters. For the tape drives, provide one external AC power source. For the D548 storage enclosure, provide two electrically separate external AC power sources. In Table 4-1, determine the external AC power requirements, in watts, for your tape drive and D548 storage enclosures. Ensure your site power planning supplies sufficient wattage. See Table 4-5 for the AC power-service requirements for these components. Table 4-1. Tape Drive: External AC Power Requirements System Component Power (Watts) AC Power (Extended) T521 or T522 tape-drive enclosure x 500 = BHFCA-EY or BHGCA-EY tape-drive enclosure ER-SL1AA-YF or ER-SL2AA-YF tape-drive enclosure x 85 = 80 D548 storage enclosure 300 TOTAL A-SIDE EXTERNAL POWER REQUIREMENTS D548 storage enclosure 300 TOTAL B-SIDE EXTERNAL POWER REQUIREMENTS Electrical Power Planning 4-5

36 DC-Powered Systems DC Power and Ground Cables Stratus supplies tested and approved cables for the ftserver T 30 CO system. Table 4-2 lists these cables, their descriptions, and part numbers.! WARNING User-supplied power or ground cables must meet ftserver T 30 system needs and comply with local safety codes and requirements. Table 4-2. DC Power and Ground Cables Ground Cables B Inverter protective ground (Green/6AWG) 6 ft. (1.82m) DC Input Cables - A side B Inverter DC input cable (Red/Black/6AWG) 25 ft. (7.62m) DC Input Cables - B side B Inverter DC input cable (Blue/Black/6AWG) 25 ft. (7.62m) DC Input Cable Pigtail B Inverter DC extension cable (Red/Black/6AWG) 1.67 ft. (0.51m) AC Output Y Cord B Inverter AC output Y cord T-Plug Adapter AW-B52600 IEC-C14 to 2 IEC-C13 connectors (for optional and external components) AC Jumper Cord B M Black (2 per T-plug adapter) 3.28 ft. (1m) 4-6 Stratus ftserver T Series: Site Planning Guide (R001L)

37 AC-Powered Systems AC-Powered Systems You must provide two separate AC power sources for ftserver T 30 AC and T 60 AC systems and for any D548 storage enclosures. This section includes the following topics: AC Operation Power-Service Requirements AC Power-Outlet Requirements Connecting a System Directly to Two Separate AC Power Sources AC Operation Power-Service Requirements You can connect the power sources to two PDUS in the rack or directly to the AC power receptacles on the system backplane and other system components. Stratus does not supply or support a UPS for the ftserver T 30 AC and T 60 AC systems. NOTE Each cabinet supports a maximum of six AC power cords, including cords for monitors, tape drives, and the modem. Use a PDU to minimize the number of power cords exiting from the cabinet. Tables 4-3 and 4-4 describe the AC power nominal input line voltage (volts AC) and frequency (Hz) requirements for ftserver T 30 AC and T 60 AC systems, respectively. Table 4-3. ftserver T 30 AC Systems: AC Power-Service Requirements Component Nominal Input Voltage; Frequency Range Receptacle Rack-mountable system volts AC; Hz See Table Rack-mountable system volts AC; 50 Hz For Japan, NEMA For other countries, see Table Rack-mountable system volts AC; Hz; high leakage current See Table 4-13 or Table Electrical Power Planning 4-7

38 AC-Powered Systems Table 4-4. ftserver T 60 AC Systems: AC Power-Service Requirements Component Nominal Input Voltage; Frequency Range Receptacle System volts AC; Hz Locking receptacle. See Table Table 4-5 describes the AC power nominal input line voltage (volts AC) and frequency (Hz) requirements for optional components. Table 4-5. Optional Components: AC Power-Service Requirements Component Nominal Input Voltage; Frequency Range Receptacle V128 LCD display volts AC; Hz See Table T521 or T522 tape-drive enclosure volts AC; Hz See Table BHFCA-EY or BHGCA-EY tape-drive enclosure ER-SL1AA-YF or ER-SL2AA-YF tape-drive enclosure volts AC; Hz See Table volts AC; Hz See Table D548 storage enclosure volts AC; Hz See Table External modem power transformer volts AC; Hz See Table 4-18.! WARNING When ftserver T Series AC systems operate at voltages greater than 120 volts AC, the systems have high leakage current (greater than 3.5 ma). Stratus ships power cords with locking connectors for voltages higher than 120V. Use these locking connectors to ensure that the excess current is safely conducted to ground. Use the following worksheets to determine AC power requirements for the site. In Table 4-6, determine the power requirements at the A-side power source. The A-side power source provides power to one side of each system and D548 storage enclosure, as well as to components that do not require two sources of power: rack-mounted tape-drive enclosures, a modem, and an LCD monitor unit. 4-8 Stratus ftserver T Series: Site Planning Guide (R001L)

39 AC-Powered Systems In Table 4-7, determine the power requirements at the B-side power source. The B-side power source provides power to the other side of each system and D548 storage enclosure. In Table 4-8, determine the power requirements for components outside of the cabinet. These components can share a power source with the A-side or B-side components.! WARNING Wiring must meet ftserver T Series system AC system needs and comply with local safety codes and requirements. See Appendix B, Electrical Circuit and Wiring Information for electrical circuit and wiring information. To determine AC power requirements 1. In the Quantity column, write the number of each type of component. 2. Multiply the entry in the Quantity column by the number in Power (Watts) column, and enter the result in the AC Power (Extended) column. 3. Add the values in the AC Power (Extended) column, and enter the sum on the bottom line. This value indicates the maximum power requirement for each power source. Table 4-6. Worksheet: Determining A-Side Power Requirements (Page 1 of 2) System Component Power (Watts) AC Power (Extended) ftserver T 60 AC system x 1300 = ftserver T 30 AC system x 500 = V128 1U LCD unit x 21 = D548 storage enclosure 300 T521 or T522 tape-drive enclosure x 500 = BHFCA-EY or BHGCA-EY tape-drive enclosure ER-SL1AA-YF or ER-SL2AA-YF tape-drive enclosure x 85 = x 80 = D548 storage enclosure x 300 = Electrical Power Planning 4-9

40 AC-Powered Systems Table 4-6. Worksheet: Determining A-Side Power Requirements (Page 2 of 2) System Component Power (Watts) AC Power (Extended) TOTAL A-SIDE POWER REQUIREMENTS Table 4-7. Worksheet: Determining B-Side Power Requirements System Component Power (Watts) AC Power (Extended) ftserver T 60 AC system x 900 = ftserver T 30 AC system x 500 = D548 storage enclosure x 300 = TOTAL B-SIDE POWER REQUIREMENTS Table 4-8. Worksheet: Determining External Component Power Requirements System Component Power (Watts) AC Power (Extended) External modem power transformer x 5 = User-supplied components TOTAL EXTERNAL POWER REQUIREMENTS The following sections provide additional information about AC operation requirements: AC Power-Outlet Requirements Connecting a System Directly to Two Separate AC Power Sources AC Power-Outlet Requirements Use Table 4-9 and Table 4-10 to determine the number of power outlets to provide from A-side and B-side power sources. To determine the number of power outlets required 1. In the Quantity column, write the number of each type of component. 2. Multiply the value in the Quantity column by the value in the A-Side Outlets or B-Side Outlets column, and enter the total in the Subtotal column Stratus ftserver T Series: Site Planning Guide (R001L)

41 AC-Powered Systems 3. Add the values in the Subtotal column, and enter the sum on the bottom line. Table 4-9. Worksheet: Determining A-Side Power-Outlet Requirements Component Quantity A-Side Outlets Subtotal ftserver T 30 AC or T 60 AC system x 1 Monitor x 1 ER-SL1AA-YF, ER-SL2AA-YF, BHFCA-EY or BHGCA-EY, T521, T522 tape-drive enclosure x 1 D548 storage enclosure 1 TOTAL NUMBER OF A-SIDE POWER OUTLETS Table Worksheet: Determining B-Side Power-Outlet Requirements Component Quantity B-Side Outlets Subtotal Modem x 1 ftserver T 30 AC or T 60 AC system x 1 D548 storage enclosure 1 TOTAL NUMBER OF B-SIDE POWER OUTLETS Connecting a System Directly to Two Separate AC Power Sources Provide two AC power sources that are as electrically independent of each other as the installation site allows. The two power sources must at least be powered by separate AC power distribution circuit breakers and, if possible, be independent of each other beyond that level. The more electrical separation between the two power sources, the less likely that they will both fail at the same time. Due to redundancy in ftserver systems, power to either side of the system keeps duplexed components of the system operational. NOTE Stratus does not supply or support UPS equipment for ftserver T 30 or T 60 systems. The A-side power source provides power to each system as well as to optional components such as a V128 1U LCD monitor unit or tape drive. Electrical Power Planning 4-11

42 AC-Powered Systems The B-side power source also provides power to each system, in stand-by mode (the B-side power source is used if power to the A-side source is interrupted). The wattage that the A-side power source must supply is always equal to or greater than the wattage the B-side power source must supply. Figure 4-3 shows the power connections for an ftserver T 30 AC system connected directly to two separate power mains. Figure 4-3. ftserver T 30 AC System Connected Directly to AC Power tlc020 1 System power receptacles 2 A-side system power cords 3 B-side system power cords 4 AC power outlet 5 AC mains distribution circuit breaker Figure 4-4 shows the power connections for an ftserver T 60 AC system directly connected to two separate AC power sources Stratus ftserver T Series: Site Planning Guide (R001L)

43 AC Power Cords Supplied by Stratus Figure 4-4. ftserver T 60 AC System Connected Directly to AC Power A B 2 s10u069 1 A-side system power cord 3 AC power distribution circuit breaker 2 B-side system power cord 4 AC power outlet AC Power Cords Supplied by Stratus Stratus supplies tested and approved AC power cords for: ftserver T 60 AC System-Power Cords ftserver T 30 AC System-Power Cords Monitor, Tape-Drive, and Storage Enclosure AC Power Cords External Modem Power Cords! WARNING Place all power cords out of the way of foot traffic.! WARNING User-supplied power cords must meet ftserver T Series system needs and must comply with local safety codes and requirements. Electrical Power Planning 4-13

44 AC Power Cords Supplied by Stratus ftserver T 60 AC System-Power Cords Table 4-11 lists the power cords that connect ftserver T 60 AC systems, which are rated at V and Hz, directly to AC power. The first marketing ID in each pair is the power cord for the A-side; the second marketing ID is the power cord for the B-side. Table ftserver T 60 AC System-Power Cords: Volts AC and Hz Locale Voltage Rating Current Rating Plug Type Length Marketing ID North America and Japan 250V 20A NEMA L ft. (4.5m) B M B M International locking power cord 250V 16A IEC (formerly IEC 309) 4.5m B M B M ftserver T 30 AC System-Power Cords Tables 4-12, 4-13, and 4-14 list the power cords that connect ftserver T 30 AC systems directly to an AC power source (not to a PDU or to a UPS). Table ftserver T 30 AC System-Power Cords: Volts AC and Hz Locale Plug Type Current Rating Length Marketing ID Japan NEMA ft. (4.6m) B North America (Chicago) North America Domestic NEMA ft. B NEMA ft. B Table ftserver T 30 AC System-Power Cords: Volts AC and 50 Hz (Page 1 of 2) Locale Plug Type Current Rating Length Marketing ID Australia AS/NZS 3112: m B M China GB m B M Continental Europe CEE 7 VII m B M 4-14 Stratus ftserver T Series: Site Planning Guide (R001L)

45 AC Power Cords Supplied by Stratus Table ftserver T 30 AC System-Power Cords: Volts AC and 50 Hz (Page 2 of 2) Great Britain BS 1363/A m B M Israel SI 32: m B M Italy CEI m B M Switzerland 1011-S m B M South Africa and India SABS164-1:1992 ZA/ m B M Table ftserver T 30 AC System Power Cords: Volts AC and Hz Locale Plug Type Current Rating Length Marketing ID International NEMA L A 4.5m B M International, locking power cord IEC (formerly IEC 309) single-phase, 2-pole, 3-wire pin and sleeve connector 16 A 4.5m B M PDU Power Cords The AA-P41104 PDU supplies power to ftserver systems. Table 4-15 lists the available power cords to connect PDUs directly to an AC power source. Table 4-16 describes the gray and black power (jumper) cables that are provided to connect ftserver systems to PDUs. Table PDU Power Cords to AC Power Locale Plug Type Rating Length Marketing ID North America and Japan IEC (formerly 320) C19 to NEMA L6-20P 20A/250V Hz 15 ft (4.5m) B50155 North America IEC C19 to NEMA L6-30P (Receptacle must be fused at no more than 20A) 30A/250V Hz 15 ft B50156 International IEC C19 to IEC A/250V Hz 15 ft (4.5m) B50154 Use this power cord to connect the PDU directly to the AC power mains. Electrical Power Planning 4-15

46 AC Power Cords Supplied by Stratus Table System Power (Jumper) Cables to a PDU Length Rating Plug Type to System Plug Type to PDU Marketing ID 2.0m 10A/250V IEC 320 C13 IEC (formerly IEC 320) C14 B50502 Monitor, Tape-Drive, and Storage Enclosure AC Power Cords Table 4-17 lists the specifications of the power cords that connect monitors, tape drives, and storage enclosures directly to external AC power sources. Table Power Cords for Monitors and Tape Drives (Page 1 of 2) Locale Voltage Rating Plug Type Current Rating Length Marketing ID Australia 250 volts AC AS/NZS 3112: A 2.5m B M Australia and New Zealand 250 volts AC AS/NZS 3112:1993; SAA/3 10A 4.5m B M China 250 volts AC GB A 2.5m B F Continental Europe Continental Europe 250 volts AC 250 volts AC CEE 7 VII 10A 2.5m B M CEE 7 VII 10A 4.5m B M Great Britain 250 volts AC BS 1363/A 10A 2.5m B M India and South Africa 250 volts AC SABS164-1:1992; ZA/3 10A 4.5m B M Israel 250 volts AC SI 32: A 2.5m B M 4-16 Stratus ftserver T Series: Site Planning Guide (R001L)

47 AC Power Cords Supplied by Stratus Table Power Cords for Monitors and Tape Drives (Page 2 of 2) Locale Voltage Rating Plug Type Current Rating Length Marketing ID Israel 250 volts AC Italy 250 volts AC Italy 250 volts AC SI 32:1971; IL3/G 10A 4.5m B M CEI A 2.5m B M CEI23-16; I3/G 10A 4.5m B M Japan 120 volts AC Japan 100 volts AC NEMA A 10 ft. (3.05m) NEMA A 15 ft. (4.5m) B B M North America (Chicago) 120 volts AC NEMA A 7 ft. (2.1m) B North America, (domestic) 120 volts AC NEMA A 10 ft. (3.05m) B South Africa 250 volts AC SABS164-1:1992 ZA/3 10A 2.5m B M Switzerland 250 volts AC 1011-S A 2.5m B M Switzerland 250 volts AC 1011-S24507; 12G 10A 4.5m B M United Kingdom 250 volts AC BS1363; A:BS89 10A 4.5m B M United States 120 volts AC NEMA A 15 ft. (4.5m) B Electrical Power Planning 4-17

48 AC Power Cords Supplied by Stratus External Modem Power Cords Table 4-18 lists the specifications of the power cords that connect the external modem to an external AC power source. Table External Modem Power Cords (Page 1 of 2) Locale Description Length Marketing ID Argentina, Bahrain, Chile, China, Cyprus, Czech Republic, Egypt, Estonia, Greece, Hong Kong, Hungary, Indonesia, Israel, Ivory Coast, Jordan, Korea, Kuwait, Liechtenstein, Luxembourg, Malaysia, Oman, Pakistan, Paraguay, Peru, Poland, Portugal, Qatar, Russia, Singapore, Slovak Republic, Slovenia, South Africa, Spain, Thailand, Turkey, Ukraine, United Arab Emirates, Uruguay, Yemen Australia Austria Belgium Bolivia, Brazil, Canada, Colombia, Costa Rica, Ecuador, Guatemala, Honduras, Japan, Mexico, Panama, Philippines, Saudi Arabia, Taiwan, United States, Venezuela Denmark Finland, Norway France, Morocco 250 volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type AS/NZS 3112: volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEE 7 VII (10A) 120 volts AC/15A, plug type NEMA volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEE 7 VII (10A) 6.5 ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (1.83m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK Stratus ftserver T Series: Site Planning Guide (R001L)

49 AC Power Cords Supplied by Stratus Table External Modem Power Cords (Page 2 of 2) Locale Description Length Marketing ID Germany Iceland, Sweden India Italy Netherlands New Zealand Switzerland United Kingdom, Ireland 250 volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEI volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type CEE 7 VII (10A) 250 volts AC/10A, plug type BS1363/A (10) 6.5 ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK ft. (2.0m) AK Electrical Power Planning 4-19

50 AC Power Cords Supplied by Stratus 4-20 Stratus ftserver T Series: Site Planning Guide (R001L)

51 Chapter 5 Network and Telephone Line Planning5- For information about planning network and telephone lines for your ftserver T Series systems, see: Network Cable Requirements Telephone Line Requirements Network Cable Requirements Ethernet PCI adapters are typically supplied in pairs and teamed in software for fault tolerance. A cable for each member of the pair is required.! WARNING Make sure Ethernet cables can be routed out of the way of foot traffic. Table 5-1 describes the Ethernet cables you must supply. Be sure to provide a cable of sufficient length for the distance between the system and a wall jack or hub. Network and Telephone Line Planning 5-1

52 Telephone Line Requirements Table 5-1. Customer-Supplied Ethernet Cables Component Quantity Cable 10/100-Mbps system Ethernet ports 10/100/1000-Mbps system Ethernet ports 10/100/1000Base-T Ethernet PCI Adapters (gigabit copper adapters for servers) Two Two Two for each pair of 10/100/1000Base-T Ethernet PCI adapters 24 AWG, 4-pair, Unshielded Twisted Pair (UTP) EIA/TIA-Verified, Category-3 or Category-5 wire, with RJ-45 modular connectors terminated with pair-wiring adhering to the EIA/TIA 568-A or EIA/TIA 568-B standard. For connections to an Ethernet hub or switch, provide a straight-through cable. For 100- or 1000-Mbps (fast Ethernet) operation, provide full-duplex, or Category-5 Ethernet cables. The maximum allowable distance from an Ethernet port to a switch or a hub is 100 meters. 1000Base-SX Ethernet PCI Adapters (gigabit fiber-optic adapters for servers) Two for each pair of 1000Base-SX Ethernet PCI adapters Multi-mode, 62.5-micron, dual fiber cable with two SC-type connectors, and two connectors compatible with the network switch. If you have a unique network requirement, Stratus Professional Services can work with you to meet that requirement. Telephone Line Requirements Generally, an ftserver T Series system requires two telephone lines: One telephone line for use when calling for service One analog telephone connection point for the external modem A dedicated phone line provides the most reliable service. ASN calls routed through a PBX might be slow due to the load on the PBX, or might not complete successfully because the calls can become disconnected. If you must use a PBX, do not route the telephone extension through a switchboard; instead, provide a direct-dial analog number. 5-2 Stratus ftserver T Series: Site Planning Guide (R001L)

53 Chapter 6 ftserver T Series Rack Configuration Planning6- Determining Rack Space Usage Make sure that the ftserver T Series systems, DC inverters, and V128 LCD units fit into the vertical space available in the rack. To determine the vertical space used 1. In the Quantity column of Table 6-1, enter the number of each component. 2. In each row, multiply the value in the Component Height column by the Quantity, and enter the subtotal in the Cumulative Height column. 3. Add the values in the Cumulative Height column together and write the resulting value in the bottom row. Compare this value to the height of your rack as measured in rack units (U). Table 6-1. Rack Space Usage Calculation Component Component Height Quantity Cumulative Height ftserver T 60 system 10U x ftserver T 30 system 4U x AA-P86600 DC inverter 3U x D548 storage enclosure 2U x V128 1U LCD unit (optional) 1U x Total Height ftserver T Series Rack Configuration Planning 6-1

54 Determining Rack Space Usage 6-2 Stratus ftserver T Series: Site Planning Guide (R001L)

55 Appendix A System SpecificationsA- For specifications of the ftserver T Series systems and their DC inverters, see: ftserver T 60 AC System Specifications ftserver T 30 AC System Specifications ftserver T 30 CO System Specifications DC-to-AC Inverter Specifications Peripheral and Storage Components NOTE The system temperature and humidity requirements defined in Tables A-2, A-3, and A-4 are the minimum requirements the site must provide. System Specifications A-1

56 ftserver T 60 AC System Specifications ftserver T 60 AC System Specifications Figure A-1 shows the front of the ftserver T 60 AC system mounted in a rack, its bezel pulled forward. Figure A-2 shows the rear of an ftserver T 60 AC system, specifying the locations of the connectors at the back of the system. Table A-1 lists the dimensions of the 24U and 38U shipping container and of the unpacked 24U and 38U cabinets. Table A-2 lists specifications for the ftserver T 60 AC system. Figure A-1. ftserver T 60 AC System - Front View s10u004a 1 Core I/O enclosures 2 CPU enclosures 3 Expansion I/O enclosures A-2 Stratus ftserver T Series: Site Planning Guide (R001L)

57 ftserver T 60 AC System Specifications Figure A-2. ftserver T 60 AC System - Rear View A B 5 s10u150a 1 SCSI port 2 10/100/1000-Mbps Ethernet port 3 10/100-Mbps Ethernet port 4 Serial ports 5 Power receptacles 6 USB ports 7 VGA (monitor) port System Specifications A-3

58 ftserver T 60 AC System Specifications Table A-1. ftserver T 60 AC Cabinet Dimensions 24U Shipping Container Height (including pallet) Width Depth 56 in. (1.42m) 41 in. (1.04m) 53 in. (1.35m) 38U Shipping Container Height (including pallet) Width Depth in. (2.03m) 41 in. (1.04m) 53 in. (1.35m) 24U Cabinet Height (including casters) Width Depth Weight, empty Weight, empty with pallet and shipping container 50 in. (1.27m) 27.5 in. (70 cm) 41 in. (1.04m) 275 lb (125 kg) 436 lb (197.8 kg) 38U Cabinet Height (including casters) Width Depth Weight, empty Weight, empty with pallet and shipping container 74 in. (1.9m) 27.5 in. (70 cm) 41 in. (1.04m) 344 lb (156 kg) 512 lb (232.2 kg) Table A-2. ftserver T 60 AC System Specifications (Page 1 of 2) Power Output wattage Nominal input voltage; Frequency range A-side power: 1300W (AC) B-side power: 900W (AC) volts AC; Hz A-4 Stratus ftserver T Series: Site Planning Guide (R001L)

59 ftserver T 60 AC System Specifications Table A-2. ftserver T 60 AC System Specifications (Page 2 of 2) Physical Dimensions Height in. (45 cm; 10U) Width Depth (including ejectors) Weight 19 in. (48.26 cm) 30.9 in. (78.5 cm) 310 lb (141 kg) Environmental Requirements Operating temperature 41 F to 95 F (5 C to 35 C) For every 800 ft. (243.8m) above 2,000 ft. (609.6m), lower the maximum operating temperature (35 C) by 1 C. Storage temperature -38 F to 140 F (-39 C to 60 C) Operating altitude Maximum rate of temperature change during operation Relative humidity during operation Relative humidity during storage Heat dissipation 0 ft. to 10,000 ft. (0m to 3,048m) 53.6 F/hr (12 C/hr) 10% to 80% (noncondensing) 5% to 95% (noncondensing) 7500 BTUs per hour Features Processors Memory Ports Two or four Intel Xeon processors in each CPU enclosure Twelve dual data rate (DDR) inline memory module (DIMM) slots in each CPU enclosure One 10/100-Mbps Ethernet port, one 10/100/1000-Mbps Ethernet port, and one external SCSI port on each core I/O enclosure Two AC power connectors, one VGA port, two serial ports, and two USB ports PCI slots One 32-bit 66MHz PCI slot reserved for a video adapter in each core I/O enclosure Ten user-configurable PCI adapter slots: two in each core I/O enclosure operating at 64-bits and 33 MHz; three in each expansion I/O enclosure operating at 64-bits and 66 MHz System Specifications A-5

60 ftserver T 30 AC System Specifications ftserver T 30 AC System Specifications Figure A-3 shows the front of an ftserver T 30 AC system, mounted in a rack with its bezel pulled forward. Figure A-4 shows the rear of an ftserver T 30 AC system, specifying the locations of the connectors at the back of the system. Table A-3 lists the specifications for the ftserver T 30 AC system. Figure A-3. ftserver T 30 AC System - Front View (Bezel Removed) 1 Core I/O enclosures 2 CPU enclosures A-6 Stratus ftserver T Series: Site Planning Guide (R001L)

61 ftserver T 30 AC System Specifications Figure A-4. ftserver T 30 AC System - Rear View s4u099b 1 SCSI port 2 10/100/1000-Mbps Ethernet port 3 10/100-Mbps Ethernet port 4 Power receptacles 5 Serial ports 6 USB ports 7 VGA (monitor) port Table A-3. ftserver T 30 AC System Specifications Power Output wattage A-side: 500W (AC) B-side: 500W (AC) Nominal input voltage Model dependent Model dependent Model dependent volts AC; Hz , volts AC; 50 Hz volts AC; Hz Physical Dimensions Height 7 in. (17.78 cm; 4U) Width in. (45 cm) System Specifications A-7

62 ftserver T 30 AC System Specifications Table A-3. ftserver T 30 AC System Specifications (Continued) Depth System weight in. (75 cm) 124 lb (56.25 kg) to 137 lb (62 kg) Environmental Operating temperature 41 F to 95 F (5 C to 35 C) For every 800 ft (243.8 m) above 2000 ft (609.6 m), lower the maximum operating temperature (35 C) by 1 C. Maximum rate of temperature change during operation Relative humidity during operation Relative humidity during storage Heat dissipation 18 F/hr (10 C/hr) or 0.30 F/min (0.17 C/min) 20% to 80% (noncondensing) 8% to 80% 3500 BTUs per hour Features Processors Memory Ports One or two Intel Xeon processors in each CPU enclosure Six dual data rate (DDR) inline memory module (DIMM) slots in each CPU enclosure One 10/100-Mbps Ethernet port, one 10/100/1000-Mbps Ethernet port, and one external SCSI port on each core I/O enclosure Two AC power connectors, one VGA port, two serial ports, and two USB ports PCI slots One 32-bit 66MHz PCI slot for a video adapter or ftserver Access Adapter in each I/O enclosure Two user-configurable PCI adapter slots in each core I/O enclosure operating at 64-bits and 33 MHz A-8 Stratus ftserver T Series: Site Planning Guide (R001L)

63 ftserver T 30 CO System Specifications ftserver T 30 CO System Specifications Figure A-5 shows the front of an ftserver T 30 CO system, mounted in a rack and with its bezel removed. Figure A-6 shows the location and placement of the front bezel filter. Figure A-7 shows the rear of an ftserver T 30 system, specifying the locations of the connectors at the back of the system. Table A-4 lists the specifications for the ftserver T 30 system. Figure A-5. ftserver T 30 CO System - Front View (Bezel Removed) Core I/O enclosures 2 CPU enclosures 3 DC-to-AC power inverters tlc071 System Specifications A-9

64 ftserver T 30 CO System Specifications Figure A-6. ftserver T 30 CO System - Front View with Bezel Filter tlc021a 1 System bezel 3 DC-to-AC power inverter bezel 2 System air filter 4 DC-to-AC power inverters air filter A-10 Stratus ftserver T Series: Site Planning Guide (R001L)

65 ftserver T 30 CO System Specifications Figure A-7. ftserver T 30 CO System - Rear View tlc003a 1 SCSI port 2 10/100/1000-Mbps Ethernet port 3 10/100-Mbps Ethernet port 4 Serial ports 5 USB ports 6 VGA (monitor) port 7 Power receptacles 8 DC-to-AC power inverters Table A-4. ftserver T 30 CO System Specifications (Page 1 of 3) Power Input wattage A-side: 1415W (DC) B-side: 1415W (DC) Nominal input voltage 48 Minimum (VDC) System Specifications A-11

66 ftserver T 30 CO System Specifications Table A-4. ftserver T 30 CO System Specifications (Page 2 of 3) Maximum (VDC) 56.7 Physical Dimensions Height 7 in. (17.78 cm; 4U) Width Depth System weight in. (45 cm) in. (75 cm) 124 lb (56.25 kg) to 137 lb (62 kg) Environmental Operating temperature Maximum rate of temperature change during operation Relative humidity during operation Relative humidity during storage Operating altitude Operating vibration Transportation vibration Earthquake vibration Acoustics Heat dissipation Meets NEBS GR-63-Core Level 3 Equipment requirements Meets NEBS GR-63-Core Level 3 Equipment requirements Meets NEBS GR-63-Core Level 3 Equipment requirements Meets NEBS GR-63-Core Level 3 Equipment requirements Meets NEBS GR-63-Core Level 3 Equipment requirements Meets NEBS GR-63-Core Level 3 Equipment requirements Meets NEBS GR-63-Core Level 3 Equipment requirements Meets NEBS GR-63-Core Level 3 Zone 4 requirements Meets NEBS GR-63-Core Level 3 Equipment requirements 4830 BTUs per hour Features Processors Memory Ports Two Intel Xeon processors in each CPU enclosure Up to six dual data rate (DDR) inline memory module (DIMM) slots in each CPU enclosure. DIMM chips must be mounted in pairs. Maximum memory is 3 GB (6 X 512 MB DIMMs). One 10/100-Mbps Ethernet port, one 10/100/1000-Mbps Ethernet port, and one external SCSI port on each core I/O enclosure Two AC power connectors, one VGA port, two serial ports, and two USB ports A-12 Stratus ftserver T Series: Site Planning Guide (R001L)

67 DC-to-AC Inverter Specifications Table A-4. ftserver T 30 CO System Specifications (Page 3 of 3) PCI slots One 32-bit 33 MHz PCI slot for a video adapter in each core I/O enclosure Two user-configurable PCI adapter slots in each core I/O enclosure, operating at 64-bits and 33 MHz DC-to-AC Inverter Specifications Tables A-5, A-6, A-7, and A-8 list the specifications for the AA-P86600 DC-to-AC inverter. Table A-5. AA-P86600 Environmental Specifications Operating ambient temperature Storage temperature range Humidity range -20 C (-4 F) to +55 C (131 F) -50 (-58 F) to +85 C (185 F) Max 95% non-condensing Table A-6. AA-P86600 Mechanical Specifications Ventilation air Mounting Weight Internal fan 3U rack height in rack mount frame, no additional clearance required top or bottom 12 lb (5.44kg) Table A-7. AA-P86600 Input Voltage, Current, and Power Nominal input voltage 48 Minimum (VDC) Maximum (VDC) 56.7 Maximum input current Protection Inrush current controlled 50 Amps DC Input undervoltage and overvoltage protection. Output overload and short-circuit protection. Less than 50 Amps System Specifications A-13

68 Peripheral and Storage Components Table A-8. AA-P86600 AC Output Specifications Waveform THD Output voltage Sinusoidal < 1% typical 120 VAC/60 Hz Voltage regulation Better than 2% Frequency stability Isolatation Power rating Peak output current into nonlinear load DC content Power factor Controlled better than 0.01% stability Fully isolated input to output 1.5 kva maximum, over full temperature range 36 Amps peak maximum for 120VAC 10mV maximum Linear powers all loads with 0 leading to 0 lagging PF Non-linear Rectified loads with up to 2.8 crest factor at full load Motor starting 4 kva output for 10 seconds minimum Peripheral and Storage Components You can find specifications for the following peripheral and storage components in the Stratus ftserver Systems Peripherals Site Planning Guide (R582). Supported tape drive enclosures D548 storage enclosure V128 LCD display V115 keyboard C719 external modem AK438 USB floppy disk drive A-14 Stratus ftserver T Series: Site Planning Guide (R001L)

69 Appendix B Electrical Circuit and Wiring InformationB- For the electrical circuit and wiring information that you need to provide to the contractor and/or facilities personnel responsible for wiring the power at the system installation site, see: DC-Powered ftserver T 30 CO Systems AC-Powered ftserver T 60 AC and T 30 AC Systems DC-Powered ftserver T 30 CO Systems The ftserver T 30 is designed to run on DC power. A DC power inverter provides AC power to the system and its components. Figure B-1 shows the rear of the inverter. The following sections provide electrical and wiring information for ftserver T 30 CO systems: Fault Protection Grounding Considerations Circuit Wiring Diagrams DC Power Cables and Connectors Electrical Circuit and Wiring Information B-1

70 DC-Powered ftserver T 30 CO Systems Figure B-1. AA-P86600 DC-to-AC Inverter - Rear View tlc043a 1 B-side DC inverter 4 A-side DC inverter 2 A-side DC input cable 5 Chassis ground cable 3 B-side DC input cable Fault Protection Each customer replaceable unit (CRU) in the ftserver T30 system contains fault/overload current protection. The two DC inputs to each DC inverter CRU are protected by fuses for protection against internal faults. However, the system relies on the power distribution system at your site for protection against potential faults in the power cords. You must use circuit breakers in each power distribution branch feeding the system. Grounding Considerations The ftserver T 30 system obtains an earth reference ground via independent ground connections to the cabinet frame. Ensure that a high-integrity safety-ground conductor is installed as part of the wiring system (in accordance with Bellcore standards). The international safety standard (EN-60950) for electronic data processing (EDP) equipment also requires a ground conductor, but calls it a potential earth (PE) ground. Depending upon local conditions, ground potentials may differ between the system cabinet and any peripheral devices connected to the system cabinet. B-2 Stratus ftserver T Series: Site Planning Guide (R001L)

71 DC-Powered ftserver T 30 CO Systems The ftserver T 30 CO system cabinets must connect to a common ground point (ground window) to ensure signal integrity and the safety-ground connection. To meet this requirement, an ftserver T 30 CO cabinet is connected to the ground window by one or two green-wire safety-ground conductor leads (#4 gauge wire), each of which can handle 60A fault current. A star ground, shown in Figure B-2, is often used to obtain the same earth reference ground. Each earth reference ground, such as the system cabinet ground, is returned separately to a common point where a 0-volt earth ground exists. The star ground ensures that all equipment is at the same potential and that no noise or safety problems associated with an unpredictable or uncharacterized grounding system will occur. Figure B-2. Star Ground Example To DC-to-AC Inverter To Modem To Tape Drive To System To Monitor Earth Reference Ground (OV) tlc072 Electrical Circuit and Wiring Information B-3

72 DC-Powered ftserver T 30 CO Systems Circuit Wiring Diagrams Figure B-3 shows a schematic diagram of DC power for the ftserver T 30 CO system. Figure B-3. DC System Wiring -48V DC 48V RTN Ground (PE) -48V DC 48V RTN Ground (PE) } } B Source A Source Grounding Stud Cabinet Frame Power Cable B Power Cable A DC Input B DC Input B DC Input A DC Input A tlc074 B-4 Stratus ftserver T Series: Site Planning Guide (R001L)

73 AC-Powered ftserver T 60 AC and T 30 AC Systems DC Power Cables and Connectors Stratus supplies tested and approved cables and connectors for the ftserver T 30 CO system. Table 4-2 provides descriptions and part numbers. NOTE User-supplied DC power cables that connect directly from the CO supply to the DC inverter s DC input cable must use an Anderson Power Products connector (Anderson part number SBS50BLU#6-BK) and two contacts (Anderson part number 1339G2-BK) at the inverter end. User-supplied DC power cables that connect directly from the CO supply to the rear of the DC inverter must use a FCI- Burndy ring lug connector (Burndy part number YAV6CL2TC14FX) at the inverter end.! WARNING User-supplied power or ground cables must meet ftserver T 30 system needs and must comply with local safety codes and requirements. AC-Powered ftserver T 60 AC and T 30 AC Systems The following sections provide electrical and wiring information for ftserver T 60 AC and T 30 AC systems: Grounding Considerations Circuit Wiring Diagrams Electrical Power Connectors Grounding Considerations The system obtains an earth reference ground through the power cords attached to the system. Similarly, each peripheral device connected to the system obtains ground through its power cord. For each peripheral device, you must ensure that a high-integrity safety-ground conductor is installed as part of the wiring system (in accordance with U.S. national electric code NFPA 70 or the equivalent). The international safety standard (EN60950) for electronic data processing (EDP) equipment also requires a ground conductor, but calls it a protective earth (PE) ground. Electrical Circuit and Wiring Information B-5

74 AC-Powered ftserver T 60 AC and T 30 AC Systems Depending upon local conditions, ground potentials may differ between the system base and any peripheral devices connected to the system base. All grounds in the system must return to the same reference point in the power distribution system, as close as possible to zero (0) volt potential relative to earth reference ground. Earth reference ground is typically a metal stake in the ground to which the ground conductors from one or more buildings are attached. As shown in Figure B-4, a star ground is often used to obtain the same earth reference ground. Each earth reference ground, such as the system base ground, is returned separately to a common point where a zero-volt (0V) earth ground exists. The star ground ensures that all equipment is at the same potential and that no noise or safety problems associated with an unpredictable or uncharacterized grounding system will occur. Figure B-4. Star Ground Example To monitor 3 Earth reference ground (0V) 2 To ftserver system Circuit Wiring Diagrams The following circuit wiring diagrams show how the hot, ground, and/or neutral AC signals should be connected to the system s power input plug: Figure B-6 illustrates a single-phase, 120-volts AC circuit connection (for ftserver T 30 AC only). Figure B-7 illustrates a single-phase, 240-volts AC circuit connection. Figure B-8 illustrates a split-phase, 120/240-volts AC circuit connection. Figure B-9 illustrates a three-phase, 208-volts AC, Y-, or -source circuit connection, phase-to-neutral. B-6 Stratus ftserver T Series: Site Planning Guide (R001L)

75 AC-Powered ftserver T 60 AC and T 30 AC Systems Figure B-10 illustrates a three-phase 208-volts AC, Y-, or -source circuit connection, phase-to-phase. Figure B-11 illustrates a three-phase 380-volts AC, Y-, or -source circuit connection, phase-to-neutral. The figures in this appendix, label the power inputs for the ftserver system as X and Y (as shown in Figure B-5) to eliminate any ambiguities in the nomenclature. For single-phase applications, the X input is connected to the L (Line) hot input, and the Y input is connected to the N (Neutral) input. However, for split-phase or three-phase applications, the X and Y inputs are connected to L1, L2, or L3 (separate lines). Therefore, for split-phase or three-phase applications, both X and Y can be electrically hot with respect to the system base (earth reference ground). Figure B-5 shows the physical locations of the X and Y inputs on the system base. Figure B-5. Power Input Labeling Y X G (PE) Power input A or B (Face View) Electrical Circuit and Wiring Information B-7

76 AC-Powered ftserver T 60 AC and T 30 AC Systems Figure B-6 shows a single-phase, 120-volts AC circuit connection. Note that this application requires a single-pole circuit breaker. Figure B-6. Single-Phase, 120-Volts AC Circuit Connection Circuit A or B L N G (PE) 120V 0V 15A Maximum Power Cord Wall X Y G (PE) To power input A or B B-8 Stratus ftserver T Series: Site Planning Guide (R001L)

77 AC-Powered ftserver T 60 AC and T 30 AC Systems Figure B-7 shows a single-phase, 240-volts AC circuit connection. Note that this application requires a single-pole circuit breaker. Figure B-7. Single-Phase, 240-Volts AC Circuit Connection Circuit A or B L N G (PE) 240V 0V Single system: 20A maximum PDU: 30A maximum Power Cord Wall X Y G (PE) To power input A or B Electrical Circuit and Wiring Information B-9

78 AC-Powered ftserver T 60 AC and T 30 AC Systems Figure B-8 shows a split-phase, 120/240-volts AC circuit connection. Note that this application requires a double-pole circuit breaker. Figure B-8. Split-Phase, 120/240 Volts AC Circuit Connection Circuit A or B L1 L2 N G (PE) 240V 120V 0V 120V Single system: 20A maximum PDU: 30A maximum Power Cord Wall X Y G (PE) To power input A or B B-10 Stratus ftserver T Series: Site Planning Guide (R001L)

79 AC-Powered ftserver T 60 AC and T 30 AC Systems Figure B-9 shows a three-phase, 208-volts AC, Y-, or -source circuit connection, which is a phase-to-neutral source connection. Note that the ftserver X input can be connected from L1, L2, or L3. This application requires a single-pole circuit breaker. Figure B-9. Three-Phase, 208-Volts AC, Y-, or -Source Circuit Connection, Phase-to-Neutral Circuit A or B L1 L2 L3 N G (PE) 208V 208V 120V 0V 120V 120V Single system: 20A maximum PDU: 30A maximum Power Cord Wall X Y G (PE) To power input A or B Electrical Circuit and Wiring Information B-11

80 AC-Powered ftserver T 60 AC and T 30 AC Systems Figure B-10 shows a three-phase, 208-volts AC, Y-, or -source circuit connection, which is a phase-to-phase source connection. Note that the ftserver X and Y inputs can be connected from L1 and L2, L2 and L3, or L1 and L3. This application requires a double-pole circuit breaker. Figure B-10. Three-Phase, 208-Volts AC, Y-, or -Source Circuit Connection, Phase-to-Phase Circuit A or B L1 L2 L3 N G (PE) 208V 208V 120V 0V 120V 120V Single system: 20A maximum PDU: 30A maximum Power Cord Wall X Y G (PE) To power input A or B B-12 Stratus ftserver T Series: Site Planning Guide (R001L)

81 AC-Powered ftserver T 60 AC and T 30 AC Systems Figure B-11 shows a three-phase, 380-volts AC, Y-, or -source circuit connection, which is a phase-to-neutral source connection. Note that the ftserver X input can be connected to L1, L2, or L3. This application requires a single-pole circuit breaker. Figure B-11. Three-Phase, 380-Volts AC, Y-, or -Source Circuit Connection, Phase-to-Neutral Circuit A or B L1 L2 L3 N G (PE) 380V 380V 220V 0V 220V 220V Single system: 20A maximum PDU: 30A maximum Power Cord Wall X Y G (PE) To power input A or B Electrical Circuit and Wiring Information B-13

82 AC-Powered ftserver T 60 AC and T 30 AC Systems Electrical Power Connectors Table B-1 describes the connectors that Stratus uses to connect ftserver systems and their peripheral devices, such as tape drives, to AC power outlets. Table B-1. Connectors for AC Power Outlets (Page 1 of 3) Connector Configuration Rating Description NEMA A, 25 volts AC 2-pole, 3-wire NEMA L A, 208/24 volts AC 2-pole, 3-wire NEMA A, 125 volts AC 2-pole, 3-wire NEMA L A, 125/25 volts AC 2-pole, 3-wire B-14 Stratus ftserver T Series: Site Planning Guide (R001L)

83 AC-Powered ftserver T 60 AC and T 30 AC Systems Table B-1. Connectors for AC Power Outlets (Page 2 of 3) Connector Configuration Rating Description CEE (7) VII 20A, 25 volts AC 2-pole, 3-wire BS A or 10A, 25 volts AC 2-pole, 3-wire CEI A, 25 volts AC 2-pole, 3-wire SI 32/ A, 25 volts AC 2-pole, 3-wire IEC A, volts AC 2-pole, 3-wire Electrical Circuit and Wiring Information B-15

84 AC-Powered ftserver T 60 AC and T 30 AC Systems Table B-1. Connectors for AC Power Outlets (Page 3 of 3) Connector Configuration Rating Description SABS 164-1: A, 25 volts AC 2-pole, 3-wire BS 1363/A 13A, 250 volts AC 2-pole, 3-wire 1011-S A, 250 volts AC 2-pole, 3-wire AS/NZS 15A, 250 volts AC 2-pole, 3-wire SAA/3/15 15A, 250 volts AC 2-pole, 3-wire AS/NZS ftserver T 60 AC only ftserver T 30 AC only B-16 Stratus ftserver T Series: Site Planning Guide (R001L)

85 Appendix C Standards ComplianceCftServer T Series systems comply with the electromagnetic interference (EMI), immunity, safety, and noise regulations listed in Tables C-1 through C-4. All necessary agency labels are on the system. NOTES 1. This system must be configured with the components listed and described in the product configuration specifications. Deviations from this list of components will void agency certification. 2. You must install all wiring, including power and communications cables, in compliance with local and national electrical code (in the United States, national electrical code NFPA 70). In addition, you must use shielded communications cables to remain in compliance with Federal Communications Commission (FCC) and other international electromagnetic compatibility (EMC) regulations. 3. All EMC emissions compliance tests are performed at a third-party, certified test laboratory. You can obtain compliance reports for these tests from your Stratus account representative, who will contact the Product Compliance Group in the Stratus engineering organization. Table C-1. EMI Standards (Page 1 of 2) Standard Description Country/Region FCC Part 15 Class A Code of Federal Regulations 47 (1998) Class A North America EN Limits and methods of measurement of radio disturbance characteristics of Information Technology Equipment European Union Standards Compliance C-1

86 Standards Compliance Table C-1. EMI Standards (Page 2 of 2) Standard Description Country/Region AS/NZS 3548 Limits and methods of measurement of radio disturbance characteristics of Information Technology Equipment Australia/New Zealand CNS13438 Chinese National Standard Taiwan VCCI Class A Voluntary Control Council for Interference by Information Technology Equipment Japan Table C-2. Immunity Standards Standard Description Country/Region EN EN Generic Immunity Standard, Electromagnetic Compatibility, Residential, Commercial, and Light Industrial Limits and methods of measurement of immunity characteristics of Information Technology Equipment European Union European Union Table C-3. Safety Standards Standard Description Country/Region UL Safety of Information Technology Equipment North America EN Safety of Information Technology Equipment European Union Table C-4. Noise Standards Standard Description Country/Region ISO ISO 7779 Acoustics. Determination of Sound Power Levels of Noise Source using Sound Intensity Measurements of Airborne Noise emitted by Computers and Business Equipment European Union European Union C-2 Stratus ftserver T Series: Site Planning Guide (R001L)

87 Standards Compliance VCCI Note BSMI Note Standards Compliance C-3

Stratus ftserver 5200 and 6500 Series: Site Planning Guide

Stratus ftserver 5200 and 6500 Series: Site Planning Guide Stratus ftserver 5200 and 6500 Series: Site Planning Guide Stratus Technologies R457-07 Notice The information contained in this document is subject to change without notice. UNLESS EXPRESSLY SET FORTH

More information

Express5800/320Ma: Site Planning Guide

Express5800/320Ma: Site Planning Guide Express5800/320Ma: Site Planning Guide NEC Solutions (America), Inc. NR573 Notice The information contained in this document is subject to change without notice. UNLESS EXPRESSLY SET FORTH IN A WRITTEN

More information

Stratus ftserver 2510, 4410, and 6210 Systems: Site Planning Guide

Stratus ftserver 2510, 4410, and 6210 Systems: Site Planning Guide Stratus ftserver 2510, 4410, and 6210 Systems: Site Planning Guide Stratus Technologies R627-03 Notice The information contained in this document is subject to change without notice. UNLESS EXPRESSLY SET

More information

ftserver 3300 Service Bulletin

ftserver 3300 Service Bulletin ftserver 3300 Service Bulletin Last Updated 2/12/04 1. Overview The ftserver 3300 is based on the 2.4-GHz or 3.06-GHz Intel IA32 architecture using Intel s Xeon processors and one-way or two-way (one or

More information

ftserver 5600 to ftserver 6600 Upgrade Procedure 3/22/04

ftserver 5600 to ftserver 6600 Upgrade Procedure 3/22/04 ftserver 5600 to ftserver 6600 Upgrade Procedure 3/22/04 Notice The information contained in this document is subject to change without notice. UNLESS EXPRESSLY SET FORTH IN A WRITTEN AGREEMENT SIGNED

More information

ftserver 6600 Upgrade Procedure 3/11/04

ftserver 6600 Upgrade Procedure 3/11/04 ftserver 6600 Upgrade Procedure 3/11/04 1 Notice The information contained in this document is subject to change without notice. UNLESS EXPRESSLY SET FORTH IN A WRITTEN AGREEMENT SIGNED BY ANAUTHORIZEDREPRESENTATIVE

More information

* * Agilent Power Distribution Unit (PDU) Installation Guide

* * Agilent Power Distribution Unit (PDU) Installation Guide Agilent Power Distribution Unit (PDU) Installation Guide For use with Agilent PDU kits and PDU installation kits for Agilent instrument racks June 2008 Edition 7 E0608 *5000-0039* 5000-0039 Notice The

More information

Installing the Cisco MDS 9020 Fabric Switch

Installing the Cisco MDS 9020 Fabric Switch CHAPTER 2 This chapter describes how to install the Cisco MDS 9020 Fabric Switch and its components, and it includes the following information: Pre-Installation, page 2-2 Installing the Switch in a Cabinet

More information

E-Series Site Preparation Guide

E-Series Site Preparation Guide E-Series Site Preparation Guide September 2017 215-11797_A0 doccomments@netapp.com Table of Contents 3 Contents Deciding whether to use this guide... 10 Specifications of the model 3040 40U cabinet...

More information

Site Preparation CHAPTER

Site Preparation CHAPTER CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies

More information

Sun StorageTek. 1U Rackmount Media Tray Reference Guide. Sun Doc Part Number: Second edition: December 2007

Sun StorageTek. 1U Rackmount Media Tray Reference Guide. Sun Doc Part Number: Second edition: December 2007 Sun StorageTek nl 1U Rackmount Media Tray Reference Guide Sun Doc Part Number: 875 4297 10 Second edition: December 2007 Legal and notice information Copyright 2007 Hewlett Packard Development Company,

More information

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions HP UPS R/T3000 ERM Installation Instructions Overview The ERM consists of two battery packs in a 2U chassis. The ERM connects directly to a UPS R/T3000 or to another ERM. Up to two ERM units can be connected.

More information

Installation Job Aid for Ethernet Routing Switch 3600 Series

Installation Job Aid for Ethernet Routing Switch 3600 Series Installation Job Aid for Ethernet Routing Switch 3600 Series Notices NN47213-303 Issue 03.01 November 2017 Notice paragraphs alert you about issues that require your attention. Following are descriptions

More information

Junos WebApp Secure 5.0 Hardware Guide

Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a

More information

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual. The power behind competitiveness Delta Infrasuite Power Management Power Distribution Unit User Manual www.deltapowersolutions.com Save This Manual This manual contains important instructions and warnings

More information

Dell MD1280 Storage Enclosure Getting Started Guide

Dell MD1280 Storage Enclosure Getting Started Guide Dell MD1280 Storage Enclosure Getting Started Guide Regulatory Model: SP-2584, E11J Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better use of your computer.

More information

TRC-190 User s Manual

TRC-190 User s Manual User s Manual Edition 3.2, May 2017 www.moxa.com/product 2017 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used only

More information

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount. This Datasheet for the IC697CHS790 Rack, 9 Slots, Rear Mount. http://www.cimtecautomation.com/parts/p-14771-ic697chs790.aspx Provides the wiring diagrams and installation guidelines for this GE Series

More information

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions HP UPS R/T3000 G2 Installation Instructions Overview The HP UPS R/T3000 G2 features a 2U rack-mount with convertible tower design and offers power protection for loads up to a maximum of 3300 VA/3000 W

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual Omnitron Systems Technology, Inc. 1 iconverter 19-Module Managed Power Chassis User s Manual 27 Mauchly, #201, Irvine, CA 92618 Phone: (949) 250-6510; Fax: (949) 250-6514 2 Omnitron Systems Technology,

More information

Installation of the POTS splitter card requires the following steps: Determining the cables you need. Installing the POTS splitter chassis

Installation of the POTS splitter card requires the following steps: Determining the cables you need. Installing the POTS splitter chassis 5910 High Density Lifeline POTS Splitter Installation Instructions Document Number 5910-A2-GZ40-00 May 2005 About the 5910 POTS Splitter The 5910 is a double-density POTS splitter that separates the (Digital

More information

TRC-190 User s Manual

TRC-190 User s Manual First Edition, November 2008 www.moxa.com/product 2008 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. The software described in this manual is furnished under a license agreement

More information

LVN5200A-R2, rev. 1, Hardware Installation Guide

LVN5200A-R2, rev. 1, Hardware Installation Guide LVN5200A-R2 LVN5250A-R2 LVN5200A-R2, rev. 1, Hardware Installation Guide Customer Support Information Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500) FREE technical support

More information

Dell Networking S4810 Open Networking (ON) Getting Started Guide

Dell Networking S4810 Open Networking (ON) Getting Started Guide Dell Networking S4810 Open Networking (ON) Getting Started Guide Regulatory Model: S4810 Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better use of your

More information

Installation Job Aid for VSP 4850GTS

Installation Job Aid for VSP 4850GTS Installation Job Aid for VSP 4850GTS Notices Release 6.1.0.0 NN46251-308 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs describe

More information

Installation Note for the Cisco ME 3800X and ME 3600X Switch Power Supply and Fan Modules

Installation Note for the Cisco ME 3800X and ME 3600X Switch Power Supply and Fan Modules Installation Note for the Cisco ME 3800X and ME 3600X Switch Power Supply and Fan Modules This document provides the installation and removal instructions for the AC and DC input power supply and fan modules

More information

Dell SC7020 Storage Controller Getting Started Guide

Dell SC7020 Storage Controller Getting Started Guide Dell SC7020 Storage Controller Getting Started Guide Regulatory Model: E03T Regulatory Type: E03T001 Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better

More information

PLC Racks IC697CHS782/783

PLC Racks IC697CHS782/783 5 1 PLC Racks IC697CHS782/783 (IC697CHS782/783) datasheet Features Accepts 3rd Party VME modules which require 0.8 spacing. Accepts all IC697 PLC module types. Rear mount rack mounts in a 10 (254 mm) deep

More information

EMC VMAX Best Practices Guide for AC Power Connections

EMC VMAX Best Practices Guide for AC Power Connections EMC VMAX Best Practices Guide for AC Power Connections For: VMAX3 Family and VMAX All Flash REVISI 06 Copyright 2014-2017 Dell Inc. or its subsidiaries. All rights reserved. Published May 2017 Dell believes

More information

Manual Version: V1.00. Video Decoder Quick Guide

Manual Version: V1.00. Video Decoder Quick Guide Manual Version: V1.00 Video Decoder Quick Guide Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. Copyright Copyright 2016 Zhejiang

More information

Installation Job Aid for VSP 4450GTX-HT- PWR+

Installation Job Aid for VSP 4450GTX-HT- PWR+ Installation Job Aid for VSP 4450GTX-HT- PWR+ Notices Release 6.1.0.0 NN46251-305 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs

More information

iconverter 2-Module Power Chassis

iconverter 2-Module Power Chassis iconverter 2-Module Power Chassis User Manual 38 Tesla, Irvine, CA 92618 USA Phone: (949) 250-6510; Fax: (949) 250-6514 Page 1 Warning The operating description in this Instruction Manual is for use by

More information

Stratus ftserver 2600, 4500, and 6300 Systems: Operation and Maintenance Guide

Stratus ftserver 2600, 4500, and 6300 Systems: Operation and Maintenance Guide Stratus ftserver 2600, 4500, and 6300 Systems: Operation and Maintenance Guide Stratus Technologies R639-01A Notice The information contained in this document is subject to change without notice. UNLESS

More information

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W.

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W. HP R/T2200 UPS Installation Instructions Overview The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W. For more information about any of the topics covered in this document, see

More information

Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02

Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02 Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02 User Manual 1.1 Overview Telect s 80A, -48 Vdc Low-Voltage Disconnect (LVD) panel is a rack-mounted component with coil-operated contactors. These

More information

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2 Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2 Cisco CRS 3-Phase AC Power Distribution Unit 2 Revised: November 18, 2016,

More information

16Hi HARDWARE INSTALLATION GUIDE

16Hi HARDWARE INSTALLATION GUIDE 16Hi HRDWRE INSTLLTION GUIDE Table of Contents Section 1 Ratings....................................................................... 3 Section 2 Site Preparation................................................................

More information

PACSystems RX7i IC698CHS009/119

PACSystems RX7i IC698CHS009/119 January 2010 The RX7i rack can be used for all RX7i CPU and I/O configurations, Series 90-70 I/O, and VME modules. Backplane connectors are spaced on 0.8" (20.3mm) centers to accommodate single-width RX7i

More information

G5 PDU Installation Guide

G5 PDU Installation Guide G5 PDU Installation Guide 1 Contents Before You Begin... 3 Overview... 3 Important Safety Information... 3 Required Tools... 5 Section 1 Introduction... 6 Classification Overview... 6 Features... 7 Form

More information

SGI InfiniteStorage 120

SGI InfiniteStorage 120 SGI InfiniteStorage 120 Mass Storage Hardware Topics Edition 003 007-4853-003 Proprietary Rights Notices COPYRIGHT 2006, 2007 SGI. All rights reserved; provided portions may be copyright in third parties,

More information

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport PTX5000 Packet Transport Router Quick Start September 2017 Part Number: 530-066788 Revision 01 This document describes how to install the Juniper Networks PTX5000 Packet Transport Router. Contents Quick

More information

Installing the Cisco AS5400XM Universal Gateway

Installing the Cisco AS5400XM Universal Gateway CHAPTER 3 Installing the Cisco AS5400XM Universal Gateway This chapter guides you through the installation of the Cisco AS5400XM universal gateway and includes the following sections: Setting Up the Chassis,

More information

Dell Storage Center. Getting Started Guide. SCv2000 and SCv2020 Storage System. Regulatory Model: E09J, E10J Regulatory Type: E09J001, E10J001

Dell Storage Center. Getting Started Guide. SCv2000 and SCv2020 Storage System. Regulatory Model: E09J, E10J Regulatory Type: E09J001, E10J001 Dell Storage Center SCv2000 and SCv2020 Storage System Getting Started Guide Regulatory Model: E09J, E10J Regulatory Type: E09J001, E10J001 Notes, Cautions, and Warnings NOTE: A NOTE indicates important

More information

Preparing to Install the VG248

Preparing to Install the VG248 CHAPTER 2 To ensure normal system operation, plan your site configuration and prepare your site before installation. Before installing the VG248, review these sections: Preparing the Installation Site,

More information

Avanti HP Series Centrifuges Preinstallation

Avanti HP Series Centrifuges Preinstallation J3HP-TB-001AC May 2009 Avanti HP Series Centrifuges Preinstallation INTRODUCTION Purchase of an Avanti HP series high performance centrifuge includes installation and Basic Instrument Training for two

More information

Installation Job Aid for Ethernet Routing Switch 5900 Series

Installation Job Aid for Ethernet Routing Switch 5900 Series Installation Job Aid for Ethernet Routing Switch 5900 Series Notices NN47211-301 Issue 05.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs

More information

Broadband Automatic Disconnect Switch. User Manual

Broadband Automatic Disconnect Switch. User Manual Reset/Test Primary/ Primary Broadband Automatic Disconnect Switch User Manual Local Power Remote Pwer Local 63V Fault Secondary Select Secondary 220V Normal 990-1929 09/2004 Introduction Introduction

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide

Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports Basic Model: KSD-541 PoE Model: KSD-541-P Installation Guide DOC.080104-1- (C) 2008 KTI Networks Inc. All rights reserved.

More information

CPCI System Subrack 1 U

CPCI System Subrack 1 U User s Manual Product No.: Doc-No: 63972-165_R1.0 January 14, 2008 Rev. Date updated Change R1.0 January 14, 2008 Initial Release Impressum: Schroff GmbH D-75334 Straubenhardt, Germany The details in this

More information

Dell SCv3000 and SCv3020 Storage System Getting Started Guide

Dell SCv3000 and SCv3020 Storage System Getting Started Guide Dell SCv3000 and SCv3020 Storage System Getting Started Guide Regulatory Model: E03T Regulatory Type: E03T001 Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make

More information

PIX 515/515E. PIX 515/515E Product Overview CHAPTER

PIX 515/515E. PIX 515/515E Product Overview CHAPTER CHAPTER 4 PIX 515/515E This chapter describes how to install the PIX 515/515E, and includes the following sections: PIX 515/515E Product Overview Installing a PIX 515/515E PIX 515/515E Feature Licenses

More information

D-Link Switch User Manual. Table of Contents

D-Link Switch User Manual. Table of Contents Table of Contents About This Guide... 1 Terms/Usage... 1 Copyright and Trademarks... 1 Product Introduction... 2 Package Contents... 2 Product Overview... 2 Front Panel... 2 Rear Panel... 2 Indicator LEDs...

More information

Installing the IPS 4345 and IPS 4360

Installing the IPS 4345 and IPS 4360 CHAPTER 4 Installing the IPS 4345 and IPS 4360 Contents This chapter describes the Cisco IPS 4345 and the IPS 4360, and includes the following sections: Installation Notes and Caveats, page 4-1 Product

More information

3+1 U CPCI Serial System

3+1 U CPCI Serial System 3+ U CPCI Serial System User s Manual Product Number: 4579-46/47/48/49/40/4/4/43/44 Doc-No: 6397-349_R.0 January 06 R.0 January 06 Initial Release Impressum: Schroff GmbH Langenalber Str. 96-00 75334 Straubenhardt,

More information

3/4 U CPCI Serial Case System

3/4 U CPCI Serial Case System 3/4 U CPCI Serial Case System User s Manual Product Number: 4579-634 Doc-No: 6397-345_R.0 October 05 R.0 October 05 Initial Release Impressum: Schroff GmbH Langenalber Str. 96-00 75334 Straubenhardt, Germany

More information

Cary 50. Pre-Installation Manual

Cary 50. Pre-Installation Manual Cary 50 Pre-Installation Manual Notices Agilent Technologies, Inc. 1999, 2006 and 2011 No part of this manual may be reproduced in any form or by any means (including electronic storage and retrieval or

More information

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0 BS 287 DUAL CHANNEL POWER SUPPLY User Manual January 2017 V1.0 Table of contents 1.0 SAFETY INSTRUCTIONS... 3 2.0 GENERAL DESCRIPTION PS 289... 4 3.0 MECHANICAL INSTALLATION... 5 4.0 MAINS POWER & SAFETY

More information

Dell SC5020 and SC5020F Storage Systems Getting Started Guide

Dell SC5020 and SC5020F Storage Systems Getting Started Guide Dell SC5020 and SC5020F Storage Systems Getting Started Guide Regulatory Model: E03T Regulatory Type: E03T001 Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make

More information

INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-6B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual

More information

INSTRUCTION MANUAL RA 19-4B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

INSTRUCTION MANUAL RA 19-4B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES INSTRUCTION MANUAL RA 19-4B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-4B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual

More information

RMB Peripheral Units Installation Guide

RMB Peripheral Units Installation Guide RMB Peripheral Units Installation Guide Part Number 65-000101 2011 by Kentrox, Inc. All rights reserved. Copyright 2011 by Kentrox, Inc. All Rights Reserved. The material discussed in this publication

More information

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-5B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual

More information

Hardened 10/100Base-TX IEEE802.3at PoE PSE Ethernet Extender

Hardened 10/100Base-TX IEEE802.3at PoE PSE Ethernet Extender Quick Start Guide This quick start guide describes how to install and use the Hardened Ethernet Extender. This is the Hardened Ethernet Extender of choice for harsh environments constrained by space. Physical

More information

Signamax Connectivity Systems Industrial 10/100BASE-TX Ethernet Extender

Signamax Connectivity Systems Industrial 10/100BASE-TX Ethernet Extender Signamax Connectivity Systems Industrial 10/100BASE-TX Ethernet Extender U S E R S G U I D E Signamax Connectivity Systems Industrial Ethernet Extender Model 065-1167A User s Guide FCC Warning This equipment

More information

INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES KEPCO INC. An ISO 9001 Company. MODEL RA 19-7B RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual

More information

Dell Networking S4100-ON Series. Set-Up Guide

Dell Networking S4100-ON Series. Set-Up Guide Dell Networking S4100-ON Series Set-Up Guide Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either

More information

Lightspeed Advanced Reporting Bottle Rocket Hardware Installation Guide

Lightspeed Advanced Reporting Bottle Rocket Hardware Installation Guide Lightspeed Advanced Reporting Bottle Rocket Hardware Installation Guide 1800 19th Street / Bakersfield, CA 93301 / Tel: 661.716.7600 / Toll Free: 877.447.6244 / www.lightspeedsystems.com Table of Contents

More information

Upgrading and Servicing Guide

Upgrading and Servicing Guide Upgrading and Servicing Guide The only warranties for Hewlett-Packard products and services are set forth in the express statements accompanying such products and services. Nothing herein should be construed

More information

INSTRUCTION MANUAL RA 55 RACK ADAPTER RACK ADAPTER FOR MST SERIES POWER MODULES

INSTRUCTION MANUAL RA 55 RACK ADAPTER RACK ADAPTER FOR MST SERIES POWER MODULES INSTRUCTION MANUAL RA 55 RACK ADAPTER RACK ADAPTER FOR MST SERIES POWER MODULES KEPCO INC. An ISO 9001 Company. MODEL RA 55 RACK ADAPTER ORDER NO. REV. NO. IMPORTANT NOTES: 1) This manual is valid for

More information

AI180I AIswitch Series 180 Integrated Chassis Installation Guide

AI180I AIswitch Series 180 Integrated Chassis Installation Guide AI180I AIswitch Series 180 Integrated Chassis Installation Guide Part Number QR-180I Rev 5 2008 by Kentrox, Inc. All rights reserved. Copyright 2008 by Kentrox, Inc. All Rights Reserved. The material discussed

More information

IBM. Setup Instructions. RS/ Model B50 SA

IBM. Setup Instructions. RS/ Model B50 SA RS/6000 7046 Model B50 IBM Setup Instructions SA38-0562-00 First Edition (September 1999) The following paragraph does not apply to the United Kingdom or any country where such provisions are inconsistent

More information

N3240 Installation and Setup Instructions

N3240 Installation and Setup Instructions IBM System Storage N3240 Installation and Setup Instructions Covering the N3240 model GA32-2203-01 Notices Mail comments to: IBM Corporation Attention Department GZW 9000 South Rita Road Tucson, AZ 85744-0001

More information

Rack Installation Instructions

Rack Installation Instructions Rack Installation Instructions For System Storage EXP2512 and EXP2524 Express Storage Enclosures Use the instructions in this document to install an IBM System Storage EXP2512 Express Storage Enclosure

More information

Rack Installation Instructions

Rack Installation Instructions Rack Installation Instructions Review the documentation that comes with your rack cabinet for safety and cabling information. Before installing your server in a rack cabinet, review the following guidelines:

More information

SuperLoader 3 Quick Start Guide

SuperLoader 3 Quick Start Guide SuperLoader 3 Contents SuperLoader 3 Quick Start Guide The Quantum SuperLoader 3 is an automated storage and retrieval device consisting of a tape drive and up to two tape magazines holding up to eight

More information

LifeSize ClearSea Installation Guide August 2012

LifeSize ClearSea Installation Guide August 2012 LifeSize ClearSea Installation Guide August 2012 LifeSize ClearSea LifeSize ClearSea Virtual Machine LifeSize ClearSea Installation Guide 2 LifeSize ClearSea This guide describes how to install and configure

More information

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 UniStream HMI Panel Installation Guide USP-070-B10, USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for

More information

ExtremeSwitching 210 and 220 Series Switches: Hardware Installation Guide

ExtremeSwitching 210 and 220 Series Switches: Hardware Installation Guide ExtremeSwitching 210 and 220 Series Switches: Hardware Installation Guide 122039-00 Published May 2017 Copyright 2017 Extreme Networks, Inc. All rights reserved. Legal Notice Extreme Networks, Inc. reserves

More information

Perle MCR200 Installation Guide

Perle MCR200 Installation Guide Perle MCR200 Installation Guide P/N 5500322-10 Introduction The Perle MCR200 Chassis is a 2 slot chassis able to accommodate up to 2 Perle Media Converter modules or 1 Media Converter Module and an MCR-MGT

More information

Installation and Getting Started Guide. HP ProCurve 600/610 External Power Supplies. PoE. Power over Ethernet Devices

Installation and Getting Started Guide. HP ProCurve 600/610 External Power Supplies.   PoE. Power over Ethernet Devices Installation and Getting Started Guide HP ProCurve 600/610 External Supplies www.hp.com/go/hpprocurve PoE over Ethernet Devices HP ProCurve 600/610 External Supplies Installation and Getting Started Guide

More information

Replacing the Power Supply

Replacing the Power Supply APPENDIX B This appendix includes information on how to replace the power supply for the Cisco AS550XM universal gateway and contains the following sections: Safety Recommendations, page B-1 Required Tools

More information

InnoMedia Business VoIP ATA Models

InnoMedia Business VoIP ATA Models InnoMedia Business VoIP ATA Models MTA8328-4, MTA8328-8, MTA8328-24 Quick Installation Guide Important Safety Instructions Protective Earthing Protective earthing is used as a safeguard. This equipment

More information

SySTIUM TECHNOLOGIES. Assembly Guide. Model 133i

SySTIUM TECHNOLOGIES. Assembly Guide. Model 133i Assembly Guide Model 133i Radio Frequency Interference Notice (USA) This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules,

More information

Instruction Manual Basic Rack PDU VP7541 and VP9571A

Instruction Manual Basic Rack PDU VP7541 and VP9571A Instruction Manual Basic Rack PDU VP7541 and VP9571A VertivCo.com/geist Table of Contents Specifications... 3 Overview... 3 Environmental... 3 Temperature... 3 Humidity... 3 Elevation... 3 Electrical...

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console 1993 Specifications CSJ 0598-01-057 1.0 Description SPECIAL SPECIFICATION ITEM 6398 Transportation Management Console This Item shall govern for the furnishing and installation of Transportation Management

More information

Industrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide

Industrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports Basic Model: KSD-541 PoE Model: KSD-541-HP Installation Guide DOC.141201-1- (C) 2014 KTI Networks Inc. All rights reserved.

More information

RADCOM s Platform Specifications. Valid from Version 7.10

RADCOM s Platform Specifications. Valid from Version 7.10 Valid from Version 7.10 RADCOM Ltd., November 2006 IP Notices: 2006 RADCOM Ltd. All rights reserved. RADCOM is a trademark of RADCOM Ltd. in Israel and/or other countries. Microsoft Windows and Microsoft

More information

EZ Switch EZ Connect N SMCFS1601/SMCFS2401

EZ Switch EZ Connect N SMCFS1601/SMCFS2401 EZ Switch EZ Connect N Draft 16/24-Port 11n Wireless Fast Ethernet USB2.0 Adapter Switch SMCFS1601/SMCFS2401 COPYRIGHT & TRADEMARKS Specifications are subject to change without notice. is a registered

More information

Express5800/320Ma: Virtual Technician Module User s Guide

Express5800/320Ma: Virtual Technician Module User s Guide Express5800/320Ma: Virtual Technician Module User s Guide NEC Solutions (America), Inc. NR561 Notice The information contained in this document is subject to change without notice. UNLESS EXPRESSLY SET

More information

Quick Start Guide. Installation. User s Manual 1

Quick Start Guide. Installation.  User s Manual 1 Quick Start Guide This quick start guide describes how to install and use the Hardened Ethernet Extender. This is the Hardened Ethernet Extender of choice for harsh environments constrained by space. Installation

More information

Rack Installation Instructions

Rack Installation Instructions Rack Installation Instructions Review the documentation that comes with your rack cabinet for safety and cabling information. When installing your server in a rack cabinet, consider the following: v Two

More information

hp uninterruptible power system r12000 xr models installation instructions

hp uninterruptible power system r12000 xr models installation instructions hp uninterruptible power system r000 xr models installation instructions Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer

More information

4170 POS System Installation Guide

4170 POS System Installation Guide 4170 POS System 4170 Installation Guide Thank you for selecting UTC RETAIL s innovative Model 4170 Point of Sale solution! This Installation Guide will help you efficiently install the 4170 POS. The document

More information

IBM. Rack Installation Instructions

IBM. Rack Installation Instructions IBM Rack Installation Instructions Review the documentation that comes with your rack cabinet for safety and cabling information. When installing your server in a rack cabinet, consider the following:

More information

VEP4600. Setup Guide

VEP4600. Setup Guide VEP4600 Setup Guide Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either potential damage to hardware

More information

Power Input Assignment Power1 12VDC DC Jack VDC Power2 - Power Ground

Power Input Assignment Power1 12VDC DC Jack VDC Power2 - Power Ground Quick Start Guide This quick start guide describes how to install and use the Hardened Ethernet Extender. This is the Hardened Ethernet Extender of choice for harsh environments constrained by space. Physical

More information

Installation and Maintenance

Installation and Maintenance CHAPTER 4 Installation and Maintenance Revised: April 19, 2010, Introduction This chapter explains how to install a SCE 1000 platform in a rack or in a general tabletop or workbench installation. Additionally,

More information

Hardware Reference Guide For Thin Clients

Hardware Reference Guide For Thin Clients b Hardware Reference Guide For Thin Clients Document Part Number: 254241-001 July 2002 This book provides basic hardware information for this series of Compaq Thin Clients. Å WARNING: Ä CAUTION: 2002 Compaq

More information