1 lindab we simplify construction UltraLink Technical information
2 Content Introduction Monitor Overview... 3 Description... 3 Mounting... 4 Connections... 4 Power supply... 5 Display... 6 Status light... 7 Settings... 7 ID-numbers... 9 Troubleshooting... 9 Technical data... 9 Maintenance Display & Sensor Overview...10 Description...10 Mounting...10 Display...11 Status light...11 Settings...11 ID-numbers...12 Troublshooting...12 Technical data...13 Maintenance...13 Introduction UltraLink is a highly accurate flow monitor without any obstacles in the airstream that creates pressure drop. It measures the flow with an angled ultrasonic beam which can be calculated and compensated to a very high accuracy over the whole flow range. The method is very stable over time due to that it is not sensitive to dirt and the design minimizes the dust collection on the flow sensors. An increased focus on energy saving has led to ventilation systems requiring low minimum flows. The low flows are a problem since they are very difficult to measure and it is makes it difficult to control the ventilation system. UltraLink, the new technology can measure lower than today s products while maintaining measurement accuracy. This offers great advantages for the user in terms of comfort and savings in energy consumption, which is of great interest. 2
3 IP42 Patented Status Monitor FTMU Airflow 1. Monitor Overview Display unit Sensor body Flow sensor Display unit Status light Air flow direction CE-mark Status Airflow IP42 IP classification Patented button Monitor FTMU Display parameters Description Application Monitor The monitor is suitable for measuring air flow and temperature. Air flow direction Design The monitor consists of a sensor body with Lindab Safe gaskets. Two flow sensors are mounted on the sensor body and connected to a display unit. The display unit is mounted ontop of a shelf on the sensor body. RTU Note! The flow sensors are placed at a fixed distance to each other and they shall never be removed. TCP/IP 3
4 Mounting Mount the sensor body into Lindab s air duct sytem according to the mounting instructions for Lindab Safe. It is important that the sensor body is mounted with the air flow direction arrow pointing in the direction of the air flow. Do not use the flow sensors as handles when you mount the monitor since they may break and changes in their positions might effect the measurement accuracy. The monitor can be connected to an RTU (remote terminal unit) via RS485 communication, the RTU can then be connected to a computer via TCP/IP Modbus. To be able to connect cords to the terminal board the rubber cable grommet on the backside of the display unit must be punctured, preferably using an awl or something else pointy to ensure tightness to the environment. When the cords have been connected they must be strain relieved. The cords can be attached to the shelf by using cable ties that are attached around cut outs in the shelf. Connections Connections are made in the terminal board which can be accessed when the cover of the display unit is removed V, power supply (AC/DC) 2. GND, ground 3. +B, connection for ModBus according to RS A, connection for ModBus according to RS SH, shield 6. GND, ground 7. AO1, analogue output 8. AO2, analogue output 9. AIN, (not used in this version) 10. MO1, (not used in this version) 11. MO2, (not used in this version) 12. GND, ground Recommendation for wiring: 24V GND +B -A SH GND AO1 AO2 AIN MO1 MO2 GND Function Cable type 24 V Supply 2-wire, thickness depending on length and load, max. 1,5 mm 2 RS485 Supply the monitor with power from a transformer. +B -A +B -A +B -A -A +B B A RS485 B 54 A 55 2-wire shielded twisted pair, min. 0,1 mm² (LIYCY cable) Connect the monitor to a remote terminal unit using RS485. Connect A on the RTU to -A on the monitor and B to +B. When connecting more than one monitor in series it is important to keep connecting A to A and B to B since crossing them will stop Modbus from working. 4
5 Power supply Transformer sizing The needed size of 24 V AC transformer(s) can be defined by adding up the dimensioning power consumption [VA] of all the components. The transformer power must exceed this. Use only safety isolating transformers. Calculation of the current demand I: where: I = (P1+P2+ +P n ) / U [A] P n is the dimensioned power consumption for each component [VA] U is the voltage (24) [V] If the current demand I exceeds 6 A ( which corresponds to approximately 150 VA for a 24 V AC transformer ), it is necessary to use more transformers to prevent overheating. Supply cable sizing The wire size of the supply cable can be determined by calculating the resistance pr per meter R. The calculation presupposes that a voltage drop of e.g. 2 V is accepted in the supply cable: where: R(per m) = U drop / (I * L) [Ω/m] U drop is the accepted voltage drop (2 V) in the cable [V] I is the current [A] L is the longest distance of supply cables from transformer to a component [m] Power consumption The power consumption for dimensioning supply cables for an UltraLink Monitor is 0,48 VA. If using a power transformer with 75 VA capacity it is possible to connect about 150 UltraLinks together. It is not recommended to use a transformer with a higher capacity than 150 VA! Wire cross section area as a function of resistance per m for copper wire 1,5 1,4 1,3 1,2 1,1 Wire cross section Area [ mm 2 ] 1 0,9 0,8 0,7 0,6 0,5 0,4 0,3 0,2 0, ,05 0,10 Copper Resistance [ Ω/m ] 0,15 0,20 5
6 Display The standard setting for the display shows the air flow in. By pressing the mode button you can change the displayed parameter. The arrow at the bottom of the display indicates the current parameter. Airflow The following parameters can be shown: Air flow () Air flow () Air velocity () Temperature () (Four different set points will be shown but they are not to be used in this version.) Monitor s ID number Status light The status light indicates: No light Flashing light Constant light Function Monitor is turned off A problem has occured Monitor is turned on and functioning as normal Settings When the monitor is connected to Modbus communication there are many settings that can be made. These are the most common: #ADDR Name Type Scale Unit Standard Comment Flow speed Float Flow speed Float 1 m 3 /h Flow speed Float Temperature 16 bit 10 C Unit status 16 bit 1-0 = Normal mode 1 = Reserved for future use 2 = Reserved for future use 3 = Measurement error #ADDR Name Unit Standard Comment 4x002 RS485 Baud Rate Configuration Baud rate 1 4x003 RS485 Parity Configuration Parity 1 4x004 RS485 Stop Bit Configuration No. of stop bits 0 = = = = = Odd; 1 = Even; 1 1 or 2 6
7 Settings for analogue outputs: #ADDR Name Unit Standard Comment 4x400 Analog Output 1 Level Configuration 0 4x401 Analog Output 1 Unit Configuration 0 4x402 Analog Output 1 Temperature Minimum -20 4x403 Analog Output 1 Temperature Maximum 50 4x404 Analog Output 1 Flow Minimum 0 4x405 Analog Output 1 Flow Maximum * 0 = 0-10 V 1 = 10-0 V 2 = 2-10 V 3 = 10-2 V Display: 0 = Flow 1 = Temperature Is always 20 which is depending on dimension see table Flow Maximum Flow maximum Ø * * nom m 3 /h
8 ID-numbers The monitors have from production been given an ID-number between 1 to 255. The given ID-number can be seen on the label on the outside of the box the monitor is delivered in, the ID-number is the same as the three last digits in the serial number. If two or more monitors have the same ID-number it is necessary that each of them get an unique ID-number to allow communication. To change the ID-number of a monitor all other monitors with the same ID must be disconnected. Monitor FTMU Ø125 Serial no Lindab UltraLink #ADDR Name Unit Standard Comment 4x001 ID-number ID-number Troubleshooting If a problem occors the status light will start to flash and an error code will be displayed. Status Airflow Error code Problem Comment Err004 Problems with flow measurement Might be caused by: something blocking the flow sensors an electronic fault the flow sensors are not connected properly into the display unit the sensor body is flawed Err015 UltraLink unknown type Problem with the configuration Err016 Factory data is corrupted Err032 Factory data errors Someone tried to tamper with factory data without having the rights to do this. 8
9 Technical data Power supply 24 (18-32) VAC Cable Max outer diameter 7 mm Power consumption Rating 20 ma 0,48 VA Ambient temperature range -30 to +50 Maximum ambient moisture Connection Cabel Protocol RS485 standard RS485 standard cable, 2-wire shielded twisted pair, min. 0,1 mm² (LIYCY cable) Modbus 95 % RH Output Flow m3/h Velocity range Flow Velocity Temperature 0,5-15 Temperature range -0 to +30 Measurement uncertainty flow Depending on which is the greatest ±5 % or (min. 5 diameters of straight duct before the monitor) Measurement uncertainty temperature 0-50 ±1 Static pressure limit Screws on lid TX12 ±1-750 to Pa Maintenance Normally doesn t require any maintenance. The visible parts of the device can be wiped with a damp cloth. 9
10 Patented Status ON/OFF 2. Display & Sensor Overview Flow sensor Sensor Double USB cable Sensor body Status light Display Double USB port CE-mark Patented Status button Display FTD ON/OFF Micro USB port for PC ON/OFF button Description Application Display parameters The sensor is suitable for measuring air flow and temperature. Design Sensor The sensor consists of a sensor body with Lindab Safe gaskets. Two flow sensors are mounted on the sensor body and can be connected to a Display via an USB cable which is attached to the flow sensors. Air flow direction USB cable Mounting Mount the sensor body into Lindab s air duct sytem according to the mounting instructions for Lindab Safe. It is important that the sensor is mounted with the air flow direction arrow pointing in the direction of the air flow. Display Display FTD The sensor can be connected to a display via the double USB cable on the sensor. Note! The flow sensors are placed at a fixed distance to each other and they shall never be removed. 10
11 ON/OFF The display can be turned on by: By pushing the button to the right By connecting a PC via the micro USB port The display is turned off by: If not connected to a PC and the right button is pressed and held for a minimum of 7 seconds The display is automatically turned off after 5 minutes. Display The standard setting for the display shows the air flow in m 3 /h. By pressing the mode button you can change the displayed parameter. Status The arrow at the bottom of the display indicates the current parameter. The following parameters can be shown: Air flow (m 3 /h) Air flow () Air velocity () Temperature () (Four different set points will be shown but they are not to be used in this version.) Sensor s ID number ON/OFF Status light The status light indicates: No light Flashing light Constant light Function Display is turned off A problem has occured Display is turned on and functioning as normal Power supply The display is powered by two AA batteries which can be changed by opening the lid on the backside of the display. 11
12 Settings When the display is connected to Modbus communication there are many settings that can be made. These are some of the most common: #ADDR Name Type Scale Unit Standard Comment Flow speed Float Flow speed Float 1 m 3 /h Flow speed Float Temperature 16 bit 10 C Unit status 16 bit 1-0 = Normal mode 1 = Reserved for future use 2 = Reserved for future use 3 = Measurement error #ADDR Name Unit Standard Comment 4x002 RS485 Baud Rate Configuration Baud rate 1 4x003 RS485 Parity Configuration Parity 1 4x004 RS485 Stop Bit Configuration No. of stop bits 0 = = = = = Odd; 1 = Even; 1 1 or 2 ID-numbers The displays have from production been given an ID-number between 1 to 255. #ADDR Name Unit Standard Comment 4x001 ID-number ID-number 12
13 Troubleshooting If a problem occors the status light will start to flash and an error code will be displayed. Status ON/OFF Error code Problem Comment Lo Low battery level Battery is getting old. Change the battery Err003 Set point can not be reached Err004 Problems with flow measurement Might be caused by: Err016 Factory data is corrupted something blocking the flow sensors an electronic fault the flow sensors are not connected properly into the display unit the sensor body is flawed Technical data Power supply Battery AA ( 2) Ambient temperature range -30 to +50 Maximum ambient moisture 95 % RH Output Flow m3/h Flow Velocity Temperature Velocity range 0,5-15 Temperature range -0 to +30 Measurement uncertainty flow (min. 5 diameters of straight duct before the sensor) Depending on which is the greatest Measurement uncertainty temperature 0-50 ±1 Static pressure limit -750 to Pa Screws on lid TX12 ±5 ±1 % or Maintenance Normally doesn t require any maintenance. The visible parts of the device can be wiped with a damp cloth. 13
14 At Lindab, good thinking is a philosophy that guides us in everything we do. We have made it our mission to create a healthy indoor climate and to simplify the construction of sustainable buildings. We do that by designing innovative products and solutions that are easy to use, as well as offering efficient availability and logistics. We are also working on ways to reduce our impact on our environment and climate. We do that by developing methods to produce our solutions using a minimum of energy and natural resources, and by reducing negative effects on the environment. We use steel in our products. It s one of few materials that can be recycled an infinite number of times without losing any of its properties. That means less carbon emissions in nature and less energy wasted. We simplify construction
lindab we simplify construction LindabUltraLink Configuration Tool Manual
lindab we simplify construction LindabUltraLink Configuration Tool Manual Contents 1. General Information...2 2. Installation...2 3. Connecting UltraLink to personal computer...2 4. Starting the UltraLink
More informationRST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions
Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND
More informationDXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions
DUAL DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL
More informationRXTP ROOM TEMPERATURE
ROOM TEMPERATURE CONTROLLER WITH PI CONTROL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4
More informationPlease Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT
Installation and Operation Instructions A/CO2-DUCT Series Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT PRECAUTIONS REMOVE POWER BEFORE WIRING. NEVER CONNECT OR DISCONNECT
More informationDSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions
Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND
More informationHPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions
DIFFERENTIAL PRESSURE Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL
More informationRXTH DUAL ROOM SENSOR / SWITCH
DUAL ROOM SENSOR / SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE
More informationOutput Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W
Differential Pressure Sensor (Air) Differential pressure transmitter with 8 selectable ranges 0 to 5/10 V, 4 to 20 ma outputs and Modbus functionality. NEMA 4X / IP65 rated enclosure. For monitoring the
More informationMXIO. Compact I/O module. Summary. Application Compact I/O module for data acquisition and HVAC control systems. Function
MXIO Compact I/O module Summary The MXIO multiple I/O compact module is a microprocessor-controlled, communicative module with the I/O mix optimized for larger HVAC control applications. The module uses
More informationMillenium II +: general characteristics
Millenium II +: general characteristics Starter kit Blind Temperature sensors Special starter kits Bare board Power supply Level detection Local extensions Accessories Standard Expandable Adjacent extensions
More informationDuct humidity and temperature sensor for all HVAC duct applications. Designed for control and monitoring applications.
FTK RS485 Modbus Duct sensor for relative humidity and temperature Data Sheet Subject to technical alteration Issue date: 18052015 Application Duct humidity and temperature sensor for all HVAC duct applications
More informationMODEL: R2K-1 SEN TRONIC AG. R2K Series
1 MODEL: R2K-1 R2K Series /RS-485 CONVERTER Functions & Features Bidirectional converter between and RS-485 used when connecting Modbus RS-485 devices to a PC CE marking Standard: Conforms to, EIA Transmission
More informationRTD-W Installation Instructions
RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485
More informationMPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS
MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS 18 channels for HART / Modbus RTU sensors 2 digital channels 16 math channels 4 relay outputs for alarm or control
More informationSmall distributed I/O module
MLIO Summary Application Function Small distributed I/O module Small I/O module MLIO is a microprocessor-controlled, communiccative module for installation outside the control panel. It is used for topologies
More informationVAT series controller and transmitter. Manual
VAT series controller and transmitter Manual 1. General describe.. 2. Notice for use.. 1 1 3. Panel & connection introduce.. 2 4. Operate introduce.. 5. Application introduce. 6. Communication. 7. Specification..
More informationSATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1
TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT NOTICE... 2 PRODUCT CONFORMITY... 3 WARRANTY AND SAFETY INSTRUCTIONS... 4 1 GENERAL... 5 1.1 SATEL I-LINK 100 MODBUS I/O- CONVERTER... 5 2 SPECIFICATIONS...
More informationISOMETER isoev425 with coupling device AGH420
with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles Preliminary datasheet isoev425_d00126_02_d_xxde/09.2015 with coupling device
More informationRTD-NET Installation Instructions
LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND
More informationJUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet
sales@jumo.co.uk info.us@jumo.net Page 1/9 JUMO PINOS L01 Calorimetric flow sensor Brief description The JUMO PINOS L01 flow sensor serves the measuring and monitoring of flow velocities of water and aqueous
More information1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882
1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature
More informationISOMETER isoev425/isoev425hc with coupling device AGH420
with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles isoev425_d00126_04_d_xxen/06.2018 with coupling device AGH420 Insulation monitoring
More informationPen Drive USB Datalogger!
SINGLE PHASE POWER METER Isolated V/I converter -RS485 Modbus - Datalogger Single-phase power meter RMS, and Voltage/Current Isolated. Signal Converter 1000 VDC / 600 VAC, 10 A AC/DC, Variable frequency
More informationasense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller
Manual for Installation CO 2 asense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller 9 10 2 1 6 10 8 3 4 5 7 Fig. 1 1 Wall plate 2 PCB (Factory supplied mounted
More informationMeasuring transducers MI4x0 series Programmable transducers for RTD sensors MI450
Measuring transducers MI4x0 series Programmable transducers for RTD sensors MI450 o Measuring of resistance of RTD sensors (Pt100, Pt1000, Ni100, Cu10,...) o Accuracy class up to: 0.5 o Programmable input
More informationInsertion Flowmeter for compressed air and gases DN50 - DN700 (2-28 )
The flow meter is based on the thermal mass flow measurement and is ideal for measuring the flow of compressed air and gases in pipes from DN50 (2 ) to DN700 (28 ). With the, the consumption of compressed
More informationRTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions
Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS PRODUCT DESCRIPTION ARTICLE CODES INTENDED AREA OF USE TECHNICAL DATA STANDARDS OPERATIONAL DIAGRAMS WIRING AND CONNECTIONS
More informationFTM84/85 Feature Application. Temperature & Humidity / Flow Measuring Specialist
FTM84/85 Feature Application IP65 protection degree, rugged aluminum case, fit in variety harsh environment Capable of temperature compensation Llinear adjustment air velocity by computer, analogue output
More informationSoft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.
Section 1.0 Introduction 1.1 Important user information... 2 1.2 General... 2 1.3 Manual description...2 Contents Section 2.0 Specification 2.1 General technical data...3 2.2 Dimensions...3 Section 3.0
More informationInstallation manual CF3-D, CF3-D-Disp
Installation manual CF3-D, CF3-D-Disp General Figure 1 The sensor The IAQ-sensor product CF3-D (for mounting in ventilation ducts) is designed to measure carbon dioxide (CO ). Option - TR is prepared for
More informationZone Pressure Touch (ZPT) Sensor - Standard Range
Product Identification BAPI s Touch Pressure Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air
More information2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...
TPR-6 Temperature Protection Relay Instruction Manual Ver. June 1 st 2010 2 Table of Contents 1. TABLE OF CONTENTS 1. Table of Contents... 2 2. Introduction... 3 3. Wiring Diagram... 5 4. Terminals Review...
More informationUSER GUIDE PEL / PEL-M
V2.0.0 (05.09.2014) 1 (6) COMMISSIONING Mounting - The transmitter should be installed above the measuring point to avoid condensation problems. - The duct overpressure is detected by connecting the measuring
More informationTEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL
TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL 1 2 CONTENTS 1. APPLICATION... 5 2. BASIC REQUIREMENTS, OPERATIONAL SAFETY... 5 3. INSTALLATION... 5 3.1. Assembly...5 3.2. Electrical Connections...7
More informationDP DP2500 DP0250
DP7000 - DP2500 DP0250 PB_DP7000_DP2500 - DP0250_07 2016 Field adjustable, multi-range differential pressure transmitters Product Bulletin The Delta Pressure transmitter series of Johnson Controls, with
More informationRS485 MODBUS Module 6RO
Version 2.0 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have
More informationUNIVERSAL CURRENT CONVERTER
UNIVERSAL CURRENT / VOLTAGE CONVERTER AC/DC Current / Voltage Analyzer The is the first CURRENT / VOLTAGE CONVERTER & ANALYZER ALL IN ONE - of the market. It allow you to connect all isolated current sensors.
More informationDIFFERENTIAL PRESSURE TRANSMITTER with MODBUS interface Optional Input module
DIFFERENTIAL RESSURE TRANSMITTER with MODBUS interface Optional Input module DT-MOD (-IN) Summary Each device is individually temperature compensated. Type name (-IN for Input module) (-AZ for autozero)
More informationIntech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.
Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-A8VI Installation Guide. The 2300 series stations are designed to
More informationZone Pressure Touch Sensor - Standard Range
Overview The Zone Pressure Touch (ZPT) Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air velocities/volumes.
More informationDPA+ LCD. Application. Types Available. Differential Pressure Transmitter. Datasheet
DPA+ LCD Differential Pressure Transmitter 703420 Datasheet Subject to technical alteration Issue date: 07.03.2018 A002 Application Differential pressure and volume flow transducer for monitoring differential
More informationLM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket
echnical data sheet Damper actuator for Modbus for adjusting air dampers in ventilation and air conditioning systems in buildings orque 5 Nm Nominal voltage AC/DC 4V Communication via Modbus RU (RS-485)
More informationSidewinder Pumps Inc. AC Timer/Controller
Sidewinder Pumps Inc. AC Timer/Controller Page 1 of 12 Rev 032417 Table of Contents 1. Warnings-------------------------------------------------------------------------------------------------- 3 1.1.
More informationPDS100 Programmable Dispensing System SAFETY INSTRUCTIONS
PDS100 Programmable Dispensing System INSTRUCTION MANUAL SAFETY INSTRUCTIONS Before using any Fluid Metering, Inc. product read the following safety instructions as well as specific product specifications
More informationMIC-2 MKII, Multi-instrument DATA SHEET
MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)
More informationFieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway
Technical Information Fieldgate Intelligent Ethernet/PROFIBUS gateway Application Fieldgate is a system component that provides an independent access route to a PROFIBUS network. It may be used in a variety
More informationMVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions
DIN RAIL ELECTRONIC FAN SPEED Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING
More informationIntech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.
Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-RTD6 Installation Guide. The 2300 series stations are designed to
More informationSDM-6RO. Expansion Module 6 relay outputs. Manufactured for
Version 1.0 5.02.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have
More informationInCos-P Pressure sensor 20 Pa Pa
InCos-P Pressure sensor 20 Pa... 7.500 Pa Electrical pressure / differential pressure sensors 24 VAC/DC supply voltage, 0...10 V / (0) analogue Compact. Easy installation. Universal. Cost effective. Safe.
More informationProgrammable transmitter of temperature, relative humidity and other derived humidity values with 0 to 10 V outputs Instruction Manual
T0210 TRANSMITTER Programmable transmitter of temperature, relative humidity and other derived humidity values with 0 to 10 V outputs Instruction Manual Instruction manual for use of T0210 transmitter
More informationIntech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.
Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-RO4 Installation Guide. The 2300 series stations are designed to
More informationInstallation and User Guide
D5 Installation and User Guide 8-Channel DALI Controller (478) Introduction The 478 is for controlling DALI ballasts, drivers and load interface units (except for the 490 Blinds Controller). Do not connect
More informationMU110-6U. Analog output module 6 channel. User guide
MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)
More informationUSER GUIDE PEL 8K / PEL 8K-M
V2.0.0 (24.10.2014) 1 (7) COMMISSIONING Mounting - The transmitter should be installed above the measuring point to avoid condensation problems. - The duct overpressure is detected by connecting the measuring
More informationMOD-RI Room Interface Modules with Modbus
Product sheet MOD3.00 Type MOD-RI MOD-RI Room Interface Modules with Modbus The MOD-RI are room interface modules designed to provide room control interface for the building management systems. The MOD-RI
More informationAirflow Pressure Sensor
Desigo TRA Airflow Pressure Sensor DXA.S04P1... Airflow Pressure Sensor (APS) is used to measure airflow for room pressurization and fume hood control applications. Differential Pressure (velocity) is
More informationInBin-P Pressure switches from 5 Pa Pa
InBin-P Pressure switches from 5 Pa...100 Pa Electrical, binary pressure or differential pressure switches with adjustable switch activation delay 24 VAC/DC supply voltage, potential free switching contact
More informationMOD-IO9 Modbus Input / Output Modules, Wall Mounted
Product sheet MOD3.9 Type MOD-IO9 MOD-IO9 Modbus Input / Output Modules, Wall Mounted MOD-IO9 and MOD-IO9-AI have been designed to be a compact wall mounted Modbus RTU input and output module. The module
More informationEE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)
is dedicated for reliable monitoring of lubrication, hydraulic and insulation oils as well as diesel fuel. In addition to highly accurate measurement of water activity (a w ) and temperature (T), calculates
More informationUSER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER TPLR-96 Series
USER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER TPLR-96 Series TEMPSEN DEVICES Plot No : 2&3, Balaji Nagar, 4 th Street, Mettukuppam, Thoraipakkam, Chennai-600097 Tele fax : +91-44-24581758,Mobil
More informationMD3. Microstepping Motor Driver Page 1 of 7. Description. Software. Mechanical Drawing. Features
Page 1 of 7 The MD3 is a stepper motor driver with an integrated motion controller that is capable of driving size 14 to 42 stepper motors from 2 to 256 microsteps per step. Peak motor currents are selectable
More informationMiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities
MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs
More informationOutput signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power supply DC V, ±10%, 0.3 W
Duct Sensor CO₂ / Humidity / Temperature For combined measurement of CO₂, relative humidity and temperature in the duct. Dual channel CO₂ technology. The measured values are output via BACnet. NEMA 4X
More informationDP2500 DP0250. Differential Pressure Transmitter. Product Bulletin
DP2500 DP0250 Differential Pressure Transmitter Product Bulletin The DP Low Differential Pressure Transmitter series is an accurate and cost competitive solution for measuring low pressures of air and
More informationRТTH DUAL ROOM SWITCH
DUAL ROOM SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS PRODUCT DESCRIPTION ARTICLE CODES INTENDED AREA OF USE TECHNICAL DATA
More informationMXPLC. Compact PLC process station. Summary. Application HVAC control systems, data acquisition, interfacing 3 rd party systems.
MXPLC Compact PLC process station Summary The MXPLC is a programmable process station with integrated I/O module with the I/O mix optimized for larger HVAC control applications. The multi-interface process
More informationDKG-210 UNIVERSAL INTERNET GATEWAY UNIT
DKG-210 UNIVERSAL INTERNET GATEWAY UNIT AC & DC SUPPLY VERSIONS DESCRIPTION The DKG-210 is designed for internet monitoring and control of industrial devices using different protocols through the RAINBOW
More informationPre-programmed room controller with display and communication
revision 10 2017 RC-C3DOC Pre-programmed room controller with display and communication RC-C3DOC is a complete pre-programmed room controller from the Regio Midi series intended to control heating, cooling
More informationDWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.
Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64
More informationRTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM
RTD-RA Installation Instructions 37.50 LEDS 4 3 2 1 D English Installation Instructions 80.00 80.00 ALL DIMENSIS IN MM C realtime Control Systems A B LEDS 4 3 2 1 D S21 J3 J6 1 2 3 4 J5 5 6 7 0V S1 0V
More informationDuct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates
1 883 1883P01 1883P02 QFM4160 AQF4150 Symaro Duct Sensors for relative humidity and temperature with calibration certificates QFM41 Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 420 ma for
More informationCOUNTIS Ci Notice d utilisation GB Operating instructions Bedienungsanleitung NL Gebruiksaanwijzing
COUNTIS Ci I F Notice d utilisation GB Operating instructions D Bedienungsanleitung NL Gebruiksaanwijzing Istruzioni per l uso SP Instrucciones de servicio P Manual de instruções PRELIMINARY OPERATIONS
More informationUser Interface Terminal for nvent RAYCHEM NGC Systems Installation Instructions DESCRIPTION TOOLS REQUIRED. Nonhazardous Locations LR67275
NGC-UIT-ORD User Interface Terminal for nvent RAYCHEM NGC Systems Installation Instructions DESCRIPTION The nvent RAYCHEM NGC-UIT-ORD is a panel mounted display used in conjunction with other approved
More informationPDS-100 Programmable Dispensing System
PDS-100 Programmable Dispensing System INSTRUCTION MANUAL OVERVIEW The PDS-100 is a precision system capable of dispensing or pumping fluids ranging from 2.5 ul per dispense or 8 ul/min continuous (Single
More informationInstallation Instructions
50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P
More informationOutput Signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power Supply DC V, ±10%, 0.3 W
Duct Sensor CO₂ / Humidity / Temperature Duct air quality sensor for combined detection of CO₂, relative humidity and temperature. Designed for control and monitoring applications. Type Overview Type Output
More informationExtruder Controls ExtruVision S
Extruder Controls ExtruVision S ExtruVision S - The compact system solution for controlling, visualization, and operating extrusion systems Combination of control panel BA Touch with 5.7'' monitor and
More information10 DIGITAL MICRO-PROCESS TOTALIZER METER with ALARMS / ANALOG OUTPUT / PULSE OUTPUT / RS-485. T Total Alarm x 1 + FRONT PANEL & KEY FUNCTIONS
0 DIGITAL MICRO-PROCESS TOTALIZER METER with ALARMS / ANALOG OUTPUT / PULSE OUTPUT / RS-85 + FEATURES! Accuracy: + - 0.00% F.S. High brightness 0." LED; Rate of display range: 0~99999 Rate / Total decimal
More informationUC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display
UC102 Communicative heating controller Summary UC102 is a communicative room heating controller with two inputs and one PWM output for control of a radiator or electrical heater. It can work autonomously,
More informationPU5 5-digit digital panel meter in 96x48 mm (BxH) Universal measuring inputs: Pt100, current, voltage, shunt, thermocouple, resistance
PU5 5-digit digital panel meter in 96x48 mm (BxH) Universal measuring inputs: Pt100, current, voltage, shunt, thermocouple, resistance red display of -9999 99999 digits installation depth: 120 mm without
More informationDigital Indicator Solutions
Digital Indicator Solutions Loop-Powered Attachable Compact Attachable Loop-Powered Smart Compact System Loop-Powered Compact Smart System Intelligent Smart System "Intelligent" Options Dual & Display
More informationLOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E
LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E Table of contents 1. INTRODUCTION...1 2. HARDWARE DESCRIPTION...2 3. INSTALLATION...6 4. CONNECTION...8 5. USER SAFETY AND PROTECTION OF THE EQUIPMENT...11
More informationUSER MANUAL MULTI COLOR TOUCH SCREEN PAPERLESS RECORDER MODEL : ARC2020
USER MANUAL MULTI COLOR MODEL : ARC2020 ACCSYS ELECTRONICS 140/6B, GOLDEN INDUSTRIAL ESTATE, JAWAHARLAL NEHRU ROAD, GERUGAMBAKKAM, CHENNAI - 600122 Tel: 044 60505599 / 60505511 E-mail : sales@accsyselectronics.com
More informationSDM-8AO. Expansion Module 8 analog outputs. Manufactured for
Version 1.0 16.05.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have
More informationMAXIMA+ Series Rotary Level Indicator
MAXIMA+ Series Rotary Level Indicator BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE
More informationPre-programmed room controller with display and communication
revision 01 2014 RC-C3DOC Pre-programmed room controller with display and communication RC-C3DOC is a complete pre-programmed room controller from the Regio Midi series intended to control heating, cooling
More informationRS 485 Mini Modbus 1AO
RS 485 Mini Modbus 1AO Version 1.0 14/08/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained
More informationThis document describes the features and functional specifications of the ECONO3 air conditioner controller.
TITLE : FUNCTIONAL SPECIFICATION FOR ECONO3 COOL REV : 01 DATE : MARCH 13, 2001. 1. INTRODUCTION 1.1 Scope of Document This document describes the features and functional specifications of the ECONO3 air
More informationASTAT XB/XBm Remote Operator
ASTAT XB/XBm Remote Operator User Manual 1 Introduction 1.1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery
More informationAIAS. Technical description
Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains AIAS - and Efficient Heating Demand Products Controlled Tunnel Ventilation Fans 1 / 4 AIAS Technical description 2 / 9 AIAS -
More informationMulti-Point Gas Detection and Control System
Multi-Point Gas Detection and Control System Specifications subject to change without notice. USA 40804 Page of 7 DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control
More informationAdapter Kit - QSI Electronics to TM Meter Installation Instructions
Adapter Kit - QSI Electronics to TM Meter Installation Instructions These installation instructions cover the adapter kit installation of the QSI1, QSI2 and QSI3 versions of communications electronics
More informationMODEL: R3-NE1. Remote I/O R3 Series. ETHERNET INTERFACE MODULE (Modbus/TCP) 27.5 (1.08)
MODEL: R-NE Remote I/O R Series ETHERNET INTERFACE MODULE (Modbus/TCP) 7. (.8) 9 (.9) (.) mm (inch) MODEL: R-NE-[][] ORDERING INFORMATION Code number: R-NE-[][] Specify a code from below for each [] and
More informationProgrammable Digital Controlled DC Power Supplies
Smart choice for power Programmable Digital Controlled DC Power Supplies High Power and Performance for: ATE Bulk Power Production Test OEM Burn-in www.xantrex.com XDC Series Digital Power Supplies 6 kw
More informationUSER S MANUAL. DAS-G01 The Power of Tomorrow
USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 0 USER S MANUAL DAS-G01 The Power of Tomorrow Richmond Heights 2018 Page 1 USER'S MANUAL TABLE OF CONTENTS Page # 1.0 GENERAL INFORMATION...
More informationMulti-Point Gas Detection and Control System
Multi-Point Gas Detection and Control System Specifications subject to change without notice. USA 50729 Page of 9 DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control
More informationPP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions
PP-8516 & PP-8616 Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions Part Number PP-8516 Static Pressure Controller/Transmitter PP-8616 Static Pressure
More informationZone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions
Product Identification BAPI s Touch Low Range Pressure Sensor with Attached Static Pressure Probe is an accurate, rugged and economical solution for measuring and reporting duct/building static pressure,
More information