1 Introduction The following specification describes the Toshiba Super Digital Inverter Heat Pump air conditioning system(s) to be installed at the site below: (ADD SITE NAME) The system(s) shall consist of the following components. It shall be the responsibility of the nominated installer to supply and install these system components in accordance with Toshiba Installation Guidelines. 1) Toshiba Super Digital Inverter external air cooled condensing unit(s) 2) Toshiba Super Digital Inverter compatible type indoor units 3) Interconnecting control wiring from Outdoor Unit(s) to Indoor Unit(s) 4) Toshiba TCC Link Integrated Controls 5) Interconnecting refrigerant pipe work from Outdoor Unit(s) to Indoor Unit(s). System Operating Range Mode of operation Cooling Heating Max. Outdoor Air Temperature Min. Outdoor Air Temperature Max. Indoor Air Temperature Min. Indoor Air Temperature 0 C db C db (562/802) -20 (1104/1404) 0 C db C wb 28-0 C db C wb 15 - Maximum indoor Humidity % RH 80 System Description The installation shall provide an energy efficient R410A Direct Expansion (DX) comfort air conditioning system(s) to the designated area(s)/zone(s) as per the (insert either equipment schedules, drawings, schematics etc) attached, utilising Toshiba Digital Inverter Heat Pump system(s) and shall be installed in accordance with relevant codes of practice and regulations. The system(s) shall comprise of a Toshiba Super Digital Inverter Heat Pump outdoor unit connected to 1 or 2 Super Digital Inverter 4-Way Cassette/Ducted/High-Wall/Ceiling type heat pump indoor fan coil units. It is recommended that the air conditioning installing contractor is a Refcom Certified Toshiba Additions Member. Full details on our website: Customer Support.

2 The system(s) shall be controlled with Toshiba s TCC-Link controls system selected in accordance with the specific control requirements detailed below: (Insert controls requirements) DELETE WARRANTIES THAT DO NOT APPLY All equipment supplied shall have a manufacturer s warranty of at least 3-years on all parts and labour in accordance with Toshiba s warranty and installation guidelines. Equipment to be installed by a Toshiba Registered installer or Qualified or Accredited All equipment supplied shall have a manufacturer s warranty of 5-years on all parts and labour in accordance with Toshiba s warranty and installation guidelines. Equipment to be installed by a Toshiba Qualified or Accredited installer. All equipment supplied shall have a manufacturer s 7 year Total Peace of Mind (TPM) warranty on all parts and labour in accordance with Toshiba s warranty and installation guidelines. Equipment to be installed by a Toshiba Accredited (TPM) installer. Design Criteria The air conditioning system(s) shall be designed and equipment selected to conform to the following design criteria: Internal Conditions Summer 22 C db, 50% RH Winter 21 C db External Conditions Summer 29 C db, 21.5 C wb Winter -5 C db System Specification The system(s) shall be of the Toshiba Super Digital Inverter Heat Pump variety. The system will be capable of both heating and cooling. Each system will use non-ozone depleting HFC refrigerant R410A. These systems can be used for replacement technology, re-using old pipework designed for old R22 & R407C refrigerants* (provided the existing pipework meets currrent legislation regarding the pressure rating of R410A) The system shall allow a user-driven operating environment to be established where users can directly request their own choice of temperature and on/off control etc. The equipment must be suitable for operating on a Volt, single-phase, 50 Hz supply. Outdoor Unit(s) Toshiba Model References Max Piping Length Max Lift Max Drop RAV-SP404ATP-E 30 m 30 m 30 m RAV-SP564ATP-E 50 m 30 m 30 m RAV-SP804ATP-E 50 m 30 m 30 m

3 RAV-SP1104AT-E 75 m 30 m 30 m RAV-SP1404AT-E 75 m 30 m 30 m RAV-SP1104AT8-E* 75 m 30 m 30 m RAV-SP1404AT8-E* 75 m 30 m 30 m RAV-SP1604AT8-E* 75 m 30 m 30 m (* 3 phase unit) The outdoor unit shall be factory assembled, pre-wired, works tested, supplied with a refrigerant pre-charge suitable for 20 m (404 & 562) and 30m ( ) of main piping and complete with fully sealed pipe work connections. It shall not be necessary to include oil traps, sight glasses, or external driers. The access panel shall be easily removable for servicing. The condensing unit shall be fitted with its own electrical compartment with all necessary electrical and control components. The casing shall be manufactured from Galvatite steel plate with a Silky Shade (Munsell 1Y ) electrostatic spray finish protected to IP X4 and shall contain the following components: Inverter Driven Twin Rotary Compressor The compressor shall be of the twin rotary type and driven by a High-Speed Calculation Vector Control Inverter, creating seamless capacity control to match the connected indoor unit(s) cooling or heating demand. Fixed speed compressors of any type are not to be used. The compressor shall be factory mounted on springs and shock-absorbing rubber to minimise vibration. Heat Exchanger The heat exchanger shall be factory constructed of rifled copper tubing, mechanically bonded to aluminium fins. The aluminium fin material shall be coated with a double synthetic hydrophilic coating to prevent corrosion and to assist condensate dispersal. The condensing coil shall have a large surface area to minimize noise and maximise heat transfer. Fan and Motor Each outdoor unit is to be fitted with no more than a single fan. The fan shall be a three-blade, flash-wing, low noise type and shall be both dynamically and statically balanced to produce minimum noise and vibration. The fan shall be directly coupled and driven by a drip proof, permanently lubricated variable speed high-efficiency inverter controlled motor. The outdoor fan speed shall be matched automatically to the energy demands of the heat exchanger. The fan must be able to overcome an external static resistance of 15Pa. Suction Line Accumulator The cylindrical accumulator shall be fabricated from press formed mild steel plates. The accumulator shall have sufficient capacity to prevent any liquid refrigerant from flowing back into the compressor section. Additional Features & Safety Devices: 4-way reversing valve, solenoid valves, pulse-modulating valve, strainer, dryer, service valves with 5/16 gauge ports, thermal protection for compressor, recycling guard timer, over-current protection, compressor suction and discharge temperature sensors, terminals, internal wiring and controls. A pulse-modulating valve will provide capacity control by maintaining suction temperatures of between 1 and 5 K higher than the evaporator inlet temperature additionally, the indoor heat exchanger will be limited to temperatures of no less than 2ºC when cooling. The outdoor unit will automatically defrost in the heating cycle.

4 Indoor Units Each indoor unit shall be from Toshiba s Digital Inverter range of units and must operate on Volt, single-phase, 50 Hz supply taken from the outdoor unit. It must be fully compatible with all TCC-Link network systems, including a self-diagnostic TCC-Link remote controller or TCC-Link central controller with LCD to set mode, room temperature, timer, louvre (as applicable), fan speed and on/off functions. In the event of a fault, an alphanumeric malfunction code will be displayed. An auxiliary 12V DC output is to be available using the CN32 connection. This can be used to operate a ventilation fan via a relay (RBC-SMFI) when the indoor unit is operated. The heat exchanger shall be factory constructed of rifled copper tubing, mechanically bonded to aluminium fins. The aluminium fin material shall be coated with a hydrophilic coating to prevent corrosion and to assist condensate dispersal. The coil shall have a large surface area to minimize noise and maximise heat transfer. A fully insulated condensate drip tray must be fitted, which spans the full width of the coil connections and complete with a drain connection point. All indoor units are provided with a return air temperature sensor. The heat exchanger will be protected against excessive temperatures both low and high. Cold draughts will be avoided when heating by automatically stopping the indoor fan motor when the heat exchanger is too cold. Excess heat is to be dissipated by operating the indoor fan motor for a further 30 seconds after unit shutdown. The evaporator fan shall be of the multi-blade type, performance matched to the coil. The fan shall be statically and dynamically balanced to ensure low noise and vibration free operation and be driven by a permanently lubricated configurable DC motor with speed control and stall protection and fitted with maintenance free sealed-for-life sleeve bearings. 4-Way Cassette RAV-SM564UTP-E RAV-SM804UTP-E RAV-SM1104UTP-E RAV-SM1404UTP-E RAV-SM1604UTP-E The unit will be manufactured from galvanised steel sheet, insulated with closed cell expanded polyurethane foam. Knockouts are to be incorporated into the main chassis of the unit: One to provide a fresh-air intake facility to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space via the unit; Three further discharge ports (2 on one side and 1 on the opposite side) are to enable a maximum of 2 spur ducts to be fitted to supply improved air distribution characteristics in irregular shaped rooms or to provide nominal cooling to adjacent areas. An integral condensate lift pump is provided with a 640mm lift capability from the drain outlet. The cassette fascia panel is to be manufactured from ABS plastic, finished in Moon White (Munsell 2.5GY 9.0/0.5) and complete with four synchronised, motor driven, fully adjustable discharge louvres. Each corner of the panel shall be removable to provide access to the drop rods to enable precise height adjustment. The airflow from the unit is to be configurable from the remote controller to compensate for high ceilings. The central return air grille must be

5 fitted with a washable, long life air filter. An optional kit shall be made available (ref: TCB- BC1602UE) incorporating blockers to allow up to two air discharge ports to be closed to create a 2, or 3-way discharge pattern as required. An optional infrared remote control kit with inclusive temperature sensor (ref: RBC- AX32U(W)-E is to be available). Compact (600 x 600) 4-Way Cassette RAV-SM404MUT-E RAV-SM564MUT-E The unit will be manufactured from galvanised steel sheet, insulated with closed cell expanded polyurethane foam. Knockouts are to be incorporated into the main chassis of the unit: One to provide a fresh-air intake facility to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space; Two further discharge ports (1 on each side) are to enable a maximum of 2 spur ducts to be fitted to supply improved air distribution characteristics in irregular shaped rooms or to provide nominal cooling to adjacent areas. An integral condensate lift pump is to be provided with a 627 mm lift capability from the drain outlet. The cassette fascia panel is to be manufactured from ABS plastic, finished in Moon White (Munsell 2.5GY 9.0/0.5) and complete with four synchronised, motor driven, fully adjustable discharge louvres. Each corner of the panel shall be removable to provide access to the drop rods to enable precise height adjustment. The airflow from the unit is to be configurable from the remote controller to compensate for high ceilings. The central return air grille must be fitted with a washable, long life air filter. An optional infrared remote control kit with inclusive temperature sensor (ref: TCB-AX32E2) is to be available. Slim Ducted RAV-SM404SDT-E RAV-SM564SDT-E The unit will be manufactured from galvanised steel sheet, insulated with closed cell expanded polyurethane foam and supplied complete with front discharge plenums The DC fan motor will be configurable, allowing a maximum external static resistance of 45 Pa to be overcome. Return air is to flow through the lower rear of the unit to allow for the return air to be taken from the conditioned space, or taken from the ceiling void. A knockout is to be provided to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space via the unit. An integral condensate lift pump is to be provided with a 271mm lift capability from the drain outlet. An optional filter kit is to be available and is to include a disposable, long life air filter and shelter plates to convert the return air location from the lower rear, to the back of the unit.

6 An optional infrared remote control kit with inclusive temperature sensor (ref: TCB-AX32E2) is to be available. Ducted RAV-SM406BTP-E RAV-SM566BTP-E RAV-SM806BTP-E RAV-SM1106BTP-E RAV-SM1406BTP-E RAV-SM1606BTP-E The unit will be manufactured from galvanised steel sheet, insulated with closed cell expanded polyurethane foam. The DC fan motor will be configurable, allowing a maximum external static resistance of 100 Pa to be overcome. Return air is to flow through the lower rear of the unit to allow for the return air to be taken from the conditioned space, or taken from the ceiling void. A knockout is to be provided to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space via the unit. An integral condensate lift pump is to be provided with a 271mm lift capability from the drain outlet. An optional filter kit is to be available and is to include a disposable, long life air filter and shelter plates to convert the return air location from the lower rear, to the back of the unit. An optional infrared remote control kit with inclusive temperature sensor (ref: TCB-AX32E2) is to be available. Optional spigot kits are available as follows:- TCB-SF56C6BE (2 x 200 spigots (406 / 566BT)) TCB-SF80C6BE (3 x 200 spigots (806BT)) TCB-SF160C6BE (4 x 200 spigots (1106 / 1406 / 1606BT)) Ceiling Suspended RAV-SM407CTP-E RAV-SM567CTP-E RAV-SM807CTP-E RAV-SM1107CTP-E RAV-SM1407CTP-E RAV-SM1607CTP-E The unit will be manufactured from galvanised steel sheet, insulated with closed cell expanded polyurethane foam and encased in an ABS plastic shell, finished in Shine White. A front mounted, motor driven, fully adjustable louvre is to be fitted. Primary, manually set louvres are to be incorporated to assist the air spread given by the motorised louvre. Return air is to flow through washable, long life air filters mounted within the intake grilles on the underside of the unit. A rear knockout is to be incorporated into the main chassis of the unit to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space via the unit.

7 Optional infrared remote control kit (ref: RBC-AX33CE2) and drain pump (ref: TCB- DP22CE) are to be available. High-Wall RAV-SM407KRTP-E RAV-SM566KRT-E RAV-SM806KRT-E The unit will be manufactured from galvanised steel sheet, insulated with closed cell expanded polyurethane foam and encased in an ABS plastic shell, finished in Pure White. A lower front mounted, motor driven, fully adjustable louvre is to be fitted. Primary, manually set louvres are to be incorporated to assist the air spread given by the motorised louvre. Return air is to flow through washable air filters mounted within the intake grilles on the upper front of the unit. An infra-red controller is to be supplied as standard. Refrigerant Pipework All pipework shall be manufactured using de-oxidised, refrigerant quality copper to BS EN 1057:1996, and must be heat-treated as follows: 6.4mm (1/4 ) OD to 15.9mm (5/8 ) OD - Soft, Half Hard or Hard Tempered The length/height difference parameters and outside diameter of all piping is to be in accordance with the appropriate Toshiba manuals. Interconnecting Controls Wiring The nominated installer shall be responsible for the following interconnecting controls wiring: 3-core & earth = Outdoor unit to Indoor Unit (1, 2, 3) 2-core, non-polar = Indoor units to Remote Controller (A, B) 2-core, twisted, screened, non-polar = External Controls Network (U3, U4 and/or X, Y) All electrical wiring, bonding and earthing shall be in accordance with the current edition of BS 7671: 2008 (IEE Wiring Regulations 17 th Edition). The voltages stated are EC harmonised voltages, but the equipment shall be suitable for volts single phase. Controls

8 The Toshiba Super Digital Inverter Heat Pump(s) shall be complete with the following TCC- Link controls. Simplified TCC-Link Remote Controller RBC-AS41E The remote controller(s) shall be surface mounted and hard wired to the indoor unit(s) via the AB connections, to provide the user with either local individual control of the air-conditioned space, or group control of upto 8 indoor units. The controller shall be manufactured in ABS plastic with a liquid crystal display (LCD). A temperature sensor is to be incorporated within the casing to allow the user to set the sensing point at the controller, or at the indoor unit. The controller shall display an alphanumeric fault code in the event of system malfunction. The controller shall provide control of the following primary functions: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louvre position (where applicable). Filter check. Test run (heating & cooling). Standard TCC-Link Remote Controller RBC-AMT32E The remote controller(s) shall be surface mounted and hard wired to the indoor unit(s) via AB connections, to provide the user with either local individual control of the air-conditioned space, or group control of up to 8 indoor units. The controller shall be manufactured in ABS plastic with a liquid crystal display (LCD). A temperature sensor is to be incorporated within the casing to allow the user to set the sensing point at the controller, or at the indoor unit. The controller shall enable the user to interrogate the system and display an alphanumeric fault code in the event of system malfunction. The controller shall be able to provide control or indicate status of the following functions: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louvre position (where applicable). Individual Louvre Control (where applicable). Filter check. Test run (heating & cooling). Minimum and maximum temperature settings in each mode Dead band between heating and cooling. Stratification control.

9 Central control address. Auto-restart. Temperature sensor in use. High ceiling compensation. Elapsed timer lock. Sensor data available from all associated indoor and outdoor units Integral elapsed timer Standard TCC-Link Remote Controller with 24 Hour, Seven Day Timer RBC-AMS41E The remote controller(s) shall be surface mounted and hard wired to the indoor unit(s) via the AB connections, to provide the user with either local individual control of the air-conditioned space, or group control of up to 8 indoor units. The controller shall be manufactured in ABS plastic with a liquid crystal display (LCD). A temperature sensor is to be incorporated within the casing to allow the user to set the sensing point at the controller, or at the indoor unit. The controller shall enable the user to interrogate the system and display an alphanumeric fault code in the event of system malfunction. The controller shall be able to provide control or indicate status of the following functions: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louvre position (where applicable). Filter check. Test run (heating & cooling). Save mode (dependant on model & system) Schedule 7 day timer operation (Operation time, start/stop, temp setting & restriction) Timer operation (Countdown timer) Minimum and maximum temperature settings in each mode Dead band between heating and cooling. Stratification control. Central control address. Auto-restart. Temperature sensor in use. High ceiling compensation. Elapsed timer lock. Sensor data available from all associated indoor and outdoor units Integral elapsed timer The Lite Vision Plus Remote Controller RBC-AMS51E-ES The remote controller(s) shall be surface mounted and hard wired to the indoor unit(s) via the AB connections, to provide the user with either local individual control of the air-conditioned

10 space, or group control of up to 8 indoor units. The controller shall be manufactured in ABS plastic with a liquid crystal display (LCD). A temperature sensor is to be incorporated within the casing to allow the user to set the sensing point at the controller, or at the indoor unit. The controller shall enable the user to interrogate the system and display an alphanumeric fault code in the event of system malfunction. The controller shall be able to provide control or indicate status of the following functions: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louvre position (where applicable). Filter check. Test run (heating & cooling). Save mode (dependant on model & system) Schedule 7 day timer operation (Operation time, start/stop, temp setting & restriction) Timer operation (Countdown timer) Minimum and maximum temperature settings in each mode Dead band between heating and cooling. Stratification control. Central control address. Auto-restart. Temperature sensor in use. High ceiling compensation. Elapsed timer lock. Sensor data available from all associated indoor and outdoor units Unique Energy Saver Function Menu based operational strategy Weekly timer function with multi programmable settings Fully compatible with Toshiba DI / SDI and VRF systems Programmable button restrictions Individual registering of the room name Illuminated display Option to display service providers name and telephone number Full ventilation options when used in conjunction with Toshiba s new VN-M air to air heat exchanger unit(s) TCC-Link Weekly & Schedule Timer TCB-EXS21TLE A weekly timer shall be connected either to the central controller and/or each standard remote controller. It should be connected via a dedicated 4-core lead supplied with the timer. The weekly timer shall be surface mounted and manufactured in ABS plastic with a liquid crystal display. The controller shall provide up to 3 on/off periods per day in a 7-day cycle with a day omit capability. In addition the controller shall be able to auto-restart the whole system after a power failure and have 100 hours backup memory.

11 TCC-Link Central Controller TCB-SC642TLE2 TOSHIBA A central controller shall be surface mounted and hard wired to the indoor unit(s) via the U3, U4 network (made available by the use of a TCB-PCNT30TLE), to provide the user with individual control of up to 64 master indoor units. The controller shall be manufactured in ABS plastic with a liquid crystal display. It shall be supplied from a v AC 50Hz power source. A maximum of 10 central control devices must be able to be fitted to a single control network (U3, U4). It must be possible to switch the controller on and off from a remote source via a volt-free contact connected across the A series terminals. The B series terminals must provide operation and general fault outputs. The controller shall enable the user to interrogate the system and display an alphanumeric fault code for each control group in the event of malfunction. The central controller shall display status and provide control of the following primary functions for each master indoor unit: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louvre position (where applicable). Filter check. Automatic or manual central control addressing with the further option to provide this from the controller. In addition the central controller shall facilitate the use of remote controllers (RBC-AMT32E, RBC-AMS41E, RBC-AMS51E-ES or RBC-AS41E) to provide the user with localised control of the air-conditioned space. When remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). The central controller can restrict the operation of local controllers, preventing changes being made to: On /off settings. On/off, mode and temperature settings. Mode and temperature settings. Mode settings. When used in conjunction with a weekly timer (TCB-EXS21TLE) the following configurable relationships must be available: Indoor units are turned on/off with the weekly timer and remain open to local override for one time period. Indoor units are turned off with the weekly timer and rely on local override to operate for one time period. Indoor units have on/off control disabled with the weekly timer and rely on local override to operate for one ON time period. Indoor units are stopped and have on/off control disabled with the weekly timer and rely on local override to operate for one ON time period. Indoor units have all functions disabled with the weekly timer and rely on local override to operate for one ON time period.

12 Indoor units are stopped and have all functions disabled with the weekly timer and rely on local override to operate for one ON time period. TCC-Link Central Compliant Manager Controller (Low Specification Model) BMS-CM1280TLE A central controller shall be surface mounted and hard wired to the outdoor unit(s). The compliant manager is capable of controlling 128 indoor units from a single location. The device has the facility to set all of the operating parameters for individual or zoned indoor units, whether they are VRF or individual spilt systems. It is also capable of displaying individual fault codes for any units on the network. The controller is normally used on an installation where there are multiple indoor units in one location. It gives the ability to link multiple refrigerant systems together for time clock control and to give an indication of any faults within the systems. There are auxiliary inputs for on/off control and relay outputs for remote run and fault indication. It is possible to connect up to 10 central controllers on one network, which controls up to 128 master indoor units from multiple locations. The controller requires a v AC 50Hz power source which connects directly to the mains input terminals on the rear of the device. The network cable terminates at the U1/U3 and U2/U4 connections on the rear of the device. Terminals COM-DI, D11, D12 and D13 are used to remotely operate all of the connected indoor units. Solution Components Network Adaptor TCB-PCNT30TLE2 Network adaptors will be required for each Master indoor unit when the central controller is used in conjunction with DI/SDI split systems. TCC-Link Central Compliant Manager Controller High Specification Model BMS-SM1280ETLE A central controller shall be surface mounted and hard wired to the outdoor unit(s). The compliant manager is capable of controlling 128 indoor units from a single location. The device has the facility to set all of the operating parameters for individual or zoned indoor units, whether they are VRF or individual spilt systems. It is also capable of displaying individual fault codes for any units on the network. The controller can be remotely connected to via a PC and all functions can be controlled via Internet Explorer. This controller can also be linked to energy monitoring relay interfaces for the collection of data for energy billing. is normally used on an installation where there are multiple indoor units in one location. The controller can also be linked to the didigital input output module for the interface to other systems.

13 The compliant manager has some advanced functions different users can be configured to give restricted access. The controller has an advanced time clocking function to give the building owner flexibility. The controller has a return back function, which returns the units setting to a pre-determined setting after an amount of time. All of these functions are accessed via the Web Interface. It gives the ability to link multiple refrigerant systems together for time clock control and to give an indication of any faults within the systems. There are auxiliary inputs for on/off control and relay outputs for remote run and fault indication. It is possible to connect up to 10 central controllers on one network, which controls up to 128 master indoor units from multiple locations. The controller requires a v AC 50Hz power source which connects directly to the mains input terminals on the rear of the device. The network cable terminates at the U1/U3 and U2/U4 connections on the rear of the device. Terminals COM-DI, D11, D12 and D13 are used to remotely operate all of the connected indoor units. Solution Components Network Adaptor Toshiba Model Reference TCB-PCNT30TLE2 Network adaptors will be required for each Master indoor unit when the central controller is used in conjunction with DI/SDI split systems. Energy Monitoring Relay Interface Toshiba Model Reference BMS-IFWH5E2 The energy monitoring relay interface connects to the RS485 Network and provides a means of interface to the pulse power meters. Up to eight power meters can be connected to each relay interface. Digital Input/Output Relay Interface Toshiba Model Reference BMS-IFDD03E The D/I module connects to the RS485 network and provides 8 inputs and 4 outputs, which could be used to interface a fire alarm system or a room occupancy sensor. The D/I module output could be used as a means of remote fault indication to another system. To facilitate the connection of Digital Inverter split systems to a U3/U4 network, a network adaptor must be fitted to each master indoor unit. Fault Monitoring & Control Interface

14 RBC-FDP3-PE Fault detection and control is to be provided via the AB network with, or without a remote controller. Each FDP3 detects any fault generated by the system and provide an output for appropriate action to be taken by the user. Red and green LEDs are to be fitted to the unit to indicate the fault/no fault condition. The detection of a fault code must illuminate the red LED and close the internal volt-free contacts. A locking function can be initiated to provide pre-set conditions of: Cooling 19ºC; Auto 21ºC; Heat 23ºC. These pre-sets are to be selectable by switches on the FDP3 unit. It must be possible to control 8 indoor units with a single FDP3 and connect 16 FDP3 units together on a D-Bus network to allow a single remote controller to group control up to 128 indoor units. Run and standby control of two groups of indoor units is to be provided. In the event of a fault on the running group, both groups will be activated. The FDP3 is able to be configured for load sharing and customised control options available from Toshiba. Fault Monitoring & BMS Control Interface RBC-FDP3-PE Fault detection and BMS control is to be provided via the AB network with, or without a remote controller. Each FDP3 detects any fault generated by the system and provide an output for appropriate action to be taken by the user. Red and green LEDs are to be fitted to the unit to indicate the fault/no fault condition. The detection of a fault code must illuminate the red LED and close the internal volt-free contacts. BMS control for temperature, fan speed, mode, louvre, on/off and remote controller lock is to be provided by variable voltage, or resistance inputs. It must be possible to control 8 indoor units with a single FDP3 and connect 16 FDP3 units together on a D-Bus network to allow a single remote controller to group control up to 128 indoor units. Run and standby control of two groups of indoor units is to be provided. In the event of a fault on the running group, both groups will be activated. The FDP3 must also be able to be configured for load sharing. Further customisation is to be available from Toshiba to fulfil specific end user requirements. Start/Stop and Fault Interface TCB-IFCB-4E Each indoor unit (master unit if grouped) is to be fitted with an interface to allow each indoor unit to be externally switched on and off by means of any volt-free external terminals. The interface shall be linked to the indoor unit using CN61 on the PCB. This device must also have the capability of providing a positive indication of the operation of the indoor unit and signal any errors (system and indoor unit stopping faults) via externally fitted volt-free contacts. The interface shall be fitted in position near the relevant indoor unit. External switching components can include: Time switch

15 BMS Passive infra-red occupation sensor Auto restart Frost thermostat Fire alarm Lon Works Interface TCB-IFLN642TLE A Lon Works Interface shall be hard wired to the U3 & U4 network, to enable the user to control up to 64 indoor units. Multiple interfaces may be connected to a Lon Works network to enable the user to monitor and adjust indoor units alongside any other integrated building services from a single PC. The interface shall enable the PC to display status, diagnostics by unit number and provide control of the following primary functions for each master indoor unit: - Mode of Operation (Auto, Cool, Heat, Fan Only) Temperature Set Point (18 C to 29 C) Fan Speed (High, Medium, Low & Auto) Louvre Position (Where applicable) On/Off The interface shall permit the user to access the control of the system remotely via the use of a modem connection. In addition the interface shall facilitate the use of Remote Controllers (RBC-AMT32E, RBC-AMS41E, RBC-AMS51E-ES or RBC-AS41E) to provide the user with local control of the air-conditioned space. When remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). Trend BMS Interface RBC-LG1/LTX-21 TCB-PCNT20E A combination of a Lon Works interface and RealTime Controls LTX-21 shall allow the Toshiba air conditioning systems to communicate with a Trend BMS. An RBC-LG1/LTX-21 combination shall be hard wired to each indoor unit via the XY terminals on each protocol converter (TCB-PCNT20E), to enable the user to individually control up to 16 master indoor units when connected to a single system. Each master indoor unit is to be fitted with a protocol converter. Multiple interfaces may be connected to a Trend network to enable the user to monitor and adjust indoor units alongside any other integrated building services from a single PC. The LTX-21 connects directly to the supervisor port on a 2 series Trend outstation to permit all functions and settings to be modified. All of the system fault codes can be passed back through to the BMS that will allow the faults to be managed by the BMS alarm supervisor.

16 The interface shall permit the user to access the control of the system remotely via the use of a modem connection. In addition the interface shall facilitate the use of Remote Controllers (RBC-AMT32E, RBC-AMS41E, RBC-AMS51E-ES or RBC-AS41E) to provide the user with local control of the air-conditioned space. When remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). Cylon (or other Modbus compatible) BMS Interface RBC-LG1/LTX-51 TCB-PCNT20E This combination of a Lon Works interface and RealTime Controls LTX-51 shall allow the Toshiba air conditioning systems to communicate with a Cylon BMS. An RBC-LG1/LTX-51 combination shall be hard wired to each indoor unit via the XY terminals on each protocol converter (TCB-PCNT20E), to enable the user to individually control up to 16 master indoor units when connected to a single system. Each master indoor unit is to be fitted with a protocol converter. Multiple interfaces may be connected to a Cylon network to enable the user to monitor and adjust indoor units alongside any other integrated building services from a single PC. The LTX-51 connects directly to the modbus port on a UCC4 to permit all functions and settings to be modified. All of the system fault codes can be passed back through to the BMS that will allow the faults to be managed by the BMS alarm supervisor. The interface shall permit the user to access the control of the system remotely via the use of a modem connection. In addition the interface shall facilitate the use of Remote Controllers (RBC-AMT32E, RBC-AMS41E, RBC-AMS51E-ES or RBC-AS41E) to provide the user with local control of the air-conditioned space. When remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). Windows Package & Windows Gateway RBC-WP1-PE TCB-IFLN642TLE TCB-PCNT20E A Windows Package (RBC-WP1-PE) shall be used in conjunction with a Gateway (TCB- IFLN642TLE). Each Gateway shall have the capability of individually controlling up to 64 master indoor units. Up to 16 Gateways can be connected to each Windows package. Each Windows Gateway is then linked to the PC via the AB terminals. If Digital / Super Digital Inverter units are to be added a Network Adaptor (TCB-PCNT30TLE) is required for each master indoor unit with the exception of the High Wall models. The Windows Package shall enable the user to control up to 1024 individual indoor units, and via the Gateway be capable of adjusting, managing and displaying all the following control functions: Mode of Operation (Auto, Cool, Heat, Fan Only)

17 Temperature Set Point (18 C to 29 C) Fan Speed (High, Medium, Low & Auto) Louvre Position (Where applicable) On/Off Fault Code Diagnostics Sensor Data Indoor Unit Locked Off On/Off Control Only Multiple Time Scheduling In addition local control may be provided to any or all zones by the use of Remote Controllers (RBC-AMT32E, RBC-AMS41E, RBC-AMS51E-ES or RBC-AS41E). When remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). The controls software shall also enable the user to display unit locations via site specific floor plans and transmit system alarms via the following media types: - Fax, SMS, Modems, and Pager. To enable the Windows Package to be installed the following minimum system requirements shall be provided either by the end-user or the installer: - PIV or Greater Processor 512MB RAM Hard Drive with 50MB Free Space 16bit High Colour 800 x 600 SVGA or Greater Display (Not shared graphics card) Win NT, Version 4.0 or Later (Service Pack 3.0 or Greater) Win 2K Win XP (Not Suitable for Windows Vista) Internet Kit RBC-IK1-PE An Internet kit shall be used in conjunction with the Windows Package and Lonworks Interface(s) to provide the following capabilities: Remote computer access to the server where the Windows Package is installed to allow up to 5 users at any one time to view, or change data using Microsoft Internet Explorer. Two levels of control: o Monitoring o Full Control Immediate access to operating conditions and historical performance, facilitating rapid response to customer/user enquiries.

TOSHIBA AIR CONDITIONING

TOSHIBA AIR CONDITIONING Introduction The following specification describes the Toshiba Digital Inverter Heat Pump air conditioning system(s) to be installed at the below site: (ADD SITE NAME) The system(s) shall consist of the

More information

TOSHIBA AIR CONDITIONING

TOSHIBA AIR CONDITIONING Introduction The following specification describes the Toshiba Super Digital Inverter Heat Pump air conditioning system(s) to be installed at the site below: (ADD SITE NAME) The system(s) shall consist

More information

Technology is nothing without control

Technology is nothing without control 46 Technology is nothing without control An innovative and complete range of integrated controls for application in the Toshiba VRF MiNi-SMMS, SMMS, SHRM systems ensures maximum comfort and excellent performance

More information

PRODUCT UPDATE 2011 Smart Manager BMS-SM1280HTLE. Note: Computer NOT supplied

PRODUCT UPDATE 2011 Smart Manager BMS-SM1280HTLE. Note: Computer NOT supplied PRODUCT UPDATE 2011 Smart Manager Toshiba Air Conditioning are pleased to introduce a new product into our current range of control options. New The BMS-SM1280HTLE Smart Manager The BMS-SM1280HTLE has

More information

Pocket Quick Reference Guide On the TOSHIBA

Pocket Quick Reference Guide On the TOSHIBA Pocket Quick Reference Guide On the TOSHIBA RBC-AMS51E / RBC-AMS54E Remote Controller Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity

More information

Technology that works fast. Controls for every need

Technology that works fast. Controls for every need Technology that works fast Controls for every need Toshiba Air Conditioning offer a number of local control options that can be used to control a single indoor unit, or up to 8 indoor units. It is possible

More information

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller Pocket Quick Reference Guide On the TOSHIBA RBC-AMS51E Remote Controller Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity of data

More information

Temperature controller Ducted systems

Temperature controller Ducted systems 2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR ARYG72LHTA ARYG90LHTA OUTDOOR AOYG72LRLA AOYG90LRLA DR_AR012EF_03 2017.04.07 Notices: Product specifications and design are subject to change

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers DATA CENTER COOLING EXPERTISE Data Center managers have unique needs. Nortek Air Solutions listens

More information

AIR COOLED HEAT PUMPS WITH SCREW COMPRESSORS AND AXIAL FANS

AIR COOLED HEAT PUMPS WITH SCREW COMPRESSORS AND AXIAL FANS PAH 2802 T K AIR R-407C R-134a Series PAH... T K from 205 to 778 kw - 2 circuits The air cooled heat pumps of PAH.T series are designed for outdoor installation and are particularly suitable for industrial

More information

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH 1 Chilled and Hot Water Fan Coil Low Static 4-Pipe Nominal Size:

More information

7. PCB AND FUNCTIONS

7. PCB AND FUNCTIONS Contents. PCB AND FUNCTIS. Outdoor Unit Control PCB... - -. Outdoor Unit Control PCB CR-C0DXH... - -. Outdoor Unit FAN PCB FAN-C00DXH... - -. Outdoor Unit FAN PCB FAN-C0DXH... - -. Outdoor Unit Filer PCB

More information

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display UC102 Communicative heating controller Summary UC102 is a communicative room heating controller with two inputs and one PWM output for control of a radiator or electrical heater. It can work autonomously,

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone

PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 0 Jl. Malibu Raya, Cengkareng Jakarta Barat 70 Indonesia Phone + 4 4 www.climanusa.com Marketing features prominent presence on the world

More information

2014 / 15 CONTROLS. for TOSHIBA air conditioning applications

2014 / 15 CONTROLS. for TOSHIBA air conditioning applications 2014 / 15 CONTROLS for TOSHIBA air conditioning applications CONTROLS Local controls TOSHIBA offer a number of local control products that can be used to control a single indoor unit, or group of up to

More information

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat Features Modern Appearance Stylish rotary dial and buttons Large LCD with backlight Support Modbus RTU protocol Support standalone operation

More information

SUPERVISION AND CONTROL FOR HYDRONIC TERMINAL UNITS

SUPERVISION AND CONTROL FOR HYDRONIC TERMINAL UNITS SUPERVISION AND CONTROL FOR HYDRONIC TERMINAL UNITS Smart design LCD display Humidity sensor Plug & Play connections Weekly and daily programs Flexible configuration Service tool available MODBUS RTU:

More information

INTERFACE SPECIFICATION

INTERFACE SPECIFICATION INTERFACE SPECIFICATION MODBUS CONVERTOR UTY-VMGX PART NO. 9708438030 Modbus is registered trademarks of Schneider Electric SA. LONWORKS is registered trademark of Echelon Corporation in the United States

More information

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN IntesisBox HS-RC-MBS-1 v.0.1 Modbus RTU (EIA-485) Interface for Hisense air conditioners. Compatible with commercial line of air conditioners commercialized by Hisense. User Manual Issue Date: 12/2017

More information

1.5 to 5 Tons INDOOR COILS C35. Upflow - Cased and Uncased PRODUCT SPECIFICATIONS C A - 2 F - 1 MODEL NUMBER IDENTIFICATION FEATURES

1.5 to 5 Tons INDOOR COILS C35. Upflow - Cased and Uncased PRODUCT SPECIFICATIONS C A - 2 F - 1 MODEL NUMBER IDENTIFICATION FEATURES INDOOR COILS C35 PRODUCT SPECIFICATIONS Upflow - Cased and Uncased Bulletin No. 20666 February 208 Supersedes November 206.5 to 5 Tons MODEL NUMBER IDENTIFICATION Unit Type C = Indoor Coil = Upflow Series

More information

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity ENVIRONMENTALLY SOUND REFRIGERANT C4H(5, 7) Product Specifications HIGH EFFICIENCY 15 and 17 TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 2, 3, 4, and 5 TONS SPLIT SYSTEM 208 / 230 Volt,

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Filter Fan Unit LIGHT

Filter Fan Unit LIGHT Filter Fan Unit LIGHT Type LIGHT EC Technical Concept Technical Concept Filter Fan Unit LIGHT Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean air to individual

More information

AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS

AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS RAH 913 K AIR R-407C R-134a Series RAH... from 307 to 1879 kw - from 1 to 4 circuits The air cooled chillers of RAH series are extremely compact units so to reduce the installation spaces and weights.

More information

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM RTD-RA Installation Instructions 37.50 LEDS 4 3 2 1 D English Installation Instructions 80.00 80.00 ALL DIMENSIS IN MM C realtime Control Systems A B LEDS 4 3 2 1 D S21 J3 J6 1 2 3 4 J5 5 6 7 0V S1 0V

More information

STRA-17 Room controller. Installation and maintenance manual. Content

STRA-17 Room controller. Installation and maintenance manual. Content Content Installation preparations... Wiring diagram...3 Display handling...5 Technical data...6 Configuration...7 Operating modes...7 Controller modes...7 Activation operating modes...7 Control states...8

More information

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting G2522en Heating controller Installation Instructions RVL470 1 Installation 1.1 Place of installation In a dry room, e.g. the boiler room Mounting choices: In a control panel (on the inner wall or on a

More information

Super Digital Inverter / RAV Series 2010 Technical training

Super Digital Inverter / RAV Series 2010 Technical training Super Digital Inverter / RAV Series 2010 Technical training 1 PRESENTATION CONTENT Features Operation Safeties 2 FEATURES CONTENT System Line up & Model Numbers System Performance Operating envelope Electrical

More information

Supplementary operating instructions for your air curtain system Controller TMC 500

Supplementary operating instructions for your air curtain system Controller TMC 500 Supplementary operating instructions for your air curtain system Controller TMC 500 (Translation of the original) Serial number: Year: Please quote this number when contacting customer service! Date 08.04.2016

More information

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours!

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours! Data sheet MK 20 GR Customized solution or off-the-shelf: The choice is yours! MK20-GR data sheet Looking for a quick and reliable solution? Then rely on our standard products: Our universal controls provide

More information

Room controller STRA-17

Room controller STRA-17 Room controller STRA-17 Application example Room 2 Room 3 Room 4 SCADA EXOline alt. RS485 Modbus Transformer STRZ-24 (Required component) STRA-17 is a preprogrammed room controller intended to control

More information

Ceiling Concealed Split System C Series

Ceiling Concealed Split System C Series Brochure AP MCC C 07A Ceiling Concealed Split System C Series features: Microprocessor Controlled ith the microprocessor controlling the operation, the MCC model can offer comfortable room conditions according

More information

Owner s Manual RBC-AX32U(W)-E RBC-AX32U(WS)-E AIR CONDITIONER (SPLIT TYPE) Wireless remote controller kit. Model name: English.

Owner s Manual RBC-AX32U(W)-E RBC-AX32U(WS)-E AIR CONDITIONER (SPLIT TYPE) Wireless remote controller kit. Model name: English. AIR CDITIER (SPLIT TYPE) Owner s Manual Wireless remote controller kit Model name: RBC-AX3U(W)-E RBC-AX3U(WS)-E Generic model name RBC-AX3U(W)-E Wireless remote controller model name WH-LSE Signal receiving

More information

RTD-NET Installation Instructions

RTD-NET Installation Instructions LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND

More information

IntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners.

IntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners. IntesisBox FJ-RC-MBS-1 v.2.5 Modbus RTU (EIA-485) Interface for Fujitsu air conditioners. User Manual Issue Date: 12/2017 r1.9 EN Order Codes: FJ-RC-MBS-1: Modbus RTU Interface for Fujitsu air conditioners

More information

Temperature controller Multi-zone ducted systems

Temperature controller Multi-zone ducted systems 2 727 emperature controller ulti-zone ducted systems ulti-zone model with up to six zone outputs RRV856 ultifunctional controller used for central control of ducted HVAC systems in combination with QAX850

More information

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions Controls Guide for XeteX Units Beyond meeting the typical specification and performance requirements, controlling the equipment is usually the most important success factor for HVAC projects. XeteX provides

More information

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication X X testregistrierung Control system Type Central BMS interface DCP-FSL II-Stand-alone Pressure independent control valve Straight-way valve Modular, stand-alone room control system, specially for decentralised

More information

Slim Ducted type. Contents MMD-AP 4SPH2UL MMD-AP0094SPH2UL MMD-AP0124SPH2UL MMD-AP0154SPH2UL MMD-AP0184SPH2UL

Slim Ducted type. Contents MMD-AP 4SPH2UL MMD-AP0094SPH2UL MMD-AP0124SPH2UL MMD-AP0154SPH2UL MMD-AP0184SPH2UL E5-3I D-AP 4SP2U Slim Ducted type D-AP0074SP2U D-AP0094SP2U D-AP024SP2U D-AP054SP2U D-AP084SP2U Contents. Specifications 2. Dimensions 3. Center of gravity 4. Piping diagram 5. Wiring diagram 6. Electrical

More information

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification General The VT76xxW series is designed for single-stage and multi-stage control of water source heat pumps with dedicated

More information

R410A D2D_AU019E/

R410A D2D_AU019E/ R41A 2. : AUU18RCLX AUU24RCLX D2D_AU19E/ 27.6.11 2-1. FEATURE MODELS : AUU18RCLX / AOU18RLX AUU24RCLX / AOU24RLX FEATURES Easy maintenance The control box is easily accessible for maintenance work Wide

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

Technical Concept. Filter Fan Unit RETURN AIR. Type RA-AC Type RA-EC

Technical Concept. Filter Fan Unit RETURN AIR. Type RA-AC Type RA-EC Technical Concept Filter Fan Unit RETURN AIR Type RA-AC Type RA-EC Filter Fan Unit RETURN AIR Technical Concept Product Description Technical Data M+W Products Filter Fan Units RETURN AIR (FFU-RA) are

More information

Technical Concept. Filter Fan Unit LIGHT. Type LIGHT AC Type LIGHT EC

Technical Concept. Filter Fan Unit LIGHT. Type LIGHT AC Type LIGHT EC Technical Concept Filter Fan Unit LIGHT Type LIGHT AC Type LIGHT EC Filter Fan Unit LIGHT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean air

More information

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors. Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling

More information

Pre-programmed room controller with display and communication

Pre-programmed room controller with display and communication revision 01 2014 RC-C3DOC Pre-programmed room controller with display and communication RC-C3DOC is a complete pre-programmed room controller from the Regio Midi series intended to control heating, cooling

More information

1.5 to 5 Tons INDOOR COILS CX35. Upflow - Cased - R-410A PRODUCT SPECIFICATIONS C X A - 6 F MODEL NUMBER IDENTIFICATION FEATURES

1.5 to 5 Tons INDOOR COILS CX35. Upflow - Cased - R-410A PRODUCT SPECIFICATIONS C X A - 6 F MODEL NUMBER IDENTIFICATION FEATURES INDOOR COILS CX35 Upflow - Cased - R-40A PRODUCT SPECIFICATIONS Bulletin No. 0668 November 06 Supersedes September 05.5 to 5 Tons MODEL NUMBER IDENTIFICATION C X 35-36 A - 6 F Unit Type C = Indoor Coil

More information

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS HV-STYLVENT. Wall or window extract fans. Elegant design harmonising with any environment

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS HV-STYLVENT. Wall or window extract fans. Elegant design harmonising with any environment WALL OR WINDOW EXTRACT FANS Series Complete range of axial flow fans for wall or window mounting applications. All the fans are supplied with tough ABS plastic grilles, shutter and single phase V- 5Hz

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Room Temperature Controller

Room Temperature Controller 3 023 Room Temperature Controller for four-pipe fan coil units RCC30 Outputs for on / off valve actuators Outputs for three-speed fan Control depending on room or return air temperature Operating modes:

More information

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN Tracer Controls Tracer Unitary Controller 7 April 2003 BAS-PRC012-EN Introduction The Tracer unitary controller provides digital control that is similar to that of a wall thermostat. It supports the following

More information

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS. Wall or window extract fans HV-STYLVENT. Elegant design harmonising with any environment

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS. Wall or window extract fans HV-STYLVENT. Elegant design harmonising with any environment WALL OR WINDOW EXTRACT FANS HV-STYLVENT Series 688 679 Shutter Reversible Natural ventilation position Complete range of axial flow fans for wall or window mounting applications. All the fans are supplied

More information

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs revision 01 2015 RCF-230CAD Communicating room controller for fan-coil applications with two analogue 0...10 V DC outputs RCF-230CAD intended to control heating and/or cooling in 2- or 4-pipe installations.

More information

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB User Guide Multipipe Units CMAA / RTMA CNT-SVU004B-GB USER GUIDE WARNING Supply the unit at least 24 hours before the initial startup to heat the compressor oil. In conditions of low water temperature,

More information

Airedale International Air Conditioning Limited. Leeds Road, Rawdon Leeds, LS19 6JY, England

Airedale International Air Conditioning Limited. Leeds Road, Rawdon Leeds, LS19 6JY, England > For the latest information on our products please visit : www.airedale.com > Please refer to the technical manuals for more detailed information Your nearest Airedale distributor is: ISO 14001 EMS52086

More information

4-step Chiller and Heat Pump Controller

4-step Chiller and Heat Pump Controller 4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW

More information

Single phase. Technical Support Division

Single phase. Technical Support Division Single phase Technical Support Division 2014.12 CMV MINI VRF System - Control System 1 1. Outdoor Unit and Indoor Unit PCB 2. Communication System 3. Controllers 2 CMV MINI VRF System - Control System

More information

7-day room temperature controller

7-day room temperature controller s 2 208 7-day room temperature controller Heating applications REV34.. Mains-independent, battery-operated room temperature controller featuring user-friendly operation, easy-to-read display and large

More information

Measure & Control Temperature & CO2 levels with analog & digital I/O

Measure & Control Temperature & CO2 levels with analog & digital I/O MADE IN OZ HTC-DIGITAL-LCD PROGRAMMABLE TEMPERATURE CONTROLLER c/w YEARLY PROGRAMMABLE TIME SWITCH COMPATIBLE WITH A WIDE RANGE OF SENSORS ROOM O/A WALL DUCT PIPE Use Features Measure & Control Temperature

More information

CTXA-AS/AT/AW, FTXA-AS/AT/AW

CTXA-AS/AT/AW, FTXA-AS/AT/AW Split Air Conditioning Technical Data CTXA-AS/AT/AW, FTXA-AS/AT/AW > CTXAA2V1BS > CTXAA2V1BT > CTXAA2V1BW > FTXAA2V1BS > FTXAA2V1BT > FTXAA2V1BW > FTXAA2V1BS > FTXAA2V1BT > FTXAA2V1BW > FTXAA2V1BS > FTXAA2V1BT

More information

IntesisBox ModBus RTU Fujitsu Air Conditioning

IntesisBox ModBus RTU Fujitsu Air Conditioning IntesisBox ModBus RTU Fujitsu Air Conditioning Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu User Manual 03/2019 r1.0 eng Intesis Software S.L.U. 2019 All Rights Reserved.

More information

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,

More information

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA

More information

1.5 to 5 Tons INDOOR COILS CH35. Horizontal PRODUCT SPECIFICATIONS CH A - 2 F MODEL NUMBER IDENTIFICATION FEATURES

1.5 to 5 Tons INDOOR COILS CH35. Horizontal PRODUCT SPECIFICATIONS CH A - 2 F MODEL NUMBER IDENTIFICATION FEATURES INDOOR COILS PRODUCT SPECIFICATIONS Horizontal Bulletin No. 20667 November 206 Supersedes August 206.5 to 5 Tons MODEL NUMBER IDENTIFICATION CH 35-8 A - 2 F Unit Type CH = Indoor - Horizontal Series Nominal

More information

U-Match Series DC Inverter Service Manual PRODUCT

U-Match Series DC Inverter Service Manual PRODUCT PRODUCT 1 PRODUCT 1 MODELS LIST 1.1 Outdoor Unit Name Product Code Power Supply (V, Ph, Hz) Appearance GUHD24NS3GO CF090W0800 220-240V~ 50/60Hz GUHD36NS3GO CF090W0860 220-240V~ 50/60Hz GUHD42NS3GO CF090W0870

More information

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position) echnical data sheet EF24A- Communicative spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx.

More information

Min. Circuit Ampacity. Max. Fuse or Breaker. Ship / Operating Weight lbs. (kg) C4H524GKD 2 24,

Min. Circuit Ampacity. Max. Fuse or Breaker. Ship / Operating Weight lbs. (kg) C4H524GKD 2 24, ENVIRONMENTALLY SOUND REFRIGERANT C4H(5, 7) SXT+ Product Specifications HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 2, 3, 4, and 5 TONS SPLIT SYSTEM 208

More information

RXTP ROOM TEMPERATURE

RXTP ROOM TEMPERATURE ROOM TEMPERATURE CONTROLLER WITH PI CONTROL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4

More information

Built-in features Built-in simplicity Built for fans & pumps

Built-in features Built-in simplicity Built for fans & pumps GE Built-in features Built-in simplicity Built for fans & pumps AF-600 FP Fan & Pump Drives imagination at work Built for variable torque Specifically designed for fan and pump applications, the AF-600

More information

Room Temperature Controller

Room Temperature Controller 3 023 Room Temperature Controller for four-pipe fan coil units RCC30 Outputs for on / off valve actuators Outputs for three-speed fan Control depending on room or return air temperature Operating modes:

More information

TPE, TPED Series 2000

TPE, TPED Series 2000 GRUNDFOS INSTRUCTIONS TPE, TPED Series 2000 Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions. CONTENTS

More information

Daikin HVAC Controls Guide Specification

Daikin HVAC Controls Guide Specification Part 1 - General VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM Advanced Multi-zone Controller 1.01. Physical characteristics A. General: The advanced multi-zone controller shall be made from plastic materials

More information

Non-communicating room controllers

Non-communicating room controllers 3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For

More information

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs revision 04 2016 RCF-230CAD Room controller with communication for fancoil applications with two analogue 0...10 V DC outputs Intended to control heating and/or cooling in 2- or 4-pipe installations. Setpoint

More information

EC centrifugal module - RadiPac

EC centrifugal module - RadiPac KG9-AS8- ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-7 Mulfingen Phone +9 798 8- Fax +9 798 8- info@de.ebmpapst.com www.ebmpapst.com Limited partnership Headquarters Mulfingen County court Stuttgart

More information

Semi Flush-mount Room Temperature Controllers with LCD

Semi Flush-mount Room Temperature Controllers with LCD 3 076 RDF300, RDF300.02, RDF340 RDF400.01 Semi Flush-mount Room Temperature Controllers with LCD for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units for use with compressors in DX type equipment

More information

1:1 Model Connection Interface

1:1 Model Connection Interface Air Conditioner Installation Manual 1:1 Model Connection Interface Model name: TCB-PCNT31TLUL Installation Manual Digital Inverter Air Conditioner 1 English Manuel d installation Climatiseur inverseur

More information

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater revision 03 2012 RCF-230CTD Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater RCF-230CTD is a room controller intended

More information

KNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS).

KNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS). PRODUCT NEWS Products News: New HC-A16KNX PAGE 1 / 8 Summary 1. This advanced product news introduces the new product HC-A16KNX. 2. The details are indicated in the description. Description 1. Applicable

More information

Micro-Master 4500 Series Controllers

Micro-Master 4500 Series Controllers Micro-Master 4500 Series Controllers Application Micro-Master controller used for horticultural and agricultural applications with Filter Flushing and Chemical Fertiliser Injection Programs 16 and 25 station

More information

CTC Low Temperature Process Chillers

CTC Low Temperature Process Chillers INNOVATE DESIGN APPLY CTC Low Temperature Process Chillers 5-500 Tons OUR BUSINESS IS COOLING YOURS TM When commercial grade isn t enough When it comes to process cooling, every application is unique in

More information

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTXB-C

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTXB-C Air Conditioning Technical Data Wall mounted unit EEDEN15-0 FTX-C Indoor Unit FTX-C TALE OF CONTENTS FTX-C 1 Features............................................................. 2 2 Specifications.......................................................

More information

IntesisBox TO-RC-MBS-1

IntesisBox TO-RC-MBS-1 IntesisBox TO-RC-MBS-1 v.1.5 MODBUS RTU (EIA485) Interface for Toshiba air conditioners from the Digital Inverter & VRF lines. User Manual Issue Date: 01/2014 Order Codes: TO-RC-MBS-1 Intesis Software

More information

IntesisBox SMS - Mitsubishi Electric air conditioners

IntesisBox SMS - Mitsubishi Electric air conditioners Order code ME-AC-SMS-32 IntesisBox SMS - Mitsubishi Electric air conditioners Controller with SMS interface for monitoring and control Mitsubishi Electric air conditioners. Control your Mitsubishi Electric

More information

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010 Product Catalog Tracer Controls Tracer Unitary Control August 2010 BAS-PRC012-EN Introduction The Tracer unitary controller provides digital control that is similar to that of a wall thermostat. It supports

More information

Reliability and extended operation

Reliability and extended operation CLIMAVENETA TELECOMSOLUTIONS Units for mobile telecounication applications, with free cooling and full DC Inverter technology. 1,5 20. Low operational and maintenance costs Wide range of full inverter

More information

J&M Fluidics, Inc. Company Product Overview

J&M Fluidics, Inc. Company Product Overview It s All about Building a Better Product for Our Clients! J&M Fluidics, Inc. Company Product Overview J&M Fluidics, Manufacturer of Air & Water-Cooled Process Chillers. Located in Telford, Pennsylvania

More information

32MP Gateway. Overview and Configuration Manual

32MP Gateway. Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual This document is the property of Carrier Corporation and is delivered on the express condition that it is not

More information

RTD-W Installation Instructions

RTD-W Installation Instructions RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485

More information

Air Conditioning Technical Data FBA-A > FBA35A2VEB > FBA50A2VEB > FBA60A2VEB > FBA71A2VEB > FBA100A2VEB > FBA125A2VEB > FBA140A2VEB

Air Conditioning Technical Data FBA-A > FBA35A2VEB > FBA50A2VEB > FBA60A2VEB > FBA71A2VEB > FBA100A2VEB > FBA125A2VEB > FBA140A2VEB Air Conditioning Technical Data FBA-A > FBAA2VEB > FBAA2VEB > FBAA2VEB > FBA71A2VEB > FBA0A2VEB > FBA1A2VEB > FBA1A2VEB Indoor Unit FBA-A TABLE OF CONTENTS FBA-A 1 Features.............................................................

More information

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide Beyond Comfort VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide August 10 th, 2010 (For Commercial and Lodging HVAC Fan Coil Applications) 028-0296-R1-LIT-VC3000-E01 Index

More information

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND

More information

Daikin HVAC Controls Guide Specification

Daikin HVAC Controls Guide Specification VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM Building Management System Integration (Open Protocol Interface) Part 1 - General 1.01. Physical characteristics A. General: The VRV Controls Network shall

More information

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication. HTC-DIGITAL-LCD Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication. Features Use Australian Made and designed LCD 2 X 16 Character Backlit Display Five Programmable

More information

Room Temperature Controllers

Room Temperature Controllers 3 021 Room Temperature Controllers for two-pipe fan coil units RCC10 Output for on / off valve actuator Outputs for three-speed fan Control depending on the room or return air temperature (RCC10) Automatic

More information