OTAHUHU SUBSTATION DIVERSITY PROJECT: REVIEW OF THE CIRCUIT BREAKER CONFIGURATION PROPOSED BY TRANSPOWER

Size: px
Start display at page:

Download "OTAHUHU SUBSTATION DIVERSITY PROJECT: REVIEW OF THE CIRCUIT BREAKER CONFIGURATION PROPOSED BY TRANSPOWER"

Transcription

1 Parsons Brinckerhoff Associates OTAHUHU SUBSTATION DIVERSITY PROJECT: REVIEW OF THE CIRCUIT BREAKER CONFIGURATION PROPOSED BY TRANSPOWER A report prepared for 23 March 2007

2 Disclaimer Notice Report for the Benefit of Electricity Commission This Report has been prepared exclusively for the benefit of the Electricity Commission. Parsons Brinckerhoff Associates Ltd () will not be liable to any other persons or organisation and assumes no responsibility to any other person or organisation for or in relation to any matter dealt with or conclusions expressed in the Report, or for any loss or damage suffered by any other persons or organisations arising from matters dealt with or conclusions expressed in the report (including without limitation matters arising from any negligent act or omission of or for any loss or damage suffered by any other party relying upon the matters dealt with or conclusions expressed in the report). No person or organisation other than the Electricity Commission is entitled to reply upon the Report or the accuracy or completeness of any conclusion and such other parties should make their own enquiries and obtain independent advice in relation to such matters. Reliance on Data In preparing this Report, has relied on information supplied by Transpower and gathered from a number of sources including public domain and proprietary data services, internet sites, news services as well as parties involved in the industry. Some of the pricing information used is deemed confidential and may compromise suppliers if made public. In addition, it may also adversely influence future tender processes if used to set precedents or benchmarks for item prices. This information therefore has to be excluded from public versions of this document. Furthermore. any projections are estimates only and may not be realised in the future. No blame or responsibility should be attached to any of these sources of information for any factual errors or misinterpretation of data in this Report. has not independently verified the accuracy of the information with which it has been provided and has not audited any financial information presented in this Report. Limitations This Report covers analysis and capital cost estimates relating to transmission lines and substations and is based on the facts known to at the time of preparation. This report does not purport to contain all relevant information for all plant discussed. has made a number of assumptive statements throughout the Report, and the Report is accordingly subject to and qualified by those assumptions. The estimates were prepared at a desktop level only and did not involve any site surveys, geotechnical analyses or detailed design work. The uncertainties inherent to capital cost estimation for large construction projects, especially where such estimates are prepared at a desktop level only should therefore be taken into account by any party relying on this report. Parsons Brinckerhoff Associates Ltd. Level 3, Revera House Mulgrave Street Wellington Phone : Fax :

3 1. INTRODUCTION The Electricity Commission requested to review section 1.1 and section 5 of Transpower s document titled Response to the Electricity Commission Queries on Grid Upgrade Plan, dated 07 March In particular we were requested to provide an opinion of the statements made by Transpower regarding existing back-to-back connections at the OTA switchyard, and the switchyard configurations. All references in this review report to specific sections of a document, refers to this Transpower report. 2. REVIEW 2.1 SECTION 1.1: BACK-TO-BACK CONNECTIONS With reference to the Transpower SLD TX25609 Rev AD 1 for Otahuhu substation, it can be confirmed that there are three back-to-back connections at the 220 kv switchyard: 1. Bay 2 GLN 1 circuit & capacitor bank C29 2. Bay 6 HLY 2 circuit & transformer T5 3. Bay 9 HLY 1 circuit & PEN 5 circuit Following our analysis of the issues raised in section 1.1 of the Transpower document with regard to back-back connections 1, we conclude as follows: First Issue: Transpower notes that any failure within the zone between the circuit breakers and disconnectors will trip out both connected circuits. PBA response : It is indeed not possible to isolate a fault in this zone without tripping out both circuits. therefore agrees with Transpower on this matter. Second Issue: Transpower notes that one circuit breaker cannot be taken out of service unless it is properly isolated from the system, and in order to do this with a back-to-back connection, both circuits have to be taken out of service. PBA response : agrees with Transpower. 1 Transpower SLD: TX25609 Rev AD: Otahuhu Substation 220/22/11 kv Single Line Diagram (Operating) CB configuration final.doc March

4 2.2 CONCLUSION Overall, supports the view that to add further back-to-back connections to the existing switchyard is not an acceptable solution. Reliability and availability of this substation are key requirements for its ongoing development and using back-to-back configurations compromises this. 3. TRANSPOWER SECTION 5 : ADDITIONAL INFORMATION SWITCHGEAR CONFIGURATIONS 3.1 SINGLE BREAKER DOUBLE BUS (SBDB) CONFIGURATION (SECTION 5.1) We note the following key points on SBDB features from Fink & Beaty 2 : The configuration allows transfer of a feeder from one bus to the other without de-energising the feeder circuit. A bus-tie circuit breaker connects the two buses. A bus fault, or maintenance on a bus, will require disconnection of all the feeder circuits connected to that bus. Operating with a closed bus-tie breaker requires a very selective bus protective relaying scheme. Disconnect switch operation becomes quite involved, with a high possibility of operator error or injury, and possible shutdown. This scheme has been a standard installation in New Zealand for many years and most existing major substations are of this configuration. It provides a reasonable trade-off between cost and reliability and has generally provided adequate service levels (bus faults are relatively rare). However, given the major impact of a bus fault, for key substations this is not a preferred option. Fink & Beaty notes that internationally this configuration is not considered good practice for important substations. Costs Based on recent cost estimates for SBDB schemes for assessment of Transpower s Otahuhu proposal, the indicative cost estimate for ONE bay includes the following equipment: Structures Busbar Circuit breaker (1) Disconnectors (3) Earth switches (1) Surge arrestor (1) CT (1) 2 Standard Handbook for Electrical Engineers, Fink & Beaty, 12 th Edition, McGraw-Hill, Refer to section 17: Substation Design CB configuration final.doc March

5 VT (1) LV cables AC/DC systems Protection and metering Controls Bay set-up costs Based on this the total cost for one bay, with one circuit per bay is $1, 438, BREAKER AND A HALF (1½ CB) CONFIGURATION (SECTION 5.2) We note the following key points on 1.5CB features from Fink & Beaty 3 : Two circuits are protected by three circuit breakers, where each circuit connects between a pair of breakers. Normally all circuit breakers are closed and both buses are energised. A circuit is tripped by opening the two associated circuit breakers. It is possible to operate with both buses out of service with a source connected opposite a load across the bay. One bay accommodates two circuits. Breaker maintenance can be performed with no loss of service to adjacent circuits. Either main bus can be taken out of service for maintenance and (single) bus failure does not require any feeder circuit to be removed from service. This scheme is generally more expensive than the SBDB configuration but is superior in flexibility, reliability and safety. However, for substations with a small number of bays, as demonstrated below, it may actually be more cost-effective to use a 1½ CB arrangement, given that the need for a bus-tie and bus-section circuit breakers is avoided. (For substations with larger numbers of bays, the effect of these fixed costs diminishes as a proportion of the additional cost per 1½ CB arrangement vs. the single CB SBDB bays.) Costs Based on recent cost estimates for SBDB schemes for assessment of Transpower s Otahuhu proposal, the indicative cost estimate for ONE bay (which is defined here to include two feeders), includes the following equipment: Structures Busbar Circuit breaker (3) Disconnectors (6) Earth switches (2) Surge arrestor (2) 3 Standard Handbook for Electrical Engineers, Fink & Beaty, 12 th Edition, McGraw-Hill, Refer to section 17: Substation Design CB configuration final.doc March

6 CT (3) VT (2) LV cables AC/DC systems Protection and metering Controls Bay set-up costs Based on this, the total cost for one bay, two circuits per bay, is $2, 968, COMPARISON OF THE CONFIGURATIONS In section 5.3 of Transpower s reply to the Commission, a comparison is made between the SBDB and 1½ CB schemes. view on the comparison is presented below Space With reference to Transpower s figures in section 5.3, it is easy to see the space impact of using a 1½ CB scheme as opposed to a SDBD scheme. Overall we agree that the 1½ CB scheme requires less substation space than the equivalent SDBD scheme. For eight circuits, because the 1½ CB scheme accommodates two circuits per bay it requires roughly half the length of the SBDB scheme with the same number of circuits. However the width of the 1.5CB scheme is approximately twice that of a SBDB scheme and requires the switchyard layout to accommodate both incoming and outgoing circuits on both sides, whereas the SBDB scheme only needs circuit access to one side. Also there are height increases in the switchyard when using the 1½ CB scheme over the SBDB scheme for AIS installations. Due to the nature of the arrangement of 1½ CB schemes the incoming/outgoing lines pass over the busbar and circuit breaker below to enable connection at the correct point of the switchyard. This requires additional gantry structures to support the lines making the 1½ CB switchyard approximately double the height of the SBDB scheme. The comparative land area require for an eight circuit switchyard of each type is as follows: 1½ CB : 5300 m 2 SBDB: 6000 m 2 This is based on a bay width of 12.2 m (40 foot) for all bays except for the bus section bay required for the SBDB switchyard, which is 15.3 m (50 foot) across. The bay depth for the 1½ CB switchyard is 107 m and the SBDB is approx 48 m CB configuration final.doc March

7 3.3.2 Costs Table 1 below provides a summary of the total costs associated with an eight circuit switchyard of each type. This comparison does not take into account the cost of the substation site. SBDB Scheme SBDB Scheme ODV Cost Transpower Cost Transpower Cost based on previous Transpower submittals 4 PBA Cost estimate single bay cost $985,220 $1,000,000 $1,330,000 $1,438,000 Number of bays required to accommodate 8 circuits Additional equipment required Additional bays required for this equipment Additional associated cost Full number of bays necessary Bus-tie and bus section circuit breakers three additional CBs Bus-tie and bus section circuit breakers three additional CBs Bus-tie and bus section circuit breakers three additional CBs Bus-tie and bus section circuit breakers three additional CBs $1,398,220 $2,200,000 5 $1,824,000 $1,580, TOTAL COST $9,279,980 $10,200,000 $12,464,000 $13,084,000 1½ CB Scheme Single bay cost (2 feeders) Number of bays required to accommodate 8 circuits Additional equipment required Additional bays required for this equipment Additional associated cost Full number of bays necessary $2,136,170 $2,300,000 $2,847,000 $2,968, N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TOTAL COST $8,544,680 $9,100,000 $11,388,000 $11,872,000 Table 1: Cost Summary for an eight circuit switchyard of each type. 4 Refer to Transpower letter from Tim George dated 6 July 2006 Auckland Grid Upgrade Proposal Component Costs. This letter contains 220 kv substation component costs which were reviewed and accepted by at the time. The information was used here to build up a substation bay cost for each type of switchyard scheme. 5 Assumed - based on total cost, cost of single bay and number of circuits required CB configuration final.doc March

8 3.4 CONCLUSION There are definite advantages in using the breaker and a half scheme over the single breaker double bus arrangement for large and important substations such as Otahuhu. These benefits include greater flexibility, reliability and safety over the SBDB scheme and for a relatively small switchyard (in terms of the number of circuits) there is not only a saving in space but also a capital cost savings for the 1½ CB scheme. therefore agrees with Transpower s decision to adopt the 1½ circuit breaker configuration in preference to the SBDB configuration for the proposed Otahuhu Substation Diversity Project CB configuration final.doc March

Network Configuration Document Selection for New Substations Framework

Network Configuration Document Selection for New Substations Framework Network Configuration Document Selection for New Substations Current version: 20/06/2018 EXTERNAL USE Page 1 of 14 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References...

More information

ASSET RISK MANAGEMENT Criticality Framework

ASSET RISK MANAGEMENT Criticality Framework ASSET RISK MANAGEMENT Criticality Framework 15 C O P Y R I G H T 2013 T R A N S P O W E R N E W Z E A L A N D L I M I T E D. A L L R I G H T S R E S E R V E D Preface This document has been prepared to

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

Power System Operating Incident Report Trip of Calvale No.2 275kV busbar and Calvale-Halys 8810 and 8811 transmission lines on 30 March 2014

Power System Operating Incident Report Trip of Calvale No.2 275kV busbar and Calvale-Halys 8810 and 8811 transmission lines on 30 March 2014 Power System Operating Incident Report Trip of Calvale No.2 275kV busbar and Calvale-Halys 8810 and 8811 transmission lines on 30 March 2014 PREPARED BY: Systems Capability DATE: 6 June 2014 STATUS: FINAL

More information

Power Transmission Division Link between power generation and distribution

Power Transmission Division Link between power generation and distribution Power Transmission Division Link between power generation and distribution Seite 4 High Voltage Substations Schemes, Devices and Types of AIS Installation Content Link between power generation and distribution

More information

Lecture 5 Substation Automation Systems. Course map

Lecture 5 Substation Automation Systems. Course map Lecture 5 Substation Automation Systems 1 Course map 2 1 Contents of the Lecture Part 1 Substation Automation Components Substation Automation Functions Communication within the Substation (Intro) Part

More information

Substation SCADA Monitoring

Substation SCADA Monitoring Substation SCADA Monitoring Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Substations are a critical component

More information

XXXX. Bear Creek Hydro Generation Project. Interconnection Facilities Study

XXXX. Bear Creek Hydro Generation Project. Interconnection Facilities Study XXXX Bear Creek Hydro Generation Project Interconnection Facilities Study Report No. SPA 2005-33 August 2005 System Planning (Lower Mainland & Vancouver Island) British Columbia Transmission Corporation

More information

Lecture 6 Substation Automation Systems

Lecture 6 Substation Automation Systems Lecture 6 Substation Automation Systems 1 Course map 2 Contents of the Lecture Part 1 Substation Automation Components & Architectures Substation Automation Functions Communication within the Substation

More information

SCADA Training - T&D Automation

SCADA Training - T&D Automation SCADA Training - T&D Automation Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This course covers all the

More information

TRIP OF CLARE SOUTH TOWNSVILLE SOUTH 132 KV TRANSMISSION LINE ON 24 JUNE 2015

TRIP OF CLARE SOUTH TOWNSVILLE SOUTH 132 KV TRANSMISSION LINE ON 24 JUNE 2015 TRIP OF CLARE SOUTH TOWNSVILLE SOUTH 132 KV TRANSMISSION LINE ON 24 JUNE 2015 AN AEMO POWER SYSTEM OPERATING INCIDENT REPORT FOR THE NATIONAL ELECTRICTY MARKET Published: October 2015 VERSION RELEASE HISTORY

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-0150 LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing

More information

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4. Branch Procedure Document No. Issue No. : : CEOP8012 5 Approved By : Specialist Engineering NETWORK : Manager Approval Date Review Date : : 29/06/2018 29/06/2021 (Supersedes CEOP8012, Generation Connection:

More information

GUIDELINES FOR SHARED TRANSMISSION CONNECTIONS IN VICTORIA

GUIDELINES FOR SHARED TRANSMISSION CONNECTIONS IN VICTORIA GUIDELINES FOR SHARED TRANSMISSION CONNECTIONS IN VICTORIA PREPARED BY: Transmission Services VERSION: 2.0 RELEASE DATE: 14 December 2011 FINAL Version Release History Version Date Approved 1.0 3 Jun 11

More information

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation 111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

ABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear Type ZX2. ABB Gas-insulated switchgear type ZX2 1

ABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear Type ZX2. ABB Gas-insulated switchgear type ZX2 1 ABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear 17.02.2015 Gas-insulated switchgear type ZX2 1 Medium voltage switchgear type ZX2 Single or double busbar systems 12 kv, 2500 A, 40 ka

More information

Guideline for the Connection of Micro Embedded Generators to the TasNetworks Distribution Network

Guideline for the Connection of Micro Embedded Generators to the TasNetworks Distribution Network Tasmanian Networks Pty Ltd ABN 24 167 357 299 Guideline for the Connection of Micro Embedded Generators to the TasNetworks Distribution Network (AS4777 Compliant) NG R PD 09 Version 2.0 July 2014 TABLE

More information

Bus Protection Application Challenges

Bus Protection Application Challenges Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference Content Introduction Application Challenges Increase

More information

Disturbance Monitoring and

Disturbance Monitoring and PRC-002-2 R1 Notification Disturbance Monitoring and Reporting Requirements Compliance Spring Workshop May 10, 2017 Objectives This presentation will discuss: Requirement R1 Part 1.2 notifications Definition

More information

Grid Automation Controller COM600 How it fits into the Smart Grid?

Grid Automation Controller COM600 How it fits into the Smart Grid? ABB Oy Distribution Automation Grid Automation Controller How it fits into the Smart Grid? May 27, 2014 Slide 1 1MRS756763 E Content Technical Presentation May 27, 2014 Slide 2 Description Grid Automation

More information

Transmission or Distribution. Phil Collins March 18, 2005

Transmission or Distribution. Phil Collins March 18, 2005 Transmission or Distribution Phil Collins March 18, 2005 CUSC Principles of Ownership Power Station Busbar clamp on busbar side of busbar isolators on generators circuit Distribution System Busbar clamp

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Air-insulated medium-voltage secondary distribution switchgear

Air-insulated medium-voltage secondary distribution switchgear DISTRIBUTION SOLUTIONS Air-insulated medium-voltage secondary distribution switchgear Compact size Complete solution Factory tested Air-insulated medium-voltage secondary distribution switchgear The ABB

More information

POWER GRIDS. We are bridging the gap. Enabling Digital Substations.

POWER GRIDS. We are bridging the gap. Enabling Digital Substations. POWER GRIDS We are bridging the gap. Enabling Digital s. 2 A B B D i g i ta l S u b s tat i o n s ABB s Digital provides customers in the utility sector with unmatched control and efficiency. The digital

More information

ABB AG - EPDS. Gas-insulated switchgear Type ZX2

ABB AG - EPDS. Gas-insulated switchgear Type ZX2 ABB AG - EPDS Gas-insulated switchgear Medium voltage switchgear Single or double busbar systems 12 kv, 2500 A, 40 ka 24 kv, 2500 A, 40 ka 36 kv, 2500 A, 40 ka Slide 2 Medium voltage switchgear With IAC

More information

QUALITY CONTROL Prepared: TenneT team Reviewed: M. Müller Approved: F. Wester BACKGROUND MATERIAL... 2

QUALITY CONTROL Prepared: TenneT team Reviewed: M. Müller Approved: F. Wester BACKGROUND MATERIAL... 2 POSITION PAPER STAKE HOLDER CONSULTATION PROCESS OFFSHORE GRID NL Type: Position paper Work stream Technical Topic: T.8 SCADA, communication interface and data links Filename ONL 15-185-T8_SCADA, communication

More information

How smart can the grid really be?

How smart can the grid really be? How smart can the grid really be? by Dale Pudney, HVT Power Systems and Luo Wei, NR Electric With the improvement of electronic communications and computing technology, it becomes possible to integrate

More information

This application note describes configuring automatic bus transfer (ABT) logic with two V57 relays.

This application note describes configuring automatic bus transfer (ABT) logic with two V57 relays. [ ] Automatic Bus Transfer Automation Bus transfer 1 Introduction This application note describes configuring automatic bus transfer (ABT) logic with two V57 relays. In the Figure 1 is presented the single

More information

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2. -and-a-half solutions SIP5-APN-002, Edition 2 www.siemens.com/protection SIPROTEC 5 Application Note -and-a half solutions SIP5-APN-002, Edition 2 -and-a-half solution Content 1 -and-a-half solutions 3

More information

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Revised: July 12, 2013 Introduction The following information includes requests for clarification

More information

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc Redundant Bus Protection Using High-Impedance Differential Relays Josh LaBlanc Purpose Discuss the configuration of the bus under study, and touch on the needs for redundant protection on the bus. Briefly

More information

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

IMP/ 001 / 014 Policy for the Protection of Distribution Networks Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

QUALITY CONTROL Prepared: TenneT team Reviewed: M. Müller Approved: F. Wester BACKGROUND MATERIAL... 2

QUALITY CONTROL Prepared: TenneT team Reviewed: M. Müller Approved: F. Wester BACKGROUND MATERIAL... 2 POSITION PAPER STAKE HOLDER CONSULTATION PROCESS OFFSHORE GRID NL Type: Position paper Work stream Technical Topic: T.8 SCADA, communication interface and data links Filename ONL 15-185-T8_SCADA, communication

More information

COMPACT SUBSTATION WITH 34.5kV GIS (GAS-INSULATED SWITCHGEAR. Cleverson Shindi Takiguchi S&C Electric Europe LTd. Cape Town/WC South Africa

COMPACT SUBSTATION WITH 34.5kV GIS (GAS-INSULATED SWITCHGEAR. Cleverson Shindi Takiguchi S&C Electric Europe LTd. Cape Town/WC South Africa COMPACT SUBSTATION WITH 34.5kV GIS (GAS-INSULATED SWITCHGEAR Cleverson Shindi Takiguchi S&C Electric Europe LTd. Cape Town/WC South Africa Alexandre Taijun Ohara S&C Electric Company Curitiba/PR Brazil

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61850-5 First edition 2003-07 Communication networks and systems in substations Part 5: Communication requirements for functions and device models IEC 2003 Copyright - all rights

More information

It is the job of the protection system equipment to recognize and remove the fault.

It is the job of the protection system equipment to recognize and remove the fault. Protection 1 (read section 13.0 of text) 1.0 Introduction Faults do not occur that frequently 1/year/100 miles of transmission is typical. Distribution systems may see more than this. However, when they

More information

Distributed bus protection application in a platform for process bus deployment in the SMART SUBSTATION

Distributed bus protection application in a platform for process bus deployment in the SMART SUBSTATION Jorge Cardenas, GE Digital Energy David McGinn, GE Digital Energy Michael Miller, GE Digital Energy Ilia Voloh, GE Digital Energy Richard Hunt, GE Digital Energy Distributed bus protection application

More information

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Authors: Dr. Brett Watson, Siemens Ltd., PO Box 4833, Loganholme, QLD 4129, Australia

More information

Appendix I: LOAD OPERATING AGREEMENT

Appendix I: LOAD OPERATING AGREEMENT PG&E Transmission Interconnection Handbook Appendix I: LOAD OPERATING AGREEMENT Purpose The following agreement establishes operating responsibilities and associated procedures for communications between

More information

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer ) Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original

More information

SP Energy Networks Business Plan

SP Energy Networks Business Plan SP Energy Networks 2015 2023 Business Plan Updated March 2014 Annex 132kV Substation Plant Strategy SP Energy Networks 29 March 2014 March 2014 Issue Date Issue No. Document Owner Amendment Details 17th

More information

PRC Coordination of Protection Systems for Performance During Faults

PRC Coordination of Protection Systems for Performance During Faults PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To

More information

3M Sensored Cable Accessories for Underground Medium Voltage Distribution System

3M Sensored Cable Accessories for Underground Medium Voltage Distribution System 3M Sensored Cable Accessories for Underground Medium Voltage Distribution System 3M Electronics & Energy Business 1 Introduction The focus on enhancing reliability and efficiency of the power grid has

More information

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District 5 WHAT IS A BUS? All connections are at the same voltage. WHAT IS A BUS? All

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

Benefits, offering and references

Benefits, offering and references DOC ID: 9AKK107045A9180 DISTRIBUTION SOLUTIONS Digital medium-voltage switchgear Benefits, offering and references Contents Digital switchgear for medium-voltage applications Digital switchgear definition

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

The Narragansett Electric Company. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No Testimony of. Todd G. Kopoyan, P.E.

The Narragansett Electric Company. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No Testimony of. Todd G. Kopoyan, P.E. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No. 0 Testimony of Todd G. Kopoyan, P.E. February 0, 00 0 0 INTRODUCTION Q. Please state your name and business address. A. My name is

More information

UNDERGROUND HV SUBSTATION DESIGN

UNDERGROUND HV SUBSTATION DESIGN 3 for 2 Bundle Offer. SGD 2440 each for Team of 3! Topics Covered Underground Substations Overview Planning New Underground Substations S/S Design Overview Expert Course Faculty Leader In his 30 years

More information

User Manual. AQ-F215 Simulator

User Manual. AQ-F215 Simulator User Manual AQ-F215 Simulator Instruction manual AQ-F215 Simulator 2 (28) Revision 1.00 Date 16.5.2014 Changes N/A Revision 1.01 Date 13.3.2018 Changes Updated visual look Readability improvements Instruction

More information

EPRI Protection Settings Evaluation Tool (PSET)

EPRI Protection Settings Evaluation Tool (PSET) EPRI Protection Settings Evaluation Tool (PSET) Mahendra Patel & Sean McGuinness Grid Operations & Planning EPRI Protection Settings Evaluation Tool (PSET) Software Intended use: Automatically assess the

More information

Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds

Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at rotection Speeds Karl Iliev San Diego Gas & Electric Company Eric Udren Quanta Technology, LLC Copyright

More information

Effective commissioning of bus bar protection systems using a dynamic simulation in the field

Effective commissioning of bus bar protection systems using a dynamic simulation in the field Effective commissioning of bus bar protection systems using a dynamic simulation in the field F Fink *, J Köppel, T Hensler *OMICRON electronics GmbH, Austria, florian.fink@omicron.at, ABB AG, Germany,

More information

AUTOMATED TESTING OF BUSBAR DIFFERENTIAL PROTECTION USING A SYSTEM-BASED APPROACH. Christopher Pritchard, Florian Fink

AUTOMATED TESTING OF BUSBAR DIFFERENTIAL PROTECTION USING A SYSTEM-BASED APPROACH. Christopher Pritchard, Florian Fink AUTOMATED TESTING OF BUSBAR DIFFERENTIAL PROTECTION USING A SYSTEM-BASED APPROACH Christopher Pritchard, Florian Fink OMICRON electronics GmbH, Klaus, Austria; Christopher.Pritchard@omicronenergy.com ABSTRACT

More information

PPL EU Relay Standardization

PPL EU Relay Standardization PPL EU Relay Standardization John Sonnelitter Senior Engineer, Transmission Relay Engineering Richard Michael Jr. Support Engineer, Transmission Relay Engineering 9/18/2018 Background PPL EU is undergoing

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

SWITCHYARD SYSTEM BC1-SS-11-SD TRAINING SYSTEM DESCRIPTION NRG ENERGY, INC. BIG CAJUN 1

SWITCHYARD SYSTEM BC1-SS-11-SD TRAINING SYSTEM DESCRIPTION NRG ENERGY, INC. BIG CAJUN 1 SWITCHYARD SYSTEM TRAINING SYSTEM DESCRIPTION NRG ENERGY, INC. BIG CAJUN 1 November 2011 PREFACE This Training System Description has been designed to assist you in meeting the requirements of Module BC1-SS-11

More information

Recording and Reporting of High Voltage and Low Voltage Switching

Recording and Reporting of High Voltage and Low Voltage Switching 1 SCOPE This document details the procedures to be adopted prior to, during, and on completion of Switching operations, and details the manner in which HV and LV Switching shall be recorded in order to

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

CONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected Generation (DCG)]

CONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected Generation (DCG)] Project Name: Kitchener-Wilmot Hydro Inc. 301 Victoria Street South Kitchener, Ontario, Canada N2G 4L2 Appendix F2: Form DG06 CONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected

More information

Submission to the International Integrated Reporting Council regarding the Consultation Draft of the International Integrated Reporting Framework

Submission to the International Integrated Reporting Council regarding the Consultation Draft of the International Integrated Reporting Framework Submission to the International Integrated Reporting Council regarding the Consultation Draft of the International Integrated Reporting Framework JULY 2013 Business Council of Australia July 2013 1 About

More information

MESP MODULAR SUBSTATION USER REQUIREMENTS

MESP MODULAR SUBSTATION USER REQUIREMENTS Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

Designing a new IEC substation architecture

Designing a new IEC substation architecture Designing a new IEC 61850 substation architecture Gerrit Dogger Senior Product and Application Specialist Cooper Power Systems gerrit.dogger@cybectec.com Garry Tennese Station Integration Specialist Manitoba

More information

Balancing and Settlement Code BSC PROCEDURE

Balancing and Settlement Code BSC PROCEDURE Balancing and Settlement Code BSC PROCEDURE Registration of Transmission System Boundary Points, Grid Supply Points, GSP Groups and Distribution Systems Connection Points BSCP25 Version 8.0 Date: 29 June

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Power Systems Communications Implementation of IEC61850 in a Substation Environment Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details

More information

January 22, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C.

January 22, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C. California Independent System Operator Corporation January 22, 2013 The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C. 20426 Re: California

More information

Digital Substation Overview of Technology, Industry

Digital Substation Overview of Technology, Industry Digital Substation Overview of Technology, Industry Trends and Standardization Efforts 4th International Scientific & Technical Conference Actual Trends in Development of Power System Protection and Automation

More information

SCHEDULE 22 COMMON CONNECTION CHARGING METHODOLOGY

SCHEDULE 22 COMMON CONNECTION CHARGING METHODOLOGY SCHEDULE 22 COMMON CONNECTION CHARGING METHODOLOGY Introduction 1. This Schedule 22 sets out the Common Connection Charging Methodology (CCCM). The CCCM is the whole of this Schedule 22 excluding only

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Medium voltage switchgear With fixed pattern circuit breaker GenieEvo

Medium voltage switchgear With fixed pattern circuit breaker GenieEvo Medium voltage switchgear With fixed pattern circuit breaker GenieEvo Simple and highly reliable switchgear for primary and secondary distribution GenieEvo is an indoor switchgear assembly circuit breaker

More information

COLLABORATE TO WIN. 03/31/2017 Digital Substation Turning IEC61850 features into benefits. Peter Rietmann, Program Manager Digital Substation NA

COLLABORATE TO WIN. 03/31/2017 Digital Substation Turning IEC61850 features into benefits. Peter Rietmann, Program Manager Digital Substation NA COLLABORATE TO WIN 03/31/2017 Digital Substation Turning IEC61850 features into benefits Peter Rietmann, Program Manager Digital Substation NA Increasing Reliability Higher functional integration and process

More information

ABB Data Center Forum 2017

ABB Data Center Forum 2017 ABB DATA CENTER FORUM 2017, 11 TH JULY 2017 ABB Data Center Forum 2017 Perfecting Data Center availability with Ultra-Fast Protection Devices Barbara Schlegel ABB DATA CENTER FORUM 2017, 11 TH JULY 2017

More information

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-012 : Control of Breaker-and-a-half diameters and double busbar configurations and use of Phasor Measurement Unit (PMU) Answers for infrastructure

More information

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B GE Energy Connections Grid Solutions MMLZ Technical Data Sheet Auxiliary Modules Publication reference: MMLZ/EN TDS/B MMLZ Technical Data Sheet FEATURES Wide choice of application specific models Fully

More information

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation Small Generator Interconnection Facilities Study Report Completed for ( Interconnection Customer ) Proposed Interconnection Pavant substation Original report dated February 17, 2016 Revised March 11, 2016

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems By Eng. Sameh Moustafa Mohamed Abd Elgowad Elbana A thesis submitted to The Faculty

More information

Ground Fault Protection. Instruction Manual

Ground Fault Protection. Instruction Manual Ground Fault Protection DSP OHMNI Accessory: DSP-CA(S) Cable Adapter Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR

More information

Power systems 5: Protection

Power systems 5: Protection Power systems 5: Protection Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. As you will recall from our Introduction to Electrical

More information

High-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY

High-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY S&C Remote Supervisory V ista Outdoor Distribution (15.5 kv through 38 kv) Electric utility customers are increasingly concerned about the frequency and duration of outages they are experiencing, and are

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Relion 630 series Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Integrated load-shedding and protection solution The PML630 is a freely-configurable

More information

Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600

Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Contents COM600 Product Overview Business Overview Product News Overview June 12-14, 2012 Slide

More information

SDRC-3 Detailed Design of the FPL Method

SDRC-3 Detailed Design of the FPL Method SDRC-3 Detailed Design of the FPL Method SDRC-3 Detailed Design of the FPL Method Report Title : SDRC-3 Detailed Design of the FPL Method Report Status : FINAL Project Ref : WPDT206 Date : 22.03.2016 Document

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

EU DONOR FUNDED SMART GRID PROGRAMME

EU DONOR FUNDED SMART GRID PROGRAMME EU DONOR FUNDED SMART GRID PROGRAMME 1 Historical Background Msunduzi Local Municipality is a local municipality in Umgungundlovu District Municipality, KwaZulu-Natal, South Africa. It encompasses the

More information

Description of the Application Process for Small Embedded Generators

Description of the Application Process for Small Embedded Generators Description of the Application Process for Small Embedded Generators This document describes the Application Process for Small Embedded Generators (as required under section 5.3.3A of the National Electricity

More information

High and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel.

High and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel. Training Course : High and Medium Voltage Substation Design, Testing and Maintenance Training Course For One Week In KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel Which Be Held As Under Details : Tel.

More information

CAPABILITY STATEMENT. A full list of our services.

CAPABILITY STATEMENT. A full list of our services. CAPABILITY STATEMENT A full list of our services. About Us MVLV Power Solutions Pty Ltd is a privately owned Western Australian based company, specialising in the Design and Manufacture of Electrical Switchboards

More information

Chapter 5A Embedded Generation Information Pack United Energy s guide to the Embedded Generation connection process for of Chapter 5A

Chapter 5A Embedded Generation Information Pack United Energy s guide to the Embedded Generation connection process for of Chapter 5A Chapter 5A Embedded Generation Information Pack United Energy s guide to the Embedded Generation connection process for of Chapter 5A Public Table of contents 1 Connection Framework... 3 2 Connection Types...

More information

ENMAX Power Corporation

ENMAX Power Corporation Decision 22769-D01-2017 Transmission Lines 138-1.80L and 138-1.81L September 15, 2017 Alberta Utilities Commission Decision 22769-D01-2017 Transmission Lines 138-1.80L and 138-1.81L Proceeding 22769 Application

More information

STCP Amendment Proposal Form

STCP Amendment Proposal Form STCP Amendment Proposal Form PA036 1. Title of Amendment Proposal STCP 09-2 Incorporation material currently within SPT SCS and making standard for both TOs. 2. Description of the Proposed Amendment (mandatory

More information

Interlocking for line bay

Interlocking for line bay Page 1 Issued: December 2000 Status: New Data subject to change without notice Features Interlocking function available for a line bay arrangement Suitable for up to double busbars and a transfer busbar

More information