EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

Size: px
Start display at page:

Download "EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES"

Transcription

1 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution network in London and the provision of the associated customer supplies. Author: Stephen Tucker Approver: Steve Mockford This document forms part of the Company's Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current version. Circulation UK Power Networks External Asset Management UK Power Networks Services Capital Programme Contractors Connections ICPs/IDNOs Health & Safety Meter Operators Legal G81 Website Network Operations Procurement Strategy & Regulation Technical Training THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE

2 Revision Record Version 2.2 Review Date 07/10/2020 Date 21/05/2018 Author Lee Strachan Reason for update: Minor version update What has changed: Reference to EDS changed to EDS Version 2.1 Review Date 07/10/2020 Date 19/09/2016 Author Lee Strachan Reason for update: Minor version update What has changed: Reference to ECS updated to EDS Version 2.0 Review Date 25/09/2022 Date 07/10/2015 Author Stephen Tucker Reason for update: Document revised following business feedback What has changed: The extent and provisions of supplies from the London 33kV network has been clarified in all relevant sections. London 33kV distribution network map added as Appendix A Version 1.0 Review Date 05/06/2016 Date 05/06/2014 Author Stephen Tucker New document UK Power Networks 2015 All rights reserved 2 of 19

3 Contents 1 Introduction Scope Abbreviations and Definitions Abbreviations Definitions Network Configuration Load Characteristics Grid Substations Feeder Groups Network Design Cables and Ducts Switchgear Protection Protection Block Diagram Customer Protection Scheme Requirements Grid Substation Protection Scheme Requirements Auto-switching and Feeder Group Setting Substation Earthing Substation Accommodation and Civil Requirements Customer Customer Substations Separation of UK Power Networks and Customer HV equipment LV Generation Emergency Trip Metering Options References UK Power Networks Standards National and International Standards Appendix A Bussing Bar Concept Appendix B 33kV Network Example Appendix C London 33kV Distribution Network Map UK Power Networks 2015 All rights reserved 3 of 19

4 Figures Figure 4.1 Ideal 132/33kV Grid Substation Configuration... 7 Figure 4.2 Feeder Group Arrangements with Bussing Busbar Concept... 8 Figure 5.1 Standard Duct Block Configuration for 33kV Main Spine... 9 Figure 5.2 Protection Overview Figure 6.1 Customer Substation Three-panel Switchboard (Minimum Requirement for 33kV POC) Figure 6.2 Customer Substation Five-panel Switchboard Figure 6.3 Customer Substation Seven-panel Switchboard Figure 7.1 Bussing Bar Concept (n-1) Outage Condition Figure 7.2 Bussing Bar Concept (n-3) Outage Condition Figure kV Network Example UK Power Networks 2015 All rights reserved 4 of 19

5 1 Introduction This standard provides guidelines for the development of the 33kV distribution network in London and the provision of the associated customer supplies. In response to customer requirements, the London 33kV network has been developed to provide high resilience connection for point loads with a maximum demand between 8MW and 15MW and building services being adapted to support 33kV rather than 11kV connections. 2 Scope This standard covers distribution networks supplying large point loads at 33kV in London including: Load characteristics. Grid substations. Feeder groups. Switchgear. Protection. Earthing. Civils. Customer substations. Customer LV supplies. Network implementation. Auto switching. 3 Abbreviations and Definitions 3.1 Abbreviations Term CBF DEF DOC DUoS IDNO MPAN OD POC REF XLPE Definition Circuit Breaker Fail Directional Earth Fault Directional Over-Current Distribution Use of System Independent Distribution Network Owner Meter Point Administration Number Outside Diameter Point of Connection Restricted Earth Fault Cross-linked Polyethylene UK Power Networks 2015 All rights reserved 5 of 19

6 3.2 Definitions Term Definition Bussing Grid Substation HV LV A section of busbar at a grid substation that is fed by a different grid substation Transformation and switching point from an upstream voltage of 132kV The ESQCR Regulations 2002 (3) defines HV as 'any voltage exceeding LV'. It should be noted that HV is a term used in the UK and many legacy documents (including those referenced in this standard) define this to be 11kV and 6.6kV. This should be taken into account when cross referencing with other documents Voltages of 1000V or less n-1 First system outage Primary Substation Transformation and switching point from voltages below 132kV to supply 11/6.6kV distribution network or customers 4 Network Configuration 4.1 Load Characteristics A 33kV distribution network has been established to supply point loads above 5MVA in London. The extent of the network is shown in Appendix B. Service congestion in the public highway and increasing load densities, as a result of large office developments and data centres, has necessitated a move to a higher distribution voltage than 11kV. The majority of buildings requesting new connections in the City of London are large in area and the plots are very densely populated. Many tenants and owners are from the financial or insurance sectors where electricity supply resilience is critical and developers can offer good supply resilience as a strong selling point. As such, the developers are typically requesting and paying for supply resilience, in excess of that required by ENA ER P2/6, from two grid substations. UK Power Networks 2015 All rights reserved 6 of 19

7 4.2 Grid Substations In the first instance 132/33kV substation assets in the vicinity of the 33kV network in London shall be utilised to provide the required 33kV connections. The need for future increases in capacity is to be catered for by upgrading existing substations or constructing new substations in accordance with the ideal single line diagram shown in Figure 4.1. The bussing bar concept is explained in Appendix A. 132/33kV BUSSING MAIN 33kV Feeder and transformer CBs are distributed between all busbar sections as required for the local network configuration. This will also determine which bus-section/coupler CBs are normally open and if auto-switching is required. Figure 4.1 Ideal 132/33kV Grid Substation Configuration Figure 4.1 is provided for guidance only, and is not intended to be overly restrictive to planners and designers. For example: Additional switch positions may be justified to cater for radial/ring feeds to nearby customers. Due to space constraints within existing transformer chambers, 60MVA cyclic rated transformers may offer a more economical solution. Note: A new generic transformer may need to be specified and sourced to support this scenario. 4.3 Feeder Groups Feeder groups typically consist of four circuits rated at 30MVA each to give an n-1 firm rating of 90MVA 1. The feeder group spines shall be run between two grid substations (each with a summer firm rating of 120MVA) as shown in Figure 4.2. Customers shall be connected into a main spine via a loop in/out arrangement (switchboard to have 2 x incomer and 1 x metered circuit-breakers as a minimum), with up to 22.5MVA ideally being connected to a single feeder via one or more customer substations. Refer to Appendix B for a typical 33kV network. Refer to EDS for the standard sizes of 33kV single core XLPE cables and the associated technical information. 1 The developments currently use feeder groups with circuits rated at 20MVA to give an overall n-1 firm rating of 60MVA. Note: The protection settings will need to be reviewed when they are reclassified at 30MVA in the future. UK Power Networks 2015 All rights reserved 7 of 19

8 132/33kV BUSSING MAIN 4 Circuits per feeder group MAIN BUSSING 132/33kV Feeder and transformer CBs are distributed between all busbar sections as required for the local network configuration. This will also determine which bus-section/coupler CBs are normally open and if auto-switching is required. Figure 4.2 Feeder Group Arrangements with Bussing Busbar Concept UK Power Networks 2015 All rights reserved 8 of 19

9 5 Network Design 5.1 Cables and Ducts Cables shall be rated to 30MVA which can usually be provided by a 630mm 2 copper conductor, XLPE insulated, 50mm 2 copper wire screen cable. The standard duct block configuration for a 33kV feeder group main spine is shown in Figure 5.1 and should be used wherever possible. (i) 200mm OD Emtelle duct, with 3 x 33kV XLPE cables in trefoil. (ii) 88.9mm OD Emtelle duct, with 1 x 7-core pilot cable. (iv) (iii) (ii) (iii) 88.9mm OD Emtelle duct, with 2 x sub-ducts, each containing 1 x fibre optic cable. (ii) (ii) (ii) (iv) 88.9mm OD Emtelle duct, with 3 x sub-ducts, each containing 1 x fibre optic cable. (i) (i) (i) (i) (v) Earth cable may be required to be run out for some distance (depending on earthing design) from primary and customer substations. I Figure 5.1 Standard Duct Block Configuration for 33kV Main Spine 5.2 Switchgear The switchgear shall be suitable for a system voltage rated for 33kV nominal. The 33kV three-phase fault level at the customer s point of connection (assuming an infinite infeed at 132kV with three transformers) is approximately 21kA therefore the switchgear shorttime withstand current should be 25kA. However, to allow for the connection of generation 2 in the network switchgear rated at 31.5kA should be considered. Refer to EAS for the approved switchgear. The equipment shall be suitable for networks having the neutral point of source transformers solidly or impedance earthed. 2 Generation of 10MVA at the customer's 11kV busbars will contribute approximately 1kA to the three-phase fault level at 33kV. UK Power Networks 2015 All rights reserved 9 of 19

10 5.3 Protection This section provides an overview of the protection and auto-switching philosophy. Refer to EDS for specific details Protection Block Diagram A simplified single line diagram depicting the proposed operation of a typical 33kV distribution feeder group network is shown in Figure 5.2. The 33kV distribution network feeder groups shall be run closed, with each section of cabling being unit protected to prevent disturbances to customers for n-1 circuit faults. The design is largely based on an HV ring connection. BUSSING BUSSING MAIN Grid Substation A 132/33kV Grid Substation B 132/33kV Directional O/C & E/F MAIN Directional O/C & E/F Customer 1 Customer 2 O/C & E/F on all customer metered breakers. Additional CTs provided according to customers protection design. Unit Protection Zone Busbar Circulating Current Protection Optional Interconnector with Unit Protection Only Programmable Autoswitching Scheme Feeder and transformer CBs are distributed between all busbar sections as required for the local network configuration. This will also determine which bus-section/ coupler CBs are normally open and if auto-switching is required. Figure 5.2 Protection Overview Customer Protection Scheme Requirements 1. All customer switchboards shall be protected by circulating current busbar protection which will trip all incoming circuits into the switchboard and services out of the switchboard. 2. All customer services shall be unit protected with backup provided by directional overcurrent (DOC) and directional earth fault (DEF). This back-up will have circuit breaker fail (CBF) enabled which will trip the incoming circuits if a service circuit-breaker is deemed to have failed. 3. Interconnectors at customer substations adjacent to other customer 33kV substations on parallel 33kV circuits shall also have unit protection. Should the unit protection pilot wires fail at these points an overcurrent and earth fault facility should be then enabled within the unit protection relay. There shall be no provision for DOC and DEF on these UK Power Networks 2015 All rights reserved 10 of 19

11 interconnections but CBF shall be installed on a separate relay to the unit protection relay which will trip the grid circuit-breakers if the interconnected customer circuit-breakers are deemed to have failed. 4. In the event of a two section customer switchboard, two zones of busbar protection shall be utilised. If current transformers can only be fitted to one side of a circuit-breaker, two protection elements on one unit protection relay will be used. 5. DEF relays shall be used at customer substation incomers as fault passage indicators. 6. Customer services on the customer side shall have overcurrent and earth fault protection and any suitable protection that is required by the customer s design which is acceptable to UK Power Networks Grid Substation Protection Scheme Requirements 1. Grid substation incoming circuit-breakers shall have bias differential transformer protection as a main protection with a two stage standby earth fault and LV and HV restrictive earth fault (REF). As a back-up, the incoming circuit-breakers will have overcurrent and earth fault with circuit-breaker fail (CBF) enabled. 2. All busbar zones will have circulating current protection and overcurrent and earth fault graded protection as back-up. 3. Grid substation feeders will be unit protected and have overcurrent and earth fault graded protection as back-up protection. 4. Grid substation interconnectors shall be unit protected and fitted with overcurrent and earth fault back-up protection. 5. The following rules shall also apply to grid substation interconnectors: Bussing busbar (load-end, as designated by Network Control) is graded to operate first. In the event of a fault on the interconnector, the incoming circuit-breaker on the bussing busbar circuit-breaker only opens for fault current running in a direction away from the bussing bar. At the main busbar (feed-end, as designated by Network Control), the overcurrent and earth fault protection is graded to operate second to switch out the faulted feeder. UK Power Networks 2015 All rights reserved 11 of 19

12 5.3.4 Auto-switching and Feeder Group Setting This section provides an overview of the auto-switching philosophy. Refer to EOS for further details. Flexible auto-switching shall be provided by a programmable microprocessor auto switching relay as follows: The signalling is to be provided via a fibre optic cable between the grid substations. For the loss of a transformer, the relay will initiate a pre-programmed switching sequence to transfer the group feeder load to the other substation. If a change of supply end is required, then the main busbar is isolated by opening the bussection (bus-coupler for double busbar equipment), and the remote auto-switching is signalled to close the bussing bus-section to energise the feeder group from the remote end. 5.4 Substation Earthing It is important that the earthing for the UK Power Networks and customer substations are considered at an early stage to ensure that a suitable substation earthing system can be installed during the construction of the building foundations. Refer to EDS which includes further guidance for developers. 5.5 Substation Accommodation and Civil Requirements The arrangements for accommodating the UK Power Networks switchgear and the customer s switchgear shall be in accordance with EDS In order of preference the following shall be provided: 1. Separate buildings for UK Power Networks and the customer with a cabled connection between UK Power Networks and the customer s equipment. The UK Power Networks substation building shall normally be provided by the customer and shall contain all of UK Power Networks connection assets. Access to this substation shall be restricted to UK Power Networks operational/authorised personnel only. 2. Separate but adjacent switch rooms within the same building owned by the customer. As above, a cabled connection shall be provided between UK Power Networks and the customer s equipment, and access to the UK Power Networks switch room shall be restricted to UK Power Networks operational/authorised personnel. In all cases the UK Power Networks switch room shall be accessible from an external door which has direct vehicular access suitable for plant delivery. Provision of other access and emergency egress doors shall comply with the door requirements detailed in EDS and EDS Where required, the customer shall also carry out the civil works to provide an access roadway, site fencing and a building to house plant and equipment. These shall all be constructed in accordance with EDS , EDS and EDS The physical dimensions of the required spatial accommodation at each voltage and for each arrangement are provided in EDS UK Power Networks 2015 All rights reserved 12 of 19

13 6 Customer 6.1 Customer Substations Where a customer is in the vicinity of the London 33kV distribution network in London large point loads (typically 5MVA) will usually be supplied at 33kV. Due to the protection requirements of this network, the customer substation shall contain a three-panel single busbar switchboard (two incomer circuit-breakers and one metered service circuit-breaker) as a minimum requirement. However, in most cases it is envisaged that customers of this type shall require multiple metered infeeds, with five and seven-panel switchboards being common where the customer chooses to step down to 11kV, or have one or more firm 33kV internal building ring networks. Five and seven-panel switchboards also add extra resilience compared to a three-panel switchboard, as the customer will remain on supply for a fault on one of the busbars. Typical 33kV switchboard single line configurations are shown in Figure 6.1, Figure 6.2 and Figure 6.3. Contractually, parallel services shall not be allowed within a customer network that is supplied from more than one UK Power Networks substation as there are safety issues in terms of protection for both the customer and UK Power Networks. A mechanical and/or electrical interlocking system shall be provided depending on the type of switchgear in accordance with EDS Note: Although loads below 5MVA are not desirable due to load balancing issues, smaller loads may be considered at the discretion of Asset Management. Customer UK Power Networks M 33kV Figure 6.1 Customer Substation Three-panel Switchboard (Minimum Requirement for 33kV POC) Customer UK Power Networks M M 33kV Figure 6.2 Customer Substation Five-panel Switchboard UK Power Networks 2015 All rights reserved 13 of 19

14 Customer UK Power Networks M M M M 33kV Figure 6.3 Customer Substation Seven-panel Switchboard 6.2 Separation of UK Power Networks and Customer HV equipment The preference is for physical separation of the UK Power Networks HV equipment from the customer s HV equipment for reasons of safety and authorisation. Both the customer and UK Power Networks need to retain full rights of access and operation over all the equipment they own. In order to realise this design the UK Power Networks substation shall include only the UK Power Networks equipment required to supply the customer substation. An HV substation shall be used to provide the customer with full control over their equipment. It is anticipated that end users shall be supplied by transformers on an n-1 contingency basis. It is assumed that the transformer shall be owned and operated by the customer, in practice this shall be negotiated between the customer and UK Power Networks during the connections process. In cases where UK Power Networks own and operate the transformers, they shall be housed within the UK Power Networks substation with suitable changes to the metering points. 6.3 LV The 33kV network shall supply large commercial or domestic customers. It is the customers responsibility to distribute the 33kV throughout their development and transform it directly to lower voltages for their end users (for example 11kV or 400/230V). The installation and maintenance of all equipment (transformer, switchgear etc) associated with these supplies is the responsibility of the customer. These supplies shall be independent of the UK Power Networks local network. 6.4 Generation Where the customer also has on-site generation either a generator inhibit shall be provided in accordance with EDS or paralleling arrangements agreed with UK Power Networks Network Control. 6.5 Emergency Trip A customer emergency trip shall be provided in accordance with EDS and EDS UK Power Networks 2015 All rights reserved 14 of 19

15 6.6 Metering Options The following sub-sections outline the metering options available to customers: Where all end connections within a building network are equipped with full settlements metering issued from UK Power Networks MPANs, a CT chamber shall not be installed nor any integral CTs connected. Where some but not all end connections within a building network are equipped with full settlements metering issued from UK Power Networks MPANs, a CT chamber shall be installed or integral CTs connected as appropriate. Where the development is of a speculative nature or the final arrangements for a building network are not finalised then a CT chamber shall be installed or integral CTs shall connected as appropriate at the intake by UK Power Networks. It is acceptable for a CT Chamber or integral CTs to remain connected when all end points of a building network have received metering and the boundary metering function is no longer required. Metering CTs, CT chambers or provisions for whole current meters within a building network shall not be installed or owned by UK Power Networks (refer to EDS ). In relation to a connection to a licensed distribution system, i.e. IDNO Inset Network, the intake connection shall not be metered and therefore no metering CT connection or metering CT chamber is required (refer to EDS ). Where metering of the intake is required the customer shall provide: Accommodation for a metering termination box to be located no further than 20m from the CT position. The metering accommodation shall be weather protected and be provided with lighting. The accommodation shall allow the metering termination box to be mounted at a height of between 1m and 1.8m, with a free working space of not less than 1m. A duct for the multicore cable from the CT position to the meter box. An external meter cabinet of a type approved by UK Power Networks. Duplicate metering CT ratio name plates are provided by the supplier of the CT chamber/integral CTs. These CT ratio name plates shall be fitted inside the metering termination box when this is installed. UK Power Networks 2015 All rights reserved 15 of 19

16 7 References 7.1 UK Power Networks Standards Regional Development Plan City of London 33kV Network EAS EDS EDS EDS EOS EDS EDS EDS EDS EDS EDS EDS MV Switchgear 33kV Single Core XLPE Cables Protection and Control Schemes for Customer Demand and Generation Connections London 33kV Distribution Network Protection Requirements (internal only) London 33kV Automatic Load Transfer Scheme (internal only) Customer EHV and HV Connections (including Generation) Earthing Design and Construction Guidelines Grid & Primary Civil Design Standards Civil Requirements for New Customer and Generator Connections between 6.6 and 33kV Substation Temporary Access Road Guidance for the Application of ENA Engineering Recommendation G88 and G81 Inset Networks (IDNOs and other Licenced DNOs) to Multi-occupied Buildings HV Customer 7.2 National and International Standards ENA ER P2/6 Security of Supply UK Power Networks 2015 All rights reserved 16 of 19

17 Appendix A Bussing Bar Concept The bussing bar arrangement is illustrated in Figure 7.1 and Figure 7.2. Both feeder groups A and B, shown in red and green respectively consist of four circuits rated at 30MVA, evenly loaded at 90MW and supplied from three 60MVA transformers. Group A is intact and supplied by Substation A with all four feeders connected to a separate bussing bar at Substation B. Group B has an onerous (n-1) condition close to Substation A. Under these conditions, the power flow on the remaining three circuits would increase to its rated value of 30MVA. All customers connected to the faulted feeder would experience no interruption with unit protection isolating the faulted cable section and supply continuity maintained via the bussing bar at Substation B as shown in Figure 7.1. For the loss of all three transformers at either Substation A or Substation B, as shown in Figure 7.2, the auto switching scheme would be configured to prevent customers at both feeder groups from experiencing an interruption, although a transient interruption during auto-closure of the bus-section circuit-breakers at both substations would be noticed. Substation A 3x60MVA 30MW 30MW 7.5MW 7.5MW 30MW 7.5MW 3x60MVA Zero Balancing Current Substation B Feeder and transformer CBs are distributed between both sets and all sections of busbars as required for the local network configuration. This will also determine which bus-section/coupler CBs are normally open and if auto switching is required. Substation A Figure 7.1 Bussing Bar Concept (n-1) Outage Condition 3x60MVA Zero Balancing Current Substation B 3x60MVA Feeder and transformer CBs are distributed between all busbar sections as required for the local network configuration. This will also determine which bus-section/coupler CBs are normally open and if auto-switching is required. Figure 7.2 Bussing Bar Concept (n-3) Outage Condition UK Power Networks 2015 All rights reserved 17 of 19

18 Appendix B 33kV Network Example Substation A T1A T2A T3A Feeder Group B Customer 1 4MVA Feeder Group A Customer 3 3.6MVA Customer 6 15MVA Customer 5 9.6MVA Customer 4 8MVA Customer 2 8MVA Feeder Group A T1B T2B T3B Substation B Feeder and transformer CBs are distributed between all busbar sections as required for the local network configuration. This will also determine which bussection/coupler CBs are normally open and if auto-switching is required. Figure kV Network Example UK Power Networks 2015 All rights reserved 18 of 19

19 Appendix C London 33kV Distribution Network Map The current extent of the London 33kV network is shown below and new connections are generally available in and around it depending on the proximity of the 33kV network to the point of connection. UK Power Networks 2015 All rights reserved 19 of 19

EDS SCADA NUMBERING SYSTEM

EDS SCADA NUMBERING SYSTEM Document Number: EDS 05-9007 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 05-9007 SCADA NUMBERING SYSTEM This standard describes the system for numbering SCADA wiring within switchgear

More information

EDS LV CUSTOMER UNMETERED SUPPLIES

EDS LV CUSTOMER UNMETERED SUPPLIES Document Number: EDS 08-2102 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-2102 LV CUSTOMER UNMETERED SUPPLIES EPN, LPN, SPN This standard details the requirements for unmetered single-phase

More information

Engineering Recommendation G87 Issue

Engineering Recommendation G87 Issue PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Engineering Recommendation G87 Issue 2-2015 Guidelines for the Provision of Low Voltage Connections to Multiple Occupancy Buildings

More information

EBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES

EBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES Network(s): Summary: ENGINEERING BULLETIN EBB 08-0061 PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES EPN, SPN This bulletin provides a framework for the pilot scheme for unmetered

More information

EDS MW AND MVAR TRANSDUCER CONNECTION

EDS MW AND MVAR TRANSDUCER CONNECTION Document Number: EDS 05-5001 Network(s): Summary: ENINEERIN DESIN STANDARD EDS 05-5001 MW AND MVAR TRANSDUCER CONNECTION EPN, LPN, SPN This standard details the convention to be used when wiring MW and

More information

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

IMP/ 001 / 014 Policy for the Protection of Distribution Networks Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy

More information

EDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES

EDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 05-0001 132KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES EPN, LPN, SPN This engineering design standard describes the requirements for

More information

Network Configuration Document Selection for New Substations Framework

Network Configuration Document Selection for New Substations Framework Network Configuration Document Selection for New Substations Current version: 20/06/2018 EXTERNAL USE Page 1 of 14 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References...

More information

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0521 NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN This document details the installation, testing

More information

ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE

ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE Document Number: ECS 05-9541 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 05-9541 LUCY GEMINI 3 CONFIGURATION PROCEDURE EPN, LPN, SPN This document details the configuration procedure for

More information

EDS GUIDANCE FOR THE APPLICATION OF ENA ENGINEERING RECOMMENDATIONS G88 AND G81 - INSET NETWORKS (IDNOS AND OTHER LICENSED DNOS)

EDS GUIDANCE FOR THE APPLICATION OF ENA ENGINEERING RECOMMENDATIONS G88 AND G81 - INSET NETWORKS (IDNOS AND OTHER LICENSED DNOS) THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE ENGINEERING DESIGN STANDARD EDS 08-0113 GUIDANCE FOR THE APPLICATION OF ENA ENGINEERING RECOMMENDATIONS G88 AND G81 - INSET

More information

Common Departures Interconnecting Facilities Requirements

Common Departures Interconnecting Facilities Requirements Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low

More information

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE Document Number: ECP 11-0501 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0501 SECONDARY SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the end-to-end process

More information

EOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR

EOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR Document Number: EOS 03-0018 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0018 SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning

More information

STCP 04-3 Issue 005 Real Time Data Provision

STCP 04-3 Issue 005 Real Time Data Provision STCP 04-3 Issue 005 Real Time Data Provision STC Procedure Document Authorisation Party Name of Party Representative Signature Date National Grid Electricity Transmission plc SP Transmission plc Scottish

More information

EOS REMSDAQ CALLISTO NX TYPE E RTU

EOS REMSDAQ CALLISTO NX TYPE E RTU Document Number: EOS 05-9306 Network(s): Summary: ENGINEERING OPERATING STANDARD EOS 05-9306 REMSDAQ CALLISTO NX TYPE E RTU EPN, LPN, SPN This standard details the application, installation and operation

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4. Branch Procedure Document No. Issue No. : : CEOP8012 5 Approved By : Specialist Engineering NETWORK : Manager Approval Date Review Date : : 29/06/2018 29/06/2021 (Supersedes CEOP8012, Generation Connection:

More information

EOS LUCY SABRE 'A' RANGE SWITCHGEAR

EOS LUCY SABRE 'A' RANGE SWITCHGEAR Document Number: EOS 03-0027 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0027 LUCY SABRE 'A' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning and operation

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

EOS LUCY GEMINI 3 TYPE E RTU

EOS LUCY GEMINI 3 TYPE E RTU Document Number: EOS 05-9305 Network(s): Summary: ENGINEERING OPERATION STANDARD EPN, LPN, SPN EOS 05-9305 LUCY GEMINI 3 TYPE E RTU This standard details the application, installation and operation of

More information

EDS HV NETWORK DESIGN

EDS HV NETWORK DESIGN Document Number: EDS 08-3000 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 08-3000 HV NETWORK DESIGN This standard details the guidelines for the design and development of the 11kV

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

SCHEDULE 22 COMMON CONNECTION CHARGING METHODOLOGY

SCHEDULE 22 COMMON CONNECTION CHARGING METHODOLOGY SCHEDULE 22 COMMON CONNECTION CHARGING METHODOLOGY Introduction 1. This Schedule 22 sets out the Common Connection Charging Methodology (CCCM). The CCCM is the whole of this Schedule 22 excluding only

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES SURGE PROTECTION IN SIGNAL Approval Amendment Record Approval Date Version Description 11/05/2016 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

More information

TENGIZ PROJECT - FIELD SUBSTATION REPLACEMENT

TENGIZ PROJECT - FIELD SUBSTATION REPLACEMENT TENGIZ PROJECT - FIELD SUBSTATION REPLACEMENT / KAZAKHSTAN >>> TENGIZ PROJECT - FIELD SUBSTATION REPLACEMENT / KAZAKHSTAN Tengiz is one of the largest oil fields in the world, and is located in western

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

11 kv Indoor Switchgear - SCADA Controlled

11 kv Indoor Switchgear - SCADA Controlled Specification 11 kv Indoor Switchgear - SCADA Controlled Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the

More information

Recording and Reporting of High Voltage and Low Voltage Switching

Recording and Reporting of High Voltage and Low Voltage Switching 1 SCOPE This document details the procedures to be adopted prior to, during, and on completion of Switching operations, and details the manner in which HV and LV Switching shall be recorded in order to

More information

INTERCONNECTION FACILITIES STUDY REPORT

INTERCONNECTION FACILITIES STUDY REPORT Interconnection Request No. TI-08-0312 INTERCONNECTION FACILITIES STUDY REPORT Prepared by Tri-State Generation and Transmission Association, Inc. 1 of 7 DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES

More information

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

GUIDELINES FOR SHARED TRANSMISSION CONNECTIONS IN VICTORIA

GUIDELINES FOR SHARED TRANSMISSION CONNECTIONS IN VICTORIA GUIDELINES FOR SHARED TRANSMISSION CONNECTIONS IN VICTORIA PREPARED BY: Transmission Services VERSION: 2.0 RELEASE DATE: 14 December 2011 FINAL Version Release History Version Date Approved 1.0 3 Jun 11

More information

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation Small Generator Interconnection Facilities Study Report Completed for ( Interconnection Customer ) Proposed Interconnection Pavant substation Original report dated February 17, 2016 Revised March 11, 2016

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Substation Workshop. 7 th February 2018

Substation Workshop. 7 th February 2018 Substation Workshop 7 th February 2018 1 Agenda Welcome and Introductions Antony White Substation Design Overview Andy Moore Question & Answer Session Break 1500kVA Transformers James Devriendt & Andy

More information

Network Asset Design Standard HV SUBSTATION FEEDER EXIT CIRCUITS ISOLATION POLICY

Network Asset Design Standard HV SUBSTATION FEEDER EXIT CIRCUITS ISOLATION POLICY Network Asset Design Standard HV SUBSTATION FEEDER EXIT CIRCUITS ISOLATION POLICY Original Issue: September 2007 Prepared by: Lee Chan & Rob Rogerson This Revision: 0 October 2007 Date For Next Review:

More information

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades

Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades May 2012 / 1910DB1202 by Hal Theobald, Product Manager, Schneider Electric Services and Reza Tajali, P.E.,

More information

Benefits, offering and references

Benefits, offering and references DOC ID: 9AKK107045A9180 DISTRIBUTION SOLUTIONS Digital medium-voltage switchgear Benefits, offering and references Contents Digital switchgear for medium-voltage applications Digital switchgear definition

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus Non-conventional instrument transformers Advanced GIS substations with IEC 61850-9-2LE process bus Content Towards the digital GIS substations Optimized substation design NCIT for gas-insulated switchgears

More information

Power System Protection and С ommunications

Power System Protection and С ommunications Power System Protection and С ommunications AKHTAR KALAM Professor School of Engineering and Science Faculty of Health, Engineering and Science Victoria University, Australia D P KOTHARI Vice Chancellor,

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

PRC Coordination of Protection Systems for Performance During Faults

PRC Coordination of Protection Systems for Performance During Faults PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Innovation on Medium Voltage Switchgear

Innovation on Medium Voltage Switchgear Bruno Rivas, Guarulhos - Brazil, April 2015 Jornadas Técnicas de ABB en Chile Innovation on Medium Voltage Switchgear May 13, 2015 Slide 1 Application 13. Mai 2015 Slide 2 PPMV Brazil Factory Unigear Insourcing

More information

OTAHUHU SUBSTATION DIVERSITY PROJECT: REVIEW OF THE CIRCUIT BREAKER CONFIGURATION PROPOSED BY TRANSPOWER

OTAHUHU SUBSTATION DIVERSITY PROJECT: REVIEW OF THE CIRCUIT BREAKER CONFIGURATION PROPOSED BY TRANSPOWER Parsons Brinckerhoff Associates OTAHUHU SUBSTATION DIVERSITY PROJECT: REVIEW OF THE CIRCUIT BREAKER CONFIGURATION PROPOSED BY TRANSPOWER A report prepared for 23 March 2007 Disclaimer Notice Report for

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

Bus Protection Application Challenges

Bus Protection Application Challenges Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference Content Introduction Application Challenges Increase

More information

2.10 Annex. SP Manweb urban network. SP Energy Networks. June SP Energy Networks Business Plan

2.10 Annex. SP Manweb urban network. SP Energy Networks. June SP Energy Networks Business Plan 2.10 Annex Environmental Discretionary Reward Scheme 3 SP Energy Networks 2015 2023 Business Plan SP Manweb urban network SP Energy Networks June 2013 Scope This annex to the SP Energy Networks 2015-2023

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

MESP MODULAR SUBSTATION USER REQUIREMENTS

MESP MODULAR SUBSTATION USER REQUIREMENTS Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers on. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a generating plant with the Oncor

More information

CHAPTER 11 HOW TO ENHANCE THE RELIABILITY & POWER QUALITY OF ELECTRICITY SUPPLY

CHAPTER 11 HOW TO ENHANCE THE RELIABILITY & POWER QUALITY OF ELECTRICITY SUPPLY CHAPTER 11 HOW TO ENHANCE THE RELIABILITY & POWER QUALITY OF ELECTRICITY SUPPLY CHAPTER 11 HOW TO ENHANCE THE RELIABILITY & POWER QUALITY OF ELECTRICITY SUPPLY 11.1 Introduction 1. HK Electric provides

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Power Systems Communications Implementation of IEC61850 in a Substation Environment Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

Unofficial Comment Form Project Disturbance Monitoring

Unofficial Comment Form Project Disturbance Monitoring Unofficial Comment Form Project 2007-11 Disturbance Monitoring Please DO NOT use this form for submitting comments. Please use the electronic form to submit comments on the Standard Authorization Request

More information

FAQ about Drives Technology

FAQ about Drives Technology FAQ about Drives Technology Power supply systems MICROMASTER 4 SINAMICS G120 ID: 25220071 Warranty, liability and support We do not accept any liability for the information contained in this document.

More information

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation 111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities

More information

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Revised: July 12, 2013 Introduction The following information includes requests for clarification

More information

Company Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes

Company Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes Company Directive STANDARD TECHNIQUE: TP18A/1 Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes Summary This document provides guidance on the application of

More information

providing electricity connection solutions

providing electricity connection solutions providing electricity connection solutions About Us Power On Connections Providing Competitive Electricity Connection Solutions Power On Connections is the UK s largest and leading Independent Connections

More information

Fair and Effective Management of DNO Connection Queues: Treatment of Requests to Change Connection Applications. Good Practice Guide

Fair and Effective Management of DNO Connection Queues: Treatment of Requests to Change Connection Applications. Good Practice Guide Fair and Effective Management of DNO Connection Queues: Treatment of Requests to Change Connection Applications Good Practice Guide November 2018 Contents Fair and Effective Management of DNO Connection

More information

3- and 4-pole switching in UPS installation

3- and 4-pole switching in UPS installation Smart tricks to improve power supply reliability White paper series Power Distribution & UPS 3- and 4-pole switching in UPS installation Janne Paananen Technology Manager, Critical Power Solutions, Eaton

More information

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer ) Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original

More information

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B GE Energy Connections Grid Solutions MMLZ Technical Data Sheet Auxiliary Modules Publication reference: MMLZ/EN TDS/B MMLZ Technical Data Sheet FEATURES Wide choice of application specific models Fully

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

Auxiliary Units for 7SR23 High Impedance Protection Energy Management Reyrolle Protection Devices Auxiliary Units for High Impedance Protection Energy Management Siemens Protection Devices Limited 2 Auxiliary Units for High Impedance Protection Description 7XG15 High Impedance

More information

Bulletin Installation of solar photovoltaic systems Rules , , , , and

Bulletin Installation of solar photovoltaic systems Rules , , , , and Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic

More information

Feasibility Study on Load Flow and Short Circuit Project

Feasibility Study on Load Flow and Short Circuit Project Feasibility Study on Load Flow and Short Circuit Project 101813-01 Prepared by: Transmission Planning Department Cleco Corporation, Inc. 2180 St. Landry Hwy P.O. Box 70 St. Landry, LA 71367 Final November

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

COMPANY PROFILE. Kontrolmatik has accomplished local and international projects with great success. Some of fields that KONTROLMATIK serves,

COMPANY PROFILE. Kontrolmatik has accomplished local and international projects with great success. Some of fields that KONTROLMATIK serves, MOBILE SUBSTATIONS COMPANY PROFILE Kontrolmatik has accomplished local and international projects with great success. As one of the leading engineering companies in Turkey, Kontrolmatik has successfully

More information

Blueprint Data Center

Blueprint Data Center Systems and Applications for Data Center Siemens Industy 1. Overview / Purpose In EM EA the datacenter market is seen as one of the fastest growing of the energy businesses. This blueprint is designed

More information

INCREASING electrical network interconnection is

INCREASING electrical network interconnection is Blair, Steven Macpherson and Booth, Campbell and Turner, Paul and Turnham, Victoria (2013) Analysis and quantification of the benefits of interconnected distribution system operation. In: 5th International

More information

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District

WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District 5 WHAT IS A BUS? All connections are at the same voltage. WHAT IS A BUS? All

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

SDRC-3 Detailed Design of the FPL Method

SDRC-3 Detailed Design of the FPL Method SDRC-3 Detailed Design of the FPL Method SDRC-3 Detailed Design of the FPL Method Report Title : SDRC-3 Detailed Design of the FPL Method Report Status : FINAL Project Ref : WPDT206 Date : 22.03.2016 Document

More information

EU DONOR FUNDED SMART GRID PROGRAMME

EU DONOR FUNDED SMART GRID PROGRAMME EU DONOR FUNDED SMART GRID PROGRAMME 1 Historical Background Msunduzi Local Municipality is a local municipality in Umgungundlovu District Municipality, KwaZulu-Natal, South Africa. It encompasses the

More information

Small Generator Interconnection System Impact Study Report. Completed For Q0047

Small Generator Interconnection System Impact Study Report. Completed For Q0047 Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

PROTECTION REQUIREMENTS OF EMBEDDED GENERATORS < 5 MVA (LV + HV UP TO 22KV)

PROTECTION REQUIREMENTS OF EMBEDDED GENERATORS < 5 MVA (LV + HV UP TO 22KV) PROTECTION REQUIREMENTS OF EMBEDDED GENERATORS < 5 MVA (LV + HV UP TO 22KV) Standard Operating Procedures Document number SOP 11-16 Issue number 3 Status Approver Approved Peter Grove Date of approval

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010 Ontario Electrical Safety Code - Bulletins 50-1-0 Bulletin 50-1-0 Installation of Solar Photovoltaic Systems Section 50; Rules: 84-020, 84-024, 84-030; Tables 11 and 19 Issued July 2010 Scope (1) Introduction

More information

JEA. Facility Connection Requirements

JEA. Facility Connection Requirements JEA Facility Connection Requirements April 2008 January 14 th, 2006 1/22 JEA Facility Connection Requirements TABLE OF CONTENTS 1.0 Introduction and Scope 1.1 Generation Facilities 1.2 Transmission Facilities

More information

Design Guidelines for SCADA & DSA

Design Guidelines for SCADA & DSA Design Guidelines for SCADA & 28 th February 2017 28 FEBRUARY 2017 ISSUE 4 PREPARED BY: PRINCIPAL ENGINEER SCADA & MANAGER AUTHORISED BY: MANAGER SECONDARY SYSTEMS DOCUMENT NUMBER: ISSUE 4 This plan is

More information

Power Transmission Division Link between power generation and distribution

Power Transmission Division Link between power generation and distribution Power Transmission Division Link between power generation and distribution Seite 4 High Voltage Substations Schemes, Devices and Types of AIS Installation Content Link between power generation and distribution

More information

2 Principle of lightning protection

2 Principle of lightning protection 2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical

More information

Information Document PRC-001-AB3-1.1(ii) Protection System Coordination ID # RS

Information Document PRC-001-AB3-1.1(ii) Protection System Coordination ID # RS Information Documents are not authoritative. Information Documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between an Information Document

More information

Distributed Generation Customer Perspectives. Focus on LV to 33kV Connections sector (PV)

Distributed Generation Customer Perspectives. Focus on LV to 33kV Connections sector (PV) Distributed Generation Customer Perspectives Focus on LV to 33kV Connections sector (PV) James Hoare CEng MIET MEI BRE National Solar Centre -Associate Consultant LHW Partnership LLP - Owner 24 th September

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information